CEMCO SLOTTEDTRACK
FLUTED METAL DECKWITH CONCRETE
MINERAL WOOLOR SPRAY FIREPROOFING
5/8" TYPE "X" DRYWALL
#8 x 1/2" FRAMINGSCREW
DRYWALL SCREW1" LOWER THANTRACK LEG
1/2" TO 1" NOMINAL GAP (2" JOINT PROTECTION) CEMCO DEFLECTION
DRIFT ANGLE - DDA(BOTH SIDES)
METAL STUDBY DESIGN
RECTORSEALFLAMESAFE/BIOSTOPSPRAY OVER MINERALWOOL (1/2" OVERLAPMETAL) ON ONE SIDEONLY
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T. GARIBEKIANDATA: 05/24/13APPROVED BY: F. SESMADATE: 05/24/13
SD01
HW-D-0577 STANDARD WALL, PERPENDICULAR TO FLUTED DECK
ASSEMBLY RATING: 1 HR
CEMCO SLOTTEDTRACKDRYWALL SCREW
1" LOWER THANTRACK LEG
5/8" TYPE "X" DRYWALL
1/2" TO 1" NOMINAL GAP(2" JOINT PROTECTION)
#8 x 1/2" FRAMINGSCREW
CEMCO DEFLECTIONDRIFT ANGLE - DDA(BOTH SIDES)
FLUTED METAL DECKWITH CONCRETE
MINERAL WOOLOR SPRAY FIREPROOFING
METAL STUDBY DESIGN
RECTORSEALFLAMESAFE/BIOSTOPSPRAY OVER MINERALWOOL (1/2" OVERLAPMETAL) ON ONE SIDEONLY
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T. GARIBEKIANDATA: 05/24/13APPROVED BY: F. SESMADATE: 05/24/13
SD02
HW-D-0577 STANDARD WALL, PERPENDICULAR TO FLUTED DECK
ASSEMBLY RATING: 2 HR
CEMCO SLOTTEDTRACKDRYWALL SCREW
1" LOWER THANTRACK LEG
5/8" TYPE "X" DRYWALL
34" NOMINAL GAP
(1 12" JOINT PROTECTION)
#8 x 1/2" FRAMINGSCREW
CEMCO DEFLECTIONDRIFT ANGLE - DDA(BOTH SIDES)
FLUTED METAL DECKWITH CONCRETE
SPRAY FIREPROOFING
METAL STUDBY DESIGN
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"
DRAWN BY: T. GARIBEKIANDATA: 11/22/13APPROVED BY: F. SESMADATE: 11/22/13
HW-D-0514 STANDARD WALL, PERPENDICULAR TO FLUTED DECK
CONFIGURATION "A"ASSEMBLY RATING: 2 HR
JOB NO.: UL DETAILSSHEET NO.:
SD02.1
CEMCO SLOTTEDTRACKDRYWALL SCREW
1" LOWER THANTRACK LEG
5/8" TYPE "X" DRYWALL
34" NOMINAL GAP
(1 12" JOINT PROTECTION)
#8 x 1/2" FRAMINGSCREW
CEMCO DEFLECTIONDRIFT ANGLE - DDA(BOTH SIDES)
FLUTED METAL DECKWITH CONCRETE
SPRAY FIREPROOFING
METAL STUDBY DESIGN
Z-CLIP
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"
DRAWN BY: T. GARIBEKIANDATA: 11/22/13APPROVED BY: F. SESMADATE: 11/22/13
HW-D-0514 STANDARD WALL, PERPENDICULAR TO FLUTED DECK
CONFIGURATION "B"ASSEMBLY RATING: 2 HR
JOB NO.: UL DETAILSSHEET NO.:
SD02.2
CEMCO SLOTTEDTRACKDRYWALL SCREW
1" LOWER THANTRACK LEG
5/8" TYPE "X" DRYWALL
34" NOMINAL GAP
(1 12" JOINT PROTECTION)
#8 x 1/2" FRAMINGSCREW
CEMCO DEFLECTIONDRIFT ANGLE - DDA(BOTH SIDES)
FLUTED METAL DECKWITH CONCRETE FILL
METAL STUDBY DESIGN
SPRAY FIREPROOFING
Z-CLIP
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"
DRAWN BY: T. GARIBEKIANDATA: 11/22/13APPROVED BY: F. SESMADATE: 11/22/13
HW-D-0514 STANDARD WALL, PERPENDICULAR TO FLUTED DECK
CONFIGURATION "C"ASSEMBLY RATING: 2 HR
JOB NO.: UL DETAILSSHEET NO.:
SD02.3
#8 x 1/2" FRAMINGSCREW
FLUTED METAL DECKFILLED WITH CONCRETE
DRYWALL SCREW1" LOWER THANTRACK LEG
CEMCO FAS STRAP
5/8" TYPE "X" DRYWALL
1" NOMINAL GAP(2" JOINT PROTECTION)
CEMCO SLOTTEDTRACK
CEMCO DEFLECTIONDRIFT ANGLE - DDA(BOTH SIDES)
METAL STUDBY DESIGN
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T.GARIBEKIANDATA: 05/24/13APPROVED BY: F. SESMADATE: 05/24/13
SD04
HW-D-0524 STANDARD WALL, OFFSET & PARALLEL UNDER FLUTED DECK
CONFIGURATION "A"ASSEMBLY RATING: 2 HR
1" NOMINAL GAP(2" JOINT PROTECTION)
DRYWALL SCREW 1"LOWER THAN TRACKLEG
5/8" TYPE "X" DRYWALL
CEMCO DEFLECTIONDRIFT ANGLE - DDA(BOTH SIDES)
RECTORSEALFLAMESAFE/ BIOSTOPSPRAY OVER MINERALWOOL 1/2" LAP OVERMETAL (ONE SIDEONLY)
CEMCO SLOTTEDTRACK
METAL STUDBY DESIGN
PRE-FORMEDMINERAL WOOL PLUG FLUTED METAL DECK
FILLED WITH CONCRETE
2" STRAP BY DESIGN
#8 x 1/2" FRAMINGSCREW
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T. GARIBEKIANDATA: 05/24/13APPROVED BY: F. SESMADATE: 05/24/13
SD06
HW-D-0524 STANDARD WALL, OFFSET & PARALLEL UNDER FLUTED DECK
CONFIGURATION "B"ASSEMBLY RATING: 2 HR
CEMCO METAL STUDSPACING BY DESIGN
5/8" TYPE"X" DRYWALL
BIOSTOP SPRAYOVER MINERAL WOOL1/2" LAP OVER METAL(ONE SIDE ONLY)
#8 x 1/2" FRAMINGSCREW
DRYWALL SCREW 1"LOWER THAN TRACKLEG
1" NOMINAL GAP(2" JOINT PROTECTION)
STEELBEAM
STRUCTURALFIREPROOFING(THICKNESS BYOTHERS)
EXPANDED METAL LATH
1/2" x 20 GA. Z-BAR OR16 GA. CRC(SPACING BY DESIGN)
MINERAL WOOL 4 PCF COMPRESSED33% IN FLUTE OR SPRAYFIREPROOFING
CONCRETE SLABOR FLUTED METALDECK WITHCONCRETE FILL
CEMCO SLOTTEDTRACK
CEMCO FIRESTIK
CEMCO DEFLECTIONDRIFT ANGLE - DDA
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T.GARIBEKIANDATA: 05/24/13APPROVED BY: F. SESMADATE: 05/24/13
SD08
HW-D-0582 STANDARD WALL, PARALLEL TO BEAM UNDER FLUTED DECK
ASSEMBLY RATING: 2 HR
#8 x 1/2" FRAMINGSCREW
CEMCO SLOTTED TRACK
DRYWALL SCREW1" LOWER THANTRACK LEG
5/8" TYPE "X"DRYWALLMETAL STUDBY DESIGN
BIOSTOP SPRAY OVERMINERAL WOOL1/2" LAP OVER METAL(ONE SIDE ONLY)
MINERAL WOOL
FLUTED METAL DECKWITH CONCRETE FILL
1" NOMINAL GAP(2" JOINT PROTECTION)
CEMCO DEFLECTIONDRIFT ANGLE - DDA(FINISH SIDES OFTHE WALL ONLY)
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T.GARIBEKIANDATA: 05/24/13APPROVED BY: F. SESMADATE:05/24/13
SD10
HW-D-0580 STANDARD CHASE WALL, PERPENDICULAR TO FLUTED DECK
ASSEMBLY RATING: 2 HR
REVISION:
SPRAYFIREPROOFING
CONCRETE SLAB OR FLUTEDMETAL DECK WITH CONCRETE FILL
STEEL BEAM
STRUCTURAL STEELFIREPROOFING(THICKNESS BY OTHERS)
1/2" x 20 GA. Z-BAR OR16 GA. CRC BY DESIGN CEMCO DEFLECTION
DRIFT ANGLE - DDA(BOTH SIDE)
5/8" TYPE"X" DRYWALL
#8 x 1/2" FRAMINGSCREW
DRYWALL SCREW1" LOWER THANTRACK LEG
1" NOMINAL GAP(2" JOINT PROTECTION)
CEMCO SLOTTEDTRACK
METAL STUDBY DESIGN
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T.GARIBEKIANDATA: 05/24/13APPROVED BY: F. SESMADATE: 05/24/13
SD12
HW-D-0579 STANDARD WALL, OFFSET & PARALLEL UNDER BEAM
ASSEMBLY RATING: 2 HR
CONCRETE SLAB OR FLUTEDMETAL DECK WITH CONCRETE FILL
STEEL BEAM
STRUCTURALFIREPROOFING(THICKNESS BY OTHERS)
1/2" x 20 GA. Z-BAR OR16 GA. CRC(SPACING BY DESIGN)
SPRAYFIREPROOFING
EXPANDED METALLATH
CEMCO DEFLECTIONDRIFT ANGLE - DDA(BOTH SIDES)
5/8" TYPE"X" DRYWALL
#8 x 1/2" FRAMINGSCREW
DRYWALL SCREW1" LOWER THAN TRACK LEG
1" NOMINAL GAP (2" JOINT PROTECTION)
CEMCO SLOTTEDTRACK
METAL STUDSPACING BY DESIGN
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T.GARIBEKIANDATA: 05/17/13APPROVED BY: F. SESMADATE: 05/17/13
SD14
HW-D-0652 STANDARD WALL, PARALLEL & CANTILEVERED UNDER BEAM
ASSEMBLY RATING: 2 HR
SPRAYFIREPROOFING
STEEL BEAM
STRUCTURALFIREPROOFING(THICKNESS BY OTHERS)
1/2" x 20 GA. Z-BAR OR16 GA. CRC(SPACING BY DESIGN)
CEMCO DEFLECTIONDRIFT ANGLE - DDA(BOTH SIDES)
CONCRETE SLAB OR FLUTEDMETAL DECK WITH CONCRETE FILL
5/8" TYPE"X" DRYWALL
#8 x 1/2" FRAMINGSCREW
DRYWALL SCREW1" LOWER THAN TRACK LEG
1" NOMINAL GAP(2" JOINT PROTECTION)
CEMCO SLOTTEDTRACK
METAL STUDSPACING BY DESIGN
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T.GARIBEKIANDATA: 05/17/13APPROVED BY: F. SESMADATE: 05/17/13
SD16
HW-D-0579 STANDARD WALL, PARALLEL & CENTERED DIRECTLY UNDER BEAM
ASSEMBLY RATING: 2 HR
L-METAL ANGLEFOR BACKING
CONCRETE SLAB ORFLUTED METAL DECKWITH CONCRETE FILL
STEEL BEAM
STRUCTURAL STEELFIREPROOFING(THICKNESS BY OTHERS)
1/2" x 20 GA. Z-BAR OR16 GA. CRC(SPACING BY DESIGN)
3"MIN
5/8" TYPE"X" DRYWALL
#8 x 1/2" FRAMINGSCREW
DRYWALL SCREW1" LOWER THAN TRACKLEG
1" NOMINAL GAP(2" JOINT PROTECTION)
CEMCO DEFLECTION DRIFTANGLE - DDA (BOTH SIDES)
CEMCO SLOTTED TRACK
METAL STUDBY DESIGN
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T.GARIBEKIANDATA: 05/17/13APPROVED BY: F. SESMADATE: 05/17/13
SD18
HW-D-0579 STANDARD WALL, UNDER STAIRWELL SLAB BYPASS @ BEAM
ASSEMBLY RATING: 2 HR
CONCRETE SLAB ORFLUTED METAL DECKWITH CONCRETE FILL
5/8" TYPE"X" DRYWALL
#8 x 1/2" FRAMINGSCREW
DRYWALL SCREW1" LOWER THAN TRACKLEG
1" NOMINAL GAP(2" JOINT PROTECTION)
CEMCO DEFLECTION DRIFTANGLE - DDA (BOTH SIDES)
CEMCO SLOTTED TRACK
METAL STUDBY DESIGN
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T.GARIBEKIANDATA: 05/21/13APPROVED BY: F. SESMADATE: 05/21/13
SD20
HW-D-0596 STANDARD WALL, @ CONCRETE STAIRWELL SLAB BYPASS
ASSEMBLY RATING: 2 HR
METAL STUDSPACING BY DESIGN
5/8" TYPE"X" DRYWALL
#8 x 1/2" FRAMINGSCREW
DRYWALL SCREW1" LOWER THANTRACK LEG
CONCRETE SLAB ORFLUTED METAL DECKWITH CONCRETE FILL
5/8" NOMINAL GAP(1 1/4"JOINT PROTECTION) CEMCO SLOTTED
TRACK
4 PSF MINERALWOOL
RECTORSEAL SEALANTBETWEEN TRACK ANDCONCRETE
CEMCO DEFLECTION DRIFTANGLE - DDA (BOTH SIDES)
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T.GARIBEKIANDATA: 05/21/13APPROVED BY: F. SESMADATE: 05/21/13
SD22
HW-D-0596 STANDARD WALL, UNDER STAIRWELL SLAB BYPASS @ BEAM WITH
MINERAL WOOL AND SPRAYASSEMBLY RATING: 2 HR
CONCRETE DECK
METAL STUDBY DESIGN
5/8" TYPE "X" DRYWALL
#8 x 1/2" FRAMINGSCREW
1" NOMINAL GAP(2" JOINT PROTECTION)
CEMCO DEFLECTIONDRIFT ANGLE - DDA(BOTH SIDES)
CEMCO SLOTTEDTRACK
DRYWALL SCREW1" LOWER THANTRACK LEG
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T.GARIBEKIANDATA: 05/16/13APPROVED BY: F. SESMADATE: 05/16/13
SD24
HW-D-0620 STANDARD WALL, PARALLEL UNDER FLUTED DECK
CONFIGURATION "A"ASSEMBLY RATING: 2 HR
MINERAL WOOL
CONCRETE DECK
METAL STUDBY DESIGN
5/8" TYPE "X"DRYWALL
#8 x 1/2" FRAMINGSCREW
CEMCO SLOTTEDTRACK
1" NOMINAL GAP(2" JOINT PROTECTION)
CEMCO DEFLECTIONDRIFT ANGLE - DDA(BOTH SIDES)
DRYWALL SCREW1" LOWER THANTRACK LEG
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T.GARIBEKIANDATA: 05/16/13APPROVED BY: F. SESMADATE: 05/16/13
SD26
HW-D-0620 STANDARD WALL, OFFSET & PARALLEL UNDER FLUTED DECK
CONFIGURATION "B"ASSEMBLY RATING: 2 HR
DRYWALL
Z-CLIP
CEMCO SLOTTEDTRACK WITH DDA
BIOSTOP SPRAY OVERMINERAL WOOL AND1/2" OVERLAP ONTODDA BEFORE DRYWALLIS INSTALLED (ONE SIDEOF WALL ONLY)
DRYWALL CUTAROUND I-BEAM WITH2" GAP
1" NOMINAL GAP(2" JOINT PROTECTION)
DDA OVER FRAMING
MINERAL WOOL 4 PCFCOMPRESSED 50% INFLUTE OR SPRAYFIREPROOFING
I-BEAM
DDA OVER FRAMINGCEMCO SLOTTEDTRACK WITH DDA
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T.GARIBEKIANDATA: 05/21/13APPROVED BY: F. SESMADATE: 05/21/13
SD28
HW-D-0583 STANDARD WALL, @ FLUTED DECK BEAM PENETRATION
ASSEMBLY RATING: 2 HR
FLUTED METAL DECKWITH CONCRETE FILL
MINERAL WOOL
BIOSTOP SPRAY OVERMINERAL WOOL 1/2" LAPOVER METAL(ONE SIDE ONLY)
1 1/8" BUNGLE HEADDRYWALL SCREW AT8" O.C.
CH STUD
CEMCO SLOTTEDTRACK
CEMCO DEFLECTIONDRIFT ANGLE - DDA
1" SHAFT LINER
1" NOMINAL GAP(2" JOINT PROTECTION)
MINERAL WOOL
5/8" TYPE "X"DRYWALL
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T.GARIBEKIANDATA: 05/21/13APPROVED BY: F. SESMADATE: 05/21/13
SD30
HW-D-0584 SHAFT WALL, PERPENDICULAR TO FLUTED DECK
ASSEMBLY RATING: 2 HR
CH STUD
CEMCO SLOTTEDTRACK
1" SHAFT LINER
1" NOMINAL GAP(2" JOINT PROTECTION)
MINERAL WOOL
5/8" TYPE "X" DRYWALL
CEMCODEFLECTION DRIFTANGLE - DDA
PRE-FORMEDMINERAL WOOL PLUG
2" STRAP BY DESIGN
FLUTED METAL DECKWITH CONCRETE FILL
RECTORSEAL FLAMESAFE/BIOSTOPSPRAY OVER MINERAL WOOL 1/2"LAP OVER METAL(ONE SIDE ONLY)
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T.G.DATA: 05/15/13APPROVED BY: F. SESMADATE: 05/15/13
SD32
HW-D-0524 SHAFT WALL, OFFSET & PARALLEL UNDER FLUTED DECK
CONFIGURATION "B"ASSEMBLY RATING: 2 HR
FLUTED METAL DECKWITH CONCRETE
CEMCO FAS STRAP
CH STUD
CEMCO SLOTTEDTRACK
CEMCODEFLECTION DRIFTANGLE - DDA
1" SHAFT LINER
1" NOMINAL GAP(2" JOINT PROTECTION)
MINERAL WOOL
5/8" TYPE "X" DRYWALL
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: O.K.DATA: 04/23/13APPROVED BY: F. SESMADATE: 01/29/13
SD34
HW-D-0524 SHAFT WALL, PARALLEL & DIRECTLY UNDER DECK FLUTE
CONFIGURATION "A"ASSEMBLY RATING: 2 HR
STEEL BEAM
CEMCO DEFLECTIONDRIFT ANGLE - DDA
SPRAYFIREPROOFING
CONCRETE SLAB OR FLUTEDMETAL DECK WITH CONCRETE FILL
STRUCTURAL STEELFIREPROOFING(THICKNESS BY OTHERS)
1/2" x 20 GA. Z-BAR OR16 GA. CRC @ 16" O.C.
CH STUD
5/8" TYPE "X" DRYWALL1" SHAFT LINER
CEMCO SLOTTEDTRACKMINERAL WOOL
1" NOMINAL GAP(2" JOINT PROTECTION)
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T.GARIBEKIANDATA: 05/21/13APPROVED BY: F. SESMADATE: 05/21/13
SD36
HW-D-0622 SHAFT WALL, DIRECTLY UNDER BEAM
ASSEMBLY RATING: 2 HR
CONCRETE SLAB OR FLUTEDMETAL DECK WITH CONCRETE FILL
STEEL BEAM
STRUCTURAL FIREPROOFING(THICKNESS BY OTHERS)
CEMCO DEFLECTIONDRIFT ANGLE - DDA
1/2" x 20 GA. Z-BAR OR16 GA. CRC @ 16" O.C.
SPRAYFIREPROOFING
1/2" x 20 GA. Z-BAR OR16 GA. CRC @ 16" O.C.
CH STUD
5/8" TYPE "X" DRYWALL1" SHAFT LINER
CEMCO SLOTTEDTRACKMINERAL WOOL
1" NOMINAL GAP(2" JOINT PROTECTION)
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T.GARIBEKIANDATA: 05/21/13APPROVED BY: F. SESMADATE: 05/21/13
SD38
HW-D-0622 SHAFT WALL, OFFSET UNDER BEAM
ASSEMBLY RATING: 2 HR
CONCRETE SLABOR FLUTED METALDECK WITHCONCRETE FILL
STEEL BEAM
STRUCTURALFIREPROOFING(THICKNESS BY OTHERS)
EXPANDED METALLATH8"
CEMCO DEFLECTIONDRIFT ANGLE - DDA
1/2" x 20 GA. Z-BAR OR16 GA. CRC @ 16" O.C.
SPRAYFIREPROOFING
CH STUD
5/8" TYPE "X" DRYWALL1" SHAFT LINER
CEMCO SLOTTEDTRACKMINERAL WOOL
1" NOMINAL GAP(2" JOINT PROTECTION)
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T.GARIBEKIANDATA: 05/21/13APPROVED BY: F. SESMADATE: 05/21/13
SD40
HW-D-0653 STANDARD SHAFT WALL, PARALLEL & CANTILEVER UNDER BEAM
ASSEMBLY RATING: 2 HR
CONCRETE SLAB ORFLUTED METAL DECKWITH CONCRETE FILL
CEMCO DEFLECTIONDRIFT ANGLE-DDA
CH STUD
5/8" TYPE "X" DRYWALL
1" SHAFT LINER
CEMCO SLOTTEDTRACK
MINERAL WOOL
5/8" NOMINAL GAP(1 1/4" JOINTPROTECTION)
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T.GARIBEKIANDATA: 05/21/13APPROVED BY: F. SESMADATE: 05/21/13
SD42
HW-D-0621 SHAFT WALL, CONCRETE SLAB BYPASS
ASSEMBLY RATING: 2 HR
CH STUD
1" SHAFT LINER
STEELBEAM
STRUCTURALFIREPROOFING(THICKNESS BY OTHERS)
MINERAL WOOL
SPRAYFIREPROOFING
MINERALWOOL
CONCRETE SLAB ORFLUTED METAL DECKWITH CONCRETE FILL
CEMCO SLOTTEDTRACK
EXPANDED METAL LATH
1/2" x 20 GA. Z-BAR OR16 GA. CRC(SPACING BY DESIGN)
CEMCO FIRESTIK
5/8" TYPE "X"DRYWALL
1 1/8" BUNGLE HEADDRYWALL SCREW@ 8" O.C.
1" NOMINAL GAP(2" JOINT PROTECTION)
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: O.K.DATA: 04/29/13APPROVED BY: F. SESMADATE: 04/29/13
SD44
HW-D-0563 SHAFT WALL, PARALLEL TO BEAM UNDER FLUTED DECK
ASSEMBLY RATING: 2 HR
MINERAL WOOL STUFFEDBETWEEN FRAMING ANDFIREPROOFING 50%COMPRESSED
(2) LAYERSDRYWALL
Z-CLIP
CEMCO SLOTTEDTRACK WITH DDA
CH STUD
DRYWALL CUTAROUND I-BEAM WITH2" GAP
1" NOMINAL GAP(2" JOINT PROTECTION)
I-BEAM
DDA OVER FRAMINGDDA OVER FRAMING
BIOSTOP SPRAYOVER MINERAL WOOLAND 1/2 OVERLAPONTO DDA BEFOREDRYWALL ISINSTALLED (ONE SIDEOF WALL ONLY)
CEMCO SLOTTEDTRACK WITH DDA
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T.GARIBEKIANDATA: 05/21/13APPROVED BY: F. SESMADATE: 05/21/13
SD46
HW-D-0623 SHAFT WALL, @ FLUTED DECK BEAM PENETRATION
ASSEMBLY RATING: 2 HR
5/8" TYPE "X" DRYWALL
#8 x 1/2" FRAMINGSCREW
CONCRETE SLAB
METAL STUDSPACING BY DESIGN
TYPICAL STEELFASTENERS BY DESIGN
DRYWALL SCREW1" LOWER THANTRACK LEG
CEMCO SLOTTEDTRACK
CEMCO DEFLECTIONDRIFT ANGLE - DDA(BOTH SIDES)
1" NOMINAL GAP(2" JOINT PROTECTION)
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T.G.DATA: 05/24/13APPROVED BY: F. SESMADATE: 05/24/13
SD64
HW-D-0576 STANDARD WALL, CONCRETE SLAB
ASSEMBLY RATING: 2 HR
CH STUD
CEMCO SLOTTEDTRACK
1" SHAFT LINER
1" NOMINAL GAP(2" JOINT PROTECTION)
MINERAL WOOL
5/8" TYPE "X" DRYWALL
CEMCODEFLECTION DRIFTANGLE - DDA
CONCRETE SLAB
DISCLAIMER:
CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.
263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM
REVISION:
SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:
DRAWN BY: T.GARIBEKIANDATA: 05/24/13APPROVED BY: F. SESMADATE: 05/24/13
SD68
HW-D-0585 SHAFT WALL, CONCRETE SLAB
ASSEMBLY RATING: 2 HR