2002 IS Catalog
138 Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Page
Introduction ............................................................................................................................. 139Loop-Powered Isolators
KFD0-CS-1.50 (Current repeater / driver / isolator / single-channel) .................................................. 140KFD0-CS-2.50 (Current repeater / driver / isolator / dual-channel) ..................................................... 141KFD0-CC-1 (Current converter / single channel / isolator) .................................................................. 142KFD0-VC-1.50m (Voltage to current converter / single-channel / isolator) ......................................... 143KFD0-VC-1.10 (Voltage to current converter / single-channel / isolator) ............................................ 144KFD0-TT-1 (Thermocouple / mV input / single-channel / isolator) ...................................................... 145KFD0-TR-1 (RTD input / single-channel / isolator) .............................................................................. 146
Analog IsolatorsKFDX-DCI (DC current input / current/voltage output / isolator) ......................................................... 147KFDX-DCV (DC voltage input / current/voltage output / isolator) ....................................................... 148KFD2-CR-1.300 (2- or 3-wire transmitter input / 4-20 mA current output / isolator) .......................... 149KFD2-CD-1.32 (Current/voltage driver / current output / isolator) ...................................................... 150KFD2-CR4-1.20 (Single input / dual output transmitter / repeater / isolator) ...................................... 151KFD2-STC4-1.20 (HART transmitter power supply / isolator) ............................................................. 152KFDX-RTD (RTD input / current/voltage output / isolator) .................................................................. 153KFDX-TC (Thermocouple input / isolator) ........................................................................................... 154KFD2-UT-1 (Universal temperature input / isolator) ............................................................................. 155KFD2-UT-1-1 (Universal temperature input / isolator) ......................................................................... 156KFDX-AC (AC current/voltage input / current/voltage output / isolator) ............................................. 157KFDX-HZ (Frequency input / current/voltage output / isolator) .......................................................... 158KFA5-DWB-1.D (Rotational speed limit alarm) .................................................................................... 159KFA6-DWB-1.D (Rotational speed limit alarm) .................................................................................... 160KFD2-DWB-1.D (Rotational speed limit alarm) ................................................................................... 161KFU8-UFC-1 (Universal frequency converter) ..................................................................................... 162KFD2-UFC-1.D (Universal frequency converter with display) .............................................................. 163KFD2-UFC-1 (Universal frequency converter / isolator) ...................................................................... 164KFU8-UFC-1.D (Universal frequency converter / isolator with display) ............................................... 165
Limit Alarm IsolatorsKFDA-DCI (DC current input / 2 Form C contact outputs / isolator) ................................................... 166KFDA-DCV (DC voltage input / 2 Form C contact outputs / isolator) .................................................. 167KFD2-GS-1.2W (DC current/voltage input / 2 Form C contact outputs / isolator) .............................. 168KFD2-CRG-1.D (Transmitter power supply / isolator) ......................................................................... 169KFU8-CRG-1.D (Transmitter power supply / isolator) ......................................................................... 170KFDA-TC (Thermocouple input / 2 Form C contact outputs / isolator) ............................................... 171KFDA-RTD (RTD input / 2 Form C contact outputs / isolator) ............................................................ 172KFDA-GU-1 (Universal input / 2 Form C contact outputs / PC interface / isolator) ............................ 173
2002 IS Catalog
139Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
With the variety of process control systems available, it is often necessary to convert an input signal intoa format that the control system will accept. Signal conditioners take signals from an assortment of fieldinstruments such as thermocouples and RTDs, and convert those signals into any of several standardinstrument signals (1-5 V, 4-20 mA, etc.) while providing isolations.
Signal conditioners are also beneficial to the accurate transfer of these signals and the elimination ofground loops.
Pepperl+Fuchs signal conditioners utilize the latest technology, offering unparalleled protection againstground loops while maintaining optimum signal accuracy and complete isolation. There are three basictypes of KF signal conditioners:
Loop Powered Repeaters/Isolators: Loop powered repeaters do not require a separatepower supply. Available in single and dual channel models, these transformer isolatedsignal conditioners transfer analog DC signals with each channel working as a DC isolatorproviding 2,500 VDC isolation between the input and output.
Analog Isolators: These units require a separate power supply and provide signalconditioning and 3-way isolation to various input signals.
Limit Alarms: This class of signal conditioners provides two Form C relay outputs withadjustable high and low switchpoints and selectable control safe and normal operation.They also require a separate power supply and provide 3-way isolation.
The latter two categories are fully field-configurable and provide 1,800 VDC isolation separating input,output and power supply. Input and output ranges, modes of operation, switchpoints, etc., can beprogrammed in the field via DIP switches on the side of the housing. Some models also offer a PCinterface. Input, zero, and span are adjustable by potentiometer to 50% for all input ranges. The wide-ranging capabilities and field-configurable settings allow for numerous options in a diverse range ofapplications.
All P+F analog isolators and limit alarms also contain the ASIC chip for increased reliability. ASIC (Appli-cation Specific Integrated Circuitry) substantially reduces failures by virtually eliminating discrete com-ponents and their solder joints where most faults occur. Printed circuit board connections are reducedby 70%.
Introduction
140
Technical Data
Connection Diagram
Model Number
2002 IS CatalogS
ignal C
ondit
ioners
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
The KFD0-CS-1.50 current repeater is afully floating isolator for standard 4-20 mAinstruments. The inputs are galvanicallyisolated from the outputs. Typicalapplications include driving I/P convertersand isolating 2-wire transmitters.
OPERATION:
The KFD0-CS-1.50 is a single-channeldevice that does not require a separatepower supply. Due to the 24 VDC inputvoltage limitation and the internal voltagedrop, the maximum output voltage underload is 23 VDC. The maximum internalresistance is 230 ohms. At input voltagesgreater than 26.1 V, the internal voltagedrop is lower than with input voltagesbelow 26.1 V.
KFD0-CS-1.50
4-20 mA isolator
Single-channel
Loop powered
Power Supply Loop powered (not intrinsically safe)Nominal voltage 12-35 VDC
Input Terminals 11+, 12-Input voltage (Vin) 10-35 VDCInput current (Uin) 4-20 mA
Power Dissipation@ 25 mA (Vin < 26.1 V) < 150 mW@ 25 mA (Vin > 26.1 V) < 400 mW
Output Terminals 1, 2Output voltage: 10 V < Vin < 26.1 V 0.9 x Vin - (0.23 x current in mA) - 0.7 Vin > 26.1 V 23 V - (0.23 x current in mA)Output current 4-20 mAShort circuit current ≤ 65 mA @ Vin>26.1 VTransfer current ≤ 40 mA
Transfer CharacteristicsCalibrated accuracy ±20 µA for 1 kΩ load @ 20ºC
(includes linearity and hysteresis)Temperature drift ≤ 2 µA / ºCResponse time ≤ 5 ms (@ 4-20 mA and Vin < 26 V)Isolation 2500 VDC
MechanicalHousing: Material Makrolon Style KF style (see page 387) Mounting 35mm DIN rail or surface mountDimensions (mm) 115 x 20 x 118Weight 100 g (3.5 oz.)
Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)
Current Repeater/Driver SingleChannel Isolator
KFD0-CS-1.50
OutputInput2 (–)
1 (+) (+) 11
(– ) 12
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
141
Technical Data
Connection Diagram
Model Number
2002 IS Catalog
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Sig
nal C
onditio
ners
CurrentRepeater/DriverDual Channel Isolator
The KFD0-CS-2.50 current repeater is afully floating isolator for standard 4-20 mAinstruments. Each channel works as a DCisolator with the inputs galvanically isolatedfrom the outputs. Typical applicationsinclude driving I/P converters and isolating2-wire transmitters.
OPERATION:
The KFD0-CS-2.50 is a dual-channeldevice that does not require a separatepower supply. Due to the 24 VDC inputvoltage limitation and the internal voltagedrop, the maximum output voltage underload is 23 VDC. The maximum internalresistance is 230 ohms. At input voltagesgreater than 26.1 V, the internal voltagedrop is lower than with input voltagesbelow 26.1 V.
KFD0-CS-2.50
4-20 mA isolator
Dual-channel
Loop powered
KFD0-CS-2.50
Output 1Input 12 (– )
1 (+)
Output 25 (– )
4 (+)
Input 2
(– ) 12
(+) 11
(– ) 10
(+) 9
(+) 8
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
Power Supply Loop powered (not intrinsically safe)Nominal voltage 12-35 VDC
Input Terminals 11+, 12- ; 8+, 9+, 10-Input voltage (Vin) 10-35 VDCInput current (Uin) 4-20 mA
Power Dissipation@ 25 mA (Vin < 26.1 V) < 150 mW@ 25 mA (Vin > 26.1 V) < 400 mW
Output Terminals 1+, 2-; 4+, 5-Output voltage: 10 V < Vin < 26.1 V 0.9 x Vin - (0.23 x current in mA) - 0.7 Vin > 26.1 V 23 V - (0.23 x current in mA)Output current 4-20 mAShort circuit current ≤ 65 mA @ Vin>26.1 VTransfer current ≤ 40 mA
Transfer CharacteristicsCalibrated accuracy ±20 µA for 1 kΩ load @ 20ºC
(includes linearity and hysteresis)Temperature drift ≤ 2 µA / ºCResponse time ≤ 5 ms (@ 4-20 mA and Vin < 26 V)Isolation 2500 VDC
MechanicalHousing: Material Makrolon Style KF style (see page 387) Mounting 35mm DIN rail or surface mountDimensions (mm) 115 x 20 x 118Weight 100 g (3.5 oz.)
Ambient Temperature -20ºC to +60ºC (-4ºF to +140ºF)
142
Technical Data
Connection Diagram
Model Number
2002 IS CatalogS
ignal C
ondit
ioners
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
The KFD0-CC-1 loop powered, 2-wireisolator that converts 2-wire voltage/current signals to a 4-20 mA signal.
The KFD0-CC-1 provides galvanicisolation for the loop. The required inputrange is set by a switch on the side of theunit. Zero and span adjustment areachieved by potentiometers on the top ofthe isolator.
KFD0-CC-1
Field selectable voltage orcurrent input
Loop-powered
Isolation of input/output
Power Supply Loop powered (not intrinsically safe)Nominal voltage 12-35 VDC
Input (selectable) Terminals 1+, 2-Input 0-20 mACurrent load ≤ 50 ΩInput voltage (Vin) 0-10 VDCVoltage load ≤ 100 kΩ
Output Terminals 9+, 8-Output 4-20 mABurnout fault signal Downscaled ≤ 3 mALoad/Ohm (Us - 12 V) / 0.02 A
Transfer CharacteristicsVoltage surge 6.5 ppm / VCalibrated accuracy ±0.1% of final value @ 20ºCLinearity fault ≤ 0.04% of final valueTemperature drift 0.050% of range / ºC
0.060% of span / ºCResponse time ≤ 250 msGalvanic Isolation safe isolated per DIN VDE 01061
design isolation voltage 253 VEff
MechanicalHousing: Material Makrolon Style KF housing (see page 387) Mounting 35mm DIN rail or surface mountDimensions (mm) 115 x 20 x 118Weight 100 g (3.5 oz.)Protection (IEC) IP20
OperatingTemperature -20ºC to +60ºC (-4ºF to +140ºF)
Current/VoltageConverter SingleChannel Isolator
KFD0-CC-1
Input Output8 (– )
9 (+)
(– ) 2
(+) 1
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
143
Technical Data
Connection Diagram
Model Number
2002 IS Catalog
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Sig
nal C
onditio
ners
Voltage to CurrentConverter SingleChannel Isolator
The KFD0-VC-1.50m receives a -50 to+50 mV signal input and produces a 4-20mA output. This loop powered module alsoprovides galvanic isolation.
The sensing range of the bipolar input unitisolates and conditions a 4-20 mA output.Fine adjustment for zero and span areperformed with the potentiometer on topof the unit.
Optional lead monitoring is available by thefield configurable DIP switches. Enablingthis feature produces an output ≤ 3 mAwhen the input wire is broken, whiledisabling produces an output ≥ 22 mA.
KFD0-VC-1.50m
-50 mV to + 50 mV voltage incurrent output isolator
Loop powered
Lead breakage monitoring
Power Supply Loop powered (not intrinsically safe)Nominal voltage 12-35 VDC
Input Terminals 1+, 3-Input voltage -50 to + 50 mVInput current Input monitoring on ≤ 15 nA
Input monitoring off ≤ 1 nA
Output Terminals 9+, 8-Output 4-20 mALead breakage enabled: ≤ 3 mA; disabled: ≥ 22 mA
Transfer CharacteristicsSensing range - 50 mV to +50 mV
Zero point 1% of final valueSpan ± 3.5% of final value
Temperature drift Zero point 0.01% of the span / ºC or±1 µV / ºC (whichever is larger)Span 0.005% of span / ºC
Response time ≤ 250 msGalvanic isolation safe isolated per DIN VDE 01061
design isolation voltage 253 VEff
MechanicalHousing: Material Makrolon Style KF housing (see page 387) Mounting 35mm DIN rail or surface mountDimensions (mm) 115 x 20 x 118Weight 100 g (3.5 oz.)Protection (IEC) IP20
Ambient Temperature -20ºC to +60ºC (-4ºF to +149ºF)
KFD0-VC-1.50m
Input Output8 (– )
9 (+)
(– ) 3
(+) 1
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
144
Technical Data
Connection Diagram
Model Number
2002 IS CatalogS
ignal C
ondit
ioners
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
The KFD0-VC-1.10 receives a -10 to +10voltage input and produces a 4-20 mAsignal output. This loop powered modulealso provides galvanic isolation.
The sensing range of the bipolar input unitisolates and conditions a 4-20 mA output.Fine adjustment for zero and span areperformed with the potentiometer on topof the unit.
KFD0-VC-1.10
-10 to +10 voltage input/4-20mA output
Loop powered
Isolation of input/output
Power Supply Loop powered (not intrinsically safe)Nominal voltage 12-35 VDC
Input Terminals 1+, 2-Input -10 to +10 VLoad ≥ 100 kΩ
Output Terminals 9+, 8-Output 4-20 mA, ≤ 35 mALoad (Ohm) ≤ (power supply - 12 V) / 0.02 A
Transfer CharacteristicsOperating voltage 6.5 ppm / VCalibrated accuracy 0.1% of final valueLinearity faults ≤ 0.04% of final valueSensing range -10 V to +10 V
Span ± 1.5% of final valueZero point ±1% of final value
Temperature drift Span 0.005% of span / ºCZero point 0.060% of span / ºC
Response time 250 msGalvanic isolation Function isolation per EN 50178
design isolation voltage 253 Veff
MechanicalHousing Material Makrolon Style KF housing (see page 387)Dimensions (mm) 115 x 20 x 118Weight 100 g (3.5 oz.)Protection IP20
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
Voltage to CurrentConverter SingleChannel Isolator
KFD0-VC-1.10
Input Output8 (– )
9 (+)
(– ) 2
(+) 1
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
145
Technical Data
Connection Diagram
Model Number
2002 IS Catalog
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Sig
nal C
onditio
ners
Thermocouple/mV Input SingleChannel Isolator
The KFD0-TT-1 is a loop powered isolatorthat accepts thermocouple inputs andconditions to a 4-20 mA output.
Types E, J, K, N, R, S, and T thermocoupleinputs with internal cold junctioncompensation (CJC) with galvanicisolation. The input voltage is linear tooutput current, not proportional totemperature. Adjustable zero, span andburnout detection are field-configurable.
KFD0-TT-1
Internal CJC
Loop powered
Lead breakage and short circuitmonitoring
Input/output isolation
Field-selectable thermocouple inputs
Power Supply Loop powered (not intrinsically safe)Nominal voltage 12-35 VDC
Input Terminals 1+, 2-, 3-Thermocouple (terminals 1,2,3) E,J,K, N,R,S or T (CJC reference to 0ºC)
Input current Input monitoring ‘ON’ ≤ 15 nAInput monitoring ‘OFF’ ≤ 1 nA
Output Terminals 9+, 8-Output 4-20 mA, ≤ 35 mALead breakage Downscaled ≤ 3 mA
Upscaled > 22 mALoad (power supply - 12 V) / 0.02 A
Transfer CharacteristicsVoltage surge 6.5 ppm / VMeasuring range (adjustable) Span 4 to 60 mV
Zero point -12 to 60 mVCharacteristics Output voltage is proportional to inputCalibrated accuracy 0.1% of final value ±1ºC for cold pointTemperature drift Span 0.005% of span / ºC
Zero point 0.01% of span / ºC or ±1µV/ºC0.01% of span/ºC or ±0.03ºC/ºC (J,K,N,T,E)0.01% of span/ºC or ±0.06ºC/ºC (R, S)Cold point ±2.0ºC (calibrated at TA = 20ºC)
Response time ≤ 250 msGalvanic isolation Function isolation per EN50178
design isolation voltage 253 Veff
MechanicalHousing Material Makrolon Style KF housing (see page 387)Dimensions (mm) 115 x 20 x 118Weight 150 g (5.3 oz.)Protection IP20
Operating Temperature -20ºC to +60ºC (-4ºF to +149ºF)
KFD0-TT-1
Output8 (– )
Input (– ) 2
(+) 1
(– ) 3
Input for Thermocouple
Passive Output
9 (+)
8 (– )(+) 1
(+) 1
(– ) 3
(– ) 2
9 (+)
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
146
Technical Data
Connection Diagram
Model Number
2002 IS CatalogS
ignal C
ondit
ioners
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
KFD0-TR-1
Output8 (– )
9 (+)Input 1
(– ) 2
(+) 3
Passive Ouput
9 (+)
8 (– )
Input for Pt100
(– ) 2 (– ) 2
(+) 3 (+) 3
(– ) 2
1 1
The KFD0-TR-1 is a loop powered isolatorthat accepts Pt100 2- and 3-wire inputs andconditions them to a 4-20 mA output.
The KFD0-TR-1 provides galvanic isolationand burnout detection (≥22 mA). Field-configurable DIP switches allow linearizationto be turned on and off.
The loop powered 2-wire converter is suitedfor the connection of the Pt100 in 2- or 3-wire mode.
KFD0-TR-1
Loop powered
PT100, 2- and 3-wire
Lead breakage (LB) monitoring
Input/output isolation
Field-configurable inputs/outputs
RTD InputSingle ChannelIsolator
Power Supply Loop powered (not intrinsically safe)Nominal voltage 12-35 VDC
Input Terminals 1+, 2-, 3+Input PT100, 2- and 3-wire connectionLead resistance ≤ 100 Ω / leadTest current ≈ 1 mA
Output Terminals 9+, 8-Output 4-20 mA (35 mA max.)Lead breakage Upscaled ≥ 22 mALoad (Ohm) ≤ (power supply - 12 V) / 0.02 A
Transfer CharacteristicsVoltage surge 6.5 ppm / VMeasuring range Span w/o linearization 25ºC to 800ºC
Span with linearization 25ºC to 430ºCZero point w/o linearization -200ºC to 466ºCZero point with linearization -86ºC to 405ºC
Calibrated accuracy 0.1% of final accuracyLinearity fault w/o linearization ≤ 0.04% final value
with linearization ≤ 0.14% final valueTemperature drift span and zero point 0.015% / ºC or
± 10 mΩ / ºCResponse time ≤ 250 msGalvanic isolation Function isolation per EN50178
design isolation voltage 50 Veff
MechanicalHousing Material Makrolon Style KF housing (see page 387)Dimensions (mm) 115 x 20 x 100 mmWeight 150 g (5.3 oz.)Protection (IEC) IP20
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
Note: For information about programming, refer to page 209or to our website at www.am.pepperl-fuchs.com
147
Technical Data
Connection Diagram
Model Number
2002 IS Catalog
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Sig
nal C
onditio
ners
KFDX-DCI
DC Current Input 7 (– )
8 (+)
12 (– )
11 (+)DC PowerSupply
(– ) 2
(+) 1Analog Output
The KFDX-DCI accepts a DC current inputand provides a fully isolated proportionalcurrent or voltage output. In order to eliminateground loops, the I/O channel is opticallyisolated to 1800 VDC and transformerisolated from the power supply.
The input can be configured in the field forone of six current ranges from 1-100 mA.Output is linear to the input, configurable forfive ranges: 0-5 V, 0-10 V, 0-1 mA, 0-20 mAor 4-20 mA. The KFDX-DCI accepts bipolarinputs and offers selectable normal or reverseoutput modes of operation (4-20 mA, 20-4mA). For inputs that do not change in polarity,select unipolar operation.
The KFDX-DCI is equipped with a dualfunction power/signal status LED. When theunit is powered, this green LED turns on.When the input signal is over 110% of thefull scale range, the LED flashes at 8 Hz;below 0% it flashes at 4 Hz.
This unit is not intrinsically safe.
KFDX-DCI
Field configurable inputs andoutputs
Wide range of DC current inputs
3-way isolation
Accepts bipolar inputs
DC Current InputCurrent/VoltageOutput Isolator
Power Supply Terminals 11+, 12- or Power RailNominal voltage 9-30 VDC (unregulated acceptable)Power consumption ≤ 1.5 W, 1 W typicalInrush current ≤ 200 mA
Input Terminals 1+, 2-Input span 1-100 mAOverload ≤ 170 mA, 60 VDC on inputImpedance 20 Ω typicalZero 50% of full scale inputSpan 50% of full scale input
Output Terminals 7-, 8+Voltage output 0-5 V, 0-10 V Impedance < 10 Ω Drive ≤ 10 mACurrent Output 0-1 mA, 0-20 mA, 4-20 mA Impedance > 100 kΩ 0-1 mA 7.5 V, max. 7.5 kΩ 0/4-20 mA 12 V, max 600 Ω
Transfer CharacteristicsAccuracy (including linearity and hysteresis) 2 mA range ± 0.35% of full scale; 0.5% max. other ranges ± 1.0% of full scale; 0.2% max. stability ± 0.025% of full scale / ºC for zero spanIsolation 3-way, 1800 VDCCommon mode rejection DC to 60 Hz: 120 dBResponse time 200 ms, 400 ms max.
MechanicalHousing Material Makrolon Style KF housing (see page 387)Dimensions (mm) 115 x 20 x 100 mmWeight 3.5 oz. (100 g)Protection (IEC) IP 20
Operating Temperature 0ºC to +55ºC (+32ºF to +131ºF)
Note: For information about programming, refer to page209 or to our website at www.am.pepperl-fuchs.com
148
Technical Data
Connection Diagram
Model Number
2002 IS CatalogS
ignal C
ondit
ioners
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
KFDX-DCV
DC Voltage InputCurrent/VoltageOutput Isolator
Power Supply Terminals 11+ and 12- or Power RailNominal voltage 9-30 VDC (unregulated acceptable)Power consumption ≤ 1.5 W, 1 W typical
Input Terminals 1+, 2-Voltage 10 mV to 100 VMaximum overload 200 VDCImpedance ≥ 100 kΩ typicalZero 50% of full scale inputSpan 50% of full scale input
Output Terminals 7-, 8+Type Selectable DC current or voltageVoltage output 0-5 V, 0-10 V Impedance < 10 kΩ Drive 10 mA, max.Current output 0-1 mA, 4-20 mA, 0-20 mA Impedance > 100 kΩ 0-1 mA 7.5 V, max. 7.5 kΩ 0/4-20 mA 12 V, max. 600 Ω
Transfer CharacteristicsAccuracy (all ranges) ± 0.1% of full scale: 0.2% max.Stability ± 0.025% of full scale / ºC max.Response time ≤ 400 ms, 200 ms typicalIsolation 3-way, 1800 VDCCommon mode rejection DC to 60 Hz, 120 dB
MechanicalHousing Material Makrolon Style KF housing (see page 387)Dimensions (mm) 115 x 20 x 100 mmWeight 100 g (3.5 oz.)Protection (IEC) IP20
Operating Temperature 0ºC to +55ºC (+32ºF to +131ºF)
The KFDX-DCV accepts a DC voltage inputand provides a fully isolated proportionalcurrent or voltage output. In order to eliminateground loops, the I/O channel is opticallyisolated to 1,800 VDC and transformerisolated from the power supply.
The input can be configured in the field forone of twelve voltage ranges from 10 mV to100V. Output is linear to the input, configurablefor five ranges: 0-5 V, 0-10 V, 0-1 mA, 0-20mA, or 4-20 mA. The KFDX-DCV acceptsbipolar inputs and offers selectable normal orreverse modes of operation (4-20 mA, 20-4mA). For inputs which do not change inpolarity, select unipolar operation.
The KFDX-DCV is outfitted with a dual functionpower/signal status LED. When the unit ispowered, this green LED turns on. When theinput signal is over 110% of the full scalerange, the LED flashes at 8 Hz.
This unit is not intrinsically safe
Field-configurable inputs/outputs
3-way isolators
Accepts bipolar inputs
Wide range of DC voltage inputs
Note: For information about programming, refer to page209 or to our website at www.am.pepperl-fuchs.com
KFDX-DCV
DC Voltage Input 7 (– )
8 (+)
12 (– )
11 (+)DC Power Supply
(– ) 2
(+) 1Analog Output
149
Technical Data
Connection Diagram
Model Number
2002 IS Catalog
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Sig
nal C
onditio
ners
KFD2-CR-1.300
KFD2-CR-1.300
DC Power Supply12 (–)
11 (+)
7 (– )
8 (+)
Input
(– ) 2
(+) 1
3
Analog Output
9 (– )
3
3
(+) 1
3
(+) 1
(– ) 2
(– ) 2
2- and 3-wire TransmitterInput 4-20 mA CurrentOutput Isolator
The KFD2-CR-1.300 is an isolator thatpowers and repeats a 4-20 mA signal froma 2- or 3-wire transmitter. It can also isolateand repeat signals from a current source.
For 2-wire transmitters, connected toterminals 1 and 3, there is 17.5 V at 20 mAavailable to the transmitter.
For 3-wire transmitters, the power is suppliedon terminals 1 and 2 with a 4-20 mA signalflowing into terminal 3. The voltage availableis approximately 16.5 V at 25 mA betweenterminals 1 and 2. Power, input and outputare galvanically isolated.
This unit is not intrinsically safe.
2- or 3-wire input
20-30 VDC power supply
4-20 mA output
3-way isolation
For information about programming, refer to page 209 or to our websiteat www.am.pepperl-fuchs.com
Power Supply Terminals 11+, 12- or Power RailNominal voltage 20-35 VDCPower consumption ≤ 1.7 W
Input Terminals 1+, 2-, 3Available voltage 2-wire: 17.5 V at 20 mA
3-wire: 16.5 V at 25 mAInput load (terminals 2, 3) 20 Ω
Output (not intrinsically safe) Terminals 7-, 8+, 9-Output signal 0-20 mAAvailable voltage 20 VDCLoad ≤ 1 kΩ
Transfer CharacteristicsAccuracy @ 20ºC ≤ ±10 µATemperature drift ≤ ±0.2 mA / ºC (0ºC to +60ºC)
±1.0 mA / ºC (-20ºC to 0ºC)Response time ≤ 50 µsGalvanic isolation, 3 way Isolation per EN50178
Isolation voltage 253 Veff
MechanicalHousing Material Makrolon Style KF Housing (see page 387)Dimensions (mm) 115 x 20 x 100 mmWeight 100 g (3.5 oz.)Protection (IEC) IP20
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
150
Technical Data
Connection Diagram
Model Number
2002 IS CatalogS
ignal C
ondit
ioners
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
KFD2-CD-1.32
KFD2-CD-1.32 KFD2-CD-1.32-2 KFD2-CD-1.32-8
2 (– )
1 (+)
8 (– )
7 (+) DC Power Supply
(+) 9 (+) 11 Analog
Output(– ) 10
Input
(+) 9
(– ) 10 (– ) 10
(+) 9
Current/VoltageDriver CurrentOutput Isolator
The KFD2-CD-1.32 provides three-wayisolation and is used for driving I/P converters,electrically operated valves and positioners.The KFD2-CD-1.32 is available in severalversions.
CURRENT INPUT OPTION
Current flowing into terminals 10 and 11(9)passes through resistor Internal Load,generating a voltage that is transferred to theDC/DC converter. A current limit circuit in linewith terminal 9 protects Rm from damage. Themaximum voltage drop across the input is only4 V at 20 mA, allowing the connection ofseveral KFD2-CD-1.32 input circuits in series.
VOLTAGE INPUT OPTION
Voltage within the specified input range istransferred to terminals 9 and 10 via anamplifier and a DC/DC converter. A voltagelimiter circuit protects the amplifier fromincorrect input switching and overvoltage, butwill draw current through a 50 mA fuse duringoperation.
CURRENT OUTPUT OPTION
Voltage transferred across the DC/DCconverter provides a proportional current atterminals 1 and 2. For all supply voltages, thereis a minimum of 17 V at 20 mA to drive loadsof up to 850 Ω.
This unit is not intrinsically safe.
KFD2-CD-1.32: 0/4 to 20mA input / outputKFD2-CD-1.32-2: 0-20mA input / 4-20mA outputKFD2-CD-1.32-8: 0-10V input / 4-20mA output
Current or voltage input options
20-30 VAC power supply
3-way isolation
Power Supply Terminals 7+, 8- or Power RailSupply voltage 20-35 VDCNominal current current output ≤ 50 mANominal current voltage output ≤ 20 mA
Input Terminals 9+, 10-, 11+Current input Voltage Input
Transmission range 0-20 mA 0-10 VMax. input current 40 mA N/AMax. input voltage 35 V 12 VDCVoltage drop ≤ 4 V at 20 mA N/AInput current N/A ≤10 µA to 50ºC w/ 10 V
Output Terminals 1+, 2-Current 0-20 mAVoltage 17 V at 20 mALoad resistance ≤ 850 Ω
Transfer CharacteristicsCalibrated accuracy @ 20ºC ±0.01% inc. nonlinearity and hysteresisTemperature drift per ºC ±0.01%Response time < 10 msGalvanic isolation Isolation per EN50178
Isolation voltage 253 Veff
MechanicalHousing Material Makrolon Style KF Housing (see page 387)Dimensions (mm) 115 x 20 x 100 mmWeight 100 g (3.5 oz.)Protection (IEC) IP20
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
Note: For information about programming, refer to page 209 or to ourwebsite at www.am.pepperl-fuchs.com
151
Technical Data
Connection Diagram
Model Number
2002 IS Catalog
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Sig
nal C
onditio
ners
KFD2-CR4-1.20
Single Input/DualOutput Transmitter/Repeater Isolator
Power Supply Terminals 14+, 15- or Power RailNominal voltage 20-32 VDCPower consumption ≈ 2.5 W
Input Terminals 1, 2, and 3Input signal 0-20 mAAvailable voltage ≥ 16 V at 20 mAInput resistance ≤ 85 Ω
Output Terminals 7-, 8+; 10-, 11+Output signal 0-20 mALoad 0-550 Ω
Transfer CharacteristicsCalibration accuracy ≤ ±20 µATemperature drift ≤ 20 ppm / ºCRise time 20 µs with 4-20 mA stageDe-energized delay 20 µs with 20-4 mA stageGalvanic isolation, 3-way Isolation per EN50178
Isolation Voltage 253 Veff
MechanicalHousing Material Makrolon Style KF housing (see page 387)Dimensions (mm) 115 x 20 x 100 mmWeight 100 g (3.5 oz.)Protection (IEC) IP20
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
The KFD2-CR4-1.20 is suited for theconnection of 2- and 3-wire transmitters.It may also be employed as a repeater for0-20 mA signals (current source).
Both outputs provide a 0-20 mA currentcorresponding to the input signal.
2-wire transmitters are connected toterminals 1 and 3. The input for the signalis terminal 3. The minimum availablevoltage is 16V at 20 mA. Current sourcesare connected to terminals 2 and 3.
The input, output and power supply aregalvanically isolated from each other.
This unit is not intrinsically safe.
Single-channel input /dual output
20-30 VDC supply voltage
Outputs isolated from each other
Power Rail Bus
3-way isolation
Note: For information about programming, refer to page 209 or to ourwebsite at www.am.pepperl-fuchs.com
KFD2-CR4-1.20
DC Power Supply15 (– )
14 (+)
7 (– )
8 (+) (– ) 2
(+) 1
3
Output 1
10 (– )
3 Input
3 3
(+) 1 (+) 1
(– ) 2
(– ) 2
11 (+)Output 2
152
Technical Data
Connection Diagram
Model Number
2002 IS CatalogS
ignal C
ondit
ioners
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
KFD2-STC4-1.20
HART TransmitterPower SupplyIsolator
Note: For information about programming, refer to page 209 or to ourwebsite at www.am.pepperl-fuchs.com
KFD2-STC4-1.20
DC Power Supply15 (– )
14 (+)
7 (– )
8 (+)
Input
(– ) 2
(+) 1
3
Output 1
10 (– )
3 3 3
(+) 1 (+) 1
(– ) 2 (– ) 2
11 (+)Output 2
SM
AR
T C
omm
unic
ator
Single channel input /dual output
HART compatible 4-20mA current source output 3-way isolation
SMART transmitter powers a 2-wireSMART transmitter and isolates the analog4-20 mA signal from the field to the controlroom as two current sources.
Digital signals which can be modulated ontothe analog signal, can also be transmittedbidirectionally.
The SMART transmitters are delivered withthe KF-STP-GN terminals. Connector jacksare integrated in these terminals for theconnection of the handheld terminals.
This unit is not intrinsically safe.
Power Supply Power Rail or terminals 14+, 15-Nominal voltage 20-32 VDCPower consumption ≈2.5 W
Input Terminals 1, 2, 3Input signal 0/4-20 mAAvailable voltage at 20 mA ≥16 V
Output Terminals 9+, 10-, 11+Output signal 4-20 mA / load 550 ΩRipple ≤ 50 µArms
Transfer CharacteristicsCalibrated accuracy ≤ 20 µATemperature drift ≤ 20 ppm / ºCFrequency range: Input/Output: Band width at 0.5 VppSignal 0 Hz to 7.5 kHz (-3 dB) Output/Input: Band width at 0.5 VppSignal 300 Hz to 7.5 kHz (-3 dB)Galvanic isolation Isolation per EN 50178
Isolation voltage 253 Veff
MechanicalHousing Material Makrolon Style KF housing (see page 387)Dimensions (mm) 107 x 20 x 115 mmWeight 100 g (3.5 oz.)Protection (IEC) IP20
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
153
Technical Data
Connection Diagram
Model Number
2002 IS Catalog
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Sig
nal C
onditio
ners
KFDX-RTD
KFDX-RTD
7 (– )
8 (+)
12 (– )
11 (+)DC Power Supply
Analog Output
(+) 1
(R) 3
(– ) 2
RTD Input
RTD InputCurrent/VoltageOutput Isolator
The KFDX-RTD isolator interfaces 3-wire RTDs(Pt100, Pt500, Pt1000, Cu10, Cu25 andCu100) to a process control system. Thisisolator also effectively eliminates ground loopswith 1800 VDC isolation separating input,output and power supply.
The input range can be configured in the fieldfor one of sixteen temperature ranges via DIPswitches. The output is linear to temperature,configurable for five ranges: 0-5 V, 0-10 V, 0-1 mA, 0-20 mA or 4-20 mA.
Span and zero potentiometers provide 50%adjustability of offset and span turndown foreach input range. To ensure accuratetemperature measurement, the KFDX-RTDcontains constant current circuitry which usesthe third lead of the RTD as a sense line forlead resistance compensation.
The KFDX-RTD is equipped with three LEDs:INPUT (green), TROUBLE (yellow) and CAL(yellow). Upon power-up, the INPUT and CALLEDs will alternately flash for 10 seconds.
This unit is not intrinsically safe.
Field selectable inputs/ outputs
Wide range of RTD inputs
3-way isolation
Lead resistance compensation
Note: For information about programming, refer to page 209 or to ourwebsite at www.am.pepperl-fuchs.com
Power Supply Terminals 11+, 12- or Power RailSupply voltage 9-30 VDCPower consumption ≤ 2.5 W, 1.5 W typicalInrush current ≤ 300 mA
Input Terminals 1+, 2-, 3Excitation current < 2 mAZero 50% of full scale inputSpan 50% of full scale input
Output Terminals 7-, 8+Voltage output 0-5 V, 0-10 VImpedance > 10 ΩDrive ≤ 10 mACurrent output 0-1 mA, 0-20 mA, 4-20 mAImpedance > 100 kΩ0-1 mA 7.5 V, max. 7.5 kΩ0/4-20 mA 12 V, max. 600 ΩAccuracy (including linearity & hysteresis)
±0.01% typical, 0.2% max. of the max.input range @ 25ºC, 0Ω lead resistance
Temperature drift ±0.015% of max. temperature range/ºCResponse time ≤ 500 ms, 250 ms typicalIsolation 3-way 1800 VDC
MechanicalHousing Material Makrolon Style KF housing (see page 387)Dimensions (mm) 115 x 20 x 100 mmWeight 100 g (3.5 oz.)Protection (IEC) IP20
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
154
Technical Data
Connection Diagram
Model Number
2002 IS CatalogS
ignal C
ondit
ioners
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
KFDX-TC
7 (– )
8 (+)
12 (– )
11 (+)DC Power Supply
(– ) 2
(+) 1
Analog Output
KFDX-TC
Thermocouple Input
Power Supply Terminals 11+ and 12- or Power RailSupply voltage 9-30 VDC (unregulated acceptable)Power consumption ≤ 2.5 W, 1.5 W typical
Input Terminals 1, 2Maximum overload ± 10 VDC on inputRange selectableImpedance ≥ 1 MΩBurnout detection selectable up/downscaleZero 50% of full scale inputSpan 50% of full scale input
Output Terminals 7-, 8+Voltage output 0-5 V, 0-10 VLine impedance > 10 ΩDrive ≤ 10 mACurrent output 0-1 mA, 0-20 mA, 4-20 mAImpedance > 100 kΩ0-1 mA 7.5 V, max. 7.5 kΩ0/4-20 mA 12V, max. 600 Ω
Transfer characteristicsTemperature drift < ±0.04% of max. input temperature
per ºC change in ambient temperatureCommon mode rejection DC to 60 Hz: 120 dBIsolation 3-way, 1,800 VDCResponse time ≤ 750 ms, 400 ms typical
MechanicalHousing Material Makrolon Style KF housing (see page 387)Dimensions (mm) 115 x 20 x 100 mmWeight 100 g (3.5 oz.)Protection (IEC) IP20
Operating Temperature 0ºC to +55ºC (+32ºF to +131ºF)
ThermocoupleInput Isolator
The KFDX-TC thermocouple input isolatorinterfaces B, E, J, K, R, S and T typethermocouples to a process control system.It also effectively eliminates ground loops with1,800 VDC isolation separating input, outputand power supply.
The input range can be configured in the fieldfor one of 16 thermocouple temperatureranges via DIP switches on the side of thehousing. The output is linear to temperature,configurable for five ranges: 0-5 V, 0-10 V, 0-1 mA, 0-20 mA, or 4-20 mA.
Span and zero potentiometers on the top plateprovide 50% adjustability of offset and spanturn-down for each input range. The KFDX-TC also features internal cold junctioncompensation (CJC) and selectableupscale /downscale thermocouple burnoutdetection.
The KFDX-TC is outfitted with three LEDs onthe front panel: INPUT (Green), TROUBLE(Yellow), and CAL (Yellow). Upon power-up,the INPUT and CAL LEDs alternately flash for10 seconds.
This unit is not intrinsically safe.
Wide range of thermocouple types
Cold junction compensation (CJC)
24 VDC supply voltage
3-way isolation
Note: For information about programming, refer to page 209or to our website at www.am.pepperl-fuchs.com
155
Technical Data
Connection Diagram
Model Number
2002 IS Catalog
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Sig
nal C
onditio
ners
UniversalTemperatureInput Isolator
The KFD2-UT-1 is designed for connection toRTDs (Pt100 and Ni100) or thermocouples (B, E,J, K, L, N, R, S and T), and provides three-wayisolation. The inputs, outputs and power supplyare galvanically isolated.
This device also features internal/external coldjunction compensation, burnout monitoring forthermocouples and burnout and short circuitmonitoring for RTDs.
All settings are programmed and calibratedthrough a serial interface to PC (on-lineprogramming--see the P+F web site for moreinformation).
A signal at terminals 2 and 3 is transmitted acrossthe isolator and converted to an equivalent outputat terminals 7 and 8. Terminal 7 has the samepolarity as terminal 2.
All parameters are programmable through a K-ADP1 cable (sold separately) that provides theconnection between the programming socket ofthe KFD2-UT and the RS232 PC interface.
Accessories include removable terminals withinternal cold junction compensation (K-CJC) anda K-SK programming software kit. The K-ADP1and K-SK are required unless the KFD2-UT isconfigured by P+F.
This unit is not intrinsically safe.
KFD2-UT-1
Universal temperature inputs
Current output
Programming & calibration via PC
3-way isolation
CJC for thermocouple and leadresistance compensation for RTDs
Power Supply Terminals 11+, 12- or Power RailSupply voltage 20-35 VDCPower consumption ≈ 1.5 W
Input Terminals 1-, 2-, 3+, 4+Thermocouple B,E,J,K,L,N,R,S or TLead resistance ≤ 50 Ω per leadTest current 400 µA with RTDs
Output Terminals 7-, 8+Output current 4-20 mA (20.5 mA at input signal exceeded)Fault signal Downscaled 2-4 mA, upscaled 20.522 mALoad ≤ 500 Ω
Transfer CharacteristicsCalibrated accuracy ± (0.01% of value in ºC + 0.05% of
range + 0.1 ºC) (4-wire)Thermocouple ± (0.05% of value in ºC + 0.05% of
range + 1ºC) (inc. ± 0.8ºC error for CJC)
Rise time ≤ 430 msGalvanic isolation Isolation per EN50178
Isolation voltage 253 Veff
MechanicalHousing Material Makrolon Style KF housing (see page 387)Dimensions (mm) 115 x 20 x 118Weight 100 g (3.5 oz.)Protection (IEC) IP20
Operating Temperature +4ºC to +60ºC (+40ºF to +140ºF)
12 (– )
11 (+)
8 (– )
7 (+) Analog Output4
3
2
1
PC
DC Power Supply
CJC Type K-CJC-GN
(– ) 2
(– ) 1
(– ) 2 (– ) 2 (– ) 2
(– ) 1
(+) 3 (+) 3
(+) 1
(+) 3
KFD2-UT-1
(+) 4
Input
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
156
Technical Data
Connection Diagram
Model Number
2002 IS CatalogS
ignal C
ondit
ioners
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
KFD2-UT-1-1
Universal temperature inputs
Voltage output
Programming & calibration via PC
3-way isolation
CJC for thermocouples and leadresistance compensation for RTDs
UniversalTemperatureInput Isolator
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
12 (– )
8 (– )
7 (+) Analog Output4
3
2
1
PC
DC Power Supply
CJC Type K-CJC-GN
(+) 4
(– ) 2
(– ) 1
(– ) 2 (– ) 2 (– ) 2
(– ) 1
(+) 3 (+) 3
(+) 1
(+) 3
KFD2-UT-1-1
11 (+)
Power Supply Terminals 11+, 12- or Power RailSupply voltage 20-35 VDCPower consumption ≈ 1.5 W
Input Terminals 1-, 2-, 3+, 4+Thermocouple B,E,J,K,L,N,R,S or TLead resistance ≤ 50 Ω per leadTest current 400 µA with RTDs
Output Terminals 7-, 8+Output voltage 1-5 V; (5.125 V input signal exceeded)Fault signal Downscaled 0-5 V, upscaled 5.025 - 5.12 VLoad ≤ 10 KΩ
Transfer CharacteristicsCalibrated accuracy ± (0.01% of value in ºC + 0.05% of
range + 0.1 ºC) (4-wire)Thermocouple ± (0.05% of value in ºC + 0.05% of
range + 1ºC) (inc. ± 0.8ºC error for CJC)
Rise time ≤ 430 msGalvanic isolation Isolation per EN50178
Isolation voltage 253 Veff
MechanicalHousing Material Makrolon Style KF housing (see page 387)Dimensions (mm) 115 x 20 x 118Weight 100 g (3.5 oz.)Protection (IEC) IP20
Operating Temperature +4ºC to +60ºC (+40ºF to +140ºF)
The KFD2-UT-1-1 is designed for connection toRTDs (Pt100 and Ni100) or thermocouples (B,E, J, K, L, N, R, S and T), and provides three-way isolation. The inputs, outputs and powersupply are galvanically isolated.
This device also features internal/external coldjunction compensation, burnout monitoring forthermocouples and burnout and short circuitmonitoring for RTDs.
All settings are programmed and calibratedthrough a serial interface to PC (on-lineprogramming).
A signal at terminals 2 and 3 is transmitted acrossthe isolator and converted to an equivalentoutput at terminals 7 and 8. Terminal 7 has thesame polarity as terminal 2.
All parameters are programmable through a K-ADP1 cable (sold separately) that provides theconnection between the programming socketof the KFD2-UT and the RS232 PC interface.
Accessories include removable terminals withinternal cold junction compensation (K-CJC) anda K-SK programming software kit. The K-ADP1and K-SK are required unless the KFD2-UT-1-1is configured by P+F.
This unit is not intrinsically safe.
157
Technical Data
Connection Diagram
Model Number
2002 IS Catalog
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Sig
nal C
onditio
ners
AC Current/VoltageInput Current/VoltageOutput Isolator
The KFDX-AC accepts an AC voltage/currentinput and provides a fully isolated proportionalDC current or voltage output. In order toeliminate ground loops, the I/O channel isoptically isolated to 1,800 VDC andtransformer isolated from the power supply.
The input can be configured in the field forone of twelve voltage ranges from 100 mV to250 V and 4 current ranges from 10 mA to100 mA. Output is linear to the input,configurable for five ranges: 0-5 V, 0-10 V, 0-1 mA, 0-20 mA, or 4-20 mA.
The KFDX-AC is outfitted with a green dualfunction power/signal status LED. When theunit is powered, the LED is illuminated. Whenthe input signal is over 110% of the full scalerange, the LED flashes at 8 Hz.
This unit is not intrinsically safe.
KFDX-AC
Wide range of inputs/outputs
Field selectable input/output
3-way isolation
Power Supply Terminals 11+, 12- or Power RailSupply voltage 9-30 VDCPower consumption ≤ 1.5 W, 1 W typical
Input Terminals 1+, 2-Input voltage / current 100 mV to 250 V / 10-100 mAOverload ≤ 300 VAC / 170 mA AC (60 Vp for
current inputs)Impedance ≥ 100 kΩ (voltage inputs) / 20 Ω
(current inputs)Zero 50% of full scale inputSpan 50% of full scale input
Output Terminals 7-, 8+Voltage 0-5 V, 0-10 V Impedance < 10 kΩ Drive ≤ 10 mACurrent 0-1 mA, 4-20 mA, 0-20 mA Impedance > 100 kΩ 0-1 mA 7.5 V, max. 7.5 kΩ 0/4-20 mA 12 V, max. 600 Ω
Transfer CharacteristicsRange ± 0.1% of full scale: 0.5% max.Stability ± 0.025% of full scale/ºC for zero and spanCommon mode rejection DC to 60 Hz: 120 dBIsolation 3-way 1,800 VDCResponse time ≤ 400 ms, 200 ms typical
MechanicalHousing Material Makrolon Style KF housing (see page 387)Dimensions (mm) 115 x 20 x 118Weight 100 g (3.5 oz.)Protection (IEC) IP20
Operating Temperature 0ºC to +55ºC (+32ºF to +131ºF)
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
KFDX-AC
AC Input Current/Voltage 7 (– )
8 (+)
12 (– )
11 (+)DC Power Supply
(+) 1Analog Output(– ) 2
158
Technical Data
Connection Diagram
Model Number
2002 IS CatalogS
ignal C
ondit
ioners
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
The KFDX-HZ accepts a frequency inputand provides a fully isolated proportionalDC current or voltage output. This isolatoralso effectively eliminates ground loopswith 1,800 VDC isolation separating input,output and power supply.
The input range can be configured in thefield for any frequency span from 2 Hz to10,000 Hz via DIP switches on the side ofthe housing. The output is configurable forfive ranges: 0-5 V, 0-10 V, 0-1 mA, 0-20mA, or 4-20 mA.
The KFDX-HZ is simply configured viapush-buttons rather than a zero and spanpotentiometer. Set the input frequencyspan by applying the maximum andminmum frequencies to the system andpressing the CAL button while the INPUTLED is lit.
The KFDX-HZ is outfitted with three LEDs:LEVEL (Green), INPUT (Yellow), andOUTPUT (Red).
This unit is not intrinsically safe.
KFDX-HZ
Span from 2 Hz to 10,000 Hz
Easy push-button calibration
3-way isolation
Power Supply Terminals 11+, 12- or Power RailSupply voltage 9-30 VDCInrush current will not exceed stead state currentPower consumption ≤ 2.5 W, 1.4 W typical
Input Terminals 1+, 2-Range 2 Hz to 10 KHz, pulseInput values 150 mVp to 150 VrmsOverload ≤ 180 VrmsImpedance ≥ 10 kΩ
Output Terminals 7-, 8+Voltage output 0-5 V, 0-10 V Impedance > 1 kΩ Drive ≤ 10 mACurrent output 0-1 mA, 0-20 mA, 4-20 mA Impedance ≥ 100 kΩ 0-1 mA 7.5 V, max. 7.5 kΩ 0/4-20 mA 12 V, max. 600 Ω
Transfer CharacteristicsAccuracy ± 0.1% of selected range @ 25ºCTemperature drift ±0.025% / ºC max. of selected rangePower < ±0.01% of max. temp. range/% of
power changeCommon mode isolation DC to 60 Hz: 100 dBIsolation 3-way 1,800 VDCResponse time ≤ 500 ms, 250 ms typical
MechanicalHousing Material Makrolon Style KF housing (see page 387)Dimensions (mm) 115 x 20 x 118Weight 100 g (3.5 oz.)Protection (IEC) IP20
Operating Temperature 0ºC to +55ºC (+32ºF to +131ºF)
Frequency InputCurrent/VoltageOutput Isolator
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
KFDX-HZ
Frequency Input 7 (– )
8 (+)
12 (– )
11 (+)DC PowerSupply
(– ) 2
(+) 1Analog Output
159
Technical Data
Connection Diagram
Model Number
2002 IS Catalog
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Sig
nal C
onditio
ners
Rotational SpeedLimit Alarm
KFA5-DWB-1.D
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
Power Supply Terminals 23, 24Nominal voltage 120 VACPower consumption 2 VA
Input Terminals 1+, 3-Connection type 2-wire sensor: terminals 1+, 3-
3-wire sensor: terminals 1+, 2- and 3start-up override terminals: 13+, 14-
Input I Sensor Input resistance 4.7 kΩ Input pulse length/interval ≥ 50 µs / ≥ 50 µs Voltage 22 V Current max. 30 mA; limitation 40 mA Lead monitoring breakage I ≤ 0.15 mA
short circuit I > 6.5 mAInput II start-up override: 1-1000 s, in 1s steps
Quiescent voltage/short circuit current: 18 V / 5 mA Active / passive I > 4 mA (> 100 ms) / I < 1.5 mA
OutputsRelay output 1 (SPDT) Terminals 10, 11, 12Relay output 2 (SPDT) Terminals 16, 17, 18Contact load 250 VAC / 2 A / cos ø > 0.7; 40 VDC / 2 A
Mechanical life ≥ 5 x 107 operationsEnergizing / de-energizing ≈ 20 ms / ≈ 20 ms
Transfer CharacteristicsFrequency range 0.001-12,000 Hz
MechanicalHousing Material Makrolon Style KF housing (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)Protection (IEC) IP20
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
The KFA5-DWB-1.D monitors for anoverspeed or underspeed condition bycomparing the input frequency to the userprogrammed reference frequency. Thereference frequency is easily programmedby the use of a keypad located on the frontof the unit. An overspeed or underspeedcondition is signaled via the relay outputs.Lead breakage and short circuits in thesensor are indicated by a red LED. Thestart-up override feature sets relay outputsto default conditions programmed by theuser, for up to 1,000 seconds.
This unit is not intrinsically safe.
Operating range 0.06-720,000RPM (0.001-12,000 Hz)
Relay outputs
Push-button programmable
Start-up override
LCD display
Lead breakage (LB) and shortcircuit (SC) monitoring
17
1618
111012
13 (+)14 (– )
23
24
Output 1
Output 2
Start Up Override
Supply 120 VAC
KFA5-DWB-1.D
(+) 1
(– ) 3
2
(+) 1
Input II
LB/SCLB/SC LB
R2
R1R1
(+) 1(+) 1(+) 1
(– ) 3(– ) 3(– ) 3(– ) 3
(+) 1
2
(– ) 3
Input I
160
Technical Data
Connection Diagram
Model Number
2002 IS CatalogS
ignal C
ondit
ioners
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
KFA6-DWB-1.D
Rotational SpeedLimit Alarm
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
17
1618
111012
13 (+)14 (– )
23
24
Output 1
Output 2
Start Up Override
Supply 240 VAC
KFA6-DWB-1.D
Sig
nal P
roce
sso
r(+) 1
(– ) 3
2
(+) 1
LB/SCLB/SC LB
R2
R1R1
(+) 1(+) 1(+) 1
(– ) 3(– ) 3(– ) 3(– ) 3
(+) 1
2
(– ) 3
Input II Input I
The KFA6-DWB-1.D monitors for anoverspeed or underspeed condition bycomparing the input frequency to the userprogrammed reference frequency. Thereference frequency is easily programmedby the use of a keypad located on the frontof the unit. An overspeed or underspeedcondition is signaled via the relay outputs.Lead breakage and short circuits in thesensor are indicated by a red LED. Thestart-up override feature sets relay outputsto default conditions programmed by theuser, for up to 1,000 seconds.
This unit is not intrinsically safe.
Operating range 0.06-720,000RPM (0.001-12,000 kHz)
Relay outputs
Push-button programmable
Start-up override
LCD display
Lead breakage (LB) and shortcircuit (SC) monitoring
Power Supply Terminals 23, 24Nominal voltage 240 VACPower consumption 2 VA
Input Terminals 1+, 3-Connection type 2-wire sensor: terminals 1+, 3-
3-wire sensor: terminals 1+, 2- and 3start-up override terminals: 13+, 14-
Input I Sensor Input resistance 4.7 kΩ Input pulse length/interval ≥ 50 µs / ≥ 50 µs Voltage 22 V Current max. 30 mA; limitation 40 mA Lead monitoring breakage I ≤ 0.15 mA
short circuit I > 6.5 mAInput II start-up override: 1-1000 s, in 1s steps
Quiescent voltage/short circuit current: 18 V / 5 mA Active / passive I > 4 mA (> 100 ms) / I < 1.5 mA
OutputsRelay output 1 (SPDT) Terminals 10, 11, 12Relay output 2 (SPDT) Terminals 16, 17, 18Contact load 250 VAC / 2 A / cos ø > 0.7; 40 VDC / 2 A
Mechanical life ≥ 5 x 107 operationsEnergizing / de-energizing ≈ 20 ms / ≈ 20 ms
Transfer CharacteristicsFrequency range 0.001-12,000 Hz
MechanicalHousing Material Makrolon Style KF housing (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)Protection (IEC) IP20
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
161
Technical Data
Connection Diagram
Model Number
2002 IS Catalog
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Sig
nal C
onditio
ners
Rotational SpeedLimit Alarm
KFD2-DWB-1.D
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
17
1618
111012
13 (+)14 (– )
23 (+)
24 (– )
Output 1
Output 2
Start Up Override
Supply 24 VDC
KFD2-DWB-1.D
Sig
nal P
roce
sso
r
Collective Error Messaging
(+) 1
(– ) 3
2
(+) 1
LB/SCLB/SC LB
R2
R1R1
(+) 1(+) 1(+) 1
(– ) 3(– ) 3(– ) 3(– ) 3
(+) 1
2
(– ) 3
Input II Input I
The KFD2-DWB-1.D monitors foroverspeed or underspeed conditions bycomparing the input frequency to the user-programmed reference frequency. Thereference frequency is easily programmedby push buttons mounted on the frontpanel. An overspeed or underspeedcondition is signaled via the relay outputs.Lead breakage and short circuits in thesensor are indicated by a red LED andthrough the collective error output viaPower Rail. The start-up override featuresets relay outputs to default conditionsprogrammed by the user, for up to 1,000seconds.
This unit is not intrinsically safe.
Operating range 0.06-720,000RPM (0.001-12,000 Hz)
Relay outputs
Push-button programmable
Collective error messaging
LCD display
Lead breakage (LB) and shortcircuit (SC) monitoring
Power Supply Terminals 23, 24Nominal voltage 20-30 VDCPower consumption 2 W
Input Terminals 1+, 3-Connection type 2-wire sensor: terminals 1+, 3-
3-wire sensor: terminals 1+, 2- and 3start-up override terminals: 13+, 14-
Input I Sensor Input resistance 4.7 kΩ Input pulse length/interval ≥ 50 µs / ≥ 50 µs Voltage 22 V Current max. 30 mA; limitation 40 mA Lead monitoring breakage I ≤ 0.15 mA
short circuit I > 6.5 mAInput II start-up override: 1-1000 s, in 1s steps
Quiescent voltage/short circuit current: 18 V / 5 mA Active / passive I > 4 mA (> 100 ms) / I < 1.5 mA
OutputsRelay output 1 (SPDT) Terminals 10, 11, 12Relay output 2 (SPDT) Terminals 16, 17, 18Contact load 250 VAC / 2 A / cos ø > 0.7; 40 VDC / 2 A
Mechanical life ≥ 5 x 107 operationsEnergizing / de-energizing ≈ 20 ms / ≈ 20 ms
Transfer CharacteristicsFrequency range 0.001-12,000 Hz
MechanicalHousing Material Makrolon Style KF housing (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)Protection (IEC) IP20
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
162
Technical Data
Connection Diagram
Model Number
2002 IS CatalogS
ignal C
ondit
ioners
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
KFU8-UFC-1
Universal FrequencyConverter
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
10
17161819 (+)20 (– )8 (+)7 (– )
1314
Output 1
Output 2
Output 3
Output 4 0/4-20 mA
Start Up Override
KFU8-UFC-1
Programming JackGND
TxDRxD
12
11
23
24Supply 24 VDC 120 VAC 240 VAC
(+) 1
(– ) 3
2
(+) 1
LB/SCLB/SC LB
R2
R1R1
(+) 1(+) 1(+) 1
(– ) 3(– ) 3(– ) 3(– ) 3
(+) 1
2
(– ) 3
Input II Input I
24 VDC / 120 VAC / 240 VAC supply
Operating range 0.06-720,000 RPM(0.001-12,000 kHz)
Analog and digital outputs
PC programmable
This universal frequency converter convertsa digital input signal into an analog outputsignal for connection to standard currentinput devices. A passive transistor outputisolates and transfers the digital signal.Two relay outputs can be programmed toactuate at desired frequencies. The unit isprogrammable with a PC and thePACTware configuration software.A debounce filter eliminates extraneoussignals from relay bounce.
Lead breakage and short circuits in thesensor are indicated by a red LED.
This unit is not intrinsically safe.
Power Supply Terminals 23, 24Nominal voltage 20-90 VDC; 40-250 VACPower consumption 2.2 W; 3 VA
InputConnection type 2-wire sensor: terminals 1+, 3-
3-wire sensor: terminals 1+, 2- and 3start-up override terminals: 13+, 14-
Input I Sensor Input resistance 4.7 kΩ Input pulse length/interval ≥ 50 µs / ≥ 50 µs Voltage 22 V Current (Im) max. 30 mA; limitation 40 mA Lead monitoring breakage I ≤ 0.15 mA
short circuit I > 6.5 mAInput II start-up override: 1-1000 s, in 1s steps Quiescent voltage/short circuit current: 18 V / 5 mA Active / passive I > 4 mA (> 100 ms) / I < 1.5 mA
OutputsRelay output 1 (SPDT) Terminals 10, 11 and 12Relay output 2 (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ø ≥ 0.7; 40 VDC / 2AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 msOutput 3 (passive transistor) Terminals 19+ and 20-Nominal current 50 mA, short circuit-protectedLogic 1 voltage drop < 2.5 VLogic 0 output switched off (leakage < 10 µA)Output 4 (current) Terminals 8+ and 7-Open circuit voltage ≤ 24 VDCOutput current 0-20 mA or 4-20 mAError signal Downscale < 3.6 mA, upscale ≥ 22 mALoad ≤ 650 Ω
MechanicalHousing Makrolon KF housing (see page387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
163
Technical Data
Connection Diagram
Model Number
2002 IS Catalog
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Sig
nal C
onditio
ners
Universal FrequencyConverter with Display
KFD2-UFC-1.D
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
10
17161819 (+)20 (– )8 (+)7 (– )
13 (+)14 (– )
Output 1
Output 2
Output 3
Output 4 0/4-20 mA
Start Up Override
KFD2-UFC-1.D
Programming JackGND
TxDRxD
Collective Error Messaging
12
11
23 (+)
24 (– )Supply 24 VDC
(+) 1
(– ) 3
2
(+) 1
LB/SCLB/SC LB
R2
R1R1
(+) 1(+) 1(+) 1
(– ) 3(– ) 3(– ) 3(– ) 3
(+) 1
2
(– ) 3
Input II Input I
This universal frequency converter convertsa digital input signal into an analog outputsignal for connection to standard currentinput devices. A passive transistor outputisolates and transfers the digital signal. Tworelay outputs can be programmed toactuate at desired frequencies. The units isprogrammable with a PC and thePACTware configuration software. Adebounce circuit eliminates extraneoussignals from relay bounce.
Lead breakage and short circuits in thesensor are indicated by a red LED andthrough the collective error output viaPower Rail.
This unit is not intrinsically safe.
24 VDC supply
Operating range 0.06-720,000RPM (0.001-12,000 kHz)
Analog and digital outputs
PC and push-buttonprogrammable
LCD display
Power Supply Terminals 23, 24Nominal voltage 20-30 VDCPower consumption 2.2 W
InputConnection type 2-wire sensor: terminals 1+, 3-
3-wire sensor: terminals 1+, 2- and 3start-up override terminals: 13+, 14-
Input I Sensor Input resistance 4.7 kΩ Input pulse length/interval ≥ 50 µs / ≥ 50 µs Voltage 22 V Current (Im) max. 30 mA; limitation 40 mA Lead monitoring breakage I ≤ 0.15 mA
short circuit I > 6.5 mAInput II start-up override: 1-1000 s, in 1s steps Quiescent voltage/short circuit current: 18 V / 5 mA Active / passive I > 4 mA (> 100 ms) / I < 1.5 mA
OutputsRelay output 1 (SPDT) Terminals 10, 11 and 12Relay output 2 (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ø ≥ 0.7; 40 VDC / 2AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 msOutput 3 (passive transistor) Terminals 19+ and 20-Nominal current 50 mA, short circuit-protectedLogic 1 voltage drop < 2.5 VLogic 0 output switched off (leakage < 10 µA)Output 4 (current) Terminals 8+ and 7-Open circuit voltage ≤ 24 VDCOutput current 0-20 mA or 4-20 mAError signal Downscale < 3.6 mA, upscale ≥ 22 mALoad ≤ 650 Ω
MechanicalHousing Makrolon KF housing (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
164
Technical Data
Connection Diagram
Model Number
2002 IS CatalogS
ignal C
ondit
ioners
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
KFD2-UFC-1
Universal FrequencyConverter Isolator
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
10
171618192087
1314
Output 1
Output 2
Output 3
Output 4 0/4-20 mA
Start Up Override
KFD2-UFC-1
Programming JackGND
TxDRxD
12
11
23
24Supply 24 VDC
(+) 1
(– ) 3
2
(+) 1
LB/SCLB/SC LB
R2
R1R1
(+) 1(+) 1(+) 1
(– ) 3(– ) 3(– ) 3(– ) 3
(+) 1
2
(– ) 3
Collective Error Messaging
Input II Input I
24 VDC supply
Operating range 0.06-720,000RPM (0.001-12,000 kHz)
Analog and digital outputs
PC programmable
This universal frequency converter convertsa digital input signal into an analog outputsignal for connection to standard currentinput devices. A passive transistor outputisolates and transfers the digital signal.Two relay outputs can be programmed toactuate at desired frequencies. The unit isprogrammable with a PC and thePACTware configuration software.A debounce filter eliminates extraneoussignals from relay bounce.
Lead breakage and short circuits in thesensor are indicated by a red LED andthrough the collective error output viaPower Rail.
This unit is not intrinsically safe.
Power Supply Terminals 23, 24 or Power RailNominal voltage 20-30 VDCPower consumption 2.2 W
InputConnection type 2-wire sensor: terminals 1+, 3-
3-wire sensor: terminals 1+, 2- and 3start-up override terminals: 13+, 14-
Input I Sensor Input resistance 4.7 kΩ Input pulse length/interval ≥ 50 µs / ≥ 50 µs Voltage 22 V Current (Im) max. 30 mA; limitation 40 mA Lead monitoring breakage I ≤ 0.15 mA
short circuit I > 6.5 mAInput II start-up override: 1-1000 s, in 1s steps Quiescent voltage/short circuit current: 18 V / 5 mA Active / passive I > 4 mA (> 100 ms) / I < 1.5 mA
OutputsRelay output 1 (SPDT) Terminals 10, 11 and 12Relay output 2 (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ø ≥ 0.7; 40 VDC / 2AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 msOutput 3 (passive transistor) Terminals 19+ and 20-Nominal current 50 mA, short circuit-protectedLogic 1 voltage drop < 2.5 VLogic 0 output switched off (leakage < 10 µA)Output 4 (current) Terminals 8+ and 7-Open circuit voltage ≤ 24 VDCOutput current 0-20 mA or 4-20 mAError signal Downscale < 3.6 mA, upscale ≥ 22 mALoad ≤ 650 Ω
MechanicalHousing Makrolon KF housing (see page 387)Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
165
Technical Data
Connection Diagram
Model Number
2002 IS Catalog
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Sig
nal C
onditio
ners
Universal FrequencyConverter Isolatorwith Display
KFU8-UFC-1.D
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
10
17161819 (+)20 (–)8 (+)7 (–)
13 (+)14 (– )
Output 1
Output 2
Output 3
Output 4 0/4-20 mA
Start Up Override
KFU8-UFC-1.D
Programming JackGND
TxDRxD
12
11
23
24Supply 24 VDC 120 VAC 240 VAC
(+) 1
(– ) 3
2
(+) 1
LB/SCLB/SC LB
R2
R1R1
(+) 1(+) 1(+) 1
(– ) 3(– ) 3(– ) 3(– ) 3
(+) 1
2
(– ) 3
Input II Input I
This universal frequency converter convertsa digital input signal into an analog outputsignal for connection to standard currentinput devices. A passive transistor outputisolates and transfers the digital signal. Tworelay outputs can be programmed toactuate at desired frequencies. The units isprogrammable with a PC and thePACTware configuration software. Adebounce circuit eliminates extraneoussignals from relay bounce.
Lead breakage and short circuits in thesensor are indicated by a red LED.
This unit is not intrinsically safe.
24 VDC / 120 VAC / 240 VAC supply
Operating range 0.06-720,000 RPM(0.001-12,000 kHz)
Analog and digital outputs
PC and push-buttonprogrammable
LCD display
Power Supply Terminals 23, 24Nominal voltage 20-90 VDC; 40-250 VACPower consumption 2.2 W; 3 VA
InputConnection type 2-wire sensor: terminals 1+, 3-
3-wire sensor: terminals 1+, 2- and 3start-up override terminals: 13+, 14-
Input I Sensor Input resistance 4.7 kΩ Input pulse length/interval ≥ 50 µs / ≥ 50 µs Voltage 22 V Current (Im) max. 30 mA; limitation 40 mA Lead monitoring breakage I ≤ 0.15 mA
short circuit I > 6.5 mAInput II start-up override: 1-1000 s, in 1s steps Quiescent voltage/short circuit current: 18 V / 5 mA Active / passive I > 4 mA (> 100 ms) / I < 1.5 mA
OutputsRelay output 1 (SPDT) Terminals 10, 11 and 12Relay output 2 (SPDT) Terminals 16, 17 and 18Contact load 250 VAC / 2 A / cos ø ≥ 0.7; 40 VDC / 2AMechanical life ≥ 5 x 107 operationsEnergizing / de-energizing delay ≈ 20 ms / ≈ 20 msOutput 3 (passive transistor) Terminals 19+ and 20-Nominal current 50 mA, short circuit-protectedLogic 1 voltage drop < 2.5 VLogic 0 output switched off (leakage < 10 µA)Output 4 (current) Terminals 8+ and 7-Open circuit voltage ≤ 24 VDCOutput current 0-20 mA or 4-20 mAError signal Downscale < 3.6 mA, upscale ≥ 22 mALoad ≤ 650 Ω
MechanicalHousing Makrolon KF housing (see page 387)
Dimensions (mm) 118 x 40 x 115Weight 300 g (10.6 oz.)
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
166
Technical Data
Connection Diagram
Model Number
2002 IS CatalogS
ignal C
ondit
ioners
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
The KFDA-DCI accepts a DC current inputand provides two adjustable contactoutputs. This limit alarm also effectivelyeliminates ground loops with 1,800 VDCisolation separating input, output andpower supply.
The KFDA-DCI is outfitted with threeLEDs. The first is a green INPUT LEDwhich indicates DC power and input signalstatus. If this LED is not illuminated uponpower-up, check wiring connections.When the signal is over 110% of the fullscale range, the INPUT LED flashes at 8Hz; below 0% it flashes at 4 Hz. Eachsetpoint has its own red LED that indicatesthe relay state. An il luminated LEDindicates a tripped condition.
This unit is not intrinsically safe.
KFDA-DCI
Wide range of DC current inputs
Field configurable input/output
3-way isolation
Accepts bipolar inputs
Power Supply Terminals 11+, 12- or Power RailNominal voltage 9-30 VDCPower consumption ≤ 2.5 W, 1.8 W typical
Input Terminals 1+, 2-Input current 1-100 mAExcitation (terminal 3+) 24 VDC @ 20 mAMaximum overload 170 mA max., 60 VDC on inputImpedance 20 Ω typical
Output Terminals 4, 5, and 6; 7, 8, and 9Type 2 SPDT (Form C) relaysCurrent ratings (resistive loads) 120 VAC @ 5A
240 VAC @ 2A28 VDC @ 5A
Mechanical life ≥ 107 operations
Repeatability (constant temp.)> 5 mA 0.1% of full scale< 5 mA 0.2% of full scaleLimit Differentials (deadbands)> 5 mA ±0.25-5% of span< 5 mA 1-5% of spanStabilityTemperature drift ±0.05% of full scale / ºC (max.)Power ±0.01% of full scale / % of power changeCommon Mode Rejection DC to 60 Hz: 120 dBIsolation 3-way 1,800 VDCResponse timeDynamic Deadband relay condition changes when proper
condition exists for 100 msNormal mode (analog filter) ≤ 400 ms, 200 ms typical
MechanicalHousing Makrolon KF style housing (see page 387)
Dimensions (mm) 115 x 20 x 118Weight 100 g (3.5 oz.)Protection (IEC) IP20
Operating Temperature 0ºC to +55ºC (+32ºF to +131ºF)
DC Current Input2 Form C ContactOutputs Isolator
KFDA-DCI
DC Input(+) 1
Output A Output B
DC Power Supply
(+24 VDC) 3
(– ) 2 4 5 6
7 8 9
11 (+) 12 (– )
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
167
Technical Data
Connection Diagram
Model Number
2002 IS Catalog
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Sig
nal C
onditio
ners
DC Voltage Input2 Form C ContactOutputs Isolator
The KFDA-DCV accepts a DC voltage inputand provides two adjustable relay outputs.This limit alarm also effectively eliminatesground loops with 1,800 VDC isolationseparating input, output and power supply.
Setpoints can be configured as HI or LO inselectable controlsafe or non-controlsafeoperating modes. The KFDA-DCV relies ondeadband (hysteresis) and constant samplingof the input to prevent false switching whenthe input varies slightly on either side of thesetoint. The input must remain beyond thesetpoint for 100ms, uninterrupted, to qualifyas a valid trip condition. To return the alarmto an untripped condition, the input signalmust be outside the deadband and remainthere for 100 ms. This time-based dynamicdeadband, in addition to the evaluation ofhysteresis, improves setpoint stability. Selectunipolar operation for inputs that do notchange in polarity.
The KFDA-DCV is equipped with three LEDs.The first is a green INPUT LED which indicatesDC power and input signal status. If this LEDdoes not illuminate on power-up, check wiringconnections. When the signal input is over110% of the full scale range, the INPUT LEDwill flash at 8 Hz; below 0% it will flash at 4Hz. Each setpoint has its own LED whichindicates the relay state; an illuminated LEDindicates a tripped condition.
This unit is not intrinsically safe.
KFDA-DCV
Wide range of DC voltage inputs
Field configurable inputs/outputs
3-way isolation
2 adjustable, independent relaycontact outputs
Power Supply Terminals 11+, 12- or Power RailNominal voltage 9-30 VDCPower consumption ≤ 2.5 W, 1.8 W typicalInrush current ≤ 300 mA max.
Input Terminals 1+, 2-Input voltage 10 mV to 200 VExcitation (terminal 3+) 24 VDC @ 20 mAImpedance > 100 kΩ typical
Output Terminals 4, 5, and 6; 7, 8 and 9Current rating (resistive loads) 120 VAC @ 5 A
240 VAC @ 2 A28 VDC @ 5 A
Mechanical life ≥ 107 operationsRepeatability (constant temperature):> 50 mV 0.1% of full scale< 50 mV 0.2% of full scaleLimit differentials (deadbands):> 50 mV 0.25-5% of span< 50 mV 1-5% of spanTemperature drift ± 0.05% of full scale / ºC (max.)Power ±0.01% of full scale/% of power changeCommon mode rejection DC to 60 Hz: 120 dBIsolation 3-way 1,800 VDCResponse time:Dynamic deadband relay condition changes when proper
condition exists for 100 msNormal mode (analog filtering) < 200 ms typical, 400 ms max.
MechanicalHousing Makrolon KF style housing (see page 387)Dimensions (mm) 115 x 20 x 118Weight 100 g (3.5 oz.)Protection (IEC) IP20
Operating Temperature 0ºC to +55ºC (+32ºF to +131ºF)
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
KFDA-DCV
DC Input(+) 1
Output A Output B
DC Power Supply
(+24 VDC) 3
(– ) 2 4 5 6
7 8 9
11 (+) 12 (– )
168
Technical Data
Connection Diagram
Model Number
2002 IS CatalogS
ignal C
ondit
ioners
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
The KFD2-GS-1.2W is a trip amplifier for twoindependently field-configurable limit alarms.Three-way galvanic isolated units convert 0/4-20mA, 0/1-5 V and 0/2-10 V signals into trip pointoutputs.
For high alarm indication, the status of the contactoutput changes when the setpoint is exceededand will not reset until a lower value is met. Thedifference between these states is the adjustablehysteresis.
The trip alarm is adjustable by a selector switchand potentiometer.
A monitoring voltage output of 0-10 V can be usedto adjust limit values and hysteresis withoutinterrupting the input signal.
This unit is not intrinsically safe.
KFD2-GS-1.2W
Single-channel, 24 VDC supply
Current and voltage analog inputs
2 programmable trip points
Power Supply Terminals 14+, 15- or Power RailNominal voltage 20-30 VDCNominal current ≤ 75 mAPower consumption ≤ 2.25 W, 1.68 W typical
InputMeasuring range voltage (terminals 1+, 3-) 0/1-5 VInput load 50 kΩMeasuring range voltage (terminals 1+, 3-) 0/2-10 VInput load 100 kΩMeasuring range voltage (terminals 2+, 3) 0/4-20 mAInput load 50 Ω
OutputOutput I (terminals 7, 8, 9) trip value 1Output II (terminals 10, 11, 12) trip value 2Contact load AC: 250V / 5A / 1250VA
DC: 125V / 5A / 150 W
FunctionResponse time 100 msAccuracy/repeatability < 0.5%Temperature drift 0.01% / ºC in reference to set limitsIsolation 1000 V
MechanicalHousing Material Makrolon Style KF housing (see page 387)Dimensions (mm) 115 x 20 x 118Weight 120 g (4.2 oz.)Protection (IEC) IP20
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
DC Current/VoltageInput 2 Form C ContactOutputs Isolator
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
8
79
14
1
Output 1
Output 2
Supply 24 VDC
KFD2-GS-1.2W
3
2
5
4
6
15
11
1012
Feed Back
Trip Value 1
Trip Value 2
0V...10V 2V...10V
0mA...20mA 4mA...20mA
Dip switchfunctionson sideof unit
Switch Position Function
S1.1 0 0/2V...10V input range1 0/1V...5V input range
S1.2 0 Low alarm output 11 High alarm output 1
S1.3 0 Low alarm output 111 High alarm output 11
S1.4 0 Relays open in alarm state output 11 Relays closed in alarm state output 1
S1.5 0 Relays open in alarm state output 111 Relays closed in alarm state output 11
S1.6 0 Output 1 independent of output 111 Limit 1 responds to both outputs
1 2 3 4 5 6
1
0
Inputrange
ON: Limit 1responds toboth outputs
High-/Low alarmMode ofoperation
169
Technical Data
Connection Diagram
Model Number
2002 IS Catalog
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Sig
nal C
onditio
ners
TransmitterPower SupplyIsolator
The KFD2-CRG-1.D transmitter powersupply is suited for a variet of measuringtasks. 2- and 3-wire transmitters as wellas active power supplies with 0/4-20 MAsignals can be connected. Two relays andan active 0/4-20 mA current output areavailable.
The input has lead breakage and short-circuit monitoring.
Programming is via a PC (usingPACTware) or by using the control panelon the front of the device.
This unit is not intrinsically safe.
KFD2-CRG-1.D
Current source or transmitterinputs
Analog output 0/4-20 mA
2 relay outputs
Lead breakage andshort-circuit monitoring
Galvanic isolation
Power Supply Terminals 23+, 24- or Power RailNominal voltage 20-30 VDCMax. voltage Um 40 VDCPower consumption ≈ 2.2 W
Input Terminals 1, 2 and 3Input signal 0/4-20 mAAvailable voltage ≥ 15 V at 20 mA
OutputOutput I Terminals 10, 11, 12Output II Terminals 16, 17, 18 Output I & II type Form C, SPDT contact Contact loading 250 VAC / 2A / cos ϕ ≥ 0.7; 40 VDC/2A Maximum voltage (Um) 40 VDC Pull-in/drop-out delay ≈ 20 ms / ≈ 20 msMechanical life 5 x 107 operationsOutput III Terminals 7, 8: analog signal Current range 0/4-20 mA Quiescent voltage ≤ 24 VDC Load ≤ 650Ω
Transfer CharacteristicsAccuracy 0.1% of full scale value (output < 10µA)Temperature current measurement: 0.003% / ºC
current output: 0.005% / ºCcurrent measurement & output: 0.006% / ºC
Linearization current measurement andcurrent output 0.025%
Input delay ≤ 200 msIsolation Galvanic isolation
MechanicalHousing Makrolon KF style housing (see page 387)Dimensions (mm) 115 x 40 x 118Weight 300 g (10.5 oz.)Protection (IEC) IP20
Operating Temperature -20ºC to +60ºC (-4ºF to +149ºF)
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
24 (– )23 (+)
8 (+)7 (– )
Output
PCDCV Power Supply
KFD2-CRG-1.D
Input
(– ) 2
(+) 1
3
3 3
3
(+) 1 (+) 1
(– ) 2
(– ) 2 101112161718
Output 1
Output 2
0/4...20mA
Collective Error Messaging
Relay 1
Relay 2
170
Technical Data
Connection Diagram
Model Number
2002 IS CatalogS
ignal C
ondit
ioners
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
KFU8-CRG-1.D
Transmitter PowerSupply Isolator
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
24 (– )23 (+)
8 (+)7 (– )
Output
PC
Universal Power
KFU8-CRG-1.D
Input
(– ) 2
(+) 1
3
3 3
3
(+) 1 (+) 1
(– ) 2
(– ) 2 101112161718
Output 1
Output 2
0/4...20mA
Relay 1
Relay 2
The KFU8-CRG-1.D transmitter powersupply is suited for a variety of measuringtasks. 2- and 3-wire transmitters as wellas active power supplies with 0/4-20 MAsignals can be connected. Two relays andan active 0/4-20 mA current output areavailable.
The input has lead breakage and shortcircuit monitoring.
The universal power requirement allowsAC or DC power of unit.
Programming is via a PC (using PACTware)or by using the control panel on the frontof the device.
This unit is not intrinsically safe.
Current source or transmitter inputs
Analog output 0/4-20 mA
2 relay outputs
Lead breakage andshort-circuit monitoring
Galvanic isolation
Power Supply Terminals 23, 24Nominal voltage 20-90 VDC or 48-253 VACMax. voltage Um 253 VDCPower consumption ≈ 2.2 W / 2.5 VA
Input Terminals 1, 2 and 3Input signal 0/4-20 mAAvailable voltage ≥ 15 V at 20 mA
OutputOutput I Terminals 10, 11, 12Output II Terminals 16, 17, 18 Output I & II type Form C, SPDT contact Contact loading 250 VAC / 2A / cos ϕ ≥ 0.7; 40 VDC/2A Maximum voltage (Um) 40 VDC Pull-in/drop-out delay ≈ 20 ms / ≈ 20 msMechanical life 5 x 107 operationsOutput III Terminals 7, 8: analog signal Current range 0/4-20 mA Quiescent voltage ≤ 24 VDC Load ≤ 650Ω
Transfer CharacteristicsAccuracy 0.1% of full scale value (output < 10µA)Temperature current measurement: 0.003% / ºC
current output: 0.005% / ºCcurrent measurement & output: 0.006% / ºC
Linearization current measurement andcurrent output 0.025%
Input delay ≤ 200 msIsolation Galvanic isolation
MechanicalHousing Makrolon KF style housing (see page 387)
Dimensions (mm) 115 x 40 x 118Weight 300 g (10.5 oz.)Protection (IEC) IP20
Operating Temperature -20ºC to +60ºC (-4ºF to +149ºF)
171
Technical Data
Connection Diagram
Model Number
2002 IS Catalog
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Sig
nal C
onditio
ners
Thermocouple Input2 Form C ContactOutputs Isolator
The KFDA-TC accepts a B, E, J, K, S, R or Ttype thermocouple input and provides twoadjustable contact outputs. This limit alarm alsoeffectively eliminates ground loops with 1,800VDC isolation separating input, output and powersupply. The KFDA-TC is configurable for multipletemperature ranges per thermocouple type. Italso accepts bipolar inputs and offers selectableupscale and downscale burnout detection.
Setpoints can be configured as HI or LO inselectable controlsafe or non-controlsafeoperating modes. The KFDA-TC relies ondeadband (hysteresis) and constant sampling ofthe input to prevent false switching when the inputvaries slightly on either side of the setpoint. Theinput must remain uninterrupted beyond thesetpoint for 100 ms to qualify as a valid tripcondition. To return the alarm to an untrippedcondition, the input signal must fall outside thedeadband and remain there for 100 ms. Thistime-based dynamic deadband improvessetpoint stability.
The KFDA-TC is equipped with three LEDs. Thefirst is a green INPUT LED which indicates DCpower and input signal status. If this LED doesnot illuminate during power-up, check wiringconnections. When the input signal is over 110%of the full scale range, the INPUT LED flashes at8 Hz; below 0% it flashes at 4 Hz. Each setpointhas its own red LED that indicates the relay state.An illuminated LED indicates a tripped condition.
This unit is not intrinsically safe.
KFDA-TC
Wide input range of thermocouples
Field configurable input/output
3-way isolation
2 adjustable independent relaycontact outputs
Power Supply Terminals 11+, 12- or Power RailNominal voltage 9-30 VDCPower consumption ≤ 2.5 W, 1.8 W typicalInrush current ≤ 300 mA
Input (not intrinsically safe) Terminals 1+, 2-Thermocouples B,E,J,K,R,S or TOverload ≤ ±10 VDC on inputImpedance > 1 MΩBurnout detection < 1.5 µA
Output (not intrinsically safe) Terminals 4, 5, and 6; 7, 8, and 9Type 2 SPDT (Form C) relaysCurrent rating 120 VAC @ 5 A
240 VAC @ 2 A28 VDC @ 5 A
Mechanical life ≥ 107 operationsRepeatability (constant temp.) 0.2% for temp. > 0ºC
0.3% for temp. < 0ºCLimit differentials (deadbands) 0.25-5% of spanTemperature drift ±0.05% of full scale / ºC (max.)Power ±0.01% of full scale / % power changeCommon mode rejection DC to 60 Hz: 120 dBIsolation 3-way 1,800 VDC
Response timeDynamic deadband relay condition changes when proper
condition exists for 100 msNormal mode (analog filter) < 250 ms
MechanicalHousing Material Makrolon Style KF housing (see page 387)Dimensions (mm) 115 x 20 x 118Weight 100 g (3.5 oz.)Protection (IEC) IP20
Operating Temperature 0ºC to +55ºC (+32ºF to +131ºF)
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
KFDA-TC
DC PowerSupply
11 (+) 12 (– )
7 8 9
Output B
(+) 1
(– ) 2
4 5 6
Output A
Thermocouple Input
172
Technical Data
Connection Diagram
Model Number
2002 IS CatalogS
ignal C
ondit
ioners
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
The KFDA-RTD limit alarm accepts a 3-wire RTDinput (Pt100, Pt500, Pt1000, Cu10, Cu100, Ni120,NiFe604) and provides two adjustable relayoutputs. This limit alarm also effectively eliminatesground loops with 1,800 VDC isolation separatinginput, output and power supply. The KFDA-RTDis configurable for up to eight temperature rangesfor each RTD type.
Setpoints can be configured as HI or LO inselectable controlsafe or non-controlsafe operatingmodes. The KFDA-RTD relies on deadband(hysteresis) and constant sampling of the input toprevent false switching when the input variesslightly on either side of the setpoint. The inputmust remain uninterrupted beyond the setpointfor 100 ms to qualify as a valid trip condition. Toreturn the alarm to an untripped condition, theinput signal must fall outside the deadband andremain there for 100 ms. This time-based dynamicdeadband improves setpoint stability.
The KFDA-RTD is outiftted with three LEDs. Thefirst is a green INPUT LED which indicates DCpower and input signal status. If this LED is notilluminated at power-up, check wiring connections.When the input signal is over 110% of the full scalerange, the INPUT LED flashes at 8 Hz; below 0%it flashes at 4 Hz. Each setpoint has its own redLED that indicates the relay state. An illuminatedLED indicates a tripped condition.
This unit is not intrinsically safe.
KFDA-RTD
Wide input range of RTD
Field configurable input/output
3-way isolation
2 adjustable independent relaycontact outputs
Power Supply Terminals 11+, 12- or Power RailNominal voltage 9-30 VDC (unregulated acceptable)Power consumption ≤ 2.5 W, 1.8 W typicalInrush current ≤ 300 mA
Input Terminals 1, 2 and 3Type 3-wire RTDsInput protection withstand ±5 VDCExcitation current:Pt100, Pt500, Pt1000 < 2 mANi120, Cu100, NiFe604 < 2 mACu10 < 10 mALead resistance 40% of base sensor resistance or
100 Ω (whichever is less) max. per lead
Output Terminals 4, 5 and 6; 7, 8 and 9Type 2 SPDT (Form C) relaysCurrent rating (resistive loads) 120 VAC @ 5 A
240 VAC @ 2 A28 VDC @ 5 A
Mechanical life ≥ 107 operationsRepeatability (constant temp.) 0.2% of full scaleLimit differentials (deadbands) 1-5% of spanTemperature drift ±0.05% of full scale / ºC (max.)Common mode rejection DC to 60 Hz: 120 dBIsolation 3-way 1,800 VDC
Response timeDynamic deadband relay condition changes when proper
condition exists for 100 msNormal mode (analog filter) ≤ 400 ms, 200 ms typical
MechanicalHousing Makrolon KF style housing (see page 387)
Dimensions (mm) 115 x 20 x 118Weight 100 g (3.5 oz.)Protection (IEC) IP20
Operating Temperature 0ºC to +55ºC (+32ºF to +131ºF)
RTD Input2 Form C ContactOutputs Isolator
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
KFDA-RTD
DC Power Supply
11 (+) 12 (– )
7 8 9
Output B 4 5 6
Output A
(– ) 2 (R) 3
(+) 1 RTD Input
173
Technical Data
Connection Diagram
Model Number
2002 IS Catalog
Pepperl+Fuchs® Inc. • Telephone (330) 486-0002 • FAX (330) 425-4607E-mail: [email protected] • www.am.pepperl-fuchs.com
Sig
nal C
onditio
ners
Universal Input 2 Form CContact Output / PCInterface Isolator
The KFD2-GU-1 universal input limit alarm isfield-configurable for 0-10 V, 0-20 mA, Pt100/Ni100 and all thermocouple inputs with three-way galvanic isolation. This unit also featuresinternal/external cold junction compensation(CJC) and burnout detection for thermocouplesand lead short circuit monitoring for RTDs andcurrent/voltage inputs. Calibration, adjustmentsand monitoring are achieved through a serialinterface to a PC.
All parameters are programmable through a K-ADP1 cable (sold separately) that provides theconnection between the programmingreceptacle of the KFD2-GU and the RS232 PCinterface.
Accessories include removable terminals withinternal cold junction compensation (K-CJC)and a K-SK programming software kit. The K-ADP1 cable and K-SK software kit are requiredunless the KFD2-GU is configured by P+F.
This unit is not intrinsically safe.
KFD2-GU-1
Universal temperature input
Programming & calibration via PC
3-way isolation
CJC for thermocouples and leadresistance compensation for RTDs
Power Supply Terminals 14+, 15- or Power RailNominal voltage 20-35 VDCMaximum voltage Um 40 VDCPower consumption 1.5 W
Input Terminals 1, 2, 3, 4, 5, 6Type Pt100, Ni100Thermocouple B,E,J,K,L,N,R,S or T
0-10 V, 0-20 mA, configuration withprogramming jack
Max. lead resistance ≤ 50 Ω per leadTest current 400 µA with RTDsNOTE: Switch off current for lead breakage monitoring during measurement
OutputOutput I (Limit 1) Terminals 7, 8 and 9Output II (Limit 2) Terminals 10, 11 and 12Contact load 253 VAC / 2 A / cos ø ≥ 0.6Mechanical life 2 x 107 operationsResponse time ≤ 370 msTemperature drift ±0.007% of switchpoint per ºC∆TPower ≤ 0.0035% of spanIsolation Galvanic isolation
MechanicalHousing Makrolon KF style housing (see page 387)
Dimensions (mm) 115 x 20 x 118Weight 100 g (3.5 oz.)Protection (IEC) IP20
Operating Temperature -20ºC to +60ºC (-4ºF to +140ºF)
Note: For information about programming,refer to our website at www.am.pepperl-fuchs.com
Sig
nal P
roce
ssor
KFD2-GU-1
11 (+) 12 (– )
7 8 9
Output 1
10 11 12
Output 2
DC Power Supply
(+) 6 (+) 5
(+) 4 (+) 3 (– ) 1 (– ) 2
(– ) 2 (– ) 2 (– ) 2
(– ) 1
(+) 3 (+) 3 (+) 3
(+) 4CJC Type K-CJC-GN
(+) 5
(– ) 2 (– ) 2 (– ) 2
(+) 6
(+) 1
(– ) 1
PC
K-ADPI