DHE – Detector Head Electronics

9
2006 Oct. 19 DES Project -- Vaidas Simaitis, University of Illinois 1 DHE – Detector Head Electronics Monsoon 80mm Crate Air Flow

description

DHE – Detector Head Electronics. Monsoon 80mm Crate Air Flow. Crate Parts. 60mm FAN (x2) on MAIN PLENUM (at both ends, only this end shown here). HEAT EXCHANGERS connect in series with ¼” copper tube. FAN power supply is in the middle (at both ends). - PowerPoint PPT Presentation

Transcript of DHE – Detector Head Electronics

Page 1: DHE – Detector Head Electronics

2006 Oct. 19 DES Project -- Vaidas Simaitis, University of Illinois 1

DHE – Detector Head Electronics

Monsoon 80mm

Crate Air Flow

Page 2: DHE – Detector Head Electronics

2006 Oct. 19 DES Project -- Vaidas Simaitis, University of Illinois 2

Crate Parts

HEAT EXCHANGER on CHILLER PLENUM (one at each end of main MONSOON cards)

92mm FAN (x2) on FAN PLENUM (one at each end of transition cards)

TRANSITION CARDS (8) (6U x 80mm)

MONSOON CARDS (10) plug in on this side (6U x 160mm Eurocards)

60mm FAN (x2) on MAIN PLENUM (at both ends, only this end shown here)

FAN power supply is in the middle (at both ends)

HEAT EXCHANGERS connect in series with ¼” copper tube

Page 3: DHE – Detector Head Electronics

2006 Oct. 19 DES Project -- Vaidas Simaitis, University of Illinois 3

Crate (without shield)

VICOR power supply with built-in 80mm fan, 30cfm listed, pressure drop unknown (x2)

MAIN PLENUM

POWER SUPPLY PLENUM

Page 4: DHE – Detector Head Electronics

2006 Oct. 19 DES Project -- Vaidas Simaitis, University of Illinois 4

Air Flow Diagram

MONSOON TRANSITION CARDS

MONSOON MAIN MODULES

COLD WATER HEAT EXCH

COLD WATER HEAT EXCH

FAN 92 mm

FAN 92 mm

FAN 92 mm

FAN 92 mm

VICOR PS

VICOR PS

120 CFM120 CFM

60 CFM

60 CFM

30 CFM

30

30

FAN 60 mm

FAN 60 mm

FAN PS FAN PS FAN 60 mm

FAN 60 mm

80 mm built in

80 mm built in

120 CFM

CO

LD

PL

EN

UM

FA

N P

LE

NU

M

FA

N P

LE

NU

M

CO

LD

PL

EN

UM

3030

30 CFM

30 CFM

30 CFM

3030

30

30

120 CFM

MAIN PLENUM 1

MAIN PLENUM 2

PWR SUPPLY PLENUM

Page 5: DHE – Detector Head Electronics

2006 Oct. 19 DES Project -- Vaidas Simaitis, University of Illinois 5

Heat Exchanger Air Side Pressure Drop

For the target of 120 CFM air flow, the pressure drop is about 0.36 inches of water

The design uses a Lytron M05-050 heat exchanger

Page 6: DHE – Detector Head Electronics

2006 Oct. 19 DES Project -- Vaidas Simaitis, University of Illinois 6

Air Pressure Diagram

MONSOON TRANSITION CARDS

~ -0.04”

MONSOON MAIN MODULES

~ -0.04”

COLD WATER HEAT EXCH

-0.36”

COLD WATER HEAT EXCH

-0.36”

FAN +0.40”

FAN +0.40”

FAN +0.40”

FAN +0.40”

VICOR PS

VICOR PS

120 CFM120 CFM

60 CFM

60 CFM

30 CFM

30

30

FAN +0.38”

FAN +0.38”

FAN PS FAN PS FAN +0.38”

FAN +0.38”

80 mm built in

80 mm built in

120 CFM

CO

LD

PL

EN

UM

FA

N P

LE

NU

M

FA

N P

LE

NU

M

CO

LD

PL

EN

UM

3030

30 CFM

30 CFM

30 CFM

3030

30

30

120 CFM

MAIN PLENUM 1

MAIN PLENUM 2

PWR SUPPLY PLENUM

+0.02” -0.02”

-0.38” H2O

+0.38” H2O

-0.00” H2O ?

+0.02”-0.02”

PRESSURE DROP PRESUMED = 0

Page 7: DHE – Detector Head Electronics

2006 Oct. 19 DES Project -- Vaidas Simaitis, University of Illinois 7

92 mm FAN Requirements

92mm FANS must do 0.40” H2O @ 30 CFM

FFB0924SHE should work

If necessary, FFB0924EHE works up to 0.48”

Page 8: DHE – Detector Head Electronics

2006 Oct. 19 DES Project -- Vaidas Simaitis, University of Illinois 8

60 mm FANS must do 0.38” H2O @ 30 CFM

FFB0624SHE should work

If necessary, FFB0624EHE ok to 0.48”

60 mm FAN Requirements

Page 9: DHE – Detector Head Electronics

2006 Oct. 19 DES Project -- Vaidas Simaitis, University of Illinois 9

92 & 60 mm DELTA fans available

92 mm

60 mm