Eff. of Harmonics

download Eff. of Harmonics

of 7

Transcript of Eff. of Harmonics

  • 8/3/2019 Eff. of Harmonics

    1/7

    Harmonics

    The Effect of Harmonics

    ORIGINS OF HARMONIC DISTORTION

    The ever increasing demand of industry and commercefor stability, adjustability and accuracy of control of

    electrical equipment led to the development of relatively

    low cost power diodes and thyristors.Now used widely for rectifier circuits for U.P.S. systems,

    static converters, and D.C. motor control, these moderndevices replace the Mercury Arc Rectifiers of earlier

    years and in consequence create new and challengingconditions for the power engineer of today.

    Although solid state devices such as the thyristor havebrought significant improvements in control techniques,

    they have the disadvantage that they produce harmonic

    currents.

    Harmonic currents can cause an unacceptabledisturbance on the supply network and adversely affectthe operation of other electrical equipment including

    power factor correction capacitors.

    WAVEFORM

    All complex waveforms can be resolved into a series of

    sinusoidal waves of various frequencies, hence anycomplex waveform is the sum of a number of odd or

    even harmonics of lesser or greater value.Thyristor convertors or rectifiers are usually referred to

    by the number of DC current pulses they produce eachcycle, the most commonly used being 6 pulse and 12

    pulse.

    There are many factors that can influence the harmonic

    content but typical harmonic currents, shown as a

    http://www.alcorn-energy.com/tech1.htmhttp://www.alcorn-energy.com/tech6.htmhttp://www.alcorn-energy.com/tech5.htmhttp://www.alcorn-energy.com/tech3.htmhttp://www.alcorn-energy.com/tech2.htmhttp://www.alcorn-energy.com/techinfo.htm
  • 8/3/2019 Eff. of Harmonics

    2/7

    percentage of the fundamental current are given in the

    following table. Some content of the harmonics not

    listed will always be present to some degree but forpractical reasons they have been ignored.

    Order ofHarmonic

    Percentage of HarmonicContent

    6 Pulse 12 Pulse

    1 100 100

    5 20 --

    7 14 --

    11 9 9

    13 8 8

    17 6 --

    19 5 --

    23 4 4

    25 4 4

    HARMONIC OVERLOADING OF CAPACITORS

    The impedance of a circuit dictates the current flow in

    that circuit.

    As the supply impedance is generally considered to be

    inductive, the network impedance increases withfrequency while the impedance of a capacitor decreases.

    This encourages a greater proportion of the currents

    circulating at frequencies above the fundamental supply

    frequency to be absorbed by the capacitor, and allequipment associated with the capacitor.

    In certain circumstances such currents can exceed the

    value of the fundamental (50Hz) capacitor current.These currents in turn cause increased voltage to be

    applied across the dielectric of the capacitor. The

    harmonic voltage due to each harmonic current added

  • 8/3/2019 Eff. of Harmonics

    3/7

    arithmetically to the fundamental voltage dictates the

    voltage stress to be sustained by the capacitor dielectric

    and for which the capacitor must be designed.

    Capacitors of the correct dielectric voltage stress must

    always be used in conditions of harmonic distortion toavoid premature failure.

    HARMONIC RESONANCE

    As frequency varies, so reactance varies and a point can

    be reached when the capacitor reactance and the supply

    reactance are equal. This point is known as the circuit orselective resonant frequency.

    Whenever power factor correction is applied to adistribution network, bringing together capacitance and

    inductance, there will always be a frequency at whichthe capacitors are in parallel resonance with the supply.

    If this condition occurs at, or close to, one of theharmonics generated by any solid state control

    equipment, then large harmonic currents can circulate

    between the supply network and the capacitorequipment, limited only by the damping resistance in

    the circuit. Such currents will add to the harmonicvoltage disturbance in the network causing an increased

    voltage distortion.

    These results in an unacceptably high voltage across the

    capacitor dielectric coupled with an excessive current

    through all the capacitor ancillary components. Themost common order of harmonics are 5th, 7th, 11th and

    13th but resonance can occur at any frequency.

    AVOIDING RESONANCE

    There are a number of ways to avoid resonance wheninstalling capacitors. On larger systems it may be

    possible to re-position the proposed capacitorinstallation onto another part of the system.

    The same value of kvar installed at high voltage rather

    than at low voltage may eliminate a resonant difficulty,or there may be other low voltage busbars where there

    is no harmonic generating load. Varying the outputrating of the capacitor bank will alter the resonant

  • 8/3/2019 Eff. of Harmonics

    4/7

    frequency.

    With multi stage capacitor switching there will be a

    different resonant frequency for each stage. Changingthe number of switching stages may avoid resonance at

    each stage of switching.

    OVERCOMING RESONANCE

    If resonance cannot be avoided an alternative solution isrequired.

    A reactor must be connected in series with eachcapacitor switching section such that the

    capacitor/reactor combination is inductive at the

    dangerous frequencies but capacitive at fundamentalfrequency. To achieve this capacitor and series

    connected reactor must have a tuning frequency belowthe lowest order of harmonic to be experienced, which

    is usually the 5th.

    This means the tuning frequency is usually in the range

    of 175Hz to 230Hz, although the actual frequency will

    depend upon the magnitude of the harmonic currentspresent. The actual tuning frequency will be varied to

    suit the specific needs of each case.

    The inclusion of a reactor in the capacitor circuit

    increases the fundamental voltage across the capacitorin the order of 5 to 9% in addition to the harmonic

    voltages previously mentioned.

    COST EFFECTIVENESS

    Due to varying site conditions, it is not always possible

    to determine with certainty that resonance will occur.

    Adding series reactors to power factor correction

    equipment is expensive and can increase the cost touneconomic levels. If later found not to be required,

    then unnecessary expenditure is incurred.

    An intermediate step is to install appropriate capacitors

    with facilities for the addition of reactors if found to benecessary at a later date, thus lowering considerably the

    initial capital cost.

    When capacitors are used in series with reactors they

  • 8/3/2019 Eff. of Harmonics

    5/7

    are rated at higher than system voltage, so when used

    without reactors they have the ability to withstand

    higher levels of harmonic overload, which alone mayresolve the situation.

    If resonance does actually occur reactors can be addedto the existing power factor correction equipment at

    minimum extra cost

    LIMITS OF HARMONIC DISTORTION

    Harmonic distortion can cause severe disturbance to

    certain electrical equipment and as it is the duty of theelectric utility to provide a clean supply, many

    countries now set limits to the harmonic distortionallowed on the distribution networks.

    In the U.K. the Electricity Council EngineeringRecommendation G5/3 provides for three levels of

    acceptance for the connection of harmonic generating

    equipment, defined as stages.

    STAGE 1 permits the connection of individual loads up to

    14kVA at 415 volt and 25OkVA at 11 kV without special

    consideration.

    STAGE 2 limits the total harmonic current which anyinstallation may produce at the point of connection with

    the supply authority, as follows:

    HARMONI

    C2 4 5 7 11 13

    415V 48A 22 56 40 19 16A

    6.6 - 11kV 13A 6 10 8 7 6A

    STAGE 3. Individual analysis of systems is required to

    ensure total harmonic distortion does not exceed 5% at415 volts and 4% at 11 kV

    Before accepting harmonic generating loads, the

    existing harmonic voltage distortion on the supplynetwork is taken into consideration in setting the

    individual limits of Stage 3, and may also restrict themaximum limits as tabulated for Stage 2.

  • 8/3/2019 Eff. of Harmonics

    6/7

    Where these limits are exceeded, it may be necessary

    to reduce or eliminate the harmonics produced.

    REDUCTION OF HARMONIC DISTORTION

    Harmonic currents can never be totally eliminated froman electrical system. They can, however, be verysignificantly reduced by using a harmonic filter.

    In its basic form a filter comprises a capacitor connectedin series with a reactor tuned to the frequency to be

    eliminated. In theory the impedance of the filter is zero

    at the tuning frequency and therefore all of theparticular harmonic current is absorbed by the filter.

    In practice, however, the capacitor and reactor areusually tuned slightly below the harmonic frequency.

    This together with the natural resistance of the circuitmeans that only a small acceptable level of harmonic

    current will flow in the network.

    When it is necessary to reduce more than one harmonic,

    a multi arm filter may be required.

    TYPES OF FILTER

    The effectiveness of any filter scheme depends on the

    net reactive output of the filter, filter tuning accuracy

    and the impedance of the network at the point ofconnection.

    Harmonics below the filter tuning frequency will be

    amplified. The experience of the filter designer istherefore important to ensure that insignificant

    distortion is not amplified to unacceptable levels.

    Where there are several harmonics present, a single

    arm filter may reduce some harmonics whilst increasing

    others, e.g. a filter for 11th harmonic may createresonance in the vicinity of 7th harmonic and high

    magnification of any 5th harmonic already on thenetwork

    In these cases it may be necessary to use a multi-armfilter where each arm is tuned to a different frequency

    Experience is paramount in the design of such filters to

    ensure:

  • 8/3/2019 Eff. of Harmonics

    7/7

    the most efficient and cost-effective solution is chosen

    there is no adverse interaction either between the system

    and the filter or between branches within the filter.

    LOAD ALTERATION

    Whenever load expansion is considered, with or without

    additional power factor correction equipment, thenetwork impedance is likely to change and existing filter

    equipment must be re-appraised in conjunction with thenew load condition and be suitably up rated.

    It is not recommended to have two or more filters finetuned to the same frequency connected on the same

    busbar system. Slight tuning differences may cause one

    filter to take a much larger share of the harmonicdistortion, or even cause a harmonic resonance

    condition leading to amplification of the very harmonicorder for which the equipment has been designed to

    reduce.

    When there is a need to vary the power factor

    correction component of a harmonic filter, careful

    consideration of all parameters is necessary.

    HARMONIC ANALYSIS

    To determine capacitor and filter requirements to meetspecific harmonic conditions, it is necessary to establish

    with accuracy the impedance of the supply network andthe value of each harmonic current experienced at the

    point of intended connection of any filter or power factor

    correction capacitor.

    [ Back ] [ Reactive Power ] [ PF Correction ] [Capacitors ] [ Harmonics ][ PCB Disposal ] [PCB Dangers ]

    For further details contact

    [email protected]: +44 (0)28 44 821197 Mobile: +44 (0)7860 638065

    Fax: +44 (0)28 44 821360Copyright 2000 Philip J. Alcorn & Co.

    While every care is taken to ensure that the information contained in this publication is correct, no legal responsibility canbe accepted for any inaccuracy. The Company reserves the right to alter or modify the information contained herein at any

    time in the light of technical or other developments.

    http://www.alcorn-energy.com/techinfo.htmhttp://www.alcorn-energy.com/tech1.htmhttp://www.alcorn-energy.com/tech2.htmhttp://www.alcorn-energy.com/tech3.htmhttp://www.alcorn-energy.com/tech3.htmhttp://www.alcorn-energy.com/tech5.htmhttp://www.alcorn-energy.com/tech5.htmhttp://www.alcorn-energy.com/tech6.htmhttp://www.alcorn-energy.com/tech6.htmmailto:[email protected]://www.alcorn-energy.com/tech1.htmhttp://www.alcorn-energy.com/tech2.htmhttp://www.alcorn-energy.com/tech3.htmhttp://www.alcorn-energy.com/tech5.htmhttp://www.alcorn-energy.com/tech6.htmmailto:[email protected]://www.alcorn-energy.com/techinfo.htm