Thank you for purchasing Coolmay EX3G HMI PLC All-in-One products. This manual mainly explains the product features, specifications and wiring methods. Detailed PLC programming, please refer to “Coolmay EX3G HMI PLC All-in-One Programming Manual”. Detailed HMI part, refer to “Coolmay HMI Programming Manual”. HMI optional RS232/RS485 FG 0V 24V Electric Design Product structure RUN: PLC operating indicator COM: flash when PLC communicates with HMI Y20 COM4 Y17 Y16 Y15 Y14 COM3 Y13 Y12 Y11 Y10 COM2 Y07 Y06 Y05 Y04 COM1 Y03 Y02 Y01 Y00 COM0 X23 X22 X21 X20 X17 X16 X15 X14 X13 X12 X11 X10 COM X07 X06 X05 X04 X03 X02 X01 X00 COM Graph 5 EX3G-70KH PLC programming port (optional RS485/WIFI) Network port (optional) Graph 6 EX3G-100HA X23 X22 X21 X20 COM X16 X15 X14 X13 X12 X11 X10 COM X07 X06 X05 X04 X03 X02 X01 X00 COM Y23 Y22 Y21 Y20 Y17 Y16 Y15 Y14 COM3 Y13 Y12 Y11 Y10 COM2 Y07 Y06 Y05 Y04 COM1 Y03 Y02 Y01 Y00 COM0 Hardware Interface AD1 AD2 AD3 AD4 GND DA0 DA1 EX3G-70KH EX3G-43HB/H Mechanical Design Input ON Input OFF Filter function High-speed counting With filter function, the filter time can be set among 0-60ms, defaulted as 10ms Digital relay output index Max current Circuit power voltage Circuit insulation On response time Mechanical life without load Electric life with rated load 2A/point, 4A/4 point COM, 5A/8 point COM, 5A/12 point COM Below DC30V/ Below AC220V Relay mechanical insulation Approx. 10ms 10 million times 300,000 times Digital transistor(MOS) output index Max current Circuit power voltage Circuit insulation Isolated voltage (power-terminal) On response time High-speed output frequency MOS tube: 2A/point, 4A/4 point COM, 5A/12 point COM; MT: 0.5A/point, 0.8A/4 point COM, 1.6A/12 point COM DC24V Optocoupler insulation 1500VAC High-speed output: 10μs, and others 0.5ms Analog input indexes Input signal Response time Analog input Precision PT100/PT1000/thermocouple/NTC/0-10V/0-5V/-10V~10V/-5V~5V/0-20mA/4-20mA/ customizations. 1 scanning cycle 0-16 channels 12 bits Analog output indexes Output signal Analog output indexes Precision 0-5V/0-10V/-10~10V/-5~5V/0-20mA/4-20mA/customizations 0-8 channels 12 bits External port COM port Environment Operating temperature Relative humidity Storage temperature Vibrational frequency 0°C~50°C 5%~95%RH -20°C~70°C 10-57Hz, amplitude 0.035mm, 57Hz-150Hz, 4.9m/s² (10 times each on X, Y, Z, total 80 minutes each) EX3G HMI PLC All-in-One User Manual Chart 3: Mounting dimension Model Max digital points Mounting dimension Boundary dimension W*H*D(mm) A(mm) B(mm) EX3G-43HB EX3G-70H EX3G-100HA 12DI/12DO 24DI/20DO 30DI/30DO 119 194 261 93 138 180 134*102*30 212*148*40 275*194*36 Four side mounting holes Terminal block of power supply FG: cover protection GND 0V: 24V negative 24V: 24V positive Terminal block of DO Terminal block of DI USB port (not available for HB series) PWR: power indicator HMI programming port PLC programming port/RS485/RS232 PLC operating switch RUN/STOP AD DA HMI RS232/RS485/CAN LCD Network port (HMI/PLC) PLC USB programming port EX3G-50KH 12DI/12DO 143 86 150*93*32 EX3G-50KH 6 13 Graph 2 Product structure More specs can be customized if bulk order. Max analog quantity 4AD/2DA 12AD/8DA 16AD/8DA 4AD/2DA Wiring specifications of terminals: 22-14AWG wire. The terminals of this serial are all pluggable ones. Definition of communication interface: Refer to Chart 4:Pin definition The features are as below. Super functions. Its PLC is compatible with FX3G, FX3U, FX3S. It operates fast. Highly integration. 1. The digital points are 30 inputs and 30 outputs at most. The digital output can be transistor, relay or mixed output. Analog can reach up to 16 input and 8 output. It has 2 PLC COM port (RS232 and Mini B-type USB port), 1 downloading port and 1 USB port on HMI. 2. The PLC part of models 70KH, 100HA all-in-one can optionally select one 485 port or two 485 ports (one is changed from existed 232 port), CAN, network port (not coexist with the one on HMI), Wifi (will cover the existed 232 port). The HMI part can optionally select one RS232 or one RS485, and network port (not coexist with the one on PLC). 3. The PLC part of models 43H(HB), 50KH can optionally select two RS485, and HMI part can select one RS232. Support several high-speed counting and high-speed pulse. 1. Commonly high-speed conting is 6-channel single phase 60KHz or AB(Z)2-channel 60KHz plus 1 channel 10KHz. 2. High-speed pulse is commonly 8 channels, HB series Y0-Y7 10KHz per channel, H/HA/KH series Y0-Y3 is 100KHz, Y4-Y7 is 10KHz. Acceleration and deceleration are independent. 3. The total high-speed counting and pulse can not exceed 480KHz. 32K steps program capacity, 32K power-off retentive registers, support interrupt, linear and circular interpolation, PID self-adjusting. Special encryption. Set password as 12345678 to thoroughly prevent reading data.(PLC only supports 8-bit password encryption) PLC is compatible with programming software GX Developer 8.86Q and GX Works2, and HMI is Coolmay HMI programming software. More models are supported to customize if bulk order. X24 X26 X25 X27 Y21 Y22 Y23 Operation switch X17 X27 X26 X25 X24 X30 X31 X32 X33 X34 X35 GND1 Y35 Y34 Y33 Y32 Y31 Y27 COM5 Y26 Y25 Y24 Y30 AD5 AD6 AD7 AD8 AD9 AD10 AD12 AD13 AD14 AD15 AD0 AD1 AD2 AD3 AD4 AD11 GND GND1 DA0 DA1 DA3 DA7 DA4 DA5 DA6 DA2 AD0 EX3G-100HA-44M-16AD8DA EX3G-100HA-60M-5AD2DA AD1 AD2 AD3 AD4 GND DA0 DA1 X30 X31 X32 X33 X34 X35 GND1 Y35 Y34 Y33 Y32 Y31 Y27 COM5 Y26 Y25 Y24 Y30 AD5 AD6 AD7 AD8 AD9 AD10 AD12 AD13 AD14 AD15 AD0 AD1 AD2 AD3 AD4 AD11 GND GND1 DA0 DA1 DA3 DA7 DA4 DA5 DA6 DA2 AD0 EX3G-70KH-44M-16AD8DA EX3G-70KH-60M-5AD2DA High-speed input: current>5.8mA/24V Common input: current >9.9mA/24V High-speed input: current<4.5mA/19V Common input: current >4mA/17V Input level Sink NPN, com isolation, S/S Output level Low level NPN, COM connects negative Output level Dry contact, COM connects positive or negative 8 channels H/KH/HA Y0-Y3 100KHz, Y4-Y7 10KHz. Acceleration and deceleration are independent.The total high-speed counting and pulse can not exceed 480KHz. . HB series Y0-Y7 10KHz per channe. series Commonly it is 6 single 0KHz for HB series, 1 , or 3 AB 10KHz, or 2 ABZ 10KHz + 1 AB 10KHz. H/KH/HA series can be 6 single phase 60KHz, or 2 AB(Z) 60KHz + 1 AB 10KHz. Refer to "Chart 1: basic parameter". 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Product Details 1 EX3G 2 43HB/43H: 4.3 50KH: 5 70KH: 7 100HA: 10 3 4 5 6 7 8 : , , : : , : : : : : _: - ~ _: - ~ ( _ _) 9 _: - ~ _: - ~ ( / , ) 10 , C3- ABZ phase counting. for HB series, 1 , or 3 AB 10KHz, or 2 ABZ 10KHz + 1 AB 10KHz. H/KH/HA series can be 6 single phase 60KHz, or 2 AB(Z) 60KHz + 1 AB 10KHz. 11 P0-high-speed pulse 10KHz; - 12 efer to "Chart 1: basic parameter". . . . . . . . . . . . . Optional COM port, r Series HMI Digital input and output (DI/DO) 16(8DI/8DO), 24(12DI/12DO), 44(24DI/20DO), 60(30DI/30DO), etc. Module type M- Main module of universal controller Digital output (DO) type R- relay T- transistor RT- both relay and transistor Analog input (AD) 4 channels for 43H(HB)/50KH, 12 for 70H, 16 for 70KH/100HA Analog output (DA) 2 channels for 43H(HB)/50KH, 8 for 70H/70KH/100HA AI type E Thermocouple E (can be customized as type K T, S or J supports negative temperature), PT PT100, PT1000 PT1000 NTC thermistor 10K, 50K, 100K A0 0-20mA A4 4-20mA V 0-10V V5 0-5V V5 5V 5V V 10V 10V only 7 and 10 inch support V5 and V AO type A0- 0-20mA A4- 4-20mA V- 0-10V V5- 0-5V V5 5V 5V V 10V 10V only 70KH 100HA support negative voltage covers 2 channels C1- singe phase high-speed counting, C2- AB phase counting Commonly it is 6 single 0KHz P- high-speed pulse; Commonly 8 channel, HB series Y0-Y7 10KHz per channel; H/KH/HA series Y0-Y3 is 100KHz, Y4-Y7 is 10KHz; That high speed counting plus high speed pulse must be within 480KHz. Naming rules EX3G 43HB Basic parameter Specifications of HMI PLC All-in-One EX3G-43HB(H)/50KH-16M EX3G-70KH/100HA-16M EX3G-43HB(H)/50KH-24M EX3G-70KH/100HA-24M EX3G-70KH/100HA-44M Digital points Analog points (optional) COM port (optional) High-speed counting (optional) High-speed pulse (optional) DI DO AD DA HMI PLC Single phase AB phase Output 12 12 12 12 24 20 43HB(H)/50KH:MT is MOS output,max load 2A. 70H/ 70KH/100HA:MT is transistor output (Y0-Y3 are MOS outputs) with max load 500mA. MR is relay output with max load 5A. MRT is mixed output, optional according to customer requirements.. Chart 1: basic parameter 485P/232H - 1P - 1C1 A0 V 2DA 4AD RT M 24 - - - - - - Electric parameter Input voltage DC24V Chart 2: electric parameter 8 8 8 8 EX3G-70KH/100HA-60M 30 30 1 2 3 4 5 6 7 8 9 11 10 12 EX3G-43HB/ : 2x 485 port EX3G-70KH/100HA: 1x 485 or 2x 485 (one is changed from the existed 232), CAN, network port (can't coexist with the one on HMI), Wifi (cover the existed 232 port) 43H 50KH / EX3G-43HB/43H/50KH: 1x 232 port. EX3G-70KH/100HA: 1x 232 port or 485 port, network port (can't coexist with the one on PLC) H/KH/HA: 6-channel 60KHz HB: 6-channel 10KHz. 8 channels. H/KH/HA: Y0-Y3 is 100KHz, Y4-Y7 is 10KHz. HB: Y0-Y7 is 10KHz per channel. Acceleration and deceleration are independent. High-speed counting and pulse can't over 480KHz. Digital input indexes ABZ phase Isolation mode Photocoupling Input impedance High-speed input 3.3KΩ Common input 4.3Ω 6 13 USB port/optional SD card HMI download port PLC USB programming port PLC USB programming port Operation switch USB port/optional SD card HMI download port Network port (optional) FG 0V 24V PLC programming port (optional RS485/WiFi) 10 11 12 1 4 3 2 8 14 7 5 15 9 16 16 Wifi COM4 16 8 4 2 4 2 16 8 16 8 5 2 H/KH/HA: 2-channel 60KHz and 1-channel 10KHz HB: 3-channel 10KHz. H/KH/HA: 2 ABZ 60KHz HB: 2 ABZ 10KHz. Note: A/B, A1/B1 is Rs485 Graph 7 COM1/COM2 EX3G-70H-16M EX3G-70H-24M EX3G-70H-38M EX3G-70H-44M 12 12 8 8 20 18 24 20 8 6 12 8 Graph 1 Mounting dimension EX3G-100HA EX3G-43HB/H EX3G-70KH EX3G-50KH 35.6 163 5 226 194 275 36 102 120 32 150 93 32 86 143 134 94 217 154 262 180 EX3G-70H 148 212 40 194 138 More models are supported to customize if bulk order. EX3G-100HA 6 13 1 10 11 9 4 3 2 5 7 8 14 12 15 16 13 6 10 11 EX3G-70H 3 2 15 8 14 9 7 5 1 4 8 EX3G-43HB/H Graph3 Graph 4 EX3G-50KH FG 0V 24V RS232/RS485(optional) HMI download port Y21 Y20 Y17 Y16 Y15 Y14 COM3 Y13 Y12 Y11 Y10 COM2 Y07 Y06 Y05 Y04 COM1 Y03 Y02 Y01 Y00 COM0 X23 X22 X21 X20 X17 X16 X15 X14 X13 X12 X11 X10 COM X07 X06 X05 X04 X03 X02 X01 X00 COM Graph 5 EX3G-70H PLC operating switch PLC prgramport X24 X25 X26 X27 AD07 AD05 AD00 GND GND DA00 DA06 A B Y22 Y23 AD06 AD04 AD03 AD02 AD01 DA01 DA02 DA03 DA04 DA05 DA07 PLC download port EX3G-70KH 30DI/30DO 217 154 226*163*35.6 16AD/8DA Ethernet port (optional) USB port/optional SD card 6 13 Automation Expert 1 4 11 10 3 2 8 5 9 7 16 PLC USB program port FG 0V 24V PLC progrm port/ optional HMI 232 port USB port/ optional SD card (HB can't support) PLC operating switch HMI download port DA0 DA1 GND AD0 AD1 AD2 AD3 GND B A Y13 Y12 Y11 Y10 Y07 Y06 Y05 Y04 Y03 Y02 Y01 Y00 COM X13 X12 X11 X10 X07 X06 X05 X04 X03 X02 X01 X00 COM PLC USB program port PLC operating switch HMI download port USB port/ optional SD card PLC progrm port/ optional HMI 232 port FG 0V 24V Y13 Y12 Y11 Y10 Y07 Y06 Y05 Y04 Y03 Y02 Y01 Y00 COM DA0 DA1 AD0 AD1 AD2 AD3 B A X13 X12 X11 X10 X07 X06 X05 X04 X03 X02 X01 X00 COM 1 4 10 11 3 16 2 8 7 9

Transcript of EX3G HMI PLC all-in-one User Manual 20210601

Page 1: EX3G HMI PLC all-in-one User Manual 20210601

Thank you for purchasing Coolmay EX3G HMI PLC All-in-One products. This manual mainly explains the product features, specifications and wiring methods. Detailed PLC programming, please refer to “Coolmay EX3G HMI PLC All-in-One Programming Manual”. Detailed HMI part, refer to “Coolmay HMI Programming Manual”.

HMI optional RS232/RS485

FG 0V 24V

Electric Design

Product structure

RUN: PLC operating

indicatorCOM: flash when PLC communicates with HMI

Y20COM4

Y17Y16Y15Y14

COM3Y13Y12Y11Y10

COM2Y07Y06Y05Y04

COM1Y03Y02Y01Y00

COM0

X23X22X21X20X17X16X15X14X13X12X11X10COMX07X06X05X04X03X02X01X00COM

Graph 5 EX3G-70KH

PLC programming port (optional RS485/WIFI)

Network port (optional)

Graph 6 EX3G-100HA

X23X22X21X20COM

X16X15X14X13X12X11X10COMX07X06X05X04X03X02X01X00COM

Y23Y22Y21Y20

Y17Y16Y15Y14

COM3Y13Y12Y11Y10

COM2Y07Y06Y05Y04

COM1Y03Y02Y01Y00

COM0

Hardware Interface

AD

1A

D2

AD

3A

D4

GND

DA

0D

A1

EX3G-70KHEX3G-43HB/H

Mechanical Design

Input ON

Input OFF

Filter function

High-speed counting

With filter function, the filter time can be set among 0-60ms, defaulted as 10ms

Digital relay output index

Max current

Circuit power voltage

Circuit insulation

On response time

Mechanical life without load

Electric life with rated load

2A/point, 4A/4 point COM, 5A/8 point COM, 5A/12 point COM

Below DC30V/ Below AC220V

Relay mechanical insulation

Approx. 10ms

10 million times

300,000 times

Digital transistor(MOS) output index

Max current

Circuit power voltage

Circuit insulation

Isolated voltage (power-terminal)

On response time

High-speed output frequency

MOS tube: 2A/point, 4A/4 point COM, 5A/12 point COM; MT: 0.5A/point, 0.8A/4 point COM, 1.6A/12 point COM

DC24V

Optocoupler insulation

1500VAC

High-speed output: 10μs, and others 0.5ms

Analog input indexes

Input signal

Response time

Analog input

Precision

PT100/PT1000/thermocouple/NTC/0-10V/0-5V/-10V~10V/-5V~5V/0-20mA/4-20mA/ customizations.

1 scanning cycle

0-16 channels

12 bits

Analog output indexes

Output signal

Analog output indexes

Precision

0-5V/0-10V/-10~10V/-5~5V/0-20mA/4-20mA/customizations

0-8 channels

12 bits

External port

COM port

Environment

Operating temperature

Relative humidity

Storage temperature

Vibrational frequency

0°C~50°C

5%~95%RH

-20°C~70°C

10-57Hz, amplitude 0.035mm, 57Hz-150Hz, 4.9m/s²(10 times each on X, Y, Z, total 80 minutes each)

EX3G HMI PLC All-in-One User Manual

Chart 3: Mounting dimension

Model Max digital

pointsMounting dimension Boundary dimension

W*H*D(mm)A(mm) B(mm)

EX3G-43HB

EX3G-70H

EX3G-100HA

12DI/12DO

24DI/20DO

30DI/30DO

119

194

261

93

138

180

134*102*30

212*148*40

275*194*36

Four side mounting holes

Terminal block of power supplyFG: cover protection GND0V: 24V negative24V: 24V positive

Terminal block of DO

Terminal block of DI

USB port (not available for HB series)

PWR: power indicator

HMI programming port

PLC programming port/RS485/RS232PLC operating switchRUN/STOP

ADDA

HMI RS232/RS485/CAN

LCD

Network port (HMI/PLC)

PLC USB programming port

EX3G-50KH 12DI/12DO 143 86 150*93*32

EX3G-50KH

6

13

Graph 2 Product structure

※ More specs can be customized if bulk order.

Max analog quantity

4AD/2DA

12AD/8DA

16AD/8DA

4AD/2DA

Wiring specifications of terminals: 22-14AWG wire. The terminals of this serial are all pluggable ones.

Definition of communication interface : Refer to Chart 4:Pin definition

The features are as below.Super functions. Its PLC is compatible with FX3G, FX3U, FX3S. It operates fast. Highly integration. 1. The digital points are 30 inputs and 30 outputs at most. The digital output can be transistor, relay or mixed output. Analog can reach up to 16 input and 8 output. It has 2 PLC COM port (RS232 and Mini B-type USB port), 1 downloading port and 1 USB port on HMI. 2. The PLC part of models 70KH, 100HA all-in-one can optionally select one 485 port or two 485 ports (one is changed from existed 232 port), CAN, network port (not coexist with the one on HMI), Wifi (will cover the existed 232 port). The HMI part can optionally select one RS232 or one RS485, and network port (not coexist with the one on PLC).

3. The PLC part of models 43H(HB), 50KH can optionally select two RS485, and HMI part can select one RS232. Support several high-speed counting and high-speed pulse. 1. Commonly high-speed conting is 6-channel single phase 60KHz or AB(Z)2-channel 60KHz plus 1 channel 10KHz. 2. High-speed pulse is commonly 8 channels, HB series Y0-Y7 10KHz per channel, H/HA/KH series Y0-Y3 is 100KHz, Y4-Y7 is 10KHz. Acceleration and deceleration are independent. 3. The total high-speed counting and pulse can not exceed 480KHz. 32K steps program capacity, 32K power-off retentive registers, support interrupt, linear and circular interpolation, PID self-adjusting. Special encryption. Set password as 12345678 to thoroughly prevent reading data.(PLC only supports 8-bit password encryption) PLC is compatible with programming software GX Developer 8.86Q and GX Works2, and HMI is Coolmay HMI programming software. More models are supported to customize if bulk order.

X24

X26X25

X27

Y21Y22Y23

Operation switch

X17

X27X26X25X24

X30

X31

X32

X33

X34

X35

GND1

Y35

Y34

Y33

Y32

Y31

Y27

COM5

Y26

Y25

Y24

Y30

AD5

AD6

AD7

AD8

AD9

AD10

AD12

AD13

AD14

AD15

AD0

AD1

AD2

AD3

AD4

AD11

GND

GND1

DA0

DA1

DA3

DA7

DA4

DA5

DA6

DA2

AD0

EX3G-100HA-44M-16AD8DA

EX3G-100HA-60M-5AD2DAAD

1A

D2

AD

3A

D4

GN

DD

A0

DA

1

X30

X31

X32

X33

X34

X35

GND1

Y35

Y34

Y33

Y32

Y31

Y27

COM5

Y26

Y25

Y24

Y30

AD

5A

D6

AD

7A

D8

AD

9A

D10

AD

12

AD

13

AD

14

AD

15

AD

0A

D1

AD

2A

D3

AD

4

AD11

GN

DGN

D1D

A0

DA

1

DA

3

DA

7

DA

4D

A5

DA

6

DA

2

AD

0

EX3G-70KH-44M-16AD8DA

EX3G-70KH-60M-5AD2DA

High-speed input: current>5.8mA/24V Common input: current >9.9mA/24V

High-speed input: current<4.5mA/19V Common input: current >4mA/17V

Input level Sink NPN, com isolation, S/S

Output level Low level NPN, COM connects negative

Output level Dry contact, COM connects positive or negative

8 channelsH/KH/HA Y0-Y3 100KHz, Y4-Y7 10KHz.

Acceleration and deceleration are independent.The total high-speedcounting and pulse can not exceed 480KHz.

. HB series Y0-Y7 10KHz per channe.series

Commonly it is 6 single 0KHz

for HB series, 1 , or 3 AB 10KHz, or 2 ABZ 10KHz + 1 AB 10KHz. H/KH/HA series can be 6 single phase 60KHz,

or 2 AB(Z) 60KHz + 1 AB 10KHz.

Refer to "Chart 1: basic parameter".

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Product Details

1 EX3G2 43HB/43H: 4.3 50KH: 5 70KH: 7 100HA: 10 3 4 5 6 7 8 : , ,

: : , : : : : : _: - ~ _: - ~ ( _ _)

9 _: - ~ _: - ~ ( / , )10 , C3- ABZ phase counting. for HB series, 1 , or 3 AB 10KHz, or 2 ABZ 10KHz + 1 AB 10KHz. H/KH/HA series can be 6 single phase 60KHz, or 2 AB(Z) 60KHz + 1 AB 10KHz.11 P0-high-speed pulse 10KHz; -

12 efer to "Chart 1: basic parameter".

.

.

.

.

.

.

.

.

.

.

.

. Optional COM port, r

SeriesHMI ”Digital input and output (DI/DO) 16(8DI/8DO), 24(12DI/12DO), 44(24DI/20DO), 60(30DI/30DO), etc.Module type M- Main module of universal controllerDigital output (DO) type R- relay T- transistor RT- both relay and transistorAnalog input (AD) 4 channels for 43H(HB)/50KH, 12 for 70H, 16 for 70KH/100HAAnalog output (DA) 2 channels for 43H(HB)/50KH, 8 for 70H/70KH/100HAAI type E Thermocouple E (can be customized as type K T, S or J supports negative temperature),

PT PT100, PT1000 PT1000 NTC thermistor 10K, 50K, 100K A0 0-20mA A4 4-20mA V 0-10V V5 0-5V V5 5V 5V V 10V 10V only 7 and 10 inch support V5 and V

AO type A0- 0-20mA A4- 4-20mA V- 0-10V V5- 0-5VV5 5V 5V V 10V 10Vonly 70KH 100HA support negative voltage covers 2 channels

C1- singe phase high-speed counting, C2- AB phase countingCommonly it is 6 single 0KHz

P- high-speed pulse; Commonly 8 channel, HB series Y0-Y7 10KHz per channel; H/KH/HA series Y0-Y3 is 100KHz, Y4-Y7 is 10KHz; That high speed counting plus high speed pulse must be within 480KHz.

” ” ”

Naming rules EX3G 43HB

Basic parameter

Specifications of HMI PLC All-in-One

EX3G-43HB(H)/50KH-16M

EX3G-70KH/100HA-16M

EX3G-43HB(H)/50KH-24M

EX3G-70KH/100HA-24M

EX3G-70KH/100HA-44M

Digital points

Analog points(optional)

COM port(optional)

High-speed counting(optional)

High-speed pulse(optional)

DI DO AD DA HMI PLCSinglephase

AB phase Output

12 12

12 12

24 20

43HB(H)/50KH:MT is MOS output,max load 2A.70H/ 70KH/100HA:MT is transistor output (Y0-Y3 are MOS outputs) with max load 500mA. MR is relay output with max load 5A. MRT is mixed output, optional according to customer requirements..

Chart 1: basic parameter

485P/232H-1P-1C1A0V2DA4ADRTM24 ------

Electric parameter

Input voltage DC24V

Chart 2: electric parameter

8 8

8 8

EX3G-70KH/100HA-60M 30 30

1 2 3 4 5 6 7 8 9 1110 12

EX

3G-4

3HB

/: 2

x 48

5 po

rtE

X3G

-70K

H/1

00H

A: 1

x 48

5 or

2x

485

(one

is c

hang

ed fr

om th

e ex

iste

d 23

2),

CA

N, n

etw

ork

port

(can

't co

exis

t with

the

one

on

HM

I), W

ifi (c

over

the

exis

ted

232

port)

43H

50K

H/

EX3G

-43H

B/43

H/50

KH: 1

x 23

2 po

rt.

EX3G

-70K

H/10

0HA:

1x

232

port

or 4

85 p

ort,

netw

ork

port

(can

't co

exist

with

the

one

on P

LC)

H/KH/HA:6-channel60KHz

HB:6-channel 10KHz.

8 channels.

H/KH/HA: Y0-Y3 is 100KHz,Y4-Y7 is 10KHz.

HB: Y0-Y7 is 10KHz per channel.

Acceleration anddeceleration are independent.

High-speed counting and pulse can't over 480KHz.

Digital input indexes

ABZ phase

Isolation mode Photocoupling

Input impedance High-speed input 3.3KΩ Common input 4.3Ω

613

USB port/optional SD card

HMI download port

PLC USB programming port

PLC USB programming port

Operation switch

USB port/optional SD cardHMI download port

Network port (optional)

FG 0V 24VPLC programming port

(optional RS485/WiFi)

10 11

12

1

4

3

28147

5

15

916

16

Wifi

COM4

16 8

4 2

4 2

16 8

16 8

5 2

H/KH/HA:2-channel60KHz and1-channel10KHz

HB:3-channel 10KHz.

H/KH/HA:2 ABZ60KHz

HB:2 ABZ 10KHz.

Note: A/B,A1/B1is Rs485

Graph 7

COM1/COM2

EX3G-70H-16M

EX3G-70H-24M

EX3G-70H-38M

EX3G-70H-44M

12 12

8 8

20 18

24 20 8 6

12 8

Graph 1 Mounting dimension

EX3G-100HAEX3G-43HB/H EX3G-70KHEX3G-50KH

35.6

163

5 226

194

275

36

102

120

32

150

93

32

86

143

134

94

217

154

262

180

EX3G-70H

148

212

40

194

138

※More models are supported to customize if bulk order.

EX3G-100HA

6

13

1

10 11 9

4 3

25

7814

12 15

16

13 6 10 11

EX3G-70H

3

215 8 14 9 7

5

1

4

8

EX3G-43HB/HGraph3 Graph 4 EX3G-50KH

FG 0V 24V

RS232/RS485(optional) HMI download port

Y21Y20Y17Y16Y15Y14

COM3Y13Y12Y11Y10

COM2Y07Y06Y05Y04

COM1Y03Y02Y01Y00

COM0

X23X22X21X20X17X16X15X14X13X12X11X10COMX07X06X05X04X03X02X01X00COM

Graph 5 EX3G-70H

PLC operating switch

PLC prgram port

X2

4X

25

X2

6X

27

AD

07

AD

05

AD

00

GN

DG

ND

DA

00

DA

06

A B Y2

2Y

23

AD

06

AD

04

AD

03

AD

02

AD

01

DA

01

DA

02

DA

03

DA

04

DA

05

DA

07

PLC download port

EX3G-70KH 30DI/30DO 217 154 226*163*35.616AD/8DA

Ethernet port (optional)USB port/optional SD card

6

13

Automation Expert

14

1110 3

2 859

7

16

PLC USB program portFG 0V 24V

PLC progrm port/

optional HMI 232 port USB port/optional SD card(HB can't support)

PLC operating switch

HMI download port

DA

0D

A1

GN

DA

D0

AD

1A

D2

AD

3G

ND

B AY13Y12Y11Y10Y07Y06Y05Y04Y03Y02Y01Y00COM

X13X12X11X10X07X06X05X04X03X02X01X00COM

PLC USB program port

PLC operating switch

HMI download port

USB port/optional SD card

PLC progrm port/optional HMI 232 port

FG 0V 24V

Y13Y12Y11Y10Y07Y06Y05Y04Y03Y02Y01Y00COM

DA

0D

A1

AD

0A

D1

AD

2A

D3

B AX13X12X11X10X07X06X05X04X03X02X01X00COM

1 4 1011 3

162 87

9

Page 2: EX3G HMI PLC all-in-one User Manual 20210601

Device allocation and power-down retention instructions

X00-X13 12 points X00-X27 24 points

Y00-Y13 12 points Y00-Y23 20pints

Auxiliary relay M

Status S [S0-S9] 10 points original state/ [S10-S999] 990 points, maintain/ [S1000-S4095] 3096 points, general

Timer T

[T0-T199] 200 points, 100ms, general / [ T250-T255] 6 points, 100ms, maintain/ [T246-T249] 4 points, 1ms accumulation, maintain / [T256-T319] 64 points, 1ms, general use/

[T200-T245] 46 points, 10ms, general use/* 10ms timer is affected by scan cycle. If scan cycle is 12ms, the timer will work every 12ms.

EX3G-43HB 43H/50KH-24M/

Programming reference

DI X

DO Y

[M0-M383] 384 points, general / [M384-M1535] 1152 points, maintain/ [M1536-M7679] 6144 points, general/ [M8000-M8511] 512 points, special

EX3G-70H-44M EX3G-70KH/100HA-60M

Counter C [C0-C15] 16 points, genera / /[C200-C219] 20 points, general use/[C220-C234] 15 points, maintain use/

[C235-C245 single phase single count], [C246-C250 single phase double count] ,[C251-C255 double phase double count]

use [C16-C199] 184 points, maintain use

Data register V,Z [V0-V7] [Z0-Z7] 16 points, used while modifying address

[D0-D127] 128 points, general / [D128-D7999] 7872 points, maintain / [D8000-D8511] 512 points, special use

Nested pointer [N0-N7] 8 points, master use

ConstantK

H

16 bits -32,768-32,767/32 bits -2,147,483,648-2,147,483,647

16 bits 0-FFFFH/32 bits 0-FFFFFFFFH

Tips……………………….........………………………...............……01

Product Features…………………………………………...………02

Product Information……………………………………..…………03

Electric Parameter………………………………………….………04

Mechanical Design…………………………………………......….05

Electric Design……………………………………….............…….06

Equivalent circuit……………………………………………………07

Analog Wiring…………………………………………...........……..08

Anti-interference Processing…………………….……………..09

Programming Reference…………………………………………10

Data Reference………………………………………………...……11

Shenzhen Coolmay Technology Co., Ltd

Tel.: 0755-86950416

86960332

26051858

26400661

Fax: 0755-26400661-808

QQ: 1687435500

Email: [email protected]

Website: https://en.coolmay.com/

Version: 2021/06

Catalog

X00-X35 30 points

Y00-Y35 30 points

[I0□□~I5□□] 6 points, input interruption use/ [I6□□~I8□□] 3 points, timer interruption use/

——

EX3G HMI PLC All-in-One User Manual

Figure 6 Input wiring

Figure 7 Equivalent circuit of relay output Figure 8 Equivalent circuit of transistor output

Figure 9 Inductive load absorption circuit

Figure 10 Pulse output wiring

Note: All internal circuit in the figure are taken as reference.※Equivalent Circuit

The PLC input (X) is an externally powered DC24V sinker (passive NPN) and the input signal is isolated

from the power supply. Connect COM to positive 24V of external power supply while using.

COM0

Y003

Y000

COM1

Y007

Y004

DC24VFuse

Load

AC0~220V~

sinker output

DC24V

DC24V

COM0

Y003

Y000

COM1

Y007

Y004

COM0Y1

COM2Y10

COM1Y4

R=200Ω C=0.22uF,250VAC

RC

~

COM1Y5

~

FWD 1N404

FWD 1N404

PLC relay output

inductive load

AC220V power supply

AC220V power supply

varistor 10D471k (undercurrents)

+

-

+

-

+

-

+

-

+

-

+

-

+

-

+

-

R

COM1

Y4

Y5

Y6

Y7Direction

Pulse

COM0

Y0

Y1

Y2

Y3

PLC internal equivalent circuit

DC24V(5V drive must string 2kΩ resistor)

GND

AD0

AD1

AD15

+104p

GND

DA0

DA1

DA7

AD

AD COM terminal

( )AD 1104p

+ ( )AD 2

* Please consider adding 104p ceramic capacitor or external magnetic ring filter to increase anti-interference ability if analog inputs are unstable.

104p

+ ( )AD 16

- DA COM terminal

+ ( 8)DA

+ ( 2)DA

+ ( 1)DA

* Analog input is AD0-AD15 and output is DA0-DA7. Negative terminals are connected to GND of input and output respectively. One negative voltage output will occupy 2 DA and max 4 negative voltage outputs can be optional. (Only connect DAx and GND. Please be subject to the test report in your package. )

The equivalent circuit of the transistor PLC output is shown in Figure 8. Seen from the figure, the output

terminals are several groups, and each group is electrically isolated, and different groups of output contacts can

be connected to different power circuits. The transistor output can only be used for DC 24V load circuits. Output

wiring is NPN, COM cathode.

For the inductive load connected to the AC circuit, the RC transient voltage absorption circuit should be

considered on the external circuit. For the inductive load of the DC loop, adding a freewheeling diode should be

considered, as shown in Figure 9.

Stepping or servo motor wiring is shown in Figure 10. 3G series PLC defaults Y0-Y7 as pulse points,

and the direction can be customized.

Note:5V drive must connect a 2KΩ resistor on DC24V.

PLC anti-jamming processing1. Strong electricity and weak electricity should be separated wiring and not common ground. When there is

strong electric interference, add magnetic ring on the power supply. And do correct and effective grounding according to the type of the chassis.

2. When the analog is disturbed, 104 ceramic capacitors can be added for filtering, and a correct and effective grounding can be performed.

More details please refer to Methods of Coolmay PLC anti jamming processing

* , " - "

PLC analog wiringTwo-wire system: The positive pole of the power supply is connected to that of the transmitter, and the negative pole of the transmitter is connected to the AD side, and the negative pole of the power supply is connected to the GND. Generally it is the wiring method of the 4-20MA/0-20MA transmitter. Three-wire system: The positive pole of the power supply is connected to that of the transmitter. The negative of the power supply and that of the signal output are the same terminal. The transmitter signal output is connected to the AD terminal. Four-wire system: The positive and negative terminals of the power supply are connected to those of the transmitter respectively, and the positive and negative of the transmitter signal outputs are connected to the AD and the GND terminal respectively.The two wires of the temperature analog are connected to the AD and the GND terminal respectively. If it is a three-wire PT100, it needs to be connected in two lines. The GND common terminal of the analog input and output can be shared.

Load

Load

Load

Load

Load

Load

Load

Fuse

Fuse

Fuse

PLC relay output

inductive load

PLC relay output

inductive load

DC24V power supply

PLC transistor output

inductive load

DC24V power supply

Figure 11 PLC analog wiring

Direction

Pulse

Direction

Pulse

Direction

Pulse

DA

TIPS Please read carefully the related manuals before using our products, and use this product under the environmental conditions specified in this manual.

1. Power on after confirmed the voltage (24VDC, >18W) and right wiring to avoid damage.2. Tighten the screws or the rail while mounting the product to avoid falling off.3. Avoid wiring or plug the cable with electricity, or it is easy to cause electric shock or circuit

damage. When the product emits odor or abnormal sound, please immediately switch off the power. While processing screw holes or wiring, do not drop the metal chips and wire head into the ventilation hole of the controller, which may cause product failure and disoperation. 4. Do not tie power cables and communication cables together or close and keep them at a distance of 10cm or more. Strong and weak currents need to be separated and correctly grounded. In severe interference situations, input and output cables of the communication and high-frequency signals should use shielded cables to improve anti-jamming performance. The grounding terminal FG on this unit must be properly grounded to improve the anti-interference ability.5. DI is an externally powered DC24V sinker (passive NPN), and the input signal is isolated from the power supply. Connect S/S to 24V of external power supply while using.6. DO (transistor) COM is common cathode.7. Please do not disassemble the product or change the wiring. Or it will possible to cause breakdown, malfunction, loss, or fire.8. While installing or disassembling the product, ensure to turn off all power. Or it may cause malfunction and breakdown.

* Programming software PLC: compatible with PLC programming software GX Developer 8.86Q and GX Works2 HMI: Coolmay HMI programming software

* Detailed information, please refer to “Coolmay EX3G HMI PLC All-in-One Programming Manual”, “EX3G HMI PLC All-in-One User Manual”, “Coolmay HMI User Manual”.

.

The soft elements power retentive of HMI PLC all-in-one is permanently retentive, i.e., all the soft elements in the holding area are not lost if the module is powered off. The real-time clock uses a rechargeable battery to ensure that the clock is the current time. All power retentive functions must ensure that the voltage is 23V or higher when DC24V power supply with loads, and the PLC power-on time is longer than 2 minutes. Otherwise, the power retentive functions will be abnormal.

No Register address

D8050

D8051

D8052

D8053

D8054

D8055

D8056

D8057

Range of set value

0-4000

0-4000

0-4000

0-4000

0-4000

0-4000

0-4000

0-4000

Output type

Registers read directly: D[8030]-D[8045] are the input values of [AD0~AD15].The constant scan-time will change to D8059 and started by M8039 (version 26232 and higher). It supports max 15 analog inputs when there exist thermocouple type, and

AD4[D8034] is the ambient temperature of thermocouples. It supports max 16 analog inputs without thermocouples.

Analog input register (AD,accuracy 12 bits). Support FROM demand or register read directly.

The temperature type is one digit after the decimal point, i.e. 182 = 18.2 degrees.

AD samplingFilter cycles = (R23600~R23615)* scan time of the PLC. The default value is 100 and the data cannot be less than or equal to zero. If R23600=1, one PLC scan cycle samples once, and the value in the first analog input is changed once. The larger the value of R23600~R23615 is set, the more stable the result is.

D8073 is the smoothing filter coefficient of all analog inputs. The setting range is 0~999.

Analog output register (DA,accuracy 12 bits). Support TO demand or direct register assignment.

TO demand direct outputs: TO K0 K0 D500 K8 , 8 analog outputs

DA0

DA1

DA2

DA3

DA4

DA5

DA6

DA7

If D8058.0~D8058.7=0, output type is 0-20mA.

If D8058.0~D8058.7=1, the type is 4-20mA.

16 bits (CTU)/ / increase counter 32 bits increase and decrease counter (CTUD) High speed counter

1K

3.9K

COM

X0 0V

X1

1K

3.9K

24V

EX3G-43HB/43H/50KH all-in-one COM

PIN# PLC-485-2serial port 3

PLC-485-1serial port 2

PLC-232serial port 3

HMI-232

Optional Default Optional

8

9

Terminal 485

√(485+)

√(485-)

√(RXD)

√(TXD)

√(GND) √(GND)

√(TXD)

√(RXD)

EX3G-70H/70KH/100HA all-in-one COM(EX3G-70H can't support WIFI)

PIN#PLC-485-1serial port 2

D 9 portb Default Optional

8

9

√(485+)

Optional and default 232

cannot coexist

PLC-485-2serial port 3

PLC-232serial port 3

Optional and default 232、Optional WIFI cannot coexist

Optional and default 232、Optional 485 cannot exist

WIFI

Optional

PLC-CAN

Optional

COM2(DB9 port near power supply)

HMI-485 HMI-232

Optional

√(485+)

√(485-)

√(485-)

√(RXD)

√(TXD)

√(GND)

√(H)

√(L)

Optional

√(RXD)

√(TXD)

√(GND)

√(485+)

√(485-)

1

6

2

3

5

4

7

1

6

2

3

5

4

7

COM1DB9 port COM1(DB9 port away from power supply) Network

port

Network

port of

HMI and

PLC do not

occupy

serial port

signal,

and can

not coexist.

Chart 4: Pin definition

* Note: Detailed settings, please refer to "Coolmay EX3G Programming Manual".

Figure 7 shows the equivalent circuit diagram of the relay output module. The output terminals are several

groups and each group is electrically isolated. Different groups of output contacts are connected to different

power circuits.

PLC digital inputs wiring:

Ports short circuit: S/S of PLC input terminal is connected to 24V, X terminal is connected to

power supply 0V, i.e., input signal.

Two-wire system (magnetic control switch): The positive pole of the magnetic switch is

connected to PLC X terminal, and the negative pole is connected to 0V.

Three-wire system (photoelectric sensor or encoder): Sensor or encoder power supply is

connected to power supply positive, signal line is connected to X terminal. Encoder

and photoelectric sensor are NPN type (PNP is customized).

PLC digital outputs wiring:

Transistor: Output is NPN, COM is connected to the negative pole, and Y is connected to

the positive pole of the power supply with a load.

Relay: Dry contact output, COM can be connected to the positive or negative.

Data register D

[R0-R22999] 23000 points, support power retentive/ [R23000~R23999] 1000 points, system internal useExtended file register R

Pointer JUMP,CALL branch use [P0-P255] 256 points/ [ - ] points and higher versionP0 P1280 1281 (26232 )

Interruption[I010~I060] 6 points, timer interruption use

FROM demand read: FROM K0 K0 D400 K16 can be read as 16-channel analog inputs.

Note Analog input range and register values please refer to Coolmay EX3G HMI PLC All in One Programming Manual: , " - - ".

TO demand direct outputs: D[8050]~D[8057] correspond to the values of [DA0~DA7].

When select negative outputs, 2 analog outputs will be covered. The configuration is as the

chart below.

(*1)

Max digital points

Any updates will be updated on our website:en.coolmay.com