Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas...

36
GRUNDFOS ALLDOS INSTRUCTIONS Vaccuperm VGS-141, -143, -145 Gas dosing system Service instructions

Transcript of Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas...

Page 1: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

GRUNDFOS ALLDOS INSTRUCTIONS

Vaccuperm VGS-141, -143, -145Gas dosing system

Service instructions

Page 2: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

2 / 36

Contents

1. Of general interest ............................................................................................................ 31.1 Structure of the documentation .........................................................................................................31.2 About this manual .............................................................................................................................31.3 User/target groups ............................................................................................................................31.4 Responsibilities of the operator.........................................................................................................41.5 Maintenance and service personnel ..................................................................................................41.6 Correct usage ...................................................................................................................................41.7 Inappropriate usage ..........................................................................................................................42. Technical Data................................................................................................................... 52.1 General Data ....................................................................................................................................52.2 Data of the optional components.......................................................................................................52.3 Dimensioned drawing .......................................................................................................................73. Installation ......................................................................................................................... 83.1 Transport and storage.......................................................................................................................83.2 Unpacking ........................................................................................................................................83.3 Mounting...........................................................................................................................................84. Commissioning ................................................................................................................. 94.1 Preparations for commissioning ........................................................................................................94.2 Checks before commissioning ........................................................................................................125. Maintenance .................................................................................................................... 145.1 Possible faults ................................................................................................................................145.2 Switching off ...................................................................................................................................155.3 Disassembling and cleaning the measuring tube ............................................................................155.4 Cleaning the rate valve ...................................................................................................................155.5 Differential pressure regulator.........................................................................................................175.6 Adjusting the Servomotor (option) ...................................................................................................186. Assembly drawings, spare part sets and spare parts ................................................... 226.1 Gas Dosing System ........................................................................................................................226.2 Measuring tube support ..................................................................................................................256.3 Rate valve ......................................................................................................................................286.4 Differential pressure regulator.........................................................................................................316.5 Spare part sets and spare parts ......................................................................................................346.6 Spare parts .....................................................................................................................................34

Page 3: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

1. Of general interest

1.1 Structure of the documentationThe Grundfos Alldos device VGS-141 / VGS-143 / VGS-145 is a state-of-the-art solution, which complies with recognised safety regulations.Conformity with applicable standards, directives and laws has been verified. Nevertheless, certain risks which cannot be prevented by the manufacturer are associated with the use of the system.Purpose of this manual: • Inform users of optimum use.• Warn users of possible residual risks when using correctly and identify measures that should be taken to avoid

damage.• Caution users against obvious misuse or inappropriate use and inform them of the necessary care that must be

taken when operating the system.

1.2 About this manualThis manual contains the following standardised safety instructions about possible residual risks:

Information about possible residual risks is provided:• On warning signs displayed in the installation location.• At the start of each section in this manual.• Directly before any operating procedures that could involve residual risks.

1.3 User/target groupsUsers are persons who are responsible for operating and monitoring the device VGS-141 / VGS-143 / VGS-145 at the installation location. The system may only be operated by trained and qualified personnel. Personnel must have appropriate technical knowledge and be familiar with the basic principles of measuring and control technology.

1.3.1 Responsibilities of the usersThe users’ responsibilities: • Read this manual before operating the VGS-141 / VGS-143 / VGS-145.• Be trained by qualified personnel from Grundfos Alldos in the operation of the system.• Observe the recognised regulations governing safety in the workplace and accident prevention.• Wear appropriate protective clothing in accordance with national regulations for the prevention of accidents when

operating the system and handling chemicals (German GUV-V D05).

WarningThese operating instructions are also available on www.Grundfosalldos.com. Prior to installation, read these installation and operating instructions. Installation and operation must comply with local regulations and accepted codes of good practice.

WarningIf these safety instructions are not observed, it may result in personal injury!

CautionIf these safety instructions are not observed, it may result in malfunction or damage to the equipment!

Note Notes or instructions that make the job easier and ensure safe operation.

3 / 36

Page 4: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

1.4 Responsibilities of the operatorThe owner of the building or operator of the VGS-141 / VGS-143 / VGS-145 is responsible for the following:• Consider this manual to be part of the product and ensure that it is kept clearly accessible in the immediate vicinity

of the system for the entire service life of the system.• Meet the installation requirements specified by the manufacturer (required water connections and fittings,

environmental conditions, electrical connection, protective tube for dosing line if necessary, audible or optical warning device for alarm messages if necessary).

• Ensure that water lines and fixings are regularly checked, serviced and maintained.• Obtain official approval for storing chemicals, if necessary.• Train users in the operation of the system.• Ensure that the regulations for the prevention of accidents are observed in the installation location

(German GUV-V D05 regulation for the prevention of accidents, "Chlorination of Water" dated January 1997).• Provide all users and service personnel with protective clothing in accordance with GUV-V D05 (face mask, gloves,

protective apron).

1.5 Maintenance and service personnelThe system may only be maintained and serviced by authorised service personnel from Grundfos Alldos.

1.6 Correct usageThe Grundfos Alldos VGS-141 / VGS-143 / VGS-145 may be used for dosing chlorine (Cl2) as being described in this manual.

1.7 Inappropriate usageApplications other than those listed in section 1.6 Correct usage are considered not to be in accordance with the intended use and are not permitted. The manufacturer, Grundfos Alldos, accepts no liability for any damage resulting from incorrect use.The system comprises state-of-the-art components and has undergone safety-related testing.

WarningUnauthorised structural modifications to the system may result in serious damage to equipment and personal injury. It is forbidden to open, modify, change the structure of, bridge, remove, bypass or disable components, especially safety equipment.

4 / 36

Page 5: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

2. Technical Data

2.1 General Data

2.1.1 Dosing Flow

2.2 Data of the optional components

2.2.1 Servomotor without electronics

Permissible medium Cl2Deviation of linearity ± 4 % of upper limitDeviation of reproducibillity ± 2 % of upper limitControl range 1:20Connections VGS-141 (up to 10kg/h) DN 10, for PVC-pipe DN 10 or PE-tube 10/14Connections VGS-143 (up to 40kg/h) DN 20, for PVC-pipe DN 20Connections VGS-145 (up to 200kg/h) DN 40, for PVC-pipe DN 40

Materials Polyurethan (enclosure), PVC, FEP, PTFE, FKM, Copper-nickel alloy and a special alloy

Type Dosing flow

VGS-141

10 - 200 g/h 0.5 - 10.5 #/day25 - 500 g/h 2 - 26 #/day50 - 1000 g/h 3 - 52 #/day100 - 2000 g/h 5 - 100 #/day200 - 4000 g/h 10 - 200 #/day400 - 8000 g/h 20 - 420 #/day500 - 10000 g/h 30 - 520 #/day

VGS-1431 - 20 kg/h 50 - 1050 #/day2 - 40 kg/h 100 - 2100 #/day

VGS-1453.5 - 70 kg/h 200 - 3700 #/day6 - 120 kg/h 400 - 6200 #/day10 - 200 kg/h 500 - 10500 #/day

Mains voltage 230 V, 50/60 Hz, 115 V, 50/60 Hz

Nominal current 0.011 A (at 230 V), 0.022 A (at 115 V)

Power consumption ca. 3 WPotentiometer 1000 ΩActuating time ca. 90 s (from minimal to maximum dosing flow)Degree of protection IP 55Permissible ambient temperature 0 °C to +50 °C

5 / 36

Page 6: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

2.2.2 Servomotor with built-in electronics

2.2.3 Manual/automatic remote indication of the position of the rate valve adjusting spindle

2.2.4 Vacuum meter with limit contacts

2.2.5 Vacuum sensors

Mains voltage 230 V, 50/60 Hz, 115 V, 50/60 Hz

Nominal current 0.011 A (at 230 V),0.022 A (at 115 V)

Signal input 4-20 mASignal output 4-20 mAManual/automatic: position indication of the servomotor: loading capacity of the contact

28 V, 1 A

Loading capacity of the signal outputoutput current: 4-20 mAminimum open-circuit voltage 10 V

Load max. 500 ΩPower consumption ca. 3 WActuating time ca. 90 s (from minimal to maximum dosing flow)Degree of protection IP 55Permissible ambient temperature 0 °C to +50 °C

Loading capacity of the Reed contact

Switched power max. 10WSwitched current max. 0.5ASwitched voltage max. 200 V (DC)Carry current 1.0 AContact resistance 150 mΩ

Breakdown voltage min. 250 V (DC)Degree of protection IP 65

Note The switch is closed in automatic position!

Measuring range -10 to 0 m WS rel.

Limit contact outputsslow-motion contacts S 21 according to DIN 16085 (E)1st limit contact: break contact (opens when the specified value is passed clockwise)2nd limit contact: make contact (closes when the specified value is passed clockwise)

Permissible contact load

voltage ohmic load inductive load in case of alternating current (cos > 0.7)230 V AC 45 mA 25 mA110 V AC 90 mA 45 mA24 V DC 200 mA -

Measuring range -1 to 0 bar rel.

Current output4 - 20 mA4 mA equates to -1 bar20 mA equates to 0 bar

Power supply 24V DCNeccessary cable for current signal 2-wire, shielded, order no. 96687719 (321-130)

6 / 36

Page 7: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

2.2.6 Measuring transducer

2.2.7 Measurement and Control Electronics Conex• see operation manual of measuring amplifiers and controller Conex® DIA-2Q or Conex® DIS-2Q

2.2.8 Chlorine measuring cell• see operation manual of the chlorine measuring cell

2.3 Dimensioned drawing

Fig. 1 Dimensional drawings of gas dosing systems VGS-141, VGS-143 and VGS-145

Measuring range1:10Below a dosing flow of 10 % no precise measurement is possible. The current signal 4 mA may probably not be reached at a dosing flow of 0 %.

Deviation of linearity < ± 4 % from upper limit of the measuring range

Current output4 - 20 mA4 mA equates to 0 % dosing flow20 mA equates to 100 % dosing flow

Power supply 24 V DCMaximum load 600 ΩPower consumption > 0.5 WDegree of protection IP 65Degree of protection 0°C to + 60°C

TM04

_080

9_09

08

390

45050

1000

1810

760

(DN

20)

730

(DN

40)

1000

610

37530 45

50552,5 52,5

740

6020

0

325 325

7 / 36

Page 8: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

3. Installation

3.1 Transport and storage• Handle with care, do not throw!• Dry and cool storage place.

3.2 Unpacking• Observe when unpacking

– No humidity should get into gas-leading parts!– No foreign matter should get into gas-leading parts!

• Mount as soon as possible after unpacking.

Fig. 2 Gas dosing system without foot for floor mounting

3.3 Mounting

3.3.1 Devices without foot (wall mounting)• Fix drilling jig to the desired place• Mark the bore holes and bore them• Put in dowels• Screw the device to the wall

3.3.2 Devices with foot (floor mounting)• Place the device at the desired place• Mark the bore holes• Remove the device• Bore the holes• Put in dowels• Place the device at the desired place• Screw the device to the floor

WarningOnly for devices without foot for floor mounting:Do not place the device standing on the pipe pieces!

TM04

_081

0_09

08

WarningPlease read Installation and operating instruction, Chapter 2: Handling Chlorine.

CautionOnly screw down the device to perfect flat and smooth surfaces.Danger of distortion!

8 / 36

Page 9: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

4. Commissioning

4.1 Preparations for commissioning

4.1.1 Electrical connections

Servomotor with built-in electronics (option) connected to Conex® DIA-2Q (Measurement and Control Electronics)• Connect the terminals with the corresponding terminals of the external control according to the connection chart.

Fig. 3 Terminal connection chart Conex® DIA-2Q

Servomotor with built-in electronics (option) connected to Conex® DIS-2Q (Microprocessor based controller)• Connect the terminals with the corresponding terminals of the external control according to the connection chart.

Fig. 4 Terminal connection chart Conex® DIS-2Q / servomotor with built-in electronics

WarningSwitch off mains before connecting!Electrical connections only by qualified personnel!Observe local rules for electrical installations!

NoteDepending on the selection of optional components: Mains connection either directly (by the customer) or via the clamp box.

TM04

_081

2_09

08

TM04

_086

1_42

08

12 11 10 8 7 6 5 4 3 2 1 NPE

(4-20 mA)(GND)

30 29 Conex DIA-2Q

white brown brown blue

mains

green/yellow

15 16 17 18 19 20 21 22 23 24 25 26

L1 N PEL1 N P E

+ -

1 2 3 4 5 6 7 8 9 10 11 12 13 14

PE

potential-free relay outputs

currentinput

servomotor mains

9 / 36

Page 10: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

Servomotor without electronics (option)• Connect the terminals with the corresponding terminals of an external control according to the connection chart.

Fig. 5 Terminal connection chart Conex® DIS-2Q / servomotor without electronics

Vacuum meter with limit contacts (option)• Connect the terminals of the plug with the corresponding terminals of an external evaluation device according to the

connection chart.

Fig. 6 Connection chart vacuum of meter with limit contacts

Vacuum sensors (option)• Connect the terminals of the plug with the corresponding terminals of an external evaluation device according to the

connection chart.

Fig. 7 Connection chartof vacuum sensor

TM04

_086

0_42

08

TM04

_081

3_09

08

TM04

_081

4_09

08

15 16 17 18 19 20 21 22 23 24 25 26

L1 N P EM1 ~

S 2 2 N 1 S 1 P E

1 2 3 4 5 6 7 8 9 10 11 12 13 14

E(100 %)

A(0 %)

S

+-

IDM

+ -

potential-free relay outputs

close

servomotor

mains

open

measuring amplifier feedback potentiometer

PE

1 2 3

1

23

24 V DC

+ -

4-20 mA+-

10 / 36

Page 11: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

Measuring transducer (option)• Connect the terminals of the plug with the corresponding terminals of an external evaluation device according to the

connection chart.

Fig. 8 Connection chart of measuring transducer

4.1.2 Measurement and Control Electronics Conex® DIA-2Q (option)• see operation manual of Conex® DIA-2Q

4.1.3 Chlorine measuring cell (option)• see operation manual of the chlorine measuring cell

4.1.4 Mounting the manual/automatic position remote indication at the rate valveThis indication shows e.g. in the switch room, if the optional servomotor is engaged and thus able to convert the incoming signals.• Loosen the cover of the adjustment knob with a big screwdriver; take off the adjustment knob.• Put the magnetic bridge sensor (item 5.6) into the lower cavity of the gearbox bearing and fasten using the two

recessed head screws (item 5.7).• Disassemble the adjustment knob by fully screwing out the clamping nut.• Insert the adjustment knob tongs into the washer disc (item 5.5) in a way that the tongs collar is in the washer disc.• Apply the washer disc to the adjustment knob enclosure so that the holding pin of the enclosure dips into the hole

of the washer disc.• Slide the spring washer over the adjustment knob tongs and screw the clamping nut onto the tongs.• Put the adjustment knob onto the gearbox spindle as far as it will go and tighten the clamping nut.• Fit the cover of the adjustment knob again.

Fig. 9 Manual/automatic position indication

TM04

_081

5_09

08

TM04

_085

9_09

08

24 V DC

+ -

2 1

4-20 mA+-

5.1

5.14

5.13

5.12

5.7

5.65.5

11 / 36

Page 12: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

4.1.5 Gas connections

• Connect line from vacuum regulator• Connect line to injector

Fig. 10 Gas connections of gas dosing systen VGS

4.2 Checks before commissioningCheck tightness of the total plant before start-up

4.2.1 Checking the gas solution lines and the diapgragm non-return of the injector• Observe the manual of the injector!

4.2.2 Checking the tightness of the vacuum linesVacuum lines are all lines between vacuum regulator and injector.• Close all container valves• Close the rate valve• Open the shut-off valve at the injection unit• Open motive water valve• Switch on the booster pump• Open the rate valve

Floater shows gas flow or vacuummeter shows more than - 9 m w.c. => Leakage in vacuum line!• Close rate valve• Switch off booster pump• Close motive water valve• Close the shut-off valve at the injection unit• Check the vacuum lines and the connection. If necessary, • carefully re-tighten them.• Check tightness again!

– Floater shows no gas flow, vacuummeter shows -9 m w.c. or less => Vacuum lines are tight.

WarningEnsure that all container valves are closed before connecting!Only use the intended gas lines!

TM04

_081

6_09

08

WarningCheck the tightness not until the total plant is ready for start-up.Danger of gas leakage! (chlorine breakout)

Note

More possible reasons for insufficient operating vacuum• injector layed out too weakly or defective• injector obstructed• booster pump layed out too weakly or defective

to injector from vacuum regulator

12 / 36

Page 13: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

4.2.3 Checking the tightness of pressure gas linesPressure gas lines are all lines from the gas containers to the vacuum regulator.• If the plant is equipped with a nitrogen rinsing device: Check tightness roughly with nitrogen.• Detailed checking with amonia.

Checking the tightness with nitrogen• Close all container valves• Open container connection valves and all shut-off valves up to the gas dosing system• Open the connection valve of the nitrogen cylinder• Slowly open the valve of the nitrogen cylinder, until the lines have a pressure of about 10 bar (read at the

manometer of the vacuum regulator).

• Apply soap water to all components under pressure– Formation of bubbles and/or pressure drop at manometer: Leakage in pressure lines!

Depressurize the plant!Eliminate leakage!Check tightness again!

• No formation of bubbles, pressure at manometer does not drop significantly within one hour: Pressure lines are tight.

Checking the tightness with ammonia• Open all container valves and container connection valves and quickly close them again• Slowly pass the open ammonia bottle along pressure-gas leading parts• Formation of white mist: Leakage in pressure lines!

Depressurize the plant!Eliminate leakage!Check tightness again!

Fig. 11 Formation of white mist

– No formation of white mist: Pressure lines are tight.

Fig. 12 No formation of white mist

Fig. 13 Danger of leakages

WarningMaximum nitrogen pressure 16 bar!Danger of damages and gas leakage when being exceeded! (chlorine breakout)

TM04

084

9 09

08TM

04 0

697

0908

WarningLiquid ammonia must not come in contact with parts of the plant!Danger of leakages by corrosion!

TM04

069

8 09

08

13 / 36

Page 14: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

5. MaintenanceRates for cleaning and maintenance• at least every 12 months• in case of malfunction

5.1 Possible faults

WarningDo not open the components of the device!Cleaning, maintenance and repair only by authorized personnel!

WarningSwitch off the whole plant before doing cleaning and maintenance work!Danger of gas break-out!

WarningCheck the tightness before restarting!Danger of gas break-out!

Fault Cause Correction

Despite constant operating conditions the vacuum varies

Spring in differential pressure regulator is soiled Clean the springSpring in differential pressure regulator is damaged Replace the spring

Despite constant operating conditions the dosing flow varies

Diaphragm in differential pressure regulator is soiled Clean the diaphragm

Diaphragm in differential pressure regulator is damaged Replace the diaphragm

Leakage at the rate valve Bar gasket in the rate valve damaged Replace the bar gasketFloater of the measuring tube is not caught Measuring tube is soiled Clean the measuring tube

Desired dosing flow is not reached

Insufficient injector vacuum Check injector, observe the manual of the injector

Servomotor (option) does not reach the 100 % -position

Adjust the potentiometer of the servomotor resp. check the settings of the electronics

Leakage in vacuum line between differential pressure regulator and injector

Eliminate leakage (see "checking the tightness")

Vacuum line between differential pressure regulator and injector too long

Observe table "suggested line lengths and diameters"

Vacuum line between vacuum regulator and gas dosing system too long

Observe table "suggested line lengths and diameters"

Admission pressure at the vacuum regulator too low

If necessary, open gas supply or clean filter (observe manual of the vacuum regulator)

Regulating channel of the adjusting plunger soiled Clean the adjusting plungerDespite correctly displayed gas flow the desired gas solution concentration cannot be reached

Leakage in vacuum line between vacuum regulator and gas dosing system

Eliminate leakage (see "checking the tightness")

Servomotor does not run Servomotor is switched to manual operation Switch servomotor to automatic operationServomotor does not reach the whole range desired Servomotor resp. electronics adjusted wrongly Adjust servomotor resp. check settings of the

electronicsServomotor runs in wrong direction Servomotor resp. electronics adjusted wrongly Adjust servomotor resp. check settings of the

electronics

The adjusting spindle (see figures in chapter 5.4) falls from the ’’automatic’’ position into the ’’manual’’position unintentionally

The spring-loaded thrust pad has been displaced and therefore cannot deliver enough preload to the holding groove of the adjusting spindle.

Adjust the thrust pad.

The spring-loaded thrust pad is damaged.

Exchange the spring-loaded thrust pad (96690346 or 50.1340); gently press on the ball. The adjusting spindle must be able to move up and down.

14 / 36

Page 15: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

5.2 Switching off• Set system to low dosing flow • While the plant is still running: Close the container valves• Let the plant run until the measuring tube shows no more gas flow• Switch off the system

– Observe operation manual of the Gas Dosing System.

5.3 Disassembling and cleaning the measuring tube

5.3.1 Required tools and accessories• Acetone

5.3.2 Procedure• Screw down the measuring tube support (see fig. 27-29, item 1.2)• Take out measuring tube (see fig. 27-29, item 1.5) with floater and stoppers

Remove measuring transducer (see fig. 27-29, item 1.9) (option)• Clean measuring tube, floater and stoppers with acetone• Replace O-rings• Remount floater and stoppers to the measuring tube

Remount measuring transducer (option)• Place measuring tube in the support• Screw the support upwards

tighten by hand

5.4 Cleaning the rate valve

5.4.1 Required tools and accessories• Allan key 5 mm• Crosstip screwdriver• Hot water (ca. 40 °C)• Soft brush• FKM grease

CautionDo not use any tools!Measuring tube and plastic parts may get damaged.

15 / 36

Page 16: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

5.4.2 Procedure• Unscrew electrical actuator (option)• Unscrew hexagon screws (see fig. 27-29, item 2.13)• Take out gear bearing (see fig. 27-29, item 2.2) with gear rack (see fig. 27-29, item 2.3)• Remove O-ring (see fig. 27-29, item 2.8)• Unscrew adjusting plunger (see fig. 27-29, item 2.15) from gear rack (see fig. 27-29, item 2.3)• Unscrew thread cap (see fig. 27-29, item 2.11)• Remove bar gasket (see fig. 27-29, item 3.10) and O-ring (see fig. 27-29, item 2.9)• Clean all parts with hot water, use brush if necessary• Dry all parts well

• Replace O-rings and bar gasket by new ones• Remount all parts in reverse sequence• In case the adjusting spindle has been dismantled: remount adjusting spindle and gear rack into the gearbox

bearing.– slightly apply FKM grease to the gear rack

• Insert the gear rack (2.3) (gearing facing behind) entirely into the gearbox bearing (see fig. 27-29, item 2.2).• Insert the adjusting spindle (stop pin facing behind) (see fig. 27-29, item 2.4) from the top into the gearbox bearing

as far as it will go.• Turn the adjusting spindle through approx. 180 ° until the stop pin dips into the front guide groove of the gearbox

bearing.• Slightly move the gear rack in short strokes and simultaneously put moderate pressure from above to the adjusting

spindle in order to make both parts gear. The gear rack should be about flush with the right wall of the gearbox bearing.

Fig. 14 Clean the rate valve

Caution Danger of corrosion when mounting moist parts!

CautionMount gear rack (see fig. 27 - 29, item 2.3) and adjusting spindle (see fig. 27 - 29, item 2.4) in the shown position.Danger of damages!

TM04

_082

5_09

08

2.4

2.3

0 mm+0,5

16 / 36

Page 17: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

5.5 Differential pressure regulator

5.5.1 Differential pressure regulator for system VGS-141Required tools and accessories• Allan key 5 mm• Screwdriver with wide blade• Hot water (ca. 40°C)• Soft brush

Procedure• Remove line to injector• Remove line to rate valve• Remove compensation line• Remove line to vacuummeter• Loosen the two hexagon screws (see fig. 27-29, item 3.27) and take off the differential pressure regulator• Remove cap (see fig. 27-29, item 3.23)• Measure the distance between the surface of the regulating nozzle (see fig. 27-29, item 3.4) and the outer edge

and note the result• Unscrew the connection piece (see fig. 27-29, item 3.3)• Remove O-ring (see fig. 27-29, item 3.5)• Take out regulating nozzle (see fig. 27-29, item 3.4)• Remove O-rings (see fig. 27-29, item 3.5)• Unscrew valve cover (see fig. 27-29, item 3.17)• Remove O-ring (see fig. 27-29, item 3.18)• Loosen the 8 hexagon screws (see fig. 27-29, item 3.19) and open the differential pressure regulator• Take out diaphragm (see fig. 27-29, item 3.9) with upper section (3.6) and lower section (3.7) of the diaphragm disk• Take out the spring (3.16)

Take out spacer (3.28) --> only for type VGS-141 with dosing flow 200 g/h or 500 g/h --> 96708777 (12.5157-302)

• Unscrew diaphragm disk• Remove diaphragm (see fig. 27-29, item 3.9) and O-ring (3.8)• Clean all parts with hot water, use brush if necessary• Dry all parts well

• Replace diaphragm and all O-rings by new ones• Remount all parts in reverse sequence

• Set regulating nozzle (see fig. 27-29, item 3.4) with the screwdriver to the distance measured before• Remount the differential pressure regulator• Establish the connections

Caution Do not remove the suspension wire of the spring!

Caution Danger of corrosion when mounting moist parts!

Caution Observe fitting position of diaphragm and diaphragm disk!

17 / 36

Page 18: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

5.5.2 Differential pressure regulator for system VGS 143 and VGS 145Required tools and accessories• Allan key 5 mm• Special tool 967087 16 (12.5030-400)• Hot water (ca. 40 °C)• Soft brush

Procedure• Remove line to injector• Remove line to rate valve• Remove compensation line• Remove line to vacuummeter• Loosen the 4 hexagon screws at the corners and take off the differential pressure regulator• Unscrew the connection piece (see fig. 27-29, item 3.1 and 3.3)• Remove O-rings (see fig. 27-29, item 3.5)• Take out regulating nozzle see fig. 27-29, item 3.4)• Remove O-ring (see fig. 27-29, item 3.5)• Unscrew valve cover (see fig. 27-29, item 3.17)• Remove O-ring (see fig. 27-29, item 3.18)• Measure the distance between the nut (see fig. 27-29, item 3.14) and the outer edge and note the result• Unscrew the nut (see fig. 27-29, item 3.14) with the special tool• Take out the spring (see fig. 27-29, item 3.16)

• Unscrew the guide piece (see fig. 27-29, item3.15)• Loosen the hexagon screws of the housing and open the differential pressure regulator• Take out diaphragm (see fig. 27-29, item 3.9) with upper section (3.6) and lower section (3.7) of the diaphragm disk• Unscrew diaphragm disk• Remove diaphragm (see fig. 27-29, item 3.9) and O-ring (3.8)• Clean all parts with hot water, use brush if necessary• Dry all parts well

• Replace diaphragm and all O-rings by new ones• Remount all parts in reverse sequence

• Set the nut (see fig. 27-29, item 3.14) with the special tool to the distance measured before• Remount the differential pressure regulator• Establish the connections

5.6 Adjusting the Servomotor (option)

In case of repairs or exchange, it may be possible to readjust the servomotor.

Caution Do not remove the suspension wire of the spring!

Caution Danger of corrosion when mounting moist parts!

Caution Observe fitting position of diaphragm and diaphragm disk!

WarningCheck the tightness before restarting (see chapter 4.2 ff)Danger of gas breakout!

Note The servomotor is already adjusted by works if ordered together with the system.

WarningThe servomotor may only be adjusted by qualified personnel, as the mains power has to be switched on.Danger!Do not touch bare wires or clamp screws!

18 / 36

Page 19: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

5.6.1 Servomotor without Electronics

Fig. 15 Adjust limit switch

• Take off the cover of the servomotor.• With the connected controller, move the servomotor to 0% dosing flow (as indicated at the measuring tube).

The gear rack at the rate valve must jut out for at least 1 mm.

• Adjust this position as zero point of the controller. Adjust lower limit switch (ST1, see figure 16) to this position of the servomotor.

• Set the controller to 10 %. • Check the dosing flow indicated at the measuring tube. If it is not 10 %:

Adjust the zero point again. Possibly the floater reaches the end stop at a dosing flow of more than 0 %.• With the connected controller, move the servomotor to 100 % dosing flow (as indicated at the measuring tube). The

gear rack at the rate valve must jut out for maximum 31 mm.

• Adjust upper limit switch (ST2, see figure 16) to this position of the servomotor.• Remount the cover of the servomotor.

Fig. 16 Servomotor with limit switch

TM04

082

6 09

08

Caution In case of undershoot: The rate valve may get damaged!

Caution In case of exceeding: The rate valve may get damaged!

TM04

085

5 37

08

min.(ST1)

max.(ST2)

+0,5 31 mm+0,5 1 mm

ST2

ST1

Potentiometerdisplay

19 / 36

Page 20: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

5.6.2 Servomotor with built-in Electronics

Fig. 17 Potentiometer and dosing flow

• Take off the cover of the servomotor.• Connect the current source 4-20 mA to terminals 8 and 10 and set it to 4 mA. If no current source is present:

disconnect terminal 8.• With the potentiometer Ymin, move the servomotor to 0 % dosing flow (as indicated at the measuring tube).

The gear rack at the rate valve must jut out for at least 1 mm.

• Adjust lower limit switch (ST1) to a value just below Ymin.• Set the current source to 5.6 mA (this corresponds to 10 %). This and the following step cannot be done without a

current source.• Check the dosing flow indicated at the measuring tube. If it is not 10 %:

Adjust the zero point again. Possibly the floater reaches the end stop at a dosing flow of more than 0 %.• Set the current source to 20 mA. If no current source is present: connect terminal 8 to terminal 6.• With the potentiometer Ymax, move the servomotor to 100 % dosing flow (as indicated at the measuring tube).

The gear rack at the rate valve must jut out for maximum 31 mm.

Fig. 18 Rate valve with gear rack

• Adjust upper limit switch (ST2) to a value just above Ymax.• Remount the cover of the servomotor.

TM04

076

5 09

08

Note For exact adjustment, a current source 4-20 mA is necessary

Caution In case of undershoot: The rate valve may get damaged!TM

04_0

827_

0908

Caution In case of exceeding: The rate valve may get damaged!

0%

20%

40% 60%

80%

100% 0%

20%

40% 60%

80%

100%

min maxY Y

31 mm+0,5

1 mm+0,5

min.(ST1)

max.(ST2)

Ymax100% = 20 mA^

Ymin0% = 4 mA^

20 / 36

Page 21: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

5.6.3 Manual operation of the servomotorIf necessary, the servomotor can also be operated manually.

• Take off the cover of the servomotor.• Set the switch to ’manual’.• Put the servomotor manually into the desired position with an insulated wire jumper, which is temporarily plugged

into the terminals 16/17 or 17/18.– By bridging of the contacts 16 and 17, the servomotor move to the position ’close’.– By bridging of the contacts 17 and 18, the servomotor move to the position ’open’.

• Remount the cover of the servomotor.(Automatic operation is set by setting the switch to ’automatic’.)

Fig. 19 Manual operation of the servomotor

5.6.4 Remote indication of the slide switch position• Remote indication of the manual/automatic slide switch position is possible if required. The tap is made with the

terminals 13,14 and 15.

Fig. 20 Remote indication of the slide switch position

WarningDanger!Do not touch bare wires or clamp screws!

TM04

_085

7_09

08

TM04

_085

8_09

08

Note The terminals 13, 14 and 15 allow remote indication of the slide switch position for AUTO/MAN.

16 17 18

+_

AUTOMAN

80%

Y

20%

0% 100%

40%

80%

100%0%

20%

40% 60%60%

min Ymax

1716 18

openclose

131415

AUTO

MANCOM

80%

Y

20%

0% 100%

40%

80%

100%0%

20%

40% 60%60%

min Ymax

21 / 36

Page 22: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

6. Assembly drawings, spare part sets and spare parts

6.1 Gas Dosing System

6.1.1 Gas Dosing System VGS-141

Fig. 21 Assembly drawing Gas dosing system VGS-141

TM04

_082

9_09

08

g/h

1200

1000

800

600

2

200

100

100

60

400

C

l 20

°C 0

.932

bar

abs

0

Netz-Zugang

Netz CONEX DOSIPOS

Netz Stellmotor

60

-10

-100

6

8

40

0

0

mWCkPa

4

20280

Kl.1,0

vers hydro-ejecteurto injectorzum Injektor

1,5

9.1

9.3

5

A B

6.2.4

B - BA - A

(12.5112-000__-001)

A B

3

11.15

12.17

22 / 36

Page 23: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

6.1.2 Gas Dosing System VGS-143

Fig. 22 Assembly drawing Gas dosing system VGS-143TM

04 0

830

0908

G1.

630

Cl

20°

C 0

.932

bar

abs

ALL

DO

S

1 50

5

2

200

10

400

600

15

800

kg/h

20 1000

1050

#/day

0

Netz Stellmotor

Netz-Zugang

-10

-100

880

60

6

Kl.1,0kPamWC

0

0

40

2

4

20

to injectorzum Injektor

vers hydro-ejecteur

Ne pas ouvrir!L entretien ne doit ètre effectuè que par du personnel qualifiè.

service personnel only.Maintenance by authorisedDo not open!

PersonalWartung nur durch autorisiertesNicht öffnen!

ATTENTION

CAUTION

ACHTUNG

A - A

A B

B - BA B

5

2

1.5

9.1

(12.5141-000__-001)

9.3

3

11.15

23 / 36

Page 24: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

6.1.3 Gas Dosing System VGS-145

Fig. 23 Assembly drawing Gas dosing system VGS-145

TM04

083

1 09

08

0

B - B

BA

A - A BA

(12.5149-000_001)

1,5

9.1

9.3

5

3

11.15

24 / 36

Page 25: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

6.2 Measuring tube support

6.2.1 Measuring tube support VGS-141

Fig. 24 Assembly drawing Measuring tube suport VGS-141

TM04

083

2 09

08

1.2

1.3

1.4*

1.6*

1.5**

1.5.2

1.5.4

1.5.3

1.1*

1.9

1.6*

1.7

1.8

1.4*

1.3

1.2

1.5**

1.5.2

1.5.4

1.5.3

1.1*

200g/h, 500g/h, 1kg/h, 2kg/h, 4kg/h, 8kg/h, 10kg/h 2kg/h, 4kg/h, 8kg/h, 10kg/h

25 / 36

Page 26: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

6.2.2 Measuring tube support VGS-143

Fig. 25 Assembly drawing Measuring tube suport VGS-143

TM04

083

4 09

08

1.1*

1.2

1.3

1.4*

1.6*

1.5**

1.5.2

1.5.4

1.5.3

1.9

1.6*

1.3

1.2

1.1*

1.5**

1.5.2

1.5.3

1.5.4

20kg/h, 40kg/h

1.4*

26 / 36

Page 27: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

6.2.3 Measuring tube support VGS-145

Fig. 26 Assembly drawing Measuring tube suport VGS-145

TM04

083

6 09

08

1.6*

1.5

1.4*

1.3

1.2

1.1*

1.53 1.53

1.9

1.6*

1.5

1.4*

1.3

1.2

1.1*

1.52 1.52

1.54 1.54

70kg/h, 120kg/h, 200kg/h

27 / 36

Page 28: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

6.3 Rate valve

6.3.1 Rate valve Gas Dosing System VGS-141

Fig. 27 Assembly drawing Rate valve VGS-141

TM04

083

8 09

08

2.11

2.15

2.10*2.9*

2.8*

2.72.3

2.1

2.2

2.4

2.5

2.14

2.16*

2.17

2.22*

2.19

2.13

2.12

2.6

2.21

2.122.12

2.20

2.19

2.26*

200g/h, 500g/h, 1kg/h, 2kg/h, 4kg/h, 8kg/h, 10kg/h

28 / 36

Page 29: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

6.3.2 Rate valve Gas Dosing System VGS-143

Fig. 28 Assembly drawing Rate valve VGS-143

TM04

083

9 09

08

2.11

2.15

2.10

2.9 2.8

2.7

2.3

2.1

2.2

2.4

2.5

2.14

2.16

2.17

2.18

2.19

2.132.12

2.6

2.21

2.12

2.12

2.20

2.19

20kg/h, 40kg/h

29 / 36

Page 30: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

6.3.3 Rate valve Gas Dosing System VGS-145

Fig. 29 Assembly drawing Rate valve VGS-145

TM04

084

0 09

08

2.11

2.15

2.10* 2.9*

2.8*2.7

2.3

2.1

2.2

2.4

2.5

2.14

2.16*

2.17

2.18*

2.19

2.12

2.6

2.21

2.12

2.12

2.20

2.19

70kg/h, 120kg/h, 200kg/h

30 / 36

Page 31: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

6.4 Differential pressure regulator

6.4.1 Differential pressure regulator VGS-141

Fig. 30 Assembly drawing Differential pressure regulator VGS-141

TM04

084

1 09

08

3.223.23

3.5 3.4

3.5*3.3

3.253.26

3.19

3.16*

3.27

3.2*3.28

3.123.6

3.8*

3.9*3.7

3.10*

3.11

3.21 3.18*3.17

3.24

3.24

200g/h, 500g/h, 1kg/h, 2kg/h, 4kg/h, 8kg/h, 10kg/h

31 / 36

Page 32: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

6.4.2 Differential pressure regulator VGS-143

Fig. 31 Assembly drawing Differential pressure regulator VGS-143

TM04

084

2 09

08

3.173.183.14

3.16*

3.15

3.18*

3.13

3.11

3.19

3.22

3.7

3.9*

3.10*

3.6

3.8*

3.19

3.21

3.1 3.3

3.4

3.5*

3.24

3.21

3.20

3.12

3.23

3.20

3.2*

20kg/h, 40kg/h

32 / 36

Page 33: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

6.4.3 Differential pressure regulator VGS-145

Fig. 32 Assembly drawing Differential pressure regulator VGS-145

TM04

084

3 09

08

3.17

3.18*

3.14

3.16*

3.15

3.18

3.13

3.11

3.19

3.22

3.7

3.9*

3.10*

3.6

3.8*

3.19

3.21

3.1 3.3

3.4

3.5

3.24

3.213.20

3.12 3.233.20

3.2*

70kg/h, 120kg/h, 200kg/h

33 / 36

Page 34: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

6.5 Spare part sets and spare partsSpare part sets are consisting of springs, diaphragm, gaskets of the rate valve and a set of o-rings. In the figures 24 to 32 the spare part sets are marked with an asterisk. We suggest to store some spare part sets to ensure fast replacing of wearing parts (only by authorized personnel), if necessary.

6.5.1 Spare part sets

6.6 Spare partsYou find the spare part positions in the assembly drawings of Gas Dosing Systems, see chapter 6.1, Gas dosing systeme

6.6.1 Spare parts VGS-141

Type Dosing flow Order no.

VGS-141 10-200 g/h to 25-500 g/h Cl2 96729331 (553-1076.1)VGS-141 50-1000 g/h to 500-10000 g/h Cl2 96688759 (553-1077.1)VGS-143 1-20 kg/h to 2-40 kg/h Cl2 96688761 (553-1078.1)VGS-145 3.5-70 kg/h to 10-200 kg/h Cl2 96688763 (553-1079.1)

Pos. Dosing flow Order no. Item

5 0,2 - 10 kg/h

96708712 (12.5022-421) Servomotor, 230V, 50/60HZ, potentiometer95712326 (12.5022-422) Servomotor, 115V, 50/60HZ, potentiometer96680874 (12.5022-431) Servomotor, 230V, 50/60HZ, 4-20mA input96708713 (12.5022-432) Servomotor, 115V, 50/60HZ, 4-20mA input

1.5

0,2 kg/h 96709011 (12.659-41)

Measuring tube (flowmeter), for sampling

0,5 kg/h 96709012 (12.659-42)1 kg/h 96709016 (12.659-51)2 kg/h 96709017 (12.659-52)4 kg/h 96681144 (12.659-46)8 kg/h 96680919 (12.5117-413)

10 kg/h 96680922 (12.5118-401)2 kg/h 96680918 (12.5117-411)

Measuring tube (flowmeter), for sampling4 kg/h 96708758 (12.5117-412)8 kg/h 96680919 (12.5117-413)

10 kg/h 96680922 (12.5118-401)

3

0,2 kg/h,0,5 kg/h 95712327 (12.5157-301)

Differential pressure controller1, 2, 4 kg/h 96680947 (12.5157-303)8, 10 kg/h 95712328 (12.5157-305)

1.5 0,2 kg/h 96709011 (12.659-41) Measuring tube (flowmeter), for sampling

9.1 0,2 - 10 kg/h96680903 (12.5096) Vacuummeter, without contacts96680904 (12.5097) Vacuummeter, with contacts

9.30,2-4/10 kg/h 96679909 (10.8368-551) PE-SL4/6, lenght 550 mm

8 kg/h 96708107 (10.8368-851) PE-SL4/6, lenght 850 mm11.15 0,2 - 10 kg/h 96708106 (10.8368-451) PE-SL4/6, length 450 mm12.17 0,2 - 10 kg/h 96708989 (12.6445-600) PE-SL10/14, length 600 mm

34 / 36

Page 35: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

6.6.2 Spare parts VGS-143

6.6.3 Spare parts VGS-145

Pos. Dosing flow Order no. Item

1.520 kg/h 96680923 (12.5118-403)

Measuring tube (flowmeter), for sampling/without sampling40 kg/h 96680924 (12.5118-404)

320 kg/h 96708607 (12.4258-103)

Differential pressure controller40 kg/h 96708606 (12.4258-101)

5 20/40 kg/h

96708712 (12.5022-421) Servomotor, 230V, 50/60HZ, potentiometer95712326 (12.5022-422) Servomotor, 115V, 50/60HZ, potentiometer96680874 (12.5022-431) Servomotor, 230V, 50/60HZ, 4-20mA input96708713 (12.5022-432) Servomotor, 115V, 50/60HZ, 4-20mA input

9.1 20/40 kg/h96680903 (12.5096) vacuummeter, without contacts96680904 (12.5097) vacuummeter, with contacts

9.3 20/40 kg/h 96679909 (10.8368-551) PE-SL4/6, lenght 550mm11.15 20/40 kg/h 96708106 (10.8368-451) PE-SL4/6, length 450mm

Pos. Dosing flow Order no. Item

1.570 kg/h 96680944 (12.5154-401)

Measuring tube (flowmeter), for sampling/without sampling120 kg/h 96680945 (12.5154-402)200 kg/h 96680946 (12.5154-403)

1.52 70/120/200 kg/h 96681013 (12.5334) Bottom limit (measuring tube)

1.5370/120 kg/h 96680940 (12.5153-1)

Floater200 kg/h 96708772 (12.5153-2)

370 kg/h 96708605 (12.4257-105)

Differential pressure controller120 kg/h 96708603 (12.4257-103)200 kg/h 96708602 (12.4257-101)

1.54 70/120/200 kg/h 96708703 (12.5011-400) Top limit (measuring tube)

5 20/40 kg/h

96708712 (12.5022-421) Servomotor, 230V, 50/60 HZ, potentiometer95712326 (12.5022-422) Servomotor, 115V, 50/60 HZ, potentiometer96680874 (12.5022-431) Servomotor, 230V, 50/60 HZ, 4-20 mA input96708713 (12.5022-432) Servomotor, 115V, 50/60 HZ, 4-20 mA input

9.1 70/120/200 kg/h96680903 (12.5096) vacuummeter, without contacts96680904 (12.5097) vacuummeter, with contacts

9.3 70/120/200 kg/h 96679909 (10.8368-551) PE-SL4/6, lenght 550 mm11.15 70/120/200 kg/h 96708106 (10.8368-451) PE-SL4/6, length 450 mm

35 / 36

Page 36: Gas dosing system - Grundfosnet.grundfos.com/Appl/WebCAPS/Grundfosliterature-1665254.pdf · 6.1 Gas Dosing System ... 1 - 20 kg/h 50 - 1050 #/day 2 ... Do not place the device standing

36

ArgentinaBombas GRUNDFOS de Argentina S.A.Ruta Panamericana km. 37.500 Lote 34A1619 - GarinPcia. de Buenos AiresPhone: +54-3327 414 444Telefax: +54-3327 411 111AustraliaGrundfos AlldosDosing & DisinfectionALLDOS Oceania Pty. Ltd.Unit 3 / 74 Murdoch CircuitAcacia Ridge QLD 4100Phone: +61 (0)7 3712 6888Telefax: +61 (0)7 3272 5188E-mail: [email protected] AustraliaGRUNDFOS Pumps Pty. Ltd. P.O. Box 2040 Regency Park South Australia 5942 Phone: +61-8-8461-4611 Telefax: +61-8-8340 0155 AustriaGRUNDFOS Pumpen Vertrieb Ges.m.b.H.Grundfosstraße 2 A-5082 Grödig/Salzburg Tel.: +43-6246-883-0 Telefax: +43-6246-883-30 BelgiumN.V. GRUNDFOS Bellux S.A. Boomsesteenweg 81-83 B-2630 Aartselaar Tél.: +32-3-870 7300 Télécopie: +32-3-870 7301BelorussiaПредставительство ГРУНДФОС в Минске220123, Минск,ул. В. Хоружей, 22, оф. 1105Тел.: +(37517) 233 97 65Факс: (37517) 233 9769E-mail: [email protected]/HerzegovinaGRUNDFOS SarajevoTrg Heroja 16,BiH-71000 SarajevoPhone: +387 33 713 290Telefax: +387 33 659 079e-mail: [email protected] GRUNDFOS Ltda.Av. Humberto de Alencar Castelo Branco, 630CEP 09850 - 300São Bernardo do Campo - SPPhone: +55-11 4393 5533Telefax: +55-11 4343 5015BulgariaGRUNDFOS Pumpen VertriebRepresentative Office - BulgariaBulgaria, 1421 SofiaLozenetz District105-107 Arsenalski blvd. Phone: +359 2963 3820, 2963 5653Telefax: +359 2963 1305CanadaGRUNDFOS Canada Inc. 2941 Brighton Road Oakville, Ontario L6H 6C9 Phone: +1-905 829 9533 Telefax: +1-905 829 9512 ChinaGrundfos AlldosDosing & DisinfectionALLDOS (Shanghai) Water Technology Co. Ltd.West Unit, 1 Floor, No. 2 Building (T 4-2)278 Jinhu Road, Jin Qiao Export Processing ZonePudong New Area Shanghai, 201206Phone: +86 21 5055 1012Telefax: +86 21 5032 0596E-mail: [email protected] ChinaGRUNDFOS Pumps (Shanghai) Co. Ltd.22 Floor, Xin Hua Lian Building755-775 Huai Hai Rd, (M)Shanghai 200020PRCPhone: +86-512-67 61 11 80Telefax: +86-512-67 61 81 67CroatiaGRUNDFOS CROATIA d.o.o.Cebini 37, BuzinHR-10010 ZagrebPhone: +385 1 6595 400 Telefax: +385 1 6595 499www.grundfos.hrCzech RepublicGRUNDFOS s.r.o.Čapkovského 21779 00 OlomoucPhone: +420-585-716 111Telefax: +420-585-716 299

DenmarkGRUNDFOS DK A/S Martin Bachs Vej 3 DK-8850 Bjerringbro Tlf.: +45-87 50 50 50 Telefax: +45-87 50 51 51 E-mail: [email protected]/DKEstoniaGRUNDFOS Pumps Eesti OÜPeterburi tee 92G11415 TallinnTel: + 372 606 1690Fax: + 372 606 1691FinlandOY GRUNDFOS Pumput AB Mestarintie 11 FIN-01730 Vantaa Phone: +358-3066 5650 Telefax: +358-3066 56550FranceGrundfos AlldosDosing & DisinfectionALLDOS S.A.R.L.7, rue GutenbergF-67610 La WantzenauTél.: +33-3 88 59 26 26Télécopie: +33-3 88 59 26 00E-mail : [email protected] FrancePompes GRUNDFOS Distribution S.A. Parc d’Activités de Chesnes 57, rue de Malacombe F-38290 St. Quentin Fallavier (Lyon) Tél.: +33-4 74 82 15 15 Télécopie: +33-4 74 94 10 51 GermanyGrundfos AlldosDosing & DisinfectionALLDOS Eichler GmbHReetzstraße 85D-76327 Pfinztal (Söllingen)Tel.: +49 7240 61-0 Telefax: +49 7240 61-177E-mail: [email protected] GermanyGRUNDFOS GMBHSchlüterstr. 33D-40699 ErkrathTel.: +49-(0) 211 929 69-0 Telefax: +49-(0) 211 929 69-3799E-mail: [email protected] in Deutschland:E-mail: [email protected] Hellas A.E.B.E. 20th km. Athinon-Markopoulou Av. P.O. Box 71 GR-19002 Peania Phone: +0030-210-66 83 400 Telefax: +0030-210-66 46 273Hong KongGRUNDFOS Pumps (Hong Kong) Ltd. Unit 1, Ground floor Siu Wai Industrial Centre 29-33 Wing Hong Street & 68 King Lam Street, Cheung Sha Wan Kowloon Phone: +852-27861706 / 27861741 Telefax: +852-27858664 HungaryGRUNDFOS Hungária Kft.Park u. 8H-2045 Törökbálint, Phone: +36-23 511 110Telefax: +36-23 511 111IndiaGRUNDFOS Pumps India Private Limited118 Old Mahabalipuram RoadThoraipakkamChennai 600 096Phone: +91-44 2496 6800IndonesiaPT GRUNDFOS Pompa Jl. Rawa Sumur III, Blok III / CC-1 Kawasan Industri, Pulogadung Jakarta 13930 Phone: +62-21-460 6909 Telefax: +62-21-460 6910 / 460 6901 IrelandGRUNDFOS (Ireland) Ltd. Unit A, Merrywell Business ParkBallymount Road LowerDublin 12 Phone: +353-1-4089 800 Telefax: +353-1-4089 830 ItalyGRUNDFOS Pompe Italia S.r.l. Via Gran Sasso 4I-20060 Truccazzano (Milano)Tel.: +39-02-95838112 Telefax: +39-02-95309290 / 95838461 JapanGRUNDFOS Pumps K.K.Gotanda Metalion Bldg. 5F,5-21-15, Higashi-gotandaShiagawa-ku, Tokyo, 141-0022 JapanPhone: +81 35 448 1391Telefax: +81 35 448 9619

KoreaGRUNDFOS Pumps Korea Ltd.6th Floor, Aju Building 679-5Yeoksam-dong, Kangnam-ku, 135-916Seoul, KoreaPhone: +82-2-5317 600Telefax: +82-2-5633 725LatviaSIA GRUNDFOS Pumps Latvia Deglava biznesa centrsAugusta Deglava ielā 60, LV-1035, Rīga,Tālr.: + 371 714 9640, 7 149 641Fakss: + 371 914 9646LithuaniaGRUNDFOS Pumps UABSmolensko g. 6LT-03201 VilniusTel: + 370 52 395 430Fax: + 370 52 395 431MalaysiaGRUNDFOS Pumps Sdn. Bhd.7 Jalan Peguam U1/25Glenmarie Industrial Park40150 Shah AlamSelangor Phone: +60-3-5569 2922Telefax: +60-3-5569 2866MéxicoBombas GRUNDFOS de México S.A. de C.V. Boulevard TLC No. 15Parque Industrial Stiva AeropuertoApodaca, N.L. 66600Phone: +52-81-8144 4000 Telefax: +52-81-8144 4010NetherlandsGrundfos AlldosDosing & DisinfectionALLDOS BVLeerlooiersstraat 6NL-8601 WK SneekTel.: +31-51 54 25 789Telefax: +31-51 54 30 550E-mail: [email protected] NetherlandsVeluwezoom 351326 AE AlmerePostbus 22015 1302 CA ALMERE Tel.: +31-88-478 6336 Telefax: +31-88-478 6332 e-mail: [email protected] ZealandGRUNDFOS Pumps NZ Ltd.17 Beatrice Tinsley CrescentNorth Harbour Industrial EstateAlbany, AucklandPhone: +64-9-415 3240Telefax: +64-9-415 3250NorwayGRUNDFOS Pumper A/S Strømsveien 344 Postboks 235, Leirdal N-1011 Oslo Tlf.: +47-22 90 47 00 Telefax: +47-22 32 21 50 PolandGRUNDFOS Pompy Sp. z o.o.ul. Klonowa 23Baranowo k. PoznaniaPL-62-081 PrzeźmierowoTel: (+48-61) 650 13 00Fax: (+48-61) 650 13 50PortugalBombas GRUNDFOS Portugal, S.A. Rua Calvet de Magalhães, 241Apartado 1079P-2770-153 Paço de ArcosTel.: +351-21-440 76 00Telefax: +351-21-440 76 90RomâniaGRUNDFOS Pompe România SRLBd. Biruintei, nr 103 Pantelimon county IlfovPhone: +40 21 200 4100Telefax: +40 21 200 4101E-mail: [email protected]ООО ГрундфосРоссия, 109544 Москва, ул. Школьная 39Тел. (+7) 495 737 30 00, 564 88 00Факс (+7) 495 737 75 36, 564 88 11E-mail [email protected] GRUNDFOS Predstavništvo BeogradDr. Milutina Ivkovića 2a/29YU-11000 Beograd Phone: +381 11 26 47 877 / 11 26 47 496Telefax: +381 11 26 48 340SingaporeGRUNDFOS (Singapore) Pte. Ltd. 24 Tuas West Road Jurong Town Singapore 638381 Phone: +65-6865 1222 Telefax: +65-6861 8402

SloveniaGRUNDFOS PUMPEN VERTRIEB Ges.m.b.H.,Podružnica LjubljanaŠlandrova 8b, SI-1231 Ljubljana-ČrnučePhone: +386 1 568 0610Telefax: +386 1 568 0619E-mail: [email protected] AfricaGrundfos AlldosDosing & DisinfectionALLDOS (Pty) LTD98 Matroosberg Road, Waterkloof ParkP.O. Box 36505, Menlo Park 01020181 ZA Pretoria E-mail: [email protected] GRUNDFOS España S.A. Camino de la Fuentecilla, s/n E-28110 Algete (Madrid) Tel.: +34-91-848 8800 Telefax: +34-91-628 0465 SwedenGRUNDFOS AB (Box 333) Lunnagårdsgatan 6 431 24 Mölndal Tel.: +46(0)771-32 23 00 Telefax: +46(0)31-331 94 60 SwitzerlandGrundfos AlldosDosing & DisinfectionALLDOS International AGSchönmattstraße 4 CH-4153 ReinachTel.: +41-61-717 5555Telefax: +41-61-717 5500E-mail: [email protected] Pumpen AG Bruggacherstrasse 10 CH-8117 Fällanden/ZH Tel.: +41-1-806 8111 Telefax: +41-1-806 8115 TaiwanGRUNDFOS Pumps (Taiwan) Ltd. 7 Floor, 219 Min-Chuan Road Taichung, Taiwan, R.O.C. Phone: +886-4-2305 0868Telefax: +886-4-2305 0878ThailandGRUNDFOS (Thailand) Ltd. 92 Chaloem Phrakiat Rama 9 Road,Dokmai, Pravej, Bangkok 10250Phone: +66-2-725 8999Telefax: +66-2-725 8998TurkeyGRUNDFOS POMPA San. ve Tic. Ltd. Sti.Gebze Organize Sanayi Bölgesi Ihsan dede Caddesi,2. yol 200. Sokak No. 20441490 Gebze/ KocaeliPhone: +90 - 262-679 7979Telefax: +90 - 262-679 7905E-mail: [email protected]ТОВ ГРУНДФОС УКРАЇНА 01010 Київ, Вул. Московська 8б, Тел.:(+38 044) 390 40 50 Фах.: (+38 044) 390 40 59E-mail: [email protected] Arab EmiratesGRUNDFOS Gulf DistributionP.O. Box 16768Jebel Ali Free ZoneDubaiPhone: +971-4- 8815 166Telefax: +971-4-8815 136United KingdomGrundfos AlldosDosing & DisinfectionALLDOS Ltd.39 Gravelly Industrial Park, Tyburn RoadBirmingham B24 8TGPhone: +44-121-3283336Telefax: +44-121-3284332E-mail: [email protected] United KingdomGRUNDFOS Pumps Ltd. Grovebury Road Leighton Buzzard/Beds. LU7 8TL Phone: +44-1525-850000 Telefax: +44-1525-850011 U.S.A.GRUNDFOS Pumps Corporation 17100 West 118th TerraceOlathe, Kansas 66061Phone: +1-913-227-3400 Telefax: +1-913-227-3500 UsbekistanПредставительство ГРУНДФОС в Ташкенте700000 Ташкент ул.Усмана Носира 1-й тупик 5Телефон: (3712) 55-68-15Факс: (3712) 53-36-35

Addresses revised 15.06.2009

15.710298 V2.0 95 714270 0210 GBRepl. 15.710298 V1.0 Repl. 95 714270 0209