VRFESEL001US 014B07 TRACE™ 700 Building Energy Modeling Guide for LG Multi V™

description

vrf

Transcript of VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

Page 1: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07 

TRACE™ 700 Building Energy Modeling Guide for 

LG Multi V™ 

 

   

 

   

Page 2: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 2 of 24  

 

TableofContents 

This Guide ............................................................................................................................................ 3 

1. Disclaimer .................................................................................................................................... 3 

Import Library ...................................................................................................................................... 4 

2. Testing the Library File ................................................................................................................. 8 

3. Import the Multi V Library File ..................................................................................................... 9 

Multi V III (Air Source) System ........................................................................................................... 11 

4. Create Systems ........................................................................................................................... 11 

5. Fan selection .............................................................................................................................. 12 

6. Create Plants .............................................................................................................................. 13 

Multi V Water II (Water Source) System ............................................................................................. 16 

7. Create Systems ........................................................................................................................... 16 

8. Fan selection .............................................................................................................................. 17 

9. Create Plants .............................................................................................................................. 17 

Energy Recovery Ventilator/ Dedicated Outdoor Air System .............................................................. 20 

10. Application considerations ........................................................................................................ 20 

11. Sample scenario ......................................................................................................................... 21 

Appendix: Multi V performance Data Library ..................................................................................... 23 

References ......................................................................................................................................... 24 

 

   

Page 3: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 3 of 24  

This Guide 

TheTraneTrace700BuildingEnergyModelingGuideforLGMultiVcontainsstep‐by‐stepinstructionstohelpusersmodelLGMultiVsystemoptions.Thedefinitionsofthecode‐wordsarecitedfromModelingGuideTRACE®700BuildingEnergyandEconomicAnalysisversion6.2.

Disclaimer 

TheBuildingEnergyModelingGuideandTraneTrace700libraryfilesareforcomparisonsandshouldbeusedasaguidelineonly.Buildingload/energyhasbeenapproximatedformodelingpurposesorinputvalueofequipment(capacity,powerinput,etc.),andactualresultsmayvarydependingonthesituation.TheconclusionsofthisModelingGuideandTraneTrace700libraryfiledonotguaranteeactualenergycostsorsavings.

ThisModelingGuideandTraneTrace700libraryfileareintendedasadesign‐andanalysisguidetohelpdesignersoptimizethedesignoftheLGMultiVVRFsystembasedonenergyutilization.Modelingaccuracyishighlydependentonuser‐supplieddata.Itistheuser’sresponsibilitytounderstandhowthedataenteredaffectsprogramoutput,andtounderstandthatanypredefinedlibrariesaretobeusedonlyasguidelinesandTraneTrace700libraryfileforenteringthatdata.ThecalculationresultsandreportsbythisguideandTraneTrace700libraryfilearemeanttoaidthesystemdesignerandarenotasubstitutefordesignservices,judgment,orexperience.

   

Page 4: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 4 of 24  

USING Trane Trace 700 TO DESIGN VRF SYSTEMS  

ThissectionbrieflydescribeshowtouseTRANETRACE700todesignVRFsystems.AllVRFdesignworkrequiresthesamegeneralfivestepprocedure:

1. DefinetheProblem.

Firstdefinethescopeandobjectivesofthedesignanalysis.

2. GatherData.

Beforedesigncalculationscanbeperformed,informationaboutthebuilding,itsenvironmentanditsHVACequipmentmustbegathered.Thisstepinvolvesextractingdatafrombuildingplans,evaluatingbuildingusageandstudyingHVACsystemneeds.Specifictypesofinformationneededinclude:

Weatherdataforthebuildingsite.

Constructionmaterialdataforenvelopesofexteriorandinteriorincludingwalls,roofs,windows,doors,andfloors.

Buildingsizeandlayoutdataincludingwall,roof,window,doorandfloorareas,exposureorientationsandexternalshadingfeatures.

Internalloadcharacteristicsdeterminedbylevelsandschedulesforoccupancy,lightingsystems,equipment,andventilationwithinthebuilding.

DataconcerningHVACequipment,controlsandcomponentstobeused.

Definetheutilityratesfortheproject

3. EnterDataIntoTRANETRACE700.

Next,useTRANETRACE700toenterbuildingandequipmentdata.WhenusingTRANETRACE700,yourbaseofoperationisthemainprogramwindow.Thendefinethefollowingtypesofdatawhichareneededforsystemdesignwork:

a. SelectWeatherData.

OpentheWeatherdialogboxusingeitherofthesemethods:

‐ IntheProjectNavigatorview,clickWeathericoninthetoolbarorclicktheSelectweatherinformationbuttoninthefloatingProjectNavigatortoolbar.

‐ Inanyview,usethemenubartoselectActions>SelectWeatherInfo.

Clickontheregionofthemapwherethebuildingislocatedtodisplayalistofavailableweatherlocationsforthatregion.

Page 5: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 5 of 24  

Scrollthroughthelisttofindthedesiredlocationandselectit.ThelocationyoupickedappearsinthelowerleftcorneroftheWeatherdialogbox.

ClickOKtoreturntothemainscreen.

b. CreateSpaces/Rooms.

TRACEperformscoolingandheatingloadcalculationsforeachindividualroom,soa"room"isthesmallestspaceforwhichyoucancalculateloads.Aroomcanbeasingleofficesurroundedbywallsorcanbetheperimeterportionofalargeopen‐planofficearea.Inotherareasoftheprogram,youhavetheoptionofgroupingroomsintozonesand/orsystemsforhigherleveldesigncalculations(i.e.designairflows,coilcapacities,designtemperatures,etc.).

Whencreatingrooms,youessentially"assign"toitallofthecomponentsthatcontributetooraffectitscoolingandheatingloads.Theseloadcomponentsinclude,butarenotlimitedto:

‐ Sizeandmassofroom

‐ Roomdesignthermostatsettings

‐ Size,construction,anddirectionofexternalwallsandroofs

‐ Size,properties,anddirectionofexternalwindowsandskylights

‐ Internalloads,suchaspeople,lights,andmiscellaneousequipment

‐ Infiltration

‐ Ventilationrequirements

‐ Partitionwallsandexposedorslab‐on‐gradefloors

c. EnterSystemData.

Alongwithenteringroominformation,youalsoneedtodefinetheHVACairdistribution,or"airside,"systemsservingthebuildingsothattheprogramknowshowtosizethefansandcoils.ThisisdonebyselectingaSystemTypeandenteringanyappropriatesysteminformation.Aftertheprogramperformscoolingandheatingloadcalculationsforindividualrooms,itcalculatesroomairflows,coilloads,fansizes,andothersystemdesigninformation.DefiningtheSystemTypetellstheprogramhowtocalculatethisdesigninformation("block"vs."sum‐of‐peaks")andwhatcomponents(coils,fans,etc.)makeupthesystem.

4. UseTRANETRACE700toGenerateDesignReports.

Page 6: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 6 of 24  

When you have finished all the steps in creating a project file, you are ready for the program to do its job and perform the Design, System, Energy, and Economics simulation phases.

To start the calculation process:

a. In the Project Navigator view, click the Calculate Output icon on Project Navigator or the toolbar or select Calculate from the TRACE Actions menu.

b. Click the Calc Now button. This generates the reports and provides you with the View Results dialog box from which you can select reports to print.

5. SelectEquipment.

Finally, use data from the reports you generated to select the appropriate cooling and heating equipment from LG VRF product catalogs. System and plant design reports provide information necessary to select all the components of your VRF system including outdoor units, indoor units, and control equipments.

LG can provide a wide variety of electronic catalogs to make selecting equipment quick and easy. Please contact your local LG sales office or LG distributor for details.

Page 7: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 7 of 24  

Import Library  

TheTRACE700programincludesaseparateLibrary/TemplateEditorapplicationthatletsusersviewthedetailedinformationfoundinthestandardtemplatesandlibraries.UsetheTRACE700“LibraryTemplateEditor”toimportthelibraryfileaccompanyingthisdocument.

ToImportthelibrary:

1. ClickEquipmentontheLibrariesmenu.

2. Select“ExportCustomLibrary”fromthe“File”Menu.

3. Renamethelibrary.expfiletooriginal_libray.exp.Thisallowsuserstheabilitytoreturntothedefaultfileifneeded.

Page 8: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 8 of 24  

4. Closethedialogbox.

Testing the Library File 

Totestthelibraryfile:

1. ClickEquipmentontheLibrariesmenu.

2. ClickCoolingontheEquipmentmenu.TheLibrary/TemplateEditorsprogramwilldisplaytheCoolingEquipmentwindow.

3. ViewcurrentEquipmentlistsintheTRACE700DataDirectory.

4. Closethedialogbox.

5. ClosetheLibrary/TemplateEditors.

 

Page 9: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 9 of 24  

Import the Multi V Library File 

ToimporttheMultiVlibraryfileintoTRACE700:

1. ObtaintheMultiVlibraryfilesfromyourLGSalesRepresentative.

2. DoubleclicktheTrace700icononyourdesktoptolaunchTrace700.OrFromtheStartmenu,selectProgramFiles>C.D.S. >Applications>TRACE700>TRACE700

3. ClicktheTRACE700“LibraryTemplateEditor.TheLibrary/TemplateEditorsappears:

4. Selectthepathwherethelibraryfilewascopiedtoandselect“ImportCustomLibrary”fromthe“File”Menu.

Page 10: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 10 of 24  

Note: During library file import, if shown an option to overwrite an existing duplicate library data for LG Multi V products from the import file, set to "yes" this option will allow to overwrite an existing database. 

5. Closethedialogbox.

6. ClosetheLibrary/TemplateEditors.

7. InTRACE700,clickFile>Exittoclosetheprogram.

   

Page 11: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 11 of 24  

Multi V (Air Source) System 

Create Systems 

ThefollowingproceduredemonstrateshowtomodeltheMultiVsystem,coolingandheatingequipment,aswellasassigningthecoilloads.

Tocreateasystem:

1. TheMultiVsystemtypeinTRACEislistedunderthe“VariableVolume”systemcategoryunderthe“CreateSystems”section.

2. PickVariableRefrigerantVolumeasthesystemtype.

3. ClickApplytosaveyourentries.

 

   

Page 12: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 12 of 24  

Fan selection 

  Toselectafan:

1. OntheFanstabofthe“CreateSystems”dialogbox,selectVRVIndoorFan.

2. Enterthetotalstaticpressureandfanenergyrateused.ThetotalstaticpressureandfanenergyrateisdifferentforeachtypeofMultiVindoorunit.NolibraryfileshavebeenprovidedforthezonelevelindoorVRFequipment.

3. Selectanindoorunit(IDU)foreachzone/spaceusingLGMultiVProductLineup.

4. Settotalstaticpressureoftheindoorunitfanatdesignflowrate.RefertotheLG’sengineeringmanualforMultiVIndoorunitsandbuildingdesigndata.Pressurelossesshouldincludefilters,coils,anddistributionsystem.Designfull‐loadpowerofthesupplyfanperunitofsupplyairflowrateatsealevel.

5. TRACE700currentlydoesnotutilizelibraryfilesforzonelevelairsideequipment.Instead,asystemtypeisdefinedinTRACE,andthatsystemisassignedtotheappropriateTRACE“Plant”(eachindividualoutdoorVRFcompressorunit).Atthesystemlevelonlyasinglefandefinitionexistsfortheentiresystem,soanaverageassumedfanpowerdensitymustbeusedforthesystemwhichisanaveragerepresentationoftheassociatedzonesattachedtothatsystem.

Page 13: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 13 of 24  

Create Plants  

Next,describethecoolingandheatingplantsrepresentedbytheVRFsystemandbackupelectricresistanceheat.VRFplantsareconsideredAir‐CooledUnitaryplants.

Tocreateplants:

1. DragtheappropriateiconsfromtheEquipmentCategorysectiontodefineeachplant.

2. RenamethecoolingplantasVRFandtheheatingplantasBackupelectricresistancebyselectingtheplantandclickingtheEditbutton.

3. SelectthecoolingplantandclickontheCoolingEquipmenttab.

4. ChoosetheVRFplantthatbestmatchesthetargetperformanceandoperation.Therearetwocategoriesofplantavailable:VRFHeatPumpandVRFHeatRecovery.

Page 14: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 14 of 24  

5. SpecifyBackupelectricresistanceasthebackupheatsource.

6. Ifnecessary,ontheHeatingEquipmenttab,refineabackupheatingplant.

7. Finally,assigneachcoilloadtotheappropriateplant.

Page 15: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 15 of 24  

Note1: The VRF Heat Recovery option is able to recover heat from one VRF indoor unit and share it with other indoor units that are connected to the same refrigerant circuit. TRACE assumes that heat can be recovered between all zones that are assigned to the system. To accurately model VRF heat recovery, the design capacity of all the indoor units (zones) assigned to the system should be no larger than the available capacity of the VRF Heat Recovery outdoor unit. This might require the creation of several systems and several cooling plants. The TRACE 700 for air source heat pump system requires the option for the heat reject fan power however, Multi V Air performance library data are already included fan power information in the performance curves.    

                                                             

Page 16: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 16 of 24  

Multi V Water (Water Source) System  

AWLHPloopisprimarilyintendedtoservewater‐loopheat‐pumpsystems.IndividualWLHPunitsoperateaccordingtotheirzonethermostats,andrejectheattoortakeheatfromthisloop.Dependingontherelativenumberofunitsoperatingintheheatingorcoolingmode,theloopwillbethermallyunbalancedandthelooptemperaturewilleitherriseorfall.Oneormoreboilersandoneormorecoolingtowersoperatetokeeptheloopwithinspecifiedlimits.InadditiontoWLHPunits,anycoolingunitwithawatercooledcondensermaybeassignedtothisloop.

 

Create Systems 

  

TomodelanappliedWSHPsystem,beginbydefiningairdistribution:

1. PickWaterSourceHeatPumpasthesystemtype.2. ClickApplytosaveentries.

Page 17: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 17 of 24  

Fan selection 

Toselectafan:

1. OntheFanstabofthe“CreateSystems”dialogbox,selectHydronicinheatpumpfanandenterthetotalstaticpressureandfanenergyrateused.ThetotalstaticpressureandfanenergyratewillbedifferentforeachtypeofMultiVindoorunit.

2. Setthetotalstaticpressureoftheindoorunitfanatdesignflowrate.RefertotheLG’sengineeringmanualforMultiVIndoorunitsandbuildingdesigndata.Pressurelossesshouldincludefilters,coils,anddistributionsystem.

Create Plants  

Tocreateaplant:

1. Next,describethecoolingandheatingplantsrepresentedbytheWSHPsystemandbackupboiler.

2. DragtheappropriateiconsfromtheEquipmentCategorysectiontodefineeachplant.

3. RenamethecoolingplantasWSHPandtheheatingplantasBackupboiler.

Page 18: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 18 of 24  

4. SelectthecoolingplantandclicktheCoolingEquipmenttab.5. Choosethewater‐sourceheatpumpthatbestmatchesthetarget

performance.6. Enterthefull‐loadconsumptionofthepumpthatservesthecommonwater

loop—theprimarychilled‐waterpump,inthiscase.

7. ClickControlstoassigntheexcessheatfromthecommonwaterlooptoloadsservedbytheheatingplantidentifiedastheenergysource.

Note: Do not remove thermal storage. The water loop is modeled as a special thermal storage type in TRACE 700. Removing the thermal storage eliminates the water loop from the simulation. 

8. Besuretoapplyyourchanges.OntheHeatingEquipmenttab,picktheboiler

thatmostcloselymatchestheanticipatedperformance.

Page 19: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 19 of 24  

9. Enterthefull‐loadconsumptionofthepumpthatcirculateshotwaterfromtheboiler.

Note: The minimum operating condenser temperature of the selected heat pump determines when the boiler turns on to maintain the condenser water temperature. To view or alter this entry, use the Library/Template Editors program. 

10. Finally,assigneachcoilloadtotheappropriateplant.

   

Page 20: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 20 of 24  

Dedicated Outdoor Air System /Energy Recovery Ventilator  

Anenthalpywheelisarevolvingcylinderfilledwithadesiccanttreatedmediumthatissuitedfortransferringsensibleandlatentheat.Heattransferoccurswhenadjacentairstreams(usuallysupplyandexhaust)passthroughthewheelinacounterflowarrangement.Theexchangemediuminsidethewheelcollectssensibleheatfromthewarmerofthetwoairstreamsandreleasesitinthecoolerairstream.Latentheattransferoccursasthemediumcollectsmoisturefromthemorehumidairstreamandreleasesit,throughevaporation,inthedrierairstream.

Likeotherenergy‐recoverydevices,enthalpywheelscanyieldsignificantenergysavingsinsystemsthatexhaustlargeamountsofair.Theirrecentgrowthinpopularitycanbeattributed,atleastinpart,totheincreasedventilationrequirementsmandatedbyASHRAEStandard62toprovideacceptableindoorairquality.

Application considerations 

_Theairstreamstargetedforenergytransfer(usuallyexhaustairandventilationair)mustbesituatedneareachother.

Figure4‐6Enthalpywheel

Page 21: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 21 of 24  

_Enthalpywheelscanrecoverbothlatentheatandsensibleheatwithaneffectivenessthattypicallyrangesfrom65percentto80percent.Addingawheelusuallyincreasesthesystemstaticpressureby0.4in.wgto0.7in.wg.

_Cross‐contaminationbetweenairstreamsispossible.Tominimizeaircarryoverincriticalapplications,addaneffectivepurgearrangement.Placementofthefaninrelationtothewheelshouldpromoteleakagefromtheoutdoor(ventilation)airstreamtotheexhaustairstreamratherthanthereverse.

_Therelativelycompactsizeofanenthalpywheelcanpermitfactoryinstallationinairhandlers,rooftopairconditioners,andsometerminaldevicessuchasunitventilators.

_Climatesthateconomicallyfavorheatpumpsaregoodcandidatesforsuccessfulenthalpy‐wheelapplications.Whenappliedincoldclimates,itmaybenecessarytosupplementtheheatingcapacityofthewheelbyaddingpreheat.

Sample scenario 

Theair‐distributionsystemforabuildingincludesanenthalpywheelwithaneffectivenessof70percent.Thewheelpreconditionstheoutdoorairenteringthebuildingbyexchangingbothsensibleandlatentheatwiththemainexhaust‐airstream.

Whenoperatingintheheatingmode,thewheelwarmsandhumidifiestheoutdoorair;duringthecoolingmode,itcoolsanddehumidifies.

Page4‐22illustrateshowtomodeltheenthalpywheelinthisexample.

Afterchoosinganairsidesystem:

1Pickthedesiredtypeofexhaust‐airheatrecoveryfromtheoptionsavailable.

Forthisexample,selectenthalpywheel.Bydefault,itsprocessairstreamislocatedontheventilationdeck.

Page 22: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 22 of 24  

2Describethewheel’seffectiveness—thatis,howefficientlyitrecoversenergy.

3Identifythescavengerairstreambydescribingthelocationoftheexhaustsidedeck.

4Choosetheschedulethatdescribeswhentheenthalpywheelispermittedtooperate.

Page 23: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 23 of 24  

Appendix: Multi V performance Data Library  

Pleasecontacttohttp://www.lg‐vrf.comorLGMultiVSalesRepresentatives.

Page 24: VRF-ES-EL-001-US 014B07 LGEngineeringStudy Trace700 BuildingEnergyModelingGuide 20140207133650

VRF‐ES‐EL‐001‐US 014B07    Page 24 of 24  

References 1. Modeling Guide Trane TRACE®700 Building Energy and Economic Analysis