Grounding
Ground Fault Protection
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
2/35
Ground Fault Protection
Course Objectives:Upon completion of this course, you will be
able to:• Define the ground fault protective schemes
utilized in the industry today for simple radial schemes• Define the ground fault protective schemes
utilized in the industry today for complex
systems
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
3/35
Ground-Fault Systems
Types of Ground Fault Protective Schemes Ground Strap
Zero Sequence
Residual
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
4/35
Ground Strap System
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
5/35
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
6/35
Ground Strap Operation
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
7/35
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
8/35
Ground Strap System
Disadvantages
* Can only be used on main disconnect
* ust be the only neutral ground ! " can lead to nuisance trippings
" desensiti#ed tripping under an actual
faulted condition
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
9/35
Ground Strap System
Disadvantages
* desensiti#ed tripping due to groundedneutrals
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
10/35
Zero Sequence System
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
11/35
Zero Sequence System
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
12/35
Zero Sequence System Operation
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
13/35
Zero Sequence System Operation
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
14/35
Zero Sequence System
Advantages
**can be used on both the main and feeder brea$ers
Disadvantages**do%nstream grounds can cause nuisance trippings
**improperly centered conductors can also causenuisance trippings
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
15/35
Residual System
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
16/35
Residual System
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
17/35
Residual System
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
18/35
Residual System Operation
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
19/35
Residual System
Advantages
&sed on main and feeder brea$ers
'eutral grounds on line side have no effect
'o control po%er required
(ne)pensive if purchased %ith brea$er
'eutral C only e)ternal device
Disadvantages
'o do%nstream grounds
'ot economical for fused s%itches
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
20/35
Complex Systems
Ground Fault Protection
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
21/35
Multi-Leel Ground Fault- ProtectionSystems
Ground Fault Protection
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
22/35
!ou"le-#nded Su"station
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
23/35
!ou"le-#nded Su"station $it% Fault
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
24/35
Single Point Ground System
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
25/35
Modi&ied !i&&erential Sc%eme
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
26/35
Modi&ied !i&&erential $it% Residual System
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
27/35
#mergency Systems
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
28/35
#mergency Systems $it% S$itc%ed 'eutral
irst !lternative
Utilize four"pole
#ransfer $witch
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
29/35
#mergency Systems
$econd !lternative
%emove the &ain
'onding (umper
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
30/35
#mergency Systems
#hird !lternative
)mploy a Differential
$cheme
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
31/35
Ground Fault
*+ hat are the two schemes often employed to provide
ground"fault protection on double"ended substations-
.+ hat is the major disadvantage of the
single"point"grounding scheme for ground" fault
protection when the tiebrea/er is closed-0+ hat are the three different types of ground"fault systems-
1+ here is the ground"fault sensor located for a ground
strap system-
2+ hat is the only disconnect device that can use a ground strap system-
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
32/35
Ground Fault
*+ hat are the two schemes often employed to provide
ground"fault protection on double"ended substations-
3source ground sensing
3modified differential scheme
.+ hat is the major disadvantage of the
single"point"grounding scheme for ground" fault
protection when the tiebrea/er is closed-
++!ll unbalanced single"phased loads from the remote halfof the switchboard are 4seen5 as fault current 6 which may
cause nuisance trippings+
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
33/35
Ground Fault
0+ hat are the three different types of ground"fault systems-
3ground strap 7also called neutral ground strap8
3zero se9uence
3residual
1+ here is the ground"fault sensor located for a ground
strap system-
3located on the main bonding jumper
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
34/35
Ground Fault
2+ hat is the only disconnect device that can use a
ground strap system-
3ground strap system can only be used on the main
disconnect
-
8/19/2019 Ground%20Fault%20Protection[1].ppt
35/35
Ground Fault
Comments or uestions-