Grounding Design of Kano Hydro Power Station(1x8MW+1x2MW) in Kano State of Nigeria
AUTHOR PANKAJ SACHDEVA,JOINT GROUP PRESIDENT,SKIPPER ELECTRICAL(I) LIMITED. M.L.SACHDEVA,FORMER CE,CEA AND SR. CONSULTANT,SKIPPER ELECTRICAL(I) LIMITED S.L.NARASIMHAN,FORMER EE,K.P.C,BANGALORE AND DIRECTOR(ELECTRICAL),BHEC
PVT. LTD
PRESENTED BY SOURAV GHOSH,ENGINEER AT SKIPPER ELECTRICAL(I) LIMITED
ABOUT M/S SKIPPER.
PRESENCE IN 50 COUNTRIES,MOSTLY EXPORT ORIENTD
MANUFACTURING PLANT : IN INDIA -3 NOS. BHIWADI IN NIGERIA – 2NOS LOGAS IN DUBAI - 1No
RANGE OF PRODUCT PRESNTLY UPTO 220KV SYSTEM & UPGRADING TO 400KV. POWER TRANSFORMER- UPTO 65MVA,220KV S/S CT,PT,ISOLATORS,CBs C&R PANELS, CAPACITOR,LT PANELS ETC.
PACKAGED S/S AND MOBILE SUBSTATION
PLANNING, DESIGN, ERECTION, TESTING & COMMISSIONING OF AIS and GIS
SCADA AND COMMUNICATION
NEW TRANSFORMER PLANT - UPTO 800KV TR.( Under Building) Railway Electrification
SYNOPSIS
THIS PAPER DEALS WITH GROUND MAT DESIGN OF POWER HOUSE AND SWITCHYARD WITH DIFFERENT SOIL RESISTIVITY VALUES AND DIFFERENT CALCULATED TOUCH AND STEP POTENTIALS WHICH IN SOME CASES EXCEED THE LIMIT VALUES
SUGGESTIONS ON REVIEWING OF PROVISIONS OF THE GROUND MAT DESIGN OF SMALL HYDRO POWER HOUSES.
INTRODUCTION
GENERATING STATIONS AND SWITCHYARDS HAVE TO BE EFFECTIVELY EARTHED FROM SAFETY CONSIDERATION COVERED UNDER LEGAL PROVISIONS OF ELECTRICITY REGULATIONS, ACTS, COMMISSIONS, ETC.
GUIDANCE PROVIDED UNDER SAFETY CODES AND STANDARDS.
EACH COUNTRY HAS HIS OWN GOVERNING REGULATIONS AND STANDARDS / CODES FOR GROUNDING OF ELECTRICAL INSTALLATIONS.
DESIGN CONCEPT
THE DESIGN OF GROUND MAT IS TAKEN UP CONSIDERING THE FOLLOWING:
PLOT LAY OUT OF S/S / LAYOUT OF A POWER HOUSE(L X B ) SOIL RESISTIVITY (OHM-M) SURFACE RESISTIVITY -RIVER STONE/CRUSHED
STONE/WASHED GRANITE/ CONCRETE ( OHM-M) MAXIMUM PERMISSIBLE GROUND RESISTANCE OF SUBSTATION
/POWER HOUSE (OHM) SHORT CIRCUIT CURRENT (KA) AND ITS DURATION (SEC) DURATION OF SHOCK (SEC) DEPTH OF BURIAL OF GROUND MAT MEMBER (MM) MATERIAL OF GROUND MAT ( STEEL/COPPER) STEP POTENTIAL ( VOLTS) TOUCH POTENTIAL ( VOLTS)
MEASUREMENT OF SOIL RESISTIVITYA TYPICAL EARTH TESTER HAS FOUR (4)
TERMINALS.C1, P1, C2, P2 AND FOUR (4) ELECTRODES SUPPLIED WITH THE INSTRUMENT ARE DRIVEN IN THE GROUND AT SPECIFIED EQUAL DISTANCES THRU CABLE AND CONNECTED TO THE INSTRUMENT IN THE ORDER OF C1, P1 AND P2, C2.
SPECIFIC RESISTIVITY =2 Π.A. R
WENNER METHOD FOR CALCULATING SOIL RESISTIVITY
ρ=2ΠaR
Notes(i)DEPTH OF BURIED ELECTRODES ASSUMED NEGLIGIBLE AS COMPARED TO SPACING BETWEEN ELECTRODES.ii)MORE THE DISTANCE BETWEEN ELECTRODES MORE THE DEPTH AT WHICH SOIL RESISTIVITY IS MEASURED.iii) IF SOIL OF HIGH RESISTIVITY IS AT TOP SURFACE AND SOIL RESISTIVITY AT DEEP LEVEL IS TO BE MEASURED, TWO OR MORE RESONANCE MODEL OF SOIL RESISTIVITY MEASUREMENT IS ADOPTED.
STANDARDS AND CODES
IS: 3043(4th Reprint June 2007 including Amendment No 1/ Jan 2007 and Amendment 2 / Jan 2010): Code of Practice for Earthing Electrical Installations.
CBI&P Publication No 223: Design of Earthing Mat of High Voltage Substations
IEEE 80-2000: Guide for Safety in AC Substation Grounding
IEEE 665-1995: Guide for Generating Station Grounding.
BS: 7430 -1998: Code of Practice for Earthing
Estimation OF EARTHHING MATERIAL PRELIMINARY SOIL RESISTIVITY ( INITIAL ESTIMATION)
AS THE SWITCHYARD PLANNED TO BE ERECTED FIRST, THE SOIL RESISTIVITY WAS MEASURED OVER A LEVEL PORTION OF LAND EARMARKED FOR POWER HOUSE.
THE SOIL RESISTIVITY MEASSUREMENT MEASUREMENT= 80 OHM-M EARTHING MATERIAL ( COPPER ) ESTIMATED PROCUREMENT ACTION INITIATED
FINAL SOIL RESISTIVITY (FINAL MEASUREMENT & ESTIMATION) THE EXCAVATION OF POWER HOUSE COMPLETED AND SWITCHYARD APPROX
LEVELLED SOIL RESISTIVITY LEVELS MEASURED AS UNDER
MAIN POWER HOUSE ( 8MW RBU) - 670 OHM-M CANAL BAY UNIT ( 2MW) - 120 OHM-M SWITCHGEAR ROOM & SERVICE BAY - 120 OHM-M OUT DOOR SWITCHYARD (ODY) - 120 OHM-M
POWER HOUSE
THE SITE OF POWER HOUSE IS EXCAVATED FIRST TO THE DESIRED GRADES AND SITE IS LEVELED.
THE GROUND MAT MEMBERS ARE LAID ON THE SURFACE OF CLEANED ROCK IN CASE OF ROCKY SURFACE OR BORROWS MADE AT SPECIFIED DEPTH (650MM) IN FISSURED ROCK OR HARD SOIL.
THE GROUND MEMBERS AND RISERS (WHERE REQUIRED) ARE JOINTED AT CROSSING POINTS BY WELDING/ BRAZING/ EXOTHERMIC MOLD.
THE CONCRETE FLOOR IS LAID DOWN. THE END MEMBERS (X AND Y AXIS) OF GROUND MAT EXTENDED BEYOND CONCRETE LAYER ARE LEFT FOR EXTENDING TO NEXT FLOOR ELEVATION FOR LAYING
ANOTHER RING OF MAT AT THAT FLOOR FOR MAKING CONNECTIONS TO EQUIPMENT AND SO ON.
DESIGN STEPS AREA OF CONDUCTOR,
(AS PER IS: 3043 CL. NO 12.2.2.1)
SPACING FACTOR FOR MESH VOLTAGE = Km
CHECK FOR ADEQUACY OF (L) FOR E STEP AND E MESH
ESTEP (TOLERABLE) = ( RK +6CS X PS)… (AS PER EQ -30 OF IEEE-80)
DESIGN STEPSIK = CURRENT RMS FLOWING THRU BODY
WEIGHT 70KG= 0.157 / √ TS
RK IS THE RESISTANCE OF BODY IN OHMS = 1000 OHMS (As per Eq -33 of IEEE-80) (As per Eq -80 of IEEE-80) CALCULATION OF GRID RESISTANCE (As per IS
3043 Cl No 9.2.3 )
RESISTANCE OF VARIOUS ELECTRODES (IACSIT Intern. Journal of Engg of Techn Vol4, No3, June 2012
S,No Details of Earthing System
Resistance Symbols
1 Single Earth Electrode =Soil Res()l=Length of strip(cm)
d= Dia of rod (cm)2 Multiple Earth Electrode Ri=Resis of one rod in
isol=Soil Res()
n= Nos of rodsS=Dist between rods
(m) = Factor as per
Table3 Strip Conductor Earthing =Soil Res()
l=Length of strip(cm)W= depth of burial of
electrode (cm)t=width (cm)
4 Earthing Plate =Soil Res()A= Area of both side
of Plate(m2)
Factor for Parallel ElectrodesNo of Electrodes Factor
2 1.00
3 1.65
4 2.15
5 2.54
6 2.87
7 3.15
8 3.39
9 3.61
10 3.81
GROUND MAT IN POWER HOUSE
THE GROUNDING SYSTEM IN A POWER HOUSE COMPRISES OF:
GROUNDING SYSTEM FOR POWER HOUSE (PH)
GROUNDING SYSTEM FOR SWITCHYARD (SY)
DESIGN ASPECT OF GROUND MAT LIMIT THE OVERALL POTENTIAL RISE. PROTECT PERSONNEL & DEVICES FROM OVER
VOLTAGES. LOW IMPEDANCE PATH TO FAULT CURRENT FOR
RELIABLE & PROMPT OPERATION OF PROTECTIVE DEVICES DURING GROUND FAULT.
STEP POTENTIAL WITHIN THE PERMISSIBLE LIMIT. TOUCH POTENTIAL WITHIN THE PERMISSBLE LIMIT.
SECURITY AND SAFETY FENCE AROUND SWITCHYARD.
MANDATORY CONNECTING ALL THE METALLIC PARTS OR STATIC PARTS OF ELECTRICAL EQUIPMENT MINIMUM AT TWO POINTS.
EARTHING OF LIGHTNING PROTECTIVE DEVICES.
DESIGN ASPECT OF GROUND MAT SOIL AND SURFACE RESISTIVITY SIZE( DEPENDING ON AREA) AND TYPE OF EARTH SYSTEM DEPTH OF BURIAL OF ELECTRODE MATERIAL OF GROUND MAT MOISTURE CONTENT OF THE SOIL. SHORT CIRCUIT RATING AND DURATION OF SHORT CIRCUIT DURATION OF SHOCK PERMISSIBLE GROUNDING RESISTANCE PERMISSIBLE TOUCH AND STEP POTENTIALS
DATA AND DESIGN THE FAULT LEVEL AT 33KV LEVEL (STEP UP VOLTAGE)
HAS BEEN CONSIDERED AS 31.5KA
THE DESIGN OF EARTH MAT 60% OF 31.5 KA HAS BEEN CONSIDERED IN ACCORDANCE WITH BS-7354-CLAUSE NO 7.3.2
THE MATERIAL OF EARTH MAT HAS BEEN CONSIDERED AS “COPPER FLAT” AND COPPER CLAD STEEL RODS
BASED ON THE AVAILABLE INPUTS,THE FOLLOWING PARAMETERS HAVE BEEN CONSIDERED FOR PRELIMINARY DESIGN IN ACCORDANCE WITH IEEE-80
INPUT DATA (Tiga Power House) Sl. no Symbol Descriptions Values PH Values ODY Units
1 Isc Fault current (60% of 31.5kA) 18900 18900 Amps
2 ρSoil resistivity (average of P1 & P2 is 75.45Ω & 81.02Ω) 80 80 Ω-m
3 ρs Surface layer resistivity 3000 3000 Ω-m
4 DSpacing between parallel conductor 4 1.6 Metre
5 LPH Length of PH and ODY 36 41.6 Metre
6 BPH Breadth of PH and ODY 28 22.4 Metre
SUMMARY OF THE RESULT Tolerable Calculat
edPower House Step voltage
(ESTEP)3938.839 V > 653.24 V
Touch voltage(ETOUCH)
1151.23 V EMESH calculated >
801.17 V
Switch Yard Step voltage (ESTEP)
3938.83 V > 2204.41 V
Touch voltage (ETOUCH)
1151.23 V EMESH calculated >
685.02V
Grid resistance 0.117Ω
DESIGN AND ITS RESULTS OF GROUND MAT OF POWER HOUSE AFTER EXCAVATION COMPLETED
INPUT DATA
Sl. no
Symbol
Descriptions
Values PH 8MW & TRL
Values PH-2MW
Values ODY
Values SB & SG room
Units
1 Isc Fault current (60% of 31.5kA) 18900 18900 18900 18900 Amps2 Ρ Soil resistivity 670.5 112 112 112 Ω-m3 ρs Surface layer resistivity 5000 5000 5000 5000 Ω-m
4 DEquivalent Diameter of the grid conductor 0.020 0.020 0.020 0.020 Metre
5 DSpacing between parallel
conductor1.5
3
4
4 Metre
6L
Length of PH, ODY & Service bay including switch gear room
16.7
12
53.5
28 Metre
7B
Breadth of PH, ODY & Service bay including switch gear room
23.4
23.4
38.75
23.4 Metre
SUMMARY OF THE RESULTLocation Particulars Tolerable Calculate
dLimits
Power House 8MW Step voltage (ESTEP ) 6483.32 V < 12590.27 V
Unsafe
Touch voltage (ETOUCH ) 1787.35V < EMESH calculated
1952.42 V Unsafe
Grid resistance RG 0.364 Ω Safe Power House 2MW Step voltage (ESTEP ) 6416.71V > 492.07 V Safe
Touch voltage (ETOUCH ) 1770.70V > EMESH calculated
396.784 V Safe
Grid resistance RG 0.061Ω SafeSwitch yard Step voltage (ESTEP ) 6416.71V > 715.70 V Safe
Touch voltage (ETOUCH ) 1770.70V > EMESH calculated
579.43 V Safe
Grid resistance RG 0.061 Ω SafeService bay & Switch gear room
Step voltage (ESTEP ) 6416.71 V > 774.68 V Safe
Touch voltage (ETOUCH ) 1770.70V > EMESH calculated
540.62 V Safe
Grid resistance RG 0.061 Ω Safe
TO LIMIT THE STEP AND TOUCH POTENTIAL WITH IN POWER HOUSE
IN CASE OF HIGH RESISTIVITY SOIL, IT HAS BEEN REVEALED THAT IT IS DIFFICULT TO MEET THE SAFETY CRITERIA OF TOUCH AND STEP POTENTIALS.
IT HAS BEEN FOUND THAT LARGE LAND AREA IS REQUIRED FOR MEETING THE REQUIREMENT.
FOR CONSIDERING THE COST EFFECTIVE SOLUTION, IT HAS BEEN NECESSARY TO RE-EXAMINE THE REQUIREMENT
IEEE-665,GUIDE FOR GENERATING STATION GROUNDINGCL NO 5.1: GROUNDING PRINCIPLE STIPULATES THAT
TOUCH AND STEP POTENTIAL SHALL MEET THE PERMISSIBLE LIMITS
CL NO 5.2.7 STIPULATES THAT “THE MAXIMUM ALLOWABLE TOUCH AND STEP VOLTAGES ARE THE CRITERIA THAT SHOULD BE MET TO ENSURE A SAFE DESIGN. IF THE TOUCH AND STEP VOLTAGES OF THE GRID DESIGN ARE BELOW THE MAXIMUM VALUES, THEN THE DESIGN IS CONSIDERED ADEQUATE.”
IEEE-665,GUIDE FOR GENERATING STATION GROUNDING CL NO 5.2.2 STATES THAT GENERATING STATIONS DIFFER FROM
SUBSTATIONS IN THAT THE PERSONNEL TO BE PROTECTED ARE GENERALLY WORKING INDOORS. BECAUSE THEY ARE NOT IN DIRECT CONTACT WITH THE EARTH OR WITH A LAYER OF CRUSHED ROCK COVERING THE EARTH, THEY ARE NOT EXPOSED TO MANY OF THE STEP AND TOUCH VOLTAGE CONDITIONS THAT PERSONNEL IN SUBSTATIONS ARE EXPOSED.
THE CEA NOTIFICATION NO-211 DATED 20TH AUG 2010 ALSO STATES THAT TOUCH AND STEP POTENTIAL SHALL BE MAINTAINED WITHIN ACCEPTABLE LIMITS.
DELIBERATION
ACCORDINGLY, TAKING COGNIZANCE OF PRACTICES IN VOGUE IN VARIOUS HYDRO POWER STATIONS, THE CRITERIA FOR STEP AND TOUCH POTENTIAL HAS NOT BEEN IGNORED AND ADOPTED AS CRITERIA FOR SAFE DESIGN BUT THIS NEEDS TO BE DELIBERATED IN THE CONFERENCE.
SURFACE LAYER RESISTIVITY IN THE PRELIMINARY DESIGN CALCULATIONS, THE SURFACE
LAYER RESISTIVITY WAS CONSIDERED AS 5000 Ω- M.
THE VALUES INDICATED FOR DRY AND WET CONDITIONS FOR THE VARIOUS SURFACE MATERIALS ARE WIDELY VARYING VIZ: FOR CONCRETE UNDER DRY CONDITION IT IS 1X106 TO 1X109OHM-M AND 21 TO 100 OHM-M FOR WET CONDITIONS.
IT IS ALSO INDICATES THAT 1X109 IS USED FOR OVEN DRIED CONCRETE.
THE VALUE OF 10,000 Ω M WAS CONSIDERED AS CONCRETE MAY NOT BE FULLY DRIED AT MIV FLOOR LEVEL.
FINAL DESIGN OF GROUND MAT OF POWER HOUSE MAIN PURPOSE OF THIS REWORK HAS BEEN TO UNDERTAKE SAFE
DESIGNING AND COST EFFECTIVE GROUNDING SYSTEMS FOR TIGA HEP.
TO ADOPT SAFE LIMITS OF TOUCH AND STEP POTENTIAL INSIDE THE POWER HOUSE WITHOUT SATELLITE GRID STATION AND SAVE COST.
TO CONSIDER SURFACE RESISTIVITY VALUE OF CONCRETE AS 10,000 Ω INSIDE THE POWER HOUSE AND THAT OF WASHED QUARTZ AS 5,000 Ω IN SWITCH YARD. WITH THE CHANGE IN THE SURFACE RESISTIVITY VALUES, THE SAFE LIMITS OF E TOUCH AND E STEP OF EARTH MAT WERE ALSO ACHIEVED IN 8MW PORTION OF POWER HOUSE AND THIS ALSO RESULTED IN REDUCTION IN THE MATERIAL REQUIRED FOR EARTH MAT.
FINAL DESIGN OF GROUND MATINPUT DATA
Sl. no
Symbol Descriptions Values PH 8MW & TRP
Values PH-2MW
Values ODY
Values SB & SG room
Units
1 IscFault current (60% of 31.5kA) 18900 18900 18900 18900 Amps
2 ρ Soil resistiviy 670.5 112 112 112 Ω-m
3 ρs
Surface layer resistivity 10000 10000 5000 10000 Ω-m
4 DSpacing between parallel conductor
1.5
3
4
4 Metre
5L
Length of PH, ODY & Service bay including switch gear room as per excavated profile
82.3
12.8
53.5
28.5
Metre
6B
Breadth of PH, ODY & Service bay including switch gear room
22.5
22.5
38.75
22.5 Metre
SUMMARY OF THE RESULTLocation Particulars Tolerabl
e Calculat
edLimits
Power house 8MW Step voltage (ESTEP ) 12619.39 V
> 7886.36 Safe
Touch voltage (ETOUCH )
3319.37 > EMESH calculated
1692.44 Safe
Grid resistance RG 0.42 Ω Safe Power house 2MW Step voltage (ESTEP ) 12611.39
V> 351.90 Safe
Touch voltage (ETOUCH )
3319.37 > EMESH calculated
340.97 V Safe
Grid resistance RG 0.053Ω SafeSwitch yard Step voltage (ESTEP ) 6466.71 > 488.51V Safe
Touch voltage (ETOUCH )
1170.78V > EMESH calculate
d
501.60 V Safe
Grid resistance RG 0.053 Ω SafeService bay & Switch gear room
Step voltage (ESTEP ) 12611.39 V
> 346.56 V Safe
Touch voltage (ETOUCH )
3319.37 > EMESH calculate
d
414.18
Safe
Grid resistance RG 0.053 Ω Safe
ISSUES FOR DELIBERATION OF CONFERENCE
THE DESIGN OF GROUNDING MAT OF POWER HOUSES AND EHV SUBSTATIONS IS CARRIED OUT LARGELY BASED ON IEEE80-2000 INCLUDING POWER HOUSE PROVISIONS OF IEEE 665-1997. THE DESIGN OF GROUND MAT ATTAINS CRITICALITY WHEN SOIL RESISTIVITY IS HIGH AND INHERITED SMALL GROUND AREA IN CASE OF SMALL POWER HOUSES (SPH). THE FOLLOWING TOPICS ARE LISTED FOR CONSIDERATION OF THE INTERNATIONAL CONFERENCE
SOIL RESISTIVITY UNIFORM SURFACE RESISTIVITY MEASURED AT THE SURFACE
OF POWER HOUSE AND SWITCH YARD WITH CONVENTIONAL METHOD OF MEASUREMENT (80 OHM-M)]
AS THE EXCAVATION AT HIGHER LEVEL FOR 2MW GEN UNIT AND 8MW GEN UNIT WAS COMPLETED AND SOIL RESISTIVITY WAS MEASURED AT BOTH THE GEN UNITS LEVELS, SWITCHGEAR CONTROL & SERVICE BAY AND ODY
THE SOIL RESISTIVITY AT ALL LOCATIONS EXCEPT 8MW UNIT WAS MEASURED AS 120 OHM-M WHEREAS SOIL RESISTIVITY AT 8MW UNIT WAS MEASURED AS 670 OHM-M.
THIS WAS COMPARATIVELY HIGH SOIL RESISTIVITY AND SMALL POWER HOUSE SURROUNDED AREA
DESIGN OF GROUND MAT IN IEEE 665, THE SAID STANDARD DOES NOT INSIST FOR
MEETING TOUCH AND STEP POTENTIAL REQUIREMENT INSIDE POWER HOUSE.
OPERATORS DURING WORKING IN THE POWER HOUSE DONOT STEP OUT OF POWER HOUSE AND DANGER OF DIFFERENT VOLTAGE GRADIENT CAN BE AVOIDED BY PROVIDING SOME ROUNDS OF GROUNDING MATERIAL (COPPER) AROUND THE POWER HOUSE.
THIS IS SIMILAR TO EXTENDING THE GROUND MAT OF S/S OUTSIDE THE FENCE TO PROTECT FROM DANGEROUS VOLTAGES WHEN UN-AUTHORIZED PERSONNEL TOUCH THE FENCE FROM OUTSIDE.
IT WAS CONSIDER TO USE SURFACE RESISTIVITY OF CONCRETE AS 10,000 OHM-M INSTEAD OF 5000 OHM-M. ON REVISION OF CALCULATION IT HAS BEEN OBSERVED THAT TOUCH AND STEP POTENTIAL AT ALL THE LOCATIONS MEET THE SAFE REQUIREMENT.
IT IS CONVENIENT FOR DESIGNER TO ADOPT 5000, 10,000OHM-M OR MORE AS THE SURFACE RESISTIVITY OF CONCRETE TO ACHIEVE TOUCH AND STEP POTENTIAL LIMITS THOUGH CONCRETE IS PROVIDED IN EVERY POWER HOUSE
GROUND RESISTANCE VALUE WHEN CALCULATED FOR EACH PORTION OF POWER HOUSE AND SWITCHYARD ARE WITHIN PERMISSIBLE LEVEL. WHEN CONNECTED TOGETHER AND RESISTANCE MEASURED, THE AVERAGE VALUE MAY BE FURTHER LESS.
REFERENCE IEEE 80-2000: GUIDE FOR SAFETY IN AC SUBSTATIONS GROUNDING IEEE 665-1995 : GIDE FOR GENERATING STATIONS GROUNDING BS 7430-1998 : CODE OF PRACTICE FOR EARTHING IS 3043 AS AMENDED : CODE OF PRACTICE FOR EARTHING
COVERING ELECTRICAL INSTALLATIONS CBI&P PUBLICATION NO 223 : DESIGN OF EARTHING MAT OF HIGH
VOLTAGE SUBSTATIONS NATIONAL ELECTRICAL SAFETY CODE ( NESC) -1990, 1997,2002
AND 2012 IE RULES 1956 AND ELECTRICITY ACT 2003 IACSIT International Journal of Engg Techn. Vol 4 No.3, June 2012, Earthing System Design of Small Hydro Power (SHP) Stn – A Rewiew By M.K.Singhal, S.N Singh