NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Inspection Type Last EditedTime InInspectionId
P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ISLAND, NY, 10309School:
3433 2020-02-10 06:12AM 2020-02-12 03:01PMARCHITECTURAL - SENIOR
3450 2020-02-10 08:59AM 2020-08-24 02:23PMARCHITECTURAL - ASSOCIATE
Asset DataQuestion Answer
Was the Building Fully Accessible for Inspection? Yes
Principal(s) Information
Principal Name Elmer Myers
Principal Organization P.S. 3 - Staten Island
Meeting with Principal? Yes
Principal Feedback The Principal provided the following comments:
1- The Heating and Cooling in the building is inconsistent from
room to room and requires control adjustment or upgrades.
2- The Playground surface is deteriorated and need refinishing.
3- The sidewalk around the building is deteriorated and need
replacement .
Custodian William Purdy III
Fireman Mike Magliaccio
Building Square Footage 66,000
Comments on the Area (Square Feet) N/A
Comments on the Stories (Floors) plus Basements 1+B
Comments on the Year Built 1959
Comments on the Student Population 675
Comments on the Staff Population 100
Comments on the Number of Classrooms 32
Weather Heavy Rain
Facade Photo
Corner of South Goff Avenue and Latourette Street - Southwest
View
Page 1 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural InspectionMain Entrance Photo
80 South Goff Avenue
Roof Photo
Roof 1 - North View
Have any Systems/Major Building Components been upgraded? Systems: HC Accessibility upgrade with Elevator, New Unisex
Toilet Room (in Cafeteria)
Years: 2009
Systems: Roofing replacement with Drains, Barrier, Roof 1-4,
New Exterior Metal Panels, Windows/Guards
replacement (full), Exterior Masonry repointing (
partial-Original Building), Exterior Doors replacement
(partial )
Years: 2015
Systems: Partial replacement of Playground surface; Library AC
upgraded .
Years: 2019
2004 (6100 SF)Have there been any New Building Additions?
1967 (37400 SF)
Tandem No Tandem
Leased Space? No
Priority ConditionExist
Last Year?
Priority
Category
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
Tripping Hazards Severely damaged stairs
treads pose a potential
tripping hazard
Site
Stairs/Ramps
Near Exit 10 Mike
Magliaccio
Yes Fireman
Page 2 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Structural Engineer Required
Structural
Condition Type
Condition
Description
Component
Affected
Location
Description
Person(s)
Notified
Person(s)
Title
Photo
Image
No condition recorded
Accessibility
Accessibility Status Question Response
Is the Primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are All floors of the building accessible through compliant means? Yes
Accessible classrooms exists on each floor? Yes
Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes
If the following spaces exist, are they ALL accessible? Art Room, Auditorium,
Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs
Yes
Physical Breakdown Structure Exists Complies Required DeficiencyAudio
Induction
System
Fire
Alarm
Strobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
YesExterior Entrances & Exits
NoNoExterior H/C Lifts
YesYesExterior Ramps and Railings
Interior Routes
NoNoCorridor and Lobby H/C Lifts
YesYesInterior Corridor Doors And
Hardware
YesInterior Corridors & Lobbies
YesYesInterior Elevators
YesInterior Lobby Doors And Hardware
YesYesInterior Ramps
Rooms & Spaces
Art Rooms
Yes YesRoom 127
Auditorium
Yes Yes1st Floor Yes Yes
Cafeteria
Yes Yes1st Floor - Students Yes Yes
Yes Yes1st Floor - Staff No No
Classrooms
Yes Yes1st Floor
Computer Rooms
Yes YesRoom 145
Gymnasium
Yes YesBasement Yes Yes
Library
Yes YesRoom 138
Main Office
Yes YesRoom 157
NoMulti-purpose Room
Nurse's Office
Yes YesRoom 119
NoPool
Page 3 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Physical Breakdown Structure Exists Complies Required DeficiencyAudio
Induction
System
Fire
Alarm
Strobe
NoScience Lab
Toilet Rooms (boys)
Yes Yes1st Floor within
Cafeteria-Unisex
Toilet Rooms (girls)
Yes Yes1st Floor within
Cafeteria-Unisex
Toilet Rooms (staff)
Yes Yes1st Floor 2004 Wing -
Unisex
Building Template
Inspection
Question Response
Architectural
ATHLETIC FIELDS Does not exist
EXTERIOR Inspected
InspectedAREAWAY
Instance on AW1-AW2 Inspected
2- Between Good and FairInstance Condition
Instance Quantity 2
Instance Quantity Uom EACH
No deficiencies recordedDeficiency
Does not existAWNINGS AND CANOPIES
InspectedCHIMNEY
MasonryMaterial Type(s)
Condition 3- Fair
BRICK:MISSING CAPDeficiency
Deficiency Location/Instance
20Deficiency Quantity
Page 4 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
EXTERIOR
CHIMNEY
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Chimney 1
Violations No violations recorded
InspectedCOPING
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existCORNICE
InspectedDOORS
InspectedDOOR HARDWARE
Condition 3- Fair
No deficiencies recordedDeficiency
InspectedDOORS AND FRAMES
Condition 3- Fair
METAL:DETERIORATED DOOR AND FRAME - MAJOR
DETERIORATION
Deficiency
Deficiency Location/Instance
2Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade K - Main Entrance
Violations No violations recorded
METAL:DETERIORATED DOOR AND FRAME - MINOR
DETERIORATION
Deficiency
Page 5 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Deficiency Location/Instance
5Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade I - Exit 9
Violations No violations recorded
InspectedLINTELS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedTRANSOM/SIDE LIGHT
Condition 3- Fair
METAL:DENTED, MINOR RUSTINGDeficiency
Deficiency Location/Instance
12Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A - Exit 4
Violations No violations recorded
InspectedEXTERIOR SOFFITS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Page 6 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
EXTERIOR
InspectedEXTERIOR WALLS
MasonryMaterial Type(s)
18,000Replacement Quantity
Replacement Uom S.F.
Instance on Metal, Glass Curtain Walls: Original, 1967 Wing Inspected
2- Between Good and FairInstance Condition
Instance Quantity 8,000
Instance Quantity Uom S.F.
No deficiencies recordedDeficiency
Instance on Masonry: 2004 Wing Inspected
2- Between Good and FairInstance Condition
Instance Quantity 6,000
Instance Quantity Uom S.F.
No deficiencies recordedDeficiency
Instance on Brick: Original, 1967 Wing Inspected
3- FairInstance Condition
Instance Quantity 4,000
Instance Quantity Uom S.F.
STONE:OPEN JOINTSDeficiency
Roof Plan Reference
Elevation
Elevation Reference Facades A, C, I, K
25Deficiency Quantity
Quantity Uom L.F.
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade A
Violations No violations recorded
BRICK:OPEN JOINTSDeficiency
Page 7 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
Roof Plan Reference
Elevation
Elevation Reference Facades A, B, C, I, K
120Deficiency Quantity
Quantity Uom S.F.
Potential Action REPOINT
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade B
Violations No violations recorded
BRICK:CRACKS/DISPLACED/SPALLED BRICK AT
BUILDING CORNERS
Deficiency
Roof Plan Reference
Elevation
Elevation Reference Facade C
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REMOVE AND REBUILD
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Page 8 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
EXTERIOR
EXTERIOR WALLS
Deficiency Photo 1
Facade C
Violations No violations recorded
Does not existLOADING DOCK
InspectedLOUVER
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedPARAPETS
ConcreteMaterial Type(s)
3,000Replacement Quantity
Replacement Uom C.F.
Instance on 2004 Wing Inspected
2- Between Good and FairInstance Condition
Instance Quantity 3,000
Instance Quantity Uom CF
No deficiencies recordedDeficiency
Does not existPLAZA DECK
InspectedROOF
InspectedROOFING
Replacement Quantity 57,000
Replacement Uom S.F.
InspectedLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedROOF BARRIER
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existROOF CAGE
InspectedROOF FENCE
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedROOF HATCH/SMOKE HATCH
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedROOFING
Instance on Modified Bitumen:Roofs 1-4 Inspected
1- GoodInstance Condition
Instance Quantity 48,000
Instance Quantity Uom S.F.
“Does the roof have major mechanical equipment sitting on Dunnage
Steel less than 18" above the Roofing?"
No
Installation Year 2015
Source of Installation Year Documented
No deficiencies recordedDeficiency
Instance on Built-Up:Roof 5 Inspected
Page 9 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
EXTERIOR
ROOF
ROOFING
ROOFING
3- FairInstance Condition
Instance Quantity 3,000
Instance Quantity Uom S.F.
“Does the roof have major mechanical equipment sitting on Dunnage
Steel less than 18" above the Roofing?"
No
Installation Year 1991
Source of Installation Year Custodial Staff
BUILT-UP:ROOFING:LOSS OF GRAVELDeficiency
Deficiency Location/Instance
200Deficiency Quantity
Quantity Uom S.F.
Potential Action INSTALL NEW GRAVEL
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Roof 5
Violations No violations recorded
Instance on Single Ply, Fully Adhered Roof:Roof 6 Inspected
3- FairInstance Condition
Instance Quantity 6,000
Instance Quantity Uom S.F.
“Does the roof have major mechanical equipment sitting on Dunnage
Steel less than 18" above the Roofing?"
No
Installation Year 2004
Source of Installation Year Documented
SINGLE PLY, FULLY ADHERED ROOF:ROOFING:OPEN
SEAMS
Deficiency
Deficiency Location/Instance
60Deficiency Quantity
Quantity Uom L.F.
Potential Action REPAIR
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Page 10 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
EXTERIOR
ROOF
ROOFING
ROOFING
Deficiency Photo 1
Roof 6
Violations No violations recorded
InspectedROOFING DRAINS
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedSPECIALTIES
Does not existBULKHEAD/PENTHOUSE
Does not existCUPOLA/ SPIRES/ TOWERS
Does not existDORMER
Does not existDUNNAGE STEEL
Does not existROOF/GRAVITY TANK
Does not existSKYLIGHT/ROOF VENT
InspectedSTAIRS/RAMPS: EXTERIOR
InspectedBUILDING CHEEK/FLANK WALLS
Condition 3- Fair
BRICK:CRACKS/SPALLING - MINORDeficiency
Deficiency Location/Instance
6Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade K - Exit 11
Violations No violations recorded
CAST IN PLACE CONCRETE:CRACKS/SPALLING - MINORDeficiency
Page 11 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Deficiency Location/Instance
8Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade B - Exit 5
Violations No violations recorded
InspectedRAILINGS
Condition 3- Fair
DAMAGEDDeficiency
Deficiency Location/Instance
5Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade - Exit 5
Violations No violations recorded
RUST - MINORDeficiency
Page 12 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
RAILINGS
Deficiency Location/Instance
8Deficiency Quantity
Quantity Uom L.F.
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade C - Exit 7
Violations No violations recorded
InspectedSTAIRS/RAMPS
Condition 4- Between Fair and Poor
STONE:CRACKS, SPALLINGDeficiency
Deficiency Location/Instance
5Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade K - Exit 11
Violations No violations recorded
CONCRETE:CRACKS/SPALLING - MINORDeficiency
Page 13 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade B - Exit 5
Violations No violations recorded
CONCRETE:CRACKS/SPALLING - MAJORDeficiency
Deficiency Location/Instance
5Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Facade B - Exit 6
Violations No violations recorded
InspectedWINDOWS
7,000Replacement Quantity
Replacement Uom S.F.
InspectedEXTERIOR GUARDS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedLINTELS
Condition 2- Between Good and Fair
Page 14 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
EXTERIOR
WINDOWS
LINTELS
No deficiencies recordedDeficiency
InspectedWINDOWS
Material Type(s) Aluminum
Instance on Aluminum - Double Hung:Original Building and 1967
Wing
Inspected
1- GoodInstance Condition
Instance Quantity 6,000
Instance Quantity Uom S.F.
Installation Year 2015
Source of Installation Year Documented
No deficiencies recordedDeficiency
Instance on Aluminum - Double Hung:2004 Wing Inspected
2- Between Good and FairInstance Condition
Instance Quantity 1,000
Instance Quantity Uom S.F.
Installation Year 2004
Source of Installation Year Documented
No deficiencies recordedDeficiency
INTERIOR Inspected
AUDITORIUM
Instance on 1st Floor (201 Seats) Inspected
Ceiling
Instance on 1st Floor (201 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor (201 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed H/C Lift
Instance on 1st Floor (201 Seats) Does not exist
Fixed Seating
Instance on 1st Floor (201 Seats) Inspected
3- FairInstance Condition
DAMAGED/BROKEN/INOPERABLEDeficiency
Seats A/4, B/105, 113, E/104, H/3 and other locationsDeficiency Location/Instance
14Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Seat A/4
Violations No violations recorded
Floor Finish
Page 15 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
INTERIOR
AUDITORIUM
Floor Finish
Instance on 1st Floor (201 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Sliding-folding Partition
Instance on 1st Floor (201 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage
Instance on 1st Floor (201 Seats) Inspected
Stage
Instance on 1st Floor (201 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage Curtain Rigging
Instance on 1st Floor (201 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Stage Curtains
Instance on 1st Floor (201 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on 1st Floor (201 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Window Curtains/Shades/Blinds
Instance on 1st Floor (201 Seats) Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
CAFETERIA
Instance on 1st Floor - Students Inspected
Instance on 1st Floor - Staff Inspected
Ceiling
Instance on 1st Floor - Students Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on 1st Floor - Staff Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor - Students Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on 1st Floor - Staff Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on 1st Floor - Students Does not exist
Instance on 1st Floor - Staff Does not exist
Floor Finish
Page 16 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
INTERIOR
CAFETERIA
Floor Finish
Instance on 1st Floor - Students Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on 1st Floor - Staff Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Sliding-folding Partition
Instance on 1st Floor - Students Not required
Instance on 1st Floor - Staff Does not exist
Stage
Instance on 1st Floor - Students Does not exist
Instance on 1st Floor - Staff Does not exist
Walls
Instance on 1st Floor - Students Inspected
2- Between Good and FairInstance Condition
GLAZED BLOCK:CRACKS/SPALLINGDeficiency
North Side of RoomDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
North Side of Room
Violations No violations recorded
MASONRY:CRACKS/SPALLINGDeficiency
West Side of RoomDeficiency Location/Instance
80Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
West Side of Room
Violations No violations recorded
Instance on 1st Floor - Staff Inspected
2- Between Good and FairInstance Condition
PLASTER:CRACKS/SPALLINGDeficiency
Page 17 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
INTERIOR
CAFETERIA
Walls
Near EntranceDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Entrance
Violations No violations recorded
Window Curtains/Shades/Blinds
Instance on 1st Floor - Students Does not exist
Instance on 1st Floor - Staff Does not exist
InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES
InspectedCeiling
Condition 2- Between Good and Fair
PLASTER:CRACKS/SPALLINGDeficiency
Exit 5Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Exit 5
Violations No violations recorded
ACOUSTIC TILES ON PLASTER:DAMAGED/MISSINGDeficiency
Corridor near Room 142Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 18 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Deficiency Photo 1
Corridor near Room 142
Violations No violations recorded
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existSpecialties
InspectedWalls
Condition 2- Between Good and Fair
PLASTER:CRACKS/SPALLINGDeficiency
Corridor near Room 101A, 103, 116, 128, 133 and other locationsDeficiency Location/Instance
75Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Corridor near Room 101A
Violations No violations recorded
GLAZED BLOCK:CRACKS/SPALLINGDeficiency
Corridor near Rooms 142, 146, 147, 152 and other locationsDeficiency Location/Instance
25Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Corridor near Room 142
Page 19 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls
Violations No violations recorded
CERAMIC TILE:BROKEN/ MISSINGDeficiency
Main Entrance LobbyDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Main Entrance Lobby
Violations No violations recorded
GYMNASIUM
Instance on Basement Inspected
Ceiling
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Fixed Equipment
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Basement Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Seating
Instance on Basement Does not exist
Sliding-folding Partition
Instance on Basement Does not exist
Stage
Instance on Basement Does not exist
Walls
Instance on Basement Inspected
2- Between Good and FairInstance Condition
GLAZED BLOCK:CRACKS/SPALLINGDeficiency
North, East Side of RoomDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 20 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
INTERIOR
GYMNASIUM
Walls
Deficiency Photo 1
North Side of Room
Violations No violations recorded
PLASTER:CRACKS/SPALLINGDeficiency
North Side of RoomDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
North Side of Room
Violations No violations recorded
Window Curtains/Shades/Blinds
Instance on Basement Does not exist
InspectedINTERIOR DOOR HARDWARE
Condition 3- Fair
No deficiencies recordedDeficiency
InspectedINTERIOR GUARDS
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
KITCHEN
Instance on 1st Floor Inspected
Ceiling
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on 1st Floor Inspected
2- Between Good and FairInstance Condition
CERAMIC TILE:BROKEN/MISSING TILESDeficiency
Servery AreaDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Page 21 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
INTERIOR
KITCHEN
Floor Finish
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Servery Area
Violations No violations recorded
Walls
Instance on 1st Floor Inspected
3- FairInstance Condition
PLASTER:CRACKS/SPALLINGDeficiency
Mop Room, StorageDeficiency Location/Instance
75Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Mop Room
Violations No violations recorded
GLAZED BLOCK:CRACKS/SPALLINGDeficiency
Near ExitDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Near Exit
Violations No violations recorded
LIBRARY
Instance on Room 138 Inspected
Page 22 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
INTERIOR
LIBRARY
Built-in Furnishing
Instance on Room 138 Does not exist
Ceiling
Instance on Room 138 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Door(s)
Instance on Room 138 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Floor Finish
Instance on Room 138 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Walls
Instance on Room 138 Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Does not existLOCKER ROOM
Does not existMULTI-PURPOSE ROOM
Does not existPOOLS
Does not existSCIENCE DEMO ROOM
Does not existSCIENCE LAB
Does not existSCIENCE PREP ROOM
Does not existSHOWER ROOM
InspectedSTAIRS/RAMPS: INTERIOR
Do Letter Stair Signs Exist? Yes
InspectedCeiling
Condition 2- Between Good and Fair
PLASTER:CRACKS/SPALLINGDeficiency
Stair A/BasementDeficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair A/Basement
Violations No violations recorded
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existPartition
InspectedRailings
Condition 2- Between Good and Fair
Page 23 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Railings
No deficiencies recordedDeficiency
InspectedStairs and Landings
Condition 2- Between Good and Fair
VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency
Exit 9Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Exit 9
Violations No violations recorded
STONE:BROKEN/MISSINGDeficiency
Stair A/1Deficiency Location/Instance
15Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Stair A/1
Violations No violations recorded
InspectedWalls
Condition 2- Between Good and Fair
GLAZED BLOCK:CRACKS/SPALLINGDeficiency
Stair A/Basement, 1Deficiency Location/Instance
15Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 24 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Walls
Deficiency Photo 1
Stair A/Basement
Violations No violations recorded
InspectedSTRUCTURAL
InspectedCOLUMNS/BEAMS/BEARING WALLS
Condition 3- Fair
MASONRY BEARING WALL:CRACKED/SPALLEDDeficiency
BasementDeficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Potential Action RESTITCH
PRIORITY 3Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Room B9
Violations No violations recorded
InspectedFLOOR STRUCTURE
Condition 3- Fair
CONCRETE SLAB ON GRADE:MINOR CRACKSDeficiency
BasementDeficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Mechanical Room ( B6 )
Violations No violations recorded
InspectedFOUNDATION WALLS
Material Type(s) Concrete
Condition 3- Fair
Page 25 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
INTERIOR
STRUCTURAL
FOUNDATION WALLS
CONCRETE:WATER INFILTRATION IN NON-
INSTRUCTIONAL SPACE
Deficiency
BasementDeficiency Location/Instance
60Deficiency Quantity
Quantity Uom S.F.
Potential Action INSTALL WATERPROOFING
PRIORITY 5Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Oil Tank Room
Violations No violations recorded
CONCRETE:CRACKED/SPALLED/REINFORCEMENT
EXPOSED
Deficiency
Basement and Facade CDeficiency Location/Instance
40Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 5Purpose of Action
Deficiency Photo 1
Facade C
Deficiency Photo 2
Room B7
Violations No violations recorded
InspectedROOF STRUCTURE
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existVAULTS-BUNKERS
InspectedTOILET ROOMS - STAFF
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Page 26 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
INTERIOR
TOILET ROOMS - STAFF
InspectedDoor(s)
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedFloor Finish
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedStalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
CERAMIC TILE:BROKEN/ MISSINGDeficiency
Rooms 113, 132Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room 132
Violations No violations recorded
InspectedTOILET ROOMS - STUDENTS
InspectedCeiling
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedDoor(s)
Condition 3- Fair
WOOD:DETERIORATED DOORDeficiency
Room B5Deficiency Location/Instance
1Deficiency Quantity
Quantity Uom EACH
Potential Action MAINTENANCE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Room B5
Violations No violations recorded
InspectedFloor Finish
Condition 2- Between Good and Fair
Page 27 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Floor Finish
No deficiencies recordedDeficiency
InspectedStalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedWalls
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
LIFE SAFETY Inspected
Does not existF.D. HOLDING AREA
Does not existSTEEL STAIRS
SITE Inspected
InspectedCONTAINERIZATION
Condition 5- Poor
FENCING DAMAGEDDeficiency
Containers AreaDeficiency Location/Instance
120Deficiency Quantity
Quantity Uom S.F.
Potential Action REPAIR
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Containers Area
Violations No violations recorded
CONTAINER DAMAGEDDeficiency
Containers AreaDeficiency Location/Instance
2Deficiency Quantity
Quantity Uom EACH
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Containers Area
Violations No violations recorded
InspectedDRAINAGE SYSTEM FOR ASPHALT
InspectedCatch Basins/Manhole - Surrounded by Asphalt
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Page 28 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
SITE
DRAINAGE SYSTEM FOR ASPHALT
Does not existCulverts - Asphalt Covering
InspectedDRAINAGE SYSTEM FOR CONCRETE
InspectedCatch Basins/Manhole - Surrounded by Concrete
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existCulverts - Concrete Covering
InspectedDRAINAGE SYSTEM FOR SOIL
InspectedCatch Basins/Manhole - Surrounded by Soil
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
Does not existCulverts - Soil Covering
Does not existDRINKING FOUNTAINS
InspectedFENCES
Condition 3- Fair
CHAIN LINK:DAMAGED/DETERIORATEDDeficiency
Along South Goff Avenue, Latourette StreetDeficiency Location/Instance
150Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along Latourette Street
Violations No violations recorded
CHAIN LINK:DAMAGED POST/RAILDeficiency
Along South Goff Avenue, Latourette Street, Everett PlaceDeficiency Location/Instance
60Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along Latourette Street
Violations No violations recorded
CONCRETE CURB:DAMAGED/DETERIORATEDDeficiency
Along Latourette Street, Cordelia Avenue, Everett PlaceDeficiency Location/Instance
90Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
Page 29 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
SITE
FENCES
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along Cordelia Avenue
Violations No violations recorded
Does not existIRRIGATION SYSTEM
InspectedPAVING
InspectedDOT Sidewalk
Does not existAsphalt
InspectedConcrete
4- Between Fair and PoorCondition
DAMAGED CURBSDeficiency
Along South Goff Avenue, Latourette Street, Cordelia Avenue,
Everett Place
Deficiency Location/Instance
155Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along South Goff Avenue
Violations No violations recorded
DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency
Along South Goff Avenue, Latourette Street, Cordelia Avenue,
Everett Place
Deficiency Location/Instance
1,050Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along South Goff Avenue
Violations No violations recorded
Page 30 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
HEAVINGDeficiency
Along South Goff Avenue, Latourette Street, Cordelia AvenueDeficiency Location/Instance
425Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along South Goff Avenue
Violations No violations recorded
Does not existPavers
InspectedSite Sidewalks & Walkways
Does not existAsphalt
InspectedConcrete
3- FairCondition
DAMAGED CURBSDeficiency
Along South Goff Avenue, Cordelia Avenue, Everett PlaceDeficiency Location/Instance
55Deficiency Quantity
Quantity Uom L.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along South Goff Avenue
Violations No violations recorded
CRACKS - MAJORDeficiency
Along South Goff Avenue, Cordelia Avenue, Everett PlaceDeficiency Location/Instance
350Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 31 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
SITE
PAVING
Site Sidewalks & Walkways
Concrete
Deficiency Photo 1
Along Cordelia Avenue
Violations No violations recorded
Does not existPavers
InspectedStudent Non-Use
Gravel Exists? No
Does not existAsphalt
InspectedConcrete
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existPavers
InspectedStudent Use
Gravel Exists? No
InspectedAsphalt
4- Between Fair and PoorCondition
CRACKS - MAJORDeficiency
SchoolyardDeficiency Location/Instance
1,950Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Schoolyard
Violations No violations recorded
InspectedConcrete
3- FairCondition
CRACKS - MAJORDeficiency
CourtyardDeficiency Location/Instance
300Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Page 32 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
SITE
PAVING
Student Use
Concrete
Deficiency Photo 1
Courtyard
Violations No violations recorded
InspectedPavers
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedPLAYGROUNDS
Along Everett PlaceInstance
Along CordeliaInstance
Benches
Instance on Along Everett Place Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Along Cordelia Does not exist
Fence
Instance on Along Everett Place Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Along Cordelia Does not exist
Pavement
Instance on Along Everett Place Inspected
3- FairInstance Condition
ASPHALT:CRACKS - MAJORDeficiency
PlaygroundDeficiency Location/Instance
130Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Playground
Violations No violations recorded
Instance on Along Cordelia Does not exist
Play Equipment
Instance on Along Everett Place Inspected
2- Between Good and FairInstance Condition
Page 33 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
SITE
PLAYGROUNDS
Play Equipment
No deficiencies recordedDeficiency
Instance on Along Cordelia Inspected
1- GoodInstance Condition
No deficiencies recordedDeficiency
Safety Surfacing
Instance on Along Everett Place Inspected
2- Between Good and FairInstance Condition
No deficiencies recordedDeficiency
Instance on Along Cordelia Inspected
1- GoodInstance Condition
No deficiencies recordedDeficiency
Unpaved Area
Instance on Along Everett Place Does not exist
Instance on Along Cordelia Does not exist
Does not existPLAYING SURFACE
InspectedRETAINING WALLS
Condition 2- Between Good and Fair
Are there any Retaining Walls 6' OR higher facing public street/sidewalk? No
CAST IN PLACE CONCRETE:CRACKS/SPALLING - MAJORDeficiency
Along Cordelia Avenue, SchoolyardDeficiency Location/Instance
20Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 3Urgency of Action
LEVEL 2Purpose of Action
Deficiency Photo 1
Along Cordelia Avenue
Violations No violations recorded
InspectedSEATING
InspectedBenches
InspectedConcrete
2- Between Good and FairCondition
No deficiencies recordedDeficiency
InspectedMetal/Wood/Plastic
2- Between Good and FairCondition
No deficiencies recordedDeficiency
Does not existBleachers
Does not existSITE WALLS (NOT RETAINING WALLS)
InspectedSTAIRS/RAMPS: EXTERIOR
InspectedRailings
Condition 2- Between Good and Fair
No deficiencies recordedDeficiency
InspectedSite Cheek/flank Walls
Condition 2- Between Good and Fair
Page 34 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)
NYC Department of Education
Building Condition Assessment Survey 2019-2020
R003Architectural Inspection
Question Response
SITE
STAIRS/RAMPS: EXTERIOR
Site Cheek/flank Walls
CAST IN PLACE CONCRETE:CRACKS/SPALLING - MAJORDeficiency
Near Exit 10Deficiency Location/Instance
10Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 4Urgency of Action
LEVEL 4Purpose of Action
Deficiency Photo 1
Near Exit 10
Violations 35341935Z
InspectedStairs/ramps
Condition 3- Fair
CAST IN PLACE CONCRETE:CRACKS/SPALLING - MAJORDeficiency
Near Exit 10Deficiency Location/Instance
80Deficiency Quantity
Quantity Uom S.F.
Potential Action REPLACE
PRIORITY 5Urgency of Action
LEVEL 6Purpose of Action
Deficiency Photo 1
Near Exit 10
Violations 35341935Z
Page 35 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)