WATER-COOLED CHILLERS SEMI-HERMETIC
Embed Size (px)
Transcript of WATER-COOLED CHILLERS SEMI-HERMETIC

WATER-COOLED CHILLERS
SEMI-HERMETICPACKAGED SYSTEMS
EPA COMPLIANT
1 to 120Nominal Tons
ww
w.D
rake
Chi
ller
s.co
m
For More Information Call: (888) 289-7299
R407C & R404A
®

TABLE OF CONTENTS
Nomenclature 3
Selection Procedure 4
100S - 250S PWC Semi-Hermetic Chillers - Capacity Table (R404A) 5
301S - 300D PWC Semi-Hermetic Chillers - Capacity Table (R404A) 6
400D - 1000D PWC Semi-Hermetic Chillers - Capacity Table (R404A) 7
100S - 301S PWC Semi-Hermetic Chillers - Capacity Table (R407C) 8
351S - 600S PWC Semi-Hermetic Chillers - Capacity Table (R407C) 9
150D - 500D PWC Semi-Hermetic Chillers - Capacity Table (R407C) 10
601D - 1200D PWC Semi-Hermetic Chillers - Capacity Table (R407C) 11
Microprosessor Features 12
Standard Features and Options 13
Single Circuit (R404A) - Dimensional & Electrical Specifications 14
Dual Circuit (R404A) - Dimensional & Electrical Specifications 15
Single Circuit (R407C) - Dimensional & Electrical Specifications 16
Dual Circuit (R407C) - Dimensional & Electrical Specifications 17
Schematical Drawings - PWC 75S - PWC 600S 18 Schematical Drawings - PWC 150D - PWC 601D 19
Schematical Drawings - PWC 1000D & PWC 1200D 20
Tank Section - Dimensional Specifications, Features and Options 21
Glycol Factor Tables 22
Notes / Custom Built Chillers 23
Along with a complete line of standard products that Drake Refrigeration, Inc. offers, we also have the ability to custom build units to each customers particular needs.
Please contact the factory or your
Drake representative for a special
application.
Due to manufacturers’s policy of continu-ous product improvement, the manufacturer reserves the right to make changes without notice. Drawings in this booklet are represen-tations of the equipment shown. Contact the factory for specific unit drawings.
© 2012 Drake Refrigeration, Inc.All rights reserved.

Drake Refrigeration, Inc.2900 Samuel Drive • Bensalem, PA 19020(888) 289-7299Phone (215) 638-5515Fax (215) 638-5518www.drakechillers.com
Example: P WC L 301 S 3 - T3 - S
P P = Packaged ES = Evaporator Section
WC WC = Water-Cooled Condenser
L L = Low Temp. Model Blank = Standard Unit
301 Nominal HP Ex. 301 = 30HP 010 = 1HP etc.
S S = Single Circuit Unit D = Dual Circuit Unit
2 1 = R134a 3 = R407C 6 = R404A, R507
T3 Electrical Requirement S2 = 208/230-1-60 S6 = 220-1-50 T3 = 208/230-3-60 T7 = 200/208-3-50 S4 = 460-1-60 T9 = 380-3-50 T4 = 460-3-60 T5 = 575-3-60
S Compressor Type S = Semi-Hermetic
NOMENCLATURE
Low ambient, or lower leaving water temperatures, can require the recirculation of glycol solutions or other fluid blends.
These solutions can effect unit
capacities. Please consult the
factory on these or other special
applications for proper sizing.
3
®

SELECTION PROCEDURE
4
WATER-COOLED SELECTION PROCEDURES
To properly select an water-cooled packaged chiller, the following information must be known:
1. The required cooling capacity, BTUH. 2. Delta T of entering and leaving fluid temperatures. 3. Fluid factor (ex. water = 500). 4. GPM of process fluid to be circulated. 5. Design condensing water temperature.
If you know any three of the items 1 through 4 above, you can calculate the fourth by using the formulas below.
For 100% water:
Cooling capacity (in BTUH) = GPM x Delta T x 500
GPM = Capacity (in BTUH) Delta T x 500
Delta T = Capacity (in BTUH) GPM x 500 Sample selection:
Select a water cooled packaged chiller to cool 100 GPM of 100% water from 54ºF to 44ºF. Design condensing temperature 105ºF Find:
A) Water-cooled chiller model.
Solution:
1. Chilled fluid Delta T = 54°F - 44°F = 10°F 2. Capacity (in BTUH) = 100 GPM x 10°F Delta T x 500 = 500,000 BTUH 3. From the PWC chiller capacity tables, it can be determined that the PWC500D3 has the capacity to meet the requirements.
*Consult the factory on sizing chillers with glycol or any fluid other than water
Consult factory on sizing
chillers with glycol or any
fluid other than water.

Drake Refrigeration, Inc.2900 Samuel Drive • Bensalem, PA 19020(888) 289-7299Phone (215) 638-5515Fax (215) 638-5518www.drakechillers.com
100S - 250S PWC SEMI-HERMETIC CHILLERS
5
MODEL COMPRESSOR LWT°F
70 90 105 120
TONS KW EER TONS KW EER TONS KW EER TONS KW EER
100S 3DBNR12M
0.0 5.5 6.4 10.3 4.7 7.2 7.8 4.1 7.7 6.4 3.5 8.1 5.2
10.0 7.0 6.8 12.2 6.0 7.9 9.1 5.3 8.6 7.4 4.5 9.2 5.9
20.0 8.8 7.2 14.6 7.5 8.5 10.7 6.6 9.4 8.5 5.7 10.1 6.8
30.0 11.0 7.5 17.8 9.4 9.0 12.6 8.2 10.0 9.8 7.1 11.0 7.7
40.0 13.7 7.5 21.9 11.6 9.3 15.0 10.2 10.6 11.5 8.7 11.8 8.8
120S 3DFNR15M
0.0 6.8 8.0 10.3 5.8 8.9 7.8 5.1 9.6 6.4 4.4 10.2 5.2
10.0 8.7 8.6 12.1 7.4 9.9 9.0 6.5 10.7 7.3 5.6 11.4 5.9
20.0 11.0 9.1 14.5 9.3 10.6 10.5 8.2 11.7 8.4 7.0 12.6 6.7
30.0 13.8 9.5 17.5 11.7 11.3 12.4 10.2 12.6 9.7 8.8 13.8 7.6
40.0 17.2 9.6 21.4 14.5 11.9 14.6 12.6 13.5 11.2 10.8 14.9 8.6
150S 3DSNR17M
0.0 7.6 8.8 10.3 6.5 9.9 7.8 5.6 10.6 6.4 4.8 11.2 5.2
10.0 9.7 9.6 12.1 8.2 10.9 9.0 7.2 11.8 7.3 6.2 12.6 5.9
20.0 12.2 10.1 14.5 10.3 11.8 10.5 9.1 12.9 8.4 7.8 14.0 6.7
30.0 15.3 10.5 17.5 12.9 12.6 12.4 11.3 14.0 9.7 9.7 15.3 7.6
40.0 19.0 10.6 21.4 16.0 13.2 14.6 13.9 14.9 11.2 11.8 16.5 8.6
200S 4C2397SH
0.0 8.3 9.3 10.7 6.9 10.2 8.1 5.8 10.4 6.6 4.7 10.5 5.4
10.0 10.8 10.3 12.6 9.0 11.6 9.3 7.6 12.1 7.6 6.3 12.4 6.1
20.0 13.6 11.0 14.9 11.5 12.8 10.7 9.8 13.7 8.6 8.2 14.3 6.9
30.0 17.1 11.5 17.8 14.4 13.9 12.4 12.5 15.2 9.8 10.5 16.1 7.8
40.0 21.1 11.8 21.5 17.9 14.8 14.5 15.6 16.5 11.3 13.2 17.8 8.6
220S 4DBNR20M
0.0 9.8 11.3 10.4 8.2 12.6 7.8 7.0 13.4 6.3 6.0 14.2 5.1
10.0 12.6 12.1 12.4 10.3 13.8 9.0 8.9 14.9 7.2 7.5 15.9 5.7
20.0 16.1 12.8 15.1 13.2 14.9 10.6 11.3 16.3 8.3 9.6 17.5 6.6
30.0 20.2 13.1 18.5 16.6 15.8 12.6 14.3 17.6 9.7 12.1 19.2 7.6
40.0 24.8 13.2 22.6 20.4 16.5 14.9 17.6 18.7 11.2 14.9 20.7 8.6
250S 4DHNR22M
0.0 10.6 12.0 10.5 8.8 13.4 7.9 7.6 14.3 6.4 6.5 15.1 5.1
10.0 13.5 12.9 12.6 11.2 14.7 9.1 9.6 15.8 7.2 8.1 16.9 5.8
20.0 17.3 13.6 15.3 14.2 15.8 10.8 12.2 17.3 8.4 10.3 18.7 6.6
30.0 21.7 13.9 18.7 17.8 16.8 12.7 15.3 18.7 9.8 13.0 20.4 7.6
40.0 26.7 14.0 22.9 22.0 17.6 15.0 18.9 19.9 11.4 16.0 22.0 8.7
Capacity TableR404A
®
1. Capacities on this chart are based on R-404A. Low ambient or lower leaving water temperatures can require the use of a glycol solution or other fluid blends. These solutions affect unit capacities. Please consult the factory on these or other special fluids.
2. KW input is for compressor(s) only.3. EER = Energy Efficiency Ratio (BTU/watt-hour). Power inputs include compressor(s) and control power.

301S - 301D PWC SEMI-HERMETIC CHILLERS
6
R404ACapacity Table
MODEL COMPRESSOR LWT°F
70 90 105 120
TONS KW EER TONS KW EER TONS KW EER TONS KW EER
301S 6DBNR32M
0.0 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
10.0 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
20.0 22.0 17.6 15.0 18.2 20.4 10.7 16.3 22.6 8.7 14.4 24.3 7.1
30.0 28.1 18.2 18.6 23.6 21.7 13.0 21.1 24.4 10.4 18.5 26.8 8.3
40.0 35.2 18.2 23.2 29.9 22.6 15.9 26.8 25.9 12.4 23.7 28.8 9.9
351S 6B4709PH
0.0 16.0 18.9 10.2 13.4 20.8 7.7 11.5 21.9 6.3 9.7 22.8 5.1
10.0 20.6 20.7 11.9 17.4 23.4 8.9 15.0 25.0 7.2 12.7 26.5 5.8
20.0 26.1 22.3 14.0 22.1 25.7 10.3 19.2 28.0 8.2 16.3 30.0 6.5
30.0 32.6 23.6 16.6 27.7 27.9 11.9 24.1 30.8 9.4 20.6 33.4 7.4
40.0 40.2 24.5 19.7 34.3 29.8 13.8 29.9 33.3 10.8 25.6 36.6 8.4
400S 6B5406PH
0.0 18.5 22.1 10.0 15.5 24.3 7.7 13.4 25.6 6.3 11.3 26.7 5.1
10.0 23.7 24.3 11.7 20.0 27.3 8.8 17.4 29.2 7.2 14.8 30.8 5.8
20.0 29.9 26.3 13.7 25.4 30.1 10.1 22.2 32.6 8.2 18.9 34.9 6.5
30.0 37.4 28.1 16.0 31.8 32.8 11.7 27.8 36.0 9.3 23.8 38.9 7.4
40.0 45.2 29.5 18.8 39.4 35.2 13.4 34.4 39.1 10.6 29.5 42.7 8.3
500S 6B6462PH
0.0 22.2 27.0 9.8 18.7 29.4 7.6 16.1 30.9 6.2 13.5 32.0 5.0
10.0 28.3 29.7 11.4 24.0 33.1 8.7 20.8 35.2 7.1 17.5 37.2 5.7
20.0 35.6 32.0 13.3 30.3 36.5 10.0 26.4 39.5 8.0 22.4 42.3 6.4
30.0 44.2 34.0 15.6 37.8 39.7 11.4 33.0 43.7 9.1 28.1 47.5 7.1
40.0 54.5 35.5 18.4 46.7 42.6 13.2 40.8 47.6 10.3 34.9 52.5 8.0
150D 3DANR10M
0.0 9.5 10.6 10.9 7.7 11.8 7.9 6.8 12.6 6.5 5.9 13.4 5.3
10.0 12.3 11.4 13.1 9.9 13.0 9.2 8.7 14.2 7.4 7.6 15.2 6.0
20.0 47.5 12.0 16.0 12.7 14.0 10.9 11.0 15.4 8.6 9.6 16.8 6.8
30.0 20.0 12.2 19.8 16.0 14.8 13.1 13.8 16.6 10.0 11.8 18.2 7.8
40.0 25.0 12.2 24.9 20.0 15.2 15.8 17.2 17.4 11.8 14.6 19.6 9.0
200D 3DBNR12M
0.0 10.9 12.8 10.3 9.3 14.4 7.8 8.2 15.4 6.4 7.0 16.2 5.2
10.0 13.9 13.6 12.2 11.9 15.8 9.1 10.5 17.2 7.4 9.1 18.4 5.9
20.0 17.5 14.4 14.6 15.1 17.0 10.7 13.3 18.8 8.5 11.4 20.2 6.8
30.0 22.0 15.0 17.8 18.8 18.0 12.6 16.4 20.0 9.8 14.2 22.0 7.7
40.0 27.3 15.0 21.9 23.2 18.6 15.0 20.3 21.2 11.5 17.3 23.6 8.8
240D 3DFNR15M
0.0 13.7 16.0 10.3 11.7 17.8 7.8 10.2 19.2 6.4 8.8 20.4 5.2
10.0 17.3 17.2 12.1 14.8 19.8 9.0 13.0 21.4 7.3 11.2 22.8 5.9
20.0 22.0 18.2 14.5 18.7 21.2 10.5 16.3 23.4 8.4 14.1 25.2 6.7
30.0 27.7 19.0 17.5 23.3 22.6 12.4 20.3 25.2 9.7 17.5 27.6 7.6
40.0 34.3 19.2 21.4 29.0 23.8 14.6 25.2 27.0 11.2 21.5 29.8 8.6
300D 3DSNR17M
0.0 15.2 17.6 10.3 12.9 19.8 7.8 11.3 21.2 6.4 9.7 22.4 5.2
10.0 19.3 19.2 12.1 16.4 21.8 9.0 14.4 23.6 7.3 12.4 25.2 5.9
20.0 24.3 20.2 14.5 20.7 23.6 10.5 18.2 25.8 8.4 15.6 28.0 6.7
30.0 30.5 21.0 17.5 25.8 25.2 12.4 22.5 28.0 9.7 19.3 30.6 7.6
40.0 38.0 21.2 21.4 32.0 26.4 14.6 27.8 29.8 11.2 23.7 33.0 8.6
1. Capacities on this chart are based on R-404A. Low ambient or lower leaving water temperatures can require the use of a glycol solution or other fluid blends. These solutions affect unit capacities. Please consult the factory on these or other special fluids.
2. KW input is for compressor(s) only.3. EER = Energy Efficiency Ratio (BTU/watt-hour). Power inputs include compressor(s) and control power.

Drake Refrigeration, Inc.2900 Samuel Drive • Bensalem, PA 19020(888) 289-7299Phone (215) 638-5515Fax (215) 638-5518www.drakechillers.com
400D - 1000D PWC SEMI-HERMETIC CHILLERS
7
MODEL COMPRESSOR LWT°F
70 90 105 120
TONS KW EER TONS KW EER TONS KW EER TONS KW EER
400D 4C2397SH
0.0 16.6 18.6 10.7 13.7 20.4 8.1 11.5 20.8 6.6 9.4 21.0 5.4
10.0 21.5 20.6 12.6 17.9 23.2 9.3 15.2 24.2 7.6 12.6 24.8 6.1
20.0 27.3 22.0 14.9 22.9 25.6 10.7 19.7 27.4 8.6 16.4 28.6 6.9
30.0 34.1 23.0 17.8 28.8 27.8 12.4 24.9 30.4 9.8 20.9 32.2 7.8
40.0 42.2 23.6 21.5 35.8 29.6 14.5 31.1 33.0 11.3 26.3 35.6 8.6
440D 4DBNR20M
0.0 19.7 22.6 10.4 16.3 25.2 7.8 14.1 26.8 6.3 12.0 28.4 5.1
10.0 25.2 24.2 12.4 20.7 27.6 9.0 17.8 29.8 7.2 15.1 31.8 5.7
20.0 32.2 25.6 15.1 26.3 29.8 10.6 22.7 32.6 8.3 19.2 35.0 6.6
30.0 40.3 26.2 18.5 33.2 31.6 12.6 28.5 35.2 9.7 24.2 38.4 7.6
40.0 49.7 26.4 22.6 40.8 33.0 14.9 35.2 37.4 11.2 29.8 41.4 8.6
500D 4DHNR22M
0.0 21.2 24.0 10.5 17.5 26.8 7.9 15.2 28.6 6.4 12.9 30.2 5.1
10.0 27.0 25.8 12.6 22.3 29.4 9.1 19.2 31.6 7.2 16.2 33.8 5.8
20.0 34.5 27.2 15.3 28.3 31.6 10.8 24.3 34.6 8.4 20.7 37.4 6.6
30.0 43.3 27.8 18.7 35.7 33.6 12.7 30.7 37.4 9.8 26.0 40.8 7.6
40.0 53.3 28.0 22.9 44.0 35.2 15.0 37.8 39.8 11.4 32.0 44.0 8.7
601D 6DBNR32M
0.0 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
10.0 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
20.0 44.0 35.2 15.0 36.3 40.8 10.7 32.7 45.2 8.7 28.8 48.6 7.1
30.0 56.2 36.4 18.6 47.2 43.4 13.0 42.2 48.8 10.4 37.0 53.6 8.3
40.0 70.3 36.4 23.2 59.8 45.2 15.9 53.7 51.8 12.4 47.3 57.6 9.9
701D 6B4709PH
0.0 32.0 37.8 10.2 26.8 41.6 7.7 23.0 43.8 6.3 19.4 45.6 5.1
10.0 41.2 41.4 11.9 34.7 46.8 8.9 30.0 50.0 7.2 25.4 53.0 5.8
20.0 52.1 44.6 14.0 44.2 51.4 10.3 38.3 56.0 8.2 32.7 60.0 6.5
30.0 65.1 47.2 16.6 55.4 55.8 11.9 48.2 61.6 9.4 41.2 66.8 7.4
40.0 80.5 49.0 19.7 68.6 59.6 13.8 59.9 66.6 10.8 51.2 73.2 8.4
800D 6B5406PH
0.0 36.9 44.2 10.0 31.0 48.6 7.7 26.8 51.2 6.3 22.6 53.4 5.1
10.0 47.4 48.6 11.7 40.1 54.6 8.8 34.8 58.4 7.2 29.6 61.6 5.8
20.0 59.9 52.6 13.7 50.9 60.2 10.1 44.4 65.2 8.2 37.9 69.8 6.5
30.0 74.7 56.2 16.0 63.7 65.6 11.7 55.6 72.0 9.3 47.6 77.8 7.4
40.0 90.5 59.0 18.8 78.8 70.4 13.4 68.9 78.2 10.6 59.0 85.4 8.3
1000D 6B6462PH
0.0 44.3 54.0 9.8 37.3 58.8 7.6 32.1 61.8 6.2 26.9 64.0 5.0
10.0 56.6 59.4 11.4 48.0 66.2 8.7 41.6 70.4 7.1 35.1 74.4 5.7
20.0 71.2 64.0 13.3 60.7 73.0 10.0 52.8 79.0 8.0 44.8 84.6 6.4
30.0 88.5 68.0 15.6 75.7 79.4 11.4 66.0 87.4 9.1 56.3 95.0 7.1
40.0 109.0 71.0 18.4 93.4 85.2 13.2 81.7 95.2 10.3 69.7 105.0 8.0
Capacity TableR404A
®
1. Capacities on this chart are based on R-404A. Low ambient or lower leaving water temperatures can require the use of a glycol solution or other fluid blends. These solutions affect unit capacities. Please consult the factory on these or other special fluids.
2. KW input is for compressor(s) only.3. EER = Energy Efficiency Ratio (BTU/watt-hour). Power inputs include compressor(s) and control power.

100S - 301S PWC SEMI-HERMETIC CHILLERSCapacity Table R407C
MODEL COMPRESSOR LWT°F
70 90 105 120
TONS KW EER TONS KW EER TONS KW EER TONS KW EER
100S 3DBNR12M
42.0 13.4 6.1 26.5 11.7 7.9 17.9 10.6 9.2 13.8 9.6 10.6 10.9
44.0 14.1 6.1 28.0 12.2 7.9 18.7 11.1 9.3 14.3 10.0 10.7 11.3
45.0 14.4 6.0 28.7 12.5 7.9 19.1 11.3 9.3 14.6 10.2 10.8 11.4
50.0 16.2 5.9 33.0 14.0 7.8 21.4 12.6 9.4 16.1 11.4 11.0 12.4
120S 3DFNR15M
42.0 15.8 8.3 22.9 13.8 9.9 16.7 12.4 11.4 13.1 11.1 13.1 10.4
44.0 16.6 8.3 24.0 14.4 10.0 17.4 13.0 11.6 13.5 11.7 13.1 10.7
45.0 17.1 8.3 24.5 14.8 10.0 17.7 13.3 11.6 13.8 11.9 13.2 10.8
50.0 19.3 8.4 27.6 16.5 10.1 19.7 14.8 11.8 15.1 13.3 13.6 11.7
150S 3DSNR17M
42.0 18.2 8.8 24.7 15.6 11.1 17.0 14.0 12.8 13.2 12.7 14.6 10.5
44.0 19.1 8.8 26.0 16.3 11.1 17.7 14.7 12.9 13.7 13.3 14.7 10.8
45.0 19.6 8.8 26.7 16.7 11.1 18.1 15.0 13.0 13.9 13.5 14.8 11.0
50.0 22.0 8.7 30.4 18.7 11.1 20.2 16.8 13.2 15.3 15.0 15.2 11.9
200S 4C2397SH
42.0 18.2 9.9 22.2 15.9 12.3 15.4 14.1 13.9 12.1 12.2 15.4 9.6
44.0 19.1 9.9 23.1 16.6 12.5 16.0 14.7 14.1 12.5 12.8 15.6 9.8
45.0 19.5 9.9 23.5 17.0 12.5 16.3 15.1 14.2 12.7 13.1 15.8 10.0
50.0 21.7 10.0 26.0 18.9 12.8 17.8 16.8 14.7 13.8 14.7 16.5 10.7
220S 4DBNR20M
42.0 23.3 11.4 24.6 20.3 14.6 16.7 17.9 16.8 12.8 15.6 18.8 10.0
44.0 24.3 11.3 25.8 21.2 14.7 17.3 18.8 17.0 13.3 16.4 19.1 10.3
45.0 24.8 11.3 26.4 21.6 14.7 17.7 19.2 17.1 13.5 16.8 19.2 10.5
50.0 27.4 10.9 30.2 24.0 14.7 19.7 21.4 17.3 14.9 18.9 19.7 11.5
250S 4DHNR22M
42.0 27.5 13.3 24.8 23.6 16.4 17.3 20.5 18.5 13.3 17.5 20.4 10.3
44.0 29.1 13.5 25.9 24.9 16.6 18.0 21.6 18.8 13.8 18.4 20.7 10.7
45.0 29.9 13.6 26.5 25.6 16.7 18.4 22.1 18.9 14.1 18.8 20.9 10.9
50.0 34.3 14.1 29.3 29.1 17.4 20.2 25.0 19.6 15.4 21.2 21.7 11.7
301S 6DBNR32M
42.0 35.2 18.4 22.9 29.3 21.3 16.5 25.7 23.8 13.0 22.9 26.4 10.4
44.0 36.8 18.4 24.0 30.5 21.4 17.1 26.8 24.0 13.4 23.9 26.7 10.8
45.0 37.5 18.4 24.5 31.1 21.4 17.4 27.3 24.1 13.6 24.4 26.9 10.9
50.0 41.3 18.0 27.5 33.9 21.4 19.1 29.8 24.3 14.7 26.9 27.7 11.7
8
1. Capacities on this chart are based on R-407C. Low ambient or lower leaving water temperatures can require the use of a glycol solution or other fluid blends. These solutions affect unit capacities. Please consult the factory on these or other special fluids.
2. KW input is for compressor(s) only.3. EER = Energy Efficiency Ratio (BTU/watt-hour). Power inputs include compressor(s) and control power.

Drake Refrigeration, Inc.2900 Samuel Drive • Bensalem, PA 19020(888) 289-7299Phone (215) 638-5515Fax (215) 638-5518www.drakechillers.com
301S - 600S PWC SEMI-HERMETIC CHILLERS R407C Capacity Table
MODEL COMPRESSOR LWT°F
70 90 105 120
TONS KW EER TONS KW EER TONS KW EER TONS KW EER
351S 6B4709PH
42.0 35.0 18.8 22.3 30.5 24.0 15.3 27.2 27.6 11.8 23.9 31.0 9.3
44.0 36.5 18.8 23.3 31.9 24.1 15.9 28.5 27.9 12.2 25.1 31.5 9.6
45.0 37.3 18.8 23.8 32.6 24.2 16.2 29.1 28.0 12.5 25.6 31.7 9.7
50.0 41.5 18.7 26.6 36.3 24.5 17.8 32.5 28.7 13.6 28.7 32.7 10.5
400S 6B5406PH
42.0 39.6 22.4 21.3 34.8 28.3 14.8 31.0 32.4 11.8 27.1 36.0 9.0
44.0 41.3 22.4 22.1 36.4 28.5 15.3 32.4 32.8 11.9 28.3 36.5 9.3
45.0 42.3 22.4 22.6 37.2 28.6 15.6 33.2 33.0 12.1 29.0 36.8 9.5
50.0 47.1 22.5 25.1 41.5 29.1 17.1 37.1 33.8 13.2 32.5 38.1 10.2
500S 6B6462PH
42.0 47.1 28.7 19.7 41.4 34.7 14.3 37.2 39.2 11.4 33.0 43.7 9.1
44.0 49.2 28.8 20.5 43.2 35.0 14.8 38.8 39.6 11.8 34.5 44.4 9.3
45.0 50.2 28.8 20.9 44.2 35.1 15.1 39.7 39.9 12.0 35.3 44.7 9.5
50.0 55.8 29.0 23.1 49.2 35.8 16.5 44.3 41.0 13.0 39.4 46.3 10.2
600S 8DSNR67M
42.0 61.6 34.6 21.4 55.1 43.5 15.2 50.3 49.4 12.2 45.5 54.7 10.0
44.0 64.1 34.5 22.3 57.4 43.8 15.7 52.3 50.0 12.6 47.5 55.5 10.3
45.0 65.4 34.5 22.8 58.6 44.0 16.0 53.4 50.3 12.8 48.5 55.9 10.4
50.0 72 34.1 25.4 64.5 44.6 17.4 59.0 51.6 13.7 53.7 57.9 11.1
9
®
1. Capacities on this chart are based on R-407C. Low ambient or lower leaving water temperatures can require the use of a glycol solution or other fluid blends. These solutions affect unit capacities. Please consult the factory on these or other special fluids.
2. KW input is for compressor(s) only.3. EER = Energy Efficiency Ratio (BTU/watt-hour). Power inputs include compressor(s) and control power.
PWCL 270S6-T4-S (Low Temperature) Model w/ Brazed Plate Heat Exchanger

PWC 440D3 Model (shown)
150D - 500D PWC SEMI-HERMETIC CHILLERSCapacity Table R407C
MODEL COMPRESSOR LWT°F
70 90 105 120
TONS KW EER TONS KW EER TONS KW EER TONS KW EER
150D 3DANR10M
42.0 22.8 10.6 25.9 19.8 13.4 17.8 17.8 15.6 13.7 16.0 17.8 10.8
44.0 24.0 10.6 27.4 20.8 13.4 18.6 18.7 15.8 14.2 16.8 18.0 11.2
45.0 24.6 10.6 28.1 21.3 13.4 19.0 19.1 15.8 14.5 17.2 18.2 11.4
50.0 27.8 10.2 32.4 23.8 13.4 21.3 21.3 16.0 16.0 19.1 18.6 12.4
200D 3DBNR12M
42.0 26.8 12.2 26.5 23.3 15.8 17.9 21.2 18.4 13.8 19.2 21.2 10.9
44.0 28.2 12.2 28.0 24.4 15.8 18.7 22.2 18.6 14.3 20.0 21.4 11.3
45.0 28.8 12.0 28.7 25.0 15.8 19.1 22.7 18.6 14.6 20.4 21.6 11.4
50.0 32.4 11.8 33 27.9 15.6 21.4 25.2 18.8 16.1 22.8 22.0 12.4
240D 3DFNR15M
42.0 31.7 16.6 22.9 27.5 19.8 16.7 49.7 22.8 13.1 22.3 26.2 10.4
44.0 33.3 16.6 24.0 28.8 20.0 17.4 26.0 23.2 13.5 23.3 26.2 10.7
45.0 34.2 16.6 24.5 29.5 20.0 17.7 26.6 23.2 13.8 23.8 26.4 10.8
50.0 38.5 16.8 27.6 33.0 20.2 19.7 29.6 23.6 15.1 26.5 27.2 11.7
300D 3DSNR17M
42.0 36.3 17.6 24.7 31.2 22.2 17.0 28.1 25.6 13.2 25.4 29.2 10.5
44.0 38.2 17.6 26.0 32.7 22.2 17.7 29.4 25.8 13.7 26.5 29.4 10.8
45.0 39.2 17.6 26.7 33.3 22.2 18.1 30.1 26.0 13.9 27.1 29.6 11.0
50.0 44.0 17.4 30.4 37.3 22.2 20.2 33.5 26.4 15.3 30.1 30.4 11.9
400D 4C2397SH
42.0 36.5 19.8 22.2 31.7 24.6 15.4 28.2 27.8 12.1 24.5 30.8 9.6
44.0 38.1 19.8 23.1 33.2 25.0 16.0 29.5 28.2 12.5 25.7 31.2 9.8
45.0 39.0 19.8 23.5 33.9 25.0 16.3 30.1 28.4 12.7 26.3 31.6 10.0
50.0 43.4 20.0 26.0 37.8 25.6 17.8 33.7 29.4 13.8 29.3 33.0 10.7
440D 4DBNR20M
42.0 46.7 22.8 24.6 40.5 29.2 16.7 35.8 33.6 12.8 31.3 37.6 10.0
44.0 48.5 22.6 25.8 42.3 29.4 17.3 37.5 34.0 13.3 32.8 38.2 10.3
45.0 49.5 22.6 26.4 43.2 29.4 17.7 38.3 34.2 13.5 33.5 38.4 10.5
50.0 54.8 21.8 30.2 48.0 29.4 19.7 42.8 34.6 14.9 37.8 39.4 11.5
500D 4DHNR22M
42.0 55.0 26.6 24.8 47.2 32.8 17.3 41.0 37.0 13.3 35.0 40.8 10.3
44.0 58.2 27.0 25.9 49.8 33.2 18.0 43.2 37.6 13.8 36.8 41.4 10.7
45.0 59.8 27.2 26.5 51.2 33.4 18.4 44.2 37.8 14.1 37.7 41.8 10.9
50.0 68.7 28.2 29.3 58.2 34.8 20.2 50.0 39.2 15.4 42.3 43.4 11.7
1. Capacities on this chart are based on R-407C. Low ambient or lower leaving water temperatures can require the use of a glycol solution or other fluid blends. These solutions affect unit capacities. Please consult the factory on these or other special fluids.
2. KW input is for compressor(s) only.3. EER = Energy Efficiency Ratio (BTU/watt-hour).
Power inputs include compressor(s) and control power.
10

Drake Refrigeration, Inc.2900 Samuel Drive • Bensalem, PA 19020(888) 289-7299Phone (215) 638-5515Fax (215) 638-5518www.drakechillers.com
601D - 1200D PWC SEMI-HERMETIC CHILLERS R407C Capacity Table
MODEL COMPRESSOR LWT°F
70 90 105 120
TONS KW EER TONS KW EER TONS KW EER TONS KW EER
601D 6DBNR32M
42.0 70.3 36.8 22.9 58.5 42.6 16.5 51.3 47.6 13.0 45.8 52.8 10.4
44.0 73.5 36.8 24.0 61.0 42.8 17.1 53.5 48.0 13.4 47.8 53.4 10.8
45.0 75.0 36.8 24.5 62.2 42.8 17.4 54.5 48.2 13.6 48.8 53.8 10.9
50.0 82.5 36.0 27.5 67.8 42.8 19.1 59.5 48.6 14.7 53.8 55.4 11.7
701D 6D4709PH
42.0 70.0 37.6 22.3 61.0 48.0 15.3 54.3 55.2 11.8 47.8 62.0 9.3
44.0 73.0 37.6 23.3 63.8 48.2 15.9 56.9 55.8 12.2 50.1 63.0 9.6
45.0 74.7 37.6 23.8 65.2 48.4 16.2 58.2 56.0 12.5 51.3 63.4 9.7
50.0 83.0 37.4 26.6 72.6 49.0 17.8 64.9 57.4 13.6 57.3 65.4 10.5
800D 6B5406PH
42.0 79.2 44.8 21.3 69.6 56.6 14.8 62.0 64.8 11.8 54.1 72.0 9.0
44.0 82.7 44.8 22.1 72.7 57.0 15.3 64.9 65.6 11.9 56.7 73.0 9.3
45.0 84.6 44.8 22.6 74.4 57.2 15.6 66.4 66.0 12.1 58.0 73.6 9.5
50.0 94.1 45.0 25.1 82.9 58.2 17.1 74.1 67.6 13.2 65.0 152.4 10.2
1000D 6B6462PH
42.0 94.2 57.4 19.7 82.8 69.4 14.3 74.3 78.4 11.4 65.9 87.4 9.1
44.0 98.3 57.6 20.5 86.5 70.0 14.8 77.7 79.2 11.8 69.0 88.8 9.3
45.0 100.4 57.6 20.9 88.4 70.2 15.1 79.4 79.8 12.0 70.5 178.8 9.5
50.0 111.7 58.0 23.1 98.3 71.6 16.5 88.5 82.0 13.0 78.7 92.6 10.2
1200D 8DSNR67M
42.0 123.2 69.2 21.4 110.2 87.0 15.2 100.5 98.8 12.2 91.0 109.4 10.0
44.0 128.2 69.0 22.3 114.8 87.6 15.7 104.7 100.0 12.6 95.0 111.0 10.3
45.0 130.8 69.0 22.8 117.2 88.0 16.0 106.8 100.6 12.8 97.0 111.8 10.4
50.0 144.0 68.2 25.4 129.0 89.2 17.4 118.0 103.2 13.7 107.3 115.8 11.1
11
1. Capacities on this chart are based on R-407C. Low ambient or lower leaving water temperatures can require the use of a glycol solution or other fluid blends. These solutions affect unit capacities. Please consult the factory on these or other special fluids.
2. KW input is for compressor(s) only.3. EER = Energy Efficiency Ratio (BTU/watt-hour). Power inputs include compressor(s) and control power.
®
PWC 1000D Model (shown)

Standard Features
• Control operates to a +/- 1°F accuracy• Powered from the chiller 24 volt control circuit. No high voltage interference.• 1 or 2 compressor control capability• Operates and displays in °F and °C• Controls chiller on inlet or outlet temperature• Scroll through set up and review mode• 30-second compressor time delay to prevent short cycling and nuisance faults• 60-second hot gas solenoid delay to prevent false hot gas feeding during compressor start up• Lock out relay shuts down the chiller when control fault settings activate• Automatic compressor lead lag on dual circuit chillers• Weather resistant for outdoor use• Basic chiller functionality for ease of set up and operation• Factory configured for job site operation• Factory default function code to reset the controller to the initial factory settings• Two L.E.D. display windows a) Inlet and outlet temperature during chiller operation b) Displays refrigerant high and low pressure in review mode 1) No cap tubes to break causing a loss of refrigerant and down time 2) No refrigerant revcovery to change out the pressure transducer• Indicator lights a) Chiller control power on/off switch with green indicator b) System pump on/off switch with green indicator c) Compressor run indicator lights d) High and low refrigerant pressure red fault indicator e) Low fluid flow red indicator• Display flashes all chiller safety faults a) High fluid temperature outlet alarm Display only - does not shut the chiller down b) Low fluid temperature outlet alarm Shuts down the chiller and requires manual reset c) High refrigerant pressure Shuts down the chiller and requires manual reset d) Low refrigerant pressure Shuts down the chiller and requires manual reset e) Low water flow through evaporator Shuts down the chiller and automatically resets when flow is restored• Monitors and logs compressor run hours
MICROPROCESSOR FEATURES
12
Indicator light display
Scrolling up & down buttons
Control power on/off switch
L.E.D. display
System pump power on/off switch

Drake Refrigeration, Inc.2900 Samuel Drive • Bensalem, PA 19020(888) 289-7299Phone (215) 638-5515Fax (215) 638-5518www.drakechillers.com
13
PWC SEMI-HERMETICR404A & R407C Packaged, Air-Cooled Chillers
Standard Features (all models)
• Microprocessor controller (see page 0 for details)• 24V control transformer • Refrigerant suction accumulator • (1-12HP) 316 STAINLESS STEEL, copper brazed plate evaporator with 1/2” insulation and secured in a steel bracket• (15-120HP) Shell and tube chiller barrel• Water flow switch• Semi-hermetic compressor with crankcase heater• Compressor vibration eliminators & spring isolator kit• Compressor oil safety control• Compressor and condenser motor contactors• Condenser(s): • Condenser clean out ports• Liquid line drier, sightglass, solenoid, TEV• Replaceable core liquid line drier (15 to 120HP)• Removable/hinged access panels• Galvanized steel sheet metal cabinet and base frame• 1/2” insulation on all water and refrigerant suction lines• Complete refrigerant charge from factory• Computerized factory run test under load conditions
Available Options (all models)
• ChillerGuard® Internet Interface Device• Compressor cylinder unloading 7.5HP and up• Compressor fusing• Fused disconnect• Non-fused disconnect• Factory installed evaporator heat tape freeze protection thermostatically controlled• Special piping for de-ionized and reverse osmosis water systems• Shell and tube chiller barrel (1 to 12HP)• Fused, STAINLESS STEEL system process pump• Pump isolation ball valve• Dual system process pump with manual or auto changeover• Water flow meter• Phase monitor• 4 year extended compressor warranty• Hot gas by-pass capacity control with solenoid valve and time delay relay• Factory-assisted start-up
PWC 400D Model w/ Custom Evaporator
and Condensers (shown)
PWC 500D Model w/ Custom Evaporator and Frame
Standard Features and Options
®

PWC SEMI-HERMETIC - SINGLE CIRCIUTR404A Packaged, Water-Cooled Chillers
MODELBTUH @ 105° COND. 20°F
LWT
LENGTH IN.
WIDTH IN.
HEIGHT IN.
FLUID CONN.
COMPRESSOR RLA EA
LRA EA MCA M.O.P. WT.
LBS.
QTY HP MODEL
100S3-T3-S
79200
65
34
42
1 1/2" FPT
1
10 3DB3R12M
43.6 215 60 90
890100S3-T4-S 20.0 106 30 45
100S3-T5-S 16.5 84 25 35
120S3-T3-S98400 12.5 3DF3R15M
48.1 275 70 100890
120S3-T4-S 23.6 138 30 50
150S3-T3-S
109200 2" FPT 15 3DS3R17M
59.6 275 80 125
1010150S3-T4-S 29.0 138 40 60
150S3-T5-S 23.6 110 30 50
200S3-T3-S
117600
60
2 1/2" MPT
17 4C2397SH
70.3 352 90 150
1120200S3-T4-S 32.0 176 40 70
200S3-T5-S 25.4 140 40 50
220S3-T3-S
135600 17 4DB3R20M
72.1 374 100 150
1120220S3-T4-S 36.1 180 50 80
220S3-T5-S 31.4 135 40 70
250S3-T3-S
146400
85
20 4DH3R22M
74.4 428 100 150
1170250S3-T4-S 40.0 206 60 90
250S3-T5-S 33.3 172 50 70
301S3-T3-S
195600 25 6DB3R32M
134.3 565 175 300
1300301S3-T4-S 67.1 283 90 150
301S3-T5-S 40.6 230 60 90
351S3-T3-S
230400
3" MPT
35 6B4709PH
136.0 550 175 300
1600351S3-T4-S 58.0 275 80 125
351S3-T5-S 49.3 220 70 110
400S3-T3-S
266400 40 6B5406PH
166.0 700 225 350
1700400S3-T4-S 78.0 350 100 175
400S3-T5-S 60.1 280 80 125
500S3-T3-S
316800 50 6B6462PH
201.0 950 300 450
1950500S3-T4-S 91.0 425 125 200
500S3-T5-S 72.8 340 100 150
Dimensional and Electrical Specifications R404A
14

Drake Refrigeration, Inc.2900 Samuel Drive • Bensalem, PA 19020(888) 289-7299Phone (215) 638-5515Fax (215) 638-5518www.drakechillers.com
PWC SEMI-HERMETIC - DUAL CIRCUITR404A Packaged, Water-Cooled Chillers
15
MODEL"BTUH @ 105°
COND. 20°F LWT"
"LENGTH IN."
"WIDTH IN."
"HEIGHT IN."
"FLUID CONN." COMPRESSOR "RLA
EA""LRA EA" MCA M.O.P. "WT.
LBS."
QTY HP MODEL
150D3-T3-S
132000
85
34
60
2 1/2"
FPT
2
8 3DA3R10M
41.0 215 100 125
1260150D3-T4-S 20.0 106 50 60
150D3-T5-S 16.4 84 40 50
200D3-T3-S
159600 10 3DB3R12M
43.6 215 100 125
1380200D3-T4-S 20.0 106 50 60
200D3-T5-S 16.5 84 40 50
240D3-T3-S195600 12.5 3DF3R15M
48.1 275 110 1501480
240D3-T4-S 23.6 138 60 70
300D3-T3-S
218400 15 3DS3R17M
59.6 275 150 175
1820300D3-T4-S 29.0 138 70 90
300D3-T5-S 23.6 110 60 70
400D3-T3-S
235200
3" MPT
17 4C2397SH
70.3 352 175 225
1990400D3-T4-S 32.0 176 80 100
400D3-T5-S 25.4 140 60 80
440D3-T3-S
272400 17 4DB3R20M
72.1 374 175 225
2040440D3-T4-S 36.1 180 90 110
440D3-T5-S 31.4 135 80 100
500D3-T3-S
291600 20 4DH3R22M
74.4 428 175 225
2190500D3-T4-S 40.0 206 100 125
500D3-T5-S 33.3 172 80 100
601D3-T3-S
392400
110
78 4" VIC
25 6DB3R32M
134.3 565 350 400
2290601D3-T4-S 67.1 283 175 200
601D3-T5-S 40.6 230 100 125
701D3-T3-S
459600 35 6B4709PH
136.0 550 350 400
2600701D3-T4-S 58.0 275 150 175
701D3-T5-S 49.3 220 125 150
800D3-T3-S
532800 40 6B5406PH
166.0 700 400 500
3000800D3-T4-S 78.0 350 200 250
800D3-T5-S 60.1 280 150 175
1000D3-T3-S
633600 120 41 50 6B6462PH
201.0 950 500 600
35001000D3-T4-S 91.0 425 225 250
1000D3-T5-S 72.8 340 175 225
Dimensional and Electrical SpecificationsR404A
®

PWC SEMI-HERMETIC - SINGLE CIRCIUTR407C Packaged, Water-Cooled Chillers
16
MODEL BTUH @ 105° COND. 45°F
LENGTH IN.
WIDTH IN.
HEIGHT IN.
FLUID CONN.
COMPRESSOR RLA EA
LRA EA MCA M.O.P. WT.
LBS.QTY HP MODEL
100S3-T3-S
135600
65
34
42
1 1/2" FPT
1
10 3DB3R12M
43.6 215 60 80
890100S3-T4-S 20.0 106 30 45
100S3-T5-S 16.5 84 25 35
120S3-T3-S159600 12.5 3DF3R15M
48.1 275 70 100890
120S3-T4-S 23.6 138 30 50
150S3-T3-S
180000 2" FPT 15 3DS3R17M
59.6 275 80 125
1010150S3-T4-S 29.0 138 40 60
150S3-T5-S 23.6 110 30 50
200S3-T3-S
181200
60
2 1/2" MPT
17 4C2397SH
70.3 352 90 150
1120200S3-T4-S 32.0 176 40 70
200S3-T5-S 25.4 140 40 50
220S3-T3-S
230400 17 4DB3R20M
85.7 374 110 175
1120220S3-T4-S 40.7 180 60 90
220S3-T5-S 33.6 135 45 70
250S3-T3-S
265200
85
20 4DH3R22M
107.1 428 150 225
1170250S3-T4-S 51.4 206 70 110
250S3-T5-S 38.8 172 50 80
301S3-T3-S
327600 25 6DB3R32M
122.9 565 175 250
1300301S3-T4-S 62.1 260 80 125
301S3-T5-S 50.0 230 70 110
351S3-T3-S
349200
3" MPT
35 6B4709PH
136.0 550 175 300
1600351S3-T4-S 58.0 275 80 125
351S3-T5-S 49.3 220 70 110
400S3-T3-S
398400 40 6B5406PH
166.0 700 225 350
1700400S3-T4-S 78.0 350 100 175
400S3-T5-S 60.1 280 80 125
500S3-T3-S
476400 50 6B6462PH
201.0 950 300 400
1950500S3-T4-S 91.0 425 125 200
500S3-T5-S 72.8 340 100 150
600S3-T3-S
640800 4" VIC 60 8DS3R67M
224.3 1070 300 500
2160600S3-T4-S 96.4 510 125 200
600S3-T5-S 80.0 405 110 200
Dimensional and Electrical Specifications R407C

Drake Refrigeration, Inc.2900 Samuel Drive • Bensalem, PA 19020(888) 289-7299Phone (215) 638-5515Fax (215) 638-5518www.drakechillers.com
17
PWC SEMI-HERMETIC - DUAL CIRCUITR407C Packaged, Water-Cooled Chillers
Dimensional and Electrical SpecificationsR407C
MODEL "BTUH @ 105° COND. 45°F
"LENGTH IN."
"WIDTH IN."
"HEIGHT IN."
"FLUID CONN."
COMPRESSOR "RLA EA"
"LRA EA" MCA M.O.P. "WT.
LBS."QTY HP MODEL
150D3-T3-S
229200
85
34
60
2 1/2" FPT
2
8 3DA3R10M
41 215 100 125
1260150D3-T4-S 20 106 50 60
150D3-T5-S 16.4 84 40 50
200D3-T3-S
272400 10 3DB3R12M
43.6 215 100 125
1380200D3-T4-S 20.0 106 50 60
200D3-T5-S 16.5 84 40 50
240D3-T3-S319200 12.5 3DF3R15M
48.1 275 110 1501480
240D3-T4-S 23.6 138 60 70
300D3-T3-S
361200 15 3DS3R17M
59.6 275 150 175
1820300D3-T4-S 29.0 138 70 90
300D3-T5-S 23.6 110 60 70
400D3-T3-S
362400
3" MPT
17 4C2397SH
70.3 352 175 225
1990400D3-T4-S 32.0 176 80 100
400D3-T5-S 25.4 140 60 80
440D3-T3-S
459600 17 4DB3R20M
85.7 374 200 250
2040440D3-T4-S 40.7 180 100 125
440D3-T5-S 33.6 135 80 100
500D3-T3-S
530400 20 4DH3R22M
107.1 428 250 300
2190500D3-T4-S 51.4 206 125 150
500D3-T5-S 38.8 172 90 125
601D3-T3-S
654000
110
78
4" VIC
25 6DB3R32M
122.9 565 300 400
2290601D3-T4-S 62.1 260 150 200
601D3-T5-S 50.0 230 125 150
701D3-T3-S
698400 35 6B4709PH
136.0 550 350 400
2600701D3-T4-S 58.0 275 150 175
701D3-T5-S 49.3 220 125 150
800D3-T3-S
796800 40 6B5406PH
166.0 700 400 500
3000800D3-T4-S 78.0 350 200 250
800D3-T5-S 60.1 280 150 175
1000D3-T3-S
952800
120 41
50 6B6462PH
201.0 950 500 600
35001000D3-T4-S 91.0 425 225 250
1000D3-T5-S 72.8 340 175 225
1200D3-T3-S
1281600 6" VIC 60 8DS3R67M
224.3 1070 600 700
40001200D3-T4-S 96.4 510 225 300
1200D3-T5-S 80.0 405 200 250
®
Custom PWC 1200D Model
w/ Bitzer Compressors (shown)

Schematical Drawings PWC SEMI-HERMETICWater-Cooled Chillers
PWC 200S, 220S Water-Cooled Semi-Hermetic
PWC 75S, 100S, 120S,150S Water-Cooled Semi-Hermetic
PWC 250S, 301S, 351S,400S, 500S, 600S Water-Cooled Semi-Hermetic18

Drake Refrigeration, Inc.2900 Samuel Drive • Bensalem, PA 19020(888) 289-7299Phone (215) 638-5515Fax (215) 638-5518www.drakechillers.com
Schematical DrawingsPWC SEMI-HERMETICWater-Cooled Chillers
PWC 601D Water-Cooled Semi-Hermetic
PWC 150D 200D, 240D,300D, 440D, 500D Water-Cooled Semi-Hermetic
®
19

Schematical Drawings PWC SEMI-HERMETICWater-Cooled Chillers
PWC 1000D Water-Cooled Semi-Hermetic
PWC 12000D Water-Cooled Semi-Hermetic
20

Drake Refrigeration, Inc.2900 Samuel Drive • Bensalem, PA 19020(888) 289-7299Phone (215) 638-5515Fax (215) 638-5518www.drakechillers.com
MODEL LENGTHIN.
WIDTHIN.
HEIGHTIN.
WATERCONN. TANK CAPACITY RECIRCULATION
PUMPFLA
230/3ØFLA
460/3ØWT.LBS.
TS200S
120 56 59
1 1/2” FPT 200 GALLONS2HP 6.4 3.2
500
TS300S 2” FPT 300 GALLONS 525
TS500S 3” FPT 500 GALLONS3HP 9.4 4.5
540
TS600S 4” FPT 600 GALLONS 560
Standard Features
• Open, vented polyethylene storage tank• 1/2” tank and fluid piping insulation• Copper fluid piping• Tank vent and drain connections• Fused evaporator fluid re-circulating STAINLESS STEEL pump• Fluid pump discharge ball valve and cleanable “Y” strainer• Control box with pump terminal block• Painted, galvanized steel sheet metal cabinet• 24 volt L.E.D. process fluid thermometers
Available Options
• STAINLESS STEEL (welded) tank• Water flow meter• Fused, STAINLESS STEEL process pump• Tank fluid sight glass• Tank liquid level indicator with dry contacts• Special piping for de-ionized and reverse osmosis water systems• STAINLESS STEEL sheet metal cabinet• 1” tank and piping insulation• Seal-tight electrical connections • Low flow by-pass loop
TS300 - 600S
Dimensional Specifications, Features and OptionsTANK SECTION
®
21

22
GLYCOL FACTOR TABLES
PROPYLENE GLYCOL CAPACITY CORRECTION FACTOR TABLE
PERCENT PROPYLENE GLYCOL BY WEIGHT 15% 20% 25% 30% 35% 40% 50%
FREEZING POINT IN °F 24 18 15 9 5 -5 -30CAPACITY FACTOR MULTIPLIER* 0.992 0.986 0.972 0.960 0.950 0.928 0.878
PRESSURE DROP MULTIPLIER 1.04 1.08 1.13 1.21 1.26 1.47 2.79
ETHYLENE GLYCOL CAPACITY CORRECTION FACTOR TABLE
PERCENT ETHYLENE GLYCOL BY WEIGHT 10% 15% 20% 25% 30% 35% 40%
FREEZING POINT IN °F 25 21 17 11 5 0 -10CAPACITY FACTOR MULTIPLIER* 0.98 0.96 0.95 0.93 0.92 0.91 0.89
PRESSURE DROP MULTIPLIER 1.08 1.11 1.16 1.21 1.27 1.32 1.38
* At standard ARI 590 conditions: 54°F entering fluid temperature, 44°F leaving fluid temperature, 95°F ambient temperature, 0.0005 fouling.
Please note: Due to manufacturer’s policy of continuous product improvement, the manufacturer reserves the right to make changes without notice. Drawings in this booklet are representations of the equipment shown. Contact the factory for specific unit drawings.
Along with the complete line of standard products that Drake Refrigeration Inc. offers, we also have the ability to custom build units to each customers particular needs. Please contact the factory or your Drake representative for your special application

Drake Refrigeration, Inc.2900 Samuel Drive • Bensalem, PA 19020(888) 289-7299Phone (215) 638-5515Fax (215) 638-5518www.drakechillers.com
23
®
Ask about our Custom Built
Water-Cooled Chillers
Notes / Custom Built Chillers
Custom PWCL1600 M6-T4-S (Low Temperature) Model w/ Dual Brazed Plate Heat Exchangers,
(Built for a name brand candy manufacturer)

PWC-Semi Rev 8/12/13
EPA COMPLIANT
ww
w.D
rake
Chi
ller
s.co
m
Drake Refrigeration, Inc.2900 Samuel Drive • Bensalem, PA 19020
(888) 289-7299Phone (215) 638-5515
Fax (215) 638-5518
®