Eff. of Harmonics
-
Upload
swapnil-sawant -
Category
Documents
-
view
225 -
download
0
Transcript of Eff. of Harmonics
-
8/3/2019 Eff. of Harmonics
1/7
Harmonics
The Effect of Harmonics
ORIGINS OF HARMONIC DISTORTION
The ever increasing demand of industry and commercefor stability, adjustability and accuracy of control of
electrical equipment led to the development of relatively
low cost power diodes and thyristors.Now used widely for rectifier circuits for U.P.S. systems,
static converters, and D.C. motor control, these moderndevices replace the Mercury Arc Rectifiers of earlier
years and in consequence create new and challengingconditions for the power engineer of today.
Although solid state devices such as the thyristor havebrought significant improvements in control techniques,
they have the disadvantage that they produce harmonic
currents.
Harmonic currents can cause an unacceptabledisturbance on the supply network and adversely affectthe operation of other electrical equipment including
power factor correction capacitors.
WAVEFORM
All complex waveforms can be resolved into a series of
sinusoidal waves of various frequencies, hence anycomplex waveform is the sum of a number of odd or
even harmonics of lesser or greater value.Thyristor convertors or rectifiers are usually referred to
by the number of DC current pulses they produce eachcycle, the most commonly used being 6 pulse and 12
pulse.
There are many factors that can influence the harmonic
content but typical harmonic currents, shown as a
http://www.alcorn-energy.com/tech1.htmhttp://www.alcorn-energy.com/tech6.htmhttp://www.alcorn-energy.com/tech5.htmhttp://www.alcorn-energy.com/tech3.htmhttp://www.alcorn-energy.com/tech2.htmhttp://www.alcorn-energy.com/techinfo.htm -
8/3/2019 Eff. of Harmonics
2/7
percentage of the fundamental current are given in the
following table. Some content of the harmonics not
listed will always be present to some degree but forpractical reasons they have been ignored.
Order ofHarmonic
Percentage of HarmonicContent
6 Pulse 12 Pulse
1 100 100
5 20 --
7 14 --
11 9 9
13 8 8
17 6 --
19 5 --
23 4 4
25 4 4
HARMONIC OVERLOADING OF CAPACITORS
The impedance of a circuit dictates the current flow in
that circuit.
As the supply impedance is generally considered to be
inductive, the network impedance increases withfrequency while the impedance of a capacitor decreases.
This encourages a greater proportion of the currents
circulating at frequencies above the fundamental supply
frequency to be absorbed by the capacitor, and allequipment associated with the capacitor.
In certain circumstances such currents can exceed the
value of the fundamental (50Hz) capacitor current.These currents in turn cause increased voltage to be
applied across the dielectric of the capacitor. The
harmonic voltage due to each harmonic current added
-
8/3/2019 Eff. of Harmonics
3/7
arithmetically to the fundamental voltage dictates the
voltage stress to be sustained by the capacitor dielectric
and for which the capacitor must be designed.
Capacitors of the correct dielectric voltage stress must
always be used in conditions of harmonic distortion toavoid premature failure.
HARMONIC RESONANCE
As frequency varies, so reactance varies and a point can
be reached when the capacitor reactance and the supply
reactance are equal. This point is known as the circuit orselective resonant frequency.
Whenever power factor correction is applied to adistribution network, bringing together capacitance and
inductance, there will always be a frequency at whichthe capacitors are in parallel resonance with the supply.
If this condition occurs at, or close to, one of theharmonics generated by any solid state control
equipment, then large harmonic currents can circulate
between the supply network and the capacitorequipment, limited only by the damping resistance in
the circuit. Such currents will add to the harmonicvoltage disturbance in the network causing an increased
voltage distortion.
These results in an unacceptably high voltage across the
capacitor dielectric coupled with an excessive current
through all the capacitor ancillary components. Themost common order of harmonics are 5th, 7th, 11th and
13th but resonance can occur at any frequency.
AVOIDING RESONANCE
There are a number of ways to avoid resonance wheninstalling capacitors. On larger systems it may be
possible to re-position the proposed capacitorinstallation onto another part of the system.
The same value of kvar installed at high voltage rather
than at low voltage may eliminate a resonant difficulty,or there may be other low voltage busbars where there
is no harmonic generating load. Varying the outputrating of the capacitor bank will alter the resonant
-
8/3/2019 Eff. of Harmonics
4/7
frequency.
With multi stage capacitor switching there will be a
different resonant frequency for each stage. Changingthe number of switching stages may avoid resonance at
each stage of switching.
OVERCOMING RESONANCE
If resonance cannot be avoided an alternative solution isrequired.
A reactor must be connected in series with eachcapacitor switching section such that the
capacitor/reactor combination is inductive at the
dangerous frequencies but capacitive at fundamentalfrequency. To achieve this capacitor and series
connected reactor must have a tuning frequency belowthe lowest order of harmonic to be experienced, which
is usually the 5th.
This means the tuning frequency is usually in the range
of 175Hz to 230Hz, although the actual frequency will
depend upon the magnitude of the harmonic currentspresent. The actual tuning frequency will be varied to
suit the specific needs of each case.
The inclusion of a reactor in the capacitor circuit
increases the fundamental voltage across the capacitorin the order of 5 to 9% in addition to the harmonic
voltages previously mentioned.
COST EFFECTIVENESS
Due to varying site conditions, it is not always possible
to determine with certainty that resonance will occur.
Adding series reactors to power factor correction
equipment is expensive and can increase the cost touneconomic levels. If later found not to be required,
then unnecessary expenditure is incurred.
An intermediate step is to install appropriate capacitors
with facilities for the addition of reactors if found to benecessary at a later date, thus lowering considerably the
initial capital cost.
When capacitors are used in series with reactors they
-
8/3/2019 Eff. of Harmonics
5/7
are rated at higher than system voltage, so when used
without reactors they have the ability to withstand
higher levels of harmonic overload, which alone mayresolve the situation.
If resonance does actually occur reactors can be addedto the existing power factor correction equipment at
minimum extra cost
LIMITS OF HARMONIC DISTORTION
Harmonic distortion can cause severe disturbance to
certain electrical equipment and as it is the duty of theelectric utility to provide a clean supply, many
countries now set limits to the harmonic distortionallowed on the distribution networks.
In the U.K. the Electricity Council EngineeringRecommendation G5/3 provides for three levels of
acceptance for the connection of harmonic generating
equipment, defined as stages.
STAGE 1 permits the connection of individual loads up to
14kVA at 415 volt and 25OkVA at 11 kV without special
consideration.
STAGE 2 limits the total harmonic current which anyinstallation may produce at the point of connection with
the supply authority, as follows:
HARMONI
C2 4 5 7 11 13
415V 48A 22 56 40 19 16A
6.6 - 11kV 13A 6 10 8 7 6A
STAGE 3. Individual analysis of systems is required to
ensure total harmonic distortion does not exceed 5% at415 volts and 4% at 11 kV
Before accepting harmonic generating loads, the
existing harmonic voltage distortion on the supplynetwork is taken into consideration in setting the
individual limits of Stage 3, and may also restrict themaximum limits as tabulated for Stage 2.
-
8/3/2019 Eff. of Harmonics
6/7
Where these limits are exceeded, it may be necessary
to reduce or eliminate the harmonics produced.
REDUCTION OF HARMONIC DISTORTION
Harmonic currents can never be totally eliminated froman electrical system. They can, however, be verysignificantly reduced by using a harmonic filter.
In its basic form a filter comprises a capacitor connectedin series with a reactor tuned to the frequency to be
eliminated. In theory the impedance of the filter is zero
at the tuning frequency and therefore all of theparticular harmonic current is absorbed by the filter.
In practice, however, the capacitor and reactor areusually tuned slightly below the harmonic frequency.
This together with the natural resistance of the circuitmeans that only a small acceptable level of harmonic
current will flow in the network.
When it is necessary to reduce more than one harmonic,
a multi arm filter may be required.
TYPES OF FILTER
The effectiveness of any filter scheme depends on the
net reactive output of the filter, filter tuning accuracy
and the impedance of the network at the point ofconnection.
Harmonics below the filter tuning frequency will be
amplified. The experience of the filter designer istherefore important to ensure that insignificant
distortion is not amplified to unacceptable levels.
Where there are several harmonics present, a single
arm filter may reduce some harmonics whilst increasing
others, e.g. a filter for 11th harmonic may createresonance in the vicinity of 7th harmonic and high
magnification of any 5th harmonic already on thenetwork
In these cases it may be necessary to use a multi-armfilter where each arm is tuned to a different frequency
Experience is paramount in the design of such filters to
ensure:
-
8/3/2019 Eff. of Harmonics
7/7
the most efficient and cost-effective solution is chosen
there is no adverse interaction either between the system
and the filter or between branches within the filter.
LOAD ALTERATION
Whenever load expansion is considered, with or without
additional power factor correction equipment, thenetwork impedance is likely to change and existing filter
equipment must be re-appraised in conjunction with thenew load condition and be suitably up rated.
It is not recommended to have two or more filters finetuned to the same frequency connected on the same
busbar system. Slight tuning differences may cause one
filter to take a much larger share of the harmonicdistortion, or even cause a harmonic resonance
condition leading to amplification of the very harmonicorder for which the equipment has been designed to
reduce.
When there is a need to vary the power factor
correction component of a harmonic filter, careful
consideration of all parameters is necessary.
HARMONIC ANALYSIS
To determine capacitor and filter requirements to meetspecific harmonic conditions, it is necessary to establish
with accuracy the impedance of the supply network andthe value of each harmonic current experienced at the
point of intended connection of any filter or power factor
correction capacitor.
[ Back ] [ Reactive Power ] [ PF Correction ] [Capacitors ] [ Harmonics ][ PCB Disposal ] [PCB Dangers ]
For further details contact
[email protected]: +44 (0)28 44 821197 Mobile: +44 (0)7860 638065
Fax: +44 (0)28 44 821360Copyright 2000 Philip J. Alcorn & Co.
While every care is taken to ensure that the information contained in this publication is correct, no legal responsibility canbe accepted for any inaccuracy. The Company reserves the right to alter or modify the information contained herein at any
time in the light of technical or other developments.
http://www.alcorn-energy.com/techinfo.htmhttp://www.alcorn-energy.com/tech1.htmhttp://www.alcorn-energy.com/tech2.htmhttp://www.alcorn-energy.com/tech3.htmhttp://www.alcorn-energy.com/tech3.htmhttp://www.alcorn-energy.com/tech5.htmhttp://www.alcorn-energy.com/tech5.htmhttp://www.alcorn-energy.com/tech6.htmhttp://www.alcorn-energy.com/tech6.htmmailto:[email protected]://www.alcorn-energy.com/tech1.htmhttp://www.alcorn-energy.com/tech2.htmhttp://www.alcorn-energy.com/tech3.htmhttp://www.alcorn-energy.com/tech5.htmhttp://www.alcorn-energy.com/tech6.htmmailto:[email protected]://www.alcorn-energy.com/techinfo.htm