Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information...

45
Page 1 Air-Cooled Chiller, Scroll Compressors Job Information Name Job01 (Restored) Tag Address Quantity Sales Team Model Number CGAM080F2*02AXD2 A1A1B1AXXA1D1AXX XXXXXBxA3A1D1X- C-X Comments General Unit nominal tonnage 80 tons Capacity 70.40 tons Unit type High efficiency Sound attenuator package Super quiet Agency listing UL/CUL Refrigerant isolation valves Refr. isolation valves (discharge valve) Freeze protection (factory inst. only) Ext. t-stat control Water strainer Factory installed Appearance options Louvers Startup allowance Unit startup by Trane TOPSS version number 147 Number of compressors 4 Number of circuits 2 Capacity steps 4 Shipping weight 5607.3 lb Operating weight 5692.2 lb Length 143.100 in Width 89.000 in Height 92.400 in Water connections 4.000 in Refrigerant R410A Refrigerant charge circuit 1 74.0 lb Refrigerant charge circuit 2 74.0 lb Oil charge circuit 1 3.54 gal Oil charge circuit 2 3.54 gal ASHRAE 90.1/CSA compliance All versions AHRI certification Certified Rated capacity (AHRI) 78.20 tons Flow switch set point Flow switch set point 15 cm/sec Evaporator Evaporator application Low temp Evap leaving temp 43.00 F Evap entering temp 53.00 F Evap flow rate 184.80 gpm Evap fluid type Ethylene glycol Evap fluid concentration 30.00 % Evap fouling factor 0.00010 hr-sq ft-deg F/Btu Evap press drop 15.60 ft H2O Total PD evap+strainer 18.50 ft H2O Evap fluid freeze point 5.10 F Min evap flow rate 114.70 gpm Min flow PD evap+strainer 7.50 ft H2O Max evap flow rate 275.30 gpm Max flow PD evap+strainer 39.60 ft H2O Saturated evap temp circuit 1 36.20 F Saturated evap temp circuit 2 36.20 F Condenser Unit application Wide ambient Fin material Lanced aluminum Ambient air temperature 105.00 F Elevation 0.00 ft Total airflow 56958 cfm Saturated cond temp circuit 1 130.40 F Saturated cond temp circuit 2 130.40 F Electrical Unit hertz 60 hertz Unit voltage 460 volt 3 phases Starter type Across the line Incoming power line connection Single point Power line connection Circuit breaker-high Enclosure type UL 1995 rated for

Transcript of Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information...

Page 1: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 1

Air-Cooled Chiller, Scroll Compressors

Job Information Name Job01 (Restored) Tag Address Quantity Sales Team Model Number CGAM080F2*02AXD2

A1A1B1AXXA1D1AXXXXXXXBxA3A1D1X-C-X

Comments

General Unit nominal tonnage 80 tons Capacity 70.40 tons Unit type High efficiency Sound attenuator

package Super quiet

Agency listing UL/CUL Refrigerant isolation valves

Refr. isolation valves (discharge valve)

Freeze protection (factory inst. only)

Ext. t-stat control Water strainer Factory installed

Appearance options Louvers Startup allowance Unit startup by Trane TOPSS version number 147 Number of compressors 4 Number of circuits 2 Capacity steps 4 Shipping weight 5607.3 lb Operating weight 5692.2 lb Length 143.100 in Width 89.000 in Height 92.400 in Water connections 4.000 in Refrigerant R410A Refrigerant charge

circuit 1 74.0 lb

Refrigerant charge circuit 2

74.0 lb Oil charge circuit 1 3.54 gal

Oil charge circuit 2 3.54 gal ASHRAE 90.1/CSA compliance

All versions

AHRI certification Certified Rated capacity (AHRI) 78.20 tons Flow switch set point Flow switch set point

15 cm/sec

Evaporator Evaporator application Low temp Evap leaving temp 43.00 F Evap entering temp 53.00 F Evap flow rate 184.80 gpm Evap fluid type Ethylene glycol Evap fluid concentration 30.00 % Evap fouling factor 0.00010 hr-sq ft-deg

F/Btu Evap press drop 15.60 ft H2O

Total PD evap+strainer 18.50 ft H2O Evap fluid freeze point 5.10 F Min evap flow rate 114.70 gpm Min flow PD

evap+strainer 7.50 ft H2O

Max evap flow rate 275.30 gpm Max flow PD evap+strainer

39.60 ft H2O

Saturated evap temp circuit 1

36.20 F Saturated evap temp circuit 2

36.20 F

Condenser Unit application Wide ambient Fin material Lanced aluminum Ambient air temperature

105.00 F Elevation 0.00 ft

Total airflow 56958 cfm Saturated cond temp circuit 1

130.40 F

Saturated cond temp circuit 2

130.40 F

Electrical Unit hertz 60 hertz Unit voltage 460 volt 3 phases Starter type Across the line Incoming power line

connection Single point

Power line connection Circuit breaker-high Enclosure type UL 1995 rated for

Page 2: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 2

type fault rated outdoor applications Short circuit High Unit power 98.30 kW Total compressor power 90.80 kW Number of fans 6 Fan motor power 7.10 kW Total fan FLA 20.20 A RLA - compressor A 33.00 A RLA - Compressor B 33.00 A RLA - Compressor D 33.00 A RLA - Compressor E 33.00 A LRA - Compressor A 215.00 A LRA - Compressor B 215.00 A LRA - Compressor D 215.00 A LRA - Compressor E 215.00 A Single point power MCA 162.20 A Single point power MOP 175.00 A Short circuit rating 65000.00 A

Performance Full load efficiency 8.6 EER IPLV 15.6 EER NPLV 14.9 EER

Acoustics Sound power level 92 dBA Sound pressure level 65 dBA

Isolator/Rigging Info Mounting weight 1 1434.8 lb Mounting weight 2 1662.1 lb Mounting weight 3 774.3 lb Mounting weight 4 885.5 lb Mounting weight 5 395.7 lb Mounting weight 6 448.8 lb Center of gravity weight 1

1811.3 lb Center of gravity weight 2

1968.7 lb

Center of gravity weight 3

832.0 lb Center of gravity weight 4

904.3 lb

Center of gravity length 59.484 in Center of gravity width 46.610 in Center of gravity height 37.891 in

Base unit module Factory charge Refrigerant charge

(HFC-410A)

Evaporator module Water connection (evap)

Grooved pipe Insulation Insulation

Controls module Unit operator interface English

Page 3: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 3

4" (1

00m

m)

7.0

GA

L (2

6.5

LIT

ER

S)

ISO

ME

TR

IC V

IEW

FR

ON

T V

IEW

BA

CK

VIE

W

TO

P V

IEW

RIG

HT

SID

E V

IEW

BR

AZ

E P

LA

TE

WA

TE

R V

OLU

ME

/ST

OR

AG

E

INLE

T/O

UT

LET

WA

TER

CO

NN

EC

TIO

N S

IZE

Page 4: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 4

13

9 1

3/1

6"

89

3/1

6"

29 9

/16

"

143

1/1

6"

LIF

TIN

G L

OC

AT

ION

4 P

LA

CE

S

RIG

HT

SID

E V

IEW

Page 5: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 5

5 7

/16"

BR

AZ

E P

LA

TE

INL

ET

\ O

UT

LE

TW

AT

ER

CO

NN

EC

TIO

N

TO

P V

IEW

CO

ND

EN

SE

R, C

ON

TRO

L P

AN

EL

AN

DV

SD

(W

HE

N O

RD

ER

ED

) R

EM

OV

ED

FO

R C

LAR

ITY

CO

MP

RE

SS

OR

S

CO

MP

RE

SS

OR

S

UNIT CONTROL PANELTHIS END OF UNIT

Page 6: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 6

92 5

/8"

84"

8 9

/16

"

88

7/8

"

88

3/1

6"

UN

IT C

ON

TR

OL

PA

NE

L

FR

ON

T V

IEW

LOU

VE

RE

D P

AN

ELS

NO

T S

HO

WN

OV

ER

CO

NT

RO

L P

AN

EL

FO

R C

LAR

ITY

Page 7: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 7

31

1/1

6"

7 7

/8"

11 1

/2"

OU

TL

ET

WA

TE

RC

ON

NE

CT

ION

INLE

T W

AT

ER

CO

NN

EC

TIO

N

BA

CK

VIE

W

Page 8: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 8

ISO

ME

TR

IC V

IEW

LOU

VE

RE

D P

AN

ELS

NO

T S

HO

WN

OV

ER

CO

NT

RO

L P

AN

EL

FO

R C

LAR

ITY

Page 9: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 9

LIFT

ING

WE

IGH

TS

W1

W2

W3

W4 W

1 -

NE

AR

SID

EW

2 -

FA

R S

IDE

W3

- N

EA

R S

IDE

W4

- F

AR

SID

E

CG

CG

CO

NT

RO

L P

AN

EL

EN

DF

RO

NT

VIE

WS

IDE

VIE

W

UN

IT C

EN

TE

R O

F G

RA

VIT

Y

SH

IPP

ING

WE

IGH

T

5607

.3 lb

1811

.3 lb

1968

.7 lb

83

2.0

lb90

4.3

lb

59.4

84 in

37.8

91

in

46.

610

in

Page 10: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 10

39 3

/8"

39

3/8"

47 1

/4"

39 3

/8"

WO

RK

ING

CLE

AR

AN

CE

PE

R N

AT

ION

AL

ELE

CT

RIC

CO

DE

AR

TIC

LE

110

-26

.

FO

R O

BS

TR

UC

TIO

NS

OR

MU

LT

IPLE

UN

ITS

,R

EF

ER

TO

TH

E C

LOS

E S

PA

CIN

G B

ULL

ET

IN.

NO

OB

ST

RU

CT

ION

S R

EC

OM

ME

ND

ED

.A

rea

Re

quire

d fo

r u

nit

oper

atio

n, m

ain

tena

nce

,an

d ac

cess

pan

el.

MO

RE

CL

EA

RA

NC

E M

AY

BE

NE

ED

ED

FO

RA

IRF

LO

W D

EP

EN

DIN

G U

PO

N T

HE

IN

ST

ALL

AT

ION

.

TO

P V

IEW

UN

IT C

LE

AR

AN

CE

NO

OB

ST

RU

CT

ION

S A

BO

VE

TH

E C

ON

DE

NS

ER

Page 11: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 11

89

3/1

6"

29 9

/16

"

ISO

ME

TR

IC V

IEW

UN

IT R

IGG

ING

IMP

RO

PE

R L

IFT

ING

AN

D M

OV

ING

!

WA

RN

ING

US

E S

PR

EA

DE

R B

AR

AS

SH

OW

N I

N D

IAG

RA

M.

RE

FE

R T

O IN

ST

AL

LAT

ION

MA

NU

AL

OR

NA

ME

PL

AT

EF

OR

UN

IT W

EIG

HT

. R

EF

ER

TO

IN

STA

LLA

TIO

NIN

ST

RU

CT

ION

S L

OC

AT

ED

INS

IDE

CO

NT

RO

L P

AN

EL

FO

R F

UR

TH

ER

RIG

GIN

G I

NF

OR

MA

TIO

N.

OT

HE

R L

IFT

ING

AR

RA

NG

EM

EN

TS

CO

UL

D R

ES

ULT

IN D

EA

TH,

SE

RIO

US

IN

JUR

Y O

R E

QU

IPM

EN

TD

AM

AG

E.

LIF

TIN

G A

UN

IT W

ITH

EQ

UA

L L

EN

GT

H S

TR

AP

S W

ILL

NO

TP

RO

DU

CE

A L

EV

EL

UN

IT D

UR

ING

TH

E L

IFT

BE

CA

US

ET

HE

CG

WIL

L N

OT

BE

AT

TH

E M

IDP

OIN

T B

ET

WE

EN

TH

EB

AS

E L

IFT

ING

HO

LES

. T

HE

FO

LLO

WIN

G A

DJU

STM

EN

TS

MU

ST

BE

MA

DE

TO

PR

OD

UC

E A

LE

VE

L L

IFT

:

- S

ING

LE S

PR

EA

DE

R B

AR

LIF

TIN

G M

ETH

OD

IF T

HE

UN

IT C

G IS

CL

OS

ER

TO

TH

E C

ON

TRO

L P

AN

EL,

TH

E S

TR

AP

S O

N T

HE

CO

NTR

OL

PA

NE

L S

IDE

OF

TH

ES

PR

EA

DE

R B

AR

MU

ST

BE

AD

JUS

TE

D T

O B

E S

HO

RT

ER

TH

AN

TH

OS

E O

N T

HE

OP

PO

SIT

E S

IDE

OF

TH

E S

PR

EA

DE

RB

AR

, ALL

OW

ING

TH

E S

PR

EA

DE

R B

AR

TO

MO

VE

TO

WA

RD

TH

E C

ON

TR

OL

PA

NE

L A

ND

OV

ER

TH

E U

NIT

CG

.S

EV

ER

AL

AD

JUS

TM

EN

TS

OF

TH

E S

TR

AP

LE

NG

TH

MA

Y B

ER

EQ

UIR

ED

TO

PR

OD

UC

E A

LE

VE

L U

NIT

DU

RIN

G L

IFT

.

- H

-TY

PE

SP

RE

AD

ER

BA

R L

IFTI

NG

ME

THO

DIF

TH

E S

TR

AP

S F

RO

M T

HE

H B

AR

TO

TH

E U

NIT

BA

SE

AR

E

TH

E S

AM

E L

EN

GT

H,

TH

E C

RA

NE

LIF

TIN

G P

OIN

T O

N T

HE

CE

NT

ER

WE

B O

F T

HE

H B

AR

MU

ST

BE

AD

JUS

TE

D T

OP

RO

DU

CE

A L

EV

EL

UN

IT L

IFT

.

Page 12: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 12

6 1

/8"

4 3

/4"

7 1

/2"

6 1

/8"

4 3

/4"

3 3

/8"

1 1

5/1

6"

CU

ST

OM

ER

CO

NT

RO

L W

IRIN

G1

0 K

NO

CK

OU

TS

7"

4 3

/4"

6 1

5/1

6"

2 1

3/1

6"

CU

ST

OM

ER

PO

WE

RW

IRIN

G (

OP

TIO

N)

CU

ST

OM

ER

PO

WE

RW

IRIN

G

32"

88 3

/4"

PO

WE

R W

IRE

CO

NN

EC

TIO

N T

O C

IRC

UIT

BR

EA

KE

R (

1Q

1)

CIR

1 &

2 (

SIN

GLE

PO

INT

PO

WE

R)

LUG

WIR

E S

IZE

RA

NG

E (P

ER

PH

AS

E)

(1 M

AX

Co

nduc

tor

per p

hase

)3/

0-3

50M

CM

65k

A

HIG

H4

600

80

UN

ITS

IZE

UN

ITE

FFV

OLT

AG

E

CU

ST

OM

ER

WIR

E S

ELE

CT

ION

TA

BLE

RIG

HT

EN

D V

IEW

LE

FT

EN

D V

IEW

ISO

ME

TR

IC V

IEW

FR

ON

T V

IEW

SH

OR

T C

IRC

UIT

RA

TIN

G

Page 13: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 13

CONTROL PANEL

1 2

3 4

5 6

123 7/8"

83 11/16"

30 3/16"

1 1/2"

321 4 5 6 87

080 5692.2 lb

UNITS IZE

MOUNTING LOCATIONS &POINT LOAD WEIGHTS TOTA L OPERATING

WEIGHT

MOUNTING HOLE DIAMETER 19mm

TOP VIEW

DIM ENS IONS ARE REFERENCE D FROM THE E ND AND SIDE OF THE UNIT BASE

1434.8 lb 1662.1 lb 774.3 lb 885.5 lb 395.7 lb 448.8 lb N/A N/A

Page 14: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 14

INS

ET

"A"

L1

1Q2

L2L3

AB

C

1

6Q1

C L3 B L2

18

A L1

CU

ST

OM

ER

SU

PPL

IED

PU

MP 3

3

M

6M1

PU

MP

CO

NT

RO

L

21

33

M

6M2

NO

TIC

E

OU

TP

UT

.M

US

T B

E C

ON

TR

OLL

ED

BY

TH

E C

HIL

LE

R

PR

OV

IDE

PU

MP

CO

NT

RO

L.

CH

ILL

ED

WA

TE

R P

UM

P

TR

AN

E P

UM

P C

ON

TR

OL

MU

ST B

E U

SE

D T

O

FA

ILU

RE

TO

CO

MP

LY

WIT

H T

HIS

RE

QU

IRE

ME

NT

. C

OU

LD

RE

SU

LT I

N D

AM

AG

E T

O T

HE

UN

IT.

380

V 60

HZ

220

V 5

0H

Z

INS

ET

"B

"

25A

H1

2

400

V 5

0H

Z U

NIT

IS F

AC

TO

RY

WIR

ED

AS

SH

OW

N,

RE

CO

NN

EC

T W

IRE

26

A T

O T

ER

MIN

ALS

H2

OR

H4

FOR

380

V 50

HZ

OR

415

V 50

HZ

PO

WE

R S

UP

PL

IES

.

25A

H2

26A

H1

575

V 60

HZ

230

V 6

0H

Z

X1

INSE

T "B

"

X2

115

V

11

0VO

R

2

EQ

UIP

ME

NT

GR

OU

ND

26A

25A

26A

H2

H3

H1

H2

380V

L1A12

H4

H3

415V

L1A

460V

60H

Z

1T1

X3X4

27V

H3

200V

60H

Z

H125A

H226A

L1L2

L3B

CA

6Q2

L2L3

BC

6Q1

L1L2B

L3CA

L2BL3C

CO

NT

RO

L P

AN

EL

UN

IT T

ER

MIN

ALS

AR

E N

OT

DE

SIG

NE

D T

O A

CC

EP

TO

TH

ER

TY

PE

S O

F C

ON

DU

CT

OR

S.

FA

ILU

RE

TO

DO

TH

E A

BO

VE

CO

UL

D R

ES

ULT

IN

EQ

UIP

ME

NT

DA

MA

GE

.

HA

ZAR

DO

US

VO

LT

AG

E!

US

E C

OP

PE

R C

ON

DU

CT

OR

S O

NL

Y!

WA

RN

ING

DIS

CO

NN

EC

T A

LL E

LEC

TR

IC P

OW

ER

INC

LUD

ING

RE

MO

TE

DIS

CO

NN

EC

TS

AN

D F

OLL

OW

LO

CK

OU

T A

ND

TA

GP

RO

CE

DU

RE

S B

EF

OR

E S

ER

VIC

ING

.IN

SU

RE

TH

AT

AL

L M

OT

OR

CA

PA

CIT

OR

S H

AV

E D

ISC

HA

RG

ED

ST

OR

ED

VO

LT

AG

E.

UN

ITS

WIT

HV

AR

IAB

LE

SP

EE

D D

RIV

E,

RE

FE

RT

O D

RIV

E I

NS

TR

UC

TIO

NS

FO

RC

AP

AC

ITO

R D

ISC

HA

RG

E.

FA

ILU

RE

TO

DO

TH

E A

BO

VE

CO

UL

D R

ES

ULT

IN

DE

AT

H O

RS

ER

IOU

S IN

JUR

Y.

PA

GE

1 O

F 2

Page 15: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 15

HE

AT

ERS

42

CIR

CU

IT 3

1X6-2

1X6-1

43

636

43

N

6Q

7

42

634

H4

41

40

41

40

40

41

H N2

11

7

1X4-32

3

PU

MP

ST

AR

TE

R C

OIL

S

536

40

41

41

5401X4-31

1X4-30539

40

J2

1X4-29

535

DU

AL

RE

LAY

OU

TP

UT

EV

AP W

AT

ER

PU

MP

RE

LA

YS

RU

N S

IGN

AL

15

PUMP 1

1A

9

PUMP 2

EQ

UIP

ME

NT

GR

OU

ND

17

18

6K5

6K

42

01

9

23 25

24 26

6F

1

6F2

16

J2

1A

13

W2

W3E-STOP

AUTO STOP

DU

AL

LO

W V

OL

TA

GE

BIN

ARY

INP

UT

EM

ER

GE

NY

ST

OP/

AU

TO S

TO

P

22

12

34

2019

1817

25

23

24

PUMP 2

PUMP 1

43

2

CH

ILLE

D W

AT

ER

PU

MP

FA

UL

T IN

PUT

DU

AL

LO

W V

OL

TA

GE

BIN

ARY

INP

UT1

A12 1X5-6

811

1X5-7812

1X5-8

818

3

26

1X5-5

817

1J2

GR

OU

ND

EQ

UIP

ME

NT

CO

NT

RO

L P

AN

EL

UN

IT T

ER

MIN

ALS

AR

E N

OT

DE

SIG

NE

D T

O A

CC

EP

TO

TH

ER

TY

PE

S O

F C

ON

DU

CT

OR

S.

FA

ILU

RE

TO

DO

TH

E A

BO

VE

CO

UL

D R

ES

UL

T IN

EQ

UIP

ME

NT

DA

MA

GE

.

HA

ZA

RD

OU

S V

OLT

AG

E!

US

E C

OP

PE

R C

ON

DU

CT

OR

S O

NL

Y!

WA

RN

ING

DIS

CO

NN

EC

T A

LL

EL

EC

TR

IC P

OW

ER

INC

LU

DIN

G R

EM

OT

E D

ISC

ON

NE

CT

SA

ND

FO

LL

OW

LO

CK

OU

T A

ND

TA

GP

RO

CE

DU

RE

S B

EF

OR

E S

ER

VIC

ING

.IN

SU

RE

TH

AT

ALL

MO

TO

RC

AP

AC

ITO

RS

HA

VE

DIS

CH

AR

GE

DS

TO

RE

D V

OLT

AG

E.

UN

ITS

WIT

HV

AR

IAB

LE S

PE

ED

DR

IVE

, RE

FE

RTO

DR

IVE

INS

TR

UC

TIO

NS

FO

RC

AP

AC

ITO

R D

ISC

HA

RG

E.

FAIL

UR

E T

O D

O T

HE

AB

OV

EC

OU

LD R

ES

UL

T IN

DE

AT

H O

RS

ER

IOU

S IN

JUR

Y.

PA

GE

2 O

F 2

Page 16: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 16

WIRED TO TRACER OR OTHER REMOTE DEVICE.

OPTIONAL FIELD ASSIGNED PROGRAMMABLE RELAYS (STAT=PRLY). CLASS

1A41, BACNET INTERFACE M ODULE USED W HEN (CO MM = BCNT).

1A15, LCI MO DULE USED WHEN (COM M = LCI).

T HE CONTACT S FOR AUT O STOP AND EMERGENCY STO P SW ITCHES ARE JUM PERED ATT HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO N. IF REM OTE CONT ROLIS DESIRED, REMOVED THE JUMPERS AND CONNECT TO THE DESIRED CONT RO L CIRCUIT.

WHEN FACTORY PROVIDED PUMP IS NOT SELECT ED. CUSTOMER M UST SUPPLY SUITABLEPUM P SYSTEM. REFER TO PUM P M ANUFACTURER FOR WIRING REQUIREM ENTS.

WIRED TO CUSTOMER 0-10 VDC PUMP SPEED SIGNAL.

HP 7.2FLA; AT 240VAC: 5 AMPS GENERAL PURPOSE.1 FIELD WIRED MODULE, RELAY AT 120V: 7 .2A RESISTIVE 2.88A PILOT DUTY,

CUSTOMER SUPPLIED 3 PHASE POWER.

FIELD CONNECTIONS ARE ONLY MADE IN A CUSTOMER PROVIDED PUMP. THESE CONNECTIONS WILL BE MADE BY THE FACTORY WHEN THE PUMP IS PROVIDED BY THE FACTORY. CUSTOMER SUPPLIED POWER 115V, 60Hz, 1PH.

CUSTOMER SUPPLIED CONTACTS FOR ALL LOW VOLTAGE CONNECTIONS MUST BE COMPATABLE WITH DRY CIRCUIT 24 VOLTS DC FOR A 12 mA RESISTIVE LOAD. SILVER OR GOLD PLATED CONTACTS RECOMMENDED.

UNIT PROVIDED DRY CONTACTS FOR THE CONDENSER/CHILLED WATER PUMP CONTROL. RELAYS ARE RATED FOR 7.2 AMPS RESISTIVE, 2.88 AMPS PILOT

HP, 7.2 FLA AT 120 VOLTS 60 HZ, CONTACTS ARE RATED FOR 5 AMPS GENERAL PURPOSE DUTY 240 VOLTS.

ALL CUSTOMER CONTROL CIRCUIT WIRING MUST BE COPPER CONDUCTORS ONLY AND HAVE A MINIMUM INSULATION RATING OF 300 VOLTS. EXCEPT AS NOTED, ALL CUSTOMER WIRING CONNECTIONS ARE MADE TO CIRCUIT BOARD MOUNTED BOX LUGS WITH A WIRE RANGE OF 14 TO 18 AWG OR DIN RAIL MOUNTED SPRING FORCE TERMINALS.

ALL FIELD WIRING MUST BE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE AND LOCAL REQUIREMENTS.

ALL UNIT POWER WIRING MUST BE 600 VOLT COPPER CONDUCTORS ONLY AND HAVE A MINIMUM TEMPERATURE INSULATION RATING OF 90 DEGREE C. REFER TO UNIT NAMEPLATE FOR MINIMUM CIRCUIT AMPACITY AND MAXIMUM OVERCURRENT PROTECTION DEVICE. PROVIDE AN EQUIPMENT GROUND IN ACCORDANCE WITH APPLICABLE ELECTRIC CODES. REFER TO WIRE RANGE

REFER TO CGAM ELECTRICAL SCHEMATIC FOR SPECIFIC ELECTRICAL CONNECTION INFORMATION AND NOTES PERTAINING TO WIRING INSTALLATION.

FIELD CONNECTIONS ARE MADE TO 1X1, OR 1Q2.SINGLE SOURCE POWER IS PROVIDED AS STANDARD ON THESE PRODUCTS,

380V/50HZ, OR H4 FOR 415V/50HZ. H4 IS ONLY AVAILABLE WITH WIRED WITH 26A CONNECTED TO H3 - RECONNECT WIRE 26A TO H2 FOR WIRE 26A SHALL BE CONNECT TO H3. 400V/50HZ UNIT IS FACTORY SHALL BE CONNECTED TO H2. FOR VOLTAGES 230V/60HZ & 575V/60HZ, FOR VOLTAGES 200V/60HZ, 220V/50HZ, 380V/60HZ, 460V/60HZ, WIRE 26A

THE PUMP IS PROVIDED BY THE FACTORY (PTYP=DHHP).(PTYP=NONE). THESE CONNECTIONS WILL BE MADE BY THE FACTORY WHEN FIELD CONNECTIONS ARE ONLY MADE IN A CUSTOMER PROVIDED PUMP

PROVIDED IN UNIT CONTROL PANEL. AS REQUIRED BY APPLICABLE CODES. GREEN GROUND SCREWS ARE FUSE SIZE IS 20 AMPS. GROUND ALL CUSTOMER SUPPLIED POWER SUPPLIES CUSTOMER SUPPLIED POWER 115/60/1 OR 220/50/1 TO POWER RELAYS. MAX.

TERMINATION RESISTOR REQUIREMENTS.SYSTEM (BAS) COMMUNICATION INSTALLATION LITERATURE FOR END OF LINE TOPOLOGY SHOULD BE DAISY CHAIN. REFER TO BUILDING AUTOMATION INTERCONNECTED CABLE SEGMENTS NOT TO EXCEED 4500 FEET. CONNECTION TO HELIX LF22P0014216 RECOMMENDED. THE SUM TOTAL OF ALL WIRED TO NEXT UNIT. 22 AWG SHIELDED COMMUNICATION WIRE EQUIVALENT

LITERATURE FOR END OF LINE TERMINATION RESISTOR REQUIREMENTS.BUILDING AUTOMATION SYSTEM (BAS) COMMUNICATION INSTALLATION 4500 FEET. CONNECTION TOPOLOGY SHOULD BE DAISY CHAIN. REFER TO THE SUM TOTAL OF ALL INTERCONNECTED CABLE SEGMENTS NOT TO EXCEED COMMUNICATION WIRE EQUIVALENT TO HELIX LF22P0014216 RECOMMENDED. WIRED TO TRACER OR OTHER TRANE REMOTE DEVICE. 22 AWG SHIELDED

WIRED TO CUSTOMER CHILLED WATER SET POINT 2-10V OR

WIRED TO CUSTOMER EXTERNAL DEMAND LIMIT 2-10V OR

WIRED TO CUSTOMER 2-10V OR 4-20mA

24

23

22

21

20

19

1/2

18

17

16

15

14.

13.

1DUTY, OR 3

TABLE FOR LUG SIZES.

12

10

11.

9

8

7

6

ANNUNICIATOR.

4-20mA.

4-20mA.

5

4

3

2

1

400V/50HZ PANELS.

% CAPACITY

Page 17: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 17

General Uni ts are constructed of a galvanized steel frame wi th ga lvanized steel panels and access doors. Com ponent surfaces are finished wi th a powder-coated paint. Al l pa int meets the requi rem ent for outdoor equipm ent o f the U.S. Navy and other Federa l Governm ent Agencies. T his pa int finish is durable enough to wi thstand a 1000-consecutive-hour sa l t spray

appl ication in accordance wi th standard ASTM B117. Each unit ships wi th ful l operating charges of refrigerant and o i l. Compressor and Motor T he uni t is equipped wi th four hermetic, d i rect-drive, 3600 rpm 60 Hz suction gas-cooled scrol l compressors. T he simple

design has only three m ajor m oving parts and a com pletely enclosed compression cham ber which leads to increased e fficiency. Overload protection is interna l to the com pressors. T he compressor includes: centri fugal o i l pump, o i l leve l sight g lass and o il charging valve. Each compressor wi l l have compressor heaters insta l led and properly sized to min im ize the amount of l iqu id refrigerant present in the o il sum p during off cycles. Unit-Mounted Starter T he contro l panel is designed per UL 1995. T he starter is in an across-the-l ine configuration, factory-mounted and fu l ly

pre-wired to the com pressor m otor and control panel . Typical ly, T rane scro l l compressors are up to fu l l speed in one second when started across-the-l ine. A factory-insta l led, factory-wi red 820 VA contro l power transformer provides al l un i t control power (120 Vac secondary) and T rane CH530 module power (24 Vac secondary). A molded case h igh interrupting capaci ty ci rcu it breaker, factory pre-wi red with terminal block power connections and

equipped with a lockable external operator handle, is avai lab le to d isconnect the ch i l ler from main power. Pow er Connection Power connections include main three-phase power and one separate 120V, 15 amp customer provided single phase power connection is requi red to power the heaters (i f used for freeze protection). Short ci rcu i t current rating of 65 kA is provided.

Evaporator Braze p late evaporator is m ade of sta in less steel wi th copper as the braze m ateria l . It is designed to withstand a re frigerant side working pressure of 430 psig (29.6 bars) and a waterside working pressure of 150 psig (10.5 bars). Evaporator is tested a t 1 .1 times m aximum allowable refrigerant side working pressure and 1.5 times m aximum al lowable water side working pressure. It has one water pass. A water stra iner and a flow swi tch are factory insta l led.

Imm ersion heaters protect the evaporator to an ambient of -20°F (-29°C). An addi tional tem perature sensor, a t the compressor discharge, enables leaving evaporator water tem perature be low 42°F (5 .5°C). Condenser A i r-cooled condenser co ils have lanced aluminum fins mechanica lly bonded to in ternal ly-finned copper tub ing. T he condenser co il has an integra l subcool ing ci rcu i t. T he maxim um al lowable working pressure of the condenser is 650 psig (44.8 bars). Condensers are factory proof and leak tested at 715 psig (49.3 bars). Di rect-drive vertical d ischarge condenser fans are ba lanced and individual ly protected. T hree-phase condenser fan m otors wi th permanently lubricated bal l bearings and external thermal overload protection are provided.

A variab le speed drive on the first fan of each ci rcui t al lows the unit to start and operate wi th ambient temperatures between 0.0 F and 125.0 F.

Page 18: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 18

Refrigerant Circuits T he uni t has dual re frigerant ci rcu its. Each refrigerant ci rcu i t has T rane scro l l com pressors p iped in para l lel wi th a passive o i l m anagement system . A passive o i l m anagement system maintains proper o il leve ls with in com pressors and has no

m oving parts. Each refrigerant ci rcui t includes fil ter drier, e lectron ic expansion va lve, l iquid l ine and discharge service valves. Capaci ty modulation is achieved by turning com pressors on and off. The uni t has four capaci ty stages. Unit Controls T he microprocessor-based contro l panel is factory-instal led and factory-tested. The control system is powered by a pre-wired control power transform er, and wi l l turn on and off compressors to meet the load. Microprocessor-based chi l led

water reset based on return water is standard. The unit com es wi th a factory insta l led flow swi tch. T he Trane CH530 m icroprocessor autom atica l ly acts to prevent un it shutdown due to abnormal operating conditions associated wi th low evaporator re frigerant tem perature and high condensing temperature. If an abnormal operating condition continues and the protective l imi t is reached, the machine wi l l shut down. T he panel includes machine protection for the fo l lowing condi tions: low evaporator refrigerant temperature and pressure,

h igh condenser re frigerant pressure, cri tica l sensor or detection ci rcu i t faul ts, h igh compressor d ischarge tem perature, lost com munication between m odules, phase loss, phase reversal , over temperature protection, external and local em ergency stop, and loss of evaporator water flow. When a fau lt is detected, the contro l system conducts m ore than 100 diagnostic checks and displays resul ts. The d isp lay wi ll identi fy the faul t, indicate date, tim e, and operating m ode at tim e of occurrence, and provide type of reset requi red and a help message.

Data conta ined in avai lab le reports includes: water and ai r tem peratures, re frigerant pressures and temperatures, flow swi tch status, EXV posi tion, and com pressor starts and run-time. A ll necessary settings and setpoints are programm ed in to the microprocessor-based control ler via the operator interface. The control ler is capable of rece iving signals simul taneously from a variety of contro l sources, in any combination, and priority order o f control sources can be programm ed. Architectural Louvered Panels Louvered panels cover the complete condensing co i l and service area beneath the condenser.

Page 19: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 19

CGAM80 HIGH Tag: CGAM-1Part Load Performance

NPLV = 14.9

TRANE Air-Cooled Series R(TM) ChillerVersion: 147.0 March 25, 2013

%Load%Load Cap.Cap. LWTevapLWTevap

EWTevapEWTevap

FlowevapFlowevap

WPDevapWPDevap

Ambient Kw Eff

100100 70.4 43.0 53.0 184.8 18.5 105.0 98.3 8.67575 52.8 43.0 50.5 184.8 18.5 86.0 50.5 12.55050 35.2 43.0 48.0 184.8 18.5 67.0 25.7 16.42525 17.6 43.0 45.5 184.8 18.5 55.0 11.5 18.3

Note: 1.NPLV = 0.01A + 0.42B + 0.45C + 0.12DWhere: A = EER at 100% at user defined ambient temperature with 1% weighting

B = EER at 75% at user defined ambient temperature with 42% weightingC = EER at 50% at user defined ambient temperature with 45% weightingD = EER at 25% at user defined ambient temperaturewith 12% weighting

2. NPLV is defined using the input design condit ions, outside of AHRI conditions at 100% full load.

3. NPLV and/or NPLV may not be reflective of local climate conditions. The Customized Part

Load Value Calculation may provide a more accurate measure of part load efficiency.

Page 20: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 1

Performance Climate Changer

Job Information Name Job01 (Restored) Tag CSAA-1 Address Quantity 1 Sales Team Model Number CSAA035UA Comments

H C H

Unit level options Fuse size circuit 2 45.00 A Fuse size circuit 1 90.00 A Available Sds (based on IBC 2006 & 2009)

No Number of marine LED lights

0 Lights

Comp #1 circuit number

1 MOP circuit 2 47.25 A

MOP circuit 1 90.00 A Single or front discharge - 1K Hz

88 dB

Single or front discharge - 500 Hz

91 dB Single or front discharge - 250 Hz

89 dB

Single or front discharge - 125 Hz

95 dB Single or front discharge - 63 Hz

98 dB

Circuit number 2 Exhaust fan motor(s) Circuit number 1 Supply fan motor(s) Single or front discharge - 8K Hz

77 dB Single or front discharge - 4K Hz

81 dB

Single or front discharge - 2K Hz

85 dB Component #2 Exhaust fan motor(s)

Component #1 Supply fan motor(s) Casing - 250 Hz 80 dB Casing - 125 Hz 86 dB Casing - 63 Hz 99 dB Integral base frame 2.5in. integral base

frame Ducted inlet - 8K Hz 67 dB

Ducted inlet - 4K Hz 71 dB Ducted inlet - 2K Hz 73 dB Ducted inlet - 1K Hz 74 dB Ducted inlet - 500 Hz 76 dB Ducted inlet - 250 Hz 74 dB Ducted inlet - 125 Hz 78 dB Ducted inlet - 63 Hz 94 dB Casing - 8K Hz 56 dB Casing - 4K Hz 49 dB Casing - 2K Hz 67 dB Casing - 1K Hz 88 dB Casing - 500 Hz 93 dB Comp #2 voltage/phase/hertz

460/3/60 Comp #1 voltage/phase/hertz

460/3/60

Roof curb weight 0.0 lb Comp #2 FLA 21.00 A Comp #1 FLA 40.00 A Comp #2 circuit

number 2

MCA circuit 1 50.00 A Rigging weight 7601.6 lb Width 100.000 in Length 285.875 in MCA circuit 2 26.25 A Installed weight 7922.2 lb FLA (CV) circuit 2 21.00 A FLA (CV) circuit 1 40.00 A

Controls and VFD/starter Factory controls package

No factory mount Controller mounting No mount

LCD screen and keypad No LCD Controller type No controller Prepackaged solution option used

MP common configuration not used

Page 21: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 2

Fan section Inlet and casing - 63 Hz 97 dB Inlet and casing - 8K

Hz 77 dB

Inlet and casing - 4K Hz

79 dB Inlet and casing - 2K Hz

81 dB

Inlet and casing - 1K Hz

81 dB Inlet and casing - 500 Hz

83 dB

Inlet and casing - 250 Hz

80 dB Inlet and casing - 125 Hz

87 dB

Motor class NEMA premium compliant ODP

Ducted inlet - 63 Hz 93 dB

Casing - 8K Hz 54 dB Casing - 4K Hz 47 dB Casing - 2K Hz 64 dB Casing - 1K Hz 84 dB Casing - 500 Hz 87 dB Casing - 250 Hz 74 dB Casing - 125 Hz 82 dB Casing - 63 Hz 94 dB Elevation 0.00 ft Ducted inlet - 8K Hz 67 dB Ducted inlet - 4K Hz 71 dB Ducted inlet - 2K Hz 73 dB Ducted inlet - 1K Hz 74 dB Ducted inlet - 500 Hz 76 dB Ducted inlet - 250 Hz 73 dB Ducted inlet - 125 Hz 77 dB Unit static efficiency 18.19 % Total brake horsepower

at min temp 15.588 hp

Total brake horsepower 14.705 hp Speed 784 rpm Design temperature 70.00 F Fan discharge loss

pressure drop 0.000 in H2O

Fan outlet velocity 3879 ft/min Fan module pressure drop

1.000 in H2O

Total static pressure 1.000 in H2O Outlet area 4.38 sq ft NEMA nominal motor efficiency

93.00 % Motor hertz 60.00 Hz

Fan size and type 20in. diameter FC, class 1

Starter/VFD - factory mounted & wired

None

Section weight 1931.0 lb Section height 67.250 in Section width 100.000 in Section length 63.750 in Fan airflow 17000 cfm Motor voltage 460/3 Motor horsepower per fan

15 hp Motor RPM 1800

Single or front discharge - 8K Hz

81 dB Single or front discharge - 4K Hz

86 dB

Single or front discharge - 2K Hz

88 dB Single or front discharge - 1K Hz

89 dB

Single or front discharge - 500 Hz

91 dB Single or front discharge - 250 Hz

90 dB

Single or front discharge - 125 Hz

95 dB Single or front discharge - 63 Hz

101 dB

Air mixing section Opening 1 top - airflow 17000 cfm Opening 1 front -

airflow 17000 cfm

Opening 1 back - airflow

17000 cfm Opening 1 back - pressure drop

0.252 in H2O

Opening 1 top - face velocity

1159 ft/min Opening 1 back - face velocity

1187 ft/min

Opening 1 top - area 14.66 sq ft Opening 1 front - area 40.50 sq ft Opening 1 back - area 14.32 sq ft Opening 1 top -

pressure drop 0.000 in H2O

Opening 1 top total pressure drop

0.000 in H2O Opening 1 back total pressure drop

0.252 in H2O

Greatest entry PD 0.252 in H2O Total mixing section pressure drop

0.252 in H2O

Air mixing section Opening 1 top - airflow 17000 cfm Opening 1 front -

airflow 17000 cfm

Opening 1 back - airflow

17000 cfm Opening 1 back - pressure drop

0.252 in H2O

Opening 1 top - face 1187 ft/min Opening 1 back - face 1187 ft/min

Page 22: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 3

velocity velocity Opening 1 top - area 14.32 sq ft Opening 1 front - area 40.50 sq ft Opening 1 back - area 14.32 sq ft Opening 1 top -

pressure drop 0.115 in H2O

Opening 1 top total pressure drop

0.115 in H2O Opening 1 back total pressure drop

0.252 in H2O

Filter pressure drop 0.709 in H2O Filter face velocity 268 ft/min Filter area 63.33 sq ft Filter airflow 17000 cfm Greatest entry PD 0.252 in H2O Total mixing section

pressure drop 0.960 in H2O

Coil section Corrosion resistant coating

None Tube diameter 5/8in. tube diameter (15.875 mm)

Tube matl/wall thickness

.020" (0.508mm) copper tubes

Coil height Unit coil height

Coil face velocity 521 ft/min Coil face area 32.63 sq ft Unit airflow 17000 cfm Coil performance

airflow 17000 cfm

Coil installed weight 171.2 lb Coil rigging weight 128.5 lb Coil section pressure drop

0.083 in H2O Air pressure drop 0.083 in H2O

Section weight 398.2 lb Section height 67.250 in Section width 100.000 in Section length 10.000 in Rows 1 row Coil type 5W System type Hot water Entering dry bulb 45.00 F Leaving dry bulb 78.00 F Nominal height coil # 1 54 in. (1372 mm) Fin type Prima flo H (Hi

efficient) Fin material Aluminum fins

Fin spacing 89 Per Foot J trap dimension 2.018 in H trap dimension 4.035 in Fluid pressure drop 7.30 ft H2O Standard fluid flow rate 60.76 gpm Fluid temperature drop 20.00 F Leaving fluid temperature

160.00 F Entering fluid temperature

180.00 F

Coil fluid percentage 100.00 % Fluid type Water Total cap coil #1 608.40 MBh Total capacity 608.40 MBh Coil fouling factor 0.00050 hr-sq ft-deg

F/Btu Fluid volume 5.12 gal

Fluid velocity 3.73 ft/s

Access section Section width 100.000 in Section length 14.000 in Section weight 242.0 lb Section height 67.250 in

Coil section Corrosion resistant coating

None Tube diameter 1/2in. tube diameter (12.7 mm)

Tube matl/wall thickness

.016" (0.406mm) copper tubes

Coil height Unit coil height

Coil face velocity 487 ft/min Coil face area 34.94 sq ft Unit airflow 17000 cfm Coil performance

airflow 17000 cfm

Coil installed weight 644.6 lb Coil rigging weight 456.9 lb Coil section pressure drop

0.637 in H2O Air pressure drop 0.637 in H2O

Section weight 883.6 lb Section height 67.250 in Section width 100.000 in Section length 14.000 in Rows 6 rows Coil type UW System type Chilled water Entering dry bulb 80.00 F Leaving wet bulb 54.36 F Leaving dry bulb 55.00 F Nominal height coil # 1 57 in. (1448 mm) Fin type Delta flo H (Hi

efficient) Fin material Aluminum fins Fin spacing 92 Per Foot J trap dimension 2.336 in H trap dimension 4.672 in Fluid pressure drop 18.65 ft H2O Standard fluid flow rate 132.24 gpm Fluid temperature rise 10.00 F Leaving fluid 55.00 F

Page 23: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 4

temperature Entering fluid temperature

45.00 F Coil fluid percentage 100.00 %

Fluid type Water Entering wet bulb 67.00 F Total capacity 663.51 MBh Sensible capacity 468.49 MBh Coil fouling factor 0.00000 hr-sq ft-deg

F/Btu Fluid volume 22.44 gal

Fluid velocity 5.04 ft/s

Access section Section width 100.000 in Section length 14.000 in Section weight 242.0 lb Section height 67.250 in

Coil section Corrosion resistant coating

None Tube diameter 5/8in. tube diameter (15.875 mm)

Tube matl/wall thickness

.020" (0.508mm) copper tubes

Coil height Unit coil height

Coil face velocity 521 ft/min Coil face area 32.63 sq ft Unit airflow 17000 cfm Coil performance

airflow 17000 cfm

Coil installed weight 335.4 lb Coil rigging weight 245.1 lb Coil section pressure drop

0.139 in H2O Air pressure drop 0.139 in H2O

Section weight 562.4 lb Section height 67.250 in Section width 100.000 in Section length 10.000 in Rows 2 rows Coil type 5W System type Hot water Entering dry bulb 55.00 F Leaving dry bulb 104.00 F Nominal height coil # 1 54 in. (1372 mm) Fin type Prima flo E (energy

efficient) Fin material Aluminum fins

Fin spacing 90 Per Foot J trap dimension 2.405 in H trap dimension 4.811 in Fluid pressure drop 3.23 ft H2O Standard fluid flow rate 90.22 gpm Fluid temperature drop 20.00 F Leaving fluid temperature

160.00 F Entering fluid temperature

180.00 F

Coil fluid percentage 100.00 % Fluid type Water Total cap coil #1 903.39 MBh Total capacity 903.39 MBh Coil fouling factor 0.00050 hr-sq ft-deg

F/Btu Fluid volume 10.85 gal

Fluid velocity 2.77 ft/s

Fan section Inlet and casing - 63 Hz 98 dB Inlet and casing - 8K

Hz 65 dB

Inlet and casing - 4K Hz

65 dB Inlet and casing - 2K Hz

72 dB

Inlet and casing - 1K Hz

75 dB Inlet and casing - 500 Hz

83 dB

Inlet and casing - 250 Hz

81 dB Inlet and casing - 125 Hz

88 dB

Motor class NEMA premium compliant ODP

Ducted inlet - 63 Hz 89 dB

Casing - 8K Hz 53 dB Casing - 4K Hz 46 dB Casing - 2K Hz 64 dB Casing - 1K Hz 87 dB Casing - 500 Hz 92 dB Casing - 250 Hz 79 dB Casing - 125 Hz 85 dB Casing - 63 Hz 98 dB Elevation 0.00 ft Ducted inlet - 8K Hz 46 dB Ducted inlet - 4K Hz 55 dB Ducted inlet - 2K Hz 63 dB Ducted inlet - 1K Hz 66 dB Ducted inlet - 500 Hz 69 dB Ducted inlet - 250 Hz 69 dB Ducted inlet - 125 Hz 74 dB Unit static efficiency 50.61 % Total brake horsepower

at min temp 27.000 hp

Total brake horsepower 25.470 hp Speed 1045 rpm Design temperature 70.00 F Fan discharge loss

pressure drop 0.000 in H2O

Page 24: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 5

Fan outlet velocity 3067 ft/min Fan module pressure drop

3.000 in H2O

Total static pressure 4.819 in H2O Outlet area 5.54 sq ft NEMA nominal motor efficiency

94.10 % Motor hertz 60.00 Hz

Fan size and type 22in. diameter FC, class 2

Starter/VFD - factory mounted & wired

None

Section weight 2196.0 lb Section height 67.250 in Section width 100.000 in Section length 63.750 in Fan airflow 17000 cfm Motor voltage 460/3 Motor horsepower per fan

30 hp Motor RPM 1800

Single or front discharge - 8K Hz

77 dB Single or front discharge - 4K Hz

81 dB

Single or front discharge - 2K Hz

85 dB Single or front discharge - 1K Hz

88 dB

Single or front discharge - 500 Hz

91 dB Single or front discharge - 250 Hz

89 dB

Single or front discharge - 125 Hz

95 dB Single or front discharge - 63 Hz

98 dB

Page 25: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 6

OPENING AND DIM ENSIONS MAY VARY FROM CONTRACT DOCUMENTS / RETURN OF APPROVED DRAWINGS CONSTITUT ES ACCEPTANCE OF THESE VARIANCES / NOT TO SCALE

Unit size: 35Product group: Indoor uni tIntegral base frame: 2.5in. integra l base framePaint: Unpain ted/field painted outdoor

Job Name: Job01 (Restored)Actual airflow: 17000 cfmSales Office:

Unit Casing: 2 in Double Wall Proposal Number: Tags: CSAA-1Rigging/Instal led Weight: 7601.6 lb/ 7922.2 lb

Performance Climate ChangerAir Handlers

22"20"20"10"10"22"15 1/2

69

46 1 /4

25 3/8

16 3/4

66 1/2

46 1/4

28 3/8100 1

23 4 5 6

7 8

910

2 2 1/217 5/8

34 1/4

23 3/4

25 3/8

18 1/8 28 3/8 72 3/831 3/4118 1/234 1/4

1.25" N.P.T.E

1.25" N.P.T.E

1.25" N.P.T.E

12

63 7/8Ship Spl it1931 lbs

96 1/8Ship Split1467 lbs

62 1/8Ship Split2328 lbs

63 7/8Ship Split2196 lbs

285 7/8

67 1/4

1 2 3 4 5 6 7 8 9 10 1112

Housed fan - 22 in.diameter FC, class 2Supply fan 30 hp 460/3TPFT dis charge opening28.400 x 28.400Heating coil - 2 rows Coiltype 5WCooling coi l - 6 rows Coi ltype UWHeating coil - 1 row Coiltype 5WDamper top-paral lel blade34.250 x 69.000Damper back-parallelblade34.250 x 69.000 (2)Opening top31.750 x 66.500Housed fan - 20 in.diameter FC, class 1Exhaust fan 15 hp 460/3BKTP discharge opening25.370 x 25.3701.25" N.P.T.EAngled fil te rs - Doors22 width x 61 height 10 w idth x 61 height 20 w idth x 61 height

For maneuvering purposes, include 1.125 inches to each ship split length for overlapping panel flange. Flange will not add to overall installed unit length shown.

Page 26: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 7

OPENING AND DIMENSIONS M AY VARY FRO M CONTRACT DO CUMENTS / RETURN O F APPROVED DRAWING S CONSTIT UTES ACCEPT ANCE O F T HESE VARIANCES / NOT TO SCALE

Unit size: 35

Product group: Indoor unitIntegral base frame: 2.5in. integral base f rame

Paint: Unpain ted/field pa inted outdoor

Job Name: Job01 (Restored)Actual airflow: 17000 cfmSales Office:

Unit Casing: 2in Double Wall

Proposal Number: Tags: CSAA-1Rigging/Installed Weight : 7601.6 lb/ 7922.2 lb

Performance Climate ChangerAi r Handlers

Pos #123456789

ModuleFan sectionAir mixing sectionAir mixing sectionCoil sectionAccess sectionCoil sectionAccess sectionCoil sectionFan section

Length63 7/848 1/848 1/810 1/814 14 14 10 1/863 7/8

Weight1931.00683.00784.00398.19242.00883.56242.00562.442196.00

Installed Unit Weight 7922.19 lbs

12345678910

0

Basic Overall Plan View: Top - Measurements in inches

S1S2S3S4

2 2 1/2

123456789

285 7/8

67 1

/4

Overall Elevation View: Right - Shipping splits indicated by bold outline. - Measurements in inches

For maneuvering purposes, incl ude 1.125 inches to each ship split length for overl apping panel fl ange. Flange will not add to overall instal led unit length shown.

Page 27: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 8

OPENING AND DIMENSIONS M AY VARY FRO M CONTRACT DO CUMENTS / RETURN O F APPROVED DRAWING S CONSTIT UTES ACCEPT ANCE O F T HESE VARIANCES / NOT TO SCALE

Unit size: 35

Product group: Indoor unitIntegral base frame: 2.5in. integral base f rame

Paint: Unpain ted/field pa inted outdoor

Job Name: Job01 (Restored)Actual airflow: 17000 cfmSales Office:

Unit Casing: 2in Double Wall

Proposal Number: Tags: CSAA-1Rigging/Installed Weight : 7601.6 lb/ 7922.2 lb

Performance Climate ChangerAi r Handlers

123456789

51 3/47 3/47 1/451 3/4

18 1/8

31 3

/4

34

1/4

28 3

/8

63 7/848 1/848 1/810 1/814

14 14

10 1/863 7/8

3.563 dia elec con(NEMA)3.563 dia elec con(NEMA)

3 5/

8

15

1/2

16 3

/4

46 1/4

10 3/4 10 3/4

66 1

/2

69 2

8 3/

8

100

Right Side of Unit Detailed Plan View: Top - Measurements in inches

123456789

63 7/848 1/848 1/810 1/814 14

14 10 1/863 7/8

Left Side of Unit Detailed Plan View: Bottom - Measurements in inches

Page 28: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 9

OPENING AND DIMENSIONS M AY VARY FRO M CONTRACT DO CUMENTS / RETURN O F APPROVED DRAWING S CONSTIT UTES ACCEPT ANCE O F T HESE VARIANCES / NOT TO SCALE

Unit size: 35

Product group: Indoor unitIntegral base frame: 2.5in. integral base f rame

Paint: Unpain ted/field pa inted outdoor

Job Name: Job01 (Restored)Actual airflow: 17000 cfmSales Office:

Unit Casing: 2in Double Wall

Proposal Number: Tags: CSAA-1Rigging/Installed Weight : 7601.6 lb/ 7922.2 lb

Performance Climate ChangerAi r Handlers

1 2 3 4 5 6 7 8 9

63 7/8 48 1/8 48 1/810 1/8

14 14 14 10 1/8

63 7/82 2 1/2

67 1

/4

Detailed Elevation View: Left - Measurements in inches

2 2 1/2 3 3

/8

4 1/4

17 5/8

60 1

/2

34 1

/4

123456789

7 7/8

7 3/4

13 3/42 1/8

7 1/4

4 7/82 1/8

6 7/8

2 1/84 7/8

7 7/822"

31 3

/4

20"20"

34 1

/4

10"

10"

22"

1.25" N.P.T.E

1.25" N.P.T.E

1.25" N.P.T.E

285 7/8

67 1

/4

Detailed Elevation View: Right - Measurements in inches

Page 29: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 10

OPENING AND DIM ENSIONS MAY VARY FROM CONTRACT DOCUMENTS / RETURN OF APPROVED DRAWINGS CONSTITUT ES ACCEPTANCE OF THESE VARIANCES / NOT TO SCALE

Unit size: 35Product group: Indoor uni tIntegral base frame: 2.5in. integra l base framePaint: Unpain ted/field painted outdoor

Job Name: Job01 (Restored)Actual airflow: 17000 cfmSales Office:

Unit Casing: 2 in Double Wall Proposal Number: Tags: CSAA-1Rigging/Instal led Weight: 7601.6 lb/ 7922.2 lb

Performance Climate ChangerAir Handlers

1 2 3 4 5 6 7 8 9

63 7/8 48 1/8 48 1/810 1/8

14 14 14 10 1/8

63 7/8

67 1

/4

285 7 /8

67

1/4

Co il connection view: Left - Measurements in inches

NPT I : Nati onal Pi pe Thread Internal Connect ionNPT E : Nat ional Pipe T hread External Connecti on

Page 30: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 11

OPENING AND DIM ENSIONS MAY VARY FROM CONTRACT DOCUMENTS / RETURN OF APPROVED DRAWINGS CONSTITUT ES ACCEPTANCE OF THESE VARIANCES / NOT TO SCALE

Unit size: 35Product group: Indoor uni tIntegral base frame: 2.5in. integra l base framePaint: Unpain ted/field painted outdoor

Job Name: Job01 (Restored)Actual airflow: 17000 cfmSales Office:

Unit Casing: 2 in Double Wall Proposal Number: Tags: CSAA-1Rigging/Instal led Weight: 7601.6 lb/ 7922.2 lb

Performance Climate ChangerAir Handlers

1 2 3 4 5 6 7 8 9

63 7/8 48 1/8 48 1/810 1/8

14 14 14 10 1/8

63 7/8

67 1

/4

285 7 /8

67

1/4

Co il connection view: Left - Measurements in inches

NPT I : Nati onal Pi pe Thread Internal Connect ionNPT E : Nat ional Pipe T hread External Connecti on

Page 31: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 12

6 48

59

61

A (

filte

r, g

as h

eat)

Cle

aran

ce it

em

s

VFD

- s

how

n)

B (

coil,

hum

idifi

er)

D (

Ext

ern

al

Sta

rter

or

C (

UV

Lig

hts)

483

484

48

61

59

61

8 48

10 48

12 48

66

61

77

82

61

61

17 48

14 48

21 48

87

61

87

61

95

64

66 52

156 64

48

128

25 48

30 48

35 48

95

109

64

64

115 64

4050 4

8

57 48

141

64

64

141

64

80 56

100

58

120

58

156 64

170

197

64

64

48 8948 56

Ext

Ves

tible

)

Int

Ves

tible

) F

(G

as

Hea

t

Sta

rter

or

E (

fan

)

F (

Ga

s H

eat

VF

D)

48 N/A

48

48 48 N/A

N/A

N/A

100

48 48 90

48 51

48 54

108

6374

79

48 10561

48 58 100

48 60 115

8484

92

48 17093 153

140

125

48 66

48 66

115

118

48 66 136

9210

61

12

48 70

48 77 156

48 77 156

138

138

N/A

48 93 179

48 101

48 101

180

153

167

194

VF

D

59

C (T

CA

C)

43

59

63

75

81

83

83

58

83

58

83

75

83

83

83

83

75

83

5256

5858

57 48

110

64

48 66 N/A

N/A83

48

48

48

48

48

48

48

48

48

48

48

48

48

48

48

48

50 48

110

64

48 66 N/A

N/A83

48

48

96

40 64

N/A

N/A

48 608348

48

9635 64

N/A

N/A48 6059

48

30 48

87

64

48 58 N/A

N/A83

48

25 48

77

64

48 51 N/A

N/A75

48

21 48

77

64

48 51 N/A

N/A75

48

TA

LL

TA

LL

TA

LL

TA

LL

TA

LL

TA

LL

TA

LL

Gas

he

at

Ac

ces

sd

oo

r

F

E

Filt

er

mix

ing

bo

x

No

te:

At

a m

inim

um

, th

e b

elo

w c

lear

ance

dim

ensi

ons

are

rec

omm

en

ded

on

on

e s

ide

of

the

uni

t fo

r re

gula

rs

ervi

ce

an

d m

aint

en

ance

. R

efe

r to

as

-bui

lt su

bm

itta

lfo

r lo

catio

ns

of i

tem

s su

ch a

s fi

lter

acc

ess

do

ors,

coi

l, p

ipin

g c

onn

ectio

ns, m

oto

r lo

cat

ion

s, e

tc.

Suf

fici

en

t cle

ara

nce

mus

t be

pro

vide

d o

n a

ll si

des

of

un

it fo

r re

mov

al o

f p

ane

ls o

r se

ctio

n-t

o-s

ect

ion

att

achm

ent

. C

lear

an

ce fo

r st

art

ers

, V

FD

s, o

r o

the

rh

igh

-vo

ltag

e d

evic

es m

ust

be

pro

vid

ed

per

NE

Cre

qu

irem

en

ts.

D

CB

A

Co

il

UV

Lig

hts

or

TC

AC

Fan

Page 32: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 13

Base Detail

6"

Page 33: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 14

GENERAL Lifting Instructions T he ai r handl ing un i ts must be rigged, l i fted, and instal led in strict accordance wi th the Instal la tion, Operation, and M aintenance manual (CLCH-SVX07B-EN). The uni ts are a lso to be insta lled in strict accordance with the speci fications. Uni ts m ay be shipped fu lly assem bled or d isassem bled to the min imum functional section size in accordance with sh ipp ing and job si te requi rem ents. Indoor uni ts shal l be sh ipped on an integra l base frame (variab le from the standard 2.5" to 8" height) for the purpose of m ounting uni ts to a housekeeping pad and provid ing addi tional height to properly trap condensate from the unit. The

in tegra l base fram e may be used for ce i l ing suspension, external iso lation, or as a housekeeping pad. Indoor sizes 3 to 30 wi ll a lso be sh ipped wi th a sh ipp ing skid designed for forkl i ft transport. Refer to the un it As-Bui l t or Product Data section of the submi ttal for the base fram e height of each uni t. A l l uni ts wi l l be sh ipped wi th an integra l base frame designed wi th the necessary number of l i ft po in ts for safe instal la tion. A l l l i fting lugs are to be uti l ized during l i ft. The l i ft poin ts wi ll be designed to accept standard rigg ing devices and be removable after insta lla tion. Uni ts sh ipped in sections wil l have a minim um of four poin ts o f l i ft.

Per ASHRAE 62.1 recomm endation, indoor a i r handl ing un its wi l l be sh ipped stre tch-wrapped to protect un i t from in-transi t ra in and debris. Insta l ling contractor is responsible for long term storage in accordance wi th the Insta l lation, Operation, and Maintenance m anual (CLCH-SVX07B-EN).

Uni t shall be UL and C-UL Listed. A i r-handling perform ance data shal l be certified in accordance wi th AHRI Standard 430. Uni t sound performance data shal l be provided using AHRI Standard 260 test methods and reported as sound power. T rane, in providing this program and data, does not certi fy or warrant NC leve ls. T hese leve ls are affected by factors speci fic to each appl ication and/or insta l la tion and therefore unable to be predicted or certi fied by T rane.

Coi l performance shall be certi fied in accordance wi th AHRI Standard 410. Unit Construction A l l uni t panels shal l be 2" sol id, double-wal l construction to facil i tate cleaning of un i t in terior. Uni t panels shal l be provided wi th a m id-span, no-through-m eta l , in terna l therm al break. Casing therm al performance shall be such that under

55°F supply a i r temperature and design condi tions on the exterior of the un i t o f 81°F dry bu lb and 73°F wet bu lb, condensation shal l not form on the casing exterior. A l l exterior and in terior indoor AHU panels wi l l be m ade of ga lvanized stee l . Unit Paint

Uni t to ship unpainted from factory. Uni t to be painted by 3rd party finisher, or by pa inting contractor at job site . Casing Deflection T he casing shal l not exceed 0.0042 inch deflection per inch of panel span at 1 .5 tim es design sta tic pressure up to a m aximum of +8 inches w.g. in al l positive pressure sections and -8 inches w.g. in a ll negative pressure sections.

T he uni t floor shall be of sufficient strength to support a 300-lb load during maintenance activi ties and shal l deflect no m ore than 0.0042 inch per inch of panel span. Insulation

Page 34: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 15

Panel insu lation shal l provide a min imum thermal resistance (R) value of 13 ft²-h-ºF/Btu throughout the enti re un i t. Insu lation shal l completely fi l l the panel cavi ties in a ll d irections so that no vo ids exist and settl ing of insula tion is prevented. Panel insula tion shal l comply wi th NFPA 90A.

Drain Pan A l l coo l ing co i l sections shall be provided with an insulated, double-wal l , galvanized or sta inless stee l drain pan. To address indoor a i r qual i ty (IAQ), the dra in pan shall be designed in accordance wi th ASHRAE 62.1 be ing of sufficient size to co llect a l l condensation produced from the co i l and sloped in two planes prom oting posi tive drainage to el iminate stagnant water condi tions. The outle t shal l be located at the lowest po int o f the pan and shal l be sufficient diameter to preclude drain pan overflow under any normal ly expected operating condi tion. A l l drain pan threaded connections shal l be visib le external to the uni t. Drain connections shall be of the sam e m ateria l as the prim ary dra in pan and shal l extend

a minim um of 2-1/2" beyond the base to ensure adequate room for field p iping of condensate dra in traps. Coi l support m em bers inside the dra in pan shall be of the sam e m ateria l as the drain pan and co i l casing. Refer to Product Data for speci fic inform ation on which sections are supplied wi th a drain pan, the dra in pan m ateria l and connection location. Access Door Construction Access doors shal l be 2" double-wal l construction. In terior and exterior door panels shal l be of the same construction as the interior and exterior wal l panels, respective ly. A l l doors shal l be provided wi th a thermal break construction of door panel and door fram e. Gasketing shal l be provided around the fu l l perimeter o f the doors to prevent ai r leakage. Surface-mounted handles shal l be provided to al low quick access to the in terior o f the functional section and to prevent through-cabinet penetrations that could like ly weaken the casing leakage and thermal perform ance. Handle hardware shal l be designed to prevent unin tended closure. Access doors shal l be hinged and rem ovable for qu ick, easy access. Hinges shal l be in terchangeable wi th the door handle hardware to a l low for a l ternating door swing in the fie ld to min imize

access interference due to unforeseen job si te obstructions. Door handle hardware shal l be ad justab le and visual ly indicate locking posi tion of door latch external to the section. A l l doors shal l be a min imum of 60" high when sufficient height is avai lab le, or the maximum height al lowed by the un i t height. Door handles shal l be provided for each la tch ing point o f the door necessary to m aintain the speci fied a i r leakage in tegri ty

o f the uni t. Optional ly for indoor AHUs and as standard on outdoor AHUs, outward swing doors are provided wi th a single handle l inked to mul tip le la tch ing po ints. Uni t doors may a lso be provided wi th an optional shatterproof window for viewing, capable of wi thstanding uni t operating pressures. Refer to Product Data for speci fic inform ation on which sections are supplied wi th an access door, the door location, a sing le handle, and a window. M IXING SECTION A mixing section shal l be provided to support the damper assembly for outdoor, re turn, and/or exhaust a i r. Dampers Dam pers shal l modulate the volume of outdoor, return, or exhaust a i r. T he dampers shal l be of double-skin ai rfoi l design wi th metal , compressib le jamb seals and extruded-vinyl blade-edge seals on a l l b lades. The b lades shal l ro tate on stain less-steel sleeve bearings. T he dam pers shal l be ra ted for a maximum leakage rate of 4 cfm/ft² a t 1 in. w.g. complying wi th ASHRAE 90.1 m aximum damper leakage. A ll leakage testing and pressure ratings shall be based on AMCA Standard

500-D. Dampers may be arranged in a para lle l or opposed-blade configuration. Dampers Dam pers shal l modulate the volume of outdoor, return, or exhaust a i r. T he dampers shal l be of double-skin ai rfoi l design wi th metal , compressib le jamb seals and extruded-vinyl blade-edge seals on a l l b lades. The b lades shal l ro tate on stain less-steel sleeve bearings. T he dam pers shal l be ra ted for a maximum leakage rate of 4 cfm/ft² a t 1 in. w.g. complying

wi th ASHRAE 90.1 m aximum damper leakage. A ll leakage testing and pressure ratings shall be based on AMCA Standard 500-D. Dampers may be arranged in a para lle l or opposed-blade configuration. Filters

Page 35: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 16

M ixing sections shal l be provided wi th a fi l ter rack as ind icated in the Product Data and As-Bui l t sections of the submi tta l . 4-inch h igh-efficiency fi l ters constructed wi th a fine fiber media m ade in to closely spaced p leats shal l be provided. T he

fi l ters shal l be capable of operating up to 625 fpm face ve loci ty wi thout loss of fi l ter e fficiency and hold ing capaci ty. The fi l ter media shal l be sealed in to a frame assem bled in a rig id manner. The m anufacturer shal l supply a side-access fi lter rack capable of hold ing 4-inch high-efficiency fil ters. COIL SECTION T he co i l section shal l be provided complete wi th co i l and coi l ho lding fram e. The co ils shall be insta lled such that headers and return bends are enclosed by uni t casings. If two or m ore cool ing coi ls are stacked in the un i t, an intermediate

drain pan shal l be insta l led between each coi l and be of the sam e m ateria l as the primary dra in pan. L ike the primary drain pan, the in term ediate drain pan shal l be designed being of sufficient size to co l lect a l l condensation produced from the coi l and sloped to prom ote posi tive dra inage to e lim inate stagnant water conditions. T he interm ediate pan shal l begin at the leading face of the water-producing device and be of sufficient length extending downstream to prevent condensate from passing through the a i r stream of the lower co il . In term ediate drain pan shal l include downspouts to d i rect condensate to the primary dra in pan. T he outlet shal l be located at the lowest po int of the pan and shal l be sufficient d iam eter to preclude drain pan overflow under any norm al ly expected operating condi tion.

Water Coils (UW, UU, UA, W, 5W, 5A, WD, 5D, D1, D2, P, or TT) T he co i ls shal l have aluminum fins and seamless copper tubes. Copper fins m ay be applied to co ils wi th 5 /8-inch tubes. Fins shall have co llars drawn, be l led, and fi rm ly bonded to tubes by mechanical expansion of the tubes. The coi l casing m ay be galvanized or stain less steel . Refer to the Product Data section of the submi ttal for the co i l casing materia l. T he co i ls shal l be proof-tested to 300 psig and leak-tested under water to 200 psig . Coi l performance data and co i ls

contain ing water or e thylene g lycol shal l be certi fied in accordance with AHRI Standard 410. Propylene glyco l and calcium chloride, or mixtures thereof, are outside the scope of AHRI Standard 410 and, therefore, do not requi re AHRI 410 ra ting or certi fication. Coi l header connections are constructed of cast i ron wi th female connections, stee l b lock wi th fem ale connections or stee l p ipe wi th m ale connections.

T ubes are 1/2" [13m m] OD 0.016" [0 .406m m] thick copper. T ubes are 5/8" [16m m] OD 0.020" [0 .508 m m] th ick copper. ACCESS/INSPECTION / TURNING SECTION A section shal l be provided to al low additional access/inspection of uni t components and space for field-instal led com ponents as needed. An access door shal l be provided for easy access. Al l access sections shall be com plete wi th a

double-wal l , removable door downstream for inspection, cleaning, and maintenance. In terior and exterior door panels shal l be of the same construction as the in terior and exterior wal l panels, respectively. A ll doors downstream of cool ing coi ls shall be provided with a thermal break construction of door panel and door fram e. FC FAN SECTION T he fan type shal l be provided as requi red for stable operation and optimum energy efficiency. T he fan shal l be a double-width, double-in let, multib lade-type, forward-curved (FC) fan. The fan shal l be equipped with se l f-a l ign ing,

anti friction bearings wi th an L-50 l ife of 200,000 hours as calcu la ted per ANSI/AFBM A Standard 9. For any bearing requi ring re lubrication, the grease l ine shal l be extended to the fan support bracket on the drive side. T he fan shall be statical ly and dynam ical ly ba lanced at the factory as a com plete fan assem bly (fan wheel, motor, drive, and belts). T he fan shaft shal l not exceed 75 percent of i ts fi rst cri tica l speed at any cata loged speed. Fan wheels shal l be keyed to the fan shaft to prevent sl ipp ing. T he fan shafts shall be sol id steel . The fan section shal l be provided wi th an access door on the drive side of the fan. Fan perform ance shal l be certi fied as complying with AHRI Standard 430.

M otor Frame

Page 36: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 17

T he motor shall be mounted integra l to the iso la ted fan assem bly and furn ished by the uni t manufacturer. The m otor is m ounted inside the uni t casing on an adjustab le base to perm i t adjustm ent of drive bel t tension (not applicable for d i rect drive p lenum fans). The m otor shal l meet or exceed al l NEMA Standards Publ ication M G 1 requi rem ents and comply wi th NEM A Premium efficiency levels when applicable except for fractional horsepower m otors which are not covered by the

NEM A classification. T he motor shal l be T -frame, squi rrel cage wi th size, type, and e lectrical characteristics as shown on the equipm ent schedule. Refer to the Product Data section for se lected fan motors wi thin each uni t. Two-Inch Spring Isolators T he fan and m otor assembly (on sizes 10 to 120) shal l be in terna l ly isola ted from the uni t casing wi th 2-inch (50.8 mm) deflection spring iso lators, furn ished and insta l led by the un it manufacturer. T he isola tion system shal l be designed to resist

loads produced by external forces, such as earthquakes, and conform to the current IBC seismic requi rem ents. Driv e Serv ice Factor T he drives shall be constant speed wi th fixed-p itch sheaves. T he drives shall be selected at a min im um 50 percent larger than the m otor brake horsepower (1.5 service factor).

Page 37: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 18

CSAA-1 - Overall Unit Acoustics

63Hz 125Hz 250Hz 500Hz 1 kHz 2 kHz 4 kHz 8 kHz

Discharge 98 95 89 91 88 85 81 77Casing 99 86 80 93 88 67 49 56

Ducted Inlet 94 78 74 76 74 73 71 67

Page 38: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 19

5.

00

h

p

7.5

0 h

p

10

.0

0

hp

15

.00

h

p

20

.0

0

hp

500 RPM

600 RPM

700 RPM

800 RPM

900 RPM

1000 R PM

1050 RPM

25 %WO50 %WO

60 %WO

70 %WO

80 %WO

90 %WO

BHP adjusted 5% for approx imate driv e los sUnitSiz e: 20FA

Operating Air flow: 17000.00 cfmOperating Static Pres sure: 1.00 in H 2O

Operating RPM: 784.14 Operating Brake Power : 14.71 hp

Altitude: 0.00 ftDes ign Temp: 70.00 FMax BHP: 15.59 hpEfficiency : 18.19 %

Date: 3/25/13Datafile: C:\CDS\TOPSS\CSAA\Cs aa_fans.ran

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

0 5000 10000 15000 20000 25000

CSAA-1 - Exhaust Fan sec [1]-1Size 35 Horizontal Draw-Thru 20 inch FC Class 1 - Single Fan

To

tal

Sta

tic

Pre

ss

ur

e (

in H

2O

)

Airflow (cfm)

CSAA-1 - Exhaust Fan sec [1]-1Size 35 Horizontal Draw-Thru 20 inch FC Class 1

63Hz 125Hz 250Hz 500Hz 1 kHz 2 kHz 4 kHz 8 kHz

Discharge 101 95 90 91 89 88 86 81Inlet + Casing 97 87 80 83 81 81 79 77

Casing 94 82 74 87 84 64 47 54Ducted Inlet 93 77 73 76 74 73 71 67

Page 39: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

Page 20

5.

00

h

p

7.

50

h

p

10

.0

0

hp

15

.00

h

p

20

.0

0

hp

25

.0

0

hp

30

.0

0 h

p

500 R PM

600 RPM

700 RPM

800 R PM

900 RPM

1000 RPM

1100 RPM

1200 R PM

25 %WO 50 %WO

60 %WO

70 %WO

80 %WO

90 %W O

BHP adjusted 5% for approx imate driv e los sUnitSiz e: 22FB

Operating Airflow : 17000.00 cfmOperating Static Pres sure: 4.82 in H 2O

Operating R PM: 1044.84 Operating Brake Pow er: 25.47 hp

Altitude: 0.00 ftDesign Temp: 70.00 F

Max BHP: 27.00 hpEfficiency : 50.61 %

Date: 3/25/13Datafile : C :\CD S\TOPSS\CSAA\Cs aa_fans.ran

0

1

2

3

4

5

6

7

8

0 5000 10000 15000 20000 25000 30000 35000 40000

CSAA-1 - Supply Fan sec [9]-1Size 35 Horizontal Draw-Thru 22 inch FC Class 2 - Single Fan

To

tal

Sta

tic

Pre

ss

ur

e (

in H

2O

)

Airflow (cfm)

CSAA-1 - Supply Fan sec [9]-1Size 35 Horizontal Draw-Thru 22 inch FC Class 2

63Hz 125Hz 250Hz 500Hz 1 kHz 2 kHz 4 kHz 8 kHz

Discharge 98 95 89 91 88 85 81 77Inlet + Casing 98 88 81 83 75 72 65 65

Casing 98 85 79 92 87 64 46 53Ducted Inlet 89 74 69 69 66 63 55 46

Page 40: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

System ChecksumsBy HP ENGINEERING

Parallel Fan Powered VAV, Htg Coil on Mixing Box OutletLaboratory Room

HEATING COIL PEAKCLG SPACE PEAKCOOLING COIL PEAK TEMPERATURES

Heating DesignMo/Hr:7 / 13Mo/Hr:7 / 15Mo/Hr:Peaked at Time: Cooling Heating

SADBOADB: 13OADB:98 / 75 / 97OADB/WB/HR:Outside Air: 55.9 75.1

Ra Plenum 77.3 68.8

ReturnPercentCoil PeakSpace PeakSpace PercentPercentNetPlenumSpace 77.3 68.8Ret/OASens. + Lat. Of TotalTot SensSpace SensOf TotalSensibleOf TotalTotalSens. + Lat 56.8 79.5

0.0 0.2Fn MtrTDBtu/h (%)Btu/hBtu/h(%)Btu/h(%)Btu/hBtu/h 0.1 0.4Fn BldTDEnvelope Loads 0.2 1.1Fn Frict 0Skylite Solar 0.00 0 0 0 0 0 0 0

0Skylite Cond 0.00 0 0 0 0 0 0 0 0Roof Cond 24.05-2,792 0 0 0 17 4,829 4,829

0.00 0Glass Solar 0 0 0 0 0 0 0 0Glass/Door Cond 0 0.00 0 0 0 0 0 0

AIRFLOWS

HeatingCooling 1,904Wall Cond 27.29-3,168-2,152 14 2,107 10 2,761 856

0Partition/Door 0.00 0 0 0 0 0 0 0Floor 0.00 0 0 0 0 0

Sec Fan 0.00 0Infiltration 0 0 0 0 0 0

87 435MinStop/Rh

51.34 1,904Sub Total ==> -5,960-2,152 14 2,107 27 7,590 5,685

870Return 435

Internal Loads

93 93Exhaust

2,007Lights 0.00 0 0 13 2,007 9 2,509 502

0 0Rm Exh

4,410People 0.00 0 16 2,450 16

0 0Auxiliary

7,526Misc 0.00 0 0 49 7,526 27 7,526 0

13,943Sub Total ==> 0.00 0 0 79 11,983 52 14,444 502

1,228Ceiling Load 0.000-752 7 1,119 0 0-1,228 0Ventilation Load 51.48-5,975 0 0 0 18 4,966 0

Sup. Fan Heat 5 1,536

ENGINEERING CKS

HeatingCooling

Ret. Fan Heat 0 0 0 % OA 10.7 10.7

Duct Heat Pkup 0 0 0 0.59 1.18cfm/ft²

0Ov/Undr Sizing

0.00 0 0

0 0 0 0

372.65cfm/ton

Exhaust Heat

-2.82 327-2-534

314.98ft²/ton

-23.12 38.10Btu/hr·ft²

10No. People 17,075Grand Total ==> 100.00-11,608-2,904100.00 15,209100.00 28,002 4,425

AREAS HEATING COIL SELECTIONCOOLING COIL SELECTIONTotal Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Coil Airflow Ent LvgCapacityton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) °F°FcfmMBh

Floor 735 Main Htg -12.8 870 61.5 75.1 2.3 28.0 23.7 864 79.5 63.4 63.9 54.3 52.3 56.7Main ClgPart 0 Aux Htg 0.0 0.0 0.0 0 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Aux Clg

ExFlr 0-4.2Preheat 13.0 54.3 93 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Opt Vent

Roof 735 0 0Reheat -8.4 72.0 54.3 435

Wall 672 0 0Humidif 0.0 0 0.0 0.0 2.3 28.0TotalOpt Vent 0.0 0.0 0.0 0

-17.0Total

Envelope LoadsSkylite SolarSkylite CondRoof CondGlass SolarGlass/Door CondWall CondPartition/DoorFloor

InfiltrationSub Total ==>

LightsPeopleMisc

Sub Total ==>

Ceiling LoadVentilation Load

Additional Reheat

OA Preheat Diff.

Ov/Undr SizingExhaust Heat

RA Preheat Diff.

Grand Total ==>

Internal Loads

0

0 0

0.00 0.00 0.00

-534

Supply Air Leakage

96

Dehumid. Ov Sizing 0 0

Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0Leakage Ups

Leakage Dwn

0 0Infil

AHU Vent

Nom Vent

Main FanTerminal

Adjacent Floor

Diffuser

Supply Air Leakage

Underflr Sup Ht Pkup Underflr Sup Ht Pkup

Adjacent Floor 0 0 0 0

0 0

0 0 0

0 0

0 0 0 0

0 0.00

0 0.00

870

870 870

0

93

93

0

0

870

870 435

435

93

93

0

0

0 4,410 0

Int Door 0

Ext Door 0 0 0

TRACE® 700 v6.2.9 calculated at 03:29 PM on 03/25/2013Project Name: Redbird Smith

Dataset Name: Alternative - 1 System Checksums Report Page 1 of 3Redbird Smith Health Center.trc

Page 41: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

System ChecksumsBy HP ENGINEERING

Parallel Fan Powered VAV, Htg Coil on Mixing Box OutletNorth Zone

HEATING COIL PEAKCLG SPACE PEAKCOOLING COIL PEAK TEMPERATURES

Heating DesignMo/Hr:7 / 17Mo/Hr:7 / 15Mo/Hr:Peaked at Time: Cooling Heating

SADBOADB: 13OADB:98 / 75 / 97OADB/WB/HR:Outside Air: 55.1 75.3

Ra Plenum 79.1 68.1

ReturnPercentCoil PeakSpace PeakSpace PercentPercentNetPlenumSpace 79.1 68.1Ret/OASens. + Lat. Of TotalTot SensSpace SensOf TotalSensibleOf TotalTotalSens. + Lat 50.0 82.2

0.0 0.2Fn MtrTDBtu/h (%)Btu/hBtu/h(%)Btu/h(%)Btu/hBtu/h 0.1 0.4Fn BldTDEnvelope Loads 0.2 1.1Fn Frict 0Skylite Solar 0.00 0 0 0 0 0 0 0

0Skylite Cond 0.00 0 0 0 0 0 0 0 0Roof Cond 31.48-66,103 0 0 0 25 113,657 113,657

0.00 11,391Glass Solar 0 0 8 16,904 3 11,391 0 3,692Glass/Door Cond -8,771 4.18-8,771 2 3,572 1 3,692 0

AIRFLOWS

HeatingCooling 8,229Wall Cond 9.02-18,935-12,141 4 9,254 3 12,288 4,060

0Partition/Door 0.00 0 0 0 0 0 0 0Floor 0.00 0 0 0 0 0

Sec Fan 0.00 0Infiltration 0 0 0 0 0 0

1,185 5,924MinStop/Rh

44.68 23,311Sub Total ==> -93,808-20,911 14 29,731 31 141,027 117,716

11,847Return 5,924

Internal Loads

1,939 1,939Exhaust

48,137Lights 0.00 0 0 22 48,137 13 60,171 12,034

0 0Rm Exh

79,335People 0.00 0 20 44,075 18

0 0Auxiliary

60,171Misc 0.00 0 0 28 60,171 13 60,171 0

187,643Sub Total ==> 0.00 0 0 70 152,383 44 199,677 12,034

39,601Ceiling Load 0.000-22,041 17 36,156 0 0-39,601 0Ventilation Load 59.28-124,469 0 0 0 23 103,375 0

Sup. Fan Heat 5 20,774

ENGINEERING CKS

HeatingCooling

Ret. Fan Heat 0 0 0 % OA 16.4 16.4

Duct Heat Pkup 0 0 0 0.34 0.67cfm/ft²

0Ov/Undr Sizing

0.00 0 0

0 0 0 0

315.99cfm/ton

Exhaust Heat

-3.96 8,324-3-14,955

470.24ft²/ton

-15.50 25.52Btu/hr·ft²

176No. People 250,555Grand Total ==> 100.00-209,953-42,952100.00 218,270100.00 449,899 75,194

AREAS HEATING COIL SELECTIONCOOLING COIL SELECTIONTotal Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Coil Airflow Ent LvgCapacityton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) °F°FcfmMBh

Floor 17,630 Main Htg -188.1 11,849 60.7 75.3 37.5 449.9 366.1 11,686 82.2 64.8 66.1 53.4 51.7 55.6Main ClgPart 0 Aux Htg 0.0 0.0 0.0 0 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Aux Clg

ExFlr 0-85.3Preheat 13.0 53.4 1,939 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Opt Vent

Roof 17,630 0 0Reheat -119.7 72.0 53.4 5,924

Wall 4,548 504 11Humidif 0.0 0 0.0 0.0 37.5 449.9TotalOpt Vent 0.0 0.0 0.0 0

-273.4Total

Envelope LoadsSkylite SolarSkylite CondRoof CondGlass SolarGlass/Door CondWall CondPartition/DoorFloor

InfiltrationSub Total ==>

LightsPeopleMisc

Sub Total ==>

Ceiling LoadVentilation Load

Additional Reheat

OA Preheat Diff.

Ov/Undr SizingExhaust Heat

RA Preheat Diff.

Grand Total ==>

Internal Loads

0

0 0

0.00 0.00 0.00

-14,955

Supply Air Leakage

96

Dehumid. Ov Sizing 0 0

Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0Leakage Ups

Leakage Dwn

0 0Infil

AHU Vent

Nom Vent

Main FanTerminal

Adjacent Floor

Diffuser

Supply Air Leakage

Underflr Sup Ht Pkup Underflr Sup Ht Pkup

Adjacent Floor 0 0 0 0

0 0

0 0 0

0 0

0 0 0 0

0 0.00

0 0.00

11,847

11,847 11,847

0

1,939

1,939

0

0

11,849

11,849 5,924

5,924

1,939

1,939

0

0

0 79,335 0

Int Door 0

Ext Door 0 0 0

TRACE® 700 v6.2.9 calculated at 03:29 PM on 03/25/2013Project Name: Redbird Smith

Dataset Name: Alternative - 1 System Checksums Report Page 2 of 3Redbird Smith Health Center.trc

Page 42: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

System ChecksumsBy HP ENGINEERING

Parallel Fan Powered VAV, Htg Coil on Mixing Box OutletSouth Zone

HEATING COIL PEAKCLG SPACE PEAKCOOLING COIL PEAK TEMPERATURES

Heating DesignMo/Hr:10 / 14Mo/Hr:7 / 15Mo/Hr:Peaked at Time: Cooling Heating

SADBOADB: 13OADB:98 / 75 / 97OADB/WB/HR:Outside Air: 60.0 74.2

Ra Plenum 77.6 69.1

ReturnPercentCoil PeakSpace PeakSpace PercentPercentNetPlenumSpace 77.6 69.1Ret/OASens. + Lat. Of TotalTot SensSpace SensOf TotalSensibleOf TotalTotalSens. + Lat 58.9 79.7

0.0 0.2Fn MtrTDBtu/h (%)Btu/hBtu/h(%)Btu/h(%)Btu/hBtu/h 0.1 0.4Fn BldTDEnvelope Loads 0.2 1.1Fn Frict 0Skylite Solar 0.00 0 0 0 0 0 0 0

0Skylite Cond 0.00 0 0 0 0 0 0 0 0Roof Cond 33.04-67,351 0 0 0 26 115,433 115,433

0.00 31,034Glass Solar 0 0 32 77,340 7 31,034 0 7,471Glass/Door Cond -17,750 8.71-17,750 0 210 2 7,471 0

AIRFLOWS

HeatingCooling 8,341Wall Cond 8.14-16,585-9,663 3 6,474 3 13,933 5,592

0Partition/Door 0.00 0 0 0 0 0 0 0Floor 0.00 0 0 0 0 0

Sec Fan 0.00 0Infiltration 0 0 0 0 0 0

1,836 9,179MinStop/Rh

49.88 46,846Sub Total ==> -101,686-27,413 35 84,023 37 167,871 121,025

18,357Return 9,179

Internal Loads

1,674 1,674Exhaust

48,137Lights 0.00 0 0 20 48,137 13 60,171 12,034

0 0Rm Exh

55,479People 0.00 0 13 30,822 12

0 0Auxiliary

60,171Misc 0.00 0 0 25 60,171 13 60,171 0

163,787Sub Total ==> 0.00 0 0 58 139,130 39 175,821 12,034

31,337Ceiling Load 0.000-16,235 7 16,479 0 0-31,337 0Ventilation Load 52.71-107,456 0 0 0 20 89,602 0

Sup. Fan Heat 7 29,595

ENGINEERING CKS

HeatingCooling

Ret. Fan Heat 0 0 0 % OA 9.1 9.1

Duct Heat Pkup 0 0 0 0.52 1.04cfm/ft²

0Ov/Undr Sizing

0.00 0 0

0 0 0 0

486.63cfm/ton

Exhaust Heat

-2.60 5,293-2-10,217

467.36ft²/ton

-16.53 25.68Btu/hr·ft²

123No. People 241,970Grand Total ==> 100.00-203,848-43,648100.00 239,632100.00 452,673 91,505

AREAS HEATING COIL SELECTIONCOOLING COIL SELECTIONTotal Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Coil Airflow Ent LvgCapacityton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) °F°FcfmMBh

Floor 17,630 Main Htg -208.8 18,357 63.7 74.2 37.7 452.7 385.8 16,647 79.7 63.4 63.4 58.4 54.2 57.5Main ClgPart 0 Aux Htg 0.0 0.0 0.0 0 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Aux Clg

ExFlr 0-82.6Preheat 13.0 58.4 1,674 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Opt Vent

Roof 17,630 0 0Reheat -136.1 72.0 58.4 9,179

Wall 4,548 1,020 22Humidif 0.0 0 0.0 0.0 37.7 452.7TotalOpt Vent 0.0 0.0 0.0 0

-291.4Total

Envelope LoadsSkylite SolarSkylite CondRoof CondGlass SolarGlass/Door CondWall CondPartition/DoorFloor

InfiltrationSub Total ==>

LightsPeopleMisc

Sub Total ==>

Ceiling LoadVentilation Load

Additional Reheat

OA Preheat Diff.

Ov/Undr SizingExhaust Heat

RA Preheat Diff.

Grand Total ==>

Internal Loads

0

0 0

0.00 0.00 0.00

-10,217

Supply Air Leakage

74

Dehumid. Ov Sizing 0 0

Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0Leakage Ups

Leakage Dwn

0 0Infil

AHU Vent

Nom Vent

Main FanTerminal

Adjacent Floor

Diffuser

Supply Air Leakage

Underflr Sup Ht Pkup Underflr Sup Ht Pkup

Adjacent Floor 0 0 0 0

0 0

0 0 0

0 0

0 0 0 0

0 0.00

0 0.00

18,357

18,357 18,357

0

1,674

1,674

0

0

18,357

18,357 9,179

9,179

1,674

1,674

0

0

0 55,479 0

Int Door 0

Ext Door 0 0 0

TRACE® 700 v6.2.9 calculated at 03:29 PM on 03/25/2013Project Name: Redbird Smith

Dataset Name: Alternative - 1 System Checksums Report Page 3 of 3Redbird Smith Health Center.trc

Page 43: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

System ChecksumsBy HP ENGINEERING

Parallel Fan Powered VAV, Htg Coil on Mixing Box OutletNorth Zone

HEATING COIL PEAKCLG SPACE PEAKCOOLING COIL PEAK TEMPERATURES

Heating DesignMo/Hr:7 / 17Mo/Hr:7 / 15Mo/Hr:Peaked at Time: Cooling Heating

SADBOADB: 13OADB:98 / 75 / 97OADB/WB/HR:Outside Air: 55.1 75.3

Ra Plenum 79.1 68.1

ReturnPercentCoil PeakSpace PeakSpace PercentPercentNetPlenumSpace 79.1 68.1Ret/OASens. + Lat. Of TotalTot SensSpace SensOf TotalSensibleOf TotalTotalSens. + Lat 50.0 82.2

0.0 0.2Fn MtrTDBtu/h (%)Btu/hBtu/h(%)Btu/h(%)Btu/hBtu/h 0.1 0.4Fn BldTDEnvelope Loads 0.2 1.1Fn Frict 0Skylite Solar 0.00 0 0 0 0 0 0 0

0Skylite Cond 0.00 0 0 0 0 0 0 0 0Roof Cond 31.48-66,103 0 0 0 25 113,657 113,657

0.00 11,391Glass Solar 0 0 8 16,904 3 11,391 0 3,692Glass/Door Cond -8,771 4.18-8,771 2 3,572 1 3,692 0

AIRFLOWS

HeatingCooling 8,229Wall Cond 9.02-18,935-12,141 4 9,254 3 12,288 4,060

0Partition/Door 0.00 0 0 0 0 0 0 0Floor 0.00 0 0 0 0 0

Sec Fan 0.00 0Infiltration 0 0 0 0 0 0

1,185 5,924MinStop/Rh

44.68 23,311Sub Total ==> -93,808-20,911 14 29,731 31 141,027 117,716

11,847Return 5,924

Internal Loads

1,939 1,939Exhaust

48,137Lights 0.00 0 0 22 48,137 13 60,171 12,034

0 0Rm Exh

79,335People 0.00 0 20 44,075 18

0 0Auxiliary

60,171Misc 0.00 0 0 28 60,171 13 60,171 0

187,643Sub Total ==> 0.00 0 0 70 152,383 44 199,677 12,034

39,601Ceiling Load 0.000-22,041 17 36,156 0 0-39,601 0Ventilation Load 59.28-124,469 0 0 0 23 103,375 0

Sup. Fan Heat 5 20,774

ENGINEERING CKS

HeatingCooling

Ret. Fan Heat 0 0 0 % OA 16.4 16.4

Duct Heat Pkup 0 0 0 0.34 0.67cfm/ft²

0Ov/Undr Sizing

0.00 0 0

0 0 0 0

315.99cfm/ton

Exhaust Heat

-3.96 8,324-3-14,955

470.24ft²/ton

-15.50 25.52Btu/hr·ft²

176No. People 250,555Grand Total ==> 100.00-209,953-42,952100.00 218,270100.00 449,899 75,194

AREAS HEATING COIL SELECTIONCOOLING COIL SELECTIONTotal Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Coil Airflow Ent LvgCapacityton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) °F°FcfmMBh

Floor 17,630 Main Htg -188.1 11,849 60.7 75.3 37.5 449.9 366.1 11,686 82.2 64.8 66.1 53.4 51.7 55.6Main ClgPart 0 Aux Htg 0.0 0.0 0.0 0 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Aux Clg

ExFlr 0-85.3Preheat 13.0 53.4 1,939 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Opt Vent

Roof 17,630 0 0Reheat -119.7 72.0 53.4 5,924

Wall 4,548 504 11Humidif 0.0 0 0.0 0.0 37.5 449.9TotalOpt Vent 0.0 0.0 0.0 0

-273.4Total

Envelope LoadsSkylite SolarSkylite CondRoof CondGlass SolarGlass/Door CondWall CondPartition/DoorFloor

InfiltrationSub Total ==>

LightsPeopleMisc

Sub Total ==>

Ceiling LoadVentilation Load

Additional Reheat

OA Preheat Diff.

Ov/Undr SizingExhaust Heat

RA Preheat Diff.

Grand Total ==>

Internal Loads

0

0 0

0.00 0.00 0.00

-14,955

Supply Air Leakage

96

Dehumid. Ov Sizing 0 0

Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0Leakage Ups

Leakage Dwn

0 0Infil

AHU Vent

Nom Vent

Main FanTerminal

Adjacent Floor

Diffuser

Supply Air Leakage

Underflr Sup Ht Pkup Underflr Sup Ht Pkup

Adjacent Floor 0 0 0 0

0 0

0 0 0

0 0

0 0 0 0

0 0.00

0 0.00

11,847

11,847 11,847

0

1,939

1,939

0

0

11,849

11,849 5,924

5,924

1,939

1,939

0

0

0 79,335 0

Int Door 0

Ext Door 0 0 0

TRACE® 700 v6.2.9 calculated at 02:54 PM on 03/25/2013Project Name: Redbird Smith

Dataset Name: Alternative - 1 System Checksums Report Page 1 of 2Redbird Smith Health Center.trc

Page 44: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO

System ChecksumsBy HP ENGINEERING

Parallel Fan Powered VAV, Htg Coil on Mixing Box OutletSouth Zone

HEATING COIL PEAKCLG SPACE PEAKCOOLING COIL PEAK TEMPERATURES

Heating DesignMo/Hr:10 / 14Mo/Hr:7 / 15Mo/Hr:Peaked at Time: Cooling Heating

SADBOADB: 13OADB:98 / 75 / 97OADB/WB/HR:Outside Air: 60.0 74.2

Ra Plenum 77.6 69.1

ReturnPercentCoil PeakSpace PeakSpace PercentPercentNetPlenumSpace 77.6 69.1Ret/OASens. + Lat. Of TotalTot SensSpace SensOf TotalSensibleOf TotalTotalSens. + Lat 58.9 79.7

0.0 0.2Fn MtrTDBtu/h (%)Btu/hBtu/h(%)Btu/h(%)Btu/hBtu/h 0.1 0.4Fn BldTDEnvelope Loads 0.2 1.1Fn Frict 0Skylite Solar 0.00 0 0 0 0 0 0 0

0Skylite Cond 0.00 0 0 0 0 0 0 0 0Roof Cond 33.04-67,351 0 0 0 26 115,433 115,433

0.00 31,034Glass Solar 0 0 32 77,340 7 31,034 0 7,471Glass/Door Cond -17,750 8.71-17,750 0 210 2 7,471 0

AIRFLOWS

HeatingCooling 8,341Wall Cond 8.14-16,585-9,663 3 6,474 3 13,933 5,592

0Partition/Door 0.00 0 0 0 0 0 0 0Floor 0.00 0 0 0 0 0

Sec Fan 0.00 0Infiltration 0 0 0 0 0 0

1,836 9,179MinStop/Rh

49.88 46,846Sub Total ==> -101,686-27,413 35 84,023 37 167,871 121,025

18,357Return 9,179

Internal Loads

1,674 1,674Exhaust

48,137Lights 0.00 0 0 20 48,137 13 60,171 12,034

0 0Rm Exh

55,479People 0.00 0 13 30,822 12

0 0Auxiliary

60,171Misc 0.00 0 0 25 60,171 13 60,171 0

163,787Sub Total ==> 0.00 0 0 58 139,130 39 175,821 12,034

31,337Ceiling Load 0.000-16,235 7 16,479 0 0-31,337 0Ventilation Load 52.71-107,456 0 0 0 20 89,602 0

Sup. Fan Heat 7 29,595

ENGINEERING CKS

HeatingCooling

Ret. Fan Heat 0 0 0 % OA 9.1 9.1

Duct Heat Pkup 0 0 0 0.52 1.04cfm/ft²

0Ov/Undr Sizing

0.00 0 0

0 0 0 0

486.63cfm/ton

Exhaust Heat

-2.60 5,293-2-10,217

467.36ft²/ton

-16.53 25.68Btu/hr·ft²

123No. People 241,970Grand Total ==> 100.00-203,848-43,648100.00 239,632100.00 452,673 91,505

AREAS HEATING COIL SELECTIONCOOLING COIL SELECTIONTotal Capacity Sens Cap. Coil Airflow Enter DB/WB/HR Leave DB/WB/HR Gross Total Glass Coil Airflow Ent LvgCapacityton MBh MBh cfm °F °F gr/lb °F °F gr/lb ft² (%) °F°FcfmMBh

Floor 17,630 Main Htg -208.8 18,357 63.7 74.2 37.7 452.7 385.8 16,647 79.7 63.4 63.4 58.4 54.2 57.5Main ClgPart 0 Aux Htg 0.0 0.0 0.0 0 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Aux Clg

ExFlr 0-82.6Preheat 13.0 58.4 1,674 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0Opt Vent

Roof 17,630 0 0Reheat -136.1 72.0 58.4 9,179

Wall 4,548 1,020 22Humidif 0.0 0 0.0 0.0 37.7 452.7TotalOpt Vent 0.0 0.0 0.0 0

-291.4Total

Envelope LoadsSkylite SolarSkylite CondRoof CondGlass SolarGlass/Door CondWall CondPartition/DoorFloor

InfiltrationSub Total ==>

LightsPeopleMisc

Sub Total ==>

Ceiling LoadVentilation Load

Additional Reheat

OA Preheat Diff.

Ov/Undr SizingExhaust Heat

RA Preheat Diff.

Grand Total ==>

Internal Loads

0

0 0

0.00 0.00 0.00

-10,217

Supply Air Leakage

74

Dehumid. Ov Sizing 0 0

Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0Leakage Ups

Leakage Dwn

0 0Infil

AHU Vent

Nom Vent

Main FanTerminal

Adjacent Floor

Diffuser

Supply Air Leakage

Underflr Sup Ht Pkup Underflr Sup Ht Pkup

Adjacent Floor 0 0 0 0

0 0

0 0 0

0 0

0 0 0 0

0 0.00

0 0.00

18,357

18,357 18,357

0

1,674

1,674

0

0

18,357

18,357 9,179

9,179

1,674

1,674

0

0

0 55,479 0

Int Door 0

Ext Door 0 0 0

TRACE® 700 v6.2.9 calculated at 02:54 PM on 03/25/2013Project Name: Redbird Smith

Dataset Name: Alternative - 1 System Checksums Report Page 2 of 2Redbird Smith Health Center.trc

Page 45: Air-Cooled Chiller, Scroll Compressors - Cherokee … Chiller, Scroll Compressors Job Information ... OP AUTO ST OP DUAL LO W ... T HE FACT ORY BY JUM PERS W2 & W3 TO ENABLE UNIT OPERATIO