Distance protection Info - 1
EV S V13/ Claus/ 23.08.00
SIPROTEC 4Distance Protection
7SA522 and 7SA6 Productmanager Distance Protection
Michael Claus
EV S V 13 Nürnberg H
Phone: +49 911 433 8261
Fax: +49 911 433 8301
Email: [email protected]
Distance protection Info - 2
EV S V13/ Claus/ 23.08.00
SIPROTEC 4 -What it means
SIPROTEC 4
is a family of numerical
Protection, Control and Automation Devices
from
Distance protection Info - 3
EV S V13/ Claus/ 23.08.00
7SA5227SA6
Experience
7SA510
7SA5117SA513
Requi
rem
ents
SIPROTEC 4Software System
System
SIPROTEC 4Hardware Platform
Variability
Distance protection: Past and Present
Distance protection Info - 4
EV S V13/ Claus/ 23.08.00
SIPROTEC 4Distance Protection 7SA522 and 7SA6
7SA522 + 7SA6
One family of distance
protection for all voltage
applications
Distance protection Info - 5
EV S V13/ Claus/ 23.08.00
SIPROTEC 4 Distance protection
7SA61 + 7SA522 Protection 4-line display MV, HV and EHV
7SA612 + 7SA5227SA611 + 7SA5227SA610
7SA63 Protection + local control integrated graphic display mainly MV
7SA6327SA631
7SA64 Protection + local control detached control panel mainly MV
7SA6427SA641All core functions are available in all the housing versions
Distance protection Info - 6
EV S V13/ Claus/ 23.08.0017.10.97en513all7
ANSI-No.
21, 21N
68
FL
SIPROTEC 4 Distance Protection, Scope of functions (1)
Distance Protection full scheme measurement with sophisticated loop selection
fast three phase and single phase tripping
with/without parallel line compensation
special filtering for CVT transients
special algorithm for detection and compensation of CT saturation Low demand on CT specification
Power swing blocking/out-of-step tripping
Fault Locator with/without parallel line compensation
Distance protection Info - 7
EV S V13/ Claus/ 23.08.0017.10.97en513all8
85-21
50N, 51N, 67N
85-67N
WI
50, 5150N-2, 51N-2
ANSI-No.
SIPROTEC 4 Distance Protection, Scope of functions (2)
Universal teleprotection interface (PUTT, POTT, Blocking, Unblocking, DTT...)
High resistance earth fault protection for earthed systems
Teleprotection interface for earth fault protection (Directional comparison, Blocking, Unblocking)
Weak infeed protection(Echo and Trip)
Overcurrent protection DMTL/IDMTL as parallel or emergency function
Distance protection Info - 8
EV S V13/ Claus/ 23.08.00
ANSI-No.
59, 27 1)
50HS
50-STUB
79
25
50BF
49 2)
1) 7SA522: Overvoltage, 7SA6: Over- and Undervoltage
2) available only in 7SA6
SIPROTEC 4 Distance Protection, Scope of functions (3)
Voltage protection 1)
Fast tripping with switch-onto-fault condition (12 ms)
STUB Bus Overcurrent protection
Single and three pole multishot automatic reclosure
Synchro-check
Circuit-breaker failure protection
Thermal overload protection 2)
Earth fault detection in compensated/isolated systems 2)
Distance protection Info - 9
EV S V13/ Claus/ 23.08.00
ANSI-No.
74TC
86
FR
47
* available approx. 1st Q/01
SIPROTEC 4 Distance Protection, Scope of functions (4)
Trip Circuit Supervision
Lock Out
Oscillographic Fault Recording (total length 15 s)
Voltage Phase Sequence
Interfaces Time synchronization (IRIG-B, DCF77)
User interface#1 (on the front for DIGSI 4)
User-(Service-)interface #2 (on the rear, DIGSI 4/Modem)
System interface (IEC60870-5-103/Profibus FMS/others)
Remote relay interfaces #1 (planned for teleprotection*)
1) Remote relay interfaces #2 (planned for teleprotection*)
1) available only in 7SA522
Distance protection Info - 10
EV S V13/ Claus/ 23.08.00
Operating system monitoring Auxiliary voltage failure
Measured value detection
Buffer battery
Hardware–Watchdog
Software–Watchdog
Working memory
Program memory
Parameter memory
Sampling frequency
1/5 A–setting
Calibration data
Earth current transformer sensitive/normal
Modules (I/O Boards)
SIPROTEC 4 Distance Protection, Monitoring
Plausibility monitoring Current sum
Current symmetry
Open conductor
Fuse Failure
1- / 2-pole failures
3-pole failures
Voltage sum
Voltage symmetry
Voltage phase rotation
!
new
Distance protection Info - 12
EV S V13/ Claus/ 23.08.00
Quadrilateral Characteristic
5 Zones (time delayed) optionally:
- Forward- Reverse- Non-directional
Prevention of load encroachment
Dependant Zone Z1b for Teleprotection andAuto-recloser
X
R
forwards
forwards
reverse
reverse
LoadLoad
Z1
Z2
Z4
Z3
Z1B
Z5
Line
SIPROTEC 4 Distance Protection
Distance protection Info - 13
EV S V13/ Claus/ 23.08.00
0
5
10
15
20
25
30
35
40
45
50
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
% of zone 1 setting
trip
pin
g t
ime
(m
s)
Relay S
SIPROTEC 4, 7SA522 + 7SA6
Relay E
Relay A
SIPROTEC 4Distance Protection: Overall Trip Time Curves at SIR = 30
G VF
ZLZQ
E
If
distance relay
Distance protection Info - 14
EV S V13/ Claus/ 23.08.00
+ 2 . 0 0
+ 1 . 6 0
+ 1 . 2 0
+ 0 . 8 0
+ 0 . 4 0
+ 0 . 0 0
- 0 . 4 0
- 0 . 8 0
- 1 . 2 0
A
0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0
m s
E s t i m a t o r 2 ( n = 6 )
E s t i m a t o r 3 ( n = 8 )
E s t i m a t o r 4 ( n = 1 0 )
N o r m a l s t a g e 1( n = 2 1 )N o r m a l s t a g e 2( n = 2 6 )
N o r m a l s t a g e 3
j u m p d e t e c t i o n
E s t i m a t o r 5 ( n = 1 3 )
E s t i m a t o r 6 ( n = 1 5 )
Estimator 1 (n=5)
SIPROTEC 4 Distance Protection, Data window position, Adaptive Measuring Algorithm
Distance protection Info - 15
EV S V13/ Claus/ 23.08.00
SIPROTEC 4 Distance Protection Function: Difference 7SA522 - 7SA6
7SA522 for solid earthed systems quadrilateral and/or MHO characteristic
(MHO circle for specific markets, quadrilateral is preferred)
full market introduction: 1999
primary market outside continental Europe
7SA6 for systems with solid grounding or
reactance (compensated) / isolated treatment of system starpoint fault detection selectable as either I>, Z<, U/I and U/I/ Market introduction: Summer 2000
Primary market continental Europe
Distance protection Info - 16
EV S V13/ Claus/ 23.08.00
SIPROTEC 4 Distance Protection 7SA522
Mho Characteristic
5 Zones optionally:
- Forward- Reverse
Prevention of load encroachment
X
R
Z1
Z2
Z4
Z1B
Z5Line
Z3 (if revers)
Load Load
Dependant Zone Z1b for Teleprotection andAuto-recloser
Distance protection Info - 17
EV S V13/ Claus/ 23.08.00
SIPROTEC 4, Distance Protection Parallel-line compensation: connection and setting
Q1
Q3
Q5
Q7
Q2
Q4
Q6
Q8
IL1(A)
IL2(B)
IL3(C)
L1 (A)L2 (B)L3 (C)
52 Circuit breaker
Line
Busbar
52 Circuit breaker
Parallel line
I4
Distance protection Info - 18
EV S V13/ Claus/ 23.08.00
Patented power swing detection provides secure operation with swing frequencies of up to 6 Hz
t/s0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6iL1/A-4-20
t/s0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6iL2/A-20
t/s0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6iL3/A-202
t/s0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6uL1/V-500
t/s0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6uL2/V-50050
t/s0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6uL3/V-50050
t/s0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6DisTRIP3p Z1BmfRelay TRIPRelay PICKUPDis. reverseDis. forwardDis.T.SEND>DisTel Rec.Ch1Power Swing
Example:400 kV400 kmfPS 2 Hz3-pole fault
Distance protection Info - 19
EV S V13/ Claus/ 23.08.00
SIPROTEC 4 Distance Protection: Fault locator
Distance protection Info - 20
EV S V13/ Claus/ 23.08.00
Z1 Z1B
L1-E
L2-E
A B1 1
2 2
Z1Z1B
A1 trips single-phase in L1 with a phase-segregated L1-receive-signal Maximum of Selectivity
Note: 3 binary channels for both directions are requested or (in preparation) one serial link
SIPROTEC 4 Distance Protection: Phase segregated Teleprotection
Distance protection Info - 21
EV S V13/ Claus/ 23.08.00
SIPROTEC 4 Distance Protection: Teleprotection with three-terminal lines
Software provides teleprotection of three-terminal lines without additional logic
Distance protection Info - 22
EV S V13/ Claus/ 23.08.00
SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection
Earth (zero sequence) current protection, 4 stages 3 definite-time stages 1 inverse-time stage: IEC, logarithmic inverse or ANSI characteristic
this stage can also be used as a 4th definite-time stage Directional determination with 3V0 and/or Ipol of an earthed power
transformer Directional determination with V2 and I2 (negative sequence) Sensitive 3I0-measurement with a dynamic from 0.003 A to 100 x In Elimination of higher harmonics with special digital filters Inrush-stabilisation with I0/100Hz Teleprotection: Directional comparison, Blocking or Unblocking Operation with weak infeed trip and echo Instantaneous trip after switch-onto-fault
Distance protection Info - 23
EV S V13/ Claus/ 23.08.00
SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection
3I0
T
T3I0>>
3I0>
T3I0>
T3I0>>>
3I0>> 3I0>>>
Definite-time characteristic
Distance protection Info - 24
EV S V13/ Claus/ 23.08.00
SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection
0 5 10 15 20 25 30 350
1
2
3
4
5
6
7
8
9
10t
3I0 / 3I0p
Example: t = 5.8 - 1.35 ln(3I0 / 3I0p)
T3I0pmax (P3145)
T3I0p (P3144)
3I0p(P3140)
T3I0min(P3141)
3I0p Startpoint(P3154)
Tripping characteristic Logarithmic Inverse
Distance protection Info - 25
EV S V13/ Claus/ 23.08.00
SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection
IEC-characteristic:
normal inverse: Tp
IpI
st *
1
14.002.0
very inverse: Tp
IpIst *1
5.13
extremly inverse: Tp
IpI
st *
1
802
long time inverse: Tp
IpIst *1
120
ANSI-characteristic:
DB
IpI
Ast
N*
1
Inverseshort inverse very inverselong inverse extremly inversemoderately inverse definite inverse
Logarithmic-inverse characteristic:
PI
IPITPITst
03
03ln*03max03 for t>T3I0Pmin, otherwise: t[s]=T3I0Pmin
Distance protection Info - 26
EV S V13/ Claus/ 23.08.00
SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection
Inverse-time characteristic: IEC
3I0/Ip
T
Tp =1
b 200 a
Reset: b = 1.045 x 3I0/IP
Pickup: a = 1.1 x 3I0/IP
Distance protection Info - 27
EV S V13/ Claus/ 23.08.00
SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection
-160
-150
-140
-130
-120
-110
-100
-90
-80
-70
-60
-50
-40
-30
-20
-10
0
10
dB
0 1 2 3 4 5 6 7 8 9 10 11
f/fn
Filter characteristic for stages 3I0>>> and 3I0>>
Distance protection Info - 28
EV S V13/ Claus/ 23.08.00
SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection
Filter characteristic for stages 3I0> and Inverse time stage
-170
-160
-150
-140
-130
-120
-110
-100
-90
-80
-70
-60
-50
-40
-30
-20
-10
0
10dB
0 1 2 3 4 5 6 7 8 9 10 11
f/fn
Distance protection Info - 29
EV S V13/ Claus/ 23.08.00
SIPROTEC 4 Distance Protection: High Resistance Earth Fault Protection
Earth faultdirection
=
EF IE> Echo
3I0>>>EF>>> Trip
P
EFp Trip
Inrush-stabilisation
T(3I0/IN)
T
Tele-protection
T
SOTF
= &
&
3I0>>> Def. Time Stage
Inverse Time Stage
&
&
P
>EF>>> block
Direc. 3I0>>>
P Direc. 3I0p
>EFp block
P 3I0p
EF Fault Det.
>EF Trip rel.
3I0>> Def. Time Stage
3I0> Def. Time Stage
= Input signal(binary input)
P = Parameter = Output Signal(alarm, command)
P3146 AddTdelay
Distance protection Info - 30
EV S V13/ Claus/ 23.08.00
Z1(A)
T1BZ1B
A B
Z1(B)
Z1B(A)
Z1B(B)
&
&
&
&(A)T1BZ1B
(B)OR
OR
OR
OR
TS
Z1 orfurtherzones
trans-mit
re-ceive
TripTrip
re-ceive
trans-mit
Z1 orfurtherzones
TS
SIPROTEC 4 Distance Protection: Permissive overreach transfer trip (POTT)
TS
Distance protection Info - 31
EV S V13/ Claus/ 23.08.00
SIPROTEC 4 Distance ProtectionSTUB protection for 11/2-circuit breaker arrangement
Busbar A
fee
de
r 1
fee
de
r 2
stub fault
IA
IB
Ik = IA+IB line isolator 1
line isolator 2
CB(A)
CB(C)
CB(B)
Busbar B
Release of STUB-stage with open line isolator:
Distance protection Info - 32
EV S V13/ Claus/ 23.08.00
Auto-reclosure (AR)
ON
OFF2nd
dead timeT1-act
TRIP1-pole3-pole
1stdead time
RE-CLOSE
*RE-
CLOSE
T2-act
TRIP
tzone-delay
ADT = Reclosure, when AR at the remote end was successfulDLC = Reclosure only on dead lineRDT = Reduced dead time, if trip had occurred with zone extension
finalTRIP
*
SIPROTEC 4Distance Protection: Auto-reclosure
Distance protection Info - 33
EV S V13/ Claus/ 23.08.00
application examples functions(separately settable for AR and
- combination with internal or manual closing)external AR
- program selection via parameters:- activation also for manual closing synchro-check / U1 > U2 < /
(settable) U1 < U2 > / U1 < U2 < / overrule
- asynchronous switching (settable) - all programs separately settablevia binary inputs
- synchronous monitoring time, after whichthe closing will be blocked (settable)
parameters measurement
- voltages U<, U>, U - evaluation of the fundamental wave
- f synchronous switching (0.01 ... 0.03 Hz) - insensitive against harmonics
- f asynchronous switching (0.03 ... 1 Hz) - for dead line check all three phases are controlled
- (1° ... 60°)
16.10.97engersyn1
Synchronism-check
Distance protection Info - 34
EV S V13/ Claus/ 23.08.00
SIPROTEC 4 Distance Protection: Breaker failure protection
2 stages
Internal initiation and via binary inputs
Extremely short reset time: approx. 10ms
End-fault protection
Pole discrepancy supervision
Distance protection Info - 35
EV S V13/ Claus/ 23.08.00
SIPROTEC 4Distance Protection
with light
or electrical exchangeable upgradeable
7SA522
Distance protection Info - 37
EV S V13/ Claus/ 23.08.00
User friendly Operation
Safe operation,reduced training requirements
Fits all applications
System conceptSIPROTEC and SICAM
Flexible Functionality and Open Communication
One Family
SIPROTEC 4 -Distance Protection
Distance protection Info - 38
EV S V13/ Claus/ 23.08.00
Full Logic Functionalit
y Additional logicInterlockingMeasured values
processing
Log. IN 1
Log. IN 2
Log.IN3
Logic inputs from the matrix to CFC
Logic outputs to theconfiguration matrix
F1
F2
>1
CFC
Log.OUT1
Distance Protection 7SA522What makes these devices so attractive ?
Distance protection Info - 39
EV S V13/ Claus/ 23.08.00
Comprehensive measured
value processing
I1 :400.9A f:50.0HzU1:12.22kVP :+8.03MW cosQ :+2.64MVar
L1 402.1A Max450.1A L2 401.2A Max421.2AL3 401.0A Max431.4AE 00.0A
% IL UL-E UL-LL1 100.0 100.4 100.1L2 100.4 100.3 100.0L3 100.1 100.1 100.4
Distance Protection 7SA522What makes these devices so attractive ?
Distance protection Info - 40
EV S V13/ Claus/ 23.08.00
The easy handling
with DIGSI 4
Distance Protection 7SA522What makes these devices so attractive ?