• Costeffective,threezonequadormho,phaseandgrounddistanceprotection
• CompleteIEC61850ProcessBussolutionprovidingresourceoptimizationandminimizingtotalP&Clifecyclecosts
• Programmablelogicforbuildingcustomizedpilotschemes• Reducedrelaytorelaywiringandassociatedinstallation
coststhroughhigh-speedinter-relaycommunications• EmbeddedIEC61850Protocol
• SimplifiedteleprotectioninterfaceswithDirectI/OcommunicationshardwareforTransferTripandcustombuiltPilot-Aideddistanceschemes
• RobustnetworksecurityenablingCriticalInfrastructureProtectionthroughusercommandlogging,anddualpermissionaccesscontrol
• Applicationflexibility-MultipleI/Ooptions,programmablelogic(FlexLogic™)
• Ambienttemperaturemonitoringwithalarmingwhenoutsidetemperatureexceedsupperthresholds
• Overheadsub-transmissionlinesandundergroundcablesincludingseriescompensatedlines.
• Circuitsrequiringthree-poleautoreclosingandindependentsynchrochecksupervision
• Circuitswithin-zonepowertransformers• SecureapplicationwithCapacitively-CoupledVoltage
Transformers(CCVTs)• Backupprotectionforgenerators,transformersandreactors
Protection and Control• Phasedistance(threezones)withindependentcompensation
settingsforin-zonepowertransformers• Grounddistance(threezones)withindependentselfand
mutualzerosequencecompensation• Out-of-steptrippingandpowerswingblocking• Linepickup• Directionalovercurrent:Phase,neutralandnegativesequence• Synchronismcheck• Four-shotauto-recloser• VTfusefailuredetector• CustomizeprotectionandcontrolfunctionswithFlexLogic™,
FlexCurves™,andFlexElements™
D30Line DisTanCe
ProTeCTion sysTem
Costeffectivehigh-speed,primaryandbackupdistanceprotection
FeaTures
aPPLiCaTions
Key BeneFiTs
• Metering-current,voltage,power,energy,frequency• Oscillography–analoganddigitalparametersat
64samples/cycle• EventRecorder-1024timetaggedeventswith0.5msscanof
digitalinputs• DataLogger-16channelswithsamplingrateupto
1sample/cycle• SettingSecurityAuditTrailfortrackingchangestoD30
configuration
monitoring and metering
Communications• Networkinginterfaces–100MbitFiberOpticEthernet,RS485,
RS232,RS422,G.703,C37.94• MultipleProtocols-IEC61850,DNP3.0Level2,ModbusRTU,
ModbusTCP/IP,IEC60870-5-104,EthernetGlobalData(EGD)• DirectI/O–securehigh-speedexchangeofdatabetween
URsforDirectTransferTripandPilot-aideddistanceschemes• EmbeddedManagedEthernetSwitchwith4-100MbitFiber
opticportsand2copperports
enerVista™ software• GraphicalLogicDesignerandLogicMonitortosimplify
designingandtestingprocedures• Documentandsoftwarearchivingtoolsettoensure
referencematerialanddeviceutilitiesareup-to-date• EnerVista™Integratorprovidingeasyintegrationofdatain
theD30intoneworexistingmonitoringandcontrolsystems
• Robustcommunicationswithupto8HardFiberBricks• SeamlessintegrationwithexistingD30functions• Redundantarchitecturefordependabilityandsecurity
ieC 61850 Process Bus interface
www.Gemultilin.com190
D30Line Distance Protection systemTr
ansm
issi
on L
ine
Prot
ectio
n
suitfordifferentpowersystemconditions.Theadvancedcomparatorbaseddistanceelements provide utmost security,sensitivity and selectivity for differenttypes of faults. Superior digital filteringtechniques provide secure and optimumreach accuracy even under worst-case CVT transients. Secure directionaldiscriminationisachievedbyusingpositivesequence memory voltage polarizationproviding reliable directionality forworst-caseclose-in faults.Anadditionalvoltagemonitoringfunctionprovidesextrasecurityto the distance element, which can beusedtoblockthedistanceelementsundervoltagesourcefusefailureconditions.
Protection and ControlThe D30 is a cost effective distanceprotection relay intended for protectingsub-transmission lines and undergroundcables of different voltage levels. Partof the Universal Relay family, the D30comeswithavarietyof versatile featurestruly integrating protection, monitoring,metering, communication and control inoneeasy-to-usedevice.TheUniversalRelayfamily offers higher degree ofmodularityin its design and functionality providingsuperior performance in protection andcontrolmeetingthetoughestrequirementsofthemarketplace.
Distance Protection
The core of theD30 relay is the distancefunction providing high degree ofsensitivity and selectivity for all types offaults. The D30 comes with three zonesof phase distance and ground distanceproviding the user maximum flexibility tocater for different applications, includingprimary sub-transmission line protectionand back-up protection for busbars, EHVand HV transmission lines, generators,transformers and reactors. The relaycan be applied to power systems withdifferentearthingconditions,lineswithin-zone transformers or tapped transformerfeeders, and overhead lines with seriescompensation. Each zone element forthe phase and ground distance canbe independently set as Quad or Mhocharacteristics with the flexibility ofdesigningdifferentcharacteristicshapesto
in-Zone Transformer Compensation
Phase distance elements in the D30can be used to detect faults throughdifferent types of three-phase wye/deltatransformers, allowing application of theD30 forbackupprotectionongenerators.VTsandCTscanbeinstalledindependentlyon either side of the power transformer.The relay automatically compensates fortransformer connections, to guaranteeaccuratereachforanytypeoffault.
Load encroachment
The load encroachment feature offersdiscrimination between line loading andfault conditions, especially for long lines
50N 51N 67N/G 21G
59P
27P
59N
52
79
50P 50_2 51P 51_2 21P 67P 67_2 68
59X
78
27X
50G 51G
50DD
Monitoring
D30 Line Distance Protection System
CLOSE TRIP
25
TransducerInputsMetering
DEVICENUMBER
21G21P2527P27X50DD50G50N50P50_251G51N51P
Ground DistancePhase DistanceSynchrocheckPhase UndervoltageAuxiliary UndervoltageCurrent Disturbance DetectorGround Instantaneous OvercurrentNeutral Instantaneous OvercurrentPhase Instantaneous OvercurrentNegative Sequence Instantaneous OvercurrentGround Time OvercurrentNeutral Time OvercurrentPhase Time Overcurrent
FUNCTION
ANSI DEVICE NUMBERS AND FUNCTIONS
DEVICENUMBER
51_25259N59P59X59_267N67P67_2687879
Negative Sequence Time OvercurrentAC Circuit BreakerNeutral OvervoltagePhase OvervoltageAuxiliary OvervoltageNegative Sequence OvervoltageNeutral Directional OvercurrentPhase Directional OvercurrentNegative Sequence Directional OvercurrentPower Swing BlockingOut-of-Step TrippingAutomatic Recloser
FUNCTION
VTFF
Functional Block DiagramDeviceNumber Function21G GroundDistance21P PhaseDistance25 SynchronismCheck27P PhaseUndervoltage27X AuxiliaryUndervoltage50DD CurrentDisturbanceDetector50G GroundInstantaneousOvercurrent50N NeutralInstantaneousOvercurrent50P PhaseInstantaneousOvercurrent50_2 NegativeSequenceInstantaneousOvercurrent51G GroundTimeOvercurrent51N NeutralTimeOvercurrent51P PhaseTimeOvercurrent51_2 NegativeSequenceTimeOvercurrent52 ACCircuitBreaker59N NeutralOvervoltage59P PhaseOvervoltage59X AuxiliaryOvervoltage59_2 NegativeSequenceOvervoltage67N NeutralDirectionalOvercurrent67P PhaseDirectionalOvercurrent67_2 NegativeSequenceDirectionalOvercurrent68 PowerSwingBlocking78 Out-of-StepTripping79 AutomaticRecloser
ANSIDeviceNumbers&Functions
The D30 is the single point for protection, control, metering, and monitoring in one integrated device that can be easily connected directly to HMI or SCADA monitoring and control systems.
D30 - Protection, metering, monitoring and Control
www.Gemultilin.com 191
D30Line Distance Protection system
Tran
smis
sion
Lin
e Pr
otec
tion
under heavy loads by supervising thedistance elements or any overcurrentelement. This preventsunwanted trippingunderheavy loadconditionsandenablesoptimum operation of the line whilemeeting regulatory requirements for lineloading.
Fault Locator
The integrated fault locator providesdistance to fault in km or miles. Parallelline zero-sequence current compensationand load current compensation enablestheD30toprovideimprovedaccuracyforfaultdistancemeasurement.
Line Pickup (switch-on-to-Fault)
TheLinePickupfeatureusesacombinationof undercurrent and undervoltage to
identifyalinethathasbeende-energized(line end open). Three instantaneousovercurrentelementsareusedto identifya previously de-energized line that hasbeenclosedontoafault.
Power swing Detection
Dynamic transients in the power systemduetoshort-circuits,circuit switching,orloadchangescantravelacrossthepowernetwork as power swings characterizedby fluctuatingcurrentsandvoltages.Thiscan result in unwanted tripping sincedistance elements can respond to thesepower swings as faults. The D30 swingdetection element provides both powerswing blocking and out-of-step trippingfunctions. The element measures thepositive sequence apparent impedanceandtracesitslocuswithrespecttoeitheratwoorthreestepuserselectablemhoorquadoperatingcharacteristics.
overvoltage and undervoltage Protection
Longlinesunderlightly loadedconditionsor no-load may experience voltagesexceeding the rated insulation voltageleveloftheline.Usethephaseovervoltageelementof theD30 to initiatea local tripaswell as a remote trip usingDirect I/O.The D30 also provides additional voltagefunctions including neutral overvoltage,negativesequenceovervoltageandphaseundervoltage
overcurrent Functions
The D30 provides overcurrent functionsforphase,neutralandgroundwhichcan
run parallel with distance protection orcan be programmed to provide primaryprotectionunderconditionswhendistanceelements are blocked during fuse-failureconditions.
autorecloser
TheD30providesmultishotautoreclosingfor 3 pole autoreclose on all types offaults with independently settable deadtime for each shot. Autoreclosing alsocan be dynamically blocked by userprogrammable logic. Four differentautoreclosemodesareavailableenablingtheusers toselect thereclosingmodetosuitspecificapplications.
synchronism Check
The D30 monitors voltage difference,phaseangledifferenceandslipfrequencyto ensure proper breaker closure as peruser defined settings. The D30 providesadditionalenhancementsinsynchronizingby checking dead source conditionsfor synchronism bypass under theseconditions.
ieC 61850 Process BusThe IEC 61850 Process Bus module isdesignedto interfacewiththeGEMultilinHardFiber System, allowing bi-directionalIEC 61850 fiber optic communications.The HardFiber System is designed tointegrate seamlessly with the existingUniversal Relay applications, includingprotection functions, FlexLogic, meteringandcommunications.
The GE Multilin HardFiber System offersthefollowingbenefits:
• CommunicatesusingopenstandardIEC61850messaging
• DrasticallyreducesP&Cdesign,installationandtestinglaborbyeliminatingindividualcopperterminations
• IntegrateswithexistingD30’sbyreplacingtraditionalCT/VTinputswithIEC61850ProcessBusmodule
• DoesnotintroducenewCyberSecurityconcerns
Visit the HardFiber System product pageon the GE Multilin web site for moredetails.
Z1 is looking through a transformer
Z1 & Z3are looking through a transformerZ3
Z3
Z1
Z1
Z1 looking through a transformer
Z1 & Z3 looking through a transformer
Distance relay quadrilateral characteristics supervised by Load Encroachment function
www.Gemultilin.com192
D30Line Distance Protection systemTr
ansm
issi
on L
ine
Prot
ectio
n
advanced automationTheD30incorporatesadvancedautomationfeatures including powerful FlexLogic™programmable logic, communication,andSCADA capabilities that far surpass whatis found in the average line protectionrelay used for subtransmission. The D30integratesseamlesslywithotherURrelaysforcompletesystemprotection.
FlexLogic™
FlexLogic™ is the powerful UR-platformprogramminglogicenginethatprovidestheability of creating customized protectionand control schemes thereby minimizingthe need, and the associated costs, ofauxiliarycomponentsandwiring.Using FlexLogic™, the D30 can beprogrammed to provide required trippinglogic alongwith custom scheme logic forbreaker control (including interlocking),transfer tripping schemes for remotebreakers and dynamic setting groupchanges.
scalable HardwareTheD30isavailablewithamultitudeofI/Oconfigurationstosuitthemostdemandingapplicationneeds.Theexpandablemodulardesign allows for easy configuration andfutureupgrades.
• Flexible,modularI/Ocoveringabroadrangeofinputsignalsandtrippingschemes
• Typesofdigitaloutputsincludetrip-ratedForm-AandSolidStateRelay(SSR)mechanicallylatching,andForm-Coutputs
• Form-AandSSRoutputsavailablewithoptionalcircuitcontinuitymonitoringandcurrentdetectiontoverifycontinuityandhealthoftheassociatedcircuitry
• Mechanicallylatchingoutputscanbeusedtodevelopsecureinterlockingapplicationsandreplaceelectromechanicallockoutrelays
monitoring and meteringTheD30 includeshighaccuracymeteringand recording for all AC signals. Voltage,current,andpowermeteringarebuiltintothe relay as a standard feature. Current
and voltage parameters are availableas total RMS magnitude, and asfundamental frequency magnitude andangle.
Fault and Disturbance recording
The advanced disturbance and eventrecording features within the D30 cansignificantly reduce the time needed forpostmortem analysis of power systemeventsandcreationof regulatory reports.Recordingfunctionsinclude:
• SequenceofEvent(SOE)-1024timestampedevents
• Oscillography,
-64digital&upto40Analogchannels
• DataLogger,disturbancerecording–16channelsupto1sample/cycle/channel
• FaultReports-Powerfulsummaryreportofpre-faultandfaultvalues
The very high sampling rate and largeamount of storage space available fordata recording in the D30 can eliminatethe need for installing costly standalonerecordingequipment.
advanced Device Health Diagnostics
The D30 performs comprehensive devicehealthdiagnostic testsduring startupandcontinuously at runtime to test its ownmajorfunctionsandcriticalhardware.Thesediagnostictestsmonitorforconditionsthatcould impact security and availability ofprotection, and present device status viaSCADA communications and front paneldisplay. Providing continuous monitoringandearlydetectionofpossibleissueshelpsimprovesystemuptime.
• Comprehensivedevicehealthdiagnosticperformedduringstartup
• MonitorstheCT/VTinputcircuitrytovalidatetheintegrityofallsignals
CommunicationsThe D30 provides advanced commun-ications technologies for remotedataandengineering access, making it easy andflexible touseand integrate intonewandexisting infrastructures. Direct support forfiberopticEthernetprovideshigh-bandwidthcommunications allowing for low-latencycontrols and high-speed file transfers ofrelay fault and event record information.The available redundant Ethernet optionand the embedded managed Ethernet
Custom Programmable Logic Designer
FlexLogicTM allows customizing the D30 for custom protection, control and automation allowing users to build line protection schemes and applications for their equipment.
www.Gemultilin.com 193
D30Line Distance Protection system
Tran
smis
sion
Lin
e Pr
otec
tion
switchprovidethemeansofcreatingfaulttolerant communication architectures inan easy, cost-effective manner withouttheneed for intermediarycommunicationhardware.
TheD30supportsthemostpopularindustrystandard protocols enabling easy, directintegrationintoDCSandSCADAsystems.
• IEC61850
• DNP3.0
• IEC60870-5-104
• ModbusRTU,ModbusTCP/IP
interoperability with embedded ieC61850
Use the D30 with integrated IEC61850to lower costs associated with lineprotection, control and automation. GEMultilin’s leadership in IEC61850 comesfrom thousands of installed devices andfollows on seven years of developmentexperiencewithUCA2.0.
• ReplaceexpensivecopperwiringbetweendeviceswithdirecttransferofdatausingGOOSEmessaging
• ConfiguresystemsbasedonIEC61850andalsomonitorandtroubleshoottheminreal-timewithEnerVista™ViewpointEngineer
• IntegrateGEMultilinIEDsandgenericIEC61850-compliantdevicesseamlesslyinEnerVista™ViewpointMonitoring
Direct i/o messaging
DirectI/Oallowsforsharingofhigh-speeddigital information between multiple URrelaysviadirectback-to-backconnectionsor multiplexed through a standard DS0multiplexer channel bank. Regardless oftheconnectionmethod,DirectI/Oprovidescontinuous real-time channel monitoringthat supplies diagnostics information onchannelhealth.Direct I/Oprovides superior relay-to-relaycommunications that can be used inadvanced interlocking, and other specialprotectionschemes.
• Communicationwithupto16URrelaysinsingleorredundantringsrather
thanstrictlylimitedtosimplisticpoint-to-pointconfigurationsbetweentwodevices
• ConnecttostandardDS0channelbanksthroughstandardRS422,G.703orIEEEC37.94interfacesorviadirectfiberopticconnections
• Noexternalorhandheldtesterrequiredtoprovidechanneldiagnosticinformation
multi-Language
TheD30supportsEnglish,French,Russian,andChineselanguagesonthefrontpanel,EnerVista™ setup software, and productmanual.EasilyswitchbetweenEnglishandanadditionallanguageonthelocaldisplayswithoutuploadingnewfirmware.
enerVistaTm softwareThe EnerVista™ Suite is an industry-leading set of software programs thatsimplifies every aspect of using the D30relay. The EnerVista™ suite provides allthe tools to monitor the status of theprotected asset, maintain the relay, andintegrateinformationmeasuredbytheD30into DCS or SCADA monitoring systems.Convenient COMTRADE and Sequence ofEvents viewersarean integralpartof theUR Setup software included with every
UR relay, to carry out postmortem eventanalysis to ensure proper protectionsystemoperation.
enerVista™ Launchpad
EnerVista™ Launchpad is a powerfulsoftware package that provides userswith all of the setup and support toolsneededforconfiguringandmaintainingGEMultilinproducts.ThesetupsoftwarewithinLaunchpad allows configuring devices inreal-time by communicating using serial,Ethernet,ormodemconnections,orofflineby creating setting files to be sent todevicesatalatertime.
Included in Launchpad is a documentarchiving and management systemthat ensures critical documentation isup-to-date and available when needed.Documentsmadeavailableinclude:
• Manuals
• ApplicationNotes
• GuideformSpecifications
• Brochures
• WiringDiagrams
• FAQ’s
• ServiceBulletins
substation monitoring
Monitor the status of your substation using the easy to use Viewpoint Monitoring HMI
www.Gemultilin.com194
D30Line Distance Protection systemTr
ansm
issi
on L
ine
Prot
ectio
n
Viewpoint monitoring
Viewpoint Monitoring is a simple-to-useand full-featured monitoring and datarecording software package for smallsystems. ViewpointMonitoring provides acompleteHMIpackagewith the followingfunctionality:
• Plug-&-PlayDeviceMonitoring
• SystemSingle-LineMonitoring&Control
• AnnunciatorAlarmScreens
• TrendingReports
• AutomaticEventRetrieval
• AutomaticWaveformRetrieval
Viewpoint engineer
Viewpoint Engineer is a set of powerfultools thatwillallowtheconfigurationandtesting of UR relays at a system levelin an easy-to-use graphical drag-and-drop environment. Viewpoint Engineerprovides the following configuration andcommissioningutilities:
• GraphicalLogicDesigner
• GraphicalSystemDesigner
• GraphicalLogicMonitor
• GraphicalSystemMonitor
Viewpoint maintenance
ViewpointMaintenanceprovidestoolsthatwillcreatereportsontheoperatingstatusoftherelay,simplifythestepstodownloadfaultandeventdata,andreducetheworkrequired for cyber-security complianceaudits. Tools available in ViewpointMaintenanceinclude:
• SettingsSecurityAuditReport
• DeviceHealthReport
• SingleClickFaultDataRetrieval
enerVista™ integrator
EnerVista™IntegratorisatoolkitthatallowsseamlessintegrationofGEMultilindevicesinto new or existing automation systems.IncludedinEnerVista™Integratoris:
• OPC/DDEServer
• GEMultilinDrivers
• AutomaticEventRetrieval
• AutomaticWaveformRetrieval
user interfaceThe D30 front panel provides extensivelocal HMI capabilities. The local displayis used formonitoring, statusmessaging,fault diagnosis, and device configuration.Userconfigurablemessagesthatcombinetextwithlivedata,canbedisplayedwhenuser-definedconditionsaremet.
Analyze transmission line faults using system voltage, current and appropriate pickup flags that are measured & recorded up to 64 samples/cycle.
Graphically view zone settings for ground & phase distance elements for the selected zones.
Power system TroubleshootingTheD30containsmanytoolsandreportsthatsimplifyandreducetheamountoftimerequiredfortroubleshootingpowersystemevents.
Record the operation of the internal D30 elements and external connected devices with 1ms time-stamped accuracy to identify the Sequence of Operation of station devices during faults and disturbances.
www.Gemultilin.com 195
D30Line Distance Protection system
Tran
smis
sion
Lin
e Pr
otec
tion
Typical Wiring
configurations.
D30-H00-HCL-F8F-H6H-m6K-P6C-u6D-W6a
TC 1
DC
1
PowerSupply
9
CPU
8
CT/VT
6
Inputs/outputs
6Inputs/outputs
*
6Inputs/outputs
*
6Inputs/outputs
*
6Inputs/outputs
*
JU MX LW KV BHT DN GS FPR
A B C
M7a
M1a
M2b
M7c
M1c
M7b
M1b
M8cM8b
M2c
M8a
M2a
M4a
M5b
M4c
M6b
M3bM3a
M6a
M4b
M5c
M5a
M3c
M6c
6K M1
M5
M2
M6
M3
M7
M4
M8
CRITICALFAILURE
OUTPUT
CONTROLPOWER
HILO
1
FILTERSURGE
B3a
B1b
B8a
B6b
B8b
B6a
B3b
B1aB2b
B5b
PERSONALCOMPUTER
UR COMPUTER
1
TXD RXD
RXD TXD
SGND SGND
1 832
207645
22
CONNECTORCONNECTOR
2 23 34 45 56 67 78 89 9
(front)
RS-232
DB-9
H8a
H7b
H7a
H8c
H7c
SURGEH8b
6H
H1b
H2b
H3b
H4b
H5b
H6b
H1a
H2a
H3a
H4a
H5a
H6a
H1c
H2c
H3c
H4c
H5c
H6c
H1
H5
H2
H6
H3
H4
I
V
I
V
I
V
I
V
I
V
I
V
CURRENTPOLARIZATION
SOURCE
A
B
C
5252
6C
P1
P5
P2
P6
P3
P7
P4
P8
P7a
P1a
P2b
P7c
P1c
P7b
P1b
P8cP8b
P2c
P8a
P2a
P4a
P5b
P4c
P6b
P3bP3a
P6a
P4b
P5c
P5a
P3c
P6cU6a
U8a
U5b
U7b
U5a
U7a
U6c
U8c
U5c
U7c
SURGE
U1a
U8b
U4c
U2c
U3aU3c
U1c
U3b
U1b
U4a
U2a
6D
SURGE
W6a
W8a
W5b
W7b
W8b
W5a
W7a
W6c
W8c
W5c
W7c
6AW1
W2
W3
W4
W1a
W2b
W1cW1b
W2c
W2a
W4a
W4c
W3bW3a
W4b
W3c
I
V
I
V
FFFFFFFF
8c8a5a 5c 7c6a 7a6c
VX
VA VB
VC VX
VA VB
VC
1c 4a
FFFFFFFFFFFF
3c2c 4c1a 4b1b 2a 3a2b 3b
IA IB IC IGIA5
IA1
IB5
IC5
IG5
IB1
IC1
IG1
D30
Minimum
PROVIDED
TC 2
Multilin
com
10BaseFL
10BaseFL
10BaseT
D1aD2a
D4bD3a
D4a IRIG-BInput
IRIG-BOutput
COM1
RS485
ALTERNATE
NORMAL
Tx2Rx2
Tx1Rx1
BNC
BNC
FibreOptic
*
RemoteDevice
Shielded
Co-axial
Co-axial
www.Gemultilin.com196
D30Line Distance Protection systemTr
ansm
issi
on L
ine
Prot
ectio
n
D30 - * ** - H * * - F ** - H ** - m ** - P ** - u ** - W** For Full sized Horizontal mountBaseUnit D30 BaseUnitCPU E RS485+RS485(IEC61850optionnotavailable) G RS485+Multi-modeST10BaseF H RS485+Mutli-modeSTRedundant10BaseF J RS485+Multi-modeST100BaseFX K RS485+Multi-modeSTRedundant100BaseFX N RS485+10/100BaseT S RS485+6port,100Mbps,ManagedEthernetSwitchSoftwareOptions 00 NoSoftwareOptions 03 IEC61850Mount H Horizontal(19"rack)-Standard A Horizontal(19"rack)-HarshChemicalEnvironmentOption V Vertical(3/4size)-Standard B Vertical(3/4size)-HarshChemicalEnvironmentOptionUserInterface K EnhancedEnglishFrontPanel L EnhancedEnglishFrontPanelwithUser-ProgrammablePushbuttons M EnhancedFrenchFrontPanel N EnhancedFrenchFrontPanelwithUser-ProgrammablePushbuttons Q EnhancedRussianFrontPanel T EnhancedRussianFrontPanelwithUser-ProgrammablePushbuttons U EnhancedChineseFrontPanel V EnhancedChineseFrontPanelwithUser-ProgrammablePushbuttons F VerticalFrontPanelwithEnglishdisplayPowerSupply H 125/250VAC/DC H RH 125/250VAC/DCwithredundant125/250VAC/DCpowersupply L 24-48V(DConly)CT/VTDSP 8L Standard4CT/4VTw/enhanceddiagnostics 8M SensitiveGround 4CT/4VTw/enhanceddiagnosticsIEC61850ProcessBus 81 8PortIEC61850ProcessBusModuleDigitalI/O XX XX XX XX XX Nomodule 4A 4A 4A 4A 4A 4SolidState(NoMonitoring)MOSFETOutputs 4C 4C 4C 4C 4C 4SolidState(Currentw/optVoltage)MOSFETOutputs 4D 4D 4D 4D 4D 16DigitalInputswithAuto-Burnish 4L 4L 4L 4L 4L 14Form-A(NoMonitoring)LatchableOutputs 67 67 67 67 67 8Form-A(NoMonitoring)Outputs 6C 6C 6C 6C 6C 8Form-COutputs 6D 6D 6D 6D 6D 16DigitalInputs 6E 6E 6E 6E 6E 4Form-COutputs,8DigitalInputs 6F 6F 6F 6F 6F 8FastForm-COutputs 6K 6K 6K 6K 6K 4Form-C&4FastForm-COutputs 6L 6L 6L 6L 6L 2Form-A(Currentw/optVoltage)&2Form-COutputs,8DigitalInputs 6M 6M 6M 6M 6M 2Form-A(Currentw/optVoltage)&4Form-COutputs,4DigitalInputs 6N 6N 6N 6N 6N 4Form-A(Currentw/optVoltage)Outputs,8DigitalInputs 6P 6P 6P 6P 6P 6Form-A(Currentw/optVoltage)Outputs,4DigitalInputs 6R 6R 6R 6R 6R 2Form-A(NoMonitoring)&2Form-COutputs,8DigitalInputs 6S 6S 6S 6S 6S 2Form-A(NoMonitoring)&4Form-COutputs,4DigitalInputs 6T 6T 6T 6T 6T 4Form-A(NoMonitoring)Outputs,8DigitalInputs 6U 6U 6U 6U 6U 6Form-A(NoMonitoring)Outputs,4DigitalInputs 6V 6V 6V 6V 6V 2Form-A(Curw/optVolt)1Form-COutput,2LatchingOutputs,8DigitalInputsTransducerI/O 5A 5A 5A 5A 5A 4dcmAInputs,4dcmAOutputs 5F 5F 5F 5F 5F 8dcmAInputsInter-RelayCommunications 7A 820nm,multi-mode,LED,1Channel 7B 1300nm,multi-mode,LED,1Channel 7C 1300nm,single-mode,ELED,1Channel 7H 820nm,multi-mode,LED,2Channels 7I 1300nm,multi-mode,LED,2Channels 7J 1300nm,single-mode,ELED,2Channels 7S G.703,2Channels 7W RS422,2Channels 73 1550nm,single-mode,LASER,2Channels 77 IEEEC37.94,820nm,multi-mode,LED,2Channel 2B IEEEC37.94SM,1300nmSinglemode,ELED,2ChannelSinglemode 2S 6port,100Mbps,ManagedEthernetSwitch,HI(125/250VAC/DC) 2T 6port,100Mbps,ManagedEthernetSwitch,LO(24-48Vdc)
ordering
ordering note: ToviewthelatestoptionsavailablefortheD30,ortoordertheURClassicFrontPanel,pleasevisitouronlinestoreformoredetails.
• URApplicationsILearningCD TRCD-URA1-C-S-1
• MultilinkEthernetSwitch ML2400-F-HI-HI-A2-A2-A6-G1
• ViewpointEngineer VPE-1
• ViewpointMaintenance VPM-1
• ViewpointMonitoringIEC61850 VP-1-61850
accessories for the D30 • ViewGuideformspecifications
• Downloadtheinstructionmanual
• ReviewapplicationsNotesandsupportdocuments