17 no. 02 · This selects the maximum DHW set point temperature. Fluctuating DHW outgoing...
Transcript of 17 no. 02 · This selects the maximum DHW set point temperature. Fluctuating DHW outgoing...
PARAMETER SETTINGS
PERFORMANCE DATA
DIAGNOSTIC CODES
2
To Obtain Performance Data:
1. Press and hold the (Down) button for two
seconds (Fig 1).
2. While holding the (Down) button, press
and hold the “Domestic Hot Water” (DHW)
button (hold both buttons at the same time)
(Fig 1).
3. Use the (Up) and (Down) buttons to
scroll to the desired information described in
Table 1. Performance Data (Fig 2).
4. The data for the performance number
automatically appears in the display (Fig 3).
5. To exit performance data, repeat step 2 above.
1
Table 1. Performance Data
To Display Diagnostic Codes:
1. Press and hold the “DHW” button for two seconds and then the (Up) button simultaneously (Fig 9).
2. The last nine maintenance codes display and flash one after the other.
3. To exit diagnostic codes and return the boiler to normal operation, press and hold the “DHW” button for two seconds, and then the (Up) button simultaneously.
1. To access the parameter settings, press and hold the red button on the PC Board for five seconds (Fig 5).
2. Press the “Mode” button on the controller (Fig 6).
3. Press the (Up) or (Down) arrows to select a parameter setting. Press the “Select” button (Fig 7).
# Data Unit
01 Water Pressure PSI/bar1
02 Water Flow Rate x0.1 GPM/LPM1
03 Supply Temperature °F/°C1
04 Return Temperature °F/°C1
05 Freeze Protection Temperature °F/°C1
06 Exhaust Temperature °F/°C1
07 Outgoing Temperature °F/°C1
08 Inlet Temperature °F/°C1
10 Heat Exchanger Outlet Temperature °F/°C1
11 Fan Frequency Hz
13 Water Flow Control Position 0=Mid, 1=Open, 2=Closed
14 Bypass Flow Control Position Degrees of Opening
15 3-Way Valve Control Position 0=Mid, 1=DHW, 2=CH
16 3-Way Valve Control Cycles x100
MODE
Eco
MODE
Eco
MODE
Eco
MODE
Eco
1
MODE 2
Eco
1
3 See “Electrical Diagnostics” section of this document.
3 Eco Eco
MODE MODE
4
2 3
4
5. To exit parameter settings and enter normal operation mode, press either the red
button on the PC Board or the “Mode” button on the controller.
COMPONENT WIRE COLOR VOLTAGE RESISTANCE PCB
Connector PIN
Power Supply Black-White 108-132 VAC N/A CN24 1-3
Flame Rod Yellow-Body More than 2 VAC2 N/A CN1 2
Spark Electrode Red-Black 11-14 VDC2 N/A CN1 11-22
Combustion Fan
Red-Black 7-48 VDC2 N/A CN1 3-5
White-Black 2-14 VDC2 N/A CN1 5-9
Yellow-Black 11-14 VDC N/A CN1 5-7
Water Flow Control Device
Red-Pink N/A 40-60Ω
CN1 18-20
White-Blue CN1 14-16
Grey-Orange 11-14 VDC N/A CN1 11-29
Brown-Grey Servo Valve Fully Open or Closed: Less than 1 VDC Servo Valve in a Mid Position: 4-6 VDC N/A CN1 25-29
Venturi Control Device
Blue-White N/A 33-43Ω
CN1 17-19
Yellow-Red (No.9) CN1 13-15
Black-Red (No.3) 11-14 VDC
N/A
CN1 11-29
Black-Brown Close Position: Less than 1 VDC Open Position: 4-6 VDC CN1 26-29
Black-Grey Close Position: 4-6 VDC Open Position: Less than 1 VDC CN1 24-29
By-Pass Flow Control Device Red-Pink
N/A 40-60Ω CN1 10-12
White-Blue CN1 6-8
3-way Valve
Brown-Grey Servo Valve Fully Open or Closed: Less than 1 VDC Servo Valve in a Mid Position: 4-6 VDC N/A
CN1 23-29
Orange-Grey 11~14 VDC CN1 11-29
Pink-Red N/A 40-60Ω
CN11 1-2
White-Blue CN11 3-4
Gas Solenoid Valve Yellow-Black 11-14 VDC2 15-25Ω CN1 28-30
Outgoing Thermistor White-White
N/A
59°F: 11.4-14kΩ 86°F: 6.4-7.8kΩ
113°F: 3.6-4.5kΩ 140°F: 2.2-2.7kΩ 221°F: 0.6-0.8kΩ
Disconnect the connector and measure at thermistor side.
CN11 18-19
White-White CN11 10-13
Inlet Thermistor White-White CN11 17-19
Exhaust Thermistor White-White CN11 16-19
Heat Exchanger Thermistor White-White CN11 15-19
Supply Thermistor White-White CN11 12-19
Return Thermistor White-White CN11 10-20
Freeze Protection Thermistor Black-Black 32°F: 38k-43k 50°F: 22k-26k 68°F: 14k-17k Disconnect the connector and measure at thermistor side. CN11 10-14
Transformer White-Grey 108-132 VAC
N/A CN18 1-2
Red-Red 20-30 VAC (possible to measure at Output terminal as substitute position) CN18 3-4
Overheat Switch Black-Black Less than 1 VDC Less than 1Ω 7(CN11)-27(CN1)
Water Flow Sensor Black-Red 11-14 VDC
N/A CN1 11-29
Yellow-Black 4-7 VDC2 More than 6 Hz (0.26 GPM) 9(CN11)-29(CN1)
Water Pressure Sensor Red-Black 11-14 VDC
N/A CN1 11-29
Yellow-Black 0 kPa: 655-745 mV; 200 kPa: 2,155-2,245 mV; 400 kPa: 3,655-3,745 mV 6(CN11)-29(CHN1)
Water Level Electrode White-White 11-14 VDC N/A 8(CN11)-29(CN1)
Integrated Pump White-Black 108-132 VAC N/A CN21 1-2
Air Handler Red-Black 11-14 VDC N/A CN8 1-2
Control Panel Black-Black 11-14 VDC N/A CN2 1-4
Additional Controller(s) White-White 11-14 VDC N/A CN29 1-3
Important Safety Notes
There are a number of (live) tests required when performing electrical diagnostics on this product. Proceed with caution at all times to avoid contact with energized components inside the boiler. Only trained and qualified service technicians should attempt to repair this product. Before checking for resistance readings, disconnect the power source to the unit and isolate the item from the circuit (unplug it).
Electrical Diagram
Refer to the Wiring Diagram attached to the back of the boiler front cover.
Flame Rod
Place one lead of your meter to the flame rod and the other to the ground. When the unit is attempting to ignite, you should read more than 2 VAC.
Amp Fuses
This unit has two (10) amp glass fuses located on the PC Board. Remove the fuses and check continuity through it. If you have continuity through each fuse, then it is functioning. Otherwise, the fuse is blown and must be replaced.
no. 02 6.8
PC Board
01-A 11-A
4. Press the (Up) or (Down) arrows to change the selection for the setting
number (such as 11-A or 11-b). Then, press the “Select” button (Fig 8).
11-
Parameter Number Setting Description
Selection Record date and parameter when individual parameters have been adjusted factory default.
Parameter Value Date Adjusted Parameter Value Date Adjusted A b C d
00 Pressure Indication on the Control Panel.
Yes No
The current pressure will cycle on the controller display.
01 Outdoor Reset Curve.
Curve 1 Curve 2 Curve 3 Curve 4 This parameter is available when Dip Switch 1 is in the OFF (default) position. Select the proper curve from below.
02
Boost No 30
Minutes 60
Minutes
This parameter is available when Dip Switch 1 is in the OFF (default) position. Boost Mode increases the CH set temperature above the outdoor reset curve target when the boiler has been running on an unusually long call for heat.
03 Maximum Outdoor Temperature at which the Boiler will Fire in CH Mode. No
Maximum 77°F (25°C)
Parameter is available when DIP switch 1 is in the OFF (default) position. This sets the maximum outdoor temperature the boiler will fire in CH mode.
10 Maximum DHW Set Point Temperature.
120°F (49°C) 140°F (60°C) This selects the maximum DHW set point temperature.
11 How Long Diverter Valve is in DHW Position.
3 Minutes 10 Seconds This selects the length of time the 3-way valve will stay in the DHW position after using DHW even if a CH demand is present.
12 DHW Recirculation Piping Setup. Crossover Valve
Dedicated Return
This parameter is available when DIP switch 3 is in the ON position. Ensure this setting corresponds to the DHW recirculation piping.
13 DHW Recirculation with Timer Relay Input.
Yes No This parameter is available when DIP switch 3 is in the ON position. This enables an external timer to also control the timing for DWH recirculation to more directly correspond to the customers needs.
14
CH Temperature Limitation During Simultaneous Operation. Yes No
This parameter is available when DIP switch 3 or 4 is in the ON position. This enables the CH temperature setting to be limited during simultaneous DHW and CH operation.
15
3-Way Valve Position During Simultaneous Operation. Normal Additional CH
This parameter is available when DIP switch 3 or 4 is in the ON position. This adjusts the 3-way valve position to open the CH side more for when the flow of the CH side is reduced due to DHW demand. This may restrict the DHW capacity.
16 LC (Limescale Condition) Check.
Available No Detection This setting enables the boiler to check for limescale conditions in the DHW side of the plate heat exchanger.
17 Adjust DHW Temperature Setting.
0°F (0°C) 1.8°F (1°C) 3.6°F (2°C)
5.4°F (3°C)
Enables the DHW output temperature to be adjusted without adjusting the set point temperature to make up for system temperature losses.
18 DHW Continuous Operation Time. 120 Minutes
60 Minutes
180 Minutes Unlimited
This setting adjusts the maximum continuous operating time of DHW, whether in DHW priority or simultaneous modes.
40 Linked Operation Between CH Pump 1 and 2.
No Yes (Linked Together) This parameter enables linked operation between the CH Pump 1 and 2.
41 Linked Operation Between Main Boiler Pump and CH Pump 1.
No Yes (Linked Together) (If selected, hydraulic
This enables the linked operation between the main boiler pump and CH pump 1.
42 Main Pump Runs When the Target Temperature is Achieved.
Continuously Intervals This selects the mode of the main pump running when the target setpoint is achieved.
43 External Pump Runs When the Setpoint Temperature is Achieved. Same as Main Pump Does Not Run
This selects the mode of the external pump(s) running when the target setpoint is achieved.
44 External Pump Runs When Freeze Protection is in Operation. Does Not
Run Same as Main Pump This selects how the external pump operates when freeze protection is in operation.
45 Freeze Protection Level. Default When Boiler is Installed
This selects the freeze protection level. Selecting “B” will prevent the boiler from operating in freeze protection mode more than necessary.
46
The Differential Temperature from Ceasing Fire to Firing Again. Normal Quick
How much temperature drop is permitted by the supply water thermistor before the boiler will fire again. CH Setting Temperature. Temperature Drop 168-182°F (75-82°C) 27°F (15°C) 15°F (8°C) 104-166°F (40-74°C) 15°F (8°C) 9°F (5°C)
47 The Time Which the Boiler is not Allowed to Fire Again for CH. Normal
(3 Minutes) Quick
(10 Seconds)
This selects the time which the boiler will not be able to fire again for CH after the burner has shutdown.
49 Will the boiler shut down on a high return water temperature.
Yes No This setting is for whether the boiler will shut down at high return water temperatures.
60 Not Available. Not Available
A0 Gas Type.
Natural Gas Liquid Propane For selecting gas type when conducting gas conversion.
A1 Not Available. Not Available
A2
Vent Material Used. PVC Material other than
PVC: CPVC/PP/Other
This selects the venting material used. The boiler is set from the factory to be installed in a PVC venting system. If CPVC, PP, or other approved venting is used, this may be adjusted. See section “5.4 PVC Venting Safety Switch” for more information.
ELECTRICAL DIAGNOSTICS
# Data Unit 17 Venturi Position 0=Closed, 1=Open
18 Venturi Cycles x100
20 Pump Cycles x100
21 Pump Hours x10
22 Pump for Boiler 0=OFF, 1=ON
23 Pump for System (Pump 1) 0=OFF, 1=ON
24 Pump for System (Pump 2) 0=OFF, 1=ON
31 Outdoor Temperature °F/°C1
32 Additional Controllers Connected See Table 3
40 Energization Hours x100
41 Combustion Hours x10
42 Combustion Cycles x100
43 Combustion Hours (DHW) x10
44 Combustion Cycles (DHW) x100
45 Commissioning Cycles x1
CH DHW Units of
Measurement Temp. Water Flow Pressure
1: English °F gal/min psi
2: Metric °C L/min bar
Units of Measurement
1. Press the “Mode” button.
2. Press the (Up) or (Down) arrows to select a unit of measurement (refer to Table 2).
For more information on parameter settings, refer to the I-Series Condensing Boiler Installation and Operation Manual.
ALTITUDE DIP
Switch 6 DIP
Switch 7
0-2,000 ft (0-610 m) (Default) OFF OFF
2,001-5,400 ft (610-1,646 m) ON OFF
5,401-7,700 ft (1,646-2,347 m) OFF ON
7,701-10,200 ft (2,347-3,109 m) ON ON
DIP Switches (Section 12 in Manual and Table 5 below)
# DIP Switch Function
1
Outdoor Temperature Sensor: Enables or disables outdoor temperature sensor. OFF (Default): Outdoor Temperature Sensor in Use ON: Outdoor Temperature Sensor Not in Use
2 Thermostat Usage: Changes mode between Thermostat Usage and Central Heating (CH) Button. OFF (Default): Thermostat Used ON: CH button used. Boiler fires based on return water temperature
3 DHW Recirculation: Enables DHW Recirculation function for Pump 2 connection. OFF (Default): Pump 2 Connection Enabled for Second CH Zone Pump ON: DHW recirculation ON (Pump 2 connection for DHW Recirculation Pump)
4 Simultaneous CH and DHW: Enables simultaneous operation between CH and DHW. OFF (Default): DHW Priority; ON: Simultaneous CH and DHW Permitted
5 Gas Valve Solenoid: Manually shuts down the integrated solenoid gas valve. OFF (Default): Normal Operation; ON: Fixed Closed (prevents boiler operation)
6 Altitude Setting: Sets the appropriate elevation of the boiler installation. OFF/ON: Depends on Altitude. See “Table 6. High Altitude DIP Switches” for specific DIP switch settings.
7 Altitude Setting: Sets the appropriate elevation of the boiler installation. OFF/ON: Depends on Altitude. See “Table 6. High Altitude DIP Switches” for specific DIP switch settings.
8 Vent Type Selection: Selects the venting material used. The boiler is set from the factory to be installed in a PVC venting system. If CPVC, PP, or other approved venting is used, this setting may be adjusted. See Section 5 in Manual for more information. OFF (Default): PVC ON: Higher Temperature Exhaust Vent Material (PP, CPVC, or Stainless Steel)
SW1 Forced Hi/Low Fire Modes (Section 12 in Manual)
SW2 Deaeration Mode (Section 10 in Manual)
SW3 Data Transfer Mode (Transfers PC Board data when replacing PC Board. Refer to instructions included in replacement parts.)
SW4 Parameter Settings (Section 12 in Manual)
OFF
ON
Power Reset
Heat Exchanger Overheat (140), Venturi Control (150), High Exhaust Temperature (540), and Freeze issue (890) can be reset by shutting down power to the boiler.
Interlock Reset Venturi (170) and Solenoid Valve Circuit (520) can be reset by pushing and holding buttons SW1 and 2 for five seconds.
Combustion Error During DHW Error can be reset by closing faucet.
Other Reset Other error can be reset by Domestic “On/Off” button or “Central Heating” (CH) button.
DIP SWITCHES
Controllers Connected
Controller Model Connected Not Connected
Controller Panel _ _ _ 1 ―
Additional Controller (BC) _ _ 1 _ _ _ 0 _
Additional Controller (BSC) _ 1 _ _ _ 0 _ _
Additional Controller (BSC2) 1 _ _ _ 0 _ _ _
Table 2. Units of Measurement
Table 3. Connecting Additional Controllers
Table 4. Diagnostic Points
Table 7. Parameter Settings
Table 5. DIP Switch Functions Table 6. High Altitude DIP Switches
Table 8. Error Reset
Table 9. Diagnostic Codes
Fig 1. “Down” and “DHW” Buttons Fig 2. “Up” and “Down” Buttons
Fig 7. “Up,” “Down” and “Select” Buttons
Fig 4. PC Board DIP Switches and Buttons
Fig 5. Red Button on PC Board
Fig 6. “Mode” Button
Fig 8. “Up,” “Down” and “Select” Buttons
Fig 9. “Up” and “DHW” Buttons
Fig 3. Data Appearing in Display
Note: BC, BSC and BSC2 are PCB recognition position.
06/2020 800000115(02)
2 When the unit is operating.
1 See “Units of Measurement” section to the right.
1
021 Continuous DHW
• This code will display when DHW is in continuous operation for extended periods of time. Ensure there are no open faucets.
• Ensure there are no leaks in fixtures or the plumbing system.
100 Air Supply or Exhaust Blockage/Condensate Trap is Full
• Fan current initial check error. • Ensure condensate line and trap is not blocked. • Ensure internal air filter is clean with no obstructions. • Ensure high altitude setting is set properly (See Table 6. High Altitude DIP Switches). • Ensure combustion air and exhaust vents are not blocked and the approved venting
materials are being used. • Ensure either the exhaust ring or intake cap is removed properly. • Ensure vent length is within limits. • Check fan for debris and ensure wheel turns freely. • Verify fan check valve is not stuck between fan casing and burner body.
110 No Ignition (Unit Not Turning On)
• Ignition Error. • Check that the gas is turned on at the boiler, gas meter, and/or propane cylinder. • If the unit is installed in a propane system, ensure that gas is in the tank. • Bleed all air from the gas lines. • Check the ground wire for the PC Board. • Ensure the flame rod wire is connected. • Ensure the igniter is operational.3 • Ensure the venting is installed in accordance with the I-Series Boiler Installation and
Operation manual. • Check that the surface of the electrode and flame rod are clean. • Check gas solenoid valves for open or short circuits.3 • Verify gas orifice installed is correct for the gas system the unit is installed in. • Check flame rod voltage to ground during ignition.
120 Flame Failure
• Boiler has flame failure. • Check that the gas is turned on at the boiler, gas meter, and/or propane cylinder. • If the unit is installed in a propane system, ensure that gas is in the tank. • Ensure the venting is installed in accordance with the I-Series Boiler Installation and
Operation Manual. • Ensure the flame rod wire is connected. • Ensure the gas type and inlet gas pressure are correct. • Bleed all air from the gas lines. • Check the ground wire to the PC Board. • Check flame rod voltage to ground during ignition.
140 Heat Exchanger Overheat
• Overheat switch is tripped. • Measure the resistance of the Overheat Switch.3 • Check the heat exchanger surface for hot spots which may indicate blockage due to
scale buildup. • Ensure the boiler pump is not locked up. • Ensure that all of the valves in the CH circuit are open. • Ensure the boiler and CH circuit does not have a freezing condition. • The surface of the heat exchanger may turn to a black color as stainless steel is
tempered even in normal conditions. This does not indicate an abnormal condition. • Check for damage on the exhaust, seal, and venting. • Ensure the parameter A0 corresponds to the gas type the unit is installed in. • Ensure the gas orifice is the proper orifice for the gas type in use. • Ensure deaeration has been performed.
150 Venturi Control
• Venturi operation error. • Ensure the venturi motor is operating correctly.3 • Replace the gas valve assembly.
161 High Outgoing Temperature
• Safety shutdown because DHW outgoing temperature is too hot. • Check sensor wiring for damage of outgoing thermistor. • Measure resistance of outgoing thermistor.3 • Ensure the gas valve has no damage and the orifice is installed correctly. • Replace the gas valve assembly.
170 Venturi Blockage
• Check the venturi and silencer for blockage. • Before resetting this error, check if the condensate drain is blocked and if the
venting is connected properly.
190 Electrical Grounding
• Secondary circuit ground fault. • Check all electrical components for electrical short.
250 Condensate Pump (Accessory)
• Boiler will operate for 60 seconds. • Confirm wire connections and harnesses are good. • Ensure the condensate reservoir is empty and condensate pump is operational.
310 Freeze Protection Thermistor
• Check sensor wiring for damage. • Measure the resistance of the sensor. Replace if necessary.
321 Outgoing Thermistor
• Check sensor wiring for damage. • Clean sensor of any scale buildup present. • Measure the resistance of the sensor. Replace if necessary.
331 Heat Exchanger Thermistor
• Check sensor wiring for damage. • Measure the resistance of the sensor. Replace if necessary.
341 Inlet Thermistor
• Check sensor wiring for damage. • Measure the resistance of the sensor. Replace if necessary.
353 Supply Thermistor
• Check sensor wiring for damage. • Clean the surface of the sensor. • Measure the resistance of the sensor. • Check the return thermistor. Replace if necessary.
380 Exhaust Thermistor
• Check sensor wiring for damage. • Clean the surface of the sensor. • Measure the resistance of the sensor. • Check the return thermistor. Replace if necessary.
363 Return Thermistor
• Check sensor wiring for damage. • Measure the resistance of the sensor. Replace if necessary.
393 Outdoor Thermistor
• Ensure that DIP switch 1 is set to the appropriate position. • Check sensor wiring for damage. • Measure the resistance of the sensor. Replace if necessary.
400 Pressure Sensor
• Check sensor wiring for damage. • Measure the voltage of the sensor. • Replace if necessary.
430 High/Low Water Pressure
• If the water pressure is too low, add water into the system until at least 13 PSI is observed.
• Ensure there are no leaking components in the CH system. • If the pressure is too high, adjust the pressure to a maximum of 30 PSI. • Ensure the pressure relief valve and water fill are working correctly. • Ensure deaeration has been performed.
443 Low Water Cut-Off (LWCO)
• Ensure the LWCO device is working correctly. • Ensure the LWCO jumper is connected properly when LWCO is not in use. • Ensure the output is 24 VAC on the PCB. If it is not, check the transformer harness
and output of transformer.
520 Solenoid Valve Circuit
• Check the flame rod and wire for damage. • Close the gas shut off valve installed near the boiler. • Ensure the flame rod and wire are not wet. • Check the output from the PC Board to the solenoid gas valve.
- If the output from the PC Board is abnormal, replace the PC Board. - If the output from the PC Board is normal, replace the gas control.
540 High Exhaust Temperature
• Check the exhaust thermistor wiring for damage. • Clean the surface of the thermistor. • Measure the resistance of the exhaust thermistor.3 • If the sensor has been replaced and the error still appears, check the return
thermistor. • If the boiler is used in a hard water area, flush the DHW plate heat exchanger. • Check the exhaust duct, seal, and venting for damage.
610 Combustion Fan
• Check the motor wire harness for loose or damaged connections. • Measure resistance and voltage of motor wire harness.3 • Ensure the combustion fan spins freely.
631 DHW Recirculation Pump
• Ensure the DHW recirculation matches the Parameter 12 setting as described in “Table 7. Parameter Settings.”
• Ensure the dedicated return line is properly installed. • Ensure the inlet water filter and bypass filter are clean and free of debris. • Ensure the DHW recirculation pump is connected to the DHW Pump
Terminal. • Ensure the capacity of the recirculation pump is sized appropriately for the
piping (DHW recirculation pump should be higher than 1.3 GPM). • Ensure air is removed from the recirculation line.
651 Water Flow Control
• Measure the resistance values and voltage of the water flow control.3 • Ensure the harness and connector are not wet. • If the voltage from the PC Board is abnormal, replace the PC Board;
otherwise, replace the water flow servo valve. 661 Bypass
• Measure the resistance values and voltage of the bypass servo valve.3 • Ensure the harness and connector are not wet. • If the voltage from the PC Board is abnormal, replace the PC Board;
otherwise, replace the bypass servo valve.
670 3-Way Valve
• Measure the resistance values and voltage of the 3-way valve control.3 • Replace the 3-way valve control device. • Check the CH system water quality to confirm it is within recommended
range and to prevent valve failures.
681 Hot Water Supply Temperature Abnormality
• If the DHW water temperature is higher than the set point temperature because the boiler bypass servo fails to close.
• Measure resistance values and voltage of the bypass flow control.3 • Replace the bypass flow control device if needed; otherwise, check the inlet
thermistor and heat exchanger thermistor wiring for damage. • Measure the resistance of the sensor. • Clean the sensor of any scale buildup present. • Replace if needed.
700 PC Board
• PC Board circuit error. • Replace PC Board.
710 Solenoid Valve Circuit
• Ensure Dip switch 5 on the PC Board is in the OFF position (default). • Ensure the gas control wire is not loose or damaged. • Replace the PC Board.
720 Flame Rod
• Check the flame rod and wire for damage. • Ensure the flame rod and wire are not wet. • If there is no issue with the flame rod or wiring, replace the PC Board.
890 Freeze Issue
• The boiler checks the heat exchanger temperature at the time of operation. • If the temperature is too low, an error will occur. • Check if there is freezing in the boiler or CH system.
999 PC Board Mismatch
• This code occurs when the PC Board and the internal logic do not match. • Check if the software versions of the board and operation board do not
match.
LC Scale Buildup in Heat Exchanger
• Flush the DHW plate heat exchanger. • The LC code will reset automatically when scaling is removed. If the LC code
remains, check the DHW thermistor, flow sensor or boiler pump.
FFF Maintenance Indicator
• This code is a placeholder in diagnostic code history indicating a service provider performed maintenance or service. Enter this code after performing service by pressing the following buttons at the same time: Up, Down, and DHW. “FFF” appears on the monitor (Fig 10).
No Code Nothing happens when DHW water flow is activated
• Verify the minimum flow rate required to fire the boiler is seen. • Measure the resistance of the flow control sensor.3 • Clean the inlet water supply filter. • On new installations, ensure the hot and cold water lines are not reversed. • Confirm the inlet water temperature is not too high. • Ensure the integrated boiler pump operates properly. • Ensure the DHW operation switch is on.
No Code Decreasing or fluctuating DHW water flow volume
• Ensure the gas pressure is proper. • Ensure the water pressure is proper. • Ensure the inlet water filter for DHW is clean. • Ensure there is no limescale buildup present. • Ensure the vent and vent settings are properly set up. • If a DHW recirculation system is used, the DHW flow volume may vary slightly. • Ensure all air has been purged from the system. • Ensure the pump is set to speed 3. • During simultaneous CH and DHW operation mode, it is possible to see
decreased DHW flow.
No Code Fluctuating DHW outgoing temperature
• Ensure the gas pressure is proper. • Ensure the water pressure is proper. • Ensure the DHW thermistor, flow servo, and bypass servo are in good
condition. • Ensure the inlet filter for DHW is clean. • If a DHW recirculation system is used, the DHW temperature may vary slightly. • Ensure all air is removed from the system.
No Code Boiler does not start heating with a heating demand present
• Supply temperature or return temperature inside the boiler may be too hot. • Ensure the pump operates properly. • If there is a demand immediately after using DHW, wait at least three minutes
for operation. No
Code The boiler does not operate with the CH setting button
• If DIP switch 2 is OFF, CH operation (the light on the CH button is off) will
function via the room thermostat. No
Code DHW recirculation does not begin
• Ensure the DHW recirculation pump is connected to the DHW_Pump terminal. • Ensure DIP switch 3 is ON. • Ensure the DHW recirculation plumbing type is set properly per Parameter 12
as described in “Table 7. Parameter Settings.” • Ensure the DHW recirculation with timer relay input is set properly per
Parameter 13 as described in “Table 7. Parameter Settings.” • Ensure the wiring to the external timer is correct. • Ensure the external timer is ON, if in use. • The recirculation logic has an OFF interval after use.
No Code Simultaneous DHW and CH is not functional
• Ensure DIP switch 4 is ON. • If CH set point temperature is lower than 140°F, it is not permitted (this
includes outdoor reset temperature settings). • Ensure the DHW inlet temperature is not too hot. • Ensure the heating load for DHW and CH are within limits to handle both
simultaneously. No
Code Cannot change the DHW set point temperature
• When DHW is being produced, the temperature setting can only be adjusted between 98°F and 110°F.
No Code Supply temperature is different from the setting temperature on the controller
• During outdoor sensor control, the supply temperature will vary dependent on the outdoor temperature.
• During simultaneous operation of DHW and CH, the supply temperature for CH is based on DHW control.
No Code CH capacity is insufficient
• Ensure the parameters are properly set for the installation. • During simultaneous operation of DHW and CH, flow volume to heating can be
reduced. No
Code Pump or fan is operating even with no demand
• The boiler may start or operate the pump for freeze protection operation. • The pump may intermittently operate to prevent it from becoming stuck.
No Code Cannot turn off ECO mode
• During DHW recirculation, ECO switch will always be on.
Fig 10. “Up,” “Down” and “DHW” Buttons
DHW CH
e:FFF
DHW
Up and Down
Gas C
on
version
Kits
Mo
dels
Gas Typ
e
Kit N
um
be
r
i12
0C
80
30
00
04
0
NG
/LPG
i0
90
C
i06
0C
Rin
nai A
merica C
orp
orati
on
con
tin
ually u
pd
ates materials, an
d as su
ch, co
nten
t is sub
ject to ch
ange w
itho
ut n
oti
ce. For fu
rther in
form
atio
n, co
ntact R
inn
ai at 1-8
00
-62
1-9
41
9 o
r visit ww
w.rin
nai.u
s
21
3
Exhau
st Gasket - 2
inch
1
09
00
06
23
1
1
1
21
5
Air Su
pp
ly Pip
e Seal Rin
g 1
08
00
00
17
1
1
1
22
0
Air Su
pp
ly Bo
x 1
08
00
00
85
1
1
1
22
1
Air Su
pp
ly Filter (set) 1
08
00
00
86
1
1
1
22
2
Air Su
pp
ly Asse
mb
ly 1
08
00
00
87
1
1
1
22
3
Air Su
pp
ly Gasket - 2
inch
1
09
00
06
24
1
1
1
40
0
3/4
DH
W C
old
Co
nn
ectio
n
80
70
00
17
7
1
1
1
40
1
Water Su
pp
ly Filter Plu
g Asse
mb
ly 1
07
00
03
17
1
1
1
40
2
Recti
fier (4
02
) V2
53
2Ffu
W/W
C/2
52
6W
M
8D
1-1
5
1
1
1
40
3
Water Flo
w Servo
and
Senso
r Assem
bly
80
70
00
17
8
1
1
1
40
5
Byp
ass Tub
e
80
70
00
17
9
1
1
1
40
6
Byp
ass Servo A
ssemb
ly 8
07
00
01
80
1
1
1
40
7
Co
ver
10
70
00
09
3
3
3
3
40
9
Flow
Turb
ine A
ssem
bly
80
70
00
18
1
1
1
1
41
0
CH
Ou
tlet Co
nn
ectio
n
80
70
00
18
2
2
2
2
41
1
Plate H
EX-Large
80
70
00
18
3
1
41
2
Plate H
EX-M
ediu
m
80
70
00
18
4
1
1
41
3
Water P
ressu
re Senso
r Asse
mb
ly 8
07
00
01
85
1
1
1
41
4
Plu
g Ban
d
10
90
00
01
8
1
1
1
41
5
Plate H
EX-C
H H
eatin
g Co
nn
ectio
n
80
70
00
18
6
1
1
1
41
7
3-W
ay Valve A
ssemb
ly 8
07
00
01
87
1
1
1
41
8
Circu
latio
n P
um
p A
ssemb
ly 8
07
00
01
88
1
1
1
41
9
Pu
mp
Co
nn
ectio
n A
ssemb
ly 8
07
00
01
89
1
1
1
42
0
Pu
mp
-Plate H
EX C
on
necti
on
Tub
e
80
70
00
19
0
1
1
1
42
1
Pu
mp
Stand
8
07
00
01
91
1
1
1
43
0
DH
W O
utlet Tu
be
8
07
00
01
92
1
1
1
43
1
Heat Exch
anger P
ipe C
on
necti
on
8
07
00
01
93
1
43
2
DH
W O
utlet
80
70
00
19
4
1
1
1
43
5
Trap D
rain P
lug A
ssy 8
07
00
01
95
1
1
1
44
0
HEX
-CH
Heati
ng C
on
necti
on
Pip
e
80
70
00
19
6
1
1
1
44
1
Heat Exch
anger P
ipe C
on
necti
on
Assy-M
ediu
m
80
70
00
19
7
1
1
44
3
Secon
dary H
eat Exchan
ger Ou
tlet Fittin
g 8
07
00
01
98
1
1
1
44
4
Secon
dary H
eat Exchan
ger Inlet Fitti
ng
80
70
00
19
9
1
1
1
44
5
Prim
ary-Secon
dary P
ipe A
ssy-Large
80
70
00
20
0
1
44
6
Prim
ary-Secon
dary P
ipe A
ssy-Med
ium
8
07
00
02
01
1
1
44
7
Prim
ary-Secon
dary C
on
necti
ng Fitti
ng
80
70
00
20
2
1
45
0
Pip
e Bracket
U2
11
-32
2X
01
1
1
1
45
1
Pip
e Bracket
80
90
00
16
8
2
1
1
45
2
Reten
tio
n C
lip
80
90
00
16
9
2
1
1
45
3
Pip
e Bracket
80
90
00
17
0
1
1
1
45
4
Clip
8
09
00
01
71
2
2
2
46
0
Therm
istor Sen
sor
80
50
00
07
9
1
1
1
46
1
Therm
istor Sen
sor
80
50
00
08
0
1
1
1
46
2
Therm
istor Sen
sor
80
50
00
08
1
1
1
1
46
3
Therm
istor Sen
sor
80
50
00
08
2
1
1
1
46
4
TWIN
Therm
istor
80
50
00
08
3
1
1
1
47
0
O-rin
g 8
07
00
02
15
3
3
3
47
1
O-rin
g 8
07
00
02
03
3
3
3
47
2
O-rin
g 8
07
00
02
04
1
4
13
1
3
47
3
O-rin
g 8
07
00
02
05
2
2
2
47
5
O-rin
g Water H
eater 2 K
T
M1
0B
-2-4
2
2
2
47
6
O-rin
g M
10
B-2
-14
2
2
2
47
7
O-rin
g KT
M1
0B
-2-1
6
2
2
2
47
8
O-rin
g, All W
ater Heaters 2
KT
M
10
B-2
-18
1
1
1
47
9
O-rin
g 8
07
00
02
06
2
2
2
48
0
O-rin
g 8
07
00
02
07
1
1
1
50
0
Clip
1
09
00
06
36
1
1
1
50
1
Clip
8
09
00
01
72
4
4
4
50
2
Clip
8
09
00
01
73
2
2
2
50
4
Clip
(i09
0C
and
i06
0C
on
ly) 8
09
00
01
74
1
1
50
5
Clip
1
09
00
06
39
2
2
2
50
6
Clip
1
09
00
06
38
6
6
6
70
0
PC
Bo
ard A
ssem
bly-C
om
bi
80
50
00
08
4
1
1
1
70
1
PC
B C
over
80
90
00
17
5
1
1
1
70
2
Integrated
Re
mo
te Co
ntro
l Assy
80
50
00
08
5
1
1
1
70
5
Transfo
rme
r 8
05
00
00
86
1
1
1
71
0
Po
wer C
ord
Assem
bly FF
10
50
00
23
8
1
1
1
71
2
Senso
r Harn
ess
80
50
00
08
7
1
1
1
71
4
Heater G
rou
nd
Harn
ess 8
05
00
00
88
1
1
1
71
5
Pu
mp
Harn
ess 8
05
00
00
89
1
1
1
71
6
Over H
eat Switch
1
05
00
02
99
1
1
1
71
7
Water P
ressu
re Co
nn
ectio
n H
arness
80
50
00
09
0
1
1
1
71
8
Therm
istor Sen
sor
80
50
00
09
1
1
1
1
71
9
Igniter G
rou
nd
Harn
ess 1
05
00
02
43
1
1
1
72
0
Gu
ide Seal
80
90
00
17
6
1
1
1
75
0
Rem
ote C
on
trol H
arness
10
50
00
24
9
1
1
1
80
0
Screw
1
09
00
07
46
4
4
4
80
1
Screw
C
P-3
05
83
2
2
2
80
2
Screw
ZB
A0
40
8U
K
3
3
3
80
3
Screw
C
P-3
05
80
1
7
15
1
5
80
4
Screw
1
09
00
06
48
3
3
3
80
7
Screw
U
21
7-4
49
5
5
5
80
8
Screw
1
09
00
06
41
3
3
3
81
0
Screw
1
09
00
01
79
8
8
8
81
1
Screw
1
08
00
00
21
2
2
2
81
3
Screw
ZA
D0
40
8U
K
2
2
2
81
4
Screw
1
09
00
06
51
6
6
6
81
6
Screw
C
P-2
08
83
-41
0U
K
1
1
1
81
8
Screw
ZFA
B0
40
8SZ
2
2
2
81
9
Therm
istor Scre
w
ZFAB
04
06
UK
2
2
2
82
0
Screw
8
09
00
01
77
2
2
22
2
2
82
1
Truss Screw
1
09
00
05
98
1
8
18
1
8
82
2
Screw
8
09
00
01
78
4
4
4
82
3
Screw
ZA
A0
40
8U
K
3
2
2
82
4
Screw
8
09
00
01
79
1
1
1
82
5
Gro
un
d Screw
1
09
00
07
93
4
4
4
82
6
Screw
8
09
00
01
80
1
1
1
82
7
Screw
8
09
00
01
81
2
2
2
82
8
Screw
8
09
00
01
82
8
8
8
83
0
Cab
le Clip
8
09
00
01
83
1
1
1
86
0
Wall B
racket 1
09
00
06
28
1
1
1
86
1
Ven
t Screen
Set 1
08
00
01
04
1
1
1
86
2
LP C
on
version
Orifi
ce-In
clud
ed
80
60
00
05
5
1
1
1
86
3
Pressu
re Relie
f Valve
8
07
00
02
11
1
1
1
86
4
Ou
tdo
or Tem
peratu
re Senso
r 8
05
00
00
96
1
1
1
88
8
User m
anu
al 8
00
00
01
14
1
1
1
88
9
Installati
on
and
Op
eratio
n M
anu
al 8
00
00
01
11
1
1
1
89
0
Tech sh
eet 8
00
00
01
15
1
1
1
89
1
User M
anu
al-French
8
00
00
01
45
1
1
1
89
2
Installati
on
and
Op
eratio
n M
anu
al-French
8
00
00
01
46
1
1
1
ITEM
DESCRIPTION
PART
NUMBER
i090C
i060C
i120C
ITEM
DESCRIPTION
PART
NUMBER
i090C
i060C
i120C
00
3
Low
er Wall M
ou
nt B
racket 1
09
00
02
81
1
1
1
00
4
Up
per W
all Mo
un
t Bracket
10
90
00
59
4
1
1
1
00
7
Co
nn
ectio
n R
ein
force
men
t Plate
8
09
00
01
65
1
1
1
00
8
Ru
bb
er Bu
shin
g C
F79
-41
02
0-A
3
3
3
01
0
Resid
enti
al Screw an
d W
asher
10
60
00
64
5
4
4
4
01
2
Co
mb
usti
on
Ch
amb
er Sup
po
rt Plate
1
09
00
05
97
2
2
2
01
5
Igniter B
racket 1
09
00
05
99
1
1
1
01
6
Igniter A
ssem
bly
10
50
00
23
0
1
1
1
01
7
Gro
un
din
g Screw
C
P-8
04
52
1
1
1
01
8
Plate H
EX B
racket 8
09
00
01
66
1
1
1
04
0
Fron
t Pan
el Assy
80
90
00
16
7
1
1
1
04
4
Screw
Co
ver 1
09
00
02
30
2
2
2
04
5
Fron
t Pan
el Packin
g-Top
1
09
00
01
20
2
2
2
04
6
Fron
t Pan
el Packin
g-Side FF
10
90
00
60
8
2
2
2
10
0
Bu
rner A
ssem
bly-Large
8
06
00
00
49
1
10
1
Bu
rner G
asket-Large
10
90
00
60
9
1
10
2
Bu
rner P
late Assem
bly-Large
8
06
00
00
50
1
10
3
Co
mb
usti
on
Ch
eck Valve A
ssem
bly
10
70
00
26
2
1
1
1
10
5
Bu
rner A
ssem
bly-M
ediu
m
80
60
00
05
1
1
1
10
6
Bu
rner G
asket-Med
ium
1
09
00
06
10
1
1
10
7
Bu
rner P
late Assem
bly-M
ediu
m
80
60
00
05
2
1
1
11
0
Co
mb
usti
on
Fan A
ssemb
ly 1
08
00
00
81
1
1
1
11
1
Fan M
ou
nti
ng P
acking
10
90
00
61
1
1
1
1
11
2
O-rin
g 1
09
00
06
12
1
1
1
11
3
Hexago
n H
ead Scre
w
ZQA
A0
51
4U
K
3
3
3
11
4
Gas V
alve Asse
mb
ly 1
06
00
01
17
1
1
1
11
5
O-rin
g 1
09
00
02
52
2
2
2
11
6
Gas C
on
ne
ctio
n P
ipe
8
06
00
00
54
1
1
1
11
7
Gas Tu
be B
racket 1
09
00
06
35
1
1
1
11
8
Inlet G
as Sup
ply C
on
necti
on
1
06
00
01
19
1
1
1
11
9
Inlet G
as Test P
ort Scre
w
10
60
00
13
8
2
2
2
12
0
O-rin
g M
10
B-1
3-4
2
2
2
12
1
No
ise Filter 1
06
00
01
20
1
1
1
13
0
Heat Exch
anger A
ssem
bly-Large
8
07
00
01
73
1
13
1
Heat Exch
anger A
ssem
bly-M
ed
ium
8
07
00
01
74
1
1
13
6
OH
S Bracket
10
90
00
61
4
1
1
1
14
5
Co
nd
ensate Trap
8
07
00
01
75
1
1
1
14
6
Ban
d R
C9
8H
Pi/e, C
on
d D
rain Tu
be, B
ott
om
KT
1
09
00
01
38
2
2
2
14
7
Co
nd
ensate D
rain tu
be
8
07
00
01
76
1
1
1
15
1
Electrod
e
10
50
00
23
3
1
1
1
15
2
Flame R
od
1
05
00
02
34
1
1
1
15
3
Electrod
e Packin
g 1
09
00
06
17
1
1
1
15
4
Electrod
e Plate
10
90
00
61
8
1
1
1
15
6
Electrod
e Slee
ve
10
90
00
62
0
1
1
1
20
0
Exhau
st Du
ct Assy
80
80
00
05
0
1
1
1
20
2
O-rin
g 1
08
00
00
18
2
2
2
20
3
Exhau
st Du
ct Packin
g 1
09
00
06
21
1
1
1
20
4
Therm
istor
10
50
00
23
5
1
1
1
20
5
O-rin
g 1
07
00
03
23
1
1
1
20
6
Exhau
st Du
ct Seal 8
08
00
00
51
1
1
1
20
7
Therm
istor Scre
w
10
90
00
62
2
1
1
1
20
8
Co
mb
usti
on
An
alysis Po
rt Cap
8
06
00
00
57
1
1
1
20
9
Ban
d
10
90
00
13
7
1
1
1
21
0
Flue C
on
necti
on
Asse
mb
ly 1
08
00
00
83
1
1
1
21
2
Exhau
st pip
e con
necti
on
po
rt - 2 in
ch
10
80
00
08
4
1
1
1
ITEM
DESCRIPTION
PART
NUMBER
i090C
i060C
i120C
H167-0775-1×01(00)