86
MAROON 2 6÷78 kW General information Dedicated heat pumps new series with Scroll compressors, with and without vapor injection. /HT version in 15 sizes Cooling capacity (A35;W7): 6÷73 KW Heating capacity (A7;W45): 6÷78 KW /MT version in 17 sizes Cooling capacity (A35;W7): 6÷68 KW Heating capacity (A7;W45): 7÷76 KW MAROON 2 is a complete dedicated HP series machines which covers the range from 6 to 78kW using the same re- frigerant gas (R410A) with single and double compressors. Unique selling points Wide operating limits and power range Automatic management for domestic hot water Hws version available for all sizes Smarter defrosting management A class pumps available for single compressor models Modularity and full accessibility

Transcript of MAROON 2 - swegon.com and heat pumps/_en... · and prevents condensation from forming. ... of ice...

MAROON 26÷78 kW

General information

Dedicated heat pumps new series with Scroll compressors, with and without vapor injection.

/HT version in 15 sizes

Cooling capacity (A35;W7): 6÷73 KW

Heating capacity (A7;W45): 6÷78 KW

/MT version in 17 sizes

Cooling capacity (A35;W7): 6÷68 KW

Heating capacity (A7;W45): 7÷76 KW

MAROON 2 is a complete dedicated HP series machines which covers the range from 6 to 78kW using the same re-frigerant gas (R410A) with single and double compressors.

Unique selling points

► Wide operating limits and power range

► Automatic management for domestic hot water

► Hws version available for all sizes

► Smarter defrosting management

► A class pumps available for single compressor models

► Modularity and full accessibility

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

2

INDEX

MAROON 2 - SINGLE COMPRESSOR 3MAROON 2 - BI COMPRESSOR 7DESCRIPTION OF THE FUNCTIONS AND ACCESSORIES 10HEAT PUMP INSTALLATION TIPS 18MAROON 2 MT TECHNICAL DATA 20MAROON 2 HT TECHNICAL DATA 22MAROON 2 MT ELECTRICAL DATA 24MAROON 2 HT ELECTRICAL DATA 25EXCHANGER DIAGRAMS - MAROON 2 MT 26EXCHANGER DIAGRAMS - MAROON 2 HT 28COOLING CAPACITIES - MAROON 2 MT 32HEATING CAPACITIES - MAROON 2 MT 34COOLING CAPACITIES - MAROON 2 MT 36HEATING CAPACITIES - MAROON 2 MT 37RECOVERY CAPACITIES - MAROON 2 MT 38COOLING CAPACITIES - MAROON 2 HT 40HEATING CAPACITIES - MAROON 2 HT 42COOLING CAPACITIES - MAROON 2 HT 44HEATING CAPACITIES - MAROON 2 HT 45RECOVERY CAPACITIES - MAROON 2 HT 46SOUND LEVELS - MAROON 2 MT 48SOUND LEVELS - MAROON 2 HT 49SOUND LEVELS - MAROON 2 MT /LN 50SOUND LEVELS - MAROON 2 HT /LN 51MAROON 2 MT DIMENSIONAL LAYOUTS 52MAROON 2 HT DIMENSIONAL LAYOUTS 70

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

3

MAROON 2 - SINGLE COMPRESSORHIGH EFFICIENCY AIR-WATER HEAT PUMPS WITH AXIAL FANS WITH A SINGLE SCROLL COMPRESSOR

PRODUCT DESCRIPTION

STRUCTUREIn galvanised sheet metal and painted with polyester powders RAL 7035 at 180°C, which confer high resistance to atmospheric agents.

The panels can be easily removed to allow total access to the internal components.

All the structures have a condensate drip tray with the relative drain.

MAROON 2/HT COMPRESSORHermetic scroll compressor, complete with circuit breaker protection included in the electric motor windings, sump heater and rubber anti-vibration supports. The compressor used in this series is specifically designed to run as a heat pump. Optimising the compression ratio to high values allows for a superior efficiency to be reached when compared with traditional scroll compressors.

The models in size 13 to 41 are equipped with a liquid injection compressor. Liquid injection allows the heat pump to run at very low outdoor temperatures while producing very hot water.

MAROON 2/MT COMPRESSORHermetic scroll compressor, complete with circuit breaker protection included in the electric motor windings, sump heater and rubber anti-vibration supports. The compressor used in this series is specifically designed to run as a heat pump. Optimising the compression ratio to high values allows for a superior efficiency to be reached when compared with traditional scroll compressors.

USER SIDE EXCHANGERAISI 316 stainless steel braze-welded plate evaporator, housed inside a closed-cell insulating casing, which reduces heat loss and prevents condensation from forming.

The exchanger is equipped with a temperature probe for anti-freeze protection, with a temperature probe for the water inlet and outlet and with a blade flow switch supplied as standard.

SOURCE SIDE EXCHANGERThis consists of a coil with copper pipes and aluminium fins with a high exchange surface with fin spacing sized so as to maximise heat transfer and reduce the noise impact. The space of the fins in the exchanger has been increased so as to allow the unit to work at very low temperatures and very high moisture concentration.

The subcooler is found at the base of the exchanger, which is an additional cooling circuit that prevents the formation of ice in the lower part of the coil and facilitates the flow of condensate during the defrosting operations. The effects

of the subcooler are: reduced defrosting operations and the safety of having a clean heat exchanger at the end of each defrosting operation.

A metal mesh protects the finned core.

FANSHelicoidal fans coupled directly to the electric motor, made of plastic material with a blade profile equipped with WINGLET, a special shape in the end part of the blades, which allows a reduction in the noise and an increase in the aeraulic performance.

The control manages the fan speed through a speed regulator phase cut in order to optimise the operating conditions, efficiency and allow the unit to operate as a heat pump also for high outdoor temperatures.

Moreover, this adjustment has a reduced noise level effect on the unit. In fact, the control device will modulate the speed of the fans at night and during mid-season. This means that every time there it is possible, the machine will minimise the fan speed and also its noise level.

The fans are axial fans directly coupled to the 6-pole electric motor, with an IP 54 degree of protection, with shaped nozzles and a safety grille in accordance with EN 294.

COOLING CIRCUITIt includes: a charging socket in the liquid and inlet line, liquid indicator, a solenoid valve, non-return valves, a dehydrator filter, 2 thermostatic expansion valves (1 for heat pump operation and 1 for chiller operation) equipped with an external pressure equalizer, pressure transducer, high and low pressure switches and a safety valve (excluding 7,9 and 11 for the /HT version and 8, 10 and 12 for the /MT version), liquid receiver and intake separator (sizes 22 to 41 for the /HT versione and 23 to 42 for the /MT version).

The models in the /HT version size 13 to 41 are equipped with an additional circuit for liquid injection to the compressor.

ELECTRIC CONTROL BOARDThe electric control board consists of:

• a main isolating switch and fuse protection of the auxiliary and power circuits

• a compressor remote control switch

• condensation/evaporation control with fan speed regulator

• pump relay or motor protection switch and remote control switch (in /1P, /1PS, /1PV or /1PVS version)

• potential free contacts for general alarm

• microprocessor control.

The standard power supply is:

• 230V/1~/50Hz for size 7 of the /HT version

• 230V/1~/50Hz for sizes 8 and 10 of the /MT version

• 400V/3N~/50Hz for sizes 9 to 41 of the /HT version

• 400V/3N~/50Hz for sizes 12 to 42 of the /MT version.

3-phase power supply is available as an accessory for the single phase models. Single-phase power supply is available as an accessory for certain 3-phase models.

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

4

CONTROLMicroprocessor control for the following functions:

• water temperature adjustment with inlet control

• anti-freeze protection

• compressor timing

• high pressure pre-alarm control

• alarm signals

• alarms reset

• remote on/off digital input

• summer/winter selection digital input.

The display is used to display the following information:

• temperature of the outlet water

• condensation temperature

• set and differential temperature settings

• description of the alarms

• pump and compressor operation counter.

The control integrates the following standard functions:

• automatic control of domestic hot water

• smooth defrosting.

Certain functions are only available with the unit adequately configured. Certain functions must be enabled from the control.

CHECKS AND SAFETY DEVICESthe units are equipped with the following safety devices:

• utility water temperature control probe (situated at the inlet of the utility heat exchanger)

• anti-freeze probe to activate the anti-freeze alarm (manually reset)

• low pressure switch (with automatic reset at limited intervals)

• low pressure switch (automatically reset at limited intervals)

• standard mechanical blade flow meter (manually reset)

• high pressure safety valve (excluding sizes 7, 9 and 11 of the /HT version and sizes 8, 10 and 12 of the /MT version)

• compressor over-heating protection

• control of the condensation pressure using the speed regulator for operation with low outdoor temperatures.

• control of the evaporation pressure using the speed regulator for operation with high outdoor temperatures in domestic hot water production or recovery.

INSPECTIONThe units are inspected in the factory and supplied complete with oil and refrigerant fluid.

VERSIONS/LN: SILENCED UNITAs well as the components of the basic version, the unit has a completely sound insulated compressor compartment made of sound-absorbing material, which is used with sound impeding material.

/HWS: MULTIPURPOSE HEAT PUMPThe unit in this setup is equipped with 2 exchangers: 1 on the

system side for air-conditioning and heating, and 1 dedicated exclusively to the production of domestic water.

T

T

Sufficient cold or hot water can be produced on the unit system side exchanger to meet the heating and cooling requirements of the building according to the seasons.

The unit on the exchanger dedicated to the DHW produces hot water to be sent to a storage tank outside the machine, which is selected and sized according to the system requirements.

The unit runs in different modes according to the season: these are automatically switched (within the season) via the reading of the temperature probes and the set-point settings. Switching times and logic are designed to guarantee maximum system efficiency and reliability.

This configuration must be associated to an adequately sized boiler in which very hot water is stored. The boiler must have a well for the domestic water operating probe to be inserted in the upper part, through which the unit controller will monitor the amount of domestic hot water that must be produced.

Summer operationThere are 3 summer modes:

• Chiller mode: the unit only produces cold chilled water for the system.

• Chiller mode with simultaneous production of domestic hot water: the unit produces chilled water for the system and domestic hot water. The recovered power for the domestic water production is complete.

• Heat pump mode for domestic hot water production: when there is no cold water and the domestic water operating probe is required to run, the unit heats the water inside the domestic water storage tank using the finned core coil as an evaporator. Using the hot external air as a source of heat guarantees the extremely high COP to be achieved.

Switching from one mode to another occurs entirely automatically according to a priority logic in the domestic hot water production and when there is load diversity, thereby recovering the condensation energy for the production of domestic hot water.

Winter operationThere are 2 winter modes:

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

5

• Heat pump mode for heating: the unit produces hot water to the system side exchanger for heating purposes.

• Heat pump for the production of domestic hot water: produces hot water to the connected exchanger of the domestic water storage tank.

Switching from one mode to another occurs entirely automatically according to a priority logic in the domestic hot water production.

In addition to the components of the basic version, the /HWS unit includes:

• a special exchanger for the production of domestic hot water

• a temperature probe to be positioned on the domestic water storage tank

• an electronic thermostatic valve (replaces the 2 mechanical thermostatic valves).

HYDRAULIC MODULE OPTIONS/1P: unit with one pumpThe unit includes a circulator (sizes 7 to 17 of the /HT version and 8 to 20 of the /MT version) or a circulation pump (sizes 22 to 41 of the /HT version and 23 to 42 for the /MT version), an expansion tank, a hydraulic circuit water drain valve, a safety valve set at 6 bar that corresponds to the maximum operating pressure value allowed.

/1PV: unit with variable capacity pumpThe unit includes, for all sizes, an EC A class circulator, an expansion tank, a hydraulic circuit water drain valve, a safety valve set at 6 bar that corresponds to the maximum operating pressure value allowed.

The circulator with an EC motor has a permanent magnet rotor that guarantees very high efficiency levels for each operating condition.

Allows up to 25% of the power consumption of a normal pump of equal power to be saved. The permanent magnets instead of the windings allows the electric motor to be brushless, thereby optimising its efficiency.

If the unit is connected to a system equipped with valves two-way, the pump will vary its flow rate so as to maintain a constant pressure head. In this case the customer will have to provide a bypass or a 3-way valve suitably positioned to ensure a minimum flow rate equal to 50% of nominal flow.

/1PS: unit with pump and tankIn addition to the components of the /1P version, the unit includes an insulated inertial storage tank.

/1PVS: unit with pump and tankIn addition to the components of the /1PV version, the unit includes an insulated inertial storage tank.

/1R: unit with domestic side pumpThe unit is equipped with a pump for the domestic side (supplied). This module can only be matched with the units in the /HWS version and can be combined with the /1P, /1PV, /1PS or /1PVS modules. The /HWS version units with no /1R module are equipped with consent to control an external pump.

The pump used for domestic hot water must be installed in a technical compartment and adequately protected against low temperatures and the risk of its hydronic circuit freezing.

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

6

STANDARD EQUIPMENT• Smooth defrosting management

• Heat source integration/backup management

• Compressor stop for external air temperatures lower than the operating limits

• Condensation/evaporation control with fan speed regulator

• Flow meter (standard)

• Directive 97/23 EEC (PED) Certification

• Summer/winter selection from digital input

• Remote On/Off from digital input

• Condensate drip tray

• Coil protection grid.

ACCESSORIESAll the units can be configured with various accessories to better meet the requirements of the specific application in which they will be set. To check availability of accessories and compatibility of their size and configuration, please refer to the price list or selection software.

COOLING CIRCUIT ACCESSORIES• electronic thermostatic valve (standard on the /HWS unit).

HYDRAULIC CIRCUIT ACCESSORIES• filling unit with manometer

• anti-freeze resistance

- basic version: electric heater on the utility exhanger

- /1P and /1PV versione: electric heaters on the utility exchanger and heating cable on the pipes

- /1PS and /1PVS versione: electric heaters on the utility exchanger and heating cable on the pipes

• additional heater

• 3-way valve to control the domestic hot water (supplied)

• hydraulically disconnected tank

• system pump with Pulse function

• electronic modulation of the water flow

• filter.

ELECTRICAL ACCESSORIES• electric power supply different from the standard one

• maximum and minimum voltage relays

• double set-point from the digital input

• RS485 serial interface

• remote user terminal

• electronic soft starter

• EC electronic fans

• compensaiton of the setpoint according to the external air temperature

• automatic control of the domestic hot water

• domestic hot water operating probe (standard on the /HWS unit)

• anti-legionella function

• heat source integration/backup management

• domestic water production with timer

• individual operating potential free contacts

• Miniboss S

• Miniboss M

VARIOUS ACCESSORIES• rubber anti-vibration mounts

• wooden cage packaging.

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

7

MAROON 2 - BI COMPRESSORHIGH EFFICIENCY AIR-WATER HEAT PUMPS WITH AXIAL FANS AND SCROLL COMPRESSORS CONNECTED IN TANDEM

PRODUCT DESCRIPTION

STRUCTUREIn galvanised sheet metal and painted with polyester powders RAL 7035 at 180°C, which confer high resistance to atmospheric agents.

The panels can be easily removed to allow total access to the internal components.

All the structures have 2 condensate drip tray (1 per coil) with the relative drain.

MAROON 2/HT COMPRESSORHermetic scroll compressors in tandem configuration, complete with circuit breaker protection included in the electric motor windings, oil level indicator, crankcase heater and rubber anti-vibration mounts. The compressors used in this series are specifically designed to run as heat pumps. Optimising the compression ratio to high values allows for a superior efficiency to be reached when compared with traditional scroll compressors. The compressors have a liquid injection system: this allows the heat pump to run at very low outdoor temperatures while producing very hot water.

MAROON 2/MT COMPRESSORHermetic scroll compressors in tandem configuration, complete with circuit breaker protection included in the electric motor windings, oil level indicator, crankcase heater and rubber anti-vibration mounts. The compressors used in this series are specifically designed to run as a heat pump. Optimising the compression ratio to high values allows for a superior efficiency to be reached when compared with traditional scroll compressors.

USER SIDE EXCHANGERAISI 316 stainless steel braze-welded plate evaporator, housed inside a closed-cell insulating casing, which reduces heat loss and prevents condensation from forming.

The exchanger is equipped with a temperature probe for anti-freeze protection, with a temperature probe for the water inlet and outlet and with a blade flow switch supplied as standard.

SOURCE SIDE EXCHANGERThis consists of 2 coils with copper pipes and aluminium fins with a high exchange surface with fin spacing sized so as to maximise heat transfer and reduce the noise impact. The space of the fins in the exchanger has been increased so as to allow the unit to work at very low temperatures and very high moisture concentration.

The subcooler is found at the base of the exchanger, which is an additional cooling circuit that prevents the formation of ice in the lower part of the coil and facilitates the flow of condensate during the defrosting operations. The effects of the subcooler are: reduced defrosting operations and the safety of having a clean heat exchanger at the end of each defrosting operation.

A metal mesh protects the finned core.

FANSA helicoidal fan coupled directly to the electric motor, made of plastic material with a blade profile equipped with WINGLET, a special shape in the end part of the blades, which allows a reduction in the noise and an increase in the aeraulic performance.

The control manages the fan speed through a speed regulator phase cut in order to optimise the operating conditions, efficiency and allow the unit to operate as a heat pump also for high outdoor temperatures.

Moreover, this adjustment has a reduced noise level effect on the unit. In fact, the control device will modulate the speed of the fans at night and during mid-season. This means that every time there it is possible, the machine will minimise the fan speed and also its noise level.

The fan is an axial fan directly coupled to the 6-pole electric motor, with an IP 54 degree of protection, with shaped nozzles and a safety grille in accordance with EN 294.

COOLING CIRCUITIt includes: a charging socket in the liquid and inlet line, liquid indicator, a solenoid valve, non-return valves, a dehydrator filter, 2 thermostatic expansion valves (1 for heat pump operation and 1 for chiller operation) equipped with an external pressure equalizer, pressure transducer, high and low pressure switches and a safety valve, liquid receiver and intake separator.

ELECTRIC CONTROL BOARDThe electric control board consists offrom:

• a main isolating switch and fuse protection of the auxiliary and power circuits

• remote switches for compressors

• condensation and evaporation control fan speed regulator

• pump relay or motor protection switch and remote control switch (in /1P or /2P version)

• potential free contacts for general alarm

• microprocessor control.

400V/3N~/50Hz power supply for all sizes.

CONTROLMicroprocessor control for the following functions:

• water temperature adjustment with inlet control

• anti-freeze protection

• compressor timing

• high pressure pre-alarm control

• alarm signals

• alarms reset

• remote on/off digital input

• summer/winter selection digital input.

The display is used to display the following information:

• temperature of the outlet water

• condensation temperature

• set and differential temperature settings

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

8

• description of the alarms

• pump and compressor operation counter.

The control integrates the following standard functions:

• automatic control of the domestic hot water

• smooth defrosting.

Certain functions are only available with the unit adequately configured. Certain functions must be enabled from the control.

CHECKS AND SAFETY DEVICES• utility water temperature control probe (situated at the inlet

of the utility heat exchanger)

• anti-freeze probe to activate the anti-freeze alarm (automatically reset at limited intervals)

• high pressure switch (with manual reset)

• low pressure switch (automatically reset at limited intervals)

• standard mechanical blade flow meter (manually reset)

• high pressure safety valve

• compressor over-heating protection

• control of the condensation pressure using the speed regulator for operation with low outdoor temperatures.

• control of the evaporation pressure using the speed regulator for operation with high outdoor temperatures in domestic hot water production or recovery

• compressor over-heating protection.

INSPECTIONThe units are inspected in the factory and supplied complete with oil and refrigerant fluid.

VERSIONS/LN: SILENCED UNITAs well as the components of the basic version, the unit has a completely sound insulated compressor compartment made of sound-absorbing material, which is used with sound impeding material.

/HWS: MULTIPURPOSE HEAT PUMPThe unit in this setup is equipped with 2 exchangers: 1 on the system side for air-conditioning and heating, and 1 dedicated exclusively to the production of domestic water.

T

T

Sufficient cold or hot water can be produced on the unit system side exchanger to meet the heating and cooling requirements of the building according to the seasons.

The unit on the exchanger dedicated to the DHW produces hot water to be sent to a storage tank outside the machine, which is selected and sized according to the system requirements.

The unit runs in different modes according to the season: these are automatically switched (within the season) via the reading of the temperature probes and the set-point settings. Switching times and logic are designed to guarantee maximum system efficiency and reliability.

This configuration must be associated to an adequately sized boiler in which very hot water is stored. The boiler must have a well for the domestic water operating probe to be inserted in the upper part, through which the unit controller will monitor the amount of domestic hot water that must be produced.

Summer operationThere are 3 summer modes:

• Chiller mode: the unit only produces cold chilled water for the system.

• Chiller mode with simultaneous production of domestic hot water: the unit produces chilled water for the system and domestic hot water. The recovered power for the domestic water production is complete.

• Heat pump mode for domestic hot water production: when there is no cold water and the domestic water operating probe is required to run, the unit heats the water inside the domestic water storage tank using the finned core coil as an evaporator. Using the hot external air as a source of heat guarantees the extremely high COP to be achieved.

Switching from one mode to another occurs entirely automatically according to a priority logic in the domestic hot water production and when there is load diversity, thereby recovering the condensation energy for the production of domestic hot water.

Winter operationThere are 2 winter modes:

• Heat pump mode for heating: the unit produces hot water to the system side exchanger for heating purposes.

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

9

• Heat pump for the production of domestic hot water: produces hot water to the connected exchanger of the domestic water storage tank.

Switching from one mode to another occurs entirely automatically according to a priority logic in the domestic hot water production.

In addition to the components of the basic version, the /HWS unit includes:

• a special exchanger for the production of domestic hot water

• a temperature probe to be positioned on the domestic water storage tank

• an electronic thermostatic valve (replaces the 2 mechanical thermostatic valves).

HYDRAULIC MODULE OPTIONS/1P: unit with one pumpThe unit includes a circulation pump installed inside the unit.

/2P: unit with two pumpsThe unit includes 2 circulation pumps installed inside the unit. Each pump is a reserve of the other, controlled in timed rotation and with automatic switchover in the event of a fault.

/1R: unit with domestic side pumpThe unit is equipped with a pump for the domestic side (supplied). This module can only be matched with the units in the /HWS setup and can be combined with the /1P or /2P modules. The HWS units with no /1R module are equipped with consent to control an external pump.

The /1R module is installed inside the unit.

ACCESSORIESAll the units can be configured with various accessories to better meet the requirements of the specific application in which they will be set. To check availability of accessories and compatibility of their size and configuration, please refer to the price list or selection software.

STANDARD EQUIPMENT• Smooth defrosting management

• Heat source integration/backup management

• Compressor stop for external air temperatures lower than the operating limits

• Condensation/evaporation control with fan speed regulator

• Flow meter (standard)

• Directive 97/23 EEC (PED) Certification

• Summer/winter selection from digital input

• Remote On/Off from digital input

• Condensate drip tray

• Coil protection grid.

COOLING CIRCUIT ACCESSORIES• electronic thermostatic valve (standard on the /HWS unit).

HYDRAULIC CIRCUIT ACCESSORIES• filling unit with manometer

• anti-freeze resistance

- basic version: electric heater on the utility exhanger

- /1P and /2P versione: electric heater on the utility exchanger and heating cable on the pipes

• 3-way valve to control the domestic hot water (supplied)

• system pump with Pulse function

• water filter.

ELECTRICAL ACCESSORIES• electric power supply different from the standard one

• maximum and minimum voltage relays

• double set-point from the digital input

• RS485 serial interface

• remote user terminal

• electronic soft starter

• EC electronic fans

• compensaiton of the setpoint according to the external air temperature

• automatic control of the domestic hot water

• domestic hot water operating probe (standard on the /HWS unit)

• anti-legionella function

• heat source integration/backup management

• domestic water production with timer

• individual operating potential free contacts

• utility pump inverter

• Miniboss S

• Miniboss M

VARIOUS ACCESSORIES• rubber anti-vibration mounts

• wooden cage packaging.

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

10

DESCRIPTION OF THE FUNCTIONS AND ACCESSORIESRemote ON/OFF from digital input (standard)All the units come with this function as standard. It consists of a remote contact for turning the machine on and off by means of a signal that can be taken inside the building or piloted by a Building Management System (BMS).

Summer/winter selection from digital input (standard) This function is standard for all heat pumps. When the unit is switched on, an operating mode must be set as either heat pump or chiller. Through this remote contact, the operating mode can be modified even inside the building and without direct access to the microprocessor control.

Smooth defrosting (standard)The control manages the defrosting according to a variable interval threshold, depending on the pressures inside the unit and the external air temperature. Crossing this information, the control can identify the presence of ice on the coil by activating the defrosting sequence only when necessary, so as to maximise the energy efficiency of the unit.

The dynamic management of the defrosting threshold allows for the function to be implemented only when the ice deposited on the coil will affect the performance in outdoor air temperatures below -5°C, when the absolute humidity of the air is very low.

Controlling the auxiliary heat source (standard)The controller can manage an external heat source, which can be of integration or backup type, depending on the type of hydraulic connection. In the diagram below, for example, the boiler will be backup to the heat pump.

The auxiliary heat source will be activated when the outdoor air temperature drops below a threshold that can be set from the control and only when the heat pump is insufficient to meet the load. Activation occurs by closing a potential free contact.

It is also possible to set the unit for the controller to switch the compressors off when the unit operates in heat pump mode and the outdoor air temperature drops below a minimum set temperature: the controller will stop the compressors before the unit goes into low pressure alarm, thereby preventing having to manually reactivate the machine.

This function is particularly useful when the heat pump is

installed in an area where the external air temperature will definitely drop below the minimum temperature allowed by the threshold (in accordance with the set-point). When the external air temperature returns above the set temperature threshold, the unit restarts automatically without requiring any intervention.

Units with an integrated pump must always be kept running in order to prevent the formation of ice and to ensure correct operation of the temperature probes and anti-freeze safety devices.

The shutdown temperature must be configured according to the higher set-point temperature and the operating limits of the machine.

A shutdown temperature other than the default can be set provided it is compatible with the unit’s operating limits.

Standard programming involves the

• /MT units having the heating set-point set at 30/35° with a shutdown temperature of -16°C

• /HT units having the heating set-point set at 40/45° with a shutdown temperature of -20°C

If the unit must also be used to produce domestic hot water, the shutdown temperature must consider the higher water set-point and the operating limits allowed.

Automatic domestic hot water control (standard)This function allows the unit to control the temperature inside a storage tank for the domestic hot water and a 3-way valve (accessory) outside the unit by means of a domestic water operating probe (accessory). Priority is always given to the production of hot water for domestic use.

The request for the function to be activated must be made when placing the order, however, it can be configured at a later stage (by qualified and authorised technical personnel) provided that the unit is connected with a suitable hydraulic circuit.

The request made when placing the order for special accessories to control the domestic hot water automatically entails the activation of the ”automatic domestic hot water control” funtion.

The heat pump normally operates on the system to meet the comfort requirements of the building, however, when the water temperature inside the tank drops below a set threshold, the control manages the production of domestic hot water: if the unit is operating as a heat pump for heating, the 3-way valve will be switched and the set-point changed; if on the other hand, the unit is producing chilled water for air conditioning, the control switches the unit to heat pump mode, assigns it the set-point for domestic hot water (usually higher than the set-point of the system) and turns the 3-way valve in the right position.

Once the temperature inside the domestic water tank has reached the set value, the unit automatically returns to the water production for the heating and air conditioning system.

Description of the winter modeThe following conditions occur in winter:

• Heating request: the temperature of the unit inlet water

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

11

coming from the system is lower than that expected, therefore, the control switches the compressor on and the unit will run until the set-point temperature is reached.

The compressor stops when the desired temperature is reached and only the circulation pump will keep running, which will keep the water circulating in the system. The unit will wait in this state until the water inlet temperature drops again.

• Domestic hot water request: let us suppose that the unit is producing hot water for the heating system (45°C) and receives the request to produce hot water from the domestic water operating probe in the storage tank since the water temperature has dropped below the set limit, (e.g. 55°C).

• Since the hot water is controlled with priority logic, the control will change the set-point bringing it to 55°C and switch the 3-way valve.

As soon as the water inside the tank will reach the required 55°C, the control will switch the 3-way valve once again to work on the system and bring the set-point back to 45°C.

If the defrosting process must be implemented, regardless of the mode the unit is running in, it will force the 3-way valve to be switched towards the system, which is less sensitive to the reduction in temperature due to the greater inertia.

Description of the mid-season mode The heating and air conditioning system is not active during the mid-season and therefore, the heat pump is solely dedicated to the production of domestic hot water.

The 3-way valve is firmly positioned on the domestic hot water tank, whereas the pump and heat exchanger will only be activated on demand from the domestic water operating probe.

When the domestic water set-point is reached, the compressor and the pump will be switched off and the control will remain in stand-by for the next request.

This function is activated by setting the unit to the ”domestic hot water only” function. For further information refer to the wiring diagram supplied with the unit.

Description of the summer modeThe following conditions occur in summer:

• Only cooling: the temperature of the unit inlet water coming from the system is higher than that expected, therefore, the control switches the compressor on and the unit will run until the set-point temperature is reached.

The unit then stops and only the pump will keep running, which will keep the water circulating in the system. The unit will wait in this state until the water inlet temperature rises again.

• Domestic hot water request: let us suppose that the unit is producing chilled water for the air conditioning system (7°C) and receives the request to produce hot water from the domestic water operating probe in the storage tank since the domestic water temperature has dropped below the set limit, (e.g. 55°C).

Since the domestic hot water is controlled with priority logic, the control will change the unit mode from chiller to heat pump, set the set-point to 55°C and switch the 3-way valve.

As soon as the water inside the tank will reach the required 55°C, the control will switch the 3-way valve once again to cihller mode, turn the 3-way valve for it to work on the system and bring the set-point back to 7°C.

Domestic water operating probe (accessory) The controller requires this accessory for the production of domestic hot water: it consists of a temperature probe with

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

12

a 6 m cable to be placed in a special well in the tank for the production of domestic water. Read the ”Heat pump installation tips” section to set it in the correct position.

Standard on HWS units.

Hydraulically disconnected tank (accessory) If the unit must also be used for the production of domestic hot water using the 3-way valve and is equipped with an inertial tank (/1PS and /1PVS units), the ”Hydraulically disconnected tank” accessory must be included.

T

The unit will be set-up with the mechanically connected tank, however, it will have a hydraulic inlet and outlet that are not connected to unit. This will allow the 3-way valve to be inserted corrected, thereby avoiding the inertial tank from being crossed during the production of the domestic hot water.

Anti-legionella function (accessory)

Anti-legionella cycles may have to controlled, depending on the type of tank chosen for the production of domestic hot water. The controller can handle activating an auxiliary heat source that will perform the thermal shock on the hot water tank, according to programmed intervals with a weekly timer.

System pump with Pulse function (accessory) As standard, the unit is set to keep the system side circulation pump always on, even if it reaches the set temperature.

When the unit is equipped with this accessory and the set-point is reached, the controller will switch the pump off, reactivating it periodically for sufficient time to detect the temperature of the water. If the controller verifies that the water temperature is still in set-point conditions, it will then turn the pump off again. Otherwise, the controller will reactivate the compressors to meet the system requirements.

Hence, this accessory allows the electrical consumption due to pumping to be significantly reduced, especially during mid-season when the load is extremely low.

The ”anti-freeze” accessory must be present for this accessory to be applied.

Domestic water production with timer (accessory)If this accessory is present, 2 temperatures can be set for the domestic water by associating different time bands: Normal and Saving. This allows you to decide when the heat pump is to concentrate on the production of hot water, however, always keeping the minimum Saving temperature, which is always managed with priority logic.

For example, focusing the production of water at Normal

temperature at night, the better electricity rates will be taken advantage of and production of hot water just before the time when consumption is higher will be guaranteed.

With this system, the unit will still never cease to control the temperature inside the domestic water tank and if there is occasional use of hot water out of the usual times, the unit will give priority to the production of domestic water until the water in the tank returns to a temperature that is equivalent to the Saving set-point.

Electronic modulation of the water flow (accessory)This accessory allows the unit to modulate the water flow so as to facilitate unit start-up even if the water in the system is not at an optimal temperature. Starting the unit after the system has been OFF for a long time, the water in the system could be too hot in summer or too cold in winter. In both cases, the modulation of the water flow guarantees the unit reaches the correct operating speed, avoiding the intervention of the safety devices.

This accessory is only available for per gli allestinimenti /1PV e /1PVS.

Electronic thermostatic valve (accessory)This accessory is particularly suitable for units that operate in very unstable heat load conditions or in conditions where the outdoor temperature is highly variable or the operating mode is changed often, as in the case of combined air conditioning, heating and production of hot water. Using the electronic thermostatic valve allows the following:

• to maximise the heat exchange to the utility exchanger

• to minimise the response time of the cooling circuit to variations in load and operating conditions

• to optimise the superheating regulation

• to maximise the energy efficiency.

EC fans (accessory)The units can be requested with EC fans, a brushless motor with electronic switchover. These motors with permanent magnets rotor guarantee very high levels of efficiency for every work condition and allow for 15% savings on the absorbed power per fan.

Moreover, through a 0-10V analogue signal sent to every fan, the microprocessor allows the condensation/evaporation to be controlled by means of continuous air flow regulations as the outdoor air temperature varies and a consequent reduction in electrical consumption and noise emission.

MINIBOSS S/M (accessory)In applications in which there is:

• the need to guarantee continuous system operation and therefore, redundancy must be foreseen by means of a reserve machine

• a system that will be activated for parts and will therefore require a progressive increase in the installed power

• there is no physical space to install one unit that guarantees

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

13

all the power, however, a number of smaller units can be installed

• in general, the MINIBOSS accessory, which is a control panel provided with the unit, can be used to combine several units and to coordinate the operation and rotation. This allows you to manage multiple units connected in parallel and coordinated by one supervisor in a rational and efficient way.

MINIBOSS S The Miniboss S allows you to connect up to 4 units in parallel: the control allows you to enable and disable them in power steps and rotate them in operation, thereby allowing all units to be used in an identical manner.

The connected units must all be the same. The Miniboss S cannot control units that have the domestic water control active.

The following can be controlled directly from the Miniboss S panel:

• the set-point of the system

• the summer/winter selection of all the machines

• the ON/OFF of the single units or the entire system.

This accessory is supplied in an electrical panel together with the unit (to be installed in a technical compartment), and must be placed on one of the machines connected in parallel and all connected units must have the same configuration.

When placing the order you must specify the number of units that must be controlled so as to allow for the proper programming of the supervisor. In addition, the hydraulic circuit that connects the units must comply with one of the following formats.

T

P P

MBS

T

MBS

T

MBS

For further information regarding the use, refer to the specific documentation.

MINIBOSS MThe Miniboss M allows a maximum of 8 unita in parallel to be controlled. The main functions are:

• controlling units with HWS configurations

• control units with ”automatic domestic hot water control” logic

• control systems with a hot/cold tank to heat/air condition and a hot tank for the production of domestic water.

Besides that also implemented by the Miniboss S,

• the set-point of the system

• the DHW set-point

• use a compensation climatic of the system set-point

• the summer/winter selection of all the machines

• the ON/OFF of the single units or the entire system

• 3-way valve switchover

• control the operation of pumps outside the units.

This accessory is supplied in an electrical panel together with the unit (to be installed in a technical compartment), and must be placed on one of the machines connected in parallel and all connected units must have the same configuration.

When placing the order you must specify the number of units that must be controlled so as to allow for the proper programming of the supervisor. In addition, the hydraulic circuit that connects the units must comply with one of the following formats.

T

T

T

MBM

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

14

T

T

T

MBM

For further information regarding the use, refer to the specific documentation.

Filling unit with manometer (accessory)This accessory allows the hydraulic system to be filled automatically and the correct working pressure to be adjustmented, which can always be verified via the manometer, and continuously maintenance maintains this pressure, topping-up the water, if necessary.

Anti-freeze heater (accessory)This accessory consists of heaters fitted on the utility exchanger, pump and tank (depending on the machine configuration) to prevent damage to the hydraulic components due to the formation of ice when the machine is out of use. The power of the anti-freeze heaters is only a few Watts, depending on the model of the unit, which is sufficient to prevent the components from malfunctioning.

The controller monitors the outlet probe of the exchanger (even when the unit is in standby) and when this detects a water temperature of 5°C or less (or 2°C below the set-point temperature, with a differential of 1°C) and triggers the anti-freeze heater.

When the temperature of the outlet water reaches 4°C (or 3°C below the set-point), it also triggers the anti-freeze alarm that stops the compressor, whilst keeping the the heaters active.

The anti-freeze heaters are located in the evaporator (the 1PS version also has an anti-freeze heater installed on the tank, on the pipes and on the pump volute that will be insulated), and on any recovery heat exchangers.

Additional heater (accessory)This is an electrical heater inserted in the inertial tank of the hydronic module that helps the heat pump fulfil its purpose when the power of the unit is insufficient.

The capacity of the heater depends on the size of the machine.

This accessory is only available with the hydraulic module with tank.

Double set-point from digital input (accessory)The double set-point allows you to set 2 different operating temperatures for the heating mode and a set-point for the cooling mode. If a double set-point is required for both modes, an electronic thermostatic valve must be installed.

The set-point temperatures must be specified when placing the order. The set-point can be changed from the keypad or digital input.

RS485 serial interface (accessory)The growing diffusion of domotic and BMS (Building Management System) systems has led to the need to integrate all the system components under one supervision. To meet this requirement, the unit can be equipped with an RS485 serial board with MODBUS protocol.

Remote user terminal (accessory)This accessory consists of a replica of the remote control panel from which the unit configuration can be completed and all its parameters can be viewed. Passwords must be entered to access the masks that enable the various editing levels.

Soft-starter (accessory)The units are equipped with the technology required to minimise peak current, however, the unit can also be fitted with a soft-starter accessory as a further precaution. It is an electronic control device that monitors the start-up of the electric motors and reduces the normal peak current of the compressor by 40%.

Domestic hot water 3-way valve (accessory)It is an on/off 3-way valve that combined with the ”automatic domestic hot water control” function, it allows the machine to control 2 separate circuits for comfort and production of domestic hot water, switching automatically from one to another, according to the system requirements.

The 3-way domestic hot water valve must be installed in a technical compartment.

Compensation of the set-point depending on the external temperature (accessory) The controller allows you to change the set-point of the unit when in chiller mode and in heat pump mode according to the external temperature. Compensation can be positive or positive: positive compensation occurs when there is an increase in the outdoor air temperature and the operating set also increases; whereas, negative compensation occurs when there is an increase in the air temperature and the set decreases.

If the unit is also used for the production of domestic hot water the climatic adjustment will not affect the temperature of the domestic water set.

Unless specified otherwise when placing the order, standard programming involves negative compensation (for both set-points) as shown in the diagrams below. All the settings can be modified directly by the controller device.

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

15

MAROON 2 /MT MAROON 2 /HT

ModeHEAT PUMP

38/42°C

SET2 =

SET1 =

50/55°C

-16°C -3 °C

SET2 = 50/55°C

-20°C -10°C

43/48°CSET1 =

Maximum and minimum voltage relays (accessory)This device continuously monitors the supply voltage of the unit, thereby verifying that it remains within a permissible range. When the voltage goes exceeds or drops below the range, the device stops the unit to avoid damaging the electric motors.

The device also monitors the phase sequence.

Inverter for utility pump (for the unit with the ST hydraulic module)

Energy savings:Variable flow pumps have become more widespread over the years to optimise air conditioning and cooling systems. Thanks to the Inverter utility pump, Blue Box offers an alternative method that differs from conventional layouts: a constant flow primary pump and a variable flow secondary pump.

Comparing the two solutions:1) The figure below shows the layout of a constant flow primary pump and a variable flow secondary pump. Please not the use of the decoupling pipe between the primary and secondary system (designed to cover the entire flow rate): if the utilities only require a percentage of the nominal power, the decoupling pipe recirculates the excess flow, which means wasting pumping energy.

EVA

POR

ATO

R

BA

CK

FLO

W P

REV

ENTE

R

PRIMARYPUMPING UNIT WITH CONSTANT FLOW

SECONDARYPUMPING

UNIT WITH

VARIABLE FLOW

The figure below shows a system with only variable flow primary pumps, which also serve the secondary system. The bypass pipe and the two-way control valve ensure minimum water flow through the evaporator when the request is below the admitted minimum water flow limit to guarantee appropriate heat exchange. The pipe and the two-way control valve are sized for a much lower water flow rate than the nominal one. This allows to considerably reduce energy losses related to the mixing process, which in traditional systems are caused by the hydraulic circuit breaker.

BY-P

ASS

PIP

E

PRIMARYPUMPING UNIT WITH VARIABLE FLOW

Benefits of the solution with the Inverter for utility pump:

• Saving a set of pumps

• Reduced overall dimensions of the machines’ housings

• Lower piping costs

• Reduced pressure drops

• Greater energy efficiency on the pump side.

As we can see from the graph under EUROVENT conditions, the systems in the diagrams have higher efficiency under part-load conditions, considering the energy consumed by the pumps as well as by the chiller (compressors plus fans).

0%

2%

4%

6%

8%

10%

12%

14%

16%

18%

20%

22%

24%

100% 75% 50% 25% Total ESEERImprovment

EER

impr

ovm

ent a

t partia

l loa

d

Energy savings in these conditions can be as high as 11% per year and sometimes even more!

Operating logic of the Inverter for utility pump:

Dp1: System side pressure drops

Dp2: Evaporator pressure drops

dwo pwo

dwi pwi

Dp2

two

twi

Dp1

EVA

POR

ATO

R

SYSTEM SIDE

MINIMUM THERMAL FLYWHEEL

SUPPLIED MODULATING BY-PASS VALVE

PUMP WITH INVERTER

When all utilities are running, the unit pump works with a nominal flow rate and system side working head equal to DP1 and evaporator pressure drop equal to Dp2.

The decrease in the system thermal load involves closing the shut-off valves of the utilities with a consequent increase in pressure drops that the pump must overcome; simultaneously, the inverter control logic will decrease the flow rate with a

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

16

consequent decrease in the evaporator pressure drop, thereby restoring the pressure head to the nominal DP1.

Key points for a variable flow primary system:In order for the components of the system to operate optimally, it is important to take some key points into account:

1) Minimum water flow and bypass valve supplied:The Inverter for utility pump accessory also includes the supplied 2-way by-pass valve, which is adequately sized in relation to the size of the unit.

If on the system side the heat load is very low, this means that many utilities are closed, which results in an increase in pressure drops. The inverter counters the Dp1 variation detected by the sensor by reducing the speed of the pump and the flow rate as a result. However, there is a limit lower than the flow rate value below which the heat exchange towards the evaporator is not performed properly and the temperature drop processed by the evaporator increases, which might activate the anti-freeze alarm. The two-way control valve adequately selected based on the machine model prevents this alarm from being triggered, thereby ensuring the minimum water flow rate towards the evaporator.

2) “Minimum thermal flywheel”:In the event of a heat load close to zero, with the unit in maximum power partialisation conditions, the pump set at the minimum flow rate and closed system valves, the machine might stop due to the anti-freeze alarm.

To prevent this problem, there must be a “minimum thermal flywheel” in the evaporator / bypass valve section.

Below is the formula to determine it:

NkP

Vol*0=

][l

=0P Machine overall cooling capacity [kW]

N : Inverse of the unit’s minimum capacity control

k : parameter [l/kW]

Scroll compressors 2 3 4 5 6 7 8 9 10 12

k [l/kW]

17.4 13 13.9 17.4 16.3 15.3 14.8 14.6 13.9 13.4

N 2 3 4 5 6 7 8 9 10 12

The water content of the evaporator, of the hydraulic module’s inertial tank (if there is one) and of the pipes between the bypass and the evaporator itself may contribute to determine the “minimum thermal flywheel”.

However, it is advisable to use three-way valves on a certain number of utilities on the system to ensure a minimum flow of water towards the system in any condition.

Please note: Where there is this accessory, the minimum cold water temperature at the outlet cannot drop below 7°C. Moreover, the temperature variation considered under the conditions specified in the project must be 5°C. Please contact our sales department for the minimum water temperature at the outlet (production of cold water) and for different temperature drop values.

You should also contact the sales department in the event of

production of hot water for water temperatures at the outlet below 40°C.

Attention: The “minimum thermal flywheel” must be between the bypass valve and the evaporator. This is a part of the “minimum water content of the system” described in the relative chapter of the manual; the difference between the “minimum water content of the system” and the “minimum thermal flywheel” can instead be positioned in any area of the system.

The “minimum thermal flywheel” allows the unit to operate correctly also in heat pump mode.

For cooling-only machines, if using ethylene glycol mixes, it is possible to reduce the “minimum thermal flywheel” based on the curves below

For scroll compressors:

% ETHYLENE GLYCOL

MINIMUM REDUCTION IN THE THERMAL FLYWHEEL

-100%

-95%

-90%

-85%

-80%

-75%

-70%

-65%

-60%

-55%

-50%

10% 20% 30%

If the unit is in heat pump mode, the “minimum thermal flywheel” is not reduced, even if there is glycol.

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

17

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

18

HEAT PUMP INSTALLATION TIPS

Using a heat pump for air conditioning, heating and production of domestic hot water has been an established practice for years and has undoubted advantages.

By its nature, the heat pump is strongly affected by the characteristics of the system, the selected operating conditions and the choices made for its installation and connection.

Below are some tips that increase the efficiency and reliability of the system:

CHOOSING THE CAPACITY OF THE HEAT PUMPS CORRECTLYThe heat pump must always be selected in excess, guaranteeing to exceed the maximum load besides the project load and possibly being able to operate even at lower temperatures than those of the project.

An integration or backup must also be contemplated, which can replace or help the heat pump in harsher operating conditions.

CHOOSING THE PROPER OPERATING TEMPERATURESHeat pumps guarantee maximum efficiency, and therefore the economic advantage in using them, since the design of the system is aimed at choosing high water temperatures for air conditioning and low ones for heating.

As can be seen from the example diagrams above, even a small variation in the temperature leads to an immediate improvement in the EER and COP.

CHOOSING THE PROPER TEMPERATURE FOR THE DOMESTIC WATERFor the same reasons in the previous point, the choice of the tank for the production of domestic water is to be made so as to maintain the set-point for the production of hot water

as low as possible. This will allow the efficiency of the system to be increased and also maximise the operating limits of the unit, thereby ensuring the production of domestic water even for very low temperatures.

In general it is not advisable to set the unit set-points the limit of the permissible operating conditions, especially in the heat pump mode, for the following reasons:

• Setting the water set-point at the maximum temperature limit reduces the operating limits of the unit.

• The water filter must always be present in the water inlet of the unit otherwise the warranty will be rendered nul and void. With the passage of time the filter element can become dirty and this will increase the pressure drops and consequently reduce the water flow. Lowering the water flow will lead to an increase in the thermal gradient of the utility exchanger that can go from 4/5°C to 9/10°C, however, since the unit controls the set-point on the return temperature, this may involve the intervention of the safety devices if the unit operates at the limits of the allowed operating conditions.

• If the heat pump is connected directly (without intermediate circuit breakers) to a hydraulic circuit divided into areas, the pressure drop of the circuit may increase on closure of one or more areas, thereby leading to a decrease of flow and then to a increase of the thermal head to the heat exchanger. As before, if the heat pump is set to operate at the permissable limits of the operating conditions, this can lead to an intervention of the safety devices.

• Depending on the position chosen for the installation of the unit.

• In summer, the unit will be subject to solar radiation. Assuming the air is at 35°, the coil (copper and aluminum and therefore excellent conductor) will be very hot. When you switch the unit on, even with the fans stopped, the evaporation will be very high, thereby leading to the definite intervention of the high pressure switch.

• Air recirculation can generate an environmental micro with a temperature less than 4/5°, leading the unit to work out of the limits.

• The clearances are very important, the upstream or downstream obstruction of the fan creates pressure drops that reduce the air flow. This reduction can generate a reduction in the operating temperatures. This decrease may lead the unit out of the operating limits.

• Air in the circuit. Air in the system, even if thoroughly vented, creates a loss of heat transfer coefficient with the consequent possibility of the high pressure safety devices intervening.

CAREFUL SELECTION OF THE DOMESTIC WATER TANKWhen you want to use a heat pump for water production the unit must always be connected to an adequately selected tank that is dedicated to the production of domestic hot water. In fact, the heat pumps cannot produce the water instantly and the plate exchanger must also work with a closed water circuit to prevent scale from forming on the inside.

The choice of the tank for the domestic water must be done very carefully because if it is not adequately sized, the system

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

19

may not be reliable. For this reason, it is strongly recommended to choose a tank that allows the heat pump to work on the technical water and not on a coil. The combination of the heat pumps with coils is in fact problematic because of the difficulty in sizing the coil surface that must always be done in the worst conditions, that is in summer conditions. Units can only be combined with coil tanks for storage provided directly by BlueBox.

POSITIONING THE DOMESTIC WATER OPERATING PROBE CORRECTLY For the domestic hot water and HWS control, the units use a supplied temperature probe, which must be installed properly: the tank must have a well in the upper part, which is long enough to almost reach the centre of the tank. The probe supplied with the unit must be inserted in the well with conductive paste in order to ensure an accurate reading of the water temperature. An incorrect temperature reading, caused by an unsuitable positioning or little conductive paste, could lead to the safety devices being triggered or the unit blocking.

SELECTING THE 3-WAY DOMESTIC WATER VALVE CORRECTLYIf you use the automatic control function of the domestic hot water, a 3-way valve with power supply 230/1~/50 is required together with a diameter of 1/4 of an inch greater than the diameter of the unit pipe. This valve must guarantee adequate speed switching and it is mandatory for the flow to never be cancelled during switching, thereby always allowing a flow.

POSITIONING THE COLD WATER TOP-UP CORRECTLYDepending on the type of tank used for the production of domestic hot water, there may be a connection for the water top-up from the mains (cold). It is very important for this connection to not be too close to the return pipe to the heat pump. In fact this could cause the cold water inlet from the mains cool the return water to the heat pump and this sudden drop in temperature of the inlet water to the ”hot” exchanger may lead to the safety devices intervening.

Even in this case using an instantaneous producer for the domestic water combined with a tank that allows the heat pump to work on the technical water allows this problem to be avoided.

CONSIDERING THE MOISTURE CONTENT IN THE WALLS AND SLABS IN THE BUILDINGLarge amounts of water are used to construct masonry works and screeds, to which one can add the rain absorbed by the unfinished works. All the moisture absorbed by the building evaporates very slowly.

Due to the high moisture content present in the entire building, in the first two periods of heating the heating requirements of the building will be increased.

If the heat pump is adequately sized to overcome the nominal heat load of the building and the first system start-up is in cold weather, the heating capacity output may be insufficient to start-up the entire system at once. In this case it is advisable to carry out its start-up per area, namely adding a few sections of the system at a time just as those already connected start to heat up or with the use of an additional electrical heater to compensate for the increased heating requirements.

ALWAYS GUARANTEEING THE MINIMUM WATER CONTENTIf the unit is connected to a hydraulic system split into areas, such as those with radiant panels, with them being controlled via solenoid valves on the manifold (heads), it is mandatory to ensure the presence of at least five litres of water for every kW of heat output of the unit in the most unfavorable condition, that is with a single open area. This is necessary to prevent the condition whereby almost all the heads are closed and the heat pump has to work with an extremely small volume of water. In this case, during the defrosting cycle, the safety devices may intervene due to excessively cold water.

STARTING-UP THE UNIT WITH WATER THAT IS TOO HOT OR TOO COLDThe safety devices may intervene if the unit is started-up in winter with a very cold water temperature and out of the operating limits of the unit. The system is brought up to its nominal speed by simply reducing the thermal load by sectioning part of the system. When the water temperature of the partial system will be within the operating range, the part of the system that was previously sectioned can then be connected.

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

20

Unit size 8 10 12 16 18 20 23 25 29 34 38 42Heating (Gross values)Nominal heating capacity (A7;W35)Heating absorbed powerCOPEfficiency ClassNominal heating capacity (A7;W45)Heating absorbed powerCOPEfficiency ClassHeating (EN14511 values)Nominal heating capacity (A7;W35)COPEfficiency ClassNominal heating capacity (A7;W45)COPEfficiency ClassCooling (Gross values)Nominal cooling capacity (A35;W18)Cooling absorbed powerEEREfficiency ClassNominal cooling capacity (A35;W7)Cooling absorbed powerEEREfficiency ClassCooling (EN14511 values)Nominal cooling capacity (A35;W18)EEREfficiency ClassNominal cooling capacity (A35;W7)EEREfficiency ClassCompressorType ScrollQuantity/Cooling circuitsCapacity controlTotal oil loadTotal refrigerant loadFansType AxialQuantityAir flow rateUser side exchangerType PlatesWater flow ratePressure dropHydraulic modulePump modelUseful pump headStorage tank capacityExpansion tank NoiseSound power levelNoise pressure levelDimensions and weightLengthDepthHeightOperating weight

MAROON 2 MT TECHNICAL DATA

(1) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 30-35°C(2) The total power is given by the sum of the power absorbed by the compressors and by the fans(3) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 40-45°C(4) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 60-65°C(5) External air temperature 35°C; input water-evaporator output temperature 23-18°C(6) External air temperature 35°C; input water-evaporator output temperature 12-7°C

(7) Sound power levels calculated compliant to ISO 3744(8) Sound pressure levels refer to 10 meters from unit in free field and directionality factor Q=2(9) Values compliant with EN 14511-3:2011This board reports the feature data of the base and standard versions; for details, refer to the specific documentation.

(1) kW 6,9 8,9 11,1 14,9 16,6 19,2 22,1 24,0 27,6 32,3 36,8 40,4(1), (2) kW 1,7 2,1 2,5 3,5 3,9 4,3 5,0 5,5 6,6 7,5 8,2 9,4

(1) 4,09 4,14 4,40 4,29 4,25 4,48 4,39 4,38 4,19 4,32 4,50 4,30A A A A A A A A A A A A

(3) kW 6,8 8,8 10,9 14,6 16,2 18,7 21,5 23,4 26,9 31,5 35,7 39,2(3), (2) kW 2,1 2,7 3,1 4,4 4,8 5,3 6,2 6,8 8,0 9,2 10,0 11,4

(3) 3,23 3,22 3,46 3,37 3,40 3,54 3,47 3,45 3,37 3,42 3,55 3,43A A A A A A A A A A A A

(1), (9) kW 6,9 8,9 11,2 15,0 16,7 19,4 22,2 24,2 27,8 32,5 37,1 40,6(1), (9) 4,06 4,12 4,36 4,16 4,16 4,37 4,29 4,28 4,10 4,23 4,40 4,23

A A A A A A A A A A A A(3), (9) kW 6,9 8,8 10,9 14,8 16,3 18,9 21,7 23,5 27,1 31,7 35,9 39,4(3), (9) 3,21 3,20 3,43 3,29 3,34 3,47 3,41 3,39 3,32 3,37 3,49 3,38

A A A A A A A A A A A A

(5) kW 8,5 10,2 13,0 17,9 19,5 22,6 26,0 28,3 32,9 39,9 43,5 45,1(5), (2) kW 2,2 2,6 3,1 4,3 4,6 5,4 6,4 6,9 8,3 9,3 10,9 11,5

(5) 3,84 3,88 4,19 4,14 4,28 4,23 4,05 4,12 3,98 4,29 4,00 3,93A A A A A A A A A A A A

(6) kW 6,2 7,6 9,7 13,4 14,2 16,8 19,1 20,8 24,4 29,6 32,4 38,6(6),(2) kW 2,1 2,5 2,9 4,0 4,4 4,9 5,9 6,4 7,6 8,7 10,1 11,0(6) 2,90 3,02 3,38 3,31 3,23 3,40 3,24 3,27 3,21 3,42 3,20 3,51

B B A A A A A A A A A A

(5), (9) kW 8,5 10,2 13,0 17,8 19,4 22,5 25,9 28,1 32,7 39,7 43,2 44,9(5), (9) 3,80 3,84 4,14 3,98 4,15 4,09 3,92 4,01 3,88 4,18 3,90 3,84

A A A A A A A A A A A A(6), (9) kW 6,2 7,5 9,6 13,2 14,1 16,6 18,9 20,7 24,2 29,4 32,2 38,4(6), (9) 2,87 2,99 3,33 3,16 3,12 3,28 3,13 3,17 3,11 3,32 3,11 3,42

C B A A A A A A A A A A

n° / n° 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1n° 1 1 1 1 1 1 1 1 1 1 1 1kg 1,1 1,3 1,3 1,2 1,7 1,9 1,8 2,5 3,3 3,3 3,3 3,3kg 2,6 3,5 4,2 5,7 6,2 7,0 8,4 9,1 10,7 12,4 13,5 14,2

n° 1 1 1 2 2 2 2 2 2 2 2 2m3/h 3.900 3.900 3.600 7.800 7.800 7.200 14.000 14.000 18.000 18.000 17.000 17.000

(1) l/h 1.190 1.525 1.916 2.554 2.860 3.304 3.792 4.131 4.752 5.561 6.334 6.939(1) kPa 4 4 6 42 28 33 34 30 33 33 34 30

P1 P1 P1 P2 P2 P2 P3 P3 P3 P3 P3 P4kPa 71 68 65 91 89 85 167 160 145 124 101 193l 70 70 70 70 70 70 130 130 130 130 130 130l 2 2 2 2 2 2 5 5 5 5 5 5

(7) dB(A) 63 65 66 68 70 70 72 73 74 75 75 75(8) dB(A) 32 34 35 37 39 39 41 42 42 43 43 43

mm 925 925 925 925 925 925 1.105 1.105 1.305 1.305 1.305 1.305mm 375 375 375 375 375 375 505 505 505 505 505 505mm 700 700 700 1.350 1.350 1.350 1.385 1.385 1.585 1.585 1.585 1.585kg 88 93 102 135 151 166 212 233 358 367 387 398

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

21

Unit size 52 62 72 82 92Heating (Gross values)Nominal heating capacity (A7;W35)Heating absorbed powerCOPEfficiency ClassNominal heating capacity (A7;W45)Heating absorbed powerCOPEfficiency ClassHeating (EN14511 values)Nominal heating capacity (A7;W35)COPEfficiency ClassNominal heating capacity (A7;W45)COPEfficiency ClassCooling (Gross values)Nominal cooling capacity (A35;W18)Cooling absorbed powerEEREfficiency ClassNominal cooling capacity (A35;W7)Cooling absorbed powerEEREfficiency ClassCooling (EN14511 values)Nominal cooling capacity (A35;W18)EEREfficiency ClassNominal cooling capacity (A35;W7)EEREfficiency ClassCompressorType ScrollQuantity/Cooling circuitsCapacity controlTotal oil loadTotal refrigerant loadFansType AxialQuantityAir flow rateUser side exchangerType PlatesWater flow ratePressure dropHydraulic modulePump modelUseful pump headNoiseSound power levelNoise pressure levelDimensions and weightLengthDepthHeightOperating weight

MAROON 2 MT TECHNICAL DATA

(1) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 30-35°C(2) The total power is given by the sum of the power absorbed by the compressors and by the fans(3) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 40-45°C(4) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 60-65°C(5) External air temperature 35°C; input water-evaporator output temperature 23-18°C(6) External air temperature 35°C; input water-evaporator output temperature 12-7°C

(7) Sound power levels calculated compliant to ISO 3744(8) Sound pressure levels refer to 10 meters from unit in free field and directionality factor Q=2(9) Values compliant with EN 14511-3:2011This board reports the feature data of the base and standard versions; for details, refer to the specific documentation.

52 62 72 82 92

(1) kW 45,6 53,4 60,6 70,6 77,0(1), (2) kW 10,9 12,1 13,9 16,3 17,9

(1) 4,18 4,40 4,37 4,34 4,30A A A A A

(3) kW 44,3 52,0 59,1 68,3 75,1(3), (2) kW 13,1 14,9 17,2 20,0 21,8

(3) 3,38 3,50 3,43 3,41 3,44A A A A A

(1), (9) kW 45,9 53,7 60,9 71,0 77,4(1), (9) 4,11 4,32 4,30 4,26 4,23

A A A A A(3), (9) kW 44,6 52,3 59,4 68,6 75,5(3), (9) 3,34 3,45 3,39 3,37 3,39

A A A A A

(5) kW 54,3 64,5 73,6 83,6 91,4(5), (2) kW 14,8 16,5 20,0 22,0 25,3

(5) 3,67 3,90 3,68 3,79 3,62B A B B C

(6) kW 40,5 48,2 55,0 62,5 68,8(6),(2) kW 13,6 15,1 18,4 20,5 23,2

(6) 2,97 3,18 2,99 3,06 2,97B A B B B

(5), (9) kW 54,0 64,2 73,2 83,2 91,1(5), (9) 3,59 3,81 3,61 3,72 3,55

C A C B C(6), (9) kW 40,2 47,9 54,7 62,2 68,4(6), (9) 2,90 3,10 2,93 2,99 2,91

C A B B B

n° / n° 2/1 2/1 2/1 2/1 2/1n° 2 2 2 2 2kg 3,6 6,8 6,8 6,8 6,8kg 15,2 17,8 20,2 23,5 25,7

n° 1 1 1 1 1m3/h 18.000 17.000 17.000 24.000 24.000

(1) l/h 7.844 9.176 10.416 12.146 13.248(1) kPa 33 35 33 35 36

P5 P5 P5 P5 P5kPa 162 156 154 145 138

(7) dB(A) 73 73 74 75 77(8) dB(A) 42 42 43 44 46

mm 1.403 1.403 1.403 1.403 1.403mm 1.203 1.203 1.203 1.203 1.203mm 2.390 2.390 2.390 2.390 2.390kg 575 592 602 620 631

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

22

Unit size 7 9 11 13 17 22 26 32 36 41Heating (Gross values)Nominal heating capacity (A7;W35)Heating absorbed powerCOPEfficiency ClassNominal heating capacity (A7;W45)Heating absorbed powerCOPEfficiency ClassHeating (EN14511 values)Nominal heating capacity (A7;W35)COPEfficiency ClassNominal heating capacity (A7;W45)COPEfficiency ClassCooling (Gross values)Nominal cooling capacity (A35;W18)Cooling absorbed powerEEREfficiency ClassNominal cooling capacity (A35;W7)Cooling absorbed powerEEREfficiency ClassCooling (EN14511 values)Nominal cooling capacity (A35;W18)EEREfficiency ClassNominal cooling capacity (A35;W7)EEREfficiency ClassCompressorType ScrollQuantity/Cooling circuitsCapacity controlTotal oil loadTotal refrigerant loadFansType AxialQuantityAir flow rateUser side exchangerType PlatesWater flow ratePressure dropHydraulic modulePump modelUseful pump headStorage tank capacityExpansion tank NoiseSound power levelNoise pressure levelDimensions and weightLengthDepthHeightOperating weight

MAROON 2 HT TECHNICAL DATA

(1) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 30-35°C(2) The total power is given by the sum of the power absorbed by the compressors and by the fans(3) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 40-45°C(4) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 60-65°C(5) External air temperature 35°C; input water-evaporator output temperature 23-18°C(6) External air temperature 35°C; input water-evaporator output temperature 12-7°C

(7) Sound power levels calculated compliant to ISO 3744(8) Sound pressure levels refer to 10 meters from unit in free field and directionality factor Q=2(9) Values compliant with EN 14511-3:2011This board reports the feature data of the base and standard versions; for details, refer to the specific documentation.

(1) kW 6,8 8,4 10,8 13,0 16,0 21,0 25,0 29,7 34,3 37,4(1), (2) kW 1,6 2,0 2,5 3,0 3,7 4,9 5,8 7,1 8,1 8,9

(1) 4,19 4,33 4,32 4,30 4,30 4,28 4,29 4,21 4,24 4,19A A A A A A A A A A

(3) kW 6,6 8,3 10,5 13,2 16,3 21,2 25,3 30,7 33,1 38,0(3), (2) kW 1,9 2,4 3,1 3,8 4,6 6,1 7,3 8,8 10,1 11,0

(3) 3,38 3,45 3,39 3,52 3,51 3,46 3,46 3,49 3,28 3,46A A A A A A A A A A

(1), (9) kW 6,8 8,5 10,8 13,1 16,1 21,1 25,2 29,9 34,5 37,6(1), (9) 4,15 4,30 4,28 4,19 4,20 4,18 4,19 4,13 4,16 4,13

A A A A A A A A A A(3), (9) kW 6,6 8,3 10,5 13,3 16,4 21,4 25,5 30,8 33,3 38,2(3), (9) 3,38 3,45 3,39 3,52 3,51 3,46 3,46 3,49 3,28 3,46

A A A A A A A A A A

(5) kW 8,3 10,4 13,3 15,4 18,6 25,2 29,9 38,1 41,9 48,4(5), (2) kW 2,0 2,6 3,4 3,8 4,6 6,3 7,4 9,7 10,4 12,3

(5) 4,24 4,07 3,88 4,10 4,03 4,02 4,05 3,91 4,05 3,95A A A A A A A A A A

(6) kW 6,1 7,7 10,1 12,1 14,5 19,8 23,1 29,9 34,0 37,8(6),(2) kW 1,9 2,4 3,2 3,7 4,5 6,1 7,0 9,2 10,1 11,5

(6) 3,24 3,18 3,15 3,29 3,24 3,25 3,33 3,26 3,38 3,27A A A A A A A A A A

(5), (9) kW 8,2 10,4 13,3 15,3 18,5 25,1 29,7 37,9 41,7 48,2(5), (9) 4,19 4,03 3,84 3,96 3,91 3,89 3,93 3,82 3,95 3,88

A A A A A A A A A A(6), (9) kW 6,0 7,7 10,0 12,0 14,4 19,6 22,9 29,8 33,8 37,6(6), (9) 3,20 3,15 3,11 3,17 3,14 3,14 3,22 3,18 3,29 3,20

A A A A A A A A A A

n° / n° 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1 1 / 1n° 1 1 1 1 1 1 1 1 1 1kg 0,7 1,2 1,2 1,2 1,2 1,9 3,4 3,4 3,4 3,4kg 2,6 3,5 4,2 6,2 7,0 8,4 9,1 10,7 12,4 13,5

n° 1 1 1 1 1 2 2 2 2 2m3/h 3.800 3.800 3.500 7.600 7.600 13.000 13.000 16.000 16.000 16.000

(1) l/h 1.166 1.451 1.856 2.239 2.750 3.603 4.298 5.109 5.895 6.439(1) kPa 4 4 6 31 28 35 36 30 31 26

P1 P1 P1 P2 P2 P3 P3 P3 P4 P4kPa 67 65 59 63 62 137 120 106 178 175

l 70 70 70 70 70 130 130 130 130 130l 2 2 2 2 2 5 5 5 5 5

(7) dB(A) 63 63 64 66 67 70 70 75 75 75(8) dB(A) 32 32 33 35 36 39 39 44 44 44

mm 1.105 1.105 1.105 1.105 1.105 1.105 1.105 1.305 1.305 1.305mm 505 505 505 505 505 505 505 505 505 505mm 982 982 982 982 982 1.385 1.385 1.585 1.585 1.585kg 108 112 118 124 133 232 251 385 405 416

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

23

Unit size 50 60 70 80 90Heating (Gross values)Nominal heating capacity (A7;W35)Heating absorbed powerCOPEfficiency ClassNominal heating capacity (A7;W45)Heating absorbed powerCOPEfficiency ClassHeating (EN14511 values)Nominal heating capacity (A7;W35)COPEfficiency ClassNominal heating capacity (A7;W45)COPEfficiency ClassCooling (Gross values)Nominal cooling capacity (A35;W18)Cooling absorbed powerEEREfficiency ClassNominal cooling capacity (A35;W7)Cooling absorbed powerEEREfficiency ClassCooling (EN14511 values)Nominal cooling capacity (A35;W18)EEREfficiency ClassNominal cooling capacity (A35;W7)EEREfficiency ClassCompressorType ScrollQuantity/Cooling circuitsCapacity controlTotal oil loadTotal refrigerant loadFansType AxialQuantityAir flow rateUser side exchangerType PlatesWater flow ratePressure dropHydraulic modulePump modelUseful pump headNoiseSound power levelNoise pressure levelDimensions and weightLengthDepthHeightOperating weight

MAROON 2 HT TECHNICAL DATA

(1) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 30-35°C(2) The total power is given by the sum of the power absorbed by the compressors and by the fans(3) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 40-45°C(4) External air temperature 7°C DB, 6°C WB; condenser input-output temperature 60-65°C(5) External air temperature 35°C; input water-evaporator output temperature 23-18°C(6) External air temperature 35°C; input water-evaporator output temperature 12-7°C

(7) Sound power levels calculated compliant to ISO 3744(8) Sound pressure levels refer to 10 meters from unit in free field and directionality factor Q=2(9) Values compliant with EN 14511-3:2011This board reports the feature data of the base and standard versions; for details, refer to the specific documentation.

(1) kW 41,8 50,3 55,9 69,3 76,2(1), (2) kW 9,7 11,5 13,3 16,1 17,8

(1) 4,31 4,38 4,20 4,30 4,27A A A A A

(3) kW 42,4 51,1 57,7 70,7 77,5(3), (2) kW 12,2 14,4 16,8 20,0 22,0

(3) 3,48 3,54 3,43 3,53 3,52A A A A A

(1), (9) kW 42,0 50,5 56,2 69,7 76,5(1), (9) 4,23 4,30 4,14 4,23 4,20

A A A A A(3), (9) kW 42,6 51,4 57,9 71,0 77,9(3), (9) 3,48 3,54 3,43 3,53 3,52

A A A A A

(5) kW 49,7 57,9 71,9 80,9 93,1(5), (2) kW 13,1 15,4 19,2 21,2 25,1

(5) 3,80 3,77 3,74 3,81 3,70A B B A B

(6) kW 39,2 44,9 55,7 63,9 72,9(6),(2) kW 12,5 14,5 18,0 20,5 23,5

(6) 3,13 3,09 3,10 3,12 3,10A B B A A

(5), (9) kW 49,5 57,7 71,6 80,5 92,8(5), (9) 3,72 3,69 3,68 3,74 3,64

B B B B C(6), (9) kW 39,0 44,6 55,4 63,6 72,5(6), (9) 3,06 3,01 3,04 3,06 3,04

B B B B B

n° / n° 2/1 2/1 2/1 2/1 2/1n° 2 2 2 2 2kg 3,8 6,8 6,8 6,8 6,8kg 14,0 18,0 19,0 23,0 25,0

n° 1 1 1 1 1m3/h 18.000 17.000 17.000 24.000 24.000

(1) l/h 7.192 8.647 9.620 11.924 13.097(1) kPa 30 32 29 34 34

P5 P5 P5 P5 P5kPa 167 161 160 146 141

(7) dB(A) 73 73 74 75 77(8) dB(A) 42 42 43 44 46

mm 1.403 1.403 1.403 1.403 1.403mm 1.203 1.203 1.203 1.203 1.203mm 2.390 2.390 2.390 2.390 2.390kg 575 592 602 620 631

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

24

Unit size 8 10 12 16 18 20 23 25 29 34 38 42

Maximum absorbed power

Maximum absorbed current

Maximum current at peak

Maximum current at peak with soft-starterFan nominal powerFan nominal currentPump motor nominal powerPump motor nominal currentElectric power supplyOptional power supply

Unit size 52 62 72 82 92

Maximum absorbed power

Maximum absorbed current

Maximum current at peak

Maximum current at peak with soft-starterFan nominal powerFan nominal currentPump motor nominal powerPump motor nominal currentElectric power supplyOptional power supply

MAROON 2 MT ELECTRICAL DATA

MAROON 2 MT ELECTRICAL DATA

(1) Electric power that must be available from the electric network for the unit to work.(2) Current at which the units' internal protections intervene. It is the maximum current absor-bed by the unit. This value must never be exceeded and must be taken into account when sizing the line and the relative protection devices (see the wiring diagram supplied with the units).(3) The values between brackets refer to the ST version units with the maximum number of

pumps available (with or without storage tank).(4) Maximum peak current calculated considering the compressor start-up with higher power and maximum current absorbed by all other devices.This board reports the feature data of the base and standard versions; for details, refer to the specific documentation.

(1),(3) kW3,1 3,9 4,5 6,3 6,4 7,6 8,9 9,6 11,2 12,9 14,2 15,93,3 4,1 4,7 6,7 6,8 8,0 9,5 10,2 11,8 13,5 14,8 16,8

(2),(3) A16,7 19,7 8,7 11,5 13,3 16,5 18,4 19,4 26,0 27,0 30,0 36,0(17,7) (20,7) (9,7) (13,5) (15,3) (18,5) (21,2) (22,2) (28,8) (29,8) (32,8) (38,6)

(4) A61,7 82,7 48,7 65,5 65,5 75,5 104,4 98,4 116,0 123,0 123,0 145,0

(62,7) (83,7) (49,7) (67,5) (67,5) (77,5) (107,2) (101,2) (118,8) (125,8) (125,8) (147,6)

(4) A37,0 49,6 29,2 39,3 39,3 45,3 62,6 59,0 69,6 73,8 73,8 87,0

(37,6) (50,2) (29,8) (40,5) (40,5) (46,5) (64,3) (60,7) (71,3) (75,5) (75,5) (88,6)n° x kW 1 x 0,2 1 x 0,2 1 x 0,2 2 x 0,2 2 x 0,2 2 x 0,2 2 x 0,3 2 x 0,3 2 x 0,6 2 x 0,6 2 x 0,6 2 x 0,6n° x A 1 x 0,7 1 x 0,7 1 x 0,7 2 x 0,7 2 x 0,7 2 x 0,7 2 x 1,7 2 x 1,7 2 x 2,5 2 x 2,5 2 x 2,5 2 x 2,5kW 0,21 0,21 0,21 0,42 0,42 0,42 0,62 0,62 0,62 0,62 0,62 0,90A 1,00 1,00 1,00 2,00 2,00 2,00 2,77 2,77 2,77 2,77 2,77 2,61

V/ph/Hz 230/1~/50 230/1~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50

V/ph/Hz 400/3N~/50 400/3N~/50 230/1~/50 230/1~/50 - - - - - - - -

(1),(3) kW18,4 21,7 25,0 29,1 31,419,8 23,1 26,4 30,5 32,8

(2),(3) A34,9 44,5 46,5 54,7 66,7(37,6) (47,2) (49,2) (57,4) (69,4)

(4) A119,7 134,5 142,5 147,7 175,7(122,4) (137,2) (145,2) (150,4) (178,4)

(4) A71,8 80,7 85,5 88,6 105,4(73,4) (82,3) (87,1) (90,2) (107,0)

n° x kW 1 x 1,3 1 x 1,3 1 x 1,3 1 x 2,1 1 x 2,1n° x A 1 x 2,5 1 x 2,5 1 x 2,5 1 x 4,7 1 x 4,7kW 1,43 1,43 1,43 1,43 1,43A 2,70 2,70 2,70 2,70 2,70

V/ph/Hz 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50

V/ph/Hz

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

25

Unit size 7 9 11 13 17 22 26 32 36 41

Maximum absorbed power

Maximum absorbed current

Maximum current at peak

Maximum current at peak with soft-starterFan nominal powerFan nominal currentPump motor nominal powerPump motor nominal currentElectric power supplyOptional power supply

Unit size 50 60 70 80 90

Maximum absorbed power

Maximum absorbed current

Maximum current at peak

Maximum current at peak with soft-starterFan nominal powerFan nominal currentPump motor nominal powerPump motor nominal currentElectric power supplyOptional power supply

MAROON 2 HT ELECTRICAL DATA

MAROON 2 HT ELECTRICAL DATA

(1) Electric power that must be available from the electric network for the unit to work.(2) Current at which the units' internal protections intervene. It is the maximum current absor-bed by the unit. This value must never be exceeded and must be taken into account when sizing the line and the relative protection devices (see the wiring diagram supplied with the units).(3) The values between brackets refer to the ST version units with the maximum number of

pumps available (with or without storage tank).(4) Maximum peak current calculated considering the compressor start-up with higher power and maximum current absorbed by all other devices.This board reports the feature data of the base and standard versions; for details, refer to the specific documentation.

(1),(3) kW2,9 3,6 4,6 5,8 7,1 9,7 13,4 13,9 15,7 17,43,1 3,8 4,8 6,3 7,6 10,3 14,0 14,5 16,6 18,3

(2),(3) A13,5 6,9 7,9 11,7 13,4 19,4 32,4 34,0 39,5 44,0(14,5) (7,9) (8,9) (13,7) (15,4) (22,2) (35,2) (36,8) (42,1) (46,6)

(4) A60,7 43,7 52,2 54,0 72,5 104,4 121,4 123,0 145,0 179,0(61,7) (44,7) (53,2) (56,0) (74,5) (107,2) (124,2) (125,8) (147,6) (181,6)

(4) A36,4 26,2 31,3 32,4 43,5 62,6 72,8 73,8 87,0 107,4(37,0) (26,8) (31,9) (33,6) (44,7) (64,3) (74,5) (75,5) (88,6) (109,0)

n° x kW 1 x 0,2 1 x 0,2 1 x 0,2 1 x 0,6 1 x 0,6 2 x 0,3 2 x 0,3 2 x 0,6 2 x 0,6 2 x 0,6n° x A 1 x 0,7 1 x 0,7 1 x 0,7 1 x 2,5 1 x 2,5 2 x 1,7 2 x 1,7 2 x 2,5 2 x 2,5 2 x 2,5kW 0,21 0,21 0,21 0,42 0,42 0,62 0,62 0,62 0,90 0,90A 1,00 1,00 1,00 2,00 2,00 2,77 2,77 2,77 2,61 2,61

V/ph/Hz 230/1~/50 230/1~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50 400/3N~/50

V/ph/Hz - - 230/1~/50 - - - - - - -

(1),(3) kW19,5 26,8 26,8 31,3 34,720,9 28,2 28,2 32,7 36,1

(2),(3) A34,5 60,5 60,5 73,7 82,7(37,2) (63,2) (63,2) (76,4) (85,4)

(4) A119,5 149,5 149,5 179,2 217,7(122,2) (152,2) (152,2) (181,9) (220,4)

(4) A71,7 89,7 89,7 107,5 130,6

(73,3) (91,3) (91,3) (109,1) (132,2)n° x kW 1 x 1,3 1 x 1,3 1 x 1,3 1 x 2,1 1 x 2,1n° x A 1 x 2,5 1 x 2,5 1 x 2,5 1 x 4,7 1 x 4,7kW 1,43 1,43 1,43 1,43 1,43A 2,70 2,70 2,70 2,70 2,70

V/ph/Hz 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50

V/ph/Hz

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

26

0

50

100

150

200

250

0 1.000 2.000 3.000 4.000 5.000 6.000 7.000 8.000 9.000 10.000

P2 P3

P4

P1

0

10

20

30

40

50

60

70

80

90

100

0 1000 2000 3000 4000 5000 6000 7000 8000 9000

8

18 23

20

1610-12-29

42

34

38

STA

TIC

HEA

D [k

Pa]

CAPACITY [l/h]

CAPACITY [l/h]

PRES

SURE

DRO

PS [k

Pa]

EXCHANGER DIAGRAMS - MAROON 2 MT

PUMP DIAGRAMS - MAROON 2 MT

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

27

0

50

100

150

200

250

5.000 6.000 7.000 8.000 9.000 10.000 11.000 12.000 13.000 14.000 15.000

P5

0

10

20

30

40

50

60

70

80

90

100

5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000

92

62

82

72

52

STA

TIC

HEA

D [k

Pa]

CAPACITY [l/h]

CAPACITY [l/h]

PRES

SURE

DRO

PS [k

Pa]

EXCHANGER DIAGRAMS - MAROON 2 MT

PUMP DIAGRAMS - MAROON 2 MT

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

28

0

50

100

150

200

250

0 1.000 2.000 3.000 4.000 5.000 6.000 7.000 8.000 9.000 10.000

P2 P3

P4

P1

0

10

20

30

40

50

60

70

80

90

100

0 1000 2000 3000 4000 5000 6000 7000 8000 9000

139

17 117 22

36

26

32

41

STA

TIC

HEA

D [k

Pa]

CAPACITY [l/h]

CAPACITY [l/h]

PRES

SURE

DRO

PS [k

Pa]

EXCHANGER DIAGRAMS - MAROON 2 HT

PUMP DIAGRAMS - MAROON 2 HT

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

29

0

50

100

150

200

250

5.000 6.000 7.000 8.000 9.000 10.000 11.000 12.000 13.000 14.000 15.000

P5

0

10

20

30

40

50

60

70

80

90

100

5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000

90

60

80

70

50

STA

TIC

HEA

D [k

Pa]

CAPACITY [l/h]

CAPACITY [l/h]

PRES

SURE

DRO

PS [k

Pa]

EXCHANGER DIAGRAMS - MAROON 2 HT

PUMP DIAGRAMS - MAROON 2 HT

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

30

25

30

35

40

45

50

55

60

65

-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50

-10

-5

0

5

10

15

20

25

-15 -10 -5 0 5 10 15 20 25 30 35 40 45 50

25

30

35

40

45

50

55

60

-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50

Notes: The thermal gradient to the utility side exchanger must be between 3°C and 6°C : the unit can only operate in this area with evaporator side glycol water

Util

ity

outle

t w

ater

tem

pera

ture

(°C

)U

tilit

y ou

tlet

wat

er t

empe

ratu

re (°

C)

Util

ity

outle

t w

ater

tem

pera

ture

(°C

)

HEATING

COOLING

RECOVERY

External air temperature (°C)

External air temperature (°C)

External air temperature (°C)

OPERATING LIMITS - MAROON 2 MT

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

31

25

30

35

40

45

50

55

60

65

70

-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50

-10

-5

0

5

10

15

20

25

-15 -10 -5 0 5 10 15 20 25 30 35 40 45 50

25

30

35

40

45

50

55

60

65

-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50

Notes: The thermal gradient to the utility side exchanger must be between 3°C and 6°C : the unit can only operate in this area with evaporator side glycol water : limit for models 7, 9 and 11

Util

ity

outle

t w

ater

tem

pera

ture

(°C

)U

tilit

y ou

tlet

wat

er t

empe

ratu

re (°

C)

Util

ity

outle

t w

ater

tem

pera

ture

(°C

)

HEATING

COOLING

RECOVERY

External air temperature (°C)

External air temperature (°C)

External air temperature (°C)

OPERATING LIMITS - MAROON 2 HT

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

32

COOLING CAPACITIES - MAROON 2 MT

Pf: Cooling power [kW]

Pa: Total absorbed compressor power [kW]

To: Utility outlet water temperature to the utility exchanger [°C]

Model

To External air temperature [°C]

[°C]25 30 35 40

Pf Pat EER Pf Pat EER Pf Pat EER Pf Pat EER

8

5 6,5 1,7 3,82 6,2 1,9 3,24 5,8 2,1 2,71 5,4 2,4 2,256 6,7 1,7 3,92 6,4 1,9 3,33 6,0 2,1 2,80 5,6 2,4 2,337 6,9 1,7 4,04 6,6 1,9 3,43 6,2 2,1 2,87 5,7 2,4 2,408 7,2 1,7 4,14 6,8 1,9 3,52 6,4 2,1 2,97 5,9 2,4 2,469 7,4 1,7 4,27 7,0 1,9 3,62 6,6 2,2 3,04 6,1 2,4 2,5410 7,6 1,7 4,37 7,2 1,9 3,71 6,8 2,2 3,13 6,3 2,4 2,6113 8,3 1,8 4,70 7,8 2,0 3,99 7,4 2,2 3,38 6,9 2,4 2,8314 8,5 1,8 4,80 8,1 2,0 4,09 7,6 2,2 3,46 7,1 2,4 2,9015 8,7 1,8 4,91 8,3 2,0 4,18 7,8 2,2 3,54 7,3 2,4 2,9716 9,0 1,8 5,02 8,5 2,0 4,30 8,0 2,2 3,63 7,5 2,5 3,0417 9,2 1,8 5,13 8,7 2,0 4,39 8,2 2,2 3,71 7,7 2,5 3,1318 9,5 1,8 5,23 9,0 2,0 4,49 8,5 2,2 3,80 7,9 2,5 3,20

10

5 8,1 2,0 4,09 7,6 2,2 3,42 7,1 2,5 2,84 6,6 2,8 2,336 8,3 2,0 4,20 7,8 2,2 3,51 7,3 2,5 2,92 6,8 2,8 2,407 8,6 2,0 4,30 8,1 2,2 3,61 7,5 2,5 3,00 7,0 2,8 2,468 8,8 2,0 4,41 8,3 2,2 3,70 7,8 2,5 3,07 7,2 2,8 2,539 9,1 2,0 4,51 8,6 2,3 3,78 8,0 2,5 3,15 7,4 2,9 2,5910 9,3 2,0 4,62 8,8 2,3 3,88 8,2 2,5 3,23 7,6 2,9 2,6613 10,1 2,1 4,91 9,5 2,3 4,13 8,9 2,6 3,45 8,3 2,9 2,8614 10,4 2,1 5,02 9,8 2,3 4,23 9,2 2,6 3,53 8,5 2,9 2,9315 10,7 2,1 5,11 10,1 2,3 4,30 9,4 2,6 3,61 8,8 2,9 2,9916 11,0 2,1 5,21 10,3 2,4 4,40 9,7 2,6 3,68 9,0 2,9 3,0617 11,3 2,1 5,31 10,6 2,4 4,48 9,9 2,6 3,77 9,2 3,0 3,1318 11,6 2,1 5,42 10,9 2,4 4,57 10,2 2,7 3,83 9,5 3,0 3,19

12

5 10,3 2,3 4,41 9,7 2,6 3,77 9,1 2,8 3,19 8,4 3,2 2,656 10,6 2,3 4,52 10,0 2,6 3,86 9,3 2,9 3,26 8,7 3,2 2,727 10,9 2,4 4,62 10,3 2,6 3,94 9,6 2,9 3,34 8,9 3,2 2,788 11,2 2,4 4,73 10,6 2,6 4,02 9,9 2,9 3,41 9,2 3,2 2,859 11,5 2,4 4,83 10,9 2,6 4,12 10,2 2,9 3,48 9,5 3,3 2,9010 11,9 2,4 4,92 11,2 2,7 4,21 10,5 2,9 3,56 9,7 3,3 2,9713 12,9 2,5 5,22 12,1 2,7 4,46 11,4 3,0 3,78 10,6 3,3 3,1714 13,2 2,5 5,32 12,5 2,7 4,54 11,7 3,0 3,86 10,9 3,4 3,2315 13,6 2,5 5,41 12,8 2,8 4,63 12,0 3,1 3,92 11,1 3,4 3,2916 13,9 2,5 5,51 13,1 2,8 4,70 12,3 3,1 4,00 11,4 3,4 3,3617 14,3 2,5 5,60 13,5 2,8 4,79 12,6 3,1 4,07 11,7 3,4 3,4118 14,6 2,6 5,68 13,8 2,8 4,88 13,0 3,1 4,14 12,0 3,5 3,48

16

5 14,0 3,4 4,16 13,2 3,7 3,57 12,5 4,1 3,02 11,6 4,6 2,516 14,4 3,4 4,25 13,6 3,7 3,66 12,9 4,1 3,10 12,0 4,6 2,587 14,8 3,4 4,35 14,0 3,8 3,74 13,2 4,2 3,17 12,3 4,7 2,658 15,2 3,4 4,44 14,4 3,8 3,82 13,6 4,2 3,26 12,7 4,7 2,729 15,6 3,4 4,54 14,8 3,8 3,91 14,0 4,2 3,33 13,1 4,7 2,7910 16,1 3,5 4,63 15,3 3,8 3,99 14,4 4,2 3,40 13,4 4,7 2,8513 17,4 3,6 4,89 16,5 3,9 4,23 15,6 4,3 3,61 14,6 4,8 3,0514 17,8 3,6 4,97 17,0 3,9 4,31 16,0 4,3 3,69 15,0 4,8 3,1115 18,3 3,6 5,07 17,4 4,0 4,39 16,4 4,4 3,76 15,4 4,8 3,1716 18,8 3,7 5,14 17,9 4,0 4,46 16,9 4,4 3,83 15,8 4,9 3,2417 19,3 3,7 5,22 18,3 4,0 4,53 17,3 4,4 3,90 16,2 4,9 3,3018 19,7 3,7 5,31 18,8 4,1 4,61 17,7 4,5 3,96 16,6 4,9 3,36

18

5 15,0 3,7 4,01 14,1 4,1 3,46 13,2 4,5 2,96 12,2 4,9 2,506 15,4 3,7 4,12 14,6 4,1 3,56 13,7 4,5 3,05 12,7 4,9 2,587 15,9 3,8 4,23 15,0 4,1 3,66 14,1 4,5 3,13 13,1 4,9 2,658 16,4 3,8 4,34 15,5 4,1 3,75 14,5 4,5 3,22 13,5 4,9 2,739 16,9 3,8 4,45 16,0 4,1 3,85 15,0 4,5 3,31 13,9 5,0 2,8110 17,4 3,8 4,57 16,4 4,2 3,96 15,4 4,5 3,40 14,4 5,0 2,8913 18,9 3,8 4,91 17,9 4,2 4,26 16,8 4,6 3,66 15,7 5,0 3,1214 19,4 3,9 5,02 18,4 4,2 4,37 17,3 4,6 3,76 16,1 5,0 3,2015 19,9 3,9 5,14 18,9 4,2 4,47 17,8 4,6 3,85 16,6 5,1 3,2916 20,5 3,9 5,27 19,5 4,2 4,58 18,3 4,6 3,94 17,1 5,1 3,3717 21,1 3,9 5,38 20,0 4,3 4,68 18,8 4,7 4,05 17,6 5,1 3,4618 21,6 3,9 5,51 20,5 4,3 4,79 19,4 4,7 4,14 18,1 5,1 3,54

20

5 17,6 4,1 4,28 16,7 4,5 3,68 15,7 5,0 3,15 14,6 5,5 2,666 18,2 4,2 4,37 17,2 4,6 3,77 16,2 5,0 3,22 15,1 5,5 2,727 18,7 4,2 4,46 17,7 4,6 3,85 16,7 5,1 3,29 15,5 5,6 2,798 19,2 4,2 4,56 18,2 4,6 3,93 17,1 5,1 3,37 16,0 5,6 2,859 19,8 4,3 4,64 18,7 4,7 4,01 17,6 5,1 3,43 16,5 5,7 2,9110 20,3 4,3 4,73 19,3 4,7 4,10 18,1 5,2 3,50 16,9 5,7 2,9713 22,1 4,4 5,01 20,9 4,8 4,34 19,7 5,3 3,72 18,4 5,8 3,1614 22,7 4,4 5,10 21,5 4,9 4,42 20,2 5,3 3,79 18,9 5,9 3,2215 23,3 4,5 5,19 22,0 4,9 4,50 20,8 5,4 3,87 19,4 5,9 3,2916 23,9 4,5 5,28 22,6 4,9 4,58 21,3 5,4 3,94 19,9 6,0 3,3517 24,5 4,6 5,38 23,2 5,0 4,66 21,9 5,5 4,00 20,5 6,0 3,4118 25,1 4,6 5,46 23,8 5,0 4,74 22,5 5,5 4,08 21,0 6,0 3,48

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

33

COOLING CAPACITIES - MAROON 2 MT

Pf: Cooling power [kW]

Pa: Total absorbed compressor power [kW]

To: Utility outlet water temperature to the utility exchanger [°C]

Model

To External air temperature [°C]

[°C]25 30 35 40

Pf Pat EER Pf Pat EER Pf Pat EER Pf Pat EER

23

5 20,0 4,9 4,05 18,9 5,4 3,50 17,8 5,9 2,99 16,6 6,6 2,536 20,5 5,0 4,14 19,5 5,4 3,58 18,4 6,0 3,07 17,2 6,6 2,607 21,2 5,0 4,23 20,1 5,5 3,66 18,9 6,0 3,14 17,7 6,7 2,668 21,8 5,0 4,32 20,7 5,5 3,74 19,5 6,1 3,21 18,3 6,7 2,739 22,4 5,1 4,40 21,3 5,6 3,81 20,1 6,1 3,28 18,8 6,7 2,7910 23,1 5,1 4,48 21,9 5,6 3,89 20,7 6,2 3,35 19,4 6,8 2,8513 25,1 5,3 4,74 23,8 5,8 4,12 22,5 6,3 3,56 21,1 6,9 3,0514 25,7 5,3 4,82 24,5 5,8 4,21 23,2 6,4 3,63 21,7 7,0 3,1115 26,4 5,4 4,91 25,2 5,9 4,28 23,8 6,4 3,70 22,3 7,0 3,1716 27,2 5,4 4,99 25,9 5,9 4,36 24,5 6,5 3,78 23,0 7,1 3,2417 27,9 5,5 5,08 26,6 6,0 4,43 25,1 6,5 3,84 23,6 7,2 3,3018 28,6 5,6 5,15 27,3 6,0 4,51 25,8 6,6 3,92 24,3 7,2 3,36

25

5 22,0 5,3 4,14 20,8 5,9 3,55 19,5 6,4 3,02 18,1 7,1 2,546 22,7 5,4 4,23 21,4 5,9 3,64 20,1 6,5 3,10 18,6 7,2 2,607 23,3 5,4 4,33 22,1 5,9 3,72 20,7 6,5 3,17 19,2 7,2 2,678 24,0 5,4 4,42 22,7 6,0 3,82 21,3 6,6 3,25 19,8 7,2 2,749 24,7 5,5 4,51 23,4 6,0 3,90 22,0 6,6 3,33 20,4 7,3 2,8110 25,4 5,5 4,60 24,1 6,0 3,98 22,6 6,6 3,40 21,0 7,3 2,8713 27,5 5,7 4,88 26,1 6,2 4,22 24,6 6,8 3,63 22,9 7,5 3,0714 28,3 5,7 4,96 26,8 6,2 4,31 25,2 6,8 3,70 23,5 7,5 3,1415 29,0 5,8 5,04 27,6 6,3 4,39 25,9 6,9 3,77 24,2 7,5 3,2016 29,8 5,8 5,14 28,3 6,3 4,47 26,6 6,9 3,85 24,9 7,6 3,2717 30,6 5,9 5,21 29,0 6,4 4,55 27,4 7,0 3,92 25,5 7,6 3,3418 31,4 5,9 5,30 29,8 6,4 4,63 28,1 7,0 3,99 26,2 7,7 3,41

29

5 25,4 6,5 3,92 24,2 7,1 3,43 22,8 7,7 2,96 21,4 8,5 2,536 26,2 6,5 4,01 24,9 7,1 3,51 23,5 7,7 3,04 22,0 8,5 2,597 27,0 6,6 4,11 25,7 7,1 3,59 24,3 7,8 3,12 22,7 8,5 2,668 27,8 6,6 4,20 26,4 7,2 3,67 25,0 7,8 3,18 23,4 8,6 2,739 28,6 6,7 4,28 27,2 7,2 3,76 25,7 7,9 3,26 24,1 8,6 2,7910 29,4 6,7 4,38 27,9 7,3 3,84 26,4 7,9 3,33 24,8 8,7 2,8613 31,8 6,9 4,63 30,3 7,5 4,07 28,7 8,1 3,54 27,0 8,8 3,0514 32,7 6,9 4,71 31,1 7,5 4,14 29,4 8,2 3,60 27,7 8,9 3,1115 33,6 7,0 4,78 31,9 7,6 4,21 30,2 8,2 3,67 28,4 9,0 3,1716 34,4 7,1 4,86 32,8 7,7 4,28 31,0 8,3 3,74 29,2 9,0 3,2317 35,3 7,2 4,94 33,6 7,7 4,35 31,8 8,4 3,80 29,9 9,1 3,2918 36,2 7,2 5,00 34,5 7,8 4,41 32,7 8,5 3,86 30,7 9,2 3,34

34

5 31,3 7,3 4,30 29,6 8,0 3,71 27,7 8,8 3,16 25,7 9,6 2,666 32,2 7,3 4,39 30,4 8,0 3,80 28,5 8,8 3,24 26,5 9,7 2,737 33,1 7,4 4,49 31,4 8,1 3,89 29,4 8,9 3,32 27,3 9,7 2,818 34,1 7,4 4,59 32,3 8,1 3,97 30,3 8,9 3,40 28,1 9,8 2,879 35,0 7,5 4,68 33,2 8,2 4,06 31,2 9,0 3,48 29,0 9,8 2,9410 36,0 7,5 4,78 34,1 8,2 4,15 32,1 9,0 3,55 29,8 9,9 3,0113 39,0 7,7 5,05 37,0 8,4 4,40 34,8 9,2 3,78 32,4 10,1 3,2114 40,0 7,8 5,14 38,0 8,5 4,48 35,7 9,3 3,86 33,3 10,1 3,2815 41,1 7,8 5,23 39,0 8,5 4,56 36,7 9,3 3,94 34,2 10,2 3,3516 42,1 7,9 5,32 40,0 8,6 4,65 37,7 9,4 4,01 35,1 10,3 3,4217 43,2 8,0 5,41 41,0 8,7 4,73 38,7 9,5 4,09 36,1 10,3 3,4918 44,3 8,1 5,49 42,1 8,8 4,81 39,6 9,5 4,16 37,0 10,4 3,55

38

5 34,0 8,5 4,02 32,3 9,3 3,48 30,3 10,2 2,97 28,2 11,3 2,506 35,0 8,5 4,11 33,2 9,3 3,56 31,2 10,3 3,04 29,0 11,3 2,567 36,1 8,6 4,21 34,2 9,4 3,65 32,2 10,3 3,12 29,9 11,4 2,638 37,1 8,6 4,30 35,2 9,4 3,72 33,1 10,4 3,19 30,8 11,5 2,699 38,1 8,7 4,39 36,2 9,5 3,81 34,0 10,4 3,26 31,7 11,5 2,7510 39,2 8,8 4,48 37,2 9,6 3,89 35,0 10,5 3,33 32,6 11,6 2,8113 42,5 9,0 4,74 40,3 9,8 4,13 38,0 10,7 3,54 35,4 11,8 3,0014 43,6 9,0 4,83 41,4 9,8 4,20 39,0 10,8 3,61 36,4 11,9 3,0615 44,7 9,1 4,92 42,5 9,9 4,28 40,0 10,9 3,68 37,3 11,9 3,1216 45,9 9,2 5,00 43,6 10,0 4,36 41,1 10,9 3,75 38,3 12,0 3,1917 47,1 9,3 5,09 44,7 10,1 4,44 42,1 11,0 3,82 39,3 12,1 3,2518 48,3 9,3 5,17 45,8 10,2 4,51 43,2 11,1 3,89 40,3 12,2 3,31

42

5 40,7 9,3 4,40 38,6 10,1 3,82 36,2 11,1 3,27 33,6 12,1 2,776 41,9 9,3 4,49 39,7 10,2 3,90 37,3 11,1 3,35 34,6 12,2 2,837 43,1 9,4 4,58 40,9 10,3 3,99 38,4 11,2 3,42 35,7 12,3 2,908 44,3 9,5 4,67 42,0 10,3 4,07 39,5 11,3 3,49 36,7 12,4 2,969 45,6 9,6 4,76 43,2 10,4 4,15 40,6 11,4 3,57 37,7 12,5 3,0310 46,8 9,7 4,85 44,4 10,5 4,23 41,7 11,5 3,64 38,8 12,6 3,0913 50,7 9,9 5,12 48,1 10,8 4,47 45,2 11,7 3,85 42,0 12,8 3,2814 52,1 10,0 5,20 49,4 10,9 4,55 46,4 11,8 3,92 43,2 12,9 3,3415 53,4 10,1 5,28 50,7 10,9 4,63 47,6 11,9 4,00 44,3 13,0 3,4116 54,8 10,2 5,37 52,0 11,1 4,70 48,9 12,0 4,07 45,5 13,1 3,4717 56,2 10,3 5,45 53,3 11,2 4,78 50,1 12,1 4,14 46,6 13,2 3,5318 57,7 10,4 5,53 54,7 11,3 4,85 51,4 12,2 4,21 47,8 13,3 3,59

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

34

HEATING CAPACITIES - MAROON 2 MT

Pt Heating capacity [kW]

Pa: Total absorbed compressor power [kW]

Ta: Dry bulb temperature of the evaporator inlet air [°C]

RH: Relative humidity of the input air at the evaporator [%]

Model

Ta RH Condenser inlet water temperature [°C]

[°C] %30/35 40/45 50/55 55/60

Pt Pat COP Pt Pat COP Pt Pat COP Pt Pat COP

8

-16 90 4,1 1,8 2,26 * * * * * * * * *-15 90 4,2 1,8 2,32 * * * * * * * * *-10 90 4,7 1,8 2,63 4,8 2,3 2,14 * * * * * *-7 89 5,0 1,8 2,86 5,1 2,2 2,30 * * * * * *-2 89 5,7 1,7 3,26 5,7 2,2 2,61 5,8 2,8 2,10 5,9 3,1 1,880 88 5,9 1,7 3,43 5,9 2,2 2,72 6,0 2,8 2,18 6,1 3,1 1,952 88 6,2 1,7 3,61 6,2 2,2 2,87 6,3 2,7 2,29 6,3 3,1 2,045 87 6,7 1,7 3,88 6,6 2,1 3,08 6,6 2,7 2,42 6,6 3,1 2,167 87 7,0 1,7 4,10 6,9 2,1 3,24 6,9 2,7 2,55 6,8 3,0 2,2610 86 7,5 1,7 4,44 7,4 2,1 3,48 7,3 2,7 2,73 7,2 3,0 2,3912 86 7,9 1,7 4,65 7,7 2,1 3,66 7,6 2,7 2,85 7,5 3,0 2,5215 86 8,5 1,7 5,04 8,2 2,1 3,93 8,0 2,6 3,06 7,9 3,0 2,68

10

-16 90 5,2 2,3 2,29 * * * * * * * * *-15 90 5,3 2,3 2,34 * * * * * * * * *-10 90 6,0 2,3 2,65 6,2 2,9 2,13 * * * * * *-7 89 6,4 2,2 2,88 6,6 2,9 2,30 * * * * * *-2 89 7,2 2,2 3,28 7,4 2,8 2,59 7,6 3,7 2,07 7,6 4,2 1,840 88 7,6 2,2 3,44 7,6 2,8 2,71 7,8 3,6 2,14 7,9 4,1 1,922 88 7,9 2,2 3,61 8,0 2,8 2,85 8,1 3,6 2,25 8,2 4,1 2,005 87 8,5 2,2 3,91 8,5 2,8 3,05 8,5 3,6 2,39 8,6 4,1 2,127 87 8,9 2,2 4,12 8,8 2,8 3,20 8,9 3,5 2,50 8,9 4,0 2,2210 86 9,6 2,1 4,46 9,4 2,7 3,44 9,4 3,5 2,67 9,4 4,0 2,3512 86 10,0 2,1 4,70 9,8 2,7 3,61 9,7 3,5 2,79 9,7 4,0 2,4515 86 10,8 2,1 5,07 10,6 2,7 3,91 10,3 3,5 2,98 10,3 3,9 2,61

12

-16 90 6,3 2,5 2,53 * * * * * * * * *-15 90 6,5 2,5 2,59 * * * * * * * * *-10 90 7,3 2,5 2,91 7,4 3,1 2,35 * * * * * *-7 89 7,9 2,5 3,13 7,9 3,1 2,52 * * * * * *-2 89 9,0 2,5 3,53 8,9 3,2 2,82 8,9 4,0 2,24 9,0 4,5 1,990 88 9,4 2,5 3,70 9,3 3,2 2,95 9,3 4,0 2,33 9,3 4,5 2,062 88 9,9 2,5 3,87 9,7 3,2 3,07 9,7 4,0 2,43 9,7 4,5 2,145 87 10,6 2,6 4,15 10,4 3,2 3,29 10,3 4,0 2,58 10,2 4,5 2,277 87 11,2 2,6 4,36 10,9 3,2 3,44 10,7 4,0 2,69 10,6 4,5 2,3610 86 12,0 2,6 4,68 11,7 3,2 3,69 11,4 4,0 2,87 11,3 4,5 2,5012 86 12,6 2,6 4,92 12,3 3,2 3,87 11,9 4,0 2,99 11,7 4,5 2,6115 86 13,5 2,6 5,28 13,2 3,2 4,13 12,7 4,0 3,20 12,5 4,5 2,79

16

-16 90 8,7 3,6 2,42 * * * * * * * * *-15 90 8,9 3,6 2,48 * * * * * * * * *-10 90 10,1 3,6 2,79 10,2 4,6 2,20 * * * * * *-7 89 10,9 3,6 3,00 10,9 4,6 2,37 * * * * * *-2 89 12,2 3,6 3,40 12,2 4,6 2,68 12,2 6,0 2,04 12,1 6,9 1,760 88 12,8 3,6 3,56 12,7 4,5 2,80 12,6 5,9 2,13 12,6 6,8 1,842 88 13,4 3,6 3,71 13,3 4,5 2,94 13,2 5,9 2,24 13,1 6,8 1,935 87 14,3 3,6 3,98 14,1 4,5 3,14 13,9 5,8 2,40 13,8 6,7 2,057 87 15,0 3,6 4,16 14,8 4,5 3,29 14,5 5,8 2,52 14,3 6,6 2,1710 86 16,1 3,6 4,45 15,7 4,5 3,52 15,4 5,7 2,69 15,1 6,6 2,3012 86 16,8 3,6 4,63 16,4 4,5 3,67 16,0 5,7 2,82 15,8 6,5 2,4315 86 18,1 3,6 4,98 17,6 4,5 3,93 17,1 5,7 3,02 16,7 6,5 2,60

18

-16 90 9,1 4,1 2,24 * * * * * * * * *-15 90 9,4 4,1 2,31 * * * * * * * * *-10 90 10,9 4,1 2,67 10,6 4,9 2,14 * * * * * *-7 89 11,9 4,1 2,91 11,5 4,9 2,34 * * * * * *-2 89 13,5 4,1 3,33 13,2 4,9 2,68 12,7 6,0 2,13 12,5 6,6 1,880 88 14,2 4,1 3,50 13,8 4,9 2,81 13,3 6,0 2,22 13,0 6,6 1,972 88 14,8 4,0 3,67 14,5 4,9 2,95 14,0 6,0 2,35 13,7 6,6 2,075 87 16,0 4,0 3,96 15,5 4,9 3,18 15,0 5,9 2,52 14,6 6,6 2,227 87 16,7 4,0 4,16 16,3 4,9 3,34 15,7 5,9 2,65 15,4 6,6 2,3410 86 18,1 4,0 4,50 17,4 4,8 3,60 16,8 5,9 2,84 16,4 6,6 2,5012 86 19,0 4,0 4,75 18,3 4,8 3,77 17,6 5,9 2,99 17,2 6,5 2,6315 86 20,4 4,0 5,12 19,7 4,8 4,10 18,8 5,9 3,21 18,3 6,5 2,82

20

-16 90 10,9 4,2 2,57 * * * * * * * * *-15 90 11,1 4,2 2,63 * * * * * * * * *-10 90 12,6 4,3 2,96 12,6 5,2 2,41 * * * * * *-7 89 13,7 4,3 3,18 13,6 5,3 2,58 * * * * * *-2 89 15,6 4,3 3,59 15,3 5,3 2,88 15,2 6,6 2,30 15,1 7,4 2,050 88 16,3 4,4 3,74 16,1 5,4 3,00 15,8 6,6 2,38 15,7 7,4 2,122 88 17,1 4,4 3,91 16,8 5,4 3,13 16,5 6,6 2,48 16,3 7,4 2,205 87 18,4 4,4 4,19 18,0 5,4 3,33 17,6 6,7 2,63 17,3 7,5 2,327 87 19,4 4,4 4,37 18,9 5,4 3,47 18,4 6,7 2,74 18,1 7,5 2,4210 86 20,9 4,5 4,67 20,2 5,5 3,71 19,6 6,7 2,90 19,3 7,5 2,5512 86 21,9 4,5 4,89 21,2 5,5 3,86 20,5 6,8 3,03 20,1 7,6 2,6615 86 23,7 4,5 5,23 22,8 5,5 4,14 21,9 6,8 3,22 21,4 7,6 2,82

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

35

Pt: Heating capacity [kW]

Pa: Total absorbed compressor power [kW]

Ta: Dry bulb temperature of the evaporator inlet air [°C]

RH: Relative humidity of the input air at the evaporator [%]

HEATING CAPACITIES - MAROON 2 MT

Model

Ta RH Condenser inlet water temperature [°C]

[°C] %30/35 40/45 50/55 55/60

Pt Pat COP Pt Pat COP Pt Pat COP Pt Pat COP

23

-16 90 12,3 4,9 2,52 * * * * * * * * *-15 90 12,7 4,9 2,59 * * * * * * * * *-10 90 14,4 5,0 2,91 14,4 6,1 2,35 * * * * * *-7 89 15,7 5,0 3,14 15,5 6,2 2,51 * * * * * *-2 89 17,9 5,1 3,54 17,6 6,2 2,82 17,4 7,8 2,24 17,5 8,7 2,000 88 18,7 5,1 3,69 18,3 6,3 2,92 18,1 7,8 2,33 18,1 8,7 2,072 88 19,7 5,1 3,85 19,3 6,3 3,07 19,0 7,8 2,43 18,9 8,8 2,165 87 21,1 5,2 4,10 20,6 6,3 3,27 20,1 7,8 2,57 20,0 8,8 2,287 87 22,2 5,2 4,29 21,7 6,3 3,41 21,2 7,9 2,70 20,9 8,8 2,3810 86 23,8 5,2 4,56 23,2 6,4 3,63 22,6 7,9 2,86 22,1 8,8 2,5112 86 25,0 5,3 4,75 24,3 6,4 3,79 23,6 7,9 2,98 23,3 8,8 2,6315 86 27,0 5,3 5,07 26,1 6,5 4,04 25,2 8,0 3,17 24,8 8,9 2,79

25

-16 90 13,2 5,5 2,42 * * * * * * * * *-15 90 13,6 5,5 2,48 * * * * * * * * *-10 90 15,6 5,5 2,83 15,5 6,9 2,26 * * * * * *-7 89 17,0 5,6 3,06 16,8 6,9 2,44 * * * * * *-2 89 19,5 5,6 3,48 19,1 6,9 2,76 18,7 8,6 2,18 18,6 9,7 1,930 88 20,4 5,6 3,64 19,9 6,9 2,88 19,5 8,6 2,26 19,4 9,7 2,002 88 21,4 5,6 3,81 20,9 6,9 3,02 20,4 8,6 2,37 20,2 9,7 2,095 87 23,0 5,6 4,09 22,4 6,9 3,23 21,7 8,6 2,52 21,4 9,7 2,217 87 24,2 5,6 4,28 23,5 6,9 3,39 22,8 8,6 2,65 22,4 9,7 2,3210 86 25,9 5,7 4,58 25,2 6,9 3,62 24,3 8,6 2,82 23,8 9,7 2,4612 86 27,2 5,7 4,79 26,4 7,0 3,79 25,4 8,6 2,95 24,9 9,6 2,5815 86 29,3 5,7 5,12 28,3 7,0 4,06 27,2 8,6 3,15 26,5 9,6 2,75

29

-16 90 15,3 6,7 2,30 * * * * * * * * *-15 90 15,7 6,7 2,36 * * * * * * * * *-10 90 18,0 6,7 2,69 17,8 8,2 2,17 * * * * * *-7 89 19,6 6,7 2,92 19,2 8,2 2,35 * * * * * *-2 89 22,3 6,7 3,32 21,9 8,2 2,69 21,4 10,1 2,11 21,2 11,4 1,860 88 23,4 6,7 3,48 22,8 8,2 2,80 22,3 10,1 2,21 22,1 11,4 1,942 88 24,6 6,7 3,65 24,1 8,2 2,96 23,5 10,1 2,33 23,2 11,3 2,055 87 26,5 6,8 3,91 25,8 8,2 3,17 25,0 10,0 2,49 24,7 11,3 2,197 87 27,8 6,8 4,10 27,1 8,2 3,32 26,3 10,0 2,63 25,9 11,2 2,3110 86 29,9 6,8 4,38 29,0 8,2 3,55 28,1 10,0 2,81 27,5 11,2 2,4612 86 31,3 6,8 4,57 30,4 8,2 3,71 29,4 10,0 2,94 28,9 11,2 2,5915 86 33,8 6,9 4,89 32,6 8,2 3,96 31,4 10,0 3,14 30,8 11,2 2,76

34

-16 90 18,0 7,5 2,39 * * * * * * * * *-15 90 18,5 7,5 2,45 * * * * * * * * *-10 90 21,2 7,6 2,79 21,0 9,3 2,24 * * * * * *-7 89 23,0 7,6 3,02 22,7 9,4 2,43 * * * * * *-2 89 26,2 7,6 3,43 25,7 9,4 2,74 25,3 11,6 2,18 25,2 13,0 1,930 88 27,5 7,7 3,59 26,9 9,4 2,87 26,3 11,6 2,26 26,1 13,0 2,012 88 28,8 7,7 3,76 28,2 9,4 3,00 27,6 11,6 2,37 27,3 13,0 2,105 87 31,0 7,7 4,03 30,2 9,4 3,22 29,4 11,6 2,53 28,9 13,0 2,227 87 32,5 7,7 4,23 31,7 9,4 3,37 30,8 11,6 2,65 30,3 13,0 2,3310 86 35,0 7,7 4,54 33,9 9,4 3,60 32,8 11,6 2,82 32,2 13,0 2,4812 86 36,9 7,8 4,76 35,5 9,4 3,77 34,3 11,6 2,95 33,6 13,0 2,5915 86 39,7 7,8 5,09 38,1 9,4 4,04 36,6 11,6 3,16 35,8 12,9 2,77

38

-16 90 20,3 8,1 2,49 * * * * * * * * *-15 90 20,9 8,2 2,56 * * * * * * * * *-10 90 24,0 8,2 2,91 23,4 10,0 2,33 * * * * * *-7 89 26,1 8,3 3,16 25,4 10,1 2,52 * * * * * *-2 89 29,8 8,3 3,57 29,0 10,2 2,85 28,0 12,6 2,23 27,4 14,1 1,950 88 31,3 8,4 3,74 30,3 10,2 2,98 29,2 12,6 2,32 28,7 14,1 2,042 88 32,8 8,4 3,92 31,9 10,2 3,12 30,7 12,6 2,43 30,1 14,1 2,135 87 35,3 8,4 4,21 34,2 10,2 3,33 32,8 12,7 2,59 32,1 14,2 2,267 87 37,1 8,4 4,40 35,9 10,3 3,50 34,5 12,7 2,72 33,7 14,2 2,3710 86 40,0 8,4 4,73 38,4 10,3 3,74 36,8 12,7 2,89 35,8 14,2 2,5112 86 41,8 8,5 4,93 40,3 10,3 3,91 38,5 12,7 3,03 37,6 14,3 2,6315 86 45,3 8,5 5,30 43,4 10,3 4,20 41,2 12,8 3,23 40,0 14,3 2,80

42

-16 90 22,8 9,1 2,51 * * * * * * * * *-15 90 23,3 9,1 2,56 * * * * * * * * *-10 90 26,6 9,3 2,87 26,3 11,2 2,34 * * * * * *-7 89 28,8 9,3 3,08 28,4 11,3 2,50 * * * * * *-2 89 32,7 9,4 3,46 32,0 11,5 2,79 31,2 14,0 2,22 30,7 15,6 1,970 88 34,2 9,5 3,62 33,5 11,5 2,91 32,4 14,1 2,30 31,9 15,6 2,042 88 35,9 9,5 3,78 35,1 11,5 3,04 34,0 14,2 2,40 33,3 15,7 2,125 87 38,7 9,6 4,05 37,6 11,6 3,24 36,2 14,2 2,55 35,4 15,8 2,247 87 40,6 9,6 4,23 39,4 11,6 3,38 37,9 14,3 2,66 37,0 15,9 2,3310 86 43,8 9,7 4,52 42,3 11,7 3,62 40,4 14,3 2,82 39,3 15,9 2,4712 86 46,1 9,7 4,73 44,2 11,7 3,76 42,3 14,4 2,94 41,1 16,0 2,5715 86 49,6 9,8 5,04 47,8 11,8 4,05 45,3 14,4 3,14 43,8 16,0 2,73

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

36

COOLING CAPACITIES - MAROON 2 MT

Pf: Cooling power [kW]

Pa: Total absorbed compressor power [kW]

To: Utility outlet water temperature to the utility exchanger [°C]

Model

To External air temperature [°C]

[°C]25 30 35 40

Pf Pat EER Pf Pat EER Pf Pat EER Pf Pat EER

52

5 42,5 11,5 3,69 40,3 12,5 3,22 38,0 13,7 2,78 35,4 15,0 2,376 43,7 11,6 3,77 41,5 12,6 3,28 39,1 13,8 2,84 36,5 15,1 2,427 45,0 11,7 3,85 42,7 12,7 3,36 40,3 13,9 2,90 37,6 15,2 2,488 46,3 11,8 3,93 44,0 12,8 3,43 41,4 14,0 2,96 38,7 15,3 2,539 47,6 11,9 4,01 45,2 12,9 3,50 42,6 14,1 3,03 39,9 15,4 2,5910 49,0 12,0 4,09 46,5 13,0 3,57 43,8 14,2 3,09 41,0 15,5 2,6513 53,0 12,2 4,33 50,4 13,3 3,78 47,5 14,5 3,27 44,5 15,8 2,8114 54,4 12,3 4,41 51,7 13,4 3,85 48,8 14,6 3,33 45,7 16,0 2,8615 55,9 12,4 4,49 53,0 13,5 3,92 50,1 14,7 3,40 46,9 16,1 2,9216 57,3 12,5 4,57 54,4 13,6 3,99 51,4 14,9 3,46 48,1 16,2 2,9717 58,8 12,6 4,66 55,8 13,7 4,06 52,7 15,0 3,52 49,4 16,3 3,0218 60,3 12,7 4,74 57,2 13,9 4,13 54,0 15,1 3,58 50,6 16,5 3,08

62

5 50,4 12,6 3,99 47,9 13,8 3,46 45,2 15,2 2,97 42,2 16,8 2,506 51,8 12,7 4,08 49,3 13,9 3,54 46,5 15,3 3,04 43,5 16,9 2,577 53,4 12,8 4,17 50,7 14,0 3,62 47,9 15,4 3,11 44,8 17,0 2,638 54,9 12,9 4,26 52,2 14,1 3,70 49,3 15,5 3,18 46,2 17,1 2,699 56,5 13,0 4,34 53,7 14,2 3,77 50,7 15,6 3,25 47,5 17,2 2,7610 58,0 13,1 4,42 55,2 14,3 3,85 52,1 15,7 3,31 48,9 17,4 2,8213 62,8 13,5 4,66 59,8 14,7 4,06 56,5 16,1 3,51 53,0 17,7 2,9914 64,5 13,6 4,73 61,3 14,9 4,13 58,0 16,2 3,57 54,4 17,9 3,0515 66,1 13,8 4,80 62,9 15,0 4,20 59,5 16,4 3,63 55,9 18,0 3,1116 67,8 13,9 4,87 64,5 15,1 4,26 61,0 16,5 3,69 57,3 18,1 3,1617 69,5 14,1 4,94 66,1 15,3 4,32 62,6 16,7 3,75 58,8 18,3 3,2118 71,2 14,2 5,01 67,8 15,5 4,38 64,1 16,9 3,80 60,3 18,5 3,26

72

5 58,4 15,1 3,88 55,1 16,6 3,31 51,6 18,4 2,80 47,7 20,4 2,346 60,1 15,2 3,96 56,7 16,8 3,38 53,1 18,5 2,86 49,2 20,6 2,397 61,8 15,3 4,03 58,4 16,9 3,46 54,7 18,7 2,93 50,7 20,7 2,458 63,6 15,4 4,12 60,1 17,0 3,53 56,3 18,8 2,99 52,2 20,8 2,519 65,3 15,6 4,19 61,8 17,2 3,60 57,9 18,9 3,06 53,7 20,9 2,5610 67,1 15,7 4,27 63,5 17,3 3,67 59,5 19,1 3,12 55,2 21,1 2,6213 72,5 16,1 4,50 68,7 17,7 3,88 64,5 19,5 3,31 59,9 21,5 2,7814 74,4 16,3 4,57 70,5 17,9 3,94 66,2 19,7 3,37 61,5 21,7 2,8415 76,3 16,4 4,64 72,3 18,0 4,01 67,9 19,8 3,43 63,1 21,8 2,8916 78,2 16,6 4,71 74,1 18,2 4,07 69,6 20,0 3,48 64,8 22,0 2,9417 80,2 16,8 4,78 76,0 18,4 4,14 71,4 20,1 3,54 66,4 22,2 3,0018 82,1 16,9 4,85 77,9 18,5 4,20 73,2 20,3 3,60 68,1 22,3 3,05

82

5 66,1 17,0 3,89 62,6 18,6 3,36 58,7 20,5 2,86 54,5 22,7 2,406 67,9 17,1 3,98 64,4 18,7 3,43 60,4 20,7 2,93 56,1 22,8 2,467 69,9 17,2 4,06 66,2 18,9 3,51 62,2 20,8 2,99 57,8 23,0 2,528 72,0 17,3 4,15 68,1 19,0 3,58 64,0 20,9 3,06 59,5 23,1 2,579 73,9 17,5 4,23 70,0 19,1 3,66 65,8 21,1 3,13 61,2 23,3 2,6310 75,9 17,6 4,32 72,0 19,3 3,74 67,7 21,2 3,19 62,9 23,4 2,6913 82,1 18,0 4,56 77,9 19,7 3,96 73,3 21,6 3,39 68,2 23,9 2,8614 84,3 18,2 4,64 79,9 19,8 4,03 75,2 21,8 3,45 70,0 24,0 2,9215 86,4 18,3 4,72 82,0 20,0 4,10 77,1 21,9 3,52 71,9 24,2 2,9716 88,6 18,5 4,80 84,1 20,2 4,17 79,1 22,1 3,58 73,7 24,3 3,0317 90,9 18,6 4,88 86,2 20,3 4,24 81,1 22,3 3,64 75,6 24,5 3,0918 93,1 18,8 4,96 88,4 20,5 4,31 83,2 22,4 3,71 77,6 24,7 3,14

92

5 72,8 19,3 3,77 68,9 21,1 3,26 64,6 23,2 2,79 59,9 25,5 2,356 74,8 19,5 3,85 70,9 21,3 3,33 66,5 23,3 2,85 61,7 25,6 2,417 77,0 19,6 3,92 72,9 21,4 3,40 68,4 23,5 2,91 63,5 25,8 2,468 79,1 19,8 4,00 75,0 21,6 3,47 70,3 23,7 2,97 65,2 26,0 2,519 81,4 20,0 4,07 77,1 21,8 3,53 72,3 23,9 3,03 67,1 26,2 2,5610 83,6 20,2 4,15 79,2 22,0 3,60 74,3 24,0 3,09 68,9 26,4 2,6113 90,4 20,7 4,36 85,6 22,6 3,79 80,3 24,6 3,26 74,5 27,0 2,7614 92,7 21,0 4,43 87,8 22,8 3,86 82,4 24,8 3,32 76,5 27,2 2,8115 95,1 21,2 4,50 90,0 23,0 3,92 84,5 25,0 3,37 78,4 27,4 2,8716 97,5 21,4 4,56 92,3 23,2 3,98 86,6 25,3 3,43 80,4 27,6 2,9217 100,0 21,6 4,63 94,7 23,4 4,04 88,8 25,5 3,49 82,5 27,8 2,9718 102,5 21,8 4,69 97,0 23,6 4,10 91,0 25,7 3,54 84,5 28,0 3,01

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

37

HEATING CAPACITIES - MAROON 2 MT

Pt: Heating capacity [kW]

Pa: Total absorbed compressor power [kW]

Ta: Dry bulb temperature of the evaporator inlet air [°C]

RH: Relative humidity of the input air at the evaporator [%]

Model

Ta RH Condenser inlet water temperature [°C]

[°C] %30/35 40/45 50/55 55/60

Pt Pat COP Pt Pat COP Pt Pat COP Pt Pat COP

52

-16 90 25,4 10,6 2,39 * * * * * * * * *-15 90 26,0 10,6 2,45 * * * * * * * * *-10 90 29,7 10,7 2,78 29,2 13,0 2,25 * * * * * *-7 89 32,2 10,8 2,99 31,8 13,0 2,44 * * * * * *-2 89 36,7 10,9 3,37 36,0 13,1 2,74 35,2 16,1 2,19 34,2 17,8 1,920 88 38,5 11,0 3,52 37,7 13,2 2,87 36,9 16,1 2,30 36,0 17,8 2,022 88 40,5 11,0 3,67 39,6 13,2 3,00 38,6 16,1 2,40 37,9 17,9 2,125 87 43,7 11,1 3,93 42,5 13,3 3,19 41,2 16,2 2,55 40,6 17,9 2,267 87 45,9 11,2 4,11 44,6 13,4 3,34 43,2 16,2 2,67 42,5 18,0 2,3610 86 49,4 11,2 4,40 48,0 13,5 3,57 46,1 16,3 2,83 45,2 18,1 2,5012 86 52,0 11,3 4,61 50,2 13,5 3,71 48,3 16,3 2,96 47,3 18,1 2,6115 86 55,9 11,3 4,93 54,1 13,6 3,98 51,8 16,4 3,15 50,5 18,2 2,78

62

-16 90 29,6 12,2 2,44 * * * * * * * * *-15 90 30,4 12,2 2,49 * * * * * * * * *-10 90 34,8 12,3 2,84 34,4 15,2 2,26 * * * * * *-7 89 37,8 12,3 3,08 37,3 15,2 2,45 * * * * * *-2 89 43,1 12,3 3,49 42,4 15,2 2,79 41,6 19,1 2,18 41,2 21,6 1,910 88 45,2 12,3 3,66 44,3 15,2 2,92 43,3 19,0 2,28 42,9 21,5 1,992 88 47,4 12,4 3,83 46,5 15,2 3,07 45,6 19,0 2,40 45,0 21,4 2,105 87 51,0 12,4 4,12 49,9 15,2 3,30 48,6 18,9 2,57 48,0 21,3 2,257 87 53,7 12,4 4,32 52,3 15,2 3,45 51,0 18,9 2,70 50,3 21,3 2,3610 86 57,7 12,5 4,62 56,2 15,2 3,70 54,5 18,8 2,89 53,5 21,2 2,5212 86 60,7 12,5 4,84 58,8 15,2 3,86 56,9 18,8 3,02 56,0 21,2 2,6415 86 65,3 12,7 5,16 63,3 15,3 4,13 61,1 18,9 3,24 59,7 21,1 2,82

72

-16 90 33,8 13,8 2,44 * * * * * * * * *-15 90 34,7 13,9 2,50 * * * * * * * * *-10 90 39,6 14,0 2,84 39,5 17,4 2,27 * * * * * *-7 89 43,0 14,0 3,07 42,6 17,5 2,44 * * * * * *-2 89 48,8 14,1 3,47 48,2 17,5 2,75 47,7 22,0 2,17 47,7 24,7 1,930 88 51,4 14,1 3,65 50,5 17,5 2,88 49,7 21,9 2,27 49,4 24,7 2,002 88 54,0 14,1 3,83 52,7 17,5 3,01 51,9 21,9 2,37 51,6 24,7 2,095 87 57,9 14,1 4,09 56,6 17,5 3,23 55,4 21,9 2,52 54,6 24,7 2,227 87 60,9 14,2 4,30 59,4 17,5 3,39 57,8 21,9 2,64 57,0 24,6 2,3210 86 65,3 14,2 4,59 63,6 17,6 3,62 61,7 21,9 2,82 60,7 24,6 2,4712 86 68,6 14,3 4,80 66,7 17,6 3,79 64,4 21,9 2,94 63,2 24,6 2,5715 86 73,7 14,3 5,14 71,6 17,6 4,06 69,1 21,9 3,15 67,6 24,6 2,75

82

-16 90 38,9 16,1 2,42 * * * * * * * * *-15 90 40,0 16,1 2,48 * * * * * * * * *-10 90 46,0 16,3 2,82 44,9 19,9 2,25 * * * * * *-7 89 50,0 16,4 3,05 48,8 20,0 2,44 * * * * * *-2 89 56,9 16,5 3,45 55,5 20,2 2,75 53,8 25,0 2,16 53,0 27,9 1,900 88 59,8 16,5 3,62 58,1 20,2 2,88 56,2 25,0 2,25 55,2 28,0 1,972 88 62,6 16,5 3,78 61,0 20,3 3,01 59,2 25,1 2,36 58,0 28,1 2,065 87 67,5 16,6 4,06 65,5 20,3 3,22 63,1 25,2 2,51 61,9 28,2 2,197 87 71,0 16,6 4,26 68,6 20,4 3,37 66,2 25,2 2,62 64,8 28,3 2,2910 86 76,2 16,7 4,56 73,7 20,4 3,61 70,9 25,3 2,80 69,0 28,3 2,4312 86 80,1 16,8 4,77 77,3 20,4 3,78 74,0 25,3 2,92 72,2 28,4 2,5415 86 86,2 16,9 5,11 83,1 20,5 4,05 79,4 25,4 3,13 77,2 28,4 2,71

92

-16 90 43,6 17,2 2,53 * * * * * * * * *-15 90 44,7 17,3 2,58 * * * * * * * * *-10 90 50,9 17,6 2,89 50,4 21,3 2,37 * * * * * *-7 89 54,9 17,8 3,09 54,3 21,6 2,52 * * * * * *-2 89 62,2 18,0 3,46 61,3 21,9 2,80 59,9 26,7 2,24 59,1 29,6 2,000 88 65,4 18,0 3,63 64,2 22,0 2,93 62,5 26,9 2,33 61,5 29,8 2,062 88 68,7 18,1 3,79 67,1 22,0 3,04 65,3 27,0 2,42 64,2 30,0 2,145 87 73,7 18,2 4,05 71,9 22,1 3,25 69,6 27,2 2,56 68,1 30,2 2,267 87 77,4 18,3 4,23 75,5 22,2 3,40 72,7 27,3 2,67 71,1 30,3 2,3510 86 83,1 18,4 4,51 80,8 22,3 3,62 77,6 27,4 2,84 75,8 30,5 2,4912 86 87,6 18,5 4,73 84,7 22,4 3,78 80,9 27,5 2,95 78,9 30,5 2,5815 86 94,1 18,7 5,03 91,0 22,5 4,04 86,9 27,6 3,15 84,4 30,7 2,75

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

38

Model

To DHW temperature [°C]

[°C]40/45 45/50 50/55 55/60

Pf Pa Pt EER COP Pf Pa Pt EER COP Pf Pa Pt EER COP Pf Pa Pt EER COP

RECOVERY CAPACITIES - MAROON 2 MT

Pf: Cooling power [kW]

Pt: Heating capacity [kW]

To: Utility outlet water temperature to the utility exchanger [°C]

8

5 5,8 1,9 7,7 3,03 4,03 5,4 2,2 7,6 2,48 3,48 5,0 2,5 7,4 2,01 3,01 4,5 2,8 7,3 1,59 2,59

7 6,2 1,9 8,1 3,28 4,28 5,8 2,2 8,0 2,68 3,69 5,3 2,5 7,8 2,17 3,16 4,8 2,8 7,6 1,72 2,72

10 6,9 1,9 8,8 3,64 4,63 6,4 2,1 8,6 3,00 4,00 5,9 2,4 8,3 2,43 3,43 5,3 2,8 8,1 1,93 2,93

14 7,8 1,9 9,7 4,18 5,18 7,3 2,1 9,4 3,44 4,44 6,7 2,4 9,1 2,80 3,80 6,1 2,7 8,8 2,25 3,25

18 8,8 1,9 10,7 4,78 5,78 8,3 2,1 10,4 3,94 4,94 7,7 2,4 10,0 3,21 4,21 7,0 2,7 9,7 2,59 3,59

10

5 7,4 2,1 9,5 3,52 4,52 6,9 2,4 9,3 2,86 3,86 6,3 2,8 9,1 2,29 3,29 5,7 3,2 8,9 1,80 2,80

7 7,9 2,1 10,0 3,80 4,80 7,4 2,4 9,8 3,08 4,08 6,8 2,7 9,5 2,48 3,48 6,1 3,1 9,3 1,95 2,95

10 8,8 2,1 10,8 4,24 5,24 8,2 2,4 10,5 3,45 4,45 7,5 2,7 10,2 2,77 3,77 6,8 3,1 9,9 2,19 3,19

14 10,0 2,1 12,0 4,85 5,85 9,3 2,4 11,6 3,95 4,95 8,6 2,7 11,2 3,19 4,19 7,8 3,1 10,8 2,54 3,54

18 11,3 2,0 13,3 5,51 6,51 10,5 2,3 12,8 4,51 5,51 9,7 2,7 12,4 3,67 4,67 8,8 3,0 11,9 2,92 3,92

12

5 9,4 2,5 11,9 3,79 4,79 8,7 2,8 11,5 3,12 4,12 8,0 3,2 11,2 2,53 3,53 7,2 3,6 10,8 2,00 2,99

7 10,1 2,5 12,6 4,06 5,06 9,4 2,8 12,2 3,34 4,34 8,6 3,2 11,8 2,72 3,72 7,7 3,6 11,3 2,15 3,15

10 11,1 2,5 13,6 4,48 5,48 10,3 2,8 13,1 3,69 4,69 9,5 3,2 12,7 3,01 4,01 8,6 3,6 12,2 2,39 3,39

14 12,6 2,5 15,1 5,05 6,05 11,7 2,8 14,5 4,19 5,19 10,8 3,2 14,0 3,42 4,42 9,8 3,6 13,4 2,73 3,73

18 14,2 2,5 16,7 5,70 6,70 13,3 2,8 16,1 4,74 5,74 12,3 3,2 15,4 3,88 4,89 11,2 3,6 14,7 3,11 4,11

16

5 12,5 3,6 16,2 3,44 4,44 11,6 4,2 15,8 2,79 3,79 10,5 4,8 15,3 2,19 3,19 9,2 5,6 14,8 1,65 2,65

7 13,4 3,6 17,0 3,68 4,68 12,4 4,2 16,6 2,99 3,99 11,3 4,8 16,1 2,37 3,37 9,9 5,5 15,5 1,79 2,80

10 14,7 3,6 18,3 4,04 5,04 13,7 4,1 17,8 3,31 4,31 12,5 4,7 17,2 2,64 3,64 11,1 5,5 16,6 2,03 3,03

14 16,5 3,6 20,2 4,53 5,54 15,4 4,1 19,6 3,75 4,75 14,2 4,7 18,9 3,02 4,02 12,7 5,4 18,1 2,35 3,35

18 18,5 3,7 22,2 5,03 6,03 17,4 4,1 21,5 4,19 5,19 16,0 4,7 20,7 3,42 4,42 14,5 5,4 19,9 2,69 3,69

18

5 13,5 3,9 17,4 3,48 4,47 12,5 4,3 16,8 2,88 3,89 11,4 4,8 16,2 2,35 3,35 10,1 5,4 15,5 1,86 2,86

7 14,5 3,9 18,4 3,75 4,75 13,5 4,3 17,8 3,12 4,12 12,3 4,8 17,1 2,55 3,55 11,0 5,4 16,4 2,02 3,02

10 16,1 3,8 19,9 4,19 5,19 14,9 4,3 19,2 3,49 4,49 13,7 4,8 18,5 2,86 3,86 12,3 5,4 17,7 2,29 3,29

14 18,3 3,8 22,1 4,82 5,82 17,1 4,2 21,3 4,03 5,03 15,7 4,7 20,5 3,33 4,33 14,2 5,3 19,6 2,67 3,67

18 20,7 3,7 24,5 5,54 6,54 19,4 4,2 23,6 4,65 5,65 18,0 4,7 22,6 3,85 4,85 16,4 5,3 21,6 3,11 4,11

20

5 15,9 4,4 20,3 3,57 4,57 14,7 5,0 19,7 2,96 3,96 13,5 5,6 19,1 2,42 3,42 12,2 6,3 18,5 1,93 2,93

7 16,9 4,5 21,4 3,80 4,80 15,8 5,0 20,8 3,15 4,15 14,5 5,6 20,1 2,58 3,58 13,1 6,3 19,4 2,06 3,06

10 18,6 4,5 23,1 4,16 5,16 17,4 5,0 22,4 3,46 4,46 16,0 5,7 21,7 2,83 3,83 14,5 6,4 20,9 2,27 3,27

14 21,1 4,5 25,6 4,67 5,67 19,7 5,1 24,7 3,89 4,89 18,2 5,7 23,9 3,20 4,20 16,5 6,4 22,9 2,58 3,58

18 23,8 4,5 28,3 5,23 6,24 22,2 5,1 27,3 4,38 5,38 20,6 5,7 26,3 3,61 4,60 18,8 6,4 25,2 2,92 3,92

23

5 17,7 5,3 23,1 3,33 4,33 16,5 6,0 22,5 2,76 3,75 15,2 6,7 21,9 2,25 3,25 13,8 7,6 21,4 1,80 2,80

7 19,0 5,4 24,3 3,54 4,54 17,7 6,0 23,7 2,94 3,94 16,3 6,8 23,1 2,41 3,41 14,8 7,6 22,4 1,93 2,93

10 20,9 5,4 26,3 3,88 4,88 19,5 6,0 25,6 3,23 4,23 18,0 6,8 24,8 2,66 3,66 16,4 7,7 24,1 2,14 3,14

14 23,7 5,5 29,1 4,34 5,34 22,2 6,1 28,3 3,63 4,64 20,6 6,8 27,4 3,01 4,01 18,8 7,7 26,5 2,43 3,43

18 26,7 5,5 32,3 4,83 5,83 25,1 6,2 31,3 4,07 5,07 23,4 6,9 30,3 3,38 4,38 21,4 7,8 29,2 2,76 3,76

25

5 19,7 5,7 25,4 3,46 4,46 18,2 6,4 24,6 2,85 3,85 16,5 7,2 23,8 2,29 3,29 14,7 8,2 22,9 1,80 2,80

7 21,1 5,7 26,7 3,70 4,70 19,5 6,4 25,9 3,05 4,05 17,8 7,2 25,0 2,47 3,47 15,9 8,2 24,1 1,94 2,94

10 23,2 5,7 28,9 4,07 5,07 21,6 6,4 28,0 3,37 4,37 19,7 7,2 27,0 2,74 3,74 17,7 8,2 25,9 2,17 3,17

14 26,3 5,7 32,0 4,59 5,59 24,5 6,4 30,9 3,82 4,82 22,5 7,2 29,7 3,12 4,12 20,3 8,2 28,5 2,49 3,49

18 29,6 5,8 35,4 5,13 6,12 27,7 6,5 34,2 4,30 5,30 25,6 7,2 32,8 3,54 4,54 23,2 8,2 31,3 2,84 3,84

29

5 23,0 6,5 29,4 3,55 4,55 21,4 7,3 28,7 2,95 3,95 19,7 8,2 27,9 2,41 3,41 17,7 9,3 27,1 1,91 2,91

7 24,5 6,5 31,0 3,79 4,79 22,9 7,3 30,2 3,16 4,16 21,2 8,2 29,3 2,59 3,59 19,1 9,3 28,4 2,06 3,06

10 26,9 6,5 33,5 4,14 5,14 25,3 7,3 32,5 3,47 4,47 23,4 8,2 31,6 2,86 3,86 21,3 9,3 30,6 2,30 3,30

14 30,4 6,6 37,0 4,61 5,61 28,5 7,3 35,9 3,89 4,89 26,5 8,2 34,8 3,23 4,23 24,3 9,3 33,6 2,62 3,62

18 34,1 6,7 40,8 5,08 6,08 32,1 7,4 39,5 4,31 5,31 29,9 8,3 38,2 3,60 4,60 27,5 9,3 36,8 2,95 3,95

38

5 28,5 7,2 35,7 3,96 4,96 26,5 8,1 34,6 3,26 4,26 24,2 9,2 33,3 2,64 3,64 21,7 10,4 32,0 2,09 3,09

7 30,5 7,2 37,7 4,24 5,24 28,4 8,1 36,5 3,50 4,50 26,0 9,1 35,1 2,84 3,84 23,3 10,4 33,7 2,25 3,26

10 33,6 7,2 40,8 4,66 5,66 31,3 8,1 39,4 3,86 4,86 28,8 9,1 37,9 3,15 4,15 26,0 10,3 36,3 2,51 3,51

14 38,0 7,2 45,2 5,24 6,24 35,5 8,1 43,6 4,38 5,38 32,8 9,1 41,9 3,59 4,59 29,7 10,3 40,0 2,88 3,88

18 42,7 7,3 50,0 5,87 6,87 40,1 8,1 48,2 4,92 5,92 37,1 9,1 46,3 4,07 5,07 33,8 10,3 44,1 3,29 4,29

42

5 30,4 9,0 39,4 3,40 4,40 28,2 10,1 38,2 2,79 3,79 25,6 11,4 37,0 2,25 3,25 22,8 12,9 35,7 1,77 2,77

7 32,5 9,0 41,5 3,63 4,63 30,1 10,1 40,2 2,99 3,99 27,5 11,4 38,9 2,41 3,41 24,6 12,9 37,5 1,90 2,90

10 35,7 9,0 44,7 3,98 4,98 33,2 10,1 43,3 3,28 4,28 30,4 11,4 41,8 2,66 3,66 27,3 12,9 40,2 2,11 3,11

14 40,3 9,0 49,3 4,47 5,47 37,6 10,1 47,7 3,71 4,71 34,6 11,4 46,0 3,02 4,02 31,2 13,0 44,1 2,40 3,40

18 45,3 9,1 54,4 4,99 5,99 42,3 10,2 52,5 4,16 5,16 39,1 11,5 50,5 3,41 4,41 35,4 13,0 48,4 2,73 3,73

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

39

Model

To DHW temperature [°C]

[°C]40/45 45/50 50/55 55/60

Pf Pa Pt EER COP Pf Pa Pt EER COP Pf Pa Pt EER COP Pf Pa Pt EER COP

RECOVERY CAPACITIES - MAROON 2 MT

Pf: Cooling power [kW]

Pt: Heating capacity [kW]

To: Utility outlet water temperature to the utility exchanger [°C]

52

5 38,5 12,1 50,5 3,19 4,19 35,8 13,4 49,2 2,67 3,67 32,8 15,0 47,8 2,19 3,19 29,8 16,6 46,4 1,79 2,79

7 41,1 12,1 53,2 3,39 4,39 38,2 13,5 51,7 2,84 3,84 35,3 15,0 50,2 2,35 3,35 32,2 16,6 48,8 1,94 2,94

10 45,2 12,2 57,4 3,71 4,71 42,2 13,5 55,8 3,12 4,12 39,1 15,0 54,1 2,60 3,60 35,8 16,6 52,4 2,15 3,15

14 51,1 12,3 63,3 4,17 5,17 47,8 13,6 61,4 3,51 4,51 44,4 15,1 59,5 2,94 3,94 40,9 16,7 57,6 2,45 3,45

18 57,5 12,3 69,8 4,68 5,68 53,9 13,7 67,6 3,93 4,93 50,3 15,2 65,4 3,32 4,32 46,5 16,8 63,2 2,77 3,77

62

5 45,9 13,5 59,3 3,41 4,41 42,0 15,6 57,6 2,70 3,70 38,5 17,6 56,1 2,19 3,19 34,8 19,8 54,6 1,76 2,76

7 48,6 13,7 62,3 3,56 4,56 45,0 15,6 60,5 2,89 3,89 41,4 17,5 59,0 2,36 3,36 37,6 19,7 57,4 1,91 2,91

10 53,1 13,9 66,9 3,82 4,82 49,6 15,6 65,2 3,19 4,19 45,9 17,5 63,4 2,62 3,62 42,0 19,6 61,6 2,14 3,14

14 59,9 14,0 73,9 4,28 5,28 56,1 15,7 71,7 3,58 4,58 52,1 17,5 69,7 2,98 3,98 48,0 19,6 67,6 2,45 3,45

18 67,2 14,2 81,4 4,73 5,73 63,1 15,8 78,9 3,98 4,98 58,9 17,6 76,5 3,34 4,34 54,5 19,6 74,1 2,78 3,78

72

5 54,0 15,8 69,8 3,42 4,42 49,1 18,3 67,4 2,68 3,68 44,7 20,7 65,4 2,16 3,16 40,3 23,2 63,5 1,74 2,74

7 57,7 15,8 73,5 3,65 4,65 52,6 18,3 70,9 2,88 3,88 48,1 20,6 68,8 2,33 3,33 43,5 23,1 66,6 1,88 2,88

10 62,6 16,2 78,8 3,86 4,86 58,2 18,3 76,4 3,18 4,18 53,4 20,6 73,9 2,59 3,59 48,4 23,0 71,5 2,10 3,10

14 70,8 16,3 87,1 4,35 5,35 66,0 18,3 84,3 3,62 4,62 60,9 20,5 81,4 2,97 3,97 55,5 22,9 78,5 2,42 3,42

18 79,7 16,3 96,1 4,88 5,88 74,6 18,3 92,9 4,07 5,07 69,1 20,5 89,6 3,37 4,37 63,3 22,9 86,2 2,77 3,77

82

5 59,9 17,7 77,6 3,38 4,38 54,3 20,6 74,8 2,64 3,64 49,3 23,2 72,5 2,12 3,12 44,2 26,0 70,2 1,70 2,70

7 63,8 17,7 81,6 3,60 4,60 58,1 20,6 78,7 2,83 3,83 53,0 23,2 76,2 2,28 3,28 47,7 26,0 73,7 1,83 2,83

10 69,1 18,2 87,3 3,79 4,79 64,1 20,6 84,7 3,12 4,12 58,7 23,2 81,9 2,53 3,53 53,1 26,0 79,1 2,04 3,04

14 78,0 18,3 96,3 4,27 5,27 72,6 20,6 93,2 3,53 4,53 66,7 23,2 89,9 2,88 3,88 60,7 26,0 86,7 2,33 3,33

18 87,8 18,4 106,1 4,78 5,78 81,8 20,6 102,5 3,97 4,97 75,6 23,2 98,7 3,26 4,26 69,0 26,0 95,0 2,66 3,66

92

5 67,3 19,6 86,9 3,44 4,44 61,2 22,6 83,8 2,71 3,71 55,7 25,3 81,0 2,20 3,20 50,1 28,1 78,3 1,78 2,78

7 71,8 19,7 91,4 3,65 4,65 65,5 22,6 88,1 2,89 3,89 59,7 25,4 85,1 2,36 3,36 53,8 28,2 82,0 1,91 2,91

10 78,3 20,0 98,3 3,91 4,91 72,1 22,7 94,8 3,18 4,18 65,9 25,4 91,3 2,60 3,60 59,6 28,3 87,9 2,11 3,11

14 87,8 20,4 108,2 4,30 5,30 81,6 22,8 104,4 3,58 4,58 74,9 25,5 100,4 2,94 3,94 68,0 28,3 96,3 2,40 3,40

18 98,9 20,6 119,5 4,80 5,80 92,1 22,9 115,1 4,02 5,02 84,9 25,5 110,4 3,32 4,32 77,3 28,4 105,7 2,73 3,73

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

40

COOLING CAPACITIES - MAROON 2 HT

Pf: Cooling power [kW]

Pa: Total absorbed compressor power [kW]

To: Utility outlet water temperature to the utility exchanger [°C]

Model

To External air temperature [°C]

[°C]25 30 35 40

Pf Pat EER Pf Pat EER Pf Pat EER Pf Pat EER

7

5 6,3 1,6 4,04 6,0 1,7 3,50 5,7 1,9 3,04 5,3 2,0 2,616 6,5 1,6 4,14 6,2 1,7 3,61 5,9 1,9 3,12 5,5 2,0 2,687 6,7 1,6 4,26 6,4 1,7 3,70 6,0 1,9 3,20 5,6 2,1 2,758 6,9 1,6 4,36 6,6 1,7 3,79 6,2 1,9 3,28 5,8 2,1 2,829 7,1 1,6 4,49 6,8 1,7 3,91 6,4 1,9 3,38 6,0 2,1 2,8910 7,3 1,6 4,60 7,0 1,7 4,00 6,6 1,9 3,46 6,2 2,1 2,9613 8,0 1,6 4,97 7,6 1,8 4,30 7,2 1,9 3,72 6,7 2,1 3,1814 8,2 1,6 5,08 7,8 1,8 4,42 7,4 1,9 3,81 6,9 2,1 3,2715 8,5 1,6 5,22 8,0 1,8 4,52 7,6 1,9 3,90 7,1 2,1 3,3416 8,7 1,6 5,33 8,3 1,8 4,64 7,8 1,9 4,00 7,3 2,1 3,4217 8,9 1,6 5,48 8,5 1,8 4,75 8,0 2,0 4,10 7,5 2,1 3,5018 9,2 1,6 5,60 8,7 1,8 4,85 8,2 2,0 4,19 7,7 2,2 3,57

9

5 8,1 2,0 4,09 7,7 2,2 3,51 7,3 2,4 3,01 6,8 2,7 2,556 8,4 2,0 4,20 8,0 2,2 3,60 7,5 2,4 3,07 7,0 2,7 2,627 8,7 2,0 4,30 8,2 2,2 3,69 7,7 2,4 3,15 7,2 2,7 2,688 8,9 2,0 4,41 8,4 2,2 3,79 7,9 2,5 3,23 7,4 2,7 2,759 9,2 2,0 4,51 8,7 2,2 3,86 8,2 2,5 3,31 7,6 2,7 2,8010 9,4 2,0 4,62 8,9 2,3 3,95 8,4 2,5 3,39 7,8 2,7 2,8713 10,2 2,1 4,94 9,7 2,3 4,23 9,1 2,5 3,62 8,5 2,8 3,0714 10,5 2,1 5,05 10,0 2,3 4,33 9,4 2,5 3,70 8,7 2,8 3,1415 10,8 2,1 5,16 10,2 2,3 4,42 9,6 2,5 3,79 9,0 2,8 3,2016 11,1 2,1 5,28 10,5 2,3 4,52 9,9 2,6 3,86 9,2 2,8 3,2717 11,4 2,1 5,42 10,8 2,3 4,62 10,1 2,6 3,94 9,4 2,8 3,3518 11,7 2,1 5,53 11,1 2,3 4,72 10,4 2,6 4,03 9,7 2,8 3,42

11

5 10,6 2,6 4,06 10,1 2,9 3,49 9,5 3,2 2,98 8,8 3,5 2,536 10,9 2,6 4,16 10,4 2,9 3,56 9,7 3,2 3,05 9,1 3,5 2,597 11,2 2,7 4,24 10,7 2,9 3,64 10,0 3,2 3,12 9,3 3,5 2,648 11,6 2,7 4,33 10,9 2,9 3,72 10,3 3,2 3,18 9,6 3,6 2,709 11,9 2,7 4,41 11,3 3,0 3,80 10,6 3,3 3,25 9,8 3,6 2,7510 12,2 2,7 4,52 11,6 3,0 3,88 10,9 3,3 3,31 10,1 3,6 2,8013 13,2 2,8 4,77 12,5 3,0 4,11 11,7 3,4 3,50 10,9 3,7 2,9614 13,5 2,8 4,86 12,8 3,1 4,18 12,0 3,4 3,57 11,2 3,7 3,0215 13,9 2,8 4,97 13,1 3,1 4,26 12,3 3,4 3,64 11,5 3,7 3,0716 14,2 2,8 5,06 13,5 3,1 4,34 12,6 3,4 3,69 11,7 3,8 3,1317 14,6 2,8 5,15 13,8 3,1 4,41 13,0 3,4 3,76 12,0 3,8 3,1918 15,0 2,9 5,24 14,2 3,2 4,48 13,3 3,5 3,83 12,3 3,8 3,24

13

5 12,2 3,0 4,03 11,8 3,4 3,51 11,4 3,8 3,04 10,9 4,2 2,616 12,5 3,0 4,11 12,1 3,4 3,58 11,7 3,8 3,11 11,2 4,2 2,667 12,8 3,0 4,21 12,4 3,4 3,67 12,0 3,8 3,17 11,5 4,2 2,728 13,1 3,1 4,30 12,7 3,4 3,74 12,3 3,8 3,23 11,7 4,2 2,789 13,5 3,1 4,40 13,0 3,4 3,82 12,6 3,8 3,30 12,0 4,2 2,8210 13,8 3,1 4,51 13,4 3,4 3,90 12,9 3,8 3,36 12,3 4,3 2,8813 14,8 3,1 4,81 14,3 3,4 4,15 13,7 3,8 3,57 13,1 4,3 3,0514 15,1 3,1 4,91 14,6 3,5 4,23 14,0 3,9 3,64 13,4 4,3 3,1015 15,5 3,1 5,02 14,9 3,5 4,33 14,4 3,9 3,71 13,7 4,3 3,1616 15,8 3,1 5,13 15,3 3,5 4,42 14,7 3,9 3,79 14,0 4,3 3,2217 16,2 3,1 5,26 15,6 3,5 4,52 15,0 3,9 3,86 14,3 4,4 3,2818 16,5 3,1 5,38 16,0 3,5 4,61 15,3 3,9 3,94 14,6 4,4 3,35

17

5 14,5 3,7 3,96 14,1 4,1 3,46 13,7 4,5 3,01 13,2 5,1 2,606 14,8 3,7 4,06 14,5 4,1 3,54 14,0 4,6 3,07 13,5 5,1 2,657 15,2 3,7 4,15 14,8 4,1 3,62 14,4 4,6 3,14 13,8 5,1 2,718 15,6 3,7 4,24 15,2 4,1 3,70 14,7 4,6 3,21 14,2 5,1 2,769 16,0 3,7 4,34 15,6 4,1 3,78 15,1 4,6 3,27 14,5 5,2 2,8110 16,4 3,7 4,43 16,0 4,1 3,86 15,4 4,6 3,34 14,8 5,2 2,8713 17,6 3,7 4,71 17,1 4,2 4,11 16,5 4,7 3,54 15,9 5,2 3,0414 18,0 3,7 4,82 17,5 4,2 4,18 16,9 4,7 3,62 16,2 5,2 3,0915 18,5 3,8 4,92 17,9 4,2 4,26 17,3 4,7 3,68 16,6 5,3 3,1616 18,9 3,8 5,01 18,3 4,2 4,35 17,7 4,7 3,75 16,9 5,3 3,2117 19,3 3,8 5,12 18,7 4,2 4,44 18,1 4,7 3,82 17,3 5,3 3,2718 19,8 3,8 5,22 19,2 4,2 4,52 18,5 4,7 3,89 17,7 5,3 3,33

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

41

COOLING CAPACITIES - MAROON 2 HT

Pf: Cooling power [kW]

Pa: Total absorbed compressor power [kW]

To: Utility outlet water temperature to the utility exchanger [°C]

Model

To External air temperature [°C]

[°C]25 30 35 40

Pf Pat EER Pf Pat EER Pf Pat EER Pf Pat EER

22

5 20,0 4,9 4,05 19,4 5,5 3,51 18,7 6,2 3,02 17,9 6,9 2,586 20,5 4,9 4,15 19,9 5,6 3,58 19,2 6,2 3,08 18,3 7,0 2,637 21,0 5,0 4,24 20,4 5,6 3,66 19,6 6,2 3,15 18,8 7,0 2,688 21,5 5,0 4,33 20,9 5,6 3,74 20,1 6,3 3,21 19,2 7,0 2,739 22,1 5,0 4,43 21,4 5,6 3,81 20,6 6,3 3,27 19,7 7,1 2,7910 22,6 5,0 4,52 21,9 5,6 3,89 21,1 6,3 3,34 20,1 7,1 2,8413 24,2 5,0 4,82 23,4 5,7 4,14 22,5 6,4 3,53 21,5 7,2 3,0014 24,7 5,0 4,92 23,9 5,7 4,22 23,0 6,4 3,60 21,9 7,2 3,0515 25,3 5,0 5,03 24,5 5,7 4,30 23,5 6,4 3,67 22,4 7,2 3,1116 25,9 5,0 5,14 25,0 5,7 4,39 24,0 6,4 3,74 22,9 7,2 3,1617 26,5 5,0 5,25 25,6 5,7 4,48 24,5 6,4 3,81 23,3 7,2 3,2218 27,0 5,0 5,37 26,1 5,7 4,57 25,0 6,5 3,88 23,8 7,3 3,28

26

5 23,1 5,7 4,08 22,5 6,3 3,56 21,8 7,1 3,08 21,0 7,9 2,656 23,7 5,7 4,16 23,1 6,4 3,64 22,4 7,1 3,15 21,5 7,9 2,717 24,3 5,7 4,25 23,7 6,4 3,72 23,0 7,1 3,22 22,1 8,0 2,778 24,9 5,8 4,34 24,3 6,4 3,79 23,5 7,2 3,29 22,6 8,0 2,839 25,6 5,8 4,42 24,9 6,4 3,87 24,1 7,2 3,36 23,2 8,0 2,8910 26,2 5,8 4,50 25,5 6,5 3,95 24,7 7,2 3,43 23,8 8,1 2,9513 28,1 5,9 4,76 27,4 6,6 4,18 26,5 7,3 3,63 25,5 8,2 3,1314 28,8 6,0 4,83 28,1 6,6 4,25 27,2 7,3 3,70 26,1 8,2 3,1915 29,5 6,0 4,92 28,7 6,6 4,32 27,8 7,4 3,77 26,7 8,2 3,2516 30,2 6,0 5,00 29,4 6,7 4,40 28,4 7,4 3,83 27,3 8,3 3,3117 30,9 6,1 5,08 30,0 6,7 4,47 29,1 7,5 3,90 28,0 8,3 3,3718 31,6 6,1 5,16 30,7 6,8 4,55 29,7 7,5 3,97 28,6 8,3 3,43

32

5 29,6 7,5 3,96 29,1 8,3 3,49 28,3 9,3 3,06 27,4 10,3 2,656 30,3 7,5 4,02 29,8 8,4 3,56 29,0 9,3 3,12 28,0 10,4 2,707 31,1 7,6 4,10 30,5 8,4 3,63 29,8 9,3 3,18 28,8 10,4 2,768 31,8 7,6 4,17 31,2 8,5 3,69 30,4 9,4 3,24 29,4 10,5 2,819 32,6 7,7 4,23 32,0 8,5 3,76 31,2 9,4 3,30 30,1 10,5 2,8710 33,4 7,8 4,30 32,7 8,6 3,83 31,9 9,5 3,36 30,8 10,5 2,9213 35,7 7,9 4,49 35,0 8,7 4,01 34,1 9,6 3,53 32,9 10,7 3,0814 36,5 8,0 4,55 35,7 8,8 4,07 34,8 9,7 3,59 33,6 10,7 3,1315 37,3 8,1 4,61 36,5 8,8 4,13 35,5 9,7 3,65 34,3 10,8 3,1816 38,1 8,2 4,66 37,3 8,9 4,18 36,3 9,8 3,70 35,0 10,8 3,2317 38,9 8,3 4,71 38,1 9,0 4,24 37,1 9,9 3,75 35,8 10,9 3,2818 39,7 8,3 4,77 38,9 9,1 4,29 37,8 9,9 3,81 36,5 11,0 3,33

36

5 32,9 8,2 4,00 32,2 9,2 3,51 31,4 10,2 3,08 30,4 11,4 2,676 33,7 8,3 4,08 33,0 9,2 3,59 32,1 10,2 3,14 31,1 11,4 2,727 34,5 8,3 4,16 33,8 9,2 3,66 32,9 10,3 3,20 31,9 11,5 2,788 35,3 8,3 4,25 34,6 9,3 3,73 33,7 10,3 3,27 32,6 11,5 2,839 36,1 8,3 4,34 35,4 9,3 3,81 34,4 10,4 3,33 33,3 11,5 2,8910 36,9 8,3 4,43 36,2 9,3 3,88 35,2 10,4 3,39 34,1 11,6 2,9413 39,4 8,4 4,70 38,6 9,4 4,12 37,6 10,5 3,59 36,4 11,7 3,1114 40,3 8,4 4,79 39,4 9,4 4,20 38,4 10,5 3,66 37,2 11,7 3,1615 41,2 8,4 4,89 40,3 9,4 4,28 39,2 10,5 3,73 37,9 11,8 3,2216 42,0 8,4 4,99 41,1 9,4 4,36 40,0 10,6 3,79 38,7 11,8 3,2817 42,9 8,4 5,08 42,0 9,5 4,44 40,9 10,6 3,86 39,5 11,8 3,3418 43,8 8,4 5,19 42,9 9,5 4,53 41,7 10,6 3,94 40,3 11,9 3,40

41

5 37,8 9,4 4,02 36,8 10,4 3,53 35,7 11,6 3,08 34,4 12,9 2,666 38,7 9,5 4,09 37,8 10,5 3,60 36,6 11,7 3,14 35,3 13,0 2,717 39,7 9,5 4,18 38,7 10,5 3,67 37,6 11,7 3,20 36,2 13,1 2,768 40,7 9,6 4,26 39,7 10,6 3,74 38,5 11,8 3,26 37,0 13,2 2,819 41,7 9,6 4,34 40,6 10,7 3,81 39,4 11,9 3,32 37,9 13,2 2,8710 42,7 9,6 4,42 41,6 10,7 3,88 40,3 11,9 3,38 38,8 13,3 2,9113 45,8 9,8 4,67 44,6 10,9 4,10 43,2 12,1 3,56 41,5 13,5 3,0714 46,8 9,9 4,75 45,6 10,9 4,16 44,2 12,2 3,62 42,4 13,6 3,1215 47,9 9,9 4,84 46,6 11,0 4,24 45,1 12,3 3,68 43,4 13,7 3,1716 49,0 9,9 4,92 47,7 11,1 4,31 46,1 12,3 3,74 44,3 13,8 3,2217 50,0 10,0 5,00 48,7 11,1 4,38 47,1 12,4 3,80 45,3 13,8 3,2718 51,2 10,1 5,09 49,8 11,2 4,45 48,2 12,5 3,86 46,2 13,9 3,32

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

42

HEATING CAPACITIES - MAROON 2 HT

Pt: Heating capacity [kW]

Pa: Total absorbed compressor power [kW]

Ta: Dry bulb temperature of the evaporator inlet air [°C]

RH: Relative humidity of the input air at the evaporator [%]

Model

Ta RH Condenser inlet water temperature [°C]

[°C] %30/35 40/45 50/55 55/60

Pt Pat COP Pt Pat COP Pt Pat COP Pt Pat COP

7

-20 90 3,3 1,5 2,22 * * * * * * * * *-15 90 3,8 1,5 2,50 3,7 1,8 2,11 * * * * * *-10 90 4,4 1,6 2,81 4,3 1,8 2,35 * * * * * *-7 89 4,8 1,6 3,01 4,7 1,9 2,50 4,6 2,2 2,07 * * *-2 89 5,4 1,6 3,37 5,3 1,9 2,79 5,2 2,3 2,28 * * *0 88 5,7 1,6 3,53 5,6 1,9 2,90 5,4 2,3 2,36 5,2 2,7 1,922 88 6,0 1,6 3,70 5,8 1,9 3,02 5,6 2,3 2,44 5,4 2,7 1,995 87 6,4 1,6 3,94 6,2 1,9 3,20 6,0 2,3 2,58 5,7 2,8 2,087 87 6,8 1,6 4,15 6,6 2,0 3,36 6,3 2,3 2,68 6,0 2,8 2,1510 86 7,3 1,6 4,46 7,0 2,0 3,59 6,7 2,4 2,84 6,3 2,8 2,2612 86 7,7 1,6 4,68 7,4 2,0 3,75 7,0 2,4 2,97 6,6 2,8 2,3415 86 8,2 1,6 5,03 7,9 2,0 4,02 7,5 2,4 3,14 7,0 2,8 2,46

9

-20 90 4,3 1,9 2,33 * * * * * * * * *-15 90 4,9 1,9 2,58 5,0 2,3 2,17 * * * * * *-10 90 5,5 1,9 2,88 5,6 2,3 2,40 * * * * * *-7 89 6,0 1,9 3,09 6,0 2,3 2,56 6,0 2,8 2,11 * * *-2 89 6,8 2,0 3,48 6,7 2,4 2,83 6,7 2,9 2,31 * * *0 88 7,1 2,0 3,65 7,0 2,4 2,94 6,9 2,9 2,39 6,8 3,5 1,942 88 7,5 2,0 3,81 7,4 2,4 3,08 7,2 2,9 2,49 7,0 3,5 1,995 87 8,0 2,0 4,09 7,9 2,4 3,28 7,6 2,9 2,61 7,4 3,5 2,097 87 8,5 2,0 4,30 8,3 2,4 3,43 8,0 2,9 2,73 7,7 3,5 2,1610 86 9,1 2,0 4,62 8,8 2,4 3,65 8,5 2,9 2,89 8,1 3,6 2,2612 86 9,5 2,0 4,84 9,3 2,4 3,83 8,9 3,0 3,01 8,4 3,6 2,3515 86 10,3 2,0 5,26 9,9 2,4 4,11 9,5 3,0 3,20 8,8 3,6 2,47

11

-20 90 5,5 2,3 2,38 * * * * * * * * *-15 90 6,3 2,4 2,64 6,3 2,8 2,21 * * * * * *-10 90 7,1 2,4 2,92 7,1 2,9 2,43 * * * * * *-7 89 7,7 2,5 3,11 7,7 3,0 2,57 7,6 3,6 2,12 * * *-2 89 8,7 2,5 3,48 8,6 3,0 2,83 8,4 3,7 2,30 * * *0 88 9,2 2,5 3,63 9,0 3,1 2,94 8,8 3,7 2,37 8,5 4,4 1,932 88 9,6 2,5 3,79 9,4 3,1 3,06 9,2 3,7 2,46 8,8 4,4 1,985 87 10,3 2,5 4,05 10,1 3,1 3,24 9,7 3,8 2,58 9,3 4,5 2,067 87 10,8 2,6 4,23 10,5 3,1 3,37 10,2 3,8 2,68 9,6 4,5 2,1210 86 11,6 2,6 4,52 11,3 3,2 3,58 10,8 3,8 2,83 10,2 4,6 2,2112 86 12,2 2,6 4,76 11,8 3,2 3,73 11,3 3,9 2,93 10,6 4,6 2,2915 86 13,1 2,6 5,09 12,7 3,2 3,99 12,0 3,9 3,10 11,2 4,7 2,40

13

-20 90 7,4 3,0 2,44 7,8 3,7 2,11 * * * * * *-15 90 8,3 3,0 2,72 8,7 3,7 2,33 * * * * * *-10 90 9,2 3,1 2,99 9,6 3,8 2,55 10,1 4,7 2,15 * * *-7 89 9,9 3,1 3,19 10,2 3,8 2,69 10,6 4,7 2,25 * * *-2 89 11,0 3,1 3,52 11,3 3,8 2,95 11,6 4,7 2,44 12,0 5,9 2,030 88 11,4 3,1 3,66 11,7 3,8 3,04 11,9 4,8 2,51 12,3 5,9 2,082 88 11,9 3,1 3,80 12,1 3,8 3,16 12,4 4,8 2,60 12,7 5,9 2,145 87 12,6 3,1 4,02 12,8 3,9 3,32 13,0 4,8 2,71 13,1 5,9 2,217 87 13,1 3,1 4,19 13,3 3,9 3,45 13,5 4,8 2,81 13,5 6,0 2,2710 86 13,9 3,1 4,44 14,0 3,9 3,63 14,1 4,8 2,93 14,1 6,0 2,3612 86 14,4 3,1 4,62 14,5 3,9 3,77 14,6 4,8 3,03 14,5 6,0 2,4315 86 15,3 3,1 4,95 15,4 3,9 3,98 15,3 4,8 3,18 15,1 6,0 2,52

17

-20 90 9,0 3,6 2,46 9,5 4,4 2,15 * * * * * *-15 90 10,1 3,7 2,73 10,6 4,5 2,36 * * * * * *-10 90 11,3 3,8 2,99 11,8 4,6 2,57 12,4 5,7 2,18 * * *-7 89 12,1 3,8 3,18 12,5 4,6 2,70 13,1 5,7 2,28 * * *-2 89 13,4 3,8 3,51 13,9 4,7 2,94 14,3 5,8 2,46 14,8 7,2 2,060 88 14,0 3,8 3,65 14,4 4,7 3,05 14,8 5,9 2,52 15,2 7,2 2,102 88 14,6 3,8 3,80 14,9 4,7 3,16 15,3 5,9 2,60 15,7 7,3 2,165 87 15,4 3,8 4,02 15,8 4,8 3,32 16,1 5,9 2,72 16,3 7,3 2,237 87 16,1 3,8 4,20 16,4 4,8 3,45 16,7 5,9 2,81 16,8 7,4 2,2710 86 17,1 3,8 4,46 17,3 4,8 3,63 17,5 5,9 2,94 17,4 7,5 2,3112 86 17,8 3,8 4,65 18,0 4,8 3,78 18,1 6,0 3,04 17,9 7,7 2,3215 86 18,9 3,8 4,97 19,0 4,7 4,00 19,0 6,0 3,19 18,5 8,2 2,27

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

43

Pt: Heating capacity [kW]

Pa: Total absorbed compressor power [kW]

Ta: Dry bulb temperature of the evaporator inlet air [°C]

RH: Relative humidity of the input air at the evaporator [%]

HEATING CAPACITIES - MAROON 2 HT

Model

Ta RH Condenser inlet water temperature [°C]

[°C] %30/35 40/45 50/55 55/60

Pt Pat COP Pt Pat COP Pt Pat COP Pt Pat COP

22

-20 90 11,8 4,8 2,45 12,5 6,0 2,08 * * * * * *-15 90 13,3 4,9 2,73 14,0 6,1 2,30 * * * * * *-10 90 14,8 4,9 3,00 15,4 6,1 2,52 16,2 7,7 2,09 * * *-7 89 15,9 5,0 3,19 16,4 6,2 2,66 17,1 7,8 2,20 * * *-2 89 17,7 5,0 3,52 18,1 6,2 2,91 18,7 7,8 2,38 19,2 9,8 1,960 88 18,4 5,0 3,65 18,8 6,2 3,01 19,2 7,9 2,44 19,7 9,9 2,002 88 19,1 5,0 3,79 19,5 6,3 3,12 19,9 7,9 2,53 20,3 9,9 2,065 87 20,3 5,0 4,02 20,6 6,3 3,28 20,9 7,9 2,64 21,1 9,9 2,137 87 21,1 5,0 4,18 21,4 6,3 3,39 21,6 7,9 2,73 21,7 9,9 2,1810 86 22,4 5,0 4,44 22,6 6,3 3,58 22,7 7,9 2,86 22,5 10,0 2,2412 86 23,2 5,0 4,63 23,4 6,3 3,71 23,4 7,9 2,95 23,0 10,1 2,2815 86 24,6 5,0 4,93 24,7 6,3 3,93 24,6 8,0 3,10 23,8 10,3 2,31

26

-20 90 13,7 5,9 2,34 14,3 7,3 1,95 * * * * * *-15 90 15,5 5,9 2,62 16,1 7,4 2,17 * * * * * *-10 90 17,4 5,9 2,93 18,0 7,4 2,41 18,6 9,3 1,99 * * *-7 89 18,7 6,0 3,14 19,2 7,5 2,58 19,8 9,4 2,11 * * *-2 89 20,9 6,0 3,50 21,4 7,5 2,86 21,9 9,4 2,33 22,4 11,7 1,920 88 21,7 6,0 3,64 22,1 7,5 2,96 22,6 9,4 2,40 23,1 11,7 1,982 88 22,7 6,0 3,80 23,1 7,5 3,09 23,6 9,4 2,50 24,0 11,7 2,045 87 24,1 6,0 4,03 24,5 7,5 3,27 24,8 9,4 2,63 25,1 11,7 2,147 87 25,2 6,0 4,19 25,5 7,5 3,40 25,8 9,4 2,74 25,9 11,8 2,2010 86 26,7 6,0 4,45 27,0 7,5 3,60 27,2 9,4 2,88 27,1 11,8 2,2912 86 27,9 6,0 4,62 28,1 7,5 3,74 28,2 9,4 2,99 27,9 11,9 2,3515 86 29,6 6,1 4,90 29,7 7,5 3,96 29,7 9,4 3,16 29,1 12,0 2,42

32

-20 90 16,7 7,3 2,29 17,5 9,0 1,94 * * * * * *-15 90 19,0 7,3 2,60 19,8 9,0 2,19 * * * * * *-10 90 21,2 7,3 2,91 22,1 9,1 2,44 22,9 11,2 2,05 * * *-7 89 22,7 7,3 3,12 23,6 9,1 2,61 24,5 11,2 2,19 * * *-2 89 25,1 7,2 3,47 26,2 9,0 2,90 27,0 11,2 2,41 27,7 13,7 2,020 88 26,1 7,2 3,61 27,1 9,0 3,01 28,0 11,2 2,50 28,6 13,7 2,092 88 27,1 7,2 3,75 28,1 9,0 3,12 29,0 11,2 2,59 29,6 13,7 2,165 87 28,8 7,2 3,97 29,7 9,0 3,31 30,5 11,2 2,73 31,1 13,7 2,277 87 29,9 7,2 4,13 30,8 9,0 3,44 31,6 11,2 2,84 32,1 13,7 2,3510 86 31,7 7,3 4,36 32,5 8,9 3,63 33,2 11,1 2,99 33,6 13,7 2,4612 86 33,1 7,3 4,53 33,8 8,9 3,77 34,4 11,1 3,10 34,7 13,6 2,5515 86 35,0 7,4 4,75 35,7 8,9 3,99 36,2 11,1 3,27 36,4 13,6 2,67

36

-20 90 18,9 8,1 2,34 19,2 9,8 1,97 * * * * * *-15 90 21,6 8,1 2,65 22,0 9,9 2,23 * * * * * *-10 90 24,3 8,2 2,96 24,9 10,0 2,48 25,4 12,3 2,06 * * *-7 89 26,0 8,2 3,16 26,6 10,1 2,65 27,3 12,4 2,19 * * *-2 89 29,0 8,3 3,49 29,7 10,2 2,92 30,4 12,6 2,42 31,0 15,5 2,000 88 30,1 8,3 3,63 30,8 10,2 3,03 31,5 12,6 2,50 32,1 15,5 2,072 88 31,3 8,3 3,77 32,1 10,2 3,14 32,8 12,6 2,60 33,4 15,6 2,145 87 33,3 8,3 4,00 34,0 10,2 3,32 34,6 12,7 2,73 35,2 15,7 2,257 87 34,5 8,3 4,15 35,2 10,2 3,45 35,9 12,7 2,83 36,4 15,7 2,3210 86 36,6 8,3 4,42 37,3 10,2 3,65 37,9 12,7 2,98 38,2 15,7 2,4312 86 38,0 8,3 4,59 38,5 10,2 3,77 39,2 12,7 3,08 39,6 15,8 2,5115 86 40,2 8,2 4,89 40,9 10,2 4,01 41,3 12,7 3,25 41,4 15,8 2,63

41

-20 90 20,8 8,8 2,36 21,6 10,7 2,01 * * * * * *-15 90 23,5 8,9 2,65 24,3 10,8 2,25 * * * * * *-10 90 26,2 8,9 2,93 27,1 10,9 2,48 28,2 13,5 2,08 * * *-7 89 28,0 9,0 3,12 28,9 11,0 2,63 29,9 13,6 2,20 * * *-2 89 31,2 9,0 3,45 32,1 11,1 2,89 33,0 13,7 2,40 34,0 17,0 2,000 88 32,6 9,1 3,60 33,4 11,1 3,00 34,2 13,8 2,48 35,1 17,0 2,062 88 33,8 9,1 3,72 34,6 11,1 3,11 35,5 13,8 2,57 36,4 17,1 2,135 87 36,1 9,1 3,96 36,8 11,2 3,29 37,5 13,9 2,71 38,2 17,2 2,227 87 37,6 9,1 4,13 38,2 11,2 3,42 38,9 13,9 2,80 39,5 17,2 2,2910 86 39,9 9,1 4,37 40,6 11,2 3,61 41,1 14,0 2,95 41,6 17,3 2,4012 86 41,6 9,1 4,55 42,2 11,2 3,75 42,6 14,0 3,04 42,9 17,3 2,4715 86 44,2 9,1 4,83 44,7 11,2 3,97 45,1 14,0 3,22 45,2 17,4 2,60

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

44

COOLING CAPACITIES - MAROON 2 HT

Pf: Cooling power [kW]

Pa: Total absorbed compressor power [kW]

To: Utility outlet water temperature to the utility exchanger [°C]

Model

To External air temperature [°C]

[°C]25 30 35 40

Pf Pat EER Pf Pat EER Pf Pat EER Pf Pat EER

50

5 39,8 10,1 3,95 38,6 11,3 3,42 37,2 12,6 2,95 35,6 14,2 2,526 40,8 10,1 4,04 39,5 11,3 3,49 38,1 12,7 3,00 36,4 14,2 2,567 41,8 10,1 4,12 40,5 11,4 3,56 39,0 12,7 3,06 37,3 14,3 2,618 42,8 10,2 4,21 41,5 11,4 3,63 39,9 12,8 3,12 38,1 14,4 2,659 43,8 10,2 4,29 42,5 11,5 3,70 40,8 12,9 3,18 39,0 14,4 2,7010 44,9 10,2 4,38 43,4 11,5 3,77 41,8 12,9 3,23 39,9 14,5 2,7513 48,0 10,3 4,64 46,4 11,6 3,99 44,6 13,1 3,41 42,5 14,7 2,8914 49,1 10,4 4,73 47,4 11,7 4,06 45,5 13,1 3,46 43,3 14,8 2,9415 50,2 10,4 4,82 48,5 11,7 4,13 46,5 13,2 3,52 44,2 14,8 2,9816 51,2 10,4 4,92 49,5 11,8 4,21 47,5 13,2 3,58 45,2 14,9 3,0317 52,4 10,4 5,01 50,6 11,8 4,29 48,5 13,3 3,65 46,1 14,9 3,0818 53,5 10,5 5,11 51,6 11,8 4,36 49,5 13,3 3,71 47,0 15,0 3,13

60

5 45,2 11,7 3,86 43,9 13,1 3,36 42,4 14,7 2,90 40,7 16,4 2,486 46,3 11,8 3,93 45,0 13,1 3,43 43,5 14,7 2,96 41,8 16,5 2,537 47,5 11,8 4,01 46,2 13,2 3,50 44,7 14,8 3,02 42,9 16,6 2,588 48,7 11,9 4,09 47,4 13,3 3,56 45,8 14,9 3,08 43,9 16,6 2,649 49,9 12,0 4,17 48,5 13,4 3,64 46,9 14,9 3,14 45,0 16,7 2,6910 51,2 12,1 4,24 49,7 13,4 3,70 48,1 15,0 3,20 46,1 16,8 2,7513 54,9 12,3 4,47 53,4 13,6 3,91 51,5 15,2 3,38 49,5 17,0 2,9014 56,2 12,4 4,55 54,6 13,7 3,98 52,7 15,3 3,44 50,6 17,1 2,9615 57,5 12,4 4,62 55,8 13,8 4,04 53,9 15,4 3,50 51,7 17,2 3,0116 58,8 12,5 4,69 57,1 13,9 4,11 55,1 15,5 3,56 52,9 17,3 3,0617 60,1 12,6 4,77 58,4 14,0 4,17 56,4 15,6 3,62 54,1 17,4 3,1118 61,5 12,7 4,84 59,7 14,1 4,24 57,6 15,7 3,68 55,3 17,5 3,17

70

5 56,5 14,3 3,94 55,4 16,1 3,44 53,8 18,1 2,98 51,9 20,3 2,566 57,9 14,4 4,00 56,7 16,2 3,51 55,1 18,1 3,04 53,1 20,4 2,617 59,3 14,6 4,07 58,1 16,3 3,57 56,5 18,2 3,09 54,4 20,5 2,668 60,7 14,7 4,14 59,4 16,4 3,63 57,8 18,3 3,15 55,7 20,6 2,719 62,1 14,8 4,20 60,8 16,5 3,69 59,1 18,4 3,21 57,0 20,7 2,7610 63,5 14,9 4,27 62,2 16,6 3,75 60,5 18,5 3,26 58,3 20,8 2,8113 67,9 15,3 4,44 66,5 16,9 3,92 64,6 18,9 3,42 62,1 21,1 2,9514 69,4 15,4 4,49 67,9 17,1 3,98 65,9 19,0 3,47 63,4 21,2 2,9915 70,9 15,6 4,55 69,3 17,2 4,03 67,3 19,1 3,52 64,8 21,3 3,0416 72,4 15,8 4,60 70,8 17,4 4,08 68,7 19,3 3,57 66,1 21,4 3,0817 74,0 15,9 4,65 72,3 17,5 4,13 70,1 19,4 3,62 67,4 21,6 3,1318 75,5 16,1 4,70 73,8 17,7 4,18 71,6 19,5 3,66 68,8 21,7 3,17

80

5 63,7 16,6 3,84 62,4 18,5 3,37 60,7 20,6 2,94 58,6 23,0 2,556 65,2 16,6 3,92 63,8 18,6 3,44 62,1 20,7 3,00 60,0 23,1 2,607 66,8 16,7 4,00 65,3 18,6 3,51 63,6 20,8 3,06 61,5 23,2 2,658 68,3 16,8 4,08 66,9 18,7 3,58 65,1 20,9 3,12 62,9 23,3 2,709 69,9 16,8 4,16 68,4 18,8 3,65 66,6 20,9 3,18 64,4 23,4 2,7510 71,5 16,9 4,24 70,0 18,8 3,72 68,1 21,0 3,24 65,8 23,5 2,8013 76,3 17,0 4,49 74,6 19,0 3,93 72,6 21,3 3,42 70,2 23,8 2,9514 78,0 17,0 4,57 76,2 19,1 4,00 74,2 21,3 3,48 71,6 23,9 3,0015 79,6 17,1 4,66 77,8 19,1 4,07 75,7 21,4 3,54 73,1 24,0 3,0516 81,3 17,1 4,75 79,5 19,2 4,14 77,3 21,5 3,60 74,6 24,1 3,1017 83,0 17,2 4,84 81,1 19,2 4,22 78,9 21,5 3,66 76,1 24,1 3,1618 84,7 17,2 4,93 82,8 19,3 4,30 80,5 21,6 3,73 77,7 24,2 3,21

90

5 73,2 19,1 3,84 71,3 21,2 3,37 69,1 23,6 2,93 66,4 26,3 2,536 75,0 19,2 3,91 73,1 21,3 3,43 70,8 23,7 2,99 68,0 26,5 2,577 76,9 19,3 3,99 74,9 21,4 3,50 72,5 23,8 3,04 69,7 26,6 2,628 78,7 19,4 4,06 76,7 21,5 3,56 74,3 24,0 3,09 71,4 26,8 2,669 80,7 19,5 4,14 78,6 21,7 3,62 76,1 24,2 3,15 73,1 27,0 2,7110 82,6 19,6 4,21 80,4 21,8 3,69 77,9 24,3 3,20 74,8 27,2 2,7513 88,5 20,0 4,43 86,1 22,2 3,88 83,3 24,8 3,36 79,9 27,7 2,8914 90,5 20,1 4,51 88,0 22,3 3,94 85,1 24,9 3,42 81,6 27,9 2,9315 92,5 20,2 4,58 90,0 22,5 4,00 87,0 25,1 3,47 83,4 28,0 2,9816 94,6 20,3 4,66 92,0 22,6 4,07 88,9 25,2 3,52 85,2 28,2 3,0217 96,7 20,4 4,73 94,0 22,8 4,13 90,8 25,4 3,57 87,0 28,4 3,0618 98,8 20,6 4,80 96,0 22,9 4,19 92,7 25,6 3,63 88,8 28,6 3,11

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

45

HEATING CAPACITIES - MAROON 2 HT

Pt: Heating capacity [kW]

Pa: Total absorbed compressor power [kW]

Ta: Dry bulb temperature of the evaporator inlet air [°C]

RH: Relative humidity of the input air at the evaporator [%]

Model

Ta RH Condenser inlet water temperature [°C]

[°C] %30/35 40/45 50/55 55/60

Pt Pat COP Pt Pat COP Pt Pat COP Pt Pat COP

50

-20 90 23,3 9,6 2,43 24,7 11,9 2,08 * * * * * *-15 90 26,4 9,7 2,73 27,7 12,0 2,31 * * * * * *-10 90 29,5 9,8 3,02 30,6 12,1 2,53 32,1 15,3 2,10 * * *-7 89 31,5 9,8 3,21 32,5 12,2 2,67 33,9 15,3 2,21 * * *-2 89 35,1 9,9 3,55 36,0 12,3 2,93 37,0 15,4 2,40 38,2 19,4 1,970 88 36,5 9,9 3,68 37,3 12,3 3,03 38,3 15,5 2,47 39,3 19,4 2,032 88 38,0 9,9 3,82 38,8 12,3 3,14 39,6 15,5 2,55 40,5 19,5 2,085 87 40,5 9,9 4,07 41,0 12,4 3,31 41,6 15,6 2,67 42,2 19,5 2,167 87 42,0 9,9 4,23 42,6 12,4 3,43 43,1 15,6 2,76 43,5 19,5 2,2310 86 44,7 9,9 4,52 45,1 12,4 3,63 45,2 15,6 2,89 45,3 19,6 2,3112 86 46,5 9,9 4,71 46,7 12,4 3,76 46,8 15,7 2,99 46,7 19,6 2,3815 86 49,5 9,8 5,05 49,6 12,4 4,01 49,3 15,7 3,15 48,7 19,6 2,48

60

-20 90 27,4 11,6 2,36 28,6 14,5 1,98 * * * * * *-15 90 31,2 11,7 2,68 32,4 14,6 2,23 * * * * * *-10 90 35,1 11,7 3,00 36,2 14,7 2,47 37,6 18,3 2,05 * * *-7 89 37,6 11,7 3,20 38,8 14,7 2,64 40,1 18,4 2,17 * * *-2 89 42,0 11,7 3,58 43,1 14,7 2,93 44,3 18,5 2,39 45,5 22,9 1,990 88 43,8 11,7 3,73 44,8 14,7 3,04 45,9 18,5 2,48 47,0 23,0 2,042 88 45,6 11,7 3,88 46,6 14,7 3,17 47,7 18,5 2,58 48,8 23,0 2,125 87 48,6 11,8 4,13 49,5 14,7 3,36 50,3 18,5 2,72 51,2 23,0 2,227 87 50,5 11,8 4,30 51,4 14,7 3,49 52,2 18,5 2,82 53,1 23,0 2,3010 86 53,9 11,8 4,58 54,6 14,7 3,71 55,2 18,5 2,98 55,6 23,0 2,4112 86 56,2 11,8 4,76 56,6 14,7 3,85 57,1 18,5 3,09 57,6 23,0 2,5015 86 59,9 11,8 5,06 60,3 14,7 4,10 60,5 18,5 3,28 60,5 23,0 2,63

70

-20 90 31,3 13,7 2,28 32,6 17,0 1,92 * * * * * *-15 90 35,5 13,7 2,59 37,0 17,1 2,16 * * * * * *-10 90 39,7 13,7 2,90 41,4 17,2 2,40 42,9 21,4 2,00 * * *-7 89 42,3 13,7 3,09 44,1 17,2 2,56 45,7 21,5 2,12 * * *-2 89 46,9 13,6 3,45 48,8 17,2 2,84 50,5 21,6 2,34 51,8 26,5 1,950 88 49,0 13,6 3,60 50,8 17,2 2,96 52,4 21,6 2,43 53,6 26,6 2,012 88 51,0 13,6 3,75 52,8 17,1 3,08 54,3 21,6 2,51 55,5 26,6 2,085 87 54,0 13,6 3,98 55,8 17,1 3,26 57,3 21,5 2,66 58,3 26,7 2,197 87 56,2 13,6 4,14 57,9 17,1 3,39 59,4 21,5 2,76 60,2 26,7 2,2610 86 59,5 13,6 4,37 61,2 17,0 3,59 62,5 21,5 2,91 63,2 26,6 2,3812 86 62,0 13,7 4,54 63,5 17,0 3,73 64,8 21,4 3,02 65,2 26,6 2,4515 86 65,8 13,8 4,78 67,2 17,0 3,94 68,3 21,4 3,20 68,5 26,5 2,58

80

-20 90 38,0 16,0 2,38 38,6 19,4 1,99 * * * * * *-15 90 43,4 16,1 2,70 44,3 19,6 2,26 * * * * * *-10 90 48,8 16,3 3,00 50,0 19,9 2,52 51,1 24,5 2,09 * * *-7 89 52,3 16,3 3,20 53,6 20,0 2,68 54,8 24,7 2,22 * * *-2 89 58,3 16,4 3,55 59,7 20,2 2,96 61,1 25,0 2,44 62,4 30,8 2,020 88 60,7 16,5 3,69 62,2 20,2 3,07 63,6 25,1 2,54 64,7 31,0 2,092 88 63,0 16,5 3,83 64,5 20,3 3,18 65,9 25,1 2,62 67,2 31,1 2,165 87 67,0 16,5 4,06 68,4 20,3 3,37 69,8 25,2 2,76 70,9 31,2 2,277 87 69,7 16,5 4,23 71,0 20,3 3,49 72,3 25,3 2,86 73,4 31,3 2,3410 86 73,8 16,5 4,48 75,2 20,3 3,69 76,4 25,3 3,01 77,2 31,4 2,4612 86 76,7 16,4 4,67 78,0 20,3 3,84 78,9 25,4 3,11 79,7 31,5 2,5315 86 81,2 16,3 4,97 82,5 20,3 4,06 83,4 25,4 3,29 83,8 31,5 2,66

90

-20 90 42,1 17,5 2,40 43,8 21,4 2,05 * * * * * *-15 90 47,7 17,7 2,70 49,5 21,6 2,29 * * * * * *-10 90 53,3 17,8 2,99 55,1 21,8 2,53 57,3 27,0 2,12 * * *-7 89 56,9 17,9 3,18 58,6 21,9 2,67 60,8 27,2 2,23 * * *-2 89 63,4 18,0 3,52 65,1 22,1 2,94 67,1 27,5 2,44 69,1 34,0 2,030 88 66,3 18,1 3,66 67,8 22,2 3,06 69,6 27,6 2,53 71,6 34,1 2,102 88 69,1 18,1 3,81 70,5 22,3 3,17 72,1 27,6 2,61 74,0 34,2 2,165 87 73,4 18,2 4,04 74,8 22,3 3,35 76,3 27,8 2,75 77,8 34,4 2,267 87 76,5 18,2 4,20 77,9 22,4 3,48 79,2 27,8 2,85 80,4 34,5 2,3310 86 81,2 18,2 4,45 82,5 22,4 3,68 83,7 28,0 2,99 84,6 34,7 2,4412 86 84,7 18,3 4,64 85,9 22,5 3,82 86,9 28,0 3,10 87,3 34,8 2,5115 86 90,0 18,3 4,93 91,1 22,5 4,04 91,9 28,1 3,27 92,1 35,0 2,63

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

46

Model

To DHW temperature [°C]

[°C]40/45 45/50 50/55 55/60

Pf Pa Pt EER COP Pf Pa Pt EER COP Pf Pa Pt EER COP Pf Pa Pt EER COP

RECOVERY CAPACITIES - MAROON 2 HT

Pf: Cooling power [kW]

Pt: Heat power [kW]

To: Utility outlet water temperature (°C)

7

5 5,5 1,7 7,2 3,16 4,16 5,1 1,9 7,0 2,65 3,65 4,7 2,1 6,8 2,20 3,20 4,2 2,4 6,6 1,78 2,78

7 5,9 1,8 7,6 3,36 4,35 5,5 1,9 7,4 2,83 3,83 5,0 2,1 7,2 2,34 3,35 4,5 2,4 6,9 1,89 2,89

10 6,5 1,8 8,2 3,70 4,70 6,0 1,9 8,0 3,10 4,10 5,5 2,2 7,7 2,56 3,56 5,0 2,4 7,4 2,07 3,07

14 7,3 1,8 9,1 4,18 5,18 6,8 2,0 8,8 3,49 4,49 6,3 2,2 8,4 2,88 3,88 5,6 2,4 8,1 2,33 3,33

18 8,3 1,8 10,0 4,71 5,71 7,7 2,0 9,6 3,94 4,94 7,1 2,2 9,3 3,24 4,24 6,4 2,4 8,8 2,63 3,62

9

5 7,3 2,2 9,5 3,31 4,31 6,8 2,5 9,2 2,77 3,77 6,2 2,7 9,0 2,29 3,29 5,6 3,0 8,6 1,84 2,84

7 7,8 2,2 10,0 3,54 4,54 7,3 2,5 9,7 2,96 3,96 6,7 2,7 9,4 2,44 3,44 6,0 3,1 9,0 1,96 2,96

10 8,6 2,2 10,8 3,89 4,90 8,0 2,5 10,4 3,24 4,24 7,3 2,7 10,1 2,67 3,67 6,6 3,1 9,6 2,15 3,15

14 9,7 2,2 11,9 4,40 5,40 9,0 2,5 11,5 3,66 4,66 8,3 2,8 11,0 3,01 4,01 7,4 3,1 10,5 2,42 3,42

18 10,9 2,2 13,1 4,98 5,97 10,2 2,5 12,6 4,14 5,15 9,3 2,8 12,1 3,39 4,39 8,4 3,1 11,5 2,72 3,72

11

5 9,6 2,9 12,5 3,29 4,29 8,9 3,2 12,2 2,76 3,76 8,2 3,6 11,8 2,28 3,27 7,3 4,0 11,3 1,84 2,84

7 10,2 2,9 13,1 3,49 4,50 9,5 3,3 12,7 2,92 3,92 8,7 3,6 12,3 2,41 3,41 7,8 4,0 11,8 1,94 2,94

10 11,2 2,9 14,1 3,80 4,80 10,4 3,3 13,7 3,17 4,18 9,5 3,6 13,2 2,62 3,61 8,5 4,0 12,6 2,11 3,11

14 12,6 3,0 15,5 4,25 5,25 11,7 3,3 15,0 3,55 4,55 10,7 3,7 14,4 2,92 3,92 9,6 4,1 13,7 2,34 3,34

18 14,1 3,0 17,0 4,75 5,75 13,1 3,3 16,4 3,96 4,95 12,0 3,7 15,7 3,25 4,25 10,8 4,1 14,9 2,64 3,65

13

5 11,4 3,2 14,6 3,57 4,57 10,9 3,6 14,6 2,99 4,00 10,3 4,2 14,5 2,48 3,48 9,6 4,7 14,3 2,03 3,03

7 12,0 3,2 15,2 3,75 4,75 11,5 3,6 15,1 3,15 4,15 10,8 4,2 15,0 2,61 3,61 10,1 4,8 14,8 2,12 3,12

10 12,9 3,2 16,1 4,05 5,05 12,3 3,6 16,0 3,39 4,39 11,7 4,2 15,8 2,81 3,81 10,8 4,8 15,6 2,28 3,28

14 14,2 3,2 17,4 4,50 5,50 13,6 3,6 17,2 3,75 4,75 12,8 4,1 16,9 3,09 4,09 11,9 4,7 16,6 2,50 3,50

18 15,6 3,1 18,7 5,02 6,02 14,9 3,6 18,5 4,15 5,15 14,0 4,1 18,1 3,41 4,41 13,4 4,7 18,1 2,82 3,82

17

5 13,6 4,1 17,7 3,33 4,33 13,1 4,6 17,7 2,82 3,82 12,5 5,3 17,8 2,36 3,36 11,7 6,0 17,7 1,95 2,95

7 14,3 4,1 18,4 3,51 4,51 13,8 4,6 18,4 2,97 3,97 13,1 5,3 18,4 2,48 3,48 12,3 6,0 18,3 2,04 3,04

10 15,4 4,1 19,5 3,79 4,79 14,8 4,6 19,5 3,19 4,19 14,1 5,3 19,4 2,67 3,67 13,2 6,0 19,2 2,19 3,19

14 17,0 4,1 21,0 4,20 5,20 16,3 4,6 20,9 3,52 4,52 15,5 5,3 20,7 2,93 3,93 14,4 6,0 20,5 2,39 3,39

18 18,7 4,0 22,7 4,64 5,64 17,9 4,6 22,5 3,89 4,90 16,9 5,3 22,2 3,22 4,22 16,3 6,0 22,3 2,70 3,70

22

5 18,8 5,5 24,3 3,39 4,39 17,9 6,3 24,2 2,85 3,85 17,0 7,2 24,1 2,36 3,36 15,8 8,2 24,0 1,93 2,93

7 19,7 5,5 25,3 3,57 4,57 18,9 6,3 25,2 2,99 4,00 17,8 7,2 25,0 2,48 3,48 16,6 8,2 24,8 2,02 3,02

10 21,3 5,5 26,8 3,85 4,85 20,3 6,3 26,6 3,22 4,22 19,2 7,2 26,4 2,67 3,67 17,8 8,2 26,0 2,17 3,17

14 23,4 5,5 28,8 4,27 5,27 22,3 6,3 28,6 3,56 4,56 21,0 7,2 28,2 2,93 3,93 19,5 8,2 27,7 2,37 3,37

18 25,6 5,4 31,0 4,75 5,75 24,4 6,2 30,6 3,93 4,93 23,0 7,1 30,1 3,23 4,23 22,0 8,2 30,2 2,67 3,68

26

5 21,6 6,7 28,3 3,21 4,21 20,7 7,6 28,3 2,72 3,72 19,6 8,6 28,3 2,27 3,27 18,4 9,8 28,3 1,87 2,87

7 22,8 6,7 29,5 3,39 4,39 21,8 7,6 29,4 2,87 3,87 20,8 8,6 29,4 2,40 3,40 19,5 9,8 29,3 1,98 2,98

10 24,6 6,7 31,3 3,67 4,67 23,6 7,6 31,2 3,11 4,11 22,5 8,6 31,1 2,60 3,60 21,1 9,8 31,0 2,15 3,15

14 27,2 6,7 33,9 4,05 5,05 26,1 7,6 33,7 3,44 4,44 24,9 8,6 33,5 2,88 3,88 23,4 9,8 33,2 2,38 3,38

18 29,9 6,7 36,6 4,45 5,45 28,7 7,6 36,3 3,78 4,78 27,4 8,6 36,0 3,18 4,18 26,4 9,8 36,3 2,69 3,69

32

5 28,8 7,7 36,4 3,76 4,76 27,9 8,7 36,6 3,22 4,22 26,8 9,8 36,6 2,73 3,73 25,4 11,1 36,6 2,28 3,28

7 30,3 7,6 37,9 3,96 4,96 29,4 8,7 38,1 3,40 4,40 28,3 9,8 38,1 2,89 3,89 26,8 11,1 37,9 2,41 3,41

10 32,6 7,7 40,2 4,26 5,26 31,6 8,6 40,3 3,67 4,67 30,4 9,8 40,2 3,12 4,12 28,9 11,1 40,0 2,61 3,61

14 35,7 7,7 43,4 4,65 5,65 34,7 8,6 43,4 4,02 5,02 33,4 9,7 43,2 3,44 4,44 31,8 11,0 42,8 2,88 3,88

18 39,1 7,8 46,9 5,03 6,03 38,0 8,7 46,7 4,38 5,38 36,6 9,7 46,3 3,76 4,76 34,8 11,0 45,8 3,16 4,16

36

5 31,6 8,9 40,5 3,54 4,54 30,6 10,1 40,6 3,03 4,03 29,3 11,4 40,7 2,57 3,57 27,8 13,0 40,7 2,14 3,15

7 33,2 8,9 42,1 3,73 4,73 32,2 10,1 42,2 3,19 4,19 30,9 11,4 42,3 2,71 3,71 29,3 13,0 42,2 2,26 3,26

10 35,6 8,9 44,5 4,02 5,02 34,5 10,0 44,6 3,44 4,44 33,2 11,4 44,6 2,92 3,92 31,6 13,0 44,5 2,43 3,43

14 39,0 8,8 47,8 4,44 5,44 37,8 10,0 47,8 3,79 4,80 36,4 11,3 47,7 3,21 4,21 34,6 12,9 47,5 2,68 3,68

18 42,6 8,7 51,2 4,91 5,91 41,3 9,9 51,2 4,18 5,18 39,8 11,2 51,0 3,54 4,54 37,8 12,8 50,6 2,94 3,94

41

5 36,3 9,9 46,2 3,65 4,65 35,0 11,2 46,2 3,13 4,13 33,6 12,7 46,2 2,65 3,65 31,7 14,4 46,1 2,21 3,21

7 38,3 9,9 48,2 3,85 4,85 37,0 11,2 48,2 3,30 4,30 35,4 12,7 48,1 2,79 3,79 33,5 14,4 47,9 2,32 3,32

10 41,3 9,9 51,2 4,16 5,16 39,9 11,2 51,1 3,56 4,56 38,2 12,7 50,9 3,01 4,01 36,2 14,4 50,6 2,50 3,50

14 45,5 9,9 55,4 4,59 5,59 44,0 11,2 55,2 3,92 4,92 42,1 12,7 54,9 3,31 4,31 39,9 14,5 54,4 2,75 3,75

18 50,0 9,9 59,9 5,06 6,06 48,3 11,2 59,5 4,32 5,32 46,3 12,7 59,0 3,64 4,64 43,8 14,5 58,3 3,03 4,03

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

47

Model

To DHW temperature [°C]

[°C]40/45 45/50 50/55 55/60

Pf Pa Pt EER COP Pf Pa Pt EER COP Pf Pa Pt EER COP Pf Pa Pt EER COP

RECOVERY CAPACITIES - MAROON 2 HT

Pf: Cooling power [kW]

Pt: Heat power [kW]

To: Utility outlet water temperature (°C)

50

5 37,7 10,9 48,6 3,47 4,47 35,9 12,6 48,5 2,84 3,84 34,0 14,4 48,3 2,36 3,36 31,9 16,2 48,1 1,97 2,97

7 39,4 11,1 50,5 3,56 4,56 37,7 12,6 50,3 2,98 3,98 35,7 14,4 50,1 2,49 3,49 33,6 16,2 49,8 2,07 3,07

10 42,5 11,0 53,5 3,85 4,85 40,6 12,6 53,2 3,22 4,22 38,4 14,3 52,8 2,68 3,68 36,0 16,2 52,2 2,23 3,23

14 46,7 11,0 57,6 4,26 5,26 44,6 12,6 57,1 3,55 4,55 42,2 14,3 56,4 2,95 3,95 39,5 16,1 55,6 2,45 3,45

18 51,2 10,8 62,0 4,74 5,75 48,8 12,4 61,3 3,93 4,93 46,2 14,2 60,4 3,26 4,26 43,2 16,1 59,3 2,69 3,69

60

5 42,8 13,0 55,8 3,30 4,30 40,7 15,2 55,9 2,68 3,68 38,7 17,3 55,9 2,24 3,24 36,6 19,4 56,0 1,89 2,89

7 45,2 13,0 58,2 3,48 4,48 43,0 15,2 58,2 2,83 3,83 40,9 17,2 58,1 2,38 3,38 38,8 19,4 58,1 2,00 3,00

10 48,5 13,4 61,8 3,63 4,63 46,5 15,1 61,7 3,07 4,07 44,3 17,2 61,5 2,58 3,58 42,0 19,3 61,3 2,18 3,18

14 53,5 13,3 66,8 4,02 5,02 51,4 15,1 66,5 3,41 4,41 49,1 17,1 66,2 2,87 3,87 46,6 19,2 65,8 2,43 3,43

18 58,9 13,3 72,3 4,43 5,43 56,7 15,1 71,7 3,76 4,76 54,2 17,0 71,2 3,18 4,18 51,5 19,1 70,6 2,69 3,69

70

5 55,1 15,3 70,4 3,61 4,61 53,0 17,8 70,8 2,97 3,97 50,8 20,2 71,0 2,52 3,52 48,3 22,6 70,9 2,13 3,13

7 57,9 15,3 73,2 3,79 4,79 55,8 17,8 73,6 3,13 4,13 53,5 20,1 73,7 2,66 3,66 51,0 22,6 73,5 2,26 3,26

10 61,9 15,7 77,6 3,95 4,95 60,1 17,7 77,8 3,39 4,39 57,7 20,0 77,7 2,88 3,88 54,9 22,4 77,4 2,45 3,45

14 68,0 15,7 83,7 4,32 5,32 65,9 17,7 83,6 3,72 4,72 63,4 19,9 83,3 3,18 4,18 60,4 22,3 82,7 2,71 3,71

18 74,4 15,9 90,2 4,68 5,68 72,1 17,8 89,9 4,06 5,06 69,4 19,9 89,3 3,49 4,49 66,2 22,2 88,4 2,98 3,98

80

5 61,4 17,6 79,1 3,48 4,48 59,0 20,5 79,5 2,87 3,87 56,5 23,2 79,8 2,43 3,43 53,8 26,1 79,9 2,06 3,06

7 64,5 17,6 82,2 3,66 4,66 62,1 20,5 82,6 3,03 4,03 59,6 23,2 82,8 2,57 3,57 56,8 26,1 82,8 2,18 3,18

10 68,9 18,1 87,0 3,82 4,82 66,7 20,5 87,2 3,26 4,26 64,1 23,2 87,3 2,77 3,77 61,2 26,0 87,2 2,35 3,35

14 75,4 17,9 93,3 4,22 5,22 73,1 20,3 93,4 3,60 4,60 70,4 23,0 93,4 3,06 4,06 67,2 25,9 93,1 2,59 3,59

18 82,3 17,6 100,0 4,67 5,67 79,8 20,1 99,9 3,97 4,97 76,9 22,8 99,7 3,37 4,37 73,4 25,7 99,1 2,86 3,86

90

5 70,7 19,7 90,4 3,59 4,59 67,7 22,9 90,6 2,96 3,96 64,7 25,9 90,6 2,50 3,50 61,5 29,0 90,5 2,12 3,12

7 74,5 19,7 94,2 3,78 4,78 71,4 22,9 94,3 3,12 4,12 68,3 25,9 94,2 2,64 3,64 64,9 29,1 94,0 2,23 3,23

10 80,2 19,9 100,1 4,03 5,03 77,1 22,9 100,0 3,36 4,36 73,8 25,9 99,7 2,85 3,85 70,1 29,1 99,2 2,41 3,41

14 88,0 20,2 108,2 4,35 5,35 85,0 22,9 107,9 3,71 4,71 81,4 25,9 107,3 3,14 4,14 77,3 29,1 106,5 2,65 3,65

18 96,7 20,1 116,8 4,80 5,80 93,4 22,8 116,2 4,09 5,09 89,5 25,9 115,3 3,46 4,46 85,1 29,1 114,2 2,92 3,92

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

48

MODELOctave bands [dB] Total

[dB(A)]63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

MODELOctave bands [dB] Total

[dB(A)]63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

SOUND LEVELS - MAROON 2 MT

SOUND LEVELS - MAROON 2 MT

Lw: sound power values in free field calculated in compliance with ISO 3744.Lp: sound pressure levels detected at 10 m from the fan side unit, not channelled in free field, in compliance with ISO 3744.Data detected with the unit that works at following conditions: A 35°C; W12/7°C

Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp

8 67 36 67 36 66 35 62 31 56 25 52 21 45 14 38 7 63 32

10 68 37 68 37 67 36 64 33 57 26 54 23 48 17 40 9 65 34

12 72 41 69 38 70 39 64 33 60 29 56 25 49 18 42 11 66 35

16 72 41 72 41 70 39 67 36 62 31 56 25 51 20 41 10 68 37

18 74 43 73 42 73 42 68 37 62 31 58 27 53 22 43 12 70 39

20 75 44 74 43 74 43 68 37 63 32 59 28 52 21 45 14 70 39

23 77 46 75 44 76 45 70 39 66 35 61 30 53 22 47 16 72 41

25 78 47 76 45 76 45 72 41 64 33 61 30 56 25 47 16 73 42

29 79 47 77 45 78 46 72 40 67 35 63 31 56 24 49 17 74 42

34 80 48 79 47 77 45 74 42 67 35 63 31 57 25 50 18 75 43

38 81 48 79 47 78 46 75 43 67 35 63 31 57 25 50 18 75 43

42 81 49 79 47 77 45 74 42 68 36 64 32 58 26 51 19 75 43

Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp

52 66 35 65 34 68 37 69 38 68 37 66 35 63 32 58 27 73 42

62 66 35 65 34 68 37 69 38 68 37 66 35 63 32 58 27 73 42

72 67 36 67 36 69 38 70 39 69 38 67 36 64 33 59 28 74 43

82 68 37 67 36 70 39 71 40 70 39 68 37 65 34 50 19 75 44

92 71 40 70 39 73 42 73 42 72 41 71 40 67 36 62 31 77 46

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

49

MODELOctave bands [dB] Total

[dB(A)]63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

MODELOctave bands [dB] Total

[dB(A)]63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

SOUND LEVELS - MAROON 2 HT

SOUND LEVELS - MAROON 2 HT

Lw: sound power values in free field calculated in compliance with ISO 3744.Lp: sound pressure levels detected at 10 m from the fan side unit, not channelled in free field, in compliance with ISO 3744.Data detected with the unit that works at following conditions: A 35°C; W12/7°C

Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp

7 67 36 67 36 66 35 62 31 56 25 52 21 45 14 38 7 63 32

9 67 36 67 36 66 35 62 31 56 25 52 21 45 14 38 7 63 32

11 68 37 67 36 67 36 62 31 56 25 53 22 46 15 39 8 64 33

13 72 41 69 38 70 39 64 33 60 29 56 25 49 18 42 11 66 35

17 72 41 69 38 70 39 65 34 60 29 56 25 50 19 43 12 67 36

22 74 43 73 42 73 42 68 37 62 31 58 27 53 22 43 12 70 39

26 75 44 74 43 74 43 68 37 63 32 59 28 52 21 45 14 70 39

32 80 49 79 48 77 46 74 43 67 36 63 32 57 26 50 19 75 44

36 81 50 79 48 78 47 75 44 67 36 63 32 57 26 50 19 75 44

41 81 50 79 48 77 46 74 43 68 37 64 33 58 27 51 20 75 44

Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp

50 66 35 65 34 68 37 69 38 68 37 66 35 63 32 58 27 73 42

60 66 35 65 34 68 37 69 38 68 37 66 35 63 32 58 27 73 42

70 67 36 67 36 69 38 70 39 69 38 67 36 64 33 59 28 74 43

80 68 37 67 36 70 39 71 40 70 39 68 37 65 34 50 19 75 44

90 71 40 70 39 73 42 73 42 72 41 71 40 67 36 62 31 77 46

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

50

MODELOctave bands [dB] Total

[dB(A)]63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

MODELOctave bands [dB] Total

[dB(A)]63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

SOUND LEVELS - MAROON 2 MT /LN

SOUND LEVELS - MAROON 2 MT /LN

Lw: sound power values in free field calculated in compliance with ISO 3744.Lp: sound pressure levels detected at 10 m from the fan side unit, not channelled in free field, in compliance with ISO 3744.Data detected with the unit that works at following conditions: A 35°C; W12/7°C

Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp

8 66 35 65 34 65 34 60 29 55 24 50 19 44 13 37 6 62 31

10 67 36 67 36 66 35 63 32 55 24 53 22 47 16 39 8 63 32

12 70 39 68 37 68 37 63 32 58 27 55 24 48 17 41 10 65 34

16 70 39 71 40 69 38 66 35 60 29 55 24 49 18 40 9 67 36

18 72 41 71 40 71 40 67 36 61 30 57 26 51 20 42 11 68 37

20 73 42 72 41 72 41 67 36 62 31 58 27 51 20 44 13 69 38

23 75 44 74 43 74 43 68 37 64 33 60 29 52 21 46 15 71 40

25 76 45 74 43 74 43 71 40 62 31 60 29 55 24 46 15 71 40

29 77 46 75 44 76 45 71 40 65 34 62 31 55 24 48 17 72 41

34 78 47 77 46 75 44 72 41 66 35 61 30 56 25 49 18 73 42

38 79 48 77 46 76 45 74 43 66 35 61 30 56 25 49 18 74 42

42 79 48 77 46 75 44 72 41 67 36 63 32 57 26 50 19 74 42

Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp

52 65 34 64 33 67 36 68 37 67 36 65 34 62 31 57 26 72 41

62 65 34 64 33 67 36 68 37 67 36 65 34 62 31 57 26 72 41

72 66 35 66 35 68 37 69 38 68 37 66 35 63 32 58 27 73 42

82 67 36 66 35 69 38 70 39 69 38 67 36 64 33 49 18 73 42

92 70 39 69 38 72 41 72 41 71 40 70 39 66 35 61 30 76 45

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

51

MODELOctave bands [dB] Total

[dB(A)]63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

MODELOctave bands [dB] Total

[dB(A)]63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz

SOUND LEVELS - MAROON 2 HT /LN

SOUND LEVELS - MAROON 2 HT /LN

Lw: sound power values in free field calculated in compliance with ISO 3744.Lp: sound pressure levels detected at 10 m from the fan side unit, not channelled in free field, in compliance with ISO 3744.Data detected with the unit that works at following conditions: A 35°C; W12/7°C

Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp

7 66 35 66 35 65 34 61 30 55 24 51 20 45 14 37 6 62 31

9 66 35 66 35 65 34 61 30 55 24 51 20 45 14 37 6 62 31

11 67 36 66 35 66 35 61 30 55 24 52 21 46 15 39 8 63 32

13 71 40 68 37 69 38 63 32 59 28 55 24 48 17 42 11 65 34

17 71 40 68 37 69 38 64 33 59 28 55 24 50 19 43 12 66 35

22 73 42 72 41 72 41 67 36 61 30 57 26 52 21 43 12 69 38

26 74 43 73 42 73 42 67 36 62 31 58 27 51 20 44 13 69 38

32 79 48 78 47 76 45 73 42 66 35 62 31 56 25 49 18 74 43

36 80 49 78 47 77 46 74 43 66 35 62 31 56 25 49 18 74 43

41 80 49 78 47 76 45 73 42 67 36 63 32 57 26 50 19 74 43

Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp Lw Lp

50 65 34 64 33 67 36 68 37 67 36 65 34 62 31 57 26 72 41

60 65 34 64 33 67 36 68 37 67 36 65 34 62 31 57 26 72 41

70 66 35 66 35 68 37 69 38 68 37 66 35 63 32 58 27 73 42

80 67 36 66 35 69 38 70 39 69 38 67 36 64 33 49 18 73 42

90 70 39 69 38 72 41 72 41 71 40 70 39 66 35 61 30 76 45

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

52

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

926 376 700

DIMENSIONI - DIMENSIONS

//

/

Codice-Code

1/20 22/11/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

\ \\\\

300

300

600

900

SPAZI DI INSTALLAZIONE / CLEARANCES

Uin

Uout

IMPRONTA A TERRA / FOOTPRINT

RpRp

Pm

GEYSER 2 MT 8-10-12

Ep

700

Cdn

76

926

Es

154 615 154

17,5

Fori\Holes 10

Uin

A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE

B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P

CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION

B

A

SCARICO CONDENSACONDENSATE DRAIN

INGRESSO ACQUA UTILIZZOUSER WATER INLET

Rp USCITA ACQUA UTILIZZOUSER WATER OUTLET

PANNELLO ASPORTABILEREMOVABLE PANEL

1"BSPMELECTRICAL SUPPLY INLET

FLUSSO ARIAAIR FLOW

EpQUADRO ELETTRICO

Cdh ø 18ELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

Uin

Uout1"

BSPM

PmGRIGLIE DI PROTEZIONE

PROTECTIVE METAL MESH

30

331,

525

042

,5

395

17,5

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)8 88 88

10 93 9312 102 102

8 1P 96 9710 1P 101 10212 1P 110 111

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

59

376

29 374 46

SD00147 - A

MAROON 2 MT DIMENSIONAL LAYOUTS

MAROON 2 MT Dimensional layout

8-10-12

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

53

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

926 376 1049

DIMENSIONI - DIMENSIONS

//

/

Codice-Code

1/20 22/11/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

\ \\\\

300

300

600

900

SPAZI DI INSTALLAZIONE / CLEARANCES

Uout

IMPRONTA A TERRA / FOOTPRINT

RpRp

Pm

GEYSER 2 MT 1PS 8-10-12

Ep

1049

Cdn

926

Lh Es

77 690 156

21

Fori\Holes 9

Uin

SCARICO CONDENSACONDENSATE DRAIN

INGRESSO ACQUA UTILIZZOUSER WATER INLET

FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET

Uout1"

BSPM

RpPANNELLO ASPORTABILE

PmGRIGLIE DI PROTEZIONE

PROTECTIVE METAL MESH

REMOVABLE PANEL AIR FLOW

EpQUADRO ELETTRICO

Lh Ø35

Cdh ø 18ELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

Uin1"

BSPMELECTRICAL SUPPLY INLET

FLUSSO ARIA

42

330

21

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)8 141 211

10 146 21612 155 225

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

832

174

Rp

Rp

59

214708

376 46

SD00148 - AMAROON 2 MT 1PS Dimensional layout

8-10-12

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

54

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

926 376 1350

DIMENSIONI - DIMENSIONS

//

/

Codice-Code

1/20 22/11/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

\ \\\\

300

300

600

900

SPAZI DI INSTALLAZIONE / CLEARANCES

Uin

Uout

IMPRONTA A TERRA / FOOTPRINT

Rp

Rp

Pm

GEYSER 2 MT 16-18-20

Ep

1350

Cdn

926

Es

155 621 150

Fori\Holes 10

430

Uin

A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE

B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P

CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION

B

A

SCARICO CONDENSACONDENSATE DRAIN

INGRESSO ACQUA UTILIZZOUSER WATER INLET

Rp PANNELLO ASPORTABILE USCITA ACQUA UTILIZZOREMOVABLE PANEL USER WATER OUTLET

Uout1"

BSPM

PmGRIGLIE DI PROTEZIONE

PROTECTIVE METAL MESH

EpQUADRO ELETTRICO

Cdh ø 18ELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

Uin1"

BSPMELECTRICAL SUPPLY INLET

FLUSSO ARIAAIR FLOW

30

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)16 134 13518 150 15120 165 166

16 1P 146 14718 1P 162 16320 1P 177 178

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

17,5

395

17,5

370

268

230

154

481

376

SD00149 - AMAROON 2 MT Dimensional layout

16-18-20

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

55

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

926 376 1699

DIMENSIONI - DIMENSIONS

//

/

Codice-Code

1/25 23/11/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

\ \\\\

300

300

600

900

SPAZI DI INSTALLAZIONE / CLEARANCES

Uout

IMPRONTA A TERRA / FOOTPRINT

RpRp

Pm

GEYSER 2 MT 1PS 16-18-20

Ep

CdnLh Es

77 690 157

22

Fori\Holes 9

Uin

SCARICO CONDENSACONDENSATE DRAIN

INGRESSO ACQUA UTILIZZOUSER WATER INLET

FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET

INGRESSO ALIMENTAZIONE ELETTRICAUin

1"BSPMELECTRICAL SUPPLY INLET

FLUSSO ARIAREMOVABLE PANEL AIR FLOW

EpQUADRO ELETTRICO

Lh Ø28

Cdh ø 18ELECTRICAL PANEL

Es

Uout1"

BSPM

RpPANNELLO ASPORTABILE

PmGRIGLIE DI PROTEZIONE

PROTECTIVE METAL MESH

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)16 191 26118 207 27720 222 292

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

174

Rp

Rp

154

214708

926

1699

1294

230

330

22

376

22

SD00150 - AMAROON 2 MT 1PS Dimensional layout

16-18-20

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

56

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1105 506 1385

DIMENSIONI - DIMENSIONS

//

/

Codice-Code

1/25 23/11/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

\ \\\\

300

300

600

900

SPAZI DI INSTALLAZIONE / CLEARANCES

Uin

Uout

IMPRONTA A TERRA / FOOTPRINT

Rp

Rp

Pm

GEYSER 2 MT 23-25

Ep13

85

Cdn

1105

Lh Es

87,5 930 87,5

Fori\Holes 12

Uin

A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE

B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P

CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION

A

SCARICO CONDENSACONDENSATE DRAIN

INGRESSO ACQUA UTILIZZOUSER WATER INLET

FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET

Uout

RpPANNELLO ASPORTABILE

PmGRIGLIE DI PROTEZIONE

PROTECTIVE METAL MESH

EpQUADRO ELETTRICO

Lh Ø34

Cdh ø 18ELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

UinELECTRICAL SUPPLY INLET

FLUSSO ARIAREMOVABLE PANEL AIR FLOW

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)23 210 21225 231 233

23 1P 223 22525 1P 244 246

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

2346

0

294

269

52

192

770

128

23

Uout

1" BSPM 1 1\4" BSPM 1" BSPM

UinA

B

B A B

BA

506

570*

* OPZIONALE \ OPTIONAL

SD00151 - AMAROON 2 MT Dimensional layout

23-25

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

57

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

926 376 1699

DIMENSIONI - DIMENSIONS

//

/

Codice-Code

1/25 23/11/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

\ \\\\

300

300

600

900

SPAZI DI INSTALLAZIONE / CLEARANCES

Uout

IMPRONTA A TERRA / FOOTPRINT

RpRp

Pm

GEYSER 2 MT 1PS 16-18-20

Ep

CdnLh Es

77 690 157

22

Fori\Holes 9

Uin

SCARICO CONDENSACONDENSATE DRAIN

INGRESSO ACQUA UTILIZZOUSER WATER INLET

FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET

INGRESSO ALIMENTAZIONE ELETTRICAUin

1"BSPMELECTRICAL SUPPLY INLET

FLUSSO ARIAREMOVABLE PANEL AIR FLOW

EpQUADRO ELETTRICO

Lh Ø28

Cdh ø 18ELECTRICAL PANEL

Es

Uout1"

BSPM

RpPANNELLO ASPORTABILE

PmGRIGLIE DI PROTEZIONE

PROTECTIVE METAL MESH

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)16 191 26118 207 27720 222 292

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

174

Rp

Rp

154

214708

926

1699

1294

230

330

22

376

22

SD00152 - AMAROON 2 MT 1PS Dimensional layout

23-25

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

58

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1306 506 1585

DIMENSIONI - DIMENSIONS

//

/

Codice-Code

1/25 23/11/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

\ \\\\

300

300

600

900

SPAZI DI INSTALLAZIONE / CLEARANCES

Uin

Uout

IMPRONTA A TERRA / FOOTPRINT

Rp

Rp

Pm

GEYSER 2 MT 29-34-38-42

Ep

1585

Cdn

1306

LhEs

88

Uin

A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE

B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P

CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION

A

SCARICO CONDENSACONDENSATE DRAIN

INGRESSO ACQUA UTILIZZOUSER WATER INLET

FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET

1" 1/4 BSPMELECTRICAL SUPPLY INLET

FLUSSO ARIAREMOVABLE PANEL AIR FLOW

EpQUADRO ELETTRICO

Lh Ø34

Cdh ø 18ELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

Uin

Uout1" 1/4 BSPM

RpPANNELLO ASPORTABILE

PmGRIGLIE DI PROTEZIONE

PROTECTIVE METAL MESH

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

2146

0

197,

446

552

870,

2

149

B

BA

506

563

282

Fori\Holes12

22

1130 88

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)29 356 35834 365 36738 385 38742 395 398

29 1P 371 37334 1P 380 38238 1P 400 40242 1P 410 413

*

* OPZIONALE \ OPTIONAL

SD00153 - AMAROON 2 MT Dimensional layout

29-34-38-42

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

59

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1306 506 2050

DIMENSIONI - DIMENSIONS

//

/

Codice-Code

1/25 23/11/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

\ \\\\

300

300

600

900

SPAZI DI INSTALLAZIONE / CLEARANCES

Uout

IMPRONTA A TERRA / FOOTPRINT

RpRp

Pm

GEYSER 2 MT 1PS 29-34-38-42

Ep

CdnLh

Fori\Holes 9

Uin

SCARICO CONDENSACONDENSATE DRAIN

INGRESSO ACQUA UTILIZZOUSER WATER INLET

FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET

Uout1" 1/4BSPM

RpPANNELLO ASPORTABILE

PmGRIGLIE DI PROTEZIONE

PROTECTIVE METAL MESH

EpQUADRO ELETTRICO

Lh Ø34

Cdh ø 22ELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

Uin1" 1/4BSPMELECTRICAL SUPPLY INLET

FLUSSO ARIAREMOVABLE PANEL AIR FLOW

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

RpRp

282

386917

1306

2050

506

563

Es

232

1766

52

204,5

28,5

84028,5

204,5

23,8

460

22,2

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)29 436 56634 445 57538 465 59542 475 605

*

* OPZIONALE \ OPTIONAL

SD00154 - AMAROON 2 MT 1PS Dimensional layout

29-34-38-42

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

60

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

926 376 1350

DIMENSIONI - DIMENSIONS

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

//

/

Codice-Code

1/20 23/11/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE GEYSER 2 MT HWS 8-20

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

SPAZI DI INSTALLAZIONE / CLEARANCES

B Uin

A Uin

Uout

1350

926

A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE

B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P

Ep

Rp

Cdh

Pm

300

300

600

900

430

376

Rp

154

48

IMPRONTA A TERRA / FOOTPRINT

155616155

395

430

10FORI/HOLES

CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION

481

Rin

Rout

INGRESSO ACQUA UTILIZZOUSER WATER INLET

USCITA ACQUA UTILIZZOUSER WATER OUTLET

FORI SOLLEVAMENTO INGRESSO ACQUA SANITARIOLIFTING HOLES RECOVERY WATER INLET

USCITA ACQUA SANITARIORECOVERY WATER OUTLET

SCARICO CONDENSACONDENSATE DRAIN

EpQUADRO ELETTRICO

Uin1"

BSPMELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

Uout1"

BSPMELECTRICAL SUPPLY INLET

Lh Ø28 Rin1"

BSPM

RpPANNELLO ASPORTABILE

Rout1"

BSPMREMOVABLE PANEL

Cdh ø 18

PmGRIGLIE DI PROTEZIONE FLUSSO ARIA

PROTECTIVE METAL MESH AIR FLOW

\ \ \ \\

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)8 129 130

10 133 13412 137 13816 141 14218 158 15920 174 175

8 1P 137 13810 1P 141 14212 1P 145 14616 1P 153 15418 1P 170 17120 1P 186 187

548

269

52

178,

526

9

151,5

30

Es

SD00155 - AMAROON 2 MT/HWS Dimensional layout

8-20

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

61

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

926 376 1699

DIMENSIONI - DIMENSIONS

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)8 182 252

10 186 25612 190 26016 198 26818 215 28520 231 301

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

//

/

Codice-Code

1/20 23/11/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE GEYSER 2 MT HWS 1PS 8-20

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

SPAZI DI INSTALLAZIONE / CLEARANCES

Uin

Uout

1699

926

Ep

Rp

Cdh

Pm

30030

0

600

900

396

376

Rp

Lh

IMPRONTA A TERRA / FOOTPRINT

158

330

376

Rin

Rout

INGRESSO ACQUA UTILIZZOUSER WATER INLET

USCITA ACQUA UTILIZZOUSER WATER OUTLET

FORI SOLLEVAMENTO INGRESSO ACQUA RECUPEROLIFTING HOLES RECOVERY WATER INLET

USCITA ACQUA RECUPERORECOVERY WATER OUTLET

SCARICO CONDENSACONDENSATE DRAIN

EpQUADRO ELETTRICO

Uin1"

BSPMELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

Uout1"

BSPMELECTRICAL SUPPLY INLET

Lh Ø28 Rin1"

BSPM

RpPANNELLO ASPORTABILE

Rout1"

BSPMREMOVABLE PANEL

Cdh ø 18

PmGRIGLIE DI PROTEZIONE FLUSSO ARIA

PROTECTIVE METAL MESH AIR FLOW

\ \ \ \\

78

5226

954

865

4,3

176

152

Lh

Rp

213709

48

Fori\Holes9690

Es

SD00156 - AMAROON 2 MT/HWS 1PS Dimensional layout

8-20

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

62

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1105 506 1385

DIMENSIONI - DIMENSIONS

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)23 220 22225 242 244

23 1P 233 23525 1P 255 257

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

//

/

Codice-Code

1/20 23/11/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE GEYSER 2 MT HWS 23-25

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

SPAZI DI INSTALLAZIONE / CLEARANCES

B Uin

A Uin

Uout

1385

1105

A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE

B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P

Rp

Cdh

Pm

300

300

600

900

567

506

Rp

5852

IMPRONTA A TERRA / FOOTPRINT

87,5

460

506

12FORI/HOLES

CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION

Rin

Rout

INGRESSO ACQUA UTILIZZOUSER WATER INLET

USCITA ACQUA UTILIZZOUSER WATER OUTLET

FORI SOLLEVAMENTO INGRESSO ACQUA RECUPEROLIFTING HOLES RECOVERY WATER INLET

USCITA ACQUA RECUPERORECOVERY WATER OUTLET

SCARICO CONDENSACONDENSATE DRAIN

Cdh ø 20

PmGRIGLIE DI PROTEZIONE FLUSSO ARIA

PROTECTIVE METAL MESH AIR FLOW

Lh Ø34 Rin1" 1/4BSPM

RpPANNELLO ASPORTABILE

Rout1" 1/4BSPMREMOVABLE PANEL

EpQUADRO ELETTRICO

Uin1" 1/4BSPMELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

Uout1" 1/4BSPMELECTRICAL SUPPLY INLET

/ / / //

930 87,5

192

269

294

770

Ep

128

LhLh

* OPZIONALE / OPTIONAL

*Es

SD00157 - AMAROON 2 MT/HWS Dimensional layout

23-25

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

63

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1105 506 1850

DIMENSIONI - DIMENSIONS

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)23 298 42825 320 450

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

//

/

Codice-Code

1/25 23/11/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE GEYSER 2 MT HWS 1PS 23-25

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

SPAZI DI INSTALLAZIONE / CLEARANCES1:20

Uin

Uout

1850

1105

Rp

Cdh

Pm

300

300

600

900

567

506

Rp

5852

IMPRONTA A TERRA / FOOTPRINT

460

506

9FORI/HOLES

Rin

Rout

INGRESSO ACQUA UTILIZZOUSER WATER INLET

USCITA ACQUA UTILIZZOUSER WATER OUTLET

FORI SOLLEVAMENTO INGRESSO ACQUA RECUPEROLIFTING HOLES RECOVERY WATER INLET

USCITA ACQUA RECUPERORECOVERY WATER OUTLET

SCARICO CONDENSACONDENSATE DRAIN

EpQUADRO ELETTRICO

Uin1" 1/4BSPMELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

Uout1" 1/4BSPMELECTRICAL SUPPLY INLET

Lh Ø34 Rin1" 1/4BSPM

RpPANNELLO ASPORTABILE

Rout1" 1/4BSPMREMOVABLE PANEL

Cdh ø 22

PmGRIGLIE DI PROTEZIONE FLUSSO ARIA

PROTECTIVE METAL MESH AIR FLOW

/ / / //

269

294Ep

128

LhLh 242

1002

*

* OPZIONALE / OPTIONAL

Rp Rp

232

862

28,559 840

28,5149

Es

Rp

SD00158 - AMAROON 2 MT/HWS 1PS Dimensional layout

23-25

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

64

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1306 506 1585

DIMENSIONI - DIMENSIONS

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

//

/

Codice-Code

1/25 23/11/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE GEYSER 2 MT HWS 29-34-38-42

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

SPAZI DI INSTALLAZIONE / CLEARANCES

B Uin

A Uin

Uout

1585

1306

A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE

B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P

Rp

Cdh

Pm

300 300

600

900

561

506

Rp

IMPRONTA A TERRA / FOOTPRINT

88

12FORI/HOLES

CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION

Rin

Rout

INGRESSO ACQUA UTILIZZOUSER WATER INLET

USCITA ACQUA UTILIZZOUSER WATER OUTLET

FORI SOLLEVAMENTO INGRESSO ACQUA RECUPEROLIFTING HOLES RECOVERY WATER INLET

USCITA ACQUA RECUPERORECOVERY WATER OUTLET

SCARICO CONDENSACONDENSATE DRAIN

Cdh ø 20

PmGRIGLIE DI PROTEZIONE FLUSSO ARIA

PROTECTIVE METAL MESH AIR FLOW

Lh Ø34 Rin1" 1/4BSPM

RpPANNELLO ASPORTABILE

Rout1" 1/4BSPMREMOVABLE PANEL

EpQUADRO ELETTRICO

Uin1" 1/4BSPMELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

Uout1" 1/4BSPMELECTRICAL SUPPLY INLET

\ \ \ \\

Ep

Lh

110

282

5246

619

787

01130 88

460

506

148

*

* OPZIONALE / OPTIONAL

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)29 368 37034 378 38038 399 40142 410 413

29 1P 383 38534 1P 393 39538 1P 414 41642 1P 425 428

LhEs

SD00159 - AMAROON 2 MT/HWS Dimensional layout

29-34-38-42

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

65

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1306 506 2050

DIMENSIONI - DIMENSIONS

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

//

/

Codice-Code

1/25 23/11/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE GEYSER 2 MT HWS 1PS 29-34-38-42

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

SPAZI DI INSTALLAZIONE / CLEARANCES

Uin

Uout

2050

1306

Rp

Cdh

Pm

300 300

600

900

561

506

Rp

IMPRONTA A TERRA / FOOTPRINT

204,5

Rin

Rout

INGRESSO ACQUA UTILIZZOUSER WATER INLET

USCITA ACQUA UTILIZZOUSER WATER OUTLET

FORI SOLLEVAMENTO INGRESSO ACQUA RECUPEROLIFTING HOLES RECOVERY WATER INLET

USCITA ACQUA RECUPERORECOVERY WATER OUTLET

SCARICO CONDENSACONDENSATE DRAIN

EpQUADRO ELETTRICO

Uin1" 1/4BSPMELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

Uout1" 1/4BSPMELECTRICAL SUPPLY INLET

Lh Ø34 Rin1" 1/4BSPM

RpPANNELLO ASPORTABILE

Rout1" 1/4BSPMREMOVABLE PANEL

Cdh ø 22

PmGRIGLIE DI PROTEZIONE FLUSSO ARIA

PROTECTIVE METAL MESH AIR FLOW

\ \ \ \\

Ep

LhLh

110

5246

619

7

460

506

1102

232

*

* OPZIONALE / OPTIONAL

148

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)29 448 57834 458 58838 479 60942 490 620

Fori\Holes9

28,5840

28,5204,5

RpRp

386917

Rp

Es

SD00160 - AMAROON 2 MT/HWS 1PS Dimensional layout

29-34-38-42

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

66ASD00165

Visto-Checked byDenominazione-Denomination

Data-DateRev. Dis.-Draftsman Descrizione revisione-Revision descriptionCodice-Code Disegno-Drawing Rev.

Dis.-DraftsmanData-DateScala-Scale Visto-Checked by Foglio diSheet N. of

Sost. il dis.-Replace draw. Sost. dal dis.-Replaced by draw.

Materiale-Material Trattamento-Treatment

Peso-Weight [kg]

SCHEMA DIMENSIONALE / DIMENSIONAL DRAWINGGEYSER 2 MT 52-62-72-82-92 SD00165

P. Frigolorpe 2

/ /

1N. Bettio

/Spessore-Thickness

/Colore vernice-Painted colour

/ /

12/12/20121/30

Codice-Code

/

/ / / //

SPAZI DI INSTALLAZIONE / CLEARANCES

1000

1000

00

1000

0

1000

0Cdh

Rp

Rp

Ep

Ep

2108 23

90

1203

167

519

251,5

371,517

9Lh Lh1403

Rp Cdh

Ep

SCARICO CONDENSA VERSIONE HPCONDENSATE DRAIN HP VERSION

INGRESSO ACQUA UTILIZZOUSER WATER INLET

USCITA ACQUA UTILIZZOUSER WATER OUTLET

Uout 2" BSPM

ø20

EpQUADRO ELETTRICO

Es

ELECTRICAL PANEL

Lh

INGRESSO ALIMENTAZIONE ELETTRICAELECTRICAL SUPPLY INLET

Uin 2" BSPMLIFTING HOLES

RpPANNELLO ASPORTABILE

REMOVABLE PANEL

Cdh

FORI DI SOLLEVAMENTO

*OPZIONALEOPTIONAL

PmGRIGLIE DI PROTEZIONE

PROTECTIVE METAL MESH

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1403 1203 2390

DIMENSIONI / DIMENSIONS

PmPm

Es

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)

52 575 57862 592 59572 602 60582 620 62392 631 634

MOD. 1P 16

MOD. 2P 32

Δ PESOΔ WEIGHT

Δ PESOΔ WEIGHT

Uout

Uin

A B C

A

A MODELLO STANDARD STANDARD MODEL

B MODELLO 1P 1P MODEL

C MODELLO 2P 2P MODEL

CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTIONS

**

Uin B C

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

SD00165 - AMAROON 2 MT Dimensional layout

52-62-72-82-92

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

67ASD00165

Visto-Checked byDenominazione-Denomination

Data-DateRev. Dis.-Draftsman Descrizione revisione-Revision descriptionCodice-Code Disegno-Drawing Rev.

Dis.-DraftsmanData-DateScala-Scale Visto-Checked by Foglio diSheet N. of

Sost. il dis.-Replace draw. Sost. dal dis.-Replaced by draw.

Materiale-Material Trattamento-Treatment

Peso-Weight [kg]

SCHEMA DIMENSIONALE / DIMENSIONAL DRAWINGGEYSER 2 MT 52-62-72-82-92 SD00165

P. Frigolorpe 2

/ /

2N. Bettio

/Spessore-Thickness

/Colore vernice-Painted colour

/ /

12/12/20121/12,5

Codice-Code

/

/ / / //

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

IMPRONTA A TERRA / FOOTPRINT

FORI DI FISSAGGIOFIXING HOLES

Fh Ø18

G..PUNTI DI APPOGGIO ANTIVIBRANTIVIBRATION DAMPER FOOT HOLDS

24 1160 24

124

1160

124

1408

1208

G1 G2

G4G3

G1(kg)

G2(kg)

G3(kg)

G4(kg)

52 156 162 150 11062 161 167 155 11372 163 169 157 11582 168 174 162 11892 171 178 165 120

SD00165 - AMAROON 2 MT Dimensional layout

52-62-72-82-92

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

68ASD00166

Visto-Checked byDenominazione-Denomination

Data-DateRev. Dis.-Draftsman Descrizione revisione-Revision descriptionCodice-Code Disegno-Drawing Rev.

Dis.-DraftsmanData-DateScala-Scale Visto-Checked by Foglio diSheet N. of

Sost. il dis.-Replace draw. Sost. dal dis.-Replaced by draw.

Materiale-Material Trattamento-Treatment

Peso-Weight [kg]

SCHEMA DIMENSIONALE / DIMENSIONAL DRAWINGGEYSER 2 MT HWS 52-62-72-82-92 SD00166

P. Frigolorpe 2

/ /

1N. Bettio

/Spessore-Thickness

/Colore vernice-Painted colour

/ /

28/11/20121/30

Codice-Code

/

/ / / //

SPAZI DI INSTALLAZIONE / CLEARANCES

1000

1000

00

1000

0

1000

0Cdh

Rp

Rp

Ep

Ep

2108 23

90

1203 167

519

251,5

371,5

179Lh Lh

1403

Rp Cdh

Ep

SCARICO CONDENSA VERSIONE HPCONDENSATE DRAIN HP VERSION

INGRESSO ACQUA UTILIZZOUSER WATER INLET

USCITA ACQUA UTILIZZOUSER WATER OUTLET

INGRESSO ACQUA RECUPERORECOVERY WATER INLET

USCITA ACQUA RECUPERORECOVERY WATER OUTLET

2" BSPM

EpQUADRO ELETTRICO

Es

ELECTRICAL PANEL

Lh

INGRESSO ALIMENTAZIONE ELETTRICAELECTRICAL SUPPLY INLET

GRIGLIE DI PROTEZIONEPROTECTIVE METAL MESH

Uout 2" BSPMLIFTING HOLES

Cdh

Uin

FORI DI SOLLEVAMENTO

Rin 2" BSPM

ø20

Rout 2" BSPMRpPANNELLO ASPORTABILE

REMOVABLE PANEL

Pm

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1403 1203 2390

DIMENSIONI / DIMENSIONS

PmOPZIONALE / OPTIONAL

PmOPZIONALE / OPTIONAL

Es

Uout

Uin

A B

A

A MODELLO STANDARD STANDARD MODELB MODELLO 1P - 2P 1P - 2P MODELC MODELLO 1R 1R MODEL

CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTIONS

Uin B

390

332

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)

52 575 57862 592 59572 602 60582 620 62392 631 634

Δ PESOΔ WEIGHT

MOD. 1R 2P 49

Δ PESOΔ WEIGHT

MOD. 1R 17

Δ PESOΔ WEIGHT

MOD. 1R 1P 33

Δ PESOΔ WEIGHT

MOD. 1P 16

Δ PESOΔ WEIGHT

MOD. 2P 32

Rout A C

Rin C

Rin A

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

SD00166 - AMAROON 2 MT/HWS Dimensional layout

52-62-72-82-92

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

69ASD00166

Visto-Checked byDenominazione-Denomination

Data-DateRev. Dis.-Draftsman Descrizione revisione-Revision descriptionCodice-Code Disegno-Drawing Rev.

Dis.-DraftsmanData-DateScala-Scale Visto-Checked by Foglio diSheet N. of

Sost. il dis.-Replace draw. Sost. dal dis.-Replaced by draw.

Materiale-Material Trattamento-Treatment

Peso-Weight [kg]

SCHEMA DIMENSIONALE / DIMENSIONAL DRAWINGGEYSER 2 MT HWS 52-62-72-82-92 SD00166

P. Frigolorpe 2

/ /

2N. Bettio

/Spessore-Thickness

/Colore vernice-Painted colour

/ /

28/11/20121/12,5

Codice-Code

/

/ / / //

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

IMPRONTA A TERRA / FOOTPRINT

FORI DI FISSAGGIOFIXING HOLES

Fh Ø18

G..PUNTI DI APPOGGIO ANTIVIBRANTIVIBRATION DAMPER FOOT HOLDS

24 1160 24

124

1160

124

1408

1208

G1 G2

G4G3

G1(kg)

G2(kg)

G3(kg)

G4(kg)

52 156 162 150 11062 161 167 155 11372 163 169 157 11582 168 174 162 11892 171 178 165 120

SD00166 - AMAROON 2 MT/HWS Dimensional layout

52-62-72-82-92

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

70

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1105 506 982

DIMENSIONI - DIMENSIONS

//

/

Codice-Code

1/20 12/12/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

/DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

\ \\\\

300

600

900

300

SPAZI DI INSTALLAZIONE / CLEARANCES

IMPRONTA A TERRA / FOOTPRINT

RpRp

Pm

GEYSER 27-9-11-13-17

Ep

982

Cdn

1105

Lp

86 930 86

21

Uin

A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE

B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P

CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION

B

A

460

21

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

506

Lp

Es

12

FORI MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)

7 107 108

9 111 112

11 117 118

13 123 124

17 132 133

7 1P 116 117

9 1P 120 121

11 1P 126 127

13 1P 132 133

17 1P 141 142

Uout

Uin

SCARICO CONDENSACONDENSATE DRAIN

INGRESSO ACQUA UTILIZZOUSER WATER INLET

USCITA ACQUA UTILIZZOUSER WATER OUTLET

Lp

PANNELLO ASPORTABILEREMOVABLE PANEL

1"BSPMELECTRICAL SUPPLY INLET

PUNTO DI SOLLEVAMENTO

Rp

LIFTING POINT

EpQUADRO ELETTRICO

Cdh ø 22ELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

Uin

FLUSSO ARIAAIR FLOW

Uout1"

BSPM

PmGRIGLIE DI PROTEZIONE

PROTECTIVE METAL MESH

276

222

660

269

53

180

586

SD00145 - A

MAROON 2 HT DIMENSIONAL LAYOUTS

MAROON 2 HT Dimensional layout

7-9-11-13-17

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

71

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1105 506 1447

DIMENSIONI - DIMENSIONS

//

/

Codice-Code

1/25 12/12/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

/DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

\ \\\\

300

300

600

900

SPAZI DI INSTALLAZIONE / CLEARANCES

IMPRONTA A TERRA / FOOTPRINT

RpRp

Pm

GEYSER 2 1PS 7-9-11-13-17

Ep14

47

Cdn

1105

Lh

Es

5928,5

Fori\Holes 9

Uin

SCARICO CONDENSACONDENSATE DRAIN

INGRESSO ACQUA UTILIZZOUSER WATER INLET

FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET

ø 22ELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

Uin1"

BSPMELECTRICAL SUPPLY INLET

GRIGLIE DI PROTEZIONEPROTECTIVE METAL MESH

EpQUADRO ELETTRICO

Lh Ø35

Cdh

REMOVABLE PANELFLUSSO ARIA

AIR FLOW

Uout1"

BSPM

RpPANNELLO ASPORTABILE

Pm

460

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

232

Rp

Rp

242862

SD00146

506

2222

84028,5

149

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)7 181 3119 185 315

11 191 32113 197 32717 206 336

Uout

1162

53

182

586

SD00146 - AMAROON 2 HT 1PS Dimensional layout

7-9-11-13-17

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

72

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1105 506 1385

DIMENSIONI - DIMENSIONS

//

/

Codice-Code

1/25 12/12/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

\ \\\\

300

300

600

900

SPAZI DI INSTALLAZIONE / CLEARANCES

Uin

Uout

IMPRONTA A TERRA / FOOTPRINT

Rp

Rp

Pm

GEYSER 2 22-26

Ep13

85

Cdn

1105

Lh Es

87,5 930 87,5

Fori\Holes 12

Uin

A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE

B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P

CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION

A

SCARICO CONDENSACONDENSATE DRAIN

INGRESSO ACQUA UTILIZZOUSER WATER INLET

FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET

ELECTRICAL SUPPLY INLET

FLUSSO ARIAREMOVABLE PANEL AIR FLOW

EpQUADRO ELETTRICO

Lh Ø34

Cdh ø 22ELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

Uin

Uout

RpPANNELLO ASPORTABILE

PmGRIGLIE DI PROTEZIONE

PROTECTIVE METAL MESH

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)22 230 23226 249 251

22 1P 242 24426 1P 261 263

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

2346

0

294

269

52

192

770

128

23

Uout

1" BSPM 1 1\4" BSPM 1" BSPM

UinA

B

B A B

BA

506

*

* OPZIONALE \ OPTIONAL

570

SD00167 - AMAROON 2 HT Dimensional layout

22-26

SD00167 - A

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

73

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1105 506 1850

DIMENSIONI - DIMENSIONS

//

/

Codice-Code

1/25 12/12/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

\ \\\\

300

300

600

900

SPAZI DI INSTALLAZIONE / CLEARANCES

Uout

IMPRONTA A TERRA / FOOTPRINT

Rp Rp

Pm

GEYSER 2 1PS 22-26

Ep

Cdn

Lh

Es

Fori\Holes 9

Uin

SCARICO CONDENSACONDENSATE DRAIN

INGRESSO ACQUA UTILIZZOUSER WATER INLET

FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET

INGRESSO ALIMENTAZIONE ELETTRICAUin

1" 1/4BSPMELECTRICAL SUPPLY INLET

FLUSSO ARIAREMOVABLE PANEL AIR FLOW

EpQUADRO ELETTRICO

Lh Ø34

Cdh ø 22ELECTRICAL PANEL

Es

Uout1"

BSPM

RpPANNELLO ASPORTABILE

PmGRIGLIE DI PROTEZIONE

PROTECTIVE METAL MESH

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)22 307 43726 326 456

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

RpRp

192

242862

1105

1850

506

570

5315

6523

0

58 28,5 840 28,5 148

460

2121

*

* OPZIONALE \ OPTIONAL

SD00168 - AMAROON 2 HT 1PS Dimensional layout

22-26

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

74

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1306 506 1585

DIMENSIONI - DIMENSIONS

//

/

Codice-Code

1/30 12/12/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

\ \\\\

300

300

600

900

SPAZI DI INSTALLAZIONE / CLEARANCES

Uin

Uout

IMPRONTA A TERRA / FOOTPRINT

Rp

Rp

Pm

GEYSER 2 32-36-41

Ep

1585

Cdn

1306

LhEs

88

Uin

A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE

B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P

CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION

A

SCARICO CONDENSACONDENSATE DRAIN

INGRESSO ACQUA UTILIZZOUSER WATER INLET

FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET

PmGRIGLIE DI PROTEZIONE

PROTECTIVE METAL MESH

ø 22ELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

Uin

Uout1" 1/4 BSPM

RpPANNELLO ASPORTABILE

1" 1/4 BSPMELECTRICAL SUPPLY INLET

FLUSSO ARIAREMOVABLE PANEL AIR FLOW

EpQUADRO ELETTRICO

Lh Ø34

Cdh

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

2146

0

197

465

5287

0

149

B

BA

506

563

282

Fori\Holes12

21

1130 88

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)32 383 38536 402 40541 413 416

32 1P 398 40036 1P 417 42041 1P 428 431

*

* OPZIONALE \ OPTIONAL

SD00169 - AMAROON 2 HT Dimensional layout

32-36-41

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

75

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1306 506 2050

DIMENSIONI - DIMENSIONS

//

/

Codice-Code

1/25 12/12/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

\ \\\\

300

300

600

900

SPAZI DI INSTALLAZIONE / CLEARANCES

Uout

IMPRONTA A TERRA / FOOTPRINT

RpRp

Pm

GEYSER 2 1PS 32-36-41

Ep

CdnLh

Fori\Holes 9

Uin

SCARICO CONDENSACONDENSATE DRAIN

INGRESSO ACQUA UTILIZZOUSER WATER INLET

FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET

Uout1" 1/4BSPM

RpPANNELLO ASPORTABILE

PmGRIGLIE DI PROTEZIONE

PROTECTIVE METAL MESH

EpQUADRO ELETTRICO

Lh Ø34

Cdh ø 22ELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

Uin1" 1/4BSPMELECTRICAL SUPPLY INLET

FLUSSO ARIAREMOVABLE PANEL AIR FLOW

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

RpRp

282

386917

1306

2050

506

563

Es

232

1766

52

204

28,5

84028,5

204

2246

022

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)32 463 59336 482 61241 493 623

*

* OPZIONALE \ OPTIONAL

SD00170 - AMAROON 2 HT 1PS Dimensional layout

32-36-41

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

76

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1105 506 982

DIMENSIONI - DIMENSIONS

//

/

Codice-Code

1/20 12/12/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

/DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

\ \\\\

300

600

900

300

SPAZI DI INSTALLAZIONE / CLEARANCES

Rin

Rout

IMPRONTA A TERRA / FOOTPRINT

RpRp

Pm

GEYSER 2 HWS 7-9-11-13-17

Ep

982

Cdn

1105

Lp

86 930 86

21

Uin

A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE

B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P

CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION

B

A

460

21

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

506 66

5326

9

Lp

Es

12

FORI MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)

7 111 112

9 116 117

11 123 124

13 130 131

17 141 142

7 1P 120 121

9 1P 125 126

11 1P 132 133

13 1P 139 140

17 1P 150 151

660

Uout

Uin

SCARICO CONDENSACONDENSATE DRAIN

INGRESSO ACQUA UTILIZZOUSER WATER INLET

USCITA ACQUA UTILIZZOUSER WATER OUTLET

INGRESSO ACQUA RECUPERORECOVERY WATER INLET

USCITA ACQUA RECUPERORECOVERY WATER OUTLET

FLUSSO ARIAAIR FLOW

1" 1\4 BSPM

1" 1\4 BSPM

Uout1"

BSPM

PmGRIGLIE DI PROTEZIONE

PROTECTIVE METAL MESH

RoutLIFTING POINT

EpQUADRO ELETTRICO

Cdh ø 22ELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

Uin

Lp

PANNELLO ASPORTABILEREMOVABLE PANEL

1"BSPMELECTRICAL SUPPLY INLET

Rin

PUNTO DI SOLLEVAMENTO

Rp

115

276

222

586

SD00171 - AMAROON 2 HT/HWS Dimensional layout

7-9-11-13-17

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

77

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1105 506 1447

DIMENSIONI - DIMENSIONS

//

/

Codice-Code

1/25 12/12/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

/DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

\ \\\\

300

300

600

900

SPAZI DI INSTALLAZIONE / CLEARANCES

Rout

IMPRONTA A TERRA / FOOTPRINT

RpRp

Pm

GEYSER 2 HWS 1PS 7-9-11-13-17

Ep14

47

Cdn

1105

Lh

Es

5928,5

Fori\Holes 9

Uin

SCARICO CONDENSACONDENSATE DRAIN

INGRESSO ACQUA UTILIZZOUSER WATER INLET

FORI SOLLEVAMENTO USCITA ACQUA UTILIZZOLIFTING HOLES USER WATER OUTLET

INGRESSO ACQUA RECUPERORECOVERY WATER INLET

USCITA ACQUA RECUPERORECOVERY WATER OUTLET

FLUSSO ARIAAIR FLOW

1" 1/4BSPM

1" 1/4BSPM

Uout1"

BSPM

RpPANNELLO ASPORTABILE

PmGRIGLIE DI PROTEZIONE

PROTECTIVE METAL MESHRout

Rin

EpQUADRO ELETTRICO

Lh Ø35

Cdh ø 22ELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

Uin1"

BSPMELECTRICAL SUPPLY INLET

REMOVABLE PANEL

53

460

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

232

Rp

Rp

242862

SD00172

50666

2222

84028,5

149

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)7 185 3159 190 320

11 197 32713 204 33417 215 345

Uout

Rin

115

269

892

SD00172 - AMAROON 2 HT/HWS 1PS Dimensional layout

7-9-11-13-17

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

78

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1105 506 1385

DIMENSIONI - DIMENSIONS

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)22 241 24326 262 264

22 1P 253 25526 1P 274 276

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

//

/

Codice-Code

1/20 12/12/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE GEYSER 2 HWS 22-26

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

SPAZI DI INSTALLAZIONE / CLEARANCES

B Uin

A Uin

Uout

1385

1105

A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE

B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P

Rp

Cdh

Pm

300

300

600

900

567

506

Rp

5852

IMPRONTA A TERRA / FOOTPRINT

88

460

506

12FORI/HOLES

CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION

Rin

Rout

INGRESSO ACQUA UTILIZZOUSER WATER INLET

USCITA ACQUA UTILIZZOUSER WATER OUTLET

FORI SOLLEVAMENTO INGRESSO ACQUA RECUPEROLIFTING HOLES RECOVERY WATER INLET

USCITA ACQUA RECUPERORECOVERY WATER OUTLET

SCARICO CONDENSACONDENSATE DRAIN

Cdh ø 20

PmGRIGLIE DI PROTEZIONE FLUSSO ARIA

PROTECTIVE METAL MESH AIR FLOW

Lh Ø34 Rin1" 1/4BSPM

RpPANNELLO ASPORTABILE

Rout1" 1/4BSPMREMOVABLE PANEL

EpQUADRO ELETTRICO

Uin1" 1/4BSPMELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

Uout1" 1/4BSPMELECTRICAL SUPPLY INLET

/ / / //

930 88

192

269

294

770

Ep

128

LhLh

* OPZIONALE / OPTIONAL

*Es

SD00173 - AMAROON 2 HT/HWS Dimensional layout

22-26

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

79

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1105 506 1850

DIMENSIONI - DIMENSIONS

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)22 318 44826 339 469

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

//

/

Codice-Code

1/25 12/12/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE GEYSER 2 HWS 1PS 22-26

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

SPAZI DI INSTALLAZIONE / CLEARANCES1:20

Uin

Uout

1850

1105

Rp

Cdh

Pm

300

300

600

900

567

506

Rp

5852

IMPRONTA A TERRA / FOOTPRINT

460

506

9FORI/HOLES

Rin

Rout

INGRESSO ACQUA UTILIZZOUSER WATER INLET

USCITA ACQUA UTILIZZOUSER WATER OUTLET

FORI SOLLEVAMENTO INGRESSO ACQUA RECUPEROLIFTING HOLES RECOVERY WATER INLET

USCITA ACQUA RECUPERORECOVERY WATER OUTLET

SCARICO CONDENSACONDENSATE DRAIN

EpQUADRO ELETTRICO

Uin1" 1/4BSPMELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

Uout1" 1/4BSPMELECTRICAL SUPPLY INLET

Lh Ø34 Rin1" 1/4BSPM

RpPANNELLO ASPORTABILE

Rout1" 1/4BSPMREMOVABLE PANEL

Cdh ø 22

PmGRIGLIE DI PROTEZIONE FLUSSO ARIA

PROTECTIVE METAL MESH AIR FLOW

/ / / //

269

294Ep

128

LhLh 242

1002

*

* OPZIONALE / OPTIONAL

Rp Rp

232

862

28,559 840

28,5149

Es

Rp

SD00174 - AMAROON 2 HT/HWS 1PS Dimensional layout

22-26

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

80

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1306 506 1585

DIMENSIONI - DIMENSIONS

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

//

/

Codice-Code

1/25 12/12/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE GEYSER 2 HWS 32-36-41

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

SPAZI DI INSTALLAZIONE / CLEARANCES

B Uin

A Uin

Uout

1585

1306

A ACQUA UTILIZZO SENZA MODULO IDRAULICOUSER WATER WITHOUT HYDRAULIC MODULE

B ACQUA UTILIZZO CON MODULO IDRAULICO 1PUSER WATER WITH HYDRAULIC MODULE 1P

Rp

Cdh

Pm

300 300

600

900

561

506

Rp

IMPRONTA A TERRA / FOOTPRINT

88

12FORI/HOLES

CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTION

Rin

Rout

INGRESSO ACQUA UTILIZZOUSER WATER INLET

USCITA ACQUA UTILIZZOUSER WATER OUTLET

FORI SOLLEVAMENTO INGRESSO ACQUA RECUPEROLIFTING HOLES RECOVERY WATER INLET

USCITA ACQUA RECUPERORECOVERY WATER OUTLET

SCARICO CONDENSACONDENSATE DRAIN

Cdh ø 20

PmGRIGLIE DI PROTEZIONE FLUSSO ARIA

PROTECTIVE METAL MESH AIR FLOW

Lh Ø34 Rin1" 1/4BSPM

RpPANNELLO ASPORTABILE

Rout1" 1/4BSPMREMOVABLE PANEL

EpQUADRO ELETTRICO

Uin1" 1/4BSPMELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

Uout1" 1/4BSPMELECTRICAL SUPPLY INLET

\ \ \ \\

Ep

Lh

110

282

5246

619

787

01130 88

460

506

148

*

* OPZIONALE / OPTIONAL

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)32 398 40036 419 42241 432 435

32 1P 413 41536 1P 434 43741 1P 447 450

LhEs

SD00175 - AMAROON 2 HT/HWS Dimensional layout

32-36-41

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

81

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1306 506 2050

DIMENSIONI - DIMENSIONS

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

//

/

Codice-Code

1/25 12/12/2012

//Colore vernice-Painted colour

/Spessore-Thickness

/

N. Bettio 1 1F. Sanavia

-DIMENSIONAL DRAWINGSCHEMA DIMENSIONALE GEYSER 2 HWS 1PS 32-36-41

Peso-Weight [kg]

Trattamento-TreatmentMateriale-Material

Sost. dal dis.-Replaced by draw.Sost. il dis.-Replace draw.ofN.SheetdiFoglioVisto-Checked byScala-Scale Data-Date Dis.-Draftsman

Rev.Disegno-DrawingCodice-CodeDescrizione revisione-Revision descriptionDis.-DraftsmanRev. Data-Date

Denominazione-DenominationVisto-Checked by

SPAZI DI INSTALLAZIONE / CLEARANCES

Uin

Uout

2050

1306

Rp

Cdh

Pm

300 300

600

900

561

506

Rp

IMPRONTA A TERRA / FOOTPRINT

204

Rin

Rout

INGRESSO ACQUA UTILIZZOUSER WATER INLET

USCITA ACQUA UTILIZZOUSER WATER OUTLET

FORI SOLLEVAMENTO INGRESSO ACQUA RECUPEROLIFTING HOLES RECOVERY WATER INLET

USCITA ACQUA RECUPERORECOVERY WATER OUTLET

SCARICO CONDENSACONDENSATE DRAIN

EpQUADRO ELETTRICO

Uin1" 1/4BSPMELECTRICAL PANEL

EsINGRESSO ALIMENTAZIONE ELETTRICA

Uout1" 1/4BSPMELECTRICAL SUPPLY INLET

Lh Ø34 Rin1" 1/4BSPM

RpPANNELLO ASPORTABILE

Rout1" 1/4BSPMREMOVABLE PANEL

Cdh ø 22

PmGRIGLIE DI PROTEZIONE FLUSSO ARIA

PROTECTIVE METAL MESH AIR FLOW

\ \ \ \\

Ep

LhLh

110

5246

619

7

460

506

1102

232

*

* OPZIONALE / OPTIONAL

148

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)32 478 60836 499 62941 512 642

Fori\Holes9

28,5840

28,5204

RpRp

386917

Rp

Es

SD00176 - AMAROON 2 HT/HWS 1PS Dimensional layout

32-36-41

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

82ASD00163

Visto-Checked byDenominazione-Denomination

Data-DateRev. Dis.-Draftsman Descrizione revisione-Revision descriptionCodice-Code Disegno-Drawing Rev.

Dis.-DraftsmanData-DateScala-Scale Visto-Checked by Foglio diSheet N. of

Sost. il dis.-Replace draw. Sost. dal dis.-Replaced by draw.

Materiale-Material Trattamento-Treatment

Peso-Weight [kg]

SCHEMA DIMENSIONALE / DIMENSIONAL DRAWINGGEYSER 2 50-60-70-80-90 SD00163

P. Frigolorpe 2

/ /

1N. Bettio

/Spessore-Thickness

/Colore vernice-Painted colour

/ /

12/12/20121/30

Codice-Code

/

/ / / //

SPAZI DI INSTALLAZIONE / CLEARANCES

1000

1000

00

1000

0

1000

0Cdh

Rp

Rp

Ep

Ep

2108 23

90

1203

167

519

251,5

371,517

9Lh Lh1403

Rp Cdh

Ep

SCARICO CONDENSA VERSIONE HPCONDENSATE DRAIN HP VERSION

INGRESSO ACQUA UTILIZZOUSER WATER INLET

USCITA ACQUA UTILIZZOUSER WATER OUTLET

Uout 2" BSPM

ø20

EpQUADRO ELETTRICO

Es

ELECTRICAL PANEL

Lh

INGRESSO ALIMENTAZIONE ELETTRICAELECTRICAL SUPPLY INLET

Uin 2" BSPMLIFTING HOLES

RpPANNELLO ASPORTABILE

REMOVABLE PANEL

Cdh

FORI DI SOLLEVAMENTO

*OPZIONALEOPTIONAL

PmGRIGLIE DI PROTEZIONE

PROTECTIVE METAL MESH

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1403 1203 2390

DIMENSIONI / DIMENSIONS

PmPm

Es

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)

50 582 58560 599 60270 609 61280 627 63090 638 641

MOD. 1P 20

MOD. 2P 40

Δ PESOΔ WEIGHT

Δ PESOΔ WEIGHT

Uout

Uin

A B C

A

A MODELLO STANDARD STANDARD MODEL

B MODELLO 1P 1P MODEL

C MODELLO 2P 2P MODEL

CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTIONS

**

Uin B C

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

SD00163 - AMAROON 2 HT Dimensional layout

50-60-70-80-90

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

83ASD00163

Visto-Checked byDenominazione-Denomination

Data-DateRev. Dis.-Draftsman Descrizione revisione-Revision descriptionCodice-Code Disegno-Drawing Rev.

Dis.-DraftsmanData-DateScala-Scale Visto-Checked by Foglio diSheet N. of

Sost. il dis.-Replace draw. Sost. dal dis.-Replaced by draw.

Materiale-Material Trattamento-Treatment

Peso-Weight [kg]

SCHEMA DIMENSIONALE / DIMENSIONAL DRAWINGGEYSER 2 50-60-70-80-90 SD00163

P. Frigolorpe 2

/ /

2N. Bettio

/Spessore-Thickness

/Colore vernice-Painted colour

/ /

12/12/20121/12,5

Codice-Code

/

/ / / //

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

IMPRONTA A TERRA / FOOTPRINT

FORI DI FISSAGGIOFIXING HOLES

Fh Ø18

G..PUNTI DI APPOGGIO ANTIVIBRANTIVIBRATION DAMPER FOOT HOLDS

24 1160 24

124

1160

124

1408

1208

G1 G2

G4G3

G1(kg)

G2(kg)

G3(kg)

G4(kg)

50 158 164 152 11160 163 169 157 11470 165 171 159 11680 170 176 164 12090 173 179 167 122

SD00163 - AMAROON 2 HT Dimensional layout

50-60-70-80-90

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

84ASD00164

Visto-Checked byDenominazione-Denomination

Data-DateRev. Dis.-Draftsman Descrizione revisione-Revision descriptionCodice-Code Disegno-Drawing Rev.

Dis.-DraftsmanData-DateScala-Scale Visto-Checked by Foglio diSheet N. of

Sost. il dis.-Replace draw. Sost. dal dis.-Replaced by draw.

Materiale-Material Trattamento-Treatment

Peso-Weight [kg]

SCHEMA DIMENSIONALE / DIMENSIONAL DRAWINGGEYSER 2 HWS 50-60-70-80-90 SD00164

P. Frigolorpe 2

/ /

1N. Bettio

/Spessore-Thickness

/Colore vernice-Painted colour

/ /

28/11/20121/30

Codice-Code

/

/ / / //

SPAZI DI INSTALLAZIONE / CLEARANCES

1000

1000

00

1000

0

1000

0Cdh

Rp

Rp

Ep

Ep

2108 23

90

1203 167

519

251,5

371,5

179Lh Lh

1403

Rp Cdh

Ep

SCARICO CONDENSA VERSIONE HPCONDENSATE DRAIN HP VERSION

INGRESSO ACQUA UTILIZZOUSER WATER INLET

USCITA ACQUA UTILIZZOUSER WATER OUTLET

INGRESSO ACQUA RECUPERORECOVERY WATER INLET

USCITA ACQUA RECUPERORECOVERY WATER OUTLET

2" BSPM

EpQUADRO ELETTRICO

Es

ELECTRICAL PANEL

Lh

INGRESSO ALIMENTAZIONE ELETTRICAELECTRICAL SUPPLY INLET

GRIGLIE DI PROTEZIONEPROTECTIVE METAL MESH

Uout 2" BSPMLIFTING HOLES

Cdh

Uin

FORI DI SOLLEVAMENTO

Rin 2" BSPM

ø20

Rout 2" BSPMRpPANNELLO ASPORTABILE

REMOVABLE PANEL

Pm

LUNGHEZZAWIDTH

PROFONDITA'DEPTH

ALTEZZAHEIGHT

1403 1203 2390

DIMENSIONI / DIMENSIONS

PmOPZIONALE / OPTIONAL

PmOPZIONALE / OPTIONAL

Es

Uout

Uin

A B

A

A MODELLO STANDARD STANDARD MODELB MODELLO 1P - 2P 1P - 2P MODELC MODELLO 1R 1R MODEL

CONNESSIONI IDRAULICHE / HYDRAULIC CONNECTIONS

Uin B

390

332

MODELLOMODEL

PESOWEIGHT

(kg)

PESO IN FUNZIONEOPERATING WEIGHT

(kg)

50 582 58560 599 60270 609 61280 627 63090 638 641

Δ PESOΔ WEIGHT

MOD. 1R 2P 57

Δ PESOΔ WEIGHT

MOD. 1R 17

Δ PESOΔ WEIGHT

MOD. 1R 1P 37

Δ PESOΔ WEIGHT

MOD. 1P 20

Δ PESOΔ WEIGHT

MOD. 2P 40

Rout A C

Rin C

Rin A

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

SD00164 - AMAROON 2 HT/HWS Dimensional layout

50-60-70-80-90

Swegon reserves the right to alter specifications. www.swegon.com

MAROON 2

85ASD00164

Visto-Checked byDenominazione-Denomination

Data-DateRev. Dis.-Draftsman Descrizione revisione-Revision descriptionCodice-Code Disegno-Drawing Rev.

Dis.-DraftsmanData-DateScala-Scale Visto-Checked by Foglio diSheet N. of

Sost. il dis.-Replace draw. Sost. dal dis.-Replaced by draw.

Materiale-Material Trattamento-Treatment

Peso-Weight [kg]

SCHEMA DIMENSIONALE / DIMENSIONAL DRAWINGGEYSER 2 HWS 50-60-70-80-90 SD00164

P. Frigolorpe 2

/ /

2N. Bettio

/Spessore-Thickness

/Colore vernice-Painted colour

/ /

28/11/20121/12,5

Codice-Code

/

/ / / //

- Proprietà riservata, riproduzione vietata a termini dilegge.Copyright.- Reserved property, reproduction prohibited accordin toexistent laws.Copyright.

MTE 56 rev. 02 date: 17/01/07

IMPRONTA A TERRA / FOOTPRINT

FORI DI FISSAGGIOFIXING HOLES

Fh Ø18

G..PUNTI DI APPOGGIO ANTIVIBRANTIVIBRATION DAMPER FOOT HOLDS

24 1160 24

124

1160

124

1408

1208

G1 G2

G4G3

G1(kg)

G2(kg)

G3(kg)

G4(kg)

50 158 164 152 11160 163 169 157 11470 165 171 159 11680 170 176 164 12090 173 179 167 122

SD00164 - AMAROON 2 HT/HWS Dimensional layout

50-60-70-80-90