The T-Flex Curbs are accessory items used to retrofit a C**H unit to the structure and are intended to lower the building’s interior sound level. This is accomplished by using the following principles:
• The first is accomplished by isolating the vibrations created by the mechanical devices of the wall mount operation using rubber isolation mounts to prevent the energy from transferring into the wall of the structure that it is mounted on. (This will be more beneficial on wood or steel frame structures
Patent No. 8,540,557
TCURBF, TCURBT, TFCF, TFCT T-FLEX CURBS
INSTALLATION INSTRUCTIONS
Bard Manufacturing Company, Inc. Bryan, Ohio 43506
www.bardhvac.com
Manual: 7960-689HSupersedes: 7960-689GDate: 6-27-18
CONTENTS
in eliminating the drumming effect of the wall than on masonry structures.)
• The second is the T-Flex Curb creates an indirect return air path and has additional sound attenuation material to lower sound transmission into the structure through the return air opening.
The offset return will require a different supply to return spacing for the applied structure than specified by the wall-mounted unit.
Wall Curb Application Guide ................................... 2
General Information ............................................... 3
TCURBF*****-*, TCURBT*****-* New Installations . 7
TFCT-32B-*, TFCF-32B-*, TFCT-53B-*, TFCF-53B-* Retrofit Installations .............................................. 8
Figures
Figure 1 TCURBF2430A .................................. 4
Figure 2 TCURBF3642A .................................. 4
Figure 3 TCURBF4860A ................................. 4
Figure 4 TCURBT2430A .................................. 4
Figure 5 TCURBT3642A .................................. 5
Figure 6 TCURBT4860A .................................. 5
Figure 7 TFCF-32B .......................................... 6
Figure 8 TFCF-53B .......................................... 6
Figure 9 TFCT-32B .......................................... 6
Figure 10 TFCT-53B .......................................... 6
Figure 11 Wall Mounting Instructions .................. 9
Figure 12 Wall Mounting Instructions .................. 9
Figure 13 Electric Heat Clearance ..................... 10
Figure 14 TCURBF2430A Supply and Return Openings ............................... 11
Figure 15 TCURBT2430A, TFCF-32A and TFCT-32A Supply and Return Openings . 12
Figure 16 TCURBT3642A and TCURBT4860A Supply and Return Openings .............. 13
Figure 17 TCURBF3642A and TCURBF4860A Supply and Return Openings .............. 14
Figure 18 TFCF-53B Supply and Return Openings . 15
Figure 19 TFCT-53B Supply and Return Openings ..16
Figure 20 Fastening Unit to Curb ...................... 17
Figure 21 Sealing with Caulk ............................ 18
Figure 22 Sealing with Caulk (Top Outlet Curb) ... 19
![Page 2: 7960-689(H) (2018 06) - Bard HVAC · 2018. 6. 27. · ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax:](https://reader036.fdocuments.in/reader036/viewer/2022062510/61346fffdfd10f4dd73bbafa/html5/thumbnails/2.jpg)
7960-689H Page 2 of 19
Wall Curb Application Guide
All curb model numbers are followed by -X (beige), -4 (gray), etc. to match unit color. All curbs have four rubber isolation mounts to reduce vibration to the installation wall.
NOTE A: A TCURB***** is required for all economizer applications. For T24 and T30 installations with CHCRV-3, a TCURB is also required.
Unit Indoor Air Connections Curb Indoor Air Connections
ApplicationFig.#
Curb Model
UsedwithUnit
Model
SupplyAir
H x W
Return AirH x W
SpacingSAtoRA
SupplyAir
H x W
Return AirH x W
SpacingSAtoRA
Alt. SpacingSA to RA
1 TCURBF2430AC24HC30H
7.88 x 27.88
13.88x 27.88
17.937.88
x 27.8813.88
x 27.886.125 17.93
2 TCURBF3642AC36HC42H
9.88 x 29.88
15.88x 29.88
30.009.88
x 29.8815.88
x 29.886.125 30.00 Used to direct replace CH3S models.
3 TCURBF4860AC48HC60H
9.88 x 29.88
15.88x 29.88
30.009.88\x 29.88
15.88x 29.88
6.125 30.00Used to direct replace CH4S and CH5S models.
4 TCURBT2430AC24HC30H
7.88 x 27.88
13.88x 27.88
17.937.88
x 27.8813.88
x 27.8817.93 ----
Used to install 2 or 2½-ton cabinet machines installed in a soffit.
5 TCURBT3642AC36HC42H
9.88 x 29.88
15.88x 29.88
30.009.88
x 29.8815.88
x 29.8830.00 ----
Used to install 3 or 3½-ton cabinet machines installed in a soffit.
6 TCURBT4860AC48HC60H
9.88 x 29.88
15.88x 29.88
30.009.88
x 29.8815.88
x 29.8830.00 ----
Used to install 4 or 5-ton cabinet machines installed in a soffit.
7 TFCT-32B C24H7.88
x 27.8813.88
x 27.8817.93
7.88x 19.88
11.88x 19.88
20.56 ----Used to install new larger cabinet 2 or 2½-ton in place of old 2-ton in a soffit.
8 TFCT-53B C36H9.88
x 29.8815.88
x 29.8830.00
7.88x 27.88
13.88x 27.88
17.93 ----Used to install new larger cabinet 3 or 3½-ton in place of old 3-ton in a soffit.
9 TFCF-32B C24H7.88
x 27.8813.88
x 27.8817.93
7.88x 19.88
11.88x 19.88
20.56 ----Used to install new larger cabinet 2 or 2½-ton in place of old 2-ton.
10 TFCF-53B C36H9.88
x 29.8815.88
x 29.8830.00
7.88x 27.88
13.88x 27.88
17.93 ----Used to install new larger cabinet 3 or 3½-ton in place of old 3-ton.
NO
TE A
![Page 3: 7960-689(H) (2018 06) - Bard HVAC · 2018. 6. 27. · ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax:](https://reader036.fdocuments.in/reader036/viewer/2022062510/61346fffdfd10f4dd73bbafa/html5/thumbnails/3.jpg)
7960-689H Page 3 of 19
GETTING OTHER INFORMATION AND PUBLICATIONSThese publications can help when installing the wall curb. They can usually be found at the local library or purchased directly from the publisher. Be sure to consult the current edition of each standard.
National Electrical Code ......................ANSI/NFPA 70
Standard for the Installation ..............ANSI/NFPA 90A of Air Conditioning and Ventilating Systems
Standard for Warm Air .......................ANSI/NFPA 90B Heating and Air Conditioning Systems
Load Calculation for ......................... ACCA Manual J Residential Winter and Summer Air Conditioning
Duct Design for Residential ............... ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection
For more information, contact these publishers:
ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax: (202) 234-4721
ANSI American National Standards Institute 11 West Street, 13th Floor New York, NY 10036 Telephone: (212) 642-4900 Fax: (212) 302-1286
ASHRAE American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc. 1791 Tullie Circle, N.E. Atlanta, GA 30329-2305 Telephone: (404) 636-8400 Fax: (404) 321-5478
NFPA National Fire Protection Association Batterymarch Park P.O. Box 9101 Quincy, MA 02269-9901 Telephone: (800) 344-3555 Fax: (617) 984-7057
SHIPPING DAMAGEUpon receipt of equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent.
GENERALThe equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
The refrigerant system is completely assembled and charged. All internal wiring is complete.
The unit is designed for use with or without duct work. Flanges are provided for attaching the supply and return ducts.
These instructions explain the recommended method to install the unit wall curb.
These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation. Note particularly “Starting Procedure” and any tags and/or labels attached to the equipment.
While these instructions are intended as a general recommended guide, they do not supersede any national and/or local codes in any way. Authorities having jurisdiction should be consulted before the installation is made. See page 3 for information on codes and standards.
Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America (ACCA). The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type, NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B. Where local regulations are at a variance with instructions, installer should adhere to local codes.
GENERAL INFORMATION
![Page 4: 7960-689(H) (2018 06) - Bard HVAC · 2018. 6. 27. · ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax:](https://reader036.fdocuments.in/reader036/viewer/2022062510/61346fffdfd10f4dd73bbafa/html5/thumbnails/4.jpg)
7960-689H Page 4 of 19
17 15/16
MIS-3216 A
TCURBF2430
C24HC30H
ALT. RETURNPOSITION
"
"8 7 7
"8 6 1
"813 7
"
26 7/16"
1670 9 70 516
9 5/16"
1 "38 8 "1640 5"827 7
17 18 "
30"
42 1/16"
22 7/16"
44 3/16"
29 7/8"
MIS-3217 A
TCURBF3642
C36HC42H
ALT. RETURNPOSITION
85 5/16"
15 7/8"
31 3/4"
84 7/8"
9 7/8"
6 1/8"
9 5/16"
30"
TCURBF4860
C48HC60H
ALT. RETURNPOSITION
9 5/16"
9 7/8"
6 1/8"
15 7/8"
93 1/8"
31 3/4"
85 5/16"
7 13/16"
44 3/16"42 1/16"
22 7/16"
29 13/16"
MIS-3218 A
827"
"840 3
17 1/8"
738 316 "
TCURBT2430
MIS-3213 AC24HC30H
51682
12"
16
8
9
"
"
" 7 7
26 7/16"
70
7 ""13 8
17 1516
9 5/16"
FIGURE 1TCURBF2430A
FIGURE 2TCURBF3642A
FIGURE 3TCURBF4860A
FIGURE 4TCURBT2430A
![Page 5: 7960-689(H) (2018 06) - Bard HVAC · 2018. 6. 27. · ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax:](https://reader036.fdocuments.in/reader036/viewer/2022062510/61346fffdfd10f4dd73bbafa/html5/thumbnails/5.jpg)
7960-689H Page 5 of 19
42 1/16"44 1/4"
22 7/16"
29 7/8"
TCURBT3642
C36HC42H
84 7/8"
24"
15 7/8"
31 3/4"
109 1/4"
30"
9 5/16"
9 7/8"
MIS-3214 A
44 1/4"
22 7/16"
29 7/8"42 1/16"
C60HC48H
TCURBT4860
117 1/8"
7 7/8"
9 7/8"
30"
24"
31 3/4"
93 1/8"
15 7/8"
9 5/16"
109 1/4"
MIS-3215 A
FIGURE 5TCURBT3642A
FIGURE 6TCURBT4860A
![Page 6: 7960-689(H) (2018 06) - Bard HVAC · 2018. 6. 27. · ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax:](https://reader036.fdocuments.in/reader036/viewer/2022062510/61346fffdfd10f4dd73bbafa/html5/thumbnails/6.jpg)
7960-689H Page 6 of 19
38 7/16"27 7/8"
22 7/16"
42 1/8"
MIS-3225 A
TFCF53
C36HC42H 9 5/16"
14 5/8"
85"
70 3/8"17 7/8"
13 7/8"
7 7/8"31 3/4"
9 5/16"
MIS-3266 A
TFCF32
C24HC30H
7 7/8"
26 3/4"
70 9/16" 11 13/16"70 3/8"
20 9/16"
33 5/16"
17 1/8"
19 7/8"38 3/16"
FIGURE 7TFCF-32B
FIGURE 8TFCF-53B
TFCT32
MIS-3222 AC24HC30H
7 710"
9 "
1620 9 "
16 9 "5
705
16
8 "
26 3/4"
"80 16
11 78 "
817 "1
"83337
819 "38 3
16 "
27 7/8"
38 1/2"
22 7/16"
42 1/16"
MIS-3223 A
TFCT53
C36HC42H
12 1/8"
9 5/16"
7 7/8"
31 3/4"
82 1/4"84 7/8"
14 3/4"
17 15/16"
13 7/8"
FIGURE 9TFCT-32B
FIGURE 10TFCT-53B
![Page 7: 7960-689(H) (2018 06) - Bard HVAC · 2018. 6. 27. · ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax:](https://reader036.fdocuments.in/reader036/viewer/2022062510/61346fffdfd10f4dd73bbafa/html5/thumbnails/7.jpg)
7960-689H Page 7 of 19
TCURBF*****-*, TCURFT*****-*NEW INSTALLATIONS
1. Frame the wall in accordance with these installation instructions. See Figures 11-17.
2. Remove the packaging from the curb, but leave attached to the skid for now.
3a. TCURB*2430A models: Measure the distance between the SA (supply air) and RA (return air) opening in the wall and verify the curb has the correct back orientation for the wall. The curbs come out of the box set up for nominal 6" spacing between SA and RA. To convert to nominal 18" spacing, remove the RA panel from the back, rotate the RA panel 180˚ and place into position covering the lower open area. There should now be nominal 18" spacing between the SA and RA openings. Once verified, replace all screws securing the RA panel into place.
3b. TCURB*3642A and TCURB*4860A models: Measure the distance between the SA (supply air) and RA (return air) opening in the wall and verify the curb has the correct back orientation for the wall. The curbs come out of the box set up for nominal 6" spacing between SA and RA. To convert to nominal 30" spacing, remove the solid panel and RA panels from the back, move the solid panel up and attach to the bottom of the SA panel. Rotate the RA panel 180˚ and place into position covering lower open area. There should now be nominal 30" spacing between the SA and RA openings. Once verified, replace all screws securing the RA panel into place.
4. Remove curb from skid and lay flat on the back on the ground or on saw horses.
5. Attach the bug screen frame to the bottom of the curb with screws provided. Insert the bug screen.
6. Remove the four (4) bolts and lock washers holding the outer frame to the inner frame.
7. On top outlet versions, leave the upper support angle on the outer frame at this time.
8. Slide the outer frame off of the inner frame and set aside.
9. On the TCURBT3642A-* and TCURBT4860A-X mount the top box to the inner frame using the screws provided. The top box is shipped attached on all other curbs.
10. On the inner frame locate the TL side indicating Top Left. On the rear of the mounting flange, apply a liberal amount of silicone caulk to weather seal the inner curb to the structure.
11. Mount the inner frame to the wall using lag bolts. Be sure to center the supply and return flanges of the back in the wall openings. Verify the curb is square.
12. Remove the lower partition blank-off plate if the unit has an economizer installed in it. On C24H and C30H units, also remove the lower partition blank-off plate if the unit has a CHCRV-3 installed in it.
13. Slide the outer frame back over the inner frame and reattach using the four (4) bolts and lock washers removed in Step 6. The bug screen should be at the bottom of the curb. The top outlet sides must slide under the top outlet box sides.
NOTE: The outside curb will need to be compressed slightly to get the bolts started. Clamps or pliers may be needed to compress the rear seal to align the bolt holes. It is necessary for the seal to be under compression so when the wall mount is installed, adequate weather sealing is maintained.
14. Remove the upper support angle now if a top outlet curb.
15. Verify the curb is square.
16. Raise the unit to the curb with a suitable lift and engage the top of the unit to the curb first by slightly tipping the unit toward the curb. On top outlet curbs, ensure the unit is underneath the lip on the top outlet box. Caulk may be applied under the lip of the top outlet box if desired.
17. Engage nuts and washers (supplied) loosely to the top two (2) bolts in the curb to help keep the top of the unit in position.
18. Pivot the unit down to engage the remainder of the bolts and fasten securely to the curb with nuts and washers (supplied) (see Figure 18).
19. Apply a liberal amount of caulk across the top seam of the curb where it meets the unit or top outlet box. Also apply caulk where the curb or top box meet the wall (see Figures 19 and 20).
20. Connect power wires and thermostat wires to the unit. Use flexible conduit to maintain vibration isolation. Use of rigid conduit is not recommended and could cancel the benefits of the curb.
21. Connect ductwork per standard practices.
![Page 8: 7960-689(H) (2018 06) - Bard HVAC · 2018. 6. 27. · ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax:](https://reader036.fdocuments.in/reader036/viewer/2022062510/61346fffdfd10f4dd73bbafa/html5/thumbnails/8.jpg)
7960-689H Page 8 of 19
TFCT-32B-*, TFCF-32B-*, TFCT-53B-*, TFCF-53B-*RETROFIT INSTALLATIONS
Adding to Existing Installation
1. Disconnect the electrical entrance and thermostat wires from the old unit.
2. Disconnect the duct work as required from the old unit.
3. Supporting the unit, remove the mechanical fasteners retaining the wall mount unit to the structure, then lower the unit and move it off to the side.
4. Remove and discard bottom mounting bracket for wall mount.
5. Remove the packaging from the curb, but leave attached to the skid for now.
6. Verify that the wall is structurally sound. Make sure the new curb mounting holes will allow lag screws or other fastening devices to be inserted into supporting wall structure.
7. Measure the distance between the supply and return opening in the wall and verify the curb has the correct back orientation for the wall. If not, remove the inner back, turn 180˚ and reattach (see Figure 20). Verify the correct dimensions are correct.
8. Remove curb from skid and lay flat on the back on the ground or on saw horses.
9. Attach the bug screen frame to the bottom of the curb with screws provided. Insert the bug screen.
10. On top outlet versions, leave the upper support angle on the outer frame at this time.
11. On the curb, locate the TL side indicating top Left. On the rear of the wall mounting flange, apply a liberal amount of silicone caulk to weather seal the inner curb to the wall structure.
12. Mount the curb to the wall using lag bolts. The rubber plugs installed in the outer curb side flanges can be removed for lag hole access. Use a long drill driver extension (12") to reach lag holes. Be sure to center the supply and return flanges of the back in the wall openings. Verify the curb is square.
13. Remove the lower partition blank-off plate if the unit has an economizer installed in it. On C24H and C30H units, also remove the lower partition blank-off plate if the unit has a CHCRV-3 installed in it.
14. Remove the upper support angle now if a top outlet curb.
15. Verify the curb is square.
16. Raise the unit to the curb with a suitable lift and engage the top of the unit to the curb first by slightly tipping the unit toward the curb. On top outlet
curbs, ensure the unit is underneath the lip on the top outlet box. Caulk may be applied under the lip of the top outlet box if desired.
17. Engage nuts and washers (supplied) loosely to the top two (2) bolts in the curb to help keep the top of the unit in position.
18. Pivot the unit down to engage the remainder of the bolts and fasten securely to the curb with nuts and washers (supplied) (see Figure 18).
19. Apply a liberal amount of caulk across the top seam of the curb where it meets the unit or top outlet box. Also apply caulk where the curb or top box meet the wall (see Figures 19 and 20).
20. Connect power wires and thermostat wires to the units. Use flexible conduit to maintain vibration isolation. Use of rigid conduit is not recommended and could cancel the benefits of the curb.
21. Connect ductwork per standard practices.
![Page 9: 7960-689(H) (2018 06) - Bard HVAC · 2018. 6. 27. · ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax:](https://reader036.fdocuments.in/reader036/viewer/2022062510/61346fffdfd10f4dd73bbafa/html5/thumbnails/9.jpg)
7960-689H Page 9 of 19
FIGURE 11Wall Mounting Instructions
FIGURE 12Wall Mounting Instructions
WOOD OR STEEL SIDING
RETURN AIROPENINGRETURN AIR
DUCTSUPPLY AIR
OPENINGSUPPLY AIR
OPENING
CONCRETE BLOCK WALL INSTALLATION WOOD FRAME WALL INSTALLATION SIDE VIEW
OPENING
WALL STRUCTURE
RETURN AIROPENING
SUPPLY AIR
MIS-3280
E
B
G
F + 1.000B
D
OPENING
FIGURE 2, A-D, FOR ACTUAL DIMENSIONS.SEE APPLICABLE CURB DIMENSIONS,
OPENINGSUPPLY DUCT
ATTACH TO TOPPLATE OF WALL
ATTACH TO BOTTOMPLATE OF WALL
EXTERIOR FINISH WALLOVER FRAME
MIS-3281
RETURN DUCT
REQUIRED FOR SOME WALLS.A SECOND MEMBER MAY BE
OVER FRAMEINTERIOR FINISHED WALL
THIS STRUCTURAL MEMBERLOCATED TO MATCH STUDSPACING FOR REST OF WALL.
1.000" CLEARANCEALL AROUND DUCT
FRAMING MATERIAL4 x 4'S, 2 x 4'S, 2 x 6'S &/OR
STRUCTURAL STEEL
![Page 10: 7960-689(H) (2018 06) - Bard HVAC · 2018. 6. 27. · ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax:](https://reader036.fdocuments.in/reader036/viewer/2022062510/61346fffdfd10f4dd73bbafa/html5/thumbnails/10.jpg)
7960-689H Page 10 of 19
FIGURE 13Electric Heat Clearance
SIDE SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1/4" CLEARANCE TO COMBUSTIBLE SURFACES.
WARNINGA minimum of 1/4" clearance must be maintained between the supply air duct and combustible materials. This is required for the first 3' of ducting.
It is important to ensure that the 1/4" minimum spacing is maintained at all points.
Failure to do this could result in overheating the combustible material and may result in a fire causing damage, injury or death.
![Page 11: 7960-689(H) (2018 06) - Bard HVAC · 2018. 6. 27. · ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax:](https://reader036.fdocuments.in/reader036/viewer/2022062510/61346fffdfd10f4dd73bbafa/html5/thumbnails/11.jpg)
7960-689H Page 11 of 19
28"
A
C
D
C
12"
12"
12"
12"
12"
B
E
14"
F
14
DUCT
TOP
FLAS
HING
AT T
IME
OF IN
STAL
LATI
ON.
WAL
LSTR
UCTU
RE
39 1/
814
Wall
Ope
ning a
nd H
ole Lo
catio
n View
NOTE
S:
MATE
RIAL
SFR
OMCO
MBUS
TABL
E
39 1/
8
OPEN
ING
THE
SIDE
MOU
NTIN
G FL
ANGE
SAN
DUN
DER
G
RETU
RNAI
R
Righ
t Side
View
SILIC
ONE
CAUL
KING
BEPL
ACED
BEHI
ND
MIS-
3276
SUPP
LYAI
R
1/4"C
LEAR
ANCE
ON
ALL
FOUR
SIDE
S OF
SUP
PLY
AIR
DUCT
ISRE
QUIR
ED
IT IS
RECO
MMEN
DED
THAT
ABE
AD O
F
WAL
L
F
Retur
n Ope
ning
64 7
/164 5
/89 7
/829
7/8
5 3/4
3 11/1
65 3
/88 3
/828
3/8
ED
CB
A
COM B
USTI
BLE
MATE
RIAL
SRE
COMM
ENDE
D 1"
CLE
ARAN
CE F
ROM
REQU
IRED
DI M
ENSI
ONS
TO M
AINT
AIN
COM B
USTI
BLE
MATE
RIAL
S1/4
"MIN
. CLE
ARAN
CE F
ROM
REQU
IRED
DI M
ENSI
ONS
TO M
AINT
AIN Su
pply
Open
ing
ENTI
RE LE
NGTH
OF
TOP.
SEAL
WIT
H BE
ADOF
CAU
LKIN
G AL
ONG FO
AM A
IR S
EAL
FIG
UR
E 1
4TC
UR
BF2
43
0A
Sup
ply
and
Ret
urn
Ope
ning
s
![Page 12: 7960-689(H) (2018 06) - Bard HVAC · 2018. 6. 27. · ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax:](https://reader036.fdocuments.in/reader036/viewer/2022062510/61346fffdfd10f4dd73bbafa/html5/thumbnails/12.jpg)
7960-689H Page 12 of 19
28"
A
C
D
C
12"
12"
12"
12"
12"
B
14"
F
E
39 1/
8
Righ
t Side
View
14
WAL
LSTR
UCTU
RE
39 1/
8
DUCT
G
NOTE
S:
MATE
RIAL
SFR
OMCO
MBUS
TABL
E
14
OPEN
ING
THE
SIDE
MOU
NTIN
G FL
ANGE
SAN
DUN
DER
Wall
Ope
ning a
nd H
ole Lo
catio
n View
RETU
RNAI
R TOP
FLAS
HING
AT T
IME
OF IN
STAL
LATI
ON.
SILIC
ONE
CAUL
KING
BEPL
ACED
BEHI
ND
MIS-
3277
SUPP
LYAI
R
1/4"C
LEAR
ANCE
ON
ALL
FOUR
SIDE
S OF
SUP
PLY
AIR
DUCT
ISRE
QUIR
ED
IT IS
RECO
MMEN
DED
THAT
ABE
AD O
F
WAL
L
FB
RECO
MMEN
DED
1" C
LEAR
ANCE
FRO
MCO
MBUS
TIBL
EMA
TERI
ALS
A
REQU
IRED
DIM
ENSI
ONS
TO M
AINT
AIN Re
turn O
penin
g
CRE
QUIR
ED D
IMEN
SION
S TO
MAI
NTAI
N1/4
"MIN
. CLE
ARAN
CE F
ROM
COMB
USTI
BLE
MATE
RIAL
S5 3
/4ED
Supp
ly Op
ening
3 13/1
6
16 7/
810
304 1
/2
8 1/2
5 1/4
4 9/16
28 1/
2EN
TIRE
LENG
TH O
F TO
P.
SEAL
WIT
H BE
ADOF
CAU
LKIN
G AL
ONG
FOAM
AIR
SEA
L
FIG
UR
E 1
5TC
UR
BT2
43
0A
, TF
CF-
32
A a
nd T
FCT-
32
AS
uppl
y an
d R
etur
n O
peni
ngs
![Page 13: 7960-689(H) (2018 06) - Bard HVAC · 2018. 6. 27. · ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax:](https://reader036.fdocuments.in/reader036/viewer/2022062510/61346fffdfd10f4dd73bbafa/html5/thumbnails/13.jpg)
7960-689H Page 13 of 19
28"
A
C
D
C
12"
12"
12"
12"
12"
B
E
16"
F
Righ
t Side
ViewNO
TES:
WAL
LSTR
UCTU
RE
SUPP
LYAI
R
MIS-
3278
SILIC
ONE
CAUL
KING
BEPL
ACED
BEHI
ND
TOP
FLAS
HING
AT T
IME
OF IN
STAL
LATI
ON.
OPEN
ING
G
Wall
Ope
ning a
nd H
ole Lo
catio
n View
THE
SIDE
MOU
NTIN
G FL
ANGE
SAN
DUN
DER
FROM
COMB
USTA
BLE
DUCT
MATE
RIAL
S
RETU
RNAI
R
1/4"C
LEAR
ANCE
ON
ALL
FOUR
SIDE
S OF
SUP
PLY
AIR
DUCT
ISRE
QUIR
ED
IT IS
RECO
MMEN
DED
THAT
ABE
AD O
F
WAL
L
FC
A
RECO
MMEN
DED
1" C
LEAR
ANCE
FRO
M
COMB
USTI
BLE
MATE
RIAL
S
REQU
IRED
DIM
ENSI
ONS
TO M
AINT
AIN
B
COM B
USTI
BLE
MATE
RIAL
S
REQU
IRED
DIM
ENSI
ONS
TO M
AINT
AIN
1/4"M
IN. C
LEAR
ANCE
FRO
M
DE
Retur
n Ope
ning
Supp
ly Op
ening12
32
16
5 1/2
4343
16
29 3/
46 1
/4
29
10 1/
2
2
30 1/
21 1
/4EN
TIRE
LENG
TH O
F TO
P.
SEAL
WIT
H BE
ADOF
CAU
LKIN
G AL
ONG
FOAM
AIR
SEA
L
FIG
UR
E 1
6TC
UR
BT3
64
2A
and
TC
UR
BT4
86
0A
Sup
ply
and
Ret
urn
Ope
ning
s
![Page 14: 7960-689(H) (2018 06) - Bard HVAC · 2018. 6. 27. · ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax:](https://reader036.fdocuments.in/reader036/viewer/2022062510/61346fffdfd10f4dd73bbafa/html5/thumbnails/14.jpg)
7960-689H Page 14 of 19
28"
A
C
D
C
12"
12"
12"
12"
12"
B
E
16"
F
G
Wall
Ope
ning a
nd H
ole Lo
catio
n View
WAL
LSTR
UCTU
RE
SUPP
LYAI
R
MIS-
3279
SILIC
ONE
CAUL
KING
BEPL
ACED
BEHI
ND
Righ
t Side
View
NOTE
S:
MATE
RIAL
SFR
OMCO
MBUS
TABL
E
TOP
FLAS
HING
AT T
IME
OF IN
STAL
LATI
ON.
OPEN
ING
THE
SIDE
MOU
NTIN
G FL
ANGE
SAN
DUN
DER
DUCT
RETU
RNAI
R
1/4"C
LEAR
ANCE
ON
ALL
FOUR
SIDE
S OF
SUP
PLY
AIR
DUCT
ISRE
QUIR
ED
IT IS
RECO
MMEN
DED
THAT
ABE
AD O
F
WAL
L
FB
A
RECO
MMEN
DED
1" C
LEAR
ANCE
FRO
MRE
QUIR
ED D
I MEN
SION
S TO
MAI
NTAI
N
COM B
USTI
BLE
MATE
RIAL
S
C
COM B
USTI
BLE
MATE
RIAL
S
1/4"M
IN. C
LEAR
ANCE
FRO
MRE
QUIR
ED D
I MEN
SION
S TO
MAI
NTAI
N Retur
n Ope
ning
5 3/4E
D
Supp
ly Op
ening
5 1/2
30 1/
210
1/2
1 1/4
52
6 1/4
3212
43 431616
ENTI
RE LE
NGTH
OF
TOP.
SEAL
WIT
H BE
ADOF
CAU
LKIN
G AL
ONG FO
AM A
IR S
EAL
FIG
UR
E 1
7TC
UR
BF3
64
2A
and
TC
UR
BF4
86
0A
Sup
ply
and
Ret
urn
Ope
ning
s
![Page 15: 7960-689(H) (2018 06) - Bard HVAC · 2018. 6. 27. · ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax:](https://reader036.fdocuments.in/reader036/viewer/2022062510/61346fffdfd10f4dd73bbafa/html5/thumbnails/15.jpg)
7960-689H Page 15 of 19
FIG
UR
E 1
8TF
CF-
53
B S
uppl
y an
d R
etur
n O
peni
ngs
28"A
C
D
C
12"
12"
12"
12"
12"
B E 14"
F
WAL
LSTR
UCTU
RE
1/4"C
LEAR
ANCE
ONAL
LFO
URSI
DES
OFSU
PPLY
AIR
DUCT
ISRE
QUIR
EDFR
OMCO
MBUS
TABL
EMA
TERI
ALS
NOTE
S:IT
ISRE
COMM
ENDE
DTH
ATA
BEAD
OFSI
LICON
ECA
ULKI
NGBE
PLAC
EDBE
HIND
THE
SIDE
MOUN
TING
FLAN
GES
AND
UNDE
RTO
PFL
ASHI
NGAT
TIME
OF IN
STAL
LATI
ON.
SUPP
LYAI
RDU
CT
RETU
RNAI
ROP
ENIN
G Righ
tSide
View
MIS-
3840
B
WAL
L
Wall
Open
ingan
dHole
Loca
tionV
iew
Retur
n Ope
ning
Supp
ly Op
ening
AB
CD
EF
GRE
QUIR
EDDI
MENS
IONS
TOMA
INTA
IN1/4
"MIN
.CLE
ARAN
CEFR
OMCO
MBUS
TIBL
EMA
TERI
ALS
281/2
81/2
51/4
313/1
617
15/16
391/8
14
REQU
IRED
DIME
NSIO
NSTO
MAIN
TAIN
RECO
MMEN
DED
1"CL
EARA
NCE
FROM
COMB
USTI
BLE
MATE
RIAL
S30
1041
/249
/1617
7/16
391/8
14
MIS-
3840
B
ENTI
RELE
NGTH
OF
TOP.
SEAL
WIT
HBE
ADOF
CAUL
KING
ALON
G
FOAM
AIR
SEAL
![Page 16: 7960-689(H) (2018 06) - Bard HVAC · 2018. 6. 27. · ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax:](https://reader036.fdocuments.in/reader036/viewer/2022062510/61346fffdfd10f4dd73bbafa/html5/thumbnails/16.jpg)
7960-689H Page 16 of 19
FIG
UR
E 1
9TF
CT-
53
B S
uppl
y an
d R
etur
n O
peni
ngs
28" A
C
D
C
12"
12"
12"
12"
12"
B E 16"
F
1414
39 1
/8
SILI
CONE
CAU
LKIN
G BE
PLA
CED
BEHI
ND
Wal
l Ope
ning
and
Hol
e Lo
catio
n Vi
ew
SUPP
LY A
IR
OPEN
ING
Righ
t Sid
e Vi
ew
G
WAL
L ST
RUCT
URE
NOTE
S:
FROM
COM
BUST
ABLE
TOP
FLAS
HING
AT
TIM
E OF
INST
ALLA
TION
.
MAT
ERIA
LS
THE
SIDE
MOU
NTIN
G FL
ANGE
S AN
D UN
DER
DUCT
39 1
/8
RETU
RN A
IR
1/4"
CLE
ARAN
CE O
N AL
LFO
UR S
IDES
OF
SUPP
LYAI
R DU
CT IS
REQ
UIRE
D
IT IS
REC
OMM
ENDE
D TH
AT A
BEA
D OF
WAL
L
FRE
QUIR
ED D
IMEN
SION
S TO
MAI
NTAI
N1/
4" M
IN. C
LEAR
ANCE
FRO
M
Retu
rn O
penin
g
4 9/
164
1/2
1030
5 3/
43
13/1
65
1/4
8 1/
228
1/2
ED
CB
A
COM
BUST
IBLE
MAT
ERIA
LSRE
COM
MEN
DED
1" C
LEAR
ANCE
FRO
MRE
QUIR
ED D
IMEN
SION
S TO
MAI
NTAI
N
COM
BUST
IBLE
MAT
ERIA
LS
Supp
ly O
penin
g
4 1/
4
MIS
-384
1 A
ENTI
RE L
ENGT
H OF
TOP
.
SEAL
WIT
H BE
ADOF
CAU
LKIN
G AL
ONG
FOAM
AIR
SEA
L
MIS
-38
41
A
![Page 17: 7960-689(H) (2018 06) - Bard HVAC · 2018. 6. 27. · ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax:](https://reader036.fdocuments.in/reader036/viewer/2022062510/61346fffdfd10f4dd73bbafa/html5/thumbnails/17.jpg)
7960-689H Page 17 of 19
FIGURE 20Fastening Unit to Curb
SURFACE
1
MIS-3086
INNER CURB
2
OUTER CURB
CAULK THIS
8
5
4
3
76
INNER BACK
![Page 18: 7960-689(H) (2018 06) - Bard HVAC · 2018. 6. 27. · ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax:](https://reader036.fdocuments.in/reader036/viewer/2022062510/61346fffdfd10f4dd73bbafa/html5/thumbnails/18.jpg)
7960-689H Page 18 of 19
FIGURE 21Sealing with Caulk
1" Recommended.
1/4" Minimumdistance required.
Supply
mounting flanges at time of installation.
DuctAir
Wall
It is recommended that a bead of siliconecaulking be placed behind the inner curb
ReturnAir
Duct
9 5/16" 22 11/32"
Seal with (2) beadsof caulking along
entire length of top and 2" down sides.
MIS-3274
![Page 19: 7960-689(H) (2018 06) - Bard HVAC · 2018. 6. 27. · ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave. N.W. Washington, DC 20009 Telephone: (202) 483-9370 Fax:](https://reader036.fdocuments.in/reader036/viewer/2022062510/61346fffdfd10f4dd73bbafa/html5/thumbnails/19.jpg)
7960-689H Page 19 of 19
FIGURE 22Sealing with Caulk (Top Outlet Curb)
1/4" Minimumdistance required.1" Recommended.
Wall
Supply
DuctAir
AirReturn
Duct
It is recommended that a bead of siliconecaulking be placed behind the inner curbmounting flanges at time of installation.
22 3/8"
24"
9 3/8"
MIS-3275
Seal with (2) beadsof caulking alongentire length of top and 2" down sides.