CE498 Lecture Nov 16

download CE498 Lecture Nov 16

of 34

Transcript of CE498 Lecture Nov 16

  • 7/27/2019 CE498 Lecture Nov 16

    1/34

    ENVIRONMENTAL ENGINEERING CONCRETESTRUCTURES

    CE 498 Design Project

    November 16, 21, 2006

  • 7/27/2019 CE498 Lecture Nov 16

    2/34

    OUTLINE

    INTRODUCTION

    LOADING CONDITIONS

    DESIGN METHOD

    WALL THICKNESS

    REINFORCEMENT

    CRACK CONTROL

  • 7/27/2019 CE498 Lecture Nov 16

    3/34

    INTRODUCTION

    Conventionally reinforced circular concrete tanks have

    been used extensively. They will be the focus of ourlecture today

    Structural design must focus on both the strength andserviceability. The tank must withstand applied loads

    without cracks that would permit leakage. This is achieved by:

    Providing proper reinforcement and distribution

    Proper spacing and detailing of construction joints

    Use of quality concrete placed using proper constructionprocedures

    A thorough review of the latest report by ACI 350 isimportant for understanding the design of tanks.

  • 7/27/2019 CE498 Lecture Nov 16

    4/34

    LOADING CONDITIONS

    The tank must be designed to withstand the loads that it

    will be subjected to during many years of use. Additionally,the loads during construction must also be considered.

    Loading conditions for partially buried tank.

    The tank must be designed and detailed to withstand the

    forces from each of these loading conditions

  • 7/27/2019 CE498 Lecture Nov 16

    5/34

    LOADING CONDITIONS

    The tank may also be subjected to uplift forces from

    hydrostatic pressure at the bottom when empty.

    It is important to consider all possible loading conditions onthe structure.

    Full effects of the soil loads and water pressure must be

    designed for without using them to minimize the effects ofeach other.

    The effects of water table must be considered for thedesign loading conditions.

  • 7/27/2019 CE498 Lecture Nov 16

    6/34

    DESIGN METHODS

    Two approaches exist for the design of RC members

    Strength design, and allowable stress design.

    Strength design is the most commonly adopted procedure forconventional buildings

    The use of strength design was considered inappropriate

    due to the lack of reliable assessment of crack widths atservice loads.

    Advances in this area of knowledge in the last two decadeshas led to the acceptance of strength design methods

    The recommendations for strength design suggest inflatedload factors to control service load crack widths in therange of 0.004 0.008 in.

  • 7/27/2019 CE498 Lecture Nov 16

    7/34

    Design Methods

    Service state analyses of RC structures should include

    computations of crack widths and their long term effectson the structure durability and functional performance.

    The current approach for RC design include computationsdone by a modified form of elastic analysis for composite

    reinforced steel/concrete systems. The effects of creep, shrinkage, volume changes, and

    temperature are well known at service level

    The computed stresses serve as the indices of performance

    of the structure.

  • 7/27/2019 CE498 Lecture Nov 16

    8/34

    DESIGN METHODS

    The load combinations to determine the required strength

    (U) are given in ACI 318. ACI 350 requires twomodifications

    Modification 1 the load factor for lateral liquid pressure istaken as 1.7 rather than 1.4. This may be over conservative

    due to the fact that tanks are filled to the top only duringleak testing or accidental overflow

    Modification 2 The members must be designed to meet therequired strength. The ACI required strength U must beincreased by multiplying with a sanitary coefficient

    The increased design loads provide more conservative designwith less cracking.

    Required strength = Sanitary coefficient X U

    Where, sanitary coefficient = 1.3 for flexure, 1.65 for directtension, and 1.3 for shear beyond the capacity provided by theconcrete.

  • 7/27/2019 CE498 Lecture Nov 16

    9/34

    WALL THICKNESS

    The walls of circular tanks are subjected to ring or hoop

    tension due to the internal pressure and restraint toconcrete shrinkage.

    Any significant cracking in the tank is unacceptable.

    The tensile stress in the concrete (due to ring tension from

    pressure and shrinkage) has to kept at a minimum to preventexcessive cracking.

    The concrete tension strength will be assumed 10% fc in thisdocument.

    RC walls 10 ft. or higher shall have a minimum thickness of12 in.

    The concrete wall thickness will be calculated as follows:

  • 7/27/2019 CE498 Lecture Nov 16

    10/34

    WALL THICKNESS

    Effects of shrinkage

    Figure 2(a) shows a block of concretewith a re-bar. The block height is 1 ft, tcorresponds to the wall thickness, thesteel area is As, and the steel percentageis r.

    Figure 2(b) shows the behavior of theblock assuming that the re-bar is absent.The block will shorten due to shrinkage.Cis the shrinkage per unit length.

    Figure 2(c) shows the behavior of theblock when the re-bar is present. The re-bar restrains some shortening.

    The difference in length between Fig.2(b) and 2(c) is xC, an unknown quantity.

  • 7/27/2019 CE498 Lecture Nov 16

    11/34

    WALL THICKNESS

    The re-bar restrains shrinkage of the concrete. As a result,

    the concrete is subjected to tension, the re-bar tocompression, but the section is in force equilibrium

    Concrete tensile stress is fcs = xCEc

    Steel compressive stress is fss= (1-x)CEs Section force equilibrium. So, rfss=fcs

    Solve for x from above equation for force equilibrium

    The resulting stresses are:

    fss=CEs[1/(1+nr)] and fcs=CEs[r/(1+nr)]

    The concrete stress due to an applied ring or hoop tensionof T will be equal to:

    T * Ec/(EcAc+EsAs) = T * 1/[Ac+nAs] = T/[Ac(1+nr)]

    The total concrete tension stress = [CEsAs + T]/[Ac+nAs]

  • 7/27/2019 CE498 Lecture Nov 16

    12/34

    WALL THICKNESS

    The usual procedure in tank design is to provide horizontal

    steel As for all the ring tension at an allowable stress fs asthough designing for a cracked section.

    Assume As=T/fs and realize Ac=12t

    Substitute in equation on previous slide to calculate tensionstress in the concrete.

    Limit the max. concrete tension stress to fc= 0.1 fc

    Then, the wall thickness can be calculated as

    t = [CEs+fsnfc]/[12fcfs]* T

    This formula can be used to estimate the wall thickness The values of C, coefficient of shrinkage for RC is in the

    range of 0.0002 to 0.0004.

    Use the value of C=0.0003

    Assume fs= allowable steel tension =18000 psi

    Therefore, wall thickness t=0.0003 T

  • 7/27/2019 CE498 Lecture Nov 16

    13/34

    WALL THICKNESS

    The allowable steel stress fs should not be made too small.

    Low fs will actually tend to increase the concrete stress andpotential cracking.

    For example, the concrete stress = fc = [CEs+fs]/[Acfs+nT]*T

    For the case of T=24,000 lb, n=8, Es=29*106 psi, C=0.0003

    and Ac=12 x 10 = 120 in3 If the allowable steel stress is reduced from 20,000 psi to

    10,000 psi, the resulting concrete stress is increased from266 psi to 322 psi.

    Desirable to use a higher allowable steel stress.

  • 7/27/2019 CE498 Lecture Nov 16

    14/34

    REINFORCEMENT

    The amount size and spacing of

    reinforcement has a great effecton the extent of cracking.

    The amount must be sufficientfor strength and serviceability

    including temperature andshrinkage effects

    The amount of temperature andshrinkage reinforcement isdependent on the length

    between construction joints

  • 7/27/2019 CE498 Lecture Nov 16

    15/34

    REINFORCEMENT

    The size of re-bars should be chosen recognizing that

    cracking can be better controlled by using larger number ofsmall diameter bars rather than fewer large diameter bars

    The size of reinforcing bars should not exceed #11.Spacing of re-bars should be limited to a maximum of 12

    in. Concrete cover should be at least 2 in. In circular tanks the locations of horizontal splices should

    be staggered by not less than one lap length or 3 ft.

    Reinforcement splices should confirm to ACI 318

    Chapter 12 of ACI 318 for determining splice lengths. The length depends on the class of splice, clear cover, clear

    distance between adjacent bars, and the size of the bar,concrete used, bar coating etc.

  • 7/27/2019 CE498 Lecture Nov 16

    16/34

    CRACK CONTROL

    Crack widths must be minimized in tank walls to preventleakage and corrosion of reinforcement

    A criterion for flexural crack width is provided in ACI 318.This is based on the Gergely-Lutz equation z=fs(dcA)

    1/3

    Where z = quantity limiting distribution of flexural re-bar

    dc= concrete cover measured from extreme tension fiber to

    center of bar located closest.

    A = effective tension area of concrete surrounding theflexural tension reinforcement having the same centroid asthe reinforcement, divided by the number of bars.

  • 7/27/2019 CE498 Lecture Nov 16

    17/34

    CRACK CONTROL

    In ACI 350, the cover is taken equal to 2.0 in. for any cover

    greater than 2.0 in. Rearranging the equation and solving for the maximum bar

    spacing give: max spacing = z3/(2 dc2 fs

    3)

    Using the limiting value of z given by ACI 350, the maximum

    bar spacing can be computed For ACI 350, z has a limiting value of 115 k/in.

    For severe environmental exposures, z = 95 k/in.

  • 7/27/2019 CE498 Lecture Nov 16

    18/34

    ANALYSIS OF VARIOUS TANKS

    Wall with fixed base and free top; triangular load

    Wall with hinged base and free top; triangular load andtrapezoidal load

    Wall with shear applied at top

    Wall with shear applied at base

    Wall with moment applied at top

    Wall with moment applied at base

  • 7/27/2019 CE498 Lecture Nov 16

    19/34

    CIRCULAR TANK ANALYSIS

    In practice, it would be rare that a base would be fixed

    against rotation and such an assumption would lead to animproperly designed wall.

    For the tank structure, assume

    Height = H = 20 ft.

    Diameter of inside = D = 54 ft.

    Weight of liquid = w = 62.5 lb/ft3

    Shrinkage coefficient = C = 0.0003

    Elasticity of steel = Es = 29 x 106 psi

    Ratio of Es/Ec = n = 8

    Concrete compressive strength = fc = 4000 psi

    Yield strength of reinforcement = fy = 60,000 psi

  • 7/27/2019 CE498 Lecture Nov 16

    20/34

    It is difficult to predict the behavior of the subgrade and its

    effect upon restraint at the base. But, it is more reasonableto assume that the base is hinged rather than fixed, whichresults in more conservative design.

    For a wall with a hinged base and free top, the coefficients

    to determine the ring tension, moments, and shears in thetank wall are shown in Tables A-5, A-7, and A-12 of theAppendix

    Each of these tables, presents the results as functions ofH2/Dt, which is a parameter.

    The values of thickness t cannot be calculated till the ringtension T is calculated.

    Assume, thickness = t = 10 in.

    Therefore, H2/Dt = (202)/(54 x 10/12) = 8.89 (approx. 9 in.)

    CIRCULAR TANK ANALYSIS

  • 7/27/2019 CE498 Lecture Nov 16

    21/34

    Table A-5 showing the ring tension values

  • 7/27/2019 CE498 Lecture Nov 16

    22/34

    Table A-7, A-12 showing the moment and shear

  • 7/27/2019 CE498 Lecture Nov 16

    23/34

    CIRCULAR TANK ANALYSIS

    In these tables, 0.0 H corresponds to the top of the tank,

    and 1.0 H corresponds to the bottom of the tank. The ring tension per foot of height is computed by

    multiplying wu HR by the coefficients in Table A-5 for thevalues of H2/Dt=9.0

    wu for the case of ring tension is computed as: wu = sanitary coefficient x (1.7 x Lateral Forces)

    wu = 1.65 x (1.7 x 62.5) = 175.3 lb/ft3

    Therefore, wu HR = 175.3 x 20 x 54/2 = 94, 662 lb/ft3

    The value of wu HR corresponds to the behavior where thebase is free to slide. Since, it cannot do that, the value ofwu HR must be multiplied by coefficients from Table A-5

  • 7/27/2019 CE498 Lecture Nov 16

    24/34

    CIRCULAR TANK ANALYSIS A plus sign indicates tension, so there is a slight

    compression at the top, but it is very small.

    The ring tension is zero at the base since it is assumed thatthe base has no radial displacement

    Figure compares the ring tension for tanks with free slidingbase, fixed base, and hinged base.

  • 7/27/2019 CE498 Lecture Nov 16

    25/34

    CIRCULAR TANK ANALYSIS

    Which case is conservative? (Fixed or hinged base)

    The amount of ring steel required is given by: As = maximum ring tension / (0.9 Fy)

    As = 67494/(0.9 * 60000) = 1.25 in2/ft.

    Therefore at 0.7H use #6bars spaced at 8 in. on center intwo curtains.

    Resulting As = 1.32in2/ft.

    The reinforcement along the height of the wall can bedetermined similarly, but it is better to have the same barand spacing.

    Concrete cracking check

    The maximum tensile stress in the concrete under serviceloads including the effects of shrinkage is

    fc = [CEsAs + Tmax, unfactored]/[Ac+nAs] = 272 psi < 400 psi

    Therefore, adequate

  • 7/27/2019 CE498 Lecture Nov 16

    26/34

    CIRCULAR TANK ANALYSIS

    The moments in vertical wall strips

    that are considered 1 ft. wide arecomputed by multiplying wuH

    3 bythe coefficients from table A-7.

    The value of wu for flexure =

    sanitary coefficient x (1.7 x lateralforces)

    Therefore, wu = 1.3 x 1.7 x 62.5 =138.1 lb/ft3

    Therefore wuH3 = 138.1 x 203 =

    1,104,800 ft-lb/ft

    The computed moments along theheight are shown in the Table.

    The figure includes the moment for

    both the hinged and fix conditions

  • 7/27/2019 CE498 Lecture Nov 16

    27/34

    CIRCULAR TANK ANALYSIS

    The actual restraint is somewhere in between fixed and

    hinged, but probably closer to hinged. For the exterior face, the hinged condition provides a

    conservative although not wasteful design

    Depending on the fixity of the base, reinforcing may be

    required to resist moment on the interior face at the lowerportion of the wall.

    The required reinforcement for the outside face of the wallfor a maximum moment of 5,524 ft-lb/ft. is:

    Mu/(ff

    cbd2) = 0.0273 (where d = t cover d

    bar/2)

    From the standard design aid of Appendix A, take the valueof 0.0273 and obtain a value for w from the Table.

    Obtain w=0.0278

    Required As = wbdfc/fy = 0.167 in2

  • 7/27/2019 CE498 Lecture Nov 16

    28/34

    CIRCULAR TANK ANALYSIS

    r=0.167/(12 x 7.5) = 0.00189

    rmin = 200/Fy = 0.0033 > 0.00189 Use #5 bars at the maximum allowable spacing of 12 in.

    As = 0.31 in2 and r = 0.0035

    The shear capacity of a 10 in. wall with fc=4000 psi is Vc= 2 (fc)

    0.5 bwd = 11,384 kips

    Therefore, f Vc = 0.85 x 11,284 = 9676 kips

    The applied shear is given by multiplying wu H2 with the

    coefficient from Table A-12 The value of wu is determined with sanitary coefficient = 1.0

    (assuming that no steel rft. will be needed)

    wuH2 = 1.0 x 1.7 x 62.5 x 202 = 42,520 kips

    Applied shear = Vu = 0.092 x wuH2 = 3912 kips < fVc

  • 7/27/2019 CE498 Lecture Nov 16

    29/34

    RECTANGULAR TANK DESIGN

    The cylindrical shape is structurally best suited for tank

    construction, but rectangular tanks are frequentlypreferred for specific purposes

    Rectangular tanks can be used instead of circular tanks whenthe footprint needs to be reduced

    Rectangular tanks are used where partitions or tanks withmore than one cell are needed.

    The behavior of rectangular tanks is different from thebehavior of circular tanks

    The behavior of circular tanks is axisymmetric. That is thereason for our analysis of only unit width of the tank

    The ring tension in circular tanks was uniform around thecircumference

  • 7/27/2019 CE498 Lecture Nov 16

    30/34

    RECTANGULAR TANK DESIGN

    The design of rectangular tanks is very similar in concept

    to the design of circular tanks The loading combinations are the same. The modifications

    for the liquid pressure loading factor and the sanitarycoefficient are the same.

    The major differences are the calculated moments, shears,and tensions in the rectangular tank walls.

    The requirements for durability are the same for rectangularand circular tanks. This is related to crack width control,which is achieved using the Gergely Lutz parameter z.

    The requirements for reinforcement (minimum or otherwise)are very similar to those for circular tanks.

    The loading conditions that must be considered for thedesign are similar to those for circular tanks.

  • 7/27/2019 CE498 Lecture Nov 16

    31/34

    RECTANGULAR TANK DESIGN

    The restraint condition at the base is needed to determine

    deflection, shears and bending moments for loadingconditions.

    Base restraint conditions considered in the publicationinclude both hinged and fixed edges.

    However, in reality, neither of these two extremes actuallyexist.

    It is important that the designer understand the degree ofrestraint provided by the reinforcing that extends into thefooting from the tank wall.

    If the designer is unsure, both extremes should beinvestigated.

    Buoyancy Forces must be considered in the design process

    The lifting force of the water pressure is resisted by the

    weight of the tank and the weight of soil on top of the slab

  • 7/27/2019 CE498 Lecture Nov 16

    32/34

    RECTANGULAR TANK BEHAVIOR

    x

    y

    y

    z

    Mx= moment per unit width about the x-axis

    stretching the fibers in the y direction when theplate is in the x-y plane. This momentdetermines the steel in the y (vertical direction).

    My= moment per unit width about the y-axisstretching the fibers in the x direction when the

    plate is in the x-y plane. This momentdetermines the steel in the x (horizontaldirection).

    Mz= moment per unit width about the z-axisstretching the fibers in the y direction when the

    plate is in the y-z plane. This moment determinesthe steel in the y (vertical direction).

  • 7/27/2019 CE498 Lecture Nov 16

    33/34

    RECTANGULAR TANK BEHAVIOR

    Mxy or Myz = torsion or twisting moments for plate or wall in the x-y and

    y-z planes, respectively.

    All these moments can be computed using the equations

    Mx=(Mx Coeff.) x q a2/1000

    My=(M

    yCoeff.) x q a2/1000

    Mz=(Mz Coeff.) x q a2/1000

    Mxy=(Mxy Coeff.) x q a2/1000

    Myz=(Myz Coeff.) x q a2/1000

    These coefficients are presented in Tables 2 and 3 for rectangular

    tanks

    The shear in one wall becomes axial tension in the adjacent wall.Follow force equilibrium - explain in class.

  • 7/27/2019 CE498 Lecture Nov 16

    34/34

    RECTANGULAR TANK BEHAVIOR

    The twisting moment effects such as Mxy may be used to

    add to the effects of orthogonal moments Mx and My forthe purpose of determining the steel reinforcement

    The Principal of Minimum Resistance may be used fordetermining the equivalent orthogonal moments for design

    Where positive moments produce tension: Mtx = Mx + |Mxy|

    Mty = My + |Mxy|

    However, if the calculated Mtx < 0,

    then Mtx

    =0 and Mty

    =My

    + |Mxy

    2/Mx

    | > 0

    If the calculated Mty < 0

    Then Mty = 0 and Mtx = Mx + |Mxy2/My| > 0

    Similar equations for where negative moments producetension