WaveLinx Wired UIM Universal Interface Module

4
Project Catalog # Type Prepared by Notes Date PS503150EN page 1 January 2021 Black 0V Violet Input 6 Blue Input 5 Green Input 4 Yellow Input 3 Orange Input 2 Brown Input 1 Red 12Vdc Dimensional and Wiring Details Typical Applications Office • Education • Healthcare • Hospitality • Retail WaveLinx Wired UIM Mini Universal Interface Module Top Product Features • 6 inputs which can be individually configured • 8 sequences with up to 30 steps per sequence • Only 45mm in diameter so can easily fit in a junction box • Configuration stored in non volatile memory • Configurable startup mode Product Features Interactive Menu • Ordering Information page 2 • Additional Resources page 3 • Connected Systems page 5 • Product Warranty 1.8” [46mm] 0.6” deep [15mm] 1.8” [46mm] Occupancy Sensor Tuning Control Receptacle Control Demand Response WaveLinx Wired 5-Wire Bus

Transcript of WaveLinx Wired UIM Universal Interface Module

Page 1: WaveLinx Wired UIM Universal Interface Module

Project Catalog # Type

Prepared by Notes Date

PS503150EN page 1January 2021

Black0V

VioletInput 6

BlueInput 5

GreenInput 4

YellowInput 3

OrangeInput 2

BrownInput 1

Red12Vdc

Dimensional and Wiring Details

Typical Applications

Office • Education • Healthcare • Hospitality • Retail

WaveLinx WiredUIM

Mini Universal Interface Module

Top Product Features• 6 inputs which can be individually configured• 8 sequences with up to 30 steps per sequence• Only 45mm in diameter so can easily fit in a junction box• Configuration stored in non volatile memory• Configurable startup mode

Product FeaturesInteractive Menu• Ordering Information page 2

• Additional Resources page 3

• Connected Systems page 5

• Product Warranty

1.8”[46mm]

0.6” deep[15mm]

1.8”[46mm]

OccupancySensor

TuningControl

ReceptacleControl

DemandResponse

WaveLinx Wired5-Wire Bus

Page 2: WaveLinx Wired UIM Universal Interface Module

UIM

PS503150EN page 2January 2021

Order Information

Catalog Number

Catalog Number Description

UIM Mini UIG interface module

Product SpecificationsKey Features• 6 inputs which each can be individually configured as 0-5V analog,

digital or photoelectric cell inputs• 8 sequences with up to 30 steps per sequence• 1.7” diameter interface easily fits in standard junction boxes• Configuration stored in Non Volatile EEPROM• Firmware storage in reflashable FLASH memory over WaveLinx Wired network• Configurable start up mode

Standards/Ratings• Manufactured in an ISO 9001 certified factory• CE compliant to all relevant standards • cULus Listed - Energy Management Equipment (UL916)• Manufactured in an ISO 9001 certified factory• Meets ASHRAE Standard 90.1 requirements• Meets IECC 2015 requirements• Meets CEC Title 24 requirements

Product Safety:• IEC 60950-1• UL 60950-1• EN 60950-1• CAN/CSA-C22.2 No. 60950-1

Environmental Regulations: • RoHS Directive 2011/65/EU• WEEE Directive 2012/19/EU

WarrantyConsult website for warranty information

+V

CAN-H

CAN-L

0V

SHIELD

Black0V

VioletInput 6

BlueInput 5

GreenInput 4

YellowInput 3

OrangeInput 2

BrownInput 1

Red12Vdc

OverviewThe UIM (Mini Universal Interface) has 6 inputs which can be individually configured as analogue inputs, digital inputs or photoelectric cell inputs.Press and Release actions can be defined individually for each of the inputs through software. This allows custom controls to be added to the WaveLinx Wired system.

Wiring Details

* Wiring from UIM to connected input devices should not exceed 32 feet.** Devices such as occupancy sensors may require switchpacks for proper operation.

WaveLinx Wired

Page 3: WaveLinx Wired UIM Universal Interface Module

UIM

PS503150EN page 3January 2021

System architectureSimple WaveLinx Wired system

wallstation

powerpack0-10V LEDcontroller

occupancy/daylight Sensor

WaveLinx Wired Local Bus (polarity, topology free)

dual technologyoccupancy sensor

WaveLinx Wired Area ControllerILS-00208 local busses

SCMD4

SCMD4

WaveLinx WiredArea Controller

relay pack for LED or plug load

LED luminaire with DALI driver

0-10V LED luminaire

Complete WaveLinx Wired system

S3

S2S1

S0

B3

B2B1

B0

A7A6

A5A4

A3

A2A1

A0

+PWR

-PWR

FRAME GND

RS 485

GND

RS 485-

RS 485+

ETHERNET

FG

PWR-

PWR+

SG

A-

B+

DMX Fixture

WallstationPowerpack

Occupancy/Daylight Sensor

0-10V LEDcontroller

WaveLinx Wired Local Bus

Occupancy Sensor

Dual Techoccupancysensor

LED Luminairewith 0-10V driver

LED Luminairewith DALI driver

Occupancy/Daylight Sensor

TC1Network timeclock

Circuit Breaker Panel

ILS-0020Small Area Controller0 Relays, 0-10V, 8 local busses

8 local busses

WaveLinx Wired Network (daisy chain wire using Cooper LCCP, LCCNP, or Belden 1502, 1502P)

WaveLinx Wired Local Bus

36 Relaysand 0-10V zones

SI-2-Dinstalled within a panel

AV & Partitoning

RI-2Relay Out

WaveLinx Wired Local Bus

SCD96DMX Out

DMX Fixture

Blind Control

CurtainControl

Circuit Breaker Panel

ILM-2110Medium Area Controller24 Relays, 12 0-10V, 4 local busses

Relay pack forLED or plug load

WaveLinx WiredConfigurationSoftware

Building LAN or VLAN

Building WLAN

ILL-3301Large Area Controller36 Relays, 36 0-10V, EG2 installed

LDCM(0-10V to Reverse Phase Module)

24 Relaysand 120-10V zones

Reverse phase track lighting

BMS ProBACnetBuildingManagement System

iLuminAPP

Wallstation

Wallstation

Circuit Breaker Panel

iLumin Touchscreen

CLS - INEOWallstation

WaveLinx Wired

Page 4: WaveLinx Wired UIM Universal Interface Module

UIM

Cooper Lighting Solutions1121 Highway 74 SouthPeachtree City, GA 30269P: 770-486-4800www.cooperlighting.com

© 2021 Cooper Lighting SolutionsAll Rights Reserved. Specifications and dimensions subject to change without notice.

PS503150EN page 4January 2021

View WaveLinx Network

and IT Guidance Technical Guide

Sample System Topology:This diagram shows the main components of the WaveLinx Wireless and Wired Connected Lighting system.The WaveLinx wireless system communicates using wireless mesh technology based on the IEEE 802.15.4 standard. A PoE LAN connection for each Wireless Area Controller (WAC) is required for power and data access to the building lighting network.The WaveLinx wired system controls the devices using relay, 0-10V, DMX and the WaveLinx wired digital local bus. The WaveLinx wired system connects to the building LAN using the EG2 module. Each WaveLinx wired area controller communicate on the WaveLinx wired network. The WaveLinx wired network supports over 60,000 devices.The Trellix Core, WaveLinx Area Controllers (WAC) and WaveLinx Ethernet Gateways (EG2) communicate with each other over the Ethernet network.Please refer to the WaveLinx Wireless Network and IT Guidance Technical Guide and WaveLinx Wired Network and IT Guidance Technical Guide for more information.

Wireless AreaController

WaveLinx WirelessSystem

Smartphone with

WaveLinx app

Trellix Core

Firewall

Up to 300 Wireless Area

Controllers (Trellix Core

Enterprise & Virtual)

Touchscreen

347V and 20A Dimming Relay

Room Based Occupancy Sensor

Wireless Controlled Lighting ready devices(up to 150 per WAC)

Area or Room(15 + 1 construction area)

ControlledReceptacle

Scene Wallstation

WaveLinx-Integrated Ambient

WaveLinx-IntegratedOutdoor

WaveLinx Wired

System

Touchscreen

20A Relay

Room Based Occupancy Sensor

Area or Room

Scene Wallstation

AddressableFixture

Relay ControlledFixture

WaveLinx Wired Network

wiredOR

wireless

IoTand

API

WaveLinx Wired local bus devices(up to 64 devices per local bus)

WaveLinx Wired Local Bus

Trellix Admin Trellix LightingTrellix ExchangePartner Apps

Smart Lighting Apps3rd Party Integration

Control Systems• Trellix• WaveLinx Wireless• WaveLinx Wired• VividTune

WaveLinx Wired