Product Description
� 240V AC maximum.
� 3-phase 4-wire, 3-phase 3-wire,1-phase 3-wire, 1-phase 2-wire.
� 600 ampere maximum main lugs.
� 400 ampere maximum main breaker.� 100 ampere maximum branch break-
ers (2 Pole 125A).
� Bolt-on branch breakers.
� Tin plated aluminum bus or silverplated copper bus.
� Factory assembled.
Type PRL1a
Application Description
� Fully rated or series rated.
� Interrupting ratings up to 200 kA sym-metrical.
� Suitable for use as Service EntranceEquipment, when specified onthe order.
Standards and Certifications
� CSA - C22.2 No. 29
� Federal Specification W-P-115c.
Options and Accessories
� Refer to Page 2-29.
Layout and Sizing
� Refer to Page 2-3.
Product Selection
Table 1-6. Base Configurations — PRL1a
Table 1-7. Branch Circuit Breakers — PRL1a
� 1-pole breakers are rated 120V AC maximum. 240 volt breakers must be used on 3-phase, 3-wire, 240 volt delta systems or on the high leg of a mid-
point delta grounded system. 50 ampere devices are available as 2-pole only. GFCI for 5 mA personnel protection.
GFP for 30 mA equipment protection. Combination Arc fault circuit breaker. HID (High Intensity Discharge) rated breaker. Switching Neutral Breaker. 1-pole device requires 2-pole space, 2-pole device requires 3-pole space.� Solenoid operated breaker.
AmpereRating
InterruptingRating(kA Sym.)240V AC
BreakerType
Main Lug Only
100225400600
————
————
Main Breaker
100100100100100100100
10 18 22 65 65100100
BABEHD/FDBQBHWEDFDEDHHFD
225225
65100
EDEDH
400400400400
65 65100200
DKKDHKDKDC
Bolt-on = BAB, QBHW, QBGF, QBHGF,QBGFEP, QBHGFEP, QBAF, QBAG
AmpereRating
InterruptingRating(kA Sym.)240V AC �
BreakerType
15 – 3015 – 607080 – 100
12515 – 50
15 – 50
15 – 20
10101010
10101010
DNBA (twin)BABBABBAB
BAB (2 Pole)QBGF
QBGFEP
QBCAF
15 – 6015 – 3015 – 30
101010
BAB-D
BAB-C
BABRSP
15 – 607080 – 10012515 – 3015 – 30
222222222222
QBHWQBHWQBHWQBHW (2 Pole)QBHGF
QBHGFEP
Table 2-1.
Table 2-2.
PanelboardsPow-R-Line C Panelboards
PRL1a
-
8/17/2019 Catalogo-panel Electrico Ch
2/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Product Selection
Table 1-8. Standard Catalogue Numbering
Ampere
Rating
Main
Device
Type
Number
of Branch
Circuits
Catalogue Number
3Ph, 4W
Aluminum
1Ph, 3W
Aluminum
3Ph, 4W
Copper
1Ph, 3W
Copper
Main Lug Only
100
-
-
-
-
18
24
30
42
P1aL4A1-18
P1aL4A1-24
P1aL4A1-30
P1aL4A1-42
P1aL1A1-18
P1aL1A1-24
P1aL1A1-30
P1aL1A1-42
P1aL4C1-18
P1aL4C1-24
P1aL4C1-30
P1aL4C1-42
P1aL1C1-24
P1aL1C1-30
P1aL1C1-42
P1aL1C1-18
225
-
-
-
-
-
-
-
18
24
30
42
60
72
84
P1aL4A2-18
P1aL4A2-24
P1aL4A2-30
P1aL4A2-42
P1aL4A2-60
P1aL4A2-72
P1aL4A2-84
P1aL1A2-18
P1aL1A2-24
P1aL1A2-30
P1aL1A2-42
P1aL1A2-60
P1aL1A2-72
P1aL1A2-84
P1aL4C2-18
P1aL4C2-24
P1aL4C2-30
P1aL4C2-42
P1aL4C2-60
P1aL4C2-72
P1aL4C2-84
P1aL1C2-18
P1aL1C2-24
P1aL1C2-30
P1aL1C2-42
P1aL1C2-60
P1aL1C2-72
P1aL1C2-84
400
-
-
-
-
-
-
24
30
42
60
72
84
P1aL4A4-24
P1aL4A4-30
P1aL4A4-42
P1aL4A4-60
P1aL4A4-72
P1aL4A4-84
P1aL1A4-24
P1aL1A4-30
P1aL1A4-42
P1aL1A4-60
P1aL1A4-72
P1aL1A4-84
P1aL4C4-24
P1aL4C4-30
P1aL4C4-42
P1aL4C4-60
P1aL4C4-72
P1aL4C4-84
P1aL1C4-24
P1aL1C4-30
P1aL1C4-42
P1aL1C4-60
P1aL1C4-72
P1aL1C4-84
600
-
-
-
-
-
-
24
30
42
60
72
84
P1aL4C6-24
P1aL4C6-30
P1aL4C6-42
P1aL4C6-60
P1aL4C6-72
P1aL4C6-84
P1aL1C6-24
P1aL1C6-30
P1aL1C6-42
P1aL1C6-60
P1aL1C6-72
P1aL1C6-84
Main Breaker
100 BAB
15
2127
P1aB4A1-15BAB
P1aB4A1-21BABP1aB4A1-27BAB
P1aB1A1-15BAB
P1aB1A1-21BABP1aB1A1-27BAB
P1aB4C1-15BAB
P1aB4C1-21BABP1aB4C1-27BAB
P1aB1C1-15BAB
P1aB1C1-21BABP1aB1C1-27BAB
100 EHD
18
24
30
P1aB4A1-18EHD
P1aB4A1-24EHD
P1aB4A1-30EHD
P1aB1A1-18EHD
P1aB1A1-24EHD
P1aB1A1-30EHD
P1aB4C1-18EHD
P1aB4C1-24EHD
P1aB4C1-30EHD
P1aB1C1-18EHD
P1aB1C1-24EHD
P1aB1C1-30EHD
225 ED
24
30
42
60
72
P1aB4A2-24ED
P1aB4A2-30ED
P1aB4A2-42ED
P1aB4A2-60ED
P1aB4A2-72ED
P1aB1A2-24ED
P1aB1A2-30ED
P1aB1A2-42ED
P1aB1A2-60ED
P1aB1A2-72ED
P1aB4C2-24ED
P1aB4C2-30ED
P1aB4C2-42ED
P1aB4C2-60ED
P1aB4C2-72ED
P1aB1C2-24ED
P1aB1C2-30ED
P1aB1C2-42ED
P1aB1C2-60ED
P1aB1C2-72ED
400 DK
24
30
42
60
72
P1aB4A4-24DK
P1aB4A4-30DK
P1aB4A4-42DK
P1aB4A4-60DK
P1aB4A4-72DK
P1aB1A4-24DK
P1aB1A4-30DK
P1aB1A4-42DK
P1aB1A4-60DK
P1aB1A4-72DK
P1aB4C4-24DK
P1aB4C4-30DK
P1aB4C4-42DK
P1aB4C4-60DK
P1aB4C4-72DK
P1aB1C4-24DK
P1aB1C4-30DK
P1aB1C4-42DK
P1aB1C4-60DK
P1aB1C4-72DK
Pow-R-Line 1a Catalogue Code
P1a B 4 A 4 - 42 KDC 400
Panelboard Type L - Main Lugs Only
B - Bottom MainBreaker
T - Top Main Breaker
1 - 1phase, 3 wire
3 - 3phase, 3 wire
4 - 3phase, 4 wire
A - Aluminum
C - Copper
1 - 100 amperes
2 - 225 amperes
4 - 400 amperes
6 - 600 amperes
-
-
-
Number of
Circuits
Main
Breaker
(if selected)
Breaker
Trip
Rating
� All possible combinations not shown for alternate main breakers, substitue breaker type suffix from Table 2-1. Add breaker trip rating to end of catalogue number.
Table 2-3.
2-2PanelboardsPow-R-Line C Panelboards
PRL1a
-
8/17/2019 Catalogo-panel Electrico Ch
3/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Box Sizing and Selection
Assembled Circuit Breaker Panelboards
Box size and box and trim catalogue num-bers for all standard panelboard types arefound inTable 2-4..
Instructions1. Using description of the required
panelboard, select the rating andtype of main required.
2. Count the total number of branchcircuit poles, including provisions,required in the panelboard. Do notcount main breaker poles. Convert2- or 3-pole branch breaker tosingle-poles, i.e., 3-pole breaker,count as 3 poles.
Determine sub-feed breaker orthrough-feed lug requirements.
3. Select the main ampere rating
section fromTable 2-4.
4. Select panelboard type from firstcolumn.
5. From Step #2, determine the num-ber of branch circuits in Column 2.
6. Read box size, box and trimcatalogue numbers across columnsto the right. Specify surface or flushmounting on the order.
Cabinets
Fronts are code-gauge steel, ASA-61 lightgray painted finish.
Boxes are code-gauge galvanized steelwithout knockouts. Standard depth is5-3/4 inches (146.1 mm). Standard widthis 20 inches (508.0 mm). An optional 28-inch (711.2 mm) wide box is available.
Top and Bottom Gutters
5-1/2 inches (139.7 mm) minimum.
Table 2-4. PRL1a Panelboard Sizing
MainsAmpere(Maximum)
Number ofBranchCircuit
Box Dimensions(Inches) Box
CatalogueNumber
TrimCatalogueNumber
H W D
MAIN LUGS ONLY OR MAIN LUGS WITH SUB-FEED LUGS
10018243042
30303036
20202020
5.755.755.755.75
EZB2030RCEZB2030RCEZB2030RCEZB2036RC
EZT2030 S or FEZT2030 S or FEZT2030 S or FEZT2036 S or F
225
18243042607284
30363642546072
20202020202020
5.755.755.755.755.755.755.75
EZB2030RCEZB2036RCEZB2036RCEZB2042RCEZB2054RCEZB2060RCEZB2072RC
EZT2030 S or FEZT2036 S or FEZT2036 S or FEZT2042 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or F
400� /600
243042607284
424854607272
202020202020
5.755.755.755.755.755.75
EZB2024RCEZB2030RCEZB2054RCEZB2060RCEZB2072RCEZB2072RC
EZT2042 S or FEZT2048 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or FEZT2072 S or F
MAIN LUGS WITH THROUGH-FEED LUGS
10018243042
30303036
20202020
5.755.755.755.75
EZB2030RCEZB2030RCEZB2030RCEZB2036RC
EZT2030 S or FEZT2030 S or FEZT2030 S or FEZT2036 S or F
225
182430426072
303636426060
202020202020
5.755.755.755.755.755.75
EZB2030RCEZB2036RCEZB2036RCEZB2042RCEZB2060RCEZB2072RC
EZT2030 S or FEZT2036 S or FEZT2036 S or FEZT2042 S or FEZT2060 S or FEZT2072 S or F
400/600
2430426072
4854607272
2020202020
5.755.755.755.755.75
EZB2048RCEZB2054RCEZB2060RCEZB2072RCEZB2072RC
EZT2048 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or FEZT2072 S or F
MAIN LUGS WITH SURGE PROTECTION DEVICE
10018243042
30303036
20202020
5.755.755.755.75
EZB2030RCEZB2030RCEZB2030RCEZB2036RC
EZT2030 S or FEZT2030 S or FEZT2030 S or FEZT2036 S or F
225
18243042607284
30363642546072
20202020202020
5.755.755.755.755.755.755.75
EZB2030RCEZB2036RCEZB2036RCEZB2042RCEZB2054RCEZB2060RCEZB2072RC
EZT2030 S or FEZT2036 S or FEZT2036 S or FEZT2042 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or F
400/600
2430426072
4854546072
2020202020
5.755.755.755.755.75
EZB2048RCEZB2054RCEZB2054RCEZB2060RCEZB2072RC
EZT2048 S or FEZT2054 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or F
� In a Sub-Feed configuration, maximum incoming and outgoing cables are 1per phase #500kcmil.
Through-Feed lugs are recommended for 400A applications.
PanelboardsPow-R-Line C Panelboards
PRL1a
-
8/17/2019 Catalogo-panel Electrico Ch
4/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Box Sizing and Selection
Assembled Circuit Breaker Panelboards
Box size and box and trim cataloguenumbers for all standard panelboardtypes are found inTable 2-5.
Instructions1. Using description of the required
panelboard, select the rating andtype of main required.
2. Count the total number of branchcircuit poles, including provisions,required in the panelboard. Do notcount main breaker poles. Convert2- or 3-pole branch breaker tosingle-poles, i.e., 3-pole breaker,count as 3 poles.
Determine sub-feed breaker orthrough-feed lug requirements.
3. Select the main ampere rating
section fromTable 2-5.
4. Select panelboard type from firstcolumn, main breaker frame fromsecond column.
5. From Step #2, determine the num-ber of branch circuits in Column 3.
6. Read box size, box and trimcatalogue numbers across columnsto the right. Specify surface or flushmounting on the order.
Cabinets
Fronts are code-gauge steel, ASA-61light gray painted finish.
Boxes are code-gauge galvanized steelwithout knockouts. Standard depth is 5-3/4 inches (146.1 mm). Standard width is20 inches (508.0 mm). An optional 28-inch (711.2 mm) wide box is available.
Top and Bottom Gutters
5-1/2 inches (139.7 mm) minimum.
Table 1-11. PRL1a Panelboard Sizing
Table 1-12. Metric box dimensions:
AmpereRating
Main BreakerTypes andPosition
NumberBranch Cct.Spaces
BoxDimensions(Inches)
BoxCatalogueNumber
TrimCatalogueNumber
H W D
100 BAB, QBHW(Horizontal)
15, 21, 27 30 20 5.75 EZB2030RC EZT2030 S or F
100/225 EHD, ED, EDH,FD(Vertical)
18, 2430426072, 84
3642486072
2020202020
5.755.755.755.755.75
EZB2036RCEZB2042RCEZB2048RCEZB2060RCEZB2072RC
EZT2036 S or FEZT2042 S or FEZT2048 S or FEZT2060 S or FEZT2072 S or F
400DK, KD, HKD,KDC(Vertical)
24304260, 72
48546072
20202020
5.755.755.755.75
EZB2048RCEZB2054RCEZB2060RCEZB2072RC
EZT2048 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or F
MAIN BREAKER WITH THROUGH-FEED LUGS
100 BAB, QBHW(Horizontal)
15, 21, 27 30 20 5.75 EZB2030RC EZT2030 S or F
100/225 EHD, HFD, FD(Vertical)
1824, 30426072
3642546072
2020202020
5.755.755.755.755.75
EZB2036RCEZB2042RCEZB2054RCEZB2060RCEZB2072RC
EZT2036 S or FEZT2042 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or F
400DK, KD, HKD,KDC(Vertical)
243042
607272
202020
5.755.755.75
EZB2060RCEZB2072RCEZB2072RC
EZT2060 S or FEZT2072 S or FEZT2072 S or F
MAIN BREAKER WITH SURGE PROTECTION DEVICE
100 BAB, QBHW(Horizontal)
15, 21, 27 42 20 5.75 EZB2042RC EZT2042 S or F
100/225 EHD, ED, EDH,FD(Vertical)
182430426072
484854607272
202020202020
5.755.755.755.755.755.75
EZB2048RCEZB2048RCEZB2054RCEZB2060RCEZB2072RCEZB2072RC
EZT2048 S or FEZT2048 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or FEZT2072 S or F
400DK, KD, HKD,KDC(Vertical)
2430, 426072
48549090
20202020
5.755.755.755.75
EZB2048RCEZB2054RCEZB2090RCEZB2090RC
EZT2048 S or FEZT2054 S or FEZT2090 S or FEZT2090 S or F
Box CatalogueNumber
Dimensions in mm
Height Width Depth
EZB2030RCEZB2036RCEZB2042RCEZB2048RCEZB2054RCEZB2060RCEZB2072RCEZB2090RC
762 914106712191372152418282286
508.0508.0508.0508.0508.0508.0508.0508.0
146146146146146146146146
Table 2-5.
Table 2-6.
2-4PanelboardsPow-R-Line C Panelboards
PRL1a
-
8/17/2019 Catalogo-panel Electrico Ch
5/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Product Description
� 600Y/347 V AC.
� 480Y/277V AC .
� 125V AC
� 3-phase 4-wire
� 1-phase 3-wire, 1-phase 2-wire.
� 3-phase 3-wire.
� 600 ampere maximum main lugs.
� 400 ampere maximum main breaker.
� 100 ampere maximum branch break-ers.
� Bolt-on branch breakers.
� Tin plated aluminum bus or silverplated copper bus.
� Factory assembled.
Type PRL2a
Application Description
� Fully rated or series rated.� Interrupting ratings up to 200 kA sym-
metrical.
� Suitable for use as Service EntranceEquipment, when specified onthe order.
Standards and Certifications
� CSA C22.2 No. 29
� Federal Specification W-P-115c.
Options and Accessories
� Refer to Page 2-29.
Layout and Sizing
� Refer to Page 2-7.
Product Selection
Table 1-13. Base Configuration — PRL2a
Table 1-14. Branch Circuit Breakers — PRL2a
� Interrupting ratings in this column are applicable to 120V AC for 1-pole breakers. At 480V, must be used on 480Y/277V grounded wye systems only. Solenoid operated breaker. GFP for 30 mA equipment protection. Requires 2-pole spaces. 277V AC only. HID (High Intensity Discharge) rated breaker. 240V AC maximum rating for these systems. At 600V, must be used on 600Y/347V grounded wye systems only.
AmpereRating
Interrupting Rating(kA Symmetrical)
BreakerType
240V AC 480Y/277V AC 600Y/347V AC 125/250V DC
Main Lug Only
100225400600
————
————
————
————
————
Main Breaker
100100100
65 65 18
14 14 14
—10—
141410
GHBGBHEHD
100100100100
65 18100200
35 14 65100
18142535
10102222
FDFDBHFDFDC
225225225225225
65 18 65100200
— 14 35 65100
—14182535
—10102222
EDFDBFDHFDFDC
250250250
65100200
35 65100
182535
102222
JDHJDJDC
400400400
65100200
35 65100
253565
102222
KDHKDKDC
AmpereRating
Interrupting Rating(kA Symmetrical)
BreakerType
240V AC 480Y/277V AC 600Y/347V AC 125/250V DC
15 – 6015 – 60
70 – 10070 – 10015 – 30
6565
656565
1414
141414
—10
—10—
1414
1414—
GHB
GBH
GHB
GBH
GHQRSP
15 – 6015 – 20
——
1414
——
——
GHBGFEP GHBHID
Provision — — — — —
Table 2-8.
Table 2-7.
PanelboardsPow-R-Line C Panelboards
PRL2a
-
8/17/2019 Catalogo-panel Electrico Ch
6/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Product Selection
Table 1-15. Standard Catalogue Numbering
Ampere
Rating
Main
Device
Type
Number
of Branch
Circuits
Catalogue Number
3Ph, 4W
Aluminum
1Ph, 3W
Aluminum
3Ph, 4W
Copper
1Ph, 3W
CopperMain Lug Only
100
18
24
30
42
P2aL4A1-18
P2aL4A1-24
P2aL4A1-30
P2aL4A1-42
-
-
-
-
P2aL4C1-18
P2aL4C1-24
P2aL4C1-30
P2aL4C1-42
-
-
-
-
225
24
30
42
60
72
P2aL4A2-24
P2aL4A2-30
P2aL4A2-42
P2aL4A2-60
P1aL4A2-72
-
-
-
-
-
P2aL4C2-24
P2aL4C2-30
P2aL4C2-42
P2aL4C2-60
P2aL4C2-72
-
-
-
-
-
400
24
30
42
60
72
P2aL4A4-24
P2aL4A4-30
P2aL4A4-42
P2aL4A4-60
P2aL4A4-72
-
-
-
-
-
P2aL4C4-24
P2aL4C4-30
P2aL4C4-42
P2aL4C4-60
P2aL4C4-72
-
-
-
-
-
600
24
30
42
60
72
-
-
-
-
-
-
-
-
-
-
P2aL4C6-24
P2aL4C6-30
P2aL4C6-42
P2aL4C6-60
P2aL4C6-72
-
-
-
-
-
Main Breaker
100 GBH
15
21
27
P2aB4A1-15GBH
P2aB4A1-21GBH
P2aB4A1-27GBH
-
-
-
P2aB4C1-15GBH
P2aB4C1-21GBH
P2aB4C1-27GBH
-
-
-
100 FDB
18
24
30
P2aB4A1-18FDB
P2aB4A1-24FDB
P2aB4A1-30FDB
-
-
-
P2aB4C1-18FDB
P2aB4C1-24FDB
P2aB4C1-30FDB
-
-
-
225 FDB
24
30
42
60
72
P2aB4A2-24FDB
P2aB4A2-30FDB
P2aB4A2-42FDB
P2aB4A2-60FDB
P2aB4A2-72FDB
-
-
-
-
-
P2aB4C2-24FDB
P2aB4C2-30FDB
P2aB4C2-42FDB
P2aB4C2-60FDB
P2aB4C2-72FDB
-
-
-
-
-
400 KD
24
30
42
60
72
P2aB4A4-24KD
P2aB4A4-30KD
P2aB4A4-42KD
P2aB4A4-60KD
P2aB4A4-72KD
-
-
-
-
-
P2aB4C4-24KD
P2aB4C4-30KD
P2aB4C4-42KD
P2aB4C4-60KD
P2aB4C4-72KD
-
-
-
-
-
Pow-R-Line 2a Catalogue Code
P2a B 4 A 4 - 42 KDC 400
Panelboard Type L - Main Lugs Only
B - Bottom MainBreaker
T - Top Main Breaker
1 - 1phase, 3 wire
3 - 3phase, 3 wire
4 - 3phase, 4 wire
A - Aluminum
C - Copper
1 - 100 amperes
2 - 225 amperes
4 - 400 amperes
6 - 600 amperes
-
-
-
Number of
Circuits
Main
Breaker
(if selected)
Breaker
Trip
Rating
� All possible combinations not shown. For alternate main breakers, substitue breaker type suffix from Table 2-7. Add breaker trip rating to end of catalogue number.
Table 2-9.
2-6PanelboardsPow-R-Line C Panelboards
PRL2a
-
8/17/2019 Catalogo-panel Electrico Ch
7/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Box Sizing and Selection
Assembled Circuit Breaker Panelboards
Box size and box and trim catalogue num-bers for all standard panelboard types arefound inTable 2-10 and 2-11.
Instructions1. Select the rating and types of mains
required from Tables.
2. Count the total number of branchcircuit poles (including spaces)required in the panelboard. Do notcount main breaker poles. Convert 2or 3 pole branch breakers to singlepoles, i.e., 3-pole breaker, count as 3poles. (140 amps per connector max-imum).
3. Using the correct table, type ofmains and ampere rating per step 1above, find total on the table, use
the next higher number.4. Read box size, box and trim
catalogue numbers across column tothe right. On trim catalogue num-bers, specify surface or flush mount-ing on the order.
Cabinets
Fronts are code-gauge steel, ASA-61 lightgray painted finish.
Boxes are code-gauge galvanized steelwithout knockouts. Standard depth is5-3/4 inches (146.1 mm). Standard widthis 20 inches (508.0 mm).
Top and Bottom Gutters
5-1/2 inches (139.7 mm) minimum.
Table 1-18. Metric box dimensions
BoxCatalogueNumber
Dimensions in mm
Height Width Depth
EZB2030RCEZB2036RCEZB2042RCEZB2048RCEZB2054RCEZB2060RCEZB2072RC
76291410671219137215241828
508508508508508508508
146146146146146146146
Table 1-16. PRL2a Panelboard Sizing
Table 1-17. PRL2a Panelboard Sizing
Main Lugs Only or Main Lugs with Sub-Feed Lugs
Mains AmpereRating
Number ofBranch Circuit
Poles
Box DimensionsInches
BoxCatalogueNumber
TrimCatalogueNumberH W D
100 Amp Main Lugs 18, 24, 30
42
30
36
20
20
5-3/4
5-3/4
EZB2030RC
EZB2036RC
EZT2030 S or F
EZT2036 S or F225 Amp Main Lugs 18
24, 3042607284
303642546072
202020202020
5-3/45-3/45-3/45-3/45-3/45-3/4
EZB2030RCEZB2036RCEZB2042RCEZB2054RCEZB2060RCEZB2072RC
EZT2030 S or FEZT2036 S or FEZT2042 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or F
400/600 Amp MainLugs
24304260
72, 84
4248546072
2020202020
5-3/45-3/45-3/45-3/45-3/4
EZB2042RCEZB2048RCEZB2054RCEZB2060RCEZB2072RC
EZT2042 S or FEZT2048 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or F
Main Lugs with Through-Feed Lugs
100 Amp Main Lugs 18, 24, 3042
3036
2020
5-3/45-3/4
EZB2030RCEZB2036RC
EZT2030 S or FEZT2036 S or F
225 Amp Main Lugs 18, 2430426072
3642486072
2020202020
5-3/45-3/4
5-3/45-3/45-3/4
EZB2036RCEZB2042RC
EZB2048RCEZB2060RCEZB2072RC
EZT2036 S or FEZT2042 S or F
EZT2048 S or FEZT2060 S or FEZT2072 S or F
400/600 Amp MainLugs
243042
60, 72
48546072
20202020
5-3/45-3/45-3/45-3/4
EZB2048RCEZB2054RCEZB2060RCEZB2072RC
EZT2048 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or F
Main Breaker Number ofBranch Circuit
Poles
Box DimensionsInches
BoxCatalogueNumber
TrimCatalogueNumberAmpere Rating Type H W D
100 GBH, GHB � (horizontal)
15, 21, 27 30 20 5-3/4 EZB2030RC EZT2030 S or F
100/225 FDB, FD,
HFD, FDCEHD�
(vertical)
18, 24
304260
72, 84
36
42486072
20
20202020
5-3/4
5-3/45-3/45-3/45-3/4
EZB2036RC
EZB2042RCEZB2048RCEZB2060RCEZB2072RC
EZT2036 S or F
EZT2042 S or FEZT2048 S or FEZT2060 S or FEZT2072 S or F
400 KDHKDKDC
(vertical)
243042
60, 72
48546072
20202020
5-3/45-3/45-3/45-3/4
EZB2048RCEZB2054RCEZB2060RCEZB2072RC
EZT2048 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or F
Main Breaker with Through-Feed Lugs
100 GBH, GHB � (horizontal)
15, 21, 27 30 20 5-3/4 EZB2030RC EZT2030 S or F
100/225 FDB, FD,HFD, FDC
EHD�
(vertical)
18, 2430426072
3642486072
2020202020
5-3/45-3/45-3/45-3/45-3/4
EZB2036RCEZB2042RCEZB2048RCEZB2060RCEZB2072RC
EZT2036 S or FEZT2042 S or FEZT2048 S or FEZT2060 S or FEZT2072 S or F
400 KDHKD, KDC(vertical)
243042
607272
202020
5-3/45-3/45-3/4
EZB2060RCEZB2072RCEZB2072RC
EZT2060 S or FEZT2072 S or FEZT2072 S or F
� In Sub-Feed configuration, maximum incoming and outgoing cables are 1 per phase #500kcmil.Through-Feed lugs are recommended for 400A applications.
Table 2-10.
Table 2-11.
Table 2-12.
PanelboardsPow-R-Line C Panelboards
PRL2a
-
8/17/2019 Catalogo-panel Electrico Ch
8/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Product Description
� 600V AC maximum (250V DC).
� 3-phase 4-wire, 3-phase 3-wire,1-phase 3-wire, 1-phase 2-wire.
� 600 ampere maximum main lugs.
� 600 ampere maximum main breaker.� 225 ampere maximum branch break-
ers.
� Bolt-on branch breakers.
� Factory assembled.
Type PRL3a
Application Description
� Lighting and appliance branchpanelboard or power distribution panel-board.
� Fully rated or series rated.
� Interrupting ratings up to 200 kA sym-metrical.
� Suitable for use as Service EntranceEquipment, when specified onthe order.
Standards and Certification
� CSA C22.2 No. 29
� Federal Specification W-P-115c.
Options and Accessories
� Refer to Page 2-29.
Layout and Sizing
�
Refer to Page 2-10.
Product Selection
Table 1-19. Base Configurations — PRL3a
AmpereRating
Interrupting Rating (kA Symmetrical) BreakerType240V AC 480V AC 600V AC 250V DC
Main Lug Only
100250400600
————
————
————
————
————
Main Breaker
100100100100100100100
18 18 65100 65100200
14 14—— 35 65100
— 14—— 18 25 35
10 10—— 10 22 22
EHDFDBEDEDHFDHFDFDC
225225225225225225
65100200 65100200
——— 35 65100
——— 18 25 35
——— 10 22 22
EDEDHEDCFDHFDFDC
250250250
65100200
35 65100
18 25 35
10 22 22
JDHJDJDC
400400400400
65 65100200
— 35 65100
— 25 35 65
10 10 22 22
DKKDHKDKDC
600600
65100
35 65
18 35
22 42
LGELGH
6 - 600 amperes
Pow-R-Line 3a Catalogue Code
P3a B 4 A 4 - 21 KD 400
Panelboard Type L - Main Lugs Only
B - Bottom MainBreaker
T - Top Main Breaker
1 - 1phase, 3 wire
3 - 3phase, 3 wire
4 - 3phase, 4 wire
A - Aluminum
C - Copper
1 - 100 amperes
2 - 225 amperes
4 - 400 amperes
-
-
-
-
Feeder
Breaker
x-Space
Main
Breaker
(if selected)
Breaker
Trip
Rating
Table 2-13.
2-8PanelboardsPow-R-Line C Panelboards
PRL3a
-
8/17/2019 Catalogo-panel Electrico Ch
9/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Table 1-20. Branch Circuit Breakers — PRL3a
� 1-pole breaker rated 120V AC. 2-pole breaker rated 120/240V AC. 50 ampere devices are available as 2-pole only. Combination Arc fault circuit breaker. HID (High Intensity Discharge) rated breaker. Switching Neutral Breaker. 1-pole device requires 2-pole space, 2-pole device requires 3-pole space. Solenoid operated breaker. 1-pole breaker rated 277V AC.� For use on 480Y/277V systems only. AIC rating for 2- and 3-pole breakers only. Maximum of six breakers per panel, 175 – 225 amperes. 1-Pole breaker rated 347V AC. For use on 600Y/347V systems only 3-Pole only
AmpereRating
Interrupting Rating (kA Symmetrical) BreakerType240V AC 480V AC 600V AC 250V DC
15 – 30 15 – 60 15 – 60
70 70 80 – 100 80 – 100 15 – 50
15 – 50
15 – 50
15 – 20 15 – 60 15 – 30 15 – 30
10�
10 �
10
10
�
10 10 �
10 10 �
10 �
10 �
10 �
10 �
10 �
10�
———
———————————
———
———————————
———
———————————
DNBA (Twin)BABBAB-HBABBAB-HBABBAB-HQBGFQBGFEPGFCBBQBCAF
BAB-D
BAB-C
BABRSP
15 – 60 15 – 60 70 70 80 – 100 80 – 100 15 – 30 15 – 30
22 �
22 22 �
22 22 �
22 22 22
————————
————————
————————
QBHWQBHW-HQBHWQBHW-HQBHWQBHW-HQBHGFQBHGFEP
15 – 20
15 – 60 15 – 60 70 – 100 70 – 100 15 – 30 15 – 60 15 – 20
65
65 65 65 65 65——
14
14
14
14
14
14
14
14
—
—10
—10
———
—
1414141414——
GHQ
GHBGBHGHBGBHGHQRSP
GHBGFEPGHBHID
15 – 60 70 – 100
18
18 14
14 ——
1010
EHDEHD
15 – 60 15 – 150 70 – 100110 – 150
18 — 18 18
14 — 14 14
14141414
10—1010
FDBFDBFDBFDB
15 – 60 15 – 150 70 – 100110 – 225
65
— 65
65
35
— 35
25
18181818
10—1010
FDFDFDFD
15 – 60 70 – 100
110 – 225
100
100
100
65
65
65
2525
25
2222
22
HFDHFD
HFD
15 – 60 70 – 100110 – 225
200200200
100100100
353535
222222
FDCFDCFDC
100 – 225100 – 225100 – 225
65100200
———
———
———
ED
EDH
EDC
100 – 225100 – 225 60 – 150 60 – 150 15 – 80 15 – 80100 – 225100 – 225 60 – 150 60 – 150 15 – 80 15 – 80
656565656565100100100100100100
353535353535656565656565
181818181818252525252525
————————————
FDE322533 LS
FDE322532 LSI
FDE316033 LS
FDE316032 LSI
FDE308033 LS
FDE308032 LSI
HFDE322533 LS
HFDE322532 LSI
HFDE316033 LS
HFDE316032 LSI
HFDE308033 LS
HFDE308032 LSI
Table 2-14.
PanelboardsPow-R-Line C Panelboards
-
8/17/2019 Catalogo-panel Electrico Ch
10/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Panel Layout Instructions
1. Select:
a. Required mains (lugs or breaker).
b. Neutral where required.
c. Branch circuits as required.
2. Layout panel as shown inFigure 1-4, using appropriate“X” dimensions.
3. Using total X units (panel height) findbox height in inches (mm) and boxcatalogue number from Table 2-15.(When total X units come out to anuneven number, use next highestnumber; i.e., if total X comes out25X, use 31X.)
Layout Example
1. Description of Panel Type PRL3a 3-
phase, 4-wire, 120/208V AC flush
mounting. Panel to have short circuitrating of 22,000 symmetrical
amperes. Main breaker 400amperes, 3-pole, bottom mounting.
Branch circuits bolt-on as follows:
12 – 20 ampere 1-pole QBHW1 – 200 ampere 3-pole ED
1 – 225 ampere 3-pole ED
2 – 125 ampere 3-pole ED
2. Layout Information fromFigure 1-4:
a. 400 ampere Neutral . . . . . = 5X
b. 12-poles of QBHW . . . . . . = 5Xc. Two 3-pole ED break ers . . . = 6X
d. Two 3-Pole ED break ers . . . = 3XMain breakers 400 amperes
e. 3-pole DK . . . . . . . . . . . . . .= 15XTotal Height. . . . . . . . . . . . = 34X
3. FromTable 2-15:
a. 34X Height (use 40X box)
b. Box Height . . . . . . . . . .72 inches(1828.8 mm)
c. Box Catalogue Number . . . . . . . . .EZB2072RC
Figure 1-4. PRL3a Layout� GHB and GBH breakers cannot be mixed on
same connector as BAB, QBHW and BABRSP. Maximum of six breakers per panel. If optional terminal kit 3TA225FDK is required,
must use 28-inch (711.2 mm) box. Horizontal mounted 15 – 150 ampere main
breakers EHD, FDB, FD, HFD and FDC, willbe furnished as branch breaker construction.Branch breakers 1-, 2- or 3-pole as required,
may be located opposite these main breakers.
Table 1-21. Box Tabulation — PRL3a
600 ampere panels are optionally available with28-inch (610 mm) wide box. Consult factory foravailability.
Cabinets
Fronts are code-gauge steel, ASA-61 lightgray painted finish.
Boxes are code-gauge galvanized steelwithout knockouts. Standarddepth is 5-3/4 inches (146.1 mm).
Standard widths are:
20-inch (508.0 mm) 100 – 600 amperes.
Standard Depth
5-3/4 inches (146.1 mm).
Top and Bottom Gutters
5-1/2 inches (139.7 mm) minimum.
Side Gutters
4 inches (101.6 mm) minimum.
Poles BAB, QBHW,
BABRSP
GHB,
GBH
�
6 - 3X
12 - 5X
18 - 8X
24 - 10X
30 - 13X
36 - 15X42 - 18X
1X
2X
3X
ED, EDH, EDC,EHD, FDB, FD,HFD, FDC150A Max. PerBranch Breaker(300A Max. PerConnector)
2X2-Pole
ED, EDH, EDCFD, HFD, FDC
(175 - 225A)3X3-Pole
Neutral
Section
5X 250A-400A
8X 600A
MainLugSection
5X 250A
8X 400-600A
MainBreakerSection
Hori-zontalMount-ing
2X2-Pole
EHD, FDB, FD,HFD, FDC
3X3-Pole
ED, EDH, EDC
VerticalMount-ing
7X EHD, FDB, FD,HFD, FDC, ED,EDH, EDC
9X FCL, FB-P
14X JDHJD, JDC
14X DK, KDHKD, KDC
18X LGE, LGH
VisorSeriesTVSS
6X 100-200kA
8X 250-400kA
1-Pole
2-Pole
1-Pole
2-Pole
1-Pole
2-Pole
3-Pole
2- or 3-Pole
“X”Units
Box Height BoxCatalogueNumber
TrimCatalogueNumber
Inches mm
250 – 400 Amperes
23X31X40X
486072
1219.21524.01828.8
EZB2048RCEZB2060RCEZB2072RC
EZT2048S or FEZT2060S or FEZT2072S or F
600 Amperes
23X31X40X
486072
1219.21524.01828.8
EZB2048RCEZB2060RCEZB2072RC
EZTV2048S or FEZTV2060S or FEZTV2072S or F
Figure 2-1.
Table 2-15.
2-10PanelboardsPow-R-Line C Panelboards
PRL3a
-
8/17/2019 Catalogo-panel Electrico Ch
11/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Type PRL4
Type PRL4B Circuit Breaker Panelboard
Product Description
� 600V AC maximum (250V DC).
� 3-phase 4-wire, 3-phase 3-wire,1-phase 3-wire, 1-phase 2-wire.
� PRL4B circuit breaker panelboard.
� PRL4F fusible switch panelboard.
� 1200 ampere maximum mains.
� 1200 ampere maximum branchdevices.
� Bolt-on branch devices.
� Factory assembled.
Standards and Certifications
� CSA C22.2 No.29
� Federal Specification W-P-115c.
Options and Accessories
� Refer to Page 2-29.
Layout and Sizing
� PRL4B — R efer to Pages 2-16.through 2-18.
� PRL4F — R efer to Pages 2-19.through 2-21.
Type PRL4F Fusible Panelboard
Application Description
� Power distribution panelboard.
� Fully rated or series rated.
� Interrupting ratings up to 200 kA sym-metrical.
Suitable for use as Service EntranceEquipment, when specified onthe order.
Pow-R-Line 4 Catalogue Code
P4 B 4 A 4 - 27 KD 400
Panelboard Type L - Main Lugs Only
B - Bottom MainBreaker
T - Top Main Breaker
S - Main Switch
1 - 1phase, 3 wire
3 - 3phase, 3 wire
4 - 3phase, 4 wire
A - Aluminum
C - Copper
1 - 100 amperes
2 - 225 amperes
4 - 400 amperes
6 - 600 amperes
8 - 800 amperes
12 - 1200 amperes
-
-
-
Feeder Breaker
X-Space
Main
Breaker
(if selected)
Breaker
Trip
Rating
2PanelboardsPow-R-Line C Panelboards
PRL4
-
8/17/2019 Catalogo-panel Electrico Ch
12/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Product Selection
Table 1-22. Base Configuration — PRL4 Main Lugs and Main Breakers
� 100% rated breaker. Requires copper bus. Breaker only available in 3-pole frame. Requires 44-inch (1117.6 mm) wide box.
Table 1-23. Base Configuration — PRL4 Main Fusible Switches
Fuses not included. Specify required fuse clips on all switches. Class J Fuse provisions are applicable only to 600 volt units. When required, use price and dimensions of 600 volt units for all voltages 600 and below.
No DC rating on 600, 800 and 1200 ampere switches .
AmpereRating
Interrupting Rating (kA Symmetrical) BreakerType
240V AC 480V AC 600V AC 250V DC
Main Lug Only250 400 600 8001200
—————
—————
—————
—————
—————
Main Breaker
250 250 250 250
65100200200
35 65100200
18 25 35—
102222—
JDHJDJDCLCL
400 400 400 400 400 400 400
400
65 65 65100100200200
200
— 35 35 65 65100200
200
— 25 25 35 35 65—
200
1010—22—22—
—
DKKDCKD �
HKDCHKD
�
KDCLCL
LA-P 600 600 600 600 600 600 600 600 600
65100200 65 65100100200200
35 65100 35 35 65 65100100
18 35 65 25 25 35 35 50 50
1042—22—25—25—
LGELGHLGULDCLD �
HLDCHLD
�
LDCCLDC �
800 800 800 800 800
65100 65100200
50 65 50 65200
25 35 25 35200
2225———
MDLHMDLCMDL
�
CHMDL �
NB-P
800 800 800 800
800 800
65100200 65
100200
50 65100 50
65100
25 35 50 25
35 50
————
——
NDHNDNDCCND �
CHND
�
CNDC
�
120012001200120012001200
65100200 65100200
50 65100 50 65100
25 35 65 25 35 65
——————
NDHNDNDCCND �
CHND
�
CNDC
�
AmpereRating
Interrupting Rating (kA Symmetrical)
240V AC 480V AC / 600V AC Device Type
Main Fusible Switch 240V AC, 250V DC
200 400 600
800
1200
SeeTable 2-20 FDPBFDPWFDPWFDPWFDPW
Main Fusible Switch 600V AC
200 400 600
800
1200
SeeTable 2-20 FDPBFDPWFDPWFDPWFDPW
Table 2-16.
Table 2-17.
2-12PanelboardsPow-R-Line C Panelboards
PRL4
-
8/17/2019 Catalogo-panel Electrico Ch
13/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Table 1-24. Branch Devices — PRL4
AmpereRating
Interrupting Rating (kA Symmetrical) BreakerType240V AC 480V AC 600V AC 250V DC
15 – 30 15 – 60 15 – 60
70 – 100 70 – 100 15 – 50
10
10
10
10
10 10
———
———
———
———
———
———
DNBA (Twin)BABBAB-H
BABBAB-HQBGF
15 – 60 15 – 60 70 – 100 70 – 100 15 – 30
22
22 22
22 22
—————
—————
—————
QBHWQBHW-HQBHWQBHW-HQBHGF
15 – 60 70 – 100 15 – 60 70 – 100
65
65
65
65
14
14
14
14
——10
10
14141414
GHB
GHB
GBH
GBH
15 – 60 70 – 100 15 – 60 70 – 100110 – 150
18
18
18 18 18
14
14
14 14 14
——141414
1010101010
EHDEHDFDBFDBFDB
15 – 60
70 – 100110 – 225 15 – 60 70 – 100110 – 225
65
65
65
100
100
100
35
35
35
65
65
65
18
1818252525
10
1010222222
FD
FDFDHFDHFDHFD
15 – 60 70 – 100110 – 225 15 – 100
200200200200
100100100150
353535—
222222—
FDCFDCFDCFCL
100 – 225100 – 225100 – 225
65100200
———
———
———
EDEDHEDC
100-225100-225100-225100-225
65656565
35353535
18181818
————
FDE322533 LS�
FDE322532 LSI�
FDE322535 LSG�
FDE322536 LSIG�
60-15060-15060-15060-150
65656565
35353535
18181818
————
FDE316033 LS�
FDE316032 LSI�
FDE316035 LSG�
FDE316036 LSIG�
15-8015-8015-8015-80
65656565
35353535
18181818
————
FDE308033 LS�
FDE308032 LSI�
FDE308035 LSG�
FDE308036 LSIG�
100-225100-225100-225100-225
100100100100
65656565
25252525
————
HFDE322533 LS�
HFDE322532 LSI�
HFDE322535 LSG�
HFDE322536 LSIG�
60-15060-15060-15060-150
100100100100
65656565
25252525
————
HFDE316033�
HFDE316032�
HFDE316035�
HFDE316036�
15-8015-8015-80
15-80
100100100
100
656565
65
252525
25
———
—
HFDE308033�
HFDE308032�
HFDE308035�
HFDE308036�Ground available in PRL4 panels only.
Ammeter DigiView DigiView Ammeter (PRL4 only)
Table 2-18
� For use on 3ph, 3w or 3ph, 4w only. 50 ampere devices are available as 2-pole only. 1-pole breakers rated 120V AC. 2-pole breakers rated 120/240V AC. 1-pole breakers rated 277V AC. At 480V, must be used on 480Y/277V grounded wye systems only. AIC rating for 2- and 3-pole breakers only. 100% rated breaker. Requires copper bus. Not available in Type 12, 4 and 4X enclosures. Breaker only available in 3-pole frame.� Available in single branch mounting only. 1-pole breakers rated at 347V AC. At 600V, must be used on 600Y/347V grounded wye systems only.
2PanelboardsPow-R-Line C Panelboards
PRL4
-
8/17/2019 Catalogo-panel Electrico Ch
14/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Table 1-25. Branch Devices — PRL4 (Continued)
AmpereRating
Interrupting Rating (kA Symmetrical) DeviceType240V AC 480V AC 600V AC 250V DC
70 – 225 250 70 – 225
250 70 – 225 250
65 65100
100200200
35 35 65
65100100
181825
253535
101022
222222
JDJDHJD
HJDJDCJDC
125 – 250 200 200 — — LCL
250 – 400 100 – 400 100 – 400 100 – 400 100 – 400 100 – 400
65 65 65100100200
— 35 35 65 65100
—2525353565
1010—22—22
DKKDCKD �
HKDCHKD
�
KDC
200 – 400 200 200 — — LCL
300 – 600 300 – 600 300 – 600
65100200
35 65100
183565
1042—
LGELGHLGU
300 – 600 300 – 600
65 65
35 35
2525
22—
LDCLD
300 – 600
300 – 600 300 – 600 300 – 600
100
100200200
65
65100100
35
355050
25
—2525
HLD
CHLD
LDCCLDC
400 – 800 400 – 800 400 – 800 400 – 800
65100 65100
50 65 50 65
25352535
2225——
MDLHMDLCMDL
CHMDL
400 – 800 400 – 800 400 – 800 400 – 800 400 – 800 400 – 800
65100200 65100200
50 65100 50 65100
25 35 65 25 35 65
——————
NDHNDNDCCND
�
CHND
�
CNDC �
600 – 1200 600 – 1200 600 – 1200 600 – 1200 600 – 1200
600 – 1200
65100200 65100
200
50 65100 50 65
100
25 35 65 25 35
65
—————
—
NDHNDNDCCND
�
CHND �
CNDC�
Integrally Fused, Current Limiting Circuit Breaker
15 – 100 125 – 225 250 – 400 400 – 600 700 – 800
200200200200200
200200200200200
200200200200200
FB-PLA-PLA-PNB-PNB-P
Table 2-18
� For use on 3ph, 3w or 3ph, 4w only. 50 ampere devices are available as 2-pole only. 1-pole breakers rated 120V AC. 2-pole breakers rated 120/240V AC. 1-pole breakers rated 277V AC. At 480V, must be used on 480Y/277V grounded wye systems only. AIC rating for 2- and 3-pole breakers only. 100% rated breaker. Requires copper bus. Not available in Type 12, 4 and 4X enclosures. Breaker only available in 3-pole frame.� Available in single branch mounting only. 1-pole breakers rated at 347V AC. At 600V, must be used on 600Y/347V grounded wye systems only.
2-14PanelboardsPow-R-Line C Panelboards
PRL4
-
8/17/2019 Catalogo-panel Electrico Ch
15/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Table 1-25.
Table 1-26.
Table 1-26.Table 1-26. FDPW and FDPB Switch Ratings,240 or 600V AC
� 100% rated breaker. Requires 44-inch (1117.6 mm) wide box. 100,000 AIC based on NEMA test procedure. Fuses not included. Specify required fuse clips on all switches. For T fuse clips, specify as an option (T fuse clips not available for
200/200 twin switches).
When branches of a twin unit are of different ampere ratings, as a 30 – 60 twin unit and layout as a 60 – 60 twin unit;when a 60 – 100 twin unit layout as a 100 – 100 twin unit. No DC rating on 600, 800 and 1200 ampere switches. Twin 200 ampere switches are not available with Class R fuse clips at 600 volts. No DC rating on 600, 800 and 1200 ampere switches. Class J fuse provisions are applicable to 600 volt units. When required, use price and dimensions of 600 volt units for all voltages 600 volts and below.� Twin 200 ampere switches are not available with Class R fuse clips at 600 volts. When shunt trip is required, 400 – 600 ampere switches used with Class R fuses are rated 100,000 AIC.
Fusible Switches 240V AC, 250V DC
30/30
60/60
100/100
200/200 200
SeeTable 2-20 FDPW-TwinFDPW-TwinFDPW-TwinFDPB-TwinFDPB-Single
400 600
800
1200
SeeTable 2-20 FDPW-SingleFDPW-SingleFDPW-SingleFDPW-Single
Fusible Switches 600V AC
30/30
60/60
100/100
200/200
200
SeeTable 2-20 FDPW-TwinFDPW-TwinFDPW-TwinFDPB-TwinFDPB-Single
400 600
800
1200
SeeTable 2-20 FDPW-SingleFDPW-SingleFDPW-SingleFDPW-Single
AmpereRating
FuseClassUsed
Short CircuitRatings(Sym. Amperes)
30 – 100200 Single200 Twin400, 600
800, 1200
R, J
R, J
R �, J , TR , J, TL
200,000200,000200,000200,000200,000
Table 2-19.
Table 2-20.
2PanelboardsPow-R-Line C Panelboards
-
8/17/2019 Catalogo-panel Electrico Ch
16/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Layout and Sizing — PRL4B
Main Lug (MLO), Main Breaker, Neutral, Through-Feed (TFL) andSub-Feed Lug (SFL) “X” Space Requirements. (For other config-urations not shown, refer to Eaton.)
* = Space available for branch devices. For device sizing,see Figure 2-4 on Page 2-18..
• = Blank means no bus under cover, to meet cablebending space requirements.
Figure 1-5. PRL4B Layout� Sub-Feed lugs are available 250 – 600 amperes. For 600 ampere use 1200 ampere space. 750kcmil lugs available on some Main Breaker arrangements.
Consult Eaton.
*
10X
7X Through-Feed Lugs
*
10XNN
MLO, SFL MLO, TFL
3Ph 4W, 3Ph 3W
250A�, 400A�,600A�, 800A
Standard Main Lug, Through-Feed and Sub-Feed Lugs�
(500 kcmil Maximum)Main Breaker with Neutral (when required)(500 kcmil Maximum)�
*
7X
*
NN
3Ph 4W,
3Ph 3W
250A, 400A,600A, 800A
*
12X
7X Through-Feed Lugs
*
12XNN
MLO MLO, TFL
3Ph 4W, 3Ph 3W
1200A38-inch(965.2 mm)MinimumWidth
Main Breaker
Main Breaker
*
3Ph 3W3Ph 4W
800A Vertically Mtd. MDL Main Breaker only in 24-inch (609.6 mm) wide box.Available with 38X and 50X Panel Height only.
16X
Blank2X
*
7X
*
N
3Ph 3W
1200A38-inch(965.2 mm)MinimumWidth
Main Breaker
3Ph 4W
Blank2X Blank2X
Blank2X
Main Breaker
*
9X Through-Feed Lugs
*
20XNN
MLO, SFL MLO, TFL
3Ph 4W
250A�, 400A�,600A�, 800A
Optional Main Lugs, Through-Feed and Sub-Feed Lugs� (750 kcmil Maximum)
*
20X
11X Through-Feed Lugs
*
20XNN
MLO MLO, TFL
3Ph 4W
1200A38-inch(965.2 mm)MinimumWidth Blank5X
*
9X Through-Feed Lugs
*
13X
3Ph 3W
400A, 600A,800A
*
15X
11X Through-Feed Lugs
*
15X
1200A38-inch(965.2 mm)MinimumWidth Blank5X
Blank
20X
Blank
13X
3X
3Ph 3W
3X
Figure 2-2.
2-16PanelboardsPow-R-Line C Panelboards
PRL4
-
8/17/2019 Catalogo-panel Electrico Ch
17/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Panel Layout and Dimensions
To determine the dimensions of a givenpanelboard enclosure, make a layoutsketch by fitting together the main,branch and lug modules according to theappropriate tables in the layout guide.Assign “X” units to each module asshown and obtain a total “X” number.
The height of the enclosure is related tothe total “X” units in the layout as showninTable 2-21. Three standard box heightsare available to accommodate any and alllayout arrangements. “X” unit totals thatdo not exactly match those in Table 2-21 must be rounded off to the next higheststandard (26X, 38X, 50X).
If a calculated “X” total for a panelexceeds 50X, the panel must be split intotwo or more separate sections with “X”space for through-feed lugs figured in forall but one section. If a neutral is re-quired, a separate neutral bar and appro-priate “X” space must be included ineach section.
Layout Example
� 1 – PRL4B panelboard, 600Y/347V,3-phase 4-wire 25 kA, 800 amperes,main lug, consisting of:
12 – 20A/1P HFD
2 – 250A/3P HJD
1 – 400A/3P KD
Reference Figure 1-6
1. From layout guide, total “X” heightof panel = 26X, (which is a designstandard and no rounding off is nec-essary).
2. FromTable 1-27, enclosureheight for 26X panel = 57 inches(1447.8 mm).
3. Width = 24 inches (609.6 mm) —directly from layout guide.
4. Enclosure depth = 11-5/16 inches(287.0 mm) — standard for all PRL4
panelboards.
Figure 1-6. PRL4B Layout Example
Table 1-26. Box Dimensions — PRL4B
� Box depth is 10.4 inches (264.2 mm), cover adds .9 inches (22.9 mm) to depth.
Note: 800 ampere maximum bus size in 24-inch (609.6 mm) wide box. Flush trimsnot available on PRL4B panels.
Top and Bottom Gutters
10-5/8-inch (269.9 mm) minimum.
Side Gutters — Minimum
24-inch (609.6 mm) wide box — 5-inch (127.0 mm).38-inch (914.4 mm) wide box — 7-inch (177.8 mm).44-inch (1117.6 mm) wide box — 8-inch (203.2 mm).
20A/1P 20A/1P 1X
20A/1P 20A/1P 1X
20A/1P 20A/1P 1X
20A/1P 20A/1P 1X
20A/1P 20A/1P 1X
20A/1P 20A/1P 1X
250A/3P 3X
250A/3P 3X
400A/3P 4X
Main 800ALugs
Neutral
10X
Total = 26X
“X”Units
CatalogueNumber
Inches mm
Height Width Depth � Height Width Depth �
26X38X50X
BX2457BX2473BX2490
5773-1/290
242424
11-5/1611-5/1611-5/16
1447.81866.92286.0
609.6 609.6 609.6
287.0287.0287.0
38X50X
BX3873BX3890
73-1/290
3838
11-5/1611-5/16
1866.92286.0
965.2 965.2
287.0287.0
38X50X
BX4473BX4490
73-1/290
4444
11-5/1611-5/16
1866.92286.0
1117.61117.6
287.0287.0
Table 2-21.
Figure 2-3. .
2PanelboardsPow-R-Line C Panelboards
PRL4
-
8/17/2019 Catalogo-panel Electrico Ch
18/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Figure 1-7. Layout for Branch and Horizontally Mounted Main Devices — PRL4B� BAB and QBHW breakers with shunt trips require one additional pole space, i.e., 1-pole is 2-pole size, 2-pole is 3-pole size, and 3-pole is 4-pole size.
If panel contains only BAB or QBHW branch breakers, use a PRL1a panelboard. GHB and GBH breakers cannot be mixed on same subchassis as BAB, QBHW. If panel contains only GHB
and GBH branch breakers, use a PRL2a panelboard. When only one single-pole breaker of the group is required on either side of chassis, the single-pole breaker space required changes from 1X to 2X. Minimum 38-inch (965.2 mm) wide box is required if optional #6 – 300 kcmil lug is required.
Breaker To Fusible Transition, All Widths
3X
3X
6X
6X
4X
6X
1X
12X
20X
1X
2X
3X
2X
6X
3X
3X
4X
Filler
Sub Panel
400 Amp. Maximum Bus Rating
1P 1P
2P 2P
3P 3P
2P 2P
3P 3P
2 or 3P
2 or 3P
2 or 3P L o a d
2 or 3P 2 or 3P
2 or 3P 2 or 3P
2 or 3P
2 or 3P
2 or 3P 2 or 3P
2 or 3P
EHD,FDB, FD,HFD, FDCFDE, HFDE(3P)
18Poles
100 AmpMax.
BAB
QBHW
GHB, GBH
DK, KD, HKD,KDC
ED, EDH, EDC
225 AmpMax.
225 AmpMax.
JD, HJD, JDC250 Amp
Max.
400 Amp Max. DK, KD, HKD, KDC, CKD, CHKD
600 AmpMax.
LD, HLD, CLD, CHLD, LDC
100 AmpMax.
FCL, FB-P
250 AmpMax.
JD, HJD, JDC
400 AmpMax.
1200 AmpMax.
LCL, LA-P
MDL, HMDL,
CMDL, CHMDL
800 Amp
Max.
ND, HND, NDC
400 AmpMax.
800 AmpMax. NB-P
4 4 - I n c h ( 1 1 1 7 . 6 m m ) W i d e B o x
2 4 - I n c h ( 6 0 9 . 6 m m ) W i d e B o x
3 8 - I n c h ( 9 6 5 . 2 m m ) W i d e B o x
1200 AmpMax.
CND, CHND, CNDC
42
Poles
4X400 AmpMax.
DK, KD, HKD, KDC,CKD, CHKD2 or 3P 2 or 3P
600 Amp Max.LGE, LGH, LGU
� Breaker may be used as main.
Figure 2-4.
2-18PanelboardsPow-R-Line C Panelboards
PRL4
-
8/17/2019 Catalogo-panel Electrico Ch
19/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Layout and Sizing — PRL4F
Main Lug (MLO), Main Switch, Neutral, Through-Feed (TFL) andSub-Feed Lug (SFL) “X” Space Requirements. (For other config-urations not shown, refer to Eaton.)
* = Space available for branch devices. For device sizing,see Figure 2-7 on Page 2-21.
• = Blank means no bus under cover, to meet cablebending space requirements.
Figure 1-8. PRL4F Layout� Sub-Feed lugs are available 250 – 600 amperes, for 600 ampere use 1200 ampere “A” space. 800 ampere and 1200 ampere mains available only in vertical mounting.
*
10X
7X Through-Feed Lugs
*
10XNN
MLO, SFL MLO, TFL
3Ph 4W, 3Ph 3W
250A�, 400A�,600A�, 800A
Standard Main Lug, Through-Feed and Sub-Feed Lugs�
(500 kcmil Maximum)Main Switch with Neutral (when required)(500 kcmil Maximum)
*
7X
*
N
3Ph 4W,3Ph 3W
200A, 400A,600A
*
12X
7X
*
12XNN
MLO MLO, TFL
3Ph 4W, 3Ph 3W
1200A
Main Switch
Main Switch
*
3Ph 3W3Ph 4W
400A and 600A Vertically Mounted Main Switch
21X
Blank Through-FeedLugs2X
800A,1200A
*
9X Through-Feed Lugs
*
20XNN
MLO, SFL MLO, TFL
3Ph 4W
250A�, 400A�,600A�, 800A
Optional Main Lugs, Through-Feed and Sub-Feed Lugs� (750 kcmil Maximum)
*
20X
11X Through-Feed Lugs
*
20XNN
MLO MLO, TFL
3Ph 4W
1200A
Blank5X
*
9X Through-Feed Lugs
*
13X
3Ph 3W
400A,600A, 800A
*
15X
11X Through-Feed Lugs
*
15X
1200A
Blank5X
Blank
20X
Blank
13X
3X
3Ph 3W
N7X
*
3Ph 4W
1200A 26X
N7X
800A & 1200A Vertically MountedMain Switch
38-inch (965.2 mm) or44-inch (1117.6 mm)Wide Box
3X
25X - 800A (750 kcmil max.)
21X - 800A (250 kcmil max.)
Figure 2-5.
2PanelboardsPow-R-Line C Panelboards
PRL4
-
8/17/2019 Catalogo-panel Electrico Ch
20/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Panel Layout and Dimensions
To determine the dimensions of a giv enpanelboard enclosure, mak e a layout sketchby fitting together the main, branc h and lugmodules according to the appropriatetables in the layout guide. Assign “X” unitsto each module as sho wn and obt ain a total“X” number.
The height of the enclosure is related tothe total “X” units in the layout as showninTable 2-22. Two standard fusible boxheights are available to accommodateany and all layout arrangements. “X” unittotals that do not exactly match those inTable 2-22 must be rounded off to thenext higher standard (50X).
If a calculated “X” total for a panelexceeds 50X, the panel must be split intotwo or more separate sections with “X”space for through-feed lugs figured in forall but one section. If a neutral is re-
quired, a separate neutral bar and appro-priate “X” space must be included ineach section.
Layout Example
� PRL4F, 3-phase 4-wire, 208Y/120Vcomplete with 400 ampere mainswitch and the following branches:
1 – 200A/3P
2 – 100A/3P
2 – 30A/3P
Panel to have short circuit rating of100,000 amperes symmetrical.
Reference Figure 2-6
1. From layout guide, total “X” heightof panel = 43X.
2. Rounded off to next higherstandard = 50X.
3. FromTable 2-22, enclosure heightfor 50X panel = 90 inches(2286.0 mm).
4. Width = 38 inches (965.2 mm).
5. Enclosure depth is standard for allPRL4 panelboards = 11-5/16 inches(287.0 mm).
Figure 1-9. Type PRL4F Layout Example
Note: In the above example if a horizontallymounted 400 ampere main switch were used,the enclosure size would be73-1/2 H x 44 W x 11-5/16 D (1866.9 mm H x1117.6 mm W x 287.0 mm D)
Table 1-27. Box Dimensions — PRL4F
� Box depth is 10.4-inch (264.2 mm) cover adds .9-inch (22.8 mm) to depth.
Note: Flush trims not available on PRL4F panels.
Top and Bottom Gutters
10-5/8 inches (269.9 mm) minimum.
Side Gutters — Minimum
� 38-inch (965 mm) wide box:
8-inch (203.2 mm) — 200 ampere maximum
8-inch (152.4 mm) 400 — 1200 ampere maximum
� 44-inch (1117.6 mm) wide box:
10-inch (254.0 mm) 200 — ampere maximum
7-inch (203.2 mm) 400 — 1200 ampere
400A Neutral 7X
30A/3P 30A/3P 4X
100A/3P 100A/3P 5X
200A/3P 6X
400A 3-PoleMain Switch
(Vert. Mounted)
21X
Total = 43X
“X”Units
CatalogueNumber
Inches mm
Height Width Depth � Height Width Depth �
38X50X
BX3873BX3890
73-1/290
3838
11-5/1611-5/16
1866.92286.0
965.2 965.2
287.0287.0
38X50X
BX4473BX4490
73-1/290
4444
11-5/1611-5/16
1866.92286.0
1117.61117.6
287.0287.0
Figure 2-6.
Table 2-22.
2-20PanelboardsPow-R-Line C Panelboards
PRL4
-
8/17/2019 Catalogo-panel Electrico Ch
21/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Figure 1-10. Branch and Horizontally Mounted Main Device Layout — PRL4F
Fusible switch may be used as horizontal main.
� 400 and 600 ampere horizontally mounted feeder switches in 38-inch (965 mm) or 44-inch (1117.6 mm) wide box. 400 and 600 ampere horizon-tally mounted main switches only in 44-inch (1117.6 mm) wide box. For vertically mounted main see Page 2-19 for sizing.
Note: See Page 2-19 for MLO or Neutral and Vertically Mounted Main space requirements.
1X
4X
4X
6X
5X
9X
15X
400A
Branch Switch
200AMain or Branch Switch
Fusible to Breaker TransitionRequires 1X Filler
30A 30A
60A 60A
100A 100A
4 4 - i n c h ( 1 1 1 7 . 6 m m ) W i d e B o x
3 8 - i n c h ( 9 6 5 . 2 m m ) W i d e B o x
600ABranch Switch
200A 200A
400AMain or Branch
600AMain or Branch
800ABranch
1200ABranch
9X
11X
11X
11X
6X
Figure 2-7.
2PanelboardsPow-R-Line C Panelboards
PRL4
-
8/17/2019 Catalogo-panel Electrico Ch
22/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Product Description
� 240V AC maximum.
� 3-phase 4-wire, 3-phase 3-wire,1-phase 3-wire, 1-phase 2-wire.
� 225 ampere maximum mains.
� 100 ampere maximum branch break-ers.
� Bolt-on branch breakers.
� Factory assembled.
Type PRL1a-LX, Column Type
Application Description
� Lighting and appliance branchpanelboard.
� Column mounting width.
� Fully rated or series rated.
� Interrupting ratings up to 200 kA sym-metrical.
Standards and Certification
� CSA C22.2 No. 29
� Federal Specification W-P-115c.
Options and Accessories
� Pullbox and trough extensions.
� See also Page 2-29.
Layout and Sizing
� Refer to Page 2-23.
Product Selection
Table 1-28. PRL1a-LX
Table 1-29. Branch Circuit Breakers — PRL1a-LX
� 1-pole breakers are rated 120V AC maximum. 240 volt breakers must be used on 3-phase, 3-
wire, 240 volt delta systems or on the high leg
of a midpoint delta grounded system. 50 ampere devices are available as 2-pole only.
GFCI for 5 mA personnel protection. GFP for 30 mA equipment protection. Arc fault circuit breaker.
Arc fault circuit breaker with GFCI. Solenoid operated breaker.
Table 1-30. Pull Box With Extension Trough
Includes pull box with trough extension.For additional trough extensions.
Neutral Bars
When Column Type panels are furnishedwith trough extensions and pull bo x, theneutral bar will be placed in the pull bo xunless other wise specified.
When troughs and pull bo x are not fur-nished, the neutral bar will be located onthe panel at the same end as the main.
Table 1-31. Additional Trough Extensions
Width and depth are the same as thepanelboard.
AmpereRating
InterruptingRating (kA Sym.)240V AC
BreakerType
Main Lug Only
100225
——
——
Main Breaker
100100100100100100100
10 18 22 65 65100100
BABEHDQBHWEDFDEDHHFD
225225
65100
EDEDH
AmpereRating
InterruptingRating (kA Sym.)240V AC�
BreakerType
15 – 60 70 80 – 100 15 – 50
15 – 50
15 – 20 15 – 20 15 – 30 15 – 30
10 10 10 10 10 10 10 10 10
BABBABBABQBGF
QBGFEP
QBAF
QBAG
BABR
BABRS
15 – 60 70 80 – 100 15 – 30 15 – 30
22 22 22 22 22
QBHWQBHWQBHWQBHGF
QBHGFEP
Description CatalogueNumber
Pullbox with 36" TroughPullbox with 48" TroughPullbox with 60" TroughPullbox with 72" TroughPullbox with 84" Trough
XCTXB036XCTXB048XCTXB060XCTXB072XCTXB084
Length CatalogueNumberInches mm
3648607284
914.41219.21524.01828.82133.6
CTXB036CTXB048CTXB060CTXB072CTXB084
Table 2-26.Table 2-25.
Table 2-24
Table 2-23
2-22PanelboardsColumn Type
Type PRL1a-LX
-
8/17/2019 Catalogo-panel Electrico Ch
23/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Box Sizing and Selection
Assembled Circuit Breaker Panelboards
Box size, box and trim catalogue num-bers for standard Column Type panel-boards listed are available fromTables 2-28 and 2-29.
Instructions
1. Using description of the requiredpanelboard, select the rating andtype of main required.
a. 100 ampere panelboards —Table2-28.
b. 225 ampere panelboards —Table2-29.
2. Count the total number of branch cir-cuit poles, including provisions,required in the panelboard. Do notcount main breaker poles. Convert 2-or 3-pole branch breaker to single
poles, i.e., 3-pole breaker, count as 3poles. Determine sub-feed breakeror through-feed lug requirements.
3. Select the panelboard main ampererating fromTables 2-28 or 2-29.
4. Panelboard Type from first column,main breaker Frame and Designa-tion, if applicable from second col-umn, and sub-feed breaker Frameand Designation, if applicable, fromthe third column.
5. From Step #2, determine the num-ber of branch circuits in Column 4.
6. Read box size, box and trim
catalogue numbers across columnsto the right. All panels are surfacemounted.
Cabinets
Boxes and trims are code-gauge steel,ASA-61 light gray painted finish.
Boxes are furnished without knoc kouts.Standard depth is 6 inc hes (152.4 mm).Standard width is 8-5/8 inc hes
(219.1 mm).
Top and Bottom Gutters
4-1/2 inches (114.3 mm) minimum.
Left Side Gutter
4-3/8 inches (111.2 mm) minimum.
Pull Box
Pull box is furnished without knock-outs. Standard dimensions
Table 2-27. Pull Box Dimensions
Figure 2-8. PRL1a-LX Trough Extension,Dimensions in Inches (mm)
Height Width Depth
Inches mm Inches mm Inches mm
12 304.8 16 406.4 6 152.4
AdditionalExtensions
(If Required)
HBox
Height
12(304.8)
6(152.4) 16
(406.4)
8-5/8(219.1)
6(152.4)
2PanelboardsColumn Type
Type PRL1a-LX
-
8/17/2019 Catalogo-panel Electrico Ch
24/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Box Sizing and Selection (Continued)
Table 1-32. 100 Ampere Maximum PRL1a-LX Column Type Panelboard Sizing
� Add suffix B to trim catalogue number for bottom fed panelboards (i.e., LTC969SB).
Table 1-33. 225 Ampere Maximum PRL1a-LX Column Type Panelboard Sizing
Add suffix B to trim catalogue number for bottom fed panelboards (i.e., LTC969SB).
PanelboardTypes
Main BreakerTypesMounting :(H) = Horizontal
(V) = Vertical
Sub-FeedBreaker TypesVerticalMounting
MaximumNumberof BranchCircuits
IncludingProvisions
Box Dimensions Inches (mm) BoxCatalogueNumber
TrimCatalogueNumber �
Height Width Depth
Main Breaker BAB, QBHW(H)
——
2739
69 (1752.6)81 (2057.4)
8-5/8 (219.2)8-5/8 (219.2)
6 (152.4)6 (152.4)
YSC969YSC981
LTC969SLTC981S
Main Lugs or Main Breaker EHD, EDFD, HFD(V)
——
3042
69 (1752.6)81 (2057.4)
8-5/8 (219.2)8-5/8 (219.2)
6 (152.4)6 (152.4)
YSC969YSC981
LTC969SLTC981S
Main Lugs or Main Breakerwith 100A Through-Feed Lugsor Sub-Feed Breaker
EHD, EDFDHFD(V)
EHD, FD, HFD 3042
78 (1981.2)90 (2286.0)
8-5/8 (219.2)8-5/8 (219.2)
6 (152.4)6 (152.4)
YSC978YSC990
LTC978SLTC990S
PanelboardTypes
Main BreakerTypes
Sub-FeedBreaker Types
MaximumNumberof Branch
CircuitsIncludingProvisions
Box Dimensions Inches BoxCatalogueNumber
TrimCatalogueNumber Vertical Mounting Height Width Depth
Main Lugs or Main Breaker ED, EDH ——
3042
69 (1752.6)81 (2057.4)
8-5/8 (219.2)8-5/8 (219.2)
6 (152.4)6 (152.4)
YSC969YSC981
LTC969SLTC981S
Main Lugs or Main Breakerwith 225A Through-Feed Lugsor Sub-Feed Breaker
ED, EDH EHD, FD, HFD,ED, EDH
3042
78 (1981.2)90 (2286.0)
8-5/8 (219.2)8-5/8 (219.2)
6 (152.4)6 (152.4)
YSC978YSC990
LTC978SLTC990S
Table 2-28.
Table 2-29.
2-24PanelboardsColumn Type
Type PRL1a-LX
-
8/17/2019 Catalogo-panel Electrico Ch
25/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Product Description
� 600Y/347V AC maximum (125V DC).
� 3-phase 4-wire, 3-phase 3-wire,1-phase 3-wire, 1-phase 2-wire.
� 225 ampere maximum mains.
� 100 ampere maximum branch break-ers.
� Bolt-on branch breakers.
� Factory assembled.
Type PRL2a-LX, Column Type
Application Description
� Lighting and appliance branchpanelboard.
� Column mounting width.
� Fully rated or series rated.
� Interrupting ratings up to 200 kA sym-metrical.
Standards and Certifications
� CSA C22.2 No.29
� Federal Specification W-P-115c.
Options and Accessories
� Pullbox and trough extensions.
� See also Page 2-29.
Layout and Sizing
� Refer to Page 2-26.
Product Selection
Table 1-34. Base Prices — PRL2a-LX
� These system voltages apply to 240 volts.
Table 1-35. Branch Circuit Breakers — PRL2a-LX
Interrupting ratings in this column are applicable to 120V AC for 1-pole breakers. At 480V, must be used on 480Y/277V grounded wye systems only. Solenoid operated breaker. GFP for 30 mA equipment protection. Requires two pole spaces. At 600V, must be used on 600Y/347V grounded wye systems only.
Table 1-36. Pull Box With Extension Trough
Includes pull bo x with trough e xtension.
For additional trough extensions, refer toTable 2-33 .
Neutral Bars
When Column Type panels are furnishedwith trough extensions and pull bo x, theneutral bar will be placed in the pull bo xunless other wise specified.
When troughs and pull bo x are not fur-nished, the neutral bar will be located onthe panel at the same end as the main.
Table 1-37. Additional Trough Extensions
Width and depth are the same as the
panelboard.
AmpereRating
Interrupting Rating (kA Symmetrical) BreakerType240V AC 600Y/347V AC 125/250V DC
Main Lug Only
100225
——
——
——
——
Main Breaker
100100
65 18
10 14
1410
GBHFDB
100100100
65100200
18 25 35
102222
FDHFDFDC
225225225225225
65 18 65100200
— 14 18 25 35
—10102222
EDFDBFDHFDFDC
AmpereRating Interrupting Rating (kA Symmetrical ) BreakerType240V AC 480Y/277V AC 600Y/347V AC 125/250V DC
15 – 20 15 – 60 70 – 100 15 – 30 15 – 60 70 – 100
65 65 65 65 65 65
14 14 14 14 14 14
————1010
—1414——14
GHQ
GHB
GHB
GHBS
GBH
GBH
15 – 60 — 14 — — GHBGFEP
Description CatalogueNumber
Pullbox with 36" TroughPullbox with 48" TroughPullbox with 60" TroughPullbox with 72" TroughPullbox with 84" Trough
XCTXB036XCTXB048XCTXB060XCTXB072XCTXB084
Length CatalogueNumberInches mm
3648607284
914.41219.21524.01828.82133.6
CTXB036CTXB048CTXB060CTXB072CTXB084
Table 2-31.
Table 2-30.
Table 2-33.Table 2-32.
2PanelboardsColumn Type
Type PRL2a-LX
-
8/17/2019 Catalogo-panel Electrico Ch
26/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Box Sizing and Selection
Assembled Circuit Breaker Panelboards
Box size, box and trim cataloguenumbers for standard column typepanelboards listed are available
fromTables 2-35 and 2-36.Instructions
1. Using description of the requiredpanelboard, select the rating andtype of main required.
a. 100 ampere panelboards —Table2-35.
b. 225 ampere panelboards —Table2-36.
2. Count the total number of branch cir-cuit poles, including provisions, re-quired in the panelboard. Do notcount main breaker poles. Convert 2-or 3-pole branch breaker to single
poles, i.e., 3-pole breaker, count as 3poles.
Determine sub-feed breaker orthrough-feed lug requirements.
3. Select the panelboard main ampererating fromTables 2-35 or 2-36.
4. Panelboard Type from first column,main breaker Frame and Designa-tion, if applicable from second col-umn, and sub-feed breaker Frameand Designation, if applicable, fromthe third column.
5. From Step #2, determine the num-ber of branch circuits in Column 4.
6. Read box size, box and trimcatalogue numbers across columnsto the right. All panels are surfacemounted.
Cabinets
Boxes and trims are code-gauge gal-vonized steel.
Boxes are furnished without knoc kouts.Standard depth is 6 inches (152.4 mm).Standard width is 8-5/8 inches
(219.1 mm).
Top and Bottom Gutters
4-1/2 inches (114.3 mm) minimum.
Left Side Gutter
3-5/16 inches (84.2 mm) minimum.
Pull Box
Pull box is furnished without knoc kouts.Standard dimensions:
Table 1-38. Pull Box Dimensions
Figure 1-11. PRL2a-LX Trough Extension,
Dimensions in Inches (mm)
Height Width Depth
Inches mm Inches mm Inches mm
12 304.8 16 406.4 6 152.4
AdditionalExtensions
(If Required)
HBox
Height
12(304.8)
6(152.4) 16
(406.4)
8-5/8(219.1)
6(152.4)
Table 2-34.
Figure 2-9.
2-26PanelboardsColumn Type
Type PRL2a-LX
-
8/17/2019 Catalogo-panel Electrico Ch
27/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Box Sizing and Selection (Continued)
Table 1-39. 100 Ampere Maximum PRL2a-LX Column Type Panelboard Sizing
� Add suffix B to tr im catalogue number for bottom fed panelboards (i.e., LTC969SB).
Table 1-40. 225 Ampere Maximum PRL2a-LX Column Type Panelboard Sizing
Add suffix B to tr im catalogue number for bottom fed panelboards (i.e., LTC969SB).
PanelboardTypes
Main BreakerTypesMounting:(H) = Horizontal
(V) = Vertical
Sub-FeedBreaker TypesVerticalMounting
MaximumNumberof BranchCircuits
IncludingProvisions
Box Dimensions Inches BoxCatalogueNumber
TrimCatalogueNumber �
Height Width Depth
Main Breaker GHB, GBH(H)
——
2739
69 (1752.6)81 (2057.7)
8-5/8 (219.2)8-5/8 (219.2)
6 (152.4)6 (152.4)
YSC969YSC981
LTC969SLTC981S
Main Lugs or Main Breaker EHD, FDHFD, FDC(V)
——
3042
69 (1752.6)81 (2057.7)
8-5/8 (219.2)8-5/8 (219.2)
6 (152.4)6 (152.4)
YSC969YSC981
LTC969SLTC981S
Main Lugs or Main Breakerwith 100A Through-Feed Lugsor Sub-Feed Breaker
EHD, FDHFD, FDC(V)
EHD, FD, HFD 3042
78 (1981.2)90 (2286.0)
8-5/8 (219.2)8-5/8 (219.2)
6 (152.4)6 (152.4)
YSC978YSC990
LTC978SLTC990S
PanelboardTypes
Main BreakerTypes
Sub-FeedBreaker Types
MaximumNumberof BranchCircuitsIncludingProvisions
Box Dimensions Inches BoxCatalogueNumber
TrimCatalogueNumber Vertical Mounting Height Width Depth
Main Lugs or Main Breaker ED, FDHFD, FDC
——
3042
69 (1752.6)81 (2057.7)
8-5/8 (219.2)8-5/8 (219.2)
6 (152.4)6 (152.4)
YSC969YSC981
LTC969SLTC981S
Main Lugs or Main Breakerwith 225A Through-Feed Lugsor Sub-Feed Breaker
ED, FDHFD, FDC
EHD, FD, HFD,ED, EDH
3042
78 (1981.2)90 (2286.0)
8-5/8 (219.2)8-5/8 (219.2)
6 (152.4)6 (152.4)
YSC978YSC990
LTC978SLTC990S
Table 2-35.
Table 2-36.
2PanelboardsColumn Type
Type PRL2a-LX
-
8/17/2019 Catalogo-panel Electrico Ch
28/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Boxes and Trims Only — Type 1
Table 1-41. Types PRL1a and PRL2a
Table 1-42. Type PRL3a 100 – 400 Amperes
Table 1-43. Type PRL4
Box Dimensions Height Box Trim
Inches mm CatalogueNumber
CatalogueNumber
20-inch W x 5-3/4-inch D(508.0 mm W x 146.1 mm D)
3036
42
48
54
60
72
90
762.0914.4
1066.8
1219.2
1371.6
1524.0
1828.8
2286.0
EZB2030RCEZB2036RCEZB2042RCEZB2048RCEZB2054RCEZB2060RCEZB2072RCEZB2090RC
EZT2030S or FEZT2036S or FEZT2042S or FEZT2048S or FEZT2054S or FEZT2060S or FEZT2072S or FEZT2090S or F
Box Dimensions Height Box Trim
Inches mm CatalogueNumber
Catalogue Number
100 – 400 Amperes 600 Amperes
20-inch W x 5-3/4-inch D
(508.0 mm W x 146.1 mm D)
48
60
72
1219.2
1524.0
1828.8
EZB2048RCEZB2060RCEZB2072RC
EZT2048S or FEZT2060S or FEZT2072S or F
EZTV2048S or FEZTV2060S or FEZTV2072S or F
Box Dimensions Height Box
Inches mm CatalogueNumber
24-inch W x 10.4-inch D
(609.6 mm W x 264.2 mm D)
57
73-1/2
90
1447.8
1866.9
2286.0
BX2457BX2473BX2490
38-inch W x 10.4-inch D
(965.2 mm W x 264.2 mm D)
73-1/2
90
1866.9
2286.0
BX3873BX3890
44-inch W x 10.4-inch D
(1117.6 mm W x 264.2 mm D)
73-1/2
90
1866.9
2286.0
BX4473BX4490
Table 2-37.
Table 2-38.
Table 2-39.
2-28PanelboardsPow-R-Line C Panelboards
Boxes and Trims
-
8/17/2019 Catalogo-panel Electrico Ch
29/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Modification Item
PRL1a PRL2a PRL3a PRL4B PRL4F Column
Type
Special Enclosure Construction
SPRINKLERPROOF (per CEC 26-008), 508mm (20") wide. Single or Multi-Section. 1a. Yes Yes Yes Yes Yes NoTYPE 2 508mm (20") wide. Single or Multi Section 1b. Yes Yes Yes Yes Yes No
TYPE 3R/12 Enclosure 1c. Yes Yes Yes Yes Yes No
TYPE 4 combination Enclosure (incorporates features required for 3R and 12 ratings) 1d. Yes Yes Yes Yes Yes No
Neutral Assemblies
200% rated neutrals ( use on systems with high harmonic content) - 100A max. bus Yes Yes Yes No No Yes
200% rated neutrals ( use on systems with high harmonic content) - 225A max. bus Yes Yes Yes No No Yes
200% rated neutrals ( use on systems with high harmonic content) - 250A max. bus No No Yes Yes Yes No
200% rated neutrals ( use on systems with high harmonic content) - 400A max. bus No No Yes Yes Yes No
200% rated neutrals ( use on systems with high harmonic content) - 600A max. bus No
No
No
No
No
No
Yes
No
No
Yes
No
No
Yes
No
No
No
200% rated neutrals ( use on systems with high harmonic content) - 800A max. bus No
200% rated neutrals ( use on systems with high harmonic content) - 1200A max. bus No
ALL 3 Phase, 4 Wire panelboa rds include a neutral assembly. For 3PH 3W applications
the neutral assembly is deleted.
24 point neutral adder for use with "twin frame" DNBA type breakers Yes No No No No No
42 point neutral adder for use with "twin frame" DNBA type breakers Yes No No No No No
Special Ground BusInsulated Ground Bus Assembly 3a. Yes Yes Yes Yes Yes No
Isolated Ground Bus Assembly 3b. Yes Yes Yes Yes Yes No
Sub Feed Assemblies (use on MLO panels only)
Sub-Feed Lugs - 100A Maximum Yes Yes Yes No No No
Sub-Feed Lugs - 225A Maximum Yes Yes Yes No No No
Sub-Feed Lugs - 250A Maximum No No Yes Yes Yes No
Sub-Feed Lugs - 400A Maximum (cable size/quantity restrictions on some panels) Yes Yes Yes Yes Yes No
Sub-Feed Lugs - 600A Maximum No No Yes Yes Yes No
Sub-Feed Lugs - 800A Maximum No No No Yes Yes No
Sub-Feed Lugs - 1200A Maximun No No No No No No
Sub-Feed Breakers - All Panelboard Ratings 4b. Yes Yes Yes Yes Yes No
Through-Feed Lug Assemblies (use with MLO or MB panels)
Through-Feed Lugs - 100A Maximum Yes Yes Yes No No No
Through-Feed Lugs - 225A Maximum Yes Yes No No No No
Through-Feed Lugs - 250A Maximum No No Yes Yes Yes No
Through-Feed Lugs - 400A Maximum Yes Yes Yes Yes Yes NoThrough-Feed Lugs - 600A Maximum No No Yes Yes Yes No
Through-Feed Lugs - 800A Maximum No No No Yes Yes No
Through-Feed Lugs - 1200A Maximun No No No Yes Yes No
Compression Lugs on Mains
Max. size: 1x750 kcmil / phase or 2x500 kcmil / phase
Refer to Eaton for enclosure dimensions.
Special Entr y Plates (Specify location, supplied loose)
Aluminum (Corflex) 7a. Yes Yes Yes Yes Yes No
Fibre (Corflex) 7b. Yes Yes Yes Yes Yes No
Brass (MIC) 7c. Yes Yes Yes Yes Yes No
Painting and Special Coatings
Painted Box (Any colour) 8a. Yes Yes Yes Yes Yes Yes
Trim (Other than ASA - 61) 8b. Yes Yes Yes Yes Yes Yes
Trim and Door Modifications
Door-in-Door 9a. Std. Std. Std. Yes Yes No
Door over Distribution 9b. Std. Std. Std. Yes Yes NoBox / Tub Modifications
Blank Box End 10a. Std. Std. Std. Std. No
Box End with Knockouts 10b. Yes Yes Yes No No No
Service Entrance
Includes barriered main breaker compartment to CSA requirements. All ratings. 11a. Yes Yes Yes Yes Yes No
Available on Panelboard Types
4a.
5a.
Yes YesYes Yes Yes Yes2b
Yes Yes Yes6a. Yes Yes Yes
2a.
2c.
Std.
Table 1-46. Panelboard Accessories and ModificationsTable 2-40.
2PanelboardsAccessories and Modifications
Type PRL 1a, 2a, 3a, 4, Column
-
8/17/2019 Catalogo-panel Electrico Ch
30/32
CAT.38.03.S.K For more information visit: www.eatoncanada.ca
Table 1-46a. Panelboard Accessories and Modifications - Continued
Modification Item
PRL1a PRL2a PRL3a PRL4B PRL4F Column
Type
Complete Assembly
Box, Interior, Breakers & Trim completely assembled prior to shipment. 12a. Yes Yes Yes Yes Yes YesMulti-Section Panels
Double Section - Cable connected - 225A Maximum (cross over cables NOT included) Yes Yes No No No No
Double Section - Cable connected - 250A Maximum (cross over cables NOT included) No No Yes Yes Yes No
Double Section - Cable connected - 400A Maximum (cross over cables NOT included) Yes Yes Yes Yes Yes No
Double Section - Cable connected - 600A Maximum (cross over cables NOT included) No No Yes Yes Yes No
Double Section - Cable connected - 800A Maximum (cross over cables NOT included) No No Yes Yes Yes No
Double Section - Cable connected - 1200A Maximum (cross over cables NOT included) No No Yes Yes Yes No
Double Section - Bus connected - 225A Maximum Yes Yes No No No No
Double Section - Bus connected - 250A Maximum No No Yes Yes Yes No
Double Section - Bus connected - 400A Maximum Yes Yes Yes Yes Yes No
Double Section - Bus connected - 600A Maximum No No Yes Yes Yes No
Double Section - Bus connected - 800A Maximum No No Yes Yes Yes No
Double Section - Bus connected - 1200A Maximum No No Yes Yes Yes No
Key Interlock (Use on main breakers - key protrudes through front cover) - All ratings. 14a. Yes Yes Yes Yes Yes No
Contactor in Mains
C-H - electrically held, installed in a separate compartment, with a removable cover. 15a. Yes Yes Yes No No NoSpecialty Contactors - mounted as above. 15b. Yes Yes Yes No No No
Cover Mounted Controls (Factory Wired) 15c. Yes Yes Yes No No No
Low Voltage Relay Troughs (Matching Box and Trim mounted adjacent to the panelboard).
30 inch high (762mm) to 72 inch high (1828mm) box & trim. 16a. Yes Yes No No No No
Relay Mounting rail for 30 inch high (762mm) to 72 inch high (1828mm) box & trim. 16b. Yes Yes No No No No
Moisture and Fungus Proofing 17a. Yes Yes Yes Yes Yes Yes
Tin Plating of Copper Bus 18a. Yes Yes Yes Yes Yes Yes
Nameplates and Circuit Directories
Engraved Lamicoid Nameplates - supplied loose or factory installed. 19a. Yes Yes Yes Yes Yes Yes
Circuit Directory Holder (Steel frame & acetate cover) 19b. Yes Yes Yes Yes Yes Yes
Circuit Breaker Handle Lock-off Devices
Non-Padlockable (supplied loose) 20a. Yes Yes Yes Yes Yes Yes
Padlockable (supplied loose) 20b. Yes Yes Yes Yes Yes Yes
Main or Branch Circuit Breaker Accessories
Auxiliary Switch (1A / 1B) 20a. Yes Yes Yes Yes Yes Yes
Shunt Trip 20b. Yes Yes Yes Yes Yes YesUndervoltage Release 20c. Yes Yes Yes Yes Yes Yes
Alarm Switch (1A / 1B) 20d. Yes Yes Yes Yes Yes Yes