RWM POWER FEED TO EACH COIL
S. Ramakrishnan
01/29/2010 2
RWM COILS
Existing Status The Six RWM coils are grouped in pairs Each Pair is fed from one sub-unit of SPA
which has 3 sub-units Each coil has two turns. Maximum of 3.33kA
Pulsed power feed. Three dedicated ckts. & power loops for
RWM Coils exist P13 circuit (EEF2-PSS-1A) is the DC link
01/29/2010 3
PROPOSED CHANGES
Proposed Change Each RWM coil is to be individually fed WP# 1513 was initiated to for the change One new Switching Power Amplifier (SPA2) has been
ordered with the specification revised to reflect all the modifications done by PPPL. In addition strict bifurcation of Power & Control sections has been specified.
SPA2 is similar to existing one with 3 sub-units Each sub-unit will switch up to 3333 Amps. ESW of SPA units - 6 seconds every 300 seconds.
Existing SPA (SPA1) will continue to be fed from the EEF2-PSS-1A, 1kV FCPC Transrex PS – See Sh. 1563
New SPA (SPA2) will be fed from the HF 1kV FCPC Transrex PS – See Sh. 1563B draft
01/29/2010 4
Additional Analog Coil Protection (ACP) (3) will be provided
Hardwired Control interfaces as required will be installed
Kirk Key system will be integrated with the rest of the System
Six grounding switches will be purchased and installed inside the NSTX test cell for the six RWM coils
PROPOSED CHANGES Contd.
01/29/2010 5
Change Implementation LOCATION New SPA to be located in the room adjacent to existing SPA
– Room 234 in FCPC 2nd floor. The new DGSs shall be located in Room 234 which has to be
cleared
Power cabling Changes FCPC to NSTX Test Cell)
– Presently 4-1/c 500mcm CABLE is installed for each of 3 ckts - 2-1/c 500mcm are in parallel in each leg.- Propose to release one conductor from each parallel
and use it for the new circuits FCPC
– Provide required cabling from new SPA and new SDS– Provide Jumper cables from existing SDS to new SDS.
NSTX Test Cell Reconnect the coils to the respective power feed inside the RWM box with appropriate links
01/29/2010 6
To provide an alternate means of shorting and grounding and to lockout and tagout the NSTX Resistive Wall Mode coils. This will be done inside NSTX Test Cell.
To provide an additional level of safety when the primary means of shorting and grounding may be compromised during maintenance and other testing.
To provide a visible means, within the test cell, to ensure that the RWM coils are shorted and grounded.
By design of the grounding switch enclosure is a means for personnel to lockout and tagout the RWM coil systems.
To remain consistent with the other NSTX coil systems regarding grounding and lockout tagout.
Provide Safety Grounding Switches for each of the six coils(BY Don McBride)
01/29/2010 7
RWM1
RWM2
RWM3
RWM4
RWM5
RWM6
B-RWM-01
01/29/2010 8
27
39
6 7 1/2 7 1/2 6
6 1
/2
6
4 1
/2
14
1/2
2 1/2 5 2 1/2 5 2 1/2 3 5/8
10
10
6 3
/4
1 2
PANEL IS 1/2"THICK GPO-3
1" X 1/8"BUS BAR
EACH AUXILIARY SWITCH IS CONNECTEDIN SERIES AND T ERMINATED HER E.PROTECT WIRING F ROM POTENTIALHIGH VOLTAGE TERMINALS.
RWM1 RWM2 RWM3
RWM4 RWM5 RWM6
THIS PANEL TO BE FITTED IN A HOFFMAN ENCLOSUREMODEL #A42N3013 WITH T-HANDLE, GROUNDING DEVICE,AND DOOR WINDOW KIT.
TB1GS-RWM6AUX.
GS-RWM5AUX.
GS-RWM4AUX.
GS-RWM3AUX.
GS-RWM2AUX.
GS-RWM1AUX.
ELECTRICAL SCHEMATIC
AUX. SWITCHES SHOWNW/ MAIN SWITCHES INCLOSED POSITION
TB1
2
1
Ground Switch Enclosure
01/29/2010 9
P1
M2
NSTX TEST CELL PLANSCALE 1/4" = 1'-0"
N5
FLOW SW. RACKS
B
6(I2
)
12(H3)
4(J2)
L
N404
N
N405
N405
N
L
5712 5704
5707
5703
5702 5701
15(J3
)
(C14)
N404 L404
WATER SKID
DN
.
CRANE H AU NCH
HEATING/COOLINGSKID
PD-345EL.105'0"
C
17(H 2)
5718
FOR DETAILED INFOR MATIONREFER TO D WG.D -EA3501
FI NISHED FLOORDEC K 9" ABOVE
945
4BA109A-3/4"NMFCTC -EE-408
4BA108A-3/4"N MFLLT-945
MGS
~12'-10"
P4
50
6000
41568TP-3" PVC
DN
EXISTIN G 7"D.HEATING PIPES
20081B-2"EL.108'-0"(SEE NOTE 6)
FI BER GLASS BARR IER TYP.
41575C A-3", ALUM. EL. 107'-7"
FI BER GLASS
TR AY L/N404
P451
12"
L
PCB-52
~12.0"
18(H2)
RWM4 41568U P-3" PVC
41568R P-3"PVC
T8 07 (TRAY)
1/C-500mcm CABLE
41568R P-3" PVC
B-RWM-01
NSTX Test Cell – Partial PlanDon McBride
01/29/2010 10
Picture showing proposed locationDon McBride
01/29/2010 11
SPA Input disconnect and ground switch (DGS) enclosure to be provided with a kirk key for accessing the cabinet. The enclosure can be accessed only if the SLD is vented.
Each of the three new output disconnect switches to be provided with kirk keys as follows: Kirk lock to access the Power component enclosure.
The power component enclosure for each switch can be accessed only if the SLD is vented.
A Kirk key will be released only if the switch is in the grounded position.
In order to gain access to the NSTX Test Cell etc. it is necessary to i) Vent the SLD and ii) All the six RWM-SDS shall be in the grounded position.
KIRK KEYSBy Don McBride
01/29/2010 12
PPPL will modify the existing Kirk key system by: Removing the existing transfer block located
on the 2nd floor FCPC and returning it to the Kirk Key Company.
The existing transfer will be replaced to accommodate the additional Kirk locks with a new transfer system mounted in an enclosure/transfer panel built by Kirk.
Estimated cost is about $2.5k.
Kirk Key Changes Contd.By Don McBride
01/29/2010 13
Perform PSCAD analysis of new scheme Power balance analysis of new scheme shows that DC link
SPA is adequate. It takes about 675Amps from the DC link during pulsing at rated current.
The 4/C cable from FCPC to NTC was reconnected with two conductors feeding one coil and the other two feeding another coil. Performance was satisfactory.
ANALYSIS/TESTS
01/29/2010 14
FOLLOWING TERMINALS ARE IN THE BOX B-RWM-1:
FROM FEED: SU1P, SU1N, SU2P, SU2N, SU3P, SU3N
TO COILS 1A, 1B; 2A, 2B;3A, 3B; 4A, 4B; 5A, 5B; 6A, 6B,
Circuit CONFIGURATION
SPA1-SU1 CKT WILL BE JUMPERED TO FEED RWM COIL 3
SPA1-SU2 CKT WILL BE JUMPERED TO FEED RWM COIL 2.
SPA1-SU3 CKT WILL BE JUMPERED TO FEED RWM COIL 1.
SPA2-SU1 CKT WILL BE JUMPERED TO FEED RWM COIL 6
SPA2-SU2 CKT WILL BE JUMPERED TO FEED RWM COIL 5.
SPA2-SU3 CKT WILL BE JUMPERED TO FEED RWM COIL 4.
Notes: Resistors (1kOhms 50W), across each coil is to be provided
RWM BOX CONNECTIONS
01/29/2010 15
FCPC 2nd Fl. NBPC
SPAProposed location
FutureNCSX Trays
NTC
Routing of cable from FCPC to NTC as installed
01/29/2010 16
Circuit - Parameters
Location of SPA
Cabling Length(500mcm- 600V)
# of condtrs used per pole
Cable Lead (R mOhm)
Cable Lead (L- uH)
Cable within Test Cell & other
50’ 1 2.5 11
FCPC 2nd Floor (North-East)
385’ 1 16.0 45
Total lead impedance 18.5 56
Total loop Impedance with coils 19.1 71
Each Coil: R = .6 mOhms; L= 16 uH)
Table
01/29/2010 17
CWD – 1563B DRAFT
01/29/2010 18
HCS interface will be provided as for SPA-1 A CICADA Rack will be installed inside Room 234
for SPA-2
SPA is self-protected ACP to be provided to protect each of new RWM
circuits Bob Marsala has designed units similar to existing
ACPs.
CONTROL & PROTECTION
01/29/2010 19
CONTROL CABLING: Provide control Cables as required within FCPC
and from FCPC to the Junction area WATER LINES:
Install water lines as required to SPA.
Control Cabling & Misc.