Infrared Thermography Survey
Prepared for: Prepared by: Henry Plunkett Qualified assistant: Henry Plunkett
Date: 31 January 2020
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
2
Section 1, Preamble:
Report Guidelines This Report of Infrared Inspection provides complete documentation of thermal patterns
detected in your in your equipment, structure or system. It uses a subjective evaluation to
help you prioritize repairs to provide the greatest return from this inspection and your
maintenance.
The Report of Infrared Inspections meets the documentation requirements of the
Infraspection Institute Standard for Infrared Inspection of Electrical Systems and Rotating
Equipment, as well as standards, practices and specifications published by ASTM, NFPA
and NETA.
How Infrared Thermography Works Infrared Imagers “see” the heat radiated from your equipment in real time, just like a video
camera sees visible light. In colour thermograms, colours in the scene are matched to the
reference bar. Colours appearing closer to the top of the reference bar indicate higher
temperatures. Colours appearing closer to the bottom of the reference bar indicate lower
temperatures.
Repairs and Priority Ratings Each thermogram is given a Subjective Repair Priority Rating which is based upon your
qualified assistant’s opinion of how critical the subject item is to the safe and profitable
operation of your overall system. The Inspection Summary section of this report explains
how to use this Subjective Repair Priority Rating to help you determine how quickly you
need to investigate and correct the potential problem. Overheating can cause premature
deterioration and costly, unplanned failure of your equipment. Overheating connectors,
conductors and components will never get better. In fact, the temperature and rate of
deterioration will increase with time. No one can predict when a failure will occur. As a
result we suggest that you use the Subjective Repair Priority Ratings as a guide but that
you investigate and take the appropriate corrective measures as soon as possible.
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
3
A Hypothetical Fault Cycle of a “Hotspot”
The birth of a hot spot is shown at point “A”.
This hot spot can progress in many ways:
1) It can fail in a matter of hours after birth;
2) It can follow the simulated pattern as shown in the graph and fail at any point or go
indefinitely.
The only thing to keep in mind is that it will never cure itself. It will eventually FAIL.
Temperature Versus Deterioration
An investigation of hundreds of contactors has shown that many with small temperature
rises (5 to 10ºC) above ambient were seriously deteriorated and others with temperatures
of 100ºC or more had very little deterioration and vice versa.
The reason for this paradox is that excessive heating over an extended period causes
connections to arc and burn to the point where severe deterioration takes place. Arcing
causes the connector to weld to the conductor which forms a low resistance path for
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
4
current flow. As a result, heating of the components drops and may even cease entirely for
a time. These unintentional welds are generally poor ones and are easily broken by
mechanical stress, high load or fault currents. Once such a weld separates, heating and
arcing takes place again until the connector re-welds to the conductor. Meanwhile,
disintegration continues and, if not detected by inspection, the equipment eventually fails.
Conclusion : Don’t be misled by temperature. Temperature does not necessarily
indicate the severity of a fault. Consider the importance of each faulty component
within the framework of your whole system. Which faults, when they fail, will cause
you the greatest interruption.
Qualitative Report
Please note, that unless otherwise stated this is a qualitative report. That is, we are only
concerned with the thermal patterns that have been observed, and not the actual
reported temperature. With an emissivity value to set 1.0 in the thermal imagers
computer, the temperature values serve only as a reference and do not provide an
accurate measurement of temperature. Temperature values stated are apparent
temperatures only, and as such are understated values. This means that in most cases the
temperature values will be the most conservative value and that actual temperatures may
be significantly greater.
Inspection Summary For the equipment inspected, we have recorded thermogram(s) and/or photographs to
document conditions found during our inspection. These thermograms and/or photographs
appear on the Image Pages found in section 3 of this report.
As a reference, each Image Page contains Evaluation Priority Ratings. Subjective
Evaluation Ratings are based upon the Qualified Thermographer’s opinion of the subject
item’s importance to the safe and continuous operation of the facility.
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
5
The following risk matrix and colour coding has been developed to aid in prioritising
repairs.
Risk Matrix Qualitative Thermal Pattern observed
Low Medium
High
Extreme
Location of Thermal Exception/ Impact of Fault
House services light and power
House services AC
Tenancy Sub-mains
Main SW/ACB/ Major retailer
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
6
Section 2, Image summary:
Glossary of Terms:
OK - No observable thermal exception. The result of “OK” indicates that no heat anomaly was found at the time of inspection. This does not guarantee that no fault is present. Circuits are required to be under load for testing to provide adequate results. While all reasonable care and effort was taken to ensure load was optimal at the time of inspection, it is not possible to have all circuits under load at the time of testing. NA – No Access. No Access could be due to site safety concerns, hazards, locks, obstacles/obstructions, or protective coverings preventing line of sight access to the components. Recommend fitting of IR transmissive windows. OFF – Circuit not in use or not running. General Fault – No thermal anomaly at time of survey, however other safety/OHS/non-compliance issue noted. Refer to section 4, for images and further details
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
7
Below is an overall summary of the issues found, based on the risk matrix:
Survey Number
Location Equipment / Asset ID Image # General condition and
Compliance Priority
1 DB P-2 Arcade and Mall Light Time Switch
OK
2 DB P-2 Court and Down Lights
Time Switch
OK
3 DB P-2 Car Park Lighting Time
Switch
OK
4 DB P-2 Lighting Breakers 1
OK
5 DB P-2 Lighting Breakers 2 Fault detailed in Section 4,
Compliance and Condition Report below.
Refer to Section 4
6 DB P-2 Lighting Breakers 3
OK
7 DB P-2 Lighting Breakers 4
OK
8 DB P-2 Space Frame Track
Lights
OK
9 DB P-2 Lighting Breakers 5 Fault detailed in Section 4,
Compliance and Condition Report below.
Refer to Section 4
10 DB P-2 Supply to Contactor Coil
C18 DBP3
OK
11 DB P-2 Pylon Sign Time Switch
OK
12 DB P-2 Lighting Breakers 6
OK
13 DB P-2 Main Switch
OK
14 DB P-2 Logo and Signs Breakers
OK
15 DB P-2 Blank Panel
OK
16 DB P-2 Blank Panel
OK
Quantity Fault Rating Recommendations
3 Low Possible deficiency and warrants further monitoring.
2 Medium Indicates deficiency; prioritize repair.
5 High Corrective measures required as soon as possible.
0 Extreme Corrective measures required immediately.
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
8
17 DB P-2 Inside Security Lights
OK
18 DB 2 Meter Panel 1
OK
19 DB 2 Meter Panel 2
OK
20 DB 2 Meter Panel 4
OK
21 DB 2 Meter Panel 6
OK
22 DB 2 Meter Panel 8
OK
23 DB 2 Meter Panel 10
OK
24 DB 2 Meter Panel 12
OK
25 DB 2 Meter Panel 3
Ok
26 DB 2 Meter Panel 5
OK
27 DB 2 Meter Panel 7
OK
28 DB 2 Meter Panel 9
OK
29 DB 2 Meter Panel 11
OK
30 DB 2 Fuses Fault detailed in Section 4,
Compliance and Condition Report below.
Refer to Section 4
31 DB 2 Fuses 1 Fault detailed in Section 4,
Compliance and Condition Report below.
Refer to Section 4
32 DB 2 Fuses 2 IV_00297 Fault detailed in Section 4, Compliance and Condition Report below.
HIGH
33 DB 2 Fuses 3 IV_00299
HIGH
34 DB 2 Fuses 4 OK
35 DB 1 Meter Panel 1 IV_00295
LOW
36 DB 1 Meter Panel 2
OK
37 DB 1 Meter Panel 3
OK
38 DB 1 Meter Panel 4
OK
39 DB 1 Meter Panel 6
OK
40 DB 1 Meter Panel 8
OK
41 DB 1 Meter Panel 10
OK
42 DB 1 Meter Panel 12 Fault detailed in Section 4,
Compliance and Condition Refer to
Section 4
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
9
Report below.
43 DB 1 Meter Panel 5
OK
44 DB 1 Meter Panel 7
OK
45 DB 1 Meter Panel 9
OK
46 DB 1 Meter Panel 11
OK
47 DB 1 Shop 45 Meter Fault detailed in Section 4,
Compliance and Condition Report below.
Refer to Section 4
48 DB 1 Sumo Salad
OK
49 DB 1 Fuses 1
OK
50 DB 1 Fuses 2
OK
51 DB 1 Fuses 3
OK
52 DB 1 Fuses 4
OK
53 House Services DB
P3 Blank Panel
OK
54 House Services DB
P3 PE Override Switch and
contactors
OK
55 House Services DB
P3 Power Breakers
Fault detailed in Section 4, Compliance and Condition Report below.
Refer to Section 4
56 House Services DB
P3 Lighting Breakers 1
OK
57 House Services DB
P3 Main Switch
OK
58 House Services DB
P3 Lighting Breakers 2
Fault detailed in Section 4, Compliance and Condition Report below.
Refer to Section 4
59 Tenancy DB 3 Office West Main Isolator
NA
60 Tenancy DB 3 Subway Shop
NA
61 Tenancy DB 3 DB P3 Main Isolator
NA
62 Tenancy DB 3 DB P3 Meter
OK
63 Tenancy DB 3 Tenancy 51-59 Meter
Panel
OK
64 Tenancy DB 3 Tenancy 61-69 Meter Panel
OK
65 Tenancy DB 3 Tenancy 71-79 Meter
Panel
OK
66 Tenancy DB 3 Main Switch
NA
67 Tenancy DB 3 Tenancies 51-60 Isolator
NA
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
10
68 Tenancy DB 3 Shop 74
NA
69 Tenancy DB 3 Shop 78
NA
70 Tenancy DB 3 Tenancies 61-70 Isolator
NA
71 Tenancy DB 3 Tenancies 71-79 Isolator
NA
72 Tenancy DB 3 Cable Zone
OK
73 Tenancy DB 3 Tenancy 51-60 Breakers
OK
74 Tenancy DB 3 Tenancy 61-70 Breakers
OK
75 Tenancy DB 3 Tenancy 71-79 Breakers IV_00310
MEDIUM
76 Plant Room 5 AHU 5A Motor
OK
77 Plant Room 5 AHU 5B Motor
OK
78 Plant Room 5
Smoke Exhaust Fans Panel
Smoke Exhaust Fans
OK
79
Plant Room 5 Mechanical
Services Switch Board 5
Main Isolator
NA
80
Plant Room 5 Mechanical
Services Switch Board 5
Condenser Unit Supply Isolator
NA
81
Plant Room 5 Mechanical
Services Switch Board 5
Meter Panel
OK
82
Plant Room 5 Mechanical
Services Switch Board 5
Fuses
OK
83
Plant Room 5 Mechanical
Services Switch Board 5
Air Supply Fan Switches
Fault detailed in Section 4, Compliance and Condition Report below.
Refer to Section 4
84 Main Switchboard
2 Main Connections
OK
85 Main Switchboard
2 Cable Zone 1
OK
86 Main Switchboard
2 Cable Zone 2
OK
87 Main Switchboard
2 MSSB7 Isolator
NA
88 Main Switchboard
2 MSSB8 Isolator
NA
89 Main Switchboard
2 Ammeter Panel
NA
90 Main Switchboard
2 Smoke Exhaust Main
Switch
No load on essential services. OFF
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
11
91 Main Switchboard
2 MSSB Meter
OK
92 Main Switchboard
2 Normal Supply Main
OK
93 Main Switchboard
2 Cable Zone 3
OK
94 Main Switchboard
2 Tenancy DB 3 Isolator
IV_00302 IV_00303
HIGH
95 Main Switchboard
2 Emergency Supply Tie to
MSB 3 Main Switch
NA
96 Main Switchboard
2 Cable Zone 4
OK
97 Main Switchboard
2 MSSB4 Isolator
OK
98 Main Switchboard
2 MSSB5 Isolator
NA
99 Plant Room 4
Smoke Exhaust Fans Panel
Smoke Exhaust Fans Panel 4
No load on essential services. OFF
100
Plant Room 4 Mechanical
Services Switchboard
Main Isolator
NA
101
Plant Room 4 Mechanical
Services Switchboard
Meter Panel
OK
102
Plant Room 4 Mechanical
Services Switchboard
MSSB 4A/4B
NA
103
Plant Room 4 Mechanical
Services Switchboard
Switch Panel
Fault detailed in Section 4, Compliance and Condition Report below.
Refer to Section 4
104
Plant Room 4 Mechanical
Services Switchboard
Fuses
OK
105 Plant Room 4 MSSB 4A/4B
Distribution Section No load on essential services.
OFF
106 Plant Room 4 MSSB 4A/4B
Control Section
OK
107 Plant Room 4 MSSB 4A/4B
Starter Section No load on essential services.
OFF
108 Plant Room 4 AHU 4A Motor IV_00304
LOW
109 Plant Room 4 AHU
4A Valve Controllers
Expansion Valve Controllers 1-3
OK
110 Plant Room 4 AHU
4A Valve Controllers
Controllers 4-6
OK
111 Plant Room 4 AHU
4B Valve Controllers
Expansion Valve Controllers 1-2
OK
112 Plant Room 4 AHU
4B Valve Controllers
Controllers 3-4
OK
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
12
113 Plant Room 4 AHU 4C Motor
OK
113A Plant Room 4 AHU 4B Motor
OK
114 Food Hall DB Food Hall Main Switch
OK
115 Food Hall DB Meter Panel
OK
116 Food Hall DB Breakers
OK
117 Food Hall DB Cable Zone Fault detailed in Section 4,
Compliance and Condition Report below.
Refer to Section 4
118 Food Hall DB Main Switch Fault detailed in Section 4,
Compliance and Condition Report below.
Refer to Section 4
119 Food Hall DB Light and Power Breakers
OK
120 Food Hall DB AC Unit
OK
121 Food Hall DB Exhaust Fan Switches
OK
122 Plant Room 3 Plant
Room 3 DB Main Isolator
NA
123 Plant Room 3 Plant
Room 3 DB Fault Panel
OK
124 Plant Room 3 Plant
Room 3 DB Fuses
OK
125 Plant Room 3 Plant
Room 3 DB Contactors
Fault detailed in Section 4, Compliance and Condition Report below.
Refer to Section 4
126 Plant Room 3 Plant
Room 3 DB AHU 3
OK
127 Plant Room 3 Laundry DB
Laundry DB
OK
128 Plant Room 3 Laundry DB
Store Room 3 Breaker
OK
129 Plant Room 3 Laundry DB
Donut King Breaker
OK
130 Plant Room 3
Electric Pump Set Control
Electric Pump Set Control No load on essential services.
OFF
131 Plant Room 1 Plant
Room 1 DB Main Isolator
NA
132 Plant Room 1 Plant
Room 1 DB Fault Panel
OK
133 Plant Room 1 Plant
Room 1 DB Fuses
OK
134 Plant Room 1 Plant
Room 1 DB Contactors
Fault detailed in Section 4, Compliance and Condition Report below.
Refer to Section 4
135 Plant Room 1 Plant
Room 1 DB AHU 1
Fault detailed in Section 4, Compliance and Condition Report below.
Refer to Section 4
136 Plant Room 2 Plant
Room 2 DB Main Isolator
NA
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
13
137 Plant Room 2 Plant
Room 2 DB Fault Panel
OK
138 Plant Room 2 Plant
Room 2 DB Fuses
OK
139 Plant Room 2 Plant
Room 2 DB Contactors
Fault detailed in Section 4, Compliance and Condition Report below.
Refer to Section 4
140 Plant Room 2 Plant
Room 2 DB AHU 2
OK
141 DB P1 Breakers
OK
142 DB P1 Fan Sub Board
OK
143 Main Site Meter Panel 1
OK
144 Main Site DB 1 Mall Shops Switch IV_00311
HIGH
145 Main Site Food Hall DB 1 Switch
NA
146 Main Site Light and Power Fuses
NA
147 Main Site Power Factor Switch
OK
148 Main Site DB 2 Small Shops
OK
149 Main Site Blank Panel
OK
150 Main Site Busbars
OK
151 Main Site Kmart Main Switch
NA
152 Main Site Busbars
NA
153 Main Site Woolworths Main Switch
OK
154 Main Site Busbars
OK
155 Main Site PFC Isolator
OK
156 Main Site Meter Panel 2
OK
157 Main Site Ammeter Panel
OK
158 Main Site Sumo Salad Exhaust Fan
Switch
NA
159 Main Site Food Hall DB Exhaust
Fan Switch
NA
160 Main Site Air Con AH 1
NA
161 Main Site Air Con AH 2
NA
162 Main Site Air Con AH 3
NA
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
14
163 Main Site Kmart 1 Exhaust Fan
Switch
NA
164 Main Site Kmart 2 Exhaust Fan
Switch
NA
165 Main Site Kmart 3 Exhaust Fan
Switch
NA
166 Main Site Mall 4 Exhaust Fan
Switch
NA
167 Main Site Mall 5 Exhaust Fan
Switch
NA
168 Main Site Exhaust Fan DB
OK
169 Main Site Light and Power DB P2
OK
170 Main Site Busbars
NA
171 Main Site Sprinkler Pump Switches No load on essential services.
OFF
172 Main Site Busbars IV_00315
HIGH
173 Main Site Main Transformer Switch
1 IV_00319
HIGH
174 Main Site Main Transformer Switch
2 IV_00319
HIGH
175 West Office DB Meters, Fuses and
Breakers
OK
176 Mechanical
Services Switchboard 8
Fuses and Contactors Fault detailed in Section 4,
Compliance and Condition Report below.
Refer to Section 4
176A Plant Room 8 AHU8 Motor IV_00323
LOW
177 Mechanical
Services Switchboard 7
Fuses and Contactors Fault detailed in Section 4,
Compliance and Condition Report below.
Refer to Section 4
177A Plant Room 7 AHU7 Motor
OK
178 Main Switchboard
3 Blank Panel
OK
179 Main Switchboard
3 Emergency Supply Tie to
MSB 2
OK
180 Main Switchboard
3 East Offices Isolator
NA
181 Main Switchboard
3 Power Factor Fault
Protection
NA
182 Main Switchboard
3 Tenancies Main Isolator
NA
183 Main Switchboard
3 Tenancy Sub Meters
OK
184 Main Switchboard
3 Ammeter Panel
OK
185 Main Switchboard
3 Supermarket Meter
OK
186 Main Switchboard
3 Meter Panel
OK
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
15
187 Main Switchboard
3 PFC Isolator
NA
188 Main Switchboard
3 MSSB 6 Smoke Exhaust
Fan Switch
No load on essential services. OK
189 Main Switchboard
3 Supermarket Main
Isolator
OK
190 Main Switchboard
3 Tenancy Breakers
Fault detailed in Section 4, Compliance and Condition Report below.
Refer to Section 4
191 Office Wing East
DB Meter and Breakers
OK
192 Western Site Main
Switch Meter Panel
OK
193 Western Site Main
Switch Fuses and Breakers
OK
194 CMO DB Breakers
OK
195 Transformer Room Light and Power DB
OK
196 Transformer Room Ammeter Panel (Heater)
OK
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
16
Section 3, Image analysis:
DB-P2, Summary and Images:
Quantity Fault Rating Recommendations
0 Low Possible deficiency and warrants further monitoring.
0 Medium Indicates deficiency; repair as time permits.
0 High Corrective measures required as soon as possible.
0 Extreme Corrective measures required immediately.
Arcade and
Mall Lighting
Time Switch
(#1)
Court and
Down Lights
Time Switch
(#2)
Car Park
Lighting(#3)
Lighting
Breakers 1
(#4)
Lighting
Breakers 2
(#5)
Lighting
Breakers 3
(#6)
Lighting
Breakers 4
(#7)
Space Frame
Track Lights
(#8)
Lighting
Breakers 5
(#9)
Supply to
Contactor
Coil C18 DBP3
(#10)
Pylon Sign
Time Switch
(#11)
Lighting
Breakers 6
(#12)
Inside Security
Lights (#17)
Main Switch
(#13)
Logo and Signs
Breakers (#14)
Blank Panel
(#15)
Blank Panel
(#16)
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
17
DB 2, Summary and Images:
Quantity Fault Rating Recommendations
0 Low Possible deficiency and warrants further monitoring.
0 Medium Indicates deficiency; repair as time permits.
2 High Corrective measures required as soon as possible.
0 Extreme Corrective measures required immediately.
DB 2
Meter
Panel 1
(#18)
Meter
Panel 2
(#19)
Meter
Panel 3
(#25)
Meter
Panel 4
(#20)
Meter
Panel 6
(#21)
Meter
Panel 8
(#22)
Meter
Panel 10
(#23)
Fuses
(#30)
Meter
Panel 5
(#26)
Meter
Panel
12
(#24)
Meter
Panel 7
(#27)
Meter
Panel 9
(#28)
Meter
Panel 11
(#29)
Fuses 1
(#31)
Fuses 2
(#32)
Fuses 3
(#33)
Fuses 4
(#34)
IV_00297 IV_00299
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
18
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
19
Image numbers
IV_00297
DB/ chassis/circuits
DB 2 Survey # 32 Shop 17
Load per phase
Red White Blue 29amps N/A N/A
Voltage drop across terminals
Red White Blue
MCB rating/cable size
MCB/fuse rating Cable
Fuse
Part numbers for replacement
Additional comments
Distance 0.5mtr
Circuit is running close to capacity resulting in high chance of blowing the fuse or damaging the cable.
Suggested repairs
Consider investigating possibility of increase in circuit capacity. Pull Fuse to ensure correct fuse cartridge is fitted, and that the cable is correctly protected
LOW MEDIUM HIGH EXTREME
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
20
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
21
Image numbers
IV_00299
DB/ chassis/circuits
DB 2 Survey # 33 Shop 21A
Load per phase
Red White Blue 26amps N/A N/A
Voltage drop across terminals
Red White Blue
MCB rating/cable size
MCB Cable
FUSE
Part numbers for replacement
Additional comments
Distance 0.5mtr
Thermal pattern consistent with cable running at full capacity
Repair suggestions
Suggest investigating possibility of increasing circuit capacity. Pull fuse to ensure correct size cartridge is fitted, and that the cable is correctly protected.
LOW MEDIUM HIGH EXTREME
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
22
DB 1, Summary and Images:
Quantity Fault Rating Recommendations
1 Low Possible deficiency and warrants further monitoring.
0 Medium Indicates deficiency; repair as time permits.
0 High Corrective measures required as soon as possible.
0 Extreme Corrective measures required immediately.
DB 1 Meter
Panel 1
(#35)
Meter
Panel 2
(#36)
Meter
Panel 3
(#37)
Meter
Panel 4
(#38)
Meter
Panel 6
(#39)
Meter
Panel 8
(#40)
Meter
Panel 10
(#41)
Shop
45
Meter
(#47)
Meter
Panel 5
(#43)
Meter
Panel
12
(#42)
Meter
Panel 7
(#44)
Meter
Panel 9
(#45)
Meter
Panel 11
(#46)
Fuses 1
(#49)
Fuses 2
(#50)
Fuses 3
(#51)
Fuses 4
(#52)
Sumo
Salad
(#48)
IV_00295
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
23
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
24
Image numbers
IV_00295
DB/ chassis/circuits
DB 1 Survey # 35 Reject Shop
Load per phase
Red White Blue 22amps 20amps 8amps
Voltage drop across terminals
Red White Blue
MCB rating/cable size
MCB/fuse rating Cable
C40 6mm2
Part numbers for replacement
Additional comments
Distance O.5mtrs
Thermal signature supports current measurements indicating an unbalance three phase circuit. The electrical installation should be balanced as far as practicable in line with standard AS/NZS 3000: 2018 Appendix C.
Repair Suggestions
Ask Tenant to balance load across all three phases by assessing power demand on appliances attached to the Red and White phases and moving them to the underutilized Blue phase.
LOW MEDIUM HIGH EXTREME
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
25
DB P3, Summary and Images:
Quantity Fault Rating Recommendations
0 Low Possible deficiency and warrants further monitoring.
0 Medium Indicates deficiency; repair as time permits.
0 High Corrective measures required as soon as possible.
0 Extreme Corrective measures required immediately.
House Services DB P3
Blank Panel
(#53)
PE Override
Switch (#54)
Power
Breakers (#55)
Lighting
Breakers 1 (#56)
Main Switch
(#57)
Lighting
Breakers 2 (#58)
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
26
Tenancy DB 3, Summary and Images:
Quantity Fault Rating Recommendations
0 Low Possible deficiency and warrants further monitoring.
0 Medium Indicates deficiency; repair as time permits.
1 High Corrective measures required as soon as possible.
0 Extreme Corrective measures required immediately.
Tenancy DB 3
Office West
Main Isolator
(#59)
Subway Shop
81(#60)
DB P3 Main
Isolator(#61)
DB P3
Meter
(#62)
Tenancy 51-59
Meter Panel(#63)
Tenancy 61-69
Meter Panel(#64)
Tenancy 71-79
Meter Panel(#65)
Main Switch(#66)
Cable
Zone(#72)
(#67)
(#68)
(#69)
(#70)
(#71)
Tenancies 51-60
Isolator (#67)
Shop 74 (#68)
Shop 78 (#69)
Tenancies 61-70
Isolator (#70)
Tenancies 71-79
Isolator (#71)
Tenancy 51-60
Breakers(#73)
Tenancy 61-70
Breakers(#74)
Tenancy 71-79
Breakers(#75)
IV_00310
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
27
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
28
Image numbers
IV_00310
DB/ chassis/circuits
Tenancy DB 3 Survey # 75 Requires Clarification
Load per phase
Red White Blue 1amp 22amps 16amps
Voltage drop across terminals
Red White Blue
MCB rating/cable size
MCB/fuse rating Cable
32amp Quicklag 6mm2
Part numbers for replacement
Additional comments
Distance O.5mtrs
Thermal signature supports current measurements indicating an unbalance three phase circuit. The electrical installation should be balanced as far as practicable in line with standard AS/NZS 3000: 2018 Appendix C. White Phase is also running close to circuit limit increasing chance of blowing fuse or damaging cable.
Repair suggestions
Ask Tenant to balance load across all three phases by assessing power demand on appliances attached to the White (priority) and Blue phases and moving them to the underutilized Red phase.
LOW MEDIUM HIGH EXTREME
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
29
Plant Room 5, Summary and Images:
Quantity Fault Rating Recommendations
0 Low Possible deficiency and warrants further monitoring.
0 Medium Indicates deficiency; repair as time permits.
0 High Corrective measures required as soon as possible.
0 Extreme Corrective measures required immediately.
Plant Room 5
Smoke Exhaust Fans
Panel 5 (#78)
AHU 5A Motor (#76) AHU 5B Motor (#77)
Smoke Exhaust Fans
Panel 5
Mechanical Services
Switchboard 5
Air Supply Fan
Switches (#83)
Main
Isolator
(#79)
Condenser
Unit Supply
Isolator (#80)
Meter
Panel (#81)
Fuses (#82)
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
30
Plant room 4 Main switchboard Plant room 2, Summary and
Images:
Quantity Fault Rating Recommendations
0 Low Possible deficiency and warrants further monitoring.
0 Medium Indicates deficiency; repair as time permits.
1 High Corrective measures required as soon as possible.
0 Extreme Corrective measures required immediately.
Main Switchboard 2
Main
Connections(#84)
Cable Zone
1(#85)
Blank Panel Cable Zone 2
(#86)
Blank Panel
Blank Panel
MSSB7 Isolator
(#87)
MSSB8 Isolator
(#88)
Ammeter Panel(#89) Smoke Exhaust Main
Switch(#90)
MSSB Meter(#91)
Normal Supply Main
Switch(#92)
Cable Zone 3
(#93)
DB3(#94)
Emergency Supply
Tie to MSB3 Main
Switch (#95)
Cable Zone 4
(#96)
MSSB4
Isolator (#97)
MSSB5
Isolator (#98)
IV_00302 and
IV_00303
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
31
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
32
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
33
Image numbers
IV_00302 and IV_00303
DB/ chassis/circuits
Plant Room 4 Main Switchboard 2
Survey # 94 DB3 Main Isolator
Load per phase
Red White Blue Too dangerous to
measure Too dangerous to
measure Too dangerous to
measure
Voltage drop across terminals
Red White Blue
MCB rating/cable size
MCB/fuse rating Cable
Part numbers for replacement
Additional comments
Distance O.5mtrs
High heat signature on the Red phase may indicate the circuit is out of balance. The electrical installation should be balanced as far as practicable in line with standard AS/NZS 3000: 2018 Appendix C.
Repair suggestions
Further safe investigation into the current loads for the three phases in this circuit is warranted. This could be achieved by installing data loggers onto the other end of outgoing cables. IE: where they connect into the main switch of DB3.
LOW MEDIUM HIGH EXTREME
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
34
Smoke Exhaust Fans
Panel 4
Plant room 4, Summary and Images:
Quantity Fault Rating Recommendations
1 Low Possible deficiency and warrants further monitoring.
0 Medium Indicates deficiency; repair as time permits.
0 High Corrective measures required as soon as possible.
0 Extreme Corrective measures required immediately.
Smoke Exhaust Fans
Panel 4 (#99)
AHU 4A Motor (#108)
Mechanical Services
Switchboard 4
Switch Panel (#103)
Main
Isolator
(#100)
MSSB 4A/4B
(#102)
Meter
Panel
(#101)
Fuses (#104)
AHU 4C Motor (#113)
IV_00304
AHU 4B Motor (#113)A
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
35
MSSB 4A/4B
Distribution Section
(#105)
Control Section
(#106)
Starter Section (#107)
AHU 4A Valve
Controllers
Expansion Valve
Controllers 1-3
(#109)
Controllers 4-6
(#110)
AHU 4B Valve
Controllers
Expansion Valve
Controllers 1-2
(#111)
Controllers 3-4
(#112)
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
36
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
37
Image numbers
IV_00304
DB/ chassis/circuits
Plant Room 4 Survey # 108 AHU 4A motor
Load per phase
Red White Blue N/A N/A N/A
Voltage drop across terminals
Red White Blue
MCB rating/cable size
MCB/fuse rating Cable
Part numbers for replacement
Additional comments
Distance O.5mtrs
Thermal pattern may indicate motor bearing or pulley tensioning problem.
Repair suggestions
Suggest having the motor bearing and drive pulley tension checked.
LOW MEDIUM HIGH EXTREME
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
38
Food Hall DB, Summary and Images:
Quantity Fault Rating Recommendations
0 Low Possible deficiency and warrants further monitoring.
0 Medium Indicates deficiency; repair as time permits.
0 High Corrective measures required as soon as possible.
0 Extreme Corrective measures required immediately.
Food Hall DB
Food Hall Main
Switch (#114)
Meter Panel (#115)
Breakers (#116)
Cable Zone (#117)
Main Switch (#118)
Light and Power
Breakers (#119)
AC Unit (#120)
Exhaust Fan Switches
(#121)
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
39
Plant Room 3, Summary and Images:
Quantity Fault Rating Recommendations
0 Low Possible deficiency and warrants further monitoring.
0 Medium Indicates deficiency; repair as time permits.
0 High Corrective measures required as soon as possible.
0 Extreme Corrective measures required immediately.
Plant Room 3 DB
Main Isolator (#122) Fault Panel (#123)
Fuses(#124) Contactors (#125)
AHU 3 (#126)
(#128)
Store Room 3
Breaker
Donut King
Breaker
(#129)
(#127)
Electric Pump Set Control
(#130)
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
40
Plant Room 1, Summary and Images:
Quantity Fault Rating Recommendations
0 Low Possible deficiency and warrants further monitoring.
0 Medium Indicates deficiency; repair as time permits.
0 High Corrective measures required as soon as possible.
0 Extreme Corrective measures required immediately.
Plant Room 1
Plant Room 1 DB
Main Isolator (#131) Fault Panel (#132)
Fuses(#133) Contactors (#134)
AHU 1 (#135)
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
41
Plant Room 2, Summary and Images:
Quantity Fault Rating Recommendations
0 Low Possible deficiency and warrants further monitoring.
0 Medium Indicates deficiency; repair as time permits.
0 High Corrective measures required as soon as possible.
0 Extreme Corrective measures required immediately.
Plant Room 2
Main Isolator (#136) Fault Panel (#137)
Fuses (#138) Contactors (#139)
AHU 2 (#140)
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
42
Site Main DB, Summary and Images:
Quantity Fault Rating Recommendations
0 Low Possible deficiency and warrants further monitoring.
1 Medium Indicates deficiency; repair as time permits.
2 High Corrective measures required as soon as possible.
0 Extreme Corrective measures required immediately.
Site main DB
Meter Panel 1
(#143)
(#158)
(#159)
(#160)
(#161)
(#162)
(#163)
(#164)
(#165)
(#166)
(#167)
Blank Blank
DB 1 Mall
Shops Switch
(#144)
Food Hall DB
1 Switch
(#145)
Light and Power
Fuses (#146)
Power Factor
Switch
(#147)
DB 2 Small
Shops(#148)
Blank
Panel(#149)
Busbars(#150)
Kmart Main
Switch(#151)
Sprinkler
Pump
Switches
(#171)
Woolworths
Main
Switch(#153)
Bu
sbar
s(#1
54
)
PFC
Isolator(#155)
Meter
Panel 2
(#156)
Ammeter
Panel
(#157) Exhaust Fan
DB(#168)
Light & Power
DB P2 (#169)
Busbars(#170)
Busbars(#172)
Busbars(#152)
Main
Transformer
Switch 1
(#173)
Main
Transformer
Switch 2
(#174)
Exhaust Fan Switches
Sumo Salad
(#158)
Food Hall DB
2 (#159)
Air Con AH 1
(#160)
Air Con AH 2
(#161)
Air Con AH 3
(#162)
Blank Panel Blank Panel
Kmart 1
(#163)
Kmart 2
(#164)
Kmart 3
(#165)
Mall 4
(#166)
Mall 5
(#167)
IV_00315
IV_00311
1
IV_00319
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
43
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
44
Image numbers
IV_00311
DB/ chassis/circuits
Site Main Switchboard Chassis # 144 Small Shops DB
Load per phase
Red White Blue Too dangerous to
measure Too dangerous to
measure Too dangerous to
measure
Voltage drop across terminals
Red White Blue
MCB rating/cable size
MCB/fuse rating Cable
Part numbers for replacement
Additional comments
Distance O.5mtrs
High heat signature on the Red phase may indicate the circuit is out of balance. The electrical installation should be balanced as far as practicable in line with standard AS/NZS 3000: 2018 Appendix C.
Repair suggestions
Further safe investigation into the current loads for the three phases in this circuit is warranted. This could be achieved by installing data loggers on the outer end of the outgoing cables, where they connect into the main switch of the small shops DB
LOW MEDIUM HIGH EXTREME
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
45
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
46
Image numbers
IV_00315
DB/ chassis/circuits
Site Main Switchboard Chassis # 172 Busbars
Load per phase
Red White Blue Too dangerous to
measure Too dangerous to
measure Too dangerous to
measure
Voltage drop across terminals
Red White Blue
MCB rating/cable size
MCB/fuse rating Cable
Part numbers for replacement
Additional comments
Distance O.5mtrs
Thermal pattern on Red phase may be indicative of an increased load or a loose connection. Uneven heating on busbar may be indicative of a Localised fault in ACB
Repair suggestions
Service ACB. No history of recent servicing. Install IR windows on rear of SMDB to facilitate safe thermographic surveying of rear of ACBs
LOW MEDIUM HIGH EXTREME
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
47
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
48
Image numbers
IV_00319
DB/ chassis/circuits
Site Main Switchboard Survey # 173 and #174 Main Transformer Switches 1 and 2
Load per phase
Red White Blue
Voltage drop across terminals
Red White Blue
MCB rating/cable size
MCB/fuse rating Cable
Part numbers for replacement
Additional comments
Distance O.5mtrs
Uneven heat patterns across the two transformers which may indicate a potential problem. ACBs have not been serviced since 2015.
Repair suggestions
Service ACBs. Fit IR windows to rear of SMDB to facilitate safe surveying of ACBs
LOW MEDIUM HIGH EXTREME
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
49
DB P1, Summary and Images:
Quantity Fault Rating Recommendations
0 Low Possible deficiency and warrants further monitoring.
0 Medium Indicates deficiency; repair as time permits.
0 High Corrective measures required as soon as possible.
0 Extreme Corrective measures required immediately.
DB P1
Breakers (#141)
Fan Sub Board
(#142)
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
50
West office and plant room 8, Summary and Images:
Quantity Fault Rating Recommendations
1 Low Possible deficiency and warrants further monitoring.
0 Medium Indicates deficiency; repair as time permits.
0 High Corrective measures required as soon as possible.
0 Extreme Corrective measures required immediately.
West Office DB
Meters, Fuses and
Breakers (#175)
Mechanical Services Switch Board 8
Fuses and Contactors
(#176)
AHU8 Motor (#176A)
IV_00323
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
51
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
52
Image numbers
IV_00323
DB/ chassis/circuits
Plant Room 8 Survey # 176A AHU8 Motor
Load per phase
Red White Blue
Voltage drop across terminals
Red White Blue
MCB rating/cable size
MCB/fuse rating Cable
Part numbers for replacement
Additional comments
Distance O.5mtrs
Thermal pattern indicates a possible bearing fault or incorrect pulley tension.
Repair suggestions
Suggest having the motor bearing and drive pulley tension checked.
LOW MEDIUM HIGH EXTREME
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
53
East office and plant room 7, Summary and Images:
Quantity Fault Rating Recommendations
0 Low Possible deficiency and warrants further monitoring.
0 Medium Indicates deficiency; repair as time permits.
0 High Corrective measures required as soon as possible.
0 Extreme Corrective measures required immediately.
Mechanical Services Switch Board 7
Fuses and Contactors
(#177)
Office Wing East DB
Meters and Breakers
(#191)
AHU7 Motor (#177A)
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
54
Main Switch Board 3, Summary and Images:
Quantity Fault Rating Recommendations
0 Low Possible deficiency and warrants further monitoring.
0 Medium Indicates deficiency; repair as time permits.
0 High Corrective measures required as soon as possible.
0 Extreme Corrective measures required immediately.
Main Switch Board 3
(#178)
Emergency
Supply Tie to MSB
2 (#179)
East Offices
Isolator (#180)
Power Factor
Fault Protection (#181)
Tenancies Main Isolator(#182)
Tenancy Sub Meters
(#183) Blank Panel
Ammeter Panel
(#184)
Supermarket Meter
(#185)
Meter Panel (#186)
PFC Isolator
(#187)
MSSB 6 Smoke
Exhaust Fan Switch
(#188)
Supermarket Main
Isolator (#189)
Tenancy
Breakers (#190)
Bla
nk
Pan
el
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
55
Western Main SMDB and CMO DB, Summary and Images:
Quantity Fault Rating Recommendations
0 Low Possible deficiency and warrants further monitoring.
0 Medium Indicates deficiency; repair as time permits.
0 High Corrective measures required as soon as possible.
0 Extreme Corrective measures required immediately.
Western Site Main Switch
Meter Panel (#189)
Fuses and Breakers
(#190)
CMO DB
CMO DB
Breakers (#191)
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
56
Transformer Room, Summary and Images:
Quantity Fault Rating Recommendations
0 Low Possible deficiency and warrants further monitoring.
0 Medium Indicates deficiency; repair as time permits.
0 High Corrective measures required as soon as possible.
0 Extreme Corrective measures required immediately.
Light and Power DB Ammeter Panel (Heater)
#195 #196
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
57
Section 4, Compliance and Condition report:
Fault #001 Hazard Rating: MEDIUM
DB Mechanical Services Switchboards in Plant Rooms 1 (#134, #135), 2 (#137, #139), 3 (#123, #125, #126), 4 (#103), 5 (#83), 7 (#177) and 8 (#176)
Supporting Images:
Panel (Detailed above)
Description of Fault: Access to live terminals. Compliant at time of commissioning but requires remediation.
Repair Suggestion: Install locks to doors of switchboards, or to doors of plantrooms to ensure unauthorized access cannot not be gained. Install signage.
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
58
Fault #002 Hazard Rating: MEDIUM
DB DB 1 Supporting Images:
Panel #42
Description of Fault: Live connections on Fuse holder.
Repair Suggestion: Requires covering with blank fuse carriers (preferred) or the cables should be removed from the fuse holders and terminated in insulated connectors.
Fault #003 Hazard Rating: Medium
DB DB 2 Supporting Images:
Panel #30, #31 and #32
Description of Fault: Fuse Carriers missing.
Repair Suggestion: #30 requires 3 X RS63A blank fuse carriers. #31 requires 2 X RS63A blank fuse carriers. #32 requires 1 X RS63A blank fuse carrier.
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
59
Fault #004 Hazard Rating: Medium
DB DB P-2 and Food Hall DB Supporting Images:
Panel DB P-2 (#5, #9), Food Hall DB (#116)
Description of Fault: Cracked insulation on Busbars increasing the risk of arc flash. Continued deterioration of this insulation will lead to a high risk of arc flashover
Repair Suggestion: Replace Busbars.
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
60
Fault #005 Hazard Rating: LOW
DB DB P-2 Supporting Images:
Panel #5 and #9
Description of Fault: Incoming cables covered in electrical tape to indicate phase. Tape adhesion is prone to deterioration.
Repair Suggestion: Lugs should be covered with phase indicating heat shrink.
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
61
Fault #006 Hazard Rating: LOW
DB DB P-2 Supporting Images:
Panel #9
Description of Fault: Blue Phase cable taped and used as Neutral which could cause confusion and incorrect reconnection. Non-compliant colour coding.
Repair Suggestion: Replace cable with black neutral cable.
Fault #007 Hazard Rating: MEDIUM
DB DB P-2 Supporting Images: Panel #9
Description of Fault: Three single phase circuits used as a three phase circuit which creates possibility of incomplete circuit shutdown when required.
Repair Suggestion: Investigate the piece of equipment being powered by these breakers. With a view to replacing the three single phase breakers with a single three phase breaker.
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
62
Fault #008 Hazard Rating: High
DB DB 2 Supporting Images: Panel N/A
Description of Fault: Cable ingress not protected against fire.
Repair Suggestion: Install cover plate and fire retardant bags.
Fault #009 Hazard Rating: High
DB DB P-3 Supporting Images: Panel #55 and #58
Description of Fault: Occurrence of Eaton Quicklag RCBOs that have been recalled for safety concerns.
Repair Suggestion: The manufacturer (Eaton) should be contacted to arrange replacement of these devices. #55 – 3 X Quicklag 20 Amp RCBO #58 – 1 X Quicklag 16 Amp RCBO
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
63
Fault #010 Hazard Rating: LOW
DB DB P-3, Main Switch Board 3 and Food Hall DB
Supporting Images:
Panel DB P-3 (#74), Main Switch Board 3 (#190), Food Hall DB (#117, #118)
Description of Fault: Loose conductors terminated with insulation tape.
Repair Suggestion: Conductors should be terminated in insulated connecters.
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
64
Fault #011 Hazard Rating: INFORMATION ONLY
DB Main Switch Board 3 Supporting Images:
Panel #178
Description of Fault: Loose Jack chain introducing a hazard and adding no real benefit.
Repair Suggestion: Jack chain was removed.
Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020
Mob: 0488 788 398 Email: [email protected] EC10475
65
Review and Recommendations
• Refer to section 2 and 3 to assist in prioritising repairs which have been highlighted
by this thermographic survey.
Electrical Compliance and General Condition Report
• All issues of electrical non-compliance are detailed in section 4.
• Issues which have been highlighted, should be dealt with as promptly as possible.
Electrical Maintenance
• No evidence of recent testing and maintenance of ACB’s was noted at time of site
visit.
• A fault developing in an ACB would lead to a major loss of power
• A routine of scheduled maintenance would mitigate against this risk
• ACBs 1 and 2 were last serviced in 2015.
31 January 2020
___________________
Henry Plunkett
Managing Director Vantage West Electrical Services & Technology Mob: 0488 788 398 Email: [email protected] Web: www.vantagewest.com.au