608 State St. South Kirkland, WA 98033 www.faira.com [email protected] +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, WA 98445 Thank you for your interest in this Faira Certified home. We have coordinated the efforts of certified and licensed inspection and title professionals to create the Faira Transparency Reports for this home. The Faira Transparency Reports are a detailed portfolio of information that is prepared on behalf of buyers in preparation for making an informed offer on the property. You may view more detailed information for this home and can make an offer at http://www.faira.com/listings/11950 All of the information in the Faira Transparency Reports was gathered and compiled without any bias or influence from the seller(s). In fact, these reports are materially identical had you as the buyer(s) ordered the same professionals to perform the evaluations on the same date. Nevertheless, Faira takes no obligation of the reports being complete or accurate. The buyers are recommended to conduct their own due-diligence to their satisfaction. Please contact us if you have any questions or would like more information. We’re happy you’ve chosen a Faira Certified home and look forward to the opportunity of working with you! The Faira Team

Transcript of FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door...

Page 1: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

608 State St. South Kirkland, WA 98033

www.faira.com

[email protected] +1.800.571.FAIR

FAIRA TRANSPARENCY REPORTS

17812 25th Ave E, Tacoma, WA 98445 Thank you for your interest in this Faira Certified home. We have coordinated the efforts of certified and licensed inspection and title professionals to create the Faira Transparency Reports for this home. The Faira Transparency Reports are a detailed portfolio of information that is prepared on behalf of buyers in preparation for making an informed offer on the property.

You may view more detailed information for this home and can make an offer at

http://www.faira.com/listings/11950 All of the information in the Faira Transparency Reports was gathered and compiled without any bias or influence from the seller(s). In fact, these reports are materially identical had you as the buyer(s) ordered the same professionals to perform the evaluations on the same date. Nevertheless, Faira takes no obligation of the reports being complete or accurate. The buyers are recommended to conduct their own due-diligence to their satisfaction. Please contact us if you have any questions or would like more information. We’re happy you’ve chosen a Faira Certified home and look forward to the opportunity of working with you! The Faira Team

Page 2: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Repaired items:

• Drain in crawl space has been resealed and tested • Carbon Monoxide alarms have been installed • Water heater control knob was on the floor next to the system • Door to Garage hinges have been tightened to address rubbing concern • Quote to clean up crawl space including insulation and pest/construction debris has been

requested. • Outlet with "reverse polarity" has been rewired

Page 3: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Confidential Inspection Report

LOCATED AT:17812 25th Ave E

Tacoma, Washington 98445

PREPARED EXCLUSIVELY FOR:Faira.com

INSPECTED ON:Wednesday, April 18, 2018

Inspector, Isaac McPhee Strong Foundations Home Inspection

Page 4: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 2 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Executive Summary

This is a summary review of the inspectors' findings during this inspection. However, it does not contain every detailed observation. This is provided as an additional service to our client, and is presented in the form of a listing of the items which, in the opinion of your inspector, merit further attention, investigation, or improvement. Some of these conditions are of such a nature as to require repair or modification by a skilled craftsman, technician, or specialist. Others can be easily handled by a homeowner such as yourself.

Often, following the inspector's advice will result in improved performance and/or extended life of the component(s) in question. In listing these items, your inspector is not offering any opinion as to who, among the parties to this transaction, should take responsibility for addressing any of these concerns. As with most of the facets of your transaction, we recommend consultation with your Real Estate Professional for further advice with regards to the following items:

= Item in poor condition, warranting immediate repair or replacement

= Item that warrants repair or replacement now or in the near term, but does not pose an immediate risk or threat

= Upgrade recommended, but not required

= Potentially dangerous or hazardous condition that should be corrected as soon as possible (safety concern)

= Item not operating at the time of the inspection, or unable to be inspected for another reason

= Item that warrants continued monitoring or further evaluation by licensed professional. Though issues may not necessarily exist in the present or are not readily visible, monitoring or further evaluation is recommended.

Exterior/Site/Ground

FOUNDATION

1: - Hairline and/or small cracks, within normal tolerances, are visible. This type of cracking is often a result of shrinkage of materials and/or minor settlement and usually does not affect the strength of the foundation. No action is indicated.

PLYWOOD SIDING

2: - Sections of the plywood siding are deteriorated, primarily at or near the bottom edges. We recommend these sections be repaired or replaced.

Additionally, the siding shows typical wear and tear and is in need of cosmetic and preventative maintenance, including filling any holes/gaps and painting as needed.

SCREENS

3: - There is some minor damage to window screens here and there. Recommend repairing any damaged screens as needed.

Page 5: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 3 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

DRAINAGE

4: - It is our opinion that the existing surface drainage system is either insufficient or defective, based on moisture conditions below the home (see "Crawl Space" section). We recommend further evaluation by a specialist to determine which repairs or upgrades to the drainage system be undertaken.

PATIO SURFACE

5: - The patio shows normal cracking and/or minor settlement. This does not impact its integrity. No action is indicated.

FENCING

6: - The fencing is deteriorated in some areas and its remaining service life is limited. Expect the need for replacement or repair in the near future. Typically, fencing around the perimeter of the home is considered a shared responsibility between owners of adjacent properties. Recommend inquiring of neighbors prior to making repairs.

GATES

7: - The north fence gate was blocked and/or were inaccessible for inspection. We recommend further review.

VEGETATION

8: - Some trees or shrubberies were observed to be in contact with or near the siding or foundation. Recommend trimming back all trees and shrubberies at least 6 inches from the home in order to protect the home's surface from moisture or pest intrusion.

TRIM

9: - Portions of trim boards were observed to be at or below grade. This may lead to deterioration of lower board ends. Recommend maintaining proper gaps between the earth and trim boards and repairing any existing damage.

FASCIA

10: - Sections of the fascia on the north side are deteriorated. We recommend they be repaired or replaced. Other fascia boards are worn and in need of typical maintenance

EAVES/SOFFITS

11: - There is mildew on the underside of the roof eaves. We recommend that it be removed with several applications of bleach prior to any repainting or refinishing.

12: - There are one or more hives or nests under the overhang at the exterior of the home. Although these are not considered a deficiency in the structure, we recommend they be removed for personal safety and/or a better appearance.

PAINT/STAIN

13: - The exterior paint is in fair to good condition but appears a bit 'tired'. There are no surfaces that need painting for other than cosmetic reasons.

Page 6: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 4 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Roofing

Composition Shingle

SURFACE

14: - Some moss was growing on the roof surface. As a result, shingles can lift or be damaged. Leaks can result and/or the roof surface can fail prematurely if the moss is left to grow unabated. Efforts should be made to kill the moss during its growing season (wet months). Typically, zinc or phosphate based chemicals are used for this and must be applied periodically.

15: - The roof surface is in generally satisfactory condition, though some isolated instances of granulation loss, cracking shingles (especially at the ridges where shingles are bent) or broken shingle corners, were observed, though nothing to suggest the need for immediate repairs. Recommend continuing to monitor as the surface ages and repairing as needed.

PLUMBING VENTS

16: - One or more plumbing vents at the roof are showing signs of tearing or warping at the neoprene flashing. Recommend replacement of any damaged plumbing flashings.

GUTTERS

17: - Debris was present in portions of the gutters, which limited our visual inspection. We recommend all debris be removed to ensure proper drainage. The condition of the gutters can be better assessed at that time.

Garage

GARAGE DOOR OPENER

18: - One of the garage door opener failed to respond to normal operating controls. We recommend the opener and/or the controls be repaired or replaced.

FLOOR

19: - There is cracking in the floor slab but there is no vertical displacement of any portion of the slab. No action is indicated.

GARAGE DOORS

20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the event of breakage, in accordance with present standards.

GENERAL COMMENT

21: - Due to the presence of personal belongings, access to portions of the area were effectively blocked at the time of our inspection. A 'walk-through' is recommended when the area is cleared and accessible.

Page 7: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 5 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Kitchen

AIR GAP

22: - The dishwasher drain has no air-gap and the drain line is not looped below the cabinet. The dishwasher will function without it, but the installation does not meet present standards. We suggest installation of an air-gap or rerouting the drain line to prevent backflow of drainwater.

Bathroom

First Floor Hallway

SHOWER WALLS

23: - The joint caulking above the shower is in marginal condition, with some staining or cracking evident. The enclosure should be recaulked to prevent moisture penetration into the surrounding materials and subsequent damage.

DOORS

24: - The door rubs on the frame. We recommend it be planed or sanded for smoother operation.

First Floor Master

WATER BASIN

25: - The drain stops are defective. We recommend they be repaired or replaced.

BATHROOM FLOOR

26: - It is important to maintain the caulking around bathtubs and showers, especially at the intersection between the tub or shower and the floor. Failure to maintain this seal will often result in damage to flooring materials, subflooring and framing.

27: - Particle board trim pieces at the bathroom floor showed signs of swelling. This is typical when this type of trim is used in bathrooms, as it is highly susceptible to moisture. Recommend replacing trim as warranted.

COUNTERTOPS

28: - The rigid grout joint between the counter and the backsplash is standard practice. There are hairline cracks and this condition is likely to return even after patching. We recommend a flexible sealant at this location.

Bedroom

Second Floor Master

DOORS

29: - The closet door doesn't latch properly. We recommend minor adjustments to the hardware to restore proper function.

Page 8: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 6 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

WINDOWS

30: - There is a defective latch on one of the windows. We recommend the hardware be repaired or replaced.

Second Floor Rear

RECEPTACLES

31: - A receptacle is wired with reversed polarity. Under some circumstances, this can be a shock hazard and/or damage electronic equipment. It is easy to correct this condition and we recommend the receptacle be repaired.

LIGHTS / FAN

32: - The ceiling fan was somewhat noisy when operating. This may indicate a motor nearing the end of its useful life. Recommend replacing if noise makes fan difficult to use.

Second Floor Right Front

LIGHTS / FAN

33: - The ceiling fan was somewhat noisy when operating. This may indicate a motor nearing the end of its useful life. Recommend replacing if noise makes fan difficult to use.

Living/Dining Room

WINDOWS

34: - One or more of the windows do not operate properly because their spring mechanisms are damaged. We recommend these windows be repaired. We recommend great care when opening window.

Interior

SURFACES: OVERALL

35: - There is wear and tear throughout the house, of the type generally resulting from age and heavy use. We make no attempt to list all cosmetic flaws and suggest that most of these deficiencies will be addressed by routine maintenance and upgrading.

DETECTORS: OVERALL

36: - Carbon monoxide detectors were not found in the home. Typical building practice calls for at least one CO detector per floor of living space. Recommend installing CO detectors due to safety concerns.

Crawl Space

ACCESS

37: - The crawlspace hatch cover is deteriorated and in need of replacement. Recommend repairing cover to properly seal the crawlspace from moisture or pest entry.

Page 9: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 7 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

FOUNDATION

38: - Hairline and/or small cracks, within normal tolerances, are visible. This type of cracking is often a result of shrinkage of materials and/or minor settlement and usually does not affect the strength of the foundation. No action is indicated.

MOISTURE

39: - The crawl space was excessively moist, with much of the soil in a soft or muddy condition, along with some standing moisture on top of the vapor barrier. This is an undesirable condition conducive to structural settlement, pest control problems and rusting of mechanical components.

Recommend further evaluation by a crawlspace or drainage specialist to determine the source of the moisture and make any necessary upgrades to drainage, as well as replacing any dirty or damage vapor barrier.

VAPOR BARRIER

40: - Vapor barrier is very dirty with construction debris, rodent droppings, and other materials. Recommend replacing vapor barrier for cleanliness, and to prevent a buildup of materials that have the potential of drawing wood destroying organisms toward the home.

PEST CONTROL

41: - The crawlspace had numerous signs of rodent activity including extensive feces, torn insulation and/or evidence of nest-building activity. An effort should be made to seal the crawlspace from animal entry and you may wish to consult with a pest control service or set traps. Diseases spread through animal urine and feces can include hantavirus, raccoon roundworm encephalitis and more, some of which can be serious or fatal.

DRAIN LINES

42: - A drain pipe in the kitchen area is disconnected and draining into the crawlspace. This is a serious condition that should be repaired as quickly as possible. We also recommend the other visible components of the drain system be evaluated by a licensed plumber to determine if any other current or potential leaks are present. Additionally, the area under this leak is wet with drain water and should be cleaned and the vapor barrier replaced.

FLOOR INSULATION

43: - In several locations, the insulation is out of place and in poor condition. A significant number of the fiberglass batts are damaged. We recommend this material be replaced and/or secured back in place.

GENERAL COMMENT

44: - The conditions observed and noted above are considered significant. Due to the presence of standing drainwater, severe rodent sign, and hanging and damaged insulation, access to the crawlspace was limited. In addition to plumbing repair service, we recommend the entire crawlspace be fully evaluated and restored by a qualified crawlspace cleaning specialist. Issues present include rodent activity, moisture activity, damaged plumbing pipes, damaged insulation and very dirty/damaged vapor barrier. Note: It is possible that additional reportable issues may be discovered over the course of cleaning and repairing the crawlspace.

Page 10: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 8 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Plumbing

GENERAL COMMENT

45: - We observed problems with the plumbing system as noted above. We recommend a licensed plumber be retained to evaluate the entire plumbing system and determine an appropriate course of action.

Water Heater

IGNITION SYSTEM

46: - The control knob to adjust the temperature and turn off the water heater was missing. This control valve is both a convenience and safety feature and should be replaced for proper operation of the unit.

GENERAL COMMENT

47: - This water heater is near the end of its expected service life. Although operating, the need for replacement should be expected within the next few years.

Heat

Forced Hot Air

GENERAL COMMENT

48: - The last service date of the gas forced air furnace appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if last service date was more than one year ago, recommend that a qualified HVAC technician inspect, clean, and service the system, and make repairs if necessary. For safety reasons, and because the system is fueled by gas, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the HVAC technician when it is serviced.

Page 11: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 9 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Wednesday, April 18, 2018Faira.com

17812 25th Ave ETacoma, Washington 98445

Dear Faira.com,

We have enclosed the report for the property inspection we conducted for you on Wednesday, April 18, 2018 at:

17812 25th Ave ETacoma, Washington 98445

Our report is designed to be clear, easy to understand, and helpful. Please take the time to review it carefully. If there is anything you would like us to explain, or if there is other information you would like, please feel free to call us. We would be happy to answer any questions you may have.

Throughout the report, you'll find special symbols at the front of certain comments. Below are the symbols and their meanings:

= Item in poor condition, warranting immediate repair or replacement

= Item that warrants repair or replacement now or in the near term, but does not pose an immediate risk or threat

= Upgrade recommended, but not required

= Potentially dangerous or hazardous condition that should be corrected as soon as possible (safety concern)

= Item not operating at the time of the inspection, or unable to be inspected for another reason

= Item that warrants continued monitoring or further evaluation by licensed professional. Though issues may not necessarily exist in the present or are not readily visible, monitoring or further evaluation is recommended.

We thank you for the opportunity to be of service to you.

Sincerely,

Inspector, Isaac McPheeStrong Foundations Home Inspection

Page 12: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 10 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Page 13: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 11 of 115

RECEIPT17812 25th Ave E

Tacoma, Washington 98445

Client:Faira.com

Receipt Number:18-04009

Receipt Date:Wednesday, April 18, 2018

Quantity Description Unit Price Amount

Strong Foundations Home Inspection • (360) 488-3145 • [email protected] • (360) 488-3145 • [email protected]

Change Due

$0.00

Thank you for your business!

1 Base Amount $400.00 $400.00

Subtotal: $400.00Cash: ($400.00)

Page 14: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Table of Contents

Executive Summary.......................................................................................................................................2

Introduction..................................................................................................................................................13

Introductory Notes.......................................................................................................................................14

Exterior/Site/Ground....................................................................................................................................14

Roofing........................................................................................................................................................24

Garage.........................................................................................................................................................29

Kitchen.........................................................................................................................................................33

Laundry Area...............................................................................................................................................37

Bathroom.....................................................................................................................................................38

Bedroom......................................................................................................................................................52

Living/Dining Room.....................................................................................................................................60

Family Room...............................................................................................................................................63

Interior.........................................................................................................................................................64

Attic..............................................................................................................................................................66

Crawl Space................................................................................................................................................68

Plumbing......................................................................................................................................................74

Water Heater...............................................................................................................................................77

Heat.............................................................................................................................................................81

Electrical System.........................................................................................................................................86

Insulation/Energy.........................................................................................................................................90

Locations of Emergency Controls................................................................................................................91

Environmental Concerns.............................................................................................................................93

Conclusion...................................................................................................................................................94

tmpE437......................................................................................................................................................95

Page 15: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 13 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Introduction

We have inspected the major structural components and mechanical systems for signs of significant non- performance, excessive or unusual wear and general state of repair. The following report is an overview of the conditions observed.

In the report, there may be specific references to areas and items that were inaccessible. We can make no representations regarding conditions that may be present but were concealed or inaccessible for review. With access and an opportunity for inspection, reportable conditions may be discovered. Inspection of the inaccessible areas will be performed upon arrangement and at additional cost after access is provided.

We do not review plans, permits, recall lists, and/or government or local municipality documents. Information regarding recalled appliances, fixtures and any other items in this property can be found on the Consumer Product Safety website. These items may be present but are not reviewed.

Our recommendations are not intended as criticisms of the building, but as professional opinions regarding conditions present. As a courtesy, the inspector may list items that they feel have priority in the Executive Summary portion of the report. Although the items listed in this section may be of higher priority in the opinion of the inspector, it is ultimately the client's responsibility to review the entire report. If the client has questions regarding any of the items listed, please contact the inspector for further consultation.

Lower priority conditions contained in the body of the report that are neglected may become higher priority conditions. Do not equate low cost with low priority. Cost should not be the primary motivation for performing repairs. All repair and upgrade recommendations are important and need attention.

This report is a "snapshot" of the property on the date of the inspection. The structure and all related components will continue to deteriorate/wear out with time and may not be in the same condition at the close of escrow.

Anywhere in the report that the inspector recommends further review, it is strongly recommended that this be done PRIOR TO THE CLOSE OF ESCROW. This report is not intended for use by anyone other than the client named herein. No other persons should rely upon the information in this report. Client agrees to indemnify, defend and hold inspector harmless from any third party claims arising out of client's unauthorized distribution of the inspection report.

By accepting this inspection report, you acknowledge that you have reviewed and are in agreement with all of the terms contained in the standard contract provided by the inspector who prepared this report.

Page 16: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 14 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Introductory Notes

ORIENTATIONFor purposes of identification and reporting, the front of this building faces east.

For purposes of identification and reporting, the front of the building is the side containing the primary access.

NOTESThe house was estimated to be approximately 14+ years old.

The weather was sunny at the time of our inspection.

It had been raining prior to our inspection.

Over the course of this inspection the temperature was estimated to be between 50 and 60 degrees.

We make no representations as to the extent or presence of code violations, nor do we warrant the legal use of this building. This information would have to be obtained from the local building and/or zoning department.

A driveway and/or street is shared with other properties. To determine if maintenance-sharing or liability agreements are in effect regarding the driveway or street, consult the owner of the subject property, neighboring owners or public records.

There may be information pertinent to this property which is a matter of public record. A search of public records is not within the scope of this inspection. We recommend the client or their representative review all appropriate public records.

The scope of this inspection is limited to reasonably accessible areas. We make no attempt to move furnishings, stored personal property, and/or vegetation. Although no problems are anticipated, removal of these items may reveal reportable items.

Your inspector may choose to include photos in your inspection report. There are times when only a picture can fully explain the condition or if the client is unable to attend the inspection. Photo inclusion is at the discretion of the inspector and in no way is meant to emphasize or highlight the only conditions that were seen. We always recommend full review of the entire inspection report.

Exterior/Site/Ground

BASIC INFORMATIONGeneral lot topography: Flat lot

Page 17: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 15 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Driveway: Concrete on grade

Walkways: Concrete

Patio: Concrete

Page 18: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 16 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Primary exterior wall covering: Masonry Board

Secondary exterior wall covering: Plywood or sheet hardboard siding

Primary exterior window material: Vinyl/plastic or vinyl clad

FOUNDATION

Hairline and/or small cracks, within normal tolerances, are visible. This type of cracking is often a result of shrinkage of materials and/or minor settlement and usually does not affect the strength of the foundation. No action is indicated.

EXTERIOR PLUMBINGThe plumbing on the exterior of the building and in the yard appears to be properly installed and in serviceable condition. We make no attempt to locate and test every hose bib. Testing of irrigation systems is beyond the scope of our inspection.

Page 19: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 17 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Testing of the irrigation system and/or automatic timer is beyond the scope of this inspection.

OUTDOOR RECEPTACLESThe receptacles were found to be properly installed and in serviceable condition.

OUTDOOR LIGHTSThe outdoor lights were tested and appeared functional at the time of the inspection.

PLYWOOD SIDING

Sections of the plywood siding are deteriorated, primarily at or near the bottom edges. We recommend these sections be repaired or replaced.

Additionally, the siding shows typical wear and tear and is in need of cosmetic and preventative maintenance, including filling any holes/gaps and painting as needed.

Caulking/sealing needed Deteriorated siding

Page 20: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 18 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

HARDBOARD SIDINGThe masonry board siding appears to be properly installed and in good condition.

DOORSThe exterior doors appear to be properly installed and in serviceable condition.

WINDOWSThe windows appear to be properly installed and in serviceable condition.

SCREENS

There is some minor damage to window screens here and there. Recommend repairing any damaged screens as needed.

GRADINGThe grading of the lot appears to properly and adequately drain excess surface water and roof runoff away from the structure.

Page 21: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 19 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

DRAINAGEA surface drainage system is designed to collect and divert roof runoff and other surface water. It is installed in solid pipe and flows continuously downhill to a point of discharge.

The surface water drainage system is below grade and cannot be viewed. Designs and materials for these systems vary widely, making it impossible to evaluate the integrity of the system with any certainty.

We could not determine the discharge location of the drainage system. We suggest inquiries and/or observation during a heavy rain to discover the discharge location and effectiveness of the system.

The drainage system should be checked for debris and cleaned regularly to ensure proper operation during heavy weather.

It is our opinion that the existing surface drainage system is either insufficient or defective, based on moisture conditions below the home (see "Crawl Space" section). We recommend further evaluation by a specialist to determine which repairs or upgrades to the drainage system be undertaken.

PUBLIC WORKSThe owner may have rights and responsibilities concerning the public improvements associated with this property. We suggest inquiries of the local public works department, particularly regarding liabilities for future maintenance costs.

The public sidewalks appear to be properly installed and are in serviceable condition.

DRIVEWAYThe minor cracks in the driveway are of a cosmetic nature only. No action is indicated.

WALKWAYSThe walkways appear to be properly installed and are in serviceable condition.

PATIO SURFACE

The patio shows normal cracking and/or minor settlement. This does not impact its integrity. No action is indicated.

Page 22: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 20 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

PATIO/PORCH COVERINGThe patio cover is a retractable awning that was not included as part of our inspection. We have no specific knowledge in this type of covering and recommend inquiring of the property owner as to its functionality.

FENCING

The fencing is deteriorated in some areas and its remaining service life is limited. Expect the need for replacement or repair in the near future. Typically, fencing around the perimeter of the home is considered a shared responsibility between owners of adjacent properties. Recommend inquiring of neighbors prior to making repairs.

GATESThe south fence gate was operating. Routine maintenance will keep it functional and maximize its service life.

Page 23: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 21 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

The north fence gate was blocked and/or were inaccessible for inspection. We recommend further review.

VEGETATION

Some trees or shrubberies were observed to be in contact with or near the siding or foundation. Recommend trimming back all trees and shrubberies at least 6 inches from the home in order to protect the home's surface from moisture or pest intrusion.

Page 24: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 22 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

TRIMThe trim shows routine wear but appears to be properly installed and in serviceable condition. We advise routine maintenance to ensure maximum service life.

Portions of trim boards were observed to be at or below grade. This may lead to deterioration of lower board ends. Recommend maintaining proper gaps between the earth and trim boards and repairing any existing damage.

Page 25: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 23 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

FASCIA

Sections of the fascia on the north side are deteriorated. We recommend they be repaired or replaced. Other fascia boards are worn and in need of typical maintenance

EAVES/SOFFITS

There is mildew on the underside of the roof eaves. We recommend that it be removed with several applications of bleach prior to any repainting or refinishing.

Page 26: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 24 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

There are one or more hives or nests under the overhang at the exterior of the home. Although these are not considered a deficiency in the structure, we recommend they be removed for personal safety and/or a better appearance.

PAINT/STAIN

The exterior paint is in fair to good condition but appears a bit 'tired'. There are no surfaces that need painting for other than cosmetic reasons.

GENERAL COMMENTAs preventive maintenance, caulking and sealing the gaps in the exterior of the building around the doors, windows, plumbing and electrical entry points will help prevent heat loss, cold air infiltration and moisture entry.

If caulking is needed for maintenance of any flashing or exterior trim, we suggest a high quality urethane sealant such as 'Sikaflex'. Latex, butyl, oil based, silicone or 'architectural grade' sealants should be avoided.

There are areas where exterior features are in need of attention. These conditions suggest lapses in maintenance. We make no attempt to list all cosmetic flaws but, do suggest attention to items relating to function and safety.

Roofing

A roof system consists of the surface materials, connections, penetrations and drainage (gutters and downspouts). We visually review these components for damage and deterioration and do not perform any destructive testing. If we find conditions suggesting damage, improper application, or limited remaining service life, these will be noted. We may also offer opinions concerning repair and replacement. Opinions stated herein concerning the roof are based on a limited visual inspection. These do not constitute a warranty that the roof is, or will remain, free of leaks.

Page 27: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 25 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Composition Shingle

BASIC INFORMATIONLocation: Covers whole buildingRoof slope: MediumMaterial: Asphalt composition shingleLayers: Single layerAge: Approximately 14+ years oldConnections and penetrations: Sealed with metal flashing

Roof drainage system: Gutters and downspouts

INSPECTION METHODOur inspection of this roof was conducted from the roof surface. The inspector walked upon the surface and visually examined the accessible roofing components.

Page 28: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 26 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

SURFACE

Some moss was growing on the roof surface. As a result, shingles can lift or be damaged. Leaks can result and/or the roof surface can fail prematurely if the moss is left to grow unabated. Efforts should be made to kill the moss during its growing season (wet months). Typically, zinc or phosphate based chemicals are used for this and must be applied periodically.

The roof surface is in generally satisfactory condition, though some isolated instances of granulation loss, cracking shingles (especially at the ridges where shingles are bent) or broken shingle corners, were observed, though nothing to suggest the need for immediate repairs. Recommend continuing to monitor as the surface ages and repairing as needed.

Page 29: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 27 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

FLASHINGS: OVERALLMetal flashing has been used to seal the connections and penetrations.

The accessible connection and penetration flashings appear to be properly installed and in serviceable condition. All of the connections and penetrations should be periodically examined for signs of leakage and repairs performed if necessary.

PLUMBING VENTS

One or more plumbing vents at the roof are showing signs of tearing or warping at the neoprene flashing. Recommend replacement of any damaged plumbing flashings.

Page 30: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 28 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

OTHER VENTSThe appliance vents appear to be properly installed and in serviceable condition.

GUTTERSRoof runoff water is channeled to the downspouts by a metal gutter system attached to the fascia boards or to the ends of the rafters along the edge of the roof.

Page 31: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 29 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Debris was present in portions of the gutters, which limited our visual inspection. We recommend all debris be removed to ensure proper drainage. The condition of the gutters can be better assessed at that time.

DOWNSPOUTSThe downspouts appear to be properly installed and in serviceable condition.

GENERAL COMMENTThe roof covering shows wear but appears to have been properly installed and is in a condition deemed acceptable for its age. We observed no signs of unusual or excessive wear of the roofing that would suggest immediate attention is required.

Garage

FRAMINGThe wall framing is not visible. The area around the garage door opening is generally the most vulnerable to movement but no adverse conditions were noted. The construction appears to be original and no action is indicated.

RECEPTACLESThe receptacles appear to be properly installed and were operational.

GFCI (ground fault circuit interrupter) protection has been installed providing an increased margin of safety. We recommend testing the device on a monthly basis.

GARAGE DOOR OPENEROne of the garage door opener(s) operated properly to raise and lower the doors, including the auto-reverse mechanisms, which stopped and reversed the direction of the doors when they struck objects in their path.

Page 32: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 30 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

One of the garage door opener failed to respond to normal operating controls. We recommend the opener and/or the controls be repaired or replaced.

FLOORThe floor is a concrete slab.

Page 33: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 31 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

There is cracking in the floor slab but there is no vertical displacement of any portion of the slab. No action is indicated.

GARAGE DOORSThe garage is equipped with two roll up doors.

The garage door springs are not provided with safety restraints to eliminate damage or injury in the event of breakage, in accordance with present standards.

FIRE SEPARATIONThe wall between the garage and the living space is of fire resistive construction as required by today's building standards.

Page 34: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 32 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

PASSAGE DOORThe door between the garage and the living space seems to be of fire resistive construction as required by today's building standards and includes an approved automatic closer. This is a positive feature which provides a greater margin of safety.

GENERAL COMMENTThis area is in need of repair as noted above or in other sections of this report.

Page 35: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 33 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Due to the presence of personal belongings, access to portions of the area were effectively blocked at the time of our inspection. A 'walk-through' is recommended when the area is cleared and accessible.

Kitchen

The kitchen is visually inspected for proper function of components, active leakage, excessive or unusual wear, and general state of repair. We inspect built-in appliances to the extent possible using normal operating controls. Freestanding stoves are operated, but refrigerators, small appliances, portable dishwashers, and microwave ovens are not tested.

BASIC INFORMATIONEnergy: Electric appliances onlyVentilation: Exhaust ducted to the exteriorRefrigerators, wine coolers, and other cooling appliances are beyond the scope of this inspection

Page 36: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 34 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

DRAIN TRAPSThe drain trap and associated piping are PVC plastic.

AIR GAP

The dishwasher drain has no air-gap and the drain line is not looped below the cabinet. The dishwasher will function without it, but the installation does not meet present standards. We suggest installation of an air-gap or rerouting the drain line to prevent backflow of drainwater.

SINKThe sink is metal.

The sink appears to be properly installed. When operated, it was observed to be fully functional and in serviceable condition.

RECEPTACLESThe receptacles appear to be properly installed and were operational.

GFCI (ground fault circuit interrupter) protection has been installed providing an increased margin of safety. We recommend testing the device on a monthly basis.

Page 37: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 35 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

LIGHTSThe overhead kitchen lights were tested and found to be operational at the time of the inspection.

HEAT OUTLETThe heating outlet is in serviceable condition. Conditioned air was observed flowing into the room when the heating system was operated.

FLOORThe wood or laminate flooring is in serviceable condition. Kitchen floors receive the most concentrated wear of any area in the house, especially at the sink and stove. We recommend these areas be coated every two to three years as preventive maintenance.

COUNTERTOPSThe countertop is tile.

Page 38: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 36 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

VENTILATIONKitchen ventilation is provided by a microwave over the burners,

STOVEThe stove was turned on with the normal operating controls and found to be in satisfactory working condition.

OVENThe oven was turned on with the normal operating controls and found to be in satisfactory working condition.

DISPOSALThe disposal was turned on with normal user controls and observed to be in satisfactory working condition.

DISHWASHERThe dishwasher was operated through a normal or rinse cycle and appeared to be in serviceable condition at the time of the inspection.

Page 39: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 37 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection. However, this area is in need of routine maintenance as noted above or in other sections of this report.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Laundry Area

Laundry areas and/or laundry rooms are visually inspected for general state of repair. Due to their hidden nature, we do not review appliances, connections, hookups, or venting.

DRYER VENTThe dryer vent appears properly installed and in serviceable condition.

Page 40: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 38 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

WASHER/DRYERThe hookups for the washer and dryer are properly installed and in serviceable condition. The appliances themselves were not tested.

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Bathroom

Bathrooms are visually inspected for proper function of components, active leakage, excessive or unusual wear and general state of repair. Fixtures are tested using normal operating features and controls. Due to finished surfaces such as drywall/plaster, tile, and flooring, much of the bathroom is considered inaccessible. We do not test or confirm proper application of secondary equipment including but not limited to steam units, spa tubs, heated towel bars, etc.

Page 41: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 39 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

First Floor Half Bath

BASIC INFORMATIONToilet: Ceramic unit with a porcelain finish

Wash basin: Ceramic unit with a porcelain finish

Page 42: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 40 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

DRAIN TRAPThe drain trap and associated piping are PVC plastic.

TOILETThe toilet was flushed and appeared to be functioning properly.

WATER BASINThe wash basin appears to be properly installed. When operated, it was observed to be fully functional and in serviceable condition.

RECEPTACLESThe receptacle appears to be properly installed and was operational.

GFCI (ground fault circuit interrupter) protection has been installed providing an increased margin of safety. We recommend testing the device on a monthly basis.

The GFCI protection for this bathroom is provided by a GFCI receptacle located in the second floor hall bathroom. We advise testing on a monthly basis.

Page 43: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 41 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

VENTILATIONVentilation in this bathroom is provided by a vent fan in the ceiling. This fan was operated and was found to be working satisfactorily.

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection.

First Floor Hallway

BASIC INFORMATIONToilet: Ceramic unit with a porcelain finish

Page 44: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 42 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Wash basin: Ceramic unit with a porcelain finish

Bathtub: Molded fiberglass

Shower walls: Molded fiberglass

Page 45: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 43 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

DRAIN TRAPThe drain trap and associated piping are PVC plastic.

TOILETThe toilet was flushed and appeared to be functioning properly.

WATER BASINThe wash basin appears to be properly installed. When operated, it was observed to be fully functional and in serviceable condition.

BATHTUBThe bathtub appears to be properly installed and in serviceable condition.

SHOWERThe shower was operated for the inspection and appeared to be in serviceable condition.

RECEPTACLESThe receptacle appears to be properly installed and was operational.

GFCI (ground fault circuit interrupter) protection has been installed providing an increased margin of safety. We recommend testing the device on a monthly basis.

Page 46: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 44 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

SHOWER WALLS

The joint caulking above the shower is in marginal condition, with some staining or cracking evident. The enclosure should be recaulked to prevent moisture penetration into the surrounding materials and subsequent damage.

BATHROOM FLOORThe finish floor in this bathroom is tile.

The floor appears to be properly installed and is in serviceable condition.

DOORS

The door rubs on the frame. We recommend it be planed or sanded for smoother operation.

Page 47: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 45 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

VENTILATIONVentilation in this bathroom is provided by a vent fan in the ceiling. This fan was operated and was found to be working satisfactorily.

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection. However, this area is in need of routine maintenance as noted above or in other sections of this report.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Page 48: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 46 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

First Floor Master

BASIC INFORMATIONToilet: Ceramic unit with a porcelain finish

Wash basins: Cast iron units with a porcelain finish

Page 49: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 47 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Bathtub: Molded fiberglass

Shower walls: Molded Plastic

Page 50: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 48 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

DRAIN TRAPThe drain trap and associated piping are PVC plastic.

TOILETThe toilet was flushed and appeared to be functioning properly.

WATER BASINThe wash basins appear to be properly installed. When operated, they were observed to be fully functional and in serviceable condition.

The drain stops are defective. We recommend they be repaired or replaced.

SHOWERThe shower was operated for the inspection and appeared to be in serviceable condition.

Page 51: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 49 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

HYDROTHERAPY TUBThe hydrotherapy tub was filled and activated by the controls and was functional.

RECEPTACLESThe receptacles appear to be properly installed and were operational.

GFCI (ground fault circuit interrupter) protection has been installed providing an increased margin of safety. We recommend testing the device on a monthly basis.

The GFCI protection for this bathroom is provided by a GFCI receptacle located in the second floor hall bathroom. We advise testing on a monthly basis.

HEAT OUTLETThe heating outlet is in serviceable condition. Conditioned air was observed flowing into the room when the heating system was operated.

SHOWER WALLSThe shower walls appear to be properly installed and in serviceable condition.

Page 52: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 50 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

BATHROOM FLOORThe finish floor in this bathroom is tile.

It is important to maintain the caulking around bathtubs and showers, especially at the intersection between the tub or shower and the floor. Failure to maintain this seal will often result in damage to flooring materials, subflooring and framing.

We suggest the use of a quality sealant such as 'GE Sanitary Silicone' or 'Dow Corning 786' for bathroom caulking. Latex and 'latex with silicone' sealants are inferior materials and their use in bathrooms is strongly discouraged.

Particle board trim pieces at the bathroom floor showed signs of swelling. This is typical when this type of trim is used in bathrooms, as it is highly susceptible to moisture. Recommend replacing trim as warranted.

COUNTERTOPSThe countertop is tile.

Page 53: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 51 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

The rigid grout joint between the counter and the backsplash is standard practice. There are hairline cracks and this condition is likely to return even after patching. We recommend a flexible sealant at this location.

VENTILATIONVentilation in this bathroom is provided by ceiling-mounted vent fans. The fans were operated and were found to be working satisfactorily.

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection. However, this area is in need of routine maintenance as noted above or in other sections of this report.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Page 54: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 52 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Bedroom

Second Floor Master

RECEPTACLESThe receptacles were found to be properly installed and in serviceable condition. The number of receptacles is considered adequate for the size of the room.

LIGHTS / FANThe bedroom lights and/or fan were tested using normal controls and appeared to be functioning properly.

HEAT OUTLETThe heating outlet is in serviceable condition. Conditioned air was observed flowing into the room when the heating system was operated.

Page 55: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 53 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

FLOORThe floors are covered with wall-to-wall carpet. No attempt was made to determine the type or condition of the material under the carpet.

DOORS

The closet door doesn't latch properly. We recommend minor adjustments to the hardware to restore proper function.

Page 56: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 54 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

WINDOWS

There is a defective latch on one of the windows. We recommend the hardware be repaired or replaced.

SMOKE DETECTORThe smoke detector alarm was properly located and appeared adequately installed.

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection. However, this area is in need of routine maintenance as noted above or in other sections of this report.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Page 57: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 55 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Second Floor Rear

RECEPTACLES

A receptacle is wired with reversed polarity. Under some circumstances, this can be a shock hazard and/or damage electronic equipment. It is easy to correct this condition and we recommend the receptacle be repaired.

LIGHTS / FAN

The ceiling fan was somewhat noisy when operating. This may indicate a motor nearing the end of its useful life. Recommend replacing if noise makes fan difficult to use.

HEAT OUTLETThe heating outlet is in serviceable condition. Conditioned air was observed flowing into the room when the heating system was operated.

FLOORThe floors are covered with wall-to-wall carpet. No attempt was made to determine the type or condition of the material under the carpet.

Page 58: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 56 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

SMOKE DETECTORThe smoke detector alarm was properly located and appeared adequately installed.

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection. However, this area is in need of routine maintenance as noted above or in other sections of this report.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Second Floor Left Front

RECEPTACLESThe receptacles were found to be properly installed and in serviceable condition. The number of receptacles is considered adequate for the size of the room.

Page 59: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 57 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

LIGHTS / FANThe bedroom lights and/or fan were tested using normal controls and appeared to be functioning properly.

HEAT OUTLETThe heating outlet is in serviceable condition. Conditioned air was observed flowing into the room when the heating system was operated.

FLOORThe floors are covered with wall-to-wall carpet. No attempt was made to determine the type or condition of the material under the carpet.

Page 60: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 58 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

SMOKE DETECTORThe smoke detector alarm was properly located and appeared adequately installed.

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection.

Second Floor Right Front

RECEPTACLESThe receptacles were found to be properly installed and in serviceable condition. The number of receptacles is considered adequate for the size of the room.

Page 61: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 59 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

LIGHTS / FAN

The ceiling fan was somewhat noisy when operating. This may indicate a motor nearing the end of its useful life. Recommend replacing if noise makes fan difficult to use.

HEAT OUTLETThe heating outlet is in serviceable condition. Conditioned air was observed flowing into the room when the heating system was operated.

Page 62: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 60 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

FLOORThe floors are covered with wall-to-wall carpet. No attempt was made to determine the type or condition of the material under the carpet.

SMOKE DETECTORThe smoke detector alarm was properly located and appeared adequately installed.

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection. However, this area is in need of routine maintenance as noted above or in other sections of this report.

Living/Dining Room

RECEPTACLESThe receptacles were found to be properly installed and in serviceable condition. The number of receptacles is considered adequate for the size of the room.

Page 63: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 61 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

HEAT OUTLETThe heating outlet is in serviceable condition. Conditioned air was observed flowing into the room when the heating system was operated.

FLOORThe floors are covered with wall-to-wall carpet. No attempt was made to determine the type or condition of the material under the carpet.

WINDOWS

One or more of the windows do not operate properly because their spring mechanisms are damaged. We recommend these windows be repaired. We recommend great care when opening window.

Page 64: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 62 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

FIREPLACE (MORE ITEMS)The prefabricated metal fireplace appears to be properly installed and in serviceable condition.

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection. However, this area is in need of routine maintenance as noted above or in other sections of this report.

Page 65: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 63 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Family Room

RECEPTACLESThe receptacles were found to be properly installed and in serviceable condition. The number of receptacles is considered adequate for the size of the room.

LIGHTSThere is no ceiling fixture in this room. Building practices require the ability to turn on a light from a switch in every room. In this case, one of the receptacles is connected to the switch, allowing control of a cord connected lamp.

HEAT OUTLETThe heating outlet is in serviceable condition. Conditioned air was observed flowing into the room when the heating system was operated.

Page 66: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 64 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

FLOORThe floors are covered with wall-to-wall carpet. No attempt was made to determine the type or condition of the material under the carpet.

GENERAL COMMENTThe finished surfaces, hardware, windows, and doors were found to be generally in good condition at the time of our inspection. However, this area is in need of routine maintenance as noted above or in other sections of this report.

Inspection of this area was limited to the surface coverings. The construction materials and manner of installation were concealed from view and inaccessible.

Interior

Our review of the interior includes inspection of walls, ceilings, floors, doors, windows, steps, stairways, balconies and railings. These features are visually examined for proper function, excessive wear and general state of repair. Some of these components may not be visible/accessible because of furnishings and/or storage. In such cases these items are not inspected.

Page 67: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 65 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

BASIC INFORMATIONNumber of bedrooms: FourNumber of bathrooms: Two and one-halfWindow material: VinylWindow type: Horizontal and Vertical sliding windowsWindow glazing: Double paneFinished ceiling material: DrywallFinished floor material: Carpet and wood or laminateFinished wall material: Drywall

SURFACES: OVERALL

There is wear and tear throughout the house, of the type generally resulting from age and heavy use. We make no attempt to list all cosmetic flaws and suggest that most of these deficiencies will be addressed by routine maintenance and upgrading.

WALLS & CEILINGSThe interior wall and ceiling blemishes are cosmetic and can be repaired in the course of routine maintenance.

FLOORS: OVERALLThe floors have a good appearance and are in serviceable condition.

STAIRSThe stairs were used several times during the inspection. The various components appear to be properly installed and no deficiencies were noted during use. The handrails were securely attached.

RAILINGSThe railings appear to properly installed and are in serviceable condition.

DOORS: OVERALLThe interior doors appear to be properly installed and in good condition, with exceptions noted below.

WINDOWS: OVERALLWe operate a representative sample of the windows, but do not necessarily open, close, and latch every window. Our inspection standards require testing a minimum of one window in every room.

Page 68: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 66 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

The windows tested appear to be properly installed and generally in serviceable condition, with exceptions noted below or elsewhere in this report.

DETECTORS: OVERALLThe smoke detectors were inspected for location only. For future reference, testing with only the built-in test button verifies proper battery and horn function, but does not test the smoke sensor. We advise testing with real or simulated smoke.

The smoke detectors are appropriately located and were found in operating condition.

Carbon monoxide detectors were not found in the home. Typical building practice calls for at least one CO detector per floor of living space. Recommend installing CO detectors due to safety concerns.

HEAT SOURCEWe observed a permanent heat source in each room throughout the building.

GENERAL COMMENTThe interior surfaces, hardware, fixtures, doors and windows appear to be properly installed and generally in serviceable condition, with exceptions noted above.

We make no attempt to list all cosmetic flaws and suggest that most of these deficiencies will be addressed by normal maintenance and upgrading.

Attic

The attic contains the roof framing and serves as a raceway for components of the mechanical systems. There are often heating ducts, electrical wiring and appliance vents in the attic. We visually examine the attic components for proper function, excessive or unusual wear, general state of repair, leakage, venting and misguided improvements. Where walking in an unfinished attic can result in damage to the ceiling, inspection is from the access opening only.

ACCESS/ENTRYThe attic access is located in the bedroom ceiling.

Page 69: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 67 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

SHEATHINGThe roof sheathing is the material directly supporting the roof covering.

The roof sheathing is 'OSB' - Oriented Strand Board, nailed solidly across the rafters.

The roof sheathing appears to be properly installed and in good condition.

ROOF TRUSSESRoof trusses support the roof sheathing and roof covering, transferring loads to the bearing walls. The bottom of a truss supports the finished ceiling. Trusses are usually engineered components assembled in a factory and delivered to the site.

The trusses are generally in good condition, where seen, and have performed adequately since their installation.

Page 70: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 68 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

VENT LINESThe vent piping for the waste system appears to be properly installed and in good condition.

VENTILATIONOur feeling regarding attic ventilation is that 'you can never have too much'. Attic ventilation can be provided by eave, gable, and ridge vents as well as by automatic and wind driven fans. We encourage use of any or all of the above.

The attic appeared to be adequately vented (though different temperature or weather conditions may reveal inadequacies in the attic venting). Good ventilation helps reduce attic moisture levels and prevents condensation on the underside of the roof. In addition, it reduces heat build-up in the attic, making the house more comfortable.

Crawl Space

The crawl space is where most of the building's structural elements and portions of its mechanical systems are located. These include foundation, structural framing, electrical, plumbing and heating. Each accessible and visible component and system is examined for proper function, excessive or unusual wear

Page 71: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 69 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

and general state of repair. It is not unusual to find occasional moisture and dampness in crawl spaces. Significant and/or frequent water accumulation can adversely affect the building foundation and support system and would indicate the need for further evaluation by a specialist. Although observed in the crawl space, some items will be reported under the individual systems to which they belong.

BASIC INFORMATIONFoundation type: Raised perimeter with isolated piersFoundation material: Poured concreteMudsill: Inaccessible, unknown if bolted, nailed or strappedWall system: Wood stud wallsFloor system: Wood joists support by beams

ACCESSThe crawl space is accessible from an exterior hatch.

The crawlspace hatch cover is deteriorated and in need of replacement. Recommend repairing cover to properly seal the crawlspace from moisture or pest entry.

Page 72: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 70 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

FOUNDATION

Hairline and/or small cracks, within normal tolerances, are visible. This type of cracking is often a result of shrinkage of materials and/or minor settlement and usually does not affect the strength of the foundation. No action is indicated.

POSTSThe floor system is supported by wooden posts set over concrete pier blocks.

The support posts have performed adequately over time and would be expected to continue to do so.

ANCHOR BOLTSBecause of the design and/or configuration of the structure, we cannot verify the presence or condition of anchor bolts. Because of the age of the structure, we assume that proper bolting was installed, as per standards in effect at the time.

Page 73: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 71 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

MOISTURE

The crawl space was excessively moist, with much of the soil in a soft or muddy condition, along with some standing moisture on top of the vapor barrier. This is an undesirable condition conducive to structural settlement, pest control problems and rusting of mechanical components.

Recommend further evaluation by a crawlspace or drainage specialist to determine the source of the moisture and make any necessary upgrades to drainage, as well as replacing any dirty or damage vapor barrier.

Page 74: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 72 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

VAPOR BARRIER

Vapor barrier is very dirty with construction debris, rodent droppings, and other materials. Recommend replacing vapor barrier for cleanliness, and to prevent a buildup of materials that have the potential of drawing wood destroying organisms toward the home.

VENTILATIONVentilation in the crawl space is adequate. Good ventilation in the crawl space is important to keep moisture levels down. Keeping the vents clear of debris and vegetation should be part of regular maintenance.

PEST CONTROL

The crawlspace had numerous signs of rodent activity including extensive feces, torn insulation and/or evidence of nest-building activity. An effort should be made to seal the crawlspace from animal entry and you may wish to consult with a pest control service or set traps. Diseases spread through animal urine and feces can include hantavirus, raccoon roundworm encephalitis and more, some of which can be serious or fatal.

Page 75: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 73 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

DRAIN LINES

A drain pipe in the kitchen area is disconnected and draining into the crawlspace. This is a serious condition that should be repaired as quickly as possible. We also recommend the other visible components of the drain system be evaluated by a licensed plumber to determine if any other current or potential leaks are present. Additionally, the area under this leak is wet with drain water and should be cleaned and the vapor barrier replaced.

FLOOR INSULATION

In several locations, the insulation is out of place and in poor condition. A significant number of the fiberglass batts are damaged. We recommend this material be replaced and/or secured back in place.

Page 76: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 74 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

GENERAL COMMENT

The conditions observed and noted above are considered significant. Due to the presence of standing drainwater, severe rodent sign, and hanging and damaged insulation, access to the crawlspace was limited. In addition to plumbing repair service, we recommend the entire crawlspace be fully evaluated and restored by a qualified crawlspace cleaning specialist. Issues present include rodent activity, moisture activity, damaged plumbing pipes, damaged insulation and very dirty/damaged vapor barrier. Note: It is possible that additional reportable issues may be discovered over the course of cleaning and repairing the crawlspace.

Plumbing

A plumbing system consists of the domestic water supply lines, drain, waste and vent lines and gas lines. Inspection of the plumbing system is limited to visible faucets, fixtures, valves, drains, traps, exposed pipes and fittings. These items are examined for proper function, excessive or unusual wear, leakage, and general state of repair. The hidden nature of piping prevents inspection of every pipe and joint. A sewer lateral test, necessary to determine the condition of the underground sewer lines, is beyond the scope of this inspection If desired, a qualified individual could be retained for such a test. Our review of the plumbing system does not include landscape watering, fire suppression systems, private water supply/waste disposal systems, or recalled plumbing supplies. Review of these systems requires a qualified and licensed specialist.

Page 77: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 75 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

BASIC INFORMATIONDomestic water source: Public supply

Landscape water source: Public supplyMain water line: IndeterminateSupply piping: Plastic where seenWaste disposal: MunicipalWaste piping: Plastic where seenWater pressure: Mid-range of normal water pressureOther installed systems: Landscape watering, not inspected

WATER SHUTOFF LOCATIONThe domestic water supply shut-off valve is in the garage.

WATER SHUTOFF COMMENTSThe main shut-off valve was located but testing the operation of this valve is not within the scope of our inspection. Operation of the valve from time to time will keep it functional and maximize its useful life.

MAIN SUPPLYThere was no evidence of surface corrosion or leakage at the exposed and accessible main supply.

Page 78: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 76 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

INTERIOR SUPPLYThe exposed and accessible supply piping generally appears to be properly installed and in good condition.

WATER PRESSUREThe system water pressure, as measured at the exterior hose bibs, is within the range of normal.

DRAIN LINESThe drain line is leaking or damaged at the crawlspace (see "Crawlspace" section for more details. We recommend that it be repaired and the rest of the drain lines be further evaluated.

SEWER CLEANOUTThe sewer cleanout is located in the crawl space.

VENT LINESThe vent piping for the waste system appears to be properly installed and in good condition.

GAS PIPINGThe gas piping appears to be properly installed and in serviceable condition. We detected no evidence of leakage at any of the exposed gas piping. Pressure testing may reveal leaks, but this procedure is beyond the scope of our inspection.

GAS METER LOCATIONThe gas meter is outside on the left side of the building. The main gas supply shutoff valve is located on the riser pipe between the ground and the meter. This valve should be turned 90 degrees (either way) in order to shut off the gas.

GENERAL COMMENT

We observed problems with the plumbing system as noted above. We recommend a licensed plumber be retained to evaluate the entire plumbing system and determine an appropriate course of action.

Page 79: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 77 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Water Heater

Our review of water heaters includes the tank, water and gas connections, electrical connections, venting and safety valves. These items are examined for proper function, excessive or unusual wear, leakage and general state of repair. We do not fully review tankless/on-demand systems and suggest you consult a specialist. The hidden nature of piping and venting prevents inspection of every pipe, joint, vent and connection.

BASIC INFORMATIONLocation: In the garage

Energy source: Natural gasCapacity: 40 gallonsAge: Estimated to be 14 years oldUnit type: Free standing tankWater heater temperature settings should be maintained in the mid-range to avoid injury from scaldingInsulation: Yes, installed behind outer jacket

Page 80: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 78 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

T/P RELEASE VALVEThe water heater is equipped with a temperature and pressure relief valve. This device is an important safety device and should not be altered or tampered with. We observed no adverse conditions.

EXPANSION TANKThe water heater is equipped with an expansion tank that appears properly installed and in serviceable condition. However, review of this equipment is beyond the scope of this inspection.

Page 81: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 79 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

GAS SUPPLYThe gas piping for the appliance includes a local 90 degree shut-off valve for use in an emergency or in case of repair. The valve was not tested at the time of inspection, but is of a type usually found to be serviceable.

The gas connector is an approved flexible type in good condition.

VENTINGThe water heater vent is properly installed and appears in serviceable condition.

COMBUSTION AIRCombustion air provides the oxygen for fuel burning appliances. Adequate ventilation around all fuel burning appliances is vital for their safe operation. The air can come from inside or outside, providing industry standards are met.

The combustion air supply is adequate.

Page 82: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 80 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

IGNITION SYSTEM

The control knob to adjust the temperature and turn off the water heater was missing. This control valve is both a convenience and safety feature and should be replaced for proper operation of the unit.

BURNERSThe burner is generally clean and appears to be in serviceable condition.

WATER CONNECTORSThe cold water inlet and hot water outlet connections appear properly installed and in serviceable condition.

SEISMIC RESTRAINTThe water heater tank has been secured. This feature will help prevent water heater movement and possible gas leakage, limit damage and provide a source of usable domestic water in the event of a major earthquake.

ELEVATION/LOCATIONThe water heater has been elevated above the garage floor in accordance with present standards. This is a beneficial configuration which helps prevent the ignition of fumes from spilled flammable liquids.

INSULATIONThere is no insulation blanket installed. Newer water heaters have built-in insulation to meet rigorous conservation standards. Installation of a blanket can be done but offers very little improvement on the existing efficiency of the unit.

Page 83: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 81 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

GENERAL COMMENT

This water heater is near the end of its expected service life. Although operating, the need for replacement should be expected within the next few years.

Heat

A heating system consists of the heating equipment, operating and safety controls, venting and the means of distribution. These items are visually examined for proper function, excessive or unusual wear and general state of repair. This is a non-evasive, basic function review only. We do not dismantle, uncover or calculate efficiency of any system. Regular servicing and inspection of heating systems is encouraged.

Forced Hot Air

BASIC INFORMATIONFurnace location: Garage

Energy source: Natural gasFurnace btu input rating: 50,000 btu'sAge: 14+ years old

Page 84: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 82 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Filter size: 16 x 16 x 1 inch (x2)

Manufacturer: Tempstar

SYSTEM NOTESForced air furnaces operate by heating a stream of air moved by a blower through a system of ducts. Important elements of the system include the heat exchanger, exhaust venting, blower, controls, ducting, and combustion air supply.

Page 85: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 83 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

GAS SUPPLYThe gas piping includes a 90 degree shutoff valve for emergency use. The valve was not tested at the time of inspection. This age and style of valve is normally found to be operable by hand and generally trouble free.

The gas connector is an approved flexible type in good condition.

BURNERSThe burners were inspected and found to be clean and in good working order.

HEAT EXCHANGERThe heat exchanger was inaccessible and could not be visually examined.

AIR FILTERSThe air filter for the heating unit is a conventional, disposable filter.

CLEARANCEThere is adequate clearance to combustible materials in the area around the heating unit as long as the space is not used for storage. We encourage good housekeeping practices in this area.

Page 86: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 84 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

VENTThe heating system vent is properly installed and appears in serviceable condition where seen.

COMBUSTION AIRCombustion air provides the oxygen for fuel burning appliances. Adequate ventilation around all fuel burning appliances is vital for their safe operation. The air can come from inside or outside, providing industry standards are met.

There is adequate combustion air for this heating unit.

THERMOSTATThe thermostat appears to be properly installed and the unit responded to the basic controls. This is a programmable device with many options for setback settings, timed events, etc. No attempt was made to test all functions of the thermostat.

HVAC WIRINGAll accessible wiring appears in good condition.

Page 87: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 85 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

GENERAL COMMENTThe heating system responded to normal operating controls. Components appear properly installed and serviceable. Routine maintenance will keep it functional and maximize its service life.

Our inspection of the heating system is non-invasive and is limited to visible components and their basic function. A full evaluation requires extensive testing and is beyond the scope of our inspection.

Page 88: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 86 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

The last service date of the gas forced air furnace appeared to be more than 1 year ago, or the inspector was unable to determine the last service date. Ask the property owner when it was last serviced. If unable to determine the last service date, or if last service date was more than one year ago, recommend that a qualified HVAC technician inspect, clean, and service the system, and make repairs if necessary. For safety reasons, and because the system is fueled by gas, this servicing should be performed annually in the future. Any needed repairs noted in this report should be brought to the attention of the HVAC technician when it is serviced.

Electrical System

An electrical system consists of the service, distribution, wiring and convenience outlets (switches, lights, and receptacles). Our examination of the electrical system includes the exposed and accessible conductors, branch circuitry, panels, overcurrent protection devices, and a random sampling of convenience outlets. We look for adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature of the electrical wiring prevents inspection of every length of wire.

BASIC INFORMATIONService entry into building: Underground service lateralVoltage supplied by utility: 120/240 voltsCapacity (available amperage): 200 amperesSystem grounding source: Foundation steelBranch circuit protection: Circuit breakersWiring method: Non-metallic sheathed cable or 'romex'

ELECTRIC METERThe electric meter is outside on the left side of the building.

Page 89: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 87 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

MAIN SERVICEThe main electrical service panel is in the garage.

MAIN DISCONNECTThe main disconnect is incorporated into the electrical service panel.

MAIN DISCONNECTThe ampacity of the main disconnect is 200 amps.

Page 90: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 88 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

CB MAIN PANELThe main service panel is in good condition with circuitry installed and fused correctly.

The circuits in the panel are labeled. We did not verify the accuracy of the labeling, but it appears to be typical. When the opportunity arises, we suggest checking the labeling by actually operating the breakers.

Page 91: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 89 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

SERVICE CAPACITYThe service entrance conductors are the wires between the utilities service drop and the main service disconnect or main service panel.

The service entrance conductors appear to be #4/0 Aluminum providing an ampacity of 200.

Our statement regarding service capacity is based upon the labeled rating of the main electrical service disconnect.

The service capacity is normal for a house this size and age, and appears adequate for the present demand and minor additional loads.

SERVICE GROUNDINGThe system and equipment grounding appears to be correct.

BRANCH CIRCUITRYThe accessible branch circuitry was examined and appeared properly installed and in serviceable condition.

RECEPTACLES: OVERALLFor reference, as receptacles are discussed in this report, present standards for typical room plugs require grounded, 3 prong receptacles within six feet of any point on all walls. Upgrading is required in older buildings only during remodeling.

Based upon our inspection of a representative number, the receptacles were generally found to be in serviceable condition and operating properly, with exceptions noted elsewhere.

SWITCHES: OVERALLWe checked a representative number of switches and found they were operating and in serviceable condition.

LIGHTS: OVERALLThe light fixtures in this building are generally in serviceable condition.

GFI PROTECTIONGFCI (ground fault circuit interrupter) protection is a modern safety feature designed to prevent shock hazards. GFCI breakers and receptacles function to de-energize a circuit or a portion of a circuit when a hazardous condition exists.

GFCI protection is inexpensive and can provide a substantial increased margin of safety.

GFCI protection is installed for all of the receptacles where this type of protection is presently required. We recommend testing these devices on a monthly basis.

GENERAL COMMENTThe electrical system is in good condition and the components are properly installed. No unsafe conditions were observed in the readily accessible portions of the installation.

Page 92: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 90 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Insulation/Energy

Insulation, weatherstripping, dampers, double-glazed glass and set-back thermostats are features that help reduce heat loss and/or gain and increase system and appliance efficiency. Our visual inspection includes review to determine if these features are present in representative locations and we may offer suggestions for upgrading. Our review of insulation is based upon uniformly insulated or are insulated to current standards. It is our opinion that all homes could benefit from energy conservation upgrades, and we suggest that you consult professionals.

ATTIC INSULATIONThe attic has blown-in or loose-fill fiberglass insulation.

The level of insulation would appear to provide an R-40+ insulating value. This provides excellent resistance to heat transfer by present standards.

WALL INSULATIONWe were unable to access the wall cavities and/or determine the presence or condition of insulation.

Page 93: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 91 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

FLOOR INSULATIONIn several locations throughout the crawlspace, the insulation is out of place and in poor condition. A significant number of the fiberglass batts are damaged. We recommend this material be replaced and/or secured back in place.

Locations of Emergency Controls

In an emergency, you may need to know where to shut off the gas, the water and/or the electrical system. We have listed below these controls and their location for your convenience. We urge that you familiarize yourself with their location and operation.

WATER SHUTOFF LOCATIONPLUMBINGThe domestic water supply shut-off valve is in the garage.

SEWER CLEANOUTPLUMBINGThe sewer cleanout is located in the crawl space.

Page 94: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 92 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

GAS METER LOCATIONPLUMBINGThe gas meter is outside on the left side of the building. The main gas supply shutoff valve is located on the riser pipe between the ground and the meter. This valve should be turned 90 degrees (either way) in order to shut off the gas.

ELECTRIC METERELECTRICAL SYSTEMThe electric meter is outside on the left side of the building.

Page 95: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 93 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

MAIN SERVICEELECTRICAL SYSTEMThe main electrical service panel is in the garage.

MAIN DISCONNECTELECTRICAL SYSTEMThe main disconnect is incorporated into the electrical service panel.

Environmental Concerns

Environmental issues include but are not limited to radon, fungi/mold, asbestos, lead paint, lead contamination, toxic waste, formaldehyde, electromagnetic radiation, buried fuel oil tanks, ground water contamination and soil contamination. We are not trained or licensed to recognize or discuss any of these materials. We may make reference to one of more of these materials in this report when we recognize one of the common forms of these substances. If further study or analysis seems prudent, the advice and services of the appropriate specialists are advised.

Page 96: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

Page 94 of 115Copyright© 2010-2018, SPECTACULAR, Strong Foundations Home Inspection, Isaac McPhee 18-04009

Conclusion

COMMENTSThe basic structures and systems of this house appear to be serviceable with exceptions as noted in our report.

Most of the items that are in need of immediate attention and/or possible major cost items that would require repair in the near future are listed in the report summary. Please refer to these items for more information.

Page 97: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

©2018 Strong Foundations Home Inspection

ADDENDA TO INSPECTION REPORT 1. The inspection to be performed for Client consists of non-intrusive visual observations to survey the readily accessible, easily visible material components, systems and equipment of the building. The inspection is designed to identify material physical deficiencies in the building’s components, systems and equipment, as they exist at the time of the inspection. The work product resulting from completing an inspection in accordance with this contract is an inspection report. The inspection report incorporates the information obtained during the inspection. The inspection report is for the sole use and benefit of the Client. Client agrees to read the entire inspection report when it is received and shall promptly call the Inspector with any questions or concerns Client may have regarding the inspection report or the inspection. The inspection report shall be considered the final and exclusive findings of the Inspector regarding the inspection of the building. Client shall not rely on any oral statement made by the Inspector prior to issuance of the inspection report. 2. Components and systems operated during the inspection will be identified in the inspection report. The identified components and systems shall be operated with normal user controls and as conditions permit. If a component or system is operated, it may be conducted without the aid of special protective clothing, exploratory probing, removing materials, testing, measuring, preparing, calculations or using special equipment, including meters or devices of any kind. Testing, measuring, or preparing calculations for any system or component to determine adequacy, capacity, or compliance with any standard is outside the scope of this contract. 3. The term “poor” or “major concern” in regard to a component mean the presence of conspicuous patent defects or material deferred maintenance of the building’s material systems, components, or building equipment as observed during the inspection. This definition specifically excludes deficiencies that may be remedied with routine maintenance, miscellaneous minor repairs, and normal operating maintenance, and excludes conditions that generally do not present material physical deficiencies of the building. 4. Inspector is an expert generalist and not acting as an expert in any SPECIFIC craft or

Page 98: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

©2018 Strong Foundations Home Inspection

trade. The inspector may make recommendations for further evaluation by an individual(s) who is an expert or specialist IN ONE OR MORE SPECIFIC BUILDING COMPONENTS OR SYSTEMS. 5. The inspection is not technically exhaustive. The cost obtaining information or the time required to conduct a technically exhaustive inspection and prepare the inspection report could outweigh the usefulness of the information and could be detrimental to the orderly and timely completion of Client’s transaction. 6. No inspection can wholly eliminate the uncertainty regarding the presence of physical deficiencies and the performance of the building’s systems. Preparation of an inspection report in accordance with this contract is intended to reduce, but not eliminate, the uncertainty regarding the potential for component or system failure and to reduce the potential that such component or system may not be initially observed. Client recognizes the inherent subjective nature of the inspector’s opinions as to issues such as workmanship, quality of original installation, and estimating the remaining useful life of any given component or system. The inspector’s opinions generally are formed without detailed knowledge from those specifically familiar with the component or system’s performance. 7. The inspection report will contain a representative indication of the property condition at the time of the inspection and is dependent on the information available to the inspector at that time. 8. It is the Client’s duty and obligation to exercise reasonable care to protect himself or herself regarding the condition of the building, including those facts that are known to or within the diligent attention and observation of the Client. SCOPE AND LIMITATIONS OF THIS INSPECTION This inspection is limited to a visual observation of the exposed and readily accessible areas of the home. The concealed and inaccessible areas are not included. The following locations are considered inaccessible due to limited height and excluded from this inspection unless otherwise stated:

Crawl space areas less than 18 inches in height

Attic spaces less than 5 feet in height

Spaces under outdoor decks less than 5 feet high Observation includes operation of the systems or components by means of the normal user controls. Dismantling of equipment, and destructive testing is not included. Some specific items are also excluded, and these are listed in the following section. If you feel there is a need for evaluation of any of these items, then you will need to arrange for specific inspections. Items not Included

Page 99: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

©2018 Strong Foundations Home Inspection

1. Recreational, leisure, playground or decorative equipment or appliances including but not limited to pools, hot tubs, saunas, steam baths, landscape lighting, fountains, shrubs, trees, and tennis courts; 2. Cosmetic conditions (wallpapering, painting, carpeting, scratches, scrapes, dents, cracks, stains, soiled or faded surfaces on the structure or equipment, soiled, faded, torn, or dirty floor, wall or window coverings etc.); 3. Noise pollution or air quality in the area; 4. Earthquake hazard, liquefaction, flood plain, soil, slide potential or any other geological conditions or evaluations; 5. Engineering level evaluations on any topic; 6. Existence or non-existence of solder or lead in water pipes, asbestos, hazardous waste, radon, urea formaldehyde urethane, lead paint or any other environmental, flammable or toxic contaminants or the existence of water or airborne diseases or illnesses and all other similar or potentially harmful substances (although the inspector may note the possible existence of asbestos in ceiling texture and furnace duct tape); 7. Zoning or municipal code (e.g. building, fire, housing (existing buildings), mechanical, electrical, plumbing, etc. code) restrictions or other legal requirements of any kind; 8. Any repairs which relate to some standard of interior decorating; 9. Cracked heat exchangers or similar devices in furnaces; 10. Any evaluation which requires the calculation of the capacity of any system or item that is expected to be part of the inspection. Examples include but are not limited to the calculation of appropriate wattage or wiring of kitchen appliances, appropriate sizing of flues or chimneys, appropriate ventilation to combustion-based items (e.g. furnaces, water heaters, fireplaces etc.), appropriate sizing, spacing and spanning of joists, beams, columns, girders, trusses, rafters, studs etc., appropriate sizing of plumbing and fuel lines, etc.; 11. Washers and dryers; 12. Circuit breaker operation; 13. Specialty evaluations such as private sewage, wells, solar heating systems, alarms, intercom systems, central vacuum systems, wood and coal stoves, pre-fab and zero clearance fireplaces, space heaters, sprinkler systems, gas logs, gas lights, elevators and common areas unless these have been specifically added to the inspection description above but only to the degree that the inspector is capable of evaluating these items;

Page 100: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

©2018 Strong Foundations Home Inspection

14. Items that are not visible and exposed including but not limited to concealed wiring, plumbing, water leaks, under bathtubs and shower stalls due to faulty pans or otherwise, vent lines, duct work, exterior foundation walls (below grade or covered by shrubs or wall/paneling, stored goods etc.) and footings, underground utilities, and systems and chimney flues; 15. Evaluations involving destructive testing; 16. Evaluation which requires moving personal goods, debris, furniture, equipment, floor covering, insulation or like materials; 17. Design problems and adequacy or operational capacity, quality or suitability; 18. Fireplace drafting; 19. To prevent damages to units, air conditioning when outside temperature below 60 degrees F or if the unit has not been warmed up or on for at least 24 hours prior to inspection; 20. Any evaluation which would involve scraping paint or other wall coverings; 21. Heating system accessories (e.g. humidifiers, electronic air cleaners etc.); 22. Legal description of property such as boundaries, egress/ingress, etc.; 23. Quality of materials; 24. Conformance with plan specifications or manufacturers specifications; 25. Flood conditions or plains; 26. Any other characteristics or items which are generally not included in a building inspection report on a regular basis. Services for inspecting or evaluating the excluded items listed above may be available from the Inspector for an additional fee or from specialists qualified to inspect or evaluate a particular category or item. Disclaimer In some cases we may recommend your consulting a specialist such as a structural engineer or licensed electrician. Hiring a specialist can be a prudent means of providing some protection of your financial investment in this property. WE DO NOT MAKE ANY TYPE OF WARRANTY OR GUARANTEE AS TO THE CONDITION OF THE PROPERTY. SOME THINGS MAY REMAIN HIDDEN OR BECOME DEFECTIVE AFTER THE INSPECTION. IT IS NOT POSSIBLE TO DETECT

Page 101: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

©2018 Strong Foundations Home Inspection

EVERY DEFECT WITHIN A BUILDING DURING THE COURSE OF A GENERAL INSPECTION. THIS REPORT SHOULD BE USED IN CONJUNCTION WITH, AND NOT A REPLACEMENT FOR , A PRE-CLOSING WALK-THROUGH BY THE CLIENT. THIS INSPECTION IS NOT AN INSURANCE POLICY AGAINST HIDDEN DEFECTS, OR CONDITIONS THAT ARE NOT VISIBLE AND READILY APPARENT AT THE TIME OF INSPECTION. THE COST OF THIS INSPECTION DOES NOT ENTITLE YOU TO ANY TYPE OF PROTECTION FROM HIDDEN FLAWS AND DEFECTS. THIS INSPECTION DOES NOT TRANSFER YOUR ULTIMATE RESPONSIBILITY TO ALL POINT HOME INSPECTIONS. ENVIRONMENTAL CONCERNS: Client acknowledges that what is being contracted for is a building inspection and not an environmental evaluation and the inspection is not intended to detect, identify or disclose any health or environmental concerns regarding this building or property, including, but not limited to, the presence of asbestos, radon, lead, urea formaldehyde, fungi, mold, mildew, PCB’s or other toxic materials or substances in the water, air, soil or building materials. CONFIDENTIAL REPORT: The inspection report to be prepared for the Client is solely and exclusively for the Client’s own information and may not be relied upon by any other person. Client agrees to maintain the confidentiality of the inspection report and agrees not to disclose any part of it to any other person. Client my distribute copies of the inspection report to other persons directly involved in this transaction, but the Client and Inspector do not in any way intend to benefit said other persons directly or indirectly through this Contract, the inspection or the inspection report. CLIENT AGREES TO INDEMNIFY, DEFEND AND HOLD THE INSPECTOR HARMLESS FROM ANY THRID PARTY CLAIMS ARISING OUT OF THE CLIENT’S UNAUTHORIZED DISTRIBUTION OF THE INSPECTION REPORT. LIQUIDATED DAMAGES: IT IS UNDERSTOOD AND AGREES BY AND BETWEEN THE PARTIES HERETO THAT THE INSPECTOR/INSPECTION COMPANY IS NOT AN INSURER, THAT THE PAYMENT FOR THE SUBJECT INSPECTION IS BASED SOLELY ON THE VALUE OF THE SERVICES PROVIDED BY THE INSPECTOR/INSPECTION COMPANY IN THE PREFORMANCE OF THE INSPECTION AND PRODUCTION OF THE INSPECTION REPORT AS DESCRIBED HEREIN, THATIT IS IMPRACTICABLE AND EXTREMELY DIFFICULT TO FIX THE ACTUAL DAMAGES, OF ANY, WHICH MAY RESULT FROM A FAILURE TO PERFORM SUCH SERVICES, AND IN CASE OF FAILURE TO PERFORM SUCH SERVICES AND A RESULTING LOSS, THE CLIENT’S DAMAGES HEREIN SHALL BE LIQUIDATER AND FIXED IN AN AMOUNT EQUAL TO THE INSPECTION FEE PAID MULTIPLIED BY ONE HUNDRED TWENT-FIVE PERCENT (125%) AS

Page 102: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

©2018 Strong Foundations Home Inspection

LIQUIDATED DAMAGES AND NOT AS A PENALTY, AND THIS REMEDY SHALL BE EXCLUSIVE. GENERAL PROVISIONS: A. This inspection contract, the inspection, and the inspection report do not constitute a warranty, guarantee, or insurance policy of any kind whatsoever. B. No legal action or proceeding of any kind, including in tort or contract can be commenced against Inspector/Inspection Company, or its officers, agents or employees more than one year after the date of the subject inspection. Time is expressly of the essence herein. THIS TIME PERIOD IS SHORTER THAN OTHERWISE PROVIDED BY LAW. C. In the event the Client discovers a material physical deficiency in a component, system or equipment of the building that was not identified and reported by the Inspector, Client shall so notify the Inspector in writing and allow Inspector and/or Inspector’s designated representative to re-inspect and document the condition(s) of the material physical deficiency prior to making any repair, alteration, or replacement to said physical deficiency. D. Should any provision of this contract be held by a court of competent jurisdiction to be either invalid or unenforceable, the remaining provisions of this contract shall remain in full force and effect, unimpaired by the court’s holding. E. This contract shall be binding upon and inure to the benefit of only the undersigned parties and their heirs, successors and assigns. F. This contract constitutes the entire integrated agreement between the parties hereto pertaining to the subject matter hereof, and may be modified only by a written agreement signed by all of the parties hereto. No oral agreements, understanding, or representations shall change, modify, or amend any part of this contract. G. Each party signing this contract warrants and represents that he/she has the full capacity and authority to execute this contract on behalf of the named party whether it is a corporation, partnership, or other entity. If this contract is executed on behalf of the Client by a third party, the person executing this contract expressly represents to the Inspector that he/she has the full and complete authority to execute this contract on the Client’s behalf and to fully and completely bind the Client to all of the terms, conditions, limitations, exceptions and exclusions of this contract. This report is the exclusive property of this inspection company and the client(s) listed in the report title. Use of this report by any unauthorized persons is prohibited. FOLLOW-UP INSPECTION POLICY Generally we discourage follow-up inspections for these reasons

Page 103: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

©2018 Strong Foundations Home Inspection

1. Quality of repairs

If repairs are made to a property based on the results of an inspection, the work should be performed by qualified contractors, not the seller. By qualified, we mean licensed, bonded, state-certified where applicable and with a reasonable amount of experience. Contractors providing repairs should provide legible documentation in the form of work orders and/or receipts. If repairs are made in this way, then there's generally no need for a follow-up inspection. Additionally, it may be better to negotiate a lower price on your home and have repairs made by contractors you choose rather than the seller making repairs as cheaply as possible. ________________________________________ As a part of our service, we sometimes provide approximate, cost of repair estimates for particular items. These estimates should be considered as background information only. It is beyond the scope of this inspection and report to supply you with accurate repair costs. Such estimates should be supplied by contractors who specialize in this type of work. Our estimates should be used only as guidelines. If you intend to negotiate the price of this property based on defects found during this inspection, we strongly suggest you obtain one or more written bids from a licensed contractor(s). It is a conflict of interest for Strong Foundations Home Inspection to recommend any specific contractor.

Page 104: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

©2018 Strong Foundations Home Inspection

Life Expectancy Charts for Homes PLEASE NOTE: These life expectancies have been determined through research and testing based on regular recommended maintenance and conditions of normal wear and tear, and not extreme weather or other conditions, neglect, over-use or abuse. Therefore, they should be used as guidelines only, and not relied upon as guarantees or warranties. Surface preparation and paint quality are the most important determinants of a paint's life expectancy. Ultraviolet (UV) rays via sunshine can shorten life expectancy. Additionally, conditions of high humidity indoors or outdoors can affect the lifespan of these components, which is why they should be inspected and maintained seasonally.

ADHESIVES, CAULK & PAINTS

YEARS

Caulking (interior & exterior) 5 to 10 Construction Glue 20+ Paint (exterior) 7 to 10 Paint (interior) 10 to 15 Roofing Adhesives/Cements 15+ Sealants 8 Stains 3 to 8 Appliance life expectancy depends to a great extent on the use it receives. Furthermore, consumers often replace appliances long before they become worn out due to changes in styling, technology and consumer preferences.

APPLIANCES YEARS Air Conditioner (window)

5 to 7

Compactor (trash) 6 Dehumidifier 8 Dishwasher 9 Disposal (food waste) 12 Dryer Vent (plastic) 5 Dryer Vent (steel) 20 Dryer (clothes) 13 Exhaust Fans 10 Freezer 10 to 20 Gas Oven 10 to 18 Hand Dryer 10 to 12 Humidifier (portable) 8 Microwave Oven 9 Range/Oven Hood 14 Electric Range 13 to 15

Page 105: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

©2018 Strong Foundations Home Inspection

Gas Range 15 to 17 Refrigerator 9 to 13 Swamp Cooler 5 to 15 Washing Machine 5 to 15 Whole-House Vacuum System 20 Modern kitchens today are larger and more elaborate. Together with the family room, they now form the “great room.”

CABINETRY & STORAGE YEARS Bathroom Cabinets 50+ Closet Shelves 100+ Entertainment Center/Home Office

10

Garage/Laundry Cabinets 70+ Kitchen Cabinets 50 Medicine Cabinet 25+ Modular (stock manufacturing-type)

50

Walls and ceilings last the full lifespan of the home.

CEILINGS & WALLS YEARS Acoustical Tile Ceiling 40+ (older than 25 years may

contain asbestos) Ceramic Tile 70+ Concrete 75+ Gypsum 75 Wood Paneling 20 to 50 Suspended Ceiling 25+ Natural stone countertops, which are less expensive than they were just a few years ago, are becoming more popular, and one can expect them to last a lifetime. Cultured marble countertops have a shorter life expectancy, however.

COUNTERTOPS YEARS Concrete 50 Cultured Marble 20 Natural Stone 100+ Laminate 20 to 30 Resin 10+ Tile 100+ Wood 100+

Page 106: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

©2018 Strong Foundations Home Inspection

Decks are exposed to a wide range of conditions in different climates, from wind and hail in some areas, to relatively consistent, dry weather in others. See FASTENERS & STEEL section for fasteners.

DECKS YEARS Deck Planks 15 Composite 8 to 25 Structural Wood 10 to 30 Exterior fiberglass, steel and wood doors will last as long as the house, while vinyl and screen doors have a shorter life expectancy. The gaskets/weatherstripping of exterior doors may have to be replaced every 5 to 8 years.

DOORS YEARS Closet (interior) 100+ Fiberglass (exterior) 100+ Fire-Rated Steel (exterior) 100+ French (interior) 30 to 50 Screen (exterior) 30 Sliding Glass/Patio (exterior) 20 (for roller wheel/track

repair/replacement) Vinyl (exterior) 20 Wood (exterior) 100+ Wood (hollow-core interior) 20 to 30 Wood (solid-core interior) 30 to 100+ Copper-plated wiring, copper-clad aluminum, and bare copper wiring are expected to last a lifetime, whereas electrical accessories and lighting controls, such as dimmer switches, may need to be replaced after 10 years. GFCIs could last 30 years, but much less if tripped regularly. Remember that faulty, damaged or overloaded electrical circuits or equipment are the leading cause of house fires, so they should be inspected regularly and repaired or updated as needed.

ELECTRICAL YEARS Accessories 10+ Arc-Fault Circuit Interrupters (AFCIs)

30

Bare Copper 100+ Bulbs (compact fluorescent) 8,000 to 10,000+ hours Bulbs (halogen) 4,000 to 8,000+ hours Bulbs (incandescent) 1,000 to 2,000+ hours Bulbs (LED) 30,000 to 50,000+ hours Copper-Clad Aluminum 100+ Copper-Plated 100+

Page 107: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

©2018 Strong Foundations Home Inspection

Fixtures 40 Ground-Fault Circuit Interrupters (GFCIs)

up to 30

Lighting Controls 30+ Residential Propane Backup Generators

12

Service Panel 60 Solar Panels 20 to 30 Solar System Batteries 3 to 12 Wind Turbine Generators 20 Floor and roof trusses and laminated strand lumber are durable household components, and engineered trim may last 30 years.

ENGINEERED LUMBER YEARS Engineered Joists 80+ Laminated Strand Lumber 100+ Laminated Veneer Lumber 80+ Trusses 100+ Fastener manufacturers do not give lifespans for their products because they vary too much based on where the fasteners are installed in a home, the materials in which they're installed, and the local climate and environment. However, inspectors can use the guidelines below to make educated judgments about the materials they inspect.

FASTENERS, CONNECTORS & STEEL

YEARS

Adjustable Steel Columns 50+ Fasteners (bright) 25 to 60 Fasteners (copper) 65 to 80+ Fasteners (galvanized) 10+ Fasteners (electro-galvanized) 15 to 45 Fasteners (hot-dipped galvanized)

35 to 60

Fasteners (stainless) 65 to 100+ Steel Beams 200+ Steel Columns 100+ Steel Plates 100+ Flooring life is dependent on maintenance and the amount of foot traffic the floor endures.

FLOORING YEARS All Wood Floors 100+ Bamboo 100+ Brick Pavers 100+

Page 108: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

©2018 Strong Foundations Home Inspection

Carpet 8 to 10 Concrete 50+ Engineered Wood 50+ Exotic Wood 100+ Granite 100+ Laminate 15 to 25 Linoleum 25 Marble 100+ Other Domestic Wood 100+ Slate 100 Terrazzo 75+ Tile 75 to 100 Vinyl 25 Concrete and poured-block footings and foundations will last a lifetime, assuming they were properly built. Waterproofing with bituminous coating lasts 10 years, but if it cracks, it is immediately damaged.

FOUNDATIONS YEARS Baseboard Waterproofing System 50 Bituminous-Coating Waterproofing

10

Concrete Block 100+ Insulated Concrete Forms (ICFs) 100 Permanent Wood Foundation (PWF; treated)

75

Post and Pier 20 to 65 Post and Tensioned Slab on Grade

100+

Poured-Concrete Footings and Foundation

100+

Slab on Grade (concrete) 100 Wood Foundation 5 to 40 Framing and structural systems have extended longevities; poured-concrete systems, timber frame houses and structural insulated panels will all last a lifetime.

FRAMING YEARS Log 80 to 200 Poured-Concrete Systems 100+ Steel 100+ Structural Insulated Panels (SIPs)

100+

Timber Frame 100+

Page 109: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

©2018 Strong Foundations Home Inspection

The quality and frequency of use will affect the longevity of garage doors and openers.

GARAGES YEARS Garage Doors 20 to 25 Garage Door Openers 10 to 15 Home technology systems have diverse life expectancies and may have to be upgraded due to evolution in technology.

HOME TECHNOLOGY YEARS Built-In Audio 20 Carbon Monoxide Detectors* 5 Doorbells 45 Home Automation System 5 to 50 Intercoms 20 Security System 5 to 20 Smoke/Heat Detectors* less than 10 Wireless Home Networks 5+ * Batteries should be changed at least annually. Thermostats may last 35 years but they are usually replaced before they fail due to technological improvements.

HVAC YEARS Air Conditioner (central) 7 to 15 Air Exchanger 15 Attic Fan 15 to 25 Boiler 40 Burner 10+ Ceiling Fan 5 to 10 Chimney Cap (concrete)

100+

Chimney Cap (metal) 10 to 20 Chimney Cap (mortar) 15 Chimney Flue Tile 40 to 120 Condenser 8 to 20 Dampers 20+ Dehumidifier 8 Diffusers, Grilles and Registers 25 Ducting 60 to 100 Electric Radiant Heater 40 Evaporative Cooler 15 to 25

Page 110: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

©2018 Strong Foundations Home Inspection

Furnace 15 to 25 Gas Fireplace 15 to 25 Heat Exchanger 10 to 15 Heat Pump 10 to 15 Heat-Recovery Ventilator 20 Hot-Water and Steam-Radiant Boiler

40

Humidifier 12 Induction and Fan-Coil Units 10 to 15 Thermostats 35 Ventilator 7 As long as they are not punctured, cut or burned and are kept dry and away from UV rays, cellulose, fiberglass and foam insulation materials will last a lifetime. This is true regardless of whether they were installed as loose-fill, housewrap or batts/rolls.

INSULATION & INFILTRATION BARRIERS

YEARS

Batts/Rolls 100+ Black Paper (felt paper) 15 to 30 Cellulose 100+ Fiberglass 100+ Foamboard 100+ Housewrap 80+ Liquid-Applied Membrane 50 Loose-Fill 100+ Rockwool 100+ Wrap Tape 80+ Masonry is one of the most enduring household components. Fireplaces, chimneys and brick veneers can last the lifetime of the home.

MASONRY & CONCRETE YEARS Brick 100+ Insulated Concrete Forms (hybrid block)

100+

Concrete Masonry Units (CMUs) 100+ Man-Made Stone 25 Masonry Sealant 2 to 20 Stone 100+ Stucco/EIFS 50+ Veneer 100+

Page 111: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

©2018 Strong Foundations Home Inspection

Custom millwork and stair parts will last a lifetime and are typically only upgraded for aesthetic reasons.

MOLDING, MILLWORK & TRIM

YEARS

Attic Stairs (pull-down) 50 Custom Millwork 100+ Pre-Built Stairs 100+ Stair Parts 100+ Stairs 100+ The lifetime of any wood product depends heavily on moisture intrusion.

PANELS YEARS Flooring Underlayment 25 Hardboard 40 Particleboard 60 Plywood 100 Softwood 30 Oriented Strand Board (OSB) 60 Wall Panels 100+ The quality of plumbing fixtures varies dramatically. The mineral content of water can shorten the life expectancy of water heaters and clog showerheads. Also, some finishes may require special maintenance with approved cleaning agents per the manufacturers in order to last their expected service lives.

PLUMBING, FIXTURES & FAUCETS

YEARS

ABS and PVC Waste Pipe 50 to 80 Accessible/ADA Handles 100+ Acrylic Kitchen Sink 50 Cast-Iron Bathtub 100 Cast-Iron Waste Pipe (above ground)

60

Cast-Iron Waste Pipe (below ground)

50 to 60

Concrete Waste Pipe 100+ Copper Water Lines 70 Enameled Steel Kitchen Sink 5 to 10+ Faucets and Spray Hose 15 to 20 Fiberglass Bathtub and Shower 20 Gas Lines (black steel) 75 Gas Lines (flex) 30

Page 112: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

©2018 Strong Foundations Home Inspection

Hose Bibs 20 to 30 Instant (on-demand) Water Heater

10

PEX 40 Plastic Water Lines 75 Saunas/Steam Room 15 to 20 Sewer Grinder Pump 10 Shower Enclosure/Module 50 Shower Doors 20 Showerheads 100+ (if not clogged by

mineral/other deposits) Soapstone Kitchen Sink 100+ Sump Pump 7 Toilet Tank Components 5 Toilets, Bidets and Urinals 100+ Vent Fan (ceiling) 5 to 10 Vessel Sink (stone, glass, porcelain, copper)

5 to 20+

Water Heater (conventional) 6 to 12 Water Line (copper) 50 Water Line (plastic) 50 Water Softener 20 Well Pump 15 Whirlpool Tub 20 to 50 Radon systems have but one moving part: the radon fan.

RADON SYSTEMS YEARS Air Exchanger 15 Barometric Backdraft Damper/Fresh-Air Intake

20

Caulking 5 to 10 Labeling 25 Manometer 15 Piping 50+ Radon Fan 5 to 8 The life of a roof depends on local weather conditions, building and design, material quality, and adequate maintenance. Hot climates drastically reduce asphalt shingle life. Roofs in areas that experience severe weather, such as hail, tornadoes and/or hurricanes, may also experience a shorter-than-normal lifespan overall or may incur isolated damage that requires repair in order to ensure the service life of the surrounding roofing materials.

ROOFING YEARS

Page 113: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

©2018 Strong Foundations Home Inspection

Aluminum Coating 3 to 7 Asphalt (architectural) 30 Asphalt Shingles (3-tab) 20 BUR (built-up roofing) 30 Clay/Concrete 100+ Coal and Tar 30 Copper 70+ EPDM (ethylene propylene diene monomer) Rubber

15 to 25

Fiber Cement 25 Green (vegetation-covered) 5 to 40 Metal 40 to 80 Modified Bitumen 20 Simulated Slate 10 to 35 Slate 60 to 150 TPO 7 to 20 Wood 25 Outside siding materials typically last a lifetime. Some exterior components may require protection through appropriate paints or sealants, as well as regular maintenance. Also, while well-maintained and undamaged flashing can last a long time, it is their connections that tend to fail, so seasonal inspection and maintenance are strongly recommended.

SIDINGS, FLASHING & ACCESSORIES

YEARS

Aluminum Gutters, Downspouts, Soffit and Fascia

20 to 40+

Aluminum Siding 25 to 40+ Asbestos Shingle 100 Brick 100+ Cementitious 100+ Copper Downspouts 100 Copper Gutters 50+ Engineered Wood 100+ Fiber Cement 100+ Galvanized Steel Gutters/Downspouts

20

Manufactured Stone 100+ Stone 100+ Stucco/EIFS 50+ Trim 25 Vinyl Gutters and Downspouts 25+ Vinyl Siding 60 Wood/Exterior Shutters 20

Page 114: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

©2018 Strong Foundations Home Inspection

Site and landscaping elements have life expectancies that vary dramatically.

SITE & LANDSCAPING YEARS American Red Clay 100+ Asphalt Driveway 15 to 20 Brick and Concrete Patio 15 to 25 Clay Paving 100+ Concrete Walks 40 to 50 Controllers 15 Gravel Walks 4 to 6 Mulch 1 to 2 Polyvinyl Fencing 100+ Sprinkler Heads 10 to 14 Underground PVC Piping 60+ Valves 20 Wood Chips 1 to 5 Wood Fencing 20 Swimming pools are composed of many systems and components, all with varying life expectancies.

SWIMMING POOLS YEARS Concrete Shell 25+ Cover 7 Diving Board 10 Filter and Pump 10 Interior Finish 10 to 35 Pool Water Heater 8 Vinyl Liner 10 Waterline Tile 15+ Aluminum windows are expected to last between 15 and 20 years, while wooden windows should last nearly 30 years.

WINDOWS YEARS Aluminum/Aluminum-Clad 15 to 20 Double-Pane 8 to 20 Skylights 10 to 20 Vinyl/Fiberglass Windows 20 to 40 Window Glazing 10+ Wood 30+ Note: Life expectancy varies with usage, weather, installation, maintenance and quality of

Page 115: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

©2018 Strong Foundations Home Inspection

materials. This list should be used only as a general guideline and not as a guarantee or warranty regarding the performance or life expectancy of any appliance, product, system or component. Evaluations are made as to the present age, and remaining economic life of an item, i.e. water heaters, roofs, plumbing, furnaces, etc. These evaluations are based on visual observation, industry averages and prior experience. THEY ARE NOT OFFERED AS A WARRANTY OR CERTIFICATION OF REMAINING LIFE.

Page 116: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

©2018 Strong Foundations Home Inspection

HOME MAINTENANCE CHECK LIST: Monthly: 1. Clean any removable dishwasher filters. 2. Purge food disposal by filling the kitchen sink with clean water, then turn on the device until the water drains through. 3. Wash refrigerator/freezer interior walls and door gaskets with a solution of one quart of warm water to two tablespoons of baking soda and wipe dry. 4. Vacuum and clean “return” air ducts/grills. 5. Inspect lighting fixtures and replace any burned-out bulbs. 6. Clean clothes dryer lint trap and/or duct for better energy efficiency and to decrease the risk of fire. Quarterly: 1. Inspect and service doors by cleaning and lubricating latches, hinges or replacing weather-stripping as might be required. 2. Inspect and repair, if necessary, exterior caulking and finish around windows, doors, and siding. 3. Replace/clean, at least quarterly, furnace, heating and cooling system filters. 4. Re-tighten knobs and pulls on cabinets. Clean and lubricate drawer tracks and guides. Semi-annually: 1. Inspect and test smoke and carbon monoxide alarms. Replace backup batteries as might be required. 2. Test (GFCI) ground fault circuit interrupters and (AFCI) arc fault breakers. 3. Inspect and maintain/clean gutters and downspouts. Runoff water must be directed away from the home. 4. Inspect attics and substructure areas for rodent droppings or other signs of pests or leaks/standing water, etc. 5. Prior to the beginning of the rainy season, test sump pumps for adequacy and function. 6. Look for moisture or decay, outside and inside the house, where flat surface decks and landing attach to the house. This is especially important if the landings do not have proper flashings. 7. Clean range hood fan grills and housings. 8. Use a vacuum cleaner to remove dust on coils behind the refrigerator/freezer. Annually: 1. Licensed contractor to inspect and service heating and air-conditioning systems. 2. Professional contractor to inspect and service wood burning appliances and chimneys. 3. Seal any foundation cracks. 4. Inspect, clean and lubricate garage vehicle door tracks and test auto-reverse functions. 5. Clean and lubricate sliding glass door and window tracks. 6. Inspect exterior paint for cracking and wear. Repaint, caulk and seal as needed.

Page 117: FAIRA TRANSPARENCY REPORTS 17812 25th Ave E, Tacoma, … · GARAGE DOORS 20: - The garage door springs are not provided with safety restraints to eliminate damage or injury in the

©2018 Strong Foundations Home Inspection

7. Reseal, as required, wood decks and landings. 8. Inspect, for water damage, pests or rot, any substructure and attic areas. 9. Inspect roof flashings, chimney caps, shingles. 10. Inspect outside electrical service lines for damage, exposed wires or proximity to tree limbs. 11. Inspect all supply hoses at sinks, toilets and washing machines. 12. Clean and repair caulking or grout in bathrooms or kitchens. 13. Clean bathroom exhaust fan blades and grills. 14. Inspect all electric coeds and replace as needed. 15. Change water filters and have fresh water systems professionally services. Tips for keeping drains clear: 1. Pour a pot of hot water down the drain once a week to help clear away fat or grease that may have built-up in the drain line or the P-trap. 2. If a drain is clogged, try pouring 1/2 cup of white vinegar down the drain. Cover the drain and let the mixture sit for a few minutes. Then pour a pot of hot water down the drain. General Safety tips: Ensure that you know where the following items are located: 1. Emergency contact telephone numbers. 2. Fire extinguishers and water hose pipes. 3. Heating gas/fuel main shut off valve. 4. Main electrical disconnect circuit breaker (breaker box/service panel). 5. Main drain line clean-out. 6. Main water shut-off valve. 7. All window and door exits.