Comparison Retrofitting Techniques for Existing Steel Moment Resisting Frames
Example 1-Special Moment Frames
-
Upload
toshicrystal -
Category
Documents
-
view
227 -
download
0
Transcript of Example 1-Special Moment Frames
-
8/13/2019 Example 1-Special Moment Frames
1/16
Steel Structures 10 - 60Instructional Material Complementing FEMA 451, Design Examples
Special Moment FramesExample
5
at25'-0"
N
7 at 25'-0"
-
8/13/2019 Example 1-Special Moment Frames
2/16
Steel Structures 10 - 61Instructional Material Complementing FEMA 451, Design Examples
Special Moment Frames
The following design steps will be reviewed:
Select preliminary member sizes
Check member local stability
Check deflection and drift
Check torsional amplification Check the column-beam moment ratio rule
Check shear requirement at panel zone
Select connection configuration
-
8/13/2019 Example 1-Special Moment Frames
3/16
Steel Structures 10 - 62Instructional Material Complementing FEMA 451, Design Examples
Special Moment Frames
Select preliminary member sizes The preliminary
member sizes are given in the next slide for the
frame in the East-West direction. These members
were selected based on the use of a 3D stiffness
model in the program RAMFRAME. As will be
discussed in a subsequent slide, the driftrequirements controlled the design of these
members.
-
8/13/2019 Example 1-Special Moment Frames
4/16
Steel Structures 10 - 63Instructional Material Complementing FEMA 451, Design Examples
SMF Example Preliminary Member Sizes
-
8/13/2019 Example 1-Special Moment Frames
5/16
Steel Structures 10 - 64Instructional Material Complementing FEMA 451, Design Examples
SMF Example Check Member Local Stability
bf
tf
twhc
Check beam flange:
(W33x141 A992)
Upper limit:
Check beam web:
Upper limit:
6.012
f
f
b
t=
0.3 7.22y
E
F=
49.6c
w
ht
=
3.76 90.6y
E
F =
OK
OK
-
8/13/2019 Example 1-Special Moment Frames
6/16
Steel Structures 10 - 65Instructional Material Complementing FEMA 451, Design Examples
SMF Example Check Deflection and Drift
The frame was checked for an allowable story drift limit of
0.020hsx. All stories in the building met the limit. Note that the
NEHRP Recommended Provisions Sec. 4.3.2.3 requires the
following check for vertical irregularity:
2
3
5.17 .
268 .0.98 1.3
3.14 .160 .
d x story
d x story
in
C in
inCin
= =
where M*pc = the sum of the moments in the column above andbelow the joint at the intersection of the beam and column
centerlines. M*pc is determined by summing the projections of the
nominal flexural strengths of the columns above and below the
joint to the beam centerline with a reduction for the axial force in
the column.
M*pb= the sum of the moments in the beams at the intersection ofthe beam and column centerlines.
-
8/13/2019 Example 1-Special Moment Frames
10/16
Steel Structures 10 - 69Instructional Material Complementing FEMA 451, Design Examples
SMF Example Column-Beam Moment Ratio
Column W14x370; beam W33x141
* 2
2
*
500
2 736 50 109
66,850
uc
pc c ycg
pc
P kips
M Z F in ksiA in
M in kips
= =
=
Adjust this by the ratio of average story height to average clearheight between beams.
* 268 . 160 .66,850 75,300251.35 . 128.44 .
pc
in inM in kips in kips
in in
+ = = +
-
8/13/2019 Example 1-Special Moment Frames
11/16
Steel Structures 10 - 70Instructional Material Complementing FEMA 451, Design Examples
SMF Example Column-Beam Moment Ratio
For beams:
( )
( )( ) ( ) ( )
*
' 2
' 2
'
2
(1.1 )
. .
/ 2 / 2 25.61 .
222 / 2
1.046 248.8 .2 25,700
12 2
248.8 .
pb y p v
v p h
h
c b
p
p
p p
M R M M
with M V S
S dist fromcol centerline to plastic hinge
d d in
V shear at plastic hinge location
wLMV M wL
L
klf inin kips
in
= +
==
= + =
=
+ = + =
+
= 221.2kips=
-
8/13/2019 Example 1-Special Moment Frames
12/16
Steel Structures 10 - 71Instructional Material Complementing FEMA 451, Design Examples
SMF Example Column-Beam Moment Ratio
*
(221.2 )(25.61 .) 5,665
(1.1 )
2[(1.1)(1.1)(25,700 ) 5,665 ] 73,500
v p h
pb y p v
M V S kips in in kips
and
M R M M
in kips in kips in kips
= = =
= +
= + =
The ratio of column moment strengths to beam moment strengths is
computed as:
*
*
75,3001.02 1.00
73,500
pc
pb
M in kipsRatio OK
M in kips
= = = >
Other ratios are also computed to be greater than 1.0
-
8/13/2019 Example 1-Special Moment Frames
13/16
Steel Structures 10 - 72Instructional Material Complementing FEMA 451, Design Examples
SMF Example Panel Zone Check
The 2005 AISC Seismic specification is used to check the panel zone strength. Notethat FEMA 350 contains a different methodology, but only the most recent AISCprovisions will be used. From analysis shown in the NEHRP Design Examples volume(FEMA 451), the factored strength that the panel zone at Story 2 of the frame in theEW direction must resist is 1,883 kips.
2 23 (3)(16.475 .)(2.66)0.6 1 (0.6)(50 )(17.92 .)( ) 1
(33.3 .)(17.92 .)( )
537.6 315
( ) determined :
(1
cf cfv y c p p
b c p p
v p
v u
b t inR F d t ksi in t
d d t in in t
R t
The required total web plus doubler plate thickness is byR R
= + = +
= +
=
.0)(537.6 315) 1,883
2.91 .
1.66 ., :
1.25 . ( 1.25 . 0.625 . )
required
doubler
p
p
p
t kips
t in
The column web thickness is in therefore the required doubler plate thickness is
t in therefore use one in plate or two in plates
+ =
=
=
-
8/13/2019 Example 1-Special Moment Frames
14/16
Steel Structures 10 - 73Instructional Material Complementing FEMA 451, Design Examples
SMF Example Connection Configuration
-
8/13/2019 Example 1-Special Moment Frames
15/16
Steel Structures 10 - 74Instructional Material Complementing FEMA 451, Design Examples
SMF Example Connection Configuration
-
8/13/2019 Example 1-Special Moment Frames
16/16
Steel Structures 10 - 75Instructional Material Complementing FEMA 451, Design Examples
Special Moment Frames
Summary
Beam to column connection capacity
Select preliminary member sizes
Check member local stability
Check deflection and drift
Check torsional amplification
Check the column-beam moment ratio rule
Check shear requirement at panel zone
Select connection configuration
Prequalified connections
Testing