· Web viewIEC 62271-100, 62271-102, 62271-1, 62155, 60044-1, 60044-5, 60383, 60815 1.2. Rated...
Transcript of · Web viewIEC 62271-100, 62271-102, 62271-1, 62155, 60044-1, 60044-5, 60383, 60815 1.2. Rated...
4. SCHEDULES OF TECHNICAL INFORMATION
Section VI – Requirements Page 1 of 677Environmental Guidelines for Contractors
CONTENTS
A 400 kV OPEN TERMINAL SWITCHGEAR
B 220 kV OPEN TERMINAL SWITCHGEAR
C EARTHING AND LIGHTNING PROTECTION
D PROTECTION AND INDICATION SYSTEM
E TARIFF METERING SYSTEM
F FAULT MONITORING SYSTEM
G 11kV XLPE INSULATED CABLE SYSTEM (with solid bonding)
H SUBSTATION CONTROL SYSTEM
I DIESEL GENERATOR
J LV SERVICES EQUIPMENT
K 400/220kV POWER TRANSFORMERS (AIS-AIS)
L 400kV SHUNT REACTOR
M 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF)
N NEUTRAL EARTHING RESISTOR
O 400kV OVERHEAD LINE
P 220 kV OVERHEAD LINE
Section VI – Requirements Page 2 of 677Environmental Guidelines for Contractors
A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
1. GENERAL
1.1. Standards IEC IEC 62271-100, 62271-102, 62271-1,
62155, 60044-1, 60044-5, 60383, 60815
1.2. Rated voltage kV 420
1.3. System Voltage kV 400
1.4. Rated frequency Hz 50
1.5. Rated lightning impulse withstand voltage (at altitude <1000m)
- Phase to earth - Phase to phase
KVp
KVp
1425
1425
- Across the isolating distance kVp 1425 (+240)
1.6. Rated switching impulse withstand voltage (at altitude <1000m)
- Phase to earth - Phase to phase
KVp
KVp
1050
1575
- Across the isolating distance kVp 900 (+345)
1.7. Rated power frequency withstand voltage (at altitude <1000m)
- Phase to earth kV 520
Section VI – Requirements Page 3 of 677Environmental Guidelines for Contractors
A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
- Phase to phase kV 520
- Across the isolating distance kV 610
1.8. Rated short-time withstand current (1 s) kA 40
1.9. Rated peak withstand current kA 100
1.10. Rated Current
- at 40 oC A 4000
- at 50 oC (Contractor to confirm by calculation) A
1.11. Material of HV conductor
1.12. Material of contacts
1.13. Minimum factors of safety for switchgear
- Busbars or other connections based on elastic limit
2.5
- Complete insulators based on electro-mechanical test
2.5
- Insulator metal fittings based on elastic limit 2.5
- Steel structures based on elastic limit of tension members and on cripping loads of compression members
2.5
- Foundations for structures against overturning or uprooting under maximum simultaneous working loadings 2.5
Section VI – Requirements Page 4 of 677Environmental Guidelines for Contractors
A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
1.14. Creepage distance (based on Um) mm/kV 31
1.15. Seismic factor
2. CIRCUIT BREAKER
2.1. Manufacturer & Place of manufacturing
2.2. Type designation
2.3. Type SF6 single pole
2.4. Standards 62271-1, IEC 62271-100, 62271-101,
62271-110, 60376, 60480
2.5. Rated operating sequence O -0.3 sec- CO -3 min - CO
2.6. Auto reclosing O -0.3 sec- CO -3 min - CO
2.7. Rated making current KAp 100
2.8 Rated breaking current kA 40
Rated breaking current (asymmetrical) KA To IEC 62271-100
- %dc %dc
2.9. Rated breaking current under out-of-phase conditions
kA 10
Section VI – Requirements Page 5 of 677Environmental Guidelines for Contractors
A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
2.10. First phase to clear factor 1.3
2.11 Transient Recovery Voltages TRVs To IEC 62271-100
2.12. Rated capacitive breaking current To IEC 62271-100
Rated line charging breaking current A
Rated cable charging breaking current A
Rated Single/Back to Back Capacitor bank breaking current
A
2.13. Rated small inductive/reactor breaking currents of: To IEC 62271-110
- small inductive A
- reactor A
2.14. Maximum overvoltage factor on any switching duty pu 2.3
2.15. Maximum overvoltage factor when interrupting rated line/cable/capacitor bank charging currents
pu 2.3
2.16. Maximum overvoltage factor when switching small inductive/reactor currents
pu 2.3
2.17. Maximum total break time (trip initiation to final arc extinction)
ms 60
2.18. Opening time (trip initiation to contact separation)
- Without current ms
Section VI – Requirements Page 6 of 677Environmental Guidelines for Contractors
A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
- With 100% rated breaking current ms
2.19. Maximum time interval between opening of first and last phase of three phase circuit breakers
ms 3
2.20. Maximum time interval between opening of interrupters of one phase
- -
2.21. Closing time from energisation of close coil to latching of circuit breaker in fully closed position
ms
2.22. Making time (energisation of close coil to contact touch)
- Without current ms
- 100% making current ms
2.23. Maximum time interval between closure of first and last phase of three phase circuit breaker
ms 3.3
2.24. Maximum time interval between closure of interrupters of one phase
- -
2.25. Minimum time from extinction of main arc to contact make during auto-reclosing duty
ms
2.26. Mechanical life of circuit breaker and mechanism in No. of operations
10,000
2.27. Electrical contact life in number of operations at:
Section VI – Requirements Page 7 of 677Environmental Guidelines for Contractors
A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
- Rated current - 4000 A
- Fault current - 40kA 15 to 20
- Cumulative ampere rating
2.28. Number of current interrupting break units in series per phase
Two
2.29. Type of operating mechanism Motor charged spring operated
2.30. Type of power device (motor charged)
- For closing Spring or hydraulic
- For opening Spring or hydraulic
2.31. Hand operating facility Yes
2.32. Manual spring release (suitably positioned to avoid accidental operation)
Yes
2.33. Mechanical on/off indicator Yes
2.34. Mechanical spring charge / discharge indication Yes
2.35. Charging time S
2.36. Number of trip coils per phase 2
2.37. Number of close coils per phase 1
Section VI – Requirements Page 8 of 677Environmental Guidelines for Contractors
A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
2.38. Nominal control and operating voltage V 110 DC
2.39. Nominal heater voltage V 240 AC
2.40. Rated power of trip coil W
2.41. Rated power of close coil W
2.42. Rated motor power W
2.43. Total load of heaters for circuit breaker W
2.44. Mass of circuit breaker complete (three pole) kg
2.45. Mass of single phase circuit breaker Kg -
2.46 Emergency Trip Facility Yes
3. ISOLATORS
3.1. Manufacturer & Place of Manufacturing
3.2. Type designation
Section VI – Requirements Page 9 of 677Environmental Guidelines for Contractors
A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
3.3. Type of operating mechanism Motor
3.4. Standards IEC 62271-102,
IEC 62271-1
3.5. Maximum capacitive current that can be interrupted by the isolator
A
3.6. Total time from initiation of opening operation to isolator in fully open position
S
3.7 Time from contact separation to extinct of capacitive arc
S
3.8 Total time from initiation of opening operation to time when isolator gap can withstand phase voltage
S
3.9 Hand operating facility Yes
3.10 Locking arrangement in on/off position Yes
3.11 Nominal control and operating voltage V 110 DC
3.12 Automatic isolation of control supplies when lock off
Yes
3.13. Accessibility to operating mechanism from ground level
Yes
3.14. Nominal heater voltage V 240 AC
3.15. Rated power of operation coil W
Section VI – Requirements Page 10 of 677Environmental Guidelines for Contractors
A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
3.16. Rated motor power W
3.17. Total load of heaters for isolator W
3.18. Total mass of three phase isolator complete kg
3.19 Mass of single phase isolator kg
3.20. Contact type
3.21. Type of interlocking
4. EARTHING SWITCH
4.1. Manufacturer & place of manufacturing
4.2. Type designation
4.3. Type of operating mechanism Motor
4.4. Standards IEC 62271-102, 62271-1
4.5. Hand operating facility Yes
4.6. Locking arrangement in on/off position Yes
Section VI – Requirements Page 11 of 677Environmental Guidelines for Contractors
A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
4.7. Nominal control and operating voltage V 110 DC
4.8. Automatic isolation of control supplies when lock off
Yes
4.9. Accessibility to operating mechanism from ground level
Yes
4.10. Nominal heater voltage V 240 AC
4.11. Total load of heaters for earthing switch W
4.22. Total mass of earthing switch complete kg
5. CURRENT TRANSFORMER
5.1. Manufacturer & Place of manufacturing
5.2. Type Post
5.3. Standards IEC 62271-1, 60044-1
5.4. Rated continuous thermal current at 40oC Rated extended primary current
5.5. Current transformers Refer to Tender Drawings
Section VI – Requirements Page 12 of 677Environmental Guidelines for Contractors
A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
- Number of cores
- Rated extended primary current 120%
- Ratio (TR – turns ratio)
I core A
II core A
III core A
IV core A
- Class
I core
II core
III core
IV core
- Knee point voltage (Ek)
I core V
II core V
III core V
IV core V
- Exciting current (IE) at Ek
I core mA
II core mA
III core mA
IV core mA
- Rated output (burden to be 25-100% rated burden) I core VA
II core VA
III core VA
Section VI – Requirements Page 13 of 677Environmental Guidelines for Contractors
A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
IV core VA
Total mass of single phase current transformer complete
kg
6. CAPACITIVE VOLTAGE TRANSFORMERS
6.1. Manufacturer & Place of manufacturing
6.2. Type Capacitive
6.3. Standards IEC 60044-5
6.4. Maximum permissible partial discharge level
Um
pC 10
6.5. Maximum permissible partial discharge level
1.2Um /3
pC 5
6.6. Method of suppressing ferroresonance phenomena
6.7. Voltage transformer Refer to Tender Drawings
- Number of secondaries
- Rated transformation ratio kV
Section VI – Requirements Page 14 of 677Environmental Guidelines for Contractors
A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
- Rated accuracy class
I secondary
II secondary
- Rated output (burden to be 25-100% rated burden) I secondary VA
II secondary VA
- Mass of single phase voltage transformer kg
7 METERING INSTRUMENT TRANSFORMERS
7.1 Manufacturer
7.2 Type designation Post
7.3 Standards IEC 60044-3, 61869
7.4 Rated continuous thermal current at 400C Rated extended primary current
7.5 Current transformers
- Number of cores
- Rated extended primary current 120%
Section VI – Requirements Page 15 of 677Environmental Guidelines for Contractors
A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
- Ratio (TR – turns ratio)
• I core
• II core
- Class
• I core
• II core
- Knee point voltage (Ek)
• I core
• II core
- Exciting current (IE) at Ek
• I core mA
• II core mA
- Rated output (burden to be 25- 100% rated burden)
• I core VA
• II core VA
Total mass of single phase current transformer complete
V
V
mA
mA
VA
VA
Refer to Tender Drawings
Section VI – Requirements Page 16 of 677Environmental Guidelines for Contractors
A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
kg
7.6 Voltage transformers
- Number of secondaries
- Maximum permissible partial discharge level Um
- Maximum permissible partial discharge level 1.2Um/√3
- Method of suppressing Ferro resonance
- Ratio (TR – turns ratio)
- Voltage factor, PU – BS EN 61869
- Rated accuracy class
• I secondary
• II secondary
- Rated output (burden to be 25-100% rated burden)
• I secondary
• II secondary
- Mass of single phase voltage transformer
pC
pC
Refer to Tender Drawings
10
5
1.5PU, 30secs
Section VI – Requirements Page 17 of 677Environmental Guidelines for Contractors
A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
VA
VA
kg
8. BUSBARS AND CONNECTIONS
8.1 Manufacturer
8.2 Type (flexible or tubular)
8.3 Material
8.4 Short-circuit current rating / duration KA/s
8.5 Normal current rating
- at 40oC- at 50oC
A
A
8.6 Maximum continuous current rating A
8.7 Flexible conductors
- stranding- nominal cross-sectional area- outer diameter- no. of conductors per bundle- spacing between conductors
mm2
mm
mm
Section VI – Requirements Page 18 of 677Environmental Guidelines for Contractors
A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
8.8 Tubular conductors
- nominal cross-sectional area- outer diameter- inner diameter
mm2
mm
mm
8.9 Maximum stress at surface of flexible conductor kV/mm
8.10 Radio influence voltage level measured at 1.1 times Us/3 at 1 MHz
µV
9 POST TYPE INSULATORS
9.1 Manufacturer
9.2 Type designation
9.3 Insulator material
9.4 Number of units in complete post insulator
9.5 Length of each unit mm
9.6 Mass of complete post insulator kg
9.7 Maximum cantilever working load (complete post insulator)
N
Section VI – Requirements Page 19 of 677Environmental Guidelines for Contractors
A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
9.8 Minimum cantilever breaking load, upright (complete post insulator)
N
9.9 Power frequency withstand voltage dry: wet kV
9.10 Basic insulation level kVp
9.11 Minimum dry/wet switching surge withstand level kVp
9.12 Radio influence voltage level measured at 1.1 times Us/3 at 1 MHz
µv
10 TENSION AND SUSPENSION INSULATORS
10.1 Manufacturer
10.2 Type designation
10.3 Insulator material
10.4 Number of units in string mm
10.5 Greatest diameter of units mm
10.6 Distance between centres of units mm
Section VI – Requirements Page 20 of 677Environmental Guidelines for Contractors
A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
10.7 Length of string, overall mm
10.8 Mass of string complete with all fittings kg
10.9 Maximum working load N
10.10 Power frequency withstand voltage of complete string
kV
10.11 Basic insulation level of complete string kVp
10.12 Minimum wet switching surge withstand level of complete string
kVp
10.13 Radio influence voltage measured at 1.1 times Us/3 at 1 MHz
µv
11. 400KV SURGE ARRESTERS
11.1 Type MOA
11.2
11.3
11.4
11.5
11.6
11.7
11.8
Standard
Rated/system voltage
Maximum overvoltage factor on the system due to any switching duty
Rated system frequency
Condition of system neutral
Nominal Discharge current
Energy capability as per IEC 60099-4
Rated Voltage – MOA
kV
pu
Hz
kAcrest
kJ/kV
kV
IEC 60099-4
420/400
2.3
50
Solid
20
360
Section VI – Requirements Page 21 of 677Environmental Guidelines for Contractors
A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
11.9
11.10
11.11
11.12
11.13
Long duration discharge class as per IEC 99-1
Maximum Continuous Operating Voltage (COV)
TOV capability for1sec10sec
Maximum residual voltage with current waveSwitching Surges – 1kA/2kA8/20 μs – 5kA8/20 μs – 20Ka
Discharge current withstand strengthHigh current 4/10 μsLow current 2000 μs
Class
kV
kVkV
kVkVkV
KAp
KAp
4
260 min
To IEC 60099-4To IEC 60099-4To IEC 60099-4
To IEC 60099-4To IEC 60099-4
12..
12.1
12.2
Manufacturer quality system in accordance withISO 9000Date of issue
Validity
Yes
Latest
Valid Certificates - Yes13. Type test certificate to be issued by independent
laboratory or independently witnessed type test certificate to be submitted
Yes
Note:- Technical parameters stated above to be confirmed following nominated Contractor’s insulation co-ordination study.
Section VI – Requirements Page 22 of 677Environmental Guidelines for Contractors
B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
1. GENERAL
1.1. Standards IEC IEC 62271-100, 62271-102, 62271-1,
62155, 60044-1, 60044-5, 60383,
60815
1.2. Rated voltage kV 245
1.3. System Voltage kV 220
1.4. Rated frequency Hz 50
1.5. Rated lightning impulse withstand voltage (at altitude <1000m)
- Phase to earth KVp 1050
- Across the isolating distance kVp 1200
1.6. Rated power frequency withstand voltage (at altitude <1000m)
- Phase to earth kV 460
- Across the isolating distance kV 530
1.7. Rated short-time withstand current (1 s) kA 31.5
1.8. Rated peak withstand current kA 80
1.9. Rated Current
- at 40 oC A 2000
Section VI – Requirements Page 23 of 677Environmental Guidelines for Contractors
B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
- at 50 oC (Contractor to confirm by calculation) A
1.10. Material of HV conductor
1.11. Material of contacts
1.12. Minimum factors of safety for switchgear
- Busbars or other connections based on elastic limit
2.5
- Complete insulators based on electro-mechanical test
2.5
- Insulator metal fittings based on elastic limit 2.5
- Steel structures based on elastic limit of tension members and on cripping loads of compression members
2.5
- Foundations for structures against overturning or uprooting under maximum simultaneous working loadings
2.5
1.13. Creepage distance (based on Um) mm/kV 31
1.14. Seismic factor
2. CIRCUIT BREAKER
2.1. Manufacturer & Place of manufacturing
2.2. Type designation
2.3. Type SF6 single pole
2.4. Standards 62271-1, IEC 62271-100, 62271-101,
62271-110, 60376, 60480
Section VI – Requirements Page 24 of 677Environmental Guidelines for Contractors
B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
2.5. Rated operating sequence O -0.3 sec- CO -3 min - CO
2.6. Auto reclosing O -0.3 sec- CO -3 min - CO
2.7. Rated making current KAp 80
2.8 Rated breaking current kA 31.5
Rated breaking current (asymmetrical) KA To IEC 62271-100
- %dc %dc
2.9. Rated breaking current under out-of-phase conditions
kA 10
2.10. First phase to clear factor 1.5
2.11 Transient Recovery Voltages TRVs To IEC 62271-100
2.12. Rated capacitive breaking current To IEC 62271-100
Rated line charging breaking current A
Rated cable charging breaking current A
Rated Single/Back to Back Capacitor bank breaking current
A
2.13. Rated small inductive/reactor breaking currents of: To IEC 62271-110
- small inductive A
- reactor A
Section VI – Requirements Page 25 of 677Environmental Guidelines for Contractors
B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
2.14. Maximum overvoltage factor on any switching duty pu 2.3
2.15. Maximum overvoltage factor when interrupting rated line/cable/capacitor bank charging currents
pu 2.3
2.16. Maximum overvoltage factor when switching small inductive/reactor currents
pu 2.3
2.17. Maximum total break time (trip initiation to final arc extinction)
ms 60
2.18. Opening time (trip initiation to contact separation)
- Without current ms
- With 100% rated breaking current ms
2.19. Maximum time interval between opening of first and last phase of three phase circuit breakers
ms 3
2.20. Maximum time interval between opening of interrupters of one phase
- - -
2.21. Closing time from energisation of close coil to latching of circuit breaker in fully closed position
ms
2.22. Making time (energisation of close coil to contact touch)
- Without current ms
- 100% making current ms
Section VI – Requirements Page 26 of 677Environmental Guidelines for Contractors
B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
2.23. Maximum time interval between closure of first and last phase of three phase circuit breaker
ms 3.3
2.24. Maximum time interval between closure of interrupters of one phase
- - -
2.25. Minimum time from extinction of main arc to contact make during auto-reclosing duty
ms
2.26. Mechanical life of circuit breaker and mechanism in No. of operations
10,000
2.27. Electrical contact life in number of operations at:
- Rated current -2000 A
- Fault current - 31.5 kA 15 to 20
- Cumulative ampere rating
2.28. Number of current interrupting break units in series per phase
One
2.29. Type of operating mechanism Motor charged spring operated
2.30. Type of power device (motor charged)
- For closing Spring or hydraulic
- For opening Spring or hydraulic
2.31. Hand operating facility Yes
2.32. Manual spring release Yes
Section VI – Requirements Page 27 of 677Environmental Guidelines for Contractors
B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
2.33. Mechanical on/off indicator Yes
2.34. Mechanical spring charge / discharge indication Yes
2.35. Charging time s
2.36. Number of trip coils per phase 2
2.37. Number of close coils per phase 1
2.38. Nominal control and operating voltage V 110 DC
2.39. Nominal heater voltage V 240 AC
2.40. Rated power of trip coil W
2.41. Rated power of close coil W
2.42. Rated motor power W
2.43. Total load of heaters for circuit breaker W
2.44. Mass of circuit breaker complete (three pole) kg
Section VI – Requirements Page 28 of 677Environmental Guidelines for Contractors
B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
2.45. Mass of single phase circuit breaker - - -
2.46 Emergency Trip Facility Yes
3. ISOLATORS
3.1. Manufacturer & Place of Manufacturing
3.2. Type designation
3.3. Type of operating mechanism Motor
3.4. Standards IEC 62271-102,
IEC 62271-1
3.5. Maximum capacitive current that can be interrupted by the isolator
A
3.6. Total time from initiation of opening operation to isolator in fully open position
s
3.7 Time from contact separation to extinct of capacitive arc
s
3.8 Total time from initiation of opening operation to time when isolator gap can withstand phase voltage
s
Section VI – Requirements Page 29 of 677Environmental Guidelines for Contractors
B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
3.9 Hand operating facility Yes
3.10 Locking arrangement in on/off position Yes
3.11 Nominal control and operating voltage V 110 DC
3.12 Automatic isolation of control supplies when lock off
Yes
3.13. Accessibility to operating mechanism from ground level
Yes
3.14. Nominal heater voltage V 240 AC
3.15. Rated power of operation coil W
3.16. Rated motor power W
3.17. Total load of heaters for isolator W
3.18. Total mass of three phase isolator complete kg
3.19 Mass of single phase isolator kg
3.20. Contact type
3.21. Type of interlocking
Section VI – Requirements Page 30 of 677Environmental Guidelines for Contractors
B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
4. EARTHING SWITCH
4.1. Manufacturer & place of manufacturing
4.2. Type designation
4.3. Type of operating mechanism Motor
4.4. Standards IEC 62271-102, 62271-1
4.5. Hand operating facility Yes
4.6. Locking arrangement in on/off position Yes
4.7. Nominal control and operating voltage V 110 DC
4.8. Automatic isolation of control supplies when lock off
Yes
4.9. Accessibility to operating mechanism from ground level
Yes
4.10. Nominal heater voltage V 240 AC
4.11. Total load of heaters for earthing switch W
Section VI – Requirements Page 31 of 677Environmental Guidelines for Contractors
B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
4.22. Total mass of earthing switch complete kg
5. CURRENT TRANSFORMER
5.1. Manufacturer & Place of manufacturing
5.2. Type Post
5.3. Standards IEC 62271-1, 60044-1
5.4. Rated continuous thermal current at 40°C Rated extended primary current
Note: All Cl PX CTs shall be ISN 1.2 A
5.5. Current transformers Refer to Tender Drawings
- Number of cores
- Rated extended primary current 120%
- Ratio (TR – turns ratio)
I core A
II core A
III core A
IV core A
- Class
I core
Section VI – Requirements Page 32 of 677Environmental Guidelines for Contractors
B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
II core
III core
IV core
- Knee point voltage (Ek)
I core V
II core V
III core V
IV core V
- Exciting current (IE) at Ek
I core mA
II core mA
III core mA
IV core mA
- Rated output (burden to be 25-100% rated burden) I core VA
II core VA
III core VA
IV core VA
Total mass of single phase current transformer complete
kg
6. CAPACITIVE VOLTAGE TRANSFORMERS
6.1. Manufacturer & Place of manufacturing
6.2. Type Capacitive
Section VI – Requirements Page 33 of 677Environmental Guidelines for Contractors
B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
6.3. Standards IEC 60044-5
6.4. Maximum permissible partial discharge level
Um
pC 10
6.5. Maximum permissible partial discharge level
1.2Um /3
pC 5
6.6. Method of suppressing ferroresonance phenomena
6.7. Voltage transformer Refer to Tender Drawings
- Number of secondaries
- Rated transformation ratio kV
- Rated accuracy class
I secondary
II secondary
- Rated output (burden to be 25-100% rated burden) I secondary VA
II secondary VA
- Mass of single phase voltage transformer kg
7 METERING INSTRUMENT TRANSFORMERS
Section VI – Requirements Page 34 of 677Environmental Guidelines for Contractors
B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
7.1 Manufacturer
7.2 Type designation Post
7.3 Standards IEC 60044-3, 61869
7.4 Rated continuous thermal current at 400C Rated extended primary current
7.5 Current transformers
- Number of cores
- Rated extended primary current
- Ratio (TR – turns ratio)
• I core
• II core
- Class
• I core
• II core
- Knee point voltage (Ek)
• I core
• II core
- Exciting current (IE) at EkV
120%
Refer to Tender Drawings
Section VI – Requirements Page 35 of 677Environmental Guidelines for Contractors
B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
• I core mA
• II core mA
- Rated output (burden to be 25- 100% rated burden)
• I core VA
• II core VA
Total mass of single phase current transformer complete
V
mA
mA
VA
VA
kg
7.6 Voltage transformers
- Number of secondaries
- Maximum permissible partial discharge level Um
- Maximum permissible partial discharge level 1.2Um/√3
- Method of suppressing Ferro resonance
- Ratio (TR – turns ratio)
pC
pC
Refer to Tender Drawings
10
5
Section VI – Requirements Page 36 of 677Environmental Guidelines for Contractors
B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
- Voltage factor, PU – BS EN 61869
- Rated accuracy class
• I secondary
• II secondary
- Rated output (burden to be 25-100% rated burden)
• I secondary
• II secondary
- Mass of single phase voltage transformer
VA
VA
kg
1.5PU, 30secs
7.10 Radio influence voltage level measured at 1.1 times Us/3 at 1 MHz
µV
8. BUSBARS AND CONNECTIONS
8.1 Manufacturer
8.2 Type (flexible or tubular)
Section VI – Requirements Page 37 of 677Environmental Guidelines for Contractors
B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
8.3 Material
8.4 Short-circuit current rating / duration KA/s
8.5 Normal current rating
- at 40oC- at 50oC
A
A
8.6 Maximum continuous current rating A
8.7 Flexible conductors
- stranding- nominal cross-sectional area- outer diameter- no. of conductors per bundle- spacing between conductors
mm2
mm
mm
8.8 Tubular conductors
- nominal cross-sectional area- outer diameter- inner diameter
mm2
mm
mm
8.9 Maximum stress at surface of flexible conductor kV/mm
8.10 Radio influence voltage level measured at 1.1 times Us/3 at 1 MHz
µV
Section VI – Requirements Page 38 of 677Environmental Guidelines for Contractors
B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
9 POST TYPE INSULATORS
9.1 Manufacturer
9.2 Type designation
9.3 Insulator material
9.4 Number of units in complete post insulator
9.5 Length of each unit mm
9.6 Mass of complete post insulator kg
9.7 Maximum cantilever working load (complete post insulator)
N
9.8 Minimum cantilever breaking load, upright (complete post insulator)
N
9.9 Power frequency withstand voltage dry: wet kV
9.10 Basic insulation level kVp
9.11 Minimum dry/wet switching surge withstand level kVp
9.12 Radio influence voltage level measured at 1.1 µv
Section VI – Requirements Page 39 of 677Environmental Guidelines for Contractors
B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
times Us/3 at 1 MHz
10 TENSION AND SUSPENSION INSULATORS
10.1 Manufacturer
10.2 Type designation
10.3 Insulator material
10.4 Number of units in string mm
10.5 Greatest diameter of units mm
10.6 Distance between centres of units mm
10.7 Length of string, overall mm
10.8 Mass of string complete with all fittings kg
10.9 Maximum working load N
10.10 Power frequency withstand voltage of complete string
kV
Section VI – Requirements Page 40 of 677Environmental Guidelines for Contractors
B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
10.11 Basic insulation level of complete string kVp
10.12 Minimum wet switching surge withstand level of complete string
kVp
10.13 Radio influence voltage measured at 1.1 times Us/3 at 1 MHz
µv
11. 220KV SURGE ARRESTERS
11.1 Type MOA
11.2 Standard IEC 6099-4
11.3 Rated/system voltage kV 245/220
- Maximum overvoltage factor on the system due to any switching duty
pu 2.3
11.4 Rated system frequency Hz 50
11.5 Condition of system neutral Solid
11.6 Nominal Discharge current kAcrest 10
Section VI – Requirements Page 41 of 677Environmental Guidelines for Contractors
B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA
Required Offered
11.7 Energy capability as per IEC 60099-4 kJ/kV
11.8 Rated Voltage – MOA kV
11.9 Long duration discharge class as per IEC 6099-4 Class 3
11.10 Maximum Continuous Operating Voltage (COV) kV To IEC 60099-4
11.11 TOV capability for
- 1sec- 10sec
kV
kV
11.12 Maximum residual voltage with current wave
- Switching Surges – 1kA/2kA- 8/20 μs – 5kA- 8/20 μs – 20Ka
kV
kV
kV
To IEC 60099-4
To IEC 60099-4
To IEC 60099-4
11.13 Discharge current withstand strength
- High current 4/10 μsLow current 2000 μs
KAp
KAp
To IEC 60099-4
To IEC 60099-4
12. Type test certificate to be issued by independent laboratory or independently witnessed type test certificate to be submitted
Yes
Section VI – Requirements Page 42 of 677Environmental Guidelines for Contractors
Section VI – Requirements Page 43 of 677Environmental Guidelines for Contractors
C. EARTHING AND LIGHTNING PROTECTION UNIT DATA
Required Offered
1. EARTHING SYSTEM
1.1. Manufacturers
1.2. Standard Applied
The following standards shall apply to the earthing installations and to the accessories:
Guide for safety in A.C. substation grounding Earthing system in A.C. installation for rated voltages
above 1000 VIEEE80 & 81
VDE 0141
1.3. Physical Properties of Copper
The most important physical properties of copper used for the earthing conductors:
Density kg/dm3 8.89
Electrical resistivity at 20C mm2/m 0.0176
Melting point C 1083
Current density at which the conductor temperature rises from 50C to 300C in a time of 1 s if all heat is retained in conductor
A/mm2 190
1.4. Physical Properties of Lead-Sheathed Copper
The most important physical properties of lead-sheathed copper used for the earth electrodes:
Section VI – Requirements Page 44 of 677Environmental Guidelines for Contractors
C. EARTHING AND LIGHTNING PROTECTION UNIT DATA
Required Offered
Thickness of lead sheath mm 2.0
Electrical resistivity of copper at 20C mm2/m 0.0176
Copper melting point C 1083
Lead melting point C 327
Current density at which the conductor temperature rises from 40C to 150C in a time of 1 s if all heat is retained in conductor
A/mm2 140
1.5. Earthing Conductors
1.5.1. Stranded copper conductors
The following stranded copper conductor will be used as earthing conductors:
Cross-section area mm2
Number of wires No.
Diameter of each wire mm
Conductor diameter mm
Density kg/m
Cross-section area mm2
Number of wires No.
Diameter of each wire mm
Conductor diameter mm
Density kg/m
Section VI – Requirements Page 45 of 677Environmental Guidelines for Contractors
C. EARTHING AND LIGHTNING PROTECTION UNIT DATA
Required Offered
Cross-section area mm
Number of wires pcs
Diameter of each wire mm
Conductor diameter mm
Density kg/m
1.5.2. Copper Flat Bars
The following copper flat bars will be used as earthing conductors:
Cross section area mm2
Dimensions mm x mm
Density kg/m
Cross section area mm2
Dimensions mm x mm
Density kg/m
Cross section area mm2
Dimensions mm x mm
Density kg/m
1.5.3. Copper Cables
The following PVC single-core copper cables will be used as earthing conductors:
Cross-section area mm2
Section VI – Requirements Page 46 of 677Environmental Guidelines for Contractors
C. EARTHING AND LIGHTNING PROTECTION UNIT DATA
Required Offered
Cross-section area mm2
Cross-section area mm2
1.6. Earth Electrodes
1.6.1. Lead-sheathed stranded copper conductors
The following lead-sheathed stranded copper conductor will be used as earth electrodes:
Thickness of lead sheath mm
Copper cross-section area mm2
Number of wires pcs
Diameter of each wire mm
Conductor diameter mm
Density kg/m
Thickness of lead sheath mm
Copper cross-section area mm2
Number of wires pcs
Diameter of each wire mm
Conductor diameter mm
Density kg/m
Thickness of lead sheath mm
Copper cross-section area mm2
Diameter of each wire mm
Section VI – Requirements Page 47 of 677Environmental Guidelines for Contractors
C. EARTHING AND LIGHTNING PROTECTION UNIT DATA
Required Offered
Conductor diameter mm
Density kg/m
1.6.2. Earth rod
Manufacturer
Length m
Diameter mm
Material (copper, stainless steel)
1.6.3. Stainless steel electrodes
The following steel flat bars will be used as earth electrodes:
Cross-section area dimensions Density
mm2
mm x mm
kg/m
1.7. Connections
Mode of Connection in the Earthing Systems:
Between earthing conductors and earth electrodes Crossing of earth electrodes
Brazed
Compression
2. LIGHTNING PROTECTION
2.1. Manufacturers
2.2. Standard Applied:
Section VI – Requirements Page 48 of 677Environmental Guidelines for Contractors
C. EARTHING AND LIGHTNING PROTECTION UNIT DATA
Required Offered
Protection of structures against lightning IEC 62305
Manufacturer
Cross-section area mm2
Thickness of lead-sheath mm
2.3. Supports
Conductor supports of the lightning protection system
Type
2.4. Earth rod
Manufacturer
Length m
Diameter mm
Material (copper, stainless steel)
3. Type test certificate (to be issued by independent laboratory or independently witnessed type test certificate available)
yes
Section VI – Requirements Page 49 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
LINE DIFFERENTIAL PROTECTION AND BACK-UP DISTANCE (87/21L)
Manufacturer
Type reference
Relay design (microprocessor based, numerical) Numerical
Auxiliary voltage range (Vn = 110Vdc) Vdc 88150
Input frequency range (50Hz nominal) Hz 47.552.5
Differential protection requirements
Phase segregated protection Yes
Ratio and Vector correction for CTs Yes
Adjustable biased differential protection characteristic Yes
Sensitivity:
- For phase faults
- For earth faults
Operating time ms <30
Distance protection requirements
3 zone ph-ph & ph-E Yes
Phase fault & Earth fault characteristic shapes (Mho, Quad) Quad
Operating time <30ms
SOTF Yes
Power swing blocking (depending on relaying point in the power system)
Yes
Voltage transformer supervision Yes
Time delays for all zones Yes
Zone enable/disable for all zones Yes
Other requirements
DEF comparison function Yes
Directional protection 67/67N
Overcurrent/Earth fault 50/51/50N/51N
Stub protection 50STB Yes
Section VI – Requirements Page 50 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Circuit breaker failure. 50BF- (application dependent)) No
Thermal overload, 49 TBA
Auto Reclose 79 (application dependent) Yes
Under/Over Voltage
Integral intertrip send and receive, with external input interface Yes
Event recording function Yes
Disturbance recording function Yes
Fault locator function Yes
Integral LCD operator interface for local interrogation Yes
Programmable scheme logic Yes
PC based configuration software for HMI, settings, logic and data recorder.
Yes
1.1 Programme name
1.2 Included / Separate
Tripping contacts rating
Carry continuous 5A
Make 30A maximum for 0.2s
Break dc 50W resistive25W
inductive(L/R40ms)
Yes
Self checking facility Yes
Integral intertrip send and receive, with external input interface Yes
Communications
Protection
Direct optical fibre TBA
1550nm single mode distance (km)
Section VI – Requirements Page 51 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
1300nm single mode distance (km)
820nm multi-mode distance (km)
Others supported TBA
G703.1
X21
Control
Communication ports (Front/rear etc)
Physical links (RS485/Fibre optic)
Protocols supported
IEC 60870-5-103 Yes
Others (please state)
Type Tests
Atmospheric Environment
Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2
Yes
Relative Humidity
Operation at 93% Yes
Tested to IEC 60068-2-3 with severity class 56 days Yes
Enclosure
IEC 60529 IP50 Yes
Mechanical Environment
Vibration IEC 60255-21-1 Yes
Shock and bump IEC 60255-21-2 Yes
Seismic IEC 60255-21-3 Yes
Insulation
Rated insulation
1000V high impedance protection CT inputs
250V for other circuits Yes
1000V open contact withstand Yes
Dielectric Tests
IEC 60255-5 – Series C of table 1 Yes
Impulse voltage
IEC 60255-5 test voltage 5kV Yes
Electromagnetic compatibility
Section VI – Requirements Page 52 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
1MHz Burst disturbance test, IEC 60255-22-1 severity class III
Yes
Electrostatic Discharge
IEC 60255-22-2 severity class III Yes
Radiated Electromagnetic Field DisturbanceIEC 60255-22-3 severity class III
Test method A, 27MHz through 500MHzYes
Electromagnetic Emissions
IEC 60255-25 Yes
Fast Transient DisturbanceIEC 60255-22-4 severity level IV
Yes
Type test certificate provided Yes
1.3DISTANCE (21)
Manufacturer
Type reference
Relay design (microprocessor based, numerical) Numerical
Auxiliary voltage range (Vn = 110Vdc) Vdc 88150
Input frequency range (50Hz nominal) Hz 47.552.5
Distance protection requirements
Minimum 3 zone ph-ph & ph-E Yes
Phase fault & Earth fault characteristic shapes (Mho, Quad)
Nominal Z1 Operating time <30ms
SOTF Yes
Power swing blocking Yes
Voltage transformer supervision Yes
Time delays for all zones Yes
Zone enable/disable for all zones Yes
Other supported Functions
DEF comparison function Yes
Directional protection 67/67N
Section VI – Requirements Page 53 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Overcurrent/Earth fault 50/51/50N/51N
Stub protection 50STB Yes
Circuit breaker failure. 50BF- (application dependent))
Thermal overload, 49 TBA
Auto Reclose 79 (application dependent)
Under/Over Voltage
Integral intertrip send and receive, with external input interface Yes
Event recording function Yes
Disturbance recording function Yes
Fault locator function Yes
Integral LCD operator interface for local interrogation Yes
Programmable logic Yes
PC based configuration software for HMI, settings, logic and data recorder.
Yes
2.1 Programme name
2.2 Included / Separate
Tripping contacts rating details
Carry continuous
Make
Break dc
A
A / time
W rest.
W & L/R
Self checking facility Yes
Section VI – Requirements Page 54 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Communications
Protection
Direct optical fibre TBA
2.3 1550nm single mode distance (km)
2.4 1300nm single mode distance (km)
2.5 820nm multi-mode distance (km)
2.6 Others supported TBA
2.7 G703.1
2.8 X21
Control
Communication ports (Front/rear etc)
Physical links (RS485/Fibre optic)
Protocols supported
IEC 61850 Yes
Others (please state)
Type Tests
Atmospheric Environment
Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2
Yes
Relative Humidity
Operation at 93% Yes
Tested to IEC 60068-2-3 with severity class 56 days Yes
Enclosure
IEC 60529 IP50 Yes
Mechanical Environment
Vibration IEC 60255-21-1 Yes
Shock and bump IEC 60255-21-2 Yes
Seismic IEC 60255-21-3 Yes
Insulation
Section VI – Requirements Page 55 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Rated insulation
1000V high impedance protection CT inputs
250V for other circuits Yes
1000V open contact withstand Yes
Dielectric Tests
IEC 60255-5 – Series C of table 1 Yes
Impulse voltage
IEC 60255-5 test voltage 5kV Yes
Electromagnetic compatibility1MHz Burst disturbance test,
IEC 60255-22-1 severity class IIIYes
Electrostatic Discharge
IEC 60255-22-2 severity class III Yes
Radiated Electromagnetic Field DisturbanceIEC 60255-22-3 severity class III
Test method A, 27MHz through 500MHzYes
Electromagnetic Emissions
IEC 60255-25 Yes
Fast Transient DisturbanceIEC 60255-22-4 severity level IV
Yes
Type test certificate provided Yes
2.9
MAIN TRANSFORMER / REACTOR BIASED DIFFERENTIAL PROTECTION 87 including HV and LV REF
Manufacturer
Type reference
Relay design (microprocessor based, numerical) numerical
Auxiliary voltage range (Vn = 110Vdc) Vdc 88150
Input frequency range (50Hz nominal) Hz 47.552.5
Section VI – Requirements Page 56 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Biased Differential function
Operation time at 5 times setting ms <25
Adjustable bias characteristics Yes
Differential current stage Id >> Yes
Magnetisation inrush restraint Yes
5th” Harmonic restraint Yes
CT ratio and vector group compensation Yes
Restricted earth fault function
HV REF Yes
LV REF Yes
Principle of REF operation
High impedance/Low impedance Low
Operation time at 5 times settings ms <30
Other requirements
Phase overcurrent function 50/51 (requirement depending on application)
No
Earth fault protection 51N (requirement depending on application) No
Integral LCD operator interface for local interrogation Yes
Programmable logic Yes
PC based configuration software for HMI, settings, logic and data recorder.
3.3 Programme name
Section VI – Requirements Page 57 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
3.4 Included / Separate
Tripping contacts rating details
Carry continuous
Make
Break dc
A
A / time
W rest.
W & L/R
Event recording function Yes
Disturbance recording function Yes
Fault recording function Yes
Self monitoring and alarm facility
Communications
Control
Communication ports (Front/rear etc)
Physical links (RS485/Fibre optic)
Protocols supported
IEC 61850 Yes
Others (please state)
Type Tests
Atmospheric Environment
Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2
Yes
Relative Humidity
Section VI – Requirements Page 58 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Operation at 93% Yes
Tested to IEC 60068-2-3 with severity class 56 days Yes
Enclosure
IEC 60529 IP50 Yes
Mechanical Environment
Vibration IEC 60255-21-1 Yes
Shock and bump IEC 60255-21-2 Yes
Seismic IEC 60255-21-3 Yes
Insulation
Rated insulation
1000V high impedance protection CT inputs
250V for other circuits Yes
1000V open contact withstand Yes
Dielectric Tests
IEC 60255-5 – Series C of table 1 Yes
Impulse voltage
IEC 60255-5 test voltage 5kV Yes
Electromagnetic compatibility
1MHz Burst disturbance test, IEC 60255-22-1 severity class III
Yes
Electrostatic Discharge
IEC 60255-22-2 severity class III Yes
Radiated Electromagnetic Field DisturbanceIEC 60255-22-3 severity class III
Test method A, 27MHz through 500MHzYes
Electromagnetic Emissions
IEC 60255-25 Yes
Section VI – Requirements Page 59 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Fast Transient DisturbanceIEC 60255-22-4 severity level IV
Yes
Type test certificate provided Yes
HV CONNECTIONS DIFFERENTIAL PROTECTION 87HC
Manufacturer
Type reference
Relay design (microprocessor based, numerical) numerical
Auxiliary voltage range (Vn = 110Vdc) Vdc 88150
Input frequency range (50Hz nominal) Hz 47.552.5
Principle of operation
High impedance/Low impedance High or Low
Biased Differential function (Low Impedance)
No of separate CT inputs 3
Operation time at 5 times setting ms <25
Adjustable bias characteristics Yes
Differential current stage Id >> Yes
Magnetisation inrush restraint Yes
5th” Harmonic restraint Yes
CT ratio and vector group compensation Yes
Section VI – Requirements Page 60 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Differential function (High Impedance)
minimum fault setting (% of CT rating) % Yes
Operating time at 5 x setting ms <30
Non Linear Resistors (Metrosils) integral Y/N
4.3
Integral LCD operator interface for local interrogation Yes
Programmable logic Yes
PC based configuration software for HMI, settings, logic and data recorder.
4.4 Programme name
4.5 Included / Separate
Tripping contacts rating details
Carry continuous
Make
Break dc
A
A / time
W rest.
W & L/R
Event recording function Yes
Disturbance recording function Yes
Fault recording function Yes
Self monitoring and alarm facility
Communications
Section VI – Requirements Page 61 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Control
Communication ports (Front/rear etc)
Physical links (RS485/Fibre optic)
Protocols supported
IEC 61850 Yes
Others (please state)
Type Tests
Atmospheric Environment
Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2
Yes
Relative Humidity
Operation at 93% Yes
Tested to IEC 60068-2-3 with severity class 56 days Yes
Enclosure
IEC 60529 IP50 Yes
Mechanical Environment
Vibration IEC 60255-21-1 Yes
Shock and bump IEC 60255-21-2 Yes
Seismic IEC 60255-21-3 Yes
Insulation
Rated insulation
1000V high impedance protection CT inputs
Section VI – Requirements Page 62 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
250V for other circuits Yes
1000V open contact withstand Yes
Dielectric Tests
IEC 60255-5 – Series C of table 1 Yes
Impulse voltage
IEC 60255-5 test voltage 5kV Yes
Electromagnetic compatibility
1MHz Burst disturbance test, IEC 60255-22-1 severity class III
Yes
Electrostatic Discharge
IEC 60255-22-2 severity class III Yes
Radiated Electromagnetic Field DisturbanceIEC 60255-22-3 severity class III
Test method A, 27MHz through 500MHzYes
Electromagnetic Emissions
IEC 60255-25 Yes
Fast Transient DisturbanceIEC 60255-22-4 severity level IV
Yes
Type test certificate provided Yes
LOW IMPEDANCE BUSBAR PROTECTION INCLUDING BREAKER FAILURE PROTECTION
Manufacturer
Type reference
Relay design (static, microprocessor-based, numerical) Numerical
Section VI – Requirements Page 63 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Auxiliary voltage range (Vn = 110Vdc) Vdc 88150
Input frequency range (50Hz nominal) Hz 47.552.5
State principle of operation, i.e. low impedance Low Z
Integral check zone feature Yes
Distributed Central and Bay Modules or Integrated (Dist / Int) Either
Maximum number of Bays
CT saturation detector and stabilisation
Integral CT supervision
CT matching functions
Phase segregated protection
Sensitivity
1. Phase faults A sec’y
2. Earth faults A sec’y
Operating time at 5 x fault setting ms 30
Two stage Circuit Breaker Failure
Adjustable current setting Adjustable time delays per stage
Yes
Other requirements
PC based configuration software for HMI, settings, logic and data recorder.
5.1 Programme name
5.2 Included / Separate Yes
Tripping contacts rating details
Section VI – Requirements Page 64 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Carry continuous
Make
Break dc
A
A / time
W rest.
W & L/R
Event recording function Yes
Disturbance recording function Yes
Self monitoring and alarm facility
Communications
Bay to central Module communication f.o.
Integral LCD operator interface for local interrogation Yes
Control
Communication ports (Front/rear etc)
Physical links (RS485/Fibre optic)
Protocols supported
IEC 61850 Yes
Others (please state)
Type Tests
Atmospheric Environment
Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes
Relative Humidity
Operation at 93% Yes
Section VI – Requirements Page 65 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Tested to IEC 60068-2-3 with severity class 56 days Yes
Enclosure
IEC 60529 IP50 Yes
Mechanical Environment
Vibration IEC 60255-21-1 Yes
Shock and bump IEC 60255-21-2 Yes
Seismic IEC 60255-21-3 Yes
Insulation
Rated insulation
1000V high impedance protection CT inputs
250V for other circuits Yes
1000V open contact withstand Yes
Dielectric Tests
IEC 60255-5 – Series C of table 1 Yes
Impulse voltage
IEC 60255-5 test voltage 5kV Yes
Electromagnetic compatibility
1MHz Burst disturbance test, IEC 60255-22-1 severity class III
Yes
Electrostatic Discharge
IEC 60255-22-2 severity class III Yes
Radiated Electromagnetic Field DisturbanceIEC 60255-22-3 severity class III
Test method A, 27MHz through 500MHzYes
Electromagnetic Emissions
IEC 60255-25 Yes
Fast Transient DisturbanceIEC 60255-22-4 severity level IV
Yes
Section VI – Requirements Page 66 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Type test certificate provided Yes
MULTI-FUNCTIONAL DIRECTIONAL OVERCURRENT & EARTH FAULT PROTECTION {67/67N/50/51/50N/51N)
Manufacturer
Type reference
Relay design (static, microprocessor-based, numerical) Numerical
Auxiliary voltage range (Vn = 110Vdc) Vdc 88150
Input frequency range (50Hz nominal) Hz 47.552.5
Number of phase CT inputs
Number of earth fault CT inputs
Number of VT inputs
Characteristics curves conforming to IEC 60255, ANSI Yes
Number of overcurrent functions (e.g. No. lowset, highset, IDMTL)
Number of earth fault functions
Number of group settings
Earth fault element suitable of high impedance REF (with external resistor)
Yes
Other functions provided Thermal overload 49 Y/N U/O Voltage 27/59 Y/N NVD 59N Y/N
Integral metering functions
No. of opto-isolator inputs
No of outputs
Programmable logic Yes
Event and Fault recording functions
Self-monitoring facility
Section VI – Requirements Page 67 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
PC based configuration software for HMI, settings, logic and data recorder.
7.1 Programme name
7.2 Included / Separate Yes
Tripping contacts rating details
Carry continuous
Make
Break dc
A
A / time
W rest.
W & L/R
Communications
Integral operator interface for local interrogation Yes
Control
Communication ports (Front/rear etc)
Physical links (RS485/Fibre optic)
Protocols supported
IEC 61850 Yes
Others (please state)
Type Tests
Atmospheric Environment
Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes
Relative Humidity
Section VI – Requirements Page 68 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Operation at 93% Yes
Tested to IEC 60068-2-3 with severity class 56 days Yes
Enclosure
IEC 60529 IP50 Yes
Mechanical Environment
Vibration IEC 60255-21-1 Yes
Shock and bump IEC 60255-21-2 Yes
Seismic IEC 60255-21-3 Yes
Insulation
Rated insulation
1000V high impedance protection CT inputs
250V for other circuits Yes
1000V open contact withstand Yes
Dielectric Tests
IEC 60255-5 – Series C of table 1 Yes
Impulse voltage
IEC 60255-5 test voltage 5kV Yes
Electromagnetic compatibility
1MHz Burst disturbance test, IEC 60255-22-1 severity class III
Yes
Electrostatic Discharge
IEC 60255-22-2 severity class III Yes
Radiated Electromagnetic Field DisturbanceIEC 60255-22-3 severity class III
Test method A, 27MHz through 500MHzYes
Electromagnetic Emissions
IEC 60255-25 Yes
Section VI – Requirements Page 69 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Fast Transient DisturbanceIEC 60255-22-4 severity level IV
Yes
Type test certificate provided Yes
8.
MULTI-FUNCTIONAL FEEDER MANAGEMENT RELAY {67/67N,50/51,50N/51N, 27, 59, 25, 79, CONTROL, METERING)
Manufacturer
Type reference
Relay design (static, microprocessor-based, numerical) Numerical
Auxiliary voltage range (Vn = 110Vdc) Vdc 88150
Input frequency range (50Hz nominal) Hz 47.552.5
Number of phase CT inputs
Number of earth fault CT inputs
Number of VT inputs
Characteristics curves conforming to IEC 60255, ANSI IEC
Number of overcurrent functions (e.g. No. lowset, highset, IDMTL)
Number of earth fault functions
Number of group settings
Earth fault element suitable of high impedance REF (with external resistor)
Yes
Other functions provided Thermal overload 49 Y/N U/O Voltage 27/59 Y/N NVD 59N Y/N Check Synch 25 Y/N Auto-reclose 79 Y/N
Section VI – Requirements Page 70 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
9.1 Feeder Control (where applicable)
Integral LCD operator interface for local control and interrogation Yes
Full control of circuit bay Close/Open of circuit breakers Close/Open of Disconnectors/Earth Switches Switching status Interlocking facilities Plant status Active circuit line diagram
Yes
Integral metering functions
No. of opto-isolator inputs
No. of outputs
Programmable logic Yes
Event and Fault recording functions
Self-monitoring facility
PC based configuration software for HMI, settings, logic and data recorder.
9.2 Programme
9.3 Included / Separate Yes
Tripping contacts rating details
Carry continuous
Make
Break dc
A
A / time
W rest.
W & L/R
Communications
Control & Monitoring
Communication ports (Front/rear etc)
Section VI – Requirements Page 71 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Physical links (RS485/Fibre optic)
Protocols supported
IEC 61850 Yes
Others (please state)
Type Tests
Atmospheric Environment
Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2
Yes
Relative Humidity
Operation at 93% Yes
Tested to IEC 60068-2-3 with severity class 56 days Yes
Enclosure
IEC 60529 IP50 Yes
Mechanical Environment
Vibration IEC 60255-21-1 Yes
Shock and bump IEC 60255-21-2 Yes
Seismic IEC 60255-21-3 Yes
Insulation
Rated insulation
1000V high impedance protection CT inputs
250V for other circuits Yes
1000V open contact withstand Yes
Section VI – Requirements Page 72 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Dielectric Tests
IEC 60255-5 – Series C of table 1 Yes
Impulse voltage
IEC 60255-5 test voltage 5kV Yes
Electromagnetic compatibility
1MHz Burst disturbance test, IEC 60255-22-1 severity class III
Yes
Electrostatic Discharge
IEC 60255-22-2 severity class III Yes
Radiated Electromagnetic Field DisturbanceIEC 60255-22-3 severity class III
Test method A, 27MHz through 500MHzYes
Electromagnetic Emissions
IEC 60255-25 Yes
Fast Transient DisturbanceIEC 60255-22-4 severity level IV
Yes
Type test certificate provided Yes
10.OVERCURRENT & EARTH FAULT PROTECTION (50/51/50N/51N)
Manufacturer
Type reference
Relay design (static, microprocessor-based, numerical) Numerical
Auxiliary voltage range (Vn = 110Vdc) Vdc 88150
Input frequency range (50Hz nominal) Hz 47.552.5
Number of phase CT inputs
Number of earth fault CT inputs
Section VI – Requirements Page 73 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Characteristics curves conforming to IEC 60255, ANSI Yes
Number of overcurrent functions (e.g. No. lowset, highset, IDMTL)
Number of earth fault functions
Number of group settings
Earth fault element suitable of high impedance REF (with external resistor)
Yes
Other functions provided Thermal overload 49 Y/N 50BF Y/N
Integral metering functions
No. of opto-isolator inputs
Programmable logic Yes
Event and Fault recording functions
Self-monitoring facility
PC based configuration software for HMI, settings, logic and data recorder.
11.1 Programme name
11.2 Included / Separate Yes
Tripping contacts rating details
Carry continuous
Make
Break dc
A
A / time
W rest.
W & L/R
Communications
Integral LCD operator interface for local interrogation Yes
Control
Communication ports (Front/rear etc)
Section VI – Requirements Page 74 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Physical links (RS485/Fibre optic)
Protocols supported
IEC 61850 Yes
Others (please state)
Type Tests
Atmospheric Environment
Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2
Yes
Relative Humidity
Operation at 93% Yes
Tested to IEC 60068-2-3 with severity class 56 days Yes
Enclosure
IEC 60529 IP50 Yes
Mechanical Environment
Vibration IEC 60255-21-1 Yes
Shock and bump IEC 60255-21-2 Yes
Seismic IEC 60255-21-3 Yes
Insulation
Rated insulation
1000V high impedance protection CT inputs
250V for other circuits Yes
1000V open contact withstand Yes
Section VI – Requirements Page 75 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Dielectric Tests
IEC 60255-5 – Series C of table 1 Yes
Impulse voltage
IEC 60255-5 test voltage 5kV Yes
Electromagnetic compatibility
1MHz Burst disturbance test, IEC 60255-22-1 severity class III
Yes
Electrostatic Discharge
IEC 60255-22-2 severity class III Yes
Radiated Electromagnetic Field DisturbanceIEC 60255-22-3 severity class III
Test method A, 27MHz through 500MHzYes
Electromagnetic Emissions
IEC 60255-25 Yes
Fast Transient DisturbanceIEC 60255-22-4 severity level IV
Yes
Type test certificate provided Yes
12.13. HIGH IMPEDANCE DIFFERENTIAL PROTECTION (87)
Manufacturer
Type reference
Relay design (static, microprocessor-based, numerical, E-Mech) Numerical
minimum fault setting (% of CT rating) %
Operating time at 5 x setting ms
Section VI – Requirements Page 76 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Non Linear Resistors (Metrosils) integral Y/N
Self monitoring (excluding E-Mech) Yes
PC based configuration software for HMI, settings, logic and data recorder.
13.1 Programme name
13.2 Included / Separate
Tripping contacts rating details
Carry continuous
Make
Break dc
A
A / time
W rest.
W & L/R
Communications (numerical relays)
Integral LCD operator interface for local interrogation Yes
Control
Communication ports (Front/rear etc)
Physical links (RS485/Fibre optic)
Protocols supported
IEC 61850 Yes
others
Section VI – Requirements Page 77 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Type Tests
Atmospheric Environment
Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes
Relative Humidity
Operation at 93% Yes
Tested to IEC 60068-2-3 with severity class 56 days Yes
Enclosure
IEC 60529 IP50 Yes
Mechanical Environment
Vibration IEC 60255-21-1 Yes
Shock and bump IEC 60255-21-2 Yes
Seismic IEC 60255-21-3 Yes
Insulation
Rated insulation
1000V high impedance protection CT inputs
250V for other circuits Yes
1000V open contact withstand Yes
Dielectric Tests
IEC 60255-5 – Series C of table 1 Yes
Impulse voltage
IEC 60255-5 test voltage 5kV Yes
Electromagnetic compatibility
Section VI – Requirements Page 78 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
1MHz Burst disturbance test, IEC 60255-22-1 severity class III
Yes
Electrostatic Discharge
IEC 60255-22-2 severity class III Yes
Radiated Electromagnetic Field DisturbanceIEC 60255-22-3 severity class III
Test method A, 27MHz through 500MHzYes
Electromagnetic Emissions
IEC 60255-25 Yes
Fast Transient DisturbanceIEC 60255-22-4 severity level IV
Yes
Type test certificate provided Yes
14. AUTO-RECLOSE RELAY (79)
Manufacturer
Type reference
Relay design (microprocessor based, numerical) Numerical
Auxiliary voltage range (Vn = 110Vdc) Vdc 88150
Input frequency range (50Hz nominal) Hz 47.552.5
Auto-Reclose Function requirements
No of CB that can be controlled 2
1ph and 3ph AR sequences 1ph+3ph
Integrated/External Check Synch
Other requirements
No of Opto-isolator inputs
No of output contacts
Integral operator interface for local interrogation Yes
Programmable scheme logic Yes
Section VI – Requirements Page 79 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
PC based configuration software for HMI, settings, logic and data recorder.
Yes
14.1 Programme name
14.2 Included / Separate
Tripping contacts rating details
Carry continuous
Make
Break dc
A
A / time
W rest.
W & L/R
Self checking facility Yes
Communications
Control
Communication ports (Front/rear etc)
Physical links (RS485/Fibre optic)
Protocols supported
IEC 61850 Yes
others
Type Tests
Atmospheric Environment
Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes
Relative Humidity
Operation at 93% Yes
Tested to IEC 60068-2-3 with severity class 56 days Yes
Enclosure
IEC 60529 IP50 Yes
Mechanical Environment
Vibration IEC 60255-21-1 Yes
Shock and bump IEC 60255-21-2 Yes
Section VI – Requirements Page 80 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Seismic IEC 60255-21-3 Yes
Insulation
Rated insulation
1000V high impedance protection CT inputs
250V for other circuits Yes
1000V open contact withstand Yes
Dielectric Tests
IEC 60255-5 – Series C of table 1 Yes
Impulse voltage
IEC 60255-5 test voltage 5kV Yes
Electromagnetic compatibility1MHz Burst disturbance test,
IEC 60255-22-1 severity class IIIYes
Electrostatic Discharge
IEC 60255-22-2 severity class III Yes
Radiated Electromagnetic Field DisturbanceIEC 60255-22-3 severity class III
Test method A, 27MHz through 500MHzYes
Electromagnetic Emissions
IEC 60255-25 Yes
Fast Transient DisturbanceIEC 60255-22-4 severity level IV
Yes
Type test certificate provided Yes
14.3
15. TRIP CIRCUIT SUPERVISIONManufacturer
Type reference
Relay design (Electro-Mech, static, numerical)
Auxiliary voltage range (Vn = 110Vdc) Vdc 88150
Operating time ms
Supervision of the whole trip circuit - CB open and closed. Yes
Relay operated indicator Yes
Type Tests
Section VI – Requirements Page 81 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Atmospheric Environment
Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes
Relative Humidity
Operation at 93% Yes
Tested to IEC 60068-2-3 with severity class 56 days Yes
Enclosure
IEC 60529 IP50 Yes
Mechanical Environment
Vibration IEC 60255-21-1 Yes
Shock and bump IEC 60255-21-2 Yes
Seismic IEC 60255-21-3 Yes
Insulation
Rated insulation
1000V high impedance protection CT inputs
250V for other circuits Yes
1000V open contact withstand Yes
Dielectric Tests
IEC 60255-5 – Series C of table 1 Yes
Impulse voltage
IEC 60255-5 test voltage 5kV Yes
Electromagnetic compatibility
1MHz Burst disturbance test, IEC 60255-22-1 severity class III
Yes
Electrostatic Discharge
IEC 60255-22-2 severity class III Yes
Section VI – Requirements Page 82 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Radiated Electromagnetic Field DisturbanceIEC 60255-22-3 severity class III
Test method A, 27MHz through 500MHzYes
Electromagnetic Emissions IEC 60255-25
Yes
Fast Transient DisturbanceIEC 60255-22-4 severity level IV
Yes
Type test certificate provided Yes
16. MULTI-CONTACT TRIPPING RELAYS
Manufacturer
Type reference
Operating time ms <12
Auxiliary voltage range (Vn = 110Vdc) Vdc 88150
Is relay mechanically latched or self resetting
Method used to reset latched relay (hand or electrical)
Burden at rated voltage
Minimum voltage at which reliable operation occurs
Tripping contacts rating details
Carry continuous
Make
Break dc
A
A / time
W rest.
W & L/R
Relay operated indicator type
Type Tests
Atmospheric Environment
Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes
Relative Humidity
Section VI – Requirements Page 83 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Operation at 93% Yes
Tested to IEC 60068-2-3 with severity class 56 days Yes
Enclosure
IEC 60529 IP50 Yes
Mechanical Environment
Vibration IEC 60255-21-1 Yes
Shock and bump IEC 60255-21-2 Yes
Seismic IEC 60255-21-3 Yes
Insulation
Rated insulation
1000V high impedance protection CT inputs
250V for other circuits Yes
1000V open contact withstand Yes
Dielectric Tests
IEC 60255-5 – Series C of table 1 Yes
Impulse voltage
IEC 60255-5 test voltage 5kV Yes
Electromagnetic compatibility
1MHz Burst disturbance test, IEC 60255-22-1 severity class III
Yes
Electrostatic Discharge
IEC 60255-22-2 severity class III Yes
Radiated Electromagnetic Field DisturbanceIEC 60255-22-3 severity class III
Test method A, 27MHz through 500MHzYes
Electromagnetic Emissions
IEC 60255-25 Yes
Section VI – Requirements Page 84 of 677Environmental Guidelines for Contractors
D. PROTECTION AND INDICATION SYSTEM UNIT DATA
Required Offered
Fast Transient DisturbanceIEC 60255-22-4 severity level IV
Yes
Type test certificate provided Yes
Section VI – Requirements Page 85 of 677Environmental Guidelines for Contractors
E. TARIFF METERING SYSTEM UNIT DATA
Required Offered
17. 1 TARIFF METER
1.1 Manufacturer
Model
1.2 Construction
Measuring Principle 3ph, 4wire
Type Numerical
Display/Reading digits ≥7
Backlit LCD Yes
1.3 Auxiliary voltage range
DC (Vn = 110Vdc) Vdc 88125
AC Vac 230
1.5 Analogue Inputs
Current (In) A 1
Current measuring range pu 1.2
Voltage (Vn) V 110
Voltage measuring range pu 0.8 – 1.15
Power consumption (burden) VA
1.6 Accuracy Class
Watt hour (IEC 602053-22) 0.2s
VAr hour (IEC 602053-23) 2.0
1.7 Measurements
Section VI – Requirements Page 86 of 677Environmental Guidelines for Contractors
E. TARIFF METERING SYSTEM UNIT DATA
Required Offered
kWh, kVArh
kW, kVAr
V, I
Four quadrant reactive energy
Max Demand
THD
1.8 Outputs
Pulsed Outputs (IEC 62053-31) 3 (min)
1.9 Data Logging
Integral Logging/Storage function
Duration days 180
Channels 4
Programmable Periods y
Inputs from external meters y/n
1.10 Other functions
Battery Back-up y/n y
Back-up duration days ≥14
GPS clock y/n y
Self checking/monitoring facility y/n y
Dual supply changeover (VT) y/n y
Section VI – Requirements Page 87 of 677Environmental Guidelines for Contractors
E. TARIFF METERING SYSTEM UNIT DATA
Required Offered
1.11 Communications
Communication ports (Front/rear etc)
RS232
RS485 y
Optical (IEC 62056-21) y
Ethernet y
Protocols supported
IEC 62056-21, DLMS y
others
Type Tests
1.12 Atmospheric Environment (62052-11)
Operating Range: -10C to 45C
Operation -25C to 55C
y
Transport/storage -25C to 70C y
1.13 Relative Humidity (62052-11)
Annual mean <75% y
30 days over one year: 95% y
1.14 Enclosure
IEC 60529 IP51
1.15 Mechanical Environment (62052-11)
Shock test IEC 60068-2-27 y
Vibration IEC 60068-2-6
1.16 Insulation Strength (IEC 62052-11) y
Dielectric Tests-
Section VI – Requirements Page 88 of 677Environmental Guidelines for Contractors
E. TARIFF METERING SYSTEM UNIT DATA
Required Offered
Impulse voltage (surge) as per IEC 61000-4-5
1.17 Electromagnetic compatibility IEC 62052-11 y
Electrostatic Discharge to IEC 61000-4-2
Immunity to Electromagnetic Fields to IEC 61000-4-3
Fast Transient Burst Test to IEC 61000-4-4
Immunity to conducted disturbance by RF fields to IEC 61000-4-6
Damped Oscillatory Waves to IEC 6100-4-12
Radio Interference Suppression to CISPR 22 class B
1.18 Type test certificate provided y
Section VI – Requirements Page 89 of 677Environmental Guidelines for Contractors
F. FAULT MONITORING SYSTEM UNIT DATA
Required Offered
1 FAULT MONITORING SYSTEM
1.1 Manufacturer
1.2 Type reference
DAU unit type
Master Station type
HMI type
Printer type
1.3 Auxiliary voltage range (Vn = 110Vdc) Vdc 88150
1.4 Analogue Inputs 8
1.5 Event inputs 16
1.6 A/D converter bit 16bit
1.7 Current input max amplitude In 30
1.8 Current/voltage accuracy % fsd ≤0.5
1.9 Scan Rate
Analogue Channel Hz ≥4000
Event Channel Hz ≥2000
1.10 Time stamp resolution ms 1
1.11 Recording range
Pre Fault ms ≥500
Post Fault ms ≥2000
1.12 Trigger response time
Section VI – Requirements Page 90 of 677Environmental Guidelines for Contractors
F. FAULT MONITORING SYSTEM UNIT DATA
Required Offered
Analogue
Event
1.13 Memory
RAM (Non Volatile) Mb ≥256
HDD Mb ≥500
1.14 Battery Back-up duration days ≥14
1.15 GPS clock input Yes
1.16 System Software
1.17 Self checking facility Yes
1.18 Communications
Communication ports (Front/rear etc)
RS232
RS485
RJ45
Other
Protocols supported
IEC 61850
others
Type Tests
1.19 Atmospheric Environment
Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes
Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes
Section VI – Requirements Page 91 of 677Environmental Guidelines for Contractors
F. FAULT MONITORING SYSTEM UNIT DATA
Required Offered
1.20 Relative Humidity
Operation at 93% Yes
Tested to IEC 60068-2-3 with severity class 56 days Yes
1.21 Enclosure
IEC 60529 IP50 Yes
1.22 Mechanical Environment
Vibration IEC 60255-21-1 Yes
Shock and bump IEC 60255-21-2 Yes
Seismic IEC 60255-21-3 Yes
1.23 Insulation
Rated insulation
1000V high impedance protection CT inputs
250V for other circuits Yes
1000V open contact withstand Yes
Dielectric Tests
IEC 60255-5 – Series C of table 1 Yes
Impulse voltage
IEC 60255-5 test voltage 5kV Yes
1.24 Electromagnetic compatibility
1MHz Burst disturbance test, IEC 60255-22-1 severity class III
Yes
Section VI – Requirements Page 92 of 677Environmental Guidelines for Contractors
F. FAULT MONITORING SYSTEM UNIT DATA
Required Offered
Electrostatic Discharge
IEC 60255-22-2 severity class III Yes
Radiated Electromagnetic Field DisturbanceIEC 60255-22-3 severity class III
Test method A, 27MHz through 500MHzYes
Electromagnetic Emissions
IEC 60255-25 Yes
Fast Transient DisturbanceIEC 60255-22-4 severity level IV
Yes
1.25 Type test certificate provided Yes
Section VI – Requirements Page 93 of 677Environmental Guidelines for Contractors
G. 11kV XLPE INSULATED CABLE SYSTEM (with solid bonding)
UNIT DATA
Required Offered
18.
1 GENERAL
1.1 Name of manufacturer
1.2 Location of manufacturing site
1.3 Manufacturers Quality Certification ISO 9001
Certified by (Company Name)
Certification valid till (year)
1.4 Circuit rating required kVA 500
1.5 General description of cable
number of cores 1or 3
system voltage kV 11
conductor size mm2
Insulation Type XLPE
metal sheath type Lead
oversheath type MDPE
1.6 Year of first commercial operation of cable type
2INSULATION CO-ORDINATION
2.1 Highest system voltage (Um) (insulation class) kV 12
2.2 Nominal voltage between conductors (U) kV 11
2.3 Rated frequency Hz 50
2.4 Nominal voltage between conductor and sheath (Uo) kV 6.35
2.5 Rated impulse withstand voltage (Up) kV 95
2.6 Rated short duration power frequency withstand voltage kV 17
Section VI – Requirements Page 94 of 677Environmental Guidelines for Contractors
G. 11kV XLPE INSULATED CABLE SYSTEM (with solid bonding)
UNIT DATA
Required Offered
3 RATINGS
3.1 Maximum continuous direct-buried current rating, assuming, Soil thermal resistivity of 2.0K.m/W
Flat spaced configuration, phase spacing of 250mm
Special bonding of metal sheaths
For, Guaranteed Current Rating (Single Circuit in Trench) A Guaranteed Current Rating (Double Circuit in one
Trench, distance between middle phases, s = 1500 mm)A
Ground temperature at burial depth oC Calculation Method IEC 60287
3.2 Maximum continuous in-air current rating, assuming, Air temperature (in shade) of 35 °C
Special bonding of metal sheaths
Flat spaced configuration, group/phase spacing of 150mm
Thermally independent of other cable circuits
For, Guaranteed Current Rating (single circuit) A Calculation Method
3.3 Maximum permissible core temperature for continuous operation
°C 90
3.4 Short circuit capacity for 1 sec
Short circuit current kA As per IEC60502
Permissible maximum sheath temperature oC 200
Permissible maximum conductor temperature oC 250
3.5 Permissible emergency overload
3.5.1 Applied on 100% continuous load
Emergency current rating A Maximum emergency temperature oC Allowable duration/operation hours Allowable total duration/annum hours Maximum average duration/annum on total life of cable hours
Section VI – Requirements Page 95 of 677Environmental Guidelines for Contractors
G. 11kV XLPE INSULATED CABLE SYSTEM (with solid bonding)
UNIT DATA
Required Offered
3.5.2 Applied on 50% continuous load Emergency current rating A Maximum emergency temperature °C Allowable duration/operation hours Allowable total duration/annum hours Maximum average duration/annum on total life of cable hours
3.5.3 Applied on 20% continuous load Emergence current rating A Maximum emergency temperature °C Allowable duration/operation hours Allowable total duration/annum hours Maximum average duration/annum on total life of cable hours
4.0CONSTRUCTION FEATURES
4.1 Conductor Material Cu or Al Nominal cross-section mm2
Shape of conductor
circular Overall diameter mm Waterblocking method Tape/yarn Semiconducting binder tape yes
4.2 Conductor screen Type of material Fully bonded
semicon. XLPE Nominal thickness mm Minimum thickness mm Nominal overall diameter mm Compound Identification Reference yes
4.3 Insulation Material XLPE Nominal thickness mm Minimum thickness mm Nominal overall diameter mm
Section VI – Requirements Page 96 of 677Environmental Guidelines for Contractors
G. 11kV XLPE INSULATED CABLE SYSTEM (with solid bonding)
UNIT DATA
Required Offered
Maximum continuous operating temperature oC 90 Compound Identification Reference yes Maximum stress at nominal voltage
At conductor screen kV/mm At insulation screen kV/mm Maximum stress at impulse voltage
At conductor screen kV/mm At insulation screen kV/mm
4.4 Insulation screen Type of material Fully bonded
semicon. XLPE Nominal thickness mm Nominal overall diameter mm Compound Identification Reference
Indelible ink marking on screen yes
4.5 XLPE Manufacturing Methods Extrusion line type e.g. CCV, MDCV, VCV
Single pass, triple extrusion yes Curing method Dry Cooling method Dry Degassing Period days
4.6 Bedding for moisture absorption Type and material
Nominal thickness mm Minimum thickness mm Nominal overall diameter over bedding mm
4.7 Metallic screen Type and material Copper wire Nominal thickness mm Minimum thickness mm Wire diameter No.
Section VI – Requirements Page 97 of 677Environmental Guidelines for Contractors
G. 11kV XLPE INSULATED CABLE SYSTEM (with solid bonding)
UNIT DATA
Required Offered
Nominal diameter over the screen mm Cross sectional area of screen mm2
Short time current density (1 sec) kA/mm2
4.8 Bedding/Binder tape Type and material
Nominal thickness mm Minimum thickness mm Nominal overall diameter over bedding mm
4.9 Metallic sheath Type and material Lead-alloy 1/2C Nominal thickness mm Minimum thickness mm Nominal diameter over the sheath mm Cross sectional area of sheath mm2
Short time current density (1 sec.) kA/mm2
4.10 Protective anti-corrosion external sheath covering Bitumen undercoat layer
Type and material MDPE Color Black Nominal thickness mm Minimum thickness mm Termite resistant yes/no Yes Type of anti-termite protection
Thermal resistivity K.m/W Max 6.0
4.11 Type of conductive outer layer Graphite/or semicon. polymer
4.12 Nominal overall cable diameter mm
4.13 Weight of completed cable
Copper kg/m Insulation kg/m Lead-Alloy kg/m Gross Weight kg/m
Section VI – Requirements Page 98 of 677Environmental Guidelines for Contractors
G. 11kV XLPE INSULATED CABLE SYSTEM (with solid bonding)
UNIT DATA
Required Offered
5 LOSSES
5.1 Maximum dielectric loss per metre / phase when operating at nominal voltage and frequency and at maximum conductor temperature
W/m
5.2 Maximum sheath loss per metre / phase when operating at nominal voltage and frequency and at current rating stipulated in Item 1.11. with sheath bonded and earthed as recommended (sectionalizing cross bonding)
W/m
5.3 Maximum conductor loss per metre / phase when operating at nominal voltage and frequency and at current rating stipulated in Item 1.11.
W/m
5.4 Total loss of cable per metre / phase of three phase circuit W/m
6 ELECTRICAL VALUES
6.1 Maximum d.c. resistance of conductor at 20oC /m
6.2 Maximum a.c. resistance of conductor at operating temperature
/m
6.3 Equivalent reactance of three phase circuit at 50 Hz /m
6.4 Electrostatic capacitance per conductor of cable at nominal voltage and operating temperature
pF/m
6.5 Maximum charging current per conductor at nominal voltage mA/m
6.6 Charging capacity of three phase system (at Uo) VAr/m
6.7 Maximum dielectric loss factor of cable at normal voltage and frequency at a conductor temperature of:
20oC
90oC
6.8 Positive & Negative sequence impedance /m
Section VI – Requirements Page 99 of 677Environmental Guidelines for Contractors
G. 11kV XLPE INSULATED CABLE SYSTEM (with solid bonding)
UNIT DATA
Required Offered
6.9 Zero sequence impedance (as installed conditions)
Resistance /m
Reactance /m
Capacitance pF/m
6.10 Surge impedance
7 BONDING & EARTHING
7.1 Number of connections to earth
7.2 Interconnected sheaths at joint positions Yes/no
8 TESTING
8.1 Routine Tests As per IEC 60502
8.2 Sample Tests As per IEC 60502
8.3 Type Tests
- Test Regime As per IEC 60502
- Date of Test
- Name of independent witness
8.4 Commissioning Tests
- AC voltage withstand test 2Uo for 1 hour
- Oversheath DC voltage test kV 10kV max for 15minutes
9 OTHER INSTALLATION DATA
9.1 Minimum cable bending radius when laid:
Section VI – Requirements Page 100 of 677Environmental Guidelines for Contractors
G. 11kV XLPE INSULATED CABLE SYSTEM (with solid bonding)
UNIT DATA
Required Offered
Direct burial mm
In air mm
In ducts mm
At terminations (with former) mm
9.2 Maximal permissible pulling force of total cable kN
9.3 Maximal side wall bearing pressure to the cable at bending points
kN/m
9.4 Delivery length per drum
Normal m
Maximum m
9.5 Maximal weight of full drum with maximum delivery length of cable
kg
9.6 Drum dimensions:
Flange diameter m
Core diameter m
Width m
Section VI – Requirements Page 101 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
19.
1 SUBSTATION CONTROL SYSTEM Yes
2.1 Substation Computer
2.1.1 Manufacturer Yes
2.1.2 Model Yes
2.1.3 Processor
2.1.4 Type
2.1.5 Word length Bits
2.1.6 Clock speed (minimum) MHz
2.1.7 Memory size
2.1.8 Supplied (minimum) Mb
2.1.9 Supportable/expandable Gb
2.1.10 Hard disk size
2.1.11 Supplied (minimum) Gb
2.1.12 Supportable/expandable Gb
2.1.13 Optical Storage Yes
2.1.14 Operating system
2.1.15 Software supplied
2.1.16 Operating temperature range °C
2.1.17 Maximum relative humidity %
2.1.18 Nominal voltage V ac
2.1.19 Operating frequency Hz
2.1.20 Starting current A
Section VI – Requirements Page 102 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
2.1.21 Power requirement W
2.1.22 Mean time between failure h
2.1.23 Mean time to repair h
2.2 Gateway
2.2.1 Manufacturer Yes
2.2.2 Model Yes
2.2.3 Processor
2.2.4 Type
2.2.5 Word length Bits
2.2.6 Clock speed (minimum) MHz
2.2.7 Memory size
2.2.8 Supplied (minimum) Mb
2.2.9 Supportable/expandable Gb
2.2.10 Hard disk size
2.2.11 Supplied (minimum) Gb
2.2.12 Supportable/expandable Gb
2.2.13 Communication Protocols To Control Centre(s)
2.2.14 NCC Main IEC 60870-5-101 Yes
2.2.15 NCC Alt IEC 60870-5-101 Yes
2.2.16 NCC TCP/IP Intranet Yes
2.2.17 RCC Main IEC 60870-5-101 Yes
2.2.18 RCC Alt IEC 60870-5-101 Yes
2.2.19 NCC IEC 60870-5-104 Yes
2.2.20 RCC IEC 60870-5-104 Yes
Section VI – Requirements Page 103 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
2.2.21 Communication Protocols in Substation
2.2.22 IEC 61850 Yes
2.2.23 List other operating Protocols
2.2.24 Data Communications Interface
2.2.25 V.35 interface at 64Kb/s Yes
2.2.26 X.21 / V.11 interface at 64Kb/s Yes
2.2.27 Operating system
2.2.28 Operating temperature range °C
2.2.29 Maximum relative humidity %
2.2.30 Nominal voltage V dc
2.2.31 Operating frequency Hz
2.2.32 Starting current A
2.2.33 Power requirement W
2.2.34 Mean time between failure h
2.2.35 Mean time to repair h
2.3.0 Operator Workstations / HMI
2.3.1 Manufacturer Yes
2.3.2 Model Yes
2.3.3 Literature reference for principle of operation Yes
2.3.4 Processor
2.3.5 Type
2.3.6 Word length Bits
2.3.7 Clock speed (minimun) MHz
Section VI – Requirements Page 104 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
2.3.8 Memory size
2.3.9 Supplied (minimum) Mb
2.3.10 Supportable/expandable Gb
2.3.11 Hard disk size
2.3.12 Supplied (minimum) Gb
2.3.13 Supportable/expandable Gb
2.3.14 Optical Storage Yes
2.3.15 Pointer Device
2.3.16 Operating system
2.3.17 Operator interface screens
2.3.18 Operating temperature range °C
2.3.19 Maximum relative humidity %
2.3.20 Nominal voltage V ac
2.3.21 Operating frequency Hz
2.3.22 Starting current A
2.3.23 Power requirement W
2.3.24 Mean time between failure h
2.3.25 Mean time to repair h
2.3.26 Operator Desk Yes
2.3.27 Manufacturer Yes
2.3.28 Type of construction
2.3.29 Finish and material of working surfaces
2.3.30 Method of mounting VDUs
2.3.31 Number
Section VI – Requirements Page 105 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
2.3.32 Operator Chairs
2.3.33 Manufacturer
2.3.34 Type of construction
2.3.35 Type of upholstery
2.3.36 Number
2.4. COLOUR VISUAL DISPLAY UNITS (VDUS)
2.4.1 Manufacturer Yes
2.4.2 Model Yes
2.4.3 Literature reference for principle of operation Yes
2.4.4 Screen size across diagonal mm
2.4.5 Usable display area mm
2.4.6 Resolution (minimum) pixels
2.4.7 Dot pitch mm
2.4.8 Operating temperature range °C
2.4.9 Operating relative humidity range %
2.4.10 Nominal voltage V ac
2.4.11 Operating frequency Hz
2.4.12 Starting current A
2.4.13 Power requirement W
2.4.14 Approximate lifetime of monitor under continuous use h
2.4.15 Mean time between failure h
2.4.16 Mean time to repair h
2.5 Substation Local Area Network (LAN)
2.5.1 Architecture and Technology Yes
Section VI – Requirements Page 106 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
2.5.2 Literature reference for principle of operation Yes
2.5.3Transmission medium (e.g. optical fibre) and physical specification
2.5.4 Protocols
2.5.5 IEC 60870-5-101
2.5.6 IEC 60870-5-104
2.5.7 IEC 61850
2.5.8 List all other protocols
2.5.9 Data transmission rate(s) Mbps
2.5.10
Physical arrangement - Identify all main elements in the supply including hubs, concentrators, bridges, routers, gateways switches etc. and the number of each
Yes
2.5.11 For each element of the LAN indicate the
2.5.12 No and type of ports
2.5.13 % of spare for each type of port
2.5.14Management software package, functions and facilities, and hardware platform
2.5.15 % Loading under various system activity scenarios including
2.5.16 normal loading for performance testing %
2.5.17 high loading for performance testing %
2.5.18 system power up %
2.5.19 main server fail-over and database resynchronisation
2.5.20 Overall availability %
2.6 INDIVIDUAL ELEMENTS
2.6.1For each element of the LAN equipment provide the following information
2.6.2 Manufacturer
Section VI – Requirements Page 107 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
2.6.3 Type
2.6.4 Nominal voltage
2.6.5 Power requirements V ac
2.6.6Range of ambient temp. and max relative humidity for continuous reliable operation
W
2.6.7 Mean time between failures oC
2.6.8 Mean time to repair %RH
2.7 PRINTERS
2.7.1 Logging Printer Yes
2.7.2 Manufacturer
2.7.3 Model
2.7.4 Literature reference for principle of operation
2.7.5 Number
2.7.6 Mounting arrangement
2.7.7 Method of printing (e.g. ink jet)
2.7.8 Print speed ppm
2.7.9 Paper feed mechanism
2.7.10 Number of columns (minimum)
2.7.11 Operating temperature range °C
2.7.12 Maximum relative humidity %
2.7.13 Nominal voltage V ac
2.7.14 Operating frequency Hz
2.7.15 Power requirement W
2.7.16 Max noise level at 1 m dB(A)
Section VI – Requirements Page 108 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
2.7.17 Mean time between failure h
2.7.18 Mean time to repair h
2.7.19 COLOUR PRINTERS
2.7.20 Manufacturer Yes
2.7.21 Model Yes
2.7.22 Literature reference for principle of operation Yes
2.7.23 Number
2.7.24 Mounting arrangement
2.7.25 Print speed (minimum) ppm
2.7.26 Technology
2.7.27 Resolution dpi
2.7.28 Paper size
2.7.29 Sheet feed paper tray capacity Sheets
2.7.30 Internal memory (minimum) Mb
2.7.31 Operating temperature range °C
2.7.32 Maximum relative humidity %
2.7.33 Nominal voltage V ac
2.7.34 Operating frequency Hz
2.7.35 Power requirement W
2.7.36 Max noise level at 1 m dB(A)
2.7.37 Mean time between failure h
2.7.38 Mean time to repair h
3.0 BAY CONTROL UNIT HARDWARE
3.1.0 19.1 General Yes
Section VI – Requirements Page 109 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
3.1.1 Manufacturer Yes
3.1.2 Module designation Yes
3.1.3 Literature reference for principle of operation Yes
3.1.4 Power supply V dc 110
3.1.5Power requirements W
3.1.6 Maximum Number of expansion modules
3.1.7 Mean-time to repair for each type of RTU H
3.1.8 Mean-time between failure for each type of RTU H
3.1.9 Local LCD Display
3.1.10 Operating temperature range °C 0 – 50
3.1.11 Operating relative humidity range % 100
3.2 BCU ENCLOSURE
3.2.1 Manufacturer
3.2.2 Module designation
3.2.3 Literature reference for enclosure
3.2.4 Weight
3.2.5 Dimensions
3.2.6.0 Degree of protection
3.2.6.1 Flush Mounted housing
3.2.6.2 Surface mounted housing
3.3 IEC STANDARDS ( OR EQUIVALENT )
3.3.1 EMC Type tests (Provide Class/Level or Severity rating)
3.3.2 EMC Compliance IEC 60255-22-3
3.3.3 Dielectric withstand test IEC 60255-4/-5
Section VI – Requirements Page 110 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
3.3.4 High Voltage impulse test IEC 60255-4/-5
3.3.5 Fast transient disturbance test IEC 61000-4-4
3.3.6 Oscillatory transient IEC 61000-4-12
3.3.7 Radiated immunity test IEC 61000-4-6
3.3.8 Electrostatic discharge test IEC 61000-4-2
3.3.9 Emitted interference test IEC 61000-4-3
3.3.10 Mechanical test Compliance
3.3.11 Vibration test IEC 60255-21-1
3.3.12 Shock test IEC 60255-21-2
3.3.13 Seismic test IEC 60255-21-3
3.3.14 Temperature rise test IEC 60068-2-2
3.4 BCU FUNCTIONS
3.4.1 The monitoring functions include:
3.4.2 Switching status monitoring (breakers)
3.4.3 Indication & alarm status monitoring
3.4.4 Analogue measurements (currents, voltages, etc.)
3.4.5 Resolution of time tagging ms 1
3.4.6.0 The control functions include:
3.4.6.1 Close / open of circuit breakers
3.4.6.2 Close / Open of isolators / disconnectors
3.4.6.3 Transformer Automatic tap change control
3.4.6.4 Breaker Voltage Synchronisation Check Control
3.4.6.5 Bay interlocking facilities
3.4.7.0 The reporting functions include:
Section VI – Requirements Page 111 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
3.4.7.1 Sequence of Events recording
3.4.7.2 Post – Mortem Review / Fault waveform capture
3.4.7.3
Tenderers to state memory capacity and functionality of Sequence of events and fault waveform capture
3.5 19.2 BCU Configuration
3.5.1 Number of processors
3.5.2 Main processor
3.5.3 Secondary processors
3.5.4 Communication processor (module)
3.5.5 Type of communication between processors
3.5.6.0 LCD Display and selector Buttons on front of BCU Yes
3.5.6.1 Functionality to include
3.5.6.2 Full control of circuit bay
3.5.6.3 Status of bay plant
3.5.6.4 Circuit active line diagram
3.5.6.5 Power system Measurements
3.5.6.6 Display alarms and events
3.6 PROCESSING UNITS
3.6.1 Main CPU
3.6.2 Manufacturer
3.6.3 Module designation
3.6.4 Literature reference for principle of operation
3.6.5 Mean - time between failure h
3.6.6 Power requirements W
Section VI – Requirements Page 112 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
3.6.7 Type of processor
3.6.8 Word length bit
3.6.9 Clock speed MHz
3.6.10.0 Kinds of memory used:
3.6.10.1 Type, size and extension capabilities KByte
3.6.10.2 Type, size and extension capabilities Kbytes
3.6.10.3 Type, size and extension capabilities Kbytes
3.7.0 SECONDARY CPU
3.7.1 Manufacturer
3.7.2 Module designation
3.7.3 Literature reference for principle of operation
3.7.4 Mean - time between failure h
3.7.5 Power requirements W
3.7.6 Type of processor
3.7.7 Word length bit
3.7.8 Clock speed MHz
3.7.9.0 Kinds of memory used:
3.7.9.1 Type, size and extension capabilities Kbytes
3.7.9.2 Type, size and extension capabilities Kbytes
3.7.9.3 Type, size and extension capabilities Kbytes
3.8 COMMUNICATIONS
3.8.1 Manufacturer Yes
3.8.2 Module designation
3.8.3 Literature reference for principle of operation
Section VI – Requirements Page 113 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
3.8.4 Number of communications channels
3.8.5 Type of processor
3.8.6 Word length
3.8.7 Clock speed bit
3.8.8 Type and size of memory MHz
3.8.9 Line interface to communication channel
3.8.10 Speed of transmission B/s
3.8.11 Number and type of communication ports
3.8.12 Meantime between failure h
3.8.13 Power requirement W
3.8.14.0 Communication Interfaces
3.8.14.1 IEC60870-5-101 direct to Control Centre(s)
3.8.14.2 IEC60870-5-103 interface to protection IED
3.8.14.3 IEC61850 interface to substation LAN
3.8.14.4IEC60870-5-101 for remote downloading of BCU data
3.8.14.5 List all Protocols available at BCU
3.8.15 Local interface for Laptop Computer
3.8.16.0 IED Interface
3.8.16.1 List of manufactures the BCU has interfaced Yes
3.8.16.2 Standard communication protocols available Yes
3.8.16.3 Optional communication protocols available Yes
3.9 POWER SUPPLY MODULE
3.9.1 Module designation
Section VI – Requirements Page 114 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
3.9.2 Literature reference for principle of operation
3.9.3 Maximum number of modules per processor
3.9.4 Nominal Input voltage VDC
3.9.5 Operating voltage range
3.9.6 Power requirement W
3.9.7 Isolation
3.9.8 Meantime between failure h
3.9.9 Power requirement W
3.10 DIGITAL INPUT MODULE
3.10.1 Module designation
3.10.2 Literature reference for principle of operation
3.10.3 Maximum number of modules per processor
3.10.4 Input voltage V dc
3.10.5.0 Is contact input type configurable as
3.10.5.1 Status and alarms
3.10.5.2 Sequence of events
3.10.5.3 BCD or parallel inputs
3.10.5.4 Pulse accumulator
3.10.5.5 Or any combination of these
3.10.6.0 Standard number of inputs per module:
3.10.6.1 double position
3.10.6.2 single position
3.10.7 Type of input circuit isolation
3.10.8 Input galvanic separation
Section VI – Requirements Page 115 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
3.10.9 Impulse voltage withstand kV
3.10.10 Scan time ms
3.10.11 Minimal pulse duration ms
3.10.12 Input impedance ohm
3.10.13 Filter time constant ms
3.10.14 Meantime between failure h
3.10.15 Power requirement W
3.11 PULSE COUNTING MODULE
3.11.1 Is this facility incorporated into the digital input module?
3.11.2 Module designation
3.11.3 Literature reference for principle of operation
3.11.4 Maximum number of modules per processor
3.11.5 Type of counter
3.11.6 Maximum count
3.11.7 Storage and resetting under control of external clock?
3.11.8 Number of inputs per module
3.11.9 Input current mA
3.11.10 Impulse voltage withstand kV
3.11.11 Signal range : pulse widths ms
3.11.12 Meantime between failure h
3.11.13 Power requirement W
3.12 COMMAND OUTPUT MODULE
3.12.1 Module designation
3.12.2 Literature reference for principle of operation
Section VI – Requirements Page 116 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
3.12.3 Maximum number of modules per processor
3.12.4.0 Contact ratings
3.12.4.1 Switched voltage V
3.12.4.2 Switched power VA max
3.12.4.3 Switched current A
3.12.4.4 Range of duration of command output S
3.12.5 Number of two position output channels per module
3.12.6 Are outputs activated by select-check-actuate procedure?
3.12.7 Are welded contacts checked prior to command output?
3.12.8 Are the outputs fused and fuse status monitored?
3.12.9 Impulse voltage withstand kV
3.12.10 Meantime between failure h
3.12.11 Power requirement W
3.13 DIGITAL OUTPUT MODULE
3.13.1 Module designation
3.13.2 Literature reference for principle of operation
3.13.3 Number of outputs per module
3.13.4 Maximum number of modules per processor
3.13.5 Maximum output current mA
3.13.6 Maximum switched output voltage V
3.13.7 Impulse voltage withstand kV
3.13.8 Type of protection against back EMF kV
3.13.9 Command duration adjustable in the range s
3.13.10 Meantime between failure h
Section VI – Requirements Page 117 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
3.13.11 Power requirement W
3.14 ANALOGUE TO DIGITAL CONVERSION MODULE
3.14.1 Module designation
3.14.2 Literature reference for principle of operation
3.14.3 Number of inputs per module
3.14.4 Maximum number of modules per processor
3.14.5 Resolution bits
3.14.6 Accuracy %
3.14.7 Common mode noise rejection dB
3.14.8 Normal mode noise rejection dB
3.14.9 Conversion time ms
3.14.10 Scanning time (per channel) ms
3.14.11 Meantime between failures h
3.14.12 Power requirement W
3.15 ANALOGUE INPUT MODULE
3.15.1 Module designation
3.15.2 Literature reference for principle of operation
3.15.3 Maximum number of modules per processor
3.15.4 Scanning resolution bits
3.15.5 Accuracy %
3.15.6 How are overflow and conversion failures dealt with?
3.15.7 Conversion time
3.15.8 Input filter attenuation at 50 Hz dB
3.15.9 Input signal types (e.g. 4-20 mA)
Section VI – Requirements Page 118 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
3.15.10 Method of isolation
3.15.11 Impulse voltage withstand kV
3.15.12 Input impedance ohm
3.15.13 Type of ADC switching
3.15.14 Standard number of inputs per module
3.15.15 Mean time between failure h
3.15.16 Power requirement W
3.16 ANALOGUE OUTPUT MODULE
3.16.1 Module designation
3.16.2 Literature reference for principle of operation
3.16.3 Number of outputs per module
3.16.4 Maximum number of modules per processor
3.16.5 Output voltage range V
3.16.6 Output current range mA
3.16.7 Type of isolation
3.16.8 Load resistance range ohms
3.16.9 Maximum error over-current ranges %
3.16.10 Impulse voltage withstand kV
3.17.0 DIRECT AC CONNECTION VOLTAGE
3.17.1 Module designation
3.17.2 Literature reference for principle of operation
3.17.3 Maximum number of modules processor
3.17.4 Number of inputs per module
3.17.5 Input voltage ranges V ac
Section VI – Requirements Page 119 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
3.17.6 Input filter attenuation at 50 Hz dB
3.17.7 Burden on instrument transformer circuit VA
3.17.8 Conversion time ms
3.17.9 Scanning resolution bits
3.17.10 Accuracy %
3.17.11 What calculations are supported
3.17.12 How are overflow and conversion failures dealt with?
3.17.13 Method of isolation
3.17.14 Impulse voltage withstand kV kV
3.18.0 DIRECT AC CONNECTION CURRENT
3.18.1 Module designation
3.18.2 Literature reference for principle of operation
3.18.3 Maximum number of modules processor
3.18.4 Number of inputs per module
3.18.5 Input current ranges A
3.18.6 Input filter attenuation at 50 Hz dB
3.18.7 Burden on instrument transformer circuit VA
3.18.8 Conversion time ms
3.18.9 Scanning resolution bits
3.18.10 Accuracy %
3.18.11 What calculations are supported
3.18.12 How are overflow and conversion failures dealt with?
3.18.13 Method of isolation
3.18.14 Impulse voltage withstand kV kV
Section VI – Requirements Page 120 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
4.0 BCU SOFTWARE
4.1.0 GENERAL REQUIREMENTS
4.1.1 Program structure
4.1.2 System software
4.1.3 Standard functions programs
4.1.4 User functions programs
4.2 CAPABILITY OF:
4.2.1 BCU program downloading from Control Centre
4.2.2 Application configuration from Control Centre
4.2.3 Remote selection of processing parameters
4.2.4 Selection of communication protocols
4.2.5 Selection of operation modes (cyclic, polled, etc.)
4.2.6 Appropriate protection of software against power failure
4.2.7 Automatic BCU re-start without software down-loading
4.3 SYSTEM SOFTWARE
4.3.1 Operating System (Monitor) Functions and capabilities
4.3.2 Calendar program Type, functions and capabilities
4.3.3 Time Synchronization Program Functions and capabilities
4.3.4 Data Base Updating program Functions and capabilities
4.3.5 Testing and Diagnostics Programs Functions and capabilities Yes
4.4.0 STANDARD FUNCTIONS PROGRAMS
4.4.1 Data Communication Programs: Functions and capabilities
4.4.2 Capability of communication protocol selection
Section VI – Requirements Page 121 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
4.4.3 Capability of operating modes selection
4.5.0 ANALOGUE MEASUREMENTS, SCANNING AND TRANSMISSION PROGRAMS
4.5.1 Capabilities of adjustments
4.5.2 Transducers constants
4.5.3 Periodic transmission/transmission by exception
4.5.4 Automatic checking of A/D-conversion accuracy
4.5.5 Smoothing
4.5.6 Threshold values
4.5.7 Limits
4.5.8 Scan duration (range)
4.5.9 Cycle duration (range) s
4.5.10 Priority of transmission s
4.5.11 Digital Input Data Scanning and transmission Program
4.6.0 FUNCTIONS AND CAPABILITIES
4.6.1 Capability of adjustments;
4.6.2 Scan duration (range) ms
4.6.3 Transient time of status information (range)
4.6.4 Cycle duration (range) ms
4.6.5 Debouncing filter s
4.6.6 Suppression of intermediate status information
4.6.7 Time tagging
4.6.8 Transmission mode
4.6.9 Priority of transmission
4.7 ALARM AND EVENT HANDLING
Section VI – Requirements Page 122 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
4.7.1 Grouping of alarms and events
4.7.2 Maximum number of groups
4.8 SUPERVISORY CONTROL PROGRAMS: FUNCTIONS AND CAPABILITIES
4.8.1 Select before execute
4.8.2 Target check
4.8.3 Cancelling control after adjustable time delay
4.8.4 Capability of adjustments:
4.8.5 Duration of output (range) s
4.8.6 Allowed duration of execution (range) s
4.8.7 Sequence of Events programs
4.8.8 Minimal sequence of events time resolution ms
4.8.9 Sequence of events memory capacity
4.8.10 Events time resolution (adjustable range)
4.8.11 Priority of transmission
4.8.12 Post - Mortem Review / Program
4.8.13 Selection of analogues for post-mortem review
4.8.14 Short interval time resolution (adjustable range) s
4.8.15 Long interval time resolution (adjustable range) s
4.9 DATA PROCESSING PROGRAMS: FUNCTIONS AND CAPABILITIES
4.9.1 Required minimum data processing:
4.9.2 Logic functions
4.9.3 Arithmetical functions (MW , Mvar etc )
4.9.4 Limiting functions s
4.9.5 Comparative functions
Section VI – Requirements Page 123 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
4.9.6 Time functions
5.0 GATEWAY SOFTWARE
5.1.0 GENERAL REQUIREMENTS
5.1.1DATABASE MANAGEMENT APPLICATION
5.1.2ALARM AND EVENT GROUPING
5.1.3 Alarm and Event Separation for NCC and DCC
5.1.4Alarm and Event storage and remote / local access
5.2.0 CAPABILITY OF:
5.2.1 Gateway program downloading from Control Centre
5.2.2 Application configuration from Control Centre
5.2.3 Remote selection of processing parameters
5.2.4 Selection of communication protocols
5.2.5 Selection of operation modes (cyclic, polled, etc.)
5.2.6 Appropriate protection of software against power failure
5.2.7 Automatic re-start without software down-loading
5.0 SYSTEM SOFTWARE
5.3.1 Operating System (Monitor) Functions and capabilities
5.3.2 Calendar program Type, functions and capabilities
5.3.3 Time Synchronization Program Functions and capabilities
5.3.4 Data Base Updating program Functions and capabilities
5.3.5 Testing and Diagnostics Programs Functions and capabilities
6.0 TRANSDUCERS
6.1.0 Current transducer.
Section VI – Requirements Page 124 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
6.1.1 Manufacturer
6.1.2 Type reference
6.1.3 Number
6.1.4 Principle (e.g. 3 phase, 3 wire, unbalanced)
6.1.5 Output range mA
6.1.6 Input ranges available A
6.1.7 Burden on instrument transformer circuit VA
6.1.8 Insulation level kV
6.1.9 Impulse withstand level kV peak
6.1.10 Minimum accuracy over working range %
6.1.11 Response time (0 to 90%) ms
6.1.12 Mounting details
6.1.13 Operating temperature range °C
6.1.14 Operating humidity range %
6.1.15 Auxiliary supply if required
6.1.16 Voltage range V
6.1.17 Power requirements VA
6.1.18 Frequency Hz
6.1.19 Type of overload protection
6.1.20 Permissible continuous input overload %A
6.2.0 VOLTAGE TRANSDUCER
6.2.1 Manufacturer
6.2.2 Type
6.2.3 Number
Section VI – Requirements Page 125 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
6.2.4 Output range mA
6.2.5 Input ranges available V
6.2.6 Burden on instrument transformer circuit VA
6.2.7 Insulation level kV
6.2.8 Impulse withstand level kV peak
6.2.9 Minimum accuracy over working range %
6.2.10 Response time (0 to 90%) ms
6.2.11 Mounting details
6.2.12 Operating temperature range °C
6.2.13 Operating humidity range %
6.2.14 Auxiliary supply
6.2.15 V range V
6.2.16 Power requirements VA
6.2.17 Frequency Hz
6.2.18 Type of overload protection
6.2.19 Permissible continuous input overload %A
6.3.0 ACTIVE POWER MW
6.3.1 Manufacturer
6.3.2 Type reference
6.3.3 Number
6.3.4 Principle (e.g. 3 phase, 3 wire, unbalanced)
6.3.5 Output range mA
6.3.6 Input ranges available
6.3.7 Voltage V
Section VI – Requirements Page 126 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
6.3.8 Current A
6.3.9 Burden on instrument transformer circuit
6.3.10 Current Transformer (CT) VA
6.3.11 Voltage Transformer (VT) VA
6.3.12 Insulation level kV
6.3.13 Impulse withstand level kV peak
6.3.14 Minimum accuracy over working range %
6.3.15 Response time (0 to 90%) ms
6.3.16 Mounting details
6.3.17 Operating temperature range °C
6.3.18 Operating humidity range %
6.3.19 Auxiliary supply if required
6.3.20 Voltage range V
6.3.21 Power requirements VA
6.3.22 Frequency Hz
6.3.23 Type of overload protection
6.3.24 Permissible continuous input overload
6.3.25 Voltage %V
6.3.26 Current %A
6.4 REACTIVE POWER MVARS
6.4.1 Manufacturer
6.4.2 Type reference
6.4.3 Number
6.4.4 Principle (e.g. 3 phase, 3 wire, unbalanced)
Section VI – Requirements Page 127 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
6.4.5 Output range mA
6.4.6 Input ranges available
6.4.7 Voltage V
6.4.8 Current A
6.4.9 Burden on instrument transformer circuit
6.4.10 Current Transformer (CT) VA
6.4.11 Voltage Transformer (VT) VA
6.4.12 Insulation level kV
6.4.13 Impulse withstand level kV peak
6.4.14 Minimum accuracy over working range %
6.4.15 Response time (0 to 90%) ms
6.4.16 Mounting details
6.4.17 Operating temperature range °C
6.4.18 Operating humidity range %
6.4.19 Auxiliary supply
6.4.20 Voltage range V
6.4.21 Power requirements VA
6.4.22 Frequency Hz
6.4.23 Type of overload protection
6.4.24 Permissible continuous input overload
6.4.25 Voltage %V
6.4.26 Current %A
6.5 FREQUENCY
6.5.1 Manufacturer
Section VI – Requirements Page 128 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
6.5.2 Type
6.5.3 Number
6.5.4 Measurement range Hz
6.5.5 Output range mA
6.5.6 Input ranges available V ac
6.5.7 Burden on instrument VT circuit VA
6.5.8 Insulation level kV
6.5.9 Impulse withstand level kV peak
6.5.10 Minimum accuracy over working range %
6.5.11 Response time (0 to 90%) ms
6.5.12 Mounting details
6.5.13 Operating temperature range °C
6.5.14 Auxiliary supply
6.5.15 Voltage range V
6.5.16 Power requirements VA
6.5.17 Frequency Hz
6.5.18 Type of overload protection
6.5.19 Permissible continuous input overload %V %
6.6 POWER FACTOR
6.6.1 Manufacturer
6.6.2 Type
6.6.3 Number
6.6.4 Measurement range
6.6.5 Output range mA
Section VI – Requirements Page 129 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
6.6.6 Input ranges available V ac
6.6.7 Burden on instrument VT circuit VA
6.6.8 Insulation level kV
6.6.9 Impulse withstand level kV peak
6.6.10 Minimum accuracy over working range %
6.6.11 Response time (0 to 90%) ms
6.6.12 Mounting details
6.6.13 Operating temperature range °C
6.6.14 Auxiliary supply
6.6.15 Voltage range V
6.6.16 Power requirements VA
6.6.17 Frequency Hz
6.6.18 Type of overload protection
6.6.19 Permissible continuous input overload %
6.7 COMBINED ACTIVE AND REACTIVE POWER
6.7.1 Manufacturer
6.7.2 Type
6.7.3 Number
6.7.4 Measurement range
6.7.5 Input ranges available
6.7.6 Voltage V ac
6.7.7 Current A
6.7.8 Burden on instrument transformer circuit
6.7.9 Current Transformer (CT) VA
Section VI – Requirements Page 130 of 677Environmental Guidelines for Contractors
H. SUBSTATION CONTROL SYSTEM UNIT DATA
Required Offered
6.7.10 Voltage Transformer (VT) VA
6.7.11 Insulation level kV
6.7.12 Impulse withstand level kV peak
6.7.13 Minimum accuracy over working range %
6.7.14 Response time (0 to 90%) ms
6.7.15 Number of analogue outputs
6.7.16 Analogue output range mA
6.7.17 Calculations available
6.7.18 Serial output protocol
6.7.19 Mounting details
6.7.20 Operating temperature range °C
6.7.21 Auxiliary supply
6.7.22 Voltage range V
6.7.23 Power requirements VA
6.7.24 Frequency Hz
6.7.25 Type of overload protection
6.7.26 Permissible continuous input overload
6.7.27 Voltage %V
6.7.28 Current %A
Section VI – Requirements Page 131 of 677Environmental Guidelines for Contractors
I. DIESEL GENERATOR UNIT DATA
Required Offered
1. GENERATOR
1. Details of automatic voltage regulating equipment
1.1 Manufacturer
1.2 Rated power kVA 500
1.3 Output voltage V 400
1.4 Rated power factor Cos Φ 0.8
1.5 Frequency Hz 50
1.6 Dimensions
Diesel Generator mxmxm
1.7 Limits of voltage regulation %
1.8 Manufacturer system in accordance with ISO 9000, 9001, 9002, 9003 and 9004
yes
2 ENGINE
2.1 Rating for site conditions kW
2.2 No and arrangement of cylinders
2.3 Any limitation in part load performance
2.4 Fuel consumption: -At rated outputAt ¾ rated outputAt ½ rated output
l/h
2.5 Lubricating oil consumption at rated output l/h
Section VI – Requirements Page 132 of 677Environmental Guidelines for Contractors
I. DIESEL GENERATOR UNIT DATA
Required Offered
2.6 Time taken for engine to run up to speed and be ready to receive load sec
2.7 Maximum load increment which may be applied with the voltage and frequency maintained within the limits specified
kVA
2.8 Estimated running hours between overhauls
Top Overhaul Hr
Major Overhaul Hr
2.9 Bulk fuel tank
Capacity l
Dimension m
2.10 Daily service fuel tank
Capacity l
Dimension m
2.11 Radiator
Air flow from radiator m3/s
Temperature rise of discharge air C
Dimension of radiator m
3 ELECTRICAL EQUIPMENT
3.1 Number of batteries for generating set and type Electrical Starter
3.2 Voltage of each battery V
3.3 Battery capacity for generating set A-h
Section VI – Requirements Page 133 of 677Environmental Guidelines for Contractors
I. DIESEL GENERATOR UNIT DATA
Required Offered
3.4 Voltage of engine starting system V
Section VI – Requirements Page 134 of 677Environmental Guidelines for Contractors
Section VI – Requirements Page 135 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
A. LVAC SWITCHGEAR (415/240 V, 50 Hz)
1. GENERAL
1.1. Rated voltage V 415
1.2. Rated frequency Hz 50
2. LVAC SWITCHBOARD
2.1. Manufacturer
2.2. Type designation
2.3. Type of switchboard Metal-clad
withdrawable type,
multi-tier
2.4. Standards IEC 60439
2.5. Number of years equipment of identical design has been in service
2.6. Rated current of busbars at 50C ambient temperature
A
2.7. Busbar cross section mm2
Section VI – Requirements Page 136 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
2.8. Busbar insulation material
2.9. Busbar insulation maximum working temperature C
210. Temperature rise on continuous operation at rated current
at 50C
2.11 Rated short-time withstand current (1 s) kA 50
2.12 Rated peak withstand current kA 125
2.13 Test voltage (1 min) V 2500
2.14. Impulse Withstand Voltage kVp
2.15. Type of internal barriers, shutters, etc. Metallic
2.16. Degree of protection IP51
2.17. Overall dimensions per cubicle
Width mm
Depth mm
Height mm max 2250
Weight kg
Section VI – Requirements Page 137 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
2.18. Method of circuit breaker withdrawal manual
3. CIRCUIT BREAKER
3.1. Manufacturer
3.2. Type designation
3.3. Type Air, withdrawable
3.4. Number of poles 3
3.5. Standard IEC 60947-2
3.6. Rated current at 50C A
3.7. Rated short-time withstand current (1 s) kA 50
3.8. Rated peak withstand current kA
3.9. Rated symmetrical breaking current kA
3.10. Rated making current kA
Section VI – Requirements Page 138 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
3.11. Breaking time s
3.12. Material of:
moving contacts
fixed contacts
3.13. Design of:
moving contacts
fixed contacts
3.14. Operating mechanism
Motor rated power W
Motor operating voltage V
3.15. Weight of draw-out unit kg
3.16 Protection Module
Type
Phase protection functions L,S,I
Neutral protection functions
Ground/Earth protection functions G
3.17. Type tests
3.17.1. Temperature Rise Test
Section VI – Requirements Page 139 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
Have heating tests at continuous rated normal current been carried out ?
report number
date
3.17.2. Basic Impulse Voltage Type Test:
Has B.I.V test been completed?
circuit breaker report number date
3.17.3 Life Test:
Has 2000 operating life test at no load (de-energised) been carried out?
report number
date
4. MOULDED CASE CIRCUIT BREAKERS (MCCBs)
4.1. Manufacturer
4.2. Type designation
4.3. Withdrawable MCCBs type yes
Section VI – Requirements Page 140 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
4.4. Number of poles 3
4.5. Standards IEC 60947-2
4.6. Rated current at 50C A
4.7. Rated short-time withstand current (1 s) kA
4.8. Rated peak withstand current kA
4.9. Rated breaking current kA
4.10. Remote signaling yes
4.11. Operating mechanism
4.12. Mass
4.13 Protection Module
Type
Phase protection functions L, I
Ground (Earth) protection function
5. CURRENT TRANSFORMERS
Section VI – Requirements Page 141 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
5.1. Manufacturer
5.2. Type
5.3. Type of primary winding (e.g. bar, wound, etc.)
5.4. Standards IEC 60044-1
5.5. Rated voltage kV
5.6. Rated lightning impulse withstand voltage phase to earth
kV
5.7. Rated power frequency withstand voltage phase to earth
kV
5.8. Partial discharge test voltage kV
5.9. Rated frequency Hz 50
5.10. Rated continuous thermal current at 50oC
5.11. Rated short-time withstand current (1 s) kA
5.12. Rated dynamic current kA
5.13. Line current transformer
Section VI – Requirements Page 142 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
5.13.1. Type designation
5.13.2. Number of cores 2
5.13.3. Rated extended primary current % 120
5.13.4. Ratio (TR = turns ratio)
I core II core
A
A
1/750 (TR)
750/1
5.13.5. Class
I core II core
PX
1.0 / FS:5
5.13.6. Knee point voltage (EK)
I core II core
V
V N/A
5.13.7. Exciting current (IE) at EK
I core II core
A
A N/A
5.13.8. Rated output (burden to be 25-100% rated burden) I core II core
VA
VA
N/A
5.14. Neutral current transformer
5.14.1. Type designation
5.14.2. Number of cores 1
Section VI – Requirements Page 143 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
5.14.3. Rated extended primary current % 120
5.14.4. Ratio (TR = turns ratio)
I core A 1/750 (TR)
5.14.5. Class
I core PX
5.14.6. Knee point voltage (EK)
I core V
5.14.7. Exciting current (IE) at EK
I core A
5.14.8. Rated output (burden to be 25-100% rated burden) I core VA N/A
5.14.9. Total mass of one current transformer complete kg
All Class PX CTs shall have a rated secondary current, ISN
6. INSTRUMENTS
6.1. Manufacturer
6.2. Standards IEC 60051
6.3. Type designation
Ammeter Voltmeter
Section VI – Requirements Page 144 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
6.4. Total scale range
Ammeter Voltmeter
6.5. Dimensions mm 96 x 96
6.6. Accuracy 1.5
6.7. Selector Switches
Ammeter Voltmeter
7.1. Restricted Earth Fault Protection
7.1.1. Manufacturer
7.1.2. Type reference
7.1.3. Relay design (electromechanical, numerical) Numerical
7.1.4. Minimum fault setting (% of CT rating) %
7.1.5. Operating time at 5 x setting ms
7.1.7. State principle of operation, i.e.
H - high impedance
L - low impedance
H
Section VI – Requirements Page 145 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
7.1.8. Current transformer requirements:
Required knee point voltage, Vk CT maximum winding resistance Magnetising current at Vk
V
A
7.1.11. Tripping contacts rating
7.2. Undervoltage / Overvoltage Relay
7.2.1. Manufacturer
7.2.2. Type reference
7.2.3. Relay design (electromechanical, static)
7.2.4. Total scale range V
7.2.5. Operate time at instantaneous voltage change for undervoltage / overvoltage relay
ms
7.2.6. Reset ratio overvoltage / undervoltage %
8. Manufacturer quality system in accordance with ISO 9000, 9001, 9002, 9003 and 9004
yes
9. Type test certificate to be issued by independent laboratory or independently witnessed type test
yes
Section VI – Requirements Page 146 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
certificate available
Section VI – Requirements Page 147 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
B D.C. SYSTEMS
1. 110 V D.C SYSTEM - SUBSTATION SERVICES SUPPLY
1.1. 110 V Battery Units
1.1.1 Manufacturer
1.1.2 Type designation
1.1.3 Number of battery units 2 x 50%
1.1.4 Type of cell Nickel-Cadmium
1.1.5 Operating voltage per cell V
1.1.6 Number of cells
Section VI – Requirements Page 148 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
1.1.7 Standard * IEEE 1115 for
calculation
* IEC 60623, 60478,
60439 for equipment
1.1.8 Discharge capacity:
10 hour rate Ah min. 250 (to be
confirmed by
calculation)
5 hour rate Ah
3 hour rate Ah
1 hour rate Ah
30 minute rate Ah
1.1.9 Final cell voltage after discharge:
10 hour rate V 1.14
5 hour rate V
3 hour rate V
1 hour rate V
30 minute rate V
1.1.10 Ampere hour efficiency:
10 hour rate %
5 hour rate %
3 hour rate %
1 hour rate %
1.1.11 Watt hour efficiency:
10 hour rate %
5 hour rate %
3 hour rate %
1 hour rate %
30 minute rate %
1.1.12. Maximum charging voltage per cell V
Section VI – Requirements Page 149 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
1.1.13. Normal charging rate range A
1.1.14. Maximum charging rate range A
1.1.15. Float charging rate A
1.1.16. Boost charging rate A
1.1.17. Normal voltage across battery on float charge V
1.1.18. Voltage per cell on float charge V
1.1.19. Normal voltage across battery on boost charge V
1.1.20. Voltage per cell on boost charge V
1.1.21. Overall dimensions of one cell mm
1.1.22. Quantity of electrolyte per cell Litres
1.1.23. Overall dimensions of each stand mm
1.1.24.1
Number of stands
1.1.25.1
Number of tiers
1.1.26.1
Material and cross section of connections: between cells between tiers between stands to battery fuse box
mm2
mm2
mm2
mm2
1.1.27.1
Method of treating copper connection against corrosion
1.1.28. Method of protecting copper connections against accidental short circuiting
1.1.29. Estimated short circuit current from fully charged battery
A
Section VI – Requirements Page 150 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
1.1.30. Anticipated life of electrolyte under actual operating conditions Years
1.1.31. Anticipated life of electrolyte under actual operating conditions Years
1.1.32.1
Operating temperatures: Normal operation
maximum
minimum Emergency discharge
maximum
minimum
C
C
C
C
1.2 110 V D.C Battery Chargers
1.2.1. Manufacturer
1.2.2. Type designation
1.2.3. Degree of protection IP 51
1.2.4. Number of chargers 2 x 100%
1.2.5. Type Thyristor Controlled
1.2.6. Charging characteristic
1.2.7. Input voltage V 3 Phase, 415
1.2.8. Input frequency and range Hz 50
1.2.9. Input power kVA
1.2.10. Minimum working power factor
1.2.11. Rated output power kW
1.2.12. Output voltage range:
Section VI – Requirements Page 151 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
float charge V
boost charge V
1.2.13. Continuous output current range:
float charge A
boost charge A
1.2.14. Accuracy of output voltage %
1.2.15. Overload range %
1.2.16. Voltage ripple %
1.2.17. Ripple frequency Hz
1.2.18. Means of adjusting output
1.2.19. Details of any forced cooling equipment for chargers
1.2.20. Ambient temperature range C
1.2.21. Ambient relative humidity range %
1.2.22. Mean time between failure (MTBF) Years
1.2.23. Overall dimensions (shall be a separate free-standing panel/cubicle)
mm
1.2.24. Weight kg
1.2.25. Boost charge maximum permitted constant potential per cell
V
1.2.26. Boost charge maximum permitted current as percentage of 5 hour capacity
%
1.2.27. Time to be re-charge to 90% capacity at maximum permitted voltage and current
hrs
1.3. Battery Fuse Boxes
Section VI – Requirements Page 152 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
1.3.1. Manufacturer
1.3.2. Type designation
1.3.3. Degree of protection IP 51
1.3.4. Fuse rated current at 50oC
1.3.5. Remote signalling yes
1.4. 110 V D.C. Switchboards
1.4.1. Manufacturer
1.4.2. Type designation
1.4.3. Degree of protection IP 51
1.4.4. Standards IEC 60439
1.4.5. Rating voltage V 110
1.4.6. Rated current of busbars at 50oC ambient temperature
A
1.4.7. Busbar cross section mm2
1.4.8. Busbar insulation material
1.4.9. Number of circuits
Section VI – Requirements Page 153 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
1.4.10. Main isolator rating A
1.4.11. Main fuse rating A
1.4.12. Single line diagram number
1.4.13. Arrangement drawing number
1.4.14. Details of Contactors:
Manufacturer
Type designation
Type
Site current rating (at 50°C) A
Rated breaking capacity kA
Short time current (1 s) kA
Maximum operating time
opening msec
closing msec
Voltage / power coil rating V/W
Typical circuit diagram number
1.4.15. Details of Earth Fault Protection:
Manufacturer
Type Designation
Brochure number
1.4.16. Details of Undervoltage / Overvoltage Protection:
Manufacturer
Type Designation
Brochure number
1.4.17. Instruments
Manufacturer Voltmeter (type) Ammeter (type) Instruments
Section VI – Requirements Page 154 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
1.4.18 Details of Moulded Case Circuit Breakers (MCCBs)
Manufacturer Type designation Number of poles Standards Rated current at 50C Rated short-time withstand
current (1 s) Rated breaking capacity Remote signaling
A
kA
kA
Yes
1.4.19 Details of Miniature Circuit Breakers (MCBs) Manufacturer Type designation Number of poles Standards Rated current at 50C Rated short-time withstand
current (1s) Breaking capacity at Remote signalling
A
kA
kA
Yes
Manufacturer quality system in accordance with ISO 9000, 9001, 9002, 9003 and 9004 Yes
Section VI – Requirements Page 155 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
Type test certificate to be issued by independent laboratory or independently witnessed type test certificate available
Yes
C. 240 V AC UNINTERRUPTIBLE POWER SUPPLY
1.C
GENERAL
The uninterruptible power supply (UPS) shall consist but not be limited to the following items:
two thyristor controlled 110 V DC / 240 V AC inverters
yes
two static interrupters and transfer switches
yes
one 240/240 V single phase isolating by-pass transformer
yes
two manual by-pass switchesyes
one UPS distribution boardyes
Section VI – Requirements Page 156 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
2. INVERTER
2.1. Manufacturer
2.2. Type designation
2.3. Degree of protectionIP51
2.4. Rated output powerVA min 1200 (to be
confirmed by
calculation)
2.5. Rated input voltage and rangeV%
2.6. Rated input currentA
2.7. Rated output voltageV
2.8. Steady state voltage variation%
2.9. Rated output currentA
2.10. Rated output frequencyHz
2.11. Steady state frequency variation%
2.12. Total harmonic distortion%
2.13. Rated output power factor
2.14. Maximum harmonic distortion:
at any single frequency%
at all frequencies%
2.15. Radio frequency interference (RFI) classification
2.16. Output voltage rise time on turn-onms
2.17. Output voltage decay time on turn-offms
2.18. Maximum transient voltage variation after full load acceptance or rejection for:
1 cycle %
0.1 s %
1 s %
Section VI – Requirements Page 157 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
2.19. Method of cooling
2.20. Ambient temperature range C
2.21. Maximum temperature rise (inside) C
2.22. Ambient relative humidity %
2.23. Method of protecting inverters against high intensity D.C voltage surges
2.24. Mean time between failure (MTBF) Years
2.25. Dimensions mm
2.26. Weight kg
3. STATIC SWITCH
Bidder shall fulfil the detailed description of offered static switch possibility with data and diagram
4. ISOLATION BY-PASS TRANSFORMER
Section VI – Requirements Page 158 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
4.1. Manufacturer
4.2. Standard applied
4.3. Type designation
4.4. Maximum continuous capacity VA
4.5. Number of phase 1
4.6. Rated voltage under full load V
4.7. Protection class IP
4.8. Dimensions overall mm
4.9. Total weight kg
5. MANUAL BY-PASS SWITCH
5.1. Manufacturer
Section VI – Requirements Page 159 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
5.2. Type of designation
5.3. Rated current at 50°C A
6. DISTRIBUTION BOARD
6.1. Manufacturer
6.2. Type designation
6.3. Degree of protection IP 51
6.4. Busbar insulation material
6.5. Number of circuits
6.6. Details of Miniature Circuit Breakers (MCBs)
Manufacturer
Type designation
Number of poles
Section VI – Requirements Page 160 of 677Environmental Guidelines for Contractors
K. LV SERVICES EQUIPMENT UNIT DATA
Required Offered
Standards
Rated current at 50oC A
Rated breaking capacity kA
Remote signalling
Manufacturer quality system in accordance with ISO 9000, 9001, 9002, 9003 and 9004
yes
Type test certificate to be issued by independent laboratory or independently witnessed type test certificate available yes
Section VI – Requirements Page 161 of 677Environmental Guidelines for Contractors
L. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA
Required Offered
1. Power Transformer
Manufacturer & Place of manufacturing
Type designation
Type
Three phase Autotransformer, oil-immersed, core type with stabilising tertiary winding
Yes
Standards IEC 60076, 60137, 60214
Altitude (If > 1000 m) m
Ambient temperature (Zone 1 – within IEC reference values, e.g. inland at altitude)
- Maximum- Average of hottest month- Annual average
Ambient temperature (Zone 2 – within IEC reference values, e.g. Coastal with high annual average)
- Maximum- Average of hottest month- Annual average
oC
oC
oC
oC
oC
oC
40
30
20
45
35
30
Section VI – Requirements Page 162 of 677Environmental Guidelines for Contractors
L. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA
Required Offered
Mounting Outdoor
Rated voltage ratio (HV/LV) kV 400/220
Rated frequency Hz 50
Vector group YNa0(d)
Cooling – 2-stage ONAN/ONAF1/ONAF2 or
ONAN/ONAF/OFAF
Function of tertiary winding (TV) Aux. supply
Method of earthing
- HV (Series) winding Solid
- LV (Common) winding Solid
- TV winding Grounded at one point
Type of windings (graded/non-graded)
- HV winding (Series) Graded
- LV winding (Common) Graded
- TV winding Non-graded
Rated voltage of windings (Ur)
- HV winding kV 400
Section VI – Requirements Page 163 of 677Environmental Guidelines for Contractors
L. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA
Required Offered
- LV winding- TV windingNote*: approximate; to manufacturer’s preference
kV
kV
220
11*
Highest voltage for equipment (Um)
- HV winding kV 420
- LV winding kV 245
- TV winding kV 12*
Rated lightning impulse withstand voltage at:
- HV terminal kV 1425
- LV terminal kV 1050
- Neutral terminal kV 170
- TV winding ≥75
Rated switching impulse voltage
- HV terminals- LV terminals
kV
kV
1050
850
Rated power frequency withstand voltage at
- HV terminal (design value only)- HV test value (IVPD enhancement level)- HV test value (IVPD PD measurement))
kV
kV
kV
630
416
365
- LV terminal (Design value) kV 460
- Neutral terminal kV 70
- TV terminal kV ≥28
Section VI – Requirements Page 164 of 677Environmental Guidelines for Contractors
L. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA
Required Offered
Rated power at site conditions (ONAF2 or OFAF) MVA 200
Rated power at site conditions (ONAN) MVA 120
Rated power of tertiary at site conditions (Full cooling) MVA 5
Maximum temperature rise at rated power at (IEC shown, Zone 1)):
- Windings K 65
Hot spot of windings K 78
- Top oil K 60
- Oil at inlet of cooler K
- Oil at outlet of cooler K
- Core K
Maximum temperature rise at rated power at (,Zone 2):
- Windings- Hot spot of windings- Top oil
- Oil at inlet of cooler- Oil at outlet of cooler- Core
K
K
K
K
K
K
55
68
50
Temperature of winding due to short circuit duration of 2 s at rated load
- HV side short circuit rating of 50kA oC 250
Section VI – Requirements Page 165 of 677Environmental Guidelines for Contractors
L. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA
Required Offered
- LV side short circuit rating of 40 kA oC 250
No-load losses at rated voltage and rated frequency kW
Load losses at 75C, and rated frequency:
- ONAF2 or OFAF rated power and principal tapping
- ONAF2 or OFAF rated power and maximum voltage ratio
- ONAF2 or OFAF rated power and minimum voltage ratio
- At ONAN rated power and principal tapping
Total auxiliary losses at full load kW
Maximum current density at rated power:
- HV (Series) winding A/mm2
- LV (Common) winding A/mm2
- TV winding A/mm2
- Tapping A/mm2
Symmetrical short circuit through current (duration 2 s) at system fault rating
- HV terminals (50 kA) kA
- LV terminals (40 kA) kA
Magnetising current (HV winding)
- At 90% rated voltage A
- At 100% rated voltage A
- At 110% rated voltage A
Section VI – Requirements Page 166 of 677Environmental Guidelines for Contractors
L. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA
Required Offered
Maximum flux density in iron at rated voltage, power frequency and principal tapping at:
- Wound limbs T
- Unwound limbs T
- Yokes T
- Shields T
Maximum flux density in iron at power frequency, principal tapping and 105% rated voltage at:
- Wound limbs T
- Unwound limbs T
- Yokes T
- Shields T
Type of tap changing On-load
Manufacturer of on-load tap changer
Type designation of on-load tap changer
OLTC location (Provisional) LV line end
Type of flux voltage variation C.F.V.V
Tapping range (Provisional) +5%/-15%
Section VI – Requirements Page 167 of 677Environmental Guidelines for Contractors
L. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA
Required Offered
Tapping step 1.25%
Number of steps (positions) 16 (17)
Arrangement of tappings (Linear, Coarse/Fine, Reversing)
Automatic voltage control Yes
Impedance voltage range at 75C, rated frequency and full rating (Provisional):
- At principal tapping > 14%
- At maximum voltage ratio >14%
- At minimum voltage ratio >14%
Resistance of winding at 75C and principal tapping:
- HV side /phase
- LV side /phase
Terminal connection
- HV terminal Outdoor bushing
- LV terminal Outdoor bushing
- Neutral terminal Outdoor bushing
- TV terminal Outdoor bushing
Section VI – Requirements Page 168 of 677Environmental Guidelines for Contractors
L. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA
Required Offered
Bushing Creepage Distance (IEC class IV = 31mm/kV
- HV terminal (420 kV)- LV terminal (kV)- Neutral terminal (36 kV)- TV terminal (12 kV)
mm
mm
mm
mm
13020
7595
≥900
300
Cable box insulation N/A
- HV terminal “
- LV terminal “
- HV neutral terminal “
- LV neutral terminal “
Isolating links for test purposes N/A
- HV terminal “
- LV terminal “
- Tertiary earthing terminal “
Current transformers
HV-Bushing turrets Refer to Tender Drawings
- Number of cores
- Rated extended primary current
- Ratio (TR = turns ratio)
I core A
II core A
III core A
Section VI – Requirements Page 169 of 677Environmental Guidelines for Contractors
L. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA
Required Offered
- Class
I core
II core
III core
- Knee point voltage (Ek)
I core V
II core V
III core V
- Exciting current (IE ) at Ek
I core mA
II core mA
III core mA
- Rated output (Burden to be 25-100% rated burden)
I core VA
II core VA
III core VA
LV Line (Only AIS connections)
- Number of cores
- Rated extended primary current
- Ratio (TR = turns ratio)
- Class
- Knee point voltage (Ek)
- Exciting current (IE ) at Ek
- Rated output (Burden to be 25-100% rated burden)
Section VI – Requirements Page 170 of 677Environmental Guidelines for Contractors
L. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA
Required Offered
Neutral (HV REF)
- Number of cores
- Rated extended primary current
- Ratio (TR = turns ratio)
I core A
- Class
I core
- Knee point voltage (Ek)
I core V
- Exciting current (IE ) at Ek
I core mA
- Rated output (Burden to be 25-100% rated burden)
I core VA
Neutral – ends
- Number of cores
- Rated extended primary current
- Ratio (TR = turns ratio)
I core A
- Class
I core
- Knee point voltage (Ek)
I core V
- Exciting current (IE ) at Ek
I core mA
- Rated output (Burden to be 25-100% rated burden)
Section VI – Requirements Page 171 of 677Environmental Guidelines for Contractors
L. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA
Required Offered
I core VA
All class PX CTs shall have a rated secondary current, ISN
A
Number of coolers per transformer
Number of stand-by coolers
Number of stand-by fans
Rating of each cooler kW
Oil
- Manufacturer
- Type designation
- Standards IEC 60296
- Minimum flash point C
- Viscosity
at 20C mm2/s
at 50C mm2/s
at 80C mm2/s
- Maximum dielectric strength for 1 min. kV
- Dielectric factor
- Acidity (neutralization value) mgKOH/g
Section VI – Requirements Page 172 of 677Environmental Guidelines for Contractors
L. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA
Required Offered
Oil preservation system Air-bag
Types and arrangement of winding:
- HV (Series) winding
- LV (Common) winding
- TV winding
- Regulating
- Windings arrangement (i.e. core/TV/LV/HV/Taps)
Conductor Material (e.g., copper, work hardened copper, etc.)
- HV (Series) windings
- LV (Common)windings
- TV windings
- Regulating windings
Conductor insulation:
- HV (Series) windings
- LV (Common) windings- TV windings- Regulating windings
- Connecting leads from winding to tap changer
Calculated thermal time constant
- ONAN cooling min
- Full cooling min
Section VI – Requirements Page 173 of 677Environmental Guidelines for Contractors
L. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA
Required Offered
Oil circulation (i.e., natural/partially directed/directed)
To the windings:
- HV windings (Series)
- LV windings (Common)
- Regulating windings
- TV windings
Through the windings:
- HV windings (Series)
- LV windings (Common)
- Regulating windings
- TV windings
Core construction:
- Taped/banded/bolted limbs
- Taped/banded/bolted yokes
- Taping/banding material
- Number of limbs
- Number of limbs wound
- Type of joint in magnetic core (90% butt, overlap, mitre, etc.)
- Type of core steel
- Specific loss of core steel at 1.5 tesla W/kg
Thickness of transformer tank
- Sides mm
Section VI – Requirements Page 174 of 677Environmental Guidelines for Contractors
L. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA
Required Offered
- Bottom mm
- Top mm
Material of transformer tank
Thickness of radiator plates mm
Total volume of conservator Litre
Minimum volume of conservator between highest and lowest levels as percentage of total cold oil at 15C volume of transformer 7.5%
Volumetric expansion of oil from 0 to 90C m3
Pressure increase inside tank due to expansion of oil
Masses of transformer
- Core and coils kg
- Total mass excluded oil kg
- Oil mass in tank kg
in radiators kg
total kg
- Total mass kg
Mass of transformer as arranged for transport (heaviest part)
kg
Section VI – Requirements Page 175 of 677Environmental Guidelines for Contractors
L. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA
Required Offered
Dimensions of transformer arranged for transport
- Height m
- Width m
- Length m
Filling medium of transformer tank for shipment
Maximum sound pressure level (NEMA TR1 – 5dB(A)) dB(A) 74
Conservator vessel, radiators, fan grilles, control boxes or cubicles and pipework anticorrosion protection
Hot dip galvanized and painted
Tank anticorrosion protection
Supply voltage for transformer auxiliaries V 415/240 AC
Control/Protection voltage V 110 DC
Manufacturer quality assurance Yes
- According to ISO 9000, 9001, 9002, 9003 and 9004 Validity
Type test certificate to be issued by:
- Independent laboratory or independently witnessed type test certificate
Yes
1.78 Special Tests to be performed:
As Type test = T
As Routine test = R
Section VI – Requirements Page 176 of 677Environmental Guidelines for Contractors
L. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA
Required Offered
- Measurement of zero-sequence impedance- Determination of sound levels- Measurement of harmonics of no-load current- Frequency response analysis (FRA)- Check of external coating- Short circuit withstand test/calculations
Yes (T)
Yes (T)
Yes (T)
Yes (R)
Yes R)
Yes (Calculation)
Section VI – Requirements Page 177 of 677Environmental Guidelines for Contractors
L. 400 kV 100 MVAr SHUNT REACTOR UNIT DATA
Required Offered
1. Shunt Reactor
1.1 Manufacturer & Place of manufacturing
1.2 Type designation
1.3 Type Outdoor, Oil Immersed
1.4 Construction (Gapped core/Air-cored shielded)
1.5 Principal standards IEC 60076-1,-2,-3, -6
1.6 Max ambient (Design) temperature
Annual average temperature
oC
oC
40
30
1.7 Altitude m <1000
1.8 Rated voltage kV 400
1.9 Highest voltage for equipment, Um; Reactor must be able to operate continuously at this voltage.
kV 420
1.10 Rated frequency Hz 50
Section VI – Requirements Page 178 of 677Environmental Guidelines for Contractors
L. 400 kV 100 MVAr SHUNT REACTOR UNIT DATA
Required Offered
1.11 Vector group YN
1.12 Cooling ONAN
1.13 Method of earthing Solid
1.14 Type (graded/non-graded) of windings Graded
1.15 Rated lightning impulse withstand voltage at:
- HV terminals kV 1425
- HV neutral-end terminals kV 125
1.16 Rated switching impulse voltage kV 1050
1.17 Rated power frequency withstand voltage at
- HV terminals (IVPD enhancement) kV 416
- HV neutral-end terminals kV 50
1.18 Rated power:
- Rated current IN
- Max continuous current at Um
A
A
144
152
- Rated (reactive) power at Ur MVAr 100
- Rated reactance XN /phase 1600
- Zero sequence reactance X0
- Mutual reactance XM /phase
Section VI – Requirements Page 179 of 677Environmental Guidelines for Contractors
L. 400 kV 100 MVAr SHUNT REACTOR UNIT DATA
Required Offered
1.19 Magnetic characteristic: Linear to percent of rated voltage
% 105
1.20 Maximum temperature rise at rated power at:
- Windings K 55
- Hot spot of windings K 68
- Top oil K 50
- Oil at inlet of cooler K
- Oil at outlet of cooler K
- Core- Tank Wall
K
K
1.21 Losses at rated voltage and rated frequency kW
1.22 Maximum current density at rated power:
- HV winding A/mm2
1.23 Maximum flux density at rated voltage, power frequency:
- Wound limbs/core packets T
- Yokes- Shield
T
T
1.24 Resistance of winding at 75C and principal tapping: /phase
Section VI – Requirements Page 180 of 677Environmental Guidelines for Contractors
L. 400 kV 100 MVAr SHUNT REACTOR UNIT DATA
Required Offered
1.25 Terminal connection
- Bushing standards- Pollution Class - Is KD Correction factor required? (mm/kV)
IEC 60137
IV (31)
Yes
- HV terminals- Minimum Voltage Class- Minimum Current rating - Manufacturer- Manufacturers designation- Type (OIP/RIP)
kV
A
Outdoor Bushing
420
400
- HV neutral-end terminals- Minimum Voltage Class- Minimum Current rating - Manufacturer- Manufacturers designation- Type (OIP/RIP/Porcelain)
kV
A
Bushing
24
400
Porcelain
1.26 Current transformers
1.26a HV-Bushing turrets (provisional – refer to protection drawings)
- Number of cores 2
- Rated extended primary current
- Ratio (TR = turns ratio)
I core A 800/400/1
II core A 800/400/1
- Class
I core 5P20
II core 5P20
Section VI – Requirements Page 181 of 677Environmental Guidelines for Contractors
L. 400 kV 100 MVAr SHUNT REACTOR UNIT DATA
Required Offered
- Knee point voltage (Ek)
I core V
II core V
- Exciting current (IE ) at Ek
I core mA
II core mA
- Rated output (Burden to be 25-100% rated burden) I core VA
II core VA
1.26b HV Neutral-End provisional – refer to protection drawings)
- Number of cores/phase 1
- Rated extended primary current
- Ratio (TR = turns ratio)
I core 800/400/1
- Class
I core 5P20
- Knee point voltage (Ek)
I core V
- Exciting current (IE ) at Ek
I core mA
- Rated output (Burden to be 25-100% rated burden) I core VA
1.26b HV Neutral
Section VI – Requirements Page 182 of 677Environmental Guidelines for Contractors
L. 400 kV 100 MVAr SHUNT REACTOR UNIT DATA
Required Offered
- Number of cores 1
- Rated extended primary current
- Ratio (TR = turns ratio)
I core 800/400/1
- Class
I core 5P20
- Knee point voltage (Ek)
I core V
- Exciting current (IE ) at Ek
I core mA
- Rated output (Burden to be 25-100% rated burden) I core VA
All class PX CTs shall have a rated secondary current, ISN
A
1.27 Radiators
- Tank or Separate Mounting- Number banks- Number of radiators elements per bank
1.28 Oil
- Manufacturer
- Type designation
- Standards IEC 60296
- Minimum flash point C
Section VI – Requirements Page 183 of 677Environmental Guidelines for Contractors
L. 400 kV 100 MVAr SHUNT REACTOR UNIT DATA
Required Offered
- Viscosity
at 20C mm2/s
at 50C mm2/s
at 80C mm2/s
- Maximum dielectric strength for 1 min. kV
- Dielectric factor
- Acidity (neutralization value) mgKOH/g
1.29 Oil preservation system
- Type (Bag/Membrane)- Breather- Oil Level Gauge Maintenance-free
Magnetic
1.30 Types and arrangement of winding:
1.31 Conductor Material (e.g., copper, work hardened copper, etc.)
1.32 Conductor type (CTC, other)
1.33 Conductor insulation:
1.34 Calculated thermal time constant Hours
1.35 Oil circulation (i.e., natural/partially directed/directed)
To the windings:
Section VI – Requirements Page 184 of 677Environmental Guidelines for Contractors
L. 400 kV 100 MVAr SHUNT REACTOR UNIT DATA
Required Offered
Through the windings:
1.36 Core construction:
- Core segment
- Core gaps
- Taped/banded/bolted limbs
- Taped/banded/bolted yokes- Taped/banded/bolted shield- Taping/banding material
- Number of limbs
- Type of joint in core (90% butt, overlap, mitre, etc.)
- Core steel
- Specific loss of core steel at 1.5 Tesla W/kg
1.37 Thickness of reactor tank
- Sides mm
- Bottom mm
- Top mm
1.38 Material of reactor tank
1.39 Thickness of radiator plates mm
1.40 Total volume of conservator litres
Section VI – Requirements Page 185 of 677Environmental Guidelines for Contractors
L. 400 kV 100 MVAr SHUNT REACTOR UNIT DATA
Required Offered
1.41 Minimum volume of conservator between highest and lowest levels as percentage of total cold oil at 15C volume of transformer 7.5%
1.42 Volumetric expansion of oil from 0 to 90C m3
1.43 Pressure increase inside tank due to expansion of oil
1.44 Masses of reactor
- Core and coils kg
- Total mass excluded oil kg
- Oil mass in tank kg
in radiators kg
total kg
- Total mass kg
1.45 Mass of reactor as arranged for transport (heaviest part) kg
1.46 Dimensions of reactor arranged for transport
- Height m
- Width m
- Length m
1.47 Filling medium of reactor tank for shipment
1.48 Maximum noise level dB(A) 86
Section VI – Requirements Page 186 of 677Environmental Guidelines for Contractors
L. 400 kV 100 MVAr SHUNT REACTOR UNIT DATA
Required Offered
1.49 Conservator vessel, radiators, control boxes or cubicles and pipework anticorrosion protection
Hot dip galvanized and painted
1.50 Tank anticorrosion protection
1.51 Supply voltage for reactor auxiliaries V 415/240 AC
1.52 Control/Protection voltage V 110 DC
1.53 Manufacturer quality assurance
- According to ISO 9000, 9001, 9002, 9003 and 9004; List current accreditation
Yes
1.54 Type test certificate to be issued by:
- Independent laboratory or independently witnessed type test certificate
Yes
1.55 Routine tests
The IVPD test IEC 60076-3:2013 based on Ur
- 1 x 3-phase test- Enhanced level- 1 hour duration- Max PD level during 1 hour stage
kV
kV
kV
kV
pC
To IEC 60076-6
Yes
Yes
416
365
250
Note 2: The method of carrying out loss measurements and any limitations of manufacturer’s test field which restricts the test programme are to be advised with bid documents.
1.56 Special Tests to be performed:
(R=Routine/All units: T=Type/1 unit))
Section VI – Requirements Page 187 of 677Environmental Guidelines for Contractors
L. 400 kV 100 MVAr SHUNT REACTOR UNIT DATA
Required Offered
- Measurement of zero-sequence reactance- Measurement of mutual reactance- Determination of sound levels- Measurement of harmonics- Verification of magnetic characteristic
Yes(T)
Yes(T)
Yes(R)
Yes(R)
Yes (T)
M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF)
UNIT DATA
Required Offered
1. EARTHING/AUXILIARY TRANSFORMER 11/0.415KV; WITH 500 KVA AUXILIARY WINDING
Section VI – Requirements Page 188 of 677Environmental Guidelines for Contractors
M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF)
UNIT DATA
Required Offered
1.Manufacturer & Place of manufacturing
1.1 Type designation
Type Three phase, oil immersed,
core type
Standards IEC 60076-1, -2, -3, -5, -6,-10,
NEMA TR1 (Noise)
Mounting Outdoor, wheel
Rated voltage ratio kV 11/0.415
Rated frequency Hz 50
Vector group ZNyn1
Cooling ONAN
Method of earthing
- HV winding Solid
- LV winding Solid
Type (graded/non-graded) of windings
- HV winding Non-graded
Section VI – Requirements Page 189 of 677Environmental Guidelines for Contractors
M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF)
UNIT DATA
Required Offered
- LV auxiliary winding Non-graded
Rated voltage of windings
- HV winding kV 11
- LV auxiliary winding kV 0.415
Highest voltage for equipment
- HV winding kV 12
- LV auxiliary winding kV 0.433
Rated lightning impulse withstand voltage at HV Terminal kV 75
Rated power frequency withstand voltage at
- HV terminal kV 28
- LV terminal kV 3
- HV neutral terminal kV 28
Rated power at site conditions kVA 500
Limitation and withstanding of fault current in neutral for 30s A 1050
Maximum temperature rise at rated power at:
Section VI – Requirements Page 190 of 677Environmental Guidelines for Contractors
M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF)
UNIT DATA
Required Offered
- Windings K 55
- Hot spot of windings K 68
- Top oil K 50
- Oil at inlet of cooler K
- Oil at outlet of cooler K
- Core K
Temperature rise of winding due to short circuit duration of
2 s and HV side short circuit current of 25 kA
- Copper windings- Aluminium windings
oC
oC
250
200
No load losses at rated voltage and rated frequency kW
Load losses at 75C, and rated frequency, rated power and principal tapping:
Maximum current density at rated power:
- HV winding A/mm2
- LV auxiliary winding A/mm2
Symmetrical short circuit withstand current (duration 2 s) at:
- HV terminal kA 25
- LV auxiliary terminal kA
Magnetising current (HV winding)
- At 90% rated voltage A
Section VI – Requirements Page 191 of 677Environmental Guidelines for Contractors
M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF)
UNIT DATA
Required Offered
- At 100% rated voltage A
- At 110% rated voltage A
Maximum flux density in core at rated voltage, power frequency and principal tapping
T
Type of tap changing Off-load
Type designation of off-load tap changer
Tapped winding HV
Tapping range +5% -5%
Tapping step 2.5%
Number of steps (positions) 4 (5)
Impedance voltage range at 75C and principal tapping:
- At principal tapping > 4%
- At maximum voltage ratio >4%
- At minimum voltage ratio >4%
Section VI – Requirements Page 192 of 677Environmental Guidelines for Contractors
M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF)
UNIT DATA
Required Offered
Resistance of winding at 75C and principal tapping:
- HV side /phase
- LV auxiliary side /phase
Zero phase sequence impedance of inter-star windings at 75C (LV windings open-circuit)
/phase
Zero phase sequence impedance of LV windings at 75C (inter-star windings open-circuit)
/phase
Terminal connection
- HV + HVN terminalNote*: Separable connector, e.g. Euromold or similar
Air-filled cable box*
- LV + LVN terminal Air-filled cable box
Isolating link for test purposes (not required if separable connector allows testing)
- HV terminal No
- LV terminal No
LV fused switch incorporated in LV terminal box A Yes
Section VI – Requirements Page 193 of 677Environmental Guidelines for Contractors
M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF)
UNIT DATA
Required Offered
Mounting of current transformer at
- HV terminal In tank
- Neutral terminals In tank or box
Current transformers Refer to Tender Drawings
HV Line
- Number of cores
- Rated extended primary current
- Ratio (TR = turns ratio)
I core
II core A
- Class
I core
II core
- Knee point voltage (Ek)
I core V
II core V
- Exciting current (IE ) at Ek
I core mA
II core mA
- Rated output (Burden to be 25-100% rated burden)
I core VA
II core VA
HV Neutral
Section VI – Requirements Page 194 of 677Environmental Guidelines for Contractors
M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF)
UNIT DATA
Required Offered
- Number of cores
- Rated extended primary current
- Ratio (TR = turns ratio)
I core A
II core
III core
- Class
I core
II core
III core
- Knee point voltage (Ek)
I core
II core
III core
- Exciting current (IE ) at Ek
I core
II core
III core
- Rated output (Burden to be 25-100% rated burden)
I core
II core
III core
LV Line (Only AIS connections)
- Number of cores
- Rated extended primary current
Section VI – Requirements Page 195 of 677Environmental Guidelines for Contractors
M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF)
UNIT DATA
Required Offered
- Ratio (TR = turns ratio)
I core
- Class
I core
- Knee point voltage (Ek)
I core
- Exciting current (IE ) at Ek
I core
- Rated output (Burden to be 25-100% rated burden)
I core
LV Neutral
- Number of cores
- Rated extended primary current
- Ratio (TR = turns ratio)
I core
- Class
I core
- Knee point voltage (Ek)
I core
- Exciting current (IE ) at Ek
I core
- Rated output (Burden to be 25-100% rated burden)
I core
All class PX CTs shall have a rated secondary current, ISN
Section VI – Requirements Page 196 of 677Environmental Guidelines for Contractors
M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF)
UNIT DATA
Required Offered
Oil:
Manufacturer
Type designation
Standards IEC 60296
Minimum flash point oC
Viscosity
At 20oC mm2/s
At 50oC mm2/s
At 80oC mm2/s
Maximum dielectric strength for 1 min kV
Dielectric factor
Acidity (neutralization value) mgKOH/g
Type of dehydrating breather (Non-sealed transformers) Silicagel
Conductor material (e.g. copper, work hardened copper, etc.):
HV windings
LV windings
Conductor insulation:
HV winding
LV winding
Calculated thermal time constant min
Section VI – Requirements Page 197 of 677Environmental Guidelines for Contractors
M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF)
UNIT DATA
Required Offered
Thickness of transformer tank
- Sides mm
- Bottom mm
- Top mm
Material of transformer tank
Thickness of radiator plates mm
Total volume of conservator litres
Masses of transformer
- Core and coils kg
- Total mass excluded oil kg
- Oil mass in tank kg
in radiators kg
total kg
- Total mass kg
Mass of transformer as arranged for transport (heaviest part) kg
Dimensions of transformer arranged for transport
- Height m
- Width m
- Length m
Section VI – Requirements Page 198 of 677Environmental Guidelines for Contractors
M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF)
UNIT DATA
Required Offered
Maximum noise level (to NEMA TR1) dB 56
Conservator vessel, radiators, fan grilles, control boxes or cubicles and pipework anticorrosion protection
Hot dip galvanized and
painted
Tank anticorrosion protection
Control/Protection voltage V 110 DC
Manufacturer quality assurance Yes
- According to ISO 9000, 9001, 9002, 9003 and 9004
Type test certificates to be issued by:
- Independent Laboratory or independently witnessed type test certificate
Yes
1.59 Special Tests to be performed:
- Measurement of zero-sequence impedance- Determination of sound levels- Measurement of harmonics of no-load current- Vibration test
Yes
No
No
No
Section VI – Requirements Page 199 of 677Environmental Guidelines for Contractors
N. NEUTRAL EARTHING RESISTOR/ REACTOR UNIT DATA
Required Offered
1.1. Manufacturer
1.2. Type
1.3. Standards IEEE 32, IEC61000-6-3
1.4. Rated voltage kV 11
1.5. Rated fault current A Refer to drawings
1.6. Continuous current A
1.7
1.8
1.9
1.10
1.11
Maximum operating time
Resistor material resistance cold
Temperature rise at rated voltage after 10 sec
Protection class
Installation: indoor/ outdoor
sec
Ohm
Deg C
10
1000
Section VI – Requirements Page 200 of 677Environmental Guidelines for Contractors
O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark UNIT DATARequired Offered
1 LINE CONDUCTOR FITTINGS ACSR
1.1 Complete line conductor:
1.1.1 Nominal area per phase mm2 990
1.1.2 Number of conductors per phase No 4
1.1.3 Distance between conductor centres of one phase mm 400
1.2 Each single conductor:
1.2.1 Code name Lark
1.2.2 International Standard IEC 61089
1.2.3 National standard ASTM B 232
1.2.4 Material of conductor Aluminium/ Galvanised
Steel1.2.5 Number and diameter of wires No/mm Al 30/2.92
St 7/2.921.2.6 Total area of conductor mm2 247.8
1.2.7 Overall diameter of stranded conductor mm 20.44
1.2.8 Resistance of conductor (dc) at 20˚C ohm/km 0.1441
1.2.9 Mass of conductor (without grease) kg/km 925
1.2.10 Total mass of greased conductor (greased to Case 2 of IEC 61089)
kg/km
1.2.11 Ultimate rated strength of conductor Newton 90,250
1.2.12 Maximum tension of conductor in still air at “everyday” temperature
Newton 18,050
1.2.13 Assumed equivalent modulus of elasticity of conductor N/mm2 80,420
1.2.14 Assumed equivalent coefficient of linear expansion of conductor
per ˚C 1.78 x 10-5
1.2.15 Maximum length of conductor on drum km 5
1.3 CONDUCTOR GREASE:
1.3.1 Type
1.3.2 Minimum drop-point temperature ˚C 120
Mass of grease per kilometre of conductor (all inner layers greased – Case 2 to IEC 61089)
kg
Section VI – Requirements Page 201 of 677Environmental Guidelines for Contractors
O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark UNIT DATARequired Offered
1.4 VIBRATION DAMPING SYSTEM:
1.4.1 Type of system (vibration damper + spacer or spacer damper)
type
1.4.2 Vibration damper (if proposed)
1.4.2.1 Type of vibration damper type Stockbridge
1.4.2.2 National / International standard IEC 61897
1.4.2.3 Number of wires in messenger cable No 19
1.4.2.4 Conductor diameter range mm 20.44
1.4.2.5 Mass of damper kg
1.4.2.6 Maximum span for:
a. One vibration damper at each end of span m
b. Two vibration dampers at each end of span m
c. Three vibration dampers at each end of span m
1.4.2.7 Dimensions from clamp mouth to vibration damper attachment:
a. First damper mm
b. Second damper when required mm
c. Third damper when required mm
1.4.3 Spacer or spacer damper
1.4.3.1 Type of spacer or spacer damper
1.4.3.2 National / International standard IEC 61854
1.4.3.3 Conductor diameter range mm 20.44
1.4.3.4 Mass kg
1.4.3.5 Symmetrical / asymmetrical in-span spacing
1.4.3.6 Maximum sub-span length m
NO’S 2 TO 3 NOT USED
Section VI – Requirements Page 202 of 677Environmental Guidelines for Contractors
O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark UNIT DATARequired Offered
4. EARTH CONDUCTOR AND FITTINGS Aluminium Clad Steel GW
4.1 Complete earth conductor system
4.1.1 Number of ACS earth conductors No 1
4.2 Each single earth conductor
4.2.1 International Standard No ASTM B416
4.2.2 Material of conductor Aluminium-clad steel
4.2.3 Number and diameter of wires No/mm 7/3.26
4.2.4 Total area of conductor mm2 58.6
4.2.5 Overall diameter of conductor mm 9.78
4.2.6 Mass of conductor kg/km 390
4.2.7 Ultimate strength of conductor Newton 71,000
4.2.8 Maximum tension of conductor in still air at “everyday” temperature
Newton
4.2.9 Assumed equivalent modulus of elasticity of conductor N/mm2 162,000
4.2.10 Assumed equivalent coefficient of linear expansion of conductor
per C 12.96 x 10-6
4.2.11 Minimum bending radius mm
4.2.12 Minimum length of conductor on drum km 4
4.3 Individual wires before stranding
4.3.1 Aluminium-clad steel ASTM B415
a. Grade of steel 20SA
4.4 Vibration damping system
4.4.1 Maximum span for:
a. One vibration damper at each end of span m
b. Two vibration dampers at each end of span m
c. Three vibration dampers at each end of span m
OPGW EARTH CONDUCTOR AND FITTINGS
5 EARTH CONDUCTOR AND FITTINGS OPGW
5.1 Complete optical earth conductor system
Section VI – Requirements Page 203 of 677Environmental Guidelines for Contractors
O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark UNIT DATARequired Offered
5.1.1 Number of OPGW earth conductors No 1
5.2 Each single optical earth conductor (OPGW)
5.2.1 International Standard No IEE 1138IEC 60794-4-1
5.2.2 Material of conductor Aluminium Alloy/
Aluminium-clad steel
5.2.3 Number and diameter of wires No/mm
5.2.4 Total area of conductor mm2
5.2.5 Overall diameter of conductor mm
5.2.6 Mass of conductor kg/km <850
5.2.7 Ultimate strength of conductor Newton ≥ 93,000
5.2.8 Maximum tension of conductor in still air at “everyday” temperature
Newton > 18,500
5.2.9 Assumed equivalent modulus of elasticity of conductor N/mm2 ≥ 70,000
5.2.10 Assumed equivalent coefficient of linear expansion of conductor
per C ≤1.98 x 10-5
5.2.11 Minimum bending radius mm
5.2.12 Short circuit current rating kA2s 496
5.2.13 Minimum length of conductor on drum km 4
5.3 Individual wires before stranding
5.3.1 Aluminium alloy Standard IEC 60104Minimum conductivity at 20ºC %IACS 52.5
5.3.2 Aluminium-clad steel Standard IEC 60232Grade of Steel 20SA
5.4 Vibration damping system
5.4.1 Maximum span for:a. One vibration damper at each end of span m
b. Two vibration dampers at each end of span m
c. Three vibration dampers at each end of span m
OPGW EARTH CONDUCTOR6 FIBRE OPTIC TRANSMISSION SYSTEM
6.1 Fibre optic data
6.1.1 Type Non-Zero Dispersion-
Shifted Single-Mode acc. to ITU G.655.
Section VI – Requirements Page 204 of 677Environmental Guidelines for Contractors
O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark UNIT DATARequired Offered
6.1.2 Wavelength nm
1550/1625
6.1.3 Number of fibres 48
6.1.4 Transmission attenuation:
a. at 1550 nm dB/km
< 0.22
b. at 1625 nm dB/km
< 0.24
6.1.5 Transmission bandwidth MHz/km
> 10 000
6.1.6 Fibre identification colour code
6.1.7 Chromatic dispersion
a. at 1550 nm ps/nm.km
< 2
b. at 1625 nm ps/nm.km
< 12.4
6.1.8 Splicing loss dB
< 0.1
6.1.9 Polarisation Mode Dispersion (PMD) ps/√km
< 20
6.1.10 Minimum bending radius mm
6.2 SDH Optical Multiplex Equipment and Regenerative Repeaters
6.2.1 Transmission mode Digital
6.2.2 Operating wavelength nm
1550
6.2.3 Optical transmitter DFB laser diode
6.2.4 Optical detector avalanche photodiode
6.2.5 Optical transmission rate:
a. STM-1 Mb/s
155.52
b. STM-4 Mb/s
622.08
6.2.6 Optical interface Compliant with ITU Rec G957 and Rec G958
6.2.7 Electrical digital interface Compliant with ITU Rec G709
6.2.8 Maximum input attenuation dB
< 6
6.2.9 Maximum admissible jitter Compliant with ITU Rec G812
6.2.10 Transmission delay s < 1
Section VI – Requirements Page 205 of 677Environmental Guidelines for Contractors
O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark UNIT DATARequired Offered
6.2.11 Operating voltage Vdc
48 (+20% -15%)
6.3 Solar arrays power supply system
6.3.1 Type of solar cell Silicon based
6.3.2 Type of batteries Nickel cadmium
6.3.3 Minimum battery autonomy (continuous operation) hours
96
6.3.4 Output voltage V dc
48 (+5%)
6.3.5 Charger and control unit
6.3.6 Manufacturer
6.3.7 Type reference
6.3.8 Place of manufacture
6.3.9 Is local technical support provided in Kenya? Y/N
6.3.10 Minimum lighting level required for proper operation of the solar arrays power supply system
lux
6.3.11 Output supply voltage range of the system V dc
6.3.12 Total power output of the solar arrays system W
6.3.13 Details of control equipment provided
6.3.14 Charging current A
6.3.15 Details of alarm monitoring facilities provided
6.3.16 Details of remote alarm indications provided
6.3.17 Operating temperature range ºC
6.3.18 Operating relative humidity range (non-condensing) %rh
6.3.19 Protection rating IP Standard
6.3.20 Vibration IEC Standard
6.3.21 Shock IEC Standard
6.3.22 Dimension of equipment (H W D) mm mm mm
6.3.23 Mass kg
6.3.24 Mean time between failures (MTBF) hours
Section VI – Requirements Page 206 of 677Environmental Guidelines for Contractors
O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark UNIT DATARequired Offered
6.3.24 Mean time to repair (MTTR) hours
6.4 Optical regenerative repeaters
(to be completed for each type of repeater used)
6.4.1 Manufacturer
6.4.2 Model reference
6.4.3 Place of Manufacture
6.4.4 Number Provided No
6.4.5 Is local technical support provided in Kenya? Y/N
6.4.6 Regenerator section length (without the use of optical booster/amplifiers)
km
6.4.7 Regenerator section length (with the use of optical boosters/amplifiers)
km
6.4.8 Nominal operating wavelength nm
6.4.9 Transmission rate M
b/s6.4.10 Type of optical transmitter
6.4.11 Minimum transmit level dBm
6.4.12 Maximum transmit level dBm
6.4.13 Type of optical receiver
6.4.14 Receiver sensitivity for BER 10-9 dBm
6.4.15 Is interworking with PDH systems possible?
6.4.16 Details of interfacing with the Telecommunications Management System
6.4.17 Service channels:
a. Number of channels
b. Bit rate
c. Type of interface
6.4.18 Engineers order wire
a. 2 wire/4 wire interface
b. Impedance
c. Bit rate (for digital)
d. Selective calling facility
Section VI – Requirements Page 207 of 677Environmental Guidelines for Contractors
O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark UNIT DATARequired Offered
6.4.19 Details of alarm monitoring facilities
6.4.20 Voltage limits for satisfactory operation
a. Nominal voltage V dc
b. Maximum voltage V dc
c. Minimum voltage V dc
6.4.21 Anticipated loading in volt-amperes at 48 V dc. VA
6.4.22 Electromagnetic interference
IEC Standard
6.4.23 Operating temperature range C
6.4.24 Operating relative humidity range(non-condensing)
%rh
6.4.25 Protection rating IP Standard
6.4.26 Vibration IEC Standard
6.4.27 Shock IEC Standard
6.4.28 Details of ventilation required
6.4.29 Mass of complete equipment kg
6.4.30 Mean time between failures (MTBF) hours
6.4.31 Mean time to repair (MTTR) hours
6.4.32 Dimensions of cubicle rack mm mm mm
6.5 Solar cells(to be completed for each type of solar cell used)
6.5.1 Manufacturer
6.5.2 Type reference
6.5.3 Place of manufacture
6.5.4 Number of solar cells provided No
6.5.5 Type of solar cells
6.5.6 Lighting level range required for proper operation of the solar cell
lux
6.5.7 Voltage output range of each solar cell V dc
6.5.8 Power output of each solar cell W
6.5.9 Method of mounting solar panels
Section VI – Requirements Page 208 of 677Environmental Guidelines for Contractors
O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark UNIT DATARequired Offered
6.5.10 Operating temperature range ºC
6.5.11 Operating relative humidity range (non-condensing) %rh
6.5.12 Protection rating IP Standard
6.5.13 Vibration IEC Standard
6.5.14 Shock IEC Standard
6.5.15 Dimension of each solar array (H W D) mm mm mm
6.5.16 Dimension of complete solar arrays system (H W D)
mm mm mm
6.5.17 Mass of each solar array kg
6.5.18 Mass of complete solar arrays system kg
6.6 Batteries (to be completed for each type of battery used)
6.6.1 Manufacturer
6.6.2 Type reference
6.6.3 Place of manufacture
6.6.4 Number of batteries provided No
6.6.5 Type of batteries
6.6.6 Number of cells per battery No
6.6.7 Voltage output of each battery cell
V dc
6.6.8 Battery voltage output range V dc
6.6.9 Total capacity of the battery system Ah
6.6.10 Time required to recharge totally discharged batteries to full capacity
hours
6.6.11 Autonomy of the battery backup support hours
6.6.12 Ampere hour capacity at 96 hour discharge rate with average temperature at 50ºC
Ah
6.6.13 Operating temperature range ºC
6.6.14 Operating relative humidity range (non-condensing) %rh
Section VI – Requirements Page 209 of 677Environmental Guidelines for Contractors
O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark UNIT DATARequired Offered
6.6.15 Dimension of each battery (H W D) mm mm mm
6.6.16 Dimension of complete battery backup system (H W D)
mm mm mm
6.6.17 Mass of each battery/ complete battery backup system
kg
7.0 Insulator and fittings
7.1 Insulator units: Long Rod
7.1.1 Suspension units
7.1.1.1 Shed profile aerodynamic
7.1.1.2 Appropriate IEC Number IEC 61109
7.1.1.3 Material Silicone rubber
7.1.1.4 Couplinga. Standardb. Type (recommended only)c. Size (recommended only)
IEC 61120Ball/Socket
20
7.1.1.5 Minimum failing load kN 160
7.1.1.6 Outside diameter: mm
7.1.1.7 Mass of unit kg
7.1.1.8 Minimum dry lightning impulse withstand kV
7.1.1.9 Minimum wet power frequency withstand kV
7.1.1.10 Creepage distance mm 16000
7.1.2 Tension units
7.1.2.1 Shed profile aerodynamic
7.1.2.2 Appropriate IEC Number IEC 61109
7.1.2.3 Material Silicone rubber
7.1.2.4 Couplinga. Standardb. Type (recommended only)c. Size (recommended only)
IEC 61120Ball/Socket
20
7.1.2.5 Minimum failing load kN 160
7.1.2.6 Outside diameter:
7.1.2.7 Mass of unit kg
Section VI – Requirements Page 210 of 677Environmental Guidelines for Contractors
O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark UNIT DATARequired Offered
7.1.2.8 Minimum dry lightning impulse withstand kV
7.1.2.9 Minimum wet power frequency withstand kV
7.1.2.10 Creepage distance mm 16000
7.2 Insulator sets complete
7.2.1 Suspension sets
7.2.1.1 Number of insulator strings in parallel 1 / 2
7.2.1.2 Minimum failing load, complete set kN 120 /2*120
7.2.1.3 Overall length of set including clamps and all fittings mm ≤ 5150
7.2.1.4 Arcing Gap mm 29007.2.1.5 Mass of set, complete with all fittings kg
7.2.1.6 Overall length of creepage path per string: Mm 16000
7.2.1.7 50 Hz voltage tests:
a. Dry withstand voltage of complete set: kV 845
b. One minute wet withstand voltage of complete set : kV 680
7.2.1.8 50% Impulse withstand: a. 1.2/50 s negative wave: kV 1550
b. 1.2/50 s positive wave: kV 1550
7.2.1.9 Corona test voltage kV 290
7.2.1.10 Set RI test voltage kV 275
7.2.1.11 Set radio noise level dB 45
7.2.2.12 Short circuit current withstand for 1 second (any part of set) kA 31.5
7.2.2 Tension sets
7.2.2.1 Number of insulator strings in parallel 2
7.2.2.2 Elastic limit load of set fittings:
a. Common to each string kN
b. Common to conductor kN
c. Separate for each sub-conductor kN
7.2.2.3 Minimum failing load, complete set kN 320
7.2.2.4 Overall length of set including clamps and all fittings mm
All flashover and withstand voltage levels corrected to normal temperature and pressure in accordance with IEC 60383Section VI – Requirements Page 211 of 677Environmental Guidelines for Contractors
O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark UNIT DATARequired Offered
7.2.2.5 Arcing Gap mm 2900
7.2.2.6 Mass of set, complete with all fittings kg
7.2.2.7 Overall length of creepage path per string: mm 16000
7.2.2.8 50 Hz voltage tests:
a. Dry withstand voltage of complete set: kV 845
b. One minute wet withstand voltage of complete set:
kV 690
7.2.2.9 50% Impulse withstand:
a. 1.2/50 s negative wave: kV 1550
b. 1.2/50 s positive wave: kV 1550
7.2.2.10 Corona test voltage kV 290
7.2.2.11 Set RI test voltage kV 275
7.2.2.12 Set radio noise level dB 45
7.2.2.13 Short circuit current withstand for 1 second (any part of set) kA 31.5
7.3 Earth conductor sets
7.3.1 Minimum failing load
a. Suspension set kN
b. Tension set kN
7.3.2 Short circuit current withstand for 1 second (any part of set)
kA 31.5
8 Clearances
8.1 Minimum clearance between live metal and tower steelwork:-
a. with suspension insulator set swing, at 65º mm 1100
b. with suspension insulator set swing, 0 - 10º mm 3100
c. with suspension insulator set swing 10 - 35º mm 1800
8.4 Minimum clearance to steelwork on which a man may stand for live line maintenance (crossarm floor)
m 5.0
8.5 Downleads – minimum clearances:
a. phase to phase clearance in still air mm 4900
All flashover and withstand voltage levels corrected to normal temperature and pressure in accordance with IEC 60383
Section VI – Requirements Page 212 of 677Environmental Guidelines for Contractors
O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark UNIT DATARequired Offered
b. phase to phase clearance under conditions of maximum (opposing) swing and sag
mm 3700
8.6 Earth conductor suspension clamps, unobstructed transverse swing angle from vertical
degrees 0 – 50
8.7 Earth conductor maximum shielding angle from vertical at tower attachment point over outer line conductors
degrees 17
9.0 QUALITY OF TOWER MATERIALS
9.1
Steel members
9.1.1 Grade/standard: EN10025-2
a. Mild steel S235
b. High tensile steel S355
9.1.2 Tensile breaking stress:
a. Mild steel N/mm2 235
b. High tensile steel N/mm2 355
9.1.3 Elongation on breaking:
a. Mild steel %
b. High tensile steel %
9.1.4 Yield point as percentage of breaking stress:
a. Mild steel %
b. High tensile steel %
9.2
Steel nuts and bolts
9.2.1 Grade/standard:
a. Mild steel 5.6
b. High tensile steel 8.8
9.2.2 Tensile breaking stress:
a. Mild steel N/mm2
b. High tensile steel N/mm2
9.2.3 Elongation on breaking:
a. Mild steel %
b. High tensile steel %
Section VI – Requirements Page 213 of 677Environmental Guidelines for Contractors
P. 220 kV OVERHEAD LINE – Line Conductor 1 x Canary UNIT DATA
Required Offered
1.0 – 3.0
4.0
Not used
Line conductor and fittings ACSR
4.1 Complete line conductor:
4.1.1 Nominal area per phase mm2 515
4.1.2 Number of conductors per phase No 1
4.2 Each single conductor:
4.2.1 Code name Canary
4.2.2 International Standard IEC 61089
4.2.3 National standard ASTM B 232
4.2.4 Material of conductor Aluminium/ Galvanised
Steel
4.2.5 Number and diameter of wires No/mm Al 54/3.28
St 7/3.28
Section VI – Requirements Page 214 of 677Environmental Guidelines for Contractors
P. 220 kV OVERHEAD LINE – Line Conductor 1 x Canary UNIT DATA
Required Offered
4.2.6 Total area of conductor mm2 515.50
4.2.7 20. OVERALL DIAMETER OF STRANDED CONDUCTOR
mm 29.52
4.2.8 Resistance of conductor (dc) at 20˚C ohm/km 0.06328
4.2.9 Mass of conductor (without grease) kg/km 1726
4.2.10 Total mass of greased conductor (greased to Case 2 of IEC 61089)
kg/km
4.2.11 Ultimate rated strength of conductor Newton 142,040
4.2.12 Maximum tension of conductor in still air at “everyday” temperature
Newton 28,408
4.2.13 Assumed equivalent modulus of elasticity of conductor N/mm2 68,650
4.2.14 Assumed equivalent coefficient of linear expansion of conductor
per ˚C 1.93 x 10-5
4.2.15 Maximum length of conductor on drum km 3
4.3 Conductor grease:
4.3.1 Type
Section VI – Requirements Page 215 of 677Environmental Guidelines for Contractors
P. 220 kV OVERHEAD LINE – Line Conductor 1 x Canary UNIT DATA
Required Offered
4.3.2 Minimum drop-point temperature ˚C 120
4.3.3 Mass of grease per kilometre of conductor (all inner layers greased – Case 2 to IEC 61089)
kg
4.4 Vibration damping system:
4.4.1 Type of system (vibration damper) type
4.4.2 VIBRATION DAMPER
4.4.2.1 Type of vibration damper type Stockbridge
4.4.2.2 National / International standard IEC 61897
4.4.2.3 Number of wires in messenger cable No 19
4.4.2.4 Conductor diameter range mm 29.52
4.4.2.5 Mass of damper kg
4.4.2.6 Maximum span for:
a. One vibration damper at each end of span m
b. Two vibration dampers at each end of span m
Section VI – Requirements Page 216 of 677Environmental Guidelines for Contractors
P. 220 kV OVERHEAD LINE – Line Conductor 1 x Canary UNIT DATA
Required Offered
c. Three vibration dampers at each end of span m
4.4.2.7 Dimensions from clamp mouth to vibration damper attachment:
a. First damper mm
b. Second damper when required mm
c. Third damper when required mm
P. 220 kV OVERHEAD LINE – Earth Conductor UNIT DATARequired Offered
5.0 Earth Conductor and fittings Aluminium
Clad Steel GW
5.1 Complete earth conductor system
5.1.1 Number of ACS earth conductors No 1
5.2 Each single earth conductor
5.2.1 International Standard No ASTM B416
5.2.2 Material of conductor Aluminium-clad steel
5.2.3 Number and diameter of wires No/mm 7/3.26
5.2.4 Total area of conductor mm2 58.6
5.2.5 Overall diameter of conductor mm 9.78
5.2.6 Mass of conductor kg/km 390
5.2.7 Ultimate strength of conductor Newton 71,000
5.2.8 Maximum tension of conductor in still air at “everyday” temperature
Newton
5.2.9 Assumed equivalent modulus of elasticity of conductor N/mm2 162,000
Section VI – Requirements Page 217 of 677Environmental Guidelines for Contractors
P. 220 kV OVERHEAD LINE – Line Conductor 1 x Canary UNIT DATA
Required Offered
5.2.10 Assumed equivalent coefficient of linear expansion of conductor
per C 12.96 x 10-6
5.2.11 Minimum bending radius mm
5.2.12 Minimum length of conductor on drum km 4
5.3 Individual wires before stranding
5.3.1 Aluminium-clad steel ASTM B415
b. Grade of steel 20SA
5.4 Vibration damping system
5.4.1 Maximum span for:
a. One vibration damper at each end of span m
b. Two vibration dampers at each end of span m
c. Three vibration dampers at each end of span m
6.0 Earth Conductor and fittings OPGW
6.1 Complete optical earth conductor system
6.1.1 Number of OPGW earth conductors No 1
6.2 Each single optical earth conductor (OPGW)
6.2.1 International Standard No IEE 1138IEC 60794-4-1
6.2.2 Material of conductor Aluminium Alloy/
Aluminium-clad steel
6.2.3 Number and diameter of wires No/mm
6.2.4 Total area of conductor mm2
6.2.5 Overall diameter of conductor mm
6.2.6 Mass of conductor kg/km <850
6.2.7 Ultimate strength of conductor Newton ≥ 93,000
6.2.8 Maximum tension of conductor in still air at “everyday” temperature
Newton > 18,500
6.2.9 Assumed equivalent modulus of elasticity of conductor N/mm2 ≥ 70,000
Section VI – Requirements Page 218 of 677Environmental Guidelines for Contractors
P. 220 kV OVERHEAD LINE – Line Conductor 1 x Canary UNIT DATA
Required Offered
6.2.10 Assumed equivalent coefficient of linear expansion of conductor
per C ≤1.98 x 10-5
6.2.11 Minimum bending radius mm
6.2.12 Short circuit current rating kA2s 496
6.2.13 Minimum length of conductor on drum km 4
6.3 Individual wires before stranding
6.3.1 Aluminium alloy Standard IEC 60104Minimum conductivity at 20ºC %IACS 52.5
6.3.2 Aluminium-clad steel Standard IEC 60232Grade of Steel 20SA
6.4 Vibration damping system
6.4.1 Maximum span for:
d. One vibration damper at each end of span m
e. Two vibration dampers at each end of span m
f. Three vibration dampers at each end of span m
7.0 FIBRE OPTIC TRANSMISSION SYSTEM
7.1 Fibre optic data
7.1.1 Type Non-Zero Dispersion-
Shifted Single-Mode acc. to ITU G.655.
7.1.2 Wavelength nm
1550/1625
7.1.3 Number of fibres 48
7.1.4 Transmission attenuation:
c. at 1550 nm dB/km
< 0.22
d. at 1625 nm dB/km
< 0.24
7.1.5 Transmission bandwidth MHz/km
> 10 000
Section VI – Requirements Page 219 of 677Environmental Guidelines for Contractors
P. 220 kV OVERHEAD LINE – Line Conductor 1 x Canary UNIT DATA
Required Offered
7.1.6 Fibre identification colour code
7.1.7 Chromatic dispersion
c. at 1550 nm ps/nm.km
< 2
d. at 1625 nm ps/nm.km
< 12.4
7.1.8 Splicing loss dB
< 0.1
7.1.9 Polarisation Mode Dispersion (PMD) ps/√km
< 20
7.1.10 Minimum bending radius mm
8.0 Insulator and fittings
8.1 Insulator units: Long Rod
8.1.1 Suspension units
8.1.1.1 Shed profile aerodynamic
8.1.1.2 Appropriate IEC Number IEC 61109
8.1.1.3 Material Silicone rubber
8.1.1.4 Couplingd. Standarde. Type (recommended only)f. Size (recommended only)
IEC 61120Ball/Socket
16
8.1.1.5 Minimum failing load kN 70
8.1.1.6 Outside diameter: mm
8.1.1.7 Mass of unit kg
Section VI – Requirements Page 220 of 677Environmental Guidelines for Contractors
P. 220 kV OVERHEAD LINE – Line Conductor 1 x Canary UNIT DATA
Required Offered
8.1.1.8 Minimum dry lightning impulse withstand kV
8.1.1.9 Minimum wet power frequency withstand kV
8.1.1.10 Creepage distance mm 9300
8.1.2 Tension units
8.1.2.1 Shed profile aerodynamic
8.1.2.2 Appropriate IEC Number IEC 61109
8.1.2.3 Material Silicone rubber
8.1.2.4 Couplingd. Standarde. Type (recommended only)f. Size (recommended only)
IEC 61120Ball/Socket
16
8.1.2.5 Minimum failing load kN 120
8.1.2.6 Outside diameter:
8.1.2.7 Mass of unit kg
8.1.2.8 Minimum dry lightning impulse withstand kV
8.1.2.9 Minimum wet power frequency withstand kV
8.1.2.10 Creepage distance mm 9300
8.2 Insulator sets complete
8.2.1 Suspension sets
8.2.1.1 Number of insulator strings in parallel 1 / 2
8.2.1.2 Minimum failing load, complete set kN 70 /2*70
8.2.1.3 Overall length of set including clamps and all fittings mm ≤ 3100
8.2.1.4 Arcing Gap mm 21008.2.1.5 Mass of set, complete with all fittings kg
8.2.1.6 Overall length of creepage path per string: Mm 9300
8.2.1.7 50 Hz voltage tests:
c. Dry withstand voltage of complete set: kV 715
d. One minute wet withstand voltage of complete set : kV 540
8.2.1.8 50% Impulse withstand:
All flashover and withstand voltage levels corrected to normal temperature and pressure in accordance with IEC 60383Section VI – Requirements Page 221 of 677Environmental Guidelines for Contractors
P. 220 kV OVERHEAD LINE – Line Conductor 1 x Canary UNIT DATA
Required Offered
c. 1.2/50 s negative wave: kV 1150
d. 1.2/50 s positive wave: kV 1150
8.2.1.9 Corona test voltage kV 245
8.2.1.10 Set RI test voltage kV 220
8.2.1.11 Set radio noise level dB 45
8.2.1.12 Short circuit current withstand for 1 second (any part of set) kA 31.5
8.2.2 Tension sets
8.2.2.1 Number of insulator strings in parallel 1/2
8.2.2.2 Minimum failing load, complete set kN 120/2*120
8.2.2.3 Overall length of set including clamps and all fittings mm
8.2.2.4 Arcing Gap mm 2100
8.2.2.5 Mass of set, complete with all fittings kg
8.2.2.6 Overall length of creepage path per string: mm 9300
8.2.2.7 50 Hz voltage tests:
c. Dry withstand voltage of complete set: kV 715
d. One minute wet withstand voltage of complete set:
kV 540
8.2.2.8 50% Impulse withstand:
c. 1.2/50 s negative wave: kV 1150
d. 1.2/50 s positive wave: kV 1150
8.2.2.9 Corona test voltage kV 245
8.2.2.10 Set RI test voltage kV 220
8.2.2.11 Set radio noise level dB 45
8.2.2.12 Short circuit current withstand for 1 second (any part of set) kA 31.5
8.3 Earth conductor sets
All flashover and withstand voltage levels corrected to normal temperature and pressure in accordance with IEC 60383
Section VI – Requirements Page 222 of 677Environmental Guidelines for Contractors
P. 220 kV OVERHEAD LINE – Line Conductor 1 x Canary UNIT DATA
Required Offered
8.3.1 Minimum failing load
c. Suspension set kN
d. Tension set kN
8.3.2 Short circuit current withstand for 1 second (any part of set)
kA 31.5
9.1 – 9.2 Not used
9.3 Minimum clearance between live metal and tower steelwork:-
a. with suspension insulator set swing, at 65º mm 500
b. with suspension insulator set swing, 0 - 10º mm 2150
c. with suspension insulator set swing 10 - 35º mm 1500
9.4 Minimum Clearance to steelwork on which a man may stand for live line maintenance (crossarm floor)
m 3.9
9.5 Downleads – minimum clearances:
c. phase to phase clearance in still air mm 3500
d. phase to phase clearance under conditions of maximum (opposing) swing and sag
mm 2650
9.6 Earth conductor suspension clamps, unobstructed transverse swing angle from vertical
degrees 0 – 50
9.7 Earth conductor maximum shielding angle from vertical at tower attachment point over outer line conductors
degrees 3
10.0-13.0 Not used
14.0 QUALITY OF TOWER MATERIALS
14.1
Steel members
14.1.1 Grade/standard: EN10025-2
a. Mild steel S235
b. High tensile steel S355
14.1.2 Tensile breaking stress:
a. Mild steel N/mm2 235
b. High tensile steel N/mm2 355
14.1.3 Elongation on breaking:
Section VI – Requirements Page 223 of 677Environmental Guidelines for Contractors
P. 220 kV OVERHEAD LINE – Line Conductor 1 x Canary UNIT DATA
Required Offered
a. Mild steel %
14.1.4 Yield point as percentage of breaking stress:
a. Mild steel %
b. High tensile steel %
14.2
Steel nuts and bolts
14.2.1 Grade/standard:
a. Mild steel 5.6
b. High tensile steel 8.8
14.2.2 Tensile breaking stress:
a. Mild steel N/mm2
b. High tensile steel N/mm2
14.2.3 Elongation on breaking:
a. Mild steel %
b. High tensile steel %
Section VI – Requirements Page 224 of 677Environmental Guidelines for Contractors