NYC Department of Education Building Condition Assessment Survey 2019-2020 R003 Architectural Inspection Inspection Type Last Edited Time In InspectionId P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ISLAND, NY, 10309 School: 3433 2020-02-10 06:12AM 2020-02-12 03:01PM ARCHITECTURAL - SENIOR 3450 2020-02-10 08:59AM 2020-08-24 02:23PM ARCHITECTURAL - ASSOCIATE Asset Data Question Answer Was the Building Fully Accessible for Inspection? Yes Principal(s) Information Principal Name Elmer Myers Principal Organization P.S. 3 - Staten Island Meeting with Principal? Yes Principal Feedback The Principal provided the following comments: 1- The Heating and Cooling in the building is inconsistent from room to room and requires control adjustment or upgrades. 2- The Playground surface is deteriorated and need refinishing. 3- The sidewalk around the building is deteriorated and need replacement . Custodian William Purdy III Fireman Mike Magliaccio Building Square Footage 66,000 Comments on the Area (Square Feet) N/A Comments on the Stories (Floors) plus Basements 1+B Comments on the Year Built 1959 Comments on the Student Population 675 Comments on the Staff Population 100 Comments on the Number of Classrooms 32 Weather Heavy Rain Facade Photo Corner of South Goff Avenue and Latourette Street - Southwest View Page 1 of 35 Print Date: 9/11/2020 Mobile Validity Version 2.0 (P)

Transcript of P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building...

Page 1: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Inspection Type Last EditedTime InInspectionId

P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ISLAND, NY, 10309School:

3433 2020-02-10 06:12AM 2020-02-12 03:01PMARCHITECTURAL - SENIOR

3450 2020-02-10 08:59AM 2020-08-24 02:23PMARCHITECTURAL - ASSOCIATE

Asset DataQuestion Answer

Was the Building Fully Accessible for Inspection? Yes

Principal(s) Information

Principal Name Elmer Myers

Principal Organization P.S. 3 - Staten Island

Meeting with Principal? Yes

Principal Feedback The Principal provided the following comments:

1- The Heating and Cooling in the building is inconsistent from

room to room and requires control adjustment or upgrades.

2- The Playground surface is deteriorated and need refinishing.

3- The sidewalk around the building is deteriorated and need

replacement .

Custodian William Purdy III

Fireman Mike Magliaccio

Building Square Footage 66,000

Comments on the Area (Square Feet) N/A

Comments on the Stories (Floors) plus Basements 1+B

Comments on the Year Built 1959

Comments on the Student Population 675

Comments on the Staff Population 100

Comments on the Number of Classrooms 32

Weather Heavy Rain

Facade Photo

Corner of South Goff Avenue and Latourette Street - Southwest

View

Page 1 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 2: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural InspectionMain Entrance Photo

80 South Goff Avenue

Roof Photo

Roof 1 - North View

Have any Systems/Major Building Components been upgraded? Systems: HC Accessibility upgrade with Elevator, New Unisex

Toilet Room (in Cafeteria)

Years: 2009

Systems: Roofing replacement with Drains, Barrier, Roof 1-4,

New Exterior Metal Panels, Windows/Guards

replacement (full), Exterior Masonry repointing (

partial-Original Building), Exterior Doors replacement

(partial )

Years: 2015

Systems: Partial replacement of Playground surface; Library AC

upgraded .

Years: 2019

2004 (6100 SF)Have there been any New Building Additions?

1967 (37400 SF)

Tandem No Tandem

Leased Space? No

Priority ConditionExist

Last Year?

Priority

Category

Condition

Description

Component

Affected

Location

Description

Person(s)

Notified

Person(s)

Title

Photo

Image

Tripping Hazards Severely damaged stairs

treads pose a potential

tripping hazard

Site

Stairs/Ramps

Near Exit 10 Mike

Magliaccio

Yes Fireman

Page 2 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 3: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Structural Engineer Required

Structural

Condition Type

Condition

Description

Component

Affected

Location

Description

Person(s)

Notified

Person(s)

Title

Photo

Image

No condition recorded

Accessibility

Accessibility Status Question Response

Is the Primary or secondary entrance on an accessible route? Yes

Is the building a multi-story building? Yes

Are All floors of the building accessible through compliant means? Yes

Accessible classrooms exists on each floor? Yes

Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes

If the following spaces exist, are they ALL accessible? Art Room, Auditorium,

Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs

Yes

Physical Breakdown Structure Exists Complies Required DeficiencyAudio

Induction

System

Fire

Alarm

Strobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

YesExterior Entrances & Exits

NoNoExterior H/C Lifts

YesYesExterior Ramps and Railings

Interior Routes

NoNoCorridor and Lobby H/C Lifts

YesYesInterior Corridor Doors And

Hardware

YesInterior Corridors & Lobbies

YesYesInterior Elevators

YesInterior Lobby Doors And Hardware

YesYesInterior Ramps

Rooms & Spaces

Art Rooms

Yes YesRoom 127

Auditorium

Yes Yes1st Floor Yes Yes

Cafeteria

Yes Yes1st Floor - Students Yes Yes

Yes Yes1st Floor - Staff No No

Classrooms

Yes Yes1st Floor

Computer Rooms

Yes YesRoom 145

Gymnasium

Yes YesBasement Yes Yes

Library

Yes YesRoom 138

Main Office

Yes YesRoom 157

NoMulti-purpose Room

Nurse's Office

Yes YesRoom 119

NoPool

Page 3 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 4: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Physical Breakdown Structure Exists Complies Required DeficiencyAudio

Induction

System

Fire

Alarm

Strobe

NoScience Lab

Toilet Rooms (boys)

Yes Yes1st Floor within

Cafeteria-Unisex

Toilet Rooms (girls)

Yes Yes1st Floor within

Cafeteria-Unisex

Toilet Rooms (staff)

Yes Yes1st Floor 2004 Wing -

Unisex

Building Template

Inspection

Question Response

Architectural

ATHLETIC FIELDS Does not exist

EXTERIOR Inspected

InspectedAREAWAY

Instance on AW1-AW2 Inspected

2- Between Good and FairInstance Condition

Instance Quantity 2

Instance Quantity Uom EACH

No deficiencies recordedDeficiency

Does not existAWNINGS AND CANOPIES

InspectedCHIMNEY

MasonryMaterial Type(s)

Condition 3- Fair

BRICK:MISSING CAPDeficiency

Deficiency Location/Instance

20Deficiency Quantity

Page 4 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 5: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

EXTERIOR

CHIMNEY

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Chimney 1

Violations No violations recorded

InspectedCOPING

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existCORNICE

InspectedDOORS

InspectedDOOR HARDWARE

Condition 3- Fair

No deficiencies recordedDeficiency

InspectedDOORS AND FRAMES

Condition 3- Fair

METAL:DETERIORATED DOOR AND FRAME - MAJOR

DETERIORATION

Deficiency

Deficiency Location/Instance

2Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade K - Main Entrance

Violations No violations recorded

METAL:DETERIORATED DOOR AND FRAME - MINOR

DETERIORATION

Deficiency

Page 5 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 6: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES

Deficiency Location/Instance

5Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade I - Exit 9

Violations No violations recorded

InspectedLINTELS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedTRANSOM/SIDE LIGHT

Condition 3- Fair

METAL:DENTED, MINOR RUSTINGDeficiency

Deficiency Location/Instance

12Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade A - Exit 4

Violations No violations recorded

InspectedEXTERIOR SOFFITS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Page 6 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 7: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

EXTERIOR

InspectedEXTERIOR WALLS

MasonryMaterial Type(s)

18,000Replacement Quantity

Replacement Uom S.F.

Instance on Metal, Glass Curtain Walls: Original, 1967 Wing Inspected

2- Between Good and FairInstance Condition

Instance Quantity 8,000

Instance Quantity Uom S.F.

No deficiencies recordedDeficiency

Instance on Masonry: 2004 Wing Inspected

2- Between Good and FairInstance Condition

Instance Quantity 6,000

Instance Quantity Uom S.F.

No deficiencies recordedDeficiency

Instance on Brick: Original, 1967 Wing Inspected

3- FairInstance Condition

Instance Quantity 4,000

Instance Quantity Uom S.F.

STONE:OPEN JOINTSDeficiency

Roof Plan Reference

Elevation

Elevation Reference Facades A, C, I, K

25Deficiency Quantity

Quantity Uom L.F.

Potential Action REPOINT

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade A

Violations No violations recorded

BRICK:OPEN JOINTSDeficiency

Page 7 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 8: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

EXTERIOR

EXTERIOR WALLS

Roof Plan Reference

Elevation

Elevation Reference Facades A, B, C, I, K

120Deficiency Quantity

Quantity Uom S.F.

Potential Action REPOINT

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade B

Violations No violations recorded

BRICK:CRACKS/DISPLACED/SPALLED BRICK AT

BUILDING CORNERS

Deficiency

Roof Plan Reference

Elevation

Elevation Reference Facade C

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REMOVE AND REBUILD

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Page 8 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 9: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

EXTERIOR

EXTERIOR WALLS

Deficiency Photo 1

Facade C

Violations No violations recorded

Does not existLOADING DOCK

InspectedLOUVER

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedPARAPETS

ConcreteMaterial Type(s)

3,000Replacement Quantity

Replacement Uom C.F.

Instance on 2004 Wing Inspected

2- Between Good and FairInstance Condition

Instance Quantity 3,000

Instance Quantity Uom CF

No deficiencies recordedDeficiency

Does not existPLAZA DECK

InspectedROOF

InspectedROOFING

Replacement Quantity 57,000

Replacement Uom S.F.

InspectedLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedROOF BARRIER

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existROOF CAGE

InspectedROOF FENCE

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedROOF HATCH/SMOKE HATCH

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedROOFING

Instance on Modified Bitumen:Roofs 1-4 Inspected

1- GoodInstance Condition

Instance Quantity 48,000

Instance Quantity Uom S.F.

“Does the roof have major mechanical equipment sitting on Dunnage

Steel less than 18" above the Roofing?"

No

Installation Year 2015

Source of Installation Year Documented

No deficiencies recordedDeficiency

Instance on Built-Up:Roof 5 Inspected

Page 9 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 10: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

EXTERIOR

ROOF

ROOFING

ROOFING

3- FairInstance Condition

Instance Quantity 3,000

Instance Quantity Uom S.F.

“Does the roof have major mechanical equipment sitting on Dunnage

Steel less than 18" above the Roofing?"

No

Installation Year 1991

Source of Installation Year Custodial Staff

BUILT-UP:ROOFING:LOSS OF GRAVELDeficiency

Deficiency Location/Instance

200Deficiency Quantity

Quantity Uom S.F.

Potential Action INSTALL NEW GRAVEL

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Roof 5

Violations No violations recorded

Instance on Single Ply, Fully Adhered Roof:Roof 6 Inspected

3- FairInstance Condition

Instance Quantity 6,000

Instance Quantity Uom S.F.

“Does the roof have major mechanical equipment sitting on Dunnage

Steel less than 18" above the Roofing?"

No

Installation Year 2004

Source of Installation Year Documented

SINGLE PLY, FULLY ADHERED ROOF:ROOFING:OPEN

SEAMS

Deficiency

Deficiency Location/Instance

60Deficiency Quantity

Quantity Uom L.F.

Potential Action REPAIR

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Page 10 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 11: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

EXTERIOR

ROOF

ROOFING

ROOFING

Deficiency Photo 1

Roof 6

Violations No violations recorded

InspectedROOFING DRAINS

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedSPECIALTIES

Does not existBULKHEAD/PENTHOUSE

Does not existCUPOLA/ SPIRES/ TOWERS

Does not existDORMER

Does not existDUNNAGE STEEL

Does not existROOF/GRAVITY TANK

Does not existSKYLIGHT/ROOF VENT

InspectedSTAIRS/RAMPS: EXTERIOR

InspectedBUILDING CHEEK/FLANK WALLS

Condition 3- Fair

BRICK:CRACKS/SPALLING - MINORDeficiency

Deficiency Location/Instance

6Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade K - Exit 11

Violations No violations recorded

CAST IN PLACE CONCRETE:CRACKS/SPALLING - MINORDeficiency

Page 11 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 12: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

BUILDING CHEEK/FLANK WALLS

Deficiency Location/Instance

8Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade B - Exit 5

Violations No violations recorded

InspectedRAILINGS

Condition 3- Fair

DAMAGEDDeficiency

Deficiency Location/Instance

5Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade - Exit 5

Violations No violations recorded

RUST - MINORDeficiency

Page 12 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 13: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

RAILINGS

Deficiency Location/Instance

8Deficiency Quantity

Quantity Uom L.F.

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade C - Exit 7

Violations No violations recorded

InspectedSTAIRS/RAMPS

Condition 4- Between Fair and Poor

STONE:CRACKS, SPALLINGDeficiency

Deficiency Location/Instance

5Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade K - Exit 11

Violations No violations recorded

CONCRETE:CRACKS/SPALLING - MINORDeficiency

Page 13 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 14: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

STAIRS/RAMPS

Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade B - Exit 5

Violations No violations recorded

CONCRETE:CRACKS/SPALLING - MAJORDeficiency

Deficiency Location/Instance

5Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade B - Exit 6

Violations No violations recorded

InspectedWINDOWS

7,000Replacement Quantity

Replacement Uom S.F.

InspectedEXTERIOR GUARDS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedLINTELS

Condition 2- Between Good and Fair

Page 14 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 15: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

EXTERIOR

WINDOWS

LINTELS

No deficiencies recordedDeficiency

InspectedWINDOWS

Material Type(s) Aluminum

Instance on Aluminum - Double Hung:Original Building and 1967

Wing

Inspected

1- GoodInstance Condition

Instance Quantity 6,000

Instance Quantity Uom S.F.

Installation Year 2015

Source of Installation Year Documented

No deficiencies recordedDeficiency

Instance on Aluminum - Double Hung:2004 Wing Inspected

2- Between Good and FairInstance Condition

Instance Quantity 1,000

Instance Quantity Uom S.F.

Installation Year 2004

Source of Installation Year Documented

No deficiencies recordedDeficiency

INTERIOR Inspected

AUDITORIUM

Instance on 1st Floor (201 Seats) Inspected

Ceiling

Instance on 1st Floor (201 Seats) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on 1st Floor (201 Seats) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed H/C Lift

Instance on 1st Floor (201 Seats) Does not exist

Fixed Seating

Instance on 1st Floor (201 Seats) Inspected

3- FairInstance Condition

DAMAGED/BROKEN/INOPERABLEDeficiency

Seats A/4, B/105, 113, E/104, H/3 and other locationsDeficiency Location/Instance

14Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Seat A/4

Violations No violations recorded

Floor Finish

Page 15 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 16: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

INTERIOR

AUDITORIUM

Floor Finish

Instance on 1st Floor (201 Seats) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Sliding-folding Partition

Instance on 1st Floor (201 Seats) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Stage

Instance on 1st Floor (201 Seats) Inspected

Stage

Instance on 1st Floor (201 Seats) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Stage Curtain Rigging

Instance on 1st Floor (201 Seats) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Stage Curtains

Instance on 1st Floor (201 Seats) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Walls

Instance on 1st Floor (201 Seats) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Window Curtains/Shades/Blinds

Instance on 1st Floor (201 Seats) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

CAFETERIA

Instance on 1st Floor - Students Inspected

Instance on 1st Floor - Staff Inspected

Ceiling

Instance on 1st Floor - Students Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on 1st Floor - Staff Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on 1st Floor - Students Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on 1st Floor - Staff Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed Equipment

Instance on 1st Floor - Students Does not exist

Instance on 1st Floor - Staff Does not exist

Floor Finish

Page 16 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 17: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

INTERIOR

CAFETERIA

Floor Finish

Instance on 1st Floor - Students Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on 1st Floor - Staff Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Sliding-folding Partition

Instance on 1st Floor - Students Not required

Instance on 1st Floor - Staff Does not exist

Stage

Instance on 1st Floor - Students Does not exist

Instance on 1st Floor - Staff Does not exist

Walls

Instance on 1st Floor - Students Inspected

2- Between Good and FairInstance Condition

GLAZED BLOCK:CRACKS/SPALLINGDeficiency

North Side of RoomDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

North Side of Room

Violations No violations recorded

MASONRY:CRACKS/SPALLINGDeficiency

West Side of RoomDeficiency Location/Instance

80Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

West Side of Room

Violations No violations recorded

Instance on 1st Floor - Staff Inspected

2- Between Good and FairInstance Condition

PLASTER:CRACKS/SPALLINGDeficiency

Page 17 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 18: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

INTERIOR

CAFETERIA

Walls

Near EntranceDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Near Entrance

Violations No violations recorded

Window Curtains/Shades/Blinds

Instance on 1st Floor - Students Does not exist

Instance on 1st Floor - Staff Does not exist

InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES

InspectedCeiling

Condition 2- Between Good and Fair

PLASTER:CRACKS/SPALLINGDeficiency

Exit 5Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Exit 5

Violations No violations recorded

ACOUSTIC TILES ON PLASTER:DAMAGED/MISSINGDeficiency

Corridor near Room 142Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 18 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 19: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Ceiling

Deficiency Photo 1

Corridor near Room 142

Violations No violations recorded

InspectedDoor(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFloor Finish

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existSpecialties

InspectedWalls

Condition 2- Between Good and Fair

PLASTER:CRACKS/SPALLINGDeficiency

Corridor near Room 101A, 103, 116, 128, 133 and other locationsDeficiency Location/Instance

75Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Corridor near Room 101A

Violations No violations recorded

GLAZED BLOCK:CRACKS/SPALLINGDeficiency

Corridor near Rooms 142, 146, 147, 152 and other locationsDeficiency Location/Instance

25Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Corridor near Room 142

Page 19 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 20: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Walls

Violations No violations recorded

CERAMIC TILE:BROKEN/ MISSINGDeficiency

Main Entrance LobbyDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Main Entrance Lobby

Violations No violations recorded

GYMNASIUM

Instance on Basement Inspected

Ceiling

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed Equipment

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Seating

Instance on Basement Does not exist

Sliding-folding Partition

Instance on Basement Does not exist

Stage

Instance on Basement Does not exist

Walls

Instance on Basement Inspected

2- Between Good and FairInstance Condition

GLAZED BLOCK:CRACKS/SPALLINGDeficiency

North, East Side of RoomDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 20 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 21: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

INTERIOR

GYMNASIUM

Walls

Deficiency Photo 1

North Side of Room

Violations No violations recorded

PLASTER:CRACKS/SPALLINGDeficiency

North Side of RoomDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

North Side of Room

Violations No violations recorded

Window Curtains/Shades/Blinds

Instance on Basement Does not exist

InspectedINTERIOR DOOR HARDWARE

Condition 3- Fair

No deficiencies recordedDeficiency

InspectedINTERIOR GUARDS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

KITCHEN

Instance on 1st Floor Inspected

Ceiling

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

CERAMIC TILE:BROKEN/MISSING TILESDeficiency

Servery AreaDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Page 21 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 22: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

INTERIOR

KITCHEN

Floor Finish

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Servery Area

Violations No violations recorded

Walls

Instance on 1st Floor Inspected

3- FairInstance Condition

PLASTER:CRACKS/SPALLINGDeficiency

Mop Room, StorageDeficiency Location/Instance

75Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Mop Room

Violations No violations recorded

GLAZED BLOCK:CRACKS/SPALLINGDeficiency

Near ExitDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Near Exit

Violations No violations recorded

LIBRARY

Instance on Room 138 Inspected

Page 22 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 23: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

INTERIOR

LIBRARY

Built-in Furnishing

Instance on Room 138 Does not exist

Ceiling

Instance on Room 138 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on Room 138 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on Room 138 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Walls

Instance on Room 138 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Does not existLOCKER ROOM

Does not existMULTI-PURPOSE ROOM

Does not existPOOLS

Does not existSCIENCE DEMO ROOM

Does not existSCIENCE LAB

Does not existSCIENCE PREP ROOM

Does not existSHOWER ROOM

InspectedSTAIRS/RAMPS: INTERIOR

Do Letter Stair Signs Exist? Yes

InspectedCeiling

Condition 2- Between Good and Fair

PLASTER:CRACKS/SPALLINGDeficiency

Stair A/BasementDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Stair A/Basement

Violations No violations recorded

InspectedDoor(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existPartition

InspectedRailings

Condition 2- Between Good and Fair

Page 23 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 24: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Railings

No deficiencies recordedDeficiency

InspectedStairs and Landings

Condition 2- Between Good and Fair

VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency

Exit 9Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Exit 9

Violations No violations recorded

STONE:BROKEN/MISSINGDeficiency

Stair A/1Deficiency Location/Instance

15Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Stair A/1

Violations No violations recorded

InspectedWalls

Condition 2- Between Good and Fair

GLAZED BLOCK:CRACKS/SPALLINGDeficiency

Stair A/Basement, 1Deficiency Location/Instance

15Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 24 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 25: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Walls

Deficiency Photo 1

Stair A/Basement

Violations No violations recorded

InspectedSTRUCTURAL

InspectedCOLUMNS/BEAMS/BEARING WALLS

Condition 3- Fair

MASONRY BEARING WALL:CRACKED/SPALLEDDeficiency

BasementDeficiency Location/Instance

40Deficiency Quantity

Quantity Uom S.F.

Potential Action RESTITCH

PRIORITY 3Urgency of Action

LEVEL 5Purpose of Action

Deficiency Photo 1

Room B9

Violations No violations recorded

InspectedFLOOR STRUCTURE

Condition 3- Fair

CONCRETE SLAB ON GRADE:MINOR CRACKSDeficiency

BasementDeficiency Location/Instance

40Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 5Purpose of Action

Deficiency Photo 1

Mechanical Room ( B6 )

Violations No violations recorded

InspectedFOUNDATION WALLS

Material Type(s) Concrete

Condition 3- Fair

Page 25 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 26: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

INTERIOR

STRUCTURAL

FOUNDATION WALLS

CONCRETE:WATER INFILTRATION IN NON-

INSTRUCTIONAL SPACE

Deficiency

BasementDeficiency Location/Instance

60Deficiency Quantity

Quantity Uom S.F.

Potential Action INSTALL WATERPROOFING

PRIORITY 5Urgency of Action

LEVEL 5Purpose of Action

Deficiency Photo 1

Oil Tank Room

Violations No violations recorded

CONCRETE:CRACKED/SPALLED/REINFORCEMENT

EXPOSED

Deficiency

Basement and Facade CDeficiency Location/Instance

40Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 5Purpose of Action

Deficiency Photo 1

Facade C

Deficiency Photo 2

Room B7

Violations No violations recorded

InspectedROOF STRUCTURE

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existVAULTS-BUNKERS

InspectedTOILET ROOMS - STAFF

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Page 26 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 27: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

INTERIOR

TOILET ROOMS - STAFF

InspectedDoor(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFloor Finish

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWalls

Condition 2- Between Good and Fair

CERAMIC TILE:BROKEN/ MISSINGDeficiency

Rooms 113, 132Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 132

Violations No violations recorded

InspectedTOILET ROOMS - STUDENTS

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 3- Fair

WOOD:DETERIORATED DOORDeficiency

Room B5Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room B5

Violations No violations recorded

InspectedFloor Finish

Condition 2- Between Good and Fair

Page 27 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 28: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Floor Finish

No deficiencies recordedDeficiency

InspectedStalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

LIFE SAFETY Inspected

Does not existF.D. HOLDING AREA

Does not existSTEEL STAIRS

SITE Inspected

InspectedCONTAINERIZATION

Condition 5- Poor

FENCING DAMAGEDDeficiency

Containers AreaDeficiency Location/Instance

120Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Containers Area

Violations No violations recorded

CONTAINER DAMAGEDDeficiency

Containers AreaDeficiency Location/Instance

2Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Containers Area

Violations No violations recorded

InspectedDRAINAGE SYSTEM FOR ASPHALT

InspectedCatch Basins/Manhole - Surrounded by Asphalt

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Page 28 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 29: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

SITE

DRAINAGE SYSTEM FOR ASPHALT

Does not existCulverts - Asphalt Covering

InspectedDRAINAGE SYSTEM FOR CONCRETE

InspectedCatch Basins/Manhole - Surrounded by Concrete

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existCulverts - Concrete Covering

InspectedDRAINAGE SYSTEM FOR SOIL

InspectedCatch Basins/Manhole - Surrounded by Soil

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existCulverts - Soil Covering

Does not existDRINKING FOUNTAINS

InspectedFENCES

Condition 3- Fair

CHAIN LINK:DAMAGED/DETERIORATEDDeficiency

Along South Goff Avenue, Latourette StreetDeficiency Location/Instance

150Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along Latourette Street

Violations No violations recorded

CHAIN LINK:DAMAGED POST/RAILDeficiency

Along South Goff Avenue, Latourette Street, Everett PlaceDeficiency Location/Instance

60Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along Latourette Street

Violations No violations recorded

CONCRETE CURB:DAMAGED/DETERIORATEDDeficiency

Along Latourette Street, Cordelia Avenue, Everett PlaceDeficiency Location/Instance

90Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

Page 29 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 30: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

SITE

FENCES

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along Cordelia Avenue

Violations No violations recorded

Does not existIRRIGATION SYSTEM

InspectedPAVING

InspectedDOT Sidewalk

Does not existAsphalt

InspectedConcrete

4- Between Fair and PoorCondition

DAMAGED CURBSDeficiency

Along South Goff Avenue, Latourette Street, Cordelia Avenue,

Everett Place

Deficiency Location/Instance

155Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along South Goff Avenue

Violations No violations recorded

DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency

Along South Goff Avenue, Latourette Street, Cordelia Avenue,

Everett Place

Deficiency Location/Instance

1,050Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along South Goff Avenue

Violations No violations recorded

Page 30 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 31: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

SITE

PAVING

DOT Sidewalk

Concrete

HEAVINGDeficiency

Along South Goff Avenue, Latourette Street, Cordelia AvenueDeficiency Location/Instance

425Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along South Goff Avenue

Violations No violations recorded

Does not existPavers

InspectedSite Sidewalks & Walkways

Does not existAsphalt

InspectedConcrete

3- FairCondition

DAMAGED CURBSDeficiency

Along South Goff Avenue, Cordelia Avenue, Everett PlaceDeficiency Location/Instance

55Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along South Goff Avenue

Violations No violations recorded

CRACKS - MAJORDeficiency

Along South Goff Avenue, Cordelia Avenue, Everett PlaceDeficiency Location/Instance

350Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 31 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 32: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

SITE

PAVING

Site Sidewalks & Walkways

Concrete

Deficiency Photo 1

Along Cordelia Avenue

Violations No violations recorded

Does not existPavers

InspectedStudent Non-Use

Gravel Exists? No

Does not existAsphalt

InspectedConcrete

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existPavers

InspectedStudent Use

Gravel Exists? No

InspectedAsphalt

4- Between Fair and PoorCondition

CRACKS - MAJORDeficiency

SchoolyardDeficiency Location/Instance

1,950Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Schoolyard

Violations No violations recorded

InspectedConcrete

3- FairCondition

CRACKS - MAJORDeficiency

CourtyardDeficiency Location/Instance

300Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 32 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 33: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

SITE

PAVING

Student Use

Concrete

Deficiency Photo 1

Courtyard

Violations No violations recorded

InspectedPavers

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedPLAYGROUNDS

Along Everett PlaceInstance

Along CordeliaInstance

Benches

Instance on Along Everett Place Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Along Cordelia Does not exist

Fence

Instance on Along Everett Place Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Along Cordelia Does not exist

Pavement

Instance on Along Everett Place Inspected

3- FairInstance Condition

ASPHALT:CRACKS - MAJORDeficiency

PlaygroundDeficiency Location/Instance

130Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Playground

Violations No violations recorded

Instance on Along Cordelia Does not exist

Play Equipment

Instance on Along Everett Place Inspected

2- Between Good and FairInstance Condition

Page 33 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 34: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

SITE

PLAYGROUNDS

Play Equipment

No deficiencies recordedDeficiency

Instance on Along Cordelia Inspected

1- GoodInstance Condition

No deficiencies recordedDeficiency

Safety Surfacing

Instance on Along Everett Place Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Along Cordelia Inspected

1- GoodInstance Condition

No deficiencies recordedDeficiency

Unpaved Area

Instance on Along Everett Place Does not exist

Instance on Along Cordelia Does not exist

Does not existPLAYING SURFACE

InspectedRETAINING WALLS

Condition 2- Between Good and Fair

Are there any Retaining Walls 6' OR higher facing public street/sidewalk? No

CAST IN PLACE CONCRETE:CRACKS/SPALLING - MAJORDeficiency

Along Cordelia Avenue, SchoolyardDeficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along Cordelia Avenue

Violations No violations recorded

InspectedSEATING

InspectedBenches

InspectedConcrete

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedMetal/Wood/Plastic

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existBleachers

Does not existSITE WALLS (NOT RETAINING WALLS)

InspectedSTAIRS/RAMPS: EXTERIOR

InspectedRailings

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedSite Cheek/flank Walls

Condition 2- Between Good and Fair

Page 34 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)

Page 35: P.S. 3 - STATEN ISLAND, 80 SOUTH GOFF AVENUE, STATEN ... · NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection R003 InspectionId Inspection

NYC Department of Education

Building Condition Assessment Survey 2019-2020

R003Architectural Inspection

Question Response

SITE

STAIRS/RAMPS: EXTERIOR

Site Cheek/flank Walls

CAST IN PLACE CONCRETE:CRACKS/SPALLING - MAJORDeficiency

Near Exit 10Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 4Purpose of Action

Deficiency Photo 1

Near Exit 10

Violations 35341935Z

InspectedStairs/ramps

Condition 3- Fair

CAST IN PLACE CONCRETE:CRACKS/SPALLING - MAJORDeficiency

Near Exit 10Deficiency Location/Instance

80Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 5Urgency of Action

LEVEL 6Purpose of Action

Deficiency Photo 1

Near Exit 10

Violations 35341935Z

Page 35 of 35 Print Date: 9/11/2020Mobile Validity Version 2.0 (P)