EN & ENL Series - Infinitier · EN & ENL ENDURANCE VRLA BATTERIES Suitable for all standby...
Transcript of EN & ENL Series - Infinitier · EN & ENL ENDURANCE VRLA BATTERIES Suitable for all standby...
EN & ENL Series valve regulated lead-acid batteries
EN & ENL
EN & ENL ENDURANCE VRLA BATTERIESSuitable for all standby applications including Telecommunications, UPS, Emergency Lighting. Endurance range Batteries from Yuasa are the engineer’s choice for even the most critical standby applications, available in 10 year (EN) and 15 year (ENL) models.
FEATURES• LongLifeinstandby(10and15yeardesignlifeoptions).• Uniquemixandmatchparallelassemblyallows extensive variations to network capacity.• ElectrolyteSuspension.A.G.M.technologyassuresno free electrolyte to spill or worry about.• Highgasrecombinationefficiency.Eliminatestheneed for forced ventilation and separate battery rooms.• CaseMaterialOxygenindex30.• FullycompliantwithBS6290-4andIEC896-2.
Layout
Terminal8mmStudorFemaleInternalThread
2 3 4 ± 2 m m
M 8
208 ± 2mm
2 0 0 ± 2 m m
2 3 6 ± 2 m m
210 ± 2mm
3 0 5 ± 2 m mEN80/EN100ENL100
2 3 6 ± 2 m m
210 ± 2mm
206 ± 2mm
2 3 6 ± 2 m m
210 ± 2mm
3 0 5 ± 2 m m
ICB 1
68
ICB 1
68
EN160-6 / EN180-6Showing 2 x ICB168ENL160
EN160-4/EN320-2
EN480-2 / EN540-2
Internal Type
x y
20mm M8
EN & ENL
General SpecificationsNominal Capacity (Ah)
10hr to 1.85vpc
3hr to 1.80vpc
1 hr to 1.75vpc
Voltage
Energy Density (Wh/L)
Specific Energy (Wh. kg)
IntResistance(m.ohms)
Maximum discharge (A)
ShortCircuitcurrent
Dimensions (mm)
Length
Width
Height overall
Weight (kg)
Terminal
Terminal Torque (Nm)
www.yuasaeurope.com
110
100
90
80
70
60
50
40
30
20
10
00 2 4 6 8 10 12 14 16 18 20 22 24
0
10
20
30
40
50
60
70
80
90
100
CHARGING CHARACTERISTICS
CHARGING TIME (HOURS)
DEP
TH O
F D
ISC
HAR
GE
%
CH
ARG
E VO
LUM
E %
10°C
20°C
30°C
40°C
0 2 4 6 8 10 120
20
40
60
80
100
STORAGE PERIOD (MONTH)
SELF DISCHARGE CHARACTERISTICS
REM
AIN
ING
CAP
ACIT
Y (%
)
0 10 20 30 40 50 601
2
5
10
100
Battery Operating Temperature (ϒC)
Des
ign
Life
(yea
rs)
ENL Series
EN Series
STANDBY FLoAT CHARGE DESIGN LIFE Charging Methods (at 20˚C)Standby use: Float charging voltage 2.26v + 0.005v
CAUTIoN- Avoid short circuit.- Do not charge in a
sealed container.
EN80-6 EN80-4 EN100-6 ENL100-6 EN100-4 EN160-6 EN180-6 ENL160-6 EN160-4 EN320-2 EN480-2 EN540-2
80 80 100 100 100 160 180 160 160 320 480 540
65 65 81 81 81 129 145 129 129 258 387 435
53 53 66 66 66 105 118 105 105 210 315 354
6 4 6 6 4 6 6 6 4 2 2 2
49 33 62 69 41 63 71 63 63 63 63 71
20.8 18 26 26 26 27 30 27 27 27 27 30
1.8 1.2 1.8 1.8 1.2 1.2 1.2 1.2 0.8 0.3 0.2 0.2
480 480 600 600 600 960 960 960 960 1920 2880 2880
800 800 1000 1000 1000 1500 1500 1500 1500 3000 4500 4500
200 200 200 200 200 305 305 305 206 206 206 206
208 208 208 208 208 210 210 210 210 210 210 210
238 238 238 234 238 240 240 236 240 240 240 240
23 17.5 23 23 17.5 35 35 35 24 24 35 35
<8mmMaleStud><FemaleInsert>
6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1 6.1
0.1CA
0.27CA
0.65CA
1CA
1 2 4 6 8 10 20 40 60 80 100 200 400 600
4.5
5.0
5.5
V
6.0
6.5
D I S C H A R G E T I M E ( M i n . )
TE
RM
IN
AL
V
OL
TA
GE
(
Vo
lt
)
4CA
2CA3CA
V
2.16
2
1.83
1.66
1.5
DENOTES FINAL VOLTAGE
0.02C
0.04C
0.06C
0.08C
0.1C
2.0
2.1
2.2
2.3
2.4
20
40
60
80
100
CHARGEDVOLTAGE(V)
CHARGINGCURRENT(A)
CHARGEVOLUME%
CHARGED VOLUME
CHARGING CURRENT
CHARGE VOLTAGE
AFTER 100% DISCHARGEAFTER 50% DISCHARGE
0 4 8 12 16 20 24 28
C H A R G I N G T I M E ( H O U R S )
0.1C Amp (max.) 2.26V/Cell Constant Voltage at 20oC
DISCHARGE CHARACTERISTIC CURVES
CHARGING CHARACTERISTIC
Distributed byYuasa Battery Sales (UK) LtdUnit 13, Hunts Rise, South Marston Park,
Swindon SN3 4TGTel: 01793 833555 Fax: 01793 833579
Email: [email protected]
Registered number 1548820
Cat. No. EVRLASF January 2014E&O.E.