Catalogo-panel Electrico Ch

download Catalogo-panel Electrico Ch

of 32

Transcript of Catalogo-panel Electrico Ch

  • 8/17/2019 Catalogo-panel Electrico Ch

    1/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Product Description

    � 240V AC maximum.

    � 3-phase 4-wire, 3-phase 3-wire,1-phase 3-wire, 1-phase 2-wire.

    � 600 ampere maximum main lugs.

    � 400 ampere maximum main breaker.� 100 ampere maximum branch break-

    ers (2 Pole 125A).

    � Bolt-on branch breakers.

    � Tin plated aluminum bus or silverplated copper bus.

    � Factory assembled.

    Type PRL1a 

    Application Description

    � Fully rated or series rated.

    � Interrupting ratings up to 200 kA sym-metrical.

    � Suitable for use as Service EntranceEquipment, when specified onthe order.

    Standards and Certifications

    � CSA - C22.2 No. 29

    � Federal Specification W-P-115c.

    Options and Accessories

    � Refer to Page 2-29.

    Layout and Sizing

    � Refer to Page 2-3.

    Product Selection

    Table 1-6. Base Configurations — PRL1a

    Table 1-7. Branch Circuit Breakers — PRL1a

    � 1-pole breakers are rated 120V AC maximum. 240 volt breakers must be used on 3-phase, 3-wire, 240 volt delta systems or on the high leg of a mid-

    point delta grounded system. 50 ampere devices are available as 2-pole only. GFCI for 5 mA personnel protection.

    GFP for 30 mA equipment protection. Combination Arc fault circuit breaker. HID (High Intensity Discharge) rated breaker. Switching Neutral Breaker. 1-pole device requires 2-pole space, 2-pole device requires 3-pole space.� Solenoid operated breaker.

    AmpereRating

    InterruptingRating(kA Sym.)240V AC

    BreakerType

    Main Lug Only

    100225400600

    ————

    ————

    Main Breaker

    100100100100100100100

      10  18  22  65  65100100

    BABEHD/FDBQBHWEDFDEDHHFD

    225225

      65100

    EDEDH

    400400400400

      65  65100200

    DKKDHKDKDC

    Bolt-on = BAB, QBHW, QBGF, QBHGF,QBGFEP, QBHGFEP, QBAF, QBAG

    AmpereRating

    InterruptingRating(kA Sym.)240V AC �

    BreakerType

    15 – 3015 – 607080 – 100

    12515 – 50 

    15 – 50 

    15 – 20

    10101010

    10101010

    DNBA (twin)BABBABBAB

    BAB (2 Pole)QBGF

    QBGFEP

    QBCAF

    15 – 6015 – 3015 – 30

    101010

    BAB-D

    BAB-C

    BABRSP

    15 – 607080 – 10012515 – 3015 – 30

    222222222222

    QBHWQBHWQBHWQBHW (2 Pole)QBHGF

    QBHGFEP 

    Table 2-1.

    Table 2-2.

    PanelboardsPow-R-Line C Panelboards

    PRL1a

  • 8/17/2019 Catalogo-panel Electrico Ch

    2/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Product Selection

    Table 1-8. Standard Catalogue Numbering

    Ampere

    Rating

    Main

    Device

    Type

    Number

    of Branch

    Circuits

    Catalogue Number

    3Ph, 4W

    Aluminum

    1Ph, 3W

    Aluminum

    3Ph, 4W

    Copper

    1Ph, 3W

    Copper

    Main Lug Only

    100

    -

    -

    -

    -

    18

    24

    30

    42

    P1aL4A1-18

    P1aL4A1-24

    P1aL4A1-30

    P1aL4A1-42

    P1aL1A1-18

    P1aL1A1-24

    P1aL1A1-30

    P1aL1A1-42

    P1aL4C1-18

    P1aL4C1-24

    P1aL4C1-30

    P1aL4C1-42

    P1aL1C1-24

    P1aL1C1-30

    P1aL1C1-42

    P1aL1C1-18

    225

    -

    -

    -

    -

    -

    -

    -

    18

    24

    30

    42

    60

    72

    84

    P1aL4A2-18

    P1aL4A2-24

    P1aL4A2-30

    P1aL4A2-42

    P1aL4A2-60

    P1aL4A2-72

    P1aL4A2-84

    P1aL1A2-18

    P1aL1A2-24

    P1aL1A2-30

    P1aL1A2-42

    P1aL1A2-60

    P1aL1A2-72

    P1aL1A2-84

    P1aL4C2-18

    P1aL4C2-24

    P1aL4C2-30

    P1aL4C2-42

    P1aL4C2-60

    P1aL4C2-72

    P1aL4C2-84

    P1aL1C2-18

    P1aL1C2-24

    P1aL1C2-30

    P1aL1C2-42

    P1aL1C2-60

    P1aL1C2-72

    P1aL1C2-84

    400

    -

    -

    -

    -

    -

    -

    24

    30

    42

    60

    72

    84

    P1aL4A4-24

    P1aL4A4-30

    P1aL4A4-42

    P1aL4A4-60

    P1aL4A4-72

    P1aL4A4-84

    P1aL1A4-24

    P1aL1A4-30

    P1aL1A4-42

    P1aL1A4-60

    P1aL1A4-72

    P1aL1A4-84

    P1aL4C4-24

    P1aL4C4-30

    P1aL4C4-42

    P1aL4C4-60

    P1aL4C4-72

    P1aL4C4-84

    P1aL1C4-24

    P1aL1C4-30

    P1aL1C4-42

    P1aL1C4-60

    P1aL1C4-72

    P1aL1C4-84

    600

    -

    -

    -

    -

    -

    -

    24

    30

    42

    60

    72

    84

    P1aL4C6-24

    P1aL4C6-30

    P1aL4C6-42

    P1aL4C6-60

    P1aL4C6-72

    P1aL4C6-84

    P1aL1C6-24

    P1aL1C6-30

    P1aL1C6-42

    P1aL1C6-60

    P1aL1C6-72

    P1aL1C6-84

    Main Breaker

    100 BAB

    15

    2127

    P1aB4A1-15BAB

    P1aB4A1-21BABP1aB4A1-27BAB

    P1aB1A1-15BAB

    P1aB1A1-21BABP1aB1A1-27BAB

    P1aB4C1-15BAB

    P1aB4C1-21BABP1aB4C1-27BAB

    P1aB1C1-15BAB

    P1aB1C1-21BABP1aB1C1-27BAB

    100 EHD

    18

    24

    30

    P1aB4A1-18EHD

    P1aB4A1-24EHD

    P1aB4A1-30EHD

    P1aB1A1-18EHD

    P1aB1A1-24EHD

    P1aB1A1-30EHD

    P1aB4C1-18EHD

    P1aB4C1-24EHD

    P1aB4C1-30EHD

    P1aB1C1-18EHD

    P1aB1C1-24EHD

    P1aB1C1-30EHD

    225 ED

    24

    30

    42

    60

    72

    P1aB4A2-24ED

    P1aB4A2-30ED

    P1aB4A2-42ED

    P1aB4A2-60ED

    P1aB4A2-72ED

    P1aB1A2-24ED

    P1aB1A2-30ED

    P1aB1A2-42ED

    P1aB1A2-60ED

    P1aB1A2-72ED

    P1aB4C2-24ED

    P1aB4C2-30ED

    P1aB4C2-42ED

    P1aB4C2-60ED

    P1aB4C2-72ED

    P1aB1C2-24ED

    P1aB1C2-30ED

    P1aB1C2-42ED

    P1aB1C2-60ED

    P1aB1C2-72ED

    400 DK

    24

    30

    42

    60

    72

    P1aB4A4-24DK

    P1aB4A4-30DK

    P1aB4A4-42DK

    P1aB4A4-60DK

    P1aB4A4-72DK

    P1aB1A4-24DK

    P1aB1A4-30DK

    P1aB1A4-42DK

    P1aB1A4-60DK

    P1aB1A4-72DK

    P1aB4C4-24DK

    P1aB4C4-30DK

    P1aB4C4-42DK

    P1aB4C4-60DK

    P1aB4C4-72DK

    P1aB1C4-24DK

    P1aB1C4-30DK

    P1aB1C4-42DK

    P1aB1C4-60DK

    P1aB1C4-72DK

    Pow-R-Line 1a Catalogue Code

    P1a B 4 A 4 - 42 KDC 400

    Panelboard Type L - Main Lugs Only

    B - Bottom MainBreaker

    T - Top Main Breaker

    1 - 1phase, 3 wire

    3 - 3phase, 3 wire

    4 - 3phase, 4 wire

    A - Aluminum

    C - Copper

    1 - 100 amperes

    2 - 225 amperes

    4 - 400 amperes

    6 - 600 amperes

    -

    -

    -

    Number of

    Circuits

    Main

    Breaker

    (if selected)

    Breaker

    Trip

    Rating

    � All possible combinations not shown for alternate main breakers, substitue breaker type suffix from Table 2-1. Add breaker trip rating to end of catalogue number.

    Table 2-3.

    2-2PanelboardsPow-R-Line C Panelboards

    PRL1a

  • 8/17/2019 Catalogo-panel Electrico Ch

    3/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Box Sizing and Selection

    Assembled Circuit Breaker Panelboards

    Box size and box and trim catalogue num-bers for all standard panelboard types arefound inTable 2-4..

    Instructions1. Using description of the required

    panelboard, select the rating andtype of main required.

    2. Count the total number of branchcircuit poles, including provisions,required in the panelboard. Do notcount main breaker poles. Convert2- or 3-pole branch breaker tosingle-poles, i.e., 3-pole breaker,count as 3 poles.

    Determine sub-feed breaker orthrough-feed lug requirements.

    3. Select the main ampere rating

    section fromTable 2-4.

    4. Select panelboard type from firstcolumn.

    5. From Step #2, determine the num-ber of branch circuits in Column 2.

    6. Read box size, box and trimcatalogue numbers across columnsto the right. Specify surface or flushmounting on the order.

    Cabinets

    Fronts are code-gauge steel, ASA-61 lightgray painted finish.

    Boxes are code-gauge galvanized steelwithout knockouts. Standard depth is5-3/4 inches (146.1 mm). Standard widthis 20 inches (508.0 mm). An optional 28-inch (711.2 mm) wide box is available.

    Top and Bottom Gutters

    5-1/2 inches (139.7 mm) minimum.

    Table 2-4. PRL1a Panelboard Sizing

    MainsAmpere(Maximum)

    Number ofBranchCircuit

    Box Dimensions(Inches) Box

    CatalogueNumber

      TrimCatalogueNumber

      H W D

    MAIN LUGS ONLY OR MAIN LUGS WITH SUB-FEED LUGS

    10018243042

    30303036

    20202020

    5.755.755.755.75

    EZB2030RCEZB2030RCEZB2030RCEZB2036RC

    EZT2030 S or FEZT2030 S or FEZT2030 S or FEZT2036 S or F

    225

    18243042607284

    30363642546072

    20202020202020

    5.755.755.755.755.755.755.75

    EZB2030RCEZB2036RCEZB2036RCEZB2042RCEZB2054RCEZB2060RCEZB2072RC

    EZT2030 S or FEZT2036 S or FEZT2036 S or FEZT2042 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or F

    400� /600

    243042607284

    424854607272

    202020202020

    5.755.755.755.755.755.75

    EZB2024RCEZB2030RCEZB2054RCEZB2060RCEZB2072RCEZB2072RC

    EZT2042 S or FEZT2048 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or FEZT2072 S or F

    MAIN LUGS WITH THROUGH-FEED LUGS

    10018243042

    30303036

    20202020

    5.755.755.755.75

    EZB2030RCEZB2030RCEZB2030RCEZB2036RC

    EZT2030 S or FEZT2030 S or FEZT2030 S or FEZT2036 S or F

    225

    182430426072

    303636426060

    202020202020

    5.755.755.755.755.755.75

    EZB2030RCEZB2036RCEZB2036RCEZB2042RCEZB2060RCEZB2072RC

    EZT2030 S or FEZT2036 S or FEZT2036 S or FEZT2042 S or FEZT2060 S or FEZT2072 S or F

    400/600

    2430426072

    4854607272

    2020202020

    5.755.755.755.755.75

    EZB2048RCEZB2054RCEZB2060RCEZB2072RCEZB2072RC

    EZT2048 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or FEZT2072 S or F

    MAIN LUGS WITH SURGE PROTECTION DEVICE

    10018243042

    30303036

    20202020

    5.755.755.755.75

    EZB2030RCEZB2030RCEZB2030RCEZB2036RC

    EZT2030 S or FEZT2030 S or FEZT2030 S or FEZT2036 S or F

    225

    18243042607284

    30363642546072

    20202020202020

    5.755.755.755.755.755.755.75

    EZB2030RCEZB2036RCEZB2036RCEZB2042RCEZB2054RCEZB2060RCEZB2072RC

    EZT2030 S or FEZT2036 S or FEZT2036 S or FEZT2042 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or F

    400/600

    2430426072

    4854546072

    2020202020

    5.755.755.755.755.75

    EZB2048RCEZB2054RCEZB2054RCEZB2060RCEZB2072RC

    EZT2048 S or FEZT2054 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or F

    � In a Sub-Feed configuration, maximum incoming and outgoing cables are 1per phase #500kcmil.

    Through-Feed lugs are recommended for 400A applications.

    PanelboardsPow-R-Line C Panelboards

    PRL1a

  • 8/17/2019 Catalogo-panel Electrico Ch

    4/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Box Sizing and Selection

    Assembled Circuit Breaker Panelboards

    Box size and box and trim cataloguenumbers for all standard panelboardtypes are found inTable 2-5.

    Instructions1. Using description of the required

    panelboard, select the rating andtype of main required.

    2. Count the total number of branchcircuit poles, including provisions,required in the panelboard. Do notcount main breaker poles. Convert2- or 3-pole branch breaker tosingle-poles, i.e., 3-pole breaker,count as 3 poles.

    Determine sub-feed breaker orthrough-feed lug requirements.

    3. Select the main ampere rating

    section fromTable 2-5.

    4. Select panelboard type from firstcolumn, main breaker frame fromsecond column.

    5. From Step #2, determine the num-ber of branch circuits in Column 3.

    6. Read box size, box and trimcatalogue numbers across columnsto the right. Specify surface or flushmounting on the order.

    Cabinets

    Fronts are code-gauge steel, ASA-61light gray painted finish.

    Boxes are code-gauge galvanized steelwithout knockouts. Standard depth is 5-3/4 inches (146.1 mm). Standard width is20 inches (508.0 mm). An optional 28-inch (711.2 mm) wide box is available.

    Top and Bottom Gutters

    5-1/2 inches (139.7 mm) minimum.

    Table 1-11. PRL1a Panelboard Sizing

    Table 1-12. Metric box dimensions:

    AmpereRating

    Main BreakerTypes andPosition

    NumberBranch Cct.Spaces

    BoxDimensions(Inches)

    BoxCatalogueNumber

    TrimCatalogueNumber

    H W D

    100 BAB, QBHW(Horizontal)

    15, 21, 27 30 20 5.75 EZB2030RC EZT2030 S or F

    100/225 EHD, ED, EDH,FD(Vertical)

    18, 2430426072, 84

    3642486072

    2020202020

    5.755.755.755.755.75

    EZB2036RCEZB2042RCEZB2048RCEZB2060RCEZB2072RC

    EZT2036 S or FEZT2042 S or FEZT2048 S or FEZT2060 S or FEZT2072 S or F

    400DK, KD, HKD,KDC(Vertical)

    24304260, 72

    48546072

    20202020

    5.755.755.755.75

    EZB2048RCEZB2054RCEZB2060RCEZB2072RC

    EZT2048 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or F

    MAIN BREAKER WITH THROUGH-FEED LUGS

    100 BAB, QBHW(Horizontal)

    15, 21, 27 30 20 5.75 EZB2030RC EZT2030 S or F

    100/225 EHD, HFD, FD(Vertical)

    1824, 30426072

    3642546072

    2020202020

    5.755.755.755.755.75

    EZB2036RCEZB2042RCEZB2054RCEZB2060RCEZB2072RC

    EZT2036 S or FEZT2042 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or F

    400DK, KD, HKD,KDC(Vertical)

    243042

    607272

    202020

    5.755.755.75

    EZB2060RCEZB2072RCEZB2072RC

    EZT2060 S or FEZT2072 S or FEZT2072 S or F

    MAIN BREAKER WITH SURGE PROTECTION DEVICE

    100 BAB, QBHW(Horizontal)

    15, 21, 27 42 20 5.75 EZB2042RC EZT2042 S or F

    100/225 EHD, ED, EDH,FD(Vertical)

    182430426072

    484854607272

    202020202020

    5.755.755.755.755.755.75

    EZB2048RCEZB2048RCEZB2054RCEZB2060RCEZB2072RCEZB2072RC

    EZT2048 S or FEZT2048 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or FEZT2072 S or F

    400DK, KD, HKD,KDC(Vertical)

    2430, 426072

    48549090

    20202020

    5.755.755.755.75

    EZB2048RCEZB2054RCEZB2090RCEZB2090RC

    EZT2048 S or FEZT2054 S or FEZT2090 S or FEZT2090 S or F

    Box CatalogueNumber

    Dimensions in mm

    Height Width Depth

    EZB2030RCEZB2036RCEZB2042RCEZB2048RCEZB2054RCEZB2060RCEZB2072RCEZB2090RC

      762  914106712191372152418282286

    508.0508.0508.0508.0508.0508.0508.0508.0

    146146146146146146146146

    Table 2-5.

    Table 2-6.

    2-4PanelboardsPow-R-Line C Panelboards

    PRL1a

  • 8/17/2019 Catalogo-panel Electrico Ch

    5/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Product Description

    � 600Y/347 V AC.

    � 480Y/277V AC .

    � 125V AC

    � 3-phase 4-wire

    � 1-phase 3-wire, 1-phase 2-wire.

    � 3-phase 3-wire.

    � 600 ampere maximum main lugs.

    � 400 ampere maximum main breaker.

    � 100 ampere maximum branch break-ers.

    � Bolt-on branch breakers.

    � Tin plated aluminum bus or silverplated copper bus.

    � Factory assembled.

    Type PRL2a 

    Application Description

    � Fully rated or series rated.� Interrupting ratings up to 200 kA sym-

    metrical.

    � Suitable for use as Service EntranceEquipment, when specified onthe order.

    Standards and Certifications

    � CSA C22.2 No. 29

    � Federal Specification W-P-115c.

    Options and Accessories

    � Refer to Page 2-29.

    Layout and Sizing

    � Refer to Page 2-7.

    Product Selection

    Table 1-13. Base Configuration — PRL2a

    Table 1-14. Branch Circuit Breakers — PRL2a

    � Interrupting ratings in this column are applicable to 120V AC for 1-pole breakers. At 480V, must be used on 480Y/277V grounded wye systems only. Solenoid operated breaker. GFP for 30 mA equipment protection. Requires 2-pole spaces. 277V AC only. HID (High Intensity Discharge) rated breaker. 240V AC maximum rating for these systems. At 600V, must be used on 600Y/347V grounded wye systems only.

    AmpereRating

    Interrupting Rating(kA Symmetrical)

    BreakerType

    240V AC 480Y/277V AC 600Y/347V AC 125/250V DC

    Main Lug Only

    100225400600

    ————

    ————

    ————

    ————

    ————

    Main Breaker

    100100100

      65  65  18

      14  14  14

    —10—

    141410

    GHBGBHEHD

    100100100100

      65  18100200

      35  14  65100

    18142535

    10102222

    FDFDBHFDFDC

    225225225225225

      65  18  65100200

    —  14  35  65100

    —14182535

    —10102222

    EDFDBFDHFDFDC

    250250250

      65100200

      35  65100

    182535

    102222

    JDHJDJDC

    400400400

      65100200

      35  65100

    253565

    102222

    KDHKDKDC

    AmpereRating

    Interrupting Rating(kA Symmetrical)

    BreakerType

    240V AC  480Y/277V AC 600Y/347V AC 125/250V DC

    15 – 6015 – 60

    70 – 10070 – 10015 – 30

    6565

    656565

    1414

    141414

    —10

    —10—

    1414

    1414—

    GHB 

    GBH

    GHB 

    GBH

    GHQRSP 

    15 – 6015 – 20

    ——

    1414

    ——

    ——

    GHBGFEP GHBHID 

    Provision — — — — —

    Table 2-8.

    Table 2-7.

    PanelboardsPow-R-Line C Panelboards

    PRL2a

  • 8/17/2019 Catalogo-panel Electrico Ch

    6/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Product Selection

    Table 1-15. Standard Catalogue Numbering

    Ampere

    Rating

    Main

    Device

    Type

    Number

    of Branch

    Circuits

    Catalogue Number

    3Ph, 4W

    Aluminum

    1Ph, 3W

    Aluminum

    3Ph, 4W

    Copper

    1Ph, 3W

    CopperMain Lug Only

    100

    18

    24

    30

    42

    P2aL4A1-18

    P2aL4A1-24

    P2aL4A1-30

    P2aL4A1-42

    -

    -

    -

    -

    P2aL4C1-18

    P2aL4C1-24

    P2aL4C1-30

    P2aL4C1-42

    -

    -

    -

    -

    225

    24

    30

    42

    60

    72

    P2aL4A2-24

    P2aL4A2-30

    P2aL4A2-42

    P2aL4A2-60

    P1aL4A2-72

    -

    -

    -

    -

    -

    P2aL4C2-24

    P2aL4C2-30

    P2aL4C2-42

    P2aL4C2-60

    P2aL4C2-72

    -

    -

    -

    -

    -

    400

    24

    30

    42

    60

    72

    P2aL4A4-24

    P2aL4A4-30

    P2aL4A4-42

    P2aL4A4-60

    P2aL4A4-72

    -

    -

    -

    -

    -

    P2aL4C4-24

    P2aL4C4-30

    P2aL4C4-42

    P2aL4C4-60

    P2aL4C4-72

    -

    -

    -

    -

    -

    600

    24

    30

    42

    60

    72

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    P2aL4C6-24

    P2aL4C6-30

    P2aL4C6-42

    P2aL4C6-60

    P2aL4C6-72

    -

    -

    -

    -

    -

    Main Breaker

    100 GBH

    15

    21

    27

    P2aB4A1-15GBH

    P2aB4A1-21GBH

    P2aB4A1-27GBH

    -

    -

    -

    P2aB4C1-15GBH

    P2aB4C1-21GBH

    P2aB4C1-27GBH

    -

    -

    -

    100 FDB

    18

    24

    30

    P2aB4A1-18FDB

    P2aB4A1-24FDB

    P2aB4A1-30FDB

    -

    -

    -

    P2aB4C1-18FDB

    P2aB4C1-24FDB

    P2aB4C1-30FDB

    -

    -

    -

    225 FDB

    24

    30

    42

    60

    72

    P2aB4A2-24FDB

    P2aB4A2-30FDB

    P2aB4A2-42FDB

    P2aB4A2-60FDB

    P2aB4A2-72FDB

    -

    -

    -

    -

    -

    P2aB4C2-24FDB

    P2aB4C2-30FDB

    P2aB4C2-42FDB

    P2aB4C2-60FDB

    P2aB4C2-72FDB

    -

    -

    -

    -

    -

    400 KD

    24

    30

    42

    60

    72

    P2aB4A4-24KD

    P2aB4A4-30KD

    P2aB4A4-42KD

    P2aB4A4-60KD

    P2aB4A4-72KD

    -

    -

    -

    -

    -

    P2aB4C4-24KD

    P2aB4C4-30KD

    P2aB4C4-42KD

    P2aB4C4-60KD

    P2aB4C4-72KD

    -

    -

    -

    -

    -

    Pow-R-Line 2a Catalogue Code

    P2a B 4 A 4 - 42 KDC 400

    Panelboard Type L - Main Lugs Only

    B - Bottom MainBreaker

    T - Top Main Breaker

    1 - 1phase, 3 wire

    3 - 3phase, 3 wire

    4 - 3phase, 4 wire

    A - Aluminum

    C - Copper

    1 - 100 amperes

    2 - 225 amperes

    4 - 400 amperes

    6 - 600 amperes

    -

    -

    -

    Number of

    Circuits

    Main

    Breaker

    (if selected)

    Breaker

    Trip

     Rating

    � All possible combinations not shown. For alternate main breakers, substitue breaker type suffix from Table 2-7. Add breaker trip rating to end of catalogue number.

    Table 2-9.

    2-6PanelboardsPow-R-Line C Panelboards

    PRL2a

  • 8/17/2019 Catalogo-panel Electrico Ch

    7/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Box Sizing and Selection

    Assembled Circuit Breaker Panelboards

    Box size and box and trim catalogue num-bers for all standard panelboard types arefound inTable 2-10 and 2-11.

    Instructions1. Select the rating and types of mains

    required from Tables.

    2. Count the total number of branchcircuit poles (including spaces)required in the panelboard. Do notcount main breaker poles. Convert 2or 3 pole branch breakers to singlepoles, i.e., 3-pole breaker, count as 3poles. (140 amps per connector max-imum).

    3. Using the correct table, type ofmains and ampere rating per step 1above, find total on the table, use

    the next higher number.4. Read box size, box and trim

    catalogue numbers across column tothe right. On trim catalogue num-bers, specify surface or flush mount-ing on the order.

    Cabinets

    Fronts are code-gauge steel, ASA-61 lightgray painted finish.

    Boxes are code-gauge galvanized steelwithout knockouts. Standard depth is5-3/4 inches (146.1 mm). Standard widthis 20 inches (508.0 mm).

    Top and Bottom Gutters

    5-1/2 inches (139.7 mm) minimum.

    Table 1-18. Metric box dimensions

    BoxCatalogueNumber

    Dimensions in mm

    Height Width Depth

    EZB2030RCEZB2036RCEZB2042RCEZB2048RCEZB2054RCEZB2060RCEZB2072RC

    76291410671219137215241828

    508508508508508508508

    146146146146146146146

    Table 1-16. PRL2a Panelboard Sizing

    Table 1-17. PRL2a Panelboard Sizing

    Main Lugs Only or Main Lugs with Sub-Feed Lugs

    Mains AmpereRating

    Number ofBranch Circuit

    Poles

    Box DimensionsInches

    BoxCatalogueNumber

    TrimCatalogueNumberH W D

    100 Amp Main Lugs 18, 24, 30

    42

    30

    36

    20

    20

    5-3/4

    5-3/4

    EZB2030RC

    EZB2036RC

    EZT2030 S or F

    EZT2036 S or F225 Amp Main Lugs 18

    24, 3042607284

    303642546072

    202020202020

    5-3/45-3/45-3/45-3/45-3/45-3/4

    EZB2030RCEZB2036RCEZB2042RCEZB2054RCEZB2060RCEZB2072RC

    EZT2030 S or FEZT2036 S or FEZT2042 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or F

    400/600 Amp MainLugs

    24304260

    72, 84

    4248546072

    2020202020

    5-3/45-3/45-3/45-3/45-3/4

    EZB2042RCEZB2048RCEZB2054RCEZB2060RCEZB2072RC

    EZT2042 S or FEZT2048 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or F

    Main Lugs with Through-Feed Lugs

    100 Amp Main Lugs 18, 24, 3042

    3036

    2020

    5-3/45-3/4

    EZB2030RCEZB2036RC

    EZT2030 S or FEZT2036 S or F

    225 Amp Main Lugs 18, 2430426072

    3642486072

    2020202020

    5-3/45-3/4

    5-3/45-3/45-3/4

    EZB2036RCEZB2042RC

    EZB2048RCEZB2060RCEZB2072RC

    EZT2036 S or FEZT2042 S or F

    EZT2048 S or FEZT2060 S or FEZT2072 S or F

    400/600 Amp MainLugs

    243042

    60, 72

    48546072

    20202020

    5-3/45-3/45-3/45-3/4

    EZB2048RCEZB2054RCEZB2060RCEZB2072RC

    EZT2048 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or F

    Main Breaker Number ofBranch Circuit

    Poles

    Box DimensionsInches

    BoxCatalogueNumber

    TrimCatalogueNumberAmpere Rating Type H W D

    100 GBH, GHB � (horizontal)

    15, 21, 27 30 20 5-3/4 EZB2030RC EZT2030 S or F

    100/225 FDB, FD,

    HFD, FDCEHD�

    (vertical)

    18, 24

    304260

    72, 84

    36

    42486072

    20

    20202020

    5-3/4

    5-3/45-3/45-3/45-3/4

    EZB2036RC

    EZB2042RCEZB2048RCEZB2060RCEZB2072RC

    EZT2036 S or F

    EZT2042 S or FEZT2048 S or FEZT2060 S or FEZT2072 S or F

    400 KDHKDKDC

    (vertical)

    243042

    60, 72

    48546072

    20202020

    5-3/45-3/45-3/45-3/4

    EZB2048RCEZB2054RCEZB2060RCEZB2072RC

    EZT2048 S or FEZT2054 S or FEZT2060 S or FEZT2072 S or F

    Main Breaker with Through-Feed Lugs

    100 GBH, GHB � (horizontal)

    15, 21, 27 30 20 5-3/4 EZB2030RC EZT2030 S or F

    100/225 FDB, FD,HFD, FDC

    EHD�

    (vertical)

    18, 2430426072

    3642486072

    2020202020

    5-3/45-3/45-3/45-3/45-3/4

    EZB2036RCEZB2042RCEZB2048RCEZB2060RCEZB2072RC

    EZT2036 S or FEZT2042 S or FEZT2048 S or FEZT2060 S or FEZT2072 S or F

    400 KDHKD, KDC(vertical)

    243042

    607272

    202020

    5-3/45-3/45-3/4

    EZB2060RCEZB2072RCEZB2072RC

    EZT2060 S or FEZT2072 S or FEZT2072 S or F

    � In Sub-Feed configuration, maximum incoming and outgoing cables are 1 per phase #500kcmil.Through-Feed lugs are recommended for 400A applications.

    Table 2-10.

    Table 2-11.

    Table 2-12.

    PanelboardsPow-R-Line C Panelboards

    PRL2a

  • 8/17/2019 Catalogo-panel Electrico Ch

    8/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Product Description

    � 600V AC maximum (250V DC).

    � 3-phase 4-wire, 3-phase 3-wire,1-phase 3-wire, 1-phase 2-wire.

    � 600 ampere maximum main lugs.

    � 600 ampere maximum main breaker.� 225 ampere maximum branch break-

    ers.

    � Bolt-on branch breakers.

    � Factory assembled.

    Type PRL3a 

    Application Description

    � Lighting and appliance branchpanelboard or power distribution panel-board.

    � Fully rated or series rated.

    � Interrupting ratings up to 200 kA sym-metrical.

    � Suitable for use as Service EntranceEquipment, when specified onthe order.

    Standards and Certification

    � CSA C22.2 No. 29

    � Federal Specification W-P-115c.

    Options and Accessories

    � Refer to Page 2-29.

    Layout and Sizing

    Refer to Page 2-10.

    Product Selection

    Table 1-19. Base Configurations — PRL3a

    AmpereRating

    Interrupting Rating (kA Symmetrical) BreakerType240V AC 480V AC 600V AC 250V DC

    Main Lug Only

    100250400600

    ————

    ————

    ————

    ————

    ————

    Main Breaker

    100100100100100100100

      18  18  65100  65100200

      14  14——  35  65100

    —  14——  18  25  35

      10  10——  10  22  22

    EHDFDBEDEDHFDHFDFDC

    225225225225225225

      65100200  65100200

    ———  35  65100

    ———  18  25  35

    ———  10  22  22

    EDEDHEDCFDHFDFDC

    250250250

      65100200

      35  65100

      18  25  35

      10  22  22

    JDHJDJDC

    400400400400

      65  65100200

    —  35  65100

    —  25  35  65

      10  10  22  22

    DKKDHKDKDC

    600600

      65100

      35  65

      18  35

      22  42

    LGELGH

    6 - 600 amperes

    Pow-R-Line 3a Catalogue Code

    P3a B 4 A 4 - 21 KD 400

    Panelboard Type L - Main Lugs Only

    B - Bottom MainBreaker

    T - Top Main Breaker

    1 - 1phase, 3 wire

    3 - 3phase, 3 wire

    4 - 3phase, 4 wire

    A - Aluminum

    C - Copper

    1 - 100 amperes

    2 - 225 amperes

    4 - 400 amperes

    -

    -

    -

    -

    Feeder

    Breaker

    x-Space

    Main

    Breaker

    (if selected)

    Breaker

    Trip

    Rating

    Table 2-13.

    2-8PanelboardsPow-R-Line C Panelboards

    PRL3a

  • 8/17/2019 Catalogo-panel Electrico Ch

    9/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Table 1-20. Branch Circuit Breakers — PRL3a 

    � 1-pole breaker rated 120V AC. 2-pole breaker rated 120/240V AC. 50 ampere devices are available as 2-pole only. Combination Arc fault circuit breaker. HID (High Intensity Discharge) rated breaker. Switching Neutral Breaker. 1-pole device requires 2-pole space, 2-pole device requires 3-pole space. Solenoid operated breaker. 1-pole breaker rated 277V AC.� For use on 480Y/277V systems only. AIC rating for 2- and 3-pole breakers only. Maximum of six breakers per panel, 175 – 225 amperes. 1-Pole breaker rated 347V AC. For use on 600Y/347V systems only 3-Pole only

    AmpereRating

    Interrupting Rating (kA Symmetrical) BreakerType240V AC 480V AC 600V AC 250V DC

      15 – 30  15 – 60  15 – 60

      70  70  80 – 100  80 – 100  15 – 50

      15 – 50

      15 – 50

      15 – 20  15 – 60  15 – 30  15 – 30

      10�

      10 �

      10

      10 

      10  10 �

      10  10 �

      10 �

      10 �

      10 �

      10 �

      10 �

      10�

    ———

    ———————————

    ———

    ———————————

    ———

    ———————————

    DNBA (Twin)BABBAB-HBABBAB-HBABBAB-HQBGFQBGFEPGFCBBQBCAF

    BAB-D

    BAB-C

    BABRSP

      15 – 60  15 – 60  70  70  80 – 100  80 – 100  15 – 30  15 – 30

      22 �

      22  22 �

      22  22 �

      22  22  22

    ————————

    ————————

    ————————

    QBHWQBHW-HQBHWQBHW-HQBHWQBHW-HQBHGFQBHGFEP

      15 – 20

      15 – 60  15 – 60  70 – 100  70 – 100  15 – 30  15 – 60  15 – 20

      65

      65  65  65  65  65——

      14

      14 

      14

      14  

    14

      14 

      14 

      14 

    —10

    —10

    ———

    1414141414——

    GHQ

    GHBGBHGHBGBHGHQRSP 

    GHBGFEPGHBHID

      15 – 60  70 – 100

      18 

      18   14 

      14 ——

    1010

    EHDEHD

      15 – 60  15 – 150  70 – 100110 – 150

      18  —  18  18

      14  —  14  14

    14141414

    10—1010

    FDBFDBFDBFDB

      15 – 60  15 – 150  70 – 100110 – 225

      65 

      —  65 

      65 

      35 

      —  35 

      25

    18181818

    10—1010

    FDFDFDFD 

      15 – 60  70 – 100

    110 – 225

    100 

    100 

    100 

      65 

      65 

      65

    2525

    25

    2222

    22

    HFDHFD

    HFD 

      15 – 60  70 – 100110 – 225

    200200200

    100100100

    353535

    222222

    FDCFDCFDC 

    100 – 225100 – 225100 – 225

      65100200

    ———

    ———

    ———

    ED 

    EDH 

    EDC 

    100 – 225100 – 225  60 – 150  60 – 150  15 – 80  15 – 80100 – 225100 – 225  60 – 150  60 – 150  15 – 80  15 – 80

    656565656565100100100100100100

    353535353535656565656565

    181818181818252525252525

    ————————————

    FDE322533 LS

    FDE322532 LSI

    FDE316033 LS

    FDE316032 LSI

    FDE308033 LS

    FDE308032 LSI

    HFDE322533 LS

    HFDE322532 LSI

    HFDE316033 LS

    HFDE316032 LSI

    HFDE308033 LS

    HFDE308032 LSI

    Table 2-14.

    PanelboardsPow-R-Line C Panelboards

  • 8/17/2019 Catalogo-panel Electrico Ch

    10/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

     

    Panel Layout Instructions

    1. Select:

    a. Required mains (lugs or breaker).

    b. Neutral where required.

    c. Branch circuits as required.

    2. Layout panel as shown inFigure 1-4, using appropriate“X” dimensions.

    3. Using total X units (panel height) findbox height in inches (mm) and boxcatalogue number from Table 2-15.(When total X units come out to anuneven number, use next highestnumber; i.e., if total X comes out25X, use 31X.)

    Layout Example

    1. Description of Panel Type PRL3a 3-

    phase, 4-wire, 120/208V AC flush

    mounting. Panel to have short circuitrating of 22,000 symmetrical

    amperes. Main breaker 400amperes, 3-pole, bottom mounting.

    Branch circuits bolt-on as follows:

    12 – 20 ampere 1-pole QBHW1 – 200 ampere 3-pole ED

    1 – 225 ampere 3-pole ED

      2 – 125 ampere 3-pole ED 

    2. Layout Information fromFigure 1-4:

    a. 400 ampere Neutral . . . . . = 5X

    b. 12-poles of QBHW . . . . . . = 5Xc. Two 3-pole ED break ers . . . = 6X

    d. Two 3-Pole ED break ers . . . = 3XMain breakers 400 amperes

    e. 3-pole DK . . . . . . . . . . . . . .= 15XTotal Height. . . . . . . . . . . . = 34X

    3. FromTable 2-15:

    a. 34X Height (use 40X box)

    b. Box Height . . . . . . . . . .72 inches(1828.8 mm)

    c. Box Catalogue Number . . . . . . . . .EZB2072RC

    Figure 1-4. PRL3a Layout� GHB and GBH breakers cannot be mixed on

    same connector as BAB, QBHW and BABRSP. Maximum of six breakers per panel. If optional terminal kit 3TA225FDK is required,

    must use 28-inch (711.2 mm) box. Horizontal mounted 15 – 150 ampere main

    breakers EHD, FDB, FD, HFD and FDC, willbe furnished as branch breaker construction.Branch breakers 1-, 2- or 3-pole as required,

    may be located opposite these main breakers.

    Table 1-21. Box Tabulation — PRL3a

    600 ampere panels are optionally available with28-inch (610 mm) wide box. Consult factory foravailability.

    Cabinets

    Fronts are code-gauge steel, ASA-61 lightgray painted finish.

    Boxes are code-gauge galvanized steelwithout knockouts. Standarddepth is 5-3/4 inches (146.1 mm).

    Standard widths are:

    20-inch (508.0 mm) 100 – 600 amperes.

    Standard Depth

    5-3/4 inches (146.1 mm).

    Top and Bottom Gutters

    5-1/2 inches (139.7 mm) minimum.

    Side Gutters

    4 inches (101.6 mm) minimum.

    Poles BAB, QBHW,

    BABRSP

    GHB,

    GBH

      6 - 3X

    12 - 5X

    18 - 8X

    24 - 10X

    30 - 13X

    36 - 15X42 - 18X

    1X

    2X

    3X

    ED, EDH, EDC,EHD, FDB, FD,HFD, FDC150A Max. PerBranch Breaker(300A Max. PerConnector)

    2X2-Pole

    ED, EDH, EDCFD, HFD, FDC

    (175 - 225A)3X3-Pole

    Neutral

    Section

    5X 250A-400A

    8X 600A

    MainLugSection

    5X 250A

    8X 400-600A

    MainBreakerSection

    Hori-zontalMount-ing

    2X2-Pole

    EHD, FDB, FD,HFD, FDC

    3X3-Pole

    ED, EDH, EDC

    VerticalMount-ing

    7X EHD, FDB, FD,HFD, FDC, ED,EDH, EDC

    9X FCL, FB-P

    14X JDHJD, JDC

    14X DK, KDHKD, KDC

    18X LGE, LGH

    VisorSeriesTVSS

    6X 100-200kA

    8X 250-400kA

    1-Pole

    2-Pole

    1-Pole

    2-Pole

    1-Pole

    2-Pole

    3-Pole

    2- or 3-Pole

    “X”Units

    Box Height BoxCatalogueNumber

    TrimCatalogueNumber

    Inches mm

    250 – 400 Amperes

    23X31X40X

    486072

    1219.21524.01828.8

    EZB2048RCEZB2060RCEZB2072RC

    EZT2048S or FEZT2060S or FEZT2072S or F

    600 Amperes

    23X31X40X

    486072

    1219.21524.01828.8

    EZB2048RCEZB2060RCEZB2072RC

    EZTV2048S or FEZTV2060S or FEZTV2072S or F

    Figure 2-1.

    Table 2-15.

    2-10PanelboardsPow-R-Line C Panelboards

    PRL3a

  • 8/17/2019 Catalogo-panel Electrico Ch

    11/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Type PRL4

    Type PRL4B Circuit Breaker Panelboard 

    Product Description

    � 600V AC maximum (250V DC).

    � 3-phase 4-wire, 3-phase 3-wire,1-phase 3-wire, 1-phase 2-wire.

    � PRL4B circuit breaker panelboard.

    � PRL4F fusible switch panelboard.

    � 1200 ampere maximum mains.

    � 1200 ampere maximum branchdevices.

    � Bolt-on branch devices.

    � Factory assembled.

    Standards and Certifications

    � CSA C22.2 No.29

    � Federal Specification W-P-115c.

    Options and Accessories

    � Refer to Page 2-29.

    Layout and Sizing

    � PRL4B — R efer to Pages 2-16.through  2-18.

    � PRL4F — R efer to Pages 2-19.through 2-21.

    Type PRL4F Fusible Panelboard 

    Application Description

    � Power distribution panelboard.

    � Fully rated or series rated.

    � Interrupting ratings up to 200 kA sym-metrical.

    Suitable for use as Service EntranceEquipment, when specified onthe order.

    Pow-R-Line 4 Catalogue Code

    P4 B 4 A 4 - 27 KD 400

    Panelboard Type L - Main Lugs Only

    B - Bottom MainBreaker

    T - Top Main Breaker

    S - Main Switch

    1 - 1phase, 3 wire

    3 - 3phase, 3 wire

    4 - 3phase, 4 wire

    A - Aluminum

    C - Copper

    1 - 100 amperes

    2 - 225 amperes

    4 - 400 amperes

    6 - 600 amperes

    8 - 800 amperes

    12 - 1200 amperes

    -

    -

    -

    Feeder Breaker

    X-Space

    Main

    Breaker

    (if selected)

    Breaker

    Trip

    Rating

    2PanelboardsPow-R-Line C Panelboards

    PRL4

  • 8/17/2019 Catalogo-panel Electrico Ch

    12/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Product Selection

    Table 1-22. Base Configuration — PRL4 Main Lugs and Main Breakers

    � 100% rated breaker. Requires copper bus. Breaker only available in 3-pole frame. Requires 44-inch (1117.6 mm) wide box.

    Table 1-23. Base Configuration — PRL4 Main Fusible Switches

    Fuses not included. Specify required fuse clips on all switches. Class J Fuse provisions are applicable only to 600 volt units. When required, use price and dimensions of 600 volt units for all voltages 600 and below.

      No DC rating on 600, 800 and 1200 ampere switches .

    AmpereRating

    Interrupting Rating (kA Symmetrical) BreakerType

    240V AC 480V AC 600V AC 250V DC

    Main Lug Only250  400  600  8001200

    —————

    —————

    —————

    —————

    —————

    Main Breaker

    250  250  250  250

      65100200200

      35  65100200

      18  25  35—

    102222—

    JDHJDJDCLCL

      400  400  400  400  400  400  400

      400

      65  65  65100100200200

    200

    —  35  35  65  65100200

    200

    —  25  25  35  35  65—

    200

    1010—22—22—

    DKKDCKD �

    HKDCHKD

     

    KDCLCL

    LA-P  600  600  600  600  600  600  600  600  600

      65100200  65  65100100200200

      35  65100  35  35  65  65100100

      18  35  65  25  25  35  35  50  50

    1042—22—25—25—

    LGELGHLGULDCLD �

    HLDCHLD

     

    LDCCLDC �

      800  800  800  800  800

      65100  65100200

      50  65  50  65200

      25  35  25  35200

    2225———

    MDLHMDLCMDL

     

    CHMDL �

    NB-P

      800  800  800  800

      800  800

      65100200  65

    100200

      50  65100  50

      65100

      25  35  50  25

      35  50

    ————

    ——

    NDHNDNDCCND �

    CHND 

    CNDC 

    120012001200120012001200

      65100200  65100200

      50  65100  50  65100

      25  35  65  25  35  65

    ——————

    NDHNDNDCCND �

    CHND 

    CNDC 

    AmpereRating

    Interrupting Rating (kA Symmetrical)

    240V AC 480V AC / 600V AC Device Type

    Main Fusible Switch 240V AC, 250V DC

      200  400  600

      800

    1200

    SeeTable 2-20 FDPBFDPWFDPWFDPWFDPW

    Main Fusible Switch 600V AC

      200  400  600

      800

    1200

    SeeTable 2-20 FDPBFDPWFDPWFDPWFDPW

    Table 2-16.

    Table 2-17.

    2-12PanelboardsPow-R-Line C Panelboards

    PRL4

  • 8/17/2019 Catalogo-panel Electrico Ch

    13/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Table 1-24. Branch Devices — PRL4

    AmpereRating

    Interrupting Rating (kA Symmetrical) BreakerType240V AC 480V AC 600V AC 250V DC

     15 – 30 15 – 60 15 – 60

     70 – 100 70 – 100 15 – 50 

      10

      10 

      10

      10 

      10  10 

    ———

    ———

    ———

    ———

    ———

    ———

    DNBA (Twin)BABBAB-H

    BABBAB-HQBGF

      15 – 60  15 – 60  70 – 100  70 – 100  15 – 30

      22 

      22  22

     

      22  22

     

    —————

    —————

    —————

    QBHWQBHW-HQBHWQBHW-HQBHGF

      15 – 60  70 – 100  15 – 60  70 – 100

      65 

      65 

      65

      65

      14 

      14 

      14

      14

    ——10

    10 

    14141414

    GHB 

    GHB 

    GBH 

    GBH

      15 – 60  70 – 100  15 – 60  70 – 100110 – 150

      18 

      18 

      18  18  18

      14 

      14 

      14  14  14

    ——141414

    1010101010

    EHDEHDFDBFDBFDB

      15 – 60

      70 – 100110 – 225  15 – 60  70 – 100110 – 225

      65 

      65 

      65

     

    100 

    100 

    100 

      35 

      35 

      35

     

    65 

      65 

      65 

    18

    1818252525

    10

    1010222222

    FD

    FDFDHFDHFDHFD

      15 – 60  70 – 100110 – 225  15 – 100

    200200200200

    100100100150

    353535—

    222222—

    FDCFDCFDCFCL

    100 – 225100 – 225100 – 225

      65100200

    ———

    ———

    ———

    EDEDHEDC

    100-225100-225100-225100-225

    65656565

    35353535

    18181818

    ————

    FDE322533 LS�

    FDE322532 LSI�

    FDE322535 LSG�

    FDE322536 LSIG�

    60-15060-15060-15060-150

    65656565

    35353535

    18181818

    ————

    FDE316033 LS�

    FDE316032 LSI�

    FDE316035 LSG�

    FDE316036 LSIG�

    15-8015-8015-8015-80

    65656565

    35353535

    18181818

    ————

    FDE308033 LS�

    FDE308032 LSI�

    FDE308035 LSG�

    FDE308036 LSIG�

    100-225100-225100-225100-225

    100100100100

    65656565

    25252525

    ————

    HFDE322533 LS�

    HFDE322532 LSI�

    HFDE322535 LSG�

    HFDE322536 LSIG�

    60-15060-15060-15060-150

    100100100100

    65656565

    25252525

    ————

    HFDE316033�

    HFDE316032�

    HFDE316035�

    HFDE316036�

    15-8015-8015-80

    15-80

    100100100

    100

    656565

    65

    252525

    25

    ———

    HFDE308033�

    HFDE308032�

    HFDE308035�

    HFDE308036�Ground available in PRL4 panels only.

    Ammeter DigiView DigiView Ammeter (PRL4 only)

    Table 2-18

    � For use on 3ph, 3w or 3ph, 4w only. 50 ampere devices are available as 2-pole only. 1-pole breakers rated 120V AC. 2-pole breakers rated 120/240V AC. 1-pole breakers rated 277V AC. At 480V, must be used on 480Y/277V grounded wye systems only. AIC rating for 2- and 3-pole breakers only. 100% rated breaker. Requires copper bus. Not available in Type 12, 4 and 4X enclosures. Breaker only available in 3-pole frame.� Available in single branch mounting only. 1-pole breakers rated at 347V AC. At 600V, must be used on 600Y/347V grounded wye systems only.

    2PanelboardsPow-R-Line C Panelboards

    PRL4

  • 8/17/2019 Catalogo-panel Electrico Ch

    14/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Table 1-25. Branch Devices — PRL4 (Continued)

    AmpereRating

    Interrupting Rating (kA Symmetrical) DeviceType240V AC 480V AC 600V AC 250V DC

      70 – 225  250  70 – 225

      250  70 – 225  250

      65  65100

    100200200

      35  35  65

      65100100

    181825

    253535

    101022

    222222

    JDJDHJD

    HJDJDCJDC

      125 – 250 200 200 — — LCL

      250 – 400  100 – 400  100 – 400  100 – 400  100 – 400  100 – 400

      65  65  65100100200

    —  35  35  65  65100

    —2525353565

    1010—22—22

    DKKDCKD �

    HKDCHKD

     

    KDC

      200 – 400 200 200 — — LCL

      300 – 600  300 – 600  300 – 600

      65100200

      35  65100

    183565

    1042—

    LGELGHLGU

      300 – 600  300 – 600

      65  65

      35  35

    2525

    22—

    LDCLD

     

      300 – 600

      300 – 600  300 – 600  300 – 600

    100

    100200200

      65

      65100100

    35

    355050

    25

    —2525

    HLD

    CHLD 

    LDCCLDC

      400 – 800  400 – 800  400 – 800  400 – 800

      65100  65100

      50  65  50  65

    25352535

    2225——

    MDLHMDLCMDL

     

    CHMDL 

      400 – 800  400 – 800  400 – 800  400 – 800  400 – 800  400 – 800

      65100200  65100200

      50  65100  50  65100

      25  35  65  25  35  65

    ——————

    NDHNDNDCCND

     

    CHND 

    CNDC �

      600 – 1200  600 – 1200  600 – 1200  600 – 1200  600 – 1200

      600 – 1200

      65100200  65100

    200

      50  65100  50  65

    100

      25  35  65  25  35

      65

    —————

    NDHNDNDCCND

     

    CHND �

    CNDC�

    Integrally Fused, Current Limiting Circuit Breaker

      15 – 100  125 – 225  250 – 400  400 – 600  700 – 800

    200200200200200

    200200200200200

    200200200200200

    FB-PLA-PLA-PNB-PNB-P

    Table 2-18

    � For use on 3ph, 3w or 3ph, 4w only. 50 ampere devices are available as 2-pole only. 1-pole breakers rated 120V AC. 2-pole breakers rated 120/240V AC. 1-pole breakers rated 277V AC. At 480V, must be used on 480Y/277V grounded wye systems only. AIC rating for 2- and 3-pole breakers only. 100% rated breaker. Requires copper bus. Not available in Type 12, 4 and 4X enclosures. Breaker only available in 3-pole frame.� Available in single branch mounting only. 1-pole breakers rated at 347V AC. At 600V, must be used on 600Y/347V grounded wye systems only.

    2-14PanelboardsPow-R-Line C Panelboards

    PRL4

  • 8/17/2019 Catalogo-panel Electrico Ch

    15/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Table 1-25.

    Table 1-26.

    Table 1-26.Table 1-26. FDPW and FDPB Switch Ratings,240 or 600V AC

    � 100% rated breaker. Requires 44-inch (1117.6 mm) wide box. 100,000 AIC based on NEMA test procedure. Fuses not included. Specify required fuse clips on all switches. For T fuse clips, specify as an option (T fuse clips not available for

    200/200 twin switches).

    When branches of a twin unit are of different ampere ratings, as a 30 – 60 twin unit and layout as a 60 – 60 twin unit;when a 60 – 100 twin unit layout as a 100 – 100 twin unit. No DC rating on 600, 800 and 1200 ampere switches. Twin 200 ampere switches are not available with Class R fuse clips at 600 volts. No DC rating on 600, 800 and 1200 ampere switches. Class J fuse provisions are applicable to 600 volt units. When required, use price and dimensions of 600 volt units for all voltages 600 volts and below.� Twin 200 ampere switches are not available with Class R fuse clips at 600 volts. When shunt trip is required, 400 – 600 ampere switches used with Class R fuses are rated 100,000 AIC.

     Fusible Switches 240V AC, 250V DC

      30/30 

      60/60 

      100/100 

      200/200  200

    SeeTable 2-20 FDPW-TwinFDPW-TwinFDPW-TwinFDPB-TwinFDPB-Single

      400  600

     

      800 

    1200 

    SeeTable 2-20 FDPW-SingleFDPW-SingleFDPW-SingleFDPW-Single

    Fusible Switches 600V AC

      30/30 

      60/60 

      100/100 

      200/200 

      200

    SeeTable 2-20 FDPW-TwinFDPW-TwinFDPW-TwinFDPB-TwinFDPB-Single

      400  600

     

      800 

    1200 

    SeeTable 2-20 FDPW-SingleFDPW-SingleFDPW-SingleFDPW-Single

    AmpereRating

    FuseClassUsed

    Short CircuitRatings(Sym. Amperes)

    30 – 100200 Single200 Twin400, 600 

    800, 1200 

    R, J 

    R, J 

    R �, J , TR , J, TL

    200,000200,000200,000200,000200,000

    Table 2-19.

    Table 2-20.

    2PanelboardsPow-R-Line C Panelboards

  • 8/17/2019 Catalogo-panel Electrico Ch

    16/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Layout and Sizing — PRL4B

    Main Lug (MLO), Main Breaker, Neutral, Through-Feed (TFL) andSub-Feed Lug (SFL) “X” Space Requirements. (For other config-urations not shown, refer to Eaton.)

    * = Space available for branch devices. For device sizing,see Figure 2-4 on Page 2-18..

    • = Blank means no bus under cover, to meet cablebending space requirements.

    Figure 1-5. PRL4B Layout� Sub-Feed lugs are available 250 – 600 amperes. For 600 ampere use 1200 ampere space. 750kcmil lugs available on some Main Breaker arrangements.

    Consult Eaton.

    *

    10X

    7X Through-Feed Lugs

    *

    10XNN

    MLO, SFL MLO, TFL

    3Ph 4W, 3Ph 3W

    250A�, 400A�,600A�, 800A

    Standard Main Lug, Through-Feed and Sub-Feed Lugs�

    (500 kcmil Maximum)Main Breaker with Neutral (when required)(500 kcmil Maximum)�

    *

    7X

    *

    NN

    3Ph 4W,

    3Ph 3W

    250A, 400A,600A, 800A

    *

    12X

    7X Through-Feed Lugs

    *

    12XNN

    MLO MLO, TFL

    3Ph 4W, 3Ph 3W

    1200A38-inch(965.2 mm)MinimumWidth

    Main Breaker

    Main Breaker

    *

    3Ph 3W3Ph 4W

    800A Vertically Mtd. MDL Main Breaker only in 24-inch (609.6 mm) wide box.Available with 38X and 50X Panel Height only.

    16X

    Blank2X

    *

    7X

    *

    N

    3Ph 3W

    1200A38-inch(965.2 mm)MinimumWidth

    Main Breaker

    3Ph 4W

    Blank2X Blank2X

    Blank2X

    Main Breaker

    *

    9X Through-Feed Lugs

    *

    20XNN

    MLO, SFL MLO, TFL

    3Ph 4W

    250A�, 400A�,600A�, 800A

    Optional Main Lugs, Through-Feed and Sub-Feed Lugs� (750 kcmil Maximum)

    *

    20X

    11X Through-Feed Lugs

    *

    20XNN

    MLO MLO, TFL

    3Ph 4W

    1200A38-inch(965.2 mm)MinimumWidth Blank5X

    *

    9X Through-Feed Lugs

    *

    13X

    3Ph 3W

    400A, 600A,800A

    *

    15X

    11X Through-Feed Lugs

    *

    15X

    1200A38-inch(965.2 mm)MinimumWidth Blank5X

    Blank

    20X

    Blank

    13X

    3X

    3Ph 3W

    3X

    Figure 2-2.

    2-16PanelboardsPow-R-Line C Panelboards

    PRL4

  • 8/17/2019 Catalogo-panel Electrico Ch

    17/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Panel Layout and Dimensions

    To determine the dimensions of a givenpanelboard enclosure, make a layoutsketch by fitting together the main,branch and lug modules according to theappropriate tables in the layout guide.Assign “X” units to each module asshown and obtain a total “X” number.

    The height of the enclosure is related tothe total “X” units in the layout as showninTable 2-21. Three standard box heightsare available to accommodate any and alllayout arrangements. “X” unit totals thatdo not exactly match those in Table 2-21 must be rounded off to the next higheststandard (26X, 38X, 50X).

    If a calculated “X” total for a panelexceeds 50X, the panel must be split intotwo or more separate sections with “X”space for through-feed lugs figured in forall but one section. If a neutral is re-quired, a separate neutral bar and appro-priate “X” space must be included ineach section.

    Layout Example

    � 1 – PRL4B panelboard, 600Y/347V,3-phase 4-wire 25 kA, 800 amperes,main lug, consisting of:

    12 – 20A/1P HFD

    2 – 250A/3P HJD

    1 – 400A/3P KD

    Reference Figure 1-6

    1. From layout guide, total “X” heightof panel = 26X, (which is a designstandard and no rounding off is nec-essary).

    2. FromTable 1-27, enclosureheight for 26X panel = 57 inches(1447.8 mm).

    3. Width = 24 inches (609.6 mm) —directly from layout guide.

    4. Enclosure depth = 11-5/16 inches(287.0 mm) — standard for all PRL4

    panelboards.

    Figure 1-6. PRL4B Layout Example

    Table 1-26. Box Dimensions — PRL4B

    � Box depth is 10.4 inches (264.2 mm), cover adds .9 inches (22.9 mm) to depth.

    Note: 800 ampere maximum bus size in 24-inch (609.6 mm) wide box. Flush trimsnot available on PRL4B panels.

    Top and Bottom Gutters

    10-5/8-inch (269.9 mm) minimum.

    Side Gutters — Minimum

    24-inch (609.6 mm) wide box — 5-inch (127.0 mm).38-inch (914.4 mm) wide box — 7-inch (177.8 mm).44-inch (1117.6 mm) wide box — 8-inch (203.2 mm).

    20A/1P 20A/1P 1X

    20A/1P 20A/1P 1X

    20A/1P 20A/1P 1X

    20A/1P 20A/1P 1X

    20A/1P 20A/1P 1X

    20A/1P 20A/1P 1X

    250A/3P 3X

    250A/3P 3X

    400A/3P 4X

    Main 800ALugs

    Neutral

    10X

    Total = 26X

    “X”Units

    CatalogueNumber

    Inches mm

    Height Width Depth � Height Width Depth �

    26X38X50X

    BX2457BX2473BX2490

    5773-1/290

    242424

    11-5/1611-5/1611-5/16

    1447.81866.92286.0

      609.6  609.6  609.6

    287.0287.0287.0

    38X50X

    BX3873BX3890

    73-1/290

    3838

    11-5/1611-5/16

    1866.92286.0

      965.2  965.2

    287.0287.0

    38X50X

    BX4473BX4490

    73-1/290

    4444

    11-5/1611-5/16

    1866.92286.0

    1117.61117.6

    287.0287.0

    Table 2-21.

    Figure 2-3. .

    2PanelboardsPow-R-Line C Panelboards

    PRL4

  • 8/17/2019 Catalogo-panel Electrico Ch

    18/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Figure 1-7. Layout for Branch and Horizontally Mounted Main Devices — PRL4B� BAB and QBHW breakers with shunt trips require one additional pole space, i.e., 1-pole is 2-pole size, 2-pole is 3-pole size, and 3-pole is 4-pole size.

    If panel contains only BAB or QBHW branch breakers, use a PRL1a panelboard. GHB and GBH breakers cannot be mixed on same subchassis as BAB, QBHW. If panel contains only GHB

     and GBH branch breakers, use a PRL2a panelboard. When only one single-pole breaker of the group is required on either side of chassis, the single-pole breaker space required changes from 1X to 2X. Minimum 38-inch (965.2 mm) wide box is required if optional #6 – 300 kcmil lug is required.

    Breaker To Fusible Transition, All Widths

    3X

    3X

    6X

    6X

    4X

    6X

    1X

    12X

    20X

    1X

    2X

    3X

    2X

    6X

    3X

    3X

    4X

    Filler

    Sub Panel

    400 Amp. Maximum Bus Rating

    1P 1P

    2P 2P

    3P 3P

    2P 2P

    3P 3P

    2 or 3P

    2 or 3P

    2 or 3P   L  o  a   d

    2 or 3P 2 or 3P

    2 or 3P 2 or 3P

    2 or 3P

    2 or 3P

    2 or 3P 2 or 3P

    2 or 3P

    EHD,FDB, FD,HFD, FDCFDE, HFDE(3P)

    18Poles

    100 AmpMax.

    BAB

    QBHW

    GHB, GBH

    DK, KD, HKD,KDC

    ED, EDH, EDC

    225 AmpMax.

    225 AmpMax.

    JD, HJD, JDC250 Amp

    Max.

    400 Amp Max. DK, KD, HKD, KDC, CKD, CHKD

    600 AmpMax.

    LD, HLD, CLD, CHLD, LDC

    100 AmpMax.

    FCL, FB-P

    250 AmpMax.

    JD, HJD, JDC

    400 AmpMax.

    1200 AmpMax. 

    LCL, LA-P

    MDL, HMDL,

    CMDL, CHMDL

    800 Amp

    Max. 

    ND, HND, NDC

    400 AmpMax.

    800 AmpMax. NB-P

       4   4  -   I  n  c   h   (   1   1   1   7 .   6  m  m   )   W   i   d  e   B  o  x

       2   4  -   I  n  c   h   (   6   0   9 .   6  m  m   )   W   i   d  e   B  o  x

       3   8  -   I  n  c   h   (   9   6   5 .   2  m  m   )   W   i   d  e   B  o  x

    1200 AmpMax. 

    CND, CHND, CNDC

    42

    Poles

    4X400 AmpMax.

    DK, KD, HKD, KDC,CKD, CHKD2 or 3P 2 or 3P

    600 Amp Max.LGE, LGH, LGU

    � Breaker may be used as main.

    Figure 2-4.

    2-18PanelboardsPow-R-Line C Panelboards

    PRL4

  • 8/17/2019 Catalogo-panel Electrico Ch

    19/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Layout and Sizing — PRL4F

    Main Lug (MLO), Main Switch, Neutral, Through-Feed (TFL) andSub-Feed Lug (SFL) “X” Space Requirements. (For other config-urations not shown, refer to Eaton.)

    * = Space available for branch devices. For device sizing,see Figure 2-7 on Page 2-21.

    • = Blank means no bus under cover, to meet cablebending space requirements.

    Figure 1-8. PRL4F Layout� Sub-Feed lugs are available 250 – 600 amperes, for 600 ampere use 1200 ampere “A” space. 800 ampere and 1200 ampere mains available only in vertical mounting.

    *

    10X

    7X Through-Feed Lugs

    *

    10XNN

    MLO, SFL MLO, TFL

    3Ph 4W, 3Ph 3W

    250A�, 400A�,600A�, 800A

    Standard Main Lug, Through-Feed and Sub-Feed Lugs�

    (500 kcmil Maximum)Main Switch with Neutral (when required)(500 kcmil Maximum)

    *

    7X

    *

    N

    3Ph 4W,3Ph 3W

    200A, 400A,600A

    *

    12X

    7X

    *

    12XNN

    MLO MLO, TFL

    3Ph 4W, 3Ph 3W

    1200A

    Main Switch

    Main Switch

    *

    3Ph 3W3Ph 4W

    400A and 600A Vertically Mounted Main Switch

    21X

    Blank Through-FeedLugs2X

    800A,1200A

    *

    9X Through-Feed Lugs

    *

    20XNN

    MLO, SFL MLO, TFL

    3Ph 4W

    250A�, 400A�,600A�, 800A

    Optional Main Lugs, Through-Feed and Sub-Feed Lugs� (750 kcmil Maximum)

    *

    20X

    11X Through-Feed Lugs

    *

    20XNN

    MLO MLO, TFL

    3Ph 4W

    1200A

    Blank5X

    *

    9X Through-Feed Lugs

    *

    13X

    3Ph 3W

    400A,600A, 800A

    *

    15X

    11X Through-Feed Lugs

    *

    15X

    1200A

    Blank5X

    Blank

    20X

    Blank

    13X

    3X

    3Ph 3W

    N7X

    *

    3Ph 4W

    1200A 26X

    N7X

    800A & 1200A Vertically MountedMain Switch

    38-inch (965.2 mm) or44-inch (1117.6 mm)Wide Box

    3X

    25X - 800A (750 kcmil max.)

    21X - 800A (250 kcmil max.)

    Figure 2-5.

    2PanelboardsPow-R-Line C Panelboards

    PRL4

  • 8/17/2019 Catalogo-panel Electrico Ch

    20/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Panel Layout and Dimensions

    To determine the dimensions of a giv enpanelboard enclosure, mak e a layout sketchby fitting together the main, branc h and lugmodules according to the appropriatetables in the layout guide. Assign “X” unitsto each module as sho wn and obt ain a total“X” number.

    The height of the enclosure is related tothe total “X” units in the layout as showninTable 2-22. Two standard fusible boxheights are available to accommodateany and all layout arrangements. “X” unittotals that do not exactly match those inTable 2-22 must be rounded off to thenext higher standard (50X).

    If a calculated “X” total for a panelexceeds 50X, the panel must be split intotwo or more separate sections with “X”space for through-feed lugs figured in forall but one section. If a neutral is re-

    quired, a separate neutral bar and appro-priate “X” space must be included ineach section.

    Layout Example

    � PRL4F, 3-phase 4-wire, 208Y/120Vcomplete with 400 ampere mainswitch and the following branches:

    1 – 200A/3P

    2 – 100A/3P

    2 – 30A/3P

    Panel to have short circuit rating of100,000 amperes symmetrical.

    Reference Figure 2-6

    1. From layout guide, total “X” heightof panel = 43X.

    2. Rounded off to next higherstandard = 50X.

    3. FromTable 2-22, enclosure heightfor 50X panel = 90 inches(2286.0 mm).

    4. Width = 38 inches (965.2 mm).

    5. Enclosure depth is standard for allPRL4 panelboards = 11-5/16 inches(287.0 mm).

    Figure 1-9. Type PRL4F Layout Example

    Note: In the above example if a horizontallymounted 400 ampere main switch were used,the enclosure size would be73-1/2 H x 44 W x 11-5/16 D (1866.9 mm H x1117.6 mm W x 287.0 mm D)

    Table 1-27. Box Dimensions — PRL4F

    � Box depth is 10.4-inch (264.2 mm) cover adds .9-inch (22.8 mm) to depth.

    Note: Flush trims not available on PRL4F panels.

    Top and Bottom Gutters

    10-5/8 inches (269.9 mm) minimum.

    Side Gutters — Minimum

    � 38-inch (965 mm) wide box:

    8-inch (203.2 mm) — 200 ampere maximum

    8-inch (152.4 mm) 400 — 1200 ampere maximum

    � 44-inch (1117.6 mm) wide box:

    10-inch (254.0 mm) 200 — ampere maximum

    7-inch (203.2 mm) 400 — 1200 ampere

    400A Neutral 7X

    30A/3P 30A/3P 4X

    100A/3P 100A/3P 5X

    200A/3P 6X

    400A 3-PoleMain Switch

    (Vert. Mounted)

    21X

    Total = 43X

    “X”Units

    CatalogueNumber

    Inches mm

    Height Width Depth � Height Width Depth �

    38X50X

    BX3873BX3890

    73-1/290

    3838

    11-5/1611-5/16

    1866.92286.0

      965.2  965.2

    287.0287.0

    38X50X

    BX4473BX4490

    73-1/290

    4444

    11-5/1611-5/16

    1866.92286.0

    1117.61117.6

    287.0287.0

    Figure 2-6.

    Table 2-22.

    2-20PanelboardsPow-R-Line C Panelboards

    PRL4

  • 8/17/2019 Catalogo-panel Electrico Ch

    21/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Figure 1-10. Branch and Horizontally Mounted Main Device Layout — PRL4F

    Fusible switch may be used as horizontal main.

    � 400 and 600 ampere horizontally mounted feeder switches in 38-inch (965 mm) or 44-inch (1117.6 mm) wide box. 400 and 600 ampere horizon-tally mounted main switches only in 44-inch (1117.6 mm) wide box. For vertically mounted main see Page 2-19  for sizing.

    Note: See Page 2-19 for MLO or Neutral and Vertically Mounted Main space requirements.

    1X

    4X

    4X

    6X

    5X

    9X

    15X

    400A

    Branch Switch

    200AMain or Branch Switch

    Fusible to Breaker TransitionRequires 1X Filler

    30A 30A

    60A 60A

    100A 100A

       4   4  -   i  n  c   h   (   1   1   1   7 .   6  m  m   )   W   i   d  e   B  o  x

       3   8  -   i  n  c   h   (   9   6   5 .   2  m  m   )   W   i   d  e   B  o  x

    600ABranch Switch

    200A 200A

    400AMain or Branch

    600AMain or Branch

    800ABranch

    1200ABranch

    9X

    11X

    11X

    11X

    6X

    Figure 2-7.

    2PanelboardsPow-R-Line C Panelboards

    PRL4

  • 8/17/2019 Catalogo-panel Electrico Ch

    22/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Product Description

    � 240V AC maximum.

    � 3-phase 4-wire, 3-phase 3-wire,1-phase 3-wire, 1-phase 2-wire.

    � 225 ampere maximum mains.

    � 100 ampere maximum branch break-ers.

    � Bolt-on branch breakers.

    � Factory assembled.

    Type PRL1a-LX, Column Type 

    Application Description

    � Lighting and appliance branchpanelboard.

    � Column mounting width.

    � Fully rated or series rated.

    � Interrupting ratings up to 200 kA sym-metrical.

    Standards and Certification

    � CSA C22.2 No. 29

    � Federal Specification W-P-115c.

    Options and Accessories

    � Pullbox and trough extensions.

    � See also Page 2-29.

    Layout and Sizing

    � Refer to Page 2-23.

    Product Selection

    Table 1-28. PRL1a-LX

    Table 1-29. Branch Circuit Breakers — PRL1a-LX

    � 1-pole breakers are rated 120V AC maximum. 240 volt breakers must be used on 3-phase, 3-

    wire, 240 volt delta systems or on the high leg

    of a midpoint delta grounded system. 50 ampere devices are available as 2-pole only.

    GFCI for 5 mA personnel protection. GFP for 30 mA equipment protection. Arc fault circuit breaker.

    Arc fault circuit breaker with GFCI. Solenoid operated breaker.

    Table 1-30. Pull Box With Extension Trough

    Includes pull box with trough extension.For additional trough extensions.

    Neutral Bars

    When Column Type panels are furnishedwith trough extensions and pull bo x, theneutral bar will be placed in the pull bo xunless other wise specified.

    When troughs and pull bo x are not fur-nished, the neutral bar will be located onthe panel at the same end as the main.

    Table 1-31. Additional Trough Extensions

    Width and depth are the same as thepanelboard.

    AmpereRating

    InterruptingRating (kA Sym.)240V AC

    BreakerType

    Main Lug Only

    100225

    ——

    ——

    Main Breaker

    100100100100100100100

      10  18  22  65  65100100

    BABEHDQBHWEDFDEDHHFD

    225225

      65100

    EDEDH

    AmpereRating

    InterruptingRating (kA Sym.)240V AC�

    BreakerType

      15 – 60  70  80 – 100  15 – 50 

      15 – 50 

      15 – 20  15 – 20  15 – 30  15 – 30

      10  10  10  10  10  10  10  10  10

    BABBABBABQBGF 

    QBGFEP 

    QBAF

    QBAG

    BABR

    BABRS

      15 – 60  70  80 – 100  15 – 30  15 – 30

      22  22  22  22  22

    QBHWQBHWQBHWQBHGF 

    QBHGFEP 

    Description CatalogueNumber

    Pullbox with 36" TroughPullbox with 48" TroughPullbox with 60" TroughPullbox with 72" TroughPullbox with 84" Trough

    XCTXB036XCTXB048XCTXB060XCTXB072XCTXB084

    Length CatalogueNumberInches mm

    3648607284

      914.41219.21524.01828.82133.6

    CTXB036CTXB048CTXB060CTXB072CTXB084

    Table 2-26.Table 2-25.

    Table 2-24

    Table 2-23

    2-22PanelboardsColumn Type

    Type PRL1a-LX

  • 8/17/2019 Catalogo-panel Electrico Ch

    23/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Box Sizing and Selection

    Assembled Circuit Breaker Panelboards

    Box size, box and trim catalogue num-bers for standard Column Type panel-boards listed are available fromTables 2-28 and 2-29.

    Instructions

    1. Using description of the requiredpanelboard, select the rating andtype of main required.

    a. 100 ampere panelboards —Table2-28.

    b. 225 ampere panelboards —Table2-29.

    2. Count the total number of branch cir-cuit poles, including provisions,required in the panelboard. Do notcount main breaker poles. Convert 2-or 3-pole branch breaker to single

    poles, i.e., 3-pole breaker, count as 3poles. Determine sub-feed breakeror through-feed lug requirements.

    3. Select the panelboard main ampererating fromTables 2-28 or 2-29.

    4. Panelboard Type from first column,main breaker Frame and Designa-tion, if applicable from second col-umn, and sub-feed breaker Frameand Designation, if applicable, fromthe third column.

    5. From Step #2, determine the num-ber of branch circuits in Column 4.

    6. Read box size, box and trim

    catalogue numbers across columnsto the right. All panels are surfacemounted.

    Cabinets

    Boxes and trims are code-gauge steel,ASA-61 light gray painted finish.

    Boxes are furnished without knoc kouts.Standard depth is 6 inc hes (152.4 mm).Standard width is 8-5/8 inc hes

    (219.1 mm).

    Top and Bottom Gutters

    4-1/2 inches (114.3 mm) minimum.

    Left Side Gutter

    4-3/8 inches (111.2 mm) minimum.

    Pull Box

    Pull box is furnished without knock-outs. Standard dimensions

    Table 2-27. Pull Box Dimensions

    Figure 2-8. PRL1a-LX Trough Extension,Dimensions in Inches (mm)

    Height Width Depth

    Inches mm Inches mm Inches mm

    12 304.8 16 406.4 6 152.4

    AdditionalExtensions

    (If Required)

    HBox

    Height

    12(304.8)

    6(152.4) 16

    (406.4)

    8-5/8(219.1)

    6(152.4)

    2PanelboardsColumn Type

    Type PRL1a-LX

  • 8/17/2019 Catalogo-panel Electrico Ch

    24/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Box Sizing and Selection (Continued)

    Table 1-32. 100 Ampere Maximum PRL1a-LX Column Type Panelboard Sizing

    � Add suffix B to trim catalogue number for bottom fed panelboards (i.e., LTC969SB).

    Table 1-33. 225 Ampere Maximum PRL1a-LX Column Type Panelboard Sizing

    Add suffix B to trim catalogue number for bottom fed panelboards (i.e., LTC969SB).

    PanelboardTypes

    Main BreakerTypesMounting :(H) = Horizontal

    (V) = Vertical

    Sub-FeedBreaker TypesVerticalMounting

    MaximumNumberof BranchCircuits

    IncludingProvisions

    Box Dimensions Inches (mm) BoxCatalogueNumber

    TrimCatalogueNumber �

    Height Width Depth

    Main Breaker BAB, QBHW(H)

    ——

    2739

    69 (1752.6)81 (2057.4)

    8-5/8 (219.2)8-5/8 (219.2)

    6 (152.4)6 (152.4)

    YSC969YSC981

    LTC969SLTC981S

    Main Lugs or Main Breaker EHD, EDFD, HFD(V)

    ——

    3042

    69 (1752.6)81 (2057.4)

    8-5/8 (219.2)8-5/8 (219.2)

    6 (152.4)6 (152.4)

    YSC969YSC981

    LTC969SLTC981S

    Main Lugs or Main Breakerwith 100A Through-Feed Lugsor Sub-Feed Breaker

    EHD, EDFDHFD(V)

    EHD, FD, HFD 3042

    78 (1981.2)90 (2286.0)

    8-5/8 (219.2)8-5/8 (219.2)

    6 (152.4)6 (152.4)

    YSC978YSC990

    LTC978SLTC990S

    PanelboardTypes

    Main BreakerTypes

    Sub-FeedBreaker Types

    MaximumNumberof Branch

    CircuitsIncludingProvisions

    Box Dimensions Inches BoxCatalogueNumber

    TrimCatalogueNumber Vertical Mounting Height Width Depth

    Main Lugs or Main Breaker ED, EDH ——

    3042

    69 (1752.6)81 (2057.4)

    8-5/8 (219.2)8-5/8 (219.2)

    6 (152.4)6 (152.4)

    YSC969YSC981

    LTC969SLTC981S

    Main Lugs or Main Breakerwith 225A Through-Feed Lugsor Sub-Feed Breaker

    ED, EDH EHD, FD, HFD,ED, EDH

    3042

    78 (1981.2)90 (2286.0)

    8-5/8 (219.2)8-5/8 (219.2)

    6 (152.4)6 (152.4)

    YSC978YSC990

    LTC978SLTC990S

    Table 2-28.

    Table 2-29.

    2-24PanelboardsColumn Type

    Type PRL1a-LX

  • 8/17/2019 Catalogo-panel Electrico Ch

    25/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Product Description

    � 600Y/347V AC maximum (125V DC).

    � 3-phase 4-wire, 3-phase 3-wire,1-phase 3-wire, 1-phase 2-wire.

    � 225 ampere maximum mains.

    � 100 ampere maximum branch break-ers.

    � Bolt-on branch breakers.

    � Factory assembled.

    Type PRL2a-LX, Column Type 

    Application Description

    � Lighting and appliance branchpanelboard.

    � Column mounting width.

    � Fully rated or series rated.

    � Interrupting ratings up to 200 kA sym-metrical.

    Standards and Certifications

    � CSA C22.2 No.29

    � Federal Specification W-P-115c.

    Options and Accessories

    � Pullbox and trough extensions.

    � See also Page 2-29.

    Layout and Sizing

    � Refer to Page 2-26.

    Product Selection

    Table 1-34. Base Prices — PRL2a-LX

    � These system voltages apply to 240 volts.

    Table 1-35. Branch Circuit Breakers — PRL2a-LX

    Interrupting ratings in this column are applicable to 120V AC for 1-pole breakers. At 480V, must be used on 480Y/277V grounded wye systems only. Solenoid operated breaker. GFP for 30 mA equipment protection. Requires two pole spaces. At 600V, must be used on 600Y/347V grounded wye systems only.

    Table 1-36. Pull Box With Extension Trough

    Includes pull bo x with trough e xtension.

    For additional trough extensions, refer toTable 2-33 .

    Neutral Bars

    When Column Type panels are furnishedwith trough extensions and pull bo x, theneutral bar will be placed in the pull bo xunless other wise specified.

    When troughs and pull bo x are not fur-nished, the neutral bar will be located onthe panel at the same end as the main.

    Table 1-37. Additional Trough Extensions

    Width and depth are the same as the

    panelboard.

    AmpereRating

    Interrupting Rating (kA Symmetrical) BreakerType240V AC 600Y/347V AC 125/250V DC

    Main Lug Only

    100225

    ——

    ——

    ——

    ——

    Main Breaker

    100100

      65  18

      10  14

    1410

    GBHFDB

    100100100

      65100200

      18  25  35

    102222

    FDHFDFDC

    225225225225225

      65  18  65100200

     —  14  18  25  35

    —10102222

    EDFDBFDHFDFDC

    AmpereRating Interrupting Rating (kA Symmetrical ) BreakerType240V AC 480Y/277V AC 600Y/347V AC 125/250V DC

      15 – 20  15 – 60  70 – 100  15 – 30  15 – 60  70 – 100

      65  65  65  65  65  65

      14  14  14  14  14  14

    ————1010

    —1414——14

    GHQ

    GHB 

    GHB 

    GHBS 

    GBH

    GBH

      15 – 60 — 14 — — GHBGFEP 

    Description CatalogueNumber

    Pullbox with 36" TroughPullbox with 48" TroughPullbox with 60" TroughPullbox with 72" TroughPullbox with 84" Trough

    XCTXB036XCTXB048XCTXB060XCTXB072XCTXB084

    Length CatalogueNumberInches mm

    3648607284

      914.41219.21524.01828.82133.6

    CTXB036CTXB048CTXB060CTXB072CTXB084

    Table 2-31.

    Table 2-30.

    Table 2-33.Table 2-32.

    2PanelboardsColumn Type

    Type PRL2a-LX

  • 8/17/2019 Catalogo-panel Electrico Ch

    26/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Box Sizing and Selection

    Assembled Circuit Breaker Panelboards

    Box size, box and trim cataloguenumbers for standard column typepanelboards listed are available

    fromTables 2-35 and 2-36.Instructions

    1. Using description of the requiredpanelboard, select the rating andtype of main required.

    a. 100 ampere panelboards —Table2-35.

    b. 225 ampere panelboards —Table2-36.

    2. Count the total number of branch cir-cuit poles, including provisions, re-quired in the panelboard. Do notcount main breaker poles. Convert 2-or 3-pole branch breaker to single

    poles, i.e., 3-pole breaker, count as 3poles.

    Determine sub-feed breaker orthrough-feed lug requirements.

    3. Select the panelboard main ampererating fromTables 2-35 or 2-36.

    4. Panelboard Type from first column,main breaker Frame and Designa-tion, if applicable from second col-umn, and sub-feed breaker Frameand Designation, if applicable, fromthe third column.

    5. From Step #2, determine the num-ber of branch circuits in Column 4.

    6. Read box size, box and trimcatalogue numbers across columnsto the right. All panels are surfacemounted.

    Cabinets

    Boxes and trims are code-gauge gal-vonized steel.

    Boxes are furnished without knoc kouts.Standard depth is 6 inches (152.4 mm).Standard width is 8-5/8 inches

    (219.1 mm).

    Top and Bottom Gutters

    4-1/2 inches (114.3 mm) minimum.

    Left Side Gutter

    3-5/16 inches (84.2 mm) minimum.

    Pull Box

    Pull box is furnished without knoc kouts.Standard dimensions:

    Table 1-38. Pull Box Dimensions

    Figure 1-11. PRL2a-LX Trough Extension,

    Dimensions in Inches (mm)

    Height Width Depth

    Inches mm Inches mm Inches mm

    12 304.8 16 406.4 6 152.4

    AdditionalExtensions

    (If Required)

    HBox

    Height

    12(304.8)

    6(152.4) 16

    (406.4)

    8-5/8(219.1)

    6(152.4)

    Table 2-34.

    Figure 2-9.

    2-26PanelboardsColumn Type

    Type PRL2a-LX

  • 8/17/2019 Catalogo-panel Electrico Ch

    27/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Box Sizing and Selection (Continued)

    Table 1-39. 100 Ampere Maximum PRL2a-LX Column Type Panelboard Sizing

    � Add suffix B to tr im catalogue number for bottom fed panelboards (i.e., LTC969SB).

    Table 1-40. 225 Ampere Maximum PRL2a-LX Column Type Panelboard Sizing

    Add suffix B to tr im catalogue number for bottom fed panelboards (i.e., LTC969SB).

    PanelboardTypes

    Main BreakerTypesMounting:(H) = Horizontal

    (V) = Vertical

    Sub-FeedBreaker TypesVerticalMounting

    MaximumNumberof BranchCircuits

    IncludingProvisions

    Box Dimensions Inches BoxCatalogueNumber

    TrimCatalogueNumber �

    Height Width Depth

    Main Breaker GHB, GBH(H)

    ——

    2739

    69 (1752.6)81 (2057.7)

    8-5/8 (219.2)8-5/8 (219.2)

    6 (152.4)6 (152.4)

    YSC969YSC981

    LTC969SLTC981S

    Main Lugs or Main Breaker EHD, FDHFD, FDC(V)

    ——

    3042

    69 (1752.6)81 (2057.7)

    8-5/8 (219.2)8-5/8 (219.2)

    6 (152.4)6 (152.4)

    YSC969YSC981

    LTC969SLTC981S

    Main Lugs or Main Breakerwith 100A Through-Feed Lugsor Sub-Feed Breaker

    EHD, FDHFD, FDC(V)

    EHD, FD, HFD 3042

    78 (1981.2)90 (2286.0)

    8-5/8 (219.2)8-5/8 (219.2)

    6 (152.4)6 (152.4)

    YSC978YSC990

    LTC978SLTC990S

    PanelboardTypes

    Main BreakerTypes

    Sub-FeedBreaker Types

    MaximumNumberof BranchCircuitsIncludingProvisions

    Box Dimensions Inches BoxCatalogueNumber

    TrimCatalogueNumber Vertical Mounting Height Width Depth

    Main Lugs or Main Breaker ED, FDHFD, FDC

    ——

    3042

    69 (1752.6)81 (2057.7)

    8-5/8 (219.2)8-5/8 (219.2)

    6 (152.4)6 (152.4)

    YSC969YSC981

    LTC969SLTC981S

    Main Lugs or Main Breakerwith 225A Through-Feed Lugsor Sub-Feed Breaker

    ED, FDHFD, FDC

    EHD, FD, HFD,ED, EDH

    3042

    78 (1981.2)90 (2286.0)

    8-5/8 (219.2)8-5/8 (219.2)

    6 (152.4)6 (152.4)

    YSC978YSC990

    LTC978SLTC990S

    Table 2-35.

    Table 2-36.

    2PanelboardsColumn Type

    Type PRL2a-LX

  • 8/17/2019 Catalogo-panel Electrico Ch

    28/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Boxes and Trims Only — Type 1

    Table 1-41. Types PRL1a and PRL2a

    Table 1-42. Type PRL3a 100 – 400 Amperes

    Table 1-43. Type PRL4

    Box Dimensions Height Box Trim

    Inches mm CatalogueNumber

    CatalogueNumber

    20-inch W x 5-3/4-inch D(508.0 mm W x 146.1 mm D)

    3036

    42

    48

    54

    60

    72

    90

    762.0914.4

    1066.8

    1219.2

    1371.6

    1524.0

    1828.8

    2286.0

    EZB2030RCEZB2036RCEZB2042RCEZB2048RCEZB2054RCEZB2060RCEZB2072RCEZB2090RC

    EZT2030S or FEZT2036S or FEZT2042S or FEZT2048S or FEZT2054S or FEZT2060S or FEZT2072S or FEZT2090S or F

    Box Dimensions Height Box Trim

    Inches mm CatalogueNumber

    Catalogue Number

    100 – 400 Amperes 600 Amperes

    20-inch W x 5-3/4-inch D

    (508.0 mm W x 146.1 mm D)

    48

    60

    72

     1219.2

    1524.0

    1828.8

    EZB2048RCEZB2060RCEZB2072RC

    EZT2048S or FEZT2060S or FEZT2072S or F

    EZTV2048S or FEZTV2060S or FEZTV2072S or F

    Box Dimensions Height Box

    Inches mm CatalogueNumber

    24-inch W x 10.4-inch D

    (609.6 mm W x 264.2 mm D)

    57

    73-1/2

    90

    1447.8

    1866.9

    2286.0

    BX2457BX2473BX2490

    38-inch W x 10.4-inch D

    (965.2 mm W x 264.2 mm D)

    73-1/2

    90

    1866.9

    2286.0

    BX3873BX3890

    44-inch W x 10.4-inch D

    (1117.6 mm W x 264.2 mm D)

    73-1/2

    90

    1866.9

    2286.0

    BX4473BX4490

    Table 2-37.

    Table 2-38.

    Table 2-39.

    2-28PanelboardsPow-R-Line C Panelboards

    Boxes and Trims

  • 8/17/2019 Catalogo-panel Electrico Ch

    29/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Modification Item

    PRL1a PRL2a PRL3a PRL4B PRL4F Column

    Type

    Special Enclosure Construction

    SPRINKLERPROOF (per CEC 26-008), 508mm (20") wide. Single or Multi-Section. 1a. Yes Yes Yes Yes Yes NoTYPE 2 508mm (20") wide. Single or Multi Section 1b. Yes Yes Yes Yes Yes No

    TYPE 3R/12 Enclosure 1c. Yes Yes Yes Yes Yes No

    TYPE 4 combination Enclosure (incorporates features required for 3R and 12 ratings) 1d. Yes Yes Yes Yes Yes No

    Neutral Assemblies

    200% rated neutrals ( use on systems with high harmonic content) - 100A max. bus Yes Yes Yes No No Yes

    200% rated neutrals ( use on systems with high harmonic content) - 225A max. bus Yes Yes Yes No No Yes

    200% rated neutrals ( use on systems with high harmonic content) - 250A max. bus No No Yes Yes Yes No

    200% rated neutrals ( use on systems with high harmonic content) - 400A max. bus No No Yes Yes Yes No

    200% rated neutrals ( use on systems with high harmonic content) - 600A max. bus No

    No

    No

    No

    No

    No

    Yes

    No

    No

    Yes

    No

    No

    Yes

    No

    No

    No

    200% rated neutrals ( use on systems with high harmonic content) - 800A max. bus No

    200% rated neutrals ( use on systems with high harmonic content) - 1200A max. bus No

     ALL 3 Phase, 4 Wire panelboa rds include a neutral assembly. For 3PH 3W applications

    the neutral assembly is deleted.

    24 point neutral adder for use with "twin frame" DNBA type breakers Yes No No No No No

    42 point neutral adder for use with "twin frame" DNBA type breakers Yes No No No No No

    Special Ground BusInsulated Ground Bus Assembly 3a. Yes Yes Yes Yes Yes No

    Isolated Ground Bus Assembly 3b. Yes Yes Yes Yes Yes No

    Sub Feed Assemblies (use on MLO panels only)

    Sub-Feed Lugs - 100A Maximum Yes Yes Yes No No No

    Sub-Feed Lugs - 225A Maximum Yes Yes Yes No No No

    Sub-Feed Lugs - 250A Maximum No No Yes Yes Yes No

    Sub-Feed Lugs - 400A Maximum (cable size/quantity restrictions on some panels) Yes Yes Yes Yes Yes No

    Sub-Feed Lugs - 600A Maximum No No Yes Yes Yes No

    Sub-Feed Lugs - 800A Maximum No No No Yes Yes No

    Sub-Feed Lugs - 1200A Maximun No No No No No No

    Sub-Feed Breakers - All Panelboard Ratings 4b. Yes Yes Yes Yes Yes No

    Through-Feed Lug Assemblies (use with MLO or MB panels)

    Through-Feed Lugs - 100A Maximum Yes Yes Yes No No No

    Through-Feed Lugs - 225A Maximum Yes Yes No No No No

    Through-Feed Lugs - 250A Maximum No No Yes Yes Yes No

    Through-Feed Lugs - 400A Maximum Yes Yes Yes Yes Yes NoThrough-Feed Lugs - 600A Maximum No No Yes Yes Yes No

    Through-Feed Lugs - 800A Maximum No No No Yes Yes No

    Through-Feed Lugs - 1200A Maximun No No No Yes Yes No

    Compression Lugs on Mains

    Max. size: 1x750 kcmil / phase or 2x500 kcmil / phase

    Refer to Eaton for enclosure dimensions.

    Special Entr y Plates (Specify location, supplied loose)

     Aluminum (Corflex) 7a. Yes Yes Yes Yes Yes No

    Fibre (Corflex) 7b. Yes Yes Yes Yes Yes No

    Brass (MIC) 7c. Yes Yes Yes Yes Yes No

    Painting and Special Coatings

    Painted Box (Any colour) 8a. Yes Yes Yes Yes Yes Yes

    Trim (Other than ASA - 61) 8b. Yes Yes Yes Yes Yes Yes

    Trim and Door Modifications

    Door-in-Door  9a. Std. Std. Std. Yes Yes No

    Door over Distribution 9b. Std. Std. Std. Yes Yes NoBox / Tub Modifications

    Blank Box End 10a. Std. Std. Std. Std. No

    Box End with Knockouts 10b. Yes Yes Yes No No No

    Service Entrance

    Includes barriered main breaker compartment to CSA requirements. All ratings. 11a. Yes Yes Yes Yes Yes No

     Available on Panelboard Types

    4a.

    5a.

    Yes YesYes Yes Yes Yes2b

    Yes Yes Yes6a. Yes Yes Yes

    2a.

    2c.

    Std.

     

    Table 1-46. Panelboard Accessories and ModificationsTable 2-40.

    2PanelboardsAccessories and Modifications

    Type PRL 1a, 2a, 3a, 4, Column

  • 8/17/2019 Catalogo-panel Electrico Ch

    30/32

    CAT.38.03.S.K For more information visit: www.eatoncanada.ca

    Table 1-46a. Panelboard Accessories and Modifications - Continued

     

    Modification Item

    PRL1a PRL2a PRL3a PRL4B PRL4F Column

    Type

    Complete Assembly

    Box, Interior, Breakers & Trim completely assembled prior to shipment. 12a. Yes Yes Yes Yes Yes YesMulti-Section Panels

    Double Section - Cable connected - 225A Maximum (cross over cables NOT included) Yes Yes No No No No

    Double Section - Cable connected - 250A Maximum (cross over cables NOT included) No No Yes Yes Yes No

    Double Section - Cable connected - 400A Maximum (cross over cables NOT included) Yes Yes Yes Yes Yes No

    Double Section - Cable connected - 600A Maximum (cross over cables NOT included) No No Yes Yes Yes No

    Double Section - Cable connected - 800A Maximum (cross over cables NOT included) No No Yes Yes Yes No

    Double Section - Cable connected - 1200A Maximum (cross over cables NOT included) No No Yes Yes Yes No

    Double Section - Bus connected - 225A Maximum Yes Yes No No No No

    Double Section - Bus connected - 250A Maximum No No Yes Yes Yes No

    Double Section - Bus connected - 400A Maximum Yes Yes Yes Yes Yes No

    Double Section - Bus connected - 600A Maximum No No Yes Yes Yes No

    Double Section - Bus connected - 800A Maximum No No Yes Yes Yes No

    Double Section - Bus connected - 1200A Maximum No No Yes Yes Yes No

    Key Interlock (Use on main breakers - key protrudes through front cover) - All ratings. 14a. Yes Yes Yes Yes Yes No

    Contactor in Mains

    C-H - electrically held, installed in a separate compartment, with a removable cover. 15a. Yes Yes Yes No No NoSpecialty Contactors - mounted as above. 15b. Yes Yes Yes No No No

    Cover Mounted Controls (Factory Wired) 15c. Yes Yes Yes No No No

    Low Voltage Relay Troughs  (Matching Box and Trim mounted adjacent to the panelboard).

    30 inch high (762mm) to 72 inch high (1828mm) box & trim. 16a. Yes Yes No No No No

    Relay Mounting rail for 30 inch high (762mm) to 72 inch high (1828mm) box & trim. 16b. Yes Yes No No No No

    Moisture and Fungus Proofing 17a. Yes Yes Yes Yes Yes Yes

    Tin Plating of Copper Bus 18a. Yes Yes Yes Yes Yes Yes

    Nameplates and Circuit Directories

    Engraved Lamicoid Nameplates - supplied loose or factory installed. 19a. Yes Yes Yes Yes Yes Yes

    Circuit Directory Holder (Steel frame & acetate cover) 19b. Yes Yes Yes Yes Yes Yes

    Circuit Breaker Handle Lock-off Devices

    Non-Padlockable (supplied loose) 20a. Yes Yes Yes Yes Yes Yes

    Padlockable (supplied loose) 20b. Yes Yes Yes Yes Yes Yes

    Main or Branch Circuit Breaker Accessories

     Auxiliary Switch (1A / 1B) 20a. Yes Yes Yes Yes Yes Yes

    Shunt Trip 20b. Yes Yes Yes Yes Yes YesUndervoltage Release 20c. Yes Yes Yes Yes Yes Yes

     Alarm Switch (1A / 1B) 20d. Yes Yes Yes Yes Yes Yes