IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au Product Catalogue 2013 487 TECHNICAL 15 Motor Protection - general information 488 Motor full load currents 489 DOL Starting Fuse links 490 Circuit Breakers 491 Assisted Starting Fuse links 492 GE Circuit Breakers 493 GE Contactors 494 Auto Transformer Starting GE Contactors 495 Fire Pump Starting Fuse Links 496 Circuit Breakers 497 Type 2 Coordination DOL Class 10 498 DOL Class 20 500 Star Delta 501 Transformers & Capacitors General Information 502 Capacitor Protection Circuit Breakers 504 Capacitor Protection Fuse Links 505 Fuse Links TRx 503 Back Up Protection MCCB & Switch 506 Fuses & MCB’s 506 Circuit Breakers 507 Discrimination & Selectivity Fuses & Fuses 509 Circuit Breakers 510 Enhanced Discrimination & Selectivity Circuit Breakers 516 Fuse Link Temperature De-rating 522 Protection of Cables with Fuse Links 523 GE Contactors for Lighting Circuits 524 Relay Equivalent Selection Chart 526 15 - TECHNICAL INFORMATION

Transcript of 15 - TECHNICAL INFORMATION - IPD Industrial Products 2 Coordination DOL Class 10 498 DOL Class 20...

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

Product Catalogue 2013 487

TEC

HN

ICA

L

15

Motor Protection - general information 488

Motor full load currents 489

DOL StartingFuse links 490Circuit Breakers 491

Assisted StartingFuse links 492GE Circuit Breakers 493GE Contactors 494

Auto Transformer StartingGE Contactors 495

Fire Pump StartingFuse Links 496Circuit Breakers 497

Type 2 CoordinationDOL Class 10 498DOL Class 20 500Star Delta 501

Transformers & CapacitorsGeneral Information 502Capacitor Protection Circuit Breakers 504Capacitor Protection Fuse Links 505Fuse Links TRx 503

Back Up ProtectionMCCB & Switch 506Fuses & MCB’s 506Circuit Breakers 507

Discrimination & SelectivityFuses & Fuses 509Circuit Breakers 510

Enhanced Discrimination & SelectivityCircuit Breakers 516

Fuse Link Temperature De-rating 522

Protection of Cables with Fuse Links 523

GE Contactors for Lighting Circuits 524

Relay Equivalent Selection Chart 526

15 - TECHNICAL INFORMATION

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

488 Product Catalogue 2013

GeneralIn a circuit that provides power to a motor a number of protective & Control devices are normally present. The combination of these devices must be coordinated to ensure the efficiency & optimal protection of the motor. Here, the protection of such circuits strongly depends on the operational requirements, as the application for which the motor is used, the required starting frequency, required service level & applicable safety standards.

Required tripping time at Trip Class 1.2 x In 1.5 x In 7.2 x In 10A t < 2 hours t < 2 min. 2 <= t <= 10sec. 10 t < 2 hours t < 4 min. 4 <= t <= 10sec. 20 t < 2 hours t < 8 min. 6 <= t <= 10sec. 30 t < 2 hours t < 12 min. 8 <= t <= 10sec.

Category Load type Ir setting (min) AC1 Non Inductive motor Energization AC2 Slip ring motor Starting Switching off while running Regenerative breaking Inching AC3 Squirrel-cage motor Energization Switching off while running AC4 Squirrel-cage motor Starting (Cos phi = 0.45 <= 100A) Switching off while running (Cos phi = 0.35 > 100A) Regenerative breaking Pluging Inching

Motor current Test with ie (AC3) current “r” Ie <= 16A 1kA 16 < Ie <= 63A 3 kA 63 < Ie <= 125A 5 kA 125 < Ie <= 315A 10 kA 315 < Ie <= 630A 18 kA After this test the original characteristics of the contactor and thermal relay MUST remain unchanged. After this test the short-circuit protection must trip within 10 ms at a fault current >= 15 x In

Co ordinationThe standards require tests to define the co ordination between the protective & switching devices within the motor circuit.Depending on the state of the components after the test two coordination.Classes, 1 & 2 have been defined.The unique properties of the Record Plus breakers allow GE to offer solutions to meet the highest standard. Type 2 co ordination.

COORDINATION TYPE 2 TEST SEQUENCE

Type 2 - Short-circuit test with current “Iq” <= 50kA This value which is generally 15kA is used to check the coordination of the device used in the motor starter circuit. For each combination with Record Plus™ breakers this value is mentioned in the following tables. After test with this current the following conditions must be met. No or minor welding of the contactors after testing; contact separation is simple and easy. The switchgear and controlgear are fully operational after test.

MOTOR PROTECTION

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

Product Catalogue 2013 489

TEC

HN

ICA

L

15

Motor Rating Full Load Current (A) kW HP At 415V At 440V At 1000V 0.09 1/8 0.4 0.38 - 0.12 1/6 0.5 0.47 - 0.18 1/4 0.6 0.56 - 0.25 1/3 0.8 0.75 - 0.37 0.5 1.1 1 0.46 0.55 0.75 1.5 1.4 0.63 0.75 1 1.8 1.7 0.76 1.1 1.5 2.6 2.4 1.1 1.5 2 3.4 3.2 1.5 2.2 3 4.8 4.5 2 3.7 5 7.6 7.2 2.7 5.5 7.5 11 10.3 4.6 7.5 10 14 13.2 5.9 11 15 21 19.8 8.8 15 20 28 26.4 11.8 18.5 25 34 32 14.3 22 30 40 38 17 30 40 55 52 23 37 50 66 62 28 45 60 80 75 33 55 75 100 94 42 75 100 135 127 57 90 125 160 150 67 110 150 200 188 84 132 175 230 216 97 150 200 260 245 108 160 220 280 264 116 185 250 320 301 134 200 270 350 329 147 220 300 380 357 160 250 350 430 404 181 300 400 510 479 214

Notes:1. Full load current values are nominal for standard squirrel-cage induction motors of rated speed 1500 rpm (4 pole). Possible deviation of FLC values ±10% depending on type and manufacturer.

MOTOR RATED OUTPUTS AND FULL LOAD CURRENTS

MOTOR PROTECTION

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

490 Product Catalogue 2013

† Type NIT for 415V or less.* Type TF, if motor FLC does not exceed 200A and voltage is 500V or less.

Notes:1. Assumed starting conditions: Motor Rating Run-Up Up to 1kW 5 x FLC for 5 secs. 1.1 to 7.5kW 6 x FLC for 10 secs. 7.6 x 75kW 7 x FLC for 10 secs. Greater than 75kW 6 x FLC for 15 secs.Operating cycle of 2 starts in rapid succession and up to 8 starts per hour.

2. Suitable adjustments to the recommended rating may be necessary for: (a) Starting conditions in excess of the assumed starting conditions. (b) High enclosure (fluid environment) temperatures, refer to fuse de-rating information indicated on page 522.

Motor FLC (A) Recommended GEC, GE or IPD Fuse-Link Rating (A) From To Type T ‘gG’ Type T ‘gM’ DIN Type ‘gL’ - ‘gG’ 0 0.7 2 - 4 0.8 1.4 4 - 4 1.5 2 6 - 6 2.1 3 10 - 10 3.1 6.1 16 - 16 6.2 9 20 - 20 9.1 11 25 20M25† 25 11.1 14.4 32 20M32† 32 14.5 15.4 35 32M35 35 15.5 18 40 32M40 40 18.1 22 50 32M50 50 22.1 28 63 32M63 63 28.1 45 80 63M80 80 45.1 58 100 63M100 100 58 80 125 100M125 125 80.1 99 160 100M160 160 99.1 128 200 - 200 128.1 180 250 200M250 250 180.1 216 315 200M315* 315 216.1 270 355 315M355 355 270.1 328 400 - 400 328.1 385 450 400M450 500 385.1 430 500 - 500 430.1 500 560 - 630 500.1 560 630 - 630 560.1 620 670 630M670 800 620.1 645 710 - 800 645.1 680 750 - 1000

FUSE SELECTION FOR DIRECT-ON-LINE MOTOR STARTING

MOTOR PROTECTION

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

Product Catalogue 2013 491

TEC

HN

ICA

L

15

GE CIRCUIT BREAKER GUIDE FOR DIRECT-ON-LINE MOTOR STARTING 415V APPLICATIONS

Notes:1. FLC values are nominal for standard squirrel-cage induction motors of rated speed 1500 rpm (4 poles). Possible deviation of FLC values ± 10% depending on type and manufacturer.

2. Circuit breaker ratings are based on carrying 100% FLC continuous and 600% FLC for 10 seconds. Operating cycle 2 starts in rapid succession and up to 8 starts per hour.

3. Suitable adjustments to the indicated ratings may be necessary for: a) Starting conditions in excess of the above conditions. b) High enclosure (fluid environment) temperatures.

Motor Rating Circuit Breaker Types and Ratings (A) MCB MCCB Type kW FLC Series G FD FD FE FE FG FG FK FK FK (A) (Curve C) 63 160 160 250 400 630 800 1250 1600 0.37 1.1 2 0.55 1.5 4 0.75 1.8 6 1.1 2.6 10 1.5 3.4 10 2.2 4.8 16 3.7 7.6 20 16 5.5 11 25 20 20 7.5 14 32 32 32 11 21 50 40 40 15 28 50 50 18.5 34 63 64 63 22 40 80 80 30 55 100 100 100 100 37 66 125 125 125 125 45 80 160 160 160 160 55 100 200 200 75 135 250 250 250 90 160 300 300 110 200 400 400 400 400 132 230 450 450 450 150 250 500 500 500 160 270 550 550 550 185 320 630 630 630 640 200 350 700 700 700 220 380 800 800 800 250 430 900 900 300 510 1050 1050 315 550 1200 1200 335 590 1250 1250 375 660 1400 400 700 1500

MOTOR PROTECTION

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

492 Product Catalogue 2013

MOTOR PROTECTION

Notes:1. Assumed starting conditions: Motor Rating Run-Up Up to 1kW 2.5 x FLC for 20 secs. 1.1 to 7.5kW 3.5 x FLC for 20 secs. Greater than 75kW 3.5 x FLC for 15 secs.Operating cycle of 2 starts in rapid succession and up to 8 starts per hour.

2. Suitable adjustments to the recommended ratings may be necessary for: (a) Starting conditions in excess of the assumed starting conditions. (b) High enclosure (fluid environment) temperatures more than 35°C. Some fuses need to be derated as indicated on page 522.

FUSE SELECTION FOR ASSISTED MOTOR STARTING(Star-Delta, Autotransformer, Resistor or Reactor) Motor FLC (A) Recommended GEC, GE or IPD Fuse-Link Rating (A) From To Type T ‘gG’ Type T ‘gM’ DIN Type ‘gL’ - ‘gG’ 0 1.4 2 - 4 1.5 2.1 4 - 4 2.2 3.1 6 - 6 3.2 5.5 10 - 10 5.6 10 16 - 16 10.1 14 20 - 20 14.1 18 25 20M25 25 18.1 22 32 - 32 22.1 28 35 32M35 35 28.1 32 40 32M40 40 32.1 40 50 - 50 40.1 51 63 - 63 51.1 80 80 - 80 80.1 100 100 - 100 100.1 125 125 - 125 125.1 160 160 - 160 160.1 200 200 - 200 200.1 250 250 - 250 250.1 315 315 - 315 315.1 355 355 - 355 355.1 400 400 - 400 400.1 450 450 - 500 450.1 500 500 - 500 500.1 560 560 - 630 560.1 630 630 - 630 630.1 670 670 - 800 670.1 710 710 - 800 710.1 750 750 - 800

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

Product Catalogue 2013 493

TEC

HN

ICA

L

15

MOTOR PROTECTION

GE CIRCUIT BREAKER GUIDE FOR ASSISTED MOTOR STARTING (STAR-DELTA, 415V APPLICATIONS)

Notes:1. FLC values are nominal for standard squirrel-cage induction motors of rated speed 1500 rpm (4 poles). Possible deviation of FLC values ± 10% depending on type and manufacturer.

2. Circuit breaker ratings are based on carrying 100% FLC continuous and 600% FLC for 10 seconds. Operating cycle 2 starts in rapid succession and up to 8 starts per hour.

3. Suitable adjustments to the indicated ratings may be necessary for: a) Starting conditions in excess of the above conditions. b) High enclosure (fluid environment) temperatures.

Motor Rating Circuit Breaker Types and Ratings (A) MCB MCCB Type kW FLC Series G FD FD FE FE FG FG FK FK (A) (Curve C) 63 160 160 250 400 630 800 1250 0.37 1.1 2 0.55 1.5 4 0.75 1.8 4 1.1 2.6 6 1.5 3.4 6 2.2 4.8 10 3.7 7.6 16 5.5 11 20 16 7.5 14 25 20 20 11 21 40 32 32 15 28 50 40 40 18.5 34 50 50 22 40 63 64 63 30 55 80 80 37 66 90 90 45 80 100 100 100 100 55 100 125 125 125 125 75 135 160 160 160 160 90 160 200 200 110 200 250 250 250 132 230 280 280 150 250 300 300 160 270 320 320 320 185 320 380 380 380 200 350 400 400 400 400 220 380 450 450 450 250 430 550 550 550 300 510 630 650 650 315 550 700 700 335 590 750 750 375 660 800 850 400 700 950

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

494 Product Catalogue 2013

MOTOR PROTECTION

GE CONTACTOR GUIDE FOR STAR-DELTA MOTOR STARTING 415V APPLICATIONS

Notes:1. FLC values are nominal for standard squirrel-cage indication motors of rated speed 1500 rpm (4 poles).Possible deviation of FLC values ± 10% depending on type and manufacture.

2. Contactor types based on the following conditions: a) Starting duration not more than 20 seconds. b) Starting frequency of 2 starts in rapid succession and up to 8 starts per hour.

3. TOL relays selected for direct connection to the line contactor, in the delta branch of the motor starter circuit.

4. Suitable adjustments to the indicated types may be necessary for: a) Starting conditions in excess of the above conditions. b) High enclosure (fluid environment) temperatures.

Motor Rating Contactor Types kW FLC (A) Line and Delta Star TOL Relay Types 0.37 1.1 MCO MCO MT03D 0.55 1.5 MCO MCO MT03E 0.75 1.8 MCO MCO MT03F 1.1 2.6 MCO MCO MT03G 1.5 3.4 MCO MCO MT03H 2.2 4.8 MCO MCO MT03J 3.7 7.6 MCO MCO MT03K 5.5 11 MC1 MCO MT03M 5.5 11 CL00 CL00 RT1L 7.5 14 MC1 MCO MT03N 7.5 14 CL00 CL00 RT1M 11 21 CL02 CL00 RT1P 15 28 CL02 CL01 RT1S 18.5 34 CL25 CL01 RT1T 18.5 34 CL03 CL01 RT1T 22 40 CL25 CL02 RT1U 22 40 CL03 CL02 RT1U 30 55 CL04 CL25 RT1V 30 55 CL04 CL03 RT1V 37 66 CL45 CL25 RT1W 37 66 CL45 CL03 RT1W 45 80 CL06 CL04 RT2G 55 100 CL07 CL45 RT2H 75 135 CL08 CL06 RT2J 90 160 CL09 CL07 RT2L 110 200 CK75C CL08 RT3D 132 230 CK75C CL08 RT3E 150 250 CK75C CL09 RT3F 160 270 CK08C CL09 RT3F 185 320 CK08C CK75C RT3F 200 350 CK85B CK75C RT4P 220 380 CK09B CK75C RT4P 250 430 CK09B CK75C RT4P 300 510 CK95B CK08C RT4R 315 550 CK10C CK08C RT5C 335 590 CK10C CK85B RT5C 375 660 CK10C CK09B RT5D 400 700 CK10C CK09B RT5D

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

Product Catalogue 2013 495

TEC

HN

ICA

L

15

GE CONTACTOR GUIDE FOR AUTOTRANSFORMER MOTOR STARTING 415V APPLICATIONS

Notes:1. FLC values are nominal for standard squirrel-cage indication motors of rated speed 1500 rpm (4 poles). Possible deviation of FLC values ± 10% depending on type and manufacture.

2. Contactor types based on the following conditions: a) Starting duration not more than 20 seconds. b) Starting frequency of 2 starts in rapid succession and up to 8 starts per hour. c) Auto-transformer tap at 80%.

3. Suitable adjustments to the indicated types may be necessary for: a) Starting conditions different to the above conditions. b) High enclosure (fluid environment) temperatures.

Motor Rating Contactor Types kW FLC (A) Line Transformer Star TOL Relay Types 0.37 1.1 MCO MCO MCO MT03F 0.55 1.5 MCO MCO MCO MT03G 0.75 1.8 MCO MCO MCO MT03H 1.1 2.6 MCO MCO MCO MT03J 1.5 3.4 MCO MCO MCO MT03K 2.2 4.8 MCO MCO MCO MT03L 3.7 7.6 MC1 MCO MC0 MT03M 3.7 7.6 CL00 CL00 CL00 RT1N 5.5 11 MC2 MC1 MC0 MT03P 5.5 11 CL01 CL00 CL00 RT1N 7.5 14 CL02 CL00 CL00 RT1P 11 21 CL25 CL01 CL01 RT1T 15 28 CL04 CL02 CL02 RT1V 18.5 34 CL45 CL25 CL02 RT1W 22 40 CL45 CL04 CL25 RT1W 30 55 CL07 CL45 CL25 RT2G 30 55 CL07 CL45 CL03 RT2G 37 66 CL08 CL06 CL04 RT2J 45 80 CL08 CL07 CL45 RT2J 55 100 CL10 CL07 CL06 RT2M 75 135 CK75C CL09 CL07 RT3E 90 160 CK08C CL10 CL08 RT3F 110 200 CK85B CK75C CL09 RT4P 132 230 CK09B CK75C CL10 RT4P 150 250 CK09B CK08C CK75C RT4P 160 270 CK95B CK08C CK75C RT4P 185 320 CK10C CK85B CK75C RT5C 200 350 CK10C CK09B CK08C RT5C 220 380 CK10C CK09B CK08C RT5C 250 430 CK11C CK95B CK85B RT5D 300 510 CK11C CK10C CK09B RT5E 315 550 CK11C CK10C CK09B RT5E 335 590 CK12B CK10C CK95B RT5E 375 660 CK12B CK11C CK95B RT5E 400 700 CK12B CK11C CK10C RT5E

MOTOR PROTECTION

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

496 Product Catalogue 2013

MOTOR PROTECTION

Notes:1. FLC values are nominal for standard squirrel-cage induction motors of rated speed 1500 rpm (4 pole). Possible deviation of FLC values ±10% depending on type and manufacturer.

2. Recommend fuse ratings are based on carrying 125% FLC continuously and operating in not less than 20 seconds at 600% FLC, in accordance with Clause 7.2.9.2 of AS/NZS 3000:2007.

3. Suitable adjustments to the recommended ratings may be necessary for high enclosure (fluid environment) temperatures, refer to de-rating information indicated on page 522.

FUSE SELECTION FOR FIRE PUMP MOTOR STARTING Motor FLC (A) Recommended GEC, GE or IPD Fuse-Link Rating (A) kW FLC (A) Type T ‘gG’ Type T ‘gM’ DINType ‘gL’ - ‘gG’ 0.37 1.1 4 - 4 0.55 1.5 6 - 4 0.75 1.8 6 - 6 1.1 2.6 10 - 6 1.5 3.4 16 - 10 2.2 4.8 16 - 16 3.7 7.6 20 - 20 5.5 11 32 20M32 25 7.5 14 35 20M35 32 11 21 50 32M50 40 15 28 63 32M63 50 18.5 34 80 63M80 63 22 40 80 63M80 80 30 55 100 63M100 100 37 66 125 100M125 125 45 80 160 100M160 160 55 100 160 - 160 75 135 250 200M250 200 90 160 250 200M250 250 110 200 315 - 315 132 230 355 315M355 315 150 250 355 315M355 355 160 270 400 - 400 185 320 450 400M450 500 200 350 450 400M450 500 220 380 500 - 630 250 430 560 - 630 300 510 630 - 800

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

Product Catalogue 2013 497

TEC

HN

ICA

L

15

MOTOR PROTECTION

GE CIRCUIT BREAKER GUIDE FOR FIRE PUMP MOTOR STARTING 415V APPLICATIONS

Notes:1. FLC values are nominal for standard squirrel-cage induction motors of rated speed 1500 rpm (4 poles). Possible deviation of FLC values ± 10% depending on type and manufacturer.

2. Circuit breaker ratings are based on carrying 125% FLC continuously and opening in not less than 20 seconds at 600% FLC, in accordance with clause 7.2.9.2 of AS/NZS 3000:2007.

3. Suitable adjustments to the indicated ratings may be necessary for high enclosure (fluid environment) temperatures.

Motor Rating Circuit Breaker Types and Ratings (A) MCB MCCB Type kW FLC Series G FD FD FE FE FG FG FK FK FK (A) (Curve C) 63 160 160 250 400 630 800 1250 1600 0.37 1.1 4 0.55 1.5 6 0.75 1.8 6 1.1 2.6 10 1.5 3.4 16 2.2 4.8 16 16 3.7 7.6 25 20 20 5.5 11 40 32 32 7.5 14 50 40 40 11 21 63 50 50 15 28 64 63 18.5 34 80 80 22 40 100 100 100 100 30 55 125 125 125 125 37 66 140 140 140 140 45 80 180 180 55 100 220 220 220 75 135 300 300 320 90 160 400 400 400 400 110 200 450 450 450 132 230 500 500 500 150 250 550 550 550 160 270 580 580 580 185 320 700 700 700 200 350 750 750 750 220 380 800 800 800 250 430 1000 1000 300 510 1250 1250 315 550 1300 335 590 1400 375 660 1500 400 700 1600

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

498 Product Catalogue 2013

MOTOR PROTECTION

Upstream Record Plus Breakers selection Type N H L IIcc values in kA Ue= 400/415V AC FD63/160 50kA 80kA 130kA FE160/250 50kA 80kA 130kA FG 400/630 50kA 80kA 130kA FK 800/1250 50kA 80kA 100kA

TYPE 2 COORDINATIONCLASS 10 PROTECTION @ 415V AC

For type 2 Coordination @ other voltage, please refer to product catalogues of your local representative.

Motor Breaker details Contactor P(kW) In Type Ie Im Type + O.R. 0.75 2 FD63 /FE160 3 (2) 35 CL25+RT1J 1.1 2.6 FD63 /FE160 3 (2) 35 CL25+RT1K 1.5 3.6 FD63 /FE160 7 70 CL03+RT1K 2.2 5 FD63 /FE160 7 80 CL03+RT12L 3 7 FD63 /FE160 7 86 CL03+RT1M 4 8.3 FD63/FE160 12.5 125 CL06+RT2AN 5.5 11.5 FD63/FE160 12.5 150 CL06+RT2AN 7.5 16.1 FD63/FE160 20 200 CL06+RT2B 10 21 FD63 /FE160 30 300 CL06-RT2C 11 22 FD63 /FE160 30 300 CL06-RT2C 15 30 FD63 /FE160 30 390 CL06-RT2D 18.5 37 FD63/FE160 50 478 CL06+RT2E 22 43 FD63/FE160 50 561 CL06+RT2G 25 49 FD63/FE160 50 635 CL06+RT2G 30 58 FD/FE160 80 800 CL09+RT2H 37 72 FD/FE160 80 934 CL09+RT2J 45 86 FD/FE160 100 1121 CK75C+RT2L 55 104 FE160 125 1346 CK85B+RT3E 75 144 FE160 160 1869 CK85B+RT3F 90 179 FE250 250 2500 CK95B+RT4N 110 207 FE250 250 2691 CK10B+RT4P 132 247 FE250 250 3214 CK10B+RT4R 160 300 FG400 350 3900 CK10B+RT5C 200 360 FG630 500 4680 CK12B+RT5C 220 400 FG630 500 5200 CK12B+RT5D 250 462 FG630 500 6004 CK12B+RT5D 300 560 FK800 800 6720 CK13B+RT5E 315 582 FK800 800 6985 CK13B+RT5C 335 619 FK800 800 6810 CK13B+RT5C

SELECTION OF ASSOCIATED COMPONENTS (1)

Notes:(1) The contactor has a breaking capacity that is sufficient to operate the specified motor up to the specified magnetic setting of the breaker.(2) The 3 AMP device is designed to operate AA current level up to 3.5 Amps.

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

Product Catalogue 2013 499

TEC

HN

ICA

L

15

MOTOR PROTECTION

Upstream Record Plus Breakers selection Type N H L IIcc values in kA Ue= 400/415V AC FE160/250 50kA 80kA 130kA FG400/630 50kA 80kA 130kA

SELECTION OF ASSOCIATED COMPONENTS (1)

Notes:(1) The contactor has a breaking capacity that is sufficient to operate the specified motor up to the specified magnetic setting of the breaker.(2) The 3 AMP device is designed to operate AA current level up to 3.5 Amps.

TYPE 2 COORDINATIONCLASS 10 AND PROTECTION

(WITH SMR2 OTHER CLASSES POSSIBLE)

Motor Breaker details Contactor P(kW) In Type Ie Im Type + O.R. 5.5 11.5 FE160 25 150 CL08 7.5 16.1 FE160 25 200 CL08 10 21 FE160 25 300 CL08 11 22 FE160 25 300 CL08 15 30 FE160 63 390 CL09 18.5 37 FE160 63 478 CL09 22 43 FE160 63 561 CL09 25 49 FE160 63 635 CL09 30 58 FE160 63 800 CL09 37 72 FE160 125 934 CK85B 45 86 FE160 125 1121 CK85B 55 104 FE160 125 1346 CK85B 75 144 FE160 160 1869 CK85B 90 179 FE250 250 2500 CK95B 110 207 FE250 250 2691 CK95B 132 247 FE250 250 2967 CK95B 160 300 FG400 350 3900 CK10C 200 360 FG630 500 4680 CK12B 220 400 FG630 500 5200 CK12B 250 462 FG630 500 6004 CK12B

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

500 Product Catalogue 2013

MOTOR PROTECTION

SELECTION OF ASSOCIATED COMPONENTS (1)

Notes:(1) The contactor has a breaking capacity that is sufficient to operate the specified motor up to the specified magnetic setting of the breaker.(2) The 3 AMP device is designed to operate AA current level up to 3.5 Amps.

TYPE 2 COORDINATIONCLASS 20(3) PROTECTION

Upstream Record Plus Breakers selection Type N H L IIcc values in kA Ue= 400/415V AC FD63/160 50kA 80kA 130kA FE160/250 50kA 80kA 130kA FG 400/630 50kA 80kA 130kA FK 800/1250 50kA 80kA 100kA

Motor Breaker details Contactor P(kW) In Type Ie Im Type + O.R. 0.75 2 FD63/FE160 3 (2) 35 CL25+RT12J 1.1 2.6 FD63/FE160 3 (2) 35 CL25+RT12K 1.5 3.6 FD63/FE160 7 70 CL03+RT12K 2.2 5 FD63/FE160 7 80 CL03+RT12L 3 6.6 FD63/FE160 7 86 CL03+RT12M 4 8.3 FD63/FE160 12.5 125 CL06+RT2AN 5.5 11.5 FD63/FE160 12.5 150 CL06+RT2AN 7.5 16.1 FD63/FE160 20 200 CL06+RT2B 10 21 FD63/FE160 30 300 CL06-RT2C 11 22 FD63/FE160 30 300 CL06-RT2C 15 30 FD63/FE160 30 390 CL06-RT22D 18.5 37 FD63/FE160 50 478 CL06+RT22E 22 43 FD63/FE160 50 561 CL06+RT22G 25 49 FD63/FE160 50 635 CL06+RT22G 30 58 FD/FE160 80 800 CL09+RT22H 37 72 FD/FE160 80 934 CL09+RT22J 45 86 FD/FE160 100 1121 CK75C+RT22L 55 104 FE160 125 1346 CK85B+RT32E 75 144 FE160 160 1869 CK85B+RT32F 90 179 FE250 250 2500 CK95B+RT32F 110 207 FE250 250 2691 CK10B+RT5LB 132 247 FE250 250 3214 CK10B+RT5LB 160 300 FG400 350 3900 CK10B+RT5LB 200 360 FG630 500 4680 CK12B+RT52LC 220 400 FG630 500 5200 CK12B+RT52LD 250 462 FG630 500 6004 CK12B+RT52LD 300 560 FK800 800 6720 CK13B+RT5LE 315 582 FK800 800 6985 CK13B+RT5LE 335 619 FK800 800 6810 CK13B+RT5LE

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

Product Catalogue 2013 501

TEC

HN

ICA

L

15

MOTOR PROTECTION

TYPE 2 COORDINATIONSTART DELTA STARTERS

Upstream Record Plus Breakers selection Type N H L IIcc values in kA Ue= 400/415V AC FD63/160 50kA 80kA 130kA FE160/250 50kA 80kA 130kA FG400/630 50kA 80kA 130kA FK800/1250 50kA 80kA 130kA

Motor Breaker details Contactor Delta Star P(kW) In Type Ie Im Type + O.R. Cont. Cont. 2.2 5.0 FD63/FE160 7 80 CL03+RT12L CL03 CL03 3 6.6 FD63/FE160 7 86 CL03+RT1M CL03 CL03 4 8.3 FD63/FE160 12.5 125 CL06+RT2AN CL04 CL04 5.5 11.5 FD63/FE160 12.5 150 CL06+RT2AN CL04 CL04 7.5 16.1 FD63/FE160 20 200 CL06+RT2B CL45 CL45 10 21 FD63/FE160 30 300 CL06-RT2C CL45 CL45 11 22 FD63/FE160 30 300 CL06-RT2C CL45 CL45 15 30 FD63/FE160 30 390 CL06-RT2D CL45 CL45 18.5 37 FD63/FE160 50 478 CL06+RT2E CL06 CL06 22 43 FD63/FE160 50 561 CL06+RT2G CL06 CL06 25 49 FD63/FE160 50 635 CL06+RT2G CL06 CL06 30 58 FD/FE160 80 800 CL09+RT2H CL09 CL09 37 72 FD/FE160 80 934 CL09+RT2J CL09 CL09 45 86 FD160 100 1121 CL09+RT2L CL09 CL09 45 86 FE160 100 1121 CK75C+RT2L CL10 CL10 55 104 FE160 125 1346 CK85B+RT3E CK75C CL10 75 144 FE160 160 1869 CK85B+RT3F CK08C CL10 90 179 FE250 250 2500 CK95B+RT4N CK85B CK75C 110 207 FE250 250 2691 CK10B+RT4P CK95B CK75C 132 247 FE250 250 3214 CK10B+RT4R CK95B CK75C 160 300 FG400 350 3900 CK10B+RT5C CK95B CK85B 200 360 FG630 500 4680 CK12B+RT5C CK10C CK10C 220 400 FG630 500 5200 CK12B+RT5D CK10C CK10C 250 462 FG630 500 6004 CK12B+RT5D CK10C CK10C 300 560 FK800 800 6720 CK13B+RT5E CK12C CK12C 315 582 FK800 800 6985 CK13B+RT5C CK12C CK12C 335 619 FK800 800 6810 CK13B+RT5C CK12C CK12C

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

502 Product Catalogue 2013

TRANSFORMER RATINGS

mVA Current (I) Current (I) Typical Z1 @ 433V PSC @ 433V kVA kVA/1000 @ 11kV @ 433V % Z in Ohms in kA 15 0.015 0.79 20 4.75 0.5937 0.421 25 0.025 1.31 33.33 4.5 0.3375 0.741 50 0.050 2.62 66.67 4.5 0.1687 1.482 100 0.100 5.25 133.34 4.75 0.0891 2.807 150 0.150 7.87 200.01 4.75 0.0594 4.211 200 0.200 10.5 266.67 4.75 0.0445 5.614 300 0.300 15.75 400.01 4.75 0.0297 8.421 315 0.315 16.53 420.01 5 0.0298 8.400 400 0.400 20.99 533.35 4.75 0.0223 11.228 500 0.500 26.24 666.69 4.75 0.0178 14.035 600 0.600 26.24 666.69 4.75 0.0148 16.843 750 0.750 39.36 1000.03 4.75 0.0119 21.053 750 0.750 39.36 1000.03 6.25 0.0156 16.000 800 0.800 41.99 1066.70 4.75 0.0111 22.457 1000 1.000 52.49 1333.37 4.75 0.0089 28.071 1200 1.200 62.98 1600.05 5 0.0078 32.001 1350 1.350 70.86 1800.05 5.25 0.0073 34.287 1500 1.500 78.73 2000.06 5.5 0.0069 36.365 2000 2.000 104.97 2666.74 5.5 0.0052 48.486 2500 2.500 131.22 3333.43 6 0.0045 55.557

Example: Fault level for 400kA Sub:

Ohms = KV Line Voltage2 x %Z = (433)2���������� ������� �� MVA 0.4x106 100

KA = KV Line Voltage = 433 = 11.228 KA��������������������� � ����������� �

Note: The attached calculations are based on zero source impendance and are intended as a guide only.

GUIDE TO LOW VOLTAGE FAULT LEVEL

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

Product Catalogue 2013 503

TEC

HN

ICA

L

15

TRANSFORMER PROTECTION

Notes:1. FLC values are typical only. Possible deviation of FLC values ±5% depending on manufacturer.2. Recommended fuse ratings allow for transformer magnetising inrush current of 12 times FLC for 0.1 seconds.3. Suitable adjustments to the recommended ratings may be necessary for high enclosure (fluid environment) temperatures, refer to de-rating information indicated on page 522.

FUSE SELECTION FOR 3-PHASE TRANSFORMER PRIMARIES AT 415VAC Transformer Recommended GEC, Rating English Electric GE or IPD Fuse-Link Rating (A) kVA Primary FLC (A) Type T ‘gG’ DIN Type ‘gL’-’gG’ 0.5 0.8 4 4 1 1.5 6 4 2 3.1 10 6 3 4.6 16 10 4 6.1 16 10 5 7.7 16 16 6 9.2 20 16 7 10.7 20 16 8 12.2 20 16 10 15 25 20 12 18 32 25 15 23 35 32 20 31 40 40 25 38 50 50 30 46 63 63 40 61 80 80 50 77 80 80 75 115 125 125 100 153 160 160 125 191 200 200 150 230 250 250 200 306 315 315 250 383 400 400 300 459 500 500 400 612 630 630 500 765 800 800 630 964 1250 1000 750 1148 1250 -

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

504 Product Catalogue 2013

TRANSFORMERS & CAPACITOR PROTECTION

Maximum crest inrush values Transformer 1st Period 2nd Period 3rd Period value 5 ms. 25 ms. 45 ms. < 50 kvA 25 x In 12 x In 5 x In >= 50 kvA 15 x In 8 x In 3.5 x In

Transformer ratings Record Plus breaker 1ph 240V 3ph 400/415V Type Trip unit Ist kVA In kVA In type & rating* 2.5 10 6.3 9 FD160N, FD160H or L LTMD-25 250 4 11 8 12 FD160N, FD160H or L LTMD-25 250 5 17 10 14 FD160N, FD160H or L LTMD-32 320 12.5 18 FD160N, FD160H or L LTMD-32 320 6.3 27 16 23 FD160N, FD160H or L LTMD-40 400 8 34 20 28 FD160N, FD160H or L LTMD-50 500 10 42 25 35 FD160N, FD160H or L LTMD-63 630 12.5 53 31.5 44 FD160N, FD160H or L LTMD-80 800 40 56 FD160N, FD160H or L LTMD-100 1000 16 68 50 70 FD160N, FD160H or L LTMD-125 1250 20 84 FD160N, FD160H or L LTMD-125 1250 63 89 FE160N, H or L SMR1-125 25 105 80 113 FE160N, H or L SMR1-125 31.5 133 100 141 FE160N, H or L SMR1-160 40 169 125 176 FE250N, H or L SMR1-250 50 211 160 225 FE250N, H or L SMR1-250 63 266 200 287 FG400N, H or L SMR1-350 80 338 250 352 FG400N, H or L SMR1-350 100 422 315 444 FG630N, H or L SMR1-500 125 528 400 563 FG630N, H or L SMR1-630 160 675 500 704 FK800N or H SMR1-800 630 887 FK1250N or H SMR1-1000 800 1126 FK1250N or H SMR1-1250 1000 1408 FK1600N or H SMR1-1600

Un = 400/415V (phase to phase voltage) Capacitor rating Record Plus Ir setting (kVAr) breaker (min) 10 FD160N, FD160H or L 21 A 15 FD160N, FD160H or L 31 A 20 FD160N, FD160H or L 41 A 25 FD160N, FD160H or L 52 A 30 FD160N, FD160H or L 62 A 35 FD160N, FD160H or L 72 A 40 FD160N, FD160H or L 83 A 45 FD160N, FD160H or L 93 A 50 FD160N, FD160H or L 103 A 60 FD160N, FD160H or L 124 A 70 FD160N or FE160N, H or L 144 A 80 FE250N, H or L 165 A 90 FE250N, H or L 186 A 100 FE250N, H or L 206 A 120 FE250N, H or L 248 A 140 FG400N, H or L 289 A 160 FG400N, H or L 330 A 180 FG400N, H or L 372 A 200 FG630N, H or L 413 A 250 FG630N, H or L 516 A 300 FG630N, H or L 619 A 350 FK800N, H or H 722 A

PROTECTION OF CAPACITOR BANKS

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

Product Catalogue 2013 505

TEC

HN

ICA

L

15

CAPACITOR PROTECTION

Notes:1. Recommended fuse ratings allow for a capacitor manufacturing tolerance of +10% on the kVAr values and the possibility of up to 30% constant overload of a capacitor bank due to harmonic currents.

2. Suitable adjustments to the recommended ratings may be necessary for high enclosure (fluid environment) temperatures, refer to de-rating information indicated on page 522.

FUSE SELECTION FOR 3-PHASE CAPACITOR BANKS AT 415VAC Capacitor Bank Recommended GEC, Rating GE or IPD Fuse-Link Rating (A) kVAr FLC (A) Type T ‘gG’ DIN Type ‘gL’-’gG’ 5 6.9 16 16 7.5 10.4 16 16 10 13.9 25 25 15 20.9 32 32 20 27.8 50 50 25 34.8 63 63 30 41.7 63 63 35 48.7 80 80 40 55.6 100 100 50 69.6 125 125 60 83.5 125 125 75 104 160 160 90 125 200 200 100 139 250 250 110 153 250 250 120 167 250 250 135 188 315 315 150 209 315 315 160 223 355 355 180 250 400 400 190 264 400 400 200 278 450 500 225 313 500 500 240 334 500 500 275 383 630 630 300 417 630 630 360 501 750 800 400 557 1000 1000

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

506 Product Catalogue 2013

BACKUP PROTECTION

Record Plus™ circuit breakers excel in their characteristics as current and energy limiting devices. This allows one to use lighter and more economical downstream busbar systems and switchgear.A frequently used combination is that of a Record Plus™ breaker, used as a protection and switching device in the mains switchboard, and a Dilos load break switch, as an incomer, in a downstream, secondary switchboard. In this application the Dilos needs to be able to withstand the current and energy values on a short-circuit event, this taking the limiting effects of the upstream breaker into account.The table indicates the maximum prospective short-circuit that the combination of an upstream Record Plus™ and a downstream Dilos or Record Plus™ in its switch disconnect variant (type Y) can withstand.

MCCB AND SWITCH DISCONECTOR BACKUP PROTECTION

Protection of Switch Disconectors (Dilos or Record PlusTM) - Valid for 400/415V AC Upstream Breaking Downstream Maximum Downstream Maximum capacity, allowable allowable Record Plus™ Icu = Ics Dilos switch short-circuit Record Plus™ short-circuit circuit breaker (kA eff.) (kA eff.) switch (kA eff.) FD160S 30 1 & 1H 18 FD63Y 30 FD160S 30 2 18 FD160Y 30 FD160N 50 1 & 1H 25 FD63Y 50 FD160N 50 2 25 FD160Y 50 FD160H 80 1 & 1H 30 FD63Y 80 FD160N 80 2 30 FD160Y 80 FD160L 150 1 & 1H 36 FD63Y 150 FD160L 150 2 36 FD160Y 150 FE160N 50 1 & 1H 25 FE63Y 50 FE160N 50 2 25 FE160Y 50 FE160H 80 1 & 1H 30 FE63Y 80 FE160H 80 2 30 FE160Y 80 FE160L 150 1 & 1H 36 FE63Y 150 FE160L 150 2 36 FE160Y 150 FE250N 50 3 50 FE250Y 50 FE250H 80 3 80 FE250Y 80 FE250L 150 3 150 FE250Y 150 FG400N 50 4 50 FG400Y 50 FG400H 80 4 80 FG400Y 80 FG400L 150 4 150 FG400Y 150 FG630N 50 4 50 FG630Y 50 FG630H 80 4 80 FG630Y 80 FG630L 150 4 150 FG630Y 150 FK800N 50 6 50 FK800Y 50 FK800H 80 6 80 FK800Y 80 FK1250N 50 6 50 FK1250Y 50 FK1250H 80 6 80 FK1250Y 80 FK1600N 50 7 50 FK1600Y 50 FK1600H 80 7 80 FK1600Y 80

FAULT-CURRENT LIMITER FUSES SELECTION FOR MINIATURE CIRCUIT BREAKERS AT 415VAC 50kA PROSPECTIVE Miniature Minimum Maximum Fuse Rating (A) Circuit Fuse For For Breaker Rating GE Series Ge Series Rating (A) (A) G60 G100 4 20 200 250 6 25 200 250 10 40 200 250 16 50 200 250 20 63 200 250 25 80 200 250 32 100 200 250 40 125 200 250 50 160 200 250 63 160 200 250 Note: Fuses are type ‘T’, ‘gG’ or DIN type ‘gL’ - ‘gG’

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

Product Catalogue 2013 507

TEC

HN

ICA

L

15

Upstream Record PlusTM type FD63/160E FD63/160S FD63/160N FD63/160H FD63/160L FE160N FE160H FE160L FE250V FE250N FE250H FE250L FG400N Icu 25 36 50 80 150 50 80 150 36 50 80 150 50 in kA Downstream Icu of the combination in kA Redline G60 & GT10 10 22 25 30 36 42 30 36 42 22 30 36 36 16 G100 15 25 30 36 42 50 36 42 50 25 30 36 36 22 GT25 <=25A 25 -- 36 42 50 65 42 50 65 -- 36 42 42 -- GT25; 32 & 40A 20 -- 30 36 42 50 36 42 50 -- 36 42 42 -- GT25; 50 & 63A 15 25 30 36 42 50 36 42 50 25 30 36 36 -- Surion GPS1B/MS <=10A 100 -- -- -- -- 150 -- -- 150 -- -- -- 150 -- GPS1B/MS 12.5A 50 -- -- -- 80 150 -- 80 150 -- -- 80 150 -- GPS1B/MS >=16A 25 -- -- 42 50 65 42 50 65 -- 42 50 65 -- GPS1B/MH <=12.5A 100 -- -- -- -- 150 -- -- 150 -- -- -- 150 -- GPS1B/MH >12.5A 50 -- -- -- 80 150 -- 80 150 -- -- 80 150 -- GPS2B/MS 10A 100 -- -- -- -- 150 -- -- 150 -- -- -- 150 -- GPS2B/MS >10A 25 -- -- 42 50 65 42 50 65 -- 42 50 65 -- GPS2B/MH 10A 100 -- -- -- -- 150 -- -- 150 -- -- -- 150 -- GPS2B/MH >10A 50 -- -- -- 80 150 -- 80 150 -- -- 80 150 -- Record PlusTM FD63/160C 18 22 25 30 36 42 30 36 42 22 30 36 42 30 FD63/160E 25 -- 30 36 42 50 36 42 50 -- 36 42 50 36 FD63/160S 36 -- -- 42 50 65 42 50 65 -- 42 50 65 42 FD63/160N 50 -- -- -- 80 150 -- 80 150 -- -- 80 150 -- FD63/160H 80 -- -- -- -- 150 -- -- 150 -- -- -- 150 -- FE160N 50 -- -- -- -- -- -- 80 150 -- -- 80 150 -- FE160H 80 -- -- -- -- -- -- -- 150 -- -- -- 150 -- FE250N 50 -- -- -- -- -- -- -- -- -- -- 80 150 -- FE250H 80 -- -- -- -- -- -- -- -- -- -- -- 150 -- FG400N 50 -- -- -- -- -- -- -- -- -- -- -- -- -- FG400H 80 -- -- -- -- -- -- -- -- -- -- -- -- -- FG630N 50 -- -- -- -- -- -- -- -- -- -- -- -- -- FG630H 80 -- -- -- -- -- -- -- -- -- -- -- -- -- FK800N 50 -- -- -- -- -- -- -- -- -- -- -- -- -- FK800H 80 -- -- -- -- -- -- -- -- -- -- -- -- -- FK1250N 50 -- -- -- -- -- -- -- -- -- -- -- -- -- FK1250H 80 -- -- -- -- -- -- -- -- -- -- -- -- --

Upstream Record PlusTM type FG400H FG400L FG630N FG630H FG630L FK800N FK800H FK800L FK1250N FK1250H FK1250L FK1600N FK1600H Icu 80 150 50 80 150 50 80 100 50 80 100 50 80 in kA Downstream Icu of the combination in kA Redline G60 & GT10 10 16 16 12 12 12 -- -- -- -- -- -- -- -- G100 15 22 22 16 16 16 -- -- -- -- -- -- -- -- GT25 <=25A 25 -- -- -- -- -- -- -- -- -- -- -- -- -- GT25; 32 & 40A 20 -- -- -- -- -- -- -- -- -- -- -- -- -- GT25; 50 & 63A 15 -- -- -- -- -- -- -- -- -- -- -- -- -- Surion GPS1B/MS <=10A 100 -- -- -- -- -- -- -- -- -- -- -- -- -- GPS1B/MS 12.5A 50 -- -- -- -- -- -- -- -- -- -- -- -- -- GPS1B/MS >=16A 25 -- -- -- -- -- -- -- -- -- -- -- -- -- GPS1B/MH <=12.5A 100 -- -- -- -- -- -- -- -- -- -- -- -- -- GPS1B/MH >12.5A 50 -- -- -- -- -- -- -- -- -- -- -- -- -- GPS2B/MS 10A 100 -- -- -- -- -- -- -- -- -- -- -- -- -- GPS2B/MS >10A 25 -- -- -- -- -- -- -- -- -- -- -- -- -- GPS2B/MH 10A 100 -- -- -- -- -- -- -- -- -- -- -- -- -- GPS2B/MH >10A 50 -- -- -- -- -- -- -- -- -- -- -- -- -- Record PlusTM FD63/160C 18 36 42 30 36 42 -- -- -- -- -- -- -- -- FD63/160E 25 42 50 36 42 50 -- -- -- -- -- -- -- -- FD63/160S 36 50 65 42 50 65 -- -- -- -- -- -- -- -- FD63/160N 50 80 150 -- 80 150 -- 80 100 -- 80 100 -- 80 FD63/160H 80 -- 150 -- -- 150 -- -- 100 -- -- 100 -- -- FE160N 50 80 150 -- 80 150 -- 80 100 -- 80 100 -- 80 FE160H 80 -- 150 -- -- 150 -- -- 100 -- -- 100 -- -- FE250N 50 80 150 -- 80 150 -- 80 100 -- 80 100 -- 80 FE250H 80 -- 150 -- -- 150 -- -- 100 -- -- 100 -- -- FG400N 50 80 150 -- 80 150 -- 80 100 -- 80 100 -- 80 FG400H 80 -- 150 -- -- 150 -- -- 100 -- -- 100 -- -- FG630N 50 -- -- -- 80 150 -- 80 100 -- 80 100 -- 80 FG630H 80 -- -- -- -- 150 -- -- 100 -- -- 100 -- -- FK800N 50 -- -- -- -- -- -- 80 100 -- 80 100 -- 80 FK800H 80 -- -- -- -- -- -- -- 100 -- -- 100 -- -- FK1250N 50 -- -- -- -- -- -- 80 100 -- 80 100 -- 80 FK1250H 80 -- -- -- -- -- -- -- 100 -- -- 100 -- --

BACKUP PROTECTION

Record Plus Moulded Case Circuit Breakers (at 400/415V AC; table B2 ed. 2c)

TEC

HN

ICA

L

15

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

508 Product Catalogue 2013

NOTES

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

Product Catalogue 2013 509

TEC

HN

ICA

L

15

Down-Stream Minimum Up-Stream Fuse Rating (A) Fuse Rating (A) Type T ‘gG’ Type T ‘gM’ DIN Type ‘gL’-’gG’ Type T ‘gG’ DIN Type ‘gL’-’gG’ 2 - - 4 4 4 - 4 6 6 6 - 6 10 10 10 - 10 16 16 16 - 16 25 25 20 - 20 32 32 25 20M25 25 40 40 32 20M32 - 40 40 32 - 32 50 50 35 32M35 35 50 50 40 32M40 40 63 63 50 32M50 50 80 80 63 32M63 - 125 125 63 - 63 125 100 80 63M80 80 160 125 100 63M100 100 160 160 125 100M125 125 200 200 160 100M160 160 250 250 200 100M200 200 315 315 250 200M250 250 400 400 315 200M315 315 500 500 355 315M355 - 560 630 400 - - 630 800 400 - 400 630 630 450 400M450 - 670 800 500 - 500 750 800 560 - - 800 1000 630 - 630 1000 1000 670 630M670 - 1250 - 710 - - 1250 - 750 - - 1250 - 800 - 800 1250 -

Notes:1. Fuses must be GE or IPD brands of fuse-links only. Not applicable for other manufacturers’ fuses.

2. The selected fuse ratings achieve discrimination for overload conditions and short-circuit currents up to 80kA.

3. This discrimination ensures that the down-stream fuse operates and the up-stream fuse remains unaffected.

4. Where the up-stream fuse supplies more than one down-stream fuse, the minimum up-stream fuse rating should be increased to allow for load biasing effects.

DISCRIMINATION BETWEEN FUSES AT 415VAC

SupplySource

Up-StreamFuse

Down-StreamFuse

Fault Point

DISCRIMINATION & SELECTIVITY

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

510 Product Catalogue 2013

Selectivity Discrimination tables: Where discrimination is partial the selectivity limits in kA Is are listed. Where ‘T’ is found in the tables, this indicates total discrimination up to the highest breaking capacity of the devices.These discrimination/selectivity limits are only valid if the ratio between the current settimes, ranks or time settings of upstream & downstream breakers are equal or higher than the factor indicated below.

Terminology LTM Thermal Magnetic Trip Unit Ir = Overload setting Im = Magnetic setting LTMD Selective Thermal Magnetic Trip Unit Ir = Overload setting Im = Magnetic setting Mag. Break™ Magnetic Only Trip Unit Im = Magnetic setting SMR1 & SMR1e Selective Electronic Trip Unit Ir = Setting on LT device Ist = Setting on ST device SMR1s, g and SMR2 Enhanced Electronic trip Unit MPRO 17, 20, 30 & 40 Mpact Electronic Trip Unit Ir = Setting on LT device Ist = Setting on ST device

LTD class, time setting at 7.2 x Ir STD Delay setting on ST device A2S Cropped short time delay setting Inst. = Setting on I ( Instantaneous ) device

SELECTIVITY DISCRIMINATION TABLES

L

L

1.6

20

TM

TM

TM

TM

DISCRIMINATION & SELECTIVITY

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

Product Catalogue 2013 511

TEC

HN

ICA

L

15

SELECTIVE TABLES(RECORD PLUS MOULDED CASE CIRCUIT BREAKERS; TABLE D1 ED. 2C)

Upstream

Downstream

FDC & FDE 63/160 LTM FDS 63/160 LTMD FDN, H & L 63/160 LTMD

In in A In in A In in A

In 40 50 63 80 100 125/160 40 50 63 80 100 125/160 40 50 63 80 100 125/160

(A) Selectivity limit in kA*

16

20

25

32

40

50

63

16

20

25

32

40

50

63

16

20

25

32

40

50

63

80

100

20

25

32

40

50

63

20

25

32

40

50

63

25

32

40

50

63

80

Redline

Reco

rd P

lus

6kA 6kA2.5kA0.6kA T T T T T T T T T T T T TT0.6kA 2.5kA 3kA 6kA 8kA T 3.5kA T T T T T 3.5kA T T T T T

0.8kA- 1.2kA 6kA 6kA T 1.6kA 3.5kA T T T T 1.6kA 3.5kA T T T T

- - 1.2kA 3kA 6kA 8kA - - 10kA T T T - - 10kA T T T

- - - 3kA 4kA 6kA - - 3.5kA T T T - - 3.5kA T T T

- - - 1.2kA 1.5kA 6kA - - - 3.5kA T T - - - 3.5kA T T

- - - - 1.5kA 2kA - - - - 8kA T - - - - 8kA T

6kA2.5kA0.6kA 6kA 10kA T 10kA 10kA T T T T 10kA 10kA T T T T

2.5kA0.6kA 3kA 6kA 8kA T 3.5kA 10kA T T T T 3.5kA 10kA T T T T- 0.8kA 1.2kA 6kA 6kA T 1.6kA 3.5kA T T T T 1.6kA 3.5kA T T T T

- - 1.2kA 3kA 6kA 8kA - - 10kA 10kA T T - - 10kA 10kA T T

- - - 3kA 4kA 6kA - - 3.5kA 10kA T T - - 3.5kA 10kA T T

- - - 1.2kA 1.5kA 6kA - - - 3.5kA 10kA T - - - 3.5kA 10kA T

- - - - 1.5kA 2kA - - - - 8kA T - - - - 8kA T

6kA2.5kA0.6kA 6kA 10kA T 10kA 10kA T T T T 10kA 10kA T T T T

2.5kA0.6kA 3kA 6kA 8kA T 3.5kA 10kA T T T T 3.5kA 10kA T T T T

- 0.8kA 1.2kA 6kA 6kA T 1.6kA 3.5kA T T T 1.6kA 3.5kA T T T15kA 15kA

- - 1.2kA 3kA 6kA 8kA - - 10kA 10kA T T - - 10kA 10kA T T

- - - 3kA 4kA 6kA - - 3.5kA 10kA T - - 3.5kA 10kA T15kA 15kA

- - - 1.2kA 1.5kA 6kA - - - 3.5kA 10kA T - - - 3.5kA 10kA T

- - - - 1.5kA 2kA - - - - 8kA T - - - - 8kA T

- - - - 1.9kA - - - - 2.5kA - - - -- - 2.5kA-

- - - - 1.9kA - - - - 2.5kA - - - -- - 2.5kA-HTI C curve

2.5kA0.6kA 6kA 6kA 10kA T 10kA 10kA T T T T 10kA 10kA T T T T

- 1kA 1.2kA 6kA 6kA T - 3.5kA 15kA T T - 3.5kA 15kA T T15kA 15kA

- - 1.2kA 3kA 6kA 10kA - - 6kA 6kA T T - - 6kA 6kA T T

- - - 3kA 4kA 6kA - - - 6kA T - - - 6kA TT T

- - - 1.2kA 1.6kA 6kA - - - 3.5kA T T - - - 3.5kA T T

- - - - 1.6kA 2kA - - - - 8kA T - - - - 8kA T

T TTT T T T T T T T T T T T T TT

- 2.5kA 15kA 15kA T T - 3.5kA T T T - 3.5kA T T TT T

- - 6kA 6kA 8kA T - - T T T - - T T TT T

- - - 6kA 8kA T - - T T T - - T T TT T

- - - - 6kA T - - 3.5kA T T - - 3.5kA T T- -

- - - - - T - - - 8kA T - - - 8kA T- -

0.5kA0.4kA 0.6kA 0.8kA 1kA 1.3kA 0.6kA 0.8kA 0.6kA 0.8kA0.9kA 1.2kA 1.5kA 3.5kA 0.9kA 1.2kA 1.5kA 3.5kA

0.5kA- 0.6kA 0.8kA 1kA 1.3kA - 0.8kA - 0.8kA0.9kA 1.2kA 1.5kA 3.5kA 0.9kA 1.2kA 1.5kA 3.5kA

-- - 0.8kA 1kA 1.3kA - - - -- 1.2kA 1.5kA 3.5kA - 1.2kA 1.5kA 3.5kA

-- - 0.8kA 1kA 1.3kA - - - -- 1.2kA 1.5kA 3.5kA - 1.2kA 1.5kA 3.5kA

-- - - 1kA 1.3kA - - - -- - 1.5kA 3.5kA - - 1.5kA 3.5kA

-- - - - 1.3kA - - - -- - - 3.5kA - - - 3.5kA

GPS1BS & GPS1MS

GPS2BS & GPS2MS

Remark; For MCB’s with D type Curve assume a C curve type with a one step higher rating.E.G. Selectivity FD160 80Amp LTM with downstream C Curve 40A MCB = 3kA, for D curve 40A, take the value mentioned for 50A C curve, here 1.2kA

*Where T is mentioned Selectivity is full up until the Icu of the downstream device

DISCRIMINATION & SELECTIVITY

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

512 Product Catalogue 2013

SELECTIVE TABLES(RECORD PLUS MOULDED CASE CIRCUIT BREAKERS; TABLE D2 ED. 2C) Upstream FE160N, H & L LTM FE160N, H & L LTMD FE160N, H & L SMR1 FE250V LTM FE250N, H & L LTMD FE250N, H & L SMR1

63A 80A 100A 125A 160A 100A 125A 160A 63A 125A 160A 160A 200A 250A 125A 160A 200A 250A 125A 160A 250A

Downstream

Selectivity limit in kA*

Redline <= 20A 6kA 6kA 8kA T T T T T T T T T T T T T T T T T T

25A 1.2kA 6kA 6kA T T T T T T T T T T T T T T T T T T

DME100 32A 1.2kA 3kA 6kA 8kA T T T T T T T T T T T T T T T T T

B/C curve 40A -- 3kA 4kA 6kA 6kA T T T T T T T T T T T T T T T T

50A -- -- 1.5kA 6kA 6kA T T T -- T T T T T T T T T T T T

63A -- -- 1.5kA 2kA 2kA T T T -- T T T T T T T T T T T T

Redline <= 20A 6kA 6kA 8kA T T T T T T T T T T T T T T T T T T

G60 & DM100 25A 1.2kA 6kA 6kA T T T T T T T T T T T T T T T T T T

B/C curve 32A 1.2kA 3kA 6kA 8kA T T T T T T T T T T T T T T T T T

40A -- 3kA 4kA 6kA 6kA T T T T T T T T T T T T T T T T

50A -- 1.2kA 1.5kA 6kA 6kA T T T -- T T T T T T T T T T T T

63A -- -- 1.5kA 2kA 2kA T T T -- T T T T T T T T T T T T

Redline <= 20A 6kA 6kA 8kA T T T T T T T T T T T T T T T T T T

G100 & GT25 25A 1.2kA 6kA 6kA T T T T T T T T T T T T T T T T T T

B/C curve 32A 1.2kA 3kA 6kA 8kA T T T T T T T T T T T T T T T T T

40A -- 3kA 4kA 6kA 6kA T T T T T T T T T T T T T T T T

50A -- -- 1.5kA 6kA 6kA T T T -- T T T T T T T T T T T T

63A -- -- 1.5kA 2kA 2kA T T T -- T T T T T T T T T T T T

Redline 80A -- -- 1.5kA 2kA 2kA -- T T -- T T 1.9kA 2.5kA 3kA T T T T T T T

HTI 100A -- -- -- -- 2kA -- -- T -- -- T 1.9kA 2.5kA 3kA -- T T T -- T T

C curve 125A -- -- -- -- -- -- -- -- -- -- -- -- -- 3kA -- T T T -- T T

Surion <= 20A 6kA 6kA 10kA T T T T T T T T T T T T T T T T T T

GPS1BS & 25A 1.2kA 6kA 6kA T T T T T T T T T T T T T T T T T T

GPS1MS 32A 1.2kA 3kA 6kA 10kA 10kA T T T T T T 10kA T T T T T T T T T

GPS2BS & 40A -- -- 4kA 6kA 6kA T T T T T T 6kA 10kA T T T T T T T T

GPS2MS 50A -- -- 1.6kA 6kA 6kA T T T -- T T 6kA 6kA 10kA T T T T T T T

63A -- -- -- 2kA 2kA -- T T -- T T 2kA 6kA 6kA T T T T T T T

Surion <= 20A T T T T T T T T T T T T T T T T T T T T T

GPS1BH & 25A 15kA 15kA T T T T T T T T T T T T T T T T T T T

GPS1MH 32A 6kA 6kA 8kA T T T T T T T T T T T T T T T T T T

GPS2BH & 40A -- 6kA 8kA T T T T T T T T T T T T T T T T T T

GPS2MH 50A -- -- 6kA T T T T T -- T T T T T T T T T T T T

63A -- -- -- T T -- T T -- T T T T T T T T T T T T

Record Plus <= 40A -- 0.8kA 1kA 1.2kA 1.6kA T T T T T T 1.6kA 2kA 2.5kA T T T T T T T

FD63/160E 50A -- -- 1kA 1.2kA 1.6kA T T T -- T T 1.6kA 2kA 2.5kA T T T T T T T

LTM/MO/GTM 63A -- -- -- 1.2kA 1.6kA T T T -- T T 1.6kA 2kA 2.5kA T T T T T T T

80A -- -- -- 1.2kA 1.6kA -- T T -- -- T 1.6kA 2kA 2.5kA T T T T T T T

100A -- -- -- -- 1.6kA -- -- T -- -- T 1.6kA 2kA 2.5kA -- T T T -- T T

125A -- -- -- -- -- -- -- -- -- -- -- -- 2kA 2.5kA -- -- T T -- -- T

160A -- -- -- -- -- -- -- -- -- -- -- -- -- 2.5kA -- -- -- T -- -- T

Record Plus <= 40A 0.6kA 0.8kA 1kA 1.2kA 1.6kA 30kA 30kA 30kA 36kA 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA

FD63/160S, N 50A -- 0.8kA 1kA 1.2kA 1.6kA 30kA 30kA 30kA -- 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA

H & L 63A -- -- 1kA 1.2kA 1.6kA 30kA 30kA 30kA -- 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA

LTMD 80A -- -- -- 1.2kA 1.6kA -- 30kA 30kA -- 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA

100A -- -- -- -- 1.6kA -- -- 30kA -- -- 36kA 1.6kA 2kA 2.5kA -- 42kA 42kA 42kA -- 50kA 50kA

125A -- -- -- -- -- -- -- -- -- -- -- -- 2kA 2.5kA -- -- 42kA 42kA -- -- 50kA

160A -- -- -- -- -- -- -- -- -- -- -- -- -- 2.5kA -- -- -- 42kA -- -- 50kA

Record Plus <= 40A 0.6kA 0.8kA 1kA 1.2kA 1.6kA 30kA 30kA 30kA 36kA 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA

FE160 N, H & L 50A -- 0.8kA 1kA 1.2kA 1.6kA 30kA 30kA 30kA -- 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA

LTM/MO/GTM 63A -- -- 1kA 1.2kA 1.6kA 30kA 30kA 30kA -- 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA

80A -- -- -- 1.2kA 1.6kA -- 30kA 30kA -- 36kA 36kA 1.6kA 2kA 2.5kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA

100A -- -- -- -- 1.6kA -- -- 30kA -- -- 36kA 1.6kA 2kA 2.5kA -- 42kA 42kA 42kA -- 50kA 50kA

125A -- -- -- -- -- -- -- -- -- -- -- -- 2kA 2.5kA -- -- 42kA 42kA -- -- 50kA

160A -- -- -- -- -- -- -- -- -- -- -- -- -- 2.5kA -- -- -- 42kA -- -- 50kA

In (A)

*Where T is mentioned Selectivity is full up until the Icu of the downstream device.

DISCRIMINATION & SELECTIVITY

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

Product Catalogue 2013 513

TEC

HN

ICA

L

15

SELECTIVE TABLES(RECORD PLUS MOULDED CASE CIRCUIT BREAKERS; TABLE D3 ED. 2C) Upstream FE160N, H & L SMR1 FE250N, H & L LTMD FE250N, H & L SMR1 FG400N, H & L SMR1 & 2 FG630N, H & L SMR1 & 2

63A 125A 160A 125A 160A 200A 250A 125A 160A 250A 250A 350A 400A 400A 500A 630A

Downstream

Selectivity limit in kA*

Redline <= 16A T T T T T T T T T T T T T T T T

20A T T T T T T T T T T T T T T T T

G60 25A T T T T T T T T T T T T T T T T

G100 & G25 32A T T T T T T T T T T T T T T T T

DM100 & 40A -- T T T T T T T T T T T T T T T

DME100 50A -- T T T T T T T T T T T T T T T

B/C curve 63A -- T T T T T T T T T T T T T T T

Redline 80A -- T T -- T T T T T T T T T T T T

HTI 100A -- -- T -- T T T -- T T T T T T T T

C curve 125A -- -- T -- -- T T -- T T T T T T T T

Surion <= 25A T T T T T T T T T T T T T T T T

GPS1BS & 32A T T T T T T T T T T T T T T T T

GPS1MS 40A -- T T T T T T T T T T T T T T T

GPS2BS & 50A -- T T T T T T T T T T T T T T T

GPS2MS 63A -- T T T T T T T T T T T T T T T

Surion <= 25A T T T T T T T T T T T T T T T T

GPS1BH & 32A T T T T T T T T T T T T T T T T

GPS1MH 40A -- T T T T T T T T T T T T T T T

GPS2BH & 50A -- T T T T T T T T T T T T T T T

GPS2MH 63A -- T T T T T T T T T T T T T T T

Record Plus <= 40A T T T T T T T T T T T T T T T T

FD63/160E 50A -- T T T T T T T T T T T T T T T

LTM/MO/GTM 63A -- T T T T T T T T T T T T T T T

80A -- -- T -- T T T T T T T T T T T T

100A -- -- T -- -- T T -- T T T T T T T T

125A -- -- -- -- -- T T -- -- T T T T T T T

160A -- -- -- -- -- -- T -- -- T T T T T T T

Record Plus <= 40A 36kA 36kA 36kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA T T T T T T

FD63/160S, N 50A -- 36kA 36kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA T T T T T T

H & L 63A -- 36kA 36kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA T T T T T T

LTMD/MO/GTM 80A -- -- 36kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA T T T T T T

100A -- -- 36kA -- 42kA 42kA 42kA -- 50kA 50kA T T T T T T

125A -- -- -- -- -- 42kA 42kA -- -- 50kA T T T T T T

160A -- -- -- -- -- -- 42kA -- -- 50kA T T T T T T

Record Plus <= 40A 36kA 36kA 36kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA T T T T T T

FE160 N, H & L 50A -- 36kA 36kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA T T T T T T

LTM/MO/GTM 63A -- 36kA 36kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA T T T T T T

80A -- 36kA 36kA 42kA 42kA 42kA 42kA 50kA 50kA 50kA T T T T T T

100A -- -- 36kA -- 42kA 42kA 42kA -- 50kA 50kA T T T T T T

125A -- -- -- -- -- 42kA 42kA -- -- 50kA T T T T T T

160A -- -- -- -- -- -- 42kA -- -- 50kA T T T T T T

Record Plus <= 40A 0.8kA 1.8kA 2.2kA 1.3kA 1.6kA 2.5kA 2.5kA 1.8kA 2.2kA 3.5kA T T T T T T

FE160 N, H & L 63A -- 1.8kA 2.2kA 1.3kA 1.6kA 2.5kA 2.5kA 1.8kA 2.2kA 3.5kA T T T T T T

LTMD/SMR1 80A -- 1.8kA 2.2kA 1.3kA 1.6kA 2.5kA 2.5kA 1.8kA 2.2kA 3.5kA T T T T T T

100A -- -- 2.2kA -- 1.6kA 2.5kA 2.5kA -- 2.2kA 3.5kA T T T T T T

125A -- -- -- -- -- 2.5kA 2.5kA -- -- 3.5kA T T T T T T

160A -- -- -- -- -- -- 2.5kA -- -- 3.5kA T T T T T T

Record Plus 125A -- -- -- -- -- -- -- -- -- -- 3.5kA 10kA 15kA T T T

FE250 N, H & L 160A -- -- -- -- -- -- -- -- -- -- 3.5kA 10kA 15kA T T T

LTMD/SMR1 200A -- -- -- -- -- -- -- -- -- -- -- 10kA 15kA T T T

250A -- -- -- -- -- -- -- -- -- -- -- 10kA 15kA T T T

Record Plus

FG400 N, H & L 250A -- -- -- -- -- -- -- -- -- -- -- 5kA 6kA 5kA 7kA 7kA

SMR1/SMR2 400A -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- 7kA

In (A)

*Where T is mentioned Selectivity is full up until the Icu of the downstream device.

DISCRIMINATION & SELECTIVITY

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

514 Product Catalogue 2013

SELECTIVE TABLES(RECORD PLUS MOULDED CASE CIRCUIT BREAKERS; TABLE D4 ED. 2C) Upstream FK800N, H FK1250N, H & FK1600N, H &

& L SMR1 L SMR1 L SMR1

800A 1000A 1250A 600A

Downstream Selectivity limit in kA*

Redline

G60, G100, G25, DM60,

DME60, DM100 & DME100 B/C curve ALL T T T T T

Surion

GPS1BS, GPS1MS, GPS2BS, GPS2MS

GPS1BH, GPS1MH, GPS2BH & GPS2MH ALL T T T T T

Record Plus

FD63/160E, S N & L types

LTM/LTMD/MO/GTM Trip Units ALL T T T T T

Record Plus

FE160 N, H & L types

LTM/LTMD/MO/GTM/SMR1 Trip Units ALL T T T T T

Record Plus

FE250 V, N, H & L types

LTM/LTMD/MO/GTM/SMR1 Trip Units ALL T T T T T

Record Plus

FG400 N, H & L types

SMR1/SMR2 Trip Units ALL T T T T T

Record Plus

FG630 N, H & L types

SMR1/SMR2 Trip Units 400A 15kA T T T T

500A 15kA T T T T

630A 15kA T T T T

Record Plus

FK800 N, H & L types

LTM/MO/SMR1e, s & g Trip Units ALL -- 15kA 15kA 25kA 25kA

Record Plus

FK1250 N, H & L types

LTM/MO/SMR1e, s & g Trip Units 1000A -- -- -- 25kA 25kA

1250A -- -- -- 25kA 25kA

* Where T is mentioned Selectivity is full up untilthe Icu of the downstream device

In (A)

DISCRIMINATION & SELECTIVITY

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

Product Catalogue 2013 515

TEC

HN

ICA

L

15

SELECTIVE TABLES(RECORD PLUS MOULDED CASE CIRCUIT BREAKERS; TABLE D4 ED. 2C) Upstream Mpact + Frame 1 Mpact + Frame 2 Mpact + Frame3

400A 630A 800A 1000A 1250A 1600A 2000A 2500A 1000A 1250A 1600A 2000A 2500A 3200A 4000A 5000A 6300A

Downstream

Selectivity limit in kA*

Redline

G60,G100,G25, DM60,

DME60, DM100 & DME100 B/C curve ALL T T T T T T T T T T T T T T T T T

Surion

GPS1BS, GPS1MS, GPS2BS, GPS2MS

GPS1BH, GPS1MH, GPS2BH & GPS2MH ALL T T T T T T T T T T T T T T T T T

Record Plus

FD63/160E, S N & L types

LTM/LTMD/MO/GTM Trip Units ALL T T T T T T T T T T T T T T T T T

FE160 N, H & L types

LTM/LTMD/MO/GTM/SMR1 Trip Units ALL T T T T T T T T T T T T T T T T T

Record Plus

FE250 V, N, H & L types

LTM/LTMD/MO/GTM/SMR1 Trip Units ALL T T T T T T T T T T T T T T T T T

Record Plus

FG400 N, H & L types

SMR1/SMR2 Trip Units 250A T T T T T T T T T T T T T T T T T

400A -- -- T T T T T T T T T T T T T T T

Record Plus

FG630 N, H & L types

SMR1/SMR2 Trip Units 400A -- -- T T T T T T T T T T T T T T T

500A -- -- -- T T T T T T T T T T T T T T

630A -- -- -- T T T T T T T T T T T T T T

Record Plus

FK800 N, H & L types

LTM/MO/SMR1e, s & g Trip Units ALL -- -- -- -- T T T T T T T T T T T T T

Record Plus

FK1250 N, H & L types

LTM/MO/SMR1e, s & g Trip Units 1000A -- -- -- -- -- T T T -- -- T T T T T T T

1250A -- -- -- -- -- -- T T -- -- -- T T T T T T

Mpact Plus

Frame 1 & Frame 2

MPRO plus 17, 18, 30 & 40 Trip Units 400A -- T T T T T T T T T T T T T T T T

630A -- -- -- T T T T T T T T T T T T T T

800A -- -- -- -- T T T T -- T T T T T T T T

1000A -- -- -- -- -- T T T -- -- T T T T T T T

1600A -- -- -- -- -- -- -- T -- -- -- -- T T T T T

2000A -- -- -- -- -- -- -- -- -- -- -- -- -- T T T T

2500A -- -- -- -- -- -- -- -- -- -- -- -- -- -- T T T

* Where T is mentioned Selectivity is full up until the Icu of the downstream device

In (A)

DISCRIMINATION & SELECTIVITY

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

516 Product Catalogue 2013

SELECTIVE PLUS TABLES(RECORD PLUS MOULDED CASE CIRCUIT BREAKERS; TABLE DB1 ED. 2C) Upstream FDC 63/160 LTM FDE 63/160 LTM FDS 63/160 LTMD 63A 80A 100A 125A 63A 80A 100A 125A 63A 80A 100A 125A Downstream 160A 160A 160A Selectivity limit in kA / Icu of combination in kA at 400-415V AC Redline <= 16A 6/18 6/18 10/18 18/18 6/22 6/22 10/22 22/22 25/25 25/25 25/25 25/25 G60 &GT10 20A 3/18 6/18 8/18 18/18 3/22 6/22 8/22 22/22 25/25 25/25 25/25 25/25 B/C curve 25A -- 6/18 6/18 18/18 -- 6/22 6/22 22/22 15/25 15/25 25/25 25/25 32A -- 3/18 6/18 18/18 -- 3/22 6/22 22/22 10/25 10/25 25/25 25/25 40A -- 3/18 4/18 18/18 -- 3/22 4/22 22/22 3.5/25 10/25 15/25 25/25 50A -- -- 1.5/18 6/18 -- -- 1.5/22 6/22 -- 3.5/25 10/25 22/25 63A -- -- -- -- -- -- -- -- -- -- 8/25 22/25 Redline <= 16A 6/18 6/18 10/18 18/18 6/25 6/25 10/25 25/25 30/30 30/30 30/30 30/30 G100 20A 3/18 6/18 8/18 18/18 3/25 6/25 8/25 25/25 30/30 30/30 30/30 30/30 B/C curve 25A -- 6/18 6/18 18/18 -- 6/25 6/25 25/25 15/30 30/30 30/30 30/30 32A -- 3/18 6/18 18/18 -- 3/25 6/25 25/25 10/30 10/30 30/30 30/30 40A -- 3/18 4/18 18/18 -- 3/25 4/25 25/25 3.5/30 10/30 15/30 25/30 50A -- -- 1.5/18 6/18 -- -- -- 6/25 -- 3.5/30 10/30 22/30 63A -- -- -- 2/18 -- -- -- 2/25 -- -- 8/30 22/30 Redline <= 20A -- -- -- -- -- -- -- -- 36/36 36/36 36/36 36/36 GT25 25A -- -- -- -- -- -- -- -- 15/36 15/36 30/36 30/36 B/C curve 32A -- -- -- -- -- -- -- -- 10/30 10/30 36/30 30/30 40A -- -- -- -- -- -- -- -- 3.5/30 10/30 15/30 25/30 50A -- -- -- -- -- -- -- -- -- 3.5/30 10/30 22/30 63A -- -- -- -- -- -- -- -- -- -- 8/30 22/30 Surion <= 10A -- -- -- -- -- -- -- -- -- -- -- -- GPS1BS & 12.5A -- -- -- -- -- -- -- -- -- -- -- -- GPS1MS 16/20A -- -- -- -- -- -- -- -- 36/36 36/36 36/36 36/36 25/32A -- -- -- -- -- -- -- -- 36/36 36/36 36/36 36/36 40A -- -- -- -- -- -- -- -- -- 36/36 36/36 36/36 50/63A -- -- -- -- -- -- -- -- -- -- 36/36 36/36 Surion <= 10A -- -- -- -- -- -- -- -- -- -- -- -- GPS2BS & 12.5A -- -- -- -- -- -- -- -- 36/36 36/36 36/36 36/36 GPS2MS 16/20A -- -- -- -- -- -- -- -- 36/36 36/36 36/36 36/36 25/32A -- -- -- -- -- -- -- -- 36/36 36/36 36/36 36/36 40A -- -- -- -- -- -- -- -- -- 36/36 36/36 36/36 50/63A -- -- -- -- -- -- -- -- -- -- 36/36 36/36 Surion <= 10A -- -- -- -- -- -- -- -- -- -- -- -- GPS1BH & 12.5A -- -- -- -- -- -- -- -- -- -- -- -- GPS1MH 16/20A -- -- -- -- -- -- -- -- -- -- -- -- GPS2BH & 25/32A -- -- -- -- -- -- -- -- -- -- -- -- GPS2MH 40A -- -- -- -- -- -- -- -- -- -- -- -- 50/63A -- -- -- -- -- -- -- -- -- -- -- --

Upstream FDN 63/160 LTMD FDH 63/160 LTMD FDL 63/160 LTMD 63A 80A 100A 125A 63A 80A 100A 125A 63A 80A 100A 125A Downstream 160A 160A 160A Selectivity limit in kA / Icu of combination in kA at 400-415V AC Redline <= 16A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/42 36/42 36/42 36/42 G60 &GT10 20A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/42 36/42 36/42 36/42 B/C curve 25A 15/30 15/30 30/30 30/30 15/36 15/36 30/36 30/36 15/42 15/42 30/42 30/42 32A 10/30 10/30 30/30 30/30 10/36 10/36 36/36 30/36 10/42 10/42 36/42 30/42 40A 3.5/30 10/30 15/30 25/30 3.5/36 10/36 15/36 25/36 3.5/42 10/42 15/42 25/42 50A -- 3.5/30 10/30 22/30 -- 3.5/36 10/36 22/36 -- 3.5/42 10/42 22/42 63A -- -- 8/30 22/30 -- -- 8/36 22/36 -- -- 8/42 22/42 Redline <= 16A 36/36 36/36 36/36 36/36 36/42 36/42 36/42 36/42 36/50 36/50 36/50 36/50 G100 20A 36/36 36/36 36/36 36/36 36/42 36/42 36/42 36/42 36/50 36/50 36/50 36/50 B/C curve 25A 15/36 36/36 30/36 30/36 15/42 36/42 30/42 30/42 15/50 15/50 30/50 30/50 32A 10/36 10/36 30/36 30/36 10/42 10/42 30/42 30/42 10/50 10/50 30/50 30/50 40A 3.5/36 10/36 15/36 25/36 3.5/42 10/42 15/42 25/42 3.5/50 10/50 15/50 25/50 50A -- 3.5/36 10/36 22/36 -- 3.5/42 10/42 22/42 -- 3.5/50 10/50 22/50 63A -- -- 8/36 22/36 -- -- 8/42 22/42 -- -- 8/50 22/50 Redline <= 20A 36/42 36/42 36/42 36/42 36/50 36/50 36/50 36/50 36/65 36/65 36/65 36/65 GT25 25A 15/42 15/42 30/42 30/42 15/50 15/50 30/50 30/50 15/65 15/65 30/65 30/65 B/C curve 32A 10/36 10/36 36/36 30/36 10/42 10/42 36/42 30/42 10/50 10/50 36/50 30/50 40A 3.5/36 10/36 15/36 25/36 3.5/42 10/42 15/42 25/42 3.5/50 10/50 15/50 25/50 50A -- 3.5/36 10/36 22/36 -- 3.5/42 10/42 22/42 -- 3.5/50 10/50 22/50 63A -- -- 8/36 22/36 -- -- 8/42 22/42 -- -- 8/50 22/50 Surion <= 10A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150 GPS1BS & 12.5A -- -- -- -- 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150 GPS1MS 16/20A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65 25/32A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65 40A -- 42/42 42/42 42/42 -- 50/50 50/50 50/50 -- 65/65 65/65 65/65 50/63A -- -- 42/42 42/42 -- -- 50/50 50/50 -- -- 65/65 65/65 Surion <= 10A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150 GPS2BS & 12.5A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65 GPS2MS 16/20A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65 25/32A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65 40A -- 42/42 42/42 42/42 -- 50/50 50/50 50/50 -- 65/65 65/65 65/65 50/63A -- -- 42/42 42/42 -- -- 50/50 50/50 -- -- 65/65 65/65 Surion <= 10A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150 GPS1BH & 12.5A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150 GPS1MH 16/20A -- -- -- -- 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150 GPS2BH & 25/32A -- -- -- -- 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150 GPS2MH 40A -- -- -- -- -- 80/80 80/80 80/80 -- 150/150 150/150 150/150 50/63A -- -- -- -- -- -- 80/80 80/80 -- -- 150/150 150/150

In (A)

In (A)

DISCRIMINATION & SELECTIVITY

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

Product Catalogue 2013 517

TEC

HN

ICA

L

15

In (A)

SELECTIVE PLUSTABLE DB1A ED 2C Upstream FDC 63/160 LTM FDE 63/160 LTM FDS 63/160 LTMD

63A 80A 100A 125A 63A 80A 100A 125A 63A 80A 100A 125A

Downstream 160A 160A 160A

Selectivity limit in kA / Icu of combination in kA at 240V AC

Redline <= 16A 6/18 6/18 10/18 18/18 6/22 6/22 10/22 10/22 25/25 25/25 25/25 25/25

DME100 20A 3/18 6/18 8/18 18/18 3/22 6/22 8/22 10/22 25/25 25/25 25/25 25/25

B/C curve 25A -- 6/18 6/18 18/18 -- 6/22 6/22 10/22 15/25 25/25 25/25 25/25

32A -- 3/18 6/18 18/18 -- 3/22 6/22 10/22 10/25 10/25 25/25 25/25

40A -- 3/18 4/18 18/18 -- 3/22 4/22 10/22 3.5/25 10/25 15/25 25/25

Upstream FDN 63/160 LTMD FDH 63/160 LTMD FDL 63/160 LTMD

63A 80A 100A 125A 63A 80A 100A 125A 63A 80A 100A 125A

Downstream 160A 160A 160A

Selectivity limit in kA / Icu of combination in kA at 240V AC

Redline <= 16A 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25

DME100 20A 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25 25/25

B/C curve 25A 15/25 25/25 25/25 25/25 15/25 25/25 25/25 25/25 15/25 25/25 25/25 25/25

32A 10/25 10/25 25/25 25/25 10/25 10/25 25/25 25/25 10/25 10/25 25/25 25/25

40A 3.5/25 10/25 15/25 25/25 3.5/25 10/25 15/25 25/25 3.5/25 10/25 15/25 25/25

In (A)

In (A)

SELECTIVE PLUSTABLE DB2A ED 2C Upstream FE160N-LTMD/SMR1 FE160H-LTMD/SMR1 FE160L-LTMD/SMR1

63A 100A 125A 160A 63A 100A 125A 160A 63A 100A 125A 160A

Downstream

Selectivity limit in kA / Icu of combination in kA at 240V AC

Redline <= 16A 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22

DME100 20A 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22

B/C curve 25A 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22

32A 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22 22/22

40A -- 22/22 22/22 22/22 -- 22/22 22/22 22/22 -- 22/22 22/22 22/22

Upstream FE250N-LTMD/SMR1 FE250H-LTMD/SMR1 FE250L-LTMD/SMR1 125A 160A 200A 250A 125A 160A 200A 250A 125A 160A 200A 250A Downstream Selectivity limit in kA / Icu of combination in kA at 240V AC Redline <= 16A 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 DME100 20A 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 B/C curve 25A 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 32A 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 40A 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18 18/18

In (A)

DISCRIMINATION & SELECTIVITY

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

518 Product Catalogue 2013

SELECTIVE PLUSTABLE DB2 ED 2C Upstream FE160N-LTMD/SMR1 FE160H-LTMD/SMR1 FE160L-LTMD/SMR1 63A 100A 125A 160A 63A 100A 125A 160A 63A 100A 125A 160A Downstream Selectivity limit in kA / Icu of combination in kA at 400-415V AC Redline <= 25A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 G60 &GT10 32A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 B/C curve 40A -- 30/30 30/30 30/30 -- 36/36 36/36 36/36 -- 42/42 42/42 42/42 50A -- 30/30 30/30 30/30 -- 36/36 36/36 36/36 -- 42/42 42/42 42/42 63A -- -- 30/30 30/30 -- -- 36/36 36/36 -- -- 42/42 42/42 Redline <= 25A 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 G100 32A 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 B/C curve 40A -- 36/36 36/36 36/36 -- 42/42 42/42 42/42 -- 50/50 50/50 50/50 50A -- 36/36 36/36 36/36 -- 42/42 42/42 42/42 -- 50/50 50/50 50/50 63A -- -- 36/36 36/36 -- -- 42/42 42/42 -- -- 50/50 50/50 Redline <= 25A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65 GT25 32A 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 B/C curve 40A -- 36/36 36/36 36/36 -- 42/42 42/42 42/42 -- 50/50 50/50 50/50 50A -- 36/36 36/36 36/36 -- 42/42 42/42 42/42 -- 50/50 50/50 50/50 63A -- -- 36/36 36/36 -- -- 42/42 42/42 -- -- 50/50 50/50 Surion <= 10A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150 GPS1BS & 12.5A -- -- -- -- 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150 GPS1MS 16/20A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65 25/32A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65 40A -- 42/42 42/42 42/42 -- 50/50 50/50 50/50 -- 65/65 65/65 65/65 50/63A -- -- 42/42 42/42 -- -- 50/50 50/50 -- -- 65/65 65/65 Surion <= 10A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150 GPS2BS & 12.5A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65 GPS2MS 16/20A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65 25/32A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65 40A -- 42/42 42/42 42/42 -- 50/50 50/50 50/50 -- 65/65 65/65 65/65 50/63A -- -- 42/42 42/42 -- -- 50/50 50/50 -- -- 65/65 65/65 Surion <= 10A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150 GPS1BH & 12.5A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150 GPS1MH 16/20A -- -- -- -- 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150 GPS2BH & 25/32A -- -- -- -- 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150 GPS2MH 40A -- -- -- -- -- 80/80 80/80 80/80 -- 150/150 150/150 150/150 50/63A -- -- -- -- -- -- 80/80 80/80 -- -- 150/150 150/150

Upstream FE250N-LTMD/SMR1 FE250H-LTMD/SMR1 FE250L-LTMD/SMR1 125A 160A 200A 250A 125A 160A 200A 250A 125A 160A 200A 250A Downstream Selectivity limit in kA / Icu of combination in kA at 400-415V AC Redline <= 25A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 G60 &GT10 32A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 B/C curve 40A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 50A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 63A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 Redline <= 25A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 G100 32A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 B/C curve 40A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 50A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 63A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 Redline <= 25A 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 42/42 42/42 42/42 42/42 GT25 32A 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 42/42 42/42 42/42 42/42 B/C curve 40A 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 42/42 42/42 42/42 42/42 50A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 63A 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 36/36 36/36 36/36 36/36 Surion <= 10A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150 GPS1BS & 12.5A -- -- -- -- 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150 GPS1MS 16/20A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65 25/32A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65 40A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65 50/63A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65 Surion <= 10A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150 GPS2BS & 12.5A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65 GPS2MS 16/20A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65 25/32A 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 65/65 65/65 65/65 65/65 40A 42/42 42/42 42/42 42/42 -- 50/50 50/50 50/50 -- 65/65 65/65 65/65 50/63A 42/42 42/42 42/42 42/42 -- -- 50/50 50/50 -- -- 65/65 65/65 Surion <= 10A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150 GPS1BH & 12.5A -- -- -- -- -- -- -- -- 150/150 150/150 150/150 150/150 GPS1MH 16/20A -- -- -- -- 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150 GPS2BH & 25/32A -- -- -- -- 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150 GPS2MH 40A -- -- -- -- 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150 50/63A -- -- -- -- 80/80 80/80 80/80 80/80 150/150 150/150 150/150 150/150

In (A)

In (A)

DISCRIMINATION & SELECTIVITY

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

Product Catalogue 2013 519

TEC

HN

ICA

L

15

Upstream FE160N-LTMD FE160H-LTMD FE160L-LTMD In (A) 100A 125A 160A 100A 125A 160A 100A 125A 160A Downstream Type & In Selectivity limit in kA / Icu of combination in kA at 400 - 415V AC Record Plus FDC63 30/30 30/30 30/30 30/36 30/36 30/36 30/42 30/42 30/42 LTM. LTMD, FDE63 30/36 30/36 30/36 30/42 30/42 30/42 30/50 30/50 30/50 GTM & MO FDS63 30/42 30/42 30/42 30/50 30/50 30/50 30/65 30/65 30/65 FDN63 30/50 30/50 30/50 30/80 30/80 30/80 30/150 30/150 30/150 FDH63 -- -- -- 30/80 30/80 30/80 30/150 30/150 30/150 Record Plus FDC160 <= 100A -- -- 30/30 -- -- 30/36 -- -- 30/42 LTM. LTMD, FDE160 <= 100A -- -- 30/36 -- -- 30/42 -- -- 30/50 GTM & MO FDS160 <= 100A -- -- 30/42 -- -- 30/50 -- -- 30/65 FDN160 <= 100A -- -- 30/50 -- -- 30/80 -- -- 30/150 FDH160 <= 100A -- -- -- -- -- 30/80 -- -- 30/150 Record Plus FDC160 125A -- -- -- -- -- -- -- -- -- LTM. LTMD, FDE160 125A -- -- -- -- -- -- -- -- -- & GTM FDS160 125A -- -- -- -- -- -- -- -- -- FDN160 125A -- -- -- -- -- -- -- -- -- FDH160 125A -- -- -- -- -- -- -- -- -- Record Plus FDC160 160A -- -- -- -- -- -- -- -- -- LTM. LTMD, FDE160 160A -- -- -- -- -- -- -- -- -- & GTM FDS160 160A -- -- -- -- -- -- -- -- -- FDN160 160A -- -- -- -- -- -- -- -- -- FDH160 160A -- -- -- -- -- -- -- -- --

Upstream FE250N-LTMD FE250H-LTMD FE250L-LTMD In (A) 125A 160A 200A 250A 125A 160A 200A 250A 125A 160A 200A 250A Downstream Type & In Selectivity limit in kA / Icu of combination in kA at 400 - 415V AC Record Plus FDC63 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 LTM. LTMD, FDE63 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 42/50 42/50 42/50 42/50 GTM & MO FDS63 42/42 42/42 42/42 42/42 42/50 42/50 42/50 42/50 42/65 42/65 42/65 42/65 FDN63 42/50 42/50 42/50 42/50 42/80 42/80 42/80 42/80 42/150 42/150 42/150 42/150 FDH63 -- -- -- -- 42/80 42/80 42/80 42/80 42/150 42/150 42/150 42/150 Record Plus FDC160 <= 100A -- 30/30 30/30 30/30 -- 36/36 36/36 36/36 -- 42/42 42/42 42/42 LTM. LTMD, FDE160 <= 100A -- 36/36 36/36 36/36 -- 42/42 42/42 42/42 -- 42/50 42/50 42/50 GTM & MO FDS160 <= 100A -- 42/42 42/42 42/42 -- 42/50 42/50 42/50 -- 42/65 42/65 42/65 FDN160 <= 100A -- 42/50 42/50 42/50 -- 42/80 42/80 42/80 -- 42/150 42/150 42/150 FDH160 <= 100A -- -- -- -- -- 42/80 42/80 42/80 -- 42/150 42/150 42/150 Record Plus FDC160 125A -- -- 30/30 30/30 -- -- 36/36 36/36 -- -- 42/42 42/42 LTM. LTMD, FDE160 125A -- -- 36/36 36/36 -- -- 42/42 42/42 -- -- 42/50 42/50 & GTM FDS160 125A -- -- 42/42 42/42 -- -- 42/50 42/50 -- -- 42/65 42/65 FDN160 125A -- -- 42/50 42/50 -- -- 42/80 42/80 -- -- 42/150 42/150 FDH160 125A -- -- -- -- -- -- 42/80 42/80 -- -- 42/150 42/150 Record Plus FDC160 160A -- -- -- 30/30 -- -- -- 36/36 -- -- -- 42/42 LTM. LTMD, FDE160 160A -- -- -- 36/36 -- -- -- 42/42 -- -- -- 42/50 & GTM FDS160 160A -- -- -- 42/42 -- -- -- 42/50 -- -- -- 42/65 FDN160 160A -- -- -- 42/50 -- -- -- 42/80 -- -- -- 42/150 FDH160 160A -- -- -- -- -- -- -- 42/80 -- -- -- 42/150

SELECTIVE PLUSTABLE DB3 ED 2C

DISCRIMINATION & SELECTIVITY

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

520 Product Catalogue 2013

Upstream FE160N-SMR1 FE160H-SMR1 FE160L-SMR1

In (A) 63A 125A 160A 63A 125A 160A 63A 125A 160A

Downstream Type & In

Selectivity limit in kA / Icu of combination in kA at 400 - 415V AC

Record Plus FDC63 -- 30/30 30/30 -- 30/36 30/36 -- 36/42 36/42

LTM. LTMD, FDE63 -- 36/36 36/36 -- 30/42 30/42 -- 36/50 36/50

GTM & MO FDS63 -- 36/42 36/42 -- 30/50 30/50 -- 36/65 36/65

FDN63 -- 36/50 36/50 -- 30/80 30/80 -- 36/150 36/150

FDH63 -- -- -- -- 30/80 30/80 -- 36/150 36/150

Record Plus FDC160 <= 100A -- -- 30/30 -- -- 30/36 -- -- 36/42

LTM. LTMD, FDE160 <= 100A -- -- 36/36 -- -- 30/42 -- -- 36/50

GTM & MO FDS160 <= 100A -- -- 36/42 -- -- 30/50 -- -- 36/65

FDN160 <= 100A -- -- 36/50 -- -- 30/80 -- -- 36/150

FDH160 <= 100A -- -- -- -- -- 30/80 -- -- 36/150

Record Plus FDC160 125A -- -- -- -- -- -- -- -- --

LTM. LTMD, FDE160 125A -- -- -- -- -- -- -- -- --

& GTM FDS160 125A -- -- -- -- -- -- -- -- --

FDN160 125A -- -- -- -- -- -- -- -- --

FDH160 125A -- -- -- -- -- -- -- -- --

Record Plus FDC160 160A -- -- -- -- -- -- -- -- --

LTM. LTMD, FDE160 160A -- -- -- -- -- -- -- -- --

& GTM FDS160 160A -- -- -- -- -- -- -- -- --

FDN160 160A -- -- -- -- -- -- -- -- --

FDH160 160A -- -- -- -- -- -- -- -- --

Upstream FE250N-SMR1 FE250H-SMR1 FE250L-SMR1

In (A) 125A 160A 200A 250A 125A 160A 200A 250A 125A 160A 200A 250A

Downstream Type & In

Selectivity limit in kA / Icu of combination in kA at 400 - 415V AC

Record Plus FDC63 30/30 30/30 30/30 30/30 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42

LTM. LTMD, FDE63 36/36 36/36 36/36 36/36 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50

GTM & MO FDS63 42/42 42/42 42/42 42/42 50/50 50/50 50/50 50/50 50/65 50/65 50/65 50/65

FDN63 50/50 50/50 50/50 50/50 50/80 50/80 50/80 50/80 50/150 50/150 50/150 50/150

FDH63 -- -- -- -- 50/80 50/80 50/80 50/80 50/150 50/150 50/150 50/150

Record Plus FDC160 <= 100A -- 30/30 30/30 30/30 -- 36/36 36/36 36/36 -- 42/42 42/42 42/42

LTM. LTMD, FDE160 <= 100A -- 36/36 36/36 36/36 -- 42/42 42/42 42/42 -- 50/50 50/50 50/50

GTM & MO FDS160 <= 100A -- 42/42 42/42 42/42 -- 50/50 50/50 50/50 -- 50/65 50/65 50/65

FDN160 <= 100A -- 50/50 50/50 50/50 -- 50/80 50/80 50/80 -- 50/150 50/150 50/150

FDH160 <= 100A -- -- -- -- -- 50/80 50/80 50/80 -- 50/150 50/150 50/150

Record Plus FDC160 125A -- -- 30/30 30/30 -- -- 36/36 36/36 -- -- 42/42 42/42

LTM. LTMD, FDE160 125A -- -- 36/36 36/36 -- -- 42/42 42/42 -- -- 50/50 50/50

& GTM FDS160 125A -- -- 42/42 42/42 -- -- 50/50 50/50 -- -- 50/65 50/65

FDN160 125A -- -- 50/50 50/50 -- -- 50/80 50/80 -- -- 50/150 50/150

FDH160 125A -- -- -- -- -- -- -- -- -- -- 50/150 50/150

Record Plus FDC160 160A -- -- -- 30/30 -- -- -- 36/36 -- -- -- 42/42

LTM. LTMD, FDE160 160A -- -- -- 36/36 -- -- -- 42/42 -- -- -- 50/50

& GTM FDS160 160A -- -- -- 42/42 -- -- -- 50/50 -- -- -- 50/65

FDN160 160A -- -- -- 50/50 -- -- -- 50/80 -- -- -- 50/150

FDH160 160A -- -- -- -- -- -- -- 50/80 -- -- -- 50/150

SELECTIVE PLUSTABLE DB4 ED 2C

DISCRIMINATION & SELECTIVITY

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

Product Catalogue 2013 521

TEC

HN

ICA

L

15

Upstream FG400N-SMR1 FG400H-SMR1 FG400L-SMR1 FG630N-SMR1 FG630H-SMR1 FG630L-SMR1

In (A) 250A 400A 250A 400A 250A 400A 400A 500A 400A 500A 400A 500A

Downstream Type & In 630A 630A 630A

Selectivity limit in kA / Icu of combination in kA at 400-415V AC

Record Plus FDC63 30/30 30/30 36/36 36/36 42/42 42/42 30/30 30/30 36/36 36/36 42/42 42/42

LTM. LTMD, FDE63 36/36 36/36 42/42 42/42 50/50 50/50 36/36 36/36 42/42 42/42 50/50 50/50

GTM & MO FDS63 42/42 42/42 50/50 50/50 65/65 65/65 42/42 42/42 50/50 50/50 65/65 65/65

FDN63 50/50 50/50 80/80 80/80 150/150 150/150 50/50 50/50 80/80 80/80 150/150 150/150

FDH63 -- -- 80/80 80/80 150/150 150/150 -- -- 80/80 80/80 150/150 150/150

Record Plus FDC160 30/30 30/30 36/36 36/36 42/42 42/42 30/30 30/30 36/36 36/36 42/42 42/42

LTM. LTMD, FDE160 36/36 36/36 42/42 42/42 50/50 50/50 36/36 36/36 42/42 42/42 50/50 50/50

GTM & MO FDS160 42/42 42/42 50/50 50/50 65/65 65/65 42/42 42/42 50/50 50/50 65/65 65/65

FDN160 50/50 50/50 80/80 80/80 150/150 150/150 50/50 50/50 80/80 80/80 150/150 150/150

FDH160 -- -- 80/80 80/80 150/150 150/150 -- -- 80/80 80/80 150/150 150/150

Record Plus FEN160 50/50 50/50 80/80 80/80 150/150 150/150 50/50 50/50 80/80 80/80 150/150 150/150

LTM.LTMD,GTM FEH160 -- -- 80/80 80/80 150/150 150/150 -- -- 80/80 80/80 150/150 150/150

MO & SMR1 FEN250 -- -- 80/80 80/80 150/150 150/150 50/50 50/50 80/80 80/80 150/150 150/150

FEH250 -- -- 80/80 80/80 150/150 150/150 -- -- 80/80 80/80 150/150 150/150

Upstream FK800N-SMR FK800H-SMR FK800L-SMR FK1250N-SMR FK1250H-SMR FK1250L-SMR FK1600N-SMR FK1600H-SMR

In (A) 800A 800A 800A 1000A 1250A 1000A 1250A 1000A 1250A 1600A 1600A

Downstream Type&In

Selectivity limit in kA / Icu of combination in kA at 400-415V AC

Record Plus

LTM. LTMD, FDN63 50/50 80/80 100/100 50/50 50/50 80/80 80/80 100/100 100/100 50/50 80/80

GTM & MO FDH63 50/50 80/80 100/100 50/50 50/50 80/80 80/80 100/100 100/100 50/50 80/80

Record Plus

LTM. LTMD, FDN160 50/50 80/80 100/100 50/50 50/50 80/80 80/80 100/100 100/100 50/50 80/80

GTM & MO FDH160 50/50 80/80 100/100 50/50 50/50 80/80 80/80 100/100 100/100 50/50 80/80

Record Plus FEN160 50/50 80/80 100/100 50/50 50/50 80/80 80/80 100/100 100/100 50/50 80/80

LTM. LTMD, FEH160 50/50 80/80 100/100 50/50 50/50 80/80 80/80 100/100 100/100 50/50 80/80

GTM, MO FEN250 50/50 80/80 100/100 50/50 50/50 80/80 80/80 100/100 100/100 50/50 80/80

& SMR1 FEH250 -- 80/80 100/100 50/50 50/50 80/80 80/80 100/100 100/100 50/50 80/80

Record Plus FGN400 50/50 80/80 100/100 50/50 50/50 80/80 80/80 100/100 100/100 50/50 80/80

SMR1 & FGH400 50/50 80/80 100/100 50/50 50/50 80/80 80/80 100/100 100/100 50/50 80/80

SMR2 FGN630 15/50 15/80 15/100 50/50 50/50 80/80 80/80 100/100 100/100 50/50 80/80

FGH630 -- 15/80 15/100 -- -- 80/80 80/80 100/100 100/100 50/50 80/80

Record Plus FKN800 -- -- -- 15/50 15/50 15/80 15/80 15/100 15/100 25/50 25/80

SMR1 FKH800 -- -- -- -- -- 15/80 15/80 15/100 15/100 25/50 25/80

FKN1250 -- -- -- -- -- -- -- -- -- 25/50 25/80

SELECTIVE PLUSTABLE DB5 ED 2C

SELECTIVE PLUSTABLE DB6 ED 2C

DISCRIMINATION & SELECTIVITY

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

522 Product Catalogue 2013

FUSE DE-RATING WITH HIGH ENCLOSURE TEMPERATURES

Fuse Nominal Maximum Load Current (A) Rating (A) Versus Fluid Environment Temperature 55°C 60°C 65°C 70°C 75°C 63 or less 80 75 70 100 95 90 125 120 110 160 145 135 200 190 180 170 250 235 225 210 315 300 285 270 255 355 350 330 315 295 400 390 380 360 340 450 425 405 380 360 500 475 450 425 400 380 560 540 520 495 465 440 630 600 570 540 510 480 670 650 615 585 550 520 710 700 665 630 595 560 750 725 710 670 630 590 800 760 720 680 640 600 1000 950 900 850 800 750 1250 1140 1070 1020 960 900

In accordance with the relevant Standards, the rated current of fuses is determined by tests conducted at 35°C ambient air temperature. When fuses are installed within enclosures, it is the temperature within the enclosure (fluid enviroment temperature) which determines whether de-rating is necessary.The effect of high enclosure temperatures on IPD Type T fuses is indicated by the table below.

De-rating notnecessary

FUSE LINK TEMPERATURE DERATING

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

Product Catalogue 2013 523

TEC

HN

ICA

L

15

Notes:1. Selection of the above fuse-links is based on the formula I2t = K2S2 given in Clause 5.3 of AS/NZS 3008.1.1:1998 where: I = Current which causes the fuse-link to operate in 5 seconds. t = 5 seconds. K = Constant of 111 for PVC insulated copper conductor, for the condition of initial. temperature 75°C and final temperature 160°C (during overcurrent condition). S = Cross-sectional area of the conductor in mm2.

2. For motor start fuse-links (i.e. those classified and marked ‘gM’) the larger of its dual current ratings is applicable, e.g. 160A for TCP100M160 type.

FUSE PROTECTION OF CABLES AGAINST TRANSIENT OVERCURRENTS

Maximum Current-Carrying Maximum GEC, Capacity (A) GE or IPD Fuse-Link Conductor Rating (A) cross-sectional area (mm2) “Unenclosed” condition. “Enclosed” condition. Ratings according to Ratings according to Type T DIN Type Table 6, Column 6 of Table 6, Column 8 of ‘gG’ ‘gL’-’gG’ AS/NZS 3008.1.1:1998 AS/NZS 3008.1.1:1998 1 13 11 16 16 1.5 16 14 20 20 2.5 23 20 35 32 4 31 26 50 40 6 40 34 63 50 10 54 47 80 80 16 72 62 125 125 25 97 87 200 200 35 120 100 250 250 50 145 125 355 355 70 185 155 450 500 95 230 185 630 630 120 265 220 710 800 150 310 250 800 1000 185 355 285 1000 1000 240 425 340 1250 1000 300 490 390 1250 1000 400 570 455 1250 1000 500 660 530 1250 1000 630 760 620 1250 1000

In some circuits such as the motors, significant transient overcurrents are produced during switching, and it is not economical practice to match cable and fuse-link ratings. For these cases, the cable is chosen for the circuit load condition and the fuse-links are chosen to withstand the transient overcurrent condition.The fuse-links provide only short-circuit current protection to the motor, associated cables and other circuits components. The necessary overload protection is provided by other means such as the motor starter’s thermal overload relay.The short-circuit protection of cables is covered by Section 5 of AS/NZS 3008.1.1:1998 and the Table below shows how fuse-links relate to these requirements in protecting V75 rated PVC insulated copper conductors.

PROTECTION OF CABLES WITH FUSE LINKS

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

524 Product Catalogue 2013

27 37 59 59 16 22 35 35 8 11 17 17 5 7 11 11 3 4 7 7 1 2 3 3 0 1 1 1 51 61 79 79 32 38 49 49 28 33 41 41 18 21 26 26 8 10 12 12 26 32 49 49 20 25 38 38 20 25 38 38 13 14 25 25 5 6 9 9 5 5 5 6 3 3 4 4 2 2 2 2 1 1 2 2 9 9 9 9 7 7 7 7 5 5 5 5 3 3 3 3 3 3 4 4 2 2 3 3 1 1 1 1 5 5 5 5 4 4 4 4 2 2 2 2 3 3 4 4 2 2 2 3 1 1 1 1 1 1 1 1 0 0 0 1 0 6 6 7 0 4 5 5 0 2 3 3 0 2 2 2 0 0 0 0

Incandescent 60 0.2754.0 001 19.0 002 63.1 003 72.2 005 5.4 0001

1.9 0002 Fluorescent 15 0.23Single arrangement 20 0.37Without compensation 40 0.44

7.0 56 5.1 001

Fluorescent 15 0.23 3.5Single arrangement 20 0.25 4.5With compensation 40 0.3 4.5

7 54.0 56 81 7.0 001

High pressure mercury 250 2.13vapour 400 3.25Without compensation 700 5.4

5.7 0001 High pressure mercury 250 1.3 20vapour 400 2.1 25With compensation 700 3.6 40

06 3.5 0001 High pressure sodium 250 3vapour 400 4.4Without compensation 1000 10.3High pressure sodium 250 1.45 40vapour 400 2.5 45With compensation 1000 5.5 100Metal iodide 250 2,17 -Without compensation 400 3,48 -

- 90,6 007 - 7,8 0001 - 93,71 0002

Metal iodide 250 1,4 32With compensation 400 2,0 45

56 6,3 007 58 3,5 0001 001 6,01 0002

Fμ A W MCR MC0 MC1 MC2Types

59 62 62 35 40 40 17 20 20 11 13 13 7 8 8 3 4 4 1 1 1 79 88 98 49 57 61 41 48 51 26 30 32 12 14 16 49 61 77 38 48 61 38 48 61 25 31 39 9 11 14 6 6 8 4 4 5 2 2 3 2 2 2 11 11 14 7 7 9 4 4 5 3 3 3 4 4 5 3 3 4 1 1 2 10 10 12 6 6 7 3 3 3 4 4 5 3 3 3 1 1 2 1 1 1 1 1 1 7 7 9 5 5 6 3 3 3 2 2 2 0 1 1

70 77 50 60 25 30 17 20 10 12 5 6 2 3 126 155 78 110 66 93 41 58 19 27 94 111 74 87 74 87 47 56 17 21 10 12 6 8 4 5 3 3 18 22 11 14 6 8 4 5 7 9 5 6 2 2 16 20 9 11 4 5 7 9 4 6 2 3 2 2 1 1 11 16 8 11 4 6 3 4 2 2

RL CL00 CL01 CL02 CL25

Maximum number of lamps per phase at 230V

GE CONTACTOR SELECTION - LIGHTING CIRCUITS

The characteristics of the most usual lighting systems are as follows:

Incandescent lampsThe connection current in very high -of the order of 15 times- rated current. Although this is a very short duration, it is only taken into account in order for the contactor connection current not to be exceeded. The power factor is always maintained at 1.Fluorescent lampsThe connection current is slightly higher than rated current. The power factor is about 0.5. To improve up to 0.9, compensating capacitors can be used. In such cases, the connection power of the capacitor must be taken into account, the effect of which is appreciably greater on the smaller contactors.High pressure mercury vapour lampsThe connection current varies, depending on type, between 1.6 and 2 times the rated current and will hold for between 3 and 5 minutes.The power factor is of the order of 0.6 and this can be improved up to approximately unit value by means of compensating capacitors. In such cases, the connection power of the capacitor must be taken into account, the effect of which is appreciably greater on the smaller contactors.High pressure sodium vapour lampsThe connection current values varies, depending on type, between 1.3 and 1.6 times the rated current and will hold between 3 and 5 minutes.The power factor is of the order of 0.45 and this can be improved up to apporximately unit value by means of compensating capacitors. In such cases, the connection power of the capacitor must be taken into account, the effect of which is appreciably greater on the smaller contactors.

CONTACTORS FOR CONTROL LIGHTING CIRCUITS

SELECTION TABLE

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

Product Catalogue 2013 525

TEC

HN

ICA

L

15

77 85 122 156 191 222 264 284 60 66 73 95 116 133 160 170 30 33 36 47 58 66 79 84 20 22 24 31 38 44 53 56 12 12 14 19 23 26 31 33 6 6 7 9 11 13 16 17 3 3 3 4 5 7 8 8 177 224 237 355 390 434 496 553 125 139 147 221 243 270 309 344 105 118 124 186 204 227 260 289 66 74 78 116 127 142 163 181 30 34 36 54 59 66 76 85 119 134 149 191 232 273 312 347 92 103 115 148 180 212 243 270 92 103 115 148 180 212 243 270 59 66 74 95 115 136 155 173 23 23 29 37 45 53 60 67 14 15 18 27 30 33 36 42 9 10 12 18 20 22 24 28 5 6 7 11 12 13 14 17 4 4 5 8 9 9 10 12 31 27 33 49 55 60 66 77 25 17 20 31 34 37 41 48 16 10 12 18 20 22 24 28 10 7 8 12 13 15 16 19 10 11 13 19 21 24 26 30 7 7 9 13 15 16 18 20 3 3 4 6 6 7 7 9 16 25 30 44 49 54 59 69 14 14 17 26 29 31 34 40 7 6 8 12 13 14 16 18 12 12 12 19 21 23 25 29 8 8 8 12 13 14 16 18 4 4 4 7 7 8 9 10 3 3 3 5 5 6 6 7 2 2 2 2 3 3 3 4 21 21 21 32 36 39 43 50 15 15 15 23 25 28 30 35 8 8 8 13 14 15 17 19 6 6 6 8 9 10 11 13 3 3 3 4 5 5 6 7

CL03 CL04 CL45 CL06 CL07 CL08 CL09 CL10

410 555 820 1320 1550 1860 1860 246 333 490 790 930 1120 1120 122 165 240 390 460 550 550 81 110 165 260 300 370 370 48 66 95 155 185 220 220 24 33 50 80 90 110 110 12 16 25 40 45 55 55 988 1245 1770 2340 2740 3910 4890 614 774 1090 1460 1700 2430 3040 516 650 920 1220 1430 2045 2550 324 409 570 770 900 1280 1600 151 190 270 360 420 600 750 621 786 900 1240 1450 1740 1740 482 610 700 960 1120 1350 1350 482 610 700 960 1120 1350 1350 310 393 440 610 720 860 860 120 152 170 240 280 330 330 75 95 136 181 211 302 377 49 62 89 119 138 198 247 30 38 54 71 83 119 149 21 27 39 51 60 86 107 156 156 171 311 311 374 467 125 125 137 249 249 299 374 78 78 86 156 156 187 234 52 52 57 104 104 125 156 54 68 96 129 150 214 268 37 46 66 88 102 146 183 16 20 28 37 44 62 78 81 81 90 163 163 195 244 72 72 80 145 145 174 217 33 33 36 65 65 78 98 52 65 93 124 145 207 259 32 41 58 78 91 129 162 18 23 33 44 52 74 92 13 16 23 31 36 52 65 6 8 12 16 18 26 32 97 97 107 195 195 234 292 69 69 76 138 138 166 208 48 48 53 96 96 115 144 37 37 40 73 73 88 110 31 31 34 62 62 75 93

CK08C CK09 CK95 CK10 CK11 CK12 CK13CK75C

3332009966392010

7904904132591214963853852489660402417

109875436432912575123412615105

6848342622

Maximum number of lamps per phase at 230V

GE CONTACTOR SELECTION - LIGHTING CIRCUITS

DIAGRAMS

Single-phase circuitThe total number of lamps will be as shown in the table.

3-phase circuit,lamps delta-connectedThe total number of lamps will be as shown in the table, multiplied by 1.73 and distributed in three equal quantities.

3-phase circuit,lamps star-connectedThe total number of lamps will be as shown in the table, multiplied by 3 and distributed in three equal quantities.

IPD INDUSTRIAL PRODUCTS Phone: 1300 556 601 www.ipdgroup.com.au

526 Product Catalogue 2013

RELAY EQUIVALENT SELECTION CHART

PANASONIC RELAY & BASE IDEC (IPD) OMRON (National) FINDER

RJ Series Compact Miniature Relay 1 POLE Relay SPDT RJ1S G2R-1-SN AHN12 46.61 Base SJ1S-07L P2RF-05-E AHNA11P 97.01 2 POLE Relay DPDT RJ2S G2R-2-SN AHN22 46.52 Base SJ2S-07L P2RF-08-E AHNA21P 97.02

RU Series Miniature Rely 2 POLE Relay DPDT RU2S MY2 HC2/HJ2 55.32 Base SY4S-05E1G2 PYF08A-E HC2/HJ2-SFD-K 94.02 4 POLE Relay 4PDT RU4S MY4 HC4/HJ4 55.34 Base SY4S-05E1G2 PYF14A-E HC4/HJ4-SFD-K 94.04

RH Series General Purpose Relay 1 POLE Relay SPDT RH1B LY1 HL1 / HC1 - Base SH1B-05C PTF08A-E HL2-SFD-K / HC2-SFD-S - 2 POLE Relay DPDT RH2B LY2 HL2 / HC2 56.32 Base SH2B-05C PTF08A-E HL2-SFD-K / HC2-SFD-S 96.02 3 POLE Relay 3PDT RH3B LY3 HC3 62.33 Base SH3B-05C PTF11A HC3-SFD-K 92.03 4 POLE Relay 4PDT RH4B LY4 HC4 56.34 Base SH4B-05C PTF14A-E HC4-TSF-K 96.04

RR2KP Series Latching Relay 2 POLE Relay DPDT RR2KP G2AK - - Base SR3P-05C PYF14A(-E) - -

RF1V Series Safety Relay 4 POLE Relay RF1V - SFS2 / SFS3 - Base SF1V-4-07L - SFS4-SFD - 6 POLE Relay RF1V - SFS4 / SFS5 / SFS6 - Base SF1V-6-07L - SFS6-SFD -

RV8H Series Slim-Line Relay Interface Relay + Base RV8H G2RV - 38.51 Note. This is a guide only for relays that are similar in the market. Consider physical size and detailed specification before making a final decision.