VLT ® 8000 AQUA General technical data Line supply (L1, L2, L3): Supply voltage 200-240 V units ...................................................................... 3 x 200/208/220/230/240 V ±10% Supply voltage 380-480 V units ............................................................... 3 x 380/400/415/440/460/480 V ±10% Supply voltage 550-600 V units .................................................................................... 3 x 550/575/600 V ±10% Supply frequency ......................................................................................................................... 50/60 Hz +/- 1% Max. imbalance of supply voltage: ......................................................................................................................... VLT 8006 - 8011 AQUA / 380 - 480 V and VLT 8002 - 8011 AQUA / 550 - 600 V ±2.0% of rated supply voltage VLT 8016 - 8072 AQUA / 550 - 600 V, VLT 8016 - 8062 AQUA / 380 - 480 V and VLT 8006 - 8032 AQUA / 200 - 240 V .................................................................. ±1.5% of rated supply voltage VLT 8100 - 8300 AQUA / 550 - 600 V, VLT 8100 - 8600 AQUA / 380 - 480 V and VLT 8042 - 8062 AQUA / 200 - 240 V .................................................................. ±3.0% of rated supply voltage Displacement factor / cos. ϕ ..................................................................................................... near unity (> 0.98) True Power Factor (kW/kVA) ........................................................................................ nominal 0.90 at rated load Input Mains (L1, L2, L3) Allowable On-OFF Switching Sequnces ........................................ approx. 1 time/2 min. Max. short-circuit current ........................................................................................................................... 100 kA VLT output data (U, V, W): Output voltage ............................................................................................................... 0-100% of supply voltage Output frequency .................................................................................................................................. 0 - 120 Hz Rated motor voltage, 200-240 V units ............................................................................ 200/208/220/230/240 V Rated motor voltage, 380-480 V units ............................................................................ 380/400/415/440/480 V Rated motor voltage, 550-600 V units .................................................................................................. 550/575 V Rated motor frequency ............................................................................................................................ 50/60 Hz Switching on output ................................................................................................................................ Unlimited Ramp times ....................................................................................................................................... 1- 3600 sec. Torque characteristics: Starting torque ............................................................................................................................. 110% for 1 min. Starting torque (parameter 110 High break-away torque) .................................... Max. torque: 130% for 0.5 sec. Acceleration torque ...................................................................................................................................... 100% Overload torque ............................................................................................................................................ 110% Control card, digital inputs: Number of programmable digital inputs ............................................................................................................... 8 Terminal nos. .......................................................................................................... 16, 17, 18, 19, 27, 29, 32, 33 Voltage level ......................................................................................................... 0-24 V DC (PNP positive logics) Voltage level, logical "0" .......................................................................................................................... < 5 V DC Voltage level, logical "1" ........................................................................................................................ > 10 V DC Maximum voltage on input ....................................................................................................................... 28 V DC Input resistance, R i ........................................................................................................................... approx. 2 k Scanning time per input ............................................................................................................................ 3 msec. Reliable galvanic isolation: All digital inputs are galvanically isolated from the supply voltage (PELV). In addition, the digital inputs can be isolated from the other terminals on the control card by connecting an external 24 V DC supply and opening switch 4. See switches 1-4. VLT 4006-4300 VT, 550-600 V, do not meet PELV requirements. MG.80.A2.02 - VLT is a registered Danfoss trademark 16

Transcript of VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 -...

Page 1: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

� General technical data

Line supply (L1, L2, L3):

Supply voltage 200-240 V units ...................................................................... 3 x 200/208/220/230/240 V ±10%Supply voltage 380-480 V units ............................................................... 3 x 380/400/415/440/460/480 V ±10%Supply voltage 550-600 V units .................................................................................... 3 x 550/575/600 V ±10%Supply frequency ......................................................................................................................... 50/60 Hz +/- 1%Max. imbalance of supply voltage: .........................................................................................................................VLT 8006 - 8011 AQUA / 380 - 480 V and VLT 8002 - 8011 AQUA / 550 - 600 V ±2.0% of rated supply voltageVLT 8016 - 8072 AQUA / 550 - 600 V, VLT 8016 - 8062 AQUA / 380 - 480 V andVLT 8006 - 8032 AQUA / 200 - 240 V .................................................................. ±1.5% of rated supply voltageVLT 8100 - 8300 AQUA / 550 - 600 V, VLT 8100 - 8600 AQUA / 380 - 480 V andVLT 8042 - 8062 AQUA / 200 - 240 V .................................................................. ±3.0% of rated supply voltageDisplacement factor / cos. ϕ ..................................................................................................... near unity (> 0.98)True Power Factor (kW/kVA) ........................................................................................ nominal 0.90 at rated loadInput Mains (L1, L2, L3) Allowable On-OFF Switching Sequnces ........................................ approx. 1 time/2 min.Max. short-circuit current ........................................................................................................................... 100 kA

VLT output data (U, V, W):

Output voltage ............................................................................................................... 0-100% of supply voltageOutput frequency .................................................................................................................................. 0 - 120 HzRated motor voltage, 200-240 V units ............................................................................ 200/208/220/230/240 VRated motor voltage, 380-480 V units ............................................................................ 380/400/415/440/480 VRated motor voltage, 550-600 V units .................................................................................................. 550/575 VRated motor frequency ............................................................................................................................ 50/60 HzSwitching on output ................................................................................................................................ UnlimitedRamp times ....................................................................................................................................... 1- 3600 sec.

Torque characteristics:

Starting torque ............................................................................................................................. 110% for 1 min.Starting torque (parameter 110 High break-away torque) .................................... Max. torque: 130% for 0.5 sec.Acceleration torque ...................................................................................................................................... 100%Overload torque ............................................................................................................................................ 110%

Control card, digital inputs:

Number of programmable digital inputs ............................................................................................................... 8Terminal nos. .......................................................................................................... 16, 17, 18, 19, 27, 29, 32, 33Voltage level ......................................................................................................... 0-24 V DC (PNP positive logics)Voltage level, logical "0" .......................................................................................................................... < 5 V DCVoltage level, logical "1" ........................................................................................................................ > 10 V DCMaximum voltage on input ....................................................................................................................... 28 V DCInput resistance, Ri ........................................................................................................................... approx. 2 kScanning time per input ............................................................................................................................ 3 msec.Reliable galvanic isolation: All digital inputs are galvanically isolated from the supply voltage (PELV). Inaddition, the digital inputs can be isolated from the other terminals on the control card by connectingan external 24 V DC supply and opening switch 4. See switches 1-4.VLT 4006-4300 VT, 550-600 V, do not meet PELV requirements.

MG.80.A2.02 - VLT is a registered Danfoss trademark16

Page 2: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

Inst

alla

tion

Control card, analogue inputs:

No. of programmable analogue voltage inputs/thermistor inputs ......................................................................... 2Terminal nos. ............................................................................................................................................... 53, 54Voltage level ........................................................................................................................ 0 - 10 V DC (scalable)Input resistance, Ri .......................................................................................................................... approx. 10No. of programmable analog current inputs ......................................................................................................... 1Terminal no. ....................................................................................................................................................... 60Current range ...................................................................................................................... 0/4 - 20 mA (scalable)Input resistance, Ri ........................................................................................................................ approx. 200Resolution .......................................................................................................................................... 10 bit + signAccuracy on input ........................................................................................................ Max. error 1% of full scaleScanning time per input ............................................................................................................................ 3 msec.Reliable galvanic isolation: All analog inputs are galvanically isolated from the supplyvoltage (PELV) and other high-voltage terminals.

Control card, pulse input :

No. of programmable pulse inputs ....................................................................................................................... 3Terminal nos. ......................................................................................................................................... 17, 29, 33Max. frequency on terminal 17 ..................................................................................................................... 5 kHzMax. frequency on terminals 29, 33 .......................................................................... 20 kHz (PNP open collector)Max. frequency on terminals 29, 33 .......................................................................................... 65 kHz (Push-pull)Voltage level ......................................................................................................... 0-24 V DC (PNP positive logics)Voltage level, logic "0" ............................................................................................................................. < 5 V DCVoltage level, logic "1" ........................................................................................................................... > 10 V DCMaximum voltage on input ....................................................................................................................... 28 V DCInput resistance, Ri ........................................................................................................................... approx. 2 kScanning time per input ............................................................................................................................ 3 msec.Resolution .......................................................................................................................................... 10 bit + signAccuracy (100-1 kHz), terminals 17, 29, 33 ............................................................. Max. error: 0.5% of full scaleAccuracy (1-5 kHz), terminal 17 ............................................................................... Max. error: 0.1% of full scaleAccuracy (1-65 kHz), terminals 29, 33 ..................................................................... Max. error: 0.1% of full scaleReliable galvanic isolation: All pulse inputs are galvanically isolated from the supply voltage (PELV).In addition, pulse inputs can be isolated from the other terminals on the control card by connectingan external 24 V DC supply and opening switch 4. See switches 1-4.VLT 4006-4300 VT, 550-600 V, do not meet PELV requirements.

Control card, digital/pulse and analog outputs:

No. of programmable digital and analog outputs ................................................................................................. 2Terminal nos. ............................................................................................................................................... 42, 45Voltage level at digital/pulse output .................................................................................................... 0 - 24 V DCMinimum load to frame (terminal 39) at digital/pulse output ........................................................................ 600Frequency ranges (digital output used as pulse output) .......................................................................... 0-32 kHzCurrent range at analog output .......................................................................................................... 0/4 - 20 mAMaximum load to frame (terminal 39) at analog output ............................................................................... 500Accuracy of analog output ....................................................................................... Max. error: 1.5% of full scaleResolution on analog output. ........................................................................................................................... 8 bitReliable galvanic isolation: All digital and analog outputs are galvanically isolated from thesupply voltage (PELV) and other high-voltage terminals.VLT 4006-4300 VT, 550-600 V, do not meet PELV requirements.

MG.80.A2.02 - VLT is a registered Danfoss trademark 17

Page 3: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

Control card, 24 V DC supply:

Terminal nos. ............................................................................................................................................... 12, 13Max. load .................................................................................................................................................. 200 mATerminal nos. ground .................................................................................................................................. 20, 39Reliable galvanic isolation: The 24 V DC supply is galvanically isolated from the supply voltage(PELV), but has the same potential as the analog outputs.

Control card, RS 485 serial communication :

Terminal nos. ............................................................................................................. 68 (TX+, RX+), 69 (TX-, RX-)Reliable galvanic isolation: Full galvanic isolation (PELV).

Relay outputs :

No. of programmable relay outputs ..................................................................................................................... 2Terminal nos., control card .................................................................................................................... 4-5 (make)Max. terminal load on 4-5, control card .............................................. 50 V AC, 1 A, 60 VA, 75 V DC, 1 A, 30 WMax. terminal load on 4-5, control card for UL/cUL applications ........................... 30 V AC, 1 A / 42.5 V DC, 1ATerminal nos., power card and relay card .......................................................................... 1-3 (break), 1-2 (make)Max. terminal load on 1-3, 1-2, power card and relay card ................................................ 240 V AC, 2 A, 60 VAMax. terminal load on 1-3, 1-2, power card .................................................................................... 50 V DC, 2 A

External 24 Volt DC supply:

Terminal nos. ............................................................................................................................................... 35, 36Voltage range ..................................................................................... 24 V DC ±15% (max. 37 V DC for 10 sec.)Max. voltage ripple ..................................................................................................................................... 2 V DCPower consumption ........................................................................... 15 W - 50 W (50 W for start-up, 20 msec.)Min. pre-fuse ............................................................................................................................................... 6 AmpReliable galvanic isolation: Full galvanic isolation if the external 24 V DC supply is also of the PELV type.

Cable lengths and cross-sections:

Max. motor cable length, shielded cable ............................................................................................ 150m/500 ftMax. motor cable length, unshielded cable ...................................................................................... 300m/1000 ftMax. motor cable length, shielded cable VLT 8011 380-480 V ......................................................... 100m/330 ftMax. motor cable length, shielded cable VLT 8011 550-600 V ........................................................... 50m/164 ftMax. DC-bus cable length, shielded cable ................................... 25m/82 ft from frequency converter to DC bar.Max. cable cross-section to motor, see next sectionMax. cross-section for control cables ....................................................................................... 1.5 mm2/16 AWGMax. cross-section for serial communication ............................................................................ 1.5 mm2/16 AWGIf UL/cUL is to be complied with, cable with temperature class 60/75 C / 140/167 F must be used(VLT 8002 - 8072 (550 - 600 V), VLT 8006 - 8072 (380 - 480 V) and VLT 8002 - 8032 (200 - 240V).If UL/cUL is to be complied with, cable with temperature class 75 C/167 F must be used (VLT 8100 -8300 (550 - 600 V), VLT 8100 - 8600 (380 - 480 V), VLT 8042 - 8062 (200 - 240 V)

Control characteristics:

Frequency range .................................................................................................................................. 0 - 120 HzResolution on output frequency ............................................................................................................. ±0.003 HzSystem response time ............................................................................................................................... 3 msec.Speed, control range (open loop) .................................................................................... 1:100 of synchro. speedSpeed, control range (closed loop) ................................................................................ 1:1000 of synchro. speedSpeed, accuracy (open loop) ............................................................................ < 1500 rpm:max. error ± 7.5 rpm> 1500 rpm: max. error of 0.5% of actual speedProcess, accuracy (closed loop) ....................................................................... < 1500 rpm: max.error ± 1.5 rpm> 1500 rpm: max. error of 0.1% of actual speedAll control characteristics are based on a 4-pole asynchronous motor

MG.80.A2.02 - VLT is a registered Danfoss trademark18

Page 4: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

Inst

alla

tion

Accuracy of Display readout (parameters 009-012 Display readout):

Motor current, 0 - 140% load ............................................................. Max. error: ±2.0% of rated output currentPower kW, Power HP, 0 - 90% load .................................................... Max. error: ±5.0% of rated output power

Externals:

Enclosure ......................................................................................... IP00/Chassis, IP20/NEMA 1, IP54/NEMA 12Vibration test ................................ 0.7 g RMS 18-1000 Hz random. 3 directions for 2 hours (IEC 68-2-34/35/36)Max. relative humidity ........................................................... 93 % +2 %, -3 % (IEC 68-2-3) for storage/transportMax. relative humidity .............................................. 95% non condensing (IEC 721-3-3; class 3K3) for operationAmbient temperature IP00/Chassis, IP20/NEMA 1, IP54/NEMA 12 ............................................................... Max.40 C/104 F (24-hour average max. 35 C/95 F)Ambient temperature IP20/NEMA 1, IP54/NEMA 12, VLT 8011 480 V .......................................................... Max.40 C/104 F (24-hour average max. 35 C/95 F)see Derating for high ambient temperatureMin. ambient temperature in full operation .......................................................................................... 0 C (32 F)Min. ambient temperature at reduced performance ........................................................................ -10 C (14 F)Temperature during storage/transport ............................................... -25 - +65 /70 C (-13 - +149 /158 F)Max. altitude above sea level ...................................................................................................... 1000 m (3300 ft)see Derating for high air pressure

VLT 8000 AQUA protection :

• Electronic motor thermal protection against overload.• Temperature monitoring of heat-sink ensures that the VLT Frequency Converter cuts out if the

temperature reaches 90 C (194 F) for IP00/Chassis and IP20/NEMA 1. For IP54/NEMA 12,the cut-out temperature is 80 C (176 F). An overtemperature can only be reset when thetemperature of the heat-sink has fallen below 60 C (140 F).

• The VLT Frequency Converter is protected against short-circuiting on motor terminals U, V, W.• The VLT Frequency Converter is protected against ground fault on motor terminals U, V, W.• Monitoring of the intermediate circuit voltage ensures that the VLT Frequency Converter cuts

out if the intermediate circuit voltage gets too high or too low.• If a motor phase is missing, the VLT Frequency Converter cuts out.• If there is a line fault, the VLT Frequency Converter is able to carry out a controlled deramping.• If a line phase is missing, the VLT Frequency Converter will cut out or autoderate when a load

is placed on the motor. Alternatively, the drive can be programmed to decrease it’s outputfrequency as needed to maintain operation if desirable.

MG.80.A2.02 - VLT is a registered Danfoss trademark 19

Page 5: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

� Technical data, line supply 3 x 200 - 240 V

According to international requirements VLT type 8006 8008 8011

Output current IVLT,N [A] 16.7 24.2 30.8

IVLT, MAX(60 s) [A] 18.4 26.6 33.9

Output (240 V) SVLT,N [kVA] 6.9 10.1 12.8

Typical shaft output PVLT,N [kW] 4.0 5.5 7.5

Typical shaft output PVLT,N [HP] 5 7.5 10

Max. cable cross-section to motor and DC-bus [mm2]/[AWG]2) 4/10 16/6 16/6

Max. input current (200 V)(RMS) IL,N [A] 16.0 23.0 30.0

Max. cable cross-section

power [mm2]/[AWG]2)4/10 16/6 16/6

Max. line-fuses [A]/UL 3) [A] 50 50 50

Line contactor[Danfoss type]

[AC value]

CI 6

AC-1

CI 9

AC-1

CI 16

AC-1

Efficiency 4) ≥ 0.98 0.98 0.98

Weight IP20/NEMA 1 [kg/lbs] 23/51 23/51 23/51

Weight IP54/NEMA 12 [kg/lbs] 35/77 35/77 38/84

Power loss at max. load. [W] Total 194 426 545

Enclosure VLT type IP20/NEMA 1, IP54/NEMA 12

According to international requirements VLT type 8016 8022 8027 8032 8042 8052 8062

Output current IVLT,N [A] (200-240 V) 46.2 59.4 74.8 88.0 115 143 170

IVLT, MAX(60 s) [A]

(200-240 V)50.6 65.3 82.3 96.8 127 158 187

IVLT,N [A] (240 V) 46.0 59.4 74.8 88.0 104 130 154

IVLT, MAX (60 s) [A] (240 V) 50.6 65.3 82.3 96.8 115 143 170

Output SVLT,N [kVA] (240 V) 19.1 24.7 31.1 36.6 41.0 52.0 61.0

Typical shaft output PVLT,N [kW] 11 15 18.5 22 30 37 45

Typical shaft output PVLT,N [HP] 15 20 25 30 40 50 60

Max. cable cross-section to motor and

DC-bus [mm2]/[AWG]2) copper 16/6 35/2 35/2 50/0 70/1/0 95/3/0 120/4/0

aluminium 16/6 35/2 35/2 50/0 95/3/05) 90/250mcm5)120/300mcm5)

Min cable, cross-section to motor and DC- bus

[mm2]/[AWG]2)10/8 10/8 10/8 16/6 10/8 10/8 10/8

Max. input current (200 V) (RMS) IL,N [A] 46.0 59.2 74.8 88.0 101.3 126.6 149.9

Max. cable, cross-section power

[mm2]/[AWG]2) copper 16/6 35/2 35/2 50/0 70/1/0 95/3/0 120/4/0

aluminium 16/6 35/2 35/2 50/0 95/3/05) 90/250mcm5)120/300mcm5)

Max. line-fuses [A]/UL 3) [A] 60 80 125 125 150 200 250

Efficiency 4) 0.96 0.96 0.96 0.96 0.96 0.96 0.96

Weight IP00/Chassis [kg/lbs] - - - - 82/180 82/180 82/180

Weight IP20/NEMA 1 [kg/lbs] 23/51 27/60 27/60 43/96 91/202 91/202 91/202

Weight IP54/NEMA 12 [kg/lbs] 34/76 44/98 45/100 50/110 94/208 94/208 94/208

Power loss at max. load.: W 545 783 1042 1243 1089 1361 1613

Enclosure IP20/NEMA 1, IP54/NEMA 12

1. Current ratings fulfill UL requirements for 208-240 V

2. American Wire Gauge

3. See Line Connection section in this manual for VLT fuse types.

4. Measured using 30m/100 ft. shielded motor cable at rated load and rated frequency.

5. Connection stud 1 x M8 / 2 x M8.

MG.80.A2.02 - VLT is a registered Danfoss trademark20

Page 6: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

Inst

alla

tion

� Technical data, line supply 3 x 380 - 480 V

According to international requirements VLT type 8006 8008 8011

Output current IVLT,N [A] (380-415 V) 10.0 13.0 16.0

IVLT, MAX(60 s) [A] (380-415 V) 11.0 14.3 17.6

IVLT,N [A] (416-480 V) 8.2 11.0 14.0

IVLT, MAX (60 s) [A] (416-480 V) 9.0 12.1 15.4

Output SVLT,N [kVA] (400 V) 7.2 9.3 11.5

SVLT,N [kVA] (480 V) 6.5 8.8 11.2

Typical shaft output PVLT,N [kW] 4.0 5.5 7.5

Typical shaft output PVLT,N [HP] 5 7.5 10

Max. cable cross-section

to motor and DC-bus [mm2]/[AWG]1) 4/10 4/10 4/10

Max. input current IL,N[A] (380 V) 9.1 12.2 15.0

(RMS) IL,N[A] (480 V) 8.3 10.6 14.0

Max. cable cross-section,

power [mm2]/[AWG]1) 4/10 4/10 4/10

Max. line-fuses [A]/UL 2) [A] 25/20 25/25 35/30

Efficiency 3) ≥ 0.96 0.96 0.96

Weight IP20/NEMA 1 [kg/lbs] 10/21 10/21 10/21

Weight IP54/NEMA 12 [kg/lbs] 13/28 13/28 13/28

Power loss at max. load. [W] Total 198 250 295

Enclosure VLT type Compact IP20/NEMA 1, IP54/NEMA 12

According to international requirements VLT type 8016 8022 8027 8032 8042 8052 8062 8072

Output current IVLT,N [A] (380-415 V) 24.0 32.0 37.5 44.0 61.0 73.0 90.0 106

IVLT, MAX(60 s) [A]

(380-415 V)26.4 35.2 41.3 48.4 67.1 80.3 99.0 117

IVLT,N [A] (416-480 V) 21.0 27.0 34.0 40.0 52.0 65.0 77.0 106

IVLT, MAX (416-480 V) 23.1 29.7 37.4 44.0 57.2 71.5 84.7 117

Output SVLT,N [kVA] (400 V) 17.3 23.0 27.0 31.6 43.8 52.5 64.7 73.4

SVLT,N [kVA] (480 V) 16.7 21.5 27.1 31.9 41.4 51.8 61.3 84.5

Typical shaft output PVLT,N [kW] 11 15 18.5 22 30 37 45 55

Typical shaft output PVLT,N [HP] 15 20 25 30 40 50 60 75

Max. cable cross-section

to motor and DC-bus [mm2]/[AWG]1) 16/6 16/6 16/6 16/6 35/2 35/2 50/0 10/8

Min. cable. cross-section

to motor and DC-bus 4) [mm2]/[AWG]1) 10/8 10/8 10/8 10/8 10/8 10/8 16/6 10/8

Max. input current IL,N [A] (380 V) 24.0 32.0 37.5 44.0 60.0 72.0 89.0 103

(RMS) IL,N [A] (480 V) 21.0 27.6 34.0 41.0 53.0 64.0 77.0 103

Max. cable, cross-section,

power [mm2]/[AWG]1) 16/6 16/6 16/6 35/2 35/2 35/2 50/0 50/0

Max. line-fuses [A]/UL 2) [A] 63/40 63/40 63/50 63/60 80/80 100/100 125/125 150/150

Efficiency at rated frequency ≥ 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96

Weight IP20/NEMA 1 [kg/lbs] 10/21 21/46 21/46 27/60 27/60 43/96 43/96 110/242

Weight IP54/NEMA 12 [kg/lbs] 13/28 43/96 43/96 46/102 55/122 61/134 63/140 112/248

Power loss at max. load.: W 419 559 655 768 1065 1275 1571 1851

Enclosure IP20/NEMA 1, IP54/NEMA 12

1 American Wire Gauge.

2 See Line Connection section in this manual for VLT fuse types.

3 Measured using 30m/100 ft. shielded motor cable at rated load and rated frequency.

4 Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Always comply with national and local regulations on

min. cable cross-section.

MG.80.A2.02 - VLT is a registered Danfoss trademark 21

Page 7: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

� Technical data, line supply 3 x 380 - 480 V

According to international requirements VLT type 8100 8125 8150 8200 8250 8300Output current IVLT,N [A] (380-415 V) 147 177 212 260 315 368

IVLT, MAX(60 s) [A] (380-415 V) 162 195 233 286 347 405IVLT,N [A](416-480 V) 130 160 190 240 302 361

IVLT, MAX (60 s) [A] (416-480 V) 143 176 209 264 332 397Output SVLT,N [kVA] (400 V) 102 123 147 180 218 255

SVLT,N [kVA] (480 V) 104 127 151 191 241 288Typical shaft output (380-415 V) PVLT,N [kW] 75 90 110 132 160 200Typical shaft output (440-480 V) PVLT,N [HP] 100 125 150 200 250 300Max. cross-section of copper cableto motor and DC-bus (380-415 V) [mm2]1) 95 120 2x70 2x70 2x95 2x120Max. cross-section of copper cableto motor and DC-bus (440-480 V) [mm2]1) 70 95 2x70 2x70 2x95 2x120Max. cross-section of aluminium cableto motor and DC-bus (380-415 V) [mm2]1) 90 120 2x70 2x95 2x120 2x150Max. cross-section of aluminium cableto motor and DC-bus (440-480 V) [mm2]1) 120 150 2x70 2x120 2x120 2x150Max. cross-section of copper cableto motor and DC-bus (380-415 V) [AWG2)]1) 3/0 4/0 2x1/0 2x2/0 2x3/0 2x250mcmMax. cross-section of copper cableto motor and DC-bus (440-480 V) [AWG2)]1) 2/0 3/0 2x1/0 2x1/0 2x3/0 2x4/0Max. cross-section of aluminium cableto motor and DC-bus (380-415 V) [AWG2)]1) 250mcm 300mcm 2x2/0 2x4/0 2x250mcm 2x350mcmMax. cross-section of aluminium cableto motor and DC-bus (440-480 V) [AWG2)]1) 4/0 250mcm 2x2/0 2x3/0 2x250mcm 2x300mcmMax. cross-section of cable to motor and DC-bus3)

[mm2/AWG2)]1) 10/8 10/8 10/8 10/8 16/6 16/6Max. input current4) IL,N [A] (400 V) 145 174 206 256 317 366(RMS) IL,N [A] (480 V) 128 158 185 236 304 356Max. cross-section of copper cableto power (380-415 V) [mm2)]1) 95 120 2x70 2x70 2x95 2x120Max. cross-section of copper cableto power (440-480 V) [mm2)]1) 70 95 2x70 2x70 2x95 2x120Max. cross-section of aluminium cableto power (380-415 V) [mm2)]1) 90 120 2x70 2x95 2x120 2x150Max. cross-section of aluminium cableto power (440-480 V) [mm2)]1) 120 150 2x70 2x120 2x120 2x150Max. cross-section of copper cableto power (380-415 V) [AWG2)]1) 3/0 4/0 2x1/0 2x2/0 2x3/0 2x250mcmMax. cross-section of copper cableto power (440-480 V) [AWG2)]1) 2/0 3/0 2x1/0 2x1/0 2x3/0 2x4/0Max. cross-section of aluminium cableto power (380-415 V) [AWG2)]1) 250mcm 300mcm 2x2/0 2x4/0 2x250mcm 2x350mcmMax. cross-section of aluminium cableto power (440-480 V) [AWG2)]1) 4/0 250mcm 2x2/0 2x3/0 2x250mcm 2x300mcmMin. cable cross-section to motorand DC-bus 3) [mm2/AWG2)] 10/8 10/8 10/8 10/8 16/6Max. line-fuses [A]/UL 5) [A] 250/200 250/250 300/300 350/350 450/400 500/500Internal drive fuses [A]/UL 5) [A] 15/15 15/15 30/30 30/30 30/30 30/30Power/Interface Board fuse [A]/UL 5) [A]Weight IP00/Chassis [kg/lbs] 99/218 99/218 132/292 132/292 132/292 132/292Weight IP20/NEMA 1 [kg/lbs] 110/242 110/242 146/322 146/322 146/322 146/322

Weight IP54/NEMA 12 [kg/lbs] 112/248 112/248 160/354 160/354 160/354 160/354

Efficiency at rated frequency ≥ 0.97 0.97 0.97 0.97 0.97 0.97Power loss at max. load. [W] 1970 2380 2860 3810 4770 5720Enclosure

1. Connection stud 1 x M8 / 2 x M8.

2. American Wire Gauge.

3. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Always comply with national and local regulations on

min. cable cross-section.

4. Drive automatically compensates for power fluctuations +/- 10% of the input voltage.

5. See Line Connection section in this manual for VLT fuse types.

MG.80.A2.02 - VLT is a registered Danfoss trademark22

Page 8: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

Inst

alla

tion

� Technical data, line supply 3 x 380 - 480 V

According to international requirements VLT type 8350 8450 8500 8600

Output current IVLT,N [A] (380-415 V) 480 600 658 745

IVLT, MAX(60 s) [A] (380-415 V) 528 660 724 820

IVLT,N [A] (440-480 V) 443 540 590 678

IVLT, MAX (60 s) [A] (440-480 V) 487 594 649 746

Output SVLT,N [kVA] (415 V) 345 431 473 536

SVLT,N [kVA] (480 V) 353 430 470 540

Typical shaft output (380-440 V) PVLT,N [kW] 250 315 355 400

Typical shaft output (441-500 V) PVLT,N [HP] 350 450 500 600

Max. cross-section of

copper cable to motor 2 x 150 2 x 185 2 x 240 2 x 300

and loadsharing (380-415 V) [mm2]1) 3 x 70 3 x 95 3 x 120 3 x 150

Max. cross-section of

copper cable to motor 2 x 120 2 x 150 2 x 185 2 x 300

and loadsharing (440-480 V) [mm2]1) 3 x 70 3 x 95 3 x 95 3 x 120

Max. cross-section of

aluminium cable to motor 2 x 185 2 x 240 2 x 300

and loadsharing (380-415 V) [mm2]1) 3 x 120 3 x 150 3 x 185 3 x 185

Max. cross-section of

aluminium cable to motor 2 x 150 2 x 185 2 x 240

and loadsharing (440-480 V) [mm2]1) 3 x 95 3 x 120 3 x 150 3 x 185

Max. cross-section of

copper cable to motor 2 x 250mcm 2 x 350mcm 2 x 400mcm 2 x 500mcm

and loadsharing (380-415 V) [AWG]2)1) 3 x 2/0 3 x 3/0 3 x 4/0 3 x 250mcm

Max. cross-section of

copper cable to motor 2 x 4/0 2 x 300mcm 2 x 350mcm 2 x 500mcm

and loadsharing (440-480 V) [AWG]2)1) 3 1/0 3 x 3/0 3 x 3/0 3 x 4/0

Max. cross-section of

aluminium cable to motor 2 x 350mcm 2 x 500mcm 2 x 600mcm 2 x 700mcm

and loadsharing (380-415 V) [AWG]2)1) 3 x 4/0 3 x 250mcm 3 x 300mcm 3 x 350mcm

Max. cross-section of

aluminium cable to motor 2 x 300mcm 2 x 400mcm 2 x 500mcm 2 x 600mcm

and loadsharing (440-480 V) [AWG]2)1) 3 x 3/0 3 x 4/0 3 x 250mcm 3 x 300mcm

1. Connection stud 1 x M8 / 2 x M8.

2. American Wire Gauge.

MG.80.A2.02 - VLT is a registered Danfoss trademark 23

Page 9: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

� Technical data, line supply 3 x 380 - 480 V

According to international requirements VLT type 8350 8450 8500 8600

Max. input current IL,MAX [A] (400 V) 389 467 584 648

(RMS) IL,MAX [A] (480 V) 356 431 526 581

Max. cross-section of

copper cable 2 x 150 2 x 185 2 x 240 2 x 300

to power (380-415 V) [mm2]1) 3 x 70 3 x 95 3 x 120 3 x 150

Max. cross-section of

copper cable 2 x 120 2 x 150 2 x 185 2 x 300

to power (440-480 V) [mm2]1) 3 x 70 3 x 95 3 x 95 3 x 120

Max. cross-section of

aluminium cable 2 x 185 2 x 240 2 x 300

to power (380-415 V) [mm2]1) 3 x 120 3 x 150 3 x 185 3 x 185

Max. cross-section of

aluminium cable 2 x 150 2 x 185 2 x 240

to power (440-480 V) [mm2]1) 3 x 95 3 x 120 3 x 150 3 x 185

Max. cross-section of

copper cable 2 x 250mcm 2 x 350mcm 2 x 400mcm 2 x 500mcm

to power (380-415 V) [AWG]2)1) 3 x 2/0 3 x 3/0 3 x 4/0 3 x 250mcm

Max. cross-section of

copper cable 2 x 4/0 2 x 300mcm 2 x 350mcm 2 x 500mcm

to power (440-480 V) [AWG]2)1) 3 1/0 3 x 3/0 3 x 3/0 3 x 4/0

Max. cross-section of

aluminium cable 2 x 350mcm 2 x 500mcm 2 x 600mcm 2 x 700mcm

to power (380-415 V) [AWG]2)1) 3 x 4/0 3 x 250mcm 3 x 300mcm 3 x 350mcm

Max. cross-section of

aluminium cable 2 x 300mcm 2 x 400mcm 2 x 500mcm 2 x 600mcm

to power (440-480 V) [AWG]2) 1) 3 x 3/0 3 x 4/0 3 x 250mcm 3 x 300mcm

Max. pre-fuses (mains) [-]/UL3) [A] 630/600 700/700 800/800 800/800

Internal drive fuses [-]/UL3) [A] 15/15 15/15 15/15 30/30

Internal drive fuses

(resistor) [-]/UL3) [A] 12/12 12/12 12/12 12/12

Integral pre-fuses (SMPS) [-]/UL3) [A] 5.0/5.0

Efficiency ≥ 0.97 0.97 0.97 0.97

Weight IP00/Chassis [kg/lsb] 480/1058 515/1135 560/1234 585/1290

Weight IP20/NEMA 1 [kg/lsb] 595/1311 630/1388 675/1488 700/1543

Weight IP54/NEMA 12 [kg/lsb] 605/1334 640/1411 685/1510 710/1565

Power loss at max. load [W] 7500 9450 10650 12000

Enclosure IP00/Chassis, IP20/NEMA 1 and IP54/NEMA 12

1. Connection stud 1 x M8 / 2 x M8.

2. American Wire Gauge.

3. See Line Connection section in this manual for fuse types.

MG.80.A2.02 - VLT is a registered Danfoss trademark24

Page 10: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

Inst

alla

tion

� Technical data, line supply 3 x 550 - 600 V

According to international requirements VLT type 8002 8003 8004 8005 8006 8008 8011

Output

Output current IVLT,N [A] (550 V) 2.6 2.9 4.1 5.2 6.4 9.5 11.5

IVLT, MAX (60 s) [A]

(550 V)2.9 3.2 4.5 5.7 7.0 10.5 12.7

IVLT,N [A] (575 V) 2.4 2.7 3.9 4.9 6.1 9.0 11.0

IVLT, MAX (60 s) [A]

(575 V)2.6 3.0 4.3 5.4 6.7 9.9 12.1

Output SVLT,N [kVA] (550 V) 2.5 2.8 3.9 5.0 6.1 9.0 11.0

SVLT,N [kVA] (575 V) 2.4 2.7 3.9 4.9 6.1 9.0 11.0

Typical shaft output PVLT,N [kW] 1.1 1.5 2.2 3 4 5.5 7.5

Typical shaft output PVLT,N [HP] 1.5 2 3 4 5 7.5 10

[mm2] 4 4 4 4 4 4 4Max. copper cable

cross-section to motor,

brake and loadsharing1)[AWG]2) 10 10 10 10 10 10 10

Input

Rated input current IVLT,N [A] (550 V) 2.5 2.8 4.0 5.1 6.2 9.2 11.2

IVLT,N [A] (600 V) 2.2 2.5 3.6 4.6 5.7 8.4 10.3

[mm2] 4 4 4 4 4 4 4Max. copper cable

cross-section, power

NEMA11)

[AWG]2)

10 10 10 10 10 10 10

Max. pre-fuses mains3) [-]/UL3) [A] 3 4 5 6 8 10 15

Efficiency ≥ 0.96 0.96 0.96 0.96 0.96 0.96 0.96

Weight IP20/NEMA 1 [kg]/[lbs] 10.5/23.1 10.5/23.1 10.5/23.1 10.5/23.1 10.5/23.1 10.5/23.1 10.5/23.1

Estimated power loss

at max. load.(550 V) [W] 65 73 103 131 161 238 288

Estimated power loss

at max. load.(600 V) [W] 63 71 102 129 160 236 288

Enclosure IP20/NEMA1

1. Connection stud 1 x M8 / 2 x M8.

2. American Wire Gage (AWG)

3. If UL/cUL is to be complied with, pre-fuses type Bussman KTS-R type or exact equivalent must be used for VLT 8002 - 8072.

If UL/cUL is to be complied with, pre-fuses type Bussman FWP semi-conductor type or exact equivalent must be used for VLT 8100 - 8250.

If UL/cUL is not to be complied with, use type gG fuse for VLT 8002 - 8072 and type gR for VLT 8100 - 8300.

Not following the recommendation may result in unnecessary damage of the drive in case of malfunction. Fuses must be designed for protection in a

circuit capable of supplying a maximum of 100.000 Arms (symmetrical), 600 V maximum.

MG.80.A2.02 - VLT is a registered Danfoss trademark 25

Page 11: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

� Technical data, line supply 3 x 550 - 600 V

According to international requirements VLT type 8016 8022 8027 8032 8042 8052 8062 8072

Output

Output current IVLT,N [A] (550 V) 18 23 28 34 43 54 65 81

IVLT, MAX (60 s) [A]

(550 V)20 25 31 37 47 59 72 89

IVLT,N [A] (575 V) 17 22 27 32 41 52 62 77

IVLT, MAX (60 s) [A]

(575 V)19 24 30 35 45 57 68 85

Output SVLT,N [kVA] (550 V) 17 22 27 32 41 51 62 77

SVLT,N [kVA] (575 V) 17 22 27 32 41 52 62 77

Typical shaft output PVLT,N [kW] 11 15 18.5 22 30 37 45 55

Typical shaft output PVLT,N [HP] 15 20 25 30 40 50 60 75

[mm2] 16 16 16 35 35 50 50 50Max. copper cable

cross-section to motor,

brake and loadsharing1)[AWG]2) 6 6 6 2 2 1/0 1/0 1/0

[mm2] 0.5 0.5 0.5 10 10 16 16 16

Min. cable cross-section

to motor, brake and

loadsharing3)[AWG]2) 20 20 20 8 8 6 6 6

Input

Rated input current IVLT,N [A] (550 V) 18 22 27 33 42 53 63 79

IVLT,N [A] (600 V) 16 21 25 30 38 49 58 72

[mm2] 16 16 16 35 35 50 50 50Max. copper cable

cross-section, power

NEMA11)[AWG]2) 6 6 6 2 2 1/0 1/0 1/0

Max. pre-fuses mains4) [-]/UL4) [A] 20 30 35 45 60 75 90 100

Efficiency ≥ 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96

Weight IP20/NEMA 1 [kg]/[lbs] 23/51 23/51 23/51 30/66 3066 48/106 48/106 48/106

Estimated power loss at

max. load.(550 V) [W] 451 576 702 852 1077 1353 1628 2029

Estimated power loss at

max. load.(600 V) [W] 446

576707 838 1074 1362 1624 2016

Enclosure IP20/NEMA 1

1. Connction stud 1 x M8 / 2 x M8.

2. American Wire Gage (AWG)

3.Min. cable cross-section is the smallest cable cross-section allowed to be fitted into the terminals to comply with IP20/NEMA 1.

4. If UL/cUL is to be complied with, pre-fuses type Bussman KTS-R type or exact equivalent must be used for VLT 8002 - 8072.

If UL/cUL is to be complied with, pre-fuses type Bussman FWP semi-conductor type or exact equivalent must be used for VLT 8100 - 8250.

If UL/cUL is not to be complied with, use type gG fuse for VLT 8002 - 8072 and type gR for VLT 8100 - 8300.

Not following the recommendation may result in unnecessary damage of the drive in case of malfunction. Fuses must be designed for

protection in a circuit capable of supplying a maximum of 100.000 Arms (symmetrical), 600 V maximum.

Always comply with national and local regulations on min. cable cross-section.

MG.80.A2.02 - VLT is a registered Danfoss trademark26

Page 12: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

Inst

alla

tion

� Technical data, line supply 3 x 550 - 600 V

According to international requirements VLT type 8100 8125 8150 8200 8250 8300

Output

Output current IVLT,N [A] (550 V) 104 131 151 201 253 289

IVLT, MAX (60 s) [A] (550 V) 114 144 166 221 278 318

IVLT,N [A] (575 V) 99 125 144 192 242 289

IVLT, MAX (60 s) [A] (575 V) 109 138 158 211 266 318

Output SVLT,N [kVA] (550 V) 99 125 144 191 241 275

SVLT,N [kVA] (575 V) 99 124 143 191 241 288

Typical shaft output PVLT,N [kW] 75 90 110 132 160 200

Typical shaft output PVLT,N [HP] 100 125 150 200 250 300

[mm2] 120 120 120 2x120 2x120 2x120Max. copper cable cross-section to

motor, brake and loadsharing1) [AWG]2) 4/0 4/0 4/0 2x4/0 2x4/0 2x4/0

[mm2] 185 185 185 2x185 2x185 2x185Max. aluminium cross-section to

motor, brake and loadsharing1)[AWG]2) 300

mcm

300

mcm

300

mcm

2x300

mcm

2x300

mcm

2x300

mcm

[mm2] 6 6 6 2x6 2x6 2x6Min. cable cross-section to motor,

brake and loadsharing3) [AWG]2) 8 8 8 2x8 2x8 2x8

Input Rated input current IVLT,N [A] (550 V) 101 128 147 196 246 281

IVLT,N [A] (600 V) 92 117 134 179 226 270

[mm2] 120 120 120 2x120 2x120 2x120Max. copper cable cross-section,

power NEMA11) [AWG]2) 4/0 4/0 4/0 2x4/0 2x4/0 2x4/0

[mm2] 185 185 185 2x185 2x185 2x185Max. aluminium cable cross-section,

power NEMA11)[AWG]2) 300

mcm

300

mcm

300

mcm

2x300

mcm

2x300

mcm

2x300

mcm

Max. pre-fuses mains4) [-]/UL4) [A] 125 175 200 250 350 400

Integral pre-fuses

(softcharge circuit, AC)5)[-]/UL4) [A]

15

(Qty.3)

15

(Qty.3)

15

(Qty.3)

30

(Qty.3)

30

(Qty.3)30 (Qty.3)

Integral pre-fuses

(softcharge resistors, DC)5)[-]/UL4) [A]

12

(Qty.1)

12

(Qty.1)

12

(Qty.1)

12

(Qty.1)

12

(Qty.2)12 (Qty.2)

Integral pre-fuses (SMPS)6) [-]/UL4) [A] 5 5 5 5 5 5

Efficiency ≥ 0.97 0.97 0.97 0.97 0.97 0.97

Weight IP00/Chassis [kg]/[lbs] 109/240 109/240 109/240 146/322 146/322 146/322

Weight IP20/NEMA 1 [kg]/[lbs] 121/267 121/267 121/267 161/355 161/355 161/355

Estimated power loss at max. load. (550 V) [W] 2605 3285 3785 5035 6340 7240

Estimated power loss at max. load. (600 V) [W] 2560 3275 3775 5030 6340 7570

Enclosure IP00/Chassis and IP20/NEMA 1

1. Connction stud 1 x M8 / 2 x M8.

2. American Wire Gage (AWG)

3. Min. cable cross-section is the smallest cable cross-section allowed to be fitted into the terminals to comply with IP20/NEMA 1.

4. If UL/cUL is to be complied with, pre-fuses type Bussman KTS-R type or exact equivalent must be used for VLT 8002 - 8072.

If UL/cUL is to be complied with, pre-fuses type Bussman FWP semi-conductor type or exact equivalent must be used for VLT 8100 - 8250.

If UL/cUL is not to be complied with, use type gG fuse for VLT 8002 - 8072 and type gR for VLT 8100 - 8300.

Not following the recommendation may result in unnecessary damage of the drive in case of malfunction. Fuses must be designed for protection in a

circuit capable of supplying a maximum of 100.000 Arms (symmetrical), 600 V maximum.

Always comply with national and local regulations on min. cable cross-section.

5. Integral pre-fuse (softcharge circuit, AC) must be AC Littelfuse KLK or exact equivalent.

Integral pre-fuse (softcharge resistors, DC) must be KLKD or exact equivalent.

6. Integral pre-fuse (SMPS) must be Bussman KTK type or exact equivalent.

MG.80.A2.02 - VLT is a registered Danfoss trademark 27

Page 13: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

� FusesUL compliance

To comply with UL/cUL approvals, pre-fuses according to the table below, are recommended.

200-240 V

VLT Bussmann SIBA Littel fuse Ferraz-Shawmut8006 KTN-R30 5012406-032 KLN-R30 ATM-R30 or A2K-30R8008 KTN-R50 5014006-050 KLN-R50 A2K-50R8011 KTN-R60 5014006-063 KLN-R60 A2K-60R8016 KTN-R60 5014006-063 KLN-R60 A2K-60R8022 KTN-R80 5014006-080 KLN-R80 A2K-80R8027 KTN-R125 2028220-125 KLN-R125 A2K-125R8032 KTN-R125 2028220-125 KLN-R125 A2K-125R8042 FWX-R150 2028220-150 L25S-150 A25X-1508052 FWX-R200 2028220-200 L25S-200 A25X-2008062 FWX-R250 2028220-250 L25S-250 A25X-250

380-500 V

Bussmann SIBA Littel fuse Ferraz-Shawmut

8006 KTS-R20 5017906-020 KLS-R20 ATM-R20 or A6K-20R

8008 KTS-R25 5017906-025 KLS-R25 ATM-R25 or A6K-25R

8011 KTS-R30 5017906-032 KLS-R30 A6K-30R

8016 KTS-R40 5012406-040 KLS-R40 A6K-40R

8022 KTS-R40 5017906-040 KLS-R40 A6K-40R

8027 KTS-R50 5014006-050 KLS-R50 A6K-50R

8032 KTS-R60 5014006-063 KLS-R60 A6K-60R

8042 KTS-R80 2028220-100 KLS-R80 A6K-80R

8052 KTS-R100 2028220-125 KLS-R100 A6K-100R

8062 KTS-R125 2028220-125 KLS-R125 A6K-125R

8072 KTS-R150 2028220-160 KLS-R150 A6K-150R

8075 FWH-R150 2028220-125 L50S-150 A50-P150

8100 FWH-R220 2028220-200 L50S-225 A50-P225

8125 FWH-R250 2028220-224 L50S-250 A50-P250

8150 FWH-R300 2028220-315 L50S-300 A50-P300

8200 FWH-R350 2028220-315 L50S-350 A50-P350

8250 FWH-R400 206xx32-400 L50S-400 A50-P400

8300 FWH-R500 206xx32-500 L50S-500 A50-P500

8350 FWH-R600 206xx32-600 L50S-600 A50-P600

8450 FWH-R700 206xx32-700 L50S-700 A50-P700

8500 FWH-R800 206xx32-800 L50S-800 A50-P800

8600 FWH-R800 206xx32-800 L50S-800 A50-P800

KTS-fuses from Bussmann may substitute KTN for 240 V drives.

FWH-fuses from Bussmann may substitute FWX for 240 V drives.

KLSR fuses from LITTEL FUSE may substitute KLNR fuses for 240 V drives.

L50S fuses from LITTEL FUSE may substitute L50S fuses for 240 V drives.

A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240 V drives.

A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240 V drives.

MG.80.A2.02 - VLT is a registered Danfoss trademark28

Page 14: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

Inst

alla

tion

550-600 V

VLT Bussmann

E52273

RK1 / JDDZ

SIBA

E180276

RK1 / JDDZ

Littel fuse

E81895

RK1 / JDDZ

Ferraz-Shawmut

E163267 / E2137

CC / JDDZ

Ferraz-Shawmut

E163267 / E2137

RK1 / JDDZ8002 KTS-R-3 5017906-004 KLSR003 - A6K-3R

8003 KTS-R-4 5017906-004 KLSR004 - A6K-4R8004 KTS-R-5 5017906-005 KLSR005 - A6K-5R8005 KTS-R-6 5017906-006 KLSR006 - A6K-6R8006 KTS-R-8 5017906-008 KLSR008 - A6K-8R8008 KTS-R-10 5017906-010 KLSR010 - A6K-10R8011 KTS-R-15 5017906-016 KLSR015 - A6K-15R

8016 KTS-R-20 5017906-020 KLSR020 - A6K-20R8022 KTS-R-30 5017906-030 KLSR030 - A6K-30R8027 KTS-R-35 5014006-040 KLSR035 - A6K-35R8032 KTS-R-45 5014006-050 KLSR045 - A6K-45R8042 KTS-R-60 5014006-063 KLSR060 - A6K-60R8052 KTS-R-75 5014006-080 KLSR075 - A6K-80R8062 KTS-R-90 5014006-100 KLSR090 - A6K-90R8072 KTS-R-100 5014006-100 KLSR100 - A6K-100R

VLT E91958

JFHR2

SIBA

E180276

RK1 / JDDZ

E71611

JFHR2

E60314

JFHR2

8100 FWP-125A 2018920-125 L70S125 - A70QS1258125 FWP-175A 2018920-180 L70S175 - A70QS1758150 FWP-200A 2018920-200 L70S200 - A70QS2008200 FWP-250A 2018920-250 L70S250 - A70QS2508250 FWP-350A 206xx32-350 L70S350 - A70QS3508300 FWP-400A 206xx32-400 L70S400 - A70QS400

Non UL compliance

If UL/cUL is not required, we recommend the above mentioned fuses or:

VLT 8032-8052 200-240 V type gR

VLT 8075-8500 380-500 V type gR

VLT 8075-8250 550-600 V type gR

1. Not following the recommendation may result in unnecessary damage of the drive in case of malfunction. Fuses must be designed

for protection in a circuit capable of supplying a maximum of 100000 Arms (symmetrical), 500 V maximum.

MG.80.A2.02 - VLT is a registered Danfoss trademark 29

Page 15: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

� Mechanical dimensionsThe dimensions listed in the following tables are forreference only. Dimension values are in mm (inches).

For all regions except North America (NA), thehardware configurations and dimensions are:

IP 00 -

VLT 8042 - VLT 8062 (200 - 240 VAC)VLT 8100 - VLT 8125 (380 - 480 VAC)VLT 8100 - VLT 8150 (550 - 600 VAC)

Air space (above and below): 250 (9.84)

VLT 8150 - VLT 8300 (380 - 480 VAC)VLT 8200 - VLT 8300 (550 - 600 VAC)

Air space (above and below): 300 (11.81)

VLT 8350 - VLT 8600 (380 - 480 VAC)

Air space (above and below): 494 (19.45)

MG.80.A2.02 - VLT is a registered Danfoss trademark30

Page 16: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

Inst

alla

tion

IP 20 -

VLT 8006 - VLT 8032 (200 - 240 VAC)

VLT 8016 - VLT 8072 (380 - 480 VAC)

VLT 8016 - VLT 8072 ( 550 - 600 VAC)

VLT 8006 - VLT 8032 (200 - 240 VAC)

VLT Model A B C a b

8006 - 8011 560 (22.0) 242 (9.5) 260 (10.2) 540 (21.3) 200 (7.9)

8016 - 8022 700 (27.6) 242 (9.5) 260 (10.2) 680 (26.8) 200 (7.9)

8027 - 8032 800 (31.5) 308 (12.1) 296 (11.7) 780 (30.7) 270 (10.6)

VLT 8016 - VLT 8072 (380 - 480 and 550 - 600 VAC)

VLT Model A B C a b

8016 - 8027 560 (22.0) 242 (9.5) 260 (10.2) 540 (21.3) 200 (7.9)

8032 - 8042 700 (27.6) 242 (9.5) 260 (10.2) 680 (26.8) 200 (7.9)

8052 - 8072 800 (31.5) 308 (12.1) 296 (11.7) 780 (30.7) 270 (10.6)

Air space (above and below): 200 (7.9)

VLT 8006 - VLT 8011 (380 - 480 VAC)

VLT 8002 - VLT 8011 (550 - 600 VAC)

VLT Model A B C a b

8002 - 8011 395 (15.6) 220 (8.7) 200 (7.9) 384 (15.1) 200 (7.9)

Air space (above and below): 100 (3.94)

MG.80.A2.02 - VLT is a registered Danfoss trademark 31

Page 17: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

IP 20

VLT 8042 - VLT 8062 (200 - 240 VAC)

VLT 8100 - VLT 8125 (380 - 460 VAC)

VLT 8100 - VLT 8150 (550 - 600 VAC)

Air space (above and below): 250 (9.84)

VLT 8350 - VLT 8600 (380 - 480 VAC)

Air space (above and below): ()

VLT 8150 - VLT 8300 (380 - 480 VAC)

VLT 8200 - VLT 8300 (550 - 600 VAC)

Air space (Above): 300 (11.81)Air space (Below): 225 (8.86)

* Order Code CN1

MG.80.A2.02 - VLT is a registered Danfoss trademark32

Page 18: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

Inst

alla

tion

IP 54 -

VLT 8006 - VLT 8032 (200 - 240 VAC)VLT 8046 - VLT 8072 (380 - 480 VAC)VLT 8006 - VLT 8032 (200 - 240 VAC)

VLT Model A B C D a b ab/be8006 - 8011 810 (31.9) 350 (13.8) 280 (11.0) 70 (2.76) 560 (22.0) 326 (12.8) 200 (7.9)8016 - 8032 940 (37.0) 400 (15.7) 280 (11.0) 70 (2.76) 690 (27.2) 375 (14.8) 200 (7.9)VLT 8006 - VLT 8075 (380 - 480 VAC)VLT Model A B C D a b ab/be8006 - 8011 530 (20.9) 282 (11.1) 195 (7.7) 85 (3.35) 330 (13.0) 258 (10.2) 100 (3.94)8016 - 8032 810 (31.9) 350 (13.8) 280 (11.0) 70 (2.76) 560 (22.0) 326 (12.8) 200 (7.9)8042 - 8072 940 (37.0) 400 (15.7) 280 (11.0) 70 (2.76) 690 (27.2) 375 (14.8) 200 (7.9)

Air Space Above unit = abAir Space Below unit = be

IP 54 -

VLT 8042 - VLT 8052 (200 - 240 VAC)VLT 8100 - VLT 8125 (380 - 480 VAC)

MG.80.A2.02 - VLT is a registered Danfoss trademark 33

Page 19: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

VLT 8150 - VLT 8300 (380 - 480 VAC)

Air space (Above): 300 (11.81)Air space (Below): 175 (6.89)

VLT 8350 - VLT 8600 (380 - 480 VAC)

MG.80.A2.02 - VLT is a registered Danfoss trademark34

Page 20: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

Inst

alla

tion

� North America Configurations and DimensionsAll dimensions are in mm (in.) and are for referenceonly. For precise dimensional detail, pleasecontact your Danfoss Sales Office.

Chassis -

VLT 8042 - VLT 8062 (200 - 240 VAC)VLT 8100 - VLT 8125 (380 - 480 VAC)VLT 8100 - VLT 8150 (550 - 600 VAC)

Air space (Above and Below): 250 (9.84)

VLT 8350 - VLT 8600 (380 - 480 VAC)

VLT 8150 - VLT 8300 (380 - 480 VAC)VLT 8200 - VLT 8300 (550 - 600 VAC)

Air space (Above and Below):300 (11.81)

MG.80.A2.02 - VLT is a registered Danfoss trademark 35

Page 21: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

Protected Chassis and NEMA 1*

VLT 8006 - VLT 8032 (200 - 240 VAC) VLT 8016 - VLT 8072 (380 - 480 VAC) VLT 8016 - VLT 8072 (550 - 600 VAC)

VLT 8006 - VLT 8032 (200 - 240 VAC)VLT Model A B C a b8006 - 8011 560 (22.0) 242 (9.5) 260 (10.2) 540 (21.3) 200 (7.9)8016 - 8022 700 (27.6) 242 (9.5) 260 (10.2) 680 (26.8) 200 (7.9)8027 - 8032 800 (31.5) 308 (12.1) 296 (11.7) 780 (30.7) 270 (10.6)VLT 8016 - VLT 8072 (380 - 480 and 550 - 600 VAC)VLT Model A B C a b8016 - 8027 560 (22.0) 242 (9.5) 260 (10.2) 540 (21.3) 200 (7.9)8032 - 8042 700 (27.6) 242 (9.5) 260 (10.2) 680 (26.8) 200 (7.9)8052 - 8072 800 (31.5) 308 (12.1) 296 (11.7) 780 (30.8) 270 (10.6)

Air space (Above and Below): 200 (7.9)

VLT 8006 - VLT 8011 ( 380 - 480 VAC)VLT 8002 - VLT 8011 (550 - 600 VAC)VLT Model A B C a b8002 - 8011 395 (15.6) 220 (8.7) 200 (7.9) 384 (15.1) 200 (7.9)

Air space (Above and Below): 100 (3.94)

* Order CN1 for NEMA 1 - Order C20 for Protected Chassis except as noted.

** Internal RFI Filter requires C20 Order Code and addition of Enclosure Extension Option for bottom of standard enclosure.

Internal RFI Filter not available for 550-600 VAC models.

MG.80.A2.02 - VLT is a registered Danfoss trademark36

Page 22: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

Inst

alla

tion

VLT 8042 - VLT 8062 (200 - 240 VAC)VLT 8100 - VLT 8125 (380 - 460 VAC)VLT 8100 - VLT 8150 (550 - 600 VAC)

Air space (Above and Below): 250 (9.84)

VLT 8350 - VLT 8600 (380 - 460 VAC)

VLT 8150 - VLT 8300 (380 - 480 VAC)VLT 8200 - VLT 8300 (550 - 600 VAC)

Air space (Above): 300 (11.81)Air space (Below): 225 (8.86)

MG.80.A2.02 - VLT is a registered Danfoss trademark 37

Page 23: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

NEMA 12 -

VLT 8006 - VLT 8032 (200 - 240 VAC)

VLT 8046 - VLT 8072 (380 - 480 VAC)

VLT 8006 - VLT 8032 (200 - 240 VAC)

VLT Model A B C D a b ab/be

8006 - 8011 810 (31.9) 350 (13.8) 280 (11.0) 70 (2.76) 560 (22.0) 326 (12.8) 200 (7.9)

8016 - 8032 940 (37.0) 400 (15.7) 280 (11.0) 70 (2.76) 690 (27.2) 375 (14.8) 200 (7.9)

VLT 8006 - VLT 8072 (380 - 480 VAC)

VLT Model A B C D a b ab/be

8016 - 8011 530 (20.9) 282 (11.1) 195 (7.7) 85 (3.35) 330 (13.0) 258 (10.2) 100 (3.94)

8016 - 8032 810 (31.9) 350 (13.8) 280 (11.0) 70 (2.76) 560 (22.0) 326 (12.8) 200 (7.9)

8042 - 8072 940 (37.0) 400 (15.7) 280 (11.0) 70 (2.76) 690 (27.2) 375 (14.8) 200 (7.9)

Air Space Above unit = ab

Air Space Below unit = be

VLT 8042 - VLT 8052 (200 - 240 VAC)VLT 8100 - VLT 8125 (380 - 480 VAC)

Air space (Above): 250 (9.84)Air space (Below): 50 (1.97)

MG.80.A2.02 - VLT is a registered Danfoss trademark38

Page 24: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

Inst

alla

tion

VLT 8150 - VLT 8300 (380 - 480 VAC)

Air space (Above): 300 (11.81)Air space (Below): 175 (6.89)

VLT 8350 - VLT 8600 (380 - 480 VAC)

MG.80.A2.02 - VLT is a registered Danfoss trademark 39

Page 25: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

� Mechanical installation

Please pay attention to the requirementsthat apply to integration and field mountingkit, see the below list. The information

given in the list must be observed to avoid seriousdamage or injury, especially when installing large units.

The VLT Frequency Converter must beinstalled vertically.

The VLT Frequency Converter is cooled by means ofair circulation. For the unit to be able to release itscooling air, the minimum distance over and below theunit must be as shown in the illustration below.To protect the unit from overheating, it must beensured that the ambient temperature does notrise above the max. temperature stated for theVLT Frequency Converter and that the 24-houraverage temperature is not exceeded. The max.temperature and 24-hour average can be seenfrom the General Technical Data.If the ambient temperature is in the range of45 - 55 C (113 - 131 F), derating of the VLTFrequency Converter will become relevant, seeDerating for ambient temperature.The service life of the VLT Frequency Converterwill be reduced if derating for ambient temperatureis not taken into account.

� Enclosure protection

IP00/Chassis

IP20/NEMA1

IP54/NEMA12

VLT 8006-8032200-240 V

- OK OK

VLT 8006-8600380-480 V

OK OK OK

VLT 8002-8072550-600 V

- OK -

VLT 8100-8300550-600 V

OK OK -

� Spacing when installing of VLT 8002-8011550-600 V IP20/NEMA1,VLT 8006-8011 380-480 V IP20/NEMA 1,Compact IP20/NEMA 1 and IP54/NEMA12.Cooling

All the above-mentioned units require a minimum spaceof 100mm (4 in.) above and below the enclosure.

Side-by-side

All the above-mentioned units can be installed sideby side without any space, since these units donot require any cooling on the sides.

MG.80.A2.02 - VLT is a registered Danfoss trademark40

Page 26: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

Inst

alla

tion

� Installation of VLT 8016-8072 550-600 VIP20/NEMA1, VLT 8006-8032 200-240 V,VLT 8016-8072 380-480 V IP00/Chassis,IP20/NEMA 1 and IP54/NEMA 12Cooling

All units in the above-mentioned series require aminimum space of 204mm (8 in.) above and belowthe enclosure and must be installed on a plane,vertical surface (no spacers). This applies both toIP00/Chassis, IP20/NEMA 1 and IP54/NEMA 12.These units can be installed side by sidewithout any spacing, since they do not requireany cooling on the sides.

Side-by-side

IP00/Chassis, IP20/NEMA 1

IP54/NEMA 12 (flange-by-flange)

� Installation of VLT 8100-8300 550-600 VIP00/Chassis and IP20/NEMA1,VLT 8042-8062 200-240 V,VLT 8100-8300 380-480 V IP00/Chassis,IP20/NEMA 1 and IP54/NEMA 12Cooling

VLT 8100-VLT 8300

All units require a minimum space of 254mm(10 in.) above and below the enclosure andmust be installed on a plane, vertical surface (nospacers). This applies to IP00/Chassis, IP20/NEMA1 and IP54/NEMA 12 units alike.

Side-by-side

VLT 8100-8300 IP00/Chassis and IP54/NEMA 12

VLT 8100-8300 IP54/NEMA 12

All IP00/Chassis and IP20/NEMA 1 units in theabove-mentioned series can be installed sideby side without any spacing.

MG.80.A2.02 - VLT is a registered Danfoss trademark 41

Page 27: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

� Installation of VLT 8350-8600 380-480 V CompactIP00/Chassis, IP20/NEMA 1 and IP54/NEMA 12Cooling

All units in the above-mentioned series require aminimum space of 400mm (15.8 in.) above theenclosure and must be installed on a plane floor.This applies to both chassis, IP20/NEMA 1 andIP54/NEMA12 units. For accessing the VLT 8350-8600AQUA it require a minimum space of 600mm (23.8in.) in front of the VLT frequency converter.

Side-by-side

Compact IP00/Chassis, IP20/NEMA 1, IP54/NEMA 12All IP00/Chassis, IP20/NEMA 1 and IP54/NEMA 12units in the above-mentioned series can be installedside by side without any space between them, sincethese units do not require cooling on the sides.

MG.80.A2.02 - VLT is a registered Danfoss trademark42

Page 28: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

Inst

alla

tion

� General information about electrical installation

� High voltage warning

The voltage of the frequency converteris dangerous whenever the equipmentis connected to line. Incorrect

installation of the motor or the frequency convertermay cause damage to the equipment, seriouspersonal injury or death.Consequently, the instructions in this manual, aswell as national and local safety regulations, mustbe complied with. Touching the electrical parts maybe fatal - even after disconnection from line: usingVLT 8006-8300 200 and 400 V wait at least 15minutes, for 600 V, wait at least 30 minutes.

NB!:It is the user’s or certified electrician’sresponsibility to ensure correctearthing/grounding and protection in

accordance with applicable national and localnorms/codes and standards.

� Earthing/GroundingThe following basic issues need to be consideredwhen installing a frequency converter.

• Safety earthing/grounding: Please note that thefrequency converter has a high leakage currentand must be grounded appropriately for safetyreasons. Apply local safety regulations.

• High-frequency earthing/grounding: Keep theground wire connections as short as possible.

Connect the different ground systems at thelowest possible conductor impedance. The lowestpossible conductor impedance is obtained bykeeping the conductor as short as possible andby using the greatest possible surface area. Aflat conductor, for example, has a lower HFimpedance than a round conductor for the sameconductor cross-section CVESS.If more than one device is installed in cabinets, thecabinet rear plate, which must be made of metal,should be used as a common ground referenceplate. The metal cabinets of the different devices aremounted on the cabinet rear plate using the lowestpossible HF impedance. This avoids having differentHF voltages for the individual devices and avoids therisk of radio interference currents running in connectioncables that may be used between the devices. Theradio interference will have been reduced.In order to obtain a low HF impedance, use thefastening bolts of the devices as HF connection to

the rear plate. It is necessary to remove insulatingpaint or similar from the fastening points.

� CablesControl cables and the filtered line cable shouldbe installed separate from the motor cables so asto avoid interference overcoupling. Normally, adistance of 204mm (8 in) will be sufficient, but it isrecommended to keep the greatest possible distancewherever possible, especially where cables areinstalled in parallel over a substantial distance.

With respect to sensitive signal cables, such astelephone cables and data cables, the greatestpossible distance is recommended with a minimumof 1m (3 ft) per 5m (15 ft) of power cable (lineand motor cable). It must be pointed out thatthe necessary distance depends on the sensitivityof the installation and the signal cables, and thattherefore no precise values can be stated.

If cable jaws are used, sensitive signal cablesare not to be placed in the same cable jaws asthe motor cable or brake cable.If signal cables are to cross power cables, thisshould be done at an angle of 90 degrees.Remember that all interference-filled in- oroutgoing cables to/from a cabinet should beshielded/armored or filtered.

� Shielded/armored cablesThe shield must be a low HF-impedance shield.This is ensured by using a braided shield of copper,aluminium or iron. Shield armor intended formechanical protection, for example, is not suitable.

MG.80.A2.02 - VLT is a registered Danfoss trademark 43

Page 29: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

� High voltage testA high voltage test can be carried out byshort-circuiting terminals U, V, W, L1, L2 and L3

and energizing by max. 2.5 kV DC for one secondbetween this short-circuit and the chassis.

NB!:The RFI switch must be closed (position ON)when high voltage tests are carried out . Theline and motor connection must be interrupted

in the case of high voltage tests of the total installationif the leakage currents are too high.

� Heat emission from VLT 8000 AQUAThe tables in General technical data show thepower loss Pϕ (W) from VLT 8000 AQUA. Themaximum cooling air temperature tIN, MAX is 40 C(104 F) at 100% load (of rated value).

� Ventilation of integrated VLT 8000 AQUAThe quantity of air required for cooling frequencyconverter can be calculated as follows:

1. Add up the values of P for all the AFDs tobe integrated in the same panel.The highest cooling air temperature (tIN) presentmust be lower than tIN, MAX 40 C (104 F).The day/night average must be 5 C (9 F) lower.The outlet temperature of the cooling air mustnot exceed: tOUT, MAX 45 C (113 F).

2. Calculate the permissible difference betweenthe temperature of the cooling air (tIN) andits outlet temperature (tOUT):

t= 45 C (113 F) -tIN.3. Calculate the required

Insert t in Kelvin

The outlet from the ventilation must be placed abovethe highest-mounted frequency converter.Allowance must be made for the pressure lossacross the filters and for the fact that the pressureis going to drop as the filters are choked.

MG.80.A2.02 - VLT is a registered Danfoss trademark44

Page 30: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

Inst

alla

tion

� Earthing/Grounding of shielded/armoredcontrol cablesGenerally speaking, control cables must be shielded/armored and the shield must be connectedby means of a cable clamp at both ends tothe metal cabinet of the unit.

The drawing below indicates how correctearthing/grounding is carried out.

Correct earthing/groundingControl cables and cables for serial communicationmust be fitted with cable clamps at both ends toensure the best possible electrical contact.

Wrong earthing/groundingDo not use twisted cable ends (pigtails), since theseincrease the shield impedance at high frequencies.

Protection with respect to ground potentialbetween PLC and VLTIf the ground potential between the VLT frequencyconverter and the PLC (etc.) is different, electricnoise may occur that will disturb the whole system.This problem can be solved by fitting an equalizingcable, to be placed next to the control cable.Minimum cable cross-section: 8 AWG.

For 50/60 Hz ground loopsIf very long control cables are used, 50/60 Hzground loops may occur that will disturb thewhole system. This problem can be solved byconnecting one end of the shield to via a ground100nF capacitor (keeping leads short).

Cables for serial communicationLow-frequency noise currents between two VLTfrequency converter can be eliminated by connectingone end of the shield to terminal 61. This terminalis connected to ground via an internal RC link. It isrecommended to use twisted-pair cables to reduce thedifferential mode interference between the conductors.

MG.80.A2.02 - VLT is a registered Danfoss trademark 45

Page 31: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

� VLT 8000 AQUA enclosures

IP20/NEMA 1VLT 8006-8011, 380-480 VVLT 8002-8011, 550-600 V

IP54/NEMA 12VLT 8006-8011, 380-480 V

IP20/NEMA 1VLT 8006-8032, 200-240 VVLT 8016-8072, 380-480 VVLT 8016-8072, 550-600 V

MG.80.A2.02 - VLT is a registered Danfoss trademark46

Page 32: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

Inst

alla

tion

� VLT 8000 AQUA enclosures

IP54/NEMA 12VLT 8006-8032, 200-240 VVLT 8016-8072, 380-480 V

IP20/NEMA 1VLT 8042-8062, 200-240 VVLT 8100-8125, 380-480 VVLT 8100-8150, 550-600 V

IP00/ChassisVLT 8042-8062, 200-240 VVLT 8100-8125, 380-480 VVLT 8100-8150, 550-600 V

IP54/NEMA 12VLT 8042-8062, 200-240 VVLT 8100-8125, 380-480 V

MG.80.A2.02 - VLT is a registered Danfoss trademark 47

Page 33: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

IP00/ChassisVLT 8150-8300, 380-480 VVLT 8200-8300, 550-600 V

IP54/NEMA 12VLT 8150-8300, 380-480 V

IP20/NEMA 1VLT 8150-8300, 380-480 VVLT 8200-8300, 550-600 V

MG.80.A2.02 - VLT is a registered Danfoss trademark48

Page 34: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

Inst

alla

tion

� Electrical installation, enclosures

Compact IP20/NEMA 1, IP54/NEMA 12VLT 8350-8600 AQUA, 380-500 V

MG.80.A2.02 - VLT is a registered Danfoss trademark 49

Page 35: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

� Electrical installation, power cables

IP20/NEMA 1, IP54/NEMA 12VLT 8006-8011, 380-480 VVLT 8002-8011, 550-600 V

IP00/Chassis, IP20/NEMA 1VLT 8006-8032, 200-240 VVLT 8016-8072, 380-480 VVLT 8016-8072, 550-600 V

IP54/NEMA 12VLT 8006-8032, 200-240 VVLT 8016-8072, 380-480 V

MG.80.A2.02 - VLT is a registered Danfoss trademark50

Page 36: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

Inst

alla

tion

� Electrical installation, power cables

IP00/Chassis, IP20/NEMA 1VLT 8042-8062, 200-240 VVLT 8100-8125, 380-480 VVLT 8100-8150, 550-600 V

IP00/Chassis, IP20/NEMA 1VLT 8150-8300, 380-480 VVLT 8200-8300, 550-600 V

IP54/NEMA 12VLT 8042-8062, 200-240 VVLT 8100-8125, 380-480 V

IP54/NEMA 12VLT8150-8300, 380-480 V

MG.80.A2.02 - VLT is a registered Danfoss trademark 51

Page 37: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

� EMC-correct electrical installation550-600 V units do not comply with EuropeanEMC and Low Voltage Directives.The following is a guideline to good engineeringpractice, when installing drives. Following theseguidelines is advised, where compliance with EN50081, EN 55011 or EN 61800-3 First environment isrequired. If the installation is in EN 61800-3 Secondenvironment, then it is acceptable to deviate from theseguidelines. It is however not recommended. See alsoCE labelling,under special conditions in this manual.

Good engineering practice to ensure EMC-correctelectrical installation:

• Use only braided screened/armoured motorcables and braided screened/armoured controlcables. The screen should provide a minimumcoverage of 80%. The screen material mustbe metal, not limited to but typically copper,aluminium, steel or lead. There are no specialrequirements for the mains cable.

• Installations using rigid metal conduits are notrequired to use screened cable, but the motorcable must be installed in conduit separate fromthe control and mains cables. Full connectionof the conduit from the drive to the motor isrequired. The EMC performance of flexibleconduits varies a lot and information from themanufacturer must be obtained.

• Connect the screen/armour/conduit to earthat both ends for motor cables as well as forcontrol cables. See also Earthing of braidedscreened/armoured control cables.

• Avoid terminating the screen/armour withtwisted ends (pigtails). Such a terminationincreases the high frequency impedance ofthe screen, which reduces its effectiveness athigh frequencies. Use low impedance cableclamps or EMC cable glands instead.

• It is important to have good electrical contactbetween the mounting plate on which thefrequency converter is installed and the metalchassis of the frequency converter unit.Exception:- IP54/NEMA 12 units designed for wall mounting- VLT 8100-8600 (380-480 V) IP20/NEMA 1- VLT 8042-8062 (200-240 V) IP20/NEMA 1

This however does not apply to IP54/NEMA 12 unitsas they are designed for wall mounting and VLT8100-8600, 380-500 VAC and VLT 8042-8062,200-240 VAC in IP20/Nema1 enclosure.

• Use starwashers and galvanically conductiveinstallation plates to secure good electrical

connections for IP00/Chassis and IP20/NEMA1 installations.

• Avoid using unscreened/unarmoured motoror control cables inside cabinets housing thedrive(s), whenever this can be avoided.

• An uninterrupted high frequency connectionbetween the frequency converter and the motoris required for IP54/NEMA 12 units.

The next illustration shows an example of anEMC-correct electrical installation of an IP 20/NEMA1 frequency converter; the frequency converter hasbeen installed in a cabinet (enclosure) together withan output contactor and is connected to a PLCwhich, in this example, is installed in a separatecabinet. For IP 54/NEMA 12 units, VLT 8100-8250(380-480 V) and VLT 8032-8052 (200-240 V) unitsin IP20/Nema 1 enclosures; screened cables areconnected by using EMC conduits to assure properEMC performance. (See next illustration.)

Other ways of making the installation may give asgood an EMC performance, provided the aboveengineering practice guidelines are followed.

Please note, that when the installation is not madeaccording to these guidelines as well as whenunscreened cables and control wires are used, someemission requirements are not complied with, althoughthe immunity requirements are fulfilled.

MG.80.A2.02 - VLT is a registered Danfoss trademark52

Page 38: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

Inst

alla

tion

MG.80.A2.02 - VLT is a registered Danfoss trademark 53

Page 39: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

� Use of EMC-correct cablesBraided screened/armoured cables are recommendedto optimise EMC immunity of the control cables andthe EMC emission from the motor cables.

The ability of a cable to reduce the in- and outgoingradiation of electric noise depends on the transferimpedance (ZT). The screen of a cable is normallydesigned to reduce the transfer of electric noise;however, a screen with a lower transfer impedance(ZT) value is more effective than a screen witha higher transfer impedance (ZT).

Transfer impedance (ZT) is rarely stated bycable manufacturers, but it is often possible toestimate transfer impedance (ZT) by assessingthe physical design of the cable.

Transfer impedance (ZT) can be assessed onthe basis of the following factors:- The conductibility of the screen material.- The contact resistance between the individual

screen conductors.- The screen coverage, i.e. the physical area

of the cable covered by the screen - oftenstated as a percentage value.

- Screen type, i.e. braided or twisted pattern.

Aluminium-clad with copper wire.

Twisted copper wire or armoured steel wire cable.

Single-layer braided copper wire with varyingpercentage screen coverage.This is the typical Danfoss reference cable.

Double-layer braided copper wire.

Twin layer of braided copper wire with a magnetic,screened/armoured intermediate layer.

Cable that runs in copper tube or steel tube.

Lead cable with 1.1 mm wall thickness.

MG.80.A2.02 - VLT is a registered Danfoss trademark54

Page 40: VLT 8000 AQUA - LEMI-BIS€¦ · VLT® 8000 AQUA General technical ... VLT 8006 - 8032 AQUA / 200 - 240 V ... Alternatively, the drive can be programmed to decrease it’soutput frequency

VLT® 8000 AQUA

Inst

alla

tion

� Tightening torque and screw sizesThe table shows the torque required when fittingterminals to the VLT frequency converter. ForVLT 8006-8032, 200-240 V, VLT 8006-8072,380-480 V and VLT 8002-8072, 550-600 V thecables must be fastened with screws. For VLT8042-8062, 200-240 V and for VLT 8100-8300the cables must be fastened with bolts.These figures apply to the following terminals:

Line terminals Nos 91, 92, 93

L1, L2, L3

Motor terminals Nos 96, 97, 98

U, V, W

Ground terminal No. 99

VLT type3 x 200-240 V

Tighteningtorque

Screwsize

VLT 8006-8011 1.8 Nm (16 ln-lbs) M4VLT 8016-8027 3 Nm (27 ln-lbs) M5VLT 8032 4 Nm (36 ln-lbs) M6

VLT type3 x 200-240 V

Tighteningtorque

Boltsize

VLT 8042-8062 11 Nm (100ln-lbs)

M8

VLT type3 x 380-480 V

Tighteningtorque

Screwsize

VLT 8006-8011 0.5 Nm (5 in-lbs) M3VLT 8016-8032 2 Nm (16 ln-lbs) M4VLT 8032-8052 3 Nm (27 ln-lbs) M5VLT 8062-8072 4 Nm (35.4 ln-lbs) M6

VLT type3 x 380-480 V

Tighteningtorque

Boltsize

VLT 8075-8125 11 Nm (100ln-lbs)

M8

VLT 8150-8300 11 Nm (100ln-lbs)

M8

VLT 8350-8600 42 Nm (375In-lbs)

M12

VLT type3 x 550-600 V

Tighteningtorque

Boltsize

VLT 8002-8011 0.5 Nm (5 in-lbs) M3VLT 8016-8027 2 Nm (16 ln-lbs) M4VLT 8032-8042 3 Nm (27 ln-lbs) M5VLT 8052-8072 4 Nm (36 ln-lbs) M6VLT 8100-8150 11 Nm (100

ln-lbs)M8

VLT 8200-8300 11 Nm (100ln-lbs)

M8

MG.80.A2.02 - VLT is a registered Danfoss trademark 55