AFFICHEURS DÉPORTÉS - REMOTE INTERFACES
ATyS D10 & D20Notice d’utilisation - Operating instructions
F GB
SOCOMEC GROUP SWITCHING PROTECTION & UPS
MAKE YOUR BUSINESS SAFE
532_212_a 9/02/05 9:00 Page 1
SOCOMEC - Réf. : 532 212 A2
PRÉSENTATION GÉNÉRALE ATyS D10 et D20 _______3INSTALLATION ATyS D10 et D20 ___________________4
Montage _______________________________________4Raccordements _________________________________4Caractéristiques_________________________________4
UTILISATION ATyS D10 ___________________________5Affichage_______________________________________5
UTILISATION ATyS D20 ___________________________6Affichage_______________________________________6Clavier _________________________________________7Version logiciel __________________________________7Programmation _________________________________8Exploitation____________________________________18Fonctionnement________________________________20Visualisation ___________________________________20
Som
mai
re
F
GENERAL PRESENTATION ATyS D10 & D20________23INSTALLATION ATyS D10 & D20___________________24
Mounting _____________________________________24Connection____________________________________24Characteristics_________________________________24
OPERATION ATYS D10___________________________25Display _______________________________________25
OPERATION ATyS D20 ___________________________26Display _______________________________________26Keypad _______________________________________27Software version _______________________________27Programming __________________________________28Control and Test modes_________________________38Operational sequences__________________________40Visualisation ___________________________________40
Sum
mar
y
GB
532_212_a 9/02/05 9:00 Page 2
ATyS D10 and D20 models are remote interfacesdesigned for easy integration on front panels. They canbe connected to ATyS 6e, 6m and C30 products to allowremote access to display or control features.
23SOCOMEC - Réf.: 532 212 A
Remote interfaces ATySGENERAL PRESENTATIONATyS D10 & D20
532_212_a 9/02/05 9:00 Page 23
Mounting
• Door fixing: 2 holes, diameter 22.5 mm• Maximum thickness of the door: 20 mm
Connection
Connection only on AtyS 6e, 6m or C30 products.
> CableRJ45 type 8/8 not isolated
> Maximum cable length3 m
> Tightning torque4 N.m
Characteristics
> IPIP21 standardIP54 using gasket
> Operation• Temperature: -10 to + 55 °C• hygrometry: 80% humidity at 55 °C
95% humidity at 40 °C
Remote interfaces ATySINSTALLATIONATyS D10 & D20
24 SOCOMEC - Réf.: 532 212 A
1
ATY
S 1
47 A
(1) RJ45 plug for ATyS connection
Ø 22.5
4036
20
= =
96 x 96
ATY
S 1
61 A
Door drilling
ATyS C30
Type RJ45
ATyS D10/D20
43
21
ATY
S 3
13 A
GB
532_212_a 9/02/05 9:00 Page 24
25SOCOMEC - Réf.: 532 212 A
ATyS D10 allows remote display of transfer systempositions, sources availability and operational mode.Programming and operations remain available directly onmaster product (ATyS 6e, 6m or C30).
Remote interfaces ATySOPERATIONATyS D10
Display
Source 1 available Power On
• ATyS Product faulty, transfer error• Possible to reset after error
disappearance the power suppliesof the master product (ATyS 6e,6m, C30) for 3 minutes
Transfer system inposition 1
Transfer system inAutomatic mode
Transfer system inposition 0
Transfer system inposition 2
Source 2 available
ATY
S 1
45 B
532_212_a 9/02/05 9:00 Page 25
Remote interfaces ATySOPERATIONATyS D20
26 SOCOMEC - Réf.: 532 212 A
DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation
Display
ATyS D20 allows remote display of transfer systempositions, sources availability, operational mode andmetering. Programming and operations (Test andControl) are also available. Master product (ATyS 6e, 6mor C30) display is deactivated as soon as the remoteinterface is connected.
Power On
Source 1 available
Manualmodeactive Padlock*
• Product faulty, transfer error• Possible to reset after error
disappearance: switch off thepower supplies of the masterproduct (ATyS 6e, 6m, C30)for 3 minutes
Transfer system inposition 1
Transfer system inautomatic mode
Control mode active Test mode active Programming mode active
Transfer systemin position 0
Transfer systemin position 2
Source 2 available
ATY
S 1
46 B
* only on ATyS 6e and 6m
532_212_a 9/02/05 9:00 Page 26
Display
Software version
Keypad
Software version of the master product is displayedimmediately after ATyS 6e, 6m or C30 power on.
Access to AUT, Test,Control and Prog modes
Direct Access to Test and Controlfunctionalities or navigation
Allows main menu accessin visualisation mode orvalidation
Priority source
Informations• source 1• source 2• sources 1 & 2(split screen)
Power factorCapacitive or inductive
Phases (wires) displayed Units
Values
Signedvalues(power)
ATY
S 3
18 A
ATY
S 1
46 C
ATY
S 3
19 A
Remote interfaces ATyS
OPERATION
27SOCOMEC - Réf.: 532 212 A
532_212_a 9/02/05 9:00 Page 27
Remote interfaces ATySOPERATIONATyS D20
28 SOCOMEC - Réf.: 532 212 A
DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation
> Enter into programming mode
• Step 1: Press the “mode” push button until Prog led is blinking
• Step 2: Press “validation” push button. PROG led becomes fixed and access code is displayed
• Step 3: Enter access code (1000 factory default) using keypad “left”,“right”, “top” and “bottom”
• Step 4: Press “validation” push button to enter programming mode
> Programming mode exit
• Step 1: Press the “ESC” push button when not entering any value, to come back to mainprogramming menu
• Step 2: Press again on “ESC” push button to exit programming
New Active mode (Automatic or Manual) depends on information from the master device (ATyS 6e, 6m ou C30)
Programming
532_212_a 9/02/05 9:00 Page 28
Programming
> Navigation in programming mode
• Step 1: To access required menu, press navigation push buttons“left” and “right”
• Step 2: To access parameter to modifypress navigation push buttons “top” and “bottom”
• Step 3: To modify the parameter, press push button “right”to make the required parameter blinking
• Step 4: Press push buttons “top” and “bottom” to increment ordecrement the value of the parameter
• Step 5: Press “validation” push button to validate
In case of parameter displayed on 2 lines, press “validation” push button after first line modificationto access next one
“ESC” push button allows to come back to main menu or to cancel the modification
Remote interfaces ATyS
OPERATION
29SOCOMEC - Réf.: 532 212 A
532_212_a 9/02/05 9:00 Page 29
Programming
ARCHITECTURE OF THE PROGRAMMING MENU
Remote interfaces ATySOPERATIONATyS D20
30 SOCOMEC - Réf.: 532 212 A
DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation
*
**** ** ** ** **
** **** **
**
** ** **
ATY
S 3
27 A
532_212_a 9/02/05 9:00 Page 30
Remote interfaces ATyS
OPERATION
31SOCOMEC - Réf.: 532 212 A
*on
ly o
n A
tys
6m**
optio
n on
ATy
S 6
e &
6m
***
only
on
ATyS
C30
****
visi
ble
if o
ptio
n LS
sel
ecte
d a
nd a
ctiv
e
** ** ** ** ****
**
***
***
***
532_212_a 9/02/05 9:00 Page 31
Programming
VARIABLES CHARACTERISTICS
Remote interfaces ATySOPERATIONATyS D20
32 SOCOMEC - Réf.: 532 212 A
DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation
> Setup
LCD Denomination Setting range Default values
nt Type of network 1BL, 2BL, 2NBL 4NBL(cf. ATyS 6 or C30 instruction manual) 3NBL, 4NBL,
41NBL, 42NBL
Un Network Nominal voltage 100 to 480 V 400 VPhase-Neutral voltage for 1BL & 41NBLPhase-Phase voltage for others
ScE** Source 1 - Switch I or II configuration I, II ISource 1 (controlled and displayed) linked to switch I or II (depending on cabling)
Fn Network nominal Frequency 50 or 60 Hz 50 Hz
Ct* CTs primary current 50 to 5000/5 A 500/5 A(5 A secondary CT)
Gen Genset start signal state NO, NC NONormally opened or closed
Pri Network priority selection 1, 2 1Keypad selection (1 or 2)Also possible via external contactUsing option
Mtf Manual Retransfer Yes, No NoActivation of the feature
LoG Type of control logic selection IMP, CON, brE*** IMPImpulse, contactor or breaker***
AC*** Number of position auxiliary contacts used, depending on transfer 0, 2, 3 2device type (switch, contactor, breaker)
rn1 Allows 0 position command after loss of main source (source 1) Yes, No No
rn2 Allows 0 position command after loss of emergency source (source 2) Yes, No No
CrS Number of permutation counter Reset Yes, No No
CP Programming code modification 0001 to 9999 1000Possible to change the code
* only on AtyS 6m** only on ATyS 6e & 6m*** only on ATyS C30.
532_212_a 9/02/05 9:00 Page 32
Programming
> Voltage thresholds
> Frequency thresholds
Remote interfaces ATyS
OPERATION
33SOCOMEC - Réf.: 532 212 A
LCD Denomination Setting range Default values
oU Network 1 over voltage threshold 102 - 120% 115%
oUh Network 1 over voltage threshold hysteresis 101 - 119% 110%(< oU)
uU Network 1 under voltage threshold 80 - 98% 85%
uUh Network 1 under voltage threshold hysteresis 81 - 99% 95%(> uU)
oU Network 2 over voltage threshold 102 - 120% 115%
oUh Network 2 over voltage threshold hysteresis 101 - 119% 110%(< oU)
uU Network 2 under voltage threshold 80 - 98% 85%
uUh Network 2 under voltage threshold hysteresis 81 - 99% 95%(> uO)
Values defined are % of nominal values.Hysteresis thresholds must be programmed according to over and under voltage thresholds (respectively under & above).
LCD Denomination Setting range Default values
oF Network 1 over frequency threshold 101 to 120% 105%
oFh Network 1 over frequency threshold hysteresis 100.5 - 119.5% 103%(< oF)
uF Network 1 under frequency threshold 80 - 99% 95%
uFh Network 1 under frequency threshold hysteresis 80.5 - 99.5% 97%(> uF)
oF Network 2 over frequency threshold 101 - 120% 105%
oFh Network 2 over frequency threshold hysteresis 100.5 - 119.5% 103%(< oF)
uF Network 2 under frequency threshold 80 - 99% 95%
uFh Network 2 under frequency threshold hysteresis 80.5 - 99.5% 97%(> uF)
Values defined are % of nominal values.Hysteresis thresholds must be programmed according to over and under frequency thresholds (respectively under & above).
532_212_a 9/02/05 9:00 Page 33
Programming
Remote interfaces ATySOPERATIONATyS D20
34 SOCOMEC - Réf.: 532 212 A
DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation
> Timers
LCD Denomination Setting range Default values
Mft Main Failure Timer From 0 to 60 s 5 sDelays priority network failure detection
dtt Delay on transfer timer From 0 to 60 s 5 sEmergency network stability validation before transfer
OMf O Main Failure Timer From 0 to 20 s 0 sRest in O position when transferringfrom main network to emergency network
Mrt Main Return Timer From 0 to 30 min 1 minMain network stability validation before re-transfer
OMr O Main Return Timer From 0 to 20 s 5 sRest in O position when re-transferring from emergency network to main network
Cdt Cool Down Timer From 0 to 10 min 4 minAllows generator cooling down period after load’sretransfer from emergency source (generator) to Main source
> Communication
LCD Denomination Setting range Default values
Add Device address 1 to 247 5
bd Communication speed 2400, 4800, 9600, 960019200, 38400
StoP Stop bit 1, 2 1
PAr Parity bit No, Odd, Even No
Only on ATyS 6e or 6m in case of optional communication module.
532_212_a 9/02/05 9:00 Page 34
• Input (In2, Ft2) and output (Ou1, S1A) programming example:
Refer to ATyS C30, 6e or 6m instruction manualfor terminals identification.
Input/Output Function Relay State
I1 to I4 Ft1, Ft2, Ft3, Ft4, Pri, NO or NCMtf, S2A, Man, TOL, TFL, EJP, CTS
O1 to O4 S1A, S2A, LS, / NO
ATY
S 3
28 A
• Step 1: Press “right” push button to makefirst variable blinking (Ft2 ou S1A)
• Step 2: press “top” and “bottom”push buttons to modify the variable
• Step 3: press “validation”
• Step 4: press “bottom” push button toacces nO variable selection
Programming
> Inputs/Outputs• 2 inputs (In1, In2) and 2 outputs (Ou1, Ou2) as standard
on ATyS C30.
• Possibility to connect 2 modules 2 Inputs/2 Outputson ATyS 6e & 6m.
- First module: In1, In2, Ou1, Ou2- Second module In3, In4, Ou3, Ou4.
Remote interfaces ATyS
OPERATION
35SOCOMEC - Réf.: 532 212 A
532_212_a 9/02/05 9:00 Page 35
Outputs
Programming
• Variables descriptionInputs
Remote interfaces ATySOPERATIONATyS D20
36 SOCOMEC - Réf.: 532 212 A
DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation
Variable Description
Ft1 Fault input 1. The fault led is blinking as soon as the input is active andFt1 is displayed on LCD. Reset when the input is de-activated
Ft2 Fault input 2. The fault led is blinking as soon as the input is active and Ft2 is displayed on LCD.Reset when the input is de-activated
Ft3* Fault input 3. The fault led is blinking as soon as the input is active and Ft3 is displayed on LCD. The transfer switch is immediately driven in 0 position.Keypad action (Esc) necessary to Reset the fault
Ft4* Fault input 4. The fault led is blinking as soon as the input is active and Ft4 is displayed on LCD. The transfer switch is immediately driven in 0 position.Keypad action (Esc) necessary to Reset the fault
Pri Priority network selection.Network 1 has priority when input is not activated. Network 2 has priority if input is active
Mtf Remote manuel re-transfer. Feature identical to manual re transfert on keypad.Re-transfer from priority network to backup network is allowed from input activation (1 s front).The Mtf variable in the setup menu must be selected (Yes) to allow input recognition
S2A Information source 2 available (Genset) used instead of voltage/ frequency measurementfrom ATyS (inhibited when S2A is selected)
Man** Information transfer system in manual mode.All automatic commands (+ test on load and control commands) are inhibited as soon as the input is activated
CTS** Remote transfer control. Possible to initiate transfer from priority source to backup sourcebefore DTT ends. If DTT is set to its maximum value (60s), the transfer is initiated as soon asthe input is activated (1 s front)
TOL** Remote test on load. Started from input activation.Re-transfer is blocked until input de-activation
TFL Remote test off load.Started from input activation (remote genset start /stop)
EJP 2 inputs one automatically affected to EJP• input 1 for EJP advice, to start generator• input 2 to transfer on emergency sourceRetransfer is activated when input 2 disapears
* only on ATyS C30, specific fault operation (Ft2 and Ft3)** only as option on ATyS C30, standard features on ATyS 6e et 6m.
Variable Description
S1A Source 1 available.Output activated as soon as source 1 is considered available (similar to front led source 1)
S2A Source 2 available.Output activated as soon as source 2 is considered available (similar to front led source 2)
LS Load shedding relay. LS timer corresponds to time available to disconnect the shed loads.The relay is activated before permutation on standby network according to LS timer.The relay is de-activated after retransfer on mains network and LS timer countdown
532_212_a 9/02/05 9:00 Page 36
Programming
Remote interfaces ATyS
OPERATION
37SOCOMEC - Réf.: 532 212 A
LOAD SHEDDING CONFIGURATIONLS variable allows associated LS timer configuration.
Output Associated funciton Setting range Default value
O1 to O4 LS 0 to 60 s (≤ DTT)* 2
> Example: load shedding configuration
function
timer
• Step 1: Press “right” push button to makefirst variable blinking (LS)
• Step 2: press push buttons “top” and“bottom” to modify the variable
• Step 3: Press “validation”
• Step 4: Press “bottom” push buttonto access timer value configuration
ATY
S 3
29 A
GB
* In case of DTT variable configuration below LS, LS will be automatically set to to DTT value.
532_212_a 9/02/05 9:00 Page 37
Control and Test modes
It is possible to start test sequences or to controlelectrically the changeover system from keypad.
NAVIGATION
Remote interfaces ATySOPERATIONATyS D20
38 SOCOMEC - Réf.: 532 212 A
DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation
> Enter Control or Test modes
• Step 1: Press “mode” push button to make test or control led blinking
• Step 2: Press “validation” push button to make control or test led become fixed
CONTROL MODE
Access code is displayed directly
TEST MODE
It is possible to test leds and LCD without entering any code by pressing directly
Test on load or test off load access codes are displayed after pressing or
Enter the code 4000 using “left”, “right”, “top”and “bottom” push buttons
Press “validation” push button to enter
532_212_a 9/02/05 9:00 Page 38
Control and Test modes
> Exit control or test modes
Press “ESC” push button
The new operational mode (automatic or manual) depends on information from masterATyS (6e, 6m ou C30)
> Control or Test modes use
Direct access by pressing and
To start a test (off load or on load) or to control the changeover switch electrically,
press , and push buttons
Remote interfaces ATyS
OPERATION
39SOCOMEC - Réf.: 532 212 A
532_212_a 9/02/05 9:00 Page 39
Operational sequences
Visualisation
Refer to ATyS 6e, 6m or C30 manuals for moreinformation on operational sequences and controls:• sources control,• tests cycles,• loss of priority source sequence,• priority source return sequence.
It is possible to display controlled parameters in bothautomatic and manual modes (but not during program-ming).No code is required to perform visualisation.Permutation cycles have priority over visualisation anddisplay timer countdown during cycle operation.
Without keypad activation or any operational sequenceduring 5 minutes, the LCD comes back to default displaymode and stops the backlight.
> If both sources are available:• One visualisation screen is split into 2 parts and
displays simultaneously voltage and frequency valueson both networks.
• If a timer is active, on one of the source, its count-down is displayed instead of voltage and frequencyvalues.
Examples:
> If only one source is present:• During permutation cycle, voltage and frequency
values of the available source (active) are displayedon 2 lines. The name of the active timer and its count-down are displayed on remaining 2 lines.
• Out of a permutation cycle, phase to phase voltagesand frequency are displayed.
Examples:
Remote interfaces ATySOPERATIONATyS D20
40 SOCOMEC - Réf.: 532 212 A
DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation
Press “left”, “right”, “top” & “bottom” push buttonsto access available screens
Press “navigation” push button to navigate in visualisation, displaying all available screens
ATY
S 3
31 A
ATY
S 3
32 A
532_212_a 9/02/05 9:00 Page 40
Visualisation
ARCHITECTURE OF VISUALISATION MENU
Remote interfaces ATyS
OPERATION
41SOCOMEC - Réf.: 532 212 A
*
**
***
****
***
***
***
***
* only on AtyS 6e & 6m** only U3-1 on AtyS C30*** only on ATyS 6m**** visible if option LS selected and active
ATY
S 3
33 A
532_212_a 9/02/05 9:00 Page 41
532_212_a 9/02/05 9:00 Page 42
532_212_a 9/02/05 9:00 Page 43
SOCOMEC - Ref.: 532 212 A - 02/05