5) Mount the fuse (3) with the screws (1)
SADTEM
4) Place the spring (4) at bottom of the holder
3) Fix the fuseholder (2) on the bushing (7) with the screw (5), rated tightening torque : 15 Nm
36 kV FT36 6.3A 1500MVA
INSTRUMENT TRANSFORMERS
This document is the property of SADTEM and may be changed without prior notice
1,1 1,8 2,7 Kg
12kV 24kV 36kV
Approx. Weight :
G
N°2-13761
24 kV FT24 6.3A 1500MVA
MOUNTING INSTRUCTIONSHIGH VOLTAGE HRC FUSES
12 kV FT12 6.3A 1000MVA
FRANCE
1) Unscrew the screws (1) and take the fuse (3) off
36kV
59506 DOUAI CEDEXBP 655
2) Take off the nut (E), useless for the assy
1
2
3
4
5
E
7
12kV and 24 kV
214330
354
SEALABLECOVER
(OPTIONAL)
82
38
INSTRUMENT TRANSFORMERS
Date: 25.04.2002
Rév: 19.02.2009
This document is the property of SADTEM and may be changed without prior notice
SADTEMFRANCE
E59506 DOUAI CEDEX
TRANSFORMER
TYPE : RV7
INDOOR VOLTAGE
BP 655
2 H.V. Bushings
STANDARD : IEC - BS - ANSI - CSA
INSULATION LEVEL : up to 24/50/125kV
N°2-35641
M10-20
NAMEPLATE
406
15°
4
M6-12
SECONDARY TERMINALS
Approx. Weight : 44 Kg
Secondary terminals
RATED TIGHTENING TORQUE
(M6) : 3 N.m
+ SCREW
+ SCREW
(M10) : 15 N.m
(±5%)
Primary terminals
4 HOLES
398
362
12
134
18
170
S1 S3 S2 UTEa1 a2 b IECX1 X2 X3 ANSI - CSA
S1 S2a bX1 X2
1S1 1S2 2S1 2S2 UTE1a 1b 2a 2b IECX1 X2 Y1 Y2 ANSI - CSA
398
225
362
170
186.5
134
345
+SCREW
H2
2 H.V. Bushings
TYPE : RV7-36
+SCREW
INSULATION LEVEL : up to 36/70/170kVTRANSFORMER
(±5%)
INDOOR VOLTAGE
RATED TIGHTENING TORQUE
(M6) : 3 N.m(M10) : 15 N.m
Secondary terminals
AH1
Approx. Weight : 48 Kg
This document is the property of SADTEM and may be changed without prior notice
MSADTEM
Primary terminals
STANDARD : IEC - BS - ANSI - CSA
FRANCE N°2-14669INSTRUMENT TRANSFORMERS
B
Rév. : 14.01.2009
BP 65559506 DOUAI CEDEX
M6-12
SECONDARY TERMINALS
Créat. : 26.09.1975
SEALABLE COVER
(OPTIONAL)
4
4 HOLES Ø12
M10-20
NAMEPLATE
15°
383
1S1 1S3 1S2 2S1 2S3 2S2 UTE1a1 1a2 1b 2a1 2a2 2b IECX1 X2 X3 Y1 Y2 Y3 ANSI - CSA
1S1 1S2 2S1 2S21a 1b 2a 2bX1 X2 Y1 Y2
S1 S3 S2a1 a2 bX1 X2 X3
S1 S2a bX1 X2
280
450
8
230
371
M10-20
A
4 HOLES Ø10
NAMEPLATE
240
240214
Ø16LIFTING LUGS
M8-12
Rév. : 16.06.2004
(M10) : 15 N.m (M8) : 8 N.m
Primary terminalsSecondary terminals
(±5%)RATED TIGHTENING TORQUE
J
1/6
N°2-14097BP 655
59506 DOUAI CEDEXFRANCE
INSTRUMENT TRANSFORMERS
SADTEMThis document is the property of SADTEM and may be changed without prior notice
Approx. Weight : 75 Kg
+SCREW
TYPE : RV9
STANDARD : IEC - BS - ANSI - CSA
INSULATION LEVEL : up to 24/50/125kV
2 H.V. Bushings
INDOOR VOLTAGETRANSFORMER
+SCREW
SECONDARY TERMINALS
H2H1B
Créat. : 25.06.1976
( )
280
M8
15,5
FT12 : 569
FT24 :673
(M10) : 15 N.m(M8) : 8 N.m(M8) : 8 N.m
(±5%)RATED TIGHTENING TORQUE
This document is the property of SADTEM and may be changed without prior notice
Primary terminalsSecondary terminalsFuse connection
INSTRUMENT TRANSFORMERS
SADTEM
HRC fuse assembly instructions according to drawing N° 2-13761
Créat. : 20.06.1978
Rév. : 04.02.2008
F
N°2-14269
Approx. Weight : 80 Kg
TYPE : RV9
AH1
24 kV
12 kV
STANDARD : IEC - BS - ANSI - CSA
INSULATION LEVEL : up to 24/50/125kV
2 H.V. Bushings
With high voltage HRC fuse (upon request)
Up to 12kV : FT 12 6.3A 1000MVAUp to 24kV : FT 24 6.3A 1500MVA
B
SECONDARY TERMINALS
H2
1/6
BP 65559506 DOUAI CEDEX
FRANCE
INDOOR VOLTAGETRANSFORMER
+SCREWM8-12
4 HOLES Ø10
Ø16LIFTING LUGS
NAMEPLATE
FUSE
( )
2308
240
214
159
M6-12
M8-1216
14
130
260
250
178
316
12
110 33
150
NAMEPLATE
4
193M10-20
AH1
333
+SCREW
SECONDARY TERMINALS
+SCREW
IEC
STANDARD : IEC - BS - ANSI - CSA
INSULATION LEVEL : up to 38.5/80/170kV
1 H.V. Bushing
L
INDOOR VOLTAGETRANSFORMER
RATED TIGHTENING TORQUE
+SCREW
(±5%)
Primary terminalsSecondary terminalsSecondary terminals
Créat. : 22.01.1982
Rév. : 11/04/2008
Approx. Weight : 30 Kg
N°2-20489BP 655
59506 DOUAI CEDEXFRANCE
(M10) : 15 N.m(M8) : 8 N.m(M6) : 3 N.m
This document is the property of SADTEM and may be changed without prior notice
INSTRUMENT TRANSFORMERS
SADTEM
TYPE : RY6A
(For secondary cover see drawing 2-38517)
X1 Y1 X2 Y2 X3 Y3 H2
1a1 2a1 1a2 2a2 1n 2n N
ANSI-CSA
14
16
AH1
+SCREW
+SCREW
IECANSI-CSA
1a1 2a1 1a2 2a2 1n 2n N X1 Y1 X2 Y2 X3 Y3 H2
SECONDARY TERMINALS
1 H.V. Bushing
C
INSULATION LEVEL : up to 38.5/80/170kVTRANSFORMER
INDOOR VOLTAGE
+SCREW
(±5%)RATED TIGHTENING TORQUE
STANDARD : IEC - BS - ANSI - CSA
Secondary terminals
Créat. : 02.02.2006
Rév. : 29.07.2008
Approx. Weight : 30 Kg
N°2-38517
Secondary terminalsPrimary terminals
FRANCE59506 DOUAI CEDEX
BP 655
(M6) : 3 N.m
This document is the property of SADTEM and may be changed without prior notice
INSTRUMENT TRANSFORMERS
SADTEM
(M10) : 15 N.m
TYPE : RY6A
(M8) : 8 N.m
M6-12
M8-12
WITH SEALABLE COVER
110
260
250
12
178 130
33
150
359
NAMEPLATE
193
4
M10-20
COVER
333
192,5
39
178
12250260
130 150
110 33
316
204158
47
280
63
168
432
+SCREW
RATED TIGHTENING TORQUE
This document is the property of SADTEM and may be changed without prior notice
Créat. : 25.04.1989
Rév. : 29.09.2003
(±5%)
(M10) : 15 N.m(M6) : 3 N.m
Primary terminalsSecondary terminals
ANSI-CSA
SADTEM
Approx. Weight : 19 Kg
BP 65559506 DOUAI CEDEX
FRANCE
X1 X2 H2
INSTRUMENT TRANSFORMERSN°2-25956
G
1a 1n 2a 2n N
a1 a2 n N
SECONDARY TERMINALS
a n N
X1 X2 X3 H2
a n da dn N X1 X2 Y1 Y2 H2
X1 X2 Y1 Y2 H2
IEC
TYPE : RY6C36
A
STANDARD : IEC - BS - ANSI - CSA
INSULATION LEVEL : up to 36/70/170kV
1 H.V. Bushing
+SCREW
INDOOR VOLTAGETRANSFORMER
H1
M6-12
M10-20
COVER(OPTIONAL) NAMEPLATE
158
M8
16 max.
677
204
48
COVER(OPTIONAL) 168
32
4
SECONDARY TERMINALS
NAME PLATE
FUSEREF: 455604/10
110
250260
130 150
33
316
178
12
(M8) : 8 N.m(M6) : 3 N.m
RATED TIGHTENING TORQUE
Primary terminalSecondary terminals
(±5%)
M6-12 + SCREW
Approx. Weight : 23 Kg
INDOOR VOLTAGETRANSFORMER
Créat : 28.06.2000
Rév: 22.03.2004
BP 65559506 DOUAI CEDEX
FRANCE
C
STANDARD : IEC - BS - ANSI - CSA
INSULATION LEVEL : up to 36/70/170kV
1 H.V. Bushing
With high voltage fuse
SADTEMThis document is the property of SADTEM and may be changed without prior notice
INSTRUMENT TRANSFORMERS
TYPE : RY6C36F
N°2-34451
1S1 1S2 2S1 2S2 P2 UTE1a 1n 2a 2n N IECX1 X2 Y1 Y2 H2 ANSI - CSA
1S1 1S2 2S1 2S2 P2a n da dn NX1 X2 Y1 Y2 H2
S1 S3 S2 P2a1 a2 n NX1 X2 X3 H2
S1 S2 P2a n NX1 X2 H2
1S1 1S2 2S1 2S2 P2 UTE1a 1n 2a 2n N IECX1 X2 Y1 Y2 H2 ANSI - CSA
1S1 1S2 2S1 2S2 P2a n da dn NX1 X2 Y1 Y2 H2
S1 S3 S2 P2a1 a2 n NX1 X2 X3 H2
S1 S2 P2a n NX1 X2 H2
208
310
211
M10-20
NAMEPLATE
4
FOR SEALABLE COVER SEE DWG: 36652
M6-12
14
16M8-12
RY7
+SCREW
TRANSFORMERINDOOR VOLTAGE
IEC
INSTRUMENT TRANSFORMERS
RATED TIGHTENING TORQUE
H.V. Bushing1
40.5/85/185kV
Secondary terminalsSecondary terminals
+SCREW
SECONDARY TERMINALS
TYPE :
20780N°2-
42 Kg
This document is the property of SADTEM and may be changed without prior notice
(±5%)
STANDARD : IEC - BS - ANSI - CSA
INSULATION LEVEL : up to
Primary terminals
Approx. Weight :
+SCREW
(M8) : 8 N.m
1a1 2a1 1a2 2a2 1n 2n N
04.06.1991Créat. :
04.10.2004Rév. :
X1 Y1 X2 Y2 X3 Y3 H2
FRANCE
HSADTEM 59506 DOUAI CEDEX
BP 655
(M6) : 3 N.m
ANSI-CSA
(M10) : 15 N.m
AH1
4 HOLESØ12
134
385 18
170
421
177
208
NAMEPLATE
4
4 HOLESØ12
134170
468
385 18
177
M6-12
M8-12
14
16
(M8) : 8 N.m
1a1 2a1 1a2 2a2 1n 2n N
TRANSFORMERINDOOR VOLTAGE
X1 Y1 X2 Y2 X3 Y3 H2
1 H.V. Bushing
INSULATION LEVEL : up to 40.5/85/185kV
STANDARD : IEC - BS - ANSI - CSA
Secondary terminals
Créat. : 29.09.2003
Rév. :
TYPE : RY7
Secondary terminals
SECONDARY TERMINALS
Primary terminals
FRANCE N°2-36652
Approx. Weight : 43 Kg
AThis document is the property of SADTEM and may be changed without prior notice
SADTEM
(±5%)
59506 DOUAI CEDEX
INSTRUMENT TRANSFORMERS
RATED TIGHTENING TORQUE
BP 655
(M6) : 3 N.m
IEC
+SCREW
+SCREW
+SCREW
ANSI-CSA
(M10) : 15 N.m
AH1
M10-20
WITH SEALABLE COVER
310
M10-20
390
39
(M8) : 8 N.m
1a1 2a1 1a2 2a2 1n 2n N
TRANSFORMERINDOOR VOLTAGE
X1 Y1 X2 Y2 X3 Y3 H2
1 H.V. Bushing
INSULATION LEVEL : up to 40.5/95/200kV
STANDARD : IEC - BS - ANSI - CSA
Secondary terminals
Créat. : 29.09.2003
Rév. : 27.11.2008
TYPE : RY8
Secondary terminals
SECONDARY TERMINALS
Primary terminals
FRANCE N°2-36650
Approx. Weight : 43 Kg
BThis document is the property of SADTEM and may be changed without prior notice
SADTEM
(±5%)
59506 DOUAI CEDEX
INSTRUMENT TRANSFORMERS
RATED TIGHTENING TORQUE
BP 655
(M6) : 3 N.m
IEC
+SCREW
+SCREW
+SCREW
ANSI-CSA
(M10) : 15 N.m
AH1
NAMEPLATE
WITH SEALABLE COVER
4
208
4 HOLESØ12
177
170
468
385
134
18
246
M6-12
M8-12
14
16
INDOOR VOLTAGE TRANSFORMERS DRY INSULATED
UP TO 36 KV
148, rue Martin du Nord – B.P.655 – 59506 DOUAI CEDEX – FRANCE Tel. : 03.27.71.32.41 - FAX : 03.27.71.32.49 SADTEM
SCDO032 rév 06-04/09 page 1
This document is the property of SADTEM and may be changed without prior notice
DESIGN
The primary and secondary windings are mounted on a very low losses core, hot cast in an insulating resin. The mounting base is supplied as a standard and is not to be dismounted.
ADVANTAGES
The casting process and the resin employed allows reduced outlines and excellent dielectric strength. The reduced dimensions of these transformers are typically well adapted for their mounting in metal en-closed and metalclad cubicles. They can be fixed in any position. These units compact and rugged, require no mainte-nance.
FUNCTION
These voltage measuring units provide two functions: - they insulate the high voltage power network from the low voltage metering circuit. - they supply a low voltage alternative signal propor-tional to the network voltage, and intented to supply meters, protection relays, measuring ins- tru-ments, etc...
STANDARDS AND TESTS
The transformers are manufactured according to the required standard: French, English, German, Cana-dian, American, Australian, International, etc... They can also be designed according to any cus-tomer specification. All the routine tests required by the relevant standard are performed on each unit. The results are noted in the report referred to the order.
The type tests have been passed when qualifying each type of transformer, the reports are available on request.
TYPICAL RATINGS
-Insulation 7.2kV to 36kV -Frequency 50Hz or 60HZ -Connection phase - ground or phase - phase -Primary voltage 2600/√3 V 2600V
to 33000/√3 to 33000
-Secondary voltage 100/√3 100,110
110/√3 220 -Accuracy metering: 15 VA CL0.2 to 300 VA CL1
relaying: 15VACL3P to 100VACL6P -Voltage factor for line to ground units
1.5xUn-30sec for grounded neutral 1.9xUn-30sec for impedant neutral 1.9xUn-8h for isolated neutral
(residual voltage winding 100/3 on request) -Voltage factor for all types 1.2xUn-continuous
CONNECTION
The secondary terminals supply L.V. to the measur-ing circuits. They must never be short-circuited. For each secondary winding, one terminal (one only) is to be grounded. The core is connected to the base, and so grounded.
Rated tightening torques :
Primary terminal (M10) 15 Nm Secondary terminal (M5) 2 Nm Secondary terminal (M6) 3 Nm Ground terminal (M8) 8 Nm
VOLTAGE TRANSFORMER WITH HIGH VOLTAGE FUSE
TYPE Y24F
148, rue Martin du Nord – B.P.655 – 59506 DOUAI CEDEX – FRANCE Tel. : 03.27.71.32.41 - FAX : 03.27.71.32.49 SADTEM
SCDO036 rév 02-02/02 page 1
This document is the property of SADTEM and may be changed without prior notice
DESIGN
The primary and secondary windings are mounted on a very low losses core, hot cast in an insulating resin. The fuse cartridge is placed in an insulating horizontal holder, cast with the transformer. The high voltage primary terminal, at the end of the fuse holder, is equipped with a spring-contact, silver plated for direct connection to the busbar. The mounting base is supplied as a standard and is not to be dismounted.
ADVANTAGES
The casting process and the resin employed allows reduced outlines and excellent dielectric strength. The reduced dimension and the integrated fuse holder of the Y24F are typically well adapted for an easy mounting in a withdrawable VTS compartment. They can be fixed in any position. These units compact and rugged, require no maintenance.
STANDARDS AND TESTS
The transformers are manufactured according to the required standard: French, German, Canadian, American, Australian, International, etc... All the routine tests required by the relevant standard are performed on each unit. The results are noted in the report referred to the order. The type tests have been passed when qualifying the transformer, the reports are available on request.
TYPICAL RATINGS
-Insulation 7.2kV to 24kV -Frequency 50Hz or 60Hz -Connection phase to ground -Primary voltage 2600/√3 to 25000/√3
-Secondary voltage 100/√3, 110/√3 -Voltage factor
1.5xUn-30sec for grounded neutral 1.9xUn-30sec for impedant neutral 1.9xUn-8h for isolated neutral (residual voltage winding 100/3 on request)
-Accuracy see chart -Thermal burden 250VA -Fuse Size DIN10 - 12/24 KV - 6A -Barrel dia 55mm maximum
148, rue Martin du Nord - B.P. 655 - 59506 DOUAI Cédex - FRANCETèl. : 03.27.71.32.41 - Fax : 03.27.71.32.49
This document ist he property of SADTEM and may be changed without prior notice
SADTEMSCDO088 rév 01-09/01 page 2
VT's TERMINALS MARKING
IE C A N S I AS IE C A N S I A SV D E C S A V D E C S AB S B S
A H1 A 2 A H1 A 2
1a X 1 1a2 a X 1 a 2
1b X 2 1a1 b X 2 a 1
2a Y1 2a2
2b Y2 2a1
B H2 A 1 B H2 A 1
2 s e c o n d a r ie s 1 secondary
P H A S E T O P H A S E
IEC ANSI AS IEC ANSI ASV D E C S A V D E C SAB S B S
A H1 A 2 A H1 A 2
a X 1 1a2 1a X 1 1a2
n X 2 1a1 1n X 2 1a1
da Y1 2a2 2a Y1 2a2
dn Y2 2a1 2n Y2 2a1
N H2 A 1 N H2 A 1
PHASE TO GROUND
1 secondary + residual 2 secondaries
VOLTAGE TRANSFORMER WITH HIGH VOLTAGE FUSE
TYPE Y24F
148, rue Martin du Nord – B.P.655 – 59506 DOUAI CEDEX – FRANCE Tel. : 03.27.71.32.41 - FAX : 03.27.71.32.49 SADTEM
SCDO036 rév 02-02/02 page 2
This document is the property of SADTEM and may be changed without prior notice
CONNECTION
The secondary terminals supply L.V. to the measuring circuits. They must never be short-circuited. For each secondary winding, one terminal (one only) is to be grounded. The core is connected to the base, and so grounded. The H.V. primary terminal is connected to the bus bar by mean of the spring contact. The L.V. primary terminal, located near the secondary terminals, must be grounded. The residual voltage winding is to be connected in open delta, closed by a resistor (typical value 100 ohms, 320W). One end of the delta must be grounded.
- Note :
The purpose of the H.V. fuse is to isolate the bus bar from the transformer if any incident occurs on it, and not to protect the transformer in case of an overload.
IEC ACCURACY ANSI - CSA ACCURACY Voltage factor accuracy 1 Secondary 2 Secondaries
1 Secondary + residual 2A 1 secondary
1 secondary + residual 2A
Cl0.2 15 VA
1.5 x 30sec Cl0.5 50 to 80 VA 30 VA + 30 VA 0.3WX
or
Cl1 50 to 200 VA 60 VA + 60 VA 0.6WXY
Cl0.2 10 VA 10 VA
1.9 x 30sec Cl0.5 50 VA 15 VA + 15 VA 30 VA 0.3WX
or 0.6WXY
Cl1 50 to 100 VA 30 VA + 30 VA 60 VA 0.6WXY
Cl0.2 10 VA
1.9 x 8h Cl0.5 50 VA 10 VA+ 10 VA 30 VA 0.6WX 0.6WX
Cl1 100 VA 20 VA+ 20 VA 60 VA
INDOOR VOLTAGE TRANSFORMERS DRY INSULATED
UP TO 36 KV
148, rue Martin du Nord – B.P.655 – 59506 DOUAI CEDEX – FRANCE Tel. : 03.27.71.32.41 - FAX : 03.27.71.32.49 SADTEM
SCDO032 rév 06-04/09 page 2
This document is the property of SADTEM and may be changed without prior notice
- Line to ground :
The H.V. primary terminal is connected to the bus bar directly or by mean of a high voltage fuse.
The L.V. primary terminal, located near the secondary terminals, must be grounded. The residual voltage winding is to be connected in open delta, closed by a resistor (typical value 100 ohms, 320W). One end of the delta must be grounded.
- Line to line:
The two H.V. terminals are connected to the bus bars directly or by mean of high voltage fuses.
- Note:
The purpose of the H.V. fuses is to isolate the bus bars from the transformer if any incident occurs on it, and not to protect the transformer in case of an overload.
TYPICAL RATINGS OF EACH UNIT IEC 50 or 60 Hz
148, rue Martin du Nord – B.P.655 – 59506 DOUAI CEDEX – FRANCE
Tel. : 03.27.71.32.41 - FAX : 03.27.71.32.49 SADTEM SCDO032 rév 06-04/09 page 3
This document is the property of SADTEM and may be changed without prior notice
MAX.PRIM. AVAILABLE BURDENS (VA) THERMAL
INSUL. BIL VOLTAGE TYPE 1 SECONDARY 2 SECONDARIES BURDENkV kV V CL0.2 CL0.5 CL1.0 CL0.5 + CL0.5 CL1 + CL1 (VA)
7.2 60 6600 V7P 15 50 100 15 15 30 30 250
11000/V3 Y12P 10 50 100 15 15 40 40 250
Y12G 30 100 200 40 40 80 80 400
11000 V12G 30 100 200 30 30 80 80 500
15000/V3 Y12P 10 50* 100* 250
Y12G 25 100 200 40 40 80 80 400
15000 V24P 15 50 100 300
Y24P 10 50* 100* 250
22000/V3 Y24M 25 100** 200** 30 30 60 60 300 to 400
Y24G2 50 200** 400** 50 50 100 100 600
Y24F 10 50 150 25 25 60 60 300
22000 V24P 10 50 100 300
V24G 50 150 400 50 50 100 100 700
RV7 150 300 700 100 100 250 250 1500
RY6C36 15 50 100 15 15 30 30 250
33000/V3 RY6A 40 150 300 50 50 150 150 600
170RY7 100 400 900 150 150 400 400 1000
33000 RV7-36 75 300 700 100 100 250 250 1500
200 33000/V3 RY8 50 300 600 100 100 200 200 800
Rated voltage factor : All units : 1.2xUn continuousPhase to ground units : 1.9xUn-30sec (8h upon request)
Phase to ground VT : Residual Voltage winding 100/3 or 110/3 2A-8h upon request* 60%** 80%
Secondary voltage : 100, 110, 100V3, 110/V3Other value upon request
} of burden with residual voltage winding 2A-8h
12
17.5
24
36
75
95
125
100
45
171
NAMEPLATE
110146
5
RATED TIGHTENING TORQUE
(M6) : 3 N.m
(±5%)
Secondary terminals(M10) : 15N.mPrimary terminals
Approx. Weight : 12 Kg
125 148
82
98
100
12205
170
4811
235
M6-12
SECONDARY TERMINALS
+ SCREW
12
15
This document is the property of SADTEM and may be changed without prior notice
BP 655
2 H.V. Bushings
SADTEM 59506 DOUAI CEDEXCréat :03.04.2003
INDOOR VOLTAGE
INSTRUMENT TRANSFORMERS
TYPE : V7P
FRANCE
C
TRANSFORMER
Rév : 14.10.2003
STANDARD : IEC - BS - ANSI - CSA
INSULATION LEVEL : up to 7,2/20/60kV
N°2-36369
M10-20
H1 H2
+ SCREW
BA
COVER(OPTIONAL)
124
204
1S1 1S2 2S1 2S2 UTE1a 1b 2a 2b IECX1 X2 Y1 Y2 ANSI-CSA
S1 S3 S2
a1 a2 b
X1 X2 X3
S1 S2
a b
X1 X2
TYPICAL RATINGS OF EACH UNIT ANSI – CSA 60 Hz
148, rue Martin du Nord – B.P.655 – 59506 DOUAI CEDEX – FRANCE
Tel. : 03.27.71.32.41 - FAX : 03.27.71.32.49 SADTEM SCDO032 rév 06-04/09 page 4
This document is the property of SADTEM and may be changed without prior notice
LINE TO LINEINSUL. BIL MAX.PRIM. TYPE AVAILABLE BURDENS (VA) THERMAL
kV kV kV 1 SECONDARY 2 SECONDARIES VA
5 60 4.8 V7P 0.6WX1.2Y 250
V12G 0.6WXY 0.6WX 0.6WX 500
15 110 14.4 V24G 0.3WX 0.6Y 0.6WX 0.6WX 700
RV15 0.3WXYZ 0.3WXY 0.6Z 0.3WXY 0.6Z 1750
27.5 125 25 V24G 0.3WX 0.6Y 700
RV7 0.3WXYZ 0.3WXY 0.3WXY 1000
RV9 0.3WXYZ 0.6ZZ 0.6WXYZ 0.6WXYZ 2000
RV9 0.3WXYZ ZZ 0.3WXYZ 0.3WXYZ 3000
27.5 150 27.6 RV7-36 0.3WXY 0.6Z 0.3WXY 0.3WXY 1000
RV7-36 0.3WXYZ 0.6ZZ 0.6WXYZ 0.6WXYZ 1500
34.5 170 34.5 RV7-36 0.3WXY 0.6Z 1000
RV7-36 0.3WXYZ 0.6WXY 0.6WXY 1500
LINE TO GROUNDINSUL. BIL MAX.PRIM. TYPE AVAILABLE BURDENS (VA) THERMAL
kV kV kV 1 SECONDARY 2 SECONDARIES VA
5 60 2.8 Y12G 0.3WX 0.6Y 0.6WX 0.6WX 400
15 110 8.4 Y24G2 0.3WXY 0.6Z 0.6WX 0.6WX 500
RY15 0.3WXYZ 0.3WXY 0.6Z 0.3WXY 0.6Z 1500
27.5 125 14.4 Y24G2 0.3WXY 0.6Z 0.6WX 0.6WX 600
Y24F 0.3WX 300
RY7 0.3WXYZ 0.3WXY 0.3WXY 1000
27.5 150 14.4 RY6A 0.3WXY 600
RY7 0.3WXYZ 0.3WXY 0.3WXY 1000
34.5 170 20 RY6A 0.3WXY 600
RY7 0.3WXYZ 0.3WXY 0.3WXY 1000200 20 RY8 0.3WXY 0.6Z 0.3WXY 0.3WXY 800
Rated voltage factor : All units : 1.2xUn continuousPhase to ground units : 1.9xUn-30sec (8h upon request)
INSUL. BIL
kV kV 500 VA 1000 VA 2000 VA 3000 VA 4000 VA
12 75 V12G RV6 RV7 RV9 RV9
17.5 95 V24G RV6 RV9 RV9 RV9
24 125 V24G RV7 RV9 RV9 RV9
36 170 RV7-36 RV7-36 ___ ___ ___
AUXILIARY POWERThermal burden (220 secondary)
124
204
M10-20
AH1
BH2
+ SCREW 110146
5
NAMEPLATE
100
125 148
48
260
11 205 20
(M6) : 3 N.m(M10) : 15N.m
RATED TIGHTENING TORQUE (±5%)
Secondary terminalsPrimary terminals
Approx. Weight : 12 Kg
M6-12+ SCREW
SECONDARY TERMINALS
Créat :17.02.2000
Rév : 30.11.2009
BP 65559506 DOUAI CEDEX
FRANCE
C
INDOOR CURRENTTRANSFORMER
TYPE : V12P
STANDARD : IEC - BS - ANSI - CSA
INSULATION LEVEL : up to 12/28/75kV
2 H.V. Bushings
SADTEMThis document is the property of SADTEM and may be changed without prior notice
INSTRUMENT TRANSFORMERSN°2-34094
124
204
M10-20
AH1
BH2
+ SCREW 110146
5
NAMEPLATE
100
125 148
48
260
11 205 20
(M6) : 3 N.m(M10) : 15N.m
RATED TIGHTENING TORQUE (±5%)
Secondary terminalsPrimary terminals
Approx. Weight : 12 Kg
M6-12+ SCREW
SECONDARY TERMINALS
Créat :17.02.2000
Rév : 30.11.2009
BP 65559506 DOUAI CEDEX
FRANCE
C
INDOOR CURRENTTRANSFORMER
TYPE : V12P
STANDARD : IEC - BS - ANSI - CSA
INSULATION LEVEL : up to 12/28/75kV
2 H.V. Bushings
SADTEMThis document is the property of SADTEM and may be changed without prior notice
INSTRUMENT TRANSFORMERSN°2-34094
65130
178
165
331
292
,5
178
278.5
5
275
150
11
52.5+SCREW
E
Secondary terminalsPrimary terminals
NAMEPLATE
2 H.V. Bushings
INSULATION LEVEL : up to 24/50/125kVTRANSFORMER
INDOOR VOLTAGE
(M5) : 2 N.m(M10) : 15 N.m
N°2-32553Créat. : 05.02.1998
Rév. : 07.05.2009
SADTEMThis document is the property of SADTEM and may be changed without prior notice
RATED TIGHTENING TORQUE
STANDARD : IEC - BS - ANSI - CSA
FRANCE
INSTRUMENT TRANSFORMERS
H2
(±5%)
Approx. Weight : 35 Kg
B
H1A
59506 DOUAI CEDEX
+SCREW
BP 655
TYPE : V24G
SECONDARY TERMINALS
M10-20
M5-12
4 HOLES Ø11
S1 S2 UTEa b IEC
X1 X2 ANSI-CSA
S1 S3 S2
a1 a2 b
X1 X2 X3
1S1 1S2 2S1 2S2
1a 1b 2a 2b
X1 X2 Y1 Y2
275
218
45
22,5 323,55
148
270 12,5
125 148
135
A H1
BP 65559506 DOUAI CEDEX
FRANCE
(M10) : 15 N.m(M5) : 2 N.m
RATED TIGHTENING TORQUE
This document is the property of SADTEM and may be changed without prior notice
Primary terminalsSecondary terminals
INSTRUMENT TRANSFORMERS
SADTEMCréat. : 11.02.1998
Rév. : 17.03.2003
TYPE : Y12G
+SCREW
+SCREW
SECONDARY TERMINALS
STANDARD : IEC - BS - ANSI - CSA
INSULATION LEVEL : up to 17.5/38/95kV
1 H.V. Bushing
INDOOR VOLTAGETRANSFORMER
C
N°2-31340
Approx. Weight : 21 Kg
(±5%)
M10-15
M5-12
COVER(OPTIONAL)
NAMEPLATE
4 HOLES Ø11
1S1 1S3 1S2 2S1 2S2 P2 UTEa1 a2 n da dn N IECX1 X2 X3 Y1 Y2 H2 ANSI-CSA
1S1 1S2 2S1 2S2 P2
1a 1n 2a 2n N
X1 X2 Y1 Y2 H2
1S1 1S2 2S1 2S2 P2a n da dn N
X1 X2 Y1 Y2 H2
S1 S3 S2 P2
a1 a2 n N
X1 X2 X3 H2
S1 S2 P2
a n N
X1 X2 H2
243
260
240
42,5
45
M10-20 130
65
175
5
NAMEPLATE
20205
125 148
15,51654 HOLES Ø11
M6-12
X1 X2 a b
E
STANDARD : IEC - BS - ANSI - CSA
INSULATION LEVEL : up to 24/50/125kV
2 H.V. Bushings
INDOOR VOLTAGETRANSFORMER
SADTEMThis document is the property of SADTEM and may be changed without prior notice
Ech:1/6
TYPE : V24P
+SCREW
B
+SCREW
SECONDARY TERMINALS
Approx. Weight : 20 Kg
IEC
Créat. : 29.01.1998
Rév. : 10.05.2007
ANSI-CSA
INSTRUMENT TRANSFORMERSN°2-32445
AH1 H2
(±5%)RATED TIGHTENING TORQUE
(M10) : 15 N.m(M6) : 3 N.m
Primary terminalsSecondary terminals
BP 65559506 DOUAI CEDEX
FRANCE
COVER(OPTIONAL)
67
218
162138,5
5
148
205 20
125 148
98
260
1527
TYPE : Y12P
STANDARD : IEC - BS - ANSI - CSA
INSULATION LEVEL : up to 17.5/38/95kV
1 H.V. Bushing
INDOOR VOLTAGETRANSFORMER
+SCREW
SECONDARY TERMINALS
INSTRUMENT TRANSFORMERS
RATED TIGHTENING TORQUE(±5%)
This document is the property of SADTEM and may be changed without prior notice
Créat. : 11.02.1998
Rév. : 02.11.1998
Approx. Weight : 15 Kg
SADTEM
Primary terminalsSecondary terminals
BP 65559506 DOUAI CEDEX
FRANCE N°2-32569C
(M10) : 15 N.m(M6) : 3 N.m
+SCREW
A H1
M10-15
M6-12
4 HOLES Ø11
COVER(OPTIONAL)
NAMEPLATE
1S1 1S2 2S1 2S2 P2 UTE1a 1n 2a 2n N IECX1 X2 Y1 Y2 H2 ANSI-CSA
S1 S3 S2 P2
a1 a2 n N
X1 X2 X3 h2
1S1 1S2 2S1 2S2 p2
a n da dn N
X1 X2 Y1 Y2 H2
S1 S2 P2
a n N
X1 X2 H2
482
55
NAMEPLATE
288
138
30
243
M6-12
SECONDARY TERMINALS
+ SCREW
4 HOLES Ø11
239,5240
108
25
130
325
Primary terminals
RATED TIGHTENING TORQUE
(M8) : 8 N.m(M6) : 3 N.m
(±5%)
H.V. CONTACT
HANDLE FUSE "DIN-10" 152/24kV 6Asupplied upon order
Secondary terminals
Approx. Weight : 23 Kg
A
(OPTIONAL)
H1
COVER
M8-15+ SCREW
566.5
216,5
519,5
INSTRUMENT TRANSFORMERS
Date: 19.02.2003
Rév : 20.04.2009
This document is the property of SADTEM and may be changed without prior notice
SADTEMFRANCE
C59506 DOUAI CEDEX
TRANSFORMER
TYPE : Y24F
INDOOR VOLTAGE
BP 655
Fused type
STANDARD : IEC - BS - ANSI - CSA
INSULATION LEVEL : up to 24/50/125kV
1 H.V. bushing
N°2-36239
1S1 1S3 1S2 2S1 2S2 P2 UTEa1 a2 n da dn N IECX1 X2 X3 Y1 Y2 H2 ANSI-CSA
1S1 1S2 2S1 2S2 P2
1a 1n 2a 2n N
X1 X2 Y1 Y2 H2
1S1 1S2 2S1 2S2 P2
a n da dn N
X1 X2 Y1 Y2 H2
S1 S3 S2 P2
a1 a2 n N
X1 X2 X3 H2
S1 S2 P2
a n N
X1 X2 H2
20
632
55
482
COVER (OPTIONAL)
281.5
585
Secondary terminalsApprox. Weight : 23 Kg
INSTRUMENT TRANSFORMERS
SADTEMThis document is the property of SADTEM and may be changed without prior notice
(±5%)
(M6) : 3N.m
+SCREW
RATED TIGHTENING TORQUETRAVEL : 14
H1
SECONDARY TERMINALS
1 H.V. Bushing
FRANCE
Créat. : 19.02.2003
Rév. : 20.04.2009N°2-36240
C
A
59506 DOUAI CEDEX
TRANSFORMER
TYPE : Y24F
INDOOR VOLTAGE
BP 655
Fused type
INSULATION LEVEL : up to 24/50/125kV
STANDARD : IEC - BS - ANSI - CSA
SILVERPLATED
H.V. CONTACT
4 HOLES Ø11
130 108
325
240 25
304.5
M6-12
NAMEPLATE
243
30
138
288
supplied upon orderFUSE "DIN-10" 12/24kV 6AHANDLE
1S1 1S3 1S2 2S1 2S2 P2 UTEa1 a2 n da dn N IECX1 X2 X3 Y1 Y2 H2 ANSI-CSA
1S1 1S2 2S1 2S2 P2
1a 1n 2a 2n N
X1 X2 Y1 Y2 H2
1S1 1S2 2S1 2S2 P2
a n da dn N
X1 X2 Y1 Y2 H2
S1 S3 S2 P2
a1 a2 n N
X1 X2 X3 H2
S1 S2 P2
a n N
X1 X2 H2
275 11.5
150 178
135
331
278.5
292 178
5
SECONDARY TERMINALS
N°2-33504
(M10) : 15 N.m(M5) : 2 N.m
STANDARD : IEC - BS - ANSI - CSA
INSULATION LEVEL : up to 24/50/125kV
1 H.V. Bushing
+SCREW
C
TYPE : Y24G2
(±5%)RATED TIGHTENING TORQUE
INSTRUMENT TRANSFORMERS
BP 65559506 DOUAI CEDEX
FRANCESADTEMThis document is the property of SADTEM and may be changed without prior notice
Approx. Weight : 35 Kg
Créat. : 03.05.1999
Rév. : 23.11.2009
Primary terminalsSecondary terminals
INDOOR VOLTAGETRANSFORMER
+SCREW
A H1
M5-12
M10-20
4 HOLES Ø11
NAMEPLATE
Secondary terminals
RATED TIGHTENING TORQUE
(M10) : 15 N.m(M6) : 3 N.m
(±5%)
Primary terminals
Approx. Weight : 20 kg
316
260
178150
23
12
120
H1A
M10-20+ SCREW
162
250
173
M6-12
SECONDARY TERMINALS
+ SCREW
NAMEPLATE
30
5
148
This document is the property of SADTEM and may be changed without prior notice
STANDARD : IEC - BS - ANSI - CSA
INSULATION LEVEL : up to 24/50/125kV
FRANCERév: 20.10.2008
SADTEM E
1 H.V. Bushing
TRANSFORMER
N°2-25750INSTRUMENT TRANSFORMERS
Créat : 31.01.1989
INDOOR VOLTAGE
BP 65559506 DOUAI CEDEX
TYPE : Y24M
1S1 1S3 1S2 2S1 2S2 P2 UTEa1 a2 n da dn N IECX1 X2 X3 Y1 Y2 H2 ANSI-CSA
1S1 1S2 2S1 2S2 P2
1a 1n 2a 2n N
X1 X2 Y1 Y2 H2
1S1 1S2 2S1 2S2 P2
a n da dn N
X1 X2 Y1 Y2 H2
S1 S3 S2 P2
a1 a2 n N
X1 X2 X3 H2
S1 S2 P2
a n N
X1 X2 H2
1527
AH1
M10-20+SCREW
138,5
250 -20
Secondary terminals
RATED TIGHTENING TORQUE
(M6) : 3 N.m(M10) : 15 N.mPrimary terminal
(±5%)
20511 20
125
98
260
148
SECONDARY TERMINALS
Approx. Weight : 14 Kg
M6-12+ SCREW
NAMEPLATE
148
5
FRANCE
STANDARD : IEC - BS - ANSI - CSA
TRANSFORMER
TYPE : Y24P
INDOOR VOLTAGEINSULATION LEVEL : up to 24/50/125kV
1 H.V. bushing
Rév: 17.11.2008 N°2-32186INSTRUMENT TRANSFORMERS
This document is the property of SADTEM and may be changed without prior notice
SADTEMFBP 655
59506 DOUAI CEDEXCréat : 09.10.1997
1S1 1S2 2S1 2S2 P2 UTE1a 1n 2a 2n N IECX1 X2 Y1 Y2 H2 ANSI-CSA
S1 S3 S2 P2
a1 a2 n N
X1 X2 X3 h2
1S1 1S2 2S1 2S2 p2
a n da dn N
X1 X2 Y1 Y2 H2
S1 S2 P2
a n N
X1 X2 H2
65130
178
165
331
292
,5
178
278.5
5
275
150
11
52.5+SCREW
E
Secondary terminalsPrimary terminals
NAMEPLATE
2 H.V. Bushings
INSULATION LEVEL : up to 24/50/125kVTRANSFORMER
INDOOR VOLTAGE
(M5) : 2 N.m(M10) : 15 N.m
N°2-32553Créat. : 05.02.1998
Rév. : 07.05.2009
SADTEMThis document is the property of SADTEM and may be changed without prior notice
RATED TIGHTENING TORQUE
STANDARD : IEC - BS - ANSI - CSA
FRANCE
INSTRUMENT TRANSFORMERS
H2
(±5%)
Approx. Weight : 35 Kg
B
H1A
59506 DOUAI CEDEX
+SCREW
BP 655
TYPE : V24G
SECONDARY TERMINALS
M10-20
M5-12
4 HOLES Ø11
S1 S2 UTEa b IEC
X1 X2 ANSI-CSA
S1 S3 S2
a1 a2 b
X1 X2 X3
1S1 1S2 2S1 2S2
1a 1b 2a 2b
X1 X2 Y1 Y2