DATE: April 29, 2014 SUBJECT: NFPA 92 Second Draft TC ...€¦ · change from the ASHRAE Handbook...
Transcript of DATE: April 29, 2014 SUBJECT: NFPA 92 Second Draft TC ...€¦ · change from the ASHRAE Handbook...
National Fire Protection Association
1 Batterymarch Park, Quincy, MA 02169-7471
Phone: 617-770-3000 • Fax: 617-770-0700 • www.nfpa.org
TO: Technical Committee on Smoke Management Systems
FROM: Tracy Vecchiarelli, Staff Liaison
DATE: April 29, 2014
SUBJECT: NFPA 92 Second Draft TC Ballot Circulation (F2014)
____________________________________________________________________________
The April 28, 2014 date for receipt of the NFPA 92 Second Draft Ballot has passed.
The preliminary Second Draft Ballot Results are as follows:
30 Members Eligible to Vote
4 Ballots Not Returned (M. Dillon, D. Evans, A. Militello and R. Sampson)
In accordance with the NFPA Regulations Governing the Development of NFPA Standards,
attached are reasons for negative votes for review so you may change your ballot if you wish.
Abstentions and affirmative comments are also included. Ballots received from alternate
members are not included unless the ballot from the principal member was not received.
If you wish to change your vote, the change must be received at NFPA on or before Tuesday,
May 6, 2014. Members who have not returned a ballot may do so now. Ballots or changes may
be made by going to the following: NFPA Ballot link
The return of ballots is required by the Regulations Governing the Development of NFPA
Standards.
Eligible to Vote: 30
Not Returned : 4
Michael Earl Dillon,Douglas H. Evans,Anthony J.
Militello,Robert C. Sampson
Vote Selection Votes Comments
Affirmative 25
Affirmative with Comment 1
Michael J. Ferreira Accepted.
Negative 0
Abstain 0
Eligible to Vote: 30
Not Returned : 4
Michael Earl Dillon,Douglas H. Evans,Anthony J.
Militello,Robert C. Sampson
Vote Selection Votes Comments
Affirmative 23
Affirmative with Comment 1
Michael J. Ferreira Accepted.
Negative 2
NFPA 92 SECOND DRAFT BALLOT CIRCULATION
SR-1, Section No. 3.3.4, See SR-1
Total Voted : 26
SR-7, New Section after 3.3.9.2, See SR-7
Page 1 of 14
John E. Kampmeyer, Sr. This conflictts with registration laws and the IBC which defiones Registered Design
Professional as follows: REGISTERED DESIGN PROFESSIONAL. An individual who is
registered or licensed to practice their respective design profession as defined by the
statutory requirements of the professional registration laws of the state or
jurisdiction in which the project is to be constructed
Elyahu Avidor The definition is for a Registered Design Professional which is a specific requirement
as opposed to the broader definition of being qualified or having credentials.
Requiring a professional registration entails a state level accreditation. Allowing the
local jurisdiction to decide on the acceptability of qualification and/or credentials
might affect the uniformity and reduce the level of professionalism of design across
the state.
Abstain 0
Eligible to Vote: 30
Not Returned : 4
Michael Earl Dillon,Douglas H. Evans,Anthony J.
Militello,Robert C. Sampson
Vote Selection Votes Comments
Affirmative 25
Affirmative with Comment 1
Michael J. Ferreira Accepted.
Negative 0
Abstain 0
SR-2, Section No. 3.3.11 [Excluding any Sub-Sections], See SR-2
Total Voted : 26
Total Voted : 26
Page 2 of 14
Eligible to Vote: 30
Not Returned : 4
Michael Earl Dillon,Douglas H. Evans,Anthony J.
Militello,Robert C. Sampson
Vote Selection Votes Comments
Affirmative 25
Affirmative with Comment 1
Michael J. Ferreira Accepted.
Negative 0
Abstain 0
Eligible to Vote: 30
Not Returned : 4
Michael Earl Dillon,Douglas H. Evans,Anthony J.
Militello,Robert C. Sampson
Vote Selection Votes Comments
Affirmative 25
Affirmative with Comment 1
Michael J. Ferreira Accepted.
Negative 0
Abstain 0
SR-21, Section No. 4.2.1 [Excluding any Sub-Sections], See SR-21
Total Voted : 26
SR-3, Section No. 4.3.1, See SR-3
Total Voted : 26
Page 3 of 14
Eligible to Vote: 30
Not Returned : 4
Michael Earl Dillon,Douglas H. Evans,Anthony J.
Militello,Robert C. Sampson
Vote Selection Votes Comments
Affirmative 25
Affirmative with Comment 1
Michael J. Ferreira Accepted.
Negative 0
Abstain 0
Eligible to Vote: 30
Not Returned : 4
Michael Earl Dillon,Douglas H. Evans,Anthony J.
Militello,Robert C. Sampson
Vote Selection Votes Comments
Affirmative 24
Affirmative with Comment 2
Kevin L. Derr It should be noted that manual reset can be accommplished via manual resetting of
the smoke control panel. It is not the intent of the requirement to physically be at the
deployable barrier.
Michael J. Ferreira Accepted.
Negative 0
Abstain 0
SR-8, Section No. 4.4.2.2, See SR-8
Total Voted : 26
SR-19, New Section after 5.5.2.5, See SR-19
Total Voted : 26
Page 4 of 14
Eligible to Vote: 30
Not Returned : 4
Michael Earl Dillon,Douglas H. Evans,Anthony J.
Militello,Robert C. Sampson
Vote Selection Votes Comments
Affirmative 23
Affirmative with Comment 0
Negative 3
Michael J. Ferreira The 2012 edition of NFPA 92 required verification of dedicated smoke control
equipment through use of the weekly self-test function that is a mandatory capability
of every UUKL-listed smoke control panel. FR-10-NFPA 92-2013 attempted to
acknowledge that there may be situations where strict compliance with the UUKL
weekly self test is not practical and other means of verification may be necessary. It
did so by deleting all requirements regarding the frequency or capabilities to be
verified. As such, it will result in widely disparate verification methods whose
effectiveness depends on the experience level of the engineer and the AHJ, rather
than relying on a consistent method that is tested as part of a 3rd-party product
listing. NFPA 92 should define what must be done in lieu of the weekly self test to
provide an acceptable level of verification. It would be much better for NFPA 92 to
revert to the 2012 version of paragraph 6.4.8.6 and then develop a more complete
description of acceptable alternatives for the next edition of NFPA 92, than to move
forward with relaxed requirements in the 2015 edition that provide no guidance or
enforcement criteria.
SR-5, Section No. 6.4.8.6, See SR-5
Page 5 of 14
Paul G. Turnbull The 2012 edition of NFPA 92 required verification of dedicated smoke control equipment
through use of the weekly self-test function that is a mandatory capability of every UUKL-listed
smoke control panel. FR-10-NFPA 92-2013 attempted to acknowledge that there may be
situations where strict compliance with the UUKL weekly self test is not practical and other
means of verification may be necessary, but it did so by deleting all requirements regarding the
frequency or capabilities to be verified. Public Comment 8-NFPA 92-2013 attempts to close this
gap by placing responsibility for specifying the frequency and capabilities to be tested on the
engineer of record and the AHJ. While this addition is better than no statement at all, it will
result in widely disparate verification methods whose effectiveness depends on the experience
level of the engineer and the AHJ, rather than relying on a consistent method that is tested by
a 3rd-party as part of the product listing. I realize there are times when an alternate method of
verification may be a better fit for the space being protected than the automatic weekly self
test, but as a standard responsible for life safety of the building occupants, NFPA 92 should
define what must be done in lieu of the weekly self test to provide an acceptable level of
verification. Committee members should note that the ICC recently voted to include specific
additional verification methods in the 2015 edition of the IFC and IBC as an alternate to the
weekly self test requirement. I think it would be much better for NFPA 92 to revert to the 2012
version of paragraph 6.4.8.6 and then develop a more complete description of acceptable
alternatives for the next edition of NFPA 92, than to move forward with relaxed requirements
in the 2015 edition that provide no guidance or enforcement criteria.
Page 6 of 14
Lawrence J. Shudak The 2012 edition of NFPA 92 required verification of dedicated smoke control
equipment through use of the weekly self-test function that is a mandatory capability
of every UUKL-listed smoke control panel. FR-10-NFPA 92-2013 attempted to
acknowledge that there may be situations where strict compliance with the UUKL
weekly self test is not practical and other means of verification may be necessary, but
it did so by deleting all requirements regarding the frequency or capabilities to be
verified. Public Comment 8-NFPA 92-2013 attempts to close this gap by placing
responsibility for specifying the frequency and capabilities to be tested on the
engineer of record and the AHJ. While this addition is better than no statement at all,
it will result in widely disparate verification methods whose effectiveness depends on
the experience level of the engineer and the AHJ, rather than relying on a consistent
method that is tested as part of a 3rd-party product listing. I realize there are times
when an alternate method of verification may be a better fit for the space being
protected than the automatic weekly self test, but as a standard responsible for life
safety of the building occupants, NFPA 92 should define what must be done in lieu of
the weekly self test to provide an acceptable level of verification. Committee
members should note that the ICC recently voted to include specific additional
verification methods in the 2015 edition of the IFC and IBC as an alternate to the
weekly self test requirement. I think it would be much better for NFPA 92 to revert to
the 2012 version of paragraph 6.4.8.6 and then develop a more complete description
of acceptable alternatives for the next edition of NFPA 92, than to move forward with
relaxed requirements in the 2015 edition that provide no guidance or enforcement
criteria.
Abstain 0
Total Voted : 26
Page 7 of 14
Eligible to Vote: 30
Not Returned : 4
Michael Earl Dillon,Douglas H. Evans,Anthony J.
Militello,Robert C. Sampson
Vote Selection Votes Comments
Affirmative 25
Affirmative with Comment 1
Michael J. Ferreira Accepted.
Negative 0
Abstain 0
Eligible to Vote: 30
Not Returned : 4
Michael Earl Dillon,Douglas H. Evans,Anthony J.
Militello,Robert C. Sampson
Vote Selection Votes Comments
Affirmative 24
Affirmative with Comment 2
Michael J. Ferreira Accepted.
SR-14, Section No. 8.6.1 [Excluding any Sub-Sections], See SR-14
Total Voted : 26
SR-10, Section No. A.4.4.1, See SR-10
Page 8 of 14
Paul G. Turnbull Information about which weather data should be used was removed as part of the
change from the ASHRAE Handbook to the Handbook of Smoke Control Engineering
because the Handbook of Smoke Control Engineering only contains one set of
weather data. Since A.4.4.1 says that newer or more site-specific sources for weather
data should be used if it is available, I feel that the previous text suggesting use of
99.6% heating dry bulb and 0.4% cooling dry bulb temperatures, and 1% extreme
wind velocity values, should be retained as guidance when these other sources of
weather data are used.
Negative 0
Abstain 0
Eligible to Vote: 30
Not Returned : 4
Michael Earl Dillon,Douglas H. Evans,Anthony J.
Militello,Robert C. Sampson
Vote Selection Votes Comments
Affirmative 24
Affirmative with Comment 2
SR-13, Section No. A.4.5.1.1, See SR-13
Total Voted : 26
Page 9 of 14
John E. Kampmeyer, Sr. The use of tenanbilityt must be approached with extreme caution. The following are some quotes on the issue:
Extracted from the Fire Protection Engineering Handbook - Fourth Edition The margin of safety designated as
acceptable for a design, therefore, needs to be determined by the designer and regulatory authority in the context of
any particular application. The different sections in this chapter describe the effects of exposure to different fire
hazards and calculation methods that may assist with decisions on acceptable design limits. Information is also
presented on lethal and post exposure health effects, which may also be relevant to these considerations, as well as to
probabilistic fire safety engineering design and forensic fire incident investigation. Additionally, the following
precautions are provided in the International Fire Code Commentary: Extracted from the IFC Commentary Also, Section
909.8.1 specifies a minimum distance for the smoke layer interface from any walking surface whereas Section 4.5.3 of
NFPA 92B has provisions that simply allows the analysis to demonstrate tenability regardless of where the layer height
is located above the floor. Defining tenability can be more difficult as there is not a standard definition as to what is
considered tenable. Any design using that approach would need to be addressed through Section 104.9. 104.9
Alternative materials and methods. The provisions of this code are not intended to prevent the installation of any
material or to prohibit any method of construction not specifically prescribed by this code, provided that any such
alternative has been approved. The fire code official is authorized to approve an alternative material or method of
construction where the fire code official finds that the proposed design is satisfactory and complies with the intent of
the provisions of this code, and that the material, method or work offered is, for the purpose intended, at least the
equivalent of that prescribed in this code in quality, strength, effectiveness, fire resistance, durability and safety. The
Handbook of Fire Protection Engineering also contains the following admonitions: Asthmatics and sufferers of other
lung conditions, such as chronic bronchitis and reactive airways dysfunction syndrome, are particularly susceptible to
bronchoconstriction on even brief exposure to very low concentrations of irritants, with distress, severely reduced
aerobic work capacity, collapse, and death resulting, depending on the sensitivity of the individual and the severity of
the exposure. It is the objective of fire safety engineering to ensure that essentially all occupants, including sensitive
subpopulations, should be able to escape safely without experiencing or developing serious health effects. Thus, safe
levels for exposure of the human population to fire effluent toxicants must be significantly lower than those
determined from experiments with uniformly healthy animal or even human surrogates.
Michael J. Ferreira Accepted.
Negative 0
Abstain 0
Total Voted : 26
Page 10 of 14
Eligible to Vote: 30
Not Returned : 4
Michael Earl Dillon,Douglas H. Evans,Anthony J.
Militello,Robert C. Sampson
Vote Selection Votes Comments
Affirmative 25
Affirmative with Comment 1
Michael J. Ferreira Accepted.
Negative 0
Abstain 0
Eligible to Vote: 30
Not Returned : 4
Michael Earl Dillon,Douglas H. Evans,Anthony J.
Militello,Robert C. Sampson
Vote Selection Votes Comments
Affirmative 24
Affirmative with Comment 2
Paul David Compton The ISO standard is no longer a DIS. The reference should simply be ISO 21927-1.
Michael J. Ferreira Accepted.
Negative 0
Abstain 0
SR-20, New Section after A.5.5.1.1, See SR-20
Total Voted : 26
SR-11, Section No. A.5.5.2.4, See SR-11
Total Voted : 26
Page 11 of 14
Eligible to Vote: 30
Not Returned : 4
Michael Earl Dillon,Douglas H. Evans,Anthony J.
Militello,Robert C. Sampson
Vote Selection Votes Comments
Affirmative 25
Affirmative with Comment 1
Michael J. Ferreira Accepted.
Negative 0
Abstain 0
Eligible to Vote: 30
Not Returned : 4
Michael Earl Dillon,Douglas H. Evans,Anthony J.
Militello,Robert C. Sampson
Vote Selection Votes Comments
Affirmative 25
Affirmative with Comment 1
Michael J. Ferreira Accepted.
Negative 0
Abstain 0
SR-9, Section No. A.6.4.8, See SR-9
Total Voted : 26
SR-22, Section No. A.6.4.4.2.2, See SR-22
Total Voted : 26
Page 12 of 14
Eligible to Vote: 30
Not Returned : 4
Michael Earl Dillon,Douglas H. Evans,Anthony J.
Militello,Robert C. Sampson
Vote Selection Votes Comments
Affirmative 25
Affirmative with Comment 1
Michael J. Ferreira Accepted.
Negative 0
Abstain 0
Eligible to Vote: 30
Not Returned : 4
Michael Earl Dillon,Douglas H. Evans,Anthony J.
Militello,Robert C. Sampson
Vote Selection Votes Comments
Affirmative 25
Affirmative with Comment 1
Michael J. Ferreira Accepted.
Negative 0
Abstain 0
SR-12, Section No. M.1.2.7, See SR-12
Total Voted : 26
SR-15, Section No. M.1.2.8, See SR-15
Total Voted : 26
Page 13 of 14
Eligible to Vote: 30
Not Returned : 4
Michael Earl Dillon,Douglas H. Evans,Anthony J.
Militello,Robert C. Sampson
Vote Selection Votes Comments
Affirmative 25
Affirmative with Comment 1
Michael J. Ferreira Accepted.
Negative 0
Abstain 0
Eligible to Vote: 30
Not Returned : 4
Michael Earl Dillon,Douglas H. Evans,Anthony J.
Militello,Robert C. Sampson
Vote Selection Votes Comments
Affirmative 25
Affirmative with Comment 1
Michael J. Ferreira Accepted.
Negative 0
Abstain 0
SR-16, Section No. M.2.1, See SR-16
Total Voted : 26
SR-18, Section No. M.1.2.9, See SR-18
Total Voted : 26
Page 14 of 14