MAROON 26÷78 kW
General information
Dedicated heat pumps new series with Scroll compressors, with and without vapor injection.
/HT version in 15 sizes
Cooling capacity (A35;W7): 6÷73 KW
Heating capacity (A7;W45): 6÷78 KW
/MT version in 17 sizes
Cooling capacity (A35;W7): 6÷68 KW
Heating capacity (A7;W45): 7÷76 KW
MAROON 2 is a complete dedicated HP series machines which covers the range from 6 to 78kW using the same re-frigerant gas (R410A) with single and double compressors.
Unique selling points
► Wide operating limits and power range
► Automatic management for domestic hot water
► Hws version available for all sizes
► Smarter defrosting management
► A class pumps available for single compressor models
► Modularity and full accessibility
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
2
INDEX
MAROON 2 - SINGLE COMPRESSOR 3MAROON 2 - BI COMPRESSOR 7DESCRIPTION OF THE FUNCTIONS AND ACCESSORIES 10HEAT PUMP INSTALLATION TIPS 18MAROON 2 MT TECHNICAL DATA 20MAROON 2 HT TECHNICAL DATA 22MAROON 2 MT ELECTRICAL DATA 24MAROON 2 HT ELECTRICAL DATA 25EXCHANGER DIAGRAMS - MAROON 2 MT 26EXCHANGER DIAGRAMS - MAROON 2 HT 28COOLING CAPACITIES - MAROON 2 MT 32HEATING CAPACITIES - MAROON 2 MT 34COOLING CAPACITIES - MAROON 2 MT 36HEATING CAPACITIES - MAROON 2 MT 37RECOVERY CAPACITIES - MAROON 2 MT 38COOLING CAPACITIES - MAROON 2 HT 40HEATING CAPACITIES - MAROON 2 HT 42COOLING CAPACITIES - MAROON 2 HT 44HEATING CAPACITIES - MAROON 2 HT 45RECOVERY CAPACITIES - MAROON 2 HT 46SOUND LEVELS - MAROON 2 MT 48SOUND LEVELS - MAROON 2 HT 49SOUND LEVELS - MAROON 2 MT /LN 50SOUND LEVELS - MAROON 2 HT /LN 51MAROON 2 MT DIMENSIONAL LAYOUTS 52MAROON 2 HT DIMENSIONAL LAYOUTS 70
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
3
MAROON 2 - SINGLE COMPRESSORHIGH EFFICIENCY AIR-WATER HEAT PUMPS WITH AXIAL FANS WITH A SINGLE SCROLL COMPRESSOR
PRODUCT DESCRIPTION
STRUCTUREIn galvanised sheet metal and painted with polyester powders RAL 7035 at 180°C, which confer high resistance to atmospheric agents.
The panels can be easily removed to allow total access to the internal components.
All the structures have a condensate drip tray with the relative drain.
MAROON 2/HT COMPRESSORHermetic scroll compressor, complete with circuit breaker protection included in the electric motor windings, sump heater and rubber anti-vibration supports. The compressor used in this series is specifically designed to run as a heat pump. Optimising the compression ratio to high values allows for a superior efficiency to be reached when compared with traditional scroll compressors.
The models in size 13 to 41 are equipped with a liquid injection compressor. Liquid injection allows the heat pump to run at very low outdoor temperatures while producing very hot water.
MAROON 2/MT COMPRESSORHermetic scroll compressor, complete with circuit breaker protection included in the electric motor windings, sump heater and rubber anti-vibration supports. The compressor used in this series is specifically designed to run as a heat pump. Optimising the compression ratio to high values allows for a superior efficiency to be reached when compared with traditional scroll compressors.
USER SIDE EXCHANGERAISI 316 stainless steel braze-welded plate evaporator, housed inside a closed-cell insulating casing, which reduces heat loss and prevents condensation from forming.
The exchanger is equipped with a temperature probe for anti-freeze protection, with a temperature probe for the water inlet and outlet and with a blade flow switch supplied as standard.
SOURCE SIDE EXCHANGERThis consists of a coil with copper pipes and aluminium fins with a high exchange surface with fin spacing sized so as to maximise heat transfer and reduce the noise impact. The space of the fins in the exchanger has been increased so as to allow the unit to work at very low temperatures and very high moisture concentration.
The subcooler is found at the base of the exchanger, which is an additional cooling circuit that prevents the formation of ice in the lower part of the coil and facilitates the flow of condensate during the defrosting operations. The effects
of the subcooler are: reduced defrosting operations and the safety of having a clean heat exchanger at the end of each defrosting operation.
A metal mesh protects the finned core.
FANSHelicoidal fans coupled directly to the electric motor, made of plastic material with a blade profile equipped with WINGLET, a special shape in the end part of the blades, which allows a reduction in the noise and an increase in the aeraulic performance.
The control manages the fan speed through a speed regulator phase cut in order to optimise the operating conditions, efficiency and allow the unit to operate as a heat pump also for high outdoor temperatures.
Moreover, this adjustment has a reduced noise level effect on the unit. In fact, the control device will modulate the speed of the fans at night and during mid-season. This means that every time there it is possible, the machine will minimise the fan speed and also its noise level.
The fans are axial fans directly coupled to the 6-pole electric motor, with an IP 54 degree of protection, with shaped nozzles and a safety grille in accordance with EN 294.
COOLING CIRCUITIt includes: a charging socket in the liquid and inlet line, liquid indicator, a solenoid valve, non-return valves, a dehydrator filter, 2 thermostatic expansion valves (1 for heat pump operation and 1 for chiller operation) equipped with an external pressure equalizer, pressure transducer, high and low pressure switches and a safety valve (excluding 7,9 and 11 for the /HT version and 8, 10 and 12 for the /MT version), liquid receiver and intake separator (sizes 22 to 41 for the /HT versione and 23 to 42 for the /MT version).
The models in the /HT version size 13 to 41 are equipped with an additional circuit for liquid injection to the compressor.
ELECTRIC CONTROL BOARDThe electric control board consists of:
• a main isolating switch and fuse protection of the auxiliary and power circuits
• a compressor remote control switch
• condensation/evaporation control with fan speed regulator
• pump relay or motor protection switch and remote control switch (in /1P, /1PS, /1PV or /1PVS version)
• potential free contacts for general alarm
• microprocessor control.
The standard power supply is:
• 230V/1~/50Hz for size 7 of the /HT version
• 230V/1~/50Hz for sizes 8 and 10 of the /MT version
• 400V/3N~/50Hz for sizes 9 to 41 of the /HT version
• 400V/3N~/50Hz for sizes 12 to 42 of the /MT version.
3-phase power supply is available as an accessory for the single phase models. Single-phase power supply is available as an accessory for certain 3-phase models.
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
4
CONTROLMicroprocessor control for the following functions:
• water temperature adjustment with inlet control
• anti-freeze protection
• compressor timing
• high pressure pre-alarm control
• alarm signals
• alarms reset
• remote on/off digital input
• summer/winter selection digital input.
The display is used to display the following information:
• temperature of the outlet water
• condensation temperature
• set and differential temperature settings
• description of the alarms
• pump and compressor operation counter.
The control integrates the following standard functions:
• automatic control of domestic hot water
• smooth defrosting.
Certain functions are only available with the unit adequately configured. Certain functions must be enabled from the control.
CHECKS AND SAFETY DEVICESthe units are equipped with the following safety devices:
• utility water temperature control probe (situated at the inlet of the utility heat exchanger)
• anti-freeze probe to activate the anti-freeze alarm (manually reset)
• low pressure switch (with automatic reset at limited intervals)
• low pressure switch (automatically reset at limited intervals)
• standard mechanical blade flow meter (manually reset)
• high pressure safety valve (excluding sizes 7, 9 and 11 of the /HT version and sizes 8, 10 and 12 of the /MT version)
• compressor over-heating protection
• control of the condensation pressure using the speed regulator for operation with low outdoor temperatures.
• control of the evaporation pressure using the speed regulator for operation with high outdoor temperatures in domestic hot water production or recovery.
INSPECTIONThe units are inspected in the factory and supplied complete with oil and refrigerant fluid.
VERSIONS/LN: SILENCED UNITAs well as the components of the basic version, the unit has a completely sound insulated compressor compartment made of sound-absorbing material, which is used with sound impeding material.
/HWS: MULTIPURPOSE HEAT PUMPThe unit in this setup is equipped with 2 exchangers: 1 on the
system side for air-conditioning and heating, and 1 dedicated exclusively to the production of domestic water.
T
T
Sufficient cold or hot water can be produced on the unit system side exchanger to meet the heating and cooling requirements of the building according to the seasons.
The unit on the exchanger dedicated to the DHW produces hot water to be sent to a storage tank outside the machine, which is selected and sized according to the system requirements.
The unit runs in different modes according to the season: these are automatically switched (within the season) via the reading of the temperature probes and the set-point settings. Switching times and logic are designed to guarantee maximum system efficiency and reliability.
This configuration must be associated to an adequately sized boiler in which very hot water is stored. The boiler must have a well for the domestic water operating probe to be inserted in the upper part, through which the unit controller will monitor the amount of domestic hot water that must be produced.
Summer operationThere are 3 summer modes:
• Chiller mode: the unit only produces cold chilled water for the system.
• Chiller mode with simultaneous production of domestic hot water: the unit produces chilled water for the system and domestic hot water. The recovered power for the domestic water production is complete.
• Heat pump mode for domestic hot water production: when there is no cold water and the domestic water operating probe is required to run, the unit heats the water inside the domestic water storage tank using the finned core coil as an evaporator. Using the hot external air as a source of heat guarantees the extremely high COP to be achieved.
Switching from one mode to another occurs entirely automatically according to a priority logic in the domestic hot water production and when there is load diversity, thereby recovering the condensation energy for the production of domestic hot water.
Winter operationThere are 2 winter modes:
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
5
• Heat pump mode for heating: the unit produces hot water to the system side exchanger for heating purposes.
• Heat pump for the production of domestic hot water: produces hot water to the connected exchanger of the domestic water storage tank.
Switching from one mode to another occurs entirely automatically according to a priority logic in the domestic hot water production.
In addition to the components of the basic version, the /HWS unit includes:
• a special exchanger for the production of domestic hot water
• a temperature probe to be positioned on the domestic water storage tank
• an electronic thermostatic valve (replaces the 2 mechanical thermostatic valves).
HYDRAULIC MODULE OPTIONS/1P: unit with one pumpThe unit includes a circulator (sizes 7 to 17 of the /HT version and 8 to 20 of the /MT version) or a circulation pump (sizes 22 to 41 of the /HT version and 23 to 42 for the /MT version), an expansion tank, a hydraulic circuit water drain valve, a safety valve set at 6 bar that corresponds to the maximum operating pressure value allowed.
/1PV: unit with variable capacity pumpThe unit includes, for all sizes, an EC A class circulator, an expansion tank, a hydraulic circuit water drain valve, a safety valve set at 6 bar that corresponds to the maximum operating pressure value allowed.
The circulator with an EC motor has a permanent magnet rotor that guarantees very high efficiency levels for each operating condition.
Allows up to 25% of the power consumption of a normal pump of equal power to be saved. The permanent magnets instead of the windings allows the electric motor to be brushless, thereby optimising its efficiency.
If the unit is connected to a system equipped with valves two-way, the pump will vary its flow rate so as to maintain a constant pressure head. In this case the customer will have to provide a bypass or a 3-way valve suitably positioned to ensure a minimum flow rate equal to 50% of nominal flow.
/1PS: unit with pump and tankIn addition to the components of the /1P version, the unit includes an insulated inertial storage tank.
/1PVS: unit with pump and tankIn addition to the components of the /1PV version, the unit includes an insulated inertial storage tank.
/1R: unit with domestic side pumpThe unit is equipped with a pump for the domestic side (supplied). This module can only be matched with the units in the /HWS version and can be combined with the /1P, /1PV, /1PS or /1PVS modules. The /HWS version units with no /1R module are equipped with consent to control an external pump.
The pump used for domestic hot water must be installed in a technical compartment and adequately protected against low temperatures and the risk of its hydronic circuit freezing.
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
6
STANDARD EQUIPMENT• Smooth defrosting management
• Heat source integration/backup management
• Compressor stop for external air temperatures lower than the operating limits
• Condensation/evaporation control with fan speed regulator
• Flow meter (standard)
• Directive 97/23 EEC (PED) Certification
• Summer/winter selection from digital input
• Remote On/Off from digital input
• Condensate drip tray
• Coil protection grid.
ACCESSORIESAll the units can be configured with various accessories to better meet the requirements of the specific application in which they will be set. To check availability of accessories and compatibility of their size and configuration, please refer to the price list or selection software.
COOLING CIRCUIT ACCESSORIES• electronic thermostatic valve (standard on the /HWS unit).
HYDRAULIC CIRCUIT ACCESSORIES• filling unit with manometer
• anti-freeze resistance
- basic version: electric heater on the utility exhanger
- /1P and /1PV versione: electric heaters on the utility exchanger and heating cable on the pipes
- /1PS and /1PVS versione: electric heaters on the utility exchanger and heating cable on the pipes
• additional heater
• 3-way valve to control the domestic hot water (supplied)
• hydraulically disconnected tank
• system pump with Pulse function
• electronic modulation of the water flow
• filter.
ELECTRICAL ACCESSORIES• electric power supply different from the standard one
• maximum and minimum voltage relays
• double set-point from the digital input
• RS485 serial interface
• remote user terminal
• electronic soft starter
• EC electronic fans
• compensaiton of the setpoint according to the external air temperature
• automatic control of the domestic hot water
• domestic hot water operating probe (standard on the /HWS unit)
• anti-legionella function
• heat source integration/backup management
• domestic water production with timer
• individual operating potential free contacts
• Miniboss S
• Miniboss M
VARIOUS ACCESSORIES• rubber anti-vibration mounts
• wooden cage packaging.
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
7
MAROON 2 - BI COMPRESSORHIGH EFFICIENCY AIR-WATER HEAT PUMPS WITH AXIAL FANS AND SCROLL COMPRESSORS CONNECTED IN TANDEM
PRODUCT DESCRIPTION
STRUCTUREIn galvanised sheet metal and painted with polyester powders RAL 7035 at 180°C, which confer high resistance to atmospheric agents.
The panels can be easily removed to allow total access to the internal components.
All the structures have 2 condensate drip tray (1 per coil) with the relative drain.
MAROON 2/HT COMPRESSORHermetic scroll compressors in tandem configuration, complete with circuit breaker protection included in the electric motor windings, oil level indicator, crankcase heater and rubber anti-vibration mounts. The compressors used in this series are specifically designed to run as heat pumps. Optimising the compression ratio to high values allows for a superior efficiency to be reached when compared with traditional scroll compressors. The compressors have a liquid injection system: this allows the heat pump to run at very low outdoor temperatures while producing very hot water.
MAROON 2/MT COMPRESSORHermetic scroll compressors in tandem configuration, complete with circuit breaker protection included in the electric motor windings, oil level indicator, crankcase heater and rubber anti-vibration mounts. The compressors used in this series are specifically designed to run as a heat pump. Optimising the compression ratio to high values allows for a superior efficiency to be reached when compared with traditional scroll compressors.
USER SIDE EXCHANGERAISI 316 stainless steel braze-welded plate evaporator, housed inside a closed-cell insulating casing, which reduces heat loss and prevents condensation from forming.
The exchanger is equipped with a temperature probe for anti-freeze protection, with a temperature probe for the water inlet and outlet and with a blade flow switch supplied as standard.
SOURCE SIDE EXCHANGERThis consists of 2 coils with copper pipes and aluminium fins with a high exchange surface with fin spacing sized so as to maximise heat transfer and reduce the noise impact. The space of the fins in the exchanger has been increased so as to allow the unit to work at very low temperatures and very high moisture concentration.
The subcooler is found at the base of the exchanger, which is an additional cooling circuit that prevents the formation of ice in the lower part of the coil and facilitates the flow of condensate during the defrosting operations. The effects of the subcooler are: reduced defrosting operations and the safety of having a clean heat exchanger at the end of each defrosting operation.
A metal mesh protects the finned core.
FANSA helicoidal fan coupled directly to the electric motor, made of plastic material with a blade profile equipped with WINGLET, a special shape in the end part of the blades, which allows a reduction in the noise and an increase in the aeraulic performance.
The control manages the fan speed through a speed regulator phase cut in order to optimise the operating conditions, efficiency and allow the unit to operate as a heat pump also for high outdoor temperatures.
Moreover, this adjustment has a reduced noise level effect on the unit. In fact, the control device will modulate the speed of the fans at night and during mid-season. This means that every time there it is possible, the machine will minimise the fan speed and also its noise level.
The fan is an axial fan directly coupled to the 6-pole electric motor, with an IP 54 degree of protection, with shaped nozzles and a safety grille in accordance with EN 294.
COOLING CIRCUITIt includes: a charging socket in the liquid and inlet line, liquid indicator, a solenoid valve, non-return valves, a dehydrator filter, 2 thermostatic expansion valves (1 for heat pump operation and 1 for chiller operation) equipped with an external pressure equalizer, pressure transducer, high and low pressure switches and a safety valve, liquid receiver and intake separator.
ELECTRIC CONTROL BOARDThe electric control board consists offrom:
• a main isolating switch and fuse protection of the auxiliary and power circuits
• remote switches for compressors
• condensation and evaporation control fan speed regulator
• pump relay or motor protection switch and remote control switch (in /1P or /2P version)
• potential free contacts for general alarm
• microprocessor control.
400V/3N~/50Hz power supply for all sizes.
CONTROLMicroprocessor control for the following functions:
• water temperature adjustment with inlet control
• anti-freeze protection
• compressor timing
• high pressure pre-alarm control
• alarm signals
• alarms reset
• remote on/off digital input
• summer/winter selection digital input.
The display is used to display the following information:
• temperature of the outlet water
• condensation temperature
• set and differential temperature settings
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
8
• description of the alarms
• pump and compressor operation counter.
The control integrates the following standard functions:
• automatic control of the domestic hot water
• smooth defrosting.
Certain functions are only available with the unit adequately configured. Certain functions must be enabled from the control.
CHECKS AND SAFETY DEVICES• utility water temperature control probe (situated at the inlet
of the utility heat exchanger)
• anti-freeze probe to activate the anti-freeze alarm (automatically reset at limited intervals)
• high pressure switch (with manual reset)
• low pressure switch (automatically reset at limited intervals)
• standard mechanical blade flow meter (manually reset)
• high pressure safety valve
• compressor over-heating protection
• control of the condensation pressure using the speed regulator for operation with low outdoor temperatures.
• control of the evaporation pressure using the speed regulator for operation with high outdoor temperatures in domestic hot water production or recovery
• compressor over-heating protection.
INSPECTIONThe units are inspected in the factory and supplied complete with oil and refrigerant fluid.
VERSIONS/LN: SILENCED UNITAs well as the components of the basic version, the unit has a completely sound insulated compressor compartment made of sound-absorbing material, which is used with sound impeding material.
/HWS: MULTIPURPOSE HEAT PUMPThe unit in this setup is equipped with 2 exchangers: 1 on the system side for air-conditioning and heating, and 1 dedicated exclusively to the production of domestic water.
T
T
Sufficient cold or hot water can be produced on the unit system side exchanger to meet the heating and cooling requirements of the building according to the seasons.
The unit on the exchanger dedicated to the DHW produces hot water to be sent to a storage tank outside the machine, which is selected and sized according to the system requirements.
The unit runs in different modes according to the season: these are automatically switched (within the season) via the reading of the temperature probes and the set-point settings. Switching times and logic are designed to guarantee maximum system efficiency and reliability.
This configuration must be associated to an adequately sized boiler in which very hot water is stored. The boiler must have a well for the domestic water operating probe to be inserted in the upper part, through which the unit controller will monitor the amount of domestic hot water that must be produced.
Summer operationThere are 3 summer modes:
• Chiller mode: the unit only produces cold chilled water for the system.
• Chiller mode with simultaneous production of domestic hot water: the unit produces chilled water for the system and domestic hot water. The recovered power for the domestic water production is complete.
• Heat pump mode for domestic hot water production: when there is no cold water and the domestic water operating probe is required to run, the unit heats the water inside the domestic water storage tank using the finned core coil as an evaporator. Using the hot external air as a source of heat guarantees the extremely high COP to be achieved.
Switching from one mode to another occurs entirely automatically according to a priority logic in the domestic hot water production and when there is load diversity, thereby recovering the condensation energy for the production of domestic hot water.
Winter operationThere are 2 winter modes:
• Heat pump mode for heating: the unit produces hot water to the system side exchanger for heating purposes.
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
9
• Heat pump for the production of domestic hot water: produces hot water to the connected exchanger of the domestic water storage tank.
Switching from one mode to another occurs entirely automatically according to a priority logic in the domestic hot water production.
In addition to the components of the basic version, the /HWS unit includes:
• a special exchanger for the production of domestic hot water
• a temperature probe to be positioned on the domestic water storage tank
• an electronic thermostatic valve (replaces the 2 mechanical thermostatic valves).
HYDRAULIC MODULE OPTIONS/1P: unit with one pumpThe unit includes a circulation pump installed inside the unit.
/2P: unit with two pumpsThe unit includes 2 circulation pumps installed inside the unit. Each pump is a reserve of the other, controlled in timed rotation and with automatic switchover in the event of a fault.
/1R: unit with domestic side pumpThe unit is equipped with a pump for the domestic side (supplied). This module can only be matched with the units in the /HWS setup and can be combined with the /1P or /2P modules. The HWS units with no /1R module are equipped with consent to control an external pump.
The /1R module is installed inside the unit.
ACCESSORIESAll the units can be configured with various accessories to better meet the requirements of the specific application in which they will be set. To check availability of accessories and compatibility of their size and configuration, please refer to the price list or selection software.
STANDARD EQUIPMENT• Smooth defrosting management
• Heat source integration/backup management
• Compressor stop for external air temperatures lower than the operating limits
• Condensation/evaporation control with fan speed regulator
• Flow meter (standard)
• Directive 97/23 EEC (PED) Certification
• Summer/winter selection from digital input
• Remote On/Off from digital input
• Condensate drip tray
• Coil protection grid.
COOLING CIRCUIT ACCESSORIES• electronic thermostatic valve (standard on the /HWS unit).
HYDRAULIC CIRCUIT ACCESSORIES• filling unit with manometer
• anti-freeze resistance
- basic version: electric heater on the utility exhanger
- /1P and /2P versione: electric heater on the utility exchanger and heating cable on the pipes
• 3-way valve to control the domestic hot water (supplied)
• system pump with Pulse function
• water filter.
ELECTRICAL ACCESSORIES• electric power supply different from the standard one
• maximum and minimum voltage relays
• double set-point from the digital input
• RS485 serial interface
• remote user terminal
• electronic soft starter
• EC electronic fans
• compensaiton of the setpoint according to the external air temperature
• automatic control of the domestic hot water
• domestic hot water operating probe (standard on the /HWS unit)
• anti-legionella function
• heat source integration/backup management
• domestic water production with timer
• individual operating potential free contacts
• utility pump inverter
• Miniboss S
• Miniboss M
VARIOUS ACCESSORIES• rubber anti-vibration mounts
• wooden cage packaging.
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
10
DESCRIPTION OF THE FUNCTIONS AND ACCESSORIESRemote ON/OFF from digital input (standard)All the units come with this function as standard. It consists of a remote contact for turning the machine on and off by means of a signal that can be taken inside the building or piloted by a Building Management System (BMS).
Summer/winter selection from digital input (standard) This function is standard for all heat pumps. When the unit is switched on, an operating mode must be set as either heat pump or chiller. Through this remote contact, the operating mode can be modified even inside the building and without direct access to the microprocessor control.
Smooth defrosting (standard)The control manages the defrosting according to a variable interval threshold, depending on the pressures inside the unit and the external air temperature. Crossing this information, the control can identify the presence of ice on the coil by activating the defrosting sequence only when necessary, so as to maximise the energy efficiency of the unit.
The dynamic management of the defrosting threshold allows for the function to be implemented only when the ice deposited on the coil will affect the performance in outdoor air temperatures below -5°C, when the absolute humidity of the air is very low.
Controlling the auxiliary heat source (standard)The controller can manage an external heat source, which can be of integration or backup type, depending on the type of hydraulic connection. In the diagram below, for example, the boiler will be backup to the heat pump.
The auxiliary heat source will be activated when the outdoor air temperature drops below a threshold that can be set from the control and only when the heat pump is insufficient to meet the load. Activation occurs by closing a potential free contact.
It is also possible to set the unit for the controller to switch the compressors off when the unit operates in heat pump mode and the outdoor air temperature drops below a minimum set temperature: the controller will stop the compressors before the unit goes into low pressure alarm, thereby preventing having to manually reactivate the machine.
This function is particularly useful when the heat pump is
installed in an area where the external air temperature will definitely drop below the minimum temperature allowed by the threshold (in accordance with the set-point). When the external air temperature returns above the set temperature threshold, the unit restarts automatically without requiring any intervention.
Units with an integrated pump must always be kept running in order to prevent the formation of ice and to ensure correct operation of the temperature probes and anti-freeze safety devices.
The shutdown temperature must be configured according to the higher set-point temperature and the operating limits of the machine.
A shutdown temperature other than the default can be set provided it is compatible with the unit’s operating limits.
Standard programming involves the
• /MT units having the heating set-point set at 30/35° with a shutdown temperature of -16°C
• /HT units having the heating set-point set at 40/45° with a shutdown temperature of -20°C
If the unit must also be used to produce domestic hot water, the shutdown temperature must consider the higher water set-point and the operating limits allowed.
Automatic domestic hot water control (standard)This function allows the unit to control the temperature inside a storage tank for the domestic hot water and a 3-way valve (accessory) outside the unit by means of a domestic water operating probe (accessory). Priority is always given to the production of hot water for domestic use.
The request for the function to be activated must be made when placing the order, however, it can be configured at a later stage (by qualified and authorised technical personnel) provided that the unit is connected with a suitable hydraulic circuit.
The request made when placing the order for special accessories to control the domestic hot water automatically entails the activation of the ”automatic domestic hot water control” funtion.
The heat pump normally operates on the system to meet the comfort requirements of the building, however, when the water temperature inside the tank drops below a set threshold, the control manages the production of domestic hot water: if the unit is operating as a heat pump for heating, the 3-way valve will be switched and the set-point changed; if on the other hand, the unit is producing chilled water for air conditioning, the control switches the unit to heat pump mode, assigns it the set-point for domestic hot water (usually higher than the set-point of the system) and turns the 3-way valve in the right position.
Once the temperature inside the domestic water tank has reached the set value, the unit automatically returns to the water production for the heating and air conditioning system.
Description of the winter modeThe following conditions occur in winter:
• Heating request: the temperature of the unit inlet water
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
11
coming from the system is lower than that expected, therefore, the control switches the compressor on and the unit will run until the set-point temperature is reached.
The compressor stops when the desired temperature is reached and only the circulation pump will keep running, which will keep the water circulating in the system. The unit will wait in this state until the water inlet temperature drops again.
• Domestic hot water request: let us suppose that the unit is producing hot water for the heating system (45°C) and receives the request to produce hot water from the domestic water operating probe in the storage tank since the water temperature has dropped below the set limit, (e.g. 55°C).
• Since the hot water is controlled with priority logic, the control will change the set-point bringing it to 55°C and switch the 3-way valve.
As soon as the water inside the tank will reach the required 55°C, the control will switch the 3-way valve once again to work on the system and bring the set-point back to 45°C.
If the defrosting process must be implemented, regardless of the mode the unit is running in, it will force the 3-way valve to be switched towards the system, which is less sensitive to the reduction in temperature due to the greater inertia.
Description of the mid-season mode The heating and air conditioning system is not active during the mid-season and therefore, the heat pump is solely dedicated to the production of domestic hot water.
The 3-way valve is firmly positioned on the domestic hot water tank, whereas the pump and heat exchanger will only be activated on demand from the domestic water operating probe.
When the domestic water set-point is reached, the compressor and the pump will be switched off and the control will remain in stand-by for the next request.
This function is activated by setting the unit to the ”domestic hot water only” function. For further information refer to the wiring diagram supplied with the unit.
Description of the summer modeThe following conditions occur in summer:
• Only cooling: the temperature of the unit inlet water coming from the system is higher than that expected, therefore, the control switches the compressor on and the unit will run until the set-point temperature is reached.
The unit then stops and only the pump will keep running, which will keep the water circulating in the system. The unit will wait in this state until the water inlet temperature rises again.
• Domestic hot water request: let us suppose that the unit is producing chilled water for the air conditioning system (7°C) and receives the request to produce hot water from the domestic water operating probe in the storage tank since the domestic water temperature has dropped below the set limit, (e.g. 55°C).
Since the domestic hot water is controlled with priority logic, the control will change the unit mode from chiller to heat pump, set the set-point to 55°C and switch the 3-way valve.
As soon as the water inside the tank will reach the required 55°C, the control will switch the 3-way valve once again to cihller mode, turn the 3-way valve for it to work on the system and bring the set-point back to 7°C.
Domestic water operating probe (accessory) The controller requires this accessory for the production of domestic hot water: it consists of a temperature probe with
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
12
a 6 m cable to be placed in a special well in the tank for the production of domestic water. Read the ”Heat pump installation tips” section to set it in the correct position.
Standard on HWS units.
Hydraulically disconnected tank (accessory) If the unit must also be used for the production of domestic hot water using the 3-way valve and is equipped with an inertial tank (/1PS and /1PVS units), the ”Hydraulically disconnected tank” accessory must be included.
T
The unit will be set-up with the mechanically connected tank, however, it will have a hydraulic inlet and outlet that are not connected to unit. This will allow the 3-way valve to be inserted corrected, thereby avoiding the inertial tank from being crossed during the production of the domestic hot water.
Anti-legionella function (accessory)
Anti-legionella cycles may have to controlled, depending on the type of tank chosen for the production of domestic hot water. The controller can handle activating an auxiliary heat source that will perform the thermal shock on the hot water tank, according to programmed intervals with a weekly timer.
System pump with Pulse function (accessory) As standard, the unit is set to keep the system side circulation pump always on, even if it reaches the set temperature.
When the unit is equipped with this accessory and the set-point is reached, the controller will switch the pump off, reactivating it periodically for sufficient time to detect the temperature of the water. If the controller verifies that the water temperature is still in set-point conditions, it will then turn the pump off again. Otherwise, the controller will reactivate the compressors to meet the system requirements.
Hence, this accessory allows the electrical consumption due to pumping to be significantly reduced, especially during mid-season when the load is extremely low.
The ”anti-freeze” accessory must be present for this accessory to be applied.
Domestic water production with timer (accessory)If this accessory is present, 2 temperatures can be set for the domestic water by associating different time bands: Normal and Saving. This allows you to decide when the heat pump is to concentrate on the production of hot water, however, always keeping the minimum Saving temperature, which is always managed with priority logic.
For example, focusing the production of water at Normal
temperature at night, the better electricity rates will be taken advantage of and production of hot water just before the time when consumption is higher will be guaranteed.
With this system, the unit will still never cease to control the temperature inside the domestic water tank and if there is occasional use of hot water out of the usual times, the unit will give priority to the production of domestic water until the water in the tank returns to a temperature that is equivalent to the Saving set-point.
Electronic modulation of the water flow (accessory)This accessory allows the unit to modulate the water flow so as to facilitate unit start-up even if the water in the system is not at an optimal temperature. Starting the unit after the system has been OFF for a long time, the water in the system could be too hot in summer or too cold in winter. In both cases, the modulation of the water flow guarantees the unit reaches the correct operating speed, avoiding the intervention of the safety devices.
This accessory is only available for per gli allestinimenti /1PV e /1PVS.
Electronic thermostatic valve (accessory)This accessory is particularly suitable for units that operate in very unstable heat load conditions or in conditions where the outdoor temperature is highly variable or the operating mode is changed often, as in the case of combined air conditioning, heating and production of hot water. Using the electronic thermostatic valve allows the following:
• to maximise the heat exchange to the utility exchanger
• to minimise the response time of the cooling circuit to variations in load and operating conditions
• to optimise the superheating regulation
• to maximise the energy efficiency.
EC fans (accessory)The units can be requested with EC fans, a brushless motor with electronic switchover. These motors with permanent magnets rotor guarantee very high levels of efficiency for every work condition and allow for 15% savings on the absorbed power per fan.
Moreover, through a 0-10V analogue signal sent to every fan, the microprocessor allows the condensation/evaporation to be controlled by means of continuous air flow regulations as the outdoor air temperature varies and a consequent reduction in electrical consumption and noise emission.
MINIBOSS S/M (accessory)In applications in which there is:
• the need to guarantee continuous system operation and therefore, redundancy must be foreseen by means of a reserve machine
• a system that will be activated for parts and will therefore require a progressive increase in the installed power
• there is no physical space to install one unit that guarantees
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
13
all the power, however, a number of smaller units can be installed
• in general, the MINIBOSS accessory, which is a control panel provided with the unit, can be used to combine several units and to coordinate the operation and rotation. This allows you to manage multiple units connected in parallel and coordinated by one supervisor in a rational and efficient way.
MINIBOSS S The Miniboss S allows you to connect up to 4 units in parallel: the control allows you to enable and disable them in power steps and rotate them in operation, thereby allowing all units to be used in an identical manner.
The connected units must all be the same. The Miniboss S cannot control units that have the domestic water control active.
The following can be controlled directly from the Miniboss S panel:
• the set-point of the system
• the summer/winter selection of all the machines
• the ON/OFF of the single units or the entire system.
This accessory is supplied in an electrical panel together with the unit (to be installed in a technical compartment), and must be placed on one of the machines connected in parallel and all connected units must have the same configuration.
When placing the order you must specify the number of units that must be controlled so as to allow for the proper programming of the supervisor. In addition, the hydraulic circuit that connects the units must comply with one of the following formats.
T
P P
MBS
T
MBS
T
MBS
For further information regarding the use, refer to the specific documentation.
MINIBOSS MThe Miniboss M allows a maximum of 8 unita in parallel to be controlled. The main functions are:
• controlling units with HWS configurations
• control units with ”automatic domestic hot water control” logic
• control systems with a hot/cold tank to heat/air condition and a hot tank for the production of domestic water.
Besides that also implemented by the Miniboss S,
• the set-point of the system
• the DHW set-point
• use a compensation climatic of the system set-point
• the summer/winter selection of all the machines
• the ON/OFF of the single units or the entire system
• 3-way valve switchover
• control the operation of pumps outside the units.
This accessory is supplied in an electrical panel together with the unit (to be installed in a technical compartment), and must be placed on one of the machines connected in parallel and all connected units must have the same configuration.
When placing the order you must specify the number of units that must be controlled so as to allow for the proper programming of the supervisor. In addition, the hydraulic circuit that connects the units must comply with one of the following formats.
T
T
T
MBM
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
14
T
T
T
MBM
For further information regarding the use, refer to the specific documentation.
Filling unit with manometer (accessory)This accessory allows the hydraulic system to be filled automatically and the correct working pressure to be adjustmented, which can always be verified via the manometer, and continuously maintenance maintains this pressure, topping-up the water, if necessary.
Anti-freeze heater (accessory)This accessory consists of heaters fitted on the utility exchanger, pump and tank (depending on the machine configuration) to prevent damage to the hydraulic components due to the formation of ice when the machine is out of use. The power of the anti-freeze heaters is only a few Watts, depending on the model of the unit, which is sufficient to prevent the components from malfunctioning.
The controller monitors the outlet probe of the exchanger (even when the unit is in standby) and when this detects a water temperature of 5°C or less (or 2°C below the set-point temperature, with a differential of 1°C) and triggers the anti-freeze heater.
When the temperature of the outlet water reaches 4°C (or 3°C below the set-point), it also triggers the anti-freeze alarm that stops the compressor, whilst keeping the the heaters active.
The anti-freeze heaters are located in the evaporator (the 1PS version also has an anti-freeze heater installed on the tank, on the pipes and on the pump volute that will be insulated), and on any recovery heat exchangers.
Additional heater (accessory)This is an electrical heater inserted in the inertial tank of the hydronic module that helps the heat pump fulfil its purpose when the power of the unit is insufficient.
The capacity of the heater depends on the size of the machine.
This accessory is only available with the hydraulic module with tank.
Double set-point from digital input (accessory)The double set-point allows you to set 2 different operating temperatures for the heating mode and a set-point for the cooling mode. If a double set-point is required for both modes, an electronic thermostatic valve must be installed.
The set-point temperatures must be specified when placing the order. The set-point can be changed from the keypad or digital input.
RS485 serial interface (accessory)The growing diffusion of domotic and BMS (Building Management System) systems has led to the need to integrate all the system components under one supervision. To meet this requirement, the unit can be equipped with an RS485 serial board with MODBUS protocol.
Remote user terminal (accessory)This accessory consists of a replica of the remote control panel from which the unit configuration can be completed and all its parameters can be viewed. Passwords must be entered to access the masks that enable the various editing levels.
Soft-starter (accessory)The units are equipped with the technology required to minimise peak current, however, the unit can also be fitted with a soft-starter accessory as a further precaution. It is an electronic control device that monitors the start-up of the electric motors and reduces the normal peak current of the compressor by 40%.
Domestic hot water 3-way valve (accessory)It is an on/off 3-way valve that combined with the ”automatic domestic hot water control” function, it allows the machine to control 2 separate circuits for comfort and production of domestic hot water, switching automatically from one to another, according to the system requirements.
The 3-way domestic hot water valve must be installed in a technical compartment.
Compensation of the set-point depending on the external temperature (accessory) The controller allows you to change the set-point of the unit when in chiller mode and in heat pump mode according to the external temperature. Compensation can be positive or positive: positive compensation occurs when there is an increase in the outdoor air temperature and the operating set also increases; whereas, negative compensation occurs when there is an increase in the air temperature and the set decreases.
If the unit is also used for the production of domestic hot water the climatic adjustment will not affect the temperature of the domestic water set.
Unless specified otherwise when placing the order, standard programming involves negative compensation (for both set-points) as shown in the diagrams below. All the settings can be modified directly by the controller device.
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
15
MAROON 2 /MT MAROON 2 /HT
ModeHEAT PUMP
38/42°C
SET2 =
SET1 =
50/55°C
-16°C -3 °C
SET2 = 50/55°C
-20°C -10°C
43/48°CSET1 =
Maximum and minimum voltage relays (accessory)This device continuously monitors the supply voltage of the unit, thereby verifying that it remains within a permissible range. When the voltage goes exceeds or drops below the range, the device stops the unit to avoid damaging the electric motors.
The device also monitors the phase sequence.
Inverter for utility pump (for the unit with the ST hydraulic module)
Energy savings:Variable flow pumps have become more widespread over the years to optimise air conditioning and cooling systems. Thanks to the Inverter utility pump, Blue Box offers an alternative method that differs from conventional layouts: a constant flow primary pump and a variable flow secondary pump.
Comparing the two solutions:1) The figure below shows the layout of a constant flow primary pump and a variable flow secondary pump. Please not the use of the decoupling pipe between the primary and secondary system (designed to cover the entire flow rate): if the utilities only require a percentage of the nominal power, the decoupling pipe recirculates the excess flow, which means wasting pumping energy.
EVA
POR
ATO
R
BA
CK
FLO
W P
REV
ENTE
R
PRIMARYPUMPING UNIT WITH CONSTANT FLOW
SECONDARYPUMPING
UNIT WITH
VARIABLE FLOW
The figure below shows a system with only variable flow primary pumps, which also serve the secondary system. The bypass pipe and the two-way control valve ensure minimum water flow through the evaporator when the request is below the admitted minimum water flow limit to guarantee appropriate heat exchange. The pipe and the two-way control valve are sized for a much lower water flow rate than the nominal one. This allows to considerably reduce energy losses related to the mixing process, which in traditional systems are caused by the hydraulic circuit breaker.
BY-P
ASS
PIP
E
PRIMARYPUMPING UNIT WITH VARIABLE FLOW
Benefits of the solution with the Inverter for utility pump:
• Saving a set of pumps
• Reduced overall dimensions of the machines’ housings
• Lower piping costs
• Reduced pressure drops
• Greater energy efficiency on the pump side.
As we can see from the graph under EUROVENT conditions, the systems in the diagrams have higher efficiency under part-load conditions, considering the energy consumed by the pumps as well as by the chiller (compressors plus fans).
0%
2%
4%
6%
8%
10%
12%
14%
16%
18%
20%
22%
24%
100% 75% 50% 25% Total ESEERImprovment
EER
impr
ovm
ent a
t partia
l loa
d
Energy savings in these conditions can be as high as 11% per year and sometimes even more!
Operating logic of the Inverter for utility pump:
Dp1: System side pressure drops
Dp2: Evaporator pressure drops
dwo pwo
dwi pwi
Dp2
two
twi
Dp1
EVA
POR
ATO
R
SYSTEM SIDE
MINIMUM THERMAL FLYWHEEL
SUPPLIED MODULATING BY-PASS VALVE
PUMP WITH INVERTER
When all utilities are running, the unit pump works with a nominal flow rate and system side working head equal to DP1 and evaporator pressure drop equal to Dp2.
The decrease in the system thermal load involves closing the shut-off valves of the utilities with a consequent increase in pressure drops that the pump must overcome; simultaneously, the inverter control logic will decrease the flow rate with a
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
16
consequent decrease in the evaporator pressure drop, thereby restoring the pressure head to the nominal DP1.
Key points for a variable flow primary system:In order for the components of the system to operate optimally, it is important to take some key points into account:
1) Minimum water flow and bypass valve supplied:The Inverter for utility pump accessory also includes the supplied 2-way by-pass valve, which is adequately sized in relation to the size of the unit.
If on the system side the heat load is very low, this means that many utilities are closed, which results in an increase in pressure drops. The inverter counters the Dp1 variation detected by the sensor by reducing the speed of the pump and the flow rate as a result. However, there is a limit lower than the flow rate value below which the heat exchange towards the evaporator is not performed properly and the temperature drop processed by the evaporator increases, which might activate the anti-freeze alarm. The two-way control valve adequately selected based on the machine model prevents this alarm from being triggered, thereby ensuring the minimum water flow rate towards the evaporator.
2) “Minimum thermal flywheel”:In the event of a heat load close to zero, with the unit in maximum power partialisation conditions, the pump set at the minimum flow rate and closed system valves, the machine might stop due to the anti-freeze alarm.
To prevent this problem, there must be a “minimum thermal flywheel” in the evaporator / bypass valve section.
Below is the formula to determine it:
NkP
Vol*0=
][l
=0P Machine overall cooling capacity [kW]
N : Inverse of the unit’s minimum capacity control
k : parameter [l/kW]
Scroll compressors 2 3 4 5 6 7 8 9 10 12
k [l/kW]
17.4 13 13.9 17.4 16.3 15.3 14.8 14.6 13.9 13.4
N 2 3 4 5 6 7 8 9 10 12
The water content of the evaporator, of the hydraulic module’s inertial tank (if there is one) and of the pipes between the bypass and the evaporator itself may contribute to determine the “minimum thermal flywheel”.
However, it is advisable to use three-way valves on a certain number of utilities on the system to ensure a minimum flow of water towards the system in any condition.
Please note: Where there is this accessory, the minimum cold water temperature at the outlet cannot drop below 7°C. Moreover, the temperature variation considered under the conditions specified in the project must be 5°C. Please contact our sales department for the minimum water temperature at the outlet (production of cold water) and for different temperature drop values.
You should also contact the sales department in the event of
production of hot water for water temperatures at the outlet below 40°C.
Attention: The “minimum thermal flywheel” must be between the bypass valve and the evaporator. This is a part of the “minimum water content of the system” described in the relative chapter of the manual; the difference between the “minimum water content of the system” and the “minimum thermal flywheel” can instead be positioned in any area of the system.
The “minimum thermal flywheel” allows the unit to operate correctly also in heat pump mode.
For cooling-only machines, if using ethylene glycol mixes, it is possible to reduce the “minimum thermal flywheel” based on the curves below
For scroll compressors:
% ETHYLENE GLYCOL
MINIMUM REDUCTION IN THE THERMAL FLYWHEEL
-100%
-95%
-90%
-85%
-80%
-75%
-70%
-65%
-60%
-55%
-50%
10% 20% 30%
If the unit is in heat pump mode, the “minimum thermal flywheel” is not reduced, even if there is glycol.
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
18
HEAT PUMP INSTALLATION TIPS
Using a heat pump for air conditioning, heating and production of domestic hot water has been an established practice for years and has undoubted advantages.
By its nature, the heat pump is strongly affected by the characteristics of the system, the selected operating conditions and the choices made for its installation and connection.
Below are some tips that increase the efficiency and reliability of the system:
CHOOSING THE CAPACITY OF THE HEAT PUMPS CORRECTLYThe heat pump must always be selected in excess, guaranteeing to exceed the maximum load besides the project load and possibly being able to operate even at lower temperatures than those of the project.
An integration or backup must also be contemplated, which can replace or help the heat pump in harsher operating conditions.
CHOOSING THE PROPER OPERATING TEMPERATURESHeat pumps guarantee maximum efficiency, and therefore the economic advantage in using them, since the design of the system is aimed at choosing high water temperatures for air conditioning and low ones for heating.
As can be seen from the example diagrams above, even a small variation in the temperature leads to an immediate improvement in the EER and COP.
CHOOSING THE PROPER TEMPERATURE FOR THE DOMESTIC WATERFor the same reasons in the previous point, the choice of the tank for the production of domestic water is to be made so as to maintain the set-point for the production of hot water
as low as possible. This will allow the efficiency of the system to be increased and also maximise the operating limits of the unit, thereby ensuring the production of domestic water even for very low temperatures.
In general it is not advisable to set the unit set-points the limit of the permissible operating conditions, especially in the heat pump mode, for the following reasons:
• Setting the water set-point at the maximum temperature limit reduces the operating limits of the unit.
• The water filter must always be present in the water inlet of the unit otherwise the warranty will be rendered nul and void. With the passage of time the filter element can become dirty and this will increase the pressure drops and consequently reduce the water flow. Lowering the water flow will lead to an increase in the thermal gradient of the utility exchanger that can go from 4/5°C to 9/10°C, however, since the unit controls the set-point on the return temperature, this may involve the intervention of the safety devices if the unit operates at the limits of the allowed operating conditions.
• If the heat pump is connected directly (without intermediate circuit breakers) to a hydraulic circuit divided into areas, the pressure drop of the circuit may increase on closure of one or more areas, thereby leading to a decrease of flow and then to a increase of the thermal head to the heat exchanger. As before, if the heat pump is set to operate at the permissable limits of the operating conditions, this can lead to an intervention of the safety devices.
• Depending on the position chosen for the installation of the unit.
• In summer, the unit will be subject to solar radiation. Assuming the air is at 35°, the coil (copper and aluminum and therefore excellent conductor) will be very hot. When you switch the unit on, even with the fans stopped, the evaporation will be very high, thereby leading to the definite intervention of the high pressure switch.
• Air recirculation can generate an environmental micro with a temperature less than 4/5°, leading the unit to work out of the limits.
• The clearances are very important, the upstream or downstream obstruction of the fan creates pressure drops that reduce the air flow. This reduction can generate a reduction in the operating temperatures. This decrease may lead the unit out of the operating limits.
• Air in the circuit. Air in the system, even if thoroughly vented, creates a loss of heat transfer coefficient with the consequent possibility of the high pressure safety devices intervening.
CAREFUL SELECTION OF THE DOMESTIC WATER TANKWhen you want to use a heat pump for water production the unit must always be connected to an adequately selected tank that is dedicated to the production of domestic hot water. In fact, the heat pumps cannot produce the water instantly and the plate exchanger must also work with a closed water circuit to prevent scale from forming on the inside.
The choice of the tank for the domestic water must be done very carefully because if it is not adequately sized, the system
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
19
may not be reliable. For this reason, it is strongly recommended to choose a tank that allows the heat pump to work on the technical water and not on a coil. The combination of the heat pumps with coils is in fact problematic because of the difficulty in sizing the coil surface that must always be done in the worst conditions, that is in summer conditions. Units can only be combined with coil tanks for storage provided directly by BlueBox.
POSITIONING THE DOMESTIC WATER OPERATING PROBE CORRECTLY For the domestic hot water and HWS control, the units use a supplied temperature probe, which must be installed properly: the tank must have a well in the upper part, which is long enough to almost reach the centre of the tank. The probe supplied with the unit must be inserted in the well with conductive paste in order to ensure an accurate reading of the water temperature. An incorrect temperature reading, caused by an unsuitable positioning or little conductive paste, could lead to the safety devices being triggered or the unit blocking.
SELECTING THE 3-WAY DOMESTIC WATER VALVE CORRECTLYIf you use the automatic control function of the domestic hot water, a 3-way valve with power supply 230/1~/50 is required together with a diameter of 1/4 of an inch greater than the diameter of the unit pipe. This valve must guarantee adequate speed switching and it is mandatory for the flow to never be cancelled during switching, thereby always allowing a flow.
POSITIONING THE COLD WATER TOP-UP CORRECTLYDepending on the type of tank used for the production of domestic hot water, there may be a connection for the water top-up from the mains (cold). It is very important for this connection to not be too close to the return pipe to the heat pump. In fact this could cause the cold water inlet from the mains cool the return water to the heat pump and this sudden drop in temperature of the inlet water to the ”hot” exchanger may lead to the safety devices intervening.
Even in this case using an instantaneous producer for the domestic water combined with a tank that allows the heat pump to work on the technical water allows this problem to be avoided.
CONSIDERING THE MOISTURE CONTENT IN THE WALLS AND SLABS IN THE BUILDINGLarge amounts of water are used to construct masonry works and screeds, to which one can add the rain absorbed by the unfinished works. All the moisture absorbed by the building evaporates very slowly.
Due to the high moisture content present in the entire building, in the first two periods of heating the heating requirements of the building will be increased.
If the heat pump is adequately sized to overcome the nominal heat load of the building and the first system start-up is in cold weather, the heating capacity output may be insufficient to start-up the entire system at once. In this case it is advisable to carry out its start-up per area, namely adding a few sections of the system at a time just as those already connected start to heat up or with the use of an additional electrical heater to compensate for the increased heating requirements.
ALWAYS GUARANTEEING THE MINIMUM WATER CONTENTIf the unit is connected to a hydraulic system split into areas, such as those with radiant panels, with them being controlled via solenoid valves on the manifold (heads), it is mandatory to ensure the presence of at least five litres of water for every kW of heat output of the unit in the most unfavorable condition, that is with a single open area. This is necessary to prevent the condition whereby almost all the heads are closed and the heat pump has to work with an extremely small volume of water. In this case, during the defrosting cycle, the safety devices may intervene due to excessively cold water.
STARTING-UP THE UNIT WITH WATER THAT IS TOO HOT OR TOO COLDThe safety devices may intervene if the unit is started-up in winter with a very cold water temperature and out of the operating limits of the unit. The system is brought up to its nominal speed by simply reducing the thermal load by sectioning part of the system. When the water temperature of the partial system will be within the operating range, the part of the system that was previously sectioned can then be connected.
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
20
Unit size 8 10 12 16 18 20 23 25 29 34 38 42Heating (Gross values)Nominal heating capacity (A7;W35)Heating absorbed powerCOPEfficiency ClassNominal heating capacity (A7;W45)Heating absorbed powerCOPEfficiency ClassHeating (EN14511 values)Nominal heating capacity (A7;W35)COPEfficiency ClassNominal heating capacity (A7;W45)COPEfficiency ClassCooling (Gross values)Nominal cooling capacity (A35;W18)Cooling absorbed powerEEREfficiency ClassNominal cooling capacity (A35;W7)Cooling absorbed powerEEREfficiency ClassCooling (EN14511 values)Nominal cooling capacity (A35;W18)EEREfficiency ClassNominal cooling capacity (A35;W7)EEREfficiency ClassCompressorType ScrollQuantity/Cooling circuitsCapacity controlTotal oil loadTotal refrigerant loadFansType AxialQuantityAir flow rateUser side exchangerType PlatesWater flow ratePressure dropHydraulic modulePump modelUseful pump headStorage tank capacityExpansion tank NoiseSound power levelNoise pressure levelDimensions and weightLengthDepthHeightOperating weight
MAROON 2 MT TECHNICAL DATA
(1) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 30-35°C(2) The total power is given by the sum of the power absorbed by the compressors and by the fans(3) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 40-45°C(4) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 60-65°C(5) External air temperature 35°C; input water-evaporator output temperature 23-18°C(6) External air temperature 35°C; input water-evaporator output temperature 12-7°C
(7) Sound power levels calculated compliant to ISO 3744(8) Sound pressure levels refer to 10 meters from unit in free field and directionality factor Q=2(9) Values compliant with EN 14511-3:2011This board reports the feature data of the base and standard versions; for details, refer to the specific documentation.
(1) kW 6,9 8,9 11,1 14,9 16,6 19,2 22,1 24,0 27,6 32,3 36,8 40,4(1), (2) kW 1,7 2,1 2,5 3,5 3,9 4,3 5,0 5,5 6,6 7,5 8,2 9,4
(1) 4,09 4,14 4,40 4,29 4,25 4,48 4,39 4,38 4,19 4,32 4,50 4,30A A A A A A A A A A A A
(3) kW 6,8 8,8 10,9 14,6 16,2 18,7 21,5 23,4 26,9 31,5 35,7 39,2(3), (2) kW 2,1 2,7 3,1 4,4 4,8 5,3 6,2 6,8 8,0 9,2 10,0 11,4
(3) 3,23 3,22 3,46 3,37 3,40 3,54 3,47 3,45 3,37 3,42 3,55 3,43A A A A A A A A A A A A
(1), (9) kW 6,9 8,9 11,2 15,0 16,7 19,4 22,2 24,2 27,8 32,5 37,1 40,6(1), (9) 4,06 4,12 4,36 4,16 4,16 4,37 4,29 4,28 4,10 4,23 4,40 4,23
A A A A A A A A A A A A(3), (9) kW 6,9 8,8 10,9 14,8 16,3 18,9 21,7 23,5 27,1 31,7 35,9 39,4(3), (9) 3,21 3,20 3,43 3,29 3,34 3,47 3,41 3,39 3,32 3,37 3,49 3,38
A A A A A A A A A A A A
(5) kW 8,5 10,2 13,0 17,9 19,5 22,6 26,0 28,3 32,9 39,9 43,5 45,1(5), (2) kW 2,2 2,6 3,1 4,3 4,6 5,4 6,4 6,9 8,3 9,3 10,9 11,5
(5) 3,84 3,88 4,19 4,14 4,28 4,23 4,05 4,12 3,98 4,29 4,00 3,93A A A A A A A A A A A A
(6) kW 6,2 7,6 9,7 13,4 14,2 16,8 19,1 20,8 24,4 29,6 32,4 38,6(6),(2) kW 2,1 2,5 2,9 4,0 4,4 4,9 5,9 6,4 7,6 8,7 10,1 11,0(6) 2,90 3,02 3,38 3,31 3,23 3,40 3,24 3,27 3,21 3,42 3,20 3,51
B B A A A A A A A A A A
(5), (9) kW 8,5 10,2 13,0 17,8 19,4 22,5 25,9 28,1 32,7 39,7 43,2 44,9(5), (9) 3,80 3,84 4,14 3,98 4,15 4,09 3,92 4,01 3,88 4,18 3,90 3,84
A A A A A A A A A A A A(6), (9) kW 6,2 7,5 9,6 13,2 14,1 16,6 18,9 20,7 24,2 29,4 32,2 38,4(6), (9) 2,87 2,99 3,33 3,16 3,12 3,28 3,13 3,17 3,11 3,32 3,11 3,42
C B A A A A A A A A A A
n° / n° 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1n° 1 1 1 1 1 1 1 1 1 1 1 1kg 1,1 1,3 1,3 1,2 1,7 1,9 1,8 2,5 3,3 3,3 3,3 3,3kg 2,6 3,5 4,2 5,7 6,2 7,0 8,4 9,1 10,7 12,4 13,5 14,2
n° 1 1 1 2 2 2 2 2 2 2 2 2m3/h 3.900 3.900 3.600 7.800 7.800 7.200 14.000 14.000 18.000 18.000 17.000 17.000
(1) l/h 1.190 1.525 1.916 2.554 2.860 3.304 3.792 4.131 4.752 5.561 6.334 6.939(1) kPa 4 4 6 42 28 33 34 30 33 33 34 30
P1 P1 P1 P2 P2 P2 P3 P3 P3 P3 P3 P4kPa 71 68 65 91 89 85 167 160 145 124 101 193l 70 70 70 70 70 70 130 130 130 130 130 130l 2 2 2 2 2 2 5 5 5 5 5 5
(7) dB(A) 63 65 66 68 70 70 72 73 74 75 75 75(8) dB(A) 32 34 35 37 39 39 41 42 42 43 43 43
mm 925 925 925 925 925 925 1.105 1.105 1.305 1.305 1.305 1.305mm 375 375 375 375 375 375 505 505 505 505 505 505mm 700 700 700 1.350 1.350 1.350 1.385 1.385 1.585 1.585 1.585 1.585kg 88 93 102 135 151 166 212 233 358 367 387 398
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
21
Unit size 52 62 72 82 92Heating (Gross values)Nominal heating capacity (A7;W35)Heating absorbed powerCOPEfficiency ClassNominal heating capacity (A7;W45)Heating absorbed powerCOPEfficiency ClassHeating (EN14511 values)Nominal heating capacity (A7;W35)COPEfficiency ClassNominal heating capacity (A7;W45)COPEfficiency ClassCooling (Gross values)Nominal cooling capacity (A35;W18)Cooling absorbed powerEEREfficiency ClassNominal cooling capacity (A35;W7)Cooling absorbed powerEEREfficiency ClassCooling (EN14511 values)Nominal cooling capacity (A35;W18)EEREfficiency ClassNominal cooling capacity (A35;W7)EEREfficiency ClassCompressorType ScrollQuantity/Cooling circuitsCapacity controlTotal oil loadTotal refrigerant loadFansType AxialQuantityAir flow rateUser side exchangerType PlatesWater flow ratePressure dropHydraulic modulePump modelUseful pump headNoiseSound power levelNoise pressure levelDimensions and weightLengthDepthHeightOperating weight
MAROON 2 MT TECHNICAL DATA
(1) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 30-35°C(2) The total power is given by the sum of the power absorbed by the compressors and by the fans(3) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 40-45°C(4) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 60-65°C(5) External air temperature 35°C; input water-evaporator output temperature 23-18°C(6) External air temperature 35°C; input water-evaporator output temperature 12-7°C
(7) Sound power levels calculated compliant to ISO 3744(8) Sound pressure levels refer to 10 meters from unit in free field and directionality factor Q=2(9) Values compliant with EN 14511-3:2011This board reports the feature data of the base and standard versions; for details, refer to the specific documentation.
52 62 72 82 92
(1) kW 45,6 53,4 60,6 70,6 77,0(1), (2) kW 10,9 12,1 13,9 16,3 17,9
(1) 4,18 4,40 4,37 4,34 4,30A A A A A
(3) kW 44,3 52,0 59,1 68,3 75,1(3), (2) kW 13,1 14,9 17,2 20,0 21,8
(3) 3,38 3,50 3,43 3,41 3,44A A A A A
(1), (9) kW 45,9 53,7 60,9 71,0 77,4(1), (9) 4,11 4,32 4,30 4,26 4,23
A A A A A(3), (9) kW 44,6 52,3 59,4 68,6 75,5(3), (9) 3,34 3,45 3,39 3,37 3,39
A A A A A
(5) kW 54,3 64,5 73,6 83,6 91,4(5), (2) kW 14,8 16,5 20,0 22,0 25,3
(5) 3,67 3,90 3,68 3,79 3,62B A B B C
(6) kW 40,5 48,2 55,0 62,5 68,8(6),(2) kW 13,6 15,1 18,4 20,5 23,2
(6) 2,97 3,18 2,99 3,06 2,97B A B B B
(5), (9) kW 54,0 64,2 73,2 83,2 91,1(5), (9) 3,59 3,81 3,61 3,72 3,55
C A C B C(6), (9) kW 40,2 47,9 54,7 62,2 68,4(6), (9) 2,90 3,10 2,93 2,99 2,91
C A B B B
n° / n° 2/1 2/1 2/1 2/1 2/1n° 2 2 2 2 2kg 3,6 6,8 6,8 6,8 6,8kg 15,2 17,8 20,2 23,5 25,7
n° 1 1 1 1 1m3/h 18.000 17.000 17.000 24.000 24.000
(1) l/h 7.844 9.176 10.416 12.146 13.248(1) kPa 33 35 33 35 36
P5 P5 P5 P5 P5kPa 162 156 154 145 138
(7) dB(A) 73 73 74 75 77(8) dB(A) 42 42 43 44 46
mm 1.403 1.403 1.403 1.403 1.403mm 1.203 1.203 1.203 1.203 1.203mm 2.390 2.390 2.390 2.390 2.390kg 575 592 602 620 631
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
22
Unit size 7 9 11 13 17 22 26 32 36 41Heating (Gross values)Nominal heating capacity (A7;W35)Heating absorbed powerCOPEfficiency ClassNominal heating capacity (A7;W45)Heating absorbed powerCOPEfficiency ClassHeating (EN14511 values)Nominal heating capacity (A7;W35)COPEfficiency ClassNominal heating capacity (A7;W45)COPEfficiency ClassCooling (Gross values)Nominal cooling capacity (A35;W18)Cooling absorbed powerEEREfficiency ClassNominal cooling capacity (A35;W7)Cooling absorbed powerEEREfficiency ClassCooling (EN14511 values)Nominal cooling capacity (A35;W18)EEREfficiency ClassNominal cooling capacity (A35;W7)EEREfficiency ClassCompressorType ScrollQuantity/Cooling circuitsCapacity controlTotal oil loadTotal refrigerant loadFansType AxialQuantityAir flow rateUser side exchangerType PlatesWater flow ratePressure dropHydraulic modulePump modelUseful pump headStorage tank capacityExpansion tank NoiseSound power levelNoise pressure levelDimensions and weightLengthDepthHeightOperating weight
MAROON 2 HT TECHNICAL DATA
(1) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 30-35°C(2) The total power is given by the sum of the power absorbed by the compressors and by the fans(3) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 40-45°C(4) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 60-65°C(5) External air temperature 35°C; input water-evaporator output temperature 23-18°C(6) External air temperature 35°C; input water-evaporator output temperature 12-7°C
(7) Sound power levels calculated compliant to ISO 3744(8) Sound pressure levels refer to 10 meters from unit in free field and directionality factor Q=2(9) Values compliant with EN 14511-3:2011This board reports the feature data of the base and standard versions; for details, refer to the specific documentation.
(1) kW 6,8 8,4 10,8 13,0 16,0 21,0 25,0 29,7 34,3 37,4(1), (2) kW 1,6 2,0 2,5 3,0 3,7 4,9 5,8 7,1 8,1 8,9
(1) 4,19 4,33 4,32 4,30 4,30 4,28 4,29 4,21 4,24 4,19A A A A A A A A A A
(3) kW 6,6 8,3 10,5 13,2 16,3 21,2 25,3 30,7 33,1 38,0(3), (2) kW 1,9 2,4 3,1 3,8 4,6 6,1 7,3 8,8 10,1 11,0
(3) 3,38 3,45 3,39 3,52 3,51 3,46 3,46 3,49 3,28 3,46A A A A A A A A A A
(1), (9) kW 6,8 8,5 10,8 13,1 16,1 21,1 25,2 29,9 34,5 37,6(1), (9) 4,15 4,30 4,28 4,19 4,20 4,18 4,19 4,13 4,16 4,13
A A A A A A A A A A(3), (9) kW 6,6 8,3 10,5 13,3 16,4 21,4 25,5 30,8 33,3 38,2(3), (9) 3,38 3,45 3,39 3,52 3,51 3,46 3,46 3,49 3,28 3,46
A A A A A A A A A A
(5) kW 8,3 10,4 13,3 15,4 18,6 25,2 29,9 38,1 41,9 48,4(5), (2) kW 2,0 2,6 3,4 3,8 4,6 6,3 7,4 9,7 10,4 12,3
(5) 4,24 4,07 3,88 4,10 4,03 4,02 4,05 3,91 4,05 3,95A A A A A A A A A A
(6) kW 6,1 7,7 10,1 12,1 14,5 19,8 23,1 29,9 34,0 37,8(6),(2) kW 1,9 2,4 3,2 3,7 4,5 6,1 7,0 9,2 10,1 11,5
(6) 3,24 3,18 3,15 3,29 3,24 3,25 3,33 3,26 3,38 3,27A A A A A A A A A A
(5), (9) kW 8,2 10,4 13,3 15,3 18,5 25,1 29,7 37,9 41,7 48,2(5), (9) 4,19 4,03 3,84 3,96 3,91 3,89 3,93 3,82 3,95 3,88
A A A A A A A A A A(6), (9) kW 6,0 7,7 10,0 12,0 14,4 19,6 22,9 29,8 33,8 37,6(6), (9) 3,20 3,15 3,11 3,17 3,14 3,14 3,22 3,18 3,29 3,20
A A A A A A A A A A
n° / n° 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1n° 1 1 1 1 1 1 1 1 1 1kg 0,7 1,2 1,2 1,2 1,2 1,9 3,4 3,4 3,4 3,4kg 2,6 3,5 4,2 6,2 7,0 8,4 9,1 10,7 12,4 13,5
n° 1 1 1 1 1 2 2 2 2 2m3/h 3.800 3.800 3.500 7.600 7.600 13.000 13.000 16.000 16.000 16.000
(1) l/h 1.166 1.451 1.856 2.239 2.750 3.603 4.298 5.109 5.895 6.439(1) kPa 4 4 6 31 28 35 36 30 31 26
P1 P1 P1 P2 P2 P3 P3 P3 P4 P4kPa 67 65 59 63 62 137 120 106 178 175
l 70 70 70 70 70 130 130 130 130 130l 2 2 2 2 2 5 5 5 5 5
(7) dB(A) 63 63 64 66 67 70 70 75 75 75(8) dB(A) 32 32 33 35 36 39 39 44 44 44
mm 1.105 1.105 1.105 1.105 1.105 1.105 1.105 1.305 1.305 1.305mm 505 505 505 505 505 505 505 505 505 505mm 982 982 982 982 982 1.385 1.385 1.585 1.585 1.585kg 108 112 118 124 133 232 251 385 405 416
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
23
Unit size 50 60 70 80 90Heating (Gross values)Nominal heating capacity (A7;W35)Heating absorbed powerCOPEfficiency ClassNominal heating capacity (A7;W45)Heating absorbed powerCOPEfficiency ClassHeating (EN14511 values)Nominal heating capacity (A7;W35)COPEfficiency ClassNominal heating capacity (A7;W45)COPEfficiency ClassCooling (Gross values)Nominal cooling capacity (A35;W18)Cooling absorbed powerEEREfficiency ClassNominal cooling capacity (A35;W7)Cooling absorbed powerEEREfficiency ClassCooling (EN14511 values)Nominal cooling capacity (A35;W18)EEREfficiency ClassNominal cooling capacity (A35;W7)EEREfficiency ClassCompressorType ScrollQuantity/Cooling circuitsCapacity controlTotal oil loadTotal refrigerant loadFansType AxialQuantityAir flow rateUser side exchangerType PlatesWater flow ratePressure dropHydraulic modulePump modelUseful pump headNoiseSound power levelNoise pressure levelDimensions and weightLengthDepthHeightOperating weight
MAROON 2 HT TECHNICAL DATA
(1) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 30-35°C(2) The total power is given by the sum of the power absorbed by the compressors and by the fans(3) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 40-45°C(4) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 60-65°C(5) External air temperature 35°C; input water-evaporator output temperature 23-18°C(6) External air temperature 35°C; input water-evaporator output temperature 12-7°C
(7) Sound power levels calculated compliant to ISO 3744(8) Sound pressure levels refer to 10 meters from unit in free field and directionality factor Q=2(9) Values compliant with EN 14511-3:2011This board reports the feature data of the base and standard versions; for details, refer to the specific documentation.
(1) kW 41,8 50,3 55,9 69,3 76,2(1), (2) kW 9,7 11,5 13,3 16,1 17,8
(1) 4,31 4,38 4,20 4,30 4,27A A A A A
(3) kW 42,4 51,1 57,7 70,7 77,5(3), (2) kW 12,2 14,4 16,8 20,0 22,0
(3) 3,48 3,54 3,43 3,53 3,52A A A A A
(1), (9) kW 42,0 50,5 56,2 69,7 76,5(1), (9) 4,23 4,30 4,14 4,23 4,20
A A A A A(3), (9) kW 42,6 51,4 57,9 71,0 77,9(3), (9) 3,48 3,54 3,43 3,53 3,52
A A A A A
(5) kW 49,7 57,9 71,9 80,9 93,1(5), (2) kW 13,1 15,4 19,2 21,2 25,1
(5) 3,80 3,77 3,74 3,81 3,70A B B A B
(6) kW 39,2 44,9 55,7 63,9 72,9(6),(2) kW 12,5 14,5 18,0 20,5 23,5
(6) 3,13 3,09 3,10 3,12 3,10A B B A A
(5), (9) kW 49,5 57,7 71,6 80,5 92,8(5), (9) 3,72 3,69 3,68 3,74 3,64
B B B B C(6), (9) kW 39,0 44,6 55,4 63,6 72,5(6), (9) 3,06 3,01 3,04 3,06 3,04
B B B B B
n° / n° 2/1 2/1 2/1 2/1 2/1n° 2 2 2 2 2kg 3,8 6,8 6,8 6,8 6,8kg 14,0 18,0 19,0 23,0 25,0
n° 1 1 1 1 1m3/h 18.000 17.000 17.000 24.000 24.000
(1) l/h 7.192 8.647 9.620 11.924 13.097(1) kPa 30 32 29 34 34
P5 P5 P5 P5 P5kPa 167 161 160 146 141
(7) dB(A) 73 73 74 75 77(8) dB(A) 42 42 43 44 46
mm 1.403 1.403 1.403 1.403 1.403mm 1.203 1.203 1.203 1.203 1.203mm 2.390 2.390 2.390 2.390 2.390kg 575 592 602 620 631
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
24
Unit size 8 10 12 16 18 20 23 25 29 34 38 42
Maximum absorbed power
Maximum absorbed current
Maximum current at peak
Maximum current at peak with soft-starterFan nominal powerFan nominal currentPump motor nominal powerPump motor nominal currentElectric power supplyOptional power supply
Unit size 52 62 72 82 92
Maximum absorbed power
Maximum absorbed current
Maximum current at peak
Maximum current at peak with soft-starterFan nominal powerFan nominal currentPump motor nominal powerPump motor nominal currentElectric power supplyOptional power supply
MAROON 2 MT ELECTRICAL DATA
MAROON 2 MT ELECTRICAL DATA
(1) Electric power that must be available from the electric network for the unit to work.(2) Current at which the units' internal protections intervene. It is the maximum current absor-bed by the unit. This value must never be exceeded and must be taken into account when sizing the line and the relative protection devices (see the wiring diagram supplied with the units).(3) The values between brackets refer to the ST version units with the maximum number of
pumps available (with or without storage tank).(4) Maximum peak current calculated considering the compressor start-up with higher power and maximum current absorbed by all other devices.This board reports the feature data of the base and standard versions; for details, refer to the specific documentation.
(1),(3) kW3,1 3,9 4,5 6,3 6,4 7,6 8,9 9,6 11,2 12,9 14,2 15,93,3 4,1 4,7 6,7 6,8 8,0 9,5 10,2 11,8 13,5 14,8 16,8
(2),(3) A16,7 19,7 8,7 11,5 13,3 16,5 18,4 19,4 26,0 27,0 30,0 36,0(17,7) (20,7) (9,7) (13,5) (15,3) (18,5) (21,2) (22,2) (28,8) (29,8) (32,8) (38,6)
(4) A61,7 82,7 48,7 65,5 65,5 75,5 104,4 98,4 116,0 123,0 123,0 145,0
(62,7) (83,7) (49,7) (67,5) (67,5) (77,5) (107,2) (101,2) (118,8) (125,8) (125,8) (147,6)
(4) A37,0 49,6 29,2 39,3 39,3 45,3 62,6 59,0 69,6 73,8 73,8 87,0
(37,6) (50,2) (29,8) (40,5) (40,5) (46,5) (64,3) (60,7) (71,3) (75,5) (75,5) (88,6)n° x kW 1 x 0,2 1 x 0,2 1 x 0,2 2 x 0,2 2 x 0,2 2 x 0,2 2 x 0,3 2 x 0,3 2 x 0,6 2 x 0,6 2 x 0,6 2 x 0,6n° x A 1 x 0,7 1 x 0,7 1 x 0,7 2 x 0,7 2 x 0,7 2 x 0,7 2 x 1,7 2 x 1,7 2 x 2,5 2 x 2,5 2 x 2,5 2 x 2,5kW 0,21 0,21 0,21 0,42 0,42 0,42 0,62 0,62 0,62 0,62 0,62 0,90A 1,00 1,00 1,00 2,00 2,00 2,00 2,77 2,77 2,77 2,77 2,77 2,61
V/ph/Hz 230/1~/50 230/1~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50
V/ph/Hz 400/3N~/50 400/3N~/50 230/1~/50 230/1~/50 - - - - - - - -
(1),(3) kW18,4 21,7 25,0 29,1 31,419,8 23,1 26,4 30,5 32,8
(2),(3) A34,9 44,5 46,5 54,7 66,7(37,6) (47,2) (49,2) (57,4) (69,4)
(4) A119,7 134,5 142,5 147,7 175,7(122,4) (137,2) (145,2) (150,4) (178,4)
(4) A71,8 80,7 85,5 88,6 105,4(73,4) (82,3) (87,1) (90,2) (107,0)
n° x kW 1 x 1,3 1 x 1,3 1 x 1,3 1 x 2,1 1 x 2,1n° x A 1 x 2,5 1 x 2,5 1 x 2,5 1 x 4,7 1 x 4,7kW 1,43 1,43 1,43 1,43 1,43A 2,70 2,70 2,70 2,70 2,70
V/ph/Hz 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50
V/ph/Hz
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
25
Unit size 7 9 11 13 17 22 26 32 36 41
Maximum absorbed power
Maximum absorbed current
Maximum current at peak
Maximum current at peak with soft-starterFan nominal powerFan nominal currentPump motor nominal powerPump motor nominal currentElectric power supplyOptional power supply
Unit size 50 60 70 80 90
Maximum absorbed power
Maximum absorbed current
Maximum current at peak
Maximum current at peak with soft-starterFan nominal powerFan nominal currentPump motor nominal powerPump motor nominal currentElectric power supplyOptional power supply
MAROON 2 HT ELECTRICAL DATA
MAROON 2 HT ELECTRICAL DATA
(1) Electric power that must be available from the electric network for the unit to work.(2) Current at which the units' internal protections intervene. It is the maximum current absor-bed by the unit. This value must never be exceeded and must be taken into account when sizing the line and the relative protection devices (see the wiring diagram supplied with the units).(3) The values between brackets refer to the ST version units with the maximum number of
pumps available (with or without storage tank).(4) Maximum peak current calculated considering the compressor start-up with higher power and maximum current absorbed by all other devices.This board reports the feature data of the base and standard versions; for details, refer to the specific documentation.
(1),(3) kW2,9 3,6 4,6 5,8 7,1 9,7 13,4 13,9 15,7 17,43,1 3,8 4,8 6,3 7,6 10,3 14,0 14,5 16,6 18,3
(2),(3) A13,5 6,9 7,9 11,7 13,4 19,4 32,4 34,0 39,5 44,0(14,5) (7,9) (8,9) (13,7) (15,4) (22,2) (35,2) (36,8) (42,1) (46,6)
(4) A60,7 43,7 52,2 54,0 72,5 104,4 121,4 123,0 145,0 179,0(61,7) (44,7) (53,2) (56,0) (74,5) (107,2) (124,2) (125,8) (147,6) (181,6)
(4) A36,4 26,2 31,3 32,4 43,5 62,6 72,8 73,8 87,0 107,4(37,0) (26,8) (31,9) (33,6) (44,7) (64,3) (74,5) (75,5) (88,6) (109,0)
n° x kW 1 x 0,2 1 x 0,2 1 x 0,2 1 x 0,6 1 x 0,6 2 x 0,3 2 x 0,3 2 x 0,6 2 x 0,6 2 x 0,6n° x A 1 x 0,7 1 x 0,7 1 x 0,7 1 x 2,5 1 x 2,5 2 x 1,7 2 x 1,7 2 x 2,5 2 x 2,5 2 x 2,5kW 0,21 0,21 0,21 0,42 0,42 0,62 0,62 0,62 0,90 0,90A 1,00 1,00 1,00 2,00 2,00 2,77 2,77 2,77 2,61 2,61
V/ph/Hz 230/1~/50 230/1~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50
V/ph/Hz - - 230/1~/50 - - - - - - -
(1),(3) kW19,5 26,8 26,8 31,3 34,720,9 28,2 28,2 32,7 36,1
(2),(3) A34,5 60,5 60,5 73,7 82,7(37,2) (63,2) (63,2) (76,4) (85,4)
(4) A119,5 149,5 149,5 179,2 217,7(122,2) (152,2) (152,2) (181,9) (220,4)
(4) A71,7 89,7 89,7 107,5 130,6
(73,3) (91,3) (91,3) (109,1) (132,2)n° x kW 1 x 1,3 1 x 1,3 1 x 1,3 1 x 2,1 1 x 2,1n° x A 1 x 2,5 1 x 2,5 1 x 2,5 1 x 4,7 1 x 4,7kW 1,43 1,43 1,43 1,43 1,43A 2,70 2,70 2,70 2,70 2,70
V/ph/Hz 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50
V/ph/Hz
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
26
0
50
100
150
200
250
0 1.000 2.000 3.000 4.000 5.000 6.000 7.000 8.000 9.000 10.000
P2 P3
P4
P1
0
10
20
30
40
50
60
70
80
90
100
0 1000 2000 3000 4000 5000 6000 7000 8000 9000
8
18 23
20
1610-12-29
42
34
38
STA
TIC
HEA
D [k
Pa]
CAPACITY [l/h]
CAPACITY [l/h]
PRES
SURE
DRO
PS [k
Pa]
EXCHANGER DIAGRAMS - MAROON 2 MT
PUMP DIAGRAMS - MAROON 2 MT
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
27
0
50
100
150
200
250
5.000 6.000 7.000 8.000 9.000 10.000 11.000 12.000 13.000 14.000 15.000
P5
0
10
20
30
40
50
60
70
80
90
100
5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000
92
62
82
72
52
STA
TIC
HEA
D [k
Pa]
CAPACITY [l/h]
CAPACITY [l/h]
PRES
SURE
DRO
PS [k
Pa]
EXCHANGER DIAGRAMS - MAROON 2 MT
PUMP DIAGRAMS - MAROON 2 MT
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
28
0
50
100
150
200
250
0 1.000 2.000 3.000 4.000 5.000 6.000 7.000 8.000 9.000 10.000
P2 P3
P4
P1
0
10
20
30
40
50
60
70
80
90
100
0 1000 2000 3000 4000 5000 6000 7000 8000 9000
139
17 117 22
36
26
32
41
STA
TIC
HEA
D [k
Pa]
CAPACITY [l/h]
CAPACITY [l/h]
PRES
SURE
DRO
PS [k
Pa]
EXCHANGER DIAGRAMS - MAROON 2 HT
PUMP DIAGRAMS - MAROON 2 HT
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
29
0
50
100
150
200
250
5.000 6.000 7.000 8.000 9.000 10.000 11.000 12.000 13.000 14.000 15.000
P5
0
10
20
30
40
50
60
70
80
90
100
5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000
90
60
80
70
50
STA
TIC
HEA
D [k
Pa]
CAPACITY [l/h]
CAPACITY [l/h]
PRES
SURE
DRO
PS [k
Pa]
EXCHANGER DIAGRAMS - MAROON 2 HT
PUMP DIAGRAMS - MAROON 2 HT
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
30
25
30
35
40
45
50
55
60
65
-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50
-10
-5
0
5
10
15
20
25
-15 -10 -5 0 5 10 15 20 25 30 35 40 45 50
25
30
35
40
45
50
55
60
-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50
Notes: The thermal gradient to the utility side exchanger must be between 3°C and 6°C : the unit can only operate in this area with evaporator side glycol water
Util
ity
outle
t w
ater
tem
pera
ture
(°C
)U
tilit
y ou
tlet
wat
er t
empe
ratu
re (°
C)
Util
ity
outle
t w
ater
tem
pera
ture
(°C
)
HEATING
COOLING
RECOVERY
External air temperature (°C)
External air temperature (°C)
External air temperature (°C)
OPERATING LIMITS - MAROON 2 MT
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
31
25
30
35
40
45
50
55
60
65
70
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50
-10
-5
0
5
10
15
20
25
-15 -10 -5 0 5 10 15 20 25 30 35 40 45 50
25
30
35
40
45
50
55
60
65
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50
Notes: The thermal gradient to the utility side exchanger must be between 3°C and 6°C : the unit can only operate in this area with evaporator side glycol water : limit for models 7, 9 and 11
Util
ity
outle
t w
ater
tem
pera
ture
(°C
)U
tilit
y ou
tlet
wat
er t
empe
ratu
re (°
C)
Util
ity
outle
t w
ater
tem
pera
ture
(°C
)
HEATING
COOLING
RECOVERY
External air temperature (°C)
External air temperature (°C)
External air temperature (°C)
OPERATING LIMITS - MAROON 2 HT
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
32
COOLING CAPACITIES - MAROON 2 MT
Pf: Cooling power [kW]
Pa: Total absorbed compressor power [kW]
To: Utility outlet water temperature to the utility exchanger [°C]
Model
To External air temperature [°C]
[°C]25 30 35 40
Pf Pat EER Pf Pat EER Pf Pat EER Pf Pat EER
8
5 6,5 1,7 3,82 6,2 1,9 3,24 5,8 2,1 2,71 5,4 2,4 2,256 6,7 1,7 3,92 6,4 1,9 3,33 6,0 2,1 2,80 5,6 2,4 2,337 6,9 1,7 4,04 6,6 1,9 3,43 6,2 2,1 2,87 5,7 2,4 2,408 7,2 1,7 4,14 6,8 1,9 3,52 6,4 2,1 2,97 5,9 2,4 2,469 7,4 1,7 4,27 7,0 1,9 3,62 6,6 2,2 3,04 6,1 2,4 2,5410 7,6 1,7 4,37 7,2 1,9 3,71 6,8 2,2 3,13 6,3 2,4 2,6113 8,3 1,8 4,70 7,8 2,0 3,99 7,4 2,2 3,38 6,9 2,4 2,8314 8,5 1,8 4,80 8,1 2,0 4,09 7,6 2,2 3,46 7,1 2,4 2,9015 8,7 1,8 4,91 8,3 2,0 4,18 7,8 2,2 3,54 7,3 2,4 2,9716 9,0 1,8 5,02 8,5 2,0 4,30 8,0 2,2 3,63 7,5 2,5 3,0417 9,2 1,8 5,13 8,7 2,0 4,39 8,2 2,2 3,71 7,7 2,5 3,1318 9,5 1,8 5,23 9,0 2,0 4,49 8,5 2,2 3,80 7,9 2,5 3,20
10
5 8,1 2,0 4,09 7,6 2,2 3,42 7,1 2,5 2,84 6,6 2,8 2,336 8,3 2,0 4,20 7,8 2,2 3,51 7,3 2,5 2,92 6,8 2,8 2,407 8,6 2,0 4,30 8,1 2,2 3,61 7,5 2,5 3,00 7,0 2,8 2,468 8,8 2,0 4,41 8,3 2,2 3,70 7,8 2,5 3,07 7,2 2,8 2,539 9,1 2,0 4,51 8,6 2,3 3,78 8,0 2,5 3,15 7,4 2,9 2,5910 9,3 2,0 4,62 8,8 2,3 3,88 8,2 2,5 3,23 7,6 2,9 2,6613 10,1 2,1 4,91 9,5 2,3 4,13 8,9 2,6 3,45 8,3 2,9 2,8614 10,4 2,1 5,02 9,8 2,3 4,23 9,2 2,6 3,53 8,5 2,9 2,9315 10,7 2,1 5,11 10,1 2,3 4,30 9,4 2,6 3,61 8,8 2,9 2,9916 11,0 2,1 5,21 10,3 2,4 4,40 9,7 2,6 3,68 9,0 2,9 3,0617 11,3 2,1 5,31 10,6 2,4 4,48 9,9 2,6 3,77 9,2 3,0 3,1318 11,6 2,1 5,42 10,9 2,4 4,57 10,2 2,7 3,83 9,5 3,0 3,19
12
5 10,3 2,3 4,41 9,7 2,6 3,77 9,1 2,8 3,19 8,4 3,2 2,656 10,6 2,3 4,52 10,0 2,6 3,86 9,3 2,9 3,26 8,7 3,2 2,727 10,9 2,4 4,62 10,3 2,6 3,94 9,6 2,9 3,34 8,9 3,2 2,788 11,2 2,4 4,73 10,6 2,6 4,02 9,9 2,9 3,41 9,2 3,2 2,859 11,5 2,4 4,83 10,9 2,6 4,12 10,2 2,9 3,48 9,5 3,3 2,9010 11,9 2,4 4,92 11,2 2,7 4,21 10,5 2,9 3,56 9,7 3,3 2,9713 12,9 2,5 5,22 12,1 2,7 4,46 11,4 3,0 3,78 10,6 3,3 3,1714 13,2 2,5 5,32 12,5 2,7 4,54 11,7 3,0 3,86 10,9 3,4 3,2315 13,6 2,5 5,41 12,8 2,8 4,63 12,0 3,1 3,92 11,1 3,4 3,2916 13,9 2,5 5,51 13,1 2,8 4,70 12,3 3,1 4,00 11,4 3,4 3,3617 14,3 2,5 5,60 13,5 2,8 4,79 12,6 3,1 4,07 11,7 3,4 3,4118 14,6 2,6 5,68 13,8 2,8 4,88 13,0 3,1 4,14 12,0 3,5 3,48
16
5 14,0 3,4 4,16 13,2 3,7 3,57 12,5 4,1 3,02 11,6 4,6 2,516 14,4 3,4 4,25 13,6 3,7 3,66 12,9 4,1 3,10 12,0 4,6 2,587 14,8 3,4 4,35 14,0 3,8 3,74 13,2 4,2 3,17 12,3 4,7 2,658 15,2 3,4 4,44 14,4 3,8 3,82 13,6 4,2 3,26 12,7 4,7 2,729 15,6 3,4 4,54 14,8 3,8 3,91 14,0 4,2 3,33 13,1 4,7 2,7910 16,1 3,5 4,63 15,3 3,8 3,99 14,4 4,2 3,40 13,4 4,7 2,8513 17,4 3,6 4,89 16,5 3,9 4,23 15,6 4,3 3,61 14,6 4,8 3,0514 17,8 3,6 4,97 17,0 3,9 4,31 16,0 4,3 3,69 15,0 4,8 3,1115 18,3 3,6 5,07 17,4 4,0 4,39 16,4 4,4 3,76 15,4 4,8 3,1716 18,8 3,7 5,14 17,9 4,0 4,46 16,9 4,4 3,83 15,8 4,9 3,2417 19,3 3,7 5,22 18,3 4,0 4,53 17,3 4,4 3,90 16,2 4,9 3,3018 19,7 3,7 5,31 18,8 4,1 4,61 17,7 4,5 3,96 16,6 4,9 3,36
18
5 15,0 3,7 4,01 14,1 4,1 3,46 13,2 4,5 2,96 12,2 4,9 2,506 15,4 3,7 4,12 14,6 4,1 3,56 13,7 4,5 3,05 12,7 4,9 2,587 15,9 3,8 4,23 15,0 4,1 3,66 14,1 4,5 3,13 13,1 4,9 2,658 16,4 3,8 4,34 15,5 4,1 3,75 14,5 4,5 3,22 13,5 4,9 2,739 16,9 3,8 4,45 16,0 4,1 3,85 15,0 4,5 3,31 13,9 5,0 2,8110 17,4 3,8 4,57 16,4 4,2 3,96 15,4 4,5 3,40 14,4 5,0 2,8913 18,9 3,8 4,91 17,9 4,2 4,26 16,8 4,6 3,66 15,7 5,0 3,1214 19,4 3,9 5,02 18,4 4,2 4,37 17,3 4,6 3,76 16,1 5,0 3,2015 19,9 3,9 5,14 18,9 4,2 4,47 17,8 4,6 3,85 16,6 5,1 3,2916 20,5 3,9 5,27 19,5 4,2 4,58 18,3 4,6 3,94 17,1 5,1 3,3717 21,1 3,9 5,38 20,0 4,3 4,68 18,8 4,7 4,05 17,6 5,1 3,4618 21,6 3,9 5,51 20,5 4,3 4,79 19,4 4,7 4,14 18,1 5,1 3,54
20
5 17,6 4,1 4,28 16,7 4,5 3,68 15,7 5,0 3,15 14,6 5,5 2,666 18,2 4,2 4,37 17,2 4,6 3,77 16,2 5,0 3,22 15,1 5,5 2,727 18,7 4,2 4,46 17,7 4,6 3,85 16,7 5,1 3,29 15,5 5,6 2,798 19,2 4,2 4,56 18,2 4,6 3,93 17,1 5,1 3,37 16,0 5,6 2,859 19,8 4,3 4,64 18,7 4,7 4,01 17,6 5,1 3,43 16,5 5,7 2,9110 20,3 4,3 4,73 19,3 4,7 4,10 18,1 5,2 3,50 16,9 5,7 2,9713 22,1 4,4 5,01 20,9 4,8 4,34 19,7 5,3 3,72 18,4 5,8 3,1614 22,7 4,4 5,10 21,5 4,9 4,42 20,2 5,3 3,79 18,9 5,9 3,2215 23,3 4,5 5,19 22,0 4,9 4,50 20,8 5,4 3,87 19,4 5,9 3,2916 23,9 4,5 5,28 22,6 4,9 4,58 21,3 5,4 3,94 19,9 6,0 3,3517 24,5 4,6 5,38 23,2 5,0 4,66 21,9 5,5 4,00 20,5 6,0 3,4118 25,1 4,6 5,46 23,8 5,0 4,74 22,5 5,5 4,08 21,0 6,0 3,48
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
33
COOLING CAPACITIES - MAROON 2 MT
Pf: Cooling power [kW]
Pa: Total absorbed compressor power [kW]
To: Utility outlet water temperature to the utility exchanger [°C]
Model
To External air temperature [°C]
[°C]25 30 35 40
Pf Pat EER Pf Pat EER Pf Pat EER Pf Pat EER
23
5 20,0 4,9 4,05 18,9 5,4 3,50 17,8 5,9 2,99 16,6 6,6 2,536 20,5 5,0 4,14 19,5 5,4 3,58 18,4 6,0 3,07 17,2 6,6 2,607 21,2 5,0 4,23 20,1 5,5 3,66 18,9 6,0 3,14 17,7 6,7 2,668 21,8 5,0 4,32 20,7 5,5 3,74 19,5 6,1 3,21 18,3 6,7 2,739 22,4 5,1 4,40 21,3 5,6 3,81 20,1 6,1 3,28 18,8 6,7 2,7910 23,1 5,1 4,48 21,9 5,6 3,89 20,7 6,2 3,35 19,4 6,8 2,8513 25,1 5,3 4,74 23,8 5,8 4,12 22,5 6,3 3,56 21,1 6,9 3,0514 25,7 5,3 4,82 24,5 5,8 4,21 23,2 6,4 3,63 21,7 7,0 3,1115 26,4 5,4 4,91 25,2 5,9 4,28 23,8 6,4 3,70 22,3 7,0 3,1716 27,2 5,4 4,99 25,9 5,9 4,36 24,5 6,5 3,78 23,0 7,1 3,2417 27,9 5,5 5,08 26,6 6,0 4,43 25,1 6,5 3,84 23,6 7,2 3,3018 28,6 5,6 5,15 27,3 6,0 4,51 25,8 6,6 3,92 24,3 7,2 3,36
25
5 22,0 5,3 4,14 20,8 5,9 3,55 19,5 6,4 3,02 18,1 7,1 2,546 22,7 5,4 4,23 21,4 5,9 3,64 20,1 6,5 3,10 18,6 7,2 2,607 23,3 5,4 4,33 22,1 5,9 3,72 20,7 6,5 3,17 19,2 7,2 2,678 24,0 5,4 4,42 22,7 6,0 3,82 21,3 6,6 3,25 19,8 7,2 2,749 24,7 5,5 4,51 23,4 6,0 3,90 22,0 6,6 3,33 20,4 7,3 2,8110 25,4 5,5 4,60 24,1 6,0 3,98 22,6 6,6 3,40 21,0 7,3 2,8713 27,5 5,7 4,88 26,1 6,2 4,22 24,6 6,8 3,63 22,9 7,5 3,0714 28,3 5,7 4,96 26,8 6,2 4,31 25,2 6,8 3,70 23,5 7,5 3,1415 29,0 5,8 5,04 27,6 6,3 4,39 25,9 6,9 3,77 24,2 7,5 3,2016 29,8 5,8 5,14 28,3 6,3 4,47 26,6 6,9 3,85 24,9 7,6 3,2717 30,6 5,9 5,21 29,0 6,4 4,55 27,4 7,0 3,92 25,5 7,6 3,3418 31,4 5,9 5,30 29,8 6,4 4,63 28,1 7,0 3,99 26,2 7,7 3,41
29
5 25,4 6,5 3,92 24,2 7,1 3,43 22,8 7,7 2,96 21,4 8,5 2,536 26,2 6,5 4,01 24,9 7,1 3,51 23,5 7,7 3,04 22,0 8,5 2,597 27,0 6,6 4,11 25,7 7,1 3,59 24,3 7,8 3,12 22,7 8,5 2,668 27,8 6,6 4,20 26,4 7,2 3,67 25,0 7,8 3,18 23,4 8,6 2,739 28,6 6,7 4,28 27,2 7,2 3,76 25,7 7,9 3,26 24,1 8,6 2,7910 29,4 6,7 4,38 27,9 7,3 3,84 26,4 7,9 3,33 24,8 8,7 2,8613 31,8 6,9 4,63 30,3 7,5 4,07 28,7 8,1 3,54 27,0 8,8 3,0514 32,7 6,9 4,71 31,1 7,5 4,14 29,4 8,2 3,60 27,7 8,9 3,1115 33,6 7,0 4,78 31,9 7,6 4,21 30,2 8,2 3,67 28,4 9,0 3,1716 34,4 7,1 4,86 32,8 7,7 4,28 31,0 8,3 3,74 29,2 9,0 3,2317 35,3 7,2 4,94 33,6 7,7 4,35 31,8 8,4 3,80 29,9 9,1 3,2918 36,2 7,2 5,00 34,5 7,8 4,41 32,7 8,5 3,86 30,7 9,2 3,34
34
5 31,3 7,3 4,30 29,6 8,0 3,71 27,7 8,8 3,16 25,7 9,6 2,666 32,2 7,3 4,39 30,4 8,0 3,80 28,5 8,8 3,24 26,5 9,7 2,737 33,1 7,4 4,49 31,4 8,1 3,89 29,4 8,9 3,32 27,3 9,7 2,818 34,1 7,4 4,59 32,3 8,1 3,97 30,3 8,9 3,40 28,1 9,8 2,879 35,0 7,5 4,68 33,2 8,2 4,06 31,2 9,0 3,48 29,0 9,8 2,9410 36,0 7,5 4,78 34,1 8,2 4,15 32,1 9,0 3,55 29,8 9,9 3,0113 39,0 7,7 5,05 37,0 8,4 4,40 34,8 9,2 3,78 32,4 10,1 3,2114 40,0 7,8 5,14 38,0 8,5 4,48 35,7 9,3 3,86 33,3 10,1 3,2815 41,1 7,8 5,23 39,0 8,5 4,56 36,7 9,3 3,94 34,2 10,2 3,3516 42,1 7,9 5,32 40,0 8,6 4,65 37,7 9,4 4,01 35,1 10,3 3,4217 43,2 8,0 5,41 41,0 8,7 4,73 38,7 9,5 4,09 36,1 10,3 3,4918 44,3 8,1 5,49 42,1 8,8 4,81 39,6 9,5 4,16 37,0 10,4 3,55
38
5 34,0 8,5 4,02 32,3 9,3 3,48 30,3 10,2 2,97 28,2 11,3 2,506 35,0 8,5 4,11 33,2 9,3 3,56 31,2 10,3 3,04 29,0 11,3 2,567 36,1 8,6 4,21 34,2 9,4 3,65 32,2 10,3 3,12 29,9 11,4 2,638 37,1 8,6 4,30 35,2 9,4 3,72 33,1 10,4 3,19 30,8 11,5 2,699 38,1 8,7 4,39 36,2 9,5 3,81 34,0 10,4 3,26 31,7 11,5 2,7510 39,2 8,8 4,48 37,2 9,6 3,89 35,0 10,5 3,33 32,6 11,6 2,8113 42,5 9,0 4,74 40,3 9,8 4,13 38,0 10,7 3,54 35,4 11,8 3,0014 43,6 9,0 4,83 41,4 9,8 4,20 39,0 10,8 3,61 36,4 11,9 3,0615 44,7 9,1 4,92 42,5 9,9 4,28 40,0 10,9 3,68 37,3 11,9 3,1216 45,9 9,2 5,00 43,6 10,0 4,36 41,1 10,9 3,75 38,3 12,0 3,1917 47,1 9,3 5,09 44,7 10,1 4,44 42,1 11,0 3,82 39,3 12,1 3,2518 48,3 9,3 5,17 45,8 10,2 4,51 43,2 11,1 3,89 40,3 12,2 3,31
42
5 40,7 9,3 4,40 38,6 10,1 3,82 36,2 11,1 3,27 33,6 12,1 2,776 41,9 9,3 4,49 39,7 10,2 3,90 37,3 11,1 3,35 34,6 12,2 2,837 43,1 9,4 4,58 40,9 10,3 3,99 38,4 11,2 3,42 35,7 12,3 2,908 44,3 9,5 4,67 42,0 10,3 4,07 39,5 11,3 3,49 36,7 12,4 2,969 45,6 9,6 4,76 43,2 10,4 4,15 40,6 11,4 3,57 37,7 12,5 3,0310 46,8 9,7 4,85 44,4 10,5 4,23 41,7 11,5 3,64 38,8 12,6 3,0913 50,7 9,9 5,12 48,1 10,8 4,47 45,2 11,7 3,85 42,0 12,8 3,2814 52,1 10,0 5,20 49,4 10,9 4,55 46,4 11,8 3,92 43,2 12,9 3,3415 53,4 10,1 5,28 50,7 10,9 4,63 47,6 11,9 4,00 44,3 13,0 3,4116 54,8 10,2 5,37 52,0 11,1 4,70 48,9 12,0 4,07 45,5 13,1 3,4717 56,2 10,3 5,45 53,3 11,2 4,78 50,1 12,1 4,14 46,6 13,2 3,5318 57,7 10,4 5,53 54,7 11,3 4,85 51,4 12,2 4,21 47,8 13,3 3,59
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
34
HEATING CAPACITIES - MAROON 2 MT
Pt Heating capacity [kW]
Pa: Total absorbed compressor power [kW]
Ta: Dry bulb temperature of the evaporator inlet air [°C]
RH: Relative humidity of the input air at the evaporator [%]
Model
Ta RH Condenser inlet water temperature [°C]
[°C] %30/35 40/45 50/55 55/60
Pt Pat COP Pt Pat COP Pt Pat COP Pt Pat COP
8
-16 90 4,1 1,8 2,26 * * * * * * * * *-15 90 4,2 1,8 2,32 * * * * * * * * *-10 90 4,7 1,8 2,63 4,8 2,3 2,14 * * * * * *-7 89 5,0 1,8 2,86 5,1 2,2 2,30 * * * * * *-2 89 5,7 1,7 3,26 5,7 2,2 2,61 5,8 2,8 2,10 5,9 3,1 1,880 88 5,9 1,7 3,43 5,9 2,2 2,72 6,0 2,8 2,18 6,1 3,1 1,952 88 6,2 1,7 3,61 6,2 2,2 2,87 6,3 2,7 2,29 6,3 3,1 2,045 87 6,7 1,7 3,88 6,6 2,1 3,08 6,6 2,7 2,42 6,6 3,1 2,167 87 7,0 1,7 4,10 6,9 2,1 3,24 6,9 2,7 2,55 6,8 3,0 2,2610 86 7,5 1,7 4,44 7,4 2,1 3,48 7,3 2,7 2,73 7,2 3,0 2,3912 86 7,9 1,7 4,65 7,7 2,1 3,66 7,6 2,7 2,85 7,5 3,0 2,5215 86 8,5 1,7 5,04 8,2 2,1 3,93 8,0 2,6 3,06 7,9 3,0 2,68
10
-16 90 5,2 2,3 2,29 * * * * * * * * *-15 90 5,3 2,3 2,34 * * * * * * * * *-10 90 6,0 2,3 2,65 6,2 2,9 2,13 * * * * * *-7 89 6,4 2,2 2,88 6,6 2,9 2,30 * * * * * *-2 89 7,2 2,2 3,28 7,4 2,8 2,59 7,6 3,7 2,07 7,6 4,2 1,840 88 7,6 2,2 3,44 7,6 2,8 2,71 7,8 3,6 2,14 7,9 4,1 1,922 88 7,9 2,2 3,61 8,0 2,8 2,85 8,1 3,6 2,25 8,2 4,1 2,005 87 8,5 2,2 3,91 8,5 2,8 3,05 8,5 3,6 2,39 8,6 4,1 2,127 87 8,9 2,2 4,12 8,8 2,8 3,20 8,9 3,5 2,50 8,9 4,0 2,2210 86 9,6 2,1 4,46 9,4 2,7 3,44 9,4 3,5 2,67 9,4 4,0 2,3512 86 10,0 2,1 4,70 9,8 2,7 3,61 9,7 3,5 2,79 9,7 4,0 2,4515 86 10,8 2,1 5,07 10,6 2,7 3,91 10,3 3,5 2,98 10,3 3,9 2,61
12
-16 90 6,3 2,5 2,53 * * * * * * * * *-15 90 6,5 2,5 2,59 * * * * * * * * *-10 90 7,3 2,5 2,91 7,4 3,1 2,35 * * * * * *-7 89 7,9 2,5 3,13 7,9 3,1 2,52 * * * * * *-2 89 9,0 2,5 3,53 8,9 3,2 2,82 8,9 4,0 2,24 9,0 4,5 1,990 88 9,4 2,5 3,70 9,3 3,2 2,95 9,3 4,0 2,33 9,3 4,5 2,062 88 9,9 2,5 3,87 9,7 3,2 3,07 9,7 4,0 2,43 9,7 4,5 2,145 87 10,6 2,6 4,15 10,4 3,2 3,29 10,3 4,0 2,58 10,2 4,5 2,277 87 11,2 2,6 4,36 10,9 3,2 3,44 10,7 4,0 2,69 10,6 4,5 2,3610 86 12,0 2,6 4,68 11,7 3,2 3,69 11,4 4,0 2,87 11,3 4,5 2,5012 86 12,6 2,6 4,92 12,3 3,2 3,87 11,9 4,0 2,99 11,7 4,5 2,6115 86 13,5 2,6 5,28 13,2 3,2 4,13 12,7 4,0 3,20 12,5 4,5 2,79
16
-16 90 8,7 3,6 2,42 * * * * * * * * *-15 90 8,9 3,6 2,48 * * * * * * * * *-10 90 10,1 3,6 2,79 10,2 4,6 2,20 * * * * * *-7 89 10,9 3,6 3,00 10,9 4,6 2,37 * * * * * *-2 89 12,2 3,6 3,40 12,2 4,6 2,68 12,2 6,0 2,04 12,1 6,9 1,760 88 12,8 3,6 3,56 12,7 4,5 2,80 12,6 5,9 2,13 12,6 6,8 1,842 88 13,4 3,6 3,71 13,3 4,5 2,94 13,2 5,9 2,24 13,1 6,8 1,935 87 14,3 3,6 3,98 14,1 4,5 3,14 13,9 5,8 2,40 13,8 6,7 2,057 87 15,0 3,6 4,16 14,8 4,5 3,29 14,5 5,8 2,52 14,3 6,6 2,1710 86 16,1 3,6 4,45 15,7 4,5 3,52 15,4 5,7 2,69 15,1 6,6 2,3012 86 16,8 3,6 4,63 16,4 4,5 3,67 16,0 5,7 2,82 15,8 6,5 2,4315 86 18,1 3,6 4,98 17,6 4,5 3,93 17,1 5,7 3,02 16,7 6,5 2,60
18
-16 90 9,1 4,1 2,24 * * * * * * * * *-15 90 9,4 4,1 2,31 * * * * * * * * *-10 90 10,9 4,1 2,67 10,6 4,9 2,14 * * * * * *-7 89 11,9 4,1 2,91 11,5 4,9 2,34 * * * * * *-2 89 13,5 4,1 3,33 13,2 4,9 2,68 12,7 6,0 2,13 12,5 6,6 1,880 88 14,2 4,1 3,50 13,8 4,9 2,81 13,3 6,0 2,22 13,0 6,6 1,972 88 14,8 4,0 3,67 14,5 4,9 2,95 14,0 6,0 2,35 13,7 6,6 2,075 87 16,0 4,0 3,96 15,5 4,9 3,18 15,0 5,9 2,52 14,6 6,6 2,227 87 16,7 4,0 4,16 16,3 4,9 3,34 15,7 5,9 2,65 15,4 6,6 2,3410 86 18,1 4,0 4,50 17,4 4,8 3,60 16,8 5,9 2,84 16,4 6,6 2,5012 86 19,0 4,0 4,75 18,3 4,8 3,77 17,6 5,9 2,99 17,2 6,5 2,6315 86 20,4 4,0 5,12 19,7 4,8 4,10 18,8 5,9 3,21 18,3 6,5 2,82
20
-16 90 10,9 4,2 2,57 * * * * * * * * *-15 90 11,1 4,2 2,63 * * * * * * * * *-10 90 12,6 4,3 2,96 12,6 5,2 2,41 * * * * * *-7 89 13,7 4,3 3,18 13,6 5,3 2,58 * * * * * *-2 89 15,6 4,3 3,59 15,3 5,3 2,88 15,2 6,6 2,30 15,1 7,4 2,050 88 16,3 4,4 3,74 16,1 5,4 3,00 15,8 6,6 2,38 15,7 7,4 2,122 88 17,1 4,4 3,91 16,8 5,4 3,13 16,5 6,6 2,48 16,3 7,4 2,205 87 18,4 4,4 4,19 18,0 5,4 3,33 17,6 6,7 2,63 17,3 7,5 2,327 87 19,4 4,4 4,37 18,9 5,4 3,47 18,4 6,7 2,74 18,1 7,5 2,4210 86 20,9 4,5 4,67 20,2 5,5 3,71 19,6 6,7 2,90 19,3 7,5 2,5512 86 21,9 4,5 4,89 21,2 5,5 3,86 20,5 6,8 3,03 20,1 7,6 2,6615 86 23,7 4,5 5,23 22,8 5,5 4,14 21,9 6,8 3,22 21,4 7,6 2,82
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
35
Pt: Heating capacity [kW]
Pa: Total absorbed compressor power [kW]
Ta: Dry bulb temperature of the evaporator inlet air [°C]
RH: Relative humidity of the input air at the evaporator [%]
HEATING CAPACITIES - MAROON 2 MT
Model
Ta RH Condenser inlet water temperature [°C]
[°C] %30/35 40/45 50/55 55/60
Pt Pat COP Pt Pat COP Pt Pat COP Pt Pat COP
23
-16 90 12,3 4,9 2,52 * * * * * * * * *-15 90 12,7 4,9 2,59 * * * * * * * * *-10 90 14,4 5,0 2,91 14,4 6,1 2,35 * * * * * *-7 89 15,7 5,0 3,14 15,5 6,2 2,51 * * * * * *-2 89 17,9 5,1 3,54 17,6 6,2 2,82 17,4 7,8 2,24 17,5 8,7 2,000 88 18,7 5,1 3,69 18,3 6,3 2,92 18,1 7,8 2,33 18,1 8,7 2,072 88 19,7 5,1 3,85 19,3 6,3 3,07 19,0 7,8 2,43 18,9 8,8 2,165 87 21,1 5,2 4,10 20,6 6,3 3,27 20,1 7,8 2,57 20,0 8,8 2,287 87 22,2 5,2 4,29 21,7 6,3 3,41 21,2 7,9 2,70 20,9 8,8 2,3810 86 23,8 5,2 4,56 23,2 6,4 3,63 22,6 7,9 2,86 22,1 8,8 2,5112 86 25,0 5,3 4,75 24,3 6,4 3,79 23,6 7,9 2,98 23,3 8,8 2,6315 86 27,0 5,3 5,07 26,1 6,5 4,04 25,2 8,0 3,17 24,8 8,9 2,79
25
-16 90 13,2 5,5 2,42 * * * * * * * * *-15 90 13,6 5,5 2,48 * * * * * * * * *-10 90 15,6 5,5 2,83 15,5 6,9 2,26 * * * * * *-7 89 17,0 5,6 3,06 16,8 6,9 2,44 * * * * * *-2 89 19,5 5,6 3,48 19,1 6,9 2,76 18,7 8,6 2,18 18,6 9,7 1,930 88 20,4 5,6 3,64 19,9 6,9 2,88 19,5 8,6 2,26 19,4 9,7 2,002 88 21,4 5,6 3,81 20,9 6,9 3,02 20,4 8,6 2,37 20,2 9,7 2,095 87 23,0 5,6 4,09 22,4 6,9 3,23 21,7 8,6 2,52 21,4 9,7 2,217 87 24,2 5,6 4,28 23,5 6,9 3,39 22,8 8,6 2,65 22,4 9,7 2,3210 86 25,9 5,7 4,58 25,2 6,9 3,62 24,3 8,6 2,82 23,8 9,7 2,4612 86 27,2 5,7 4,79 26,4 7,0 3,79 25,4 8,6 2,95 24,9 9,6 2,5815 86 29,3 5,7 5,12 28,3 7,0 4,06 27,2 8,6 3,15 26,5 9,6 2,75
29
-16 90 15,3 6,7 2,30 * * * * * * * * *-15 90 15,7 6,7 2,36 * * * * * * * * *-10 90 18,0 6,7 2,69 17,8 8,2 2,17 * * * * * *-7 89 19,6 6,7 2,92 19,2 8,2 2,35 * * * * * *-2 89 22,3 6,7 3,32 21,9 8,2 2,69 21,4 10,1 2,11 21,2 11,4 1,860 88 23,4 6,7 3,48 22,8 8,2 2,80 22,3 10,1 2,21 22,1 11,4 1,942 88 24,6 6,7 3,65 24,1 8,2 2,96 23,5 10,1 2,33 23,2 11,3 2,055 87 26,5 6,8 3,91 25,8 8,2 3,17 25,0 10,0 2,49 24,7 11,3 2,197 87 27,8 6,8 4,10 27,1 8,2 3,32 26,3 10,0 2,63 25,9 11,2 2,3110 86 29,9 6,8 4,38 29,0 8,2 3,55 28,1 10,0 2,81 27,5 11,2 2,4612 86 31,3 6,8 4,57 30,4 8,2 3,71 29,4 10,0 2,94 28,9 11,2 2,5915 86 33,8 6,9 4,89 32,6 8,2 3,96 31,4 10,0 3,14 30,8 11,2 2,76
34
-16 90 18,0 7,5 2,39 * * * * * * * * *-15 90 18,5 7,5 2,45 * * * * * * * * *-10 90 21,2 7,6 2,79 21,0 9,3 2,24 * * * * * *-7 89 23,0 7,6 3,02 22,7 9,4 2,43 * * * * * *-2 89 26,2 7,6 3,43 25,7 9,4 2,74 25,3 11,6 2,18 25,2 13,0 1,930 88 27,5 7,7 3,59 26,9 9,4 2,87 26,3 11,6 2,26 26,1 13,0 2,012 88 28,8 7,7 3,76 28,2 9,4 3,00 27,6 11,6 2,37 27,3 13,0 2,105 87 31,0 7,7 4,03 30,2 9,4 3,22 29,4 11,6 2,53 28,9 13,0 2,227 87 32,5 7,7 4,23 31,7 9,4 3,37 30,8 11,6 2,65 30,3 13,0 2,3310 86 35,0 7,7 4,54 33,9 9,4 3,60 32,8 11,6 2,82 32,2 13,0 2,4812 86 36,9 7,8 4,76 35,5 9,4 3,77 34,3 11,6 2,95 33,6 13,0 2,5915 86 39,7 7,8 5,09 38,1 9,4 4,04 36,6 11,6 3,16 35,8 12,9 2,77
38
-16 90 20,3 8,1 2,49 * * * * * * * * *-15 90 20,9 8,2 2,56 * * * * * * * * *-10 90 24,0 8,2 2,91 23,4 10,0 2,33 * * * * * *-7 89 26,1 8,3 3,16 25,4 10,1 2,52 * * * * * *-2 89 29,8 8,3 3,57 29,0 10,2 2,85 28,0 12,6 2,23 27,4 14,1 1,950 88 31,3 8,4 3,74 30,3 10,2 2,98 29,2 12,6 2,32 28,7 14,1 2,042 88 32,8 8,4 3,92 31,9 10,2 3,12 30,7 12,6 2,43 30,1 14,1 2,135 87 35,3 8,4 4,21 34,2 10,2 3,33 32,8 12,7 2,59 32,1 14,2 2,267 87 37,1 8,4 4,40 35,9 10,3 3,50 34,5 12,7 2,72 33,7 14,2 2,3710 86 40,0 8,4 4,73 38,4 10,3 3,74 36,8 12,7 2,89 35,8 14,2 2,5112 86 41,8 8,5 4,93 40,3 10,3 3,91 38,5 12,7 3,03 37,6 14,3 2,6315 86 45,3 8,5 5,30 43,4 10,3 4,20 41,2 12,8 3,23 40,0 14,3 2,80
42
-16 90 22,8 9,1 2,51 * * * * * * * * *-15 90 23,3 9,1 2,56 * * * * * * * * *-10 90 26,6 9,3 2,87 26,3 11,2 2,34 * * * * * *-7 89 28,8 9,3 3,08 28,4 11,3 2,50 * * * * * *-2 89 32,7 9,4 3,46 32,0 11,5 2,79 31,2 14,0 2,22 30,7 15,6 1,970 88 34,2 9,5 3,62 33,5 11,5 2,91 32,4 14,1 2,30 31,9 15,6 2,042 88 35,9 9,5 3,78 35,1 11,5 3,04 34,0 14,2 2,40 33,3 15,7 2,125 87 38,7 9,6 4,05 37,6 11,6 3,24 36,2 14,2 2,55 35,4 15,8 2,247 87 40,6 9,6 4,23 39,4 11,6 3,38 37,9 14,3 2,66 37,0 15,9 2,3310 86 43,8 9,7 4,52 42,3 11,7 3,62 40,4 14,3 2,82 39,3 15,9 2,4712 86 46,1 9,7 4,73 44,2 11,7 3,76 42,3 14,4 2,94 41,1 16,0 2,5715 86 49,6 9,8 5,04 47,8 11,8 4,05 45,3 14,4 3,14 43,8 16,0 2,73
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
36
COOLING CAPACITIES - MAROON 2 MT
Pf: Cooling power [kW]
Pa: Total absorbed compressor power [kW]
To: Utility outlet water temperature to the utility exchanger [°C]
Model
To External air temperature [°C]
[°C]25 30 35 40
Pf Pat EER Pf Pat EER Pf Pat EER Pf Pat EER
52
5 42,5 11,5 3,69 40,3 12,5 3,22 38,0 13,7 2,78 35,4 15,0 2,376 43,7 11,6 3,77 41,5 12,6 3,28 39,1 13,8 2,84 36,5 15,1 2,427 45,0 11,7 3,85 42,7 12,7 3,36 40,3 13,9 2,90 37,6 15,2 2,488 46,3 11,8 3,93 44,0 12,8 3,43 41,4 14,0 2,96 38,7 15,3 2,539 47,6 11,9 4,01 45,2 12,9 3,50 42,6 14,1 3,03 39,9 15,4 2,5910 49,0 12,0 4,09 46,5 13,0 3,57 43,8 14,2 3,09 41,0 15,5 2,6513 53,0 12,2 4,33 50,4 13,3 3,78 47,5 14,5 3,27 44,5 15,8 2,8114 54,4 12,3 4,41 51,7 13,4 3,85 48,8 14,6 3,33 45,7 16,0 2,8615 55,9 12,4 4,49 53,0 13,5 3,92 50,1 14,7 3,40 46,9 16,1 2,9216 57,3 12,5 4,57 54,4 13,6 3,99 51,4 14,9 3,46 48,1 16,2 2,9717 58,8 12,6 4,66 55,8 13,7 4,06 52,7 15,0 3,52 49,4 16,3 3,0218 60,3 12,7 4,74 57,2 13,9 4,13 54,0 15,1 3,58 50,6 16,5 3,08
62
5 50,4 12,6 3,99 47,9 13,8 3,46 45,2 15,2 2,97 42,2 16,8 2,506 51,8 12,7 4,08 49,3 13,9 3,54 46,5 15,3 3,04 43,5 16,9 2,577 53,4 12,8 4,17 50,7 14,0 3,62 47,9 15,4 3,11 44,8 17,0 2,638 54,9 12,9 4,26 52,2 14,1 3,70 49,3 15,5 3,18 46,2 17,1 2,699 56,5 13,0 4,34 53,7 14,2 3,77 50,7 15,6 3,25 47,5 17,2 2,7610 58,0 13,1 4,42 55,2 14,3 3,85 52,1 15,7 3,31 48,9 17,4 2,8213 62,8 13,5 4,66 59,8 14,7 4,06 56,5 16,1 3,51 53,0 17,7 2,9914 64,5 13,6 4,73 61,3 14,9 4,13 58,0 16,2 3,57 54,4 17,9 3,0515 66,1 13,8 4,80 62,9 15,0 4,20 59,5 16,4 3,63 55,9 18,0 3,1116 67,8 13,9 4,87 64,5 15,1 4,26 61,0 16,5 3,69 57,3 18,1 3,1617 69,5 14,1 4,94 66,1 15,3 4,32 62,6 16,7 3,75 58,8 18,3 3,2118 71,2 14,2 5,01 67,8 15,5 4,38 64,1 16,9 3,80 60,3 18,5 3,26
72
5 58,4 15,1 3,88 55,1 16,6 3,31 51,6 18,4 2,80 47,7 20,4 2,346 60,1 15,2 3,96 56,7 16,8 3,38 53,1 18,5 2,86 49,2 20,6 2,397 61,8 15,3 4,03 58,4 16,9 3,46 54,7 18,7 2,93 50,7 20,7 2,458 63,6 15,4 4,12 60,1 17,0 3,53 56,3 18,8 2,99 52,2 20,8 2,519 65,3 15,6 4,19 61,8 17,2 3,60 57,9 18,9 3,06 53,7 20,9 2,5610 67,1 15,7 4,27 63,5 17,3 3,67 59,5 19,1 3,12 55,2 21,1 2,6213 72,5 16,1 4,50 68,7 17,7 3,88 64,5 19,5 3,31 59,9 21,5 2,7814 74,4 16,3 4,57 70,5 17,9 3,94 66,2 19,7 3,37 61,5 21,7 2,8415 76,3 16,4 4,64 72,3 18,0 4,01 67,9 19,8 3,43 63,1 21,8 2,8916 78,2 16,6 4,71 74,1 18,2 4,07 69,6 20,0 3,48 64,8 22,0 2,9417 80,2 16,8 4,78 76,0 18,4 4,14 71,4 20,1 3,54 66,4 22,2 3,0018 82,1 16,9 4,85 77,9 18,5 4,20 73,2 20,3 3,60 68,1 22,3 3,05
82
5 66,1 17,0 3,89 62,6 18,6 3,36 58,7 20,5 2,86 54,5 22,7 2,406 67,9 17,1 3,98 64,4 18,7 3,43 60,4 20,7 2,93 56,1 22,8 2,467 69,9 17,2 4,06 66,2 18,9 3,51 62,2 20,8 2,99 57,8 23,0 2,528 72,0 17,3 4,15 68,1 19,0 3,58 64,0 20,9 3,06 59,5 23,1 2,579 73,9 17,5 4,23 70,0 19,1 3,66 65,8 21,1 3,13 61,2 23,3 2,6310 75,9 17,6 4,32 72,0 19,3 3,74 67,7 21,2 3,19 62,9 23,4 2,6913 82,1 18,0 4,56 77,9 19,7 3,96 73,3 21,6 3,39 68,2 23,9 2,8614 84,3 18,2 4,64 79,9 19,8 4,03 75,2 21,8 3,45 70,0 24,0 2,9215 86,4 18,3 4,72 82,0 20,0 4,10 77,1 21,9 3,52 71,9 24,2 2,9716 88,6 18,5 4,80 84,1 20,2 4,17 79,1 22,1 3,58 73,7 24,3 3,0317 90,9 18,6 4,88 86,2 20,3 4,24 81,1 22,3 3,64 75,6 24,5 3,0918 93,1 18,8 4,96 88,4 20,5 4,31 83,2 22,4 3,71 77,6 24,7 3,14
92
5 72,8 19,3 3,77 68,9 21,1 3,26 64,6 23,2 2,79 59,9 25,5 2,356 74,8 19,5 3,85 70,9 21,3 3,33 66,5 23,3 2,85 61,7 25,6 2,417 77,0 19,6 3,92 72,9 21,4 3,40 68,4 23,5 2,91 63,5 25,8 2,468 79,1 19,8 4,00 75,0 21,6 3,47 70,3 23,7 2,97 65,2 26,0 2,519 81,4 20,0 4,07 77,1 21,8 3,53 72,3 23,9 3,03 67,1 26,2 2,5610 83,6 20,2 4,15 79,2 22,0 3,60 74,3 24,0 3,09 68,9 26,4 2,6113 90,4 20,7 4,36 85,6 22,6 3,79 80,3 24,6 3,26 74,5 27,0 2,7614 92,7 21,0 4,43 87,8 22,8 3,86 82,4 24,8 3,32 76,5 27,2 2,8115 95,1 21,2 4,50 90,0 23,0 3,92 84,5 25,0 3,37 78,4 27,4 2,8716 97,5 21,4 4,56 92,3 23,2 3,98 86,6 25,3 3,43 80,4 27,6 2,9217 100,0 21,6 4,63 94,7 23,4 4,04 88,8 25,5 3,49 82,5 27,8 2,9718 102,5 21,8 4,69 97,0 23,6 4,10 91,0 25,7 3,54 84,5 28,0 3,01
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
37
HEATING CAPACITIES - MAROON 2 MT
Pt: Heating capacity [kW]
Pa: Total absorbed compressor power [kW]
Ta: Dry bulb temperature of the evaporator inlet air [°C]
RH: Relative humidity of the input air at the evaporator [%]
Model
Ta RH Condenser inlet water temperature [°C]
[°C] %30/35 40/45 50/55 55/60
Pt Pat COP Pt Pat COP Pt Pat COP Pt Pat COP
52
-16 90 25,4 10,6 2,39 * * * * * * * * *-15 90 26,0 10,6 2,45 * * * * * * * * *-10 90 29,7 10,7 2,78 29,2 13,0 2,25 * * * * * *-7 89 32,2 10,8 2,99 31,8 13,0 2,44 * * * * * *-2 89 36,7 10,9 3,37 36,0 13,1 2,74 35,2 16,1 2,19 34,2 17,8 1,920 88 38,5 11,0 3,52 37,7 13,2 2,87 36,9 16,1 2,30 36,0 17,8 2,022 88 40,5 11,0 3,67 39,6 13,2 3,00 38,6 16,1 2,40 37,9 17,9 2,125 87 43,7 11,1 3,93 42,5 13,3 3,19 41,2 16,2 2,55 40,6 17,9 2,267 87 45,9 11,2 4,11 44,6 13,4 3,34 43,2 16,2 2,67 42,5 18,0 2,3610 86 49,4 11,2 4,40 48,0 13,5 3,57 46,1 16,3 2,83 45,2 18,1 2,5012 86 52,0 11,3 4,61 50,2 13,5 3,71 48,3 16,3 2,96 47,3 18,1 2,6115 86 55,9 11,3 4,93 54,1 13,6 3,98 51,8 16,4 3,15 50,5 18,2 2,78
62
-16 90 29,6 12,2 2,44 * * * * * * * * *-15 90 30,4 12,2 2,49 * * * * * * * * *-10 90 34,8 12,3 2,84 34,4 15,2 2,26 * * * * * *-7 89 37,8 12,3 3,08 37,3 15,2 2,45 * * * * * *-2 89 43,1 12,3 3,49 42,4 15,2 2,79 41,6 19,1 2,18 41,2 21,6 1,910 88 45,2 12,3 3,66 44,3 15,2 2,92 43,3 19,0 2,28 42,9 21,5 1,992 88 47,4 12,4 3,83 46,5 15,2 3,07 45,6 19,0 2,40 45,0 21,4 2,105 87 51,0 12,4 4,12 49,9 15,2 3,30 48,6 18,9 2,57 48,0 21,3 2,257 87 53,7 12,4 4,32 52,3 15,2 3,45 51,0 18,9 2,70 50,3 21,3 2,3610 86 57,7 12,5 4,62 56,2 15,2 3,70 54,5 18,8 2,89 53,5 21,2 2,5212 86 60,7 12,5 4,84 58,8 15,2 3,86 56,9 18,8 3,02 56,0 21,2 2,6415 86 65,3 12,7 5,16 63,3 15,3 4,13 61,1 18,9 3,24 59,7 21,1 2,82
72
-16 90 33,8 13,8 2,44 * * * * * * * * *-15 90 34,7 13,9 2,50 * * * * * * * * *-10 90 39,6 14,0 2,84 39,5 17,4 2,27 * * * * * *-7 89 43,0 14,0 3,07 42,6 17,5 2,44 * * * * * *-2 89 48,8 14,1 3,47 48,2 17,5 2,75 47,7 22,0 2,17 47,7 24,7 1,930 88 51,4 14,1 3,65 50,5 17,5 2,88 49,7 21,9 2,27 49,4 24,7 2,002 88 54,0 14,1 3,83 52,7 17,5 3,01 51,9 21,9 2,37 51,6 24,7 2,095 87 57,9 14,1 4,09 56,6 17,5 3,23 55,4 21,9 2,52 54,6 24,7 2,227 87 60,9 14,2 4,30 59,4 17,5 3,39 57,8 21,9 2,64 57,0 24,6 2,3210 86 65,3 14,2 4,59 63,6 17,6 3,62 61,7 21,9 2,82 60,7 24,6 2,4712 86 68,6 14,3 4,80 66,7 17,6 3,79 64,4 21,9 2,94 63,2 24,6 2,5715 86 73,7 14,3 5,14 71,6 17,6 4,06 69,1 21,9 3,15 67,6 24,6 2,75
82
-16 90 38,9 16,1 2,42 * * * * * * * * *-15 90 40,0 16,1 2,48 * * * * * * * * *-10 90 46,0 16,3 2,82 44,9 19,9 2,25 * * * * * *-7 89 50,0 16,4 3,05 48,8 20,0 2,44 * * * * * *-2 89 56,9 16,5 3,45 55,5 20,2 2,75 53,8 25,0 2,16 53,0 27,9 1,900 88 59,8 16,5 3,62 58,1 20,2 2,88 56,2 25,0 2,25 55,2 28,0 1,972 88 62,6 16,5 3,78 61,0 20,3 3,01 59,2 25,1 2,36 58,0 28,1 2,065 87 67,5 16,6 4,06 65,5 20,3 3,22 63,1 25,2 2,51 61,9 28,2 2,197 87 71,0 16,6 4,26 68,6 20,4 3,37 66,2 25,2 2,62 64,8 28,3 2,2910 86 76,2 16,7 4,56 73,7 20,4 3,61 70,9 25,3 2,80 69,0 28,3 2,4312 86 80,1 16,8 4,77 77,3 20,4 3,78 74,0 25,3 2,92 72,2 28,4 2,5415 86 86,2 16,9 5,11 83,1 20,5 4,05 79,4 25,4 3,13 77,2 28,4 2,71
92
-16 90 43,6 17,2 2,53 * * * * * * * * *-15 90 44,7 17,3 2,58 * * * * * * * * *-10 90 50,9 17,6 2,89 50,4 21,3 2,37 * * * * * *-7 89 54,9 17,8 3,09 54,3 21,6 2,52 * * * * * *-2 89 62,2 18,0 3,46 61,3 21,9 2,80 59,9 26,7 2,24 59,1 29,6 2,000 88 65,4 18,0 3,63 64,2 22,0 2,93 62,5 26,9 2,33 61,5 29,8 2,062 88 68,7 18,1 3,79 67,1 22,0 3,04 65,3 27,0 2,42 64,2 30,0 2,145 87 73,7 18,2 4,05 71,9 22,1 3,25 69,6 27,2 2,56 68,1 30,2 2,267 87 77,4 18,3 4,23 75,5 22,2 3,40 72,7 27,3 2,67 71,1 30,3 2,3510 86 83,1 18,4 4,51 80,8 22,3 3,62 77,6 27,4 2,84 75,8 30,5 2,4912 86 87,6 18,5 4,73 84,7 22,4 3,78 80,9 27,5 2,95 78,9 30,5 2,5815 86 94,1 18,7 5,03 91,0 22,5 4,04 86,9 27,6 3,15 84,4 30,7 2,75
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
38
Model
To DHW temperature [°C]
[°C]40/45 45/50 50/55 55/60
Pf Pa Pt EER COP Pf Pa Pt EER COP Pf Pa Pt EER COP Pf Pa Pt EER COP
RECOVERY CAPACITIES - MAROON 2 MT
Pf: Cooling power [kW]
Pt: Heating capacity [kW]
To: Utility outlet water temperature to the utility exchanger [°C]
8
5 5,8 1,9 7,7 3,03 4,03 5,4 2,2 7,6 2,48 3,48 5,0 2,5 7,4 2,01 3,01 4,5 2,8 7,3 1,59 2,59
7 6,2 1,9 8,1 3,28 4,28 5,8 2,2 8,0 2,68 3,69 5,3 2,5 7,8 2,17 3,16 4,8 2,8 7,6 1,72 2,72
10 6,9 1,9 8,8 3,64 4,63 6,4 2,1 8,6 3,00 4,00 5,9 2,4 8,3 2,43 3,43 5,3 2,8 8,1 1,93 2,93
14 7,8 1,9 9,7 4,18 5,18 7,3 2,1 9,4 3,44 4,44 6,7 2,4 9,1 2,80 3,80 6,1 2,7 8,8 2,25 3,25
18 8,8 1,9 10,7 4,78 5,78 8,3 2,1 10,4 3,94 4,94 7,7 2,4 10,0 3,21 4,21 7,0 2,7 9,7 2,59 3,59
10
5 7,4 2,1 9,5 3,52 4,52 6,9 2,4 9,3 2,86 3,86 6,3 2,8 9,1 2,29 3,29 5,7 3,2 8,9 1,80 2,80
7 7,9 2,1 10,0 3,80 4,80 7,4 2,4 9,8 3,08 4,08 6,8 2,7 9,5 2,48 3,48 6,1 3,1 9,3 1,95 2,95
10 8,8 2,1 10,8 4,24 5,24 8,2 2,4 10,5 3,45 4,45 7,5 2,7 10,2 2,77 3,77 6,8 3,1 9,9 2,19 3,19
14 10,0 2,1 12,0 4,85 5,85 9,3 2,4 11,6 3,95 4,95 8,6 2,7 11,2 3,19 4,19 7,8 3,1 10,8 2,54 3,54
18 11,3 2,0 13,3 5,51 6,51 10,5 2,3 12,8 4,51 5,51 9,7 2,7 12,4 3,67 4,67 8,8 3,0 11,9 2,92 3,92
12
5 9,4 2,5 11,9 3,79 4,79 8,7 2,8 11,5 3,12 4,12 8,0 3,2 11,2 2,53 3,53 7,2 3,6 10,8 2,00 2,99
7 10,1 2,5 12,6 4,06 5,06 9,4 2,8 12,2 3,34 4,34 8,6 3,2 11,8 2,72 3,72 7,7 3,6 11,3 2,15 3,15
10 11,1 2,5 13,6 4,48 5,48 10,3 2,8 13,1 3,69 4,69 9,5 3,2 12,7 3,01 4,01 8,6 3,6 12,2 2,39 3,39
14 12,6 2,5 15,1 5,05 6,05 11,7 2,8 14,5 4,19 5,19 10,8 3,2 14,0 3,42 4,42 9,8 3,6 13,4 2,73 3,73
18 14,2 2,5 16,7 5,70 6,70 13,3 2,8 16,1 4,74 5,74 12,3 3,2 15,4 3,88 4,89 11,2 3,6 14,7 3,11 4,11
16
5 12,5 3,6 16,2 3,44 4,44 11,6 4,2 15,8 2,79 3,79 10,5 4,8 15,3 2,19 3,19 9,2 5,6 14,8 1,65 2,65
7 13,4 3,6 17,0 3,68 4,68 12,4 4,2 16,6 2,99 3,99 11,3 4,8 16,1 2,37 3,37 9,9 5,5 15,5 1,79 2,80
10 14,7 3,6 18,3 4,04 5,04 13,7 4,1 17,8 3,31 4,31 12,5 4,7 17,2 2,64 3,64 11,1 5,5 16,6 2,03 3,03
14 16,5 3,6 20,2 4,53 5,54 15,4 4,1 19,6 3,75 4,75 14,2 4,7 18,9 3,02 4,02 12,7 5,4 18,1 2,35 3,35
18 18,5 3,7 22,2 5,03 6,03 17,4 4,1 21,5 4,19 5,19 16,0 4,7 20,7 3,42 4,42 14,5 5,4 19,9 2,69 3,69
18
5 13,5 3,9 17,4 3,48 4,47 12,5 4,3 16,8 2,88 3,89 11,4 4,8 16,2 2,35 3,35 10,1 5,4 15,5 1,86 2,86
7 14,5 3,9 18,4 3,75 4,75 13,5 4,3 17,8 3,12 4,12 12,3 4,8 17,1 2,55 3,55 11,0 5,4 16,4 2,02 3,02
10 16,1 3,8 19,9 4,19 5,19 14,9 4,3 19,2 3,49 4,49 13,7 4,8 18,5 2,86 3,86 12,3 5,4 17,7 2,29 3,29
14 18,3 3,8 22,1 4,82 5,82 17,1 4,2 21,3 4,03 5,03 15,7 4,7 20,5 3,33 4,33 14,2 5,3 19,6 2,67 3,67
18 20,7 3,7 24,5 5,54 6,54 19,4 4,2 23,6 4,65 5,65 18,0 4,7 22,6 3,85 4,85 16,4 5,3 21,6 3,11 4,11
20
5 15,9 4,4 20,3 3,57 4,57 14,7 5,0 19,7 2,96 3,96 13,5 5,6 19,1 2,42 3,42 12,2 6,3 18,5 1,93 2,93
7 16,9 4,5 21,4 3,80 4,80 15,8 5,0 20,8 3,15 4,15 14,5 5,6 20,1 2,58 3,58 13,1 6,3 19,4 2,06 3,06
10 18,6 4,5 23,1 4,16 5,16 17,4 5,0 22,4 3,46 4,46 16,0 5,7 21,7 2,83 3,83 14,5 6,4 20,9 2,27 3,27
14 21,1 4,5 25,6 4,67 5,67 19,7 5,1 24,7 3,89 4,89 18,2 5,7 23,9 3,20 4,20 16,5 6,4 22,9 2,58 3,58
18 23,8 4,5 28,3 5,23 6,24 22,2 5,1 27,3 4,38 5,38 20,6 5,7 26,3 3,61 4,60 18,8 6,4 25,2 2,92 3,92
23
5 17,7 5,3 23,1 3,33 4,33 16,5 6,0 22,5 2,76 3,75 15,2 6,7 21,9 2,25 3,25 13,8 7,6 21,4 1,80 2,80
7 19,0 5,4 24,3 3,54 4,54 17,7 6,0 23,7 2,94 3,94 16,3 6,8 23,1 2,41 3,41 14,8 7,6 22,4 1,93 2,93
10 20,9 5,4 26,3 3,88 4,88 19,5 6,0 25,6 3,23 4,23 18,0 6,8 24,8 2,66 3,66 16,4 7,7 24,1 2,14 3,14
14 23,7 5,5 29,1 4,34 5,34 22,2 6,1 28,3 3,63 4,64 20,6 6,8 27,4 3,01 4,01 18,8 7,7 26,5 2,43 3,43
18 26,7 5,5 32,3 4,83 5,83 25,1 6,2 31,3 4,07 5,07 23,4 6,9 30,3 3,38 4,38 21,4 7,8 29,2 2,76 3,76
25
5 19,7 5,7 25,4 3,46 4,46 18,2 6,4 24,6 2,85 3,85 16,5 7,2 23,8 2,29 3,29 14,7 8,2 22,9 1,80 2,80
7 21,1 5,7 26,7 3,70 4,70 19,5 6,4 25,9 3,05 4,05 17,8 7,2 25,0 2,47 3,47 15,9 8,2 24,1 1,94 2,94
10 23,2 5,7 28,9 4,07 5,07 21,6 6,4 28,0 3,37 4,37 19,7 7,2 27,0 2,74 3,74 17,7 8,2 25,9 2,17 3,17
14 26,3 5,7 32,0 4,59 5,59 24,5 6,4 30,9 3,82 4,82 22,5 7,2 29,7 3,12 4,12 20,3 8,2 28,5 2,49 3,49
18 29,6 5,8 35,4 5,13 6,12 27,7 6,5 34,2 4,30 5,30 25,6 7,2 32,8 3,54 4,54 23,2 8,2 31,3 2,84 3,84
29
5 23,0 6,5 29,4 3,55 4,55 21,4 7,3 28,7 2,95 3,95 19,7 8,2 27,9 2,41 3,41 17,7 9,3 27,1 1,91 2,91
7 24,5 6,5 31,0 3,79 4,79 22,9 7,3 30,2 3,16 4,16 21,2 8,2 29,3 2,59 3,59 19,1 9,3 28,4 2,06 3,06
10 26,9 6,5 33,5 4,14 5,14 25,3 7,3 32,5 3,47 4,47 23,4 8,2 31,6 2,86 3,86 21,3 9,3 30,6 2,30 3,30
14 30,4 6,6 37,0 4,61 5,61 28,5 7,3 35,9 3,89 4,89 26,5 8,2 34,8 3,23 4,23 24,3 9,3 33,6 2,62 3,62
18 34,1 6,7 40,8 5,08 6,08 32,1 7,4 39,5 4,31 5,31 29,9 8,3 38,2 3,60 4,60 27,5 9,3 36,8 2,95 3,95
38
5 28,5 7,2 35,7 3,96 4,96 26,5 8,1 34,6 3,26 4,26 24,2 9,2 33,3 2,64 3,64 21,7 10,4 32,0 2,09 3,09
7 30,5 7,2 37,7 4,24 5,24 28,4 8,1 36,5 3,50 4,50 26,0 9,1 35,1 2,84 3,84 23,3 10,4 33,7 2,25 3,26
10 33,6 7,2 40,8 4,66 5,66 31,3 8,1 39,4 3,86 4,86 28,8 9,1 37,9 3,15 4,15 26,0 10,3 36,3 2,51 3,51
14 38,0 7,2 45,2 5,24 6,24 35,5 8,1 43,6 4,38 5,38 32,8 9,1 41,9 3,59 4,59 29,7 10,3 40,0 2,88 3,88
18 42,7 7,3 50,0 5,87 6,87 40,1 8,1 48,2 4,92 5,92 37,1 9,1 46,3 4,07 5,07 33,8 10,3 44,1 3,29 4,29
42
5 30,4 9,0 39,4 3,40 4,40 28,2 10,1 38,2 2,79 3,79 25,6 11,4 37,0 2,25 3,25 22,8 12,9 35,7 1,77 2,77
7 32,5 9,0 41,5 3,63 4,63 30,1 10,1 40,2 2,99 3,99 27,5 11,4 38,9 2,41 3,41 24,6 12,9 37,5 1,90 2,90
10 35,7 9,0 44,7 3,98 4,98 33,2 10,1 43,3 3,28 4,28 30,4 11,4 41,8 2,66 3,66 27,3 12,9 40,2 2,11 3,11
14 40,3 9,0 49,3 4,47 5,47 37,6 10,1 47,7 3,71 4,71 34,6 11,4 46,0 3,02 4,02 31,2 13,0 44,1 2,40 3,40
18 45,3 9,1 54,4 4,99 5,99 42,3 10,2 52,5 4,16 5,16 39,1 11,5 50,5 3,41 4,41 35,4 13,0 48,4 2,73 3,73
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
39
Model
To DHW temperature [°C]
[°C]40/45 45/50 50/55 55/60
Pf Pa Pt EER COP Pf Pa Pt EER COP Pf Pa Pt EER COP Pf Pa Pt EER COP
RECOVERY CAPACITIES - MAROON 2 MT
Pf: Cooling power [kW]
Pt: Heating capacity [kW]
To: Utility outlet water temperature to the utility exchanger [°C]
52
5 38,5 12,1 50,5 3,19 4,19 35,8 13,4 49,2 2,67 3,67 32,8 15,0 47,8 2,19 3,19 29,8 16,6 46,4 1,79 2,79
7 41,1 12,1 53,2 3,39 4,39 38,2 13,5 51,7 2,84 3,84 35,3 15,0 50,2 2,35 3,35 32,2 16,6 48,8 1,94 2,94
10 45,2 12,2 57,4 3,71 4,71 42,2 13,5 55,8 3,12 4,12 39,1 15,0 54,1 2,60 3,60 35,8 16,6 52,4 2,15 3,15
14 51,1 12,3 63,3 4,17 5,17 47,8 13,6 61,4 3,51 4,51 44,4 15,1 59,5 2,94 3,94 40,9 16,7 57,6 2,45 3,45
18 57,5 12,3 69,8 4,68 5,68 53,9 13,7 67,6 3,93 4,93 50,3 15,2 65,4 3,32 4,32 46,5 16,8 63,2 2,77 3,77
62
5 45,9 13,5 59,3 3,41 4,41 42,0 15,6 57,6 2,70 3,70 38,5 17,6 56,1 2,19 3,19 34,8 19,8 54,6 1,76 2,76
7 48,6 13,7 62,3 3,56 4,56 45,0 15,6 60,5 2,89 3,89 41,4 17,5 59,0 2,36 3,36 37,6 19,7 57,4 1,91 2,91
10 53,1 13,9 66,9 3,82 4,82 49,6 15,6 65,2 3,19 4,19 45,9 17,5 63,4 2,62 3,62 42,0 19,6 61,6 2,14 3,14
14 59,9 14,0 73,9 4,28 5,28 56,1 15,7 71,7 3,58 4,58 52,1 17,5 69,7 2,98 3,98 48,0 19,6 67,6 2,45 3,45
18 67,2 14,2 81,4 4,73 5,73 63,1 15,8 78,9 3,98 4,98 58,9 17,6 76,5 3,34 4,34 54,5 19,6 74,1 2,78 3,78
72
5 54,0 15,8 69,8 3,42 4,42 49,1 18,3 67,4 2,68 3,68 44,7 20,7 65,4 2,16 3,16 40,3 23,2 63,5 1,74 2,74
7 57,7 15,8 73,5 3,65 4,65 52,6 18,3 70,9 2,88 3,88 48,1 20,6 68,8 2,33 3,33 43,5 23,1 66,6 1,88 2,88
10 62,6 16,2 78,8 3,86 4,86 58,2 18,3 76,4 3,18 4,18 53,4 20,6 73,9 2,59 3,59 48,4 23,0 71,5 2,10 3,10
14 70,8 16,3 87,1 4,35 5,35 66,0 18,3 84,3 3,62 4,62 60,9 20,5 81,4 2,97 3,97 55,5 22,9 78,5 2,42 3,42
18 79,7 16,3 96,1 4,88 5,88 74,6 18,3 92,9 4,07 5,07 69,1 20,5 89,6 3,37 4,37 63,3 22,9 86,2 2,77 3,77
82
5 59,9 17,7 77,6 3,38 4,38 54,3 20,6 74,8 2,64 3,64 49,3 23,2 72,5 2,12 3,12 44,2 26,0 70,2 1,70 2,70
7 63,8 17,7 81,6 3,60 4,60 58,1 20,6 78,7 2,83 3,83 53,0 23,2 76,2 2,28 3,28 47,7 26,0 73,7 1,83 2,83
10 69,1 18,2 87,3 3,79 4,79 64,1 20,6 84,7 3,12 4,12 58,7 23,2 81,9 2,53 3,53 53,1 26,0 79,1 2,04 3,04
14 78,0 18,3 96,3 4,27 5,27 72,6 20,6 93,2 3,53 4,53 66,7 23,2 89,9 2,88 3,88 60,7 26,0 86,7 2,33 3,33
18 87,8 18,4 106,1 4,78 5,78 81,8 20,6 102,5 3,97 4,97 75,6 23,2 98,7 3,26 4,26 69,0 26,0 95,0 2,66 3,66
92
5 67,3 19,6 86,9 3,44 4,44 61,2 22,6 83,8 2,71 3,71 55,7 25,3 81,0 2,20 3,20 50,1 28,1 78,3 1,78 2,78
7 71,8 19,7 91,4 3,65 4,65 65,5 22,6 88,1 2,89 3,89 59,7 25,4 85,1 2,36 3,36 53,8 28,2 82,0 1,91 2,91
10 78,3 20,0 98,3 3,91 4,91 72,1 22,7 94,8 3,18 4,18 65,9 25,4 91,3 2,60 3,60 59,6 28,3 87,9 2,11 3,11
14 87,8 20,4 108,2 4,30 5,30 81,6 22,8 104,4 3,58 4,58 74,9 25,5 100,4 2,94 3,94 68,0 28,3 96,3 2,40 3,40
18 98,9 20,6 119,5 4,80 5,80 92,1 22,9 115,1 4,02 5,02 84,9 25,5 110,4 3,32 4,32 77,3 28,4 105,7 2,73 3,73
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
40
COOLING CAPACITIES - MAROON 2 HT
Pf: Cooling power [kW]
Pa: Total absorbed compressor power [kW]
To: Utility outlet water temperature to the utility exchanger [°C]
Model
To External air temperature [°C]
[°C]25 30 35 40
Pf Pat EER Pf Pat EER Pf Pat EER Pf Pat EER
7
5 6,3 1,6 4,04 6,0 1,7 3,50 5,7 1,9 3,04 5,3 2,0 2,616 6,5 1,6 4,14 6,2 1,7 3,61 5,9 1,9 3,12 5,5 2,0 2,687 6,7 1,6 4,26 6,4 1,7 3,70 6,0 1,9 3,20 5,6 2,1 2,758 6,9 1,6 4,36 6,6 1,7 3,79 6,2 1,9 3,28 5,8 2,1 2,829 7,1 1,6 4,49 6,8 1,7 3,91 6,4 1,9 3,38 6,0 2,1 2,8910 7,3 1,6 4,60 7,0 1,7 4,00 6,6 1,9 3,46 6,2 2,1 2,9613 8,0 1,6 4,97 7,6 1,8 4,30 7,2 1,9 3,72 6,7 2,1 3,1814 8,2 1,6 5,08 7,8 1,8 4,42 7,4 1,9 3,81 6,9 2,1 3,2715 8,5 1,6 5,22 8,0 1,8 4,52 7,6 1,9 3,90 7,1 2,1 3,3416 8,7 1,6 5,33 8,3 1,8 4,64 7,8 1,9 4,00 7,3 2,1 3,4217 8,9 1,6 5,48 8,5 1,8 4,75 8,0 2,0 4,10 7,5 2,1 3,5018 9,2 1,6 5,60 8,7 1,8 4,85 8,2 2,0 4,19 7,7 2,2 3,57
9
5 8,1 2,0 4,09 7,7 2,2 3,51 7,3 2,4 3,01 6,8 2,7 2,556 8,4 2,0 4,20 8,0 2,2 3,60 7,5 2,4 3,07 7,0 2,7 2,627 8,7 2,0 4,30 8,2 2,2 3,69 7,7 2,4 3,15 7,2 2,7 2,688 8,9 2,0 4,41 8,4 2,2 3,79 7,9 2,5 3,23 7,4 2,7 2,759 9,2 2,0 4,51 8,7 2,2 3,86 8,2 2,5 3,31 7,6 2,7 2,8010 9,4 2,0 4,62 8,9 2,3 3,95 8,4 2,5 3,39 7,8 2,7 2,8713 10,2 2,1 4,94 9,7 2,3 4,23 9,1 2,5 3,62 8,5 2,8 3,0714 10,5 2,1 5,05 10,0 2,3 4,33 9,4 2,5 3,70 8,7 2,8 3,1415 10,8 2,1 5,16 10,2 2,3 4,42 9,6 2,5 3,79 9,0 2,8 3,2016 11,1 2,1 5,28 10,5 2,3 4,52 9,9 2,6 3,86 9,2 2,8 3,2717 11,4 2,1 5,42 10,8 2,3 4,62 10,1 2,6 3,94 9,4 2,8 3,3518 11,7 2,1 5,53 11,1 2,3 4,72 10,4 2,6 4,03 9,7 2,8 3,42
11
5 10,6 2,6 4,06 10,1 2,9 3,49 9,5 3,2 2,98 8,8 3,5 2,536 10,9 2,6 4,16 10,4 2,9 3,56 9,7 3,2 3,05 9,1 3,5 2,597 11,2 2,7 4,24 10,7 2,9 3,64 10,0 3,2 3,12 9,3 3,5 2,648 11,6 2,7 4,33 10,9 2,9 3,72 10,3 3,2 3,18 9,6 3,6 2,709 11,9 2,7 4,41 11,3 3,0 3,80 10,6 3,3 3,25 9,8 3,6 2,7510 12,2 2,7 4,52 11,6 3,0 3,88 10,9 3,3 3,31 10,1 3,6 2,8013 13,2 2,8 4,77 12,5 3,0 4,11 11,7 3,4 3,50 10,9 3,7 2,9614 13,5 2,8 4,86 12,8 3,1 4,18 12,0 3,4 3,57 11,2 3,7 3,0215 13,9 2,8 4,97 13,1 3,1 4,26 12,3 3,4 3,64 11,5 3,7 3,0716 14,2 2,8 5,06 13,5 3,1 4,34 12,6 3,4 3,69 11,7 3,8 3,1317 14,6 2,8 5,15 13,8 3,1 4,41 13,0 3,4 3,76 12,0 3,8 3,1918 15,0 2,9 5,24 14,2 3,2 4,48 13,3 3,5 3,83 12,3 3,8 3,24
13
5 12,2 3,0 4,03 11,8 3,4 3,51 11,4 3,8 3,04 10,9 4,2 2,616 12,5 3,0 4,11 12,1 3,4 3,58 11,7 3,8 3,11 11,2 4,2 2,667 12,8 3,0 4,21 12,4 3,4 3,67 12,0 3,8 3,17 11,5 4,2 2,728 13,1 3,1 4,30 12,7 3,4 3,74 12,3 3,8 3,23 11,7 4,2 2,789 13,5 3,1 4,40 13,0 3,4 3,82 12,6 3,8 3,30 12,0 4,2 2,8210 13,8 3,1 4,51 13,4 3,4 3,90 12,9 3,8 3,36 12,3 4,3 2,8813 14,8 3,1 4,81 14,3 3,4 4,15 13,7 3,8 3,57 13,1 4,3 3,0514 15,1 3,1 4,91 14,6 3,5 4,23 14,0 3,9 3,64 13,4 4,3 3,1015 15,5 3,1 5,02 14,9 3,5 4,33 14,4 3,9 3,71 13,7 4,3 3,1616 15,8 3,1 5,13 15,3 3,5 4,42 14,7 3,9 3,79 14,0 4,3 3,2217 16,2 3,1 5,26 15,6 3,5 4,52 15,0 3,9 3,86 14,3 4,4 3,2818 16,5 3,1 5,38 16,0 3,5 4,61 15,3 3,9 3,94 14,6 4,4 3,35
17
5 14,5 3,7 3,96 14,1 4,1 3,46 13,7 4,5 3,01 13,2 5,1 2,606 14,8 3,7 4,06 14,5 4,1 3,54 14,0 4,6 3,07 13,5 5,1 2,657 15,2 3,7 4,15 14,8 4,1 3,62 14,4 4,6 3,14 13,8 5,1 2,718 15,6 3,7 4,24 15,2 4,1 3,70 14,7 4,6 3,21 14,2 5,1 2,769 16,0 3,7 4,34 15,6 4,1 3,78 15,1 4,6 3,27 14,5 5,2 2,8110 16,4 3,7 4,43 16,0 4,1 3,86 15,4 4,6 3,34 14,8 5,2 2,8713 17,6 3,7 4,71 17,1 4,2 4,11 16,5 4,7 3,54 15,9 5,2 3,0414 18,0 3,7 4,82 17,5 4,2 4,18 16,9 4,7 3,62 16,2 5,2 3,0915 18,5 3,8 4,92 17,9 4,2 4,26 17,3 4,7 3,68 16,6 5,3 3,1616 18,9 3,8 5,01 18,3 4,2 4,35 17,7 4,7 3,75 16,9 5,3 3,2117 19,3 3,8 5,12 18,7 4,2 4,44 18,1 4,7 3,82 17,3 5,3 3,2718 19,8 3,8 5,22 19,2 4,2 4,52 18,5 4,7 3,89 17,7 5,3 3,33
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
41
COOLING CAPACITIES - MAROON 2 HT
Pf: Cooling power [kW]
Pa: Total absorbed compressor power [kW]
To: Utility outlet water temperature to the utility exchanger [°C]
Model
To External air temperature [°C]
[°C]25 30 35 40
Pf Pat EER Pf Pat EER Pf Pat EER Pf Pat EER
22
5 20,0 4,9 4,05 19,4 5,5 3,51 18,7 6,2 3,02 17,9 6,9 2,586 20,5 4,9 4,15 19,9 5,6 3,58 19,2 6,2 3,08 18,3 7,0 2,637 21,0 5,0 4,24 20,4 5,6 3,66 19,6 6,2 3,15 18,8 7,0 2,688 21,5 5,0 4,33 20,9 5,6 3,74 20,1 6,3 3,21 19,2 7,0 2,739 22,1 5,0 4,43 21,4 5,6 3,81 20,6 6,3 3,27 19,7 7,1 2,7910 22,6 5,0 4,52 21,9 5,6 3,89 21,1 6,3 3,34 20,1 7,1 2,8413 24,2 5,0 4,82 23,4 5,7 4,14 22,5 6,4 3,53 21,5 7,2 3,0014 24,7 5,0 4,92 23,9 5,7 4,22 23,0 6,4 3,60 21,9 7,2 3,0515 25,3 5,0 5,03 24,5 5,7 4,30 23,5 6,4 3,67 22,4 7,2 3,1116 25,9 5,0 5,14 25,0 5,7 4,39 24,0 6,4 3,74 22,9 7,2 3,1617 26,5 5,0 5,25 25,6 5,7 4,48 24,5 6,4 3,81 23,3 7,2 3,2218 27,0 5,0 5,37 26,1 5,7 4,57 25,0 6,5 3,88 23,8 7,3 3,28
26
5 23,1 5,7 4,08 22,5 6,3 3,56 21,8 7,1 3,08 21,0 7,9 2,656 23,7 5,7 4,16 23,1 6,4 3,64 22,4 7,1 3,15 21,5 7,9 2,717 24,3 5,7 4,25 23,7 6,4 3,72 23,0 7,1 3,22 22,1 8,0 2,778 24,9 5,8 4,34 24,3 6,4 3,79 23,5 7,2 3,29 22,6 8,0 2,839 25,6 5,8 4,42 24,9 6,4 3,87 24,1 7,2 3,36 23,2 8,0 2,8910 26,2 5,8 4,50 25,5 6,5 3,95 24,7 7,2 3,43 23,8 8,1 2,9513 28,1 5,9 4,76 27,4 6,6 4,18 26,5 7,3 3,63 25,5 8,2 3,1314 28,8 6,0 4,83 28,1 6,6 4,25 27,2 7,3 3,70 26,1 8,2 3,1915 29,5 6,0 4,92 28,7 6,6 4,32 27,8 7,4 3,77 26,7 8,2 3,2516 30,2 6,0 5,00 29,4 6,7 4,40 28,4 7,4 3,83 27,3 8,3 3,3117 30,9 6,1 5,08 30,0 6,7 4,47 29,1 7,5 3,90 28,0 8,3 3,3718 31,6 6,1 5,16 30,7 6,8 4,55 29,7 7,5 3,97 28,6 8,3 3,43
32
5 29,6 7,5 3,96 29,1 8,3 3,49 28,3 9,3 3,06 27,4 10,3 2,656 30,3 7,5 4,02 29,8 8,4 3,56 29,0 9,3 3,12 28,0 10,4 2,707 31,1 7,6 4,10 30,5 8,4 3,63 29,8 9,3 3,18 28,8 10,4 2,768 31,8 7,6 4,17 31,2 8,5 3,69 30,4 9,4 3,24 29,4 10,5 2,819 32,6 7,7 4,23 32,0 8,5 3,76 31,2 9,4 3,30 30,1 10,5 2,8710 33,4 7,8 4,30 32,7 8,6 3,83 31,9 9,5 3,36 30,8 10,5 2,9213 35,7 7,9 4,49 35,0 8,7 4,01 34,1 9,6 3,53 32,9 10,7 3,0814 36,5 8,0 4,55 35,7 8,8 4,07 34,8 9,7 3,59 33,6 10,7 3,1315 37,3 8,1 4,61 36,5 8,8 4,13 35,5 9,7 3,65 34,3 10,8 3,1816 38,1 8,2 4,66 37,3 8,9 4,18 36,3 9,8 3,70 35,0 10,8 3,2317 38,9 8,3 4,71 38,1 9,0 4,24 37,1 9,9 3,75 35,8 10,9 3,2818 39,7 8,3 4,77 38,9 9,1 4,29 37,8 9,9 3,81 36,5 11,0 3,33
36
5 32,9 8,2 4,00 32,2 9,2 3,51 31,4 10,2 3,08 30,4 11,4 2,676 33,7 8,3 4,08 33,0 9,2 3,59 32,1 10,2 3,14 31,1 11,4 2,727 34,5 8,3 4,16 33,8 9,2 3,66 32,9 10,3 3,20 31,9 11,5 2,788 35,3 8,3 4,25 34,6 9,3 3,73 33,7 10,3 3,27 32,6 11,5 2,839 36,1 8,3 4,34 35,4 9,3 3,81 34,4 10,4 3,33 33,3 11,5 2,8910 36,9 8,3 4,43 36,2 9,3 3,88 35,2 10,4 3,39 34,1 11,6 2,9413 39,4 8,4 4,70 38,6 9,4 4,12 37,6 10,5 3,59 36,4 11,7 3,1114 40,3 8,4 4,79 39,4 9,4 4,20 38,4 10,5 3,66 37,2 11,7 3,1615 41,2 8,4 4,89 40,3 9,4 4,28 39,2 10,5 3,73 37,9 11,8 3,2216 42,0 8,4 4,99 41,1 9,4 4,36 40,0 10,6 3,79 38,7 11,8 3,2817 42,9 8,4 5,08 42,0 9,5 4,44 40,9 10,6 3,86 39,5 11,8 3,3418 43,8 8,4 5,19 42,9 9,5 4,53 41,7 10,6 3,94 40,3 11,9 3,40
41
5 37,8 9,4 4,02 36,8 10,4 3,53 35,7 11,6 3,08 34,4 12,9 2,666 38,7 9,5 4,09 37,8 10,5 3,60 36,6 11,7 3,14 35,3 13,0 2,717 39,7 9,5 4,18 38,7 10,5 3,67 37,6 11,7 3,20 36,2 13,1 2,768 40,7 9,6 4,26 39,7 10,6 3,74 38,5 11,8 3,26 37,0 13,2 2,819 41,7 9,6 4,34 40,6 10,7 3,81 39,4 11,9 3,32 37,9 13,2 2,8710 42,7 9,6 4,42 41,6 10,7 3,88 40,3 11,9 3,38 38,8 13,3 2,9113 45,8 9,8 4,67 44,6 10,9 4,10 43,2 12,1 3,56 41,5 13,5 3,0714 46,8 9,9 4,75 45,6 10,9 4,16 44,2 12,2 3,62 42,4 13,6 3,1215 47,9 9,9 4,84 46,6 11,0 4,24 45,1 12,3 3,68 43,4 13,7 3,1716 49,0 9,9 4,92 47,7 11,1 4,31 46,1 12,3 3,74 44,3 13,8 3,2217 50,0 10,0 5,00 48,7 11,1 4,38 47,1 12,4 3,80 45,3 13,8 3,2718 51,2 10,1 5,09 49,8 11,2 4,45 48,2 12,5 3,86 46,2 13,9 3,32
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
42
HEATING CAPACITIES - MAROON 2 HT
Pt: Heating capacity [kW]
Pa: Total absorbed compressor power [kW]
Ta: Dry bulb temperature of the evaporator inlet air [°C]
RH: Relative humidity of the input air at the evaporator [%]
Model
Ta RH Condenser inlet water temperature [°C]
[°C] %30/35 40/45 50/55 55/60
Pt Pat COP Pt Pat COP Pt Pat COP Pt Pat COP
7
-20 90 3,3 1,5 2,22 * * * * * * * * *-15 90 3,8 1,5 2,50 3,7 1,8 2,11 * * * * * *-10 90 4,4 1,6 2,81 4,3 1,8 2,35 * * * * * *-7 89 4,8 1,6 3,01 4,7 1,9 2,50 4,6 2,2 2,07 * * *-2 89 5,4 1,6 3,37 5,3 1,9 2,79 5,2 2,3 2,28 * * *0 88 5,7 1,6 3,53 5,6 1,9 2,90 5,4 2,3 2,36 5,2 2,7 1,922 88 6,0 1,6 3,70 5,8 1,9 3,02 5,6 2,3 2,44 5,4 2,7 1,995 87 6,4 1,6 3,94 6,2 1,9 3,20 6,0 2,3 2,58 5,7 2,8 2,087 87 6,8 1,6 4,15 6,6 2,0 3,36 6,3 2,3 2,68 6,0 2,8 2,1510 86 7,3 1,6 4,46 7,0 2,0 3,59 6,7 2,4 2,84 6,3 2,8 2,2612 86 7,7 1,6 4,68 7,4 2,0 3,75 7,0 2,4 2,97 6,6 2,8 2,3415 86 8,2 1,6 5,03 7,9 2,0 4,02 7,5 2,4 3,14 7,0 2,8 2,46
9
-20 90 4,3 1,9 2,33 * * * * * * * * *-15 90 4,9 1,9 2,58 5,0 2,3 2,17 * * * * * *-10 90 5,5 1,9 2,88 5,6 2,3 2,40 * * * * * *-7 89 6,0 1,9 3,09 6,0 2,3 2,56 6,0 2,8 2,11 * * *-2 89 6,8 2,0 3,48 6,7 2,4 2,83 6,7 2,9 2,31 * * *0 88 7,1 2,0 3,65 7,0 2,4 2,94 6,9 2,9 2,39 6,8 3,5 1,942 88 7,5 2,0 3,81 7,4 2,4 3,08 7,2 2,9 2,49 7,0 3,5 1,995 87 8,0 2,0 4,09 7,9 2,4 3,28 7,6 2,9 2,61 7,4 3,5 2,097 87 8,5 2,0 4,30 8,3 2,4 3,43 8,0 2,9 2,73 7,7 3,5 2,1610 86 9,1 2,0 4,62 8,8 2,4 3,65 8,5 2,9 2,89 8,1 3,6 2,2612 86 9,5 2,0 4,84 9,3 2,4 3,83 8,9 3,0 3,01 8,4 3,6 2,3515 86 10,3 2,0 5,26 9,9 2,4 4,11 9,5 3,0 3,20 8,8 3,6 2,47
11
-20 90 5,5 2,3 2,38 * * * * * * * * *-15 90 6,3 2,4 2,64 6,3 2,8 2,21 * * * * * *-10 90 7,1 2,4 2,92 7,1 2,9 2,43 * * * * * *-7 89 7,7 2,5 3,11 7,7 3,0 2,57 7,6 3,6 2,12 * * *-2 89 8,7 2,5 3,48 8,6 3,0 2,83 8,4 3,7 2,30 * * *0 88 9,2 2,5 3,63 9,0 3,1 2,94 8,8 3,7 2,37 8,5 4,4 1,932 88 9,6 2,5 3,79 9,4 3,1 3,06 9,2 3,7 2,46 8,8 4,4 1,985 87 10,3 2,5 4,05 10,1 3,1 3,24 9,7 3,8 2,58 9,3 4,5 2,067 87 10,8 2,6 4,23 10,5 3,1 3,37 10,2 3,8 2,68 9,6 4,5 2,1210 86 11,6 2,6 4,52 11,3 3,2 3,58 10,8 3,8 2,83 10,2 4,6 2,2112 86 12,2 2,6 4,76 11,8 3,2 3,73 11,3 3,9 2,93 10,6 4,6 2,2915 86 13,1 2,6 5,09 12,7 3,2 3,99 12,0 3,9 3,10 11,2 4,7 2,40
13
-20 90 7,4 3,0 2,44 7,8 3,7 2,11 * * * * * *-15 90 8,3 3,0 2,72 8,7 3,7 2,33 * * * * * *-10 90 9,2 3,1 2,99 9,6 3,8 2,55 10,1 4,7 2,15 * * *-7 89 9,9 3,1 3,19 10,2 3,8 2,69 10,6 4,7 2,25 * * *-2 89 11,0 3,1 3,52 11,3 3,8 2,95 11,6 4,7 2,44 12,0 5,9 2,030 88 11,4 3,1 3,66 11,7 3,8 3,04 11,9 4,8 2,51 12,3 5,9 2,082 88 11,9 3,1 3,80 12,1 3,8 3,16 12,4 4,8 2,60 12,7 5,9 2,145 87 12,6 3,1 4,02 12,8 3,9 3,32 13,0 4,8 2,71 13,1 5,9 2,217 87 13,1 3,1 4,19 13,3 3,9 3,45 13,5 4,8 2,81 13,5 6,0 2,2710 86 13,9 3,1 4,44 14,0 3,9 3,63 14,1 4,8 2,93 14,1 6,0 2,3612 86 14,4 3,1 4,62 14,5 3,9 3,77 14,6 4,8 3,03 14,5 6,0 2,4315 86 15,3 3,1 4,95 15,4 3,9 3,98 15,3 4,8 3,18 15,1 6,0 2,52
17
-20 90 9,0 3,6 2,46 9,5 4,4 2,15 * * * * * *-15 90 10,1 3,7 2,73 10,6 4,5 2,36 * * * * * *-10 90 11,3 3,8 2,99 11,8 4,6 2,57 12,4 5,7 2,18 * * *-7 89 12,1 3,8 3,18 12,5 4,6 2,70 13,1 5,7 2,28 * * *-2 89 13,4 3,8 3,51 13,9 4,7 2,94 14,3 5,8 2,46 14,8 7,2 2,060 88 14,0 3,8 3,65 14,4 4,7 3,05 14,8 5,9 2,52 15,2 7,2 2,102 88 14,6 3,8 3,80 14,9 4,7 3,16 15,3 5,9 2,60 15,7 7,3 2,165 87 15,4 3,8 4,02 15,8 4,8 3,32 16,1 5,9 2,72 16,3 7,3 2,237 87 16,1 3,8 4,20 16,4 4,8 3,45 16,7 5,9 2,81 16,8 7,4 2,2710 86 17,1 3,8 4,46 17,3 4,8 3,63 17,5 5,9 2,94 17,4 7,5 2,3112 86 17,8 3,8 4,65 18,0 4,8 3,78 18,1 6,0 3,04 17,9 7,7 2,3215 86 18,9 3,8 4,97 19,0 4,7 4,00 19,0 6,0 3,19 18,5 8,2 2,27
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
43
Pt: Heating capacity [kW]
Pa: Total absorbed compressor power [kW]
Ta: Dry bulb temperature of the evaporator inlet air [°C]
RH: Relative humidity of the input air at the evaporator [%]
HEATING CAPACITIES - MAROON 2 HT
Model
Ta RH Condenser inlet water temperature [°C]
[°C] %30/35 40/45 50/55 55/60
Pt Pat COP Pt Pat COP Pt Pat COP Pt Pat COP
22
-20 90 11,8 4,8 2,45 12,5 6,0 2,08 * * * * * *-15 90 13,3 4,9 2,73 14,0 6,1 2,30 * * * * * *-10 90 14,8 4,9 3,00 15,4 6,1 2,52 16,2 7,7 2,09 * * *-7 89 15,9 5,0 3,19 16,4 6,2 2,66 17,1 7,8 2,20 * * *-2 89 17,7 5,0 3,52 18,1 6,2 2,91 18,7 7,8 2,38 19,2 9,8 1,960 88 18,4 5,0 3,65 18,8 6,2 3,01 19,2 7,9 2,44 19,7 9,9 2,002 88 19,1 5,0 3,79 19,5 6,3 3,12 19,9 7,9 2,53 20,3 9,9 2,065 87 20,3 5,0 4,02 20,6 6,3 3,28 20,9 7,9 2,64 21,1 9,9 2,137 87 21,1 5,0 4,18 21,4 6,3 3,39 21,6 7,9 2,73 21,7 9,9 2,1810 86 22,4 5,0 4,44 22,6 6,3 3,58 22,7 7,9 2,86 22,5 10,0 2,2412 86 23,2 5,0 4,63 23,4 6,3 3,71 23,4 7,9 2,95 23,0 10,1 2,2815 86 24,6 5,0 4,93 24,7 6,3 3,93 24,6 8,0 3,10 23,8 10,3 2,31
26
-20 90 13,7 5,9 2,34 14,3 7,3 1,95 * * * * * *-15 90 15,5 5,9 2,62 16,1 7,4 2,17 * * * * * *-10 90 17,4 5,9 2,93 18,0 7,4 2,41 18,6 9,3 1,99 * * *-7 89 18,7 6,0 3,14 19,2 7,5 2,58 19,8 9,4 2,11 * * *-2 89 20,9 6,0 3,50 21,4 7,5 2,86 21,9 9,4 2,33 22,4 11,7 1,920 88 21,7 6,0 3,64 22,1 7,5 2,96 22,6 9,4 2,40 23,1 11,7 1,982 88 22,7 6,0 3,80 23,1 7,5 3,09 23,6 9,4 2,50 24,0 11,7 2,045 87 24,1 6,0 4,03 24,5 7,5 3,27 24,8 9,4 2,63 25,1 11,7 2,147 87 25,2 6,0 4,19 25,5 7,5 3,40 25,8 9,4 2,74 25,9 11,8 2,2010 86 26,7 6,0 4,45 27,0 7,5 3,60 27,2 9,4 2,88 27,1 11,8 2,2912 86 27,9 6,0 4,62 28,1 7,5 3,74 28,2 9,4 2,99 27,9 11,9 2,3515 86 29,6 6,1 4,90 29,7 7,5 3,96 29,7 9,4 3,16 29,1 12,0 2,42
32
-20 90 16,7 7,3 2,29 17,5 9,0 1,94 * * * * * *-15 90 19,0 7,3 2,60 19,8 9,0 2,19 * * * * * *-10 90 21,2 7,3 2,91 22,1 9,1 2,44 22,9 11,2 2,05 * * *-7 89 22,7 7,3 3,12 23,6 9,1 2,61 24,5 11,2 2,19 * * *-2 89 25,1 7,2 3,47 26,2 9,0 2,90 27,0 11,2 2,41 27,7 13,7 2,020 88 26,1 7,2 3,61 27,1 9,0 3,01 28,0 11,2 2,50 28,6 13,7 2,092 88 27,1 7,2 3,75 28,1 9,0 3,12 29,0 11,2 2,59 29,6 13,7 2,165 87 28,8 7,2 3,97 29,7 9,0 3,31 30,5 11,2 2,73 31,1 13,7 2,277 87 29,9 7,2 4,13 30,8 9,0 3,44 31,6 11,2 2,84 32,1 13,7 2,3510 86 31,7 7,3 4,36 32,5 8,9 3,63 33,2 11,1 2,99 33,6 13,7 2,4612 86 33,1 7,3 4,53 33,8 8,9 3,77 34,4 11,1 3,10 34,7 13,6 2,5515 86 35,0 7,4 4,75 35,7 8,9 3,99 36,2 11,1 3,27 36,4 13,6 2,67
36
-20 90 18,9 8,1 2,34 19,2 9,8 1,97 * * * * * *-15 90 21,6 8,1 2,65 22,0 9,9 2,23 * * * * * *-10 90 24,3 8,2 2,96 24,9 10,0 2,48 25,4 12,3 2,06 * * *-7 89 26,0 8,2 3,16 26,6 10,1 2,65 27,3 12,4 2,19 * * *-2 89 29,0 8,3 3,49 29,7 10,2 2,92 30,4 12,6 2,42 31,0 15,5 2,000 88 30,1 8,3 3,63 30,8 10,2 3,03 31,5 12,6 2,50 32,1 15,5 2,072 88 31,3 8,3 3,77 32,1 10,2 3,14 32,8 12,6 2,60 33,4 15,6 2,145 87 33,3 8,3 4,00 34,0 10,2 3,32 34,6 12,7 2,73 35,2 15,7 2,257 87 34,5 8,3 4,15 35,2 10,2 3,45 35,9 12,7 2,83 36,4 15,7 2,3210 86 36,6 8,3 4,42 37,3 10,2 3,65 37,9 12,7 2,98 38,2 15,7 2,4312 86 38,0 8,3 4,59 38,5 10,2 3,77 39,2 12,7 3,08 39,6 15,8 2,5115 86 40,2 8,2 4,89 40,9 10,2 4,01 41,3 12,7 3,25 41,4 15,8 2,63
41
-20 90 20,8 8,8 2,36 21,6 10,7 2,01 * * * * * *-15 90 23,5 8,9 2,65 24,3 10,8 2,25 * * * * * *-10 90 26,2 8,9 2,93 27,1 10,9 2,48 28,2 13,5 2,08 * * *-7 89 28,0 9,0 3,12 28,9 11,0 2,63 29,9 13,6 2,20 * * *-2 89 31,2 9,0 3,45 32,1 11,1 2,89 33,0 13,7 2,40 34,0 17,0 2,000 88 32,6 9,1 3,60 33,4 11,1 3,00 34,2 13,8 2,48 35,1 17,0 2,062 88 33,8 9,1 3,72 34,6 11,1 3,11 35,5 13,8 2,57 36,4 17,1 2,135 87 36,1 9,1 3,96 36,8 11,2 3,29 37,5 13,9 2,71 38,2 17,2 2,227 87 37,6 9,1 4,13 38,2 11,2 3,42 38,9 13,9 2,80 39,5 17,2 2,2910 86 39,9 9,1 4,37 40,6 11,2 3,61 41,1 14,0 2,95 41,6 17,3 2,4012 86 41,6 9,1 4,55 42,2 11,2 3,75 42,6 14,0 3,04 42,9 17,3 2,4715 86 44,2 9,1 4,83 44,7 11,2 3,97 45,1 14,0 3,22 45,2 17,4 2,60
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
44
COOLING CAPACITIES - MAROON 2 HT
Pf: Cooling power [kW]
Pa: Total absorbed compressor power [kW]
To: Utility outlet water temperature to the utility exchanger [°C]
Model
To External air temperature [°C]
[°C]25 30 35 40
Pf Pat EER Pf Pat EER Pf Pat EER Pf Pat EER
50
5 39,8 10,1 3,95 38,6 11,3 3,42 37,2 12,6 2,95 35,6 14,2 2,526 40,8 10,1 4,04 39,5 11,3 3,49 38,1 12,7 3,00 36,4 14,2 2,567 41,8 10,1 4,12 40,5 11,4 3,56 39,0 12,7 3,06 37,3 14,3 2,618 42,8 10,2 4,21 41,5 11,4 3,63 39,9 12,8 3,12 38,1 14,4 2,659 43,8 10,2 4,29 42,5 11,5 3,70 40,8 12,9 3,18 39,0 14,4 2,7010 44,9 10,2 4,38 43,4 11,5 3,77 41,8 12,9 3,23 39,9 14,5 2,7513 48,0 10,3 4,64 46,4 11,6 3,99 44,6 13,1 3,41 42,5 14,7 2,8914 49,1 10,4 4,73 47,4 11,7 4,06 45,5 13,1 3,46 43,3 14,8 2,9415 50,2 10,4 4,82 48,5 11,7 4,13 46,5 13,2 3,52 44,2 14,8 2,9816 51,2 10,4 4,92 49,5 11,8 4,21 47,5 13,2 3,58 45,2 14,9 3,0317 52,4 10,4 5,01 50,6 11,8 4,29 48,5 13,3 3,65 46,1 14,9 3,0818 53,5 10,5 5,11 51,6 11,8 4,36 49,5 13,3 3,71 47,0 15,0 3,13
60
5 45,2 11,7 3,86 43,9 13,1 3,36 42,4 14,7 2,90 40,7 16,4 2,486 46,3 11,8 3,93 45,0 13,1 3,43 43,5 14,7 2,96 41,8 16,5 2,537 47,5 11,8 4,01 46,2 13,2 3,50 44,7 14,8 3,02 42,9 16,6 2,588 48,7 11,9 4,09 47,4 13,3 3,56 45,8 14,9 3,08 43,9 16,6 2,649 49,9 12,0 4,17 48,5 13,4 3,64 46,9 14,9 3,14 45,0 16,7 2,6910 51,2 12,1 4,24 49,7 13,4 3,70 48,1 15,0 3,20 46,1 16,8 2,7513 54,9 12,3 4,47 53,4 13,6 3,91 51,5 15,2 3,38 49,5 17,0 2,9014 56,2 12,4 4,55 54,6 13,7 3,98 52,7 15,3 3,44 50,6 17,1 2,9615 57,5 12,4 4,62 55,8 13,8 4,04 53,9 15,4 3,50 51,7 17,2 3,0116 58,8 12,5 4,69 57,1 13,9 4,11 55,1 15,5 3,56 52,9 17,3 3,0617 60,1 12,6 4,77 58,4 14,0 4,17 56,4 15,6 3,62 54,1 17,4 3,1118 61,5 12,7 4,84 59,7 14,1 4,24 57,6 15,7 3,68 55,3 17,5 3,17
70
5 56,5 14,3 3,94 55,4 16,1 3,44 53,8 18,1 2,98 51,9 20,3 2,566 57,9 14,4 4,00 56,7 16,2 3,51 55,1 18,1 3,04 53,1 20,4 2,617 59,3 14,6 4,07 58,1 16,3 3,57 56,5 18,2 3,09 54,4 20,5 2,668 60,7 14,7 4,14 59,4 16,4 3,63 57,8 18,3 3,15 55,7 20,6 2,719 62,1 14,8 4,20 60,8 16,5 3,69 59,1 18,4 3,21 57,0 20,7 2,7610 63,5 14,9 4,27 62,2 16,6 3,75 60,5 18,5 3,26 58,3 20,8 2,8113 67,9 15,3 4,44 66,5 16,9 3,92 64,6 18,9 3,42 62,1 21,1 2,9514 69,4 15,4 4,49 67,9 17,1 3,98 65,9 19,0 3,47 63,4 21,2 2,9915 70,9 15,6 4,55 69,3 17,2 4,03 67,3 19,1 3,52 64,8 21,3 3,0416 72,4 15,8 4,60 70,8 17,4 4,08 68,7 19,3 3,57 66,1 21,4 3,0817 74,0 15,9 4,65 72,3 17,5 4,13 70,1 19,4 3,62 67,4 21,6 3,1318 75,5 16,1 4,70 73,8 17,7 4,18 71,6 19,5 3,66 68,8 21,7 3,17
80
5 63,7 16,6 3,84 62,4 18,5 3,37 60,7 20,6 2,94 58,6 23,0 2,556 65,2 16,6 3,92 63,8 18,6 3,44 62,1 20,7 3,00 60,0 23,1 2,607 66,8 16,7 4,00 65,3 18,6 3,51 63,6 20,8 3,06 61,5 23,2 2,658 68,3 16,8 4,08 66,9 18,7 3,58 65,1 20,9 3,12 62,9 23,3 2,709 69,9 16,8 4,16 68,4 18,8 3,65 66,6 20,9 3,18 64,4 23,4 2,7510 71,5 16,9 4,24 70,0 18,8 3,72 68,1 21,0 3,24 65,8 23,5 2,8013 76,3 17,0 4,49 74,6 19,0 3,93 72,6 21,3 3,42 70,2 23,8 2,9514 78,0 17,0 4,57 76,2 19,1 4,00 74,2 21,3 3,48 71,6 23,9 3,0015 79,6 17,1 4,66 77,8 19,1 4,07 75,7 21,4 3,54 73,1 24,0 3,0516 81,3 17,1 4,75 79,5 19,2 4,14 77,3 21,5 3,60 74,6 24,1 3,1017 83,0 17,2 4,84 81,1 19,2 4,22 78,9 21,5 3,66 76,1 24,1 3,1618 84,7 17,2 4,93 82,8 19,3 4,30 80,5 21,6 3,73 77,7 24,2 3,21
90
5 73,2 19,1 3,84 71,3 21,2 3,37 69,1 23,6 2,93 66,4 26,3 2,536 75,0 19,2 3,91 73,1 21,3 3,43 70,8 23,7 2,99 68,0 26,5 2,577 76,9 19,3 3,99 74,9 21,4 3,50 72,5 23,8 3,04 69,7 26,6 2,628 78,7 19,4 4,06 76,7 21,5 3,56 74,3 24,0 3,09 71,4 26,8 2,669 80,7 19,5 4,14 78,6 21,7 3,62 76,1 24,2 3,15 73,1 27,0 2,7110 82,6 19,6 4,21 80,4 21,8 3,69 77,9 24,3 3,20 74,8 27,2 2,7513 88,5 20,0 4,43 86,1 22,2 3,88 83,3 24,8 3,36 79,9 27,7 2,8914 90,5 20,1 4,51 88,0 22,3 3,94 85,1 24,9 3,42 81,6 27,9 2,9315 92,5 20,2 4,58 90,0 22,5 4,00 87,0 25,1 3,47 83,4 28,0 2,9816 94,6 20,3 4,66 92,0 22,6 4,07 88,9 25,2 3,52 85,2 28,2 3,0217 96,7 20,4 4,73 94,0 22,8 4,13 90,8 25,4 3,57 87,0 28,4 3,0618 98,8 20,6 4,80 96,0 22,9 4,19 92,7 25,6 3,63 88,8 28,6 3,11
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
45
HEATING CAPACITIES - MAROON 2 HT
Pt: Heating capacity [kW]
Pa: Total absorbed compressor power [kW]
Ta: Dry bulb temperature of the evaporator inlet air [°C]
RH: Relative humidity of the input air at the evaporator [%]
Model
Ta RH Condenser inlet water temperature [°C]
[°C] %30/35 40/45 50/55 55/60
Pt Pat COP Pt Pat COP Pt Pat COP Pt Pat COP
50
-20 90 23,3 9,6 2,43 24,7 11,9 2,08 * * * * * *-15 90 26,4 9,7 2,73 27,7 12,0 2,31 * * * * * *-10 90 29,5 9,8 3,02 30,6 12,1 2,53 32,1 15,3 2,10 * * *-7 89 31,5 9,8 3,21 32,5 12,2 2,67 33,9 15,3 2,21 * * *-2 89 35,1 9,9 3,55 36,0 12,3 2,93 37,0 15,4 2,40 38,2 19,4 1,970 88 36,5 9,9 3,68 37,3 12,3 3,03 38,3 15,5 2,47 39,3 19,4 2,032 88 38,0 9,9 3,82 38,8 12,3 3,14 39,6 15,5 2,55 40,5 19,5 2,085 87 40,5 9,9 4,07 41,0 12,4 3,31 41,6 15,6 2,67 42,2 19,5 2,167 87 42,0 9,9 4,23 42,6 12,4 3,43 43,1 15,6 2,76 43,5 19,5 2,2310 86 44,7 9,9 4,52 45,1 12,4 3,63 45,2 15,6 2,89 45,3 19,6 2,3112 86 46,5 9,9 4,71 46,7 12,4 3,76 46,8 15,7 2,99 46,7 19,6 2,3815 86 49,5 9,8 5,05 49,6 12,4 4,01 49,3 15,7 3,15 48,7 19,6 2,48
60
-20 90 27,4 11,6 2,36 28,6 14,5 1,98 * * * * * *-15 90 31,2 11,7 2,68 32,4 14,6 2,23 * * * * * *-10 90 35,1 11,7 3,00 36,2 14,7 2,47 37,6 18,3 2,05 * * *-7 89 37,6 11,7 3,20 38,8 14,7 2,64 40,1 18,4 2,17 * * *-2 89 42,0 11,7 3,58 43,1 14,7 2,93 44,3 18,5 2,39 45,5 22,9 1,990 88 43,8 11,7 3,73 44,8 14,7 3,04 45,9 18,5 2,48 47,0 23,0 2,042 88 45,6 11,7 3,88 46,6 14,7 3,17 47,7 18,5 2,58 48,8 23,0 2,125 87 48,6 11,8 4,13 49,5 14,7 3,36 50,3 18,5 2,72 51,2 23,0 2,227 87 50,5 11,8 4,30 51,4 14,7 3,49 52,2 18,5 2,82 53,1 23,0 2,3010 86 53,9 11,8 4,58 54,6 14,7 3,71 55,2 18,5 2,98 55,6 23,0 2,4112 86 56,2 11,8 4,76 56,6 14,7 3,85 57,1 18,5 3,09 57,6 23,0 2,5015 86 59,9 11,8 5,06 60,3 14,7 4,10 60,5 18,5 3,28 60,5 23,0 2,63
70
-20 90 31,3 13,7 2,28 32,6 17,0 1,92 * * * * * *-15 90 35,5 13,7 2,59 37,0 17,1 2,16 * * * * * *-10 90 39,7 13,7 2,90 41,4 17,2 2,40 42,9 21,4 2,00 * * *-7 89 42,3 13,7 3,09 44,1 17,2 2,56 45,7 21,5 2,12 * * *-2 89 46,9 13,6 3,45 48,8 17,2 2,84 50,5 21,6 2,34 51,8 26,5 1,950 88 49,0 13,6 3,60 50,8 17,2 2,96 52,4 21,6 2,43 53,6 26,6 2,012 88 51,0 13,6 3,75 52,8 17,1 3,08 54,3 21,6 2,51 55,5 26,6 2,085 87 54,0 13,6 3,98 55,8 17,1 3,26 57,3 21,5 2,66 58,3 26,7 2,197 87 56,2 13,6 4,14 57,9 17,1 3,39 59,4 21,5 2,76 60,2 26,7 2,2610 86 59,5 13,6 4,37 61,2 17,0 3,59 62,5 21,5 2,91 63,2 26,6 2,3812 86 62,0 13,7 4,54 63,5 17,0 3,73 64,8 21,4 3,02 65,2 26,6 2,4515 86 65,8 13,8 4,78 67,2 17,0 3,94 68,3 21,4 3,20 68,5 26,5 2,58
80
-20 90 38,0 16,0 2,38 38,6 19,4 1,99 * * * * * *-15 90 43,4 16,1 2,70 44,3 19,6 2,26 * * * * * *-10 90 48,8 16,3 3,00 50,0 19,9 2,52 51,1 24,5 2,09 * * *-7 89 52,3 16,3 3,20 53,6 20,0 2,68 54,8 24,7 2,22 * * *-2 89 58,3 16,4 3,55 59,7 20,2 2,96 61,1 25,0 2,44 62,4 30,8 2,020 88 60,7 16,5 3,69 62,2 20,2 3,07 63,6 25,1 2,54 64,7 31,0 2,092 88 63,0 16,5 3,83 64,5 20,3 3,18 65,9 25,1 2,62 67,2 31,1 2,165 87 67,0 16,5 4,06 68,4 20,3 3,37 69,8 25,2 2,76 70,9 31,2 2,277 87 69,7 16,5 4,23 71,0 20,3 3,49 72,3 25,3 2,86 73,4 31,3 2,3410 86 73,8 16,5 4,48 75,2 20,3 3,69 76,4 25,3 3,01 77,2 31,4 2,4612 86 76,7 16,4 4,67 78,0 20,3 3,84 78,9 25,4 3,11 79,7 31,5 2,5315 86 81,2 16,3 4,97 82,5 20,3 4,06 83,4 25,4 3,29 83,8 31,5 2,66
90
-20 90 42,1 17,5 2,40 43,8 21,4 2,05 * * * * * *-15 90 47,7 17,7 2,70 49,5 21,6 2,29 * * * * * *-10 90 53,3 17,8 2,99 55,1 21,8 2,53 57,3 27,0 2,12 * * *-7 89 56,9 17,9 3,18 58,6 21,9 2,67 60,8 27,2 2,23 * * *-2 89 63,4 18,0 3,52 65,1 22,1 2,94 67,1 27,5 2,44 69,1 34,0 2,030 88 66,3 18,1 3,66 67,8 22,2 3,06 69,6 27,6 2,53 71,6 34,1 2,102 88 69,1 18,1 3,81 70,5 22,3 3,17 72,1 27,6 2,61 74,0 34,2 2,165 87 73,4 18,2 4,04 74,8 22,3 3,35 76,3 27,8 2,75 77,8 34,4 2,267 87 76,5 18,2 4,20 77,9 22,4 3,48 79,2 27,8 2,85 80,4 34,5 2,3310 86 81,2 18,2 4,45 82,5 22,4 3,68 83,7 28,0 2,99 84,6 34,7 2,4412 86 84,7 18,3 4,64 85,9 22,5 3,82 86,9 28,0 3,10 87,3 34,8 2,5115 86 90,0 18,3 4,93 91,1 22,5 4,04 91,9 28,1 3,27 92,1 35,0 2,63
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
46
Model
To DHW temperature [°C]
[°C]40/45 45/50 50/55 55/60
Pf Pa Pt EER COP Pf Pa Pt EER COP Pf Pa Pt EER COP Pf Pa Pt EER COP
RECOVERY CAPACITIES - MAROON 2 HT
Pf: Cooling power [kW]
Pt: Heat power [kW]
To: Utility outlet water temperature (°C)
7
5 5,5 1,7 7,2 3,16 4,16 5,1 1,9 7,0 2,65 3,65 4,7 2,1 6,8 2,20 3,20 4,2 2,4 6,6 1,78 2,78
7 5,9 1,8 7,6 3,36 4,35 5,5 1,9 7,4 2,83 3,83 5,0 2,1 7,2 2,34 3,35 4,5 2,4 6,9 1,89 2,89
10 6,5 1,8 8,2 3,70 4,70 6,0 1,9 8,0 3,10 4,10 5,5 2,2 7,7 2,56 3,56 5,0 2,4 7,4 2,07 3,07
14 7,3 1,8 9,1 4,18 5,18 6,8 2,0 8,8 3,49 4,49 6,3 2,2 8,4 2,88 3,88 5,6 2,4 8,1 2,33 3,33
18 8,3 1,8 10,0 4,71 5,71 7,7 2,0 9,6 3,94 4,94 7,1 2,2 9,3 3,24 4,24 6,4 2,4 8,8 2,63 3,62
9
5 7,3 2,2 9,5 3,31 4,31 6,8 2,5 9,2 2,77 3,77 6,2 2,7 9,0 2,29 3,29 5,6 3,0 8,6 1,84 2,84
7 7,8 2,2 10,0 3,54 4,54 7,3 2,5 9,7 2,96 3,96 6,7 2,7 9,4 2,44 3,44 6,0 3,1 9,0 1,96 2,96
10 8,6 2,2 10,8 3,89 4,90 8,0 2,5 10,4 3,24 4,24 7,3 2,7 10,1 2,67 3,67 6,6 3,1 9,6 2,15 3,15
14 9,7 2,2 11,9 4,40 5,40 9,0 2,5 11,5 3,66 4,66 8,3 2,8 11,0 3,01 4,01 7,4 3,1 10,5 2,42 3,42
18 10,9 2,2 13,1 4,98 5,97 10,2 2,5 12,6 4,14 5,15 9,3 2,8 12,1 3,39 4,39 8,4 3,1 11,5 2,72 3,72
11
5 9,6 2,9 12,5 3,29 4,29 8,9 3,2 12,2 2,76 3,76 8,2 3,6 11,8 2,28 3,27 7,3 4,0 11,3 1,84 2,84
7 10,2 2,9 13,1 3,49 4,50 9,5 3,3 12,7 2,92 3,92 8,7 3,6 12,3 2,41 3,41 7,8 4,0 11,8 1,94 2,94
10 11,2 2,9 14,1 3,80 4,80 10,4 3,3 13,7 3,17 4,18 9,5 3,6 13,2 2,62 3,61 8,5 4,0 12,6 2,11 3,11
14 12,6 3,0 15,5 4,25 5,25 11,7 3,3 15,0 3,55 4,55 10,7 3,7 14,4 2,92 3,92 9,6 4,1 13,7 2,34 3,34
18 14,1 3,0 17,0 4,75 5,75 13,1 3,3 16,4 3,96 4,95 12,0 3,7 15,7 3,25 4,25 10,8 4,1 14,9 2,64 3,65
13
5 11,4 3,2 14,6 3,57 4,57 10,9 3,6 14,6 2,99 4,00 10,3 4,2 14,5 2,48 3,48 9,6 4,7 14,3 2,03 3,03
7 12,0 3,2 15,2 3,75 4,75 11,5 3,6 15,1 3,15 4,15 10,8 4,2 15,0 2,61 3,61 10,1 4,8 14,8 2,12 3,12
10 12,9 3,2 16,1 4,05 5,05 12,3 3,6 16,0 3,39 4,39 11,7 4,2 15,8 2,81 3,81 10,8 4,8 15,6 2,28 3,28
14 14,2 3,2 17,4 4,50 5,50 13,6 3,6 17,2 3,75 4,75 12,8 4,1 16,9 3,09 4,09 11,9 4,7 16,6 2,50 3,50
18 15,6 3,1 18,7 5,02 6,02 14,9 3,6 18,5 4,15 5,15 14,0 4,1 18,1 3,41 4,41 13,4 4,7 18,1 2,82 3,82
17
5 13,6 4,1 17,7 3,33 4,33 13,1 4,6 17,7 2,82 3,82 12,5 5,3 17,8 2,36 3,36 11,7 6,0 17,7 1,95 2,95
7 14,3 4,1 18,4 3,51 4,51 13,8 4,6 18,4 2,97 3,97 13,1 5,3 18,4 2,48 3,48 12,3 6,0 18,3 2,04 3,04
10 15,4 4,1 19,5 3,79 4,79 14,8 4,6 19,5 3,19 4,19 14,1 5,3 19,4 2,67 3,67 13,2 6,0 19,2 2,19 3,19
14 17,0 4,1 21,0 4,20 5,20 16,3 4,6 20,9 3,52 4,52 15,5 5,3 20,7 2,93 3,93 14,4 6,0 20,5 2,39 3,39
18 18,7 4,0 22,7 4,64 5,64 17,9 4,6 22,5 3,89 4,90 16,9 5,3 22,2 3,22 4,22 16,3 6,0 22,3 2,70 3,70
22
5 18,8 5,5 24,3 3,39 4,39 17,9 6,3 24,2 2,85 3,85 17,0 7,2 24,1 2,36 3,36 15,8 8,2 24,0 1,93 2,93
7 19,7 5,5 25,3 3,57 4,57 18,9 6,3 25,2 2,99 4,00 17,8 7,2 25,0 2,48 3,48 16,6 8,2 24,8 2,02 3,02
10 21,3 5,5 26,8 3,85 4,85 20,3 6,3 26,6 3,22 4,22 19,2 7,2 26,4 2,67 3,67 17,8 8,2 26,0 2,17 3,17
14 23,4 5,5 28,8 4,27 5,27 22,3 6,3 28,6 3,56 4,56 21,0 7,2 28,2 2,93 3,93 19,5 8,2 27,7 2,37 3,37
18 25,6 5,4 31,0 4,75 5,75 24,4 6,2 30,6 3,93 4,93 23,0 7,1 30,1 3,23 4,23 22,0 8,2 30,2 2,67 3,68
26
5 21,6 6,7 28,3 3,21 4,21 20,7 7,6 28,3 2,72 3,72 19,6 8,6 28,3 2,27 3,27 18,4 9,8 28,3 1,87 2,87
7 22,8 6,7 29,5 3,39 4,39 21,8 7,6 29,4 2,87 3,87 20,8 8,6 29,4 2,40 3,40 19,5 9,8 29,3 1,98 2,98
10 24,6 6,7 31,3 3,67 4,67 23,6 7,6 31,2 3,11 4,11 22,5 8,6 31,1 2,60 3,60 21,1 9,8 31,0 2,15 3,15
14 27,2 6,7 33,9 4,05 5,05 26,1 7,6 33,7 3,44 4,44 24,9 8,6 33,5 2,88 3,88 23,4 9,8 33,2 2,38 3,38
18 29,9 6,7 36,6 4,45 5,45 28,7 7,6 36,3 3,78 4,78 27,4 8,6 36,0 3,18 4,18 26,4 9,8 36,3 2,69 3,69
32
5 28,8 7,7 36,4 3,76 4,76 27,9 8,7 36,6 3,22 4,22 26,8 9,8 36,6 2,73 3,73 25,4 11,1 36,6 2,28 3,28
7 30,3 7,6 37,9 3,96 4,96 29,4 8,7 38,1 3,40 4,40 28,3 9,8 38,1 2,89 3,89 26,8 11,1 37,9 2,41 3,41
10 32,6 7,7 40,2 4,26 5,26 31,6 8,6 40,3 3,67 4,67 30,4 9,8 40,2 3,12 4,12 28,9 11,1 40,0 2,61 3,61
14 35,7 7,7 43,4 4,65 5,65 34,7 8,6 43,4 4,02 5,02 33,4 9,7 43,2 3,44 4,44 31,8 11,0 42,8 2,88 3,88
18 39,1 7,8 46,9 5,03 6,03 38,0 8,7 46,7 4,38 5,38 36,6 9,7 46,3 3,76 4,76 34,8 11,0 45,8 3,16 4,16
36
5 31,6 8,9 40,5 3,54 4,54 30,6 10,1 40,6 3,03 4,03 29,3 11,4 40,7 2,57 3,57 27,8 13,0 40,7 2,14 3,15
7 33,2 8,9 42,1 3,73 4,73 32,2 10,1 42,2 3,19 4,19 30,9 11,4 42,3 2,71 3,71 29,3 13,0 42,2 2,26 3,26
10 35,6 8,9 44,5 4,02 5,02 34,5 10,0 44,6 3,44 4,44 33,2 11,4 44,6 2,92 3,92 31,6 13,0 44,5 2,43 3,43
14 39,0 8,8 47,8 4,44 5,44 37,8 10,0 47,8 3,79 4,80 36,4 11,3 47,7 3,21 4,21 34,6 12,9 47,5 2,68 3,68
18 42,6 8,7 51,2 4,91 5,91 41,3 9,9 51,2 4,18 5,18 39,8 11,2 51,0 3,54 4,54 37,8 12,8 50,6 2,94 3,94
41
5 36,3 9,9 46,2 3,65 4,65 35,0 11,2 46,2 3,13 4,13 33,6 12,7 46,2 2,65 3,65 31,7 14,4 46,1 2,21 3,21
7 38,3 9,9 48,2 3,85 4,85 37,0 11,2 48,2 3,30 4,30 35,4 12,7 48,1 2,79 3,79 33,5 14,4 47,9 2,32 3,32
10 41,3 9,9 51,2 4,16 5,16 39,9 11,2 51,1 3,56 4,56 38,2 12,7 50,9 3,01 4,01 36,2 14,4 50,6 2,50 3,50
14 45,5 9,9 55,4 4,59 5,59 44,0 11,2 55,2 3,92 4,92 42,1 12,7 54,9 3,31 4,31 39,9 14,5 54,4 2,75 3,75
18 50,0 9,9 59,9 5,06 6,06 48,3 11,2 59,5 4,32 5,32 46,3 12,7 59,0 3,64 4,64 43,8 14,5 58,3 3,03 4,03
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
47
Model
To DHW temperature [°C]
[°C]40/45 45/50 50/55 55/60
Pf Pa Pt EER COP Pf Pa Pt EER COP Pf Pa Pt EER COP Pf Pa Pt EER COP
RECOVERY CAPACITIES - MAROON 2 HT
Pf: Cooling power [kW]
Pt: Heat power [kW]
To: Utility outlet water temperature (°C)
50
5 37,7 10,9 48,6 3,47 4,47 35,9 12,6 48,5 2,84 3,84 34,0 14,4 48,3 2,36 3,36 31,9 16,2 48,1 1,97 2,97
7 39,4 11,1 50,5 3,56 4,56 37,7 12,6 50,3 2,98 3,98 35,7 14,4 50,1 2,49 3,49 33,6 16,2 49,8 2,07 3,07
10 42,5 11,0 53,5 3,85 4,85 40,6 12,6 53,2 3,22 4,22 38,4 14,3 52,8 2,68 3,68 36,0 16,2 52,2 2,23 3,23
14 46,7 11,0 57,6 4,26 5,26 44,6 12,6 57,1 3,55 4,55 42,2 14,3 56,4 2,95 3,95 39,5 16,1 55,6 2,45 3,45
18 51,2 10,8 62,0 4,74 5,75 48,8 12,4 61,3 3,93 4,93 46,2 14,2 60,4 3,26 4,26 43,2 16,1 59,3 2,69 3,69
60
5 42,8 13,0 55,8 3,30 4,30 40,7 15,2 55,9 2,68 3,68 38,7 17,3 55,9 2,24 3,24 36,6 19,4 56,0 1,89 2,89
7 45,2 13,0 58,2 3,48 4,48 43,0 15,2 58,2 2,83 3,83 40,9 17,2 58,1 2,38 3,38 38,8 19,4 58,1 2,00 3,00
10 48,5 13,4 61,8 3,63 4,63 46,5 15,1 61,7 3,07 4,07 44,3 17,2 61,5 2,58 3,58 42,0 19,3 61,3 2,18 3,18
14 53,5 13,3 66,8 4,02 5,02 51,4 15,1 66,5 3,41 4,41 49,1 17,1 66,2 2,87 3,87 46,6 19,2 65,8 2,43 3,43
18 58,9 13,3 72,3 4,43 5,43 56,7 15,1 71,7 3,76 4,76 54,2 17,0 71,2 3,18 4,18 51,5 19,1 70,6 2,69 3,69
70
5 55,1 15,3 70,4 3,61 4,61 53,0 17,8 70,8 2,97 3,97 50,8 20,2 71,0 2,52 3,52 48,3 22,6 70,9 2,13 3,13
7 57,9 15,3 73,2 3,79 4,79 55,8 17,8 73,6 3,13 4,13 53,5 20,1 73,7 2,66 3,66 51,0 22,6 73,5 2,26 3,26
10 61,9 15,7 77,6 3,95 4,95 60,1 17,7 77,8 3,39 4,39 57,7 20,0 77,7 2,88 3,88 54,9 22,4 77,4 2,45 3,45
14 68,0 15,7 83,7 4,32 5,32 65,9 17,7 83,6 3,72 4,72 63,4 19,9 83,3 3,18 4,18 60,4 22,3 82,7 2,71 3,71
18 74,4 15,9 90,2 4,68 5,68 72,1 17,8 89,9 4,06 5,06 69,4 19,9 89,3 3,49 4,49 66,2 22,2 88,4 2,98 3,98
80
5 61,4 17,6 79,1 3,48 4,48 59,0 20,5 79,5 2,87 3,87 56,5 23,2 79,8 2,43 3,43 53,8 26,1 79,9 2,06 3,06
7 64,5 17,6 82,2 3,66 4,66 62,1 20,5 82,6 3,03 4,03 59,6 23,2 82,8 2,57 3,57 56,8 26,1 82,8 2,18 3,18
10 68,9 18,1 87,0 3,82 4,82 66,7 20,5 87,2 3,26 4,26 64,1 23,2 87,3 2,77 3,77 61,2 26,0 87,2 2,35 3,35
14 75,4 17,9 93,3 4,22 5,22 73,1 20,3 93,4 3,60 4,60 70,4 23,0 93,4 3,06 4,06 67,2 25,9 93,1 2,59 3,59
18 82,3 17,6 100,0 4,67 5,67 79,8 20,1 99,9 3,97 4,97 76,9 22,8 99,7 3,37 4,37 73,4 25,7 99,1 2,86 3,86
90
5 70,7 19,7 90,4 3,59 4,59 67,7 22,9 90,6 2,96 3,96 64,7 25,9 90,6 2,50 3,50 61,5 29,0 90,5 2,12 3,12
7 74,5 19,7 94,2 3,78 4,78 71,4 22,9 94,3 3,12 4,12 68,3 25,9 94,2 2,64 3,64 64,9 29,1 94,0 2,23 3,23
10 80,2 19,9 100,1 4,03 5,03 77,1 22,9 100,0 3,36 4,36 73,8 25,9 99,7 2,85 3,85 70,1 29,1 99,2 2,41 3,41
14 88,0 20,2 108,2 4,35 5,35 85,0 22,9 107,9 3,71 4,71 81,4 25,9 107,3 3,14 4,14 77,3 29,1 106,5 2,65 3,65
18 96,7 20,1 116,8 4,80 5,80 93,4 22,8 116,2 4,09 5,09 89,5 25,9 115,3 3,46 4,46 85,1 29,1 114,2 2,92 3,92
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
48
MODELOctave bands [dB] Total
[dB(A)]63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
MODELOctave bands [dB] Total
[dB(A)]63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
SOUND LEVELS - MAROON 2 MT
SOUND LEVELS - MAROON 2 MT
Lw: sound power values in free field calculated in compliance with ISO 3744.Lp: sound pressure levels detected at 10 m from the fan side unit, not channelled in free field, in compliance with ISO 3744.Data detected with the unit that works at following conditions: A 35°C; W12/7°C
Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp
8 67 36 67 36 66 35 62 31 56 25 52 21 45 14 38 7 63 32
10 68 37 68 37 67 36 64 33 57 26 54 23 48 17 40 9 65 34
12 72 41 69 38 70 39 64 33 60 29 56 25 49 18 42 11 66 35
16 72 41 72 41 70 39 67 36 62 31 56 25 51 20 41 10 68 37
18 74 43 73 42 73 42 68 37 62 31 58 27 53 22 43 12 70 39
20 75 44 74 43 74 43 68 37 63 32 59 28 52 21 45 14 70 39
23 77 46 75 44 76 45 70 39 66 35 61 30 53 22 47 16 72 41
25 78 47 76 45 76 45 72 41 64 33 61 30 56 25 47 16 73 42
29 79 47 77 45 78 46 72 40 67 35 63 31 56 24 49 17 74 42
34 80 48 79 47 77 45 74 42 67 35 63 31 57 25 50 18 75 43
38 81 48 79 47 78 46 75 43 67 35 63 31 57 25 50 18 75 43
42 81 49 79 47 77 45 74 42 68 36 64 32 58 26 51 19 75 43
Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp
52 66 35 65 34 68 37 69 38 68 37 66 35 63 32 58 27 73 42
62 66 35 65 34 68 37 69 38 68 37 66 35 63 32 58 27 73 42
72 67 36 67 36 69 38 70 39 69 38 67 36 64 33 59 28 74 43
82 68 37 67 36 70 39 71 40 70 39 68 37 65 34 50 19 75 44
92 71 40 70 39 73 42 73 42 72 41 71 40 67 36 62 31 77 46
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
49
MODELOctave bands [dB] Total
[dB(A)]63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
MODELOctave bands [dB] Total
[dB(A)]63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
SOUND LEVELS - MAROON 2 HT
SOUND LEVELS - MAROON 2 HT
Lw: sound power values in free field calculated in compliance with ISO 3744.Lp: sound pressure levels detected at 10 m from the fan side unit, not channelled in free field, in compliance with ISO 3744.Data detected with the unit that works at following conditions: A 35°C; W12/7°C
Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp
7 67 36 67 36 66 35 62 31 56 25 52 21 45 14 38 7 63 32
9 67 36 67 36 66 35 62 31 56 25 52 21 45 14 38 7 63 32
11 68 37 67 36 67 36 62 31 56 25 53 22 46 15 39 8 64 33
13 72 41 69 38 70 39 64 33 60 29 56 25 49 18 42 11 66 35
17 72 41 69 38 70 39 65 34 60 29 56 25 50 19 43 12 67 36
22 74 43 73 42 73 42 68 37 62 31 58 27 53 22 43 12 70 39
26 75 44 74 43 74 43 68 37 63 32 59 28 52 21 45 14 70 39
32 80 49 79 48 77 46 74 43 67 36 63 32 57 26 50 19 75 44
36 81 50 79 48 78 47 75 44 67 36 63 32 57 26 50 19 75 44
41 81 50 79 48 77 46 74 43 68 37 64 33 58 27 51 20 75 44
Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp
50 66 35 65 34 68 37 69 38 68 37 66 35 63 32 58 27 73 42
60 66 35 65 34 68 37 69 38 68 37 66 35 63 32 58 27 73 42
70 67 36 67 36 69 38 70 39 69 38 67 36 64 33 59 28 74 43
80 68 37 67 36 70 39 71 40 70 39 68 37 65 34 50 19 75 44
90 71 40 70 39 73 42 73 42 72 41 71 40 67 36 62 31 77 46
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
50
MODELOctave bands [dB] Total
[dB(A)]63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
MODELOctave bands [dB] Total
[dB(A)]63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
SOUND LEVELS - MAROON 2 MT /LN
SOUND LEVELS - MAROON 2 MT /LN
Lw: sound power values in free field calculated in compliance with ISO 3744.Lp: sound pressure levels detected at 10 m from the fan side unit, not channelled in free field, in compliance with ISO 3744.Data detected with the unit that works at following conditions: A 35°C; W12/7°C
Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp
8 66 35 65 34 65 34 60 29 55 24 50 19 44 13 37 6 62 31
10 67 36 67 36 66 35 63 32 55 24 53 22 47 16 39 8 63 32
12 70 39 68 37 68 37 63 32 58 27 55 24 48 17 41 10 65 34
16 70 39 71 40 69 38 66 35 60 29 55 24 49 18 40 9 67 36
18 72 41 71 40 71 40 67 36 61 30 57 26 51 20 42 11 68 37
20 73 42 72 41 72 41 67 36 62 31 58 27 51 20 44 13 69 38
23 75 44 74 43 74 43 68 37 64 33 60 29 52 21 46 15 71 40
25 76 45 74 43 74 43 71 40 62 31 60 29 55 24 46 15 71 40
29 77 46 75 44 76 45 71 40 65 34 62 31 55 24 48 17 72 41
34 78 47 77 46 75 44 72 41 66 35 61 30 56 25 49 18 73 42
38 79 48 77 46 76 45 74 43 66 35 61 30 56 25 49 18 74 42
42 79 48 77 46 75 44 72 41 67 36 63 32 57 26 50 19 74 42
Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp
52 65 34 64 33 67 36 68 37 67 36 65 34 62 31 57 26 72 41
62 65 34 64 33 67 36 68 37 67 36 65 34 62 31 57 26 72 41
72 66 35 66 35 68 37 69 38 68 37 66 35 63 32 58 27 73 42
82 67 36 66 35 69 38 70 39 69 38 67 36 64 33 49 18 73 42
92 70 39 69 38 72 41 72 41 71 40 70 39 66 35 61 30 76 45
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
51
MODELOctave bands [dB] Total
[dB(A)]63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
MODELOctave bands [dB] Total
[dB(A)]63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
SOUND LEVELS - MAROON 2 HT /LN
SOUND LEVELS - MAROON 2 HT /LN
Lw: sound power values in free field calculated in compliance with ISO 3744.Lp: sound pressure levels detected at 10 m from the fan side unit, not channelled in free field, in compliance with ISO 3744.Data detected with the unit that works at following conditions: A 35°C; W12/7°C
Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp
7 66 35 66 35 65 34 61 30 55 24 51 20 45 14 37 6 62 31
9 66 35 66 35 65 34 61 30 55 24 51 20 45 14 37 6 62 31
11 67 36 66 35 66 35 61 30 55 24 52 21 46 15 39 8 63 32
13 71 40 68 37 69 38 63 32 59 28 55 24 48 17 42 11 65 34
17 71 40 68 37 69 38 64 33 59 28 55 24 50 19 43 12 66 35
22 73 42 72 41 72 41 67 36 61 30 57 26 52 21 43 12 69 38
26 74 43 73 42 73 42 67 36 62 31 58 27 51 20 44 13 69 38
32 79 48 78 47 76 45 73 42 66 35 62 31 56 25 49 18 74 43
36 80 49 78 47 77 46 74 43 66 35 62 31 56 25 49 18 74 43
41 80 49 78 47 76 45 73 42 67 36 63 32 57 26 50 19 74 43
Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp
50 65 34 64 33 67 36 68 37 67 36 65 34 62 31 57 26 72 41
60 65 34 64 33 67 36 68 37 67 36 65 34 62 31 57 26 72 41
70 66 35 66 35 68 37 69 38 68 37 66 35 63 32 58 27 73 42
80 67 36 66 35 69 38 70 39 69 38 67 36 64 33 49 18 73 42
90 70 39 69 38 72 41 72 41 71 40 70 39 66 35 61 30 76 45
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
52
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
926 376 700
DIMENSIONI - DIMENSIONS
//
/
Codice-Code
1/20 22/11/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
\ \\\\
300
300
600
900
SPAZI DI INSTALLAZIONE / CLEARANCES
Uin
Uout
IMPRONTA A TERRA / FOOTPRINT
RpRp
Pm
GEYSER 2 MT 8-10-12
Ep
700
Cdn
76
926
Es
154 615 154
17,5
Fori\Holes 10
Uin
A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE
B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P
CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION
B
A
SCARICO CONDENSACONDENSATE DRAIN
INGRESSO ACQUA UTILIZZOUSER WATER INLET
Rp USCITA ACQUA UTILIZZOUSER WATER OUTLET
PANNELLO ASPORTABILEREMOVABLE PANEL
1"BSPMELECTRICAL SUPPLY INLET
FLUSSO ARIAAIR FLOW
EpQUADRO ELETTRICO
Cdh ø 18ELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
Uin
Uout1"
BSPM
PmGRIGLIE DI PROTEZIONE
PROTECTIVE METAL MESH
30
331,
525
042
,5
395
17,5
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)8 88 88
10 93 9312 102 102
8 1P 96 9710 1P 101 10212 1P 110 111
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
59
376
29 374 46
SD00147 - A
MAROON 2 MT DIMENSIONAL LAYOUTS
MAROON 2 MT Dimensional layout
8-10-12
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
53
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
926 376 1049
DIMENSIONI - DIMENSIONS
//
/
Codice-Code
1/20 22/11/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
\ \\\\
300
300
600
900
SPAZI DI INSTALLAZIONE / CLEARANCES
Uout
IMPRONTA A TERRA / FOOTPRINT
RpRp
Pm
GEYSER 2 MT 1PS 8-10-12
Ep
1049
Cdn
926
Lh Es
77 690 156
21
Fori\Holes 9
Uin
SCARICO CONDENSACONDENSATE DRAIN
INGRESSO ACQUA UTILIZZOUSER WATER INLET
FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET
Uout1"
BSPM
RpPANNELLO ASPORTABILE
PmGRIGLIE DI PROTEZIONE
PROTECTIVE METAL MESH
REMOVABLE PANEL AIR FLOW
EpQUADRO ELETTRICO
Lh Ø35
Cdh ø 18ELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
Uin1"
BSPMELECTRICAL SUPPLY INLET
FLUSSO ARIA
42
330
21
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)8 141 211
10 146 21612 155 225
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
832
174
Rp
Rp
59
214708
376 46
SD00148 - AMAROON 2 MT 1PS Dimensional layout
8-10-12
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
54
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
926 376 1350
DIMENSIONI - DIMENSIONS
//
/
Codice-Code
1/20 22/11/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
\ \\\\
300
300
600
900
SPAZI DI INSTALLAZIONE / CLEARANCES
Uin
Uout
IMPRONTA A TERRA / FOOTPRINT
Rp
Rp
Pm
GEYSER 2 MT 16-18-20
Ep
1350
Cdn
926
Es
155 621 150
Fori\Holes 10
430
Uin
A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE
B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P
CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION
B
A
SCARICO CONDENSACONDENSATE DRAIN
INGRESSO ACQUA UTILIZZOUSER WATER INLET
Rp PANNELLO ASPORTABILE USCITA ACQUA UTILIZZOREMOVABLE PANEL USER WATER OUTLET
Uout1"
BSPM
PmGRIGLIE DI PROTEZIONE
PROTECTIVE METAL MESH
EpQUADRO ELETTRICO
Cdh ø 18ELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
Uin1"
BSPMELECTRICAL SUPPLY INLET
FLUSSO ARIAAIR FLOW
30
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)16 134 13518 150 15120 165 166
16 1P 146 14718 1P 162 16320 1P 177 178
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
17,5
395
17,5
370
268
230
154
481
376
SD00149 - AMAROON 2 MT Dimensional layout
16-18-20
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
55
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
926 376 1699
DIMENSIONI - DIMENSIONS
//
/
Codice-Code
1/25 23/11/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
\ \\\\
300
300
600
900
SPAZI DI INSTALLAZIONE / CLEARANCES
Uout
IMPRONTA A TERRA / FOOTPRINT
RpRp
Pm
GEYSER 2 MT 1PS 16-18-20
Ep
CdnLh Es
77 690 157
22
Fori\Holes 9
Uin
SCARICO CONDENSACONDENSATE DRAIN
INGRESSO ACQUA UTILIZZOUSER WATER INLET
FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET
INGRESSO ALIMENTAZIONE ELETTRICAUin
1"BSPMELECTRICAL SUPPLY INLET
FLUSSO ARIAREMOVABLE PANEL AIR FLOW
EpQUADRO ELETTRICO
Lh Ø28
Cdh ø 18ELECTRICAL PANEL
Es
Uout1"
BSPM
RpPANNELLO ASPORTABILE
PmGRIGLIE DI PROTEZIONE
PROTECTIVE METAL MESH
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)16 191 26118 207 27720 222 292
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
174
Rp
Rp
154
214708
926
1699
1294
230
330
22
376
22
SD00150 - AMAROON 2 MT 1PS Dimensional layout
16-18-20
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
56
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1105 506 1385
DIMENSIONI - DIMENSIONS
//
/
Codice-Code
1/25 23/11/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
\ \\\\
300
300
600
900
SPAZI DI INSTALLAZIONE / CLEARANCES
Uin
Uout
IMPRONTA A TERRA / FOOTPRINT
Rp
Rp
Pm
GEYSER 2 MT 23-25
Ep13
85
Cdn
1105
Lh Es
87,5 930 87,5
Fori\Holes 12
Uin
A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE
B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P
CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION
A
SCARICO CONDENSACONDENSATE DRAIN
INGRESSO ACQUA UTILIZZOUSER WATER INLET
FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET
Uout
RpPANNELLO ASPORTABILE
PmGRIGLIE DI PROTEZIONE
PROTECTIVE METAL MESH
EpQUADRO ELETTRICO
Lh Ø34
Cdh ø 18ELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
UinELECTRICAL SUPPLY INLET
FLUSSO ARIAREMOVABLE PANEL AIR FLOW
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)23 210 21225 231 233
23 1P 223 22525 1P 244 246
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
2346
0
294
269
52
192
770
128
23
Uout
1" BSPM 1 1\4" BSPM 1" BSPM
UinA
B
B A B
BA
506
570*
* OPZIONALE \ OPTIONAL
SD00151 - AMAROON 2 MT Dimensional layout
23-25
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
57
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
926 376 1699
DIMENSIONI - DIMENSIONS
//
/
Codice-Code
1/25 23/11/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
\ \\\\
300
300
600
900
SPAZI DI INSTALLAZIONE / CLEARANCES
Uout
IMPRONTA A TERRA / FOOTPRINT
RpRp
Pm
GEYSER 2 MT 1PS 16-18-20
Ep
CdnLh Es
77 690 157
22
Fori\Holes 9
Uin
SCARICO CONDENSACONDENSATE DRAIN
INGRESSO ACQUA UTILIZZOUSER WATER INLET
FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET
INGRESSO ALIMENTAZIONE ELETTRICAUin
1"BSPMELECTRICAL SUPPLY INLET
FLUSSO ARIAREMOVABLE PANEL AIR FLOW
EpQUADRO ELETTRICO
Lh Ø28
Cdh ø 18ELECTRICAL PANEL
Es
Uout1"
BSPM
RpPANNELLO ASPORTABILE
PmGRIGLIE DI PROTEZIONE
PROTECTIVE METAL MESH
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)16 191 26118 207 27720 222 292
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
174
Rp
Rp
154
214708
926
1699
1294
230
330
22
376
22
SD00152 - AMAROON 2 MT 1PS Dimensional layout
23-25
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
58
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1306 506 1585
DIMENSIONI - DIMENSIONS
//
/
Codice-Code
1/25 23/11/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
\ \\\\
300
300
600
900
SPAZI DI INSTALLAZIONE / CLEARANCES
Uin
Uout
IMPRONTA A TERRA / FOOTPRINT
Rp
Rp
Pm
GEYSER 2 MT 29-34-38-42
Ep
1585
Cdn
1306
LhEs
88
Uin
A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE
B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P
CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION
A
SCARICO CONDENSACONDENSATE DRAIN
INGRESSO ACQUA UTILIZZOUSER WATER INLET
FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET
1" 1/4 BSPMELECTRICAL SUPPLY INLET
FLUSSO ARIAREMOVABLE PANEL AIR FLOW
EpQUADRO ELETTRICO
Lh Ø34
Cdh ø 18ELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
Uin
Uout1" 1/4 BSPM
RpPANNELLO ASPORTABILE
PmGRIGLIE DI PROTEZIONE
PROTECTIVE METAL MESH
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
2146
0
197,
446
552
870,
2
149
B
BA
506
563
282
Fori\Holes12
22
1130 88
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)29 356 35834 365 36738 385 38742 395 398
29 1P 371 37334 1P 380 38238 1P 400 40242 1P 410 413
*
* OPZIONALE \ OPTIONAL
SD00153 - AMAROON 2 MT Dimensional layout
29-34-38-42
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
59
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1306 506 2050
DIMENSIONI - DIMENSIONS
//
/
Codice-Code
1/25 23/11/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
\ \\\\
300
300
600
900
SPAZI DI INSTALLAZIONE / CLEARANCES
Uout
IMPRONTA A TERRA / FOOTPRINT
RpRp
Pm
GEYSER 2 MT 1PS 29-34-38-42
Ep
CdnLh
Fori\Holes 9
Uin
SCARICO CONDENSACONDENSATE DRAIN
INGRESSO ACQUA UTILIZZOUSER WATER INLET
FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET
Uout1" 1/4BSPM
RpPANNELLO ASPORTABILE
PmGRIGLIE DI PROTEZIONE
PROTECTIVE METAL MESH
EpQUADRO ELETTRICO
Lh Ø34
Cdh ø 22ELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
Uin1" 1/4BSPMELECTRICAL SUPPLY INLET
FLUSSO ARIAREMOVABLE PANEL AIR FLOW
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
RpRp
282
386917
1306
2050
506
563
Es
232
1766
52
204,5
28,5
84028,5
204,5
23,8
460
22,2
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)29 436 56634 445 57538 465 59542 475 605
*
* OPZIONALE \ OPTIONAL
SD00154 - AMAROON 2 MT 1PS Dimensional layout
29-34-38-42
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
60
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
926 376 1350
DIMENSIONI - DIMENSIONS
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
//
/
Codice-Code
1/20 23/11/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE GEYSER 2 MT HWS 8-20
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
SPAZI DI INSTALLAZIONE / CLEARANCES
B Uin
A Uin
Uout
1350
926
A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE
B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P
Ep
Rp
Cdh
Pm
300
300
600
900
430
376
Rp
154
48
IMPRONTA A TERRA / FOOTPRINT
155616155
395
430
10FORI/HOLES
CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION
481
Rin
Rout
INGRESSO ACQUA UTILIZZOUSER WATER INLET
USCITA ACQUA UTILIZZOUSER WATER OUTLET
FORI SOLLEVAMENTO INGRESSO ACQUA SANITARIOLIFTING HOLES RECOVERY WATER INLET
USCITA ACQUA SANITARIORECOVERY WATER OUTLET
SCARICO CONDENSACONDENSATE DRAIN
EpQUADRO ELETTRICO
Uin1"
BSPMELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
Uout1"
BSPMELECTRICAL SUPPLY INLET
Lh Ø28 Rin1"
BSPM
RpPANNELLO ASPORTABILE
Rout1"
BSPMREMOVABLE PANEL
Cdh ø 18
PmGRIGLIE DI PROTEZIONE FLUSSO ARIA
PROTECTIVE METAL MESH AIR FLOW
\ \ \ \\
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)8 129 130
10 133 13412 137 13816 141 14218 158 15920 174 175
8 1P 137 13810 1P 141 14212 1P 145 14616 1P 153 15418 1P 170 17120 1P 186 187
548
269
52
178,
526
9
151,5
30
Es
SD00155 - AMAROON 2 MT/HWS Dimensional layout
8-20
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
61
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
926 376 1699
DIMENSIONI - DIMENSIONS
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)8 182 252
10 186 25612 190 26016 198 26818 215 28520 231 301
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
//
/
Codice-Code
1/20 23/11/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE GEYSER 2 MT HWS 1PS 8-20
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
SPAZI DI INSTALLAZIONE / CLEARANCES
Uin
Uout
1699
926
Ep
Rp
Cdh
Pm
30030
0
600
900
396
376
Rp
Lh
IMPRONTA A TERRA / FOOTPRINT
158
330
376
Rin
Rout
INGRESSO ACQUA UTILIZZOUSER WATER INLET
USCITA ACQUA UTILIZZOUSER WATER OUTLET
FORI SOLLEVAMENTO INGRESSO ACQUA RECUPEROLIFTING HOLES RECOVERY WATER INLET
USCITA ACQUA RECUPERORECOVERY WATER OUTLET
SCARICO CONDENSACONDENSATE DRAIN
EpQUADRO ELETTRICO
Uin1"
BSPMELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
Uout1"
BSPMELECTRICAL SUPPLY INLET
Lh Ø28 Rin1"
BSPM
RpPANNELLO ASPORTABILE
Rout1"
BSPMREMOVABLE PANEL
Cdh ø 18
PmGRIGLIE DI PROTEZIONE FLUSSO ARIA
PROTECTIVE METAL MESH AIR FLOW
\ \ \ \\
78
5226
954
865
4,3
176
152
Lh
Rp
213709
48
Fori\Holes9690
Es
SD00156 - AMAROON 2 MT/HWS 1PS Dimensional layout
8-20
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
62
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1105 506 1385
DIMENSIONI - DIMENSIONS
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)23 220 22225 242 244
23 1P 233 23525 1P 255 257
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
//
/
Codice-Code
1/20 23/11/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE GEYSER 2 MT HWS 23-25
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
SPAZI DI INSTALLAZIONE / CLEARANCES
B Uin
A Uin
Uout
1385
1105
A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE
B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P
Rp
Cdh
Pm
300
300
600
900
567
506
Rp
5852
IMPRONTA A TERRA / FOOTPRINT
87,5
460
506
12FORI/HOLES
CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION
Rin
Rout
INGRESSO ACQUA UTILIZZOUSER WATER INLET
USCITA ACQUA UTILIZZOUSER WATER OUTLET
FORI SOLLEVAMENTO INGRESSO ACQUA RECUPEROLIFTING HOLES RECOVERY WATER INLET
USCITA ACQUA RECUPERORECOVERY WATER OUTLET
SCARICO CONDENSACONDENSATE DRAIN
Cdh ø 20
PmGRIGLIE DI PROTEZIONE FLUSSO ARIA
PROTECTIVE METAL MESH AIR FLOW
Lh Ø34 Rin1" 1/4BSPM
RpPANNELLO ASPORTABILE
Rout1" 1/4BSPMREMOVABLE PANEL
EpQUADRO ELETTRICO
Uin1" 1/4BSPMELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
Uout1" 1/4BSPMELECTRICAL SUPPLY INLET
/ / / //
930 87,5
192
269
294
770
Ep
128
LhLh
* OPZIONALE / OPTIONAL
*Es
SD00157 - AMAROON 2 MT/HWS Dimensional layout
23-25
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
63
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1105 506 1850
DIMENSIONI - DIMENSIONS
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)23 298 42825 320 450
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
//
/
Codice-Code
1/25 23/11/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE GEYSER 2 MT HWS 1PS 23-25
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
SPAZI DI INSTALLAZIONE / CLEARANCES1:20
Uin
Uout
1850
1105
Rp
Cdh
Pm
300
300
600
900
567
506
Rp
5852
IMPRONTA A TERRA / FOOTPRINT
460
506
9FORI/HOLES
Rin
Rout
INGRESSO ACQUA UTILIZZOUSER WATER INLET
USCITA ACQUA UTILIZZOUSER WATER OUTLET
FORI SOLLEVAMENTO INGRESSO ACQUA RECUPEROLIFTING HOLES RECOVERY WATER INLET
USCITA ACQUA RECUPERORECOVERY WATER OUTLET
SCARICO CONDENSACONDENSATE DRAIN
EpQUADRO ELETTRICO
Uin1" 1/4BSPMELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
Uout1" 1/4BSPMELECTRICAL SUPPLY INLET
Lh Ø34 Rin1" 1/4BSPM
RpPANNELLO ASPORTABILE
Rout1" 1/4BSPMREMOVABLE PANEL
Cdh ø 22
PmGRIGLIE DI PROTEZIONE FLUSSO ARIA
PROTECTIVE METAL MESH AIR FLOW
/ / / //
269
294Ep
128
LhLh 242
1002
*
* OPZIONALE / OPTIONAL
Rp Rp
232
862
28,559 840
28,5149
Es
Rp
SD00158 - AMAROON 2 MT/HWS 1PS Dimensional layout
23-25
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
64
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1306 506 1585
DIMENSIONI - DIMENSIONS
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
//
/
Codice-Code
1/25 23/11/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE GEYSER 2 MT HWS 29-34-38-42
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
SPAZI DI INSTALLAZIONE / CLEARANCES
B Uin
A Uin
Uout
1585
1306
A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE
B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P
Rp
Cdh
Pm
300 300
600
900
561
506
Rp
IMPRONTA A TERRA / FOOTPRINT
88
12FORI/HOLES
CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION
Rin
Rout
INGRESSO ACQUA UTILIZZOUSER WATER INLET
USCITA ACQUA UTILIZZOUSER WATER OUTLET
FORI SOLLEVAMENTO INGRESSO ACQUA RECUPEROLIFTING HOLES RECOVERY WATER INLET
USCITA ACQUA RECUPERORECOVERY WATER OUTLET
SCARICO CONDENSACONDENSATE DRAIN
Cdh ø 20
PmGRIGLIE DI PROTEZIONE FLUSSO ARIA
PROTECTIVE METAL MESH AIR FLOW
Lh Ø34 Rin1" 1/4BSPM
RpPANNELLO ASPORTABILE
Rout1" 1/4BSPMREMOVABLE PANEL
EpQUADRO ELETTRICO
Uin1" 1/4BSPMELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
Uout1" 1/4BSPMELECTRICAL SUPPLY INLET
\ \ \ \\
Ep
Lh
110
282
5246
619
787
01130 88
460
506
148
*
* OPZIONALE / OPTIONAL
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)29 368 37034 378 38038 399 40142 410 413
29 1P 383 38534 1P 393 39538 1P 414 41642 1P 425 428
LhEs
SD00159 - AMAROON 2 MT/HWS Dimensional layout
29-34-38-42
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
65
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1306 506 2050
DIMENSIONI - DIMENSIONS
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
//
/
Codice-Code
1/25 23/11/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE GEYSER 2 MT HWS 1PS 29-34-38-42
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
SPAZI DI INSTALLAZIONE / CLEARANCES
Uin
Uout
2050
1306
Rp
Cdh
Pm
300 300
600
900
561
506
Rp
IMPRONTA A TERRA / FOOTPRINT
204,5
Rin
Rout
INGRESSO ACQUA UTILIZZOUSER WATER INLET
USCITA ACQUA UTILIZZOUSER WATER OUTLET
FORI SOLLEVAMENTO INGRESSO ACQUA RECUPEROLIFTING HOLES RECOVERY WATER INLET
USCITA ACQUA RECUPERORECOVERY WATER OUTLET
SCARICO CONDENSACONDENSATE DRAIN
EpQUADRO ELETTRICO
Uin1" 1/4BSPMELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
Uout1" 1/4BSPMELECTRICAL SUPPLY INLET
Lh Ø34 Rin1" 1/4BSPM
RpPANNELLO ASPORTABILE
Rout1" 1/4BSPMREMOVABLE PANEL
Cdh ø 22
PmGRIGLIE DI PROTEZIONE FLUSSO ARIA
PROTECTIVE METAL MESH AIR FLOW
\ \ \ \\
Ep
LhLh
110
5246
619
7
460
506
1102
232
*
* OPZIONALE / OPTIONAL
148
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)29 448 57834 458 58838 479 60942 490 620
Fori\Holes9
28,5840
28,5204,5
RpRp
386917
Rp
Es
SD00160 - AMAROON 2 MT/HWS 1PS Dimensional layout
29-34-38-42
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
66ASD00165
Visto-Checked byDenominazione-Denomination
Data-DateRev. Dis.-Draftsman Descrizione revisione-Revision descriptionCodice-Code Disegno-Drawing Rev.
Dis.-DraftsmanData-DateScala-Scale Visto-Checked by Foglio diSheet N. of
Sost. il dis.-Replace draw. Sost. dal dis.-Replaced by draw.
Materiale-Material Trattamento-Treatment
Peso-Weight [kg]
SCHEMA DIMENSIONALE / DIMENSIONAL DRAWINGGEYSER 2 MT 52-62-72-82-92 SD00165
P. Frigolorpe 2
/ /
1N. Bettio
/Spessore-Thickness
/Colore vernice-Painted colour
/ /
12/12/20121/30
Codice-Code
/
/ / / //
SPAZI DI INSTALLAZIONE / CLEARANCES
1000
1000
00
1000
0
1000
0Cdh
Rp
Rp
Ep
Ep
2108 23
90
1203
167
519
251,5
371,517
9Lh Lh1403
Rp Cdh
Ep
SCARICO CONDENSA VERSIONE HPCONDENSATE DRAIN HP VERSION
INGRESSO ACQUA UTILIZZOUSER WATER INLET
USCITA ACQUA UTILIZZOUSER WATER OUTLET
Uout 2" BSPM
ø20
EpQUADRO ELETTRICO
Es
ELECTRICAL PANEL
Lh
INGRESSO ALIMENTAZIONE ELETTRICAELECTRICAL SUPPLY INLET
Uin 2" BSPMLIFTING HOLES
RpPANNELLO ASPORTABILE
REMOVABLE PANEL
Cdh
FORI DI SOLLEVAMENTO
*OPZIONALEOPTIONAL
PmGRIGLIE DI PROTEZIONE
PROTECTIVE METAL MESH
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1403 1203 2390
DIMENSIONI / DIMENSIONS
PmPm
Es
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)
52 575 57862 592 59572 602 60582 620 62392 631 634
MOD. 1P 16
MOD. 2P 32
Δ PESOΔ WEIGHT
Δ PESOΔ WEIGHT
Uout
Uin
A B C
A
A MODELLO STANDARD STANDARD MODEL
B MODELLO 1P 1P MODEL
C MODELLO 2P 2P MODEL
CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTIONS
**
Uin B C
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
SD00165 - AMAROON 2 MT Dimensional layout
52-62-72-82-92
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
67ASD00165
Visto-Checked byDenominazione-Denomination
Data-DateRev. Dis.-Draftsman Descrizione revisione-Revision descriptionCodice-Code Disegno-Drawing Rev.
Dis.-DraftsmanData-DateScala-Scale Visto-Checked by Foglio diSheet N. of
Sost. il dis.-Replace draw. Sost. dal dis.-Replaced by draw.
Materiale-Material Trattamento-Treatment
Peso-Weight [kg]
SCHEMA DIMENSIONALE / DIMENSIONAL DRAWINGGEYSER 2 MT 52-62-72-82-92 SD00165
P. Frigolorpe 2
/ /
2N. Bettio
/Spessore-Thickness
/Colore vernice-Painted colour
/ /
12/12/20121/12,5
Codice-Code
/
/ / / //
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
IMPRONTA A TERRA / FOOTPRINT
FORI DI FISSAGGIOFIXING HOLES
Fh Ø18
G..PUNTI DI APPOGGIO ANTIVIBRANTIVIBRATION DAMPER FOOT HOLDS
24 1160 24
124
1160
124
1408
1208
G1 G2
G4G3
G1(kg)
G2(kg)
G3(kg)
G4(kg)
52 156 162 150 11062 161 167 155 11372 163 169 157 11582 168 174 162 11892 171 178 165 120
SD00165 - AMAROON 2 MT Dimensional layout
52-62-72-82-92
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
68ASD00166
Visto-Checked byDenominazione-Denomination
Data-DateRev. Dis.-Draftsman Descrizione revisione-Revision descriptionCodice-Code Disegno-Drawing Rev.
Dis.-DraftsmanData-DateScala-Scale Visto-Checked by Foglio diSheet N. of
Sost. il dis.-Replace draw. Sost. dal dis.-Replaced by draw.
Materiale-Material Trattamento-Treatment
Peso-Weight [kg]
SCHEMA DIMENSIONALE / DIMENSIONAL DRAWINGGEYSER 2 MT HWS 52-62-72-82-92 SD00166
P. Frigolorpe 2
/ /
1N. Bettio
/Spessore-Thickness
/Colore vernice-Painted colour
/ /
28/11/20121/30
Codice-Code
/
/ / / //
SPAZI DI INSTALLAZIONE / CLEARANCES
1000
1000
00
1000
0
1000
0Cdh
Rp
Rp
Ep
Ep
2108 23
90
1203 167
519
251,5
371,5
179Lh Lh
1403
Rp Cdh
Ep
SCARICO CONDENSA VERSIONE HPCONDENSATE DRAIN HP VERSION
INGRESSO ACQUA UTILIZZOUSER WATER INLET
USCITA ACQUA UTILIZZOUSER WATER OUTLET
INGRESSO ACQUA RECUPERORECOVERY WATER INLET
USCITA ACQUA RECUPERORECOVERY WATER OUTLET
2" BSPM
EpQUADRO ELETTRICO
Es
ELECTRICAL PANEL
Lh
INGRESSO ALIMENTAZIONE ELETTRICAELECTRICAL SUPPLY INLET
GRIGLIE DI PROTEZIONEPROTECTIVE METAL MESH
Uout 2" BSPMLIFTING HOLES
Cdh
Uin
FORI DI SOLLEVAMENTO
Rin 2" BSPM
ø20
Rout 2" BSPMRpPANNELLO ASPORTABILE
REMOVABLE PANEL
Pm
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1403 1203 2390
DIMENSIONI / DIMENSIONS
PmOPZIONALE / OPTIONAL
PmOPZIONALE / OPTIONAL
Es
Uout
Uin
A B
A
A MODELLO STANDARD STANDARD MODELB MODELLO 1P - 2P 1P - 2P MODELC MODELLO 1R 1R MODEL
CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTIONS
Uin B
390
332
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)
52 575 57862 592 59572 602 60582 620 62392 631 634
Δ PESOΔ WEIGHT
MOD. 1R 2P 49
Δ PESOΔ WEIGHT
MOD. 1R 17
Δ PESOΔ WEIGHT
MOD. 1R 1P 33
Δ PESOΔ WEIGHT
MOD. 1P 16
Δ PESOΔ WEIGHT
MOD. 2P 32
Rout A C
Rin C
Rin A
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
SD00166 - AMAROON 2 MT/HWS Dimensional layout
52-62-72-82-92
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
69ASD00166
Visto-Checked byDenominazione-Denomination
Data-DateRev. Dis.-Draftsman Descrizione revisione-Revision descriptionCodice-Code Disegno-Drawing Rev.
Dis.-DraftsmanData-DateScala-Scale Visto-Checked by Foglio diSheet N. of
Sost. il dis.-Replace draw. Sost. dal dis.-Replaced by draw.
Materiale-Material Trattamento-Treatment
Peso-Weight [kg]
SCHEMA DIMENSIONALE / DIMENSIONAL DRAWINGGEYSER 2 MT HWS 52-62-72-82-92 SD00166
P. Frigolorpe 2
/ /
2N. Bettio
/Spessore-Thickness
/Colore vernice-Painted colour
/ /
28/11/20121/12,5
Codice-Code
/
/ / / //
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
IMPRONTA A TERRA / FOOTPRINT
FORI DI FISSAGGIOFIXING HOLES
Fh Ø18
G..PUNTI DI APPOGGIO ANTIVIBRANTIVIBRATION DAMPER FOOT HOLDS
24 1160 24
124
1160
124
1408
1208
G1 G2
G4G3
G1(kg)
G2(kg)
G3(kg)
G4(kg)
52 156 162 150 11062 161 167 155 11372 163 169 157 11582 168 174 162 11892 171 178 165 120
SD00166 - AMAROON 2 MT/HWS Dimensional layout
52-62-72-82-92
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
70
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1105 506 982
DIMENSIONI - DIMENSIONS
//
/
Codice-Code
1/20 12/12/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
/DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
\ \\\\
300
600
900
300
SPAZI DI INSTALLAZIONE / CLEARANCES
IMPRONTA A TERRA / FOOTPRINT
RpRp
Pm
GEYSER 27-9-11-13-17
Ep
982
Cdn
1105
Lp
86 930 86
21
Uin
A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE
B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P
CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION
B
A
460
21
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
506
Lp
Es
12
FORI MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)
7 107 108
9 111 112
11 117 118
13 123 124
17 132 133
7 1P 116 117
9 1P 120 121
11 1P 126 127
13 1P 132 133
17 1P 141 142
Uout
Uin
SCARICO CONDENSACONDENSATE DRAIN
INGRESSO ACQUA UTILIZZOUSER WATER INLET
USCITA ACQUA UTILIZZOUSER WATER OUTLET
Lp
PANNELLO ASPORTABILEREMOVABLE PANEL
1"BSPMELECTRICAL SUPPLY INLET
PUNTO DI SOLLEVAMENTO
Rp
LIFTING POINT
EpQUADRO ELETTRICO
Cdh ø 22ELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
Uin
FLUSSO ARIAAIR FLOW
Uout1"
BSPM
PmGRIGLIE DI PROTEZIONE
PROTECTIVE METAL MESH
276
222
660
269
53
180
586
SD00145 - A
MAROON 2 HT DIMENSIONAL LAYOUTS
MAROON 2 HT Dimensional layout
7-9-11-13-17
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
71
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1105 506 1447
DIMENSIONI - DIMENSIONS
//
/
Codice-Code
1/25 12/12/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
/DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
\ \\\\
300
300
600
900
SPAZI DI INSTALLAZIONE / CLEARANCES
IMPRONTA A TERRA / FOOTPRINT
RpRp
Pm
GEYSER 2 1PS 7-9-11-13-17
Ep14
47
Cdn
1105
Lh
Es
5928,5
Fori\Holes 9
Uin
SCARICO CONDENSACONDENSATE DRAIN
INGRESSO ACQUA UTILIZZOUSER WATER INLET
FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET
ø 22ELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
Uin1"
BSPMELECTRICAL SUPPLY INLET
GRIGLIE DI PROTEZIONEPROTECTIVE METAL MESH
EpQUADRO ELETTRICO
Lh Ø35
Cdh
REMOVABLE PANELFLUSSO ARIA
AIR FLOW
Uout1"
BSPM
RpPANNELLO ASPORTABILE
Pm
460
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
232
Rp
Rp
242862
SD00146
506
2222
84028,5
149
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)7 181 3119 185 315
11 191 32113 197 32717 206 336
Uout
1162
53
182
586
SD00146 - AMAROON 2 HT 1PS Dimensional layout
7-9-11-13-17
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
72
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1105 506 1385
DIMENSIONI - DIMENSIONS
//
/
Codice-Code
1/25 12/12/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
\ \\\\
300
300
600
900
SPAZI DI INSTALLAZIONE / CLEARANCES
Uin
Uout
IMPRONTA A TERRA / FOOTPRINT
Rp
Rp
Pm
GEYSER 2 22-26
Ep13
85
Cdn
1105
Lh Es
87,5 930 87,5
Fori\Holes 12
Uin
A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE
B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P
CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION
A
SCARICO CONDENSACONDENSATE DRAIN
INGRESSO ACQUA UTILIZZOUSER WATER INLET
FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET
ELECTRICAL SUPPLY INLET
FLUSSO ARIAREMOVABLE PANEL AIR FLOW
EpQUADRO ELETTRICO
Lh Ø34
Cdh ø 22ELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
Uin
Uout
RpPANNELLO ASPORTABILE
PmGRIGLIE DI PROTEZIONE
PROTECTIVE METAL MESH
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)22 230 23226 249 251
22 1P 242 24426 1P 261 263
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
2346
0
294
269
52
192
770
128
23
Uout
1" BSPM 1 1\4" BSPM 1" BSPM
UinA
B
B A B
BA
506
*
* OPZIONALE \ OPTIONAL
570
SD00167 - AMAROON 2 HT Dimensional layout
22-26
SD00167 - A
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
73
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1105 506 1850
DIMENSIONI - DIMENSIONS
//
/
Codice-Code
1/25 12/12/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
\ \\\\
300
300
600
900
SPAZI DI INSTALLAZIONE / CLEARANCES
Uout
IMPRONTA A TERRA / FOOTPRINT
Rp Rp
Pm
GEYSER 2 1PS 22-26
Ep
Cdn
Lh
Es
Fori\Holes 9
Uin
SCARICO CONDENSACONDENSATE DRAIN
INGRESSO ACQUA UTILIZZOUSER WATER INLET
FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET
INGRESSO ALIMENTAZIONE ELETTRICAUin
1" 1/4BSPMELECTRICAL SUPPLY INLET
FLUSSO ARIAREMOVABLE PANEL AIR FLOW
EpQUADRO ELETTRICO
Lh Ø34
Cdh ø 22ELECTRICAL PANEL
Es
Uout1"
BSPM
RpPANNELLO ASPORTABILE
PmGRIGLIE DI PROTEZIONE
PROTECTIVE METAL MESH
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)22 307 43726 326 456
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
RpRp
192
242862
1105
1850
506
570
5315
6523
0
58 28,5 840 28,5 148
460
2121
*
* OPZIONALE \ OPTIONAL
SD00168 - AMAROON 2 HT 1PS Dimensional layout
22-26
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
74
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1306 506 1585
DIMENSIONI - DIMENSIONS
//
/
Codice-Code
1/30 12/12/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
\ \\\\
300
300
600
900
SPAZI DI INSTALLAZIONE / CLEARANCES
Uin
Uout
IMPRONTA A TERRA / FOOTPRINT
Rp
Rp
Pm
GEYSER 2 32-36-41
Ep
1585
Cdn
1306
LhEs
88
Uin
A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE
B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P
CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION
A
SCARICO CONDENSACONDENSATE DRAIN
INGRESSO ACQUA UTILIZZOUSER WATER INLET
FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET
PmGRIGLIE DI PROTEZIONE
PROTECTIVE METAL MESH
ø 22ELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
Uin
Uout1" 1/4 BSPM
RpPANNELLO ASPORTABILE
1" 1/4 BSPMELECTRICAL SUPPLY INLET
FLUSSO ARIAREMOVABLE PANEL AIR FLOW
EpQUADRO ELETTRICO
Lh Ø34
Cdh
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
2146
0
197
465
5287
0
149
B
BA
506
563
282
Fori\Holes12
21
1130 88
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)32 383 38536 402 40541 413 416
32 1P 398 40036 1P 417 42041 1P 428 431
*
* OPZIONALE \ OPTIONAL
SD00169 - AMAROON 2 HT Dimensional layout
32-36-41
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
75
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1306 506 2050
DIMENSIONI - DIMENSIONS
//
/
Codice-Code
1/25 12/12/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
\ \\\\
300
300
600
900
SPAZI DI INSTALLAZIONE / CLEARANCES
Uout
IMPRONTA A TERRA / FOOTPRINT
RpRp
Pm
GEYSER 2 1PS 32-36-41
Ep
CdnLh
Fori\Holes 9
Uin
SCARICO CONDENSACONDENSATE DRAIN
INGRESSO ACQUA UTILIZZOUSER WATER INLET
FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET
Uout1" 1/4BSPM
RpPANNELLO ASPORTABILE
PmGRIGLIE DI PROTEZIONE
PROTECTIVE METAL MESH
EpQUADRO ELETTRICO
Lh Ø34
Cdh ø 22ELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
Uin1" 1/4BSPMELECTRICAL SUPPLY INLET
FLUSSO ARIAREMOVABLE PANEL AIR FLOW
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
RpRp
282
386917
1306
2050
506
563
Es
232
1766
52
204
28,5
84028,5
204
2246
022
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)32 463 59336 482 61241 493 623
*
* OPZIONALE \ OPTIONAL
SD00170 - AMAROON 2 HT 1PS Dimensional layout
32-36-41
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
76
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1105 506 982
DIMENSIONI - DIMENSIONS
//
/
Codice-Code
1/20 12/12/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
/DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
\ \\\\
300
600
900
300
SPAZI DI INSTALLAZIONE / CLEARANCES
Rin
Rout
IMPRONTA A TERRA / FOOTPRINT
RpRp
Pm
GEYSER 2 HWS 7-9-11-13-17
Ep
982
Cdn
1105
Lp
86 930 86
21
Uin
A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE
B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P
CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION
B
A
460
21
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
506 66
5326
9
Lp
Es
12
FORI MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)
7 111 112
9 116 117
11 123 124
13 130 131
17 141 142
7 1P 120 121
9 1P 125 126
11 1P 132 133
13 1P 139 140
17 1P 150 151
660
Uout
Uin
SCARICO CONDENSACONDENSATE DRAIN
INGRESSO ACQUA UTILIZZOUSER WATER INLET
USCITA ACQUA UTILIZZOUSER WATER OUTLET
INGRESSO ACQUA RECUPERORECOVERY WATER INLET
USCITA ACQUA RECUPERORECOVERY WATER OUTLET
FLUSSO ARIAAIR FLOW
1" 1\4 BSPM
1" 1\4 BSPM
Uout1"
BSPM
PmGRIGLIE DI PROTEZIONE
PROTECTIVE METAL MESH
RoutLIFTING POINT
EpQUADRO ELETTRICO
Cdh ø 22ELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
Uin
Lp
PANNELLO ASPORTABILEREMOVABLE PANEL
1"BSPMELECTRICAL SUPPLY INLET
Rin
PUNTO DI SOLLEVAMENTO
Rp
115
276
222
586
SD00171 - AMAROON 2 HT/HWS Dimensional layout
7-9-11-13-17
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
77
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1105 506 1447
DIMENSIONI - DIMENSIONS
//
/
Codice-Code
1/25 12/12/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
/DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
\ \\\\
300
300
600
900
SPAZI DI INSTALLAZIONE / CLEARANCES
Rout
IMPRONTA A TERRA / FOOTPRINT
RpRp
Pm
GEYSER 2 HWS 1PS 7-9-11-13-17
Ep14
47
Cdn
1105
Lh
Es
5928,5
Fori\Holes 9
Uin
SCARICO CONDENSACONDENSATE DRAIN
INGRESSO ACQUA UTILIZZOUSER WATER INLET
FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET
INGRESSO ACQUA RECUPERORECOVERY WATER INLET
USCITA ACQUA RECUPERORECOVERY WATER OUTLET
FLUSSO ARIAAIR FLOW
1" 1/4BSPM
1" 1/4BSPM
Uout1"
BSPM
RpPANNELLO ASPORTABILE
PmGRIGLIE DI PROTEZIONE
PROTECTIVE METAL MESHRout
Rin
EpQUADRO ELETTRICO
Lh Ø35
Cdh ø 22ELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
Uin1"
BSPMELECTRICAL SUPPLY INLET
REMOVABLE PANEL
53
460
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
232
Rp
Rp
242862
SD00172
50666
2222
84028,5
149
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)7 185 3159 190 320
11 197 32713 204 33417 215 345
Uout
Rin
115
269
892
SD00172 - AMAROON 2 HT/HWS 1PS Dimensional layout
7-9-11-13-17
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
78
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1105 506 1385
DIMENSIONI - DIMENSIONS
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)22 241 24326 262 264
22 1P 253 25526 1P 274 276
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
//
/
Codice-Code
1/20 12/12/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE GEYSER 2 HWS 22-26
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
SPAZI DI INSTALLAZIONE / CLEARANCES
B Uin
A Uin
Uout
1385
1105
A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE
B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P
Rp
Cdh
Pm
300
300
600
900
567
506
Rp
5852
IMPRONTA A TERRA / FOOTPRINT
88
460
506
12FORI/HOLES
CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION
Rin
Rout
INGRESSO ACQUA UTILIZZOUSER WATER INLET
USCITA ACQUA UTILIZZOUSER WATER OUTLET
FORI SOLLEVAMENTO INGRESSO ACQUA RECUPEROLIFTING HOLES RECOVERY WATER INLET
USCITA ACQUA RECUPERORECOVERY WATER OUTLET
SCARICO CONDENSACONDENSATE DRAIN
Cdh ø 20
PmGRIGLIE DI PROTEZIONE FLUSSO ARIA
PROTECTIVE METAL MESH AIR FLOW
Lh Ø34 Rin1" 1/4BSPM
RpPANNELLO ASPORTABILE
Rout1" 1/4BSPMREMOVABLE PANEL
EpQUADRO ELETTRICO
Uin1" 1/4BSPMELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
Uout1" 1/4BSPMELECTRICAL SUPPLY INLET
/ / / //
930 88
192
269
294
770
Ep
128
LhLh
* OPZIONALE / OPTIONAL
*Es
SD00173 - AMAROON 2 HT/HWS Dimensional layout
22-26
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
79
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1105 506 1850
DIMENSIONI - DIMENSIONS
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)22 318 44826 339 469
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
//
/
Codice-Code
1/25 12/12/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE GEYSER 2 HWS 1PS 22-26
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
SPAZI DI INSTALLAZIONE / CLEARANCES1:20
Uin
Uout
1850
1105
Rp
Cdh
Pm
300
300
600
900
567
506
Rp
5852
IMPRONTA A TERRA / FOOTPRINT
460
506
9FORI/HOLES
Rin
Rout
INGRESSO ACQUA UTILIZZOUSER WATER INLET
USCITA ACQUA UTILIZZOUSER WATER OUTLET
FORI SOLLEVAMENTO INGRESSO ACQUA RECUPEROLIFTING HOLES RECOVERY WATER INLET
USCITA ACQUA RECUPERORECOVERY WATER OUTLET
SCARICO CONDENSACONDENSATE DRAIN
EpQUADRO ELETTRICO
Uin1" 1/4BSPMELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
Uout1" 1/4BSPMELECTRICAL SUPPLY INLET
Lh Ø34 Rin1" 1/4BSPM
RpPANNELLO ASPORTABILE
Rout1" 1/4BSPMREMOVABLE PANEL
Cdh ø 22
PmGRIGLIE DI PROTEZIONE FLUSSO ARIA
PROTECTIVE METAL MESH AIR FLOW
/ / / //
269
294Ep
128
LhLh 242
1002
*
* OPZIONALE / OPTIONAL
Rp Rp
232
862
28,559 840
28,5149
Es
Rp
SD00174 - AMAROON 2 HT/HWS 1PS Dimensional layout
22-26
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
80
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1306 506 1585
DIMENSIONI - DIMENSIONS
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
//
/
Codice-Code
1/25 12/12/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE GEYSER 2 HWS 32-36-41
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
SPAZI DI INSTALLAZIONE / CLEARANCES
B Uin
A Uin
Uout
1585
1306
A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE
B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P
Rp
Cdh
Pm
300 300
600
900
561
506
Rp
IMPRONTA A TERRA / FOOTPRINT
88
12FORI/HOLES
CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION
Rin
Rout
INGRESSO ACQUA UTILIZZOUSER WATER INLET
USCITA ACQUA UTILIZZOUSER WATER OUTLET
FORI SOLLEVAMENTO INGRESSO ACQUA RECUPEROLIFTING HOLES RECOVERY WATER INLET
USCITA ACQUA RECUPERORECOVERY WATER OUTLET
SCARICO CONDENSACONDENSATE DRAIN
Cdh ø 20
PmGRIGLIE DI PROTEZIONE FLUSSO ARIA
PROTECTIVE METAL MESH AIR FLOW
Lh Ø34 Rin1" 1/4BSPM
RpPANNELLO ASPORTABILE
Rout1" 1/4BSPMREMOVABLE PANEL
EpQUADRO ELETTRICO
Uin1" 1/4BSPMELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
Uout1" 1/4BSPMELECTRICAL SUPPLY INLET
\ \ \ \\
Ep
Lh
110
282
5246
619
787
01130 88
460
506
148
*
* OPZIONALE / OPTIONAL
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)32 398 40036 419 42241 432 435
32 1P 413 41536 1P 434 43741 1P 447 450
LhEs
SD00175 - AMAROON 2 HT/HWS Dimensional layout
32-36-41
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
81
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1306 506 2050
DIMENSIONI - DIMENSIONS
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
//
/
Codice-Code
1/25 12/12/2012
//Colore vernice-Painted colour
/Spessore-Thickness
/
N. Bettio 1 1F. Sanavia
-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE GEYSER 2 HWS 1PS 32-36-41
Peso-Weight [kg]
Trattamento-TreatmentMateriale-Material
Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman
Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date
Denominazione-DenominationVisto-Checked by
SPAZI DI INSTALLAZIONE / CLEARANCES
Uin
Uout
2050
1306
Rp
Cdh
Pm
300 300
600
900
561
506
Rp
IMPRONTA A TERRA / FOOTPRINT
204
Rin
Rout
INGRESSO ACQUA UTILIZZOUSER WATER INLET
USCITA ACQUA UTILIZZOUSER WATER OUTLET
FORI SOLLEVAMENTO INGRESSO ACQUA RECUPEROLIFTING HOLES RECOVERY WATER INLET
USCITA ACQUA RECUPERORECOVERY WATER OUTLET
SCARICO CONDENSACONDENSATE DRAIN
EpQUADRO ELETTRICO
Uin1" 1/4BSPMELECTRICAL PANEL
EsINGRESSO ALIMENTAZIONE ELETTRICA
Uout1" 1/4BSPMELECTRICAL SUPPLY INLET
Lh Ø34 Rin1" 1/4BSPM
RpPANNELLO ASPORTABILE
Rout1" 1/4BSPMREMOVABLE PANEL
Cdh ø 22
PmGRIGLIE DI PROTEZIONE FLUSSO ARIA
PROTECTIVE METAL MESH AIR FLOW
\ \ \ \\
Ep
LhLh
110
5246
619
7
460
506
1102
232
*
* OPZIONALE / OPTIONAL
148
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)32 478 60836 499 62941 512 642
Fori\Holes9
28,5840
28,5204
RpRp
386917
Rp
Es
SD00176 - AMAROON 2 HT/HWS 1PS Dimensional layout
32-36-41
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
82ASD00163
Visto-Checked byDenominazione-Denomination
Data-DateRev. Dis.-Draftsman Descrizione revisione-Revision descriptionCodice-Code Disegno-Drawing Rev.
Dis.-DraftsmanData-DateScala-Scale Visto-Checked by Foglio diSheet N. of
Sost. il dis.-Replace draw. Sost. dal dis.-Replaced by draw.
Materiale-Material Trattamento-Treatment
Peso-Weight [kg]
SCHEMA DIMENSIONALE / DIMENSIONAL DRAWINGGEYSER 2 50-60-70-80-90 SD00163
P. Frigolorpe 2
/ /
1N. Bettio
/Spessore-Thickness
/Colore vernice-Painted colour
/ /
12/12/20121/30
Codice-Code
/
/ / / //
SPAZI DI INSTALLAZIONE / CLEARANCES
1000
1000
00
1000
0
1000
0Cdh
Rp
Rp
Ep
Ep
2108 23
90
1203
167
519
251,5
371,517
9Lh Lh1403
Rp Cdh
Ep
SCARICO CONDENSA VERSIONE HPCONDENSATE DRAIN HP VERSION
INGRESSO ACQUA UTILIZZOUSER WATER INLET
USCITA ACQUA UTILIZZOUSER WATER OUTLET
Uout 2" BSPM
ø20
EpQUADRO ELETTRICO
Es
ELECTRICAL PANEL
Lh
INGRESSO ALIMENTAZIONE ELETTRICAELECTRICAL SUPPLY INLET
Uin 2" BSPMLIFTING HOLES
RpPANNELLO ASPORTABILE
REMOVABLE PANEL
Cdh
FORI DI SOLLEVAMENTO
*OPZIONALEOPTIONAL
PmGRIGLIE DI PROTEZIONE
PROTECTIVE METAL MESH
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1403 1203 2390
DIMENSIONI / DIMENSIONS
PmPm
Es
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)
50 582 58560 599 60270 609 61280 627 63090 638 641
MOD. 1P 20
MOD. 2P 40
Δ PESOΔ WEIGHT
Δ PESOΔ WEIGHT
Uout
Uin
A B C
A
A MODELLO STANDARD STANDARD MODEL
B MODELLO 1P 1P MODEL
C MODELLO 2P 2P MODEL
CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTIONS
**
Uin B C
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
SD00163 - AMAROON 2 HT Dimensional layout
50-60-70-80-90
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
83ASD00163
Visto-Checked byDenominazione-Denomination
Data-DateRev. Dis.-Draftsman Descrizione revisione-Revision descriptionCodice-Code Disegno-Drawing Rev.
Dis.-DraftsmanData-DateScala-Scale Visto-Checked by Foglio diSheet N. of
Sost. il dis.-Replace draw. Sost. dal dis.-Replaced by draw.
Materiale-Material Trattamento-Treatment
Peso-Weight [kg]
SCHEMA DIMENSIONALE / DIMENSIONAL DRAWINGGEYSER 2 50-60-70-80-90 SD00163
P. Frigolorpe 2
/ /
2N. Bettio
/Spessore-Thickness
/Colore vernice-Painted colour
/ /
12/12/20121/12,5
Codice-Code
/
/ / / //
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
IMPRONTA A TERRA / FOOTPRINT
FORI DI FISSAGGIOFIXING HOLES
Fh Ø18
G..PUNTI DI APPOGGIO ANTIVIBRANTIVIBRATION DAMPER FOOT HOLDS
24 1160 24
124
1160
124
1408
1208
G1 G2
G4G3
G1(kg)
G2(kg)
G3(kg)
G4(kg)
50 158 164 152 11160 163 169 157 11470 165 171 159 11680 170 176 164 12090 173 179 167 122
SD00163 - AMAROON 2 HT Dimensional layout
50-60-70-80-90
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
84ASD00164
Visto-Checked byDenominazione-Denomination
Data-DateRev. Dis.-Draftsman Descrizione revisione-Revision descriptionCodice-Code Disegno-Drawing Rev.
Dis.-DraftsmanData-DateScala-Scale Visto-Checked by Foglio diSheet N. of
Sost. il dis.-Replace draw. Sost. dal dis.-Replaced by draw.
Materiale-Material Trattamento-Treatment
Peso-Weight [kg]
SCHEMA DIMENSIONALE / DIMENSIONAL DRAWINGGEYSER 2 HWS 50-60-70-80-90 SD00164
P. Frigolorpe 2
/ /
1N. Bettio
/Spessore-Thickness
/Colore vernice-Painted colour
/ /
28/11/20121/30
Codice-Code
/
/ / / //
SPAZI DI INSTALLAZIONE / CLEARANCES
1000
1000
00
1000
0
1000
0Cdh
Rp
Rp
Ep
Ep
2108 23
90
1203 167
519
251,5
371,5
179Lh Lh
1403
Rp Cdh
Ep
SCARICO CONDENSA VERSIONE HPCONDENSATE DRAIN HP VERSION
INGRESSO ACQUA UTILIZZOUSER WATER INLET
USCITA ACQUA UTILIZZOUSER WATER OUTLET
INGRESSO ACQUA RECUPERORECOVERY WATER INLET
USCITA ACQUA RECUPERORECOVERY WATER OUTLET
2" BSPM
EpQUADRO ELETTRICO
Es
ELECTRICAL PANEL
Lh
INGRESSO ALIMENTAZIONE ELETTRICAELECTRICAL SUPPLY INLET
GRIGLIE DI PROTEZIONEPROTECTIVE METAL MESH
Uout 2" BSPMLIFTING HOLES
Cdh
Uin
FORI DI SOLLEVAMENTO
Rin 2" BSPM
ø20
Rout 2" BSPMRpPANNELLO ASPORTABILE
REMOVABLE PANEL
Pm
LUNGHEZZAWIDTH
PROFONDITA'DEPTH
ALTEZZAHEIGHT
1403 1203 2390
DIMENSIONI / DIMENSIONS
PmOPZIONALE / OPTIONAL
PmOPZIONALE / OPTIONAL
Es
Uout
Uin
A B
A
A MODELLO STANDARD STANDARD MODELB MODELLO 1P - 2P 1P - 2P MODELC MODELLO 1R 1R MODEL
CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTIONS
Uin B
390
332
MODELLOMODEL
PESOWEIGHT
(kg)
PESO IN FUNZIONEOPERATING WEIGHT
(kg)
50 582 58560 599 60270 609 61280 627 63090 638 641
Δ PESOΔ WEIGHT
MOD. 1R 2P 57
Δ PESOΔ WEIGHT
MOD. 1R 17
Δ PESOΔ WEIGHT
MOD. 1R 1P 37
Δ PESOΔ WEIGHT
MOD. 1P 20
Δ PESOΔ WEIGHT
MOD. 2P 40
Rout A C
Rin C
Rin A
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
SD00164 - AMAROON 2 HT/HWS Dimensional layout
50-60-70-80-90
Swegon reserves the right to alter specifications. www.swegon.com
MAROON 2
85ASD00164
Visto-Checked byDenominazione-Denomination
Data-DateRev. Dis.-Draftsman Descrizione revisione-Revision descriptionCodice-Code Disegno-Drawing Rev.
Dis.-DraftsmanData-DateScala-Scale Visto-Checked by Foglio diSheet N. of
Sost. il dis.-Replace draw. Sost. dal dis.-Replaced by draw.
Materiale-Material Trattamento-Treatment
Peso-Weight [kg]
SCHEMA DIMENSIONALE / DIMENSIONAL DRAWINGGEYSER 2 HWS 50-60-70-80-90 SD00164
P. Frigolorpe 2
/ /
2N. Bettio
/Spessore-Thickness
/Colore vernice-Painted colour
/ /
28/11/20121/12,5
Codice-Code
/
/ / / //
- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.
MTE 56 rev. 02 date: 17/01/07
IMPRONTA A TERRA / FOOTPRINT
FORI DI FISSAGGIOFIXING HOLES
Fh Ø18
G..PUNTI DI APPOGGIO ANTIVIBRANTIVIBRATION DAMPER FOOT HOLDS
24 1160 24
124
1160
124
1408
1208
G1 G2
G4G3
G1(kg)
G2(kg)
G3(kg)
G4(kg)
50 158 164 152 11160 163 169 157 11470 165 171 159 11680 170 176 164 12090 173 179 167 122
SD00164 - AMAROON 2 HT/HWS Dimensional layout
50-60-70-80-90