RXYQ5-54PAY1, PAYL, PTLR-410A Heat Pump 50Hz, 60Hz
Si34 - 803
Si34-803
3. Special Control....................................................................................1433.1 Startup Control .....................................................................................1433.2 Large Capacity Start Up Control (Heating)...........................................1443.3 Oil Return Operation ............................................................................1453.4 Defrosting Operation ............................................................................1473.5 Pump-down Residual Operation ..........................................................1483.6 Standby ................................................................................................1493.7 Stopping Operation ..............................................................................150
4. Protection Control ...............................................................................1524.1 High Pressure Protection Control.........................................................1524.2 Low Pressure Protection Control..........................................................1534.3 Discharge Pipe Protection Control .......................................................1544.4 Inverter Protection Control ...................................................................1554.5 STD Compressor Overload Protection.................................................1564.6 Injection Control (only for RXYQ5P(A))................................................156
5. Other Control.......................................................................................1575.1 Outdoor Unit Rotation...........................................................................1575.2 Emergency Operation ..........................................................................1585.3 Demand Operation ...............................................................................1645.4 Heating Operation Prohibition ..............................................................164
6. Outline of Control (Indoor Unit) ...........................................................1656.1 Drain Pump Control..............................................................................1656.2 Louver Control for Preventing Ceiling Dirt............................................1676.3 Thermostat Sensor in Remote Controller.............................................1686.4 Thermostat Control While in Normal Operation ...................................1706.5 Thermostat Control in Dry Operation ...................................................1706.6 Electronic Expansion Valve Control .....................................................1716.7 Hot Start Control (In Heating Operation Only)......................................1716.8 Freeze Prevention ................................................................................1726.9 Heater Control ......................................................................................1726.10 List of Swing Flap Operations ..............................................................1736.11 Control of Outdoor Air Processing Unit
(Unique Control for Outdoor Air Processing Unit) ................................174
Part 5 Test Operation ...............................................................1791. Test Operation ....................................................................................180
1.1 Installation Process ..............................................................................1801.2 Procedure and Outline .........................................................................1811.3 Operation When Power is Turned On ..................................................195
2. Outdoor Unit PC Board Layout ...........................................................1963. Field Setting ........................................................................................197
3.1 Field Setting from Remote Controller ...................................................1973.2 Field Setting from Outdoor Unit............................................................214
Part 6 Troubleshooting .............................................................2391. Symptom-based Troubleshooting .......................................................2422. Troubleshooting by Remote Controller ...............................................245
2.1 The INSPECTION / TEST Button.........................................................2452.2 Self-diagnosis by Wired Remote Controller .........................................2462.3 Self-diagnosis by Wireless Remote Controller .....................................247
ii Table of Contents
Si34-803
2.4 Operation of The Remote Controllers Inspection / Test Operation Button ..........................................................................250
2.5 Remote Controller Service Mode .........................................................2512.6 Remote Controller Self-Diagnosis Function .........................................253
3. Troubleshooting by Indication on the Remote Controller ....................2603.1 A0 Indoor Unit: Error of External Protection Device............................2603.2 A1 Indoor Unit: PC Board Defect ........................................................2613.3 A3 Indoor Unit: Malfunction of Drain Level Control System (S1L) ......2623.4 A6 Indoor Unit: Fan Motor (M1F) Lock, Overload...............................2643.5 A7 Indoor Unit: Malfunction of Swing Flap Motor (M1S).....................2683.6 Abnormal Power Supply Voltage..........................................................2703.7 A9 Indoor Unit: Malfunction of Moving Part of
Electronic Expansion Valve (Y1E)........................................................2713.8 AF Indoor Unit: Drain Level above Limit .............................................2733.9 AJ Indoor Unit: Malfunction of Capacity Determination Device ..........2743.10 C1 Indoor Unit: Failure of Transmission
(Between Indoor unit PC Board and Fan PC Board)............................2753.11 C4 Indoor Unit: Malfunction of Thermistor (R2T) for
Heat Exchanger....................................................................................2773.12 C5 Indoor Unit: Malfunction of Thermistor (R3T) for Gas Pipes .........2783.13 C6 Indoor Unit: Failure of Combination
(Between Indoor unit PC Board and Fan PC Board)............................2793.14 C9 Indoor Unit: Malfunction of Thermistor (R1T) for Suction Air.........2803.15 CC Indoor Unit: Malfunction of Humidity Sensor System ....................2813.16 CJ Indoor Unit: Malfunction of Thermostat Sensor
in Remote Controller ............................................................................2823.17 E1 Outdoor Unit: PC Board Defect .....................................................2833.18 E3 Outdoor Unit: Actuation of High Pressure Switch..........................2843.19 E4 Outdoor Unit: Actuation of Low Pressure Sensor..........................2863.20 E5 Outdoor Unit: Inverter Compressor Motor Lock.............................2883.21 E6 Outdoor Unit: STD Compressor Motor Overcurrent/Lock..............2903.22 E7 Outdoor Unit: Malfunction of Outdoor Unit Fan Motor ...................2913.23 E9 Outdoor Unit: Malfunction of Moving Part of
Electronic Expansion Valve (Y1E, Y2E)...............................................2943.24 F3 Outdoor Unit: Abnormal Discharge Pipe Temperature..................2963.25 F6 Outdoor Unit: Refrigerant Overcharged.........................................2973.26 H7 Outdoor Unit: Abnormal Outdoor Fan Motor Signal ......................2983.27 H9 Outdoor Unit: Malfunction of Thermistor (R1T) for Outdoor Air.....2993.28 J2 Outdoor Unit: Current Sensor Malfunction ....................................3003.29 J3 Outdoor Unit: Malfunction of Discharge Pipe Thermistor
(R3, R31~33T) .....................................................................................3013.30 J5 Outdoor Unit: Malfunction of Thermistor (R2T, R7T) for
Suction Pipe .........................................................................................3023.31 J6 Outdoor Unit: Malfunction of Thermistor (R4T) for
Outdoor Unit Heat Exchanger ..............................................................3033.32 J7 Outdoor Unit: Malfunction of Liquid Pipe Thermistor (R6T)...........3043.33 J9 Outdoor Unit: Malfunction of Subcooling Heat Exchanger
Gas Pipe Thermistor (R5T) ..................................................................3053.34 JA Outdoor Unit: Malfunction of High Pressure Sensor......................3063.35 JC Outdoor Unit: Malfunction of Low Pressure Sensor ......................3073.36 L4 Outdoor Unit: Malfunction of Inverter Radiating
Fin Temperature Rise...........................................................................308
Table of Contents iii
Si34-803
3.37 L5 Outdoor Unit: Inverter Compressor Abnormal ...............................3103.38 L8 Outdoor Unit: Inverter Current Abnormal.......................................3123.39 L9 Outdoor Unit: Inverter Start up Error .............................................3143.40 LC Outdoor Unit: Malfunction of Transmission Between
Inverter and Control PC Board .............................................................3163.41 P1 Outdoor Unit: Inverter Over-Ripple Protection...............................3193.42 P4 Outdoor Unit: Malfunction of Inverter Radiating
Fin Temperature Rise Sensor ..............................................................3203.43 PJ Outdoor Unit: Faulty Field Setting after Replacing Main PC Board or
Faulty Combination of PC Board..........................................................3223.44 U0 Outdoor Unit: Low Pressure Drop Due to Refrigerant Shortage or
Electronic Expansion Valve Failure......................................................3233.45 U1 Reverse Phase, Open Phase ........................................................3243.46 U2 Outdoor Unit: Power Supply Insufficient or
Instantaneous Failure...........................................................................3253.47 U3 Outdoor Unit: Check Operation not Executed ...............................3283.48 U4 Malfunction of Transmission Between Indoor Units ......................3293.49 U5 Indoor Unit: Malfunction of Transmission Between
Remote Controller and Indoor Unit.......................................................3313.50 U7 Indoor Unit: Malfunction of Transmission Between
Outdoor Units .......................................................................................3323.51 U8 Indoor Unit: Malfunction of Transmission Between
Main and Sub Remote Controllers .......................................................3343.52 U9 Indoor Unit: Malfunction of Transmission Between
Indoor and Outdoor Units in the Same System....................................3353.53 UA Improper Combination of Indoor and Outdoor Units,
Indoor Units and Remote Controller.....................................................3363.54 UC Address Duplication of Centralized Controller...............................3383.55 UE Malfunction of Transmission Between
Centralized Controller and Indoor Unit .................................................3393.56 UF System is not Set yet.....................................................................3423.57 UH Malfunction of System, Refrigerant System Address Undefined...343
4. Troubleshooting (OP: Central Remote Controller) ..............................3454.1 M1 PC Board Defect ...........................................................................3454.2 M8 Malfunction of Transmission Between Optional Controllers for
Centralized Control...............................................................................3464.3 MA Improper Combination of Optional Controllers for
Centralized Control...............................................................................3484.4 MC Address Duplication, Improper Setting .........................................350
5. Troubleshooting (OP: Unified ON/OFF Controller) .............................3535.1 Operation Lamp Blinks .........................................................................3535.2 Display Under Centralized Control Blinks (Repeats Single Blink) .....3555.3 Display Under Centralized Control Blinks (Repeats Double Blink) ....358
Part 7 Appendix.........................................................................3631. Piping Diagrams..................................................................................364
1.1 Outdoor Unit .........................................................................................3641.2 Indoor Unit............................................................................................371
2. Wiring Diagrams for Reference...........................................................3752.1 Outdoor Unit .........................................................................................3752.2 Field Wiring ..........................................................................................385
iv Table of Contents
Si34-803
2.3 Indoor Unit............................................................................................391
3. List of Electrical and Functional Parts .................................................4063.1 Outdoor Unit .........................................................................................4063.2 Outdoor Unit - 60Hz .............................................................................4093.3 Indoor Side ...........................................................................................412
4. Option List ...........................................................................................4194.1 Option List of Controllers......................................................................4194.2 Option Lists (Outdoor Unit)...................................................................421
5. Piping Installation Point.......................................................................4235.1 Piping Installation Point ........................................................................4235.2 The Example of a Wrong Pattern .........................................................424
6. Example of connection (R-410A Type) ...............................................4257. Thermistor Resistance / Temperature Characteristics........................4278. Pressure Sensor .................................................................................4299. Method of Checking The Inverters Power Transistors and
Diode Modules ....................................................................................4309.1 Method of Checking The Inverters Power Transistors and
Diode Modules .....................................................................................430
Part 8 Precautions for New Refrigerant (R-410A) ....................4331. Precautions for New Refrigerant (R-410A) .........................................434
1.1 Outline ..................................................................................................4341.2 Refrigerant Cylinders............................................................................4361.3 Service Tools........................................................................................437
Index ............................................................................................. i
Drawings & Flow Charts ............................................................... iii
Table of Contents v
Introduction Si34-803
1. Introduction1.1 Safety Cautions
Cautions and Warnings
Be sure to read the following safety cautions before conducting repair work.The caution items are classified into Warning and Caution. The Warning items are especially important since they can lead to death or serious injury if they are not followed closely. The Caution items can also lead to serious accidents under some conditions if they are not followed. Therefore, be sure to observe all the safety caution items described below.About the pictograms
This symbol indicates an item for which caution must be exercised. The pictogram shows the item to which attention must be paid.
This symbol indicates a prohibited action. The prohibited item or action is shown inside or near the symbol.
This symbol indicates an action that must be taken, or an instruction. The instruction is shown inside or near the symbol.
After the repair work is complete, be sure to conduct a test operation to ensure that the equipment operates normally, and explain the cautions for operating the product to the customer
1.1.1 Caution in RepairWarning
Be sure to disconnect the power cable plug from the plug socket before disassembling the equipment for a repair.Working on the equipment that is connected to a power supply can cause an electrical shook.If it is necessary to supply power to the equipment to conduct the repair or inspecting the circuits, do not touch any electrically charged sections of the equipment.
If the refrigerant gas discharges during the repair work, do not touch the discharging refrigerant gas.The refrigerant gas can cause frostbite.
When disconnecting the suction or discharge pipe of the compressor at the welded section, release the refrigerant gas completely at a well-ventilated place first.If there is a gas remaining inside the compressor, the refrigerant gas or refrigerating machine oil discharges when the pipe is disconnected, and it can cause injury.
If the refrigerant gas leaks during the repair work, ventilate the area. The refrigerant gas can generate toxic gases when it contacts flames.
The step-up capacitor supplies high-voltage electricity to the electrical components of the outdoor unit.Be sure to discharge the capacitor completely before conducting repair work.A charged capacitor can cause an electrical shock.
Do not start or stop the air conditioner operation by plugging or unplugging the power cable plug.Plugging or unplugging the power cable plug to operate the equipment can cause an electrical shock or fire.
vi
Si34-803 Introduction
1.1.2 Cautions Regarding Products after Repair
Caution
Do not repair the electrical components with wet hands.Working on the equipment with wet hands can cause an electrical shock.
Do not clean the air conditioner by splashing water.Washing the unit with water can cause an electrical shock.
Be sure to provide the grounding when repairing the equipment in a humid or wet place, to avoid electrical shocks.
Be sure to turn off the power switch and unplug the power cable when cleaning the equipment.The internal fan rotates at a high speed, and cause injury.
Do not tilt the unit when removing it.The water inside the unit can spill and wet the furniture and floor.
Be sure to check that the refrigerating cycle section has cooled down sufficiently before conducting repair work.Working on the unit when the refrigerating cycle section is hot can cause burns.
Use the welder in a well-ventilated place.Using the welder in an enclosed room can cause oxygen deficiency.
Warning
Be sure to use parts listed in the service parts list of the applicable model and appropriate tools to conduct repair work. Never attempt to modify the equipment. The use of inappropriate parts or tools can cause an electrical shock, excessive heat generation or fire.
When relocating the equipment, make sure that the new installation site has sufficient strength to withstand the weight of the equipment.If the installation site does not have sufficient strength and if the installation work is not conducted securely, the equipment can fall and cause injury.
Be sure to install the product correctly by using the provided standard installation frame.Incorrect use of the installation frame and improper installation can cause the equipment to fall, resulting in injury.
For integral units only
Be sure to install the product securely in the installation frame mounted on a window frame.If the unit is not securely mounted, it can fall and cause injury.
For integral units only
Be sure to use an exclusive power circuit for the equipment, and follow the technical standards related to the electrical equipment, the internal wiring regulations and the instruction manual for installation when conducting electrical work.Insufficient power circuit capacity and improper electrical work can cause an electrical shock or fire.
vii
Introduction Si34-803
1.1.3 Inspection after Repair
Be sure to use the specified cable to connect between the indoor and outdoor units. Make the connections securely and route the cable properly so that there is no force pulling the cable at the connection terminals.Improper connections can cause excessive heat generation or fire.
When connecting the cable between the indoor and outdoor units, make sure that the terminal cover does not lift off or dismount because of the cable.If the cover is not mounted properly, the terminal connection section can cause an electrical shock, excessive heat generation or fire.
Do not damage or modify the power cable.Damaged or modified power cable can cause an electrical shock or fire.Placing heavy items on the power cable, and heating or pulling the power cable can damage the cable.
Do not mix air or gas other than the specified refrigerant (R-410A) in the refrigerant system.If air enters the refrigerating system, an excessively high pressure results, causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leak and repair it before charging the refrigerant. After charging refrigerant, make sure that there is no refrigerant leak. If the leak cannot be located and the repair work must be stopped, be sure to perform pump-down and close the service valve, to prevent the refrigerant gas from leaking into the room. The refrigerant gas itself is harmless, but it can generate toxic gases when it contacts flames, such as fan and other heaters, stoves and ranges.
When replacing the coin battery in the remote controller, be sure to disposed of the old battery to prevent children from swallowing it.If a child swallows the coin battery, see a doctor immediately.
Warning
Caution
Installation of a leakage breaker is necessary in some cases depending on the conditions of the installation site, to prevent electrical shocks.
Do not install the equipment in a place where there is a possibility of combustible gas leaks.If a combustible gas leaks and remains around the unit, it can cause a fire.
Be sure to install the packing and seal on the installation frame properly.If the packing and seal are not installed properly, water can enter the room and wet the furniture and floor.
For integral units only
Warning
Check to make sure that the power cable plug is not dirty or loose, then insert the plug into a power outlet all the way.If the plug has dust or loose connection, it can cause an electrical shock or fire.
If the power cable and lead wires have scratches or deteriorated, be sure to replace them.Damaged cable and wires can cause an electrical shock, excessive heat generation or fire.
Do not use a joined power cable or extension cable, or share the same power outlet with other electrical appliances, since it can cause an electrical shock, excessive heat generation or fire.
viii
Si34-803 Introduction
1.1.4 Using IconsIcons are used to attract the attention of the reader to specific information. The meaning of each icon is described in the table below:
1.1.5 Using Icons List
Caution
Check to see if the parts and wires are mounted and connected properly, and if the connections at the soldered or crimped terminals are secure.Improper installation and connections can cause excessive heat generation, fire or an electrical shock.
If the installation platform or frame has corroded, replace it.Corroded installation platform or frame can cause the unit to fall, resulting in injury.
Check the grounding, and repair it if the equipment is not properly grounded.Improper grounding can cause an electrical shock.
Be sure to measure the insulation resistance after the repair, and make sure that the resistance is 1 Mohm or higher.Faulty insulation can cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair.Faulty drainage can cause the water to enter the room and wet the furniture and floor.
Icon Type of Information
Description
Note:
Note A note provides information that is not indispensable, but may nevertheless be valuable to the reader, such as tips and tricks.
Caution
Caution A caution is used when there is danger that the reader, through incorrect manipulation, may damage equipment, loose data, get an unexpected result or has to restart (part of) a procedure.
Warning
Warning A warning is used when there is danger of personal injury.
Reference A reference guides the reader to other places in this binder or in this manual, where he/she will find additional information on a specific topic.
ix
Introduction Si34-803
1.2 PREFACEThank you for your continued patronage of Daikin products.
This is the new service manual for Daikin's Year 2008 VRVIII series Heat Pump System.Daikin offers a wide range of models to respond to building and office air conditioning needs. We are confident that customers will be able to find the models that best suit their needs.
This service manual contains information regarding the servicing of VRVIII series R-410A Heat Pump System.
June, 2008
After Sales Service Division
x
Si34-803
General Information 1
Part 1General Information
1. Model Names of Indoor/Outdoor Units....................................................22. External Appearance...............................................................................3
2.1 Indoor Units ..............................................................................................32.2 Outdoor Units ...........................................................................................4
3. Combination of Outdoor Units.................................................................64. Model Selection.......................................................................................8
Model Names of Indoor/Outdoor Units Si34-803
1. Model Names of Indoor/Outdoor UnitsIndoor Units
Note:FXDQ has following 2 Series, as show below. FXDQ-PB, NBVET: without Drain Pump FXDQ-PB, NBVE: with Drain Pump BEV unit is required for each indoor unit. MA: RoHS Directive models; Specifications, Dimensions and other functions are not changed compared with
M type.
Outdoor UnitsNormal Series
High COP Series (Energy Saving Series)
Type Model Name Power SupplyCeiling Mounted Cassette Type(Round Flow)
FXFQ 25P 32P 40P 50P 63P 80P 100P 125P
VECeiling Mounted Cassette Type (Double Flow)
FXCQ 20M 25M 32M 40M 50M 63M 80M 125M
Ceiling Mounted Cassette Corner Type FXKQ 25MA 32MA 40MA 63MA
VE
Slim Ceiling Mounted Duct Type
FXDQ-PBVE 20PB 25PB 32PB
FXDQ-PBVET 20PB 25PB 32PB
FXDQ-NBVE 40NB 50NB 63NB
FXDQ-NBVET 40NB 50NB 63NB
Ceiling Mounted Built-In Type FXSQ 20M 25M 32M 40M 50M 63M 80M 100M 125M
Ceiling Mounted Duct Type (Middle and high static pressure)
FXMQ 40P 50P 63P 80P 100P 125P
Ceiling Mounted Duct Type FXMQ 200MA 250MA
Ceiling Suspended Type FXHQ 32MA 63MA 100MA
Wall Mounted Type FXAQ 20MA 25MA 32MA 40MA 50MA 63MA
Floor Standing Type FXLQ 20MA 25MA 32MA 40MA 50MA 63MA
Concealed Floor Standing Type FXNQ 20MA 25MA 32MA 40MA 50MA 63MA
Outdoor Air Processing Unit
FXMQ-MF 125MF 200MF 250MF
V1Ceiling Suspended Cassette Type FXUQ 71MA 100MA 125MA
Connection Unit BEVQ-MA 71MA 100MA 125MA VE
Series Model Name Power Supply
Heat Pump RXYQ
5P(A) 8P(A) 10P(A) 12P(A) 14P(A) 16P(A) 18P(A) 20P(A) 22P(A) Y1(E)YL(E)TL(E)
24P(A) 26P(A) 28P(A) 30P(A) 32P(A) 34P(A) 36P(A) 38P(A) 40P(A)
42P(A) 44P(A) 46P(A) 48P(A) 50P(A) 52P(A) 54P(A)
Series Model Name Power Supply
Heat Pump RXYQ16P(A)H 18P(A)H 24P(A)H 26P(A)H 28P(A)H 30P(A)H 32P(A)H 34P(A)H 36P(A)H Y1(E)
YL(E)TL(E)38P(A)H 40P(A)H 42P(A)H 44P(A)H 46P(A)H 48P(A)H 50P(A)H
Power Supply VE : 1 phase 220~240V, 50HzV1 : 1 phase 220~240V, 50HzY1 : 3 phase 380~415V, 50HzYL : 3 phase 380V, 60HzTL : 3 phase 220V, 60Hz
E:The unit with anti corrosion treatment
2 General Information
Si34-803 External Appearance
2. External Appearance2.1 Indoor UnitsCeiling Mounted Cassette Type (Round Flow)
FXFQ25PFXFQ32PFXFQ40PFXFQ50PFXFQ63PFXFQ80PFXFQ100PFXFQ125P
Ceiling Mounted Duct Type
FXMQ200MAFXMQ250MA
Ceiling Mounted Cassette Type (Double Flow)
FXCQ20MFXCQ25MFXCQ32MFXCQ40MFXCQ50MFXCQ63MFXCQ80MFXCQ125M
Ceiling Suspended Type
FXHQ32MAFXHQ63MAFXHQ100MA
Ceiling Mounted Cassette Corner Type
FXKQ25MAFXKQ32MAFXKQ40MAFXKQ63MA
Wall Mounted Type
FXAQ20MAFXAQ25MAFXAQ32MAFXAQ40MAFXAQ50MAFXAQ63MA
Slim Ceiling Mounted Duct Type
FXDQ20PB FXDQ40NBFXDQ25PB FXDQ50NBFXDQ32PB FXDQ63NB
with Drain Pump (VE)without Drain Pump (VET)
Floor Standing Type
FXLQ20MAFXLQ25MAFXLQ32MAFXLQ40MAFXLQ50MAFXLQ63MA
Ceiling Mounted Built-In Type
FXSQ20MFXSQ25MFXSQ32MFXSQ40MFXSQ50MFXSQ63MFXSQ80MFXSQ100MFXSQ125M
Concealed Floor Standing Type
FXNQ20MAFXNQ25MAFXNQ32MAFXNQ40MAFXNQ50MAFXNQ63MA
Ceiling Mounted Duct Type (Middle and high static pressure)
FXMQ40PFXMQ50PFXMQ63PFXMQ80PFXMQ100PFXMQ125P
Ceiling Suspended Cassette Type (Connection Unit Series)
FXUQ71MA +FXUQ100MA +FXUQ125MA +
Connection Unit
BEVQ71MABEVQ100MABEVQ125MA
General Information 3
External Appearance Si34-803
2.2 Outdoor UnitsNormal Series (Space Saving Series)
RXYQ5P(A) RXYQ8P(A), 10P(A)
RXYQ20P(A), 22P(A), 24P(A), 26P(A), 28P(A) RXYQ30P(A), 32P(A), 34P(A), 36P(A)
RXYQ38P(A), 40P(A), 42P(A), 44P(A), 46P(A) RXYQ48P(A), 50P(A), 52P(A), 54P(A)
RXYQ12P(A), 14P(A), 16P(A), 18P(A)
5HP 8, 10HP 12, 14, 16, 18HP
20, 22, 24, 26, 28HP
38, 40, 42, 44, 46HP
30, 32, 34, 36HP
48, 50, 52, 54HP
4 General Information
Si34-803 External Appearance
High COP Series (Energy Saving Series)
RXYQ16P(A)H, 18P(A)H RXYQ24P(A)H, 26P(A)H
RXYQ28P(A)H, 30P(A)H
16, 18HP 24, 26HP
28, 30HP
RXYQ32P(A)H, 34P(A)H
RXYQ36P(A)H, 38P(A)H, 40P(A)H, 42P(A)H, 44P(A)H, 46P(A)H, 48P(A)H, 50P(A)H
32, 34HP
36, 38, 40, 42, 44, 46, 48, 50HP
General Information 5
Combination of Outdoor Units Si34-803
3. Combination of Outdoor UnitsNormal Series
Note: For multiple connection of 18HP system or more, an optional Daikin Outdoor Unit Multi Connection Piping Kit is required.
System Capacity
Number of units
Module Outdoor Unit Multi Connection Piping Kit (Option)5 8 10 12 14 16 18
5HP 1
8HP 1 10HP 1 12HP 1 14HP 1 16HP 1 18HP 1 20HP 2
Heat Pump: BHFP22P100
22HP 2 24HP 2 26HP 2 28HP 2 30HP 2 32HP 2 34HP 2 36HP 2 38HP 3
Heat Pump: BHFP22P151
40HP 3 42HP 3 44HP 3 46HP 3 48HP 3 50HP 3 52HP 3 54HP 3
6 General Information
Si34-803 Combination of Outdoor Units
High COP Series (Energy Saving Series)
Note: For multiple connection of 16HP system or more, an optional Daikin Outdoor Unit Multi Connection Piping Kit is required.
System Capacity
Number of units
Module Outdoor Unit Multi Connection Piping Kit (Option)8 10 12 14 16 18
16HP 2
Heat Pump: BHFP22P100
18HP 2 24HP 3 26HP 3 28HP 3 30HP 3 32HP 3 34HP 3 36HP 3 38HP 3
Heat Pump: BHFP22P151
40HP 3 42HP 3 44HP 3 46HP 3 48HP 3 50HP 3
General Information 7
Model Selection Si34-803
4. Model Selection VRV III Heat Pump Series
Outdoor UnitsNormal Type (Space Saving Type)
High-COP Type (Energy Saving Type)
Maximum number ofconnectable indoor units*
Total capacity index of connectable indoor units*HP Combination
RXYQ5P(A)
RXYQ8P(A)
RXYQ10P(A)
RXYQ12P(A)
RXYQ14P(A)
RXYQ16P(A)
RXYQ18P(A)
RXYQ8P(A) + RXYQ12P(A)
RXYQ10P(A) + RXYQ12P(A)
RXYQ8P(A) + RXYQ16P(A)
RXYQ8P(A) + RXYQ18P(A)
RXYQ10P(A) + RXYQ18P(A)
RXYQ12P(A) + RXYQ18P(A)
RXYQ16P(A) x 2
RXYQ16P(A) + RXYQ18P(A)
RXYQ18P(A) x 2
RXYQ8P(A) + RXYQ12P(A) + RXYQ18P(A)
RXYQ8P(A) + RXYQ16P(A) x 2
RXYQ8P(A) + RXYQ16P(A) + RXYQ18P(A)
RXYQ8P(A) + RXYQ18P(A) x 2
RXYQ10P(A) + RXYQ18P(A) x 2
RXYQ12P(A) + RXYQ18P(A) x 2
62.5 to 162.5 (250)
100 to 260 (400)
125 to 325 (500)
150 to 390 (600)
175 to 455 (700)
200 to 520 (800)
225 to 585 (900)
250 to 650 (800)
275 to 715 (880)
300 to 780 (960)
325 to 845 (1,040)
350 to 910 (1,120)
375 to 975 (1,200)
400 to 1,040 (1,280)
425 to 1,105 (1,360)
450 to 1,170 (1,440)
475 to 1,235 (1,235)
500 to 1,300 (1,300)
525 to 1,365 (1,365)
550 to 1,430 (1,430)
575 to 1,495 (1,495)
600 to 1,560 (1,560)
Model name
RXYQ5P(A)
RXYQ8P(A)
RXYQ10P(A)
RXYQ12P(A)
RXYQ14P(A)
RXYQ16P(A)
RXYQ18P(A)
RXYQ20P(A)
RXYQ22P(A)
RXYQ24P(A)
RXYQ26P(A)
RXYQ28P(A)
RXYQ30P(A)
RXYQ32P(A)
RXYQ34P(A)
RXYQ36P(A)
RXYQ38P(A)
RXYQ40P(A)
RXYQ42P(A)
RXYQ44P(A)
RXYQ46P(A)
RXYQ48P(A)
5 HP
8 HP
10 HP
12 HP
14 HP
16 HP
18 HP
20 HP
22 HP
24 HP
26 HP
28 HP
30 HP
32 HP
34 HP
36 HP
38 HP
40 HP
42 HP
44 HP
46 HP
48 HP
8 (12)
13 (20)
16 (25)
19 (30)
23 (35)
26 (40)
29 (45)
32 (40)
35 (44)
39 (48)
42 (52)
45 (56)
48 (60)
52 (64)
55 (64)
58 (64)
61 (61)
64 (64)
Outdoor unit multi connection piping kit
BHFP22P100
BHFP22P151
RXYQ14P(A) + RXYQ18P(A) x 2
RXYQ16P(A) + RXYQ18P(A) x 2
RXYQ18P(A) x 3
625 to 1,625 (1,625)
650 to 1,690 (1,690)
675 to 1,755 (1,755)
RXYQ50P(A)
RXYQ52P(A)
RXYQ54P(A)
50 HP
52 HP
54 HP
Note: For multiple connection of 20 HP systems and above, the above Daikin optional kit (separately sold) is required. *Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for single outdoor units, 160%
for double outdoor units, and 130% for triple outdoor units.
Maximum number ofconnectable indoor units*
Total capacity index of connectable indoor units*HP Combination
RXYQ8P(A) x 2 200 to 520 (640)
Model name
RXYQ16P(A)H16 HP 26 (32)
Outdoor unit multi connection piping kit
BHFP22P100RXYQ8P(A) + RXYQ10P(A) 225 to 585 (720)RXYQ18P(A)H18 HP 29 (36)
RXYQ8P(A) x 3 300 to 780 (780)RXYQ24P(A)H24 HP 39 (39)
RXYQ8P(A) x 2 + RXYQ10P(A) 325 to 845 (845)RXYQ26P(A)H26 HP 42 (42)
RXYQ8P(A) x 2 + RXYQ12P(A) 350 to 910 (910)RXYQ28P(A)H28 HP 45 (45)
RXYQ8P(A) + RXYQ10P(A) + RXYQ12P(A) 375 to 975 (975)RXYQ30P(A)H30 HP 48 (48)
52 (52)
55 (55)
58 (58)
RXYQ8P(A) + RXYQ12P(A) x 2 400 to 1,040 (1,040)RXYQ32P(A)H32 HP
RXYQ10P(A) + RXYQ12P(A) x 2 425 to 1,105 (1,105)RXYQ34P(A)H34 HP
BHFP22P151RXYQ12P(A) x 3 450 to 1,170 (1,170)RXYQ36P(A)H36 HP
RXYQ12P(A) x 2 + RXYQ14P(A) 475 to 1,235 (1,235)RXYQ38P(A)H38 HP 61 (61)
RXYQ12P(A) x 2 + RXYQ16P(A) 500 to 1,300 (1,300)RXYQ40P(A)H40 HP
64 (64)
RXYQ12P(A) x 2 + RXYQ18P(A) 525 to 1,365 (1,365)RXYQ42P(A)H42 HP
RXYQ12P(A) + RXYQ16P(A) x 2 550 to 1,430 (1,430)RXYQ44P(A)H44 HP
RXYQ12P(A) + RXYQ16P(A) + RXYQ18P(A) 575 to 1,495 (1,495)RXYQ46P(A)H46 HP
RXYQ16P(A) x 3 600 to 1,560 (1,560)RXYQ48P(A)H48 HP
RXYQ16P(A) x 2 + RXYQ18P(A) 625 to 1,625 (1,625)RXYQ50P(A)H50 HP
Note: For multiple connection of 16 HP systems and above, the above Daikin optional kit (separately sold) is required.*Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for single outdoor units, 160% for double outdoor units, and 130% for triple outdoor units.
8 General Information
Si34-803 Model Selection
Connectable Indoor Unit
Note: FXDQ has following 2 Series, as show below.FXDQ-PB, NBVET: without Drain PumpFXDQ-PB, NBVE : with Drain Pump BEV unit is required for each indoor unit.
Indoor unit capacity
Use the above tables to determine the capacities of indoor units to be connected. Make sure the total capacity of indoor units connected to each outdoor unit is within the specified value (kW).
The total capacity of connected indoor units must be within a range of 50 to 130% of the rated capacity of the outdoor unit.In some models, it is not possible to connect the maximum number of connectable indoor units. Select models so the total capacity of connected indoor units conforms to the specification.
Type Model Name Power Supply
Ceiling Mounted Cassette Type(Multi Flow)
FXFQ 25P 32P 40P 50P 63P 80P 100P 125P
VE
Ceiling Mounted Cassette Type (Double Flow)
FXCQ 20M 25M 32M 40M 50M 63M 80M 125M
Ceiling Mounted Cassette Corner Type FXKQ 25MA 32MA 40MA 63MA
Slim Ceiling Mounted Duct Type
FXDQ-PBVE 20PB 25PB 32PB
FXDQ-PBVET 20PB 25PB 32PB
FXDQ-NBVE 40NB 50NB 63NB
FXDQ-NBVET 40NB 50NB 63NB
Ceiling Mounted Built-In Type FXSQ 20M 25M 32M 40M 50M 63M 80M 100M 125M
Ceiling Mounted Duct Type (Middle and high static pressure)
FXMQ 40P 50P 63P 80P 100P 125P
Ceiling Mounted Duct Type FXMQ 200MA 250MA
Ceiling Suspended Type FXHQ 32MA 63MA 100MA
Wall Mounted Type FXAQ 20MA 25MA 32MA 40MA 50MA 63MA
Floor Standing Type FXLQ 20MA 25MA 32MA 40MA 50MA 63MA
Concealed Floor Standing Type FXNQ 20MA 25MA 32MA 40MA 50MA 63MA
Outdoor Air Processing Unit
FXMQ-MF 125MF 200MF 250MF
V1Ceiling Suspended Cassette Type FXUQ 71MA 100MA 125MA
Connection Unit BEVQ-MA 71MA 100MA 125MA VE
New refrigerant model code P20 type
P25 type
P32 type
P40 type
P50 type
P63 type
P80 type
P100 type
P125 type
P200 type
P250 type
Selecting model capacity 2.2kW
2.8kW
3.5kW
4.5kW
5.6kW
7.0kW
9.0kW
11.2kW
14.0kW
22.4kW
28.0kW
Equivalent output 0.8HP 1HP 1.25HP 1.6HP 2.0HP 2.5HP 3.2HP 4HP 5HP 8HP 10HP
General Information 9
Model Selection Si34-803
Differences from Conventional Models
ItemDifferences
Object New model (P(A) Model) Conventional model (P Model)
Compressor Connection of equalizer oil pipeNONE(No particular changes in terms of service)
NONE(No particular changes in terms of service)
Workability
Equalizer oil pipe for multi-outdoor-unit system NONE NONE
Procedure for calculating refrigerant refilling quantity
Refilling quantity due to piping length + Adjustment quantity according to models of outdoor units
Refilling quantity due to piping length + Adjustment quantity according to models of outdoor units
Optional accessories Branch pipe for outdoor unit connectionY branchType: BHFP22P100/151
Y branchType: BHFP22P100/151
Refrigerant chargeChange of refrigerant amountRefrigerant amount reduced to less than 12 kg.
Less than 12 kg
Some of heat pump units require refrigerant amount of not less than 12 kg.(Heat recovery units have been designed for refrigerant amount of less than 12 kg.)
10 General Information
Si34-803
Specifications 11
Part 2Specifications
1. Specifications ........................................................................................121.1 Outdoor Units .........................................................................................121.2 Indoor Units ............................................................................................54
Specifications Si34-803
1. Specifications1.1 Outdoor UnitsHeat Pump 50Hz Standard Series
Notes:1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Model Name RXYQ5PAY1(E) RXYQ8PAY1(E)
1 Cooling Capacity (19.5CWB)
kcal / h 12,100 19,400
Btu / h 48,100 76,800
kW 14.1 22.5
2 Cooling Capacity (19.0CWB) kW 14.0 22.4
3 Heating Capacity
kcal / h 13,800 21,500
Btu / h 54,600 85,300
kW 16.0 25.0
Casing ColorWithout(E) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
With(E) Light Camel (2.5Y6.5/1.5) Light Camel (2.5Y6.5/1.5)
Dimensions: (HWD) mm 1680635765 1680930765
Heat Exchanger Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Piston Displacement m/h 13.34 16.90
Number of Revolutions r.p.m 6300 7980
Motor OutputNumber of Units kW 2.81 4.51
Starting Method Soft Start Soft Start
Fan
Type Propeller Fan Propeller Fan
Motor Output kW 0.351 0.751
Air Flow Rate m/min 95 180
Drive Direct Drive Direct Drive
Connecting Pipes
Liquid Pipe mm 9.5 (Brazing Connection) 9.5 (Brazing Connection)Gas Pipe mm 15.9 (Brazing Connection) 19.1 (Brazing Connection)
Product Mass (Machine weight) kg 160 205
Safety Devices High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload ProtectorHigh Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
Defrost Method Deicer Deicer
Capacity Control % 28~100 20~100
Refrigerant
Refrigerant Name R-410A R-410A
Charge kg 6.2 7.2
Control Electronic Expansion Valve Electronic Expansion Valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Standard Accessories Installation Manual, Operation Manual, Clamps Installation Manual, Operation Manual, Connection Pipes, Clamps
Drawing No. C: 4D061005 C: 4D061006
The Reference NumberC~: Partly corrected drawings.J~: Original drawing is JapaneseV~: Printing Convenience
Conversion Formulae
kcal/h=kW860Btu/h=kW3412
cfm=m/min35.3
12 Specifications
Si34-803 Specifications
Notes:1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Model Name RXYQ10PAY1(E) RXYQ12PAY1(E)
1 Cooling Capacity (19.5CWB)
kcal / h 24,300 29,000
Btu / h 96,200 115,000
kW 28.2 33.7
2 Cooling Capacity (19.0CWB) kW 28.0 33.5
3 Heating Capacity
kcal / h 27,100 32,300
Btu / h 107,000 128,000
kW 31.5 37.5
Casing ColorWithout(E) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
With(E) Light Camel (2.5Y6.5/1.5) Light Camel (2.5Y6.5/1.5)
Dimensions: (HWD) mm 1680930765 16801240765
Heat Exchanger Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Piston Displacement m/h 13.34+10.53 13.34+10.53
Number of Revolutions r.p.m 6300, 2900 6300, 2900
Motor OutputNumber of Units kW (1.4+4.5)1 (2.5+4.5)1
Starting Method Soft Start Soft Start
Fan
Type Propeller Fan Propeller Fan
Motor Output kW 0.751 0.352
Air Flow Rate m/min 185 233
Drive Direct Drive Direct Drive
Connecting Pipes
Liquid Pipe mm 9.5 (Brazing Connection) 12.7 (Brazing Connection)Gas Pipe mm 22.2 (Brazing Connection) 28.6 (Brazing Connection)
Product Mass (Machine Weight) kg 249 285
Safety Devices High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload ProtectorHigh Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
Defrost Method Deicer Deicer
Capacity Control % 14~100 14~100
Refrigerant
Refrigerant Name R-410A R-410A
Charge kg 7.9 9.5
Control Electronic Expansion Valve Electronic Expansion Valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Standard Accessories Installation Manual, Operation Manual, Connection Pipes, ClampsInstallation Manual, Operation Manual, Connection Pipes, Clamps
Drawing No. C: 4D061007 C: 4D061008
Conversion Formulae
kcal/h=kW860Btu/h=kW3412
cfm=m/min35.3
Specifications 13
Specifications Si34-803
Notes:1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Model Name RXYQ14PAY1(E) RXYQ16PAY1(E)
1 Cooling Capacity (19.5CWB)
kcal / h 34,600 39,000
Btu / h 137,000 155,000
kW 40.2 45.3
2 Cooling Capacity (19.0CWB) kW 40.0 45.0
3 Heating Capacity
kcal / h 38,700 43,000
Btu / h 154,000 171,000
kW 45.0 50.0
Casing ColorWithout(E) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
With(E) Light Camel (2.5Y6.5/1.5) Light Camel (2.5Y6.5/1.5)
Dimensions: (HWD) mm 16801240765 16801240765
Heat Exchanger Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Piston Displacement m/h 13.34+10.53+10.53 13.34+10.53+10.53
Number of Revolutions r.p.m 6300, 29002 6300, 29002
Motor OutputNumber of Units kW (1.6+4.5+4.5)1 (2.7+4.5+4.5)1
Starting Method Soft Start Soft Start
Fan
Type Propeller Fan Propeller Fan
Motor Output kW 0.352 0.352
Air Flow Rate m/min 233 233
Drive Direct Drive Direct Drive
Connecting Pipes
Liquid Pipe mm 12.7 (Brazing Connection) 12.7 (Brazing Connection)Gas Pipe mm 28.6 (Brazing Connection) 28.6 (Brazing Connection)
Product Mass (Machine Weight) kg 329 329
Safety Devices High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload ProtectorHigh Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
Defrost Method Deicer Deicer
Capacity Control % 10~100 10~100
Refrigerant
Refrigerant Name R-410A R-410A
Charge kg 11.3 11.5
Control Electronic Expansion Valve Electronic Expansion Valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Standard Accessories Installation Manual, Operation Manual, Connection Pipes, ClampsInstallation Manual, Operation Manual, Connection Pipes, Clamps
Drawing No. C: 4D061009 C: 4D061010
Conversion Formulae
kcal/h=kW860Btu/h=kW3412
cfm=m/min35.3
14 Specifications
Si34-803 Specifications
Notes:1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Model Name (Combination Unit) RXYQ18PAY1(E) RXYQ20PAY1(E)
Model Name (Independent Unit) RXYQ8PAY1(E)+RXYQ12PAY1(E)
1 Cooling Capacity (19.5CWB)
kcal / h 42,000 48,300
Btu / h 168,000 192,000
kW 49.3 56.2
2 Cooling Capacity (19.0CWB) kW 49.0 55.9
3 Heating Capacity
kcal / h 48,600 53,800
Btu / h 193,000 213,000
kW 56.5 62.5
Casing ColorWithout(E) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
With(E) Light Camel (2.5Y6.5/1.5) Light Camel (2.5Y6.5/1.5)
Dimensions: (HWD) mm 16801240765 (1680930765)+(16801240765)
Heat Exchanger Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Piston Displacement m/h 16.90+10.53+10.53 (16.90)+(13.34+10.53)
Number of Revolutions r.p.m 7980, 2900, 2900 (7980)+(6300, 2900)
Motor OutputNumber of Units kW (4.3+4.5+4.5)1 (4.51)+((2.5+4.5)1)
Starting Method Soft Start Soft Start
Fan
Type Propeller Fan Propeller Fan
Motor Output kW 0.752 (0.751)+(0.352)
Air Flow Rate m/min 239 180+233
Drive Direct Drive Direct Drive
Connecting Pipes
Liquid Pipe mm 15.9 (Brazing Connection) 15.9 (Brazing Connection)Gas Pipe mm 28.6 (Brazing Connection) 28.6 (Brazing Connection)
Product Mass (Machine Weight) kg 341 205+285
Safety Devices High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload ProtectorHigh Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
Defrost Method Deicer Deicer
Capacity Control % 9~100 8~100
Refrigerant
Refrigerant Name R-410A R-410A
Charge kg 11.7 7.2+9.5
Control Electronic Expansion Valve Electronic Expansion Valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Standard Accessories Installation Manual, Operation Manual, Connection Pipes, ClampsInstallation Manual, Operation Manual, Connection Pipes, Clamps
Drawing No. C: 4D061011
Conversion Formulae
kcal/h=kW860Btu/h=kW3412
cfm=m/min35.3
Specifications 15
Specifications Si34-803
Notes:1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Model Name (Combination Unit) RXYQ22PAY1(E) RXYQ24PAY1(E)
Model Name (Independent Unit) RXYQ10PAY1(E)+RXYQ12PAY1(E) RXYQ8PAY1(E)+RXYQ16PAY1(E)
1 Cooling Capacity (19.5CWB)
kcal / h 53,200 58,300
Btu / h 211,000 231,000
kW 61.9 67.8
2 Cooling Capacity (19.0CWB) kW 61.5 67.4
3 Heating Capacity
kcal / h 59,300 64,500
Btu / h 235,000 256,000
kW 69.0 75.0
Casing ColorWithout(E) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
With(E) Light Camel (2.5Y6.5/1.5) Light Camel (2.5Y6.5/1.5)
Dimensions: (HWD) mm (1680930765)+(16801240765) (1680930765)+(16801240765)
Heat Exchanger Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Piston Displacement m/h (13.34+10.53)+(13.34+10.53) 16.90+(13.34+10.53+10.53)
Number of Revolutions r.p.m (6300, 2900)+(6300, 2900) 7980+(6300, 29002)
Motor OutputNumber of Units kW ((1.4+4.5)1)+((2.5+4.5)1) (4.51)+((2.7+4.5+4.5)1)
Starting Method Soft Start Soft Start
Fan
Type Propeller Fan Propeller Fan
Motor Output kW (0.751)+(0.352) (0.751)+(0.352)
Air Flow Rate m/min 185+233 180+233
Drive Direct Drive Direct Drive
Connecting Pipes
Liquid Pipe mm 15.9 (Brazing Connection) 15.9 (Brazing Connection)Gas Pipe mm 28.6 (Brazing Connection) 34.9 (Brazing Connection)
Product Mass (Machine Weight) kg 249+285 205+329
Safety Devices High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload ProtectorHigh Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
Defrost Method Deicer Deicer
Capacity Control % 7~100 6~100
Refrigerant
Refrigerant Name R-410A R-410A
Charge kg 7.9+9.5 7.2+11.5
Control Electronic Expansion Valve Electronic Expansion Valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Standard Accessories Installation Manual, Operation Manual, Connection Pipes, ClampsInstallation Manual, Operation Manual, Connection Pipes, Clamps
Drawing No.
Conversion Formulae
kcal/h=kW860Btu/h=kW3412
cfm=m/min35.3
16 Specifications
Si34-803 Specifications
Notes:1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Model Name (Combination Unit) RXYQ26PAY1(E) RXYQ28PAY1(E)
Model Name (Independent Unit) RXYQ8PAY1(E)+RXYQ18PAY1(E) RXYQ10PAY1(E)+RXYQ18PAY1(E)
1 Cooling Capacity (19.5CWB)
kcal / h 61,700 66,700
Btu / h 250,000 26,400
kW 71.8 77.5
2 Cooling Capacity (19.0CWB) kW 71.4 77.0
3 Heating Capacity
kcal / h 70,100 75,700
Btu / h 278,000 300,000
kW 81.5 88.0
Casing ColorWithout(E) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
With(E) Light Camel (2.5Y6.5/1.5) Light Camel (2.5Y6.5/1.5)
Dimensions: (HWD) mm (1680930765)+(16801240765) (1680930765)+(16801240765)
Heat Exchanger Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Piston Displacement m/h (16.90)+(16.90+10.53+10.53) (13.34+10.53)+(16.90+10.53+10.53)
Number of Revolutions r.p.m (7980)+(7980, 2900, 2900) (6300, 2900)+(7980, 29002)
Motor OutputNumber of Units kW (4.51)+((4.3+4.5+4.5)1) ((1.4+4.5)1)+((4.3+4.5+4.5)1)
Starting Method Soft Start Soft Start
Fan
Type Propeller Fan Propeller Fan
Motor Output kW (0.751)+(0.752) (0.751)+(0.752)
Air Flow Rate m/min 180+239 185+239
Drive Direct Drive Direct Drive
Connecting Pipes
Liquid Pipe mm 19.1 (Brazing Connection) 19.1 (Brazing Connection)Gas Pipe mm 34.9 (Brazing Connection) 34.9 (Brazing Connection)
Product Mass (Machine Weight) kg 205+341 249+341
Safety Devices High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload ProtectorHigh Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
Defrost Method Deicer Deicer
Capacity Control % 6~100 5~100
Refrigerant
Refrigerant Name R-410A R-410A
Charge kg 7.2+11.7 7.9+11.7
Control Electronic Expansion Valve Electronic Expansion Valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Standard Accessories Installation Manual, Operation Manual, Connection Pipes, ClampsInstallation Manual, Operation Manual, Connection Pipes, Clamps
Drawing No.
Conversion Formulae
kcal/h=kW860Btu/h=kW3412
cfm=m/min35.3
Specifications 17
Specifications Si34-803
Notes:1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Model Name (Combination Unit) RXYQ30PAY1(E) RXYQ32PAY1(E)
Model Name (Independent Unit) RXYQ12PAY1(E)+RXYQ18PAY1(E) RXYQ16PAY1(E)+RXYQ16PAY1(E)
1 Cooling Capacity (19.5CWB)
kcal / h 71,400 77,800
Btu / h 283,000 309,000
kW 83 90.5
2 Cooling Capacity (19.0CWB) kW 82.5 90.0
3 Heating Capacity
kcal / h 80,800 86,000
Btu / h 321,000 341,000
kW 94.0 100
Casing ColorWithout(E) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
With(E) Light Camel (2.5Y6.5/1.5) Light Camel (2.5Y6.5/1.5)
Dimensions: (HWD) mm (16801240765)+(16801240765) (16801240765)+(16801240765)
Heat Exchanger Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Piston Displacement m/h (13.34+10.53)+(16.90+10.53+10.53) (13.34+10.53+10.53)+(13.34+10.53+10.53)
Number of Revolutions r.p.m (6300, 2900)+(7980, 2900, 2900) (6300, 2900, 2900)+(6300, 2900, 2900)
Motor OutputNumber of Units kW ((2.5+4.5)1)+((4.3+4.5+4.5)1) ((2.7+4.5+4.5)1)+((2.7+4.5+4.5)1)
Starting Method Soft Start Soft Start
Fan
Type Propeller Fan Propeller Fan
Motor Output kW (0.352)+(0.752) (0.352)+(0.352)
Air Flow Rate m/min 233+239 233+233
Drive Direct Drive Direct Drive
Connecting Pipes
Liquid Pipe mm 19.1 (Brazing Connection) 19.1 (Brazing Connection)Gas Pipe mm 34.9 (Brazing Connection) 34.9 (Brazing Connection)
Product Mass (Machine Weight) kg 285+341 329+329
Safety Devices High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload ProtectorHigh Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
Defrost Method Deicer Deicer
Capacity Control % 5~100 5~100
Refrigerant
Refrigerant Name R-410A R-410A
Charge kg 9.5+11.7 11.5+11.5
Control Electronic Expansion Valve Electronic Expansion Valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Standard Accessories Installation Manual, Operation Manual, Connection Pipes, ClampsInstallation Manual, Operation Manual, Connection Pipes, Clamps
Drawing No.
Conversion Formulae
kcal/h=kW860Btu/h=kW3412
cfm=m/min35.3
18 Specifications
Si34-803 Specifications
Notes:1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Model Name (Combination Unit) RXYQ34PAY1(E) RXYQ36PAY1(E)
Model Name (Independent Unit) RXYQ16PAY1(E)+RXYQ18PAY1(E) RXYQ18PAY1(E)+RXYQ18PAY1(E)
1 Cooling Capacity (19.5CWB)
kcal / h 81,400 85,100
Btu / h 323,000 338,000
kW 94.6 99.0
2 Cooling Capacity (19.0CWB) kW 94.0 98.0
3 Heating Capacity
kcal / h 92,000 97,200
Btu / h 365,000 386,000
kW 107 113
Casing ColorWithout(E) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
With(E) Light Camel (2.5Y6.5/1.5) Light Camel (2.5Y6.5/1.5)
Dimensions: (HWD) mm (16801240765)+(16801240765) (16801240765)+(16801240765)
Heat Exchanger Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Piston Displacement m/h (13.34+10.53+10.53)+(16.90+10.53+10.53) (16.90+10.53+10.53)+(16.90+10.53+10.53)
Number of Revolutions r.p.m (6300, 2900, 2900)+(7980, 2900, 2900) (7980, 2900, 2900)+(7980, 2900, 2900)
Motor OutputNumber of Units kW ((2.7+4.5+4.5)1)+((4.3+4.5+4.5)1) ((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1)
Starting Method Soft Start Soft Start
Fan
Type Propeller Fan Propeller Fan
Motor Output kW (0.352)+(0.752) (0.752)+(0.752)
Air Flow Rate m/min 233+239 239+239
Drive Direct Drive Direct Drive
Connecting Pipes
Liquid Pipe mm 19.1 (Brazing Connection) 19.1 (Brazing Connection)Gas Pipe mm 34.9 (Brazing Connection) 41.3 (Brazing Connection)
Product Mass (Machine Weight) kg 329+341 341+341
Safety Devices High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload ProtectorHigh Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
Defrost Method Deicer Deicer
Capacity Control % 5~100 4~100
Refrigerant
Refrigerant Name R-410A R-410A
Charge kg 11.5+11.7 11.7+11.7
Control Electronic Expansion Valve Electronic Expansion Valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Standard Accessories Installation Manual, Operation Manual, Connection Pipes, ClampsInstallation Manual, Operation Manual, Connection Pipes, Clamps
Drawing No.
Conversion Formulae
kcal/h=kW860Btu/h=kW3412
cfm=m/min35.3
Specifications 19
Specifications Si34-803
Notes:1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Model Name (Combination Unit) RXYQ38PAY1(E) RXYQ40PAY1(E)
Model Name (Independent Unit) RXYQ8PAY1(E)+RXYQ12PAY1(E)+RXYQ18PAY1(E) RXYQ8PAY1(E)+RXYQ16PAY1(E)+RXYQ16PAY1(E)
1 Cooling Capacity (19.5CWB)
kcal / h 91,200 97,200
Btu / h 362,000 386,000
kW 106 113
2 Cooling Capacity (19.0CWB) kW 105 112
3 Heating Capacity
kcal / h 102,000 108,000
Btu / h 406,000 427,000
kW 119 125
Casing ColorWithout(E) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
With(E) Light Camel (2.5Y6.5/1.5) Light Camel (2.5Y6.5/1.5)
Dimensions: (HWD) mm (1680930765)+(16801240765)+(16801240765) (1680930765)+(16801240765)+(16801240765)
Heat Exchanger Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Piston Displacement m/h (16.90)+(13.34+10.53)+(16.90+10.53+10.53) (16.90)+(13.34+10.53+10.53)+(13.34+10.53+10.53)
Number of Revolutions r.p.m (7980)+(6300, 2900)+(7980, 2900, 2900) (7980)+(6300, 2900, 2900)+(6300, 2900, 2900)
Motor OutputNumber of Units kW (4.51)+((2.5+4.5)1)+((4.3+4.5+4.5)1) (4.51)+((2.7+4.5+4.5)1)+((2.7+4.5+4.5)1)
Starting Method Soft Start Soft Start
Fan
Type Propeller Fan Propeller Fan
Motor Output kW (0.751)+(0.352)+(0.752) (0.751)+(0.352)+(0.352)
Air Flow Rate m/min 180+233+239 180+233+233
Drive Direct Drive Direct Drive
Connecting Pipes
Liquid Pipe mm 19.1 (Brazing Connection) 19.1 (Brazing Connection)Gas Pipe mm 41.3 (Brazing Connection) 41.3 (Brazing Connection)
Product Mass (Machine Weight) kg 205+285+341 205+329+329
Safety Devices High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload ProtectorHigh Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
Defrost Method Deicer Deicer
Capacity Control % 4~100 4~100
Refrigerant
Refrigerant Name R-410A R-410A
Charge kg 7.2+9.5+11.7 7.2+11.5+11.5
Control Electronic Expansion Valve Electronic Expansion Valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Standard Accessories Installation Manual, Operation Manual, Connection Pipes, ClampsInstallation Manual, Operation Manual, Connection Pipes, Clamps
Drawing No.
Conversion Formulae
kcal/h=kW860Btu/h=kW3412
cfm=m/min35.3
20 Specifications
Si34-803 Specifications
Notes:1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Model Name (Combination Unit) RXYQ42PAY1(E) RXYQ44PAY1(E)
Model Name (Independent Unit) RXYQ8PAY1(E)+RXYQ16PAY1(E)+RXYQ18PAY1(E) RXYQ8PAY1(E)+RXYQ18PAY1(E)+RXYQ18PAY1(E)
1 Cooling Capacity (19.5CWB)
kcal / h 101,000 104,000
Btu / h 399,000 413,000
kW 117 121
2 Cooling Capacity (19.0CWB) kW 116 120
3 Heating Capacity
kcal / h 114,000 119,000
Btu / h 450,000 471,000
kW 132 138
Casing ColorWithout(E) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
With(E) Light Camel (2.5Y6.5/1.5) Light Camel (2.5Y6.5/1.5)
Dimensions: (HWD) mm (1680930765)+(16801240765)+(16801240765) (1680930765)+(16801240765)+(16801240765)
Heat Exchanger Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Piston Displacement m/h (16.90)+(13.34+10.53+10.53)+(16.90+10.53+10.53) (16.90)+(16.90+10.53+10.53)+(16.90+10.53+10.53)
Number of Revolutions r.p.m (7980)+(6300, 2900, 2900)+(7980, 2900, 2900) (7980)+(7980, 29002)+(7980, 2900, 2900)
Motor OutputNumber of Units kW (4.51)+((2.7+4.5+4.5)1)+((4.3+4.5+4.5)1) (4.51)+((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1)
Starting Method Soft Start Soft Start
Fan
Type Propeller Fan Propeller Fan
Motor Output kW (0.751)+(0.352)+(0.752) (0.751)+(0.752)+(0.752)
Air Flow Rate m/min 180+233+239 180+239+239
Drive Direct Drive Direct Drive
Connecting Pipes
Liquid Pipe mm 19.1 (Brazing Connection) 19.1 (Brazing Connection)Gas Pipe mm 41.3 (Brazing Connection) 41.3 (Brazing Connection)
Product Mass (Machine Weight) kg 205+329+341 205+341+341
Safety Devices High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload ProtectorHigh Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
Defrost Method Deicer Deicer
Capacity Control % 4~100 4~100
Refrigerant
Refrigerant Name R-410A R-410A
Charge kg 7.2+11.5+11.7 7.2+11.7+11.7
Control Electronic Expansion Valve Electronic Expansion Valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Standard Accessories Installation Manual, Operation Manual, Connection Pipes, ClampsInstallation Manual, Operation Manual, Connection Pipes, Clamps
Drawing No.
Conversion Formulae
kcal/h=kW860Btu/h=kW3412
cfm=m/min35.3
Specifications 21
Specifications Si34-803
Notes:1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Model Name (Combination Unit) RXYQ46PAY1(E) RXYQ48PAY1(E)
Model Name (Independent Unit) RXYQ10PAY1(E)+RXYQ18PAY1(E)+RXYQ18PAY1(E) RXYQ12PAY1(E)+RXYQ18PAY1(E)+RXYQ18PAY1(E)
1 Cooling Capacity (19.5CWB)
kcal / h 109,000 114,000
Btu / h 433,000 454,000
kW 127 133
2 Cooling Capacity (19.0CWB) kW 126 132
3 Heating Capacity
kcal / h 124,000 130,000
Btu / h 495,000 515,000
kW 145 151
Casing ColorWithout(E) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
With(E) Light Camel (2.5Y6.5/1.5) Light Camel (2.5Y6.5/1.5)
Dimensions: (HWD) mm (1680930765)+(16801240765)+(16801240765) (16801240765)+(16801240765)+(16801240765)
Heat Exchanger Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Piston Displacement m/h (13.34+10.53)+(16.90+10.53+10.53)+(16.90+10.53+10.53) (13.34+10.53)+(16.90+10.53+10.53)+(16.90+10.53+10.53)
Number of Revolutions r.p.m (6300, 2900)+(7980, 2900, 2900)+(7980, 2900, 2900) (6300, 2900)+(7980, 2900, 2900)+(7980, 2900, 2900)
Motor OutputNumber of Units kW ((1.4+4.5)1)+((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1) ((2.5+4.5)1)+((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1)
Starting Method Soft Start Soft Start
Fan
Type Propeller Fan Propeller Fan
Motor Output kW (0.751)+(0.752)+(0.752) (0.352)+(0.752)+(0.752)
Air Flow Rate m/min 185+239+239 233+239+239
Drive Direct Drive Direct Drive
Connecting Pipes
Liquid Pipe mm 19.1 (Brazing Connection) 19.1 (Brazing Connection)Gas Pipe mm 41.3 (Brazing Connection) 41.3 (Brazing Connection)
Product Mass (Machine Weight) kg 249+341+341 285+341+341
Safety Devices High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload ProtectorHigh Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
Defrost Method Deicer Deicer
Capacity Control % 3~100 3~100
Refrigerant
Refrigerant Name R-410A R-410A
Charge kg 7.9+11.7+11.7 9.5+11.7+11.7
Control Electronic Expansion Valve Electronic Expansion Valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Standard Accessories Installation Manual, Operation Manual, Connection Pipes, ClampsInstallation Manual, Operation Manual, Connection Pipes, Clamps
Drawing No.
Conversion Formulae
kcal/h=kW860Btu/h=kW3412
cfm=m/min35.3
22 Specifications
Si34-803 Specifications
Notes:1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Model Name (Combination Unit) RXYQ50PAY1(E) RXYQ52PAY1(E)
Model Name (Independent Unit) RXYQ14PAY1(E)+RXYQ18PAY1(E)+RXYQ18PAY1(E) RXYQ16PAY1(E)+RXYQ18PAY1(E)+RXYQ18PAY1(E)
1 Cooling Capacity (19.5CWB)
kcal / h 120,000 124,000
Btu / h 474,000 491,000
kW 139 144
2 Cooling Capacity (19.0CWB) kW 138 143
3 Heating Capacity
kcal / h 136,000 140,000
Btu / h 539,000 556,000
kW 158 163
Casing ColorWithout(E) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
With(E) Light Camel (2.5Y6.5/1.5) Light Camel (2.5Y6.5/1.5)
Dimensions: (HWD) mm (16801240765)+(16801240765)+(16801240765) (16801240765)+(16801240765)+(16801240765)
Heat Exchanger Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Piston Displacement m/h (13.34+10.53+10.53)+(16.90+10.53+10.53)+(16.90+10.53+10.53) (13.34+10.53+10.53)+(16.90+10.53+10.53)+(16.90+10.53+10.53)
Number of Revolutions r.p.m (6300, 29002)+(7980, 2900, 2900)+(7980, 2900, 2900) (6300, 29002)+(7980, 2900, 2900)+(7980, 2900, 2900)
Motor OutputNumber of Units kW ((1.6+4.5+4.5)1)+((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1) ((2.7+4.5+4.5)1)+((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1)
Starting Method Soft Start Soft Start
Fan
Type Propeller Fan Propeller Fan
Motor Output kW (0.352)+(0.752)+(0.752) (0.352)+(0.752)+(0.752)
Air Flow Rate m/min 233+239+239 233+239+239
Drive Direct Drive Direct Drive
Connecting Pipes
Liquid Pipe mm 19.1 (Brazing Connection) 19.1 (Brazing Connection)Gas Pipe mm 41.3 (Brazing Connection) 41.3 (Brazing Connection)
Product Mass (Machine Weight) kg 329+341+341 329+341+341
Safety Devices High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload ProtectorHigh Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
Defrost Method Deicer Deicer
Capacity Control % 3~100 3~100
Refrigerant
Refrigerant Name R-410A R-410A
Charge kg 11.3+11.7+11.7 11.5+11.7+11.7
Control Electronic Expansion Valve Electronic Expansion Valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Standard Accessories Installation Manual, Operation Manual, Connection Pipes, ClampsInstallation Manual, Operation Manual, Connection Pipes, Clamps
Drawing No.
Conversion Formulae
kcal/h=kW860Btu/h=kW3412
cfm=m/min35.3
Specifications 23
Specifications Si34-803
Notes:1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Model Name (Combination Unit) RXYQ54PAY1(E)
Model Name (Independent Unit) RXYQ18PAY1(E)+RXYQ18PAY1(E)+RXYQ18PAY1(E)
1 Cooling Capacity (19.5CWB)
kcal / h 127,000
Btu / h 505,000
kW 148
2 Cooling Capacity (19.0CWB) kW 147
3 Heating Capacity
kcal / h 146,000
Btu / h 580,000
kW 170
Casing ColorWithout(E) Ivory White (5Y7.5/1)
With(E) Light Camel (2.5Y6.5/1.5)
Dimensions: (HWD) mm (16801240765)+(16801240765)+(16801240765)
Heat Exchanger Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type
Piston Displacement m/h (16.90+10.53+10.53)+(16.90+10.53+10.53)+(16.90+10.53+10.53)
Number of Revolutions r.p.m (7980, 2900, 2900)+(7980, 2900, 2900)+(7980, 2900, 2900)
Motor OutputNumber of Units kW ((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1)+((4.3+4.5+4.5)1)
Starting Method Soft Start
Fan
Type Propeller Fan
Motor Output kW (0.752)+(0.752)+(0.752)
Air Flow Rate m/min 239+239+239
Drive Direct Drive
Connecting Pipes
Liquid Pipe mm 19.1 (Brazing Connection)Gas Pipe mm 41.3 (Brazing Connection)
Product Mass (Machine Weight) kg 341+341+341
Safety Devices High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
Defrost Method Deicer
Capacity Control % 3~100
Refrigerant
Refrigerant Name R-410A
Charge kg 11.7+11.7+11.7
Control Electronic Expansion Valve
Refrigerator Oil Refer to the nameplate of compressor
Standard Accessories Installation Manual, Operation Manual, Connection Pipes, Clamps
Drawing No.
Conversion Formulae
kcal/h=kW860Btu/h=kW3412
cfm=m/min35.3
24 Specifications
Si34-803 Specifications
Heat Pump 50Hz High COP Series
Notes:1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Model Name RXYQ16PAHY1(E) RXYQ18PAHY1(E)
Model Name (Independent Unit) RXYQ8PAY1(E)+RXYQ8PAY1(E) RXYQ8PAY1(E)+RXYQ10PAY1(E)
1 Cooling Capacity (19.5CWB)
kcal / h 38,800 43,600
Btu / h 154,000 173,000
kW 45.1 50.7
2 Cooling Capacity (19.0CWB) kW 44.8 50.4
3 Heating Capacity
kcal / h 43,000 48,600
Btu / h 171,000 193,000
kW 50.0 56.5
Casing ColorWithout(E) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
With(E) Light Camel (2.5Y6.5/1.5) Light Camel (2.5Y6.5/1.5)
Dimensions: (HWD) mm (1680930765)+(1680930765) (1680930765)+(1680930765)
Heat Exchanger Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Piston Displacement m/h (16.90)+(16.90) (16.90)+(13.34+10.53)
Number of Revolutions r.p.m (7980)+(7980) (7980)+(6300,2900)
Motor OutputNumber of Units kW (4.51)+(4.51) (4.51)+((1.4+4.5)1)
Starting Method Soft start Soft start
Fan
Type Propeller Fan Propeller Fan
Motor Output kW (0.751)+(0.751) (0.751)+(0.751)
Air Flow Rate m/min 180+180 180+185
Drive Direct Drive Direct Drive
Connecting Pipes
Liquid Pipe mm 12.7(Brazing Connection) 15.9(Brazing Connection)Gas Pipe mm 28.6(Brazing Connection) 28.6(Brazing Connection)
Product Mass (Machine weight) kg 205+205 205+249
Safety Devices High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
Defrost Method Deicer Deicer
Capacity Control % 10~100 8~100
Refrigerant
Refrigerant Name R-410A R-410A
Charge kg 7.2+7.2 7.2+7.9
Control Electronic Expansion Valve Electronic Expansion Valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Standard Accessories Installation Manual, Operation Manual, Connection Pipes, ClampsInstallation Manual, Operation Manual, Connection Pipes, Clamps
Drawing No.
Conversion Formulae
kcal/h=kW860Btu/h=kW3412
cfm=m/min35.3
Specifications 25
Specifications Si34-803
Notes:1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Model Name RXYQ24PAHY1(E) RXYQ26PAHY1(E)
Model Name (Independent Unit) RXYQ8PAY1(E)+RXYQ8PAY1(E)+RXYQ8PAY1(E) RXYQ8PAY1(E)+RXYQ8PAY1(E)+RXYQ10PAY1(E)
1 Cooling Capacity (19.5CWB)
kcal / h 58,100 63,000
Btu / h 231,000 250,000
kW 67.6 73.2
2 Cooling Capacity (19.0CWB) kW 67.2 72.8
3 Heating Capacity
kcal / h 64,500 70,100
Btu / h 260,000 278,000
kW 75.0 81.5
Casing ColorWithout(E) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
With(E) Light Camel (2.5Y6.5/1.5) Light Camel (2.5Y6.5/1.5)
Dimensions: (HWD) mm (1680930765)+(1680930765)+(1680930765) (1680930765)+(1680930765)+(1680930765)
Heat Exchanger Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Piston Displacement m/h (16.90)+(16.90)+(16.90) (16.90)+(16.90)+(13.34+10.53)
Number of Revolutions r.p.m (7980)+(7980)+(7980) (7980)+(7980)+(6300,2900)
Motor OutputNumber of Units kW (4.51)+(4.51)+(4.51) (4.51)+(4.51)+((1.4+4.5)1)
Starting Method Soft start Soft start
Fan
Type Propeller Fan Propeller Fan
Motor Output kW (0.751)+(0.751)+(0.751) (0.751)+(0.751)+(0.751)
Air Flow Rate m/min 180+180+180 180+180+185
Drive Direct Drive Direct Drive
Connecting Pipes
Liquid Pipe mm 15.9(Brazing Connection) 19.1(Brazing Connection)Gas Pipe mm 34.9(Brazing Connection) 34.9(Brazing Connection)
Product Mass (Machine weight) kg 205+205+205 205+205+249
Safety Devices High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
Defrost Method Deicer Deicer
Capacity Control % 7~100 6~100
Refrigerant
Refrigerant Name R-410A R-410A
Charge kg 7.2+7.2+7.2 7.2+7.2+7.9
Control Electronic Expansion Valve Electronic Expansion Valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Standard AccessoriesInstallation Manual, Operation Manual, Connection Pipes, Clamps
Installation Manual, Operation Manual, Connection Pipes, Clamps
Drawing No.
Conversion Formulae
kcal/h=kW860Btu/h=kW3412
cfm=m/min35.3
26 Specifications
Si34-803 Specifications
Notes:1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Model Name RXYQ28PAHY1(E) RXYQ30PAHY1(E)
Model Name (Independent Unit) RXYQ8PAY1(E)+RXYQ8PAY1(E)+RXYQ12PAY1(E) RXYQ8PAY1(E)+RXYQ10PAY1(E)+RXYQ12PAY1(E)
1 Cooling Capacity (19.5CWB)
kcal / h 67,800 72,600
Btu / h 269,000 288,000
kW 78.8 84.4
2 Cooling Capacity (19.0CWB) kW 78.3 83.9
3 Heating Capacity
kcal / h 75,300 80,800
Btu / h 299,000 321,000
kW 87.5 94.0
Casing ColorWithout(E) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
With(E) Light Camel (2.5Y6.5/1.5) Light Camel (2.5Y6.5/1.5)
Dimensions: (HWD) mm (1680930765)+(1680930765)+(16801240765) (1680930765)+(1680930765)+(16801240765)
Heat Exchanger Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Piston Displacement m/h (16.90)+(16.90)+(13.34+10.53) (16.90)+(13.34+10.53)+(13.34+10.53)
Number of Revolutions r.p.m (7980)+(7980)+(6300,2900) (7980)+(6300,2900)+(6300,2900)
Motor OutputNumber of Units kW (4.51)+(4.51)+((2.5+4.5)1) (4.51)+((1.4+4.5)1)+((2.5+4.5)1)
Starting Method Soft start Soft start
Fan
Type Propeller Fan Propeller Fan
Motor Output kW (0.751)+(0.751)+(0.352) (0.751)+(0.751)+(0.352)
Air Flow Rate m/min 180+180+233 180+185+233
Drive Direct Drive Direct Drive
Connecting Pipes
Liquid Pipe mm 19.1(Brazing Connection) 19.1(Brazing Connection)Gas Pipe mm 34.9(Brazing Connection) 34.9(Brazing Connection)
Product Mass (Machine weight) kg 205+205+285 205+249+285
Safety Devices High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
Defrost Method Deicer Deicer
Capacity Control % 6~100 5~100
Refrigerant
Refrigerant Name R-410A R-410A
Charge kg 7.2+7.2+9.5 7.2+7.9+9.5
Control Electronic Expansion Valve Electronic Expansion Valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Standard Accessories Installation Manual, Operation Manual, Connection Pipes, ClampsInstallation Manual, Operation Manual, Connection Pipes, Clamps
Drawing No.
Conversion Formulae
kcal/h=kW860Btu/h=kW3412
cfm=m/min35.3
Specifications 27
Specifications Si34-803
Notes:1 Indoor temp. : 27CDB, 19.5CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.2 Indoor temp. : 27CDB, 19.0CWB / outdoor temp. : 35CDB / Equivalent piping length : 7.5m, level
difference : 0m.3 Indoor temp. : 20CDB / outdoor temp. : 7CDB, 6CWB / Equivalent piping length : 7.5m, level difference :
0m.4 The units with anti-corrosion treatment will be available as standard. Please specify the suffix E as
RXYQ5PAY1E.
Model Name RXYQ32PAHY1(E) RXYQ34PAHY1(E)
Model Name (Independent Unit) RXYQ8PAY1(E)+RXYQ12PAY1(E)+RXYQ12PAY1(E) RXYQ10PAY1(E)+RXYQ12PAY1(E)+RXYQ12PAY1(E)
1 Cooling Capacity (19.5CWB)
kcal / h 77,300 82,200
Btu / h 307,000 326,000
kW 89.9 95.6
2 Cooling Capacity (19.0CWB) kW 89.4 95.0
3 Heating Capacity
kcal / h 86,000 92,000
Btu / h 341,000 365,000
kW 100 107
Casing ColorWithout(E) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)
With(E) Light Camel (2.5Y6.5/1.5) Light Camel (2.5Y6.5/1.5)
Dimensions: (HWD) mm (1680930765)+(16801240765)+(16801240765) (1680930765)+(16801240765)+(16801240765)
Heat Exchanger Cross Fin Coil Cross Fin Coil
Comp.
Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type
Piston Displacement m/h (16.90)+(13.34+10.53)+(13.34+10.53) (13.34+10.53)+(13.34+10.53)+(13.34+10.53)
Number of Revolutions r.p.m (7980)+(6300,2900)+(6300,2900) (6300,2900)+(6300,2900)+(6300,2900)
Motor OutputNumber of Units kW (4.51)+((2.5+4.5)1)+((2.5+4.5)1) ((1.4+4.5)1)+((2.5+4.5)1)+((2.5+4.5)1)
Starting Method Soft start Soft start
Fan
Type Propeller Fan Propeller Fan
Motor Output kW (0.751)+(0.352)+(0.352) (0.751)+(0.352)+(0.352)
Air Flow Rate m/min 180+233+233 185+233+233
Drive Direct Drive Direct Drive
Connecting Pipes
Liquid Pipe mm 19.1(Brazing Connection) 19.1(Brazing Connection)Gas Pipe mm 34.9(Brazing Connection) 34.9(Brazing Connection)
Product Mass (Machine weight) kg 205+285+285 249+285+285
Safety Devices High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
High Pressure Switch, Fan Driver Overload Protector, Over Current Relay, Inverter Overload Protector
Defrost Method Deicer Deicer
Capacity Control % 5~100 5~100
Refrigerant
Refrigerant Name R-410A R-410A
Charge kg 7.2+9.5+9.5 7.9+9.5+9.5
Control Electronic Expansion Valve Electronic Expansion Valve
Refrigerator Oil Refer to the nameplate of compressor Refer to the nameplate of compressor
Standard Accessories Installation Manual, Operation Manual, Connection Pipes, ClampsInstallation Manual, Operation Manual, Connection Pipes, Clamps
Drawing No.
Conversion Formulae
kcal/h=kW860Btu/h=kW3412
cfm=m/