AFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC GROUP SWITCHING PROTECTION & UPS MAKE YOUR BUSINESS SAFE

Transcript of 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS...

Page 1: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

AFFICHEURS DÉPORTÉS - REMOTE INTERFACES

ATyS D10 & D20Notice d’utilisation - Operating instructions

F GB

SOCOMEC GROUP SWITCHING PROTECTION & UPS

MAKE YOUR BUSINESS SAFE

532_212_a 9/02/05 9:00 Page 1

Page 2: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

SOCOMEC - Réf. : 532 212 A2

PRÉSENTATION GÉNÉRALE ATyS D10 et D20 _______3INSTALLATION ATyS D10 et D20 ___________________4

Montage _______________________________________4Raccordements _________________________________4Caractéristiques_________________________________4

UTILISATION ATyS D10 ___________________________5Affichage_______________________________________5

UTILISATION ATyS D20 ___________________________6Affichage_______________________________________6Clavier _________________________________________7Version logiciel __________________________________7Programmation _________________________________8Exploitation____________________________________18Fonctionnement________________________________20Visualisation ___________________________________20

Som

mai

re

F

GENERAL PRESENTATION ATyS D10 & D20________23INSTALLATION ATyS D10 & D20___________________24

Mounting _____________________________________24Connection____________________________________24Characteristics_________________________________24

OPERATION ATYS D10___________________________25Display _______________________________________25

OPERATION ATyS D20 ___________________________26Display _______________________________________26Keypad _______________________________________27Software version _______________________________27Programming __________________________________28Control and Test modes_________________________38Operational sequences__________________________40Visualisation ___________________________________40

Sum

mar

y

GB

532_212_a 9/02/05 9:00 Page 2

Page 3: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

ATyS D10 and D20 models are remote interfacesdesigned for easy integration on front panels. They canbe connected to ATyS 6e, 6m and C30 products to allowremote access to display or control features.

23SOCOMEC - Réf.: 532 212 A

Remote interfaces ATySGENERAL PRESENTATIONATyS D10 & D20

532_212_a 9/02/05 9:00 Page 23

Page 4: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

Mounting

• Door fixing: 2 holes, diameter 22.5 mm• Maximum thickness of the door: 20 mm

Connection

Connection only on AtyS 6e, 6m or C30 products.

> CableRJ45 type 8/8 not isolated

> Maximum cable length3 m

> Tightning torque4 N.m

Characteristics

> IPIP21 standardIP54 using gasket

> Operation• Temperature: -10 to + 55 °C• hygrometry: 80% humidity at 55 °C

95% humidity at 40 °C

Remote interfaces ATySINSTALLATIONATyS D10 & D20

24 SOCOMEC - Réf.: 532 212 A

1

ATY

S 1

47 A

(1) RJ45 plug for ATyS connection

Ø 22.5

4036

20

= =

96 x 96

ATY

S 1

61 A

Door drilling

ATyS C30

Type RJ45

ATyS D10/D20

43

21

ATY

S 3

13 A

GB

532_212_a 9/02/05 9:00 Page 24

Page 5: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

25SOCOMEC - Réf.: 532 212 A

ATyS D10 allows remote display of transfer systempositions, sources availability and operational mode.Programming and operations remain available directly onmaster product (ATyS 6e, 6m or C30).

Remote interfaces ATySOPERATIONATyS D10

Display

Source 1 available Power On

• ATyS Product faulty, transfer error• Possible to reset after error

disappearance the power suppliesof the master product (ATyS 6e,6m, C30) for 3 minutes

Transfer system inposition 1

Transfer system inAutomatic mode

Transfer system inposition 0

Transfer system inposition 2

Source 2 available

ATY

S 1

45 B

532_212_a 9/02/05 9:00 Page 25

Page 6: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

Remote interfaces ATySOPERATIONATyS D20

26 SOCOMEC - Réf.: 532 212 A

DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation

Display

ATyS D20 allows remote display of transfer systempositions, sources availability, operational mode andmetering. Programming and operations (Test andControl) are also available. Master product (ATyS 6e, 6mor C30) display is deactivated as soon as the remoteinterface is connected.

Power On

Source 1 available

Manualmodeactive Padlock*

• Product faulty, transfer error• Possible to reset after error

disappearance: switch off thepower supplies of the masterproduct (ATyS 6e, 6m, C30)for 3 minutes

Transfer system inposition 1

Transfer system inautomatic mode

Control mode active Test mode active Programming mode active

Transfer systemin position 0

Transfer systemin position 2

Source 2 available

ATY

S 1

46 B

* only on ATyS 6e and 6m

532_212_a 9/02/05 9:00 Page 26

Page 7: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

Display

Software version

Keypad

Software version of the master product is displayedimmediately after ATyS 6e, 6m or C30 power on.

Access to AUT, Test,Control and Prog modes

Direct Access to Test and Controlfunctionalities or navigation

Allows main menu accessin visualisation mode orvalidation

Priority source

Informations• source 1• source 2• sources 1 & 2(split screen)

Power factorCapacitive or inductive

Phases (wires) displayed Units

Values

Signedvalues(power)

ATY

S 3

18 A

ATY

S 1

46 C

ATY

S 3

19 A

Remote interfaces ATyS

OPERATION

27SOCOMEC - Réf.: 532 212 A

532_212_a 9/02/05 9:00 Page 27

Page 8: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

Remote interfaces ATySOPERATIONATyS D20

28 SOCOMEC - Réf.: 532 212 A

DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation

> Enter into programming mode

• Step 1: Press the “mode” push button until Prog led is blinking

• Step 2: Press “validation” push button. PROG led becomes fixed and access code is displayed

• Step 3: Enter access code (1000 factory default) using keypad “left”,“right”, “top” and “bottom”

• Step 4: Press “validation” push button to enter programming mode

> Programming mode exit

• Step 1: Press the “ESC” push button when not entering any value, to come back to mainprogramming menu

• Step 2: Press again on “ESC” push button to exit programming

New Active mode (Automatic or Manual) depends on information from the master device (ATyS 6e, 6m ou C30)

Programming

532_212_a 9/02/05 9:00 Page 28

Page 9: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

Programming

> Navigation in programming mode

• Step 1: To access required menu, press navigation push buttons“left” and “right”

• Step 2: To access parameter to modifypress navigation push buttons “top” and “bottom”

• Step 3: To modify the parameter, press push button “right”to make the required parameter blinking

• Step 4: Press push buttons “top” and “bottom” to increment ordecrement the value of the parameter

• Step 5: Press “validation” push button to validate

In case of parameter displayed on 2 lines, press “validation” push button after first line modificationto access next one

“ESC” push button allows to come back to main menu or to cancel the modification

Remote interfaces ATyS

OPERATION

29SOCOMEC - Réf.: 532 212 A

532_212_a 9/02/05 9:00 Page 29

Page 10: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

Programming

ARCHITECTURE OF THE PROGRAMMING MENU

Remote interfaces ATySOPERATIONATyS D20

30 SOCOMEC - Réf.: 532 212 A

DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation

*

**** ** ** ** **

** **** **

**

** ** **

ATY

S 3

27 A

532_212_a 9/02/05 9:00 Page 30

Page 11: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

Remote interfaces ATyS

OPERATION

31SOCOMEC - Réf.: 532 212 A

*on

ly o

n A

tys

6m**

optio

n on

ATy

S 6

e &

6m

***

only

on

ATyS

C30

****

visi

ble

if o

ptio

n LS

sel

ecte

d a

nd a

ctiv

e

** ** ** ** ****

**

***

***

***

532_212_a 9/02/05 9:00 Page 31

Page 12: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

Programming

VARIABLES CHARACTERISTICS

Remote interfaces ATySOPERATIONATyS D20

32 SOCOMEC - Réf.: 532 212 A

DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation

> Setup

LCD Denomination Setting range Default values

nt Type of network 1BL, 2BL, 2NBL 4NBL(cf. ATyS 6 or C30 instruction manual) 3NBL, 4NBL,

41NBL, 42NBL

Un Network Nominal voltage 100 to 480 V 400 VPhase-Neutral voltage for 1BL & 41NBLPhase-Phase voltage for others

ScE** Source 1 - Switch I or II configuration I, II ISource 1 (controlled and displayed) linked to switch I or II (depending on cabling)

Fn Network nominal Frequency 50 or 60 Hz 50 Hz

Ct* CTs primary current 50 to 5000/5 A 500/5 A(5 A secondary CT)

Gen Genset start signal state NO, NC NONormally opened or closed

Pri Network priority selection 1, 2 1Keypad selection (1 or 2)Also possible via external contactUsing option

Mtf Manual Retransfer Yes, No NoActivation of the feature

LoG Type of control logic selection IMP, CON, brE*** IMPImpulse, contactor or breaker***

AC*** Number of position auxiliary contacts used, depending on transfer 0, 2, 3 2device type (switch, contactor, breaker)

rn1 Allows 0 position command after loss of main source (source 1) Yes, No No

rn2 Allows 0 position command after loss of emergency source (source 2) Yes, No No

CrS Number of permutation counter Reset Yes, No No

CP Programming code modification 0001 to 9999 1000Possible to change the code

* only on AtyS 6m** only on ATyS 6e & 6m*** only on ATyS C30.

532_212_a 9/02/05 9:00 Page 32

Page 13: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

Programming

> Voltage thresholds

> Frequency thresholds

Remote interfaces ATyS

OPERATION

33SOCOMEC - Réf.: 532 212 A

LCD Denomination Setting range Default values

oU Network 1 over voltage threshold 102 - 120% 115%

oUh Network 1 over voltage threshold hysteresis 101 - 119% 110%(< oU)

uU Network 1 under voltage threshold 80 - 98% 85%

uUh Network 1 under voltage threshold hysteresis 81 - 99% 95%(> uU)

oU Network 2 over voltage threshold 102 - 120% 115%

oUh Network 2 over voltage threshold hysteresis 101 - 119% 110%(< oU)

uU Network 2 under voltage threshold 80 - 98% 85%

uUh Network 2 under voltage threshold hysteresis 81 - 99% 95%(> uO)

Values defined are % of nominal values.Hysteresis thresholds must be programmed according to over and under voltage thresholds (respectively under & above).

LCD Denomination Setting range Default values

oF Network 1 over frequency threshold 101 to 120% 105%

oFh Network 1 over frequency threshold hysteresis 100.5 - 119.5% 103%(< oF)

uF Network 1 under frequency threshold 80 - 99% 95%

uFh Network 1 under frequency threshold hysteresis 80.5 - 99.5% 97%(> uF)

oF Network 2 over frequency threshold 101 - 120% 105%

oFh Network 2 over frequency threshold hysteresis 100.5 - 119.5% 103%(< oF)

uF Network 2 under frequency threshold 80 - 99% 95%

uFh Network 2 under frequency threshold hysteresis 80.5 - 99.5% 97%(> uF)

Values defined are % of nominal values.Hysteresis thresholds must be programmed according to over and under frequency thresholds (respectively under & above).

532_212_a 9/02/05 9:00 Page 33

Page 14: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

Programming

Remote interfaces ATySOPERATIONATyS D20

34 SOCOMEC - Réf.: 532 212 A

DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation

> Timers

LCD Denomination Setting range Default values

Mft Main Failure Timer From 0 to 60 s 5 sDelays priority network failure detection

dtt Delay on transfer timer From 0 to 60 s 5 sEmergency network stability validation before transfer

OMf O Main Failure Timer From 0 to 20 s 0 sRest in O position when transferringfrom main network to emergency network

Mrt Main Return Timer From 0 to 30 min 1 minMain network stability validation before re-transfer

OMr O Main Return Timer From 0 to 20 s 5 sRest in O position when re-transferring from emergency network to main network

Cdt Cool Down Timer From 0 to 10 min 4 minAllows generator cooling down period after load’sretransfer from emergency source (generator) to Main source

> Communication

LCD Denomination Setting range Default values

Add Device address 1 to 247 5

bd Communication speed 2400, 4800, 9600, 960019200, 38400

StoP Stop bit 1, 2 1

PAr Parity bit No, Odd, Even No

Only on ATyS 6e or 6m in case of optional communication module.

532_212_a 9/02/05 9:00 Page 34

Page 15: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

• Input (In2, Ft2) and output (Ou1, S1A) programming example:

Refer to ATyS C30, 6e or 6m instruction manualfor terminals identification.

Input/Output Function Relay State

I1 to I4 Ft1, Ft2, Ft3, Ft4, Pri, NO or NCMtf, S2A, Man, TOL, TFL, EJP, CTS

O1 to O4 S1A, S2A, LS, / NO

ATY

S 3

28 A

• Step 1: Press “right” push button to makefirst variable blinking (Ft2 ou S1A)

• Step 2: press “top” and “bottom”push buttons to modify the variable

• Step 3: press “validation”

• Step 4: press “bottom” push button toacces nO variable selection

Programming

> Inputs/Outputs• 2 inputs (In1, In2) and 2 outputs (Ou1, Ou2) as standard

on ATyS C30.

• Possibility to connect 2 modules 2 Inputs/2 Outputson ATyS 6e & 6m.

- First module: In1, In2, Ou1, Ou2- Second module In3, In4, Ou3, Ou4.

Remote interfaces ATyS

OPERATION

35SOCOMEC - Réf.: 532 212 A

532_212_a 9/02/05 9:00 Page 35

Page 16: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

Outputs

Programming

• Variables descriptionInputs

Remote interfaces ATySOPERATIONATyS D20

36 SOCOMEC - Réf.: 532 212 A

DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation

Variable Description

Ft1 Fault input 1. The fault led is blinking as soon as the input is active andFt1 is displayed on LCD. Reset when the input is de-activated

Ft2 Fault input 2. The fault led is blinking as soon as the input is active and Ft2 is displayed on LCD.Reset when the input is de-activated

Ft3* Fault input 3. The fault led is blinking as soon as the input is active and Ft3 is displayed on LCD. The transfer switch is immediately driven in 0 position.Keypad action (Esc) necessary to Reset the fault

Ft4* Fault input 4. The fault led is blinking as soon as the input is active and Ft4 is displayed on LCD. The transfer switch is immediately driven in 0 position.Keypad action (Esc) necessary to Reset the fault

Pri Priority network selection.Network 1 has priority when input is not activated. Network 2 has priority if input is active

Mtf Remote manuel re-transfer. Feature identical to manual re transfert on keypad.Re-transfer from priority network to backup network is allowed from input activation (1 s front).The Mtf variable in the setup menu must be selected (Yes) to allow input recognition

S2A Information source 2 available (Genset) used instead of voltage/ frequency measurementfrom ATyS (inhibited when S2A is selected)

Man** Information transfer system in manual mode.All automatic commands (+ test on load and control commands) are inhibited as soon as the input is activated

CTS** Remote transfer control. Possible to initiate transfer from priority source to backup sourcebefore DTT ends. If DTT is set to its maximum value (60s), the transfer is initiated as soon asthe input is activated (1 s front)

TOL** Remote test on load. Started from input activation.Re-transfer is blocked until input de-activation

TFL Remote test off load.Started from input activation (remote genset start /stop)

EJP 2 inputs one automatically affected to EJP• input 1 for EJP advice, to start generator• input 2 to transfer on emergency sourceRetransfer is activated when input 2 disapears

* only on ATyS C30, specific fault operation (Ft2 and Ft3)** only as option on ATyS C30, standard features on ATyS 6e et 6m.

Variable Description

S1A Source 1 available.Output activated as soon as source 1 is considered available (similar to front led source 1)

S2A Source 2 available.Output activated as soon as source 2 is considered available (similar to front led source 2)

LS Load shedding relay. LS timer corresponds to time available to disconnect the shed loads.The relay is activated before permutation on standby network according to LS timer.The relay is de-activated after retransfer on mains network and LS timer countdown

532_212_a 9/02/05 9:00 Page 36

Page 17: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

Programming

Remote interfaces ATyS

OPERATION

37SOCOMEC - Réf.: 532 212 A

LOAD SHEDDING CONFIGURATIONLS variable allows associated LS timer configuration.

Output Associated funciton Setting range Default value

O1 to O4 LS 0 to 60 s (≤ DTT)* 2

> Example: load shedding configuration

function

timer

• Step 1: Press “right” push button to makefirst variable blinking (LS)

• Step 2: press push buttons “top” and“bottom” to modify the variable

• Step 3: Press “validation”

• Step 4: Press “bottom” push buttonto access timer value configuration

ATY

S 3

29 A

GB

* In case of DTT variable configuration below LS, LS will be automatically set to to DTT value.

532_212_a 9/02/05 9:00 Page 37

Page 18: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

Control and Test modes

It is possible to start test sequences or to controlelectrically the changeover system from keypad.

NAVIGATION

Remote interfaces ATySOPERATIONATyS D20

38 SOCOMEC - Réf.: 532 212 A

DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation

> Enter Control or Test modes

• Step 1: Press “mode” push button to make test or control led blinking

• Step 2: Press “validation” push button to make control or test led become fixed

CONTROL MODE

Access code is displayed directly

TEST MODE

It is possible to test leds and LCD without entering any code by pressing directly

Test on load or test off load access codes are displayed after pressing or

Enter the code 4000 using “left”, “right”, “top”and “bottom” push buttons

Press “validation” push button to enter

532_212_a 9/02/05 9:00 Page 38

Page 19: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

Control and Test modes

> Exit control or test modes

Press “ESC” push button

The new operational mode (automatic or manual) depends on information from masterATyS (6e, 6m ou C30)

> Control or Test modes use

Direct access by pressing and

To start a test (off load or on load) or to control the changeover switch electrically,

press , and push buttons

Remote interfaces ATyS

OPERATION

39SOCOMEC - Réf.: 532 212 A

532_212_a 9/02/05 9:00 Page 39

Page 20: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

Operational sequences

Visualisation

Refer to ATyS 6e, 6m or C30 manuals for moreinformation on operational sequences and controls:• sources control,• tests cycles,• loss of priority source sequence,• priority source return sequence.

It is possible to display controlled parameters in bothautomatic and manual modes (but not during program-ming).No code is required to perform visualisation.Permutation cycles have priority over visualisation anddisplay timer countdown during cycle operation.

Without keypad activation or any operational sequenceduring 5 minutes, the LCD comes back to default displaymode and stops the backlight.

> If both sources are available:• One visualisation screen is split into 2 parts and

displays simultaneously voltage and frequency valueson both networks.

• If a timer is active, on one of the source, its count-down is displayed instead of voltage and frequencyvalues.

Examples:

> If only one source is present:• During permutation cycle, voltage and frequency

values of the available source (active) are displayedon 2 lines. The name of the active timer and its count-down are displayed on remaining 2 lines.

• Out of a permutation cycle, phase to phase voltagesand frequency are displayed.

Examples:

Remote interfaces ATySOPERATIONATyS D20

40 SOCOMEC - Réf.: 532 212 A

DisplayKeypadSoftware versionProgrammingControl and Test modesOperational sequencesVisualisation

Press “left”, “right”, “top” & “bottom” push buttonsto access available screens

Press “navigation” push button to navigate in visualisation, displaying all available screens

ATY

S 3

31 A

ATY

S 3

32 A

532_212_a 9/02/05 9:00 Page 40

Page 21: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

Visualisation

ARCHITECTURE OF VISUALISATION MENU

Remote interfaces ATyS

OPERATION

41SOCOMEC - Réf.: 532 212 A

*

**

***

****

***

***

***

***

* only on AtyS 6e & 6m** only U3-1 on AtyS C30*** only on ATyS 6m**** visible if option LS selected and active

ATY

S 3

33 A

532_212_a 9/02/05 9:00 Page 41

Page 22: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

532_212_a 9/02/05 9:00 Page 42

Page 23: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

532_212_a 9/02/05 9:00 Page 43

Page 24: 532 212 a 9/02/05 9:00 Page 1 AFFICHEURS DÉPORTÉS · PDF fileAFFICHEURS DÉPORTÉS - REMOTE INTERFACES ATyS D10 & D20 Notice d’utilisation - Operating instructions F GB SOCOMEC

SOCOMEC - Ref.: 532 212 A - 02/05

This document is not contractual. SOCOMEC reservesthe right to modify features without prior notice in view ofcontinued improvements.

H E A D O F F I C ESOCOMEC GROUP SWITCHGEAR AND UPSS.A. capital 10 923 800 € - R.C. Strasbourg 548500 149 B1, rue de Westhouse - B.P. 10 - 67235 Benfeld CedexTél. +33 03 88 57 41 41 Fax +33 03 88 57 78 78

S A L E S M A N A G E M E N T D I V I S I O NSOCOMEC95, rue Pierre Grange 94132 Fontenay-sous-Bois Cedex Tél. +33 01 45 14 63 90Fax +33 01 45 14 63 38

www.socomec.com

532_212_a 9/02/05 9:00 Page 44