Cooling system idiosyncrasies 2006
-
Upload
politeknik-negeri-bali -
Category
Documents
-
view
1.878 -
download
19
Transcript of Cooling system idiosyncrasies 2006
c:\sporlan 2006\cooling idiosyncrasies
by
Garth Denison
Sr. Product Application EngineerSporlan Valve DivisionParker Hannifin Canada
2006 / 2007 SeminarCooling Systems
" Idiosyncrasies "
There is humor in those
Cooling Idiosyncrasies.
c:\sporlan 2006\cooling idiosyncrasies
" Cooling Systems Idiosyncrasies "
A behavioral characteristic unique to an individual or group
The Sporlan Valve Division, Parker Hannifin assumes no obligations or liability for any advice furnished or for any results, property damage or personal injury including death that may result with respect to the use of this information. All such advice is given and accepted at users risk. This disclosure of information herein is not a license to operate under, or a recommendation to infringe any patent of Sporlan Division of Parker Hannifin or others.
® Registered trademark of Sporlan Valve Division, Parker Hannifin Corporation, Cleveland Ohio USA© Copyright 2005 by Sporlan Valve Division, Parker Hannifin Inc
c:\sporlan 2006\cooling idiosyncrasies
Service Guide to Various
System Idiosyncrasies
Bull HeadingSplit Condensers
above 50°F
below 50°F
c:\sporlan 2006\cooling idiosyncrasies
35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120
DRY BULB TEMPERATURE - °F
10 15 20 25
30
35
40
45
50
55
55
60
60
EN
THA
LPY
-BTU
PER
PO
UN
D O
F D
RY
AIR
ENTHALPY - BTU PER POUND OF DRY AIR
15
20
25
30
35
40
45
50
ENTHALPY - B
TU PER P
OUND OF D
RY AIR
SATURATION TE
MPERATURE - °F
.002
.004
.006
.008
.010
.012
.014
.016
.018
.020
.022
.024
.026
.028
35
3540
40 45
45 50
50 55
55 60
6065
6570
70
75
75
80
80
85 WET BULB TEMPERATURE - °F
85
90
10% RELATIVE HUMIDITY
20%
30%
40%
50%
60%
70%
80%
90%
12.5
13.0
13.5
14.0 VOLU
ME - CU
.FT. PER LB. DRY AIR
14.5
15.0
HU
MID
ITY
RAT
IO -
POU
ND
S M
OIS
TUR
E P
ER
PO
UN
D D
RY
AIR
.05
.1
.15
.2
.25
.3
.35
.4
.45
.5
.55
.6
.65
.7
.75
.8
.85
.9
.95
1
1.05
1.1
1.15
1.2
1.25
1.3
1.35
VA
POuR
PR
ES
SU
RE
-IN
CH
ES
OF
ME
RC
UR
Y
010
2025
30
35
40
45
50
55
60
65
70
75
80
85
DEW
PO
INT
TEM
PER
ATU
RE
-°F
1.000.95
0.90
0.85
0.80
0.75
0.70
0.65
0.60
0.55
0.50
0.45
0.40
0.350.300.250.200.15SENSIBLE HEAT RATIO = Qs / Qt
SE
NS
IBLE
HE
AT R
ATIO
= Q
s / Q
t
R-410A
CT 162 °F, CP 715 psia
Note importance ofsub-cooling
Bull Heading
above 50°F
Split
Con
dens
ers
below 50°FAB
POE
MO
c:\sporlan 2006\cooling idiosyncrasies
For 2006
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
Refrigerant Science of Yester Year
Temp / Press psigName Formula Flammable 0°F and 85°F
F-12 CCl2F2 No 9.2 91.7
Sulphur Dioxide SO2 No 8.9” 50.6
Ammonia NH3 Yes (16 to 25) 15.7 151.7
Butane C4H10 Yes (1.6 to 6.5) 15.0” 26.2
Iso Butane C4H10 Yes (1.8 to 8.5) 6.3” 43.9
Carbon Dioxide CO2 No 293.9 1012.3
Methyl Chloride CH3Cl Yes (8.1 to 17.2) 4.1 79.4
Ethyl Chloride C2H5Cl Yes (3.7 to 12) 21.6” 11.9
Methylene Chloride CH2Cl2 Yes (8.1 to 17.2) 27.9” 9.9”
Dichlorotetrafluoroethane C2Cl2F4 No 17.8” 21.0
Source: Frigidaire engineering manual Nov. 15, 1938
c:\sporlan 2006\cooling idiosyncrasies
Global Warming … Kyoto
c:\sporlan 2006\cooling idiosyncrasies
" Typical Receiver Types "
c:\sporlan 2006\cooling idiosyncrasies
Receivers
For receivers having an internal diameter of 6 inches (150 mm) or smaller: ARI 495, UL listed, steel, brazed, 400 psig (2760 kPa) pressure rating, with pipe threaded female access fittings for inlet, outlet, and pressure relief valve.
Receivers larger than 6 inches (150 mm) diameter: ARI 495, welded steel,tested and stamped according to ASME Boiler and Pressure Vessel Code:Section VIII; 400 psig (2760 kPa) pressure rating, with pipe threaded femaleaccess fittings for inlet, outlet, pressure relief valves, and a liquid level indicator.
Typical receiver accessories ..
Relief device (valve or fusible plug)
Dual relief valve saddle assemblyLiquid level indicator / alarmSight glassReceiver heaterInsulated receiverAccess / Isolation valves
c:\sporlan 2006\cooling idiosyncrasies
Typical Receiver Types
From condenser To evaporator
Receiver
indicates vapour
indicates liquid
Minimum refrigerant charge is 15% of receiverscapacity to ensure a liquid seal at the dip tube.
Liquid Line
Surge Receiver
No minimum receiver refrigerant charge needed
Receiver styles:vertical
horizontal
Vent line
c:\sporlan 2006\cooling idiosyncrasies
System with Receiver
The circled area represents a typical receiver installed in the liquid condensate line.
Receiver may or may not effect the quantity of sub-cooling depending onrefrigerant’s speed, receivers ambient and system’s refrigerative effect.
c:\sporlan 2006\cooling idiosyncrasies
System with Surge Receiver
The circled area represents a typical surge receiver installed in the liquid line.
A surge receiver will not effect the quantity of sub-cooling. Refrigerantnot required to accommodate the load will back into the surge receiver.
c:\sporlan 2006\cooling idiosyncrasies
Receiver Components & Accessories
Level indicators / Alarm actuators
Typical relief valve
Dual relief valve assembly
Pressure transducer,gauge and relief valve
Straight-thrurelief valve
Poly Tetra FluoroEthylene (Teflon)
&Fusible plugs
c:\sporlan 2006\cooling idiosyncrasies
R.V.Setting
Tolerance
+ 10 % R.V. Full Open
Maximum system operating pressure
Relief Valve (R.V.) Setting
- 10 % Potential R.V. “Seep” Point
Relief Valve Parameters
Relief valve parameters as a percent of R.V. set pressure.
PSI
440
400
360
320
Suction header
High PressureReceiver
Reliefvalves
Added protection is a High / Low By-pass valve if system pressure nears thepotential relief valve “Seep” Point.
Source: Henry Technologies
A typical installation with a pressure vessel havinga maximum working pressure of 400 PSI might be:
Relief Valves 400 PSI: Set at the design working pressure of the vessel OR25 % higher than the maximum working pressure of the system.
High / Low: Set at approximately 80 – 85% of relief valve setting. 330 PSI
Relief Valve: Table below for code parameters for a400 PSI relief valve. IN
OUT
High / LowBypass valve
c:\sporlan 2006\cooling idiosyncrasies
Receiver Components & Accessories
Synthetic ester oil based greaseusing a lithium soap.
SKF system grease LGLT-2
Operating temperature range
-55ºC to 110ºC
-65ºF to 230ºF
Indoors Outdoors
c:\sporlan 2006\cooling idiosyncrasies
Receiver Heaters
Various Heater TypesStrap-on heaterInsertion heaterEmersion heaterPeel & Stick foil backedMagnetic heater stripsBlanket heater
c:\sporlan 2006\cooling idiosyncrasies
" Reversing Fuses "
For testing purposes ONLY …How can a technician change rotationon a three phase application without
moving a wire ?
Thought Provoking !!!
c:\sporlan 2006\cooling idiosyncrasies
Reversing Fuses
EXTREME CAUTION
Uninstalled Fuses
Blo
wn
/ Bad
Fus
e
Blo
wn
/ Bad
Fus
e
Heavy Wire
Heavy Wire
Fuse
Fuse
c:\sporlan 2006\cooling idiosyncrasies
Reversing Fuses
EXTREME CAUTION
Installed Fuses
Blo
wn
/ Bad
Fus
eB
lown / B
ad FuseHeavy WireFuse
Fuse
c:\sporlan 2006\cooling idiosyncrasies
" Receivers and their Affects "
c:\sporlan 2006\cooling idiosyncrasies
Air Cooled Condenser Typical Split Condenserc/w Standard Receiver
Liquid lines
Summer
ORI / OROA
Restrictor tube tolow side may beused to controlpump out rate ofinactive condenser
To evaporator
Receiver
R-22 condenser converted to R-404A,approximately a 10% gain in capacity.
Minimum refrigerant charge is 15% of receiverscapacity to ensure a liquid seal at the dip tube.
c:\sporlan 2006\cooling idiosyncrasies
Air Cooled Condenser
Liquid lines
Summer
ORI / OROA
Restrictor tube tolow side may beused to controlpump out rate ofinactive condenser
8, 12 or 16D
To evaporator
Receiver
Typical Split Condenserc/w By-pass Receiver
R-22 condenser converted to R-404A,approximately a 10% gain in capacity.
Shown de-energized
c:\sporlan 2006\cooling idiosyncrasies
Three Way Solenoid
From condenser
To receiver
To liquid line De-energized
Energized
1. High pressure refrigerant 2. Piston vent line3. Open to low pressure
8D, 12D, 16D
c:\sporlan 2006\cooling idiosyncrasies
De-energized
c:\sporlan 2006\cooling idiosyncrasies
Energized
c:\sporlan 2006\cooling idiosyncrasies
Air Cooled Condenser
Liquid lines
Summer
ORI / OROA
Restrictor tube tolow side may beused to controlpump out rate ofinactive condenser
Liquid Line
Surge Receiver
No minimum receiver refrigerant charge needed
Typical Split Condenserc/w Surge Receiver
R-22 condenser converted to R-404A,approximately a 10% gain in capacity.
Vent to condenser inlet,check valve installed
in this line.
“weir”
receiverinlet / outlet
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
Why Typical Split Condenser Vertical Drop ?
Air Cooled Condenser
Split Condenser Circuits
Liquid lines
ORIT / OROA
Restrictor tube tolow side may beused to controlpump out rate ofinactive condenser
** Note: ARI check valve acceptable leak rate is 750 ml/minuteone US gal = 3.8 liters (1 liter = 1000 ml)
** Typical 6 ft.
Density Specific. 1 psiRef. lb/ft3 Gravity Lift in ft.
R-22 74.5 1.20 1.93R-134a 75.1 1.21 1.91R-404A 65.5 1.05 2.20R-407C 70.8 1.14 2.03R-507A 65.5 1.05 2.20
R-410A 67.7 1.09 2.12
R-12 81.8 1.31 1.76R-502 76.0 1.22 1.89R-718 62.3 1.00 2.31
Specific Gravity = Density / 62.311 psi Lift in ft. = 2.31 / SG
Densities are at 25ºC or 77ºF
23.222.926.424.426.4
25.5
21.122.127.7
Lift ininches
c:\sporlan 2006\cooling idiosyncrasies
" Multi Receivers and their Affects "
c:\sporlan 2006\cooling idiosyncrasies
Variances in Lift Verses Density .. @ 1 psi
one psi
Typical refrigerant1.8 feet or 21.6 inches
Refrigerants
Water H2O2.31 feet or 27.7 inches
Water
one psi
Typical lubricant2.5 feet or 30 inches
Lubricants
one psi
Refrigerant R-7173.9 feet or 47 inches
Ammonia
one psi
c:\sporlan 2006\cooling idiosyncrasies
Series ReceiversWater cooled condensersInsufficient existing capacity
Normally 2 or 3 in series
Multi Receivers
Parallel ReceiversDifficult in controlling liquid levels
Possible liquid in one and vapour in other
c:\sporlan 2006\cooling idiosyncrasies
When Supplemental Receiversare Needed
Auxiliary receivers may be necessary when refrigerant pumpdown capacity is less than the proper operational charge of refrigerant in the system. This condition sometimes occurs inwater cooled systems where the condenser-receivers have limited capacity and it can alsooccur in any system where large evaporators or long liquid lines are used or where the pumpdown liquid solenoid valves cannot be located close to the TEV’s. To correct this condition, an additional receiver with the necessary holding capacity should be installed in series with and close to the outlet of the main receiver on the compression unit.
The auxiliary receiver should be installed on the same level or below the main receiver on thecompression unit. Both the main and auxiliary receiver must have their own service valves,fusible plug or relief valve. The liquid line sightglass, drier and the liquid line to the evaporatorshould then be connected in the normal manner to the service valve which is installed on theoutlet fitting of the auxiliary receiver.
c:\sporlan 2006\cooling idiosyncrasies
Supplemental Receivers
" Series " Receivers
Main
Auxiliary
Receiver
Catch-All
See-All
Solenoid
Catch-All
See-All
Solenoid
c:\sporlan 2006\cooling idiosyncrasies
Typical Copeland " C " Line Condensing Units
Liquid InOutletValve
Cross sectional view of two refrigerant receivers in series
one psi
Typical refrigerant2.0 feet or 24 inches
Refrigerants
c:\sporlan 2006\cooling idiosyncrasies
" Effects of Sub-cooling "
An Idea Whose Time Has Come
c:\sporlan 2006\cooling idiosyncrasies
Sub-cooling
The reduction of the liquid refrigerant’s temperatureto a point below its saturation temperature.
Sub-cooling is always the removal of sensible heatonly from a liquid phase fluid.
Definition:
Up to 20% increase in Btu loadingDecrease in electrical usage as much as 25%Reducing pull-down time up to 50%Provide more uniform refrigerating temperaturesReduces first cost, by permitting down sizing ofcompressors in new system.
Obtainable:
c:\sporlan 2006\cooling idiosyncrasies
Understanding Heat in the five Regionsof a Ph Diagram
Sensible heatregions
Latent heatregion
Satu
rated
liqui
d lin
e …
Bubbl
e Poin
t
Satu
rate
d va
pour
line
…D
ew P
oint
SuperheatedVapour region
SubcooledLiquid region
" Quality "(% vapour)
Liquid / Vapourmixture region
0.1 0.2 0.3
0.4 0.5 0.6
0.7
0.8
0.9
Solid region Triple point
Critical PointGaseous region
c:\sporlan 2006\cooling idiosyncrasies
Consider the Following:
The compressor is a fixed displacement pump. It is pumping a certain number of CFM (pounds) of refrigerant through thecycle, and really doesn’t care how many Btu’s are in each oneof those pounds. So by increasing the number of Btu’s perpound, we can increase the capacity of the system while notincreasing the mass flow of refrigerant.
Increasing Sub-cooling Reduces Flash Gas,Increases Net Refrigeration Effect.
c:\sporlan 2006\cooling idiosyncrasies
Sub-cooling can:
1. Increase capacity2. Decrease electrical usage3. Reduce equipment maintenance4. Produce better temperature control5. Reduce pull-down time after defrost6. Reduce first costs
c:\sporlan 2006\cooling idiosyncrasies
What do the headlights on a motor car and on a bus have to do with you, the
refrigeration and air conditioningtechnician ?
Thought Provoking !!!
c:\sporlan 2006\cooling idiosyncrasies
MC and B tanks
40 cu ft
" B " Bus10 cu ft
" MC " Motor Car
(acetylene)
MCB
Acetylene HeadlightsHenry Ford Museum, Dearborn Michigan
c:\sporlan 2006\cooling idiosyncrasies
" Accomplishing Sub-cooling "
c:\sporlan 2006\cooling idiosyncrasies
Types of Sub-cooler
Ambient sub-coolingAirWaterRefrigerant
Mechanical sub-coolingIntegral part of systemSelf contained refrigeration systemUsually brazed plate heat exchangers
Both styles actually refrigerate the refrigerant.
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
PREFERRED
ACCEPTABLE
NEVER
Installation & Mounting ...
For Single Phase, Liquid-to-Liquid Applications
c:\sporlan 2006\cooling idiosyncrasies
Installation & Mounting ...Effect of Inclination on Two Phase, Refrigerant Applications
55
3030
45
45 60
60
90
90
0
-3%-2%-10%
-16%
-38%
-9%
-15%
-37%
Evaporator -No measurable difference
within ± 5º of vertical.
Based on testing conducted by NIST. R-22 evaporator.
c:\sporlan 2006\cooling idiosyncrasies
Installation & Mounting ...Effect of Inclination on Two Phase, Refrigerant Applications
55
3030
45
45 60
60
90
90
0Condenser -
No measurable difference.
Short term limited test.
Based on testing conducted by NIST. R-22 evaporator.
c:\sporlan 2006\cooling idiosyncrasies
Typical Plate to Plate Heat Exchangers,Sub-coolers
Sub-coolers
The brazed plate heat exchanger is substantiallysmall than other technologiesthat could be used.
The EPR valve should normally be set to maintaindesired liquid temperature. This is normally 50°F
but may be as low as 40°F for some systems.
Mechanical sub-coolers leavingliquid refrigerant temperature isusually controlled by a temperaturesensor on the condensers liquidcondensate drop leg.
c:\sporlan 2006\cooling idiosyncrasies
Refrigeration Retrofitting R-22 to R-404A
Regaining the Lost Capacity
from receiver
toliquid manifold
TEV’s
tosuction manifold
EPR
solenoids
Plate to PlateHeat exchanger
Plate to PlateHeat Exchanger
c:\sporlan 2006\cooling idiosyncrasies
Specific Heat .. the amount of heat needed to raise / lower onepound of a substance one F°. (Btu/lb. F° sensible heat)
Thermodynamic 411
R-22
R-404A
Btu/lb F°Cp 0.300
Cp 0.367
R-407C
R-410A
Btu/lb F°Cp 0.368
Cp 0.440
Refrigerant Liquids
Source DuPont AG3 and AG2
c:\sporlan 2006\cooling idiosyncrasies
Sub-cooling Calculation Example
R-22 has a Specific heat (Cp ) of 0.300
Example:
Liquid refrigerant entering sub-cooler is 100ºF
Desired refrigerant temperature leaving sub-cooler 50ºF
Formula used is Mass x Specific heat (Cp) x Delta temperature
Refrigeration effected needed per pound of mass flow is 1 x 0.300 x 50 = 15 btu’s
A system having a mass flow rate of 13 pounds per minute needs 13 x 15 = 195 btu’s or 1 ton
Using the same conditions:360,000 btu’s (30 ton LT) rack would need approximately 105 lbs/min
Sub-cooling capacity 105 x 0.300 x 50 = 1575 btu’s or 1575 / 200 = 7.9 tons
TEV’s for Sub-cooler .... One three tons and one five ton
c:\sporlan 2006\cooling idiosyncrasies
Plate to Plate Heat Exchanger
from receiver
toliquid manifold
TEV’s
tosuction manifold
EPR
solenoids
Mechanical Sub-cooler
The brazed plate heat exchanger is substantially smaller thanother technologies that could be used as a liquid sub-cooler.Typically the rack controller has a temperature sensorthat will sense the refrigerant drop leg (condenser return)line to the receiver. Depending on the refrigerant type andsystem design it is quite normal to supply 40 to 50 °Fsub-cooled liquid refrigerant throughout the network.
An example of a typical Sub-coolers operation is as follows:no solenoids energized = no additional sub-cooling# 1 solenoid energized = 3 additional tons# 2 solenoid energized = 5 additional tons# 1 and # 2 solenoids energized = 8 additional tons
The EPR is normally set to maintain the minimum desiredliquid refrigerant supply temperature. This is normally50°F but may be as low as 40°F for some systems. A sub-cooler EPR settings of 68 psig will have a SST of 40°F for R-22 and 29°F for R-404A.
The liquid line solenoids in front of the sub-cooler expansion valves close when the condensers drop leg temperature gets below the set point thereby shutting off the sub-cooler.
Plate to PlateHeat exchanger
c:\sporlan 2006\cooling idiosyncrasies
How Sub Cooling Affects System Capacity
R-22
For every 10F° of sub coolingof R-22 will equal a 6% reduction in refrigerant mass flow requirements.
Example: SCT 100 FSST – 25 FSC 0FSH 25 FLOAD 5TBTU/LB 62.6
SCT 100 FSST – 25 FSC 50FSH 25 FLOAD 5TBTU/LB 77.6
Summary:
77.6 / 62.6 = 1.24Therefore 2F° SC = 1 % capacity increaseRefrigerant circulated 15.9 to 12.9 lb/minCompressor displacement from 44.1 to 35.5 cfm
R-404A / R-507
For every 10F° of sub coolingof R-404A / R-507 will equala 10% reduction in refrigerantmass flow requirements.
SCT 100 FSST – 25 FSC 0FSH 25 FLOAD 5TBTU/LB 38.6
SCT 100 FSST – 25 FSC 50FSH 25 FLOAD 5TBTU/LB 58.4
Example:
Summary:
58.4 / 38.6 = 1.51Therefore 1F° SC = 1 % capacity increaseRefrigerant circulated 25.9 to 17.2 lb/minCompressor displacement from 49.7 to 32.9 cfm
NOTE: the above outlined calculation were determined by the use of DuPrex computer program
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
What is the controlling capacityfactor of any refrigeration
system ?
The choke point …." Evaporator "
Thought Provoking !!!
c:\sporlan 2006\cooling idiosyncrasies
" Economizers when Multi Staging "
c:\sporlan 2006\cooling idiosyncrasies
Open Economizer
refrigerant vapour to compressor’s inter-stage
liquid refrigerantto
Evaporator (s)liquid refrigerantfrom condenser
saturated refrigerantat inter-stage pressure
spraynozzles
open economizer
indicates vapour
indicates liquid
The " Open or Flash " economizer is simply a tank, which is vented to the compressors inter-stage.The refrigerant flashes, evaporating some of the refrigerant, cooling the remaining liquid to the saturation temperature corresponding to the inlet pressure of the compressor inter-stage. The open or flash economizer is an economical, efficient method of cooling liquid refrigerant en-route to the evaporator (s). Open economizers are generally used when high efficiency is requiredas they also reduce the BHP requirements.
c:\sporlan 2006\cooling idiosyncrasies
2nd stage
1st stage
Open Economizer
" Open or Flash " economizer
c:\sporlan 2006\cooling idiosyncrasies
closed economizer
refrigerant vapour to compressors inter-stage
Sub-cooled liquidrefrigerant to
evaporator (s)
liquid refrigerantfrom condenser
levelcontroller
indicates vapour
indicates liquid
liquidrefrigerant
Closed Economizer
The " Closed " economizer takes the liquid from the condenser and splits the flow into two streams.Most of the refrigerant flow goes through the tubes of a shell and tube heat exchanger; the remainingrefrigerant goes to the shell side through a control valve to be boiled off to cool the refrigerant in thetubes. The vapour generated is vented to the inlet of the compressors inter-stage.
c:\sporlan 2006\cooling idiosyncrasies
Closed Economizer
2nd stage
1st stage
" Closed " economizer
c:\sporlan 2006\cooling idiosyncrasies
Two Stage A/C Cooling !!
His and Hers ??
c:\sporlan 2006\cooling idiosyncrasies
Summary
Up to 20% increase in Btu loadingDecrease in electrical usage as much as 25%Reducing pull-down time up to 50%Provide more uniform refrigerating temperaturesReduces first cost, by permitting down sizing ofcompressors in new system.
Catch-All
See-All
Solenoid
Possible reselection of TEVand distributor orifice disc needed
c:\sporlan 2006\cooling idiosyncrasies
Affects of Sub-coolingon TEV’s Capacity
Refrigerant 100°F 60°F 50°F 40°F(0°SC) (40°SC) (50°SC) (60°SC)
R-134a 100% 1.29 1.36 1.42R-401A 100% 1.25 1.31 1.36R-409A 100% 1.23 1.28 1.34
R-404A 100% 1.43 1.54 1.64R-408A 100% 1.27 1.34 1.40R-507 100% 1.40 1.50 1.59
R-22 100% 1.23 1.29 1.34R-407C 100% 1.28 1.35 1.42
c:\sporlan 2006\cooling idiosyncrasies
" Accumulators and their Affects "
c:\sporlan 2006\cooling idiosyncrasies
Hold approximately 50% of systems charge in TEV systems
Hold approximately 70% of systems charge in fixed orifice systems
Standard screen in 3 inchdiameter accumulators
Standard screen in 3 through 6 inchdiameter accumulators
Metering orifice for oil return to the compressor located behind screen0.055” diameter for 3 through 5 inch diameter accumulators
0.080” diameter for 6 inch diameter accumulators
Accumulator Design
c:\sporlan 2006\cooling idiosyncrasies
Original R-22 Screen
60 x 60 mesh of surface area
Smaller mesh can trap POE oils and
additives.
Mesh .. Number of openings per linear inch, measured from the centre of one wire to a point one inch distant.
Accumulator Screens
Mesh 0.001’s Microns
10 = 0.0580 = 150030 = 0.0194 = 50060 = 0.0097 = 250
100 = 0.0058 = 150 140 = 0.0041 = 105200 = 0.0029 = 74350 = 0.0017 = 44
Increased surface area retains more contaminants without plugging.
30 x 30 mesh screen prevents POE oils & additives from becoming trapped due to surface tension .
Enhanced HFC Screen
c:\sporlan 2006\cooling idiosyncrasies
Odor eaters ..
Odors … Bacteria
CharcoalBaking Soda
FDS (feminine deodorant spray)
foam core insulation, not fiberglass
Thought Provoking !!!
Personal level ..Vicks Vapor Rub … your upper lipBasil … nasal snort
c:\sporlan 2006\cooling idiosyncrasies
Effects of Hydrostatic Pressures ?
Lets Look at it.
c:\sporlan 2006\cooling idiosyncrasies
Temperature °F
Pres
sure
ps
ig
200
600
1000
1400
1800
2200
2600
40 60 80 100 120 140 160 180
Typical Effects of Hydrostatic Pressure
Hydrostatic PressureIncrease
R-12/R-134a is 40 psi / each F°R-22 is 60 psi / each F°
R-410A is 45 psi / each Fº
4BA / 4BWBurst Pressure
1040thru1600
R-2240°F is 70 psi
180°F is 540 psi
R-12/R-134a40°F is 37 psi
180°F is 330 psi
R-410AR-22
R-12 & R-134a
ReliefDevices390 psi
thru800 psi
R-410A40°F is 120 psi155°F is 645 psi
3200
Receiver to Solenoid ?
c:\sporlan 2006\cooling idiosyncrasies
Liquid line solenoid100 feet away.
System:
R-22, with MO- 25ºF SSTElectric defrostPump out systemLP control cutout1 psig (- 40ºF)
Freezer at- 17ºF
Freezer at- 17ºF
Freezer at- 17ºF
Troubled System … 6 TEV’s ReplacedStill High Super Heat ?
“Tee”
Found a 30Fº ∆ across Tee
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
Blood Storage RoomProblem: loss of critical temperaturecontrol, in a continuous operation.
Picture is of Hot Gas stabilizer line atevaporator inlet, solenoid 8 ft aboveoutside box in a 74ºF ambient.
Blood Storage Roomcritical application
- 30ºC or - 22ºF
c:\sporlan 2006\cooling idiosyncrasies
Modern ServiceTechnician
Fouling !!!!!
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
A 0.042" Film of Dirt on a Coil
Equals 21% Loss in
Heat Transfer Efficiency
c:\sporlan 2006\cooling idiosyncrasies
" Servicing a Winter Charge"
c:\sporlan 2006\cooling idiosyncrasies
SporlanBulletin90-30-1
c:\sporlan 2006\cooling idiosyncrasies
SporlanBulletin90-30-1
c:\sporlan 2006\cooling idiosyncrasies
Sporlan Bulletin 90-30-1
Refrigerants listedR-12 R-22 R-134a R-401A R-401BR-402A R-402B R-404A R-407C R-408AR-409A R-502 R-507
c:\sporlan 2006\cooling idiosyncrasies
SporlanBulletin90-30-1
c:\sporlan 2006\cooling idiosyncrasies
Sporlan Bulletin 90-30-1
c:\sporlan 2006\cooling idiosyncrasies
Sporlan Bulletin 90-30-1
c:\sporlan 2006\cooling idiosyncrasies
Servicing a Winter Charge !!!
To calculate the correct additional winter operationalrefrigerant charge needed at winter design follow
the procedure as outlined in Sporlanbulletin 90-30-1 dated July 1998.
How to calculate the needed additional refrigerant if only a partial charge exists.
1. Calculate the correct added winter refrigerant charge for the winter design conditions. eg: 128 lbs @ - 20ºF. (follow procedure as outlined in Sporlan bulletin 90-30-1 dated July 1998)
2. Take and record the current outdoor ambient air temperature. eg: + 20ºF3. Add refrigerant until the sight glass just clears and record the quantity of refrigerant added. eg: 17 lbs4. Recalculate the added winter charge for the current existing ambient temperature. eg: 98 lbs @ + 20ºF.
(this unit now contains the correct operational winter charge for its current ambient air temperature)5. Additional refrigerant needed to operate at – 20ºF is 128 – 98 = 30 lbs.6. In this example the billable refrigerant charge would be 17 + 30 or 47 lbs.
c:\sporlan 2006\cooling idiosyncrasies
Fin and Tube Heat Exchangers
Used for both evaporatorsand condensers.
TUBESPrimary Surface, usuallymade of copper (Cu).
FINSSecondary
Surface,usually madeof Aluminum
(Al)
c:\sporlan 2006\cooling idiosyncrasies
Coefficient of Expansion
Coefficient of Expansion
Cu is 0.0000104 of an inch / per inch / per F°
or
1.04E-5 per inch / per F°
Al is 0.0000130 of an inch / per inch / per F°
or
1.30E-5 per inch / per F°
Source: American Machinists Handbook, p 33 - 29
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
2 Lines of Nozzles
c:\sporlan 2006\cooling idiosyncrasies
Air Cooled Condenser
c:\sporlan 2006\cooling idiosyncrasies
Air Cooled Condenser
c:\sporlan 2006\cooling idiosyncrasies
“Aluminum will creep and move approximately 33% morethan copper. This large movement will eventually lead tofatigue failure.”
“Through repetitive thermal cycling, aluminum laminations(fins) can become loose, resulting in early failure.”
Cu vs Al
Source: elettra technology inc.
H2O (hard or soft) will evaporate AND cause residue (residual) deposits of either or both mineral and / or oxides to be left behind. This residuewill be deposited on or between the Cu and Al thereby increasing theheat exchanger’s fouling factor. This increase interferes with the heat transfer process causing a loss of efficiency and capacity.
c:\sporlan 2006\cooling idiosyncrasies
Other Considerations
• Continues running of water .. Added costswater cost / sewer charge
• Roof will not dry off … permanent roof damage
• Loss of head pressure control as temperature changes
• Environmental aspects
• Outdoor installation, freezing prospects
• Repeated calls to start / stop adjust etc:
• Equipment life shortened, rust, motors, belts, drives
c:\sporlan 2006\cooling idiosyncrasies
And Then There is theOther Contractor
Modern ServiceTechnician
c:\sporlan 2006\cooling idiosyncrasies
Poor Bulb Location = Floodback
Show smashed compressor parts …………….
c:\sporlan 2006\cooling idiosyncrasies
Built-in Redundancy !!!
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
10 Units in 48” wide passage !!!
c:\sporlan 2006\cooling idiosyncrasies
Location .. Location .. Location
First Rule in Real Estate
c:\sporlan 2006\cooling idiosyncrasies
Residential Split Systems
Traditional / StandardMethod
Typical Cool ClimateInstallation ?
c:\sporlan 2006\cooling idiosyncrasies
Residential Split Systems
Second Alternative, Knee Braces on outside wall.Pro’s: Not effected by ground thermo shear.
Landscaping not completed .. RNC market.Con’s: Sound transmission, harmonics through wall.
Isolation pads may be needed ?
Secure top of hairpin only .. Allows opening / closing
Preferred InstallationMethod
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
Didn’t like the look …Must hide the Condensing unit
c:\sporlan 2006\cooling idiosyncrasies
R-410A ? Under the Deck …unit will die of emphysema !!!
RedRock Clubhouse, prestigious golf course inSouth Carolina. Removed 4” of pine needles toget units in and then only 1” top clearance onsecond unit.
c:\sporlan 2006\cooling idiosyncrasies
Typical Ductless Split Installation
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
Then There is the Contractor ABC( Always Bring Cash )
c:\sporlan 2006\cooling idiosyncrasies
Cross supports ????
Safe
ty …
!!!!!!
Chicken crates
Entranced way
c:\sporlan 2006\cooling idiosyncrasies
Home on pillars, note condensers discharge ducton top of unit, complete with turning vane.
Attic installation in a SouthernState. Do it yourself installationdream.
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
Access Ladder to Roof
c:\sporlan 2006\cooling idiosyncrasies
Three Compressors !!!
c:\sporlan 2006\cooling idiosyncrasies
FIDO
c:\sporlan 2006\cooling idiosyncrasies
38HQ three piece heat pump, Low ceiling re-circulated air.Note: longer piping run but proper location of fittings for oil return.
Installation is everything ?Location Location Location
c:\sporlan 2006\cooling idiosyncrasiesGate Valves ????
The Plumber !!!
c:\sporlan 2006\cooling idiosyncrasies
Nylon Tie Wraps !!!!
c:\sporlan 2006\cooling idiosyncrasies
Controlling Lubricantsand Discharge Temperature
c:\sporlan 2006\cooling idiosyncrasies
Typical Refractometer
c:\sporlan 2006\cooling idiosyncrasies
Refractometer Readings
Approved OEM POE Lubricants:
Copeland, all reciprocating and scroll refrigerationEmkarate … RL32CF .. 1.4546
Carlyle / Carrier all O6D & O6EEmkarate … RL68H … 1.4557
Carlyle / Carrier all O5T & O6T screwsEmkarate … RL100S .. 1.4574
Mineral Oils .. 3GS: 1.4942, 4GS: 1.4973, 5GS: 1.4953
Alkylbenzene … 150: 1.4865, 200TD: 1.4859, 300: 1.4844
Source Nu-Calgon 3-240
(150 / 32) (500 / 100)(300 / 68)Viscosities SUS / ISO
c:\sporlan 2006\cooling idiosyncrasies
Polyolester Lubricants
RL22H RL22N RL32CF RL32S RL32H RL68H RL68HP RL68S RL100S RL150S RL220H1.4519 1.4521 1.4546 1.4546 1.4530 1.4557 1.4557 1.4564 1.4574 1.4581 1.4580
Emkarate OEM approved lubricants
Bitzer Recp. X XScrew
Bock X X X Bristol XCarlyle Recp. X
Screw XCopeland XD/Bush Recp. X X
Screw X Embraco XGrasso XManeurope XMatsushita XPrestcold XRoyce X XSabroe X X X X X X X Sea Container X SRM X Tecumseh XThermoking XTrane* Screw X
Scroll XYork* Recp. X
Screw X
McQ
uay
R-1
34a
cent
rifug
als m
odel
s 05
0, 0
63,
079,
087
Car
rier R
-134
a ce
ntrif
ugal
s mod
els
19X
T, 1
9XR
, 19
XR
T, 1
9EX
Emkarate lubricantRefractive index
source: Nu-Calgon 3-68 + Carrier
Suffixes:CF = Copeland formulationH = High solubilityS = Standard solubilityN = Special for McQuayHP = Special for Carrier
by Garth Denison
* Trane and York low pressure centrifugals use OEM approved mineral lubricants.
Bitzer ScrewEmkarate RL170H
1.4576BVA Solest 170
1.4558
c:\sporlan 2006\cooling idiosyncrasies
Cross Lubricant Contamination
POE
ABMO
AB … Alkylbenzene OilMO … Mineral OilPOE … Polyol ester Oil
< 50 %
< 5 % < 5
%
Note:
Lubricants are 100% misciblewith each other. Their degree
of miscibility with variousrefrigerants varies from
0% to 100%.
Generally Accepted Lubricants
CFC’s and HCFC’s use MO or ABHFC’s and PFC’s use POE
c:\sporlan 2006\cooling idiosyncrasies
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 1001.440
1.445
1.450
1.455
1.460
1.465
1.470
1.475
1.480
1.485
1.490
1.495
1.500
Refractometer GraphRefractive Index vs Residual Oil Content
Residual (%, wt) of Old Oil
c:\sporlan 2006\cooling idiosyncrasies
Note: Always take readings after " De-gassing " lubricant
1.51
1.50
1.49
1.48
1.47
1.46
1.45
1.44
1.52
1.51
1.50
1.49
1.48
1.47
1.46
1.45
1.44
1.52
RefractiveIndex
nD
Scale
Refractometer Eye Piece
nD = reactive Divergence
c:\sporlan 2006\cooling idiosyncrasies
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 1001.440
1.445
1.450
1.455
1.460
1.465
1.470
1.475
1.480
1.485
1.490
1.495
1.500
MO3C / 3GS – 1.49424C / 4GS – 1.49735C / 5GS – 1.4953
AB150 – 1.4856
200TD – 1.4859300 – 1.4844
POECopeland – 1.4546
Carlyle O6D/E – 1.4557Carlyle O5/6T – 1.4574
Refractometer GraphRefractive Index vs Residual Oil Content
Residual (%, wt) of Old Oil
POE1.4557
MO1.4942
Sample lubricant example,a reading 1.474 would
represent 44% POElubricant.
c:\sporlan 2006\cooling idiosyncrasies
POE
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 1001.440
1.445
1.450
1.455
1.460
1.465
1.470
1.475
1.480
1.485
1.490
1.495
1.500
MO
AB
MO3C / 3GS – 1.49424C / 4GS – 1.49735C / 5GS – 1.4953
AB150 – 1.4856
200TD – 1.4859300 – 1.4844
POECopeland – 1.4546
Carlyle O6D/E – 1.4557Carlyle O5/6T – 1.4574 Source: Nu-Calgon # 3 – 242
Maximum cross lubricant contamination with POE’s is 5%
Refractometer GraphRefractive Index vs Residual Oil Content
Residual (%, wt) of Old Oil
Acceptablerange1.4546
to1.4595
c:\sporlan 2006\cooling idiosyncrasies
Desired refractive range is between
1.4546 to 1.4595
This will ensure less than
5% cross lubricant
Refractometer Graph
Refractometer Sources:
1. ATAGO P/N N-30002. Copeland P/N 998-RMET-00
c:\sporlan 2006\cooling idiosyncrasies
Service Refractometer
1.4546 to 1.4595
c:\sporlan 2006\cooling idiosyncrasies
Temperature ResponsiveExpansion Valve (TREV)
Typical U.S. Green Compressors
OEM Discharge head sensor:
Refrigeration dutyopens 325°F +/- 8closes 250°F +/- 12
Air Conditioning dutyopens 295°F +/- 5closes 235 minimum
Typical Black Compressors
eg: OEM Demand Cooling™
Injects refrigerant at 292°FShuts refrigerant off at 282°F
If compressor operates at310°F for 60 seconds thecontroller will shut the unitoff on safety.
Y 1037
c:\sporlan 2006\cooling idiosyncrasies
Lubricant Functions
Other Functions: …1. Makes a fluid seal .. prevents blow by
2. Acts as a coolant .. compressor and hermetic motor
3. Dampens mechanical noise .. POE’s 1½ louder, dB scale
4. Provides electrical insulation .. hermetic systems (25Kv)
Purpose: … to minimize friction and prevent wear of moving parts.
Tribology: .. the study of interacting surfaces in relative motion and associatedissues, such as friction, lubrication and wear. (friction and wear)
c:\sporlan 2006\cooling idiosyncrasies
Additional Piping Considerations
Refrigerant goes to Lubricant
Lubricant DOES NOT go to Refrigerant
Refrigerant is soluble (dissolved) in lubricant .. similar to sugar in coffee (one liquid phase) until CST (Critical Solution Temperature)
is reached then there is two liquid phases (one refrigerant + one lubricant).
Note: OEM’s of ductless splits recommend NO traps.
c:\sporlan 2006\cooling idiosyncrasies
Lubricant movement within a typical system
Properly designed refrigeration / air conditioning system3 to 5% of compressor’s lubricant is in circulation at all times.MO / AB is approximately 30% miscible with their typical refrigerant’s, the remaining lubricant travels by peristalsis, this is caused by the refrigerant’s velocity.
POE lubricants with HCFC or HFC refrigerants are 100% misciblebetween from + 176° F (+ 80° C) through – 76° F (- 60° C), thereforethe circulating lubricant travels in suspension.
Miscibility … the ability to mixSolubility … the ability to dissolveCST … Critical Solution TemperatureLubricants are miscible with other lubricantsLubricants are miscible at different percentages in refrigerantMoisture (H2O) is soluble in POE lubricant
c:\sporlan 2006\cooling idiosyncrasies
Variances in Lift Verses Density .. @ 1 psi
one psi
Typical refrigerant2 feet or 24 inches
Refrigerants
Water H2O2.31 feet or 27.7 inches
Water
one psi
Typical lubricant2.5 feet or 30 inches
Lubricants
one psi
Refrigerant R-7173.9 feet or 47 inches
Ammonia
one psi
c:\sporlan 2006\cooling idiosyncrasies
“RISER”45° Street El
45° Street El
90° Short Radius El
Oil Trap Construction
c:\sporlan 2006\cooling idiosyncrasies
The oil drains from the riser & sloped horizontal piping to fill the trap
Oil Trap During the Off Cycle
c:\sporlan 2006\cooling idiosyncrasies
If a large surge of vapour enters the trap
The oil could be forced out of the trap as a slug
For this reason the oil holding volume of the
trap is kept to a MINIMUM
Oil Trap at Start Up
c:\sporlan 2006\cooling idiosyncrasies
Which trap is more likely to kill a compressor with
an oil slug?
Oil Traps Compared
c:\sporlan 2006\cooling idiosyncrasies
Usually, the amount of vapour entering the trap gradually increases
The oil is then pushed through the trap until a gap is formed here
Because the gap has a small area,
the vapour passes through at high
velocity
The high velocity vapour carries oil droplets up the riser
Oil Trap at Start Up
c:\sporlan 2006\cooling idiosyncrasies
Downward direction of flow & Horizontal line size is increased so
pressure drop is kept in an acceptable range
Riser line size is
reduced to maintain vapour velocity and oil
return up the riser
Reduced Size Riser
c:\sporlan 2006\cooling idiosyncrasies
smaller RISER
“A”
larger RISER
“B”
The large volume of
vapour flow is split between
risers
Each riser has enough flow & velocity to carry
oil up the pipe
Double Riserat Full Capacity
c:\sporlan 2006\cooling idiosyncrasies
smallerRISER
“A”
largerRISER
“B”
The small volume of vapour flow is not enough to carry oil
up both risers
The oil can’t be carried up the risers and fills
the trap
This blocks vapour flow in
Riser “B”
Then all the small volume of
flow shifts to Riser “A” with
enough velocity to carry oil up
the pipe
Double Riserat Low Capacity
c:\sporlan 2006\cooling idiosyncrasies
Lubricant Miscibility SummaryCFC’s
w / Mineral oil-76F 2 phases +164F 2 phases +176F
w / Alkylbenzene -76F 2 phases -17F 1 phase +176F
HCFC’sw / Mineral oil -58F 2 phases +149F 2 phases +162F
w / Alkylbenzene -58F 2 phases +151F 1 phase +162F
w / Polyol ester-58F 1 phase +162F
w / Mineral oil-76F 2 phases +126F 2 phases +176F
w / Alkylbenzene-76F 2 phases +135F 2 phases +176F
w / Polyol ester -76F or -60C 1 phase +176F or +80C
Source: DuPont HP P.U.S.H.
HFC’s
c:\sporlan 2006\cooling idiosyncrasies
Influence of Mineral Lubricant Filmon Heat Transfer
Source: Technicold Services Inc, George Briley P.E.
A film of only 1.5 mils of oil drops the heat transfer coefficient14% and a film of 3 mils dropsthe heat transfer by 25%. As the surfaces continue to “foul”, thesystem efficiency decreasesaccordingly.
Note: 1.0 mil = 0.001 inchAverage copper BTU/Hr/SF/Fº is 85 to 100
c:\sporlan 2006\cooling idiosyncrasies
Lubricant is required to lubricate the moving parts within the compressor.Unfortunately lubricant and refrigerant have an affinity to each other and lubricant is constantly being depleted from the compressor sump and circulating about the piping system. Lubricant can get logged up in parts of the piping system and note return to the compressor sump. The rate of lubricant depletion must be equaled by the rate of lubricant being returned otherwise it is only a matter of time until the compressor is destroyed from lack of lubrication. Piping systems are designed as a trade off between pressure drop (system efficiency) and velocity (lubricant return). In other words larger pipes have less pressure drop which is good for system efficiency and smaller pipes cause higher velocities which improve lubricantmovement and the return of lubricant to where it belongs. Another problem with lubricant getting out is the piping system is that it acts as an insulator reducing heat transfer in coils. Oil separators capture most of the lubricant as it leaves the compressor and return it back to the compressor sump whereit belongs. There are three types of oil separators; impingement, helical, and coallescing.
OIL SEPARATORS
c:\sporlan 2006\cooling idiosyncrasies
Impingement separators use screens in the upper half to cause fine particlesof oil to collect and form larger ones. The velocity of the discharge gas is reduced when it enters the large volume of the oil separator which helps theoil droplets to impinge on the screen. The droplets grow large enough in sizeto fall to the bottom. When sufficient oil has been collected a float operatedneedle valve opens and allows the difference in high side and low side pressureto return the oil to the crankcase. The black arrow in the graphic is above thefitting for the oil return line. Impingement separators are approximately 80% to 85% efficient and are in common use. The drawing shows a serviceabletype impingement oil separator. They are also available as a sealed unit.
Impingementtype
c:\sporlan 2006\cooling idiosyncrasies
Helical separators (aka .. cyclone) depend on the interior shell designto force the refrigerant / oil mixture along a spiral path. That creates a centrifugal force which forces the lubricant droplets to the outsideof the spiral where they collect and drain to the float valve below.A supposed drawback to this type of unit is that centrifugal forceonly works effectively on relative large lubricant droplets. This meansthat smaller droplets remain in the refrigerant and are re-circulatedthrough the system. However manufacturers of helical separators claimthat up to 99% efficiency can be achieved.
Helical / Cyclonetype
c:\sporlan 2006\cooling idiosyncrasies
In coalescing separators, the refrigerant/oil mixture is passed througha filter of exceptionally pure, extremely fine glass fibers, which forma capturing matrix. This matrix excites the oil molecules, causing themto collide and form larger droplets which are forced to the filter's outerdrain layer where they drain by gravity into the sump. Coalescing unitsare capable of delivering between 95% to 99%+ efficiency, dependingon the grade of filter core used and the design details. There are some coalescing oil separator manufacturers that claim their units have 99.99% efficiency.
Coalescingtype
c:\sporlan 2006\cooling idiosyncrasies
Polly Ester
Polly’s unsavory background is that she’s nothing but acid and alcohol.Manufacturers have tried to neutralizer / stabilizer her for years. Shegoes everywhere and she’ll pick up anything and everything on her travels. She’s expensive, $ 40 to $ 50 per gallon. She sucks, veryhygroscopic as she picks up water readily. She’s a loud mouth,reciprocating compressors using Polly will be about 50% (1-1/2 times)louder on the dB scale as the same compressor using mineral oil. She’sa tramp, as Polly is polar in nature she will carry wear particulates insuspension as she flows throughout the system.
Let’s call her what she is, she’s a bitch.
Something to think about.
c:\sporlan 2006\cooling idiosyncrasies
Grams or CC’s of H2O @ 20°C (68°F)
Pounds of Refrigerant
25 50 100 250 500 1000 2000
10 0.12 0.25 0.5 1.1 2.3 4.5 9.2
30 0.4 0.7 1.4 3.4 6.8 13.6 27.2
50 0.5 1.1 2.3 5.7 11.3 22.7 45.2
100 1.2 2.3 4.5 11.3 22.7 45.4 91
250 2.9 5.8 11.3 28.4 56.7 113.4 227
500 5.6 11.3 22.7 56.7 113.4 226.8 454
1000 11.3 22.7 45.4 113.4 226.8 453.6 907
1500 17.0 34.0 68.0 70.1 340.2 680.4 1361
2000 22.7 45.4 90.7 226.8 453.6 907.2 1814
ppm
H2O
Notes: 1 gram = 20 drops of H2O or 1 gram = 1 ccppm’s x weight x 453.59 ÷ 1,000,000 = grams or cc of H2O
POELubricant
c:\sporlan 2006\cooling idiosyncrasies
Generally Accepted Piping Criteria
Inline flare by flare relief valves:
Under certain circumstances it may be necessary to install an inline relief differentialrelief valve. The purpose of this valve is to relief a situation where hydrostatic pressurecould develop due to liquid refrigerant being trapped leaving it no room for expansionas the temperature increases. This situation is usually caused by the systems pipinggeometry and/or installed ancillary devices.
Split system with buried piping:
In some installations it may become necessary to bury the line set. An example of thismay be under a sidewalk for safety reasons. If this situation arises use a minimum of 6 inch or larger diameter irrigation type tubing open at both ends above grade, this should provide adequate ventilation. The ends of this tubing can be covered with large mesh screening to keep small critters out but will allow adequate air circulation to preventthe condensation of refrigerant vapour in the underground section. Good installationpractice would also include the installation of a properly sized suction line accumulator.
c:\sporlan 2006\cooling idiosyncrasies
Best Piping Practices
Liquid Line for Multi Evaporators
Split system A/C or Refrigeration
Multi-Evaporators Hot Gas
Liquid Line Stacked Evaporators
Suction Line Stacked Evaporators
How to Modify Defective Piping Installation
Split Circuited Condensers
c:\sporlan 2006\cooling idiosyncrasies
Liquid Line Piping for Multi evaporators or cases with defrost
Refrigerant Piping Practices
Liquid Line
Liquid Line
Case coilCase coilCase coil
Case coilCase coilCase coil A
B
Denotes TEVcontinued …...
c:\sporlan 2006\cooling idiosyncrasies
Liquid Line
Liquid Line
Case coilCase coilCase coil
Case coilCase coilCase coil A
B
Denotes TEVcontinued …...
Liquid Line Piping for Multi evaporators or cases with defrost
Refrigerant Piping Practices
c:\sporlan 2006\cooling idiosyncrasies
Liquid Line
Liquid Line
Case coilCase coilCase coil
Case coilCase coilCase coil A
B8 inch
minimum
NO
“B” is recommended because liquid hammer will not effect the fittings also expansion and contraction will take place on liquid header not the branch fittings.
Denotes TEV
“A” is not recommended because of liquid hammer also expansion and contraction will “work” the elbow and cause a failure.
Liquid Line Piping for Multi evaporators or cases with defrost
Refrigerant Piping Practices
c:\sporlan 2006\cooling idiosyncrasies
Split system, 100 ft apart, evaporator above condensing unit
Refrigerant Piping Practices
Evaporator coil
Condensing unit
Evaporator coil A
B
Condensing unit
continued …...Denotes TEV
c:\sporlan 2006\cooling idiosyncrasies
Split A/C system, 100 ft apart, evaporator above condensing unit
Refrigerant Piping Practices
Evaporator coil
Condensing unit
Evaporator coil A
B
Condensing unit
90 feet
10 feet
continued …...Denotes TEV
c:\sporlan 2006\cooling idiosyncrasies
Split A/C system, 100 ft apart, evaporator above condensing unit
Refrigerant Piping Practices
Evaporator coil
Condensing unit
Evaporator coil A
B
Condensing unit
90 feet
10 feet
10 feet
90 feet
Note: 100 feet of 7/8 tubing will hold 25 pounds of liquid R-22 refrigerant.
“B” is recommended because only 10 ft of liquid refrigerant (10 % of 25 = 2.5 lbs) will drain on off cycle into condensing unit, less chance of damage on start-up.
Note: 100 feet of 7/8 tubing will hold 25 pounds of liquid R-22 refrigerant.
“A” is not recommended because 90 ft of liquid refrigerant (90 % of 25 = 22.5 lbs) will drain on off cycle into condensing unit,damage compressor on start-up.
Denotes TEV
c:\sporlan 2006\cooling idiosyncrasies
Same Circuit Multi Evaporators with Hot Gas Defrost
Refrigerant Piping Practices
Hot Gas Defrost Line
EvaporatorEvaporator
EvaporatorEvaporator A
B
Hot Gas Defrost Line
continued …...Denotes TEV
c:\sporlan 2006\cooling idiosyncrasies
Same Circuit Multi Evaporators with Hot Gas Defrost
Refrigerant Piping Practices
Hot Gas Defrost Line
EvaporatorEvaporator
EvaporatorEvaporator A
B
Hot Gas Defrost Line
continued …...Denotes TEV
c:\sporlan 2006\cooling idiosyncrasies
Same Circuit Multi Evaporators with Hot Gas Defrost
Refrigerant Piping Practices
Hot Gas Defrost Line
EvaporatorEvaporator
EvaporatorEvaporator A
B
Hot Gas Defrost Line
“A” is not recommended becausewhen the ‘Hot Gas” is off liquidrefrigerant can be feed from oneevaporator to the other evaporator.
“B” is recommended because thereis a check valve in the Hot Gas lineleading to the side inlet “Tee”.Thereby preventing liquid refrigerantfrom entering the other evaporatorwhen Hot Gas defrost is not in use.
Denotes TEV
c:\sporlan 2006\cooling idiosyncrasies
Liquid Line Feed to Stacked Evaporator Coils
Refrigerant Piping Practices
B
Condensing unitCondensing unitReceiver Receiver
Evaporator
Evaporator
Evaporator
Evaporator
Evaporator
Evaporator
A
continued …...Denotes TEV
c:\sporlan 2006\cooling idiosyncrasies
Liquid Line Feed to Stacked Evaporator Coils
Refrigerant Piping Practices
A B
Condensing unitCondensing unitReceiver Receiver
Evaporator
Evaporator
Evaporator
Evaporator
Evaporator
Evaporator
continued …...Denotes TEV
c:\sporlan 2006\cooling idiosyncrasies
Liquid Line Feed to Stacked Evaporator Coils
Refrigerant Piping Practices
Evaporator
Evaporator
Evaporator
B
Condensing unitCondensing unitReceiver Receiver
Evaporator
Evaporator
Evaporator
A
“A” is not recommended because of the “static head”ofliquid, only the bottom coil will receive a full column ofliquid, the middle would have liquid and some vapourand the top coil could receive little liquid and the majorityof the vapour therefore poor system performance. Vapourbubbles will rise to the top coil.
Note the receiver, because there is a two phase conditionin the receiver little or no sub-cooling is available.
“B” is recommended as all coils will be feed equalquality refrigerant therefore having balancedevaporators and good performance.
Denotes TEV
c:\sporlan 2006\cooling idiosyncrasies
Suction Lines from Stacked Evaporator Coils
Refrigerant Piping Practices
Condensing unitCondensing unitReceiver Receiver
Denotes TEV
B
Evaporator
Evaporator
EvaporatorTEVbulb
Evaporator
Evaporator
Evaporator
ATEVbulb
c:\sporlan 2006\cooling idiosyncrasies
Suction Lines from Stacked Evaporator Coils
Refrigerant Piping Practices
Condensing unitCondensing unitReceiver Receiver
Denotes TEV
B
Evaporator
Evaporator
EvaporatorTEVbulb
Evaporator
Evaporator
Evaporator
ATEVbulb
c:\sporlan 2006\cooling idiosyncrasies
Suction Lines from Stacked Evaporator Coils
Refrigerant Piping Practices
Condensing unitCondensing unitReceiver Receiver
Denotes TEV
The remote TEV bulbs and external equalizing line connectionsmust be located so that the conditions effecting one valve can-not influence the other valves. The double elbow configurationallows the corresponding section of the evaporator coil to drainfreely while isolating the remote bulb and equalizer line from the suction pressure and temperature of the above coil section.
Arrange the suction line so that the refrigerant vapour leavingthe top coil flows downwards, connection to the pipes leavingthe other coils. This manifold pipe should drop below the lowestcoil outlet before turning upward. This allows all of the oil todrain out of the evaporators and congregate before it must becarried up a vertical riser.
The single suction line then rises above the height of the evaporator coils, preventing refrigerant and oil inside the evaporator from free draining into the suction line, and towardsthe compressor, when the system is off.
Double elbow configuration
Must drop below lowestheader outlet
Must rise above height of evaporators
B
Evaporator
Evaporator
EvaporatorTEVbulb
Evaporator
Evaporator
Evaporator
ATEVbulb
c:\sporlan 2006\cooling idiosyncrasies
Liquid Line Feed to Stacked Evaporator Coils
Refrigerant Piping Practices
Evaporator
Evaporator
Evaporator
Condensing unitReceiver
“A” is not recommended because of the “static head”ofliquid, only the bottom coil will receive a full column ofliquid, the middle would have liquid and some vapourand the top coil could receive little liquid and the majorityof the vapour therefore poor system performance. Vapourbubbles will rise to the top coil.
Note the receiver, because there is a two phase conditionin the receiver little or no sub-cooling is available.
Denotes TEV
" A "To the low side of system
Capped
c:\sporlan 2006\cooling idiosyncrasies
Liquid line toremote evaporators
Receiver
Catch-All
See-All
Solenoid
Liquid Hammercan split LR 90º ells
" Stand pipe " of a minimum length (12”) will help prevent split ells caused by liquid hammer.
Problem
Modern ServiceTechnician
Owner
c:\sporlan 2006\cooling idiosyncrasies
Roof Line
LiquidCondensate line
Receiver
Liquid Line
Suction Line
Discharge Line
Condenser
Compressor
Controlling Liquid Line Pressure
High Pressure Vapour LineORD - 4
ORI -Outdoorambient
Indoorambient
hot gas binging.ppt
Considerations: 1 pisg pressure lifts ref. 1.8 ft.Binding line equals pressure between receiverand condenser. If receiver 20 pisg higher ref.will not flow down.
ORD-4-20ORD-4-25ORD-4-30ORD-4-35
220205
c:\sporlan 2006\cooling idiosyncrasies
ORD-4-35
ORD-4-20ORD-4-25ORD-4-30ORD-4-35
*
* is standard
ORD-4-35
DischargePressure240 psig
ReceiverPressure175 psig
" A "" B " " C "
Refrigerant Flow
Normal operation A to B is a ∆ 65 psigIf B pressure drops >5 ORD #1 opens
# 1 # 2
Series Refrigerant ORD Operation
c:\sporlan 2006\cooling idiosyncrasies
Roof Line
LiquidCondensate line Hot Gas Binding Line
Receiver
Liquid Line
Suction Line
Discharge Line
Condenser
Compressor
Hot Gas Binding
High Pressure Vapour LineORD - 4
ORI -Outdoorambient
Indoorambient
hot gas binging.ppt
Considerations: 1 pisg pressure lifts ref. 1.8 ft.Binding line equals pressure between receiverand condenser. If receiver 20 pisg higher ref.will not flow down.
ORD-4-20ORD-4-25ORD-4-30ORD-4-35
220205
R-22
100 = 196105 = 210110 = 226115 = 242120 = 260125 = 278
226
ORI -
c:\sporlan 2006\cooling idiosyncrasies
What Does This Tell You ?
c:\sporlan 2006\cooling idiosyncrasies
What Does This Tell You ?
c:\sporlan 2006\cooling idiosyncrasies
Result …….
c:\sporlan 2006\cooling idiosyncrasies
Refrigerant Migration Protection
A description of methods, using a Liquid Line Solenoid Valve (LLSV) installed in the liquid line just before the metering device, to prevent liquid refrigerant in the evaporator from flowing intocrankcase of the compressor during the off cycle and causing a flooded compressor start.
by Garth Denison
1. Solenoid Drop (minimum protection)
When the cooling thermostat is satisfied, the LLSV is de-energized closing off the liquid line. The compressor also cycles off. The closing of the liquid line prevents any refrigerant migration to the low side of the system. Since there maybe refrigerant remaining in the low side of the system which could migrate to the lubricant in the crankcase of the compressor, it is highly recommended that a crankcase heater be used with this system.
~
~
~
~
LLSV
CC
TC
L1 L2
Legend
CC – compressor contactorCR – control relayHP – high pressure contacts L1-L2 control powerLLSV – liquid line solenoid valveLP – low pressure contactsOL – compressor overloadsTC – thermostat cooling
c:\sporlan 2006\cooling idiosyncrasies
2. Pump Down ControlWhen the cooling thermostat is satisfied, the LLSV is de-energized closing off the liquid line.With this control, the compressor remains operating drawing the refrigerant out of the low side of the system until the low side pressure is low enough to open the low pressure switch(LPS) stopping the compressor.
If the LLSV leaks, the low side pressure will increase to close the LPS starting the compressor.The compressor will continue to cycle as long as the LPS is closed. This repeated cycling will cause the compressor winding to overheat and lead to compressor failure.
Also, if the compressor is equipped with suction pressure unloaders, leaking through theunloader will cause the compressor to rapid cycle. Therefore it is not recommended to usea pump down control on a system with suction pressure unloaders.
~
~
~
~
CC
LLSV
TC
L1 L2
HP LP OL
Legend
CC – compressor contactorCR – control relayHP – high pressure contacts L1-L2 control powerLLSV – liquid line solenoid valveLP – low pressure contactsOL – compressor overloadsTC – thermostat cooling
Refrigerant Migration Protection
c:\sporlan 2006\cooling idiosyncrasies
3. Pump Out Control:
This system operates similar to the pump down control, only with a pump out control, a compressor lock-out relay is used to prevent the compressor from cycling on the LPS.With the lock-out relay, the compressor reverts back to the cooling thermostat control and will not restart until the thermostat senses a need for cooling.
A crankcase heater should be used in conjunction with the pump out control.
~
~
~
~CC
L1 L2
CR
TC
HP LP OL
LLSV
CR1
CR2
CC
Legend
CC – compressor contactorCR – control relayHP – high pressure contacts L1-L2 control powerLLSV – liquid line solenoid valveLP – low pressure contactsOL – compressor overloadsTC – thermostat cooling
Refrigerant Migration Protection
c:\sporlan 2006\cooling idiosyncrasies
Sound !!!!!
c:\sporlan 2006\cooling idiosyncrasies
Harmonics … Pulsations What are They ?
Condensations and refractions are clusters of variouslengths of sound waves that catch up with each otherwithin the piping system. This causes the amplitude of the sound level to increase causing loud disturbingpulsating harmonic sounds.
Possible means of limiting or greatly reducing these harmonics.
• Add mass and additional clamping to discharge line, attach angle iron to the dischargeline with hose clamps. (eg: 10” x 1-1/2” x 1-1/2” x ¼” angle iron)
• Change discharge piping configuration, this changes length of reverberation channel.• Install sound pulsation plate between compressor and discharge service valve.
These plates are designed to create a 5 psi backpressure thereby changing the soundwave length and frequency that is being emitted from the compressor.
• Change compressor rotation as gas passages are not equal in length.• Move pressure operated unloader to other side bank.• Install large discharge muffler to smooth out pulsations.• Change the type of compressor from reciprocating to dynamic compression.• All field piping must be of “Prime” value, not divisible equally by 2, 3, 4 or 6. • A lubricant change will lower the sound level … R-22 POE to R-22 MO or AB
c:\sporlan 2006\cooling idiosyncrasies
Discharge Pulsation PlatesCarlyle Compressors
06DA818 (6D48) is 5/16”06DA824 (6D68) is 3/8”06DA337 (6D73) is 7/16”06DA537 (6D75) is 7/16”
06E250 is 1/2” 06E275 is 5/8”06E260 is 9/16” 06E299 is 23/32”06E266 is 9/16”
All restrictor plates 1/8” thick, centre hole diameter as specified below.
1 ¾
” 2 ½
”
½” dia. (4)
⅜” dia.(2)
06D series06E series
Remember .. Two (2) service valve gaskets are required with each plate, one for each side when restrictor installed.
c:\sporlan 2006\cooling idiosyncrasies
Mufflers & Baffle Plates
Discharge Pulsation PlatesCarlyle Compressors
Assist in pressure pulsation and sound reductions.Size mufflers per discharge line size or larger.Size baffle plates per application recommendations.
Baffle Platesaka .. pulsation plates
or muffler plates
c:\sporlan 2006\cooling idiosyncrasies
Discharge Pulsation Plates
Copeland:Application Recommendations of Compressor Muffler Plates
Application Engineering Bulletin AE-4 - 1181
c:\sporlan 2006\cooling idiosyncrasies
Discharge Pulsation PlatesCarlyle:
Application Recommendations With Baffle PlatesCarlyle Technical Bulletin 99T – 4
c:\sporlan 2006\cooling idiosyncrasies
Discharge Pulsation PlatesCarlyle:
Application Recommendations With Baffle PlatesCarlyle Technical Bulletin 99T – 4
c:\sporlan 2006\cooling idiosyncrasies
An Important IndustryDistinction
There is a common misunderstanding within the refrigeration industryaround the refrigerant Pressure Enthalpy (Ph) diagram. Some industryindividuals are under the impression that a refrigerant Pressure Enthalpy(Ph) diagram and a Mollier diagram are synonymous with each other. This is misleading and incorrect, they are NOT identical, nor are they interchangeable. The Mollier diagram is the European version of the Anglo-American Psychrometric chart. The Psychrometric chart and theMollier diagram are identical in content but not in appearance. Both thePsychrometric chart and the Mollier diagram deal with the properties andmeasurements of AIR not the properties and measurements of “Refrigerants”. Only the Pressure Enthalpy (Ph) diagram deals with theproperties and measurements of refrigerants.
Mollier diagramPh diagram
Something to think about.
An Important IndustryDistinction
c:\sporlan 2006\cooling idiosyncrasies
Future … Crystal Ball
Around the Corner !!
R-404A
R-134a
Recovery
R-407C
R-410A
R-507A
c:\sporlan 2006\cooling idiosyncrasies
When .. 5 ≈ 31+ ≈ 5 = 34
Years
R-11R-12R-22R-500R-502
1986
R-134aR-404AR-407CR-410AR-507
2020
R-123, R-124, R-125, R-134a, R-143a, R-218, R-400, R-401A, R-401B, R-401C,
R-402A, R-402B, R-403A, R-403B, R-404A, R-405A, R-406A, R-407A,R-407B, R-407C, R-408A, R-409A,R-410A, R-410B, R-412A, R-414A,R-414B, R-416A, R-417A, R-420AR-421A, R-422A, R-423A, R-424A.
Simplicity is Around the Corner
United Nation Environmental Program (UNEP) a.k.a. Montreal Protocol
c:\sporlan 2006\cooling idiosyncrasies
Domestic / White goods, Vending:R-134a .. Rotary or Scroll
Auto A/C:R-134a .. Future R-744 (CO2)
Residential A/C & HP: < 5 tonR-410A .. Scroll
Commercial A/C & HP 5 thru 100 ton:R-410A .. Scroll, (Screws R-134a larger units)
Commercial Refrigeration:R-404A / R-507 Reciprocating or Screw,(Scroll under development)
Large tonnage 100 thru 10,000 ton:R-134a .. Centrifugal or Screw
Retrofit market:A/C DX applications .. R-407CA/C Flooded .. R-134aRefrigeration / Process .. R-404A / R-507
Application Future In North Americaas seen by Garth Denison
Original refrigerantsR-11R-12R-22
R-500R-502
Interim refrigerantsmorgasbord
(31+)
Future refrigerantsR-134aR-410A
R-404A / R-507R-407C
1986
2020
c:\sporlan 2006\cooling idiosyncrasies
" What’s on the Horizon "
customer
System Engineer
c:\sporlan 2006\cooling idiosyncrasies
CO2 Direct Expansion – MT and LT
LT 181 kWor
51.5 Ton
c:\sporlan 2006\cooling idiosyncrasies
Graphic Representation of Compressing Details
CO2 or R-744 is a TranscriticalRefrigerant
c:\sporlan 2006\cooling idiosyncrasies
MT CO2 Multi Compressor Set for Field Test .. Qo = 160 kW or 45.5 tons
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
ICE
Beautiful, Scenic, Dangerous,Hazardous, Costly
c:\sporlan 2006\cooling idiosyncrasiesBeautiful
c:\sporlan 2006\cooling idiosyncrasies
Scenic
c:\sporlan 2006\cooling idiosyncrasies
Dangerous
c:\sporlan 2006\cooling idiosyncrasies
Hazardous
c:\sporlan 2006\cooling idiosyncrasies
Frozen / Broken Waterline in Garage !!!!
Very Costly
c:\sporlan 2006\cooling idiosyncrasies
LOOKING DEEP INTO PROBLEM AREAS
c:\sporlan 2006\cooling idiosyncrasies
Refrigeration Ice Plants
Canary " Passing "
R-717 …. NO Contact LensesVaseline in groin and arm pits !
Safety Rope / Buddy System
c:\sporlan 2006\cooling idiosyncrasies
When mixing a calcium chloride brine for freezing ice creamwith a desired freezing point of minus 30°F or lower is neededand no hydrometer is available use a large Irish potato, if the potato does not float in the brine mixture add more calcium chloride to the brine solution.
Calcium Chloride Brine minus 30°F
c:\sporlan 2006\cooling idiosyncrasies
You exited FastFastBlue Dancing Flame
Methyl Chloride
c:\sporlan 2006\cooling idiosyncrasies
SO2
Rats .. Cockroaches disappearedPlants .. Grass, Produce diedCanaries, Budges, Parrots goneLong hoses, water, open windows
SO2 no smell, carbon filters
c:\sporlan 2006\cooling idiosyncrasies
Unique Historical ServiceTechniques
Do you remember: ………….
When hot water froze faster than cold water !!!
Temper proofing controls .. clear nail polish.
Service trucks carried sanitary napkins (Kotex)
Service trucks carried feminine deodorant spray (FDS)
Service trucks carried petroleum jelly (Vaseline)
Service trucks carried Vicks Vapor Rub or Basil
c:\sporlan 2006\cooling idiosyncrasies
You ARE the Perfect HVAC&R System
Compressor _________________Controller ___________________Control system _____________Piping network _Refrigerant ______________Evaporator ____________Lubricant _______Condenser __________________Head pressure ________Capacity control __________Filter / Drier _________________Purge system _______________Power supply _________________Fine Tuning _______________
HeartBrain
NervesCardiovascular system
Life bloodSkin / Sweat
(LDL / HDL) CholesterolLungs
Blood pressureHeart rate
LiverKidney
DietExercise
Comparing Systems
" Education is Just the Beginning "Modern ServiceTechnician
c:\sporlan 2006\cooling idiosyncrasies
Diagnostic Means
Manifold gauges _______________Periodic check __________________Thermometer ___________________________Fluid ailments (refrigerant, lubricant, H2O) _______Touch, Sound, Sight, Smell _____________________Maintenance ________________________Superheat / Sub-cooling _________________________Sight glass _____________________________Know how / Experience, Intuitiveness _____Preventative Care _________________________
Manometer / StethoscopeNon-destructive testing
TemperatureLaboratory analysis
SensesRoutine physicals
PulseMRI / X-Ray
Diagnostic skillsMedication
Modern ServiceTechnician
You ARE the Perfect HVAC&R System
" Education is Just the Beginning "
c:\sporlan 2006\cooling idiosyncrasies
Cold W.A.R. IntroducedJune 2003
W hether it’sA ir ConditioningR efrigeration
c:\sporlan 2006\cooling idiosyncrasies
Sporlan Division of Parker Hannifin has introduced a new service oriented no charge information support program titled“Cold W.A.R.” This monthly e-mail based only information network program is designed to provide you, the service technician, with a collection of associated technical informationtopic papers in a simple comprehensive format. Don’t miss thisopportunity to increase your existing knowledge base. Sign uptoday and start receiving your personal direct e-mail copy.
c:\sporlan 2006\cooling idiosyncrasies
c:\sporlan 2006\cooling idiosyncrasies
CONCLUSIONHaving been through this presentation,
it would be quite natural for you toconclude that it is virtually
impossible to design aperfect refrigeration
system.
This is probably true.
c:\sporlan 2006\cooling idiosyncrasies
“Refrigerant molecules are square, through constant and continuoususe the corners are rounded off, that’s why you need to add
additional refrigerant !!"
This reaction is similar to a box of cereal, it started off fullbut through constant moving and shaking
it settles and now looks only half full.
Why do I need to continuously add morerefrigerant every year?
Thought Provoking !!!
Customer
c:\sporlan 2006\cooling idiosyncrasies
Why do Women Live Longer
then Men ?
c:\sporlan 2006\cooling idiosyncrasies
Visit us at www.sporlan.com
The Sporlan Valve Division, Parker Hannifin assumes no obligations or liability for any advice furnished or for any results, property damage or personal injury including death that may result with respect to the use of this information. All such advice is given and accepted at users risk. This disclosure of information herein is not a license to operate under, or a recommendation to infringe any patent of Sporlan Division of Parker Hannifin or others.
Dated May 2006Supersedes
® Registered trademark of Sporlan Valve Division, Parker Hannifin Corporation, Cleveland Ohio USA© Copyright 2005 by Sporlan Valve Division, Parker Hannifin Inc