9. VPEG Sequence Control ST16
Transcript of 9. VPEG Sequence Control ST16
SEQUENCE CONTROL (SEQUENCE TABLE)
PT. Yokogawa IndonesiaWisma Aldiron Dirgantara 2nd floor, suite 202-209
Jl. Jend. Gatot Subroto Kav.72 Jakarta 12780Phone : 021-799 0102, Fax : 021-799 0070
SEQUENCE CONTROL (SEQUENCE TABLE)
Engineering Course
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
TYPES OF SEQUENCE CONTROL BLOCKS
The following function blocks are catagorized as sequence control blocks:
1.Sequence Table Blocks
2.Logic Chart Block
3.Sequential Function Chart Block
4.Switch Instrument Blocks
5.Sequence Element Blocks
6.Valve Monitoring Block
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
TYPES OF SEQUENCE CONTROL BLOCKS (1/2)
Sequence Table BlocksThis function blocks realizes sequence control by operating other function blocks and/or process or software I/O.
There are two basic type of Sequence Table blocks:
• Sequence Table Block ST16
• Rule Extension Block ST16E
On top of the basic types above, there are also other types such as
Sequence Table Block M_ST16 (Number of condition signals: 32 to 64, number of action signals: 32 to 64 / Total 96)
Rule Extension Block M_ST16
Sequence Table Block L_ST16 (Number of condition signals: 64, number of action signals: 64 / Total 128)
Rule Extension Block L_ST16
The conditions & operations are arranged in the table format & specifies which operation is performed by the combination of conditions.
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Sequence Table block (ST16, ST16E) is a decision table type function block that describes the relationship between input signal and output signal in a Y/N (Yes/No) fashion.
The ST16 block has a sequence control function that handles a total of 64 I/O signals and 32 rules. The I/O signals can also be redistributed in the 8-signal unit.
The rule extension block (ST16E) is used for extending the rules of ST16 block. It connects to an ST16 block and only allows connection to a step-type ST16 block. Hence, it cannot be used/activated independently.
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
I/O connection is set by describing connection information & data in the input connection information setting area, condition setting area, output connection information setting area & operation specification setting area of the sequence table.
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
When the phase step sequence table is used, the number of processes (number of steps) may be insuficient depending on the process that is being performed.
Solution: use the rule expansion format sequence table block (ST16E) to expand the number of rules.
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Complete Sequence Table Configuration
••Condition SignalCondition Signal Enter the element symbol in the Tag Name Data Item column (eg. FC002.ALRM) and condition specification in the Data column (eg. HI).
••Action SignalAction Signal Enter the element symbol in the Tag Name Data Item column (eg. %AN0010.PV) and action specification in the Data column (eg. H).
••Rule NumberRule Number Up to 32 rules per block may be used. The output is based on each rule condition and condition testing result.
••Condition RuleCondition Rule Use Y/N pattern (in combination) to condition rule. If the testing result of condition signal corresponds with the Y/N pattern, the condition is then said satisfied.
••Action RuleAction Rule Use Y/N pattern (in combination) to action rule. If the the testing result of condition signal is satisfied, action rule will be manipulated according to the Y/N pattern.
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Complete Sequence Table Configuration
••Step LabelStep Label Step labels are used for phase indication when performing step sequence control in the Sequence Table. The labels are character strings that combine two or less alphanumeric characters (A to Z, 0 to 9).
••Next Step LabelNext Step Label THEN Execute the next step label when the corresponding rule condition status is true or satisfied & after the manipulated output is completed. ELSE Execute the next step label when the corresponding rule status is false.
••Tag Name.Data ItemTag Name.Data Item Describe the connection information of the condition and action signal (eg. FC001.MODE, FC001.PSW, TIMER001.OP, etc).
••DataData Describe the specification of condition and action signal (eg. AUT, HI, L, H, STOP, RUN, etc).
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Complete Sequence Table Configuration
••CommentComment Comments are defined by user to describe the meaning of symbols & contents of status manipulation of condition & action rules.
••Processing TimingProcessing Timing There ara two processing timings: Start/Execution Timing It refers to the timing at which control algorithms are executed when receiving input signals. Select one of the following type
- Periodic Execution (T) - One-Shot Processing (O) - Startup at Initial Cold Start/Restart of FCS (I) - Restricted Initial Execution (B)
Output Timing It indicates the condition or behaviour of action signals in conjunction with the condition rule status change (applicable with T & O type of Start Timing only). Select either
- Output Only When Condition Change (C) or - Output Each Time Conditions Are Satisfied (E)
••Scan PeriodScan Period Sequence table with periodic execution type (T) is Sequence table with periodic execution type (T) is activated at defined scan period. activated at defined scan period. There are three types of scan periods:There are three types of scan periods:
-- Basic Scan (1 second Basic Scan (1 second –– fixed)fixed) -- Medium Speed Scan ( 200 & 500 milliseconds)Medium Speed Scan ( 200 & 500 milliseconds)
50, 100, 250 milliseconds are also applicable.50, 100, 250 milliseconds are also applicable. -- High Speed Scan (200 & 500 milliseconds)High Speed Scan (200 & 500 milliseconds)
50, 100, 250 milliseconds are also applicable.50, 100, 250 milliseconds are also applicable.
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Start / Execution Timing
Periodic Execution (T)Periodic Execution (T)The periodic execution means that the sequence control block is repeatedly executed in a preset cycle.
OneOne--Shot Execution (O)Shot Execution (O)When execution timing of a function block is defined as one-shot type, the block is executed only when it is invoked by other function block. A one-shot function block can invoke another one-shot function block. However, such succession is limited to seven blocks. Invocation can only be initiated from the same FCS.
Invoking function block
One-shot type function block
Invocation signal
Sequence process execution
ACT.OFF
ACT.ON
Idle
Executing
One-Shot Processing Conceptual Diagram
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Start / Execution Timing
Initial Execution/Restart Execution (I)Initial Execution/Restart Execution (I)In this execution type, the sequence block executes its process when the FCS performs a cold start or a restart.
Restricted Initial Execution (B)Restricted Initial Execution (B)In restricted initial execution, the sequence control block executes only when the FCS performs a cold start, not include restart.
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Output Timing
Output Only When Conditions Are Changed (C)Output Only When Conditions Are Changed (C)The sequence table blocks output an operation/action signal only at the timing when the judged conditions are changed from false to true. This is applicable only with periodic execution (T) or one-shot start (O) start timing.
Condition rule change
Action rule change
Action change/interuption is possible eventhough the conditions rule are satisfied
False
True
False
True
“Output Only When Conditions Are Changed” Conceptual Figure
Condition detection (a change from false to true state)
NoteNote: However, if non-latched output is specified for the action signal, the operation changes when the condition is switched from true to false.
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Output Timing
Output Each Time Conditions Are Satisfied (E)Output Each Time Conditions Are Satisfied (E)The sequence table blocks output its operation/action signal every scan period as long as the judged conditions are satisfied.
Condition rule change
Action rule change
Action change/interuption is not possible as long as the condition remains satisfied.
False
True
False
True
“Output Each Time Conditions Are Satisfied” Conceptual Figure
Condition detection (false or true state)
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Execution & Output Timing Combination
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Sequence Description Example (AND Gate)
The basic logical AND gate can be configured in a Sequence Table as follow:
In the example above, only when all conditions signals are satisfied the action/output operation may be performed.
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Sequence Description Example (OR Gate)
The basic logical OR gate can be configured in a Sequence Table as follow:
In the example above, when any of conditions signals is satisfied the action/output operation may be performed.
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Operation Of Non-Step Sequence
In a non step sequence table, all 32 rules are subject to condition testing and the output operation is performed according to the conditions.
As for condition testing, a condition is satisfied when all conditions (Y/N) for the same rule number are true. Rule column that is blank is considered true unconditionally.
Operations/actions are executed according to the operation contents of Y/N patterned for the rule number whose conditions are satisfied.
When the conditions of multiple rules are satisfied simultaneously with respect to the same action signal, if request for both Y/N are detected as the resultant operations, the request for Y takes precedence and the operation for N will not be executed.
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Operation Of Non-Step Sequence (Example)
Here is an example of the sequence that normally monitors operation to prevent the buffer tank in the processing piping system from overflow. The sequence table below monitors the conditions in rule numbers 01 to 04 simultaneously. If any condition becomes true, the action/operation in the same rule will be executed. The monitoring continues after the execution.
LAHH100.PV
LAH100.PV
LAL100.PV
LALL100.PV
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Operation Of Step Sequence
In a step sequence table, the process control sequence of a phase-step process is divided into the smallest phase units (steps) on the condition monitoring and operation, then these steps are executed one by one. Only step label 00 and the rule corresponding to the
current step number are subject to condition testing & operation.
Step label 00 is executed during each period & it may only be used at the head of a sequence table group. So it cannot be used as a next step label.
The next execution step label must be described in THEN/ELSE part in order to advance the next step. If both are left blank the same step is executed each time & will not advance.
The next step specified in THEN part is the step to advance when the condition test result is satisfied (true state).
The next step specified in ELSE part is the step to advance when the condition test result is unsatisfied (false state). It will proceeds to the next step without executing the action/operation rules.
If there are multiple requests for step transition in the same step, the step advances to the next step label with the smallest rule number.
The next step execution is done during the next scan period.
Only the actions for the rules whose conditions are satisfied in the step currently being executed, are in operation.
Only the step currently being executed is subject to condition testing.
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Operation Of Step Sequence (Example)
Sequence SpecificationSequence Specification
1. Push the start button
Valve A opens to fill the tank with water. 2. When the tank is full
Switch A becomes ON.
Valve A is closed. 3. Push the start button again (with the tank full of water)
Valve B opens to drain the tank. 4. When the tank level becomes low
Switch B becomes ON
Valve B is closed
Water injection processing (Step label A1)
Water drain processing (Step label A2)
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Operation Of Step Sequence (Example)
Water injection processing (Step label A1)
Water drain processing (Step label A2)
In the above sequence table, rules number 01 & 02 are step A1. Rules number 03 & up are step A2. Rules number o5 and beyond do not have any Y/N pattern for the condition rule or action rule or move-destination step label, so they are not subject to condition testing nor action execution.
Step A1 monitors the conditions for rules number 01 & 02 simultaneously. Whichever the condition is satisfied will be executed. Executing the action of rule 01 does not advance the step since there is no designation in the move- destination step label. After executing the action, A1 resumes monitoring rules number 01& 02 again. When rule number 02 conditions become true, the action of rule 02 is executed & the step advances to A2 as stated in the move-destination step label.
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Number Of Condition & Action Signal
By default, sequence table ST16 has 32 condition signals and 32 action/operation signals. However, this allocation of condition & action signal can be changed on 8-signal unit basis.
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Number Of Condition & Action Signal
Table : Combination of Condition & Action Signal Counts
Number Of Condition SignalNumber Of Condition Signal Number Of Action SignalNumber Of Action Signal
8 56
16 48
24 40
32 (default) 32 (default)
40 24
48 16
56 8
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Rule Extension
The number of rules in one sequence table is fixed at 32 & cannot be modified. However, if the number of rules in a sequence table is not enough to describe one phase unit, it can be extended in the 32-rule unit by connecting to another sequence table. The number of rules can be extended for a step-type sequence table.
Type the tag number of the extended sequence table in the NEXT box of the first/extending sequence table.
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Switch Instrument Block Valve Monitoring Block (VLVM)
Timer Block (TM) Regulatory Control Blocks
Software Counter Block (CTS) Calculation Blocks
Pulse Train Input Counter Block (CTP) Faceplate Blocks
Code Input Block (CI) SFC Blocks
Code Output Block (CO) Unit Instrument Blocks
Relational Expression Block (RL) Sequence Table Blocks
Resource Scheduler Block (RS) Logic Chart Block
Condition Signal Description (Function Blocks and I/O Data)
Function blocks that can be processed in a sequence table are shown below.
I/O data that can be processed in a sequence table are shown below.
Processing I/O (Digital Input/Output)
Software I/O (Internal Switch, Annunciator, Global Switch)
Communication I/O
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Switch Instrument & Enhanced Switch Instrument Blocks) 1/2
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Switch Instrument & Enhanced Switch Instrument Blocks) 2/2
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Timer Block [TM])
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Software Counter Block [CTS])
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Pulse Train Input [CTP])
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Code Input Block [CI])
Condition Signal Description (Code Output Block [CO])
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Relational Expression Block [RL])
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Resource Scheduler Block [RS])
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Valve Monitoring Block [VLVM])
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Regulatory Control Block) 1/4
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Regulatory Control Block) 2/4
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Regulatory Control Block) 3/4
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Regulatory Control Block) 4/4
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Calculation Block) 1/4
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Calculation Block) 2/4
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Calculation Block) 3/4
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Calculation Block) 4/4
The table lists the calculation blocks that can be referenced in the condition signal as one- shot operation.
The format is:
TAGNAME.ACT.ON
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Faceplate Block)
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Sequential Function Chart Block)
The following lists the data items of SFC block that can describe data values in condition specifications and their setting ranges:
STEPNO: 1 to 99
SWCR[5]: 0 to 15
SWST[5]: 0,1
SWOP[5]: -15 to 15
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Unit Supervision Block)
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Processing I/O Block)
Condition Signal Description (Global Switch)
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Software / Common Switch)
Condition Signal Description (Communication I/O)
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
SEQUENCE TABLE BLOCK (ST16, ST16E)
Condition Signal Description (Annunciator Message)
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
LABORATORY WORKS
Create a logic sequence from these control narratives:
Case 1Case 1
In a cascade loop, if the process variable of the slave controller is High- High alarm then the slave controller mode will have to switch to CASCADE mode and the master controller mode will have to switch to AUTO mode. However, the operator is allowed to change the mode of slave controller to MANUAL or AUTO mode even tough the process variable is still in High-High alarm state.
Case 2Case 2
In a cascade loop, if the process variable of the slave controller is High- High alarm then the slave controller mode will have to switch to CASCADE mode and the master controller mode will have to switch to AUTO mode. The control mode of the slave controller cannot be changed until the alarm vanishes (process variable is in normal state).
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT YOKOGAWA INDONESIATraining Center – Technical Support Group
PT. Yokogawa IndonesiaWisma Aldiron Dirgantara 2nd floor, suite 202-209