    COOLING TOWER

    PROBLEMS & SOLUTIONS

    by Paul R. Puckorius

    Puckorius & Associates, Inc.

    www.Puckorius.com

    www.watertrainingservices.comApril 13, 2011

    Presented by Process Cooling

    http://www.puckorius.com/http://www.puckorius.com/
  • 8/7/2019 Cooling Water - Packarious

    3/57

    Archivewww.process-cooling.com

    Add to your favorites

  • 8/7/2019 Cooling Water - Packarious

    4/57

    COOLING TOWER SYSTEM

    PROBLEMS & SOLUTIONS Cooling Tower-Where & What

    * Materials of Construction

    * Fill- Splash vs High Efficiency

    Heat Transfer Equipment

    * Proper Initial Startup Recirculation Lines

    * Initial Protection/ Stagnant Water

  • 8/7/2019 Cooling Water - Packarious

    5/57

    NEW GALVANIZED STEEL

    COOLING TOWERPROBLEM -White Rust

    This is corrosion of Galvanized SteelSOLUTION -Proper Initial Startup if

    a New Tower

    *Follow Manufacturers GuidelinesThis takes several weeks/ months

    at a controlled pH ( 6.0- 8.0 )

  • 8/7/2019 Cooling Water - Packarious

    6/57

    NEW GALVANIZED STEEL

    COOLING TOWERPROBLEM -White Rust

    This is corrosion of Galvanized SteelSOLUTION -Proper Initial Startup if

    a New Tower- Rapid -12-48 hours

    *Use 100-150 ppm phosphate with agood phosphate scale inhibitor and

    a pH of 7.0-7.5. Then maintain 3-5

    ppm phosphate in tower treatment

  • 8/7/2019 Cooling Water - Packarious

    7/57

    NEW GALVANIZED STEEL

    COOLING TOWERPROBLEM -White Rust

    This is corrosion of Galvanized SteelSOLUTION -Proper Initial Startup if

    a New Tower- Rapid -12-48 hours

    *Use 100-150 ppm poly silicate witha pH of 7.5-8.5. Then maintain a

    silicate level of 20-30 ppm.

  • 8/7/2019 Cooling Water - Packarious

    8/57

    GALVANIZED COOLING TOWERS-

    POTENTIAL VENT CONTAMINATION

  • 8/7/2019 Cooling Water - Packarious

    9/57

    OLD GALVANIZED STEEL

    COOLING TOWERPROBLEM -White Rust

    This is corrosion of Galvanized Steel

    SOLUTION

    *Clean with Citric Acid

    *Use Rapid Passivation- either

    phosphate or poly silicate method or

    epoxy coating of water wet areas

    * Consider Magnesium Anodes

  • 8/7/2019 Cooling Water - Packarious

    10/57

    GALV. STEEL COOLINGTOWER SEVERE CORROSION

  • 8/7/2019 Cooling Water - Packarious

    11/57

    GALV. TUBING IN TOWER

    (Fluid Coolers)PROBLEM -White Rust & Leaks

    This is corrosion of Galvanized SteelSOLUTION -Proper Initial Startup if

    a New Fluid Cooler

    *Follow Manufacturers GuidelinesThis takes several weeks/ months

    at a controlled pH ( 6.0- 8.0 )

  • 8/7/2019 Cooling Water - Packarious

    12/57

  • 8/7/2019 Cooling Water - Packarious

    13/57

    GALV. TUBING IN TOWER

    ( Fluid Cooler)PROBLEM -White Rust- Leaks

    This is corrosion of Galvanized Steel

    SOLUTION -Proper Initial Startup if

    a New Cooler- Rapid -12-48 hours

    *Use 100-150 ppm phosphate with agood phosphate scale inhibitor and

    a pH of 7.0-7.5. Then maintain 3-5

    ppm phosphate in water treatment

  • 8/7/2019 Cooling Water - Packarious

    14/57

    CORRODED GALV. STEEL PIPE

  • 8/7/2019 Cooling Water - Packarious

    15/57

    GALV. TUBING IN TOWER

    (Fluid Cooler)PROBLEM -White Rust

    This is corrosion of Galvanized Steel

    SOLUTION

    *Clean with Citric Acid

    *Use Rapid Passivation- eitherphosphate or poly silicate method or

    epoxy coating of water wet areas

  • 8/7/2019 Cooling Water - Packarious

    16/57

  • 8/7/2019 Cooling Water - Packarious

    17/57

    REBUILDING WITH TREATED

    COOLING TOWER WOODPROBLEMLeaching of preservative-

    copper/arsenic- can cause copper

    plating on mild steel & corrosionSOLUTION

    *Treat with a copper Inhibitor at

    50-100 ppm to tie-up the copper

    and to fix preservative in the wood

    during treated wood replacement

  • 8/7/2019 Cooling Water - Packarious

    18/57

  • 8/7/2019 Cooling Water - Packarious

    19/57

    PROBLEMCan harbor Legionella

    bacteria and add as food source

    but may increase tower efficiencySOLUTIONNeed to add biocide to

    the cooling tower return and to

    maintain a residual through the fill-if oxidant hold 0.5 ppm free and/or

    use a non-oxidant weekly till gone

    COOLING TOWER WITHALGAE COATED SPLASH FILL

  • 8/7/2019 Cooling Water - Packarious

    20/57

    SPLASH FILL WITH ALGAE

  • 8/7/2019 Cooling Water - Packarious

    21/57

    COOLING TOWER WITH

    HIGH DENSITY FILM FILLPROBLEMIf plugged or restricted

    will reduce tower efficiency and

    could collapse fill into tower basinSOLUTIONUsually high in biofilm-

    add biocide and dispersant to the

    return water to tower- if an oxidantused should be positive out of fill-

    find that hydrogen peroxide works

  • 8/7/2019 Cooling Water - Packarious

    22/57

    FOULED FILM FILL

  • 8/7/2019 Cooling Water - Packarious

    23/57

    FOULED FILM FILL

  • 8/7/2019 Cooling Water - Packarious

    24/57

    NEW HIGH DENSITY FILM FILL

  • 8/7/2019 Cooling Water - Packarious

    25/57

  • 8/7/2019 Cooling Water - Packarious

    26/57

    CYCLONECARTRIDGE

    FILTERS

  • 8/7/2019 Cooling Water - Packarious

    27/57

    STONES AND FIBERS PLUGGINGCONDENSER TUBES

  • 8/7/2019 Cooling Water - Packarious

    28/57

    Filter Types and Sizing Dense Particles- Cyclone Type

    Light Weight- Sand & Cartridge

    Mixture- Sand & Cartridge & MMF* Oil- Absorbant Type

    Full Flow or Side Stream

    Side Stream Filters Tower Volume 3-4times per day (often 3-5% recirc. rate)

    *Multi-Media Filter

  • 8/7/2019 Cooling Water - Packarious

    29/57

    Obtaing Cleaner Cooling

    Water Use Filters- On Every Cooling Tower

    Use Water Agitators in Basin w/Filters

    Use Chemical Dispersants w/Filters

  • 8/7/2019 Cooling Water - Packarious

    30/57

    NEW MILD STEEL TUBED

    HEAT EXCHANGERPROBLEMCorrosion and rust

    deposits found after 6 months in

    service- started up without initialhigh level corrosion inhibitor

    SOLUTION

    *Clean with Hydro-blast or Chemical*Use a Rapid Passivation with a

    Phosphate-based inhibitor ( 60 ppm)

  • 8/7/2019 Cooling Water - Packarious

    31/57

    MILD STEEL TUBES AND TUBESHEET W/ RUST DEPOSITS

  • 8/7/2019 Cooling Water - Packarious

    32/57

    CLEANED MILD STEEL TUBESAND TUBE SHEET

  • 8/7/2019 Cooling Water - Packarious

    33/57

    NEW MILD STEEL TUBED

    HEAT EXCHANGERPROBLEMStartup needed with a

    combination alkaline cleaner and a

    mild steel passivation treatmentSOLUTION- If an isolated bundle:

    * Clean/Passivate w/ 1.5% Phosphate

    & cleaner for 2-4 hours at 120-140*F.* If not isolated use a phosphate at

    40-60 ppm (PO4), ambient, for 48 hrs

  • 8/7/2019 Cooling Water - Packarious

    34/57

    NEW COPPER TUBED

    HEAT EXCHANGERPROBLEMCorrosion can occur withinone year if no initial passivation- pits

    & localized attack often w/enhanced

    tubes but also smooth tubes

    SOLUTIONInitial Protection Needed

    * Treat exchanger with 50-100 ppm ofa good copper corrosion inhibitor

    * Keep high level for 24 hours- then

    maintain 5 ppm copper inhibitor

  • 8/7/2019 Cooling Water - Packarious

    35/57

    SUPER ENHANCED COPPERTUBE

  • 8/7/2019 Cooling Water - Packarious

    36/57

    ENHANCED COPPER TUBE W/ PIT

  • 8/7/2019 Cooling Water - Packarious

    37/57

    ENHANCED COPPER

    TUBED CHILLERPROBLEM - Corrosion can occur withpits & localized attack in grooves

    with low copper inhibitor (1-2 ppm)

    SOLUTION

    *Need to maintain 3-5 ppm copper

    inhibitor (active) at all times

    * If chiller shut down- restart

    w/copper inhibitor at 10-20 ppm

    (active) for a week

  • 8/7/2019 Cooling Water - Packarious

    38/57

    NEW STAINLESS STEEL

    PLATE & FRAME BUNDLEPROBLEMCorrosion and leaks- bundle

    periodically stagnant

    SOLUTION*Sulfate reducing bacteria (SRB) can

    cause pits and loss of protection

    *Add a good SRB biocide regularly*Eliminate stagnant water or rinse

    with10% H2O2 before stagnant period

  • 8/7/2019 Cooling Water - Packarious

    39/57

    STAINLESS STEEL PLATE &FRAME HEAT EXCHANGER

  • 8/7/2019 Cooling Water - Packarious

    40/57

  • 8/7/2019 Cooling Water - Packarious

    41/57

    MILD STEEL TUBE SHEET

    WITH COPPER TUBESPROBLEMSevere tube sheet

    corrosion due to galvanic couple

    SOLUTION- Little from water treatment* Use a multi-coat epoxy (different

    colors) after blasting & rebuilding

    * Also coat water box and channelwith same- Inspect & repair yearly

    * New chiller should be coated

  • 8/7/2019 Cooling Water - Packarious

    42/57

    SEVERE CORROSION OF MILD STEELTUBE SHEET DUE TO COPPER TUBES

  • 8/7/2019 Cooling Water - Packarious

    43/57

    EPOXY COATED TUBE SHEET

  • 8/7/2019 Cooling Water - Packarious

    44/57

    ZINC SACRIFICIAL ANODE

  • 8/7/2019 Cooling Water - Packarious

    45/57

    NEW MILD STEEL PIPING

    PROBLEMOften stagnant for

    weeks/months after hydrotest- can

    cause serious corrosion/deposits.

    SOLUTION- Initial water treated with a

    combination alkaline cleaner and a

    mild steel passivation treatment

    * Use a phosphate/cleaner combo at50-100 ppm (PO4) and maintain till

    operating then reduce to 20 ppm PO4

  • 8/7/2019 Cooling Water - Packarious

    46/57

    FOULED STEEL PIPE

  • 8/7/2019 Cooling Water - Packarious

    47/57

  • 8/7/2019 Cooling Water - Packarious

    48/57

    A Complete Cooling Water

    Treatment Program Proper Initial Conditioning

    Scale Control

    Fouling Control

    Corrosion Control

    Microbio ControlAll items must be controlled. If one area is

    not controlled, the entire program may fail.

  • 8/7/2019 Cooling Water - Packarious

    49/57

    Need to Know Your System-All Water Contacted Surfaces

    Metals- tubes, lines, water boxes, tube

    sheets, and cooling towerEquipment Design- water in tubes, water on

    shell, jackets, fill type in tower

    Operation- max. water temp, min. watervelocity, any stagnant periods, anycontamination from air or water or process

    Water-Concentrated Tower Water

  • 8/7/2019 Cooling Water - Packarious

    50/57

    Water Conservation for

    Cooling Tower Systems Higher Cycles of Concentration

    Newest Technology Currently Available

    ChemicalsScale Inhibitors (Crystal Modifiers)

    Softening w/blowdown Return

    Non-Chemical

    Filters

    Several Electric/pulse/wave devices

  • 8/7/2019 Cooling Water - Packarious

    51/57

    Water Reuse- Saving Fresh

    Successful in many Industries-the nearfuture of most

    Use of Internally generated used waterSoftener rinse, RO reject, boiler blow

    down, chiller condensate,

    Externally available recycle water

    treated municipal waste water (recyclewater) and even rain water.

  • 8/7/2019 Cooling Water - Packarious

    52/57

    Green Products Available

    ChemicalsBiocides- Ozone. Chlorine Dioxide,

    Peroxides, Quats

    Corrosion Inhibitors- Organics, Silicates,and even Tin Salts

    Deposit inhibitors- from Oysters

    Non-Chemical

    Filters

    Devices- Pulse/Electric/Precipitators

  • 8/7/2019 Cooling Water - Packarious

    53/57

    Measuring Results-To Verify

    Equipment Protection System Inspections during outages

    Monitoring Systems on-line

    Corrosion by coupons & Instantaneous

    Deposits by heat transfer monitors

    Bio-corrosion by specific monitorsBio-deposits by ATP, DNA, Sessile

    rather than Planktonic

  • 8/7/2019 Cooling Water - Packarious

    54/57

    THANK YOU FOR LISTENING

    GLAD TO ANSWER ANY AND ALLQUESTIONS

    Cooling Tower

    Problems & Solutions

  • 8/7/2019 Cooling Water - Packarious

    55/57

    NEED MORE HELP?

    HOW TO CONTACT US?Puckorius & Associates, Inc.

    6621 West 56th Ave Suite 200 Arvada, Colorado 80002

    Phone-303-674-9897 Fax-303-674-1453

    Florida Office- 9005 Lake Lynn Drive Sebring, FL 33876

    Phone 863-655-1036

    E-mail [email protected] - www.Puckorius.com &www.watertrainingservices.com