Cooling system idiosyncrasies 2006

236
c:\sporlan 2006\cooling idiosyncrasies by Garth Denison Sr. Product Application Engineer Sporlan Valve Division Parker Hannifin Canada 2006 / 2007 Seminar Cooling Systems " Idiosyncrasies " Th e re is hu mor in those Coo ling Idiosyncra s ie s .

Transcript of Cooling system idiosyncrasies 2006

Page 1: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

by

Garth Denison

Sr. Product Application EngineerSporlan Valve DivisionParker Hannifin Canada

2006 / 2007 SeminarCooling Systems

" Idiosyncrasies "

There is humor in those

Cooling Idiosyncrasies.

Page 2: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

" Cooling Systems Idiosyncrasies "

A behavioral characteristic unique to an individual or group

The Sporlan Valve Division, Parker Hannifin assumes no obligations or liability for any advice furnished or for any results, property damage or personal injury including death that may result with respect to the use of this information. All such advice is given and accepted at users risk. This disclosure of information herein is not a license to operate under, or a recommendation to infringe any patent of Sporlan Division of Parker Hannifin or others.

® Registered trademark of Sporlan Valve Division, Parker Hannifin Corporation, Cleveland Ohio USA© Copyright 2005 by Sporlan Valve Division, Parker Hannifin Inc

Page 3: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Service Guide to Various

System Idiosyncrasies

Bull HeadingSplit Condensers

above 50°F

below 50°F

Page 4: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120

DRY BULB TEMPERATURE - °F

10 15 20 25

30

35

40

45

50

55

55

60

60

EN

THA

LPY

-BTU

PER

PO

UN

D O

F D

RY

AIR

ENTHALPY - BTU PER POUND OF DRY AIR

15

20

25

30

35

40

45

50

ENTHALPY - B

TU PER P

OUND OF D

RY AIR

SATURATION TE

MPERATURE - °F

.002

.004

.006

.008

.010

.012

.014

.016

.018

.020

.022

.024

.026

.028

35

3540

40 45

45 50

50 55

55 60

6065

6570

70

75

75

80

80

85 WET BULB TEMPERATURE - °F

85

90

10% RELATIVE HUMIDITY

20%

30%

40%

50%

60%

70%

80%

90%

12.5

13.0

13.5

14.0 VOLU

ME - CU

.FT. PER LB. DRY AIR

14.5

15.0

HU

MID

ITY

RAT

IO -

POU

ND

S M

OIS

TUR

E P

ER

PO

UN

D D

RY

AIR

.05

.1

.15

.2

.25

.3

.35

.4

.45

.5

.55

.6

.65

.7

.75

.8

.85

.9

.95

1

1.05

1.1

1.15

1.2

1.25

1.3

1.35

VA

POuR

PR

ES

SU

RE

-IN

CH

ES

OF

ME

RC

UR

Y

010

2025

30

35

40

45

50

55

60

65

70

75

80

85

DEW

PO

INT

TEM

PER

ATU

RE

-°F

1.000.95

0.90

0.85

0.80

0.75

0.70

0.65

0.60

0.55

0.50

0.45

0.40

0.350.300.250.200.15SENSIBLE HEAT RATIO = Qs / Qt

SE

NS

IBLE

HE

AT R

ATIO

= Q

s / Q

t

R-410A

CT 162 °F, CP 715 psia

Note importance ofsub-cooling

Bull Heading

above 50°F

Split

Con

dens

ers

below 50°FAB

POE

MO

Page 5: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

For 2006

Page 6: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 7: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Refrigerant Science of Yester Year

Temp / Press psigName Formula Flammable 0°F and 85°F

F-12 CCl2F2 No 9.2 91.7

Sulphur Dioxide SO2 No 8.9” 50.6

Ammonia NH3 Yes (16 to 25) 15.7 151.7

Butane C4H10 Yes (1.6 to 6.5) 15.0” 26.2

Iso Butane C4H10 Yes (1.8 to 8.5) 6.3” 43.9

Carbon Dioxide CO2 No 293.9 1012.3

Methyl Chloride CH3Cl Yes (8.1 to 17.2) 4.1 79.4

Ethyl Chloride C2H5Cl Yes (3.7 to 12) 21.6” 11.9

Methylene Chloride CH2Cl2 Yes (8.1 to 17.2) 27.9” 9.9”

Dichlorotetrafluoroethane C2Cl2F4 No 17.8” 21.0

Source: Frigidaire engineering manual Nov. 15, 1938

Page 8: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Global Warming … Kyoto

Page 9: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

" Typical Receiver Types "

Page 10: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Receivers

For receivers having an internal diameter of 6 inches (150 mm) or smaller: ARI 495, UL listed, steel, brazed, 400 psig (2760 kPa) pressure rating, with pipe threaded female access fittings for inlet, outlet, and pressure relief valve.

Receivers larger than 6 inches (150 mm) diameter: ARI 495, welded steel,tested and stamped according to ASME Boiler and Pressure Vessel Code:Section VIII; 400 psig (2760 kPa) pressure rating, with pipe threaded femaleaccess fittings for inlet, outlet, pressure relief valves, and a liquid level indicator.

Typical receiver accessories ..

Relief device (valve or fusible plug)

Dual relief valve saddle assemblyLiquid level indicator / alarmSight glassReceiver heaterInsulated receiverAccess / Isolation valves

Page 11: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Typical Receiver Types

From condenser To evaporator

Receiver

indicates vapour

indicates liquid

Minimum refrigerant charge is 15% of receiverscapacity to ensure a liquid seal at the dip tube.

Liquid Line

Surge Receiver

No minimum receiver refrigerant charge needed

Receiver styles:vertical

horizontal

Vent line

Page 12: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

System with Receiver

The circled area represents a typical receiver installed in the liquid condensate line.

Receiver may or may not effect the quantity of sub-cooling depending onrefrigerant’s speed, receivers ambient and system’s refrigerative effect.

Page 13: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

System with Surge Receiver

The circled area represents a typical surge receiver installed in the liquid line.

A surge receiver will not effect the quantity of sub-cooling. Refrigerantnot required to accommodate the load will back into the surge receiver.

Page 14: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Receiver Components & Accessories

Level indicators / Alarm actuators

Typical relief valve

Dual relief valve assembly

Pressure transducer,gauge and relief valve

Straight-thrurelief valve

Poly Tetra FluoroEthylene (Teflon)

&Fusible plugs

Page 15: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

R.V.Setting

Tolerance

+ 10 % R.V. Full Open

Maximum system operating pressure

Relief Valve (R.V.) Setting

- 10 % Potential R.V. “Seep” Point

Relief Valve Parameters

Relief valve parameters as a percent of R.V. set pressure.

PSI

440

400

360

320

Suction header

High PressureReceiver

Reliefvalves

Added protection is a High / Low By-pass valve if system pressure nears thepotential relief valve “Seep” Point.

Source: Henry Technologies

A typical installation with a pressure vessel havinga maximum working pressure of 400 PSI might be:

Relief Valves 400 PSI: Set at the design working pressure of the vessel OR25 % higher than the maximum working pressure of the system.

High / Low: Set at approximately 80 – 85% of relief valve setting. 330 PSI

Relief Valve: Table below for code parameters for a400 PSI relief valve. IN

OUT

High / LowBypass valve

Page 16: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Receiver Components & Accessories

Synthetic ester oil based greaseusing a lithium soap.

SKF system grease LGLT-2

Operating temperature range

-55ºC to 110ºC

-65ºF to 230ºF

Indoors Outdoors

Page 17: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Receiver Heaters

Various Heater TypesStrap-on heaterInsertion heaterEmersion heaterPeel & Stick foil backedMagnetic heater stripsBlanket heater

Page 18: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

" Reversing Fuses "

For testing purposes ONLY …How can a technician change rotationon a three phase application without

moving a wire ?

Thought Provoking !!!

Page 19: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Reversing Fuses

EXTREME CAUTION

Uninstalled Fuses

Blo

wn

/ Bad

Fus

e

Blo

wn

/ Bad

Fus

e

Heavy Wire

Heavy Wire

Fuse

Fuse

Page 20: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Reversing Fuses

EXTREME CAUTION

Installed Fuses

Blo

wn

/ Bad

Fus

eB

lown / B

ad FuseHeavy WireFuse

Fuse

Page 21: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

" Receivers and their Affects "

Page 22: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Air Cooled Condenser Typical Split Condenserc/w Standard Receiver

Liquid lines

Summer

ORI / OROA

Restrictor tube tolow side may beused to controlpump out rate ofinactive condenser

To evaporator

Receiver

R-22 condenser converted to R-404A,approximately a 10% gain in capacity.

Minimum refrigerant charge is 15% of receiverscapacity to ensure a liquid seal at the dip tube.

Page 23: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Air Cooled Condenser

Liquid lines

Summer

ORI / OROA

Restrictor tube tolow side may beused to controlpump out rate ofinactive condenser

8, 12 or 16D

To evaporator

Receiver

Typical Split Condenserc/w By-pass Receiver

R-22 condenser converted to R-404A,approximately a 10% gain in capacity.

Shown de-energized

Page 24: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Three Way Solenoid

From condenser

To receiver

To liquid line De-energized

Energized

1. High pressure refrigerant 2. Piston vent line3. Open to low pressure

8D, 12D, 16D

Page 25: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

De-energized

Page 26: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Energized

Page 27: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Air Cooled Condenser

Liquid lines

Summer

ORI / OROA

Restrictor tube tolow side may beused to controlpump out rate ofinactive condenser

Liquid Line

Surge Receiver

No minimum receiver refrigerant charge needed

Typical Split Condenserc/w Surge Receiver

R-22 condenser converted to R-404A,approximately a 10% gain in capacity.

Vent to condenser inlet,check valve installed

in this line.

“weir”

receiverinlet / outlet

Page 28: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 29: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Why Typical Split Condenser Vertical Drop ?

Air Cooled Condenser

Split Condenser Circuits

Liquid lines

ORIT / OROA

Restrictor tube tolow side may beused to controlpump out rate ofinactive condenser

** Note: ARI check valve acceptable leak rate is 750 ml/minuteone US gal = 3.8 liters (1 liter = 1000 ml)

** Typical 6 ft.

Density Specific. 1 psiRef. lb/ft3 Gravity Lift in ft.

R-22 74.5 1.20 1.93R-134a 75.1 1.21 1.91R-404A 65.5 1.05 2.20R-407C 70.8 1.14 2.03R-507A 65.5 1.05 2.20

R-410A 67.7 1.09 2.12

R-12 81.8 1.31 1.76R-502 76.0 1.22 1.89R-718 62.3 1.00 2.31

Specific Gravity = Density / 62.311 psi Lift in ft. = 2.31 / SG

Densities are at 25ºC or 77ºF

23.222.926.424.426.4

25.5

21.122.127.7

Lift ininches

Page 30: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

" Multi Receivers and their Affects "

Page 31: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Variances in Lift Verses Density .. @ 1 psi

one psi

Typical refrigerant1.8 feet or 21.6 inches

Refrigerants

Water H2O2.31 feet or 27.7 inches

Water

one psi

Typical lubricant2.5 feet or 30 inches

Lubricants

one psi

Refrigerant R-7173.9 feet or 47 inches

Ammonia

one psi

Page 32: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Series ReceiversWater cooled condensersInsufficient existing capacity

Normally 2 or 3 in series

Multi Receivers

Parallel ReceiversDifficult in controlling liquid levels

Possible liquid in one and vapour in other

Page 33: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

When Supplemental Receiversare Needed

Auxiliary receivers may be necessary when refrigerant pumpdown capacity is less than the proper operational charge of refrigerant in the system. This condition sometimes occurs inwater cooled systems where the condenser-receivers have limited capacity and it can alsooccur in any system where large evaporators or long liquid lines are used or where the pumpdown liquid solenoid valves cannot be located close to the TEV’s. To correct this condition, an additional receiver with the necessary holding capacity should be installed in series with and close to the outlet of the main receiver on the compression unit.

The auxiliary receiver should be installed on the same level or below the main receiver on thecompression unit. Both the main and auxiliary receiver must have their own service valves,fusible plug or relief valve. The liquid line sightglass, drier and the liquid line to the evaporatorshould then be connected in the normal manner to the service valve which is installed on theoutlet fitting of the auxiliary receiver.

Page 34: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Supplemental Receivers

" Series " Receivers

Main

Auxiliary

Receiver

Catch-All

See-All

Solenoid

Catch-All

See-All

Solenoid

Page 35: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Typical Copeland " C " Line Condensing Units

Liquid InOutletValve

Cross sectional view of two refrigerant receivers in series

one psi

Typical refrigerant2.0 feet or 24 inches

Refrigerants

Page 36: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

" Effects of Sub-cooling "

An Idea Whose Time Has Come

Page 37: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Sub-cooling

The reduction of the liquid refrigerant’s temperatureto a point below its saturation temperature.

Sub-cooling is always the removal of sensible heatonly from a liquid phase fluid.

Definition:

Up to 20% increase in Btu loadingDecrease in electrical usage as much as 25%Reducing pull-down time up to 50%Provide more uniform refrigerating temperaturesReduces first cost, by permitting down sizing ofcompressors in new system.

Obtainable:

Page 38: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Understanding Heat in the five Regionsof a Ph Diagram

Sensible heatregions

Latent heatregion

Satu

rated

liqui

d lin

e …

Bubbl

e Poin

t

Satu

rate

d va

pour

line

…D

ew P

oint

SuperheatedVapour region

SubcooledLiquid region

" Quality "(% vapour)

Liquid / Vapourmixture region

0.1 0.2 0.3

0.4 0.5 0.6

0.7

0.8

0.9

Solid region Triple point

Critical PointGaseous region

Page 39: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Consider the Following:

The compressor is a fixed displacement pump. It is pumping a certain number of CFM (pounds) of refrigerant through thecycle, and really doesn’t care how many Btu’s are in each oneof those pounds. So by increasing the number of Btu’s perpound, we can increase the capacity of the system while notincreasing the mass flow of refrigerant.

Increasing Sub-cooling Reduces Flash Gas,Increases Net Refrigeration Effect.

Page 40: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Sub-cooling can:

1. Increase capacity2. Decrease electrical usage3. Reduce equipment maintenance4. Produce better temperature control5. Reduce pull-down time after defrost6. Reduce first costs

Page 41: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

What do the headlights on a motor car and on a bus have to do with you, the

refrigeration and air conditioningtechnician ?

Thought Provoking !!!

Page 42: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

MC and B tanks

40 cu ft

" B " Bus10 cu ft

" MC " Motor Car

(acetylene)

MCB

Acetylene HeadlightsHenry Ford Museum, Dearborn Michigan

Page 43: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

" Accomplishing Sub-cooling "

Page 44: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Types of Sub-cooler

Ambient sub-coolingAirWaterRefrigerant

Mechanical sub-coolingIntegral part of systemSelf contained refrigeration systemUsually brazed plate heat exchangers

Both styles actually refrigerate the refrigerant.

Page 45: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 46: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

PREFERRED

ACCEPTABLE

NEVER

Installation & Mounting ...

For Single Phase, Liquid-to-Liquid Applications

Page 47: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Installation & Mounting ...Effect of Inclination on Two Phase, Refrigerant Applications

55

3030

45

45 60

60

90

90

0

-3%-2%-10%

-16%

-38%

-9%

-15%

-37%

Evaporator -No measurable difference

within ± 5º of vertical.

Based on testing conducted by NIST. R-22 evaporator.

Page 48: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Installation & Mounting ...Effect of Inclination on Two Phase, Refrigerant Applications

55

3030

45

45 60

60

90

90

0Condenser -

No measurable difference.

Short term limited test.

Based on testing conducted by NIST. R-22 evaporator.

Page 49: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Typical Plate to Plate Heat Exchangers,Sub-coolers

Sub-coolers

The brazed plate heat exchanger is substantiallysmall than other technologiesthat could be used.

The EPR valve should normally be set to maintaindesired liquid temperature. This is normally 50°F

but may be as low as 40°F for some systems.

Mechanical sub-coolers leavingliquid refrigerant temperature isusually controlled by a temperaturesensor on the condensers liquidcondensate drop leg.

Page 50: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Refrigeration Retrofitting R-22 to R-404A

Regaining the Lost Capacity

from receiver

toliquid manifold

TEV’s

tosuction manifold

EPR

solenoids

Plate to PlateHeat exchanger

Plate to PlateHeat Exchanger

Page 51: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Specific Heat .. the amount of heat needed to raise / lower onepound of a substance one F°. (Btu/lb. F° sensible heat)

Thermodynamic 411

R-22

R-404A

Btu/lb F°Cp 0.300

Cp 0.367

R-407C

R-410A

Btu/lb F°Cp 0.368

Cp 0.440

Refrigerant Liquids

Source DuPont AG3 and AG2

Page 52: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Sub-cooling Calculation Example

R-22 has a Specific heat (Cp ) of 0.300

Example:

Liquid refrigerant entering sub-cooler is 100ºF

Desired refrigerant temperature leaving sub-cooler 50ºF

Formula used is Mass x Specific heat (Cp) x Delta temperature

Refrigeration effected needed per pound of mass flow is 1 x 0.300 x 50 = 15 btu’s

A system having a mass flow rate of 13 pounds per minute needs 13 x 15 = 195 btu’s or 1 ton

Using the same conditions:360,000 btu’s (30 ton LT) rack would need approximately 105 lbs/min

Sub-cooling capacity 105 x 0.300 x 50 = 1575 btu’s or 1575 / 200 = 7.9 tons

TEV’s for Sub-cooler .... One three tons and one five ton

Page 53: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Plate to Plate Heat Exchanger

from receiver

toliquid manifold

TEV’s

tosuction manifold

EPR

solenoids

Mechanical Sub-cooler

The brazed plate heat exchanger is substantially smaller thanother technologies that could be used as a liquid sub-cooler.Typically the rack controller has a temperature sensorthat will sense the refrigerant drop leg (condenser return)line to the receiver. Depending on the refrigerant type andsystem design it is quite normal to supply 40 to 50 °Fsub-cooled liquid refrigerant throughout the network.

An example of a typical Sub-coolers operation is as follows:no solenoids energized = no additional sub-cooling# 1 solenoid energized = 3 additional tons# 2 solenoid energized = 5 additional tons# 1 and # 2 solenoids energized = 8 additional tons

The EPR is normally set to maintain the minimum desiredliquid refrigerant supply temperature. This is normally50°F but may be as low as 40°F for some systems. A sub-cooler EPR settings of 68 psig will have a SST of 40°F for R-22 and 29°F for R-404A.

The liquid line solenoids in front of the sub-cooler expansion valves close when the condensers drop leg temperature gets below the set point thereby shutting off the sub-cooler.

Plate to PlateHeat exchanger

Page 54: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

How Sub Cooling Affects System Capacity

R-22

For every 10F° of sub coolingof R-22 will equal a 6% reduction in refrigerant mass flow requirements.

Example: SCT 100 FSST – 25 FSC 0FSH 25 FLOAD 5TBTU/LB 62.6

SCT 100 FSST – 25 FSC 50FSH 25 FLOAD 5TBTU/LB 77.6

Summary:

77.6 / 62.6 = 1.24Therefore 2F° SC = 1 % capacity increaseRefrigerant circulated 15.9 to 12.9 lb/minCompressor displacement from 44.1 to 35.5 cfm

R-404A / R-507

For every 10F° of sub coolingof R-404A / R-507 will equala 10% reduction in refrigerantmass flow requirements.

SCT 100 FSST – 25 FSC 0FSH 25 FLOAD 5TBTU/LB 38.6

SCT 100 FSST – 25 FSC 50FSH 25 FLOAD 5TBTU/LB 58.4

Example:

Summary:

58.4 / 38.6 = 1.51Therefore 1F° SC = 1 % capacity increaseRefrigerant circulated 25.9 to 17.2 lb/minCompressor displacement from 49.7 to 32.9 cfm

NOTE: the above outlined calculation were determined by the use of DuPrex computer program

Page 55: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 56: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 57: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 58: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 59: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

What is the controlling capacityfactor of any refrigeration

system ?

The choke point …." Evaporator "

Thought Provoking !!!

Page 60: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

" Economizers when Multi Staging "

Page 61: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Open Economizer

refrigerant vapour to compressor’s inter-stage

liquid refrigerantto

Evaporator (s)liquid refrigerantfrom condenser

saturated refrigerantat inter-stage pressure

spraynozzles

open economizer

indicates vapour

indicates liquid

The " Open or Flash " economizer is simply a tank, which is vented to the compressors inter-stage.The refrigerant flashes, evaporating some of the refrigerant, cooling the remaining liquid to the saturation temperature corresponding to the inlet pressure of the compressor inter-stage. The open or flash economizer is an economical, efficient method of cooling liquid refrigerant en-route to the evaporator (s). Open economizers are generally used when high efficiency is requiredas they also reduce the BHP requirements.

Page 62: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

2nd stage

1st stage

Open Economizer

" Open or Flash " economizer

Page 63: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

closed economizer

refrigerant vapour to compressors inter-stage

Sub-cooled liquidrefrigerant to

evaporator (s)

liquid refrigerantfrom condenser

levelcontroller

indicates vapour

indicates liquid

liquidrefrigerant

Closed Economizer

The " Closed " economizer takes the liquid from the condenser and splits the flow into two streams.Most of the refrigerant flow goes through the tubes of a shell and tube heat exchanger; the remainingrefrigerant goes to the shell side through a control valve to be boiled off to cool the refrigerant in thetubes. The vapour generated is vented to the inlet of the compressors inter-stage.

Page 64: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Closed Economizer

2nd stage

1st stage

" Closed " economizer

Page 65: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Two Stage A/C Cooling !!

His and Hers ??

Page 66: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Summary

Up to 20% increase in Btu loadingDecrease in electrical usage as much as 25%Reducing pull-down time up to 50%Provide more uniform refrigerating temperaturesReduces first cost, by permitting down sizing ofcompressors in new system.

Catch-All

See-All

Solenoid

Possible reselection of TEVand distributor orifice disc needed

Page 67: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Affects of Sub-coolingon TEV’s Capacity

Refrigerant 100°F 60°F 50°F 40°F(0°SC) (40°SC) (50°SC) (60°SC)

R-134a 100% 1.29 1.36 1.42R-401A 100% 1.25 1.31 1.36R-409A 100% 1.23 1.28 1.34

R-404A 100% 1.43 1.54 1.64R-408A 100% 1.27 1.34 1.40R-507 100% 1.40 1.50 1.59

R-22 100% 1.23 1.29 1.34R-407C 100% 1.28 1.35 1.42

Page 68: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

" Accumulators and their Affects "

Page 69: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Hold approximately 50% of systems charge in TEV systems

Hold approximately 70% of systems charge in fixed orifice systems

Standard screen in 3 inchdiameter accumulators

Standard screen in 3 through 6 inchdiameter accumulators

Metering orifice for oil return to the compressor located behind screen0.055” diameter for 3 through 5 inch diameter accumulators

0.080” diameter for 6 inch diameter accumulators

Accumulator Design

Page 70: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Original R-22 Screen

60 x 60 mesh of surface area

Smaller mesh can trap POE oils and

additives.

Mesh .. Number of openings per linear inch, measured from the centre of one wire to a point one inch distant.

Accumulator Screens

Mesh 0.001’s Microns

10 = 0.0580 = 150030 = 0.0194 = 50060 = 0.0097 = 250

100 = 0.0058 = 150 140 = 0.0041 = 105200 = 0.0029 = 74350 = 0.0017 = 44

Increased surface area retains more contaminants without plugging.

30 x 30 mesh screen prevents POE oils & additives from becoming trapped due to surface tension .

Enhanced HFC Screen

Page 71: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Odor eaters ..

Odors … Bacteria

CharcoalBaking Soda

FDS (feminine deodorant spray)

foam core insulation, not fiberglass

Thought Provoking !!!

Personal level ..Vicks Vapor Rub … your upper lipBasil … nasal snort

Page 72: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Effects of Hydrostatic Pressures ?

Lets Look at it.

Page 73: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Temperature °F

Pres

sure

ps

ig

200

600

1000

1400

1800

2200

2600

40 60 80 100 120 140 160 180

Typical Effects of Hydrostatic Pressure

Hydrostatic PressureIncrease

R-12/R-134a is 40 psi / each F°R-22 is 60 psi / each F°

R-410A is 45 psi / each Fº

4BA / 4BWBurst Pressure

1040thru1600

R-2240°F is 70 psi

180°F is 540 psi

R-12/R-134a40°F is 37 psi

180°F is 330 psi

R-410AR-22

R-12 & R-134a

ReliefDevices390 psi

thru800 psi

R-410A40°F is 120 psi155°F is 645 psi

3200

Receiver to Solenoid ?

Page 74: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Liquid line solenoid100 feet away.

System:

R-22, with MO- 25ºF SSTElectric defrostPump out systemLP control cutout1 psig (- 40ºF)

Freezer at- 17ºF

Freezer at- 17ºF

Freezer at- 17ºF

Troubled System … 6 TEV’s ReplacedStill High Super Heat ?

“Tee”

Found a 30Fº ∆ across Tee

Page 75: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 76: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 77: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 78: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Blood Storage RoomProblem: loss of critical temperaturecontrol, in a continuous operation.

Picture is of Hot Gas stabilizer line atevaporator inlet, solenoid 8 ft aboveoutside box in a 74ºF ambient.

Blood Storage Roomcritical application

- 30ºC or - 22ºF

Page 79: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Modern ServiceTechnician

Fouling !!!!!

Page 80: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 81: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

A 0.042" Film of Dirt on a Coil

Equals 21% Loss in

Heat Transfer Efficiency

Page 82: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

" Servicing a Winter Charge"

Page 83: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

SporlanBulletin90-30-1

Page 84: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

SporlanBulletin90-30-1

Page 85: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Sporlan Bulletin 90-30-1

Refrigerants listedR-12 R-22 R-134a R-401A R-401BR-402A R-402B R-404A R-407C R-408AR-409A R-502 R-507

Page 86: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

SporlanBulletin90-30-1

Page 87: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Sporlan Bulletin 90-30-1

Page 88: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Sporlan Bulletin 90-30-1

Page 89: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Servicing a Winter Charge !!!

To calculate the correct additional winter operationalrefrigerant charge needed at winter design follow

the procedure as outlined in Sporlanbulletin 90-30-1 dated July 1998.

How to calculate the needed additional refrigerant if only a partial charge exists.

1. Calculate the correct added winter refrigerant charge for the winter design conditions. eg: 128 lbs @ - 20ºF. (follow procedure as outlined in Sporlan bulletin 90-30-1 dated July 1998)

2. Take and record the current outdoor ambient air temperature. eg: + 20ºF3. Add refrigerant until the sight glass just clears and record the quantity of refrigerant added. eg: 17 lbs4. Recalculate the added winter charge for the current existing ambient temperature. eg: 98 lbs @ + 20ºF.

(this unit now contains the correct operational winter charge for its current ambient air temperature)5. Additional refrigerant needed to operate at – 20ºF is 128 – 98 = 30 lbs.6. In this example the billable refrigerant charge would be 17 + 30 or 47 lbs.

Page 90: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Fin and Tube Heat Exchangers

Used for both evaporatorsand condensers.

TUBESPrimary Surface, usuallymade of copper (Cu).

FINSSecondary

Surface,usually madeof Aluminum

(Al)

Page 91: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Coefficient of Expansion

Coefficient of Expansion

Cu is 0.0000104 of an inch / per inch / per F°

or

1.04E-5 per inch / per F°

Al is 0.0000130 of an inch / per inch / per F°

or

1.30E-5 per inch / per F°

Source: American Machinists Handbook, p 33 - 29

Page 92: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 93: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

2 Lines of Nozzles

Page 94: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Air Cooled Condenser

Page 95: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Air Cooled Condenser

Page 96: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

“Aluminum will creep and move approximately 33% morethan copper. This large movement will eventually lead tofatigue failure.”

“Through repetitive thermal cycling, aluminum laminations(fins) can become loose, resulting in early failure.”

Cu vs Al

Source: elettra technology inc.

H2O (hard or soft) will evaporate AND cause residue (residual) deposits of either or both mineral and / or oxides to be left behind. This residuewill be deposited on or between the Cu and Al thereby increasing theheat exchanger’s fouling factor. This increase interferes with the heat transfer process causing a loss of efficiency and capacity.

Page 97: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Other Considerations

• Continues running of water .. Added costswater cost / sewer charge

• Roof will not dry off … permanent roof damage

• Loss of head pressure control as temperature changes

• Environmental aspects

• Outdoor installation, freezing prospects

• Repeated calls to start / stop adjust etc:

• Equipment life shortened, rust, motors, belts, drives

Page 98: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

And Then There is theOther Contractor

Modern ServiceTechnician

Page 99: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Poor Bulb Location = Floodback

Show smashed compressor parts …………….

Page 100: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Built-in Redundancy !!!

Page 101: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 102: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

10 Units in 48” wide passage !!!

Page 103: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Location .. Location .. Location

First Rule in Real Estate

Page 104: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Residential Split Systems

Traditional / StandardMethod

Typical Cool ClimateInstallation ?

Page 105: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Residential Split Systems

Second Alternative, Knee Braces on outside wall.Pro’s: Not effected by ground thermo shear.

Landscaping not completed .. RNC market.Con’s: Sound transmission, harmonics through wall.

Isolation pads may be needed ?

Secure top of hairpin only .. Allows opening / closing

Preferred InstallationMethod

Page 106: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 107: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 108: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 109: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 110: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 111: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 112: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Didn’t like the look …Must hide the Condensing unit

Page 113: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

R-410A ? Under the Deck …unit will die of emphysema !!!

RedRock Clubhouse, prestigious golf course inSouth Carolina. Removed 4” of pine needles toget units in and then only 1” top clearance onsecond unit.

Page 114: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Typical Ductless Split Installation

Page 115: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 116: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 117: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 118: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 119: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 120: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 121: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 122: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 123: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 124: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 125: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 126: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 127: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 128: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Then There is the Contractor ABC( Always Bring Cash )

Page 129: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Cross supports ????

Safe

ty …

!!!!!!

Chicken crates

Entranced way

Page 130: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Home on pillars, note condensers discharge ducton top of unit, complete with turning vane.

Attic installation in a SouthernState. Do it yourself installationdream.

Page 131: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 132: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Access Ladder to Roof

Page 133: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Three Compressors !!!

Page 134: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

FIDO

Page 135: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

38HQ three piece heat pump, Low ceiling re-circulated air.Note: longer piping run but proper location of fittings for oil return.

Installation is everything ?Location Location Location

Page 136: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasiesGate Valves ????

The Plumber !!!

Page 137: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Nylon Tie Wraps !!!!

Page 138: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Controlling Lubricantsand Discharge Temperature

Page 139: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Typical Refractometer

Page 140: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Refractometer Readings

Approved OEM POE Lubricants:

Copeland, all reciprocating and scroll refrigerationEmkarate … RL32CF .. 1.4546

Carlyle / Carrier all O6D & O6EEmkarate … RL68H … 1.4557

Carlyle / Carrier all O5T & O6T screwsEmkarate … RL100S .. 1.4574

Mineral Oils .. 3GS: 1.4942, 4GS: 1.4973, 5GS: 1.4953

Alkylbenzene … 150: 1.4865, 200TD: 1.4859, 300: 1.4844

Source Nu-Calgon 3-240

(150 / 32) (500 / 100)(300 / 68)Viscosities SUS / ISO

Page 141: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Polyolester Lubricants

RL22H RL22N RL32CF RL32S RL32H RL68H RL68HP RL68S RL100S RL150S RL220H1.4519 1.4521 1.4546 1.4546 1.4530 1.4557 1.4557 1.4564 1.4574 1.4581 1.4580

Emkarate OEM approved lubricants

Bitzer Recp. X XScrew

Bock X X X Bristol XCarlyle Recp. X

Screw XCopeland XD/Bush Recp. X X

Screw X Embraco XGrasso XManeurope XMatsushita XPrestcold XRoyce X XSabroe X X X X X X X Sea Container X SRM X Tecumseh XThermoking XTrane* Screw X

Scroll XYork* Recp. X

Screw X

McQ

uay

R-1

34a

cent

rifug

als m

odel

s 05

0, 0

63,

079,

087

Car

rier R

-134

a ce

ntrif

ugal

s mod

els

19X

T, 1

9XR

, 19

XR

T, 1

9EX

Emkarate lubricantRefractive index

source: Nu-Calgon 3-68 + Carrier

Suffixes:CF = Copeland formulationH = High solubilityS = Standard solubilityN = Special for McQuayHP = Special for Carrier

by Garth Denison

* Trane and York low pressure centrifugals use OEM approved mineral lubricants.

Bitzer ScrewEmkarate RL170H

1.4576BVA Solest 170

1.4558

Page 142: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Cross Lubricant Contamination

POE

ABMO

AB … Alkylbenzene OilMO … Mineral OilPOE … Polyol ester Oil

< 50 %

< 5 % < 5

%

Note:

Lubricants are 100% misciblewith each other. Their degree

of miscibility with variousrefrigerants varies from

0% to 100%.

Generally Accepted Lubricants

CFC’s and HCFC’s use MO or ABHFC’s and PFC’s use POE

Page 143: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 1001.440

1.445

1.450

1.455

1.460

1.465

1.470

1.475

1.480

1.485

1.490

1.495

1.500

Refractometer GraphRefractive Index vs Residual Oil Content

Residual (%, wt) of Old Oil

Page 144: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Note: Always take readings after " De-gassing " lubricant

1.51

1.50

1.49

1.48

1.47

1.46

1.45

1.44

1.52

1.51

1.50

1.49

1.48

1.47

1.46

1.45

1.44

1.52

RefractiveIndex

nD

Scale

Refractometer Eye Piece

nD = reactive Divergence

Page 145: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 1001.440

1.445

1.450

1.455

1.460

1.465

1.470

1.475

1.480

1.485

1.490

1.495

1.500

MO3C / 3GS – 1.49424C / 4GS – 1.49735C / 5GS – 1.4953

AB150 – 1.4856

200TD – 1.4859300 – 1.4844

POECopeland – 1.4546

Carlyle O6D/E – 1.4557Carlyle O5/6T – 1.4574

Refractometer GraphRefractive Index vs Residual Oil Content

Residual (%, wt) of Old Oil

POE1.4557

MO1.4942

Sample lubricant example,a reading 1.474 would

represent 44% POElubricant.

Page 146: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

POE

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 1001.440

1.445

1.450

1.455

1.460

1.465

1.470

1.475

1.480

1.485

1.490

1.495

1.500

MO

AB

MO3C / 3GS – 1.49424C / 4GS – 1.49735C / 5GS – 1.4953

AB150 – 1.4856

200TD – 1.4859300 – 1.4844

POECopeland – 1.4546

Carlyle O6D/E – 1.4557Carlyle O5/6T – 1.4574 Source: Nu-Calgon # 3 – 242

Maximum cross lubricant contamination with POE’s is 5%

Refractometer GraphRefractive Index vs Residual Oil Content

Residual (%, wt) of Old Oil

Acceptablerange1.4546

to1.4595

Page 147: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Desired refractive range is between

1.4546 to 1.4595

This will ensure less than

5% cross lubricant

Refractometer Graph

Refractometer Sources:

1. ATAGO P/N N-30002. Copeland P/N 998-RMET-00

Page 148: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Service Refractometer

1.4546 to 1.4595

Page 149: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Temperature ResponsiveExpansion Valve (TREV)

Typical U.S. Green Compressors

OEM Discharge head sensor:

Refrigeration dutyopens 325°F +/- 8closes 250°F +/- 12

Air Conditioning dutyopens 295°F +/- 5closes 235 minimum

Typical Black Compressors

eg: OEM Demand Cooling™

Injects refrigerant at 292°FShuts refrigerant off at 282°F

If compressor operates at310°F for 60 seconds thecontroller will shut the unitoff on safety.

Y 1037

Page 150: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Lubricant Functions

Other Functions: …1. Makes a fluid seal .. prevents blow by

2. Acts as a coolant .. compressor and hermetic motor

3. Dampens mechanical noise .. POE’s 1½ louder, dB scale

4. Provides electrical insulation .. hermetic systems (25Kv)

Purpose: … to minimize friction and prevent wear of moving parts.

Tribology: .. the study of interacting surfaces in relative motion and associatedissues, such as friction, lubrication and wear. (friction and wear)

Page 151: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Additional Piping Considerations

Refrigerant goes to Lubricant

Lubricant DOES NOT go to Refrigerant

Refrigerant is soluble (dissolved) in lubricant .. similar to sugar in coffee (one liquid phase) until CST (Critical Solution Temperature)

is reached then there is two liquid phases (one refrigerant + one lubricant).

Note: OEM’s of ductless splits recommend NO traps.

Page 152: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Lubricant movement within a typical system

Properly designed refrigeration / air conditioning system3 to 5% of compressor’s lubricant is in circulation at all times.MO / AB is approximately 30% miscible with their typical refrigerant’s, the remaining lubricant travels by peristalsis, this is caused by the refrigerant’s velocity.

POE lubricants with HCFC or HFC refrigerants are 100% misciblebetween from + 176° F (+ 80° C) through – 76° F (- 60° C), thereforethe circulating lubricant travels in suspension.

Miscibility … the ability to mixSolubility … the ability to dissolveCST … Critical Solution TemperatureLubricants are miscible with other lubricantsLubricants are miscible at different percentages in refrigerantMoisture (H2O) is soluble in POE lubricant

Page 153: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Variances in Lift Verses Density .. @ 1 psi

one psi

Typical refrigerant2 feet or 24 inches

Refrigerants

Water H2O2.31 feet or 27.7 inches

Water

one psi

Typical lubricant2.5 feet or 30 inches

Lubricants

one psi

Refrigerant R-7173.9 feet or 47 inches

Ammonia

one psi

Page 154: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

“RISER”45° Street El

45° Street El

90° Short Radius El

Oil Trap Construction

Page 155: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

The oil drains from the riser & sloped horizontal piping to fill the trap

Oil Trap During the Off Cycle

Page 156: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

If a large surge of vapour enters the trap

The oil could be forced out of the trap as a slug

For this reason the oil holding volume of the

trap is kept to a MINIMUM

Oil Trap at Start Up

Page 157: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Which trap is more likely to kill a compressor with

an oil slug?

Oil Traps Compared

Page 158: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Usually, the amount of vapour entering the trap gradually increases

The oil is then pushed through the trap until a gap is formed here

Because the gap has a small area,

the vapour passes through at high

velocity

The high velocity vapour carries oil droplets up the riser

Oil Trap at Start Up

Page 159: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Downward direction of flow & Horizontal line size is increased so

pressure drop is kept in an acceptable range

Riser line size is

reduced to maintain vapour velocity and oil

return up the riser

Reduced Size Riser

Page 160: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

smaller RISER

“A”

larger RISER

“B”

The large volume of

vapour flow is split between

risers

Each riser has enough flow & velocity to carry

oil up the pipe

Double Riserat Full Capacity

Page 161: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

smallerRISER

“A”

largerRISER

“B”

The small volume of vapour flow is not enough to carry oil

up both risers

The oil can’t be carried up the risers and fills

the trap

This blocks vapour flow in

Riser “B”

Then all the small volume of

flow shifts to Riser “A” with

enough velocity to carry oil up

the pipe

Double Riserat Low Capacity

Page 162: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Lubricant Miscibility SummaryCFC’s

w / Mineral oil-76F 2 phases +164F 2 phases +176F

w / Alkylbenzene -76F 2 phases -17F 1 phase +176F

HCFC’sw / Mineral oil -58F 2 phases +149F 2 phases +162F

w / Alkylbenzene -58F 2 phases +151F 1 phase +162F

w / Polyol ester-58F 1 phase +162F

w / Mineral oil-76F 2 phases +126F 2 phases +176F

w / Alkylbenzene-76F 2 phases +135F 2 phases +176F

w / Polyol ester -76F or -60C 1 phase +176F or +80C

Source: DuPont HP P.U.S.H.

HFC’s

Page 163: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Influence of Mineral Lubricant Filmon Heat Transfer

Source: Technicold Services Inc, George Briley P.E.

A film of only 1.5 mils of oil drops the heat transfer coefficient14% and a film of 3 mils dropsthe heat transfer by 25%. As the surfaces continue to “foul”, thesystem efficiency decreasesaccordingly.

Note: 1.0 mil = 0.001 inchAverage copper BTU/Hr/SF/Fº is 85 to 100

Page 164: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Lubricant is required to lubricate the moving parts within the compressor.Unfortunately lubricant and refrigerant have an affinity to each other and lubricant is constantly being depleted from the compressor sump and circulating about the piping system. Lubricant can get logged up in parts of the piping system and note return to the compressor sump. The rate of lubricant depletion must be equaled by the rate of lubricant being returned otherwise it is only a matter of time until the compressor is destroyed from lack of lubrication. Piping systems are designed as a trade off between pressure drop (system efficiency) and velocity (lubricant return). In other words larger pipes have less pressure drop which is good for system efficiency and smaller pipes cause higher velocities which improve lubricantmovement and the return of lubricant to where it belongs. Another problem with lubricant getting out is the piping system is that it acts as an insulator reducing heat transfer in coils. Oil separators capture most of the lubricant as it leaves the compressor and return it back to the compressor sump whereit belongs. There are three types of oil separators; impingement, helical, and coallescing.

OIL SEPARATORS

Page 165: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Impingement separators use screens in the upper half to cause fine particlesof oil to collect and form larger ones. The velocity of the discharge gas is reduced when it enters the large volume of the oil separator which helps theoil droplets to impinge on the screen. The droplets grow large enough in sizeto fall to the bottom. When sufficient oil has been collected a float operatedneedle valve opens and allows the difference in high side and low side pressureto return the oil to the crankcase. The black arrow in the graphic is above thefitting for the oil return line. Impingement separators are approximately 80% to 85% efficient and are in common use. The drawing shows a serviceabletype impingement oil separator. They are also available as a sealed unit.

Impingementtype

Page 166: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Helical separators (aka .. cyclone) depend on the interior shell designto force the refrigerant / oil mixture along a spiral path. That creates a centrifugal force which forces the lubricant droplets to the outsideof the spiral where they collect and drain to the float valve below.A supposed drawback to this type of unit is that centrifugal forceonly works effectively on relative large lubricant droplets. This meansthat smaller droplets remain in the refrigerant and are re-circulatedthrough the system. However manufacturers of helical separators claimthat up to 99% efficiency can be achieved.

Helical / Cyclonetype

Page 167: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

In coalescing separators, the refrigerant/oil mixture is passed througha filter of exceptionally pure, extremely fine glass fibers, which forma capturing matrix. This matrix excites the oil molecules, causing themto collide and form larger droplets which are forced to the filter's outerdrain layer where they drain by gravity into the sump. Coalescing unitsare capable of delivering between 95% to 99%+ efficiency, dependingon the grade of filter core used and the design details. There are some coalescing oil separator manufacturers that claim their units have 99.99% efficiency.

Coalescingtype

Page 168: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Polly Ester

Polly’s unsavory background is that she’s nothing but acid and alcohol.Manufacturers have tried to neutralizer / stabilizer her for years. Shegoes everywhere and she’ll pick up anything and everything on her travels. She’s expensive, $ 40 to $ 50 per gallon. She sucks, veryhygroscopic as she picks up water readily. She’s a loud mouth,reciprocating compressors using Polly will be about 50% (1-1/2 times)louder on the dB scale as the same compressor using mineral oil. She’sa tramp, as Polly is polar in nature she will carry wear particulates insuspension as she flows throughout the system.

Let’s call her what she is, she’s a bitch.

Something to think about.

Page 169: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Grams or CC’s of H2O @ 20°C (68°F)

Pounds of Refrigerant

25 50 100 250 500 1000 2000

10 0.12 0.25 0.5 1.1 2.3 4.5 9.2

30 0.4 0.7 1.4 3.4 6.8 13.6 27.2

50 0.5 1.1 2.3 5.7 11.3 22.7 45.2

100 1.2 2.3 4.5 11.3 22.7 45.4 91

250 2.9 5.8 11.3 28.4 56.7 113.4 227

500 5.6 11.3 22.7 56.7 113.4 226.8 454

1000 11.3 22.7 45.4 113.4 226.8 453.6 907

1500 17.0 34.0 68.0 70.1 340.2 680.4 1361

2000 22.7 45.4 90.7 226.8 453.6 907.2 1814

ppm

H2O

Notes: 1 gram = 20 drops of H2O or 1 gram = 1 ccppm’s x weight x 453.59 ÷ 1,000,000 = grams or cc of H2O

POELubricant

Page 170: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Generally Accepted Piping Criteria

Inline flare by flare relief valves:

Under certain circumstances it may be necessary to install an inline relief differentialrelief valve. The purpose of this valve is to relief a situation where hydrostatic pressurecould develop due to liquid refrigerant being trapped leaving it no room for expansionas the temperature increases. This situation is usually caused by the systems pipinggeometry and/or installed ancillary devices.

Split system with buried piping:

In some installations it may become necessary to bury the line set. An example of thismay be under a sidewalk for safety reasons. If this situation arises use a minimum of 6 inch or larger diameter irrigation type tubing open at both ends above grade, this should provide adequate ventilation. The ends of this tubing can be covered with large mesh screening to keep small critters out but will allow adequate air circulation to preventthe condensation of refrigerant vapour in the underground section. Good installationpractice would also include the installation of a properly sized suction line accumulator.

Page 171: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Best Piping Practices

Liquid Line for Multi Evaporators

Split system A/C or Refrigeration

Multi-Evaporators Hot Gas

Liquid Line Stacked Evaporators

Suction Line Stacked Evaporators

How to Modify Defective Piping Installation

Split Circuited Condensers

Page 172: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Liquid Line Piping for Multi evaporators or cases with defrost

Refrigerant Piping Practices

Liquid Line

Liquid Line

Case coilCase coilCase coil

Case coilCase coilCase coil A

B

Denotes TEVcontinued …...

Page 173: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Liquid Line

Liquid Line

Case coilCase coilCase coil

Case coilCase coilCase coil A

B

Denotes TEVcontinued …...

Liquid Line Piping for Multi evaporators or cases with defrost

Refrigerant Piping Practices

Page 174: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Liquid Line

Liquid Line

Case coilCase coilCase coil

Case coilCase coilCase coil A

B8 inch

minimum

NO

“B” is recommended because liquid hammer will not effect the fittings also expansion and contraction will take place on liquid header not the branch fittings.

Denotes TEV

“A” is not recommended because of liquid hammer also expansion and contraction will “work” the elbow and cause a failure.

Liquid Line Piping for Multi evaporators or cases with defrost

Refrigerant Piping Practices

Page 175: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Split system, 100 ft apart, evaporator above condensing unit

Refrigerant Piping Practices

Evaporator coil

Condensing unit

Evaporator coil A

B

Condensing unit

continued …...Denotes TEV

Page 176: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Split A/C system, 100 ft apart, evaporator above condensing unit

Refrigerant Piping Practices

Evaporator coil

Condensing unit

Evaporator coil A

B

Condensing unit

90 feet

10 feet

continued …...Denotes TEV

Page 177: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Split A/C system, 100 ft apart, evaporator above condensing unit

Refrigerant Piping Practices

Evaporator coil

Condensing unit

Evaporator coil A

B

Condensing unit

90 feet

10 feet

10 feet

90 feet

Note: 100 feet of 7/8 tubing will hold 25 pounds of liquid R-22 refrigerant.

“B” is recommended because only 10 ft of liquid refrigerant (10 % of 25 = 2.5 lbs) will drain on off cycle into condensing unit, less chance of damage on start-up.

Note: 100 feet of 7/8 tubing will hold 25 pounds of liquid R-22 refrigerant.

“A” is not recommended because 90 ft of liquid refrigerant (90 % of 25 = 22.5 lbs) will drain on off cycle into condensing unit,damage compressor on start-up.

Denotes TEV

Page 178: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Same Circuit Multi Evaporators with Hot Gas Defrost

Refrigerant Piping Practices

Hot Gas Defrost Line

EvaporatorEvaporator

EvaporatorEvaporator A

B

Hot Gas Defrost Line

continued …...Denotes TEV

Page 179: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Same Circuit Multi Evaporators with Hot Gas Defrost

Refrigerant Piping Practices

Hot Gas Defrost Line

EvaporatorEvaporator

EvaporatorEvaporator A

B

Hot Gas Defrost Line

continued …...Denotes TEV

Page 180: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Same Circuit Multi Evaporators with Hot Gas Defrost

Refrigerant Piping Practices

Hot Gas Defrost Line

EvaporatorEvaporator

EvaporatorEvaporator A

B

Hot Gas Defrost Line

“A” is not recommended becausewhen the ‘Hot Gas” is off liquidrefrigerant can be feed from oneevaporator to the other evaporator.

“B” is recommended because thereis a check valve in the Hot Gas lineleading to the side inlet “Tee”.Thereby preventing liquid refrigerantfrom entering the other evaporatorwhen Hot Gas defrost is not in use.

Denotes TEV

Page 181: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Liquid Line Feed to Stacked Evaporator Coils

Refrigerant Piping Practices

B

Condensing unitCondensing unitReceiver Receiver

Evaporator

Evaporator

Evaporator

Evaporator

Evaporator

Evaporator

A

continued …...Denotes TEV

Page 182: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Liquid Line Feed to Stacked Evaporator Coils

Refrigerant Piping Practices

A B

Condensing unitCondensing unitReceiver Receiver

Evaporator

Evaporator

Evaporator

Evaporator

Evaporator

Evaporator

continued …...Denotes TEV

Page 183: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Liquid Line Feed to Stacked Evaporator Coils

Refrigerant Piping Practices

Evaporator

Evaporator

Evaporator

B

Condensing unitCondensing unitReceiver Receiver

Evaporator

Evaporator

Evaporator

A

“A” is not recommended because of the “static head”ofliquid, only the bottom coil will receive a full column ofliquid, the middle would have liquid and some vapourand the top coil could receive little liquid and the majorityof the vapour therefore poor system performance. Vapourbubbles will rise to the top coil.

Note the receiver, because there is a two phase conditionin the receiver little or no sub-cooling is available.

“B” is recommended as all coils will be feed equalquality refrigerant therefore having balancedevaporators and good performance.

Denotes TEV

Page 184: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Suction Lines from Stacked Evaporator Coils

Refrigerant Piping Practices

Condensing unitCondensing unitReceiver Receiver

Denotes TEV

B

Evaporator

Evaporator

EvaporatorTEVbulb

Evaporator

Evaporator

Evaporator

ATEVbulb

Page 185: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Suction Lines from Stacked Evaporator Coils

Refrigerant Piping Practices

Condensing unitCondensing unitReceiver Receiver

Denotes TEV

B

Evaporator

Evaporator

EvaporatorTEVbulb

Evaporator

Evaporator

Evaporator

ATEVbulb

Page 186: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Suction Lines from Stacked Evaporator Coils

Refrigerant Piping Practices

Condensing unitCondensing unitReceiver Receiver

Denotes TEV

The remote TEV bulbs and external equalizing line connectionsmust be located so that the conditions effecting one valve can-not influence the other valves. The double elbow configurationallows the corresponding section of the evaporator coil to drainfreely while isolating the remote bulb and equalizer line from the suction pressure and temperature of the above coil section.

Arrange the suction line so that the refrigerant vapour leavingthe top coil flows downwards, connection to the pipes leavingthe other coils. This manifold pipe should drop below the lowestcoil outlet before turning upward. This allows all of the oil todrain out of the evaporators and congregate before it must becarried up a vertical riser.

The single suction line then rises above the height of the evaporator coils, preventing refrigerant and oil inside the evaporator from free draining into the suction line, and towardsthe compressor, when the system is off.

Double elbow configuration

Must drop below lowestheader outlet

Must rise above height of evaporators

B

Evaporator

Evaporator

EvaporatorTEVbulb

Evaporator

Evaporator

Evaporator

ATEVbulb

Page 187: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Liquid Line Feed to Stacked Evaporator Coils

Refrigerant Piping Practices

Evaporator

Evaporator

Evaporator

Condensing unitReceiver

“A” is not recommended because of the “static head”ofliquid, only the bottom coil will receive a full column ofliquid, the middle would have liquid and some vapourand the top coil could receive little liquid and the majorityof the vapour therefore poor system performance. Vapourbubbles will rise to the top coil.

Note the receiver, because there is a two phase conditionin the receiver little or no sub-cooling is available.

Denotes TEV

" A "To the low side of system

Capped

Page 188: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Liquid line toremote evaporators

Receiver

Catch-All

See-All

Solenoid

Liquid Hammercan split LR 90º ells

" Stand pipe " of a minimum length (12”) will help prevent split ells caused by liquid hammer.

Problem

Modern ServiceTechnician

Owner

Page 189: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Roof Line

LiquidCondensate line

Receiver

Liquid Line

Suction Line

Discharge Line

Condenser

Compressor

Controlling Liquid Line Pressure

High Pressure Vapour LineORD - 4

ORI -Outdoorambient

Indoorambient

hot gas binging.ppt

Considerations: 1 pisg pressure lifts ref. 1.8 ft.Binding line equals pressure between receiverand condenser. If receiver 20 pisg higher ref.will not flow down.

ORD-4-20ORD-4-25ORD-4-30ORD-4-35

220205

Page 190: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

ORD-4-35

ORD-4-20ORD-4-25ORD-4-30ORD-4-35

*

* is standard

ORD-4-35

DischargePressure240 psig

ReceiverPressure175 psig

" A "" B " " C "

Refrigerant Flow

Normal operation A to B is a ∆ 65 psigIf B pressure drops >5 ORD #1 opens

# 1 # 2

Series Refrigerant ORD Operation

Page 191: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Roof Line

LiquidCondensate line Hot Gas Binding Line

Receiver

Liquid Line

Suction Line

Discharge Line

Condenser

Compressor

Hot Gas Binding

High Pressure Vapour LineORD - 4

ORI -Outdoorambient

Indoorambient

hot gas binging.ppt

Considerations: 1 pisg pressure lifts ref. 1.8 ft.Binding line equals pressure between receiverand condenser. If receiver 20 pisg higher ref.will not flow down.

ORD-4-20ORD-4-25ORD-4-30ORD-4-35

220205

R-22

100 = 196105 = 210110 = 226115 = 242120 = 260125 = 278

226

ORI -

Page 192: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

What Does This Tell You ?

Page 193: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

What Does This Tell You ?

Page 194: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Result …….

Page 195: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Refrigerant Migration Protection

A description of methods, using a Liquid Line Solenoid Valve (LLSV) installed in the liquid line just before the metering device, to prevent liquid refrigerant in the evaporator from flowing intocrankcase of the compressor during the off cycle and causing a flooded compressor start.

by Garth Denison

1. Solenoid Drop (minimum protection)

When the cooling thermostat is satisfied, the LLSV is de-energized closing off the liquid line. The compressor also cycles off. The closing of the liquid line prevents any refrigerant migration to the low side of the system. Since there maybe refrigerant remaining in the low side of the system which could migrate to the lubricant in the crankcase of the compressor, it is highly recommended that a crankcase heater be used with this system.

~

~

~

~

LLSV

CC

TC

L1 L2

Legend

CC – compressor contactorCR – control relayHP – high pressure contacts L1-L2 control powerLLSV – liquid line solenoid valveLP – low pressure contactsOL – compressor overloadsTC – thermostat cooling

Page 196: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

2. Pump Down ControlWhen the cooling thermostat is satisfied, the LLSV is de-energized closing off the liquid line.With this control, the compressor remains operating drawing the refrigerant out of the low side of the system until the low side pressure is low enough to open the low pressure switch(LPS) stopping the compressor.

If the LLSV leaks, the low side pressure will increase to close the LPS starting the compressor.The compressor will continue to cycle as long as the LPS is closed. This repeated cycling will cause the compressor winding to overheat and lead to compressor failure.

Also, if the compressor is equipped with suction pressure unloaders, leaking through theunloader will cause the compressor to rapid cycle. Therefore it is not recommended to usea pump down control on a system with suction pressure unloaders.

~

~

~

~

CC

LLSV

TC

L1 L2

HP LP OL

Legend

CC – compressor contactorCR – control relayHP – high pressure contacts L1-L2 control powerLLSV – liquid line solenoid valveLP – low pressure contactsOL – compressor overloadsTC – thermostat cooling

Refrigerant Migration Protection

Page 197: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

3. Pump Out Control:

This system operates similar to the pump down control, only with a pump out control, a compressor lock-out relay is used to prevent the compressor from cycling on the LPS.With the lock-out relay, the compressor reverts back to the cooling thermostat control and will not restart until the thermostat senses a need for cooling.

A crankcase heater should be used in conjunction with the pump out control.

~

~

~

~CC

L1 L2

CR

TC

HP LP OL

LLSV

CR1

CR2

CC

Legend

CC – compressor contactorCR – control relayHP – high pressure contacts L1-L2 control powerLLSV – liquid line solenoid valveLP – low pressure contactsOL – compressor overloadsTC – thermostat cooling

Refrigerant Migration Protection

Page 198: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Sound !!!!!

Page 199: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Harmonics … Pulsations What are They ?

Condensations and refractions are clusters of variouslengths of sound waves that catch up with each otherwithin the piping system. This causes the amplitude of the sound level to increase causing loud disturbingpulsating harmonic sounds.

Possible means of limiting or greatly reducing these harmonics.

• Add mass and additional clamping to discharge line, attach angle iron to the dischargeline with hose clamps. (eg: 10” x 1-1/2” x 1-1/2” x ¼” angle iron)

• Change discharge piping configuration, this changes length of reverberation channel.• Install sound pulsation plate between compressor and discharge service valve.

These plates are designed to create a 5 psi backpressure thereby changing the soundwave length and frequency that is being emitted from the compressor.

• Change compressor rotation as gas passages are not equal in length.• Move pressure operated unloader to other side bank.• Install large discharge muffler to smooth out pulsations.• Change the type of compressor from reciprocating to dynamic compression.• All field piping must be of “Prime” value, not divisible equally by 2, 3, 4 or 6. • A lubricant change will lower the sound level … R-22 POE to R-22 MO or AB

Page 200: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Discharge Pulsation PlatesCarlyle Compressors

06DA818 (6D48) is 5/16”06DA824 (6D68) is 3/8”06DA337 (6D73) is 7/16”06DA537 (6D75) is 7/16”

06E250 is 1/2” 06E275 is 5/8”06E260 is 9/16” 06E299 is 23/32”06E266 is 9/16”

All restrictor plates 1/8” thick, centre hole diameter as specified below.

1 ¾

” 2 ½

½” dia. (4)

⅜” dia.(2)

06D series06E series

Remember .. Two (2) service valve gaskets are required with each plate, one for each side when restrictor installed.

Page 201: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Mufflers & Baffle Plates

Discharge Pulsation PlatesCarlyle Compressors

Assist in pressure pulsation and sound reductions.Size mufflers per discharge line size or larger.Size baffle plates per application recommendations.

Baffle Platesaka .. pulsation plates

or muffler plates

Page 202: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Discharge Pulsation Plates

Copeland:Application Recommendations of Compressor Muffler Plates

Application Engineering Bulletin AE-4 - 1181

Page 203: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Discharge Pulsation PlatesCarlyle:

Application Recommendations With Baffle PlatesCarlyle Technical Bulletin 99T – 4

Page 204: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Discharge Pulsation PlatesCarlyle:

Application Recommendations With Baffle PlatesCarlyle Technical Bulletin 99T – 4

Page 205: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

An Important IndustryDistinction

There is a common misunderstanding within the refrigeration industryaround the refrigerant Pressure Enthalpy (Ph) diagram. Some industryindividuals are under the impression that a refrigerant Pressure Enthalpy(Ph) diagram and a Mollier diagram are synonymous with each other. This is misleading and incorrect, they are NOT identical, nor are they interchangeable. The Mollier diagram is the European version of the Anglo-American Psychrometric chart. The Psychrometric chart and theMollier diagram are identical in content but not in appearance. Both thePsychrometric chart and the Mollier diagram deal with the properties andmeasurements of AIR not the properties and measurements of “Refrigerants”. Only the Pressure Enthalpy (Ph) diagram deals with theproperties and measurements of refrigerants.

Mollier diagramPh diagram

Something to think about.

An Important IndustryDistinction

Page 206: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Future … Crystal Ball

Around the Corner !!

R-404A

R-134a

Recovery

R-407C

R-410A

R-507A

Page 207: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

When .. 5 ≈ 31+ ≈ 5 = 34

Years

R-11R-12R-22R-500R-502

1986

R-134aR-404AR-407CR-410AR-507

2020

R-123, R-124, R-125, R-134a, R-143a, R-218, R-400, R-401A, R-401B, R-401C,

R-402A, R-402B, R-403A, R-403B, R-404A, R-405A, R-406A, R-407A,R-407B, R-407C, R-408A, R-409A,R-410A, R-410B, R-412A, R-414A,R-414B, R-416A, R-417A, R-420AR-421A, R-422A, R-423A, R-424A.

Simplicity is Around the Corner

United Nation Environmental Program (UNEP) a.k.a. Montreal Protocol

Page 208: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Domestic / White goods, Vending:R-134a .. Rotary or Scroll

Auto A/C:R-134a .. Future R-744 (CO2)

Residential A/C & HP: < 5 tonR-410A .. Scroll

Commercial A/C & HP 5 thru 100 ton:R-410A .. Scroll, (Screws R-134a larger units)

Commercial Refrigeration:R-404A / R-507 Reciprocating or Screw,(Scroll under development)

Large tonnage 100 thru 10,000 ton:R-134a .. Centrifugal or Screw

Retrofit market:A/C DX applications .. R-407CA/C Flooded .. R-134aRefrigeration / Process .. R-404A / R-507

Application Future In North Americaas seen by Garth Denison

Original refrigerantsR-11R-12R-22

R-500R-502

Interim refrigerantsmorgasbord

(31+)

Future refrigerantsR-134aR-410A

R-404A / R-507R-407C

1986

2020

Page 209: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

" What’s on the Horizon "

customer

System Engineer

Page 210: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

CO2 Direct Expansion – MT and LT

LT 181 kWor

51.5 Ton

Page 211: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Graphic Representation of Compressing Details

CO2 or R-744 is a TranscriticalRefrigerant

Page 212: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

MT CO2 Multi Compressor Set for Field Test .. Qo = 160 kW or 45.5 tons

Page 213: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 214: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 215: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

ICE

Beautiful, Scenic, Dangerous,Hazardous, Costly

Page 216: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasiesBeautiful

Page 217: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Scenic

Page 218: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Dangerous

Page 219: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Hazardous

Page 220: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Frozen / Broken Waterline in Garage !!!!

Very Costly

Page 221: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

LOOKING DEEP INTO PROBLEM AREAS

Page 222: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Refrigeration Ice Plants

Canary " Passing "

R-717 …. NO Contact LensesVaseline in groin and arm pits !

Safety Rope / Buddy System

Page 223: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

When mixing a calcium chloride brine for freezing ice creamwith a desired freezing point of minus 30°F or lower is neededand no hydrometer is available use a large Irish potato, if the potato does not float in the brine mixture add more calcium chloride to the brine solution.

Calcium Chloride Brine minus 30°F

Page 224: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

You exited FastFastBlue Dancing Flame

Methyl Chloride

Page 225: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

SO2

Rats .. Cockroaches disappearedPlants .. Grass, Produce diedCanaries, Budges, Parrots goneLong hoses, water, open windows

SO2 no smell, carbon filters

Page 226: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Unique Historical ServiceTechniques

Do you remember: ………….

When hot water froze faster than cold water !!!

Temper proofing controls .. clear nail polish.

Service trucks carried sanitary napkins (Kotex)

Service trucks carried feminine deodorant spray (FDS)

Service trucks carried petroleum jelly (Vaseline)

Service trucks carried Vicks Vapor Rub or Basil

Page 227: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

You ARE the Perfect HVAC&R System

Compressor _________________Controller ___________________Control system _____________Piping network _Refrigerant ______________Evaporator ____________Lubricant _______Condenser __________________Head pressure ________Capacity control __________Filter / Drier _________________Purge system _______________Power supply _________________Fine Tuning _______________

HeartBrain

NervesCardiovascular system

Life bloodSkin / Sweat

(LDL / HDL) CholesterolLungs

Blood pressureHeart rate

LiverKidney

DietExercise

Comparing Systems

" Education is Just the Beginning "Modern ServiceTechnician

Page 228: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Diagnostic Means

Manifold gauges _______________Periodic check __________________Thermometer ___________________________Fluid ailments (refrigerant, lubricant, H2O) _______Touch, Sound, Sight, Smell _____________________Maintenance ________________________Superheat / Sub-cooling _________________________Sight glass _____________________________Know how / Experience, Intuitiveness _____Preventative Care _________________________

Manometer / StethoscopeNon-destructive testing

TemperatureLaboratory analysis

SensesRoutine physicals

PulseMRI / X-Ray

Diagnostic skillsMedication

Modern ServiceTechnician

You ARE the Perfect HVAC&R System

" Education is Just the Beginning "

Page 229: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Cold W.A.R. IntroducedJune 2003

W hether it’sA ir ConditioningR efrigeration

Page 230: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Sporlan Division of Parker Hannifin has introduced a new service oriented no charge information support program titled“Cold W.A.R.” This monthly e-mail based only information network program is designed to provide you, the service technician, with a collection of associated technical informationtopic papers in a simple comprehensive format. Don’t miss thisopportunity to increase your existing knowledge base. Sign uptoday and start receiving your personal direct e-mail copy.

Page 231: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Page 232: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Second Tuesday each month

[email protected]

NEW

Page 233: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

CONCLUSIONHaving been through this presentation,

it would be quite natural for you toconclude that it is virtually

impossible to design aperfect refrigeration

system.

This is probably true.

Page 234: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

“Refrigerant molecules are square, through constant and continuoususe the corners are rounded off, that’s why you need to add

additional refrigerant !!"

This reaction is similar to a box of cereal, it started off fullbut through constant moving and shaking

it settles and now looks only half full.

Why do I need to continuously add morerefrigerant every year?

Thought Provoking !!!

Customer

Page 235: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Why do Women Live Longer

then Men ?

Page 236: Cooling system idiosyncrasies 2006

c:\sporlan 2006\cooling idiosyncrasies

Visit us at www.sporlan.com

The Sporlan Valve Division, Parker Hannifin assumes no obligations or liability for any advice furnished or for any results, property damage or personal injury including death that may result with respect to the use of this information. All such advice is given and accepted at users risk. This disclosure of information herein is not a license to operate under, or a recommendation to infringe any patent of Sporlan Division of Parker Hannifin or others.

Dated May 2006Supersedes

® Registered trademark of Sporlan Valve Division, Parker Hannifin Corporation, Cleveland Ohio USA© Copyright 2005 by Sporlan Valve Division, Parker Hannifin Inc