10/1100/F/001EINTRODUCTION TOVIBRATION ISOLATION

Rubber in shear mountings

CLAMPAD isolation pads

Open spring mountings up to100mm static deflection

Caged spring mountings up to 50mm static deflection

Restrained spring mountings up to 25mm static deflection

TM

Positional isolation hangers

Spring and rubber isolation assemblies

Inertia base systems

Flexible connections

Floating floor systems

Technical application back-up

Vibration surveys

INTRODUCTION TO VIBRATION ISOLATION

IMPORTANCE OF STATIC DEFLECTION

ISOLATION EFFICIENCY CHART

To isolate unwanted machine vibration, it was once sufficient to mount the offending equipment on a piece of cork or felt. But today, with greater knowledge and higher expected standards,this traditional solution is usually inadequate, both in large building structures and in general industrial enviroment.

In building construction, improved design allows lighter but inherently more flexible structures to be used. At the same time, increasingly powerful air-conditioning and auxiliaryequipment is needed and may often be installed in upper level

Similarly in general industry, the size of vibration producingequipment is increasing whilst the community and workforcedemand improved living and working conditions, free from severe vibration or structure born noise.

Both situations require engineered vibration control systems which give predictable results appropriate to the surrounding environment.

plantrooms. Equipment vibration therefore can be a major problem in such structures.

Isolation of vibration is accomplished by supporting the equipment on resilient mounting elements such as springs or rubber, which compress under the equipment weight. The degree of isolation achieved is directly related to the amount

of compression (i.e. static deflection) of the mounting.The greater the static deflection which can be achieved (without compressing too solid) , the better will be the resulting vibration isolation.

This chart illustrates the theoretical relationship betweenisolation efficiency, disturbing frequency and static deflection (or dynamic natural frequency) for a simple isolation system ona rigid foundation. It is also grouped into zones suggestingisolation efficiency ranges appropriate to different applications.

To use the chart, determine the lowest rotation speed of the equipment and consider this to be the disturbing frequency.Move vertically to intersect the diagonal line corresponding tothe percentage isolation required; then move horizontally leftand read the dynamic natural frequency or static deflection required of the mounting.

It is sufficient to use static deflection to select the correctisolator for spring mounted systems; but for rubber and pad mounts, selection should be made on the basis of dynamicnatural frequency.

SHOCK ABSORPTIO

N

APPLICATIO

NS

AMPLIF

ICATIO

N

TO B

E AVO

IDED

NON-C

RITIC

AL

APPLICATIO

NSG

ENERAL

APPLICATIO

NSCRIT

ICAL

APPLICATIO

NS20

00

3000

1000800

600

400

300

500

200

100

DISTURBING FREQUENCY CYCLES PER MINUTE

STA

TIC

DE

FLE

CT

ION

(m

m)

250200150125

10075

50

2520

1512107.5

5.0

2.52.0

1.5

0.50.751.01.3

0.2531.0

22.0

14.016.0

12.0

10.0

7.0

8.0 9.0

6.0

5.0

4.0

3.0

2.5

2.0

1.5

1.0

0%

70%

90%

80%

95%

97%

98%

99%

NON-C

RITIC

AL

APPLICATIO

NS

97%

CRITIC

AL

APPLICATIO

NSGENERAL

APPLICATIO

NS

99%

98%

95%

90%

80%

90%

90%

70%

80%

80%

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

400

300

500

600

800

1000

GENERAL

APPLICATIO

NS

GENERAL

APPLICATIO

NS

3000

2000

99%

99%

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

1000

1000

3000

3000

99%

99%

99%

99%

97%

NON-C

RITIC

AL

APPLICATIO

NS

97%

NON-C

RITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

1000

1000

1000

1000

GENERAL

APPLICATIO

NS

GENERAL

APPLICATIO

NS

GENERAL

APPLICATIO

NS

GENERAL

APPLICATIO

NS

3000

3000

3000

3000

2000

2000

99%

99%

99%

99%

99%

99%

99%

99%

98%

98%

95%

95%

AM

PL

IFIC

AT

ION

TO

BE

AV

OID

ED

97%

97%

97%

97%

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NS

CRITIC

AL

APPLICATIO

NSGENERAL

APPLICATIO

NS

GENERAL

APPLICATIO

NS

GENERAL

APPLICATIO

NS

GENERAL

APPLICATIO

NS

GENERAL

APPLICATIO

NS

GENERAL

APPLICATIO

NS

GENERAL

APPLICATIO

NS

GENERAL

APPLICATIO

NS

99%

99%

99%

99%

99%

99%

99%

99%

99%

99%

99%

99%

99%

99%

99%

99%

98%

98%

98%

98%

RESONANCE

0%

90%

90%

90%

90%

70%

70%

80%

80%

80%

80%

DY

NA

MIC

NA

TU

IRA

L F

RE

QU

EN

CY

( n

) H

Zf

Page 3: Vibration Isolation Equipment - nendle

NendleTM

DATA SHEET No :

HEAD OFFICE:TACITUS HOUSE, 153 HIGH STREET,ALDERSHOT, HANTS. GU11 1TT.TEL: +44 (0) 1252 344222 FAX: +44 (0) 1252 333782

e-mail: [email protected] web site: www.nendle.co.uk

E&EO

Nendle reserve the right to update equipment design at anytime without prior notice.

SOUTH WEST REGIONAL OFFICE:THE SHIP, WEST STREET, BANWELL, SOMERSET, BS29 6DA.TEL: +44 (0) 1934 820777 FAX: +44 (0) 1934 820682

e-mail: [email protected] web site: www.nendle.co.uk

10/1100/B/001EEFFECTIVENESS OFISOLATION

EFFECTIVENESS OF ISOLATION

STATIC DEFLECTION GUIDE

USING VIBRATION MOUNTINGS

The effectiveness of any resilient isolation system is usuallyexpressed in terms of its isolation efficiency, defined as thepercentage of the total vibratory force which is absorbed by theisolators.

Using the graph, the isolation efficiency of a simplespring system may be estimated from given values of staticdeflection and disturbing frequency. For rubber isolators, amore realistic estimate is obtained by using values of dynamic natural frequency instead of static deflection.

However, in assesing the level of isolation efficiency whichmight be acceptable in any situation, consideration must also be given to the following:

Equipment type and operating weight

Magnitude and nature of the vibratory forces

Restriction on equipment motion (see Inertia Blocks ) Location of equipment within the structure

For example, an isolation efficiency of 80% is probably satisfactory for a 5 kW machine located in the basement, buttotally inadequate for a 100 kW machine installed on a flexible upper level floor; particularly when adjacent to valuable office or residential accomodation. In this case an isolationefficiency close to 98% would be required.

The Static Deflection Guide shown below summarises theimportant theoretical relationship between disturbing frequency, static deflection and installed environment.

The table provides a guide to the isolator type and necessarystatic deflection for given values of operating speed and isolation efficiency. It also suggests appropriate levels of isolation efficiency for various operating locations.To use the table, read the minimum static deflection directlyagainst machine disturbing frequency (operating speed) andrequired isolation efficiency.Two static deflection figures appear, one for basement or ongradeinstallations; the other for upper level installations wheresome allowance is made for flexibility of the supporting structure.Select the appropriate figure.For rubber and pad mounts, static deflections have been corrected for average rubber hardness to approximate selectionsbased on dynamic natural frequency (see Isolation EfficiencyChart on previous page)

Some simple guidelines for successful vibration control:

(1) Mounting support points and load ratings should be selected so that the static deflections of all mountings are as uniform as possible.

(2) Unrestricted movement of resiliently mounted equipment is essential for effective isolation.

* Ensure that adequate clearance is maintained around the installed equipment, particularly underneath it, to permit free movement - especially where high deflection mountings are used.

* All connections to resiliently supported equipment should themselves be flexible. As well as restricting equipment motion, any fixed connection can offer a direct path for transmission of vibration to the surrounding structure, bypassing the isolation system.

(3) Top heavy machinery, especially when mounted on a narrow base, can become unstable if mountings are located too close to each other beneath the equipment. Such instability can be avoided by use of outrigger brackets which space the mountings further apart and raise the mounting location points closer to the vertical centre of gravity of the equipment.

(4) A rigid base is essential for resiliently supported equipment to avoid misalignment of drive components. Any flexibility in the machine base should be eliminated by the addition of steel stiffeners or use of a concrete inertia base.

(5) Piping, ductwork and ancillary equipment connections should not impose dead loads on the resiliently mounted equipment . Their weight should be separately supported.

Individual data sheets are available for each type of isolator,which provide further details on correct installation and opereation.

200

300

3.3

5.0

125

60

190

90

35

250

110

40

150

50

27

190

70

40

250

90

50

190

100

50

230

120

60

RPM HZ

500

700

8.3

11.7

20

11 18

10

20

10 18

20

11

11 8 25

2515

15

10

6

754

86

8

4 4

55

6

3

31500 25.0

16.71000

3000

2000

50.0

33.3

0.8

2

1.5 1.5

* * * *

* *

*

ISOLATOR STATIC DEFLECTION (mm)

High Deflection Springs

RubberMountings

25mm DeflectionSprings

Pad Mountings

DISTURBING FREQUENCY

ISOLATION EFFICIENCY

80%

ISOLATION EFFICIENCY

90%

ISOLATION EFFICIENCY

95%

ISOLATION EFFICIENCY

98%

GROUND FLOOR

UPPER FLOOR

GROUND FLOOR

UPPER FLOOR

GROUND FLOOR

UPPER FLOOR

GROUND FLOOR

UPPER FLOOR

NON-CRITICAL AREAS

GENERAL AREAS

CRITICAL AREAS

FactoriesWorkshopsGaragesWarehousesLaundriesBasements

SchoolsDept. StoresSupermarketsTelephone ExchangesHotels

Multi-storey BldgsOfficesHospitals- Service AreasChurchesSchoolsRestaurants

Multi-storey BldgsHospitals- Ward AreasBroadcasting StudiosTheatresAuditoriumsLibraries

* CONSULT NENDLE TECHNICAL DEPARTMENT

Page 4: Vibration Isolation Equipment - nendle

NendleTM

DATA SHEET No :

HEAD OFFICE:TACITUS HOUSE, 153 HIGH STREET,ALDERSHOT, HANTS. GU11 1TT.TEL: +44 (0) 1252 344222 FAX: +44 (0) 1252 333782

e-mail: [email protected] web site: www.nendle.co.uk

E&EO

Nendle reserve the right to update equipment design at anytime without prior notice.

SOUTH WEST REGIONAL OFFICE:THE SHIP, WEST STREET, BANWELL, SOMERSET, BS29 6DA.TEL: +44 (0) 1934 820777 FAX: +44 (0) 1934 820682

e-mail: [email protected] web site: www.nendle.co.uk

10/1150/F/001ECLAMPADTM ISOLATIONMEDIA

CLAMPAD ISOLATION MEDIA

APPLICATION

CLAMPAD MEETS THE NEED FOR COST EFFECTIVE VIBRATION ISOLATION OF PUMPS AND SECONDARY HIGH FREQUENCY ISOLATION FOR AIR HANDLING UNITS, CHILLERS, PIPEWORK, TRANSFORMERS & FLOATING FLOOR SYSTEMS.

TM

TM

NR 15

NR 17

NH 6

NH 12

NM 50

NM 30

AHU

CLAMPAD

INSTALLATION SUGGESTIONS

CLAMPAD

CLAMPAD IS ALSO SUPPLIED IN THE FORM OF ISOLATION WASHERS TO SUIT STUDDING DIAMETERS FROM M4 TO M20. CLAMPAD LOCATED EXTERNALLY SHALL BE ESCAPULATED IN NEOPRENE AND CODED 'W'.

ISOLATION WASHERS CLAMPAD WASHERS Reference : CIW - 6 Sizes M4 - M20

TM

TM

CLAMPAD RANGE

CLAMPAD

PUMP ISOLATION PIPEWORK ISOLATION

AHU SECONDARY ISOLATION

NR 8

NR 3

Page 5: Vibration Isolation Equipment - nendle

NendleTM

DATA SHEET No :

HEAD OFFICE:TACITUS HOUSE, 153 HIGH STREET,ALDERSHOT, HANTS. GU11 1TT.TEL: +44 (0) 1252 344222 FAX: +44 (0) 1252 333782

e-mail: [email protected] web site: www.nendle.co.uk

E&EO

Nendle reserve the right to update equipment design at anytime without prior notice.

SOUTH WEST REGIONAL OFFICE:THE SHIP, WEST STREET, BANWELL, SOMERSET, BS29 6DA.TEL: +44 (0) 1934 820777 FAX: +44 (0) 1934 820682

e-mail: [email protected] web site: www.nendle.co.uk

10/1150/B/001ETECHNICAL DATACLAMPAD ISOLATION MEDIA

STANDARD CLAMPAD SIZE : Width 1000 Cut To Length

CLAMPADTM STATIC LOAD CHARACTERISTICS

0.1

1

10

100

35 70 140 210 280 350

LOAD (Kpa)

STA

TIC

DE

FLE

CT

ION

mm

NH 12 ( NH 6 = NH12 X 0.5) NM 30 NM 50

CLAMPADTM STATIC LOAD CHARACTERISTICS

0.1

1

10

6.25 12.5 25 37.5 50LOAD (Kpa)

STA

TIC

DE

FLE

CT

ION

mm

NR 8 NR 15 NR 17

Page 6: Vibration Isolation Equipment - nendle

NendleTM

DATA SHEET No :

HEAD OFFICE:TACITUS HOUSE, 153 HIGH STREET,ALDERSHOT, HANTS. GU11 1TT.TEL: +44 (0) 1252 344222 FAX: +44 (0) 1252 333782

e-mail: [email protected] web site: www.nendle.co.uk

E&EO

Nendle reserve the right to update equipment design at anytime without prior notice.

SOUTH WEST REGIONAL OFFICE:THE SHIP, WEST STREET, BANWELL, SOMERSET, BS29 6DA.TEL: +44 (0) 1934 820777 FAX: +44 (0) 1934 820682

e-mail: [email protected] web site: www.nendle.co.uk

CLAMPAD ISOLATION MEDIAMODEL: NR3

10/1200/F/001E

Page 7: Vibration Isolation Equipment - nendle

NendleTM

DATA SHEET No :

HEAD OFFICE:TACITUS HOUSE, 153 HIGH STREET,ALDERSHOT, HANTS. GU11 1TT.TEL: +44 (0) 1252 344222 FAX: +44 (0) 1252 333782

e-mail: [email protected] web site: www.nendle.co.uk

E&EO

Nendle reserve the right to update equipment design at anytime without prior notice.

SOUTH WEST REGIONAL OFFICE:THE SHIP, WEST STREET, BANWELL, SOMERSET, BS29 6DA.TEL: +44 (0) 1934 820777 FAX: +44 (0) 1934 820682

e-mail: [email protected] web site: www.nendle.co.uk

10/1225/F/001ECLAMPAD ISOLATION MEDIAMODEL: NR8

Page 8: Vibration Isolation Equipment - nendle

NendleTM

DATA SHEET No :

HEAD OFFICE:TACITUS HOUSE, 153 HIGH STREET,ALDERSHOT, HANTS. GU11 1TT.TEL: +44 (0) 1252 344222 FAX: +44 (0) 1252 333782

e-mail: [email protected] web site: www.nendle.co.uk

E&EO

Nendle reserve the right to update equipment design at anytime without prior notice.

SOUTH WEST REGIONAL OFFICE:THE SHIP, WEST STREET, BANWELL, SOMERSET, BS29 6DA.TEL: +44 (0) 1934 820777 FAX: +44 (0) 1934 820682

e-mail: [email protected] web site: www.nendle.co.uk

10/1250/F/001EVIBRATION ISOLATORSMODEL: RV

Isolator Model Maximum Load Deflection A B C D E FKg mm mm mm mm mm mm mm

RV 1A 30 5.5 38 48 83 35 64 8RV 1B 40 5.5 38 48 83 35 64 8RV 1C 60 5.5 38 48 83 35 64 8RV 1D 115 5.5 38 48 83 35 64 8RV 2A 70 6 41 64 108 48 83 11RV 2B 110 6 41 64 108 48 83 11RV 2C 175 6 41 64 108 48 83 11RV 2D 285 6 41 64 108 48 83 11RV 3A 185 7 48 89 152 73 118 14RV 3B 285 7 48 89 152 73 118 14RV 3C 465 7 48 89 152 73 118 14RV 3D 690 7 48 89 152 73 118 14

RV

RV 3 Load Vs Deflection

0

100

200

300

400

500

600

700

800

0 1 2 3 4 5 6 7

Deflection (mm)

Loa

d (K

g)

RV3D

RV3C

RV3B

RV3A

RV 2 Load Vs Deflection

0

50

100

150

200

250

300

0 1 2 3 4 5 6

Deflection (mm)

Loa

d (K

g)

RV2D

RV2C

RV2B

RV2A

RV 1 Load Vs Deflection

0

20

40

60

80

100

120

140

0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5

Deflection (mm)

Loa

d (K

g)

RV1D

RV1C

RV1B

RV1A

Page 9: Vibration Isolation Equipment - nendle

NendleTM

DATA SHEET No :

HEAD OFFICE:TACITUS HOUSE, 153 HIGH STREET,ALDERSHOT, HANTS. GU11 1TT.TEL: +44 (0) 1252 344222 FAX: +44 (0) 1252 333782

e-mail: [email protected] web site: www.nendle.co.uk

E&EO

Nendle reserve the right to update equipment design at anytime without prior notice.

SOUTH WEST REGIONAL OFFICE:THE SHIP, WEST STREET, BANWELL, SOMERSET, BS29 6DA.TEL: +44 (0) 1934 820777 FAX: +44 (0) 1934 820682

e-mail: [email protected] web site: www.nendle.co.uk

10/1300/F/001EVIBRATION ISOLATORSMODEL: RVD

Isolator Size Maximum Load Deflection A B C D E FKg mm mm mm mm mm mm mm

RV 1A 20 10 48 48 83 35 64 8RV 1B 50 10 48 48 83 35 64 8RV 1C 95 10 48 48 83 35 64 8RV 1D 155 10 48 48 83 35 64 8RV 2A 60 11 54 64 108 48 83 11RV 2B 105 11 54 64 108 48 83 11RV 2C 170 11 54 64 108 48 83 11RV 2D 315 11 54 64 108 48 83 11RV 3A 250 12 60 89 153 73 118 14RV 3B 420 12 60 89 153 73 118 14RV 3C 700 12 60 89 153 73 118 14RV 3D 870 12 60 89 153 73 118 14

RVD

RVD 1 Load Vs Deflection

0

20

40

60

80

100

120

140

160

180

0 1 2 3 4 5 6 7 8 9 10

Deflection (mm)

Loa

d (K

g)

RVD1D

RVD1C

RVD1B

RVD1A

RVD 2 Load Vs Deflection

0

50

100

150

200

250

300

350

0 1 2 3 4 5 6 7 8 9 10 11

Deflection (mm)

Loa

d (K

g)

RVD2D

RVD2C

RVD2B

RVD2A

RVD3 Load Vs Deflection

0

100

200

300

400

500

600

700

800

900

1000

0 2 4 6 8 10 12

Deflection (mm)

Loa

d (K

g)

RVD3D

RVD3C

RVD3B

RVD3A

Page 10: Vibration Isolation Equipment - nendle

NendleTM

DATA SHEET No :

HEAD OFFICE:TACITUS HOUSE, 153 HIGH STREET,ALDERSHOT, HANTS. GU11 1TT.TEL: +44 (0) 1252 344222 FAX: +44 (0) 1252 333782

e-mail: [email protected] web site: www.nendle.co.uk

E&EO

Nendle reserve the right to update equipment design at anytime without prior notice.

SOUTH WEST REGIONAL OFFICE:THE SHIP, WEST STREET, BANWELL, SOMERSET, BS29 6DA.TEL: +44 (0) 1934 820777 FAX: +44 (0) 1934 820682

e-mail: [email protected] web site: www.nendle.co.uk

10/1350/F/001EVIBRATION ISOLATORSHIGH DEFLECTION SPRINGRANGE

Page 11: Vibration Isolation Equipment - nendle

NendleTM

DATA SHEET No :

HEAD OFFICE:TACITUS HOUSE, 153 HIGH STREET,ALDERSHOT, HANTS. GU11 1TT.TEL: +44 (0) 1252 344222 FAX: +44 (0) 1252 333782

e-mail: [email protected] web site: www.nendle.co.uk

E&EO

Nendle reserve the right to update equipment design at anytime without prior notice.

SOUTH WEST REGIONAL OFFICE:THE SHIP, WEST STREET, BANWELL, SOMERSET, BS29 6DA.TEL: +44 (0) 1934 820777 FAX: +44 (0) 1934 820682

e-mail: [email protected] web site: www.nendle.co.uk

10/1350/B/001EVIBRATION ISOLATORSSPRING SELECTION CHARTS

1720 Kg Max Load Spring

1520 Kg Max Load Spring

1000 Kg Max Load Spring

1200 Kg Max Load Spring

860 Kg Max Load Spring 760 Kg Max Load Spring

600 Kg Max Load Spring 500 Kg Max Load Spring 400 Kg Max Load Spring 300 Kg Max Load Spring

25 Kg Max Load Spring 50 Kg Max Load Spring

120 Kg Max Load Spring

200 Kg Max Load Spring

350 Kg Max Load Spring 400 Kg Max Load Spring

700 Kg Max Load Spring

25 & 50 mm Deflection Spring Selection Charts

5 3 2.8 2.5 2.2

NATURAL FREQUENCY fn

7.1 4.9 4.1 3.5 3.2

NATURAL FREQUENCY fn

Spring RateKg F/mm

0,03

0,03

0,04

0,05

0,060,07

0,080,10,130,17

Spring RateKg F/mm

0,04

0,060,07

0,21

0,13

0,501,00

LOAD/DEFLECTION CHART 50mm DEFLECTION SPRING

0

200

400

600

800

1000

1200

1400

1600

1800

2000

0 10 20 30 40 50

DEFLECTION mm

LO

AD

Kg

LOAD / DEFLECTION CHART 25mm DEFLECTION SPRING

0

100

200

300

400

500

600

700

800

0 5 10 15 20 25

DEFLECTION mm

LO

AD

Kg

Page 12: Vibration Isolation Equipment - nendle

NendleTM

DATA SHEET No :

HEAD OFFICE:TACITUS HOUSE, 153 HIGH STREET,ALDERSHOT, HANTS. GU11 1TT.TEL: +44 (0) 1252 344222 FAX: +44 (0) 1252 333782

e-mail: [email protected] web site: www.nendle.co.uk

E&EO

Nendle reserve the right to update equipment design at anytime without prior notice.

SOUTH WEST REGIONAL OFFICE:THE SHIP, WEST STREET, BANWELL, SOMERSET, BS29 6DA.TEL: +44 (0) 1934 820777 FAX: +44 (0) 1934 820682

e-mail: [email protected] web site: www.nendle.co.uk

10/1400/F/001EISOLATION ELEMENTMODEL : OS

1

2

KEY :

1. RETAINING CUPS, 2. SPRING ELEMENT,

25 Kg Max Load Spring

50 Kg Max Load Spring

7.1 4.9 4.1 3.5 3.2

NATURAL FREQUENCY fn

Spring RateKg F/mm

0,50

1,00

Isolation Element, 25mm deflection

THIS ISOLATION ELEMENT HAS A LOAD

RANGE OF UP TO 50 Kgs, WITH

A WORKING DEFLECTION OF Nom. 25 mm.

THE ISOLATORS HAVE BEEN DESIGNED

FOR USE WITH INERTIA BASES, FAN BASES

AND GENERAL APPLICATIONS.

Performance may vary depending on installation

TYPICAL ISOLATOR CODE : OS - 20

87 F

RE

E H

EIG

HT

1

LOAD / DEFLECTION CHART 25mm DEFLECTION SPRING

0

10

20

30

40

50

60

0 5 10 15 20 25

DEFLECTION mm

LO

AD

Kg

Page 13: Vibration Isolation Equipment - nendle

NendleTM

DATA SHEET No :

HEAD OFFICE:TACITUS HOUSE, 153 HIGH STREET,ALDERSHOT, HANTS. GU11 1TT.TEL: +44 (0) 1252 344222 FAX: +44 (0) 1252 333782

e-mail: [email protected] web site: www.nendle.co.uk

E&EO

Nendle reserve the right to update equipment design at anytime without prior notice.

SOUTH WEST REGIONAL OFFICE:THE SHIP, WEST STREET, BANWELL, SOMERSET, BS29 6DA.TEL: +44 (0) 1934 820777 FAX: +44 (0) 1934 820682

e-mail: [email protected] web site: www.nendle.co.uk

10/1450/F/001EVIBRATION ISOLATORMODEL: OS-1-25

3

5

6

7

1

2

KEY :

1. RETAINING CUPS, 2. SPRING ELEMENT, 3. ADJUSTABLE LEVELLING BOLT, 4. ANCHOR BOLTS

5. EQUIPMENT MOUNTING POINT, 6. HIGH FREQUENCY ISOLATION MEDIA, 7. MACHINE BASE PLATE,

4

25 Kg Max Load Spring 50 Kg Max Load Spring

120 Kg Max Load Spring

200 Kg Max Load Spring

350 Kg Max Load Spring

7.1 4.9 4.1 3.5 3.2

NATURAL FREQUENCY fn

Spring RateKg F/mm

0,07

0,21

0,13

0,501,00

Open Single Spring Isolator,25mm deflection

THIS SINGLE OPEN SPRING ISOLATOR HAS

A LOAD RANGE OF UP TO 350 Kgs, WITH A

WORKING DEFLECTION OF Nom. 25 mm.

THE ISOLATORS HAVE BEEN DESIGNED

FOR USE WITH INERTIA BASES, FAN BASES

AND GENERAL APPLICATIONS.

Performance may vary depending on installation

7912

120

150

TYPICAL ISOLATOR CODE : OS - 1 - 25 - 6035

87 F

RE

E H

EIG

HT

NO

M. 4

0

LOAD / DEFLECTION CHART 25mm DEFLECTION SPRING

0

50

100

150

200

250

300

350

400

0 5 10 15 20 25

DEFLECTION mm

LO

AD

Kg

Page 14: Vibration Isolation Equipment - nendle

NendleTM

DATA SHEET No :

HEAD OFFICE:TACITUS HOUSE, 153 HIGH STREET,ALDERSHOT, HANTS. GU11 1TT.TEL: +44 (0) 1252 344222 FAX: +44 (0) 1252 333782

e-mail: [email protected] web site: www.nendle.co.uk

E&EO

Nendle reserve the right to update equipment design at anytime without prior notice.

SOUTH WEST REGIONAL OFFICE:THE SHIP, WEST STREET, BANWELL, SOMERSET, BS29 6DA.TEL: +44 (0) 1934 820777 FAX: +44 (0) 1934 820682

e-mail: [email protected] web site: www.nendle.co.uk

10/1500/F/001EVIBRATION ISOLATORMODEL: OS-1-50

3

5

67

1

2

KEY :

1. RETAINING CUPS, 2. SPRING ELEMENT, 3. ADJUSTABLE LEVELLING BOLT,

4. ANCHOR BOLTS, 5. EQUIPMENT MOUNTING POINT,

6. HIGH FREQUENCY ISOLATION MEDIA, 7. MACHINE BASE PLATE,

4

Open Single Spring Isolator,50mm deflection

THIS SINGLE OPEN SPRING ISOLATOR HAS

A LOAD RANGE OF UP TO 860 Kgs, WITH A

WORKING DEFLECTION OF Nom. 50 mm.

THE ISOLATORS HAVE BEEN DESIGNED

FOR USE WITH INERTIA BASES, FAN BASES

AND GENERAL APPLICATIONS.

Performance may vary depending on installation

7912

120

150

Spring RateKg F/mm

860 Kg Max Load Spring

760 Kg Max Load Spring

600 Kg Max Load Spring

500 Kg Max Load Spring

400 Kg Max Load Spring

300 Kg Max Load Spring

0,06

0,07

0,08

0,1

0,13

0,17

5 3 2.8 2.5 2.2

NATURAL FREQUENCY fn

136 Free Height

Nom. 40

TYPICAL ISOLATOR CODE : OS - 1 - 50 - 7076

LOAD/DEFLECTION CHART 50mm DEFLECTION SPRING

0

100

200

300

400

500

600

700

800

900

1000

0 10 20 30 40 50

DEFLECTION mm

LO

AD

Kg

Page 15: Vibration Isolation Equipment - nendle

NendleTM

DATA SHEET No :

HEAD OFFICE:TACITUS HOUSE, 153 HIGH STREET,ALDERSHOT, HANTS. GU11 1TT.TEL: +44 (0) 1252 344222 FAX: +44 (0) 1252 333782

e-mail: [email protected] web site: www.nendle.co.uk

E&EO

Nendle reserve the right to update equipment design at anytime without prior notice.

SOUTH WEST REGIONAL OFFICE:THE SHIP, WEST STREET, BANWELL, SOMERSET, BS29 6DA.TEL: +44 (0) 1934 820777 FAX: +44 (0) 1934 820682

e-mail: [email protected] web site: www.nendle.co.uk

10/1550/F/001EVIBRATION ISOLATORMODEL: NRS-1-25

3

5

1

2

KEY :

1. RETAINING CUPS, 2. SPRING ELEMENT, 3. ADJUSTABLE LEVELLING BOLT, 4. ANCHOR BOLTS

5. MACHINE BASE, 6. HIGH FREQUENCY ISOLATION MEDIA, 7. MACHINE BASE PLATE,

4

25 Kg Max Load Spring 50 Kg Max Load Spring

120 Kg Max Load Spring

200 Kg Max Load Spring

350 Kg Max Load Spring

7.1 4.9 4.1 3.5 3.2

NATURAL FREQUENCY fn

Spring RateKg F/mm

0,07

0,21

0,13

0,501,00

Restrained Single Spring Isolator,

25 mm deflection

THIS SINGLE OPEN SPRING ISOLATOR HAS

A LOAD RANGE OF UP TO 350 Kgs, WITH A

WORKING DEFLECTION OF Nom. 25 mm.

THE ISOLATORS HAVE BEEN DESIGNED

FOR USE WITH INERTIA BASES, FAN

BASES AND GENERAL APPLICATIONS.

Performance may vary depending on installation

150

6

7

1380

80

6

20

TYPICAL ISOLATOR CODE : NRS - 1 - 25 - 6035

20

145

NO

MIN

AL

WO

RK

ING

HE

IGH

T

120

LOAD / DEFLECTION CHART 25mm DEFLECTION SPRING

0

50

100

150

200

250

300

350

400

0 5 10 15 20 25

DEFLECTION mm

LO

AD

Kg

Page 16: Vibration Isolation Equipment - nendle

NendleTM

DATA SHEET No :

HEAD OFFICE:TACITUS HOUSE, 153 HIGH STREET,ALDERSHOT, HANTS. GU11 1TT.TEL: +44 (0) 1252 344222 FAX: +44 (0) 1252 333782

e-mail: [email protected] web site: www.nendle.co.uk

E&EO

Nendle reserve the right to update equipment design at anytime without prior notice.

SOUTH WEST REGIONAL OFFICE:THE SHIP, WEST STREET, BANWELL, SOMERSET, BS29 6DA.TEL: +44 (0) 1934 820777 FAX: +44 (0) 1934 820682

e-mail: [email protected] web site: www.nendle.co.uk

10/1600/F/001EVIBRATION ISOLATORMODEL: NRS-1-50

3

4

1

2

KEY :

1. RETAINING CUPS, 2. SPRING ELEMENT, 3. ADJUSTABLE LEVELLING BOLT, 4. HIGH FREQUENCY ISOLATION MEDIA,5. MACHINE BASE PLATE, 6. FIXING BOLT OPTIONAL

NATURAL FREQUENCY fn

Spring RateKg F/mm

Restrained Single Spring Isolator,50mm deflection

THIS SINGLE RESTRAINED SPRING

ISOLATOR HAS A LOAD

RANGE OF UP TO 860 Kgs,

WITH A WORKING

DEFLECTION OF Nom. 50 mm.

THE ISOLATORS HAVE BEEN

DESIGNED FOR USE

WITH INERTIA BASES,

FAN BASES AND

GENERAL APPLICATIONS.

Performance may vary depending on installation

5 3 2.8 2.5 2.2

860 Kg Max Load Spring

760 Kg Max Load Spring

600 Kg Max Load Spring

500 Kg Max Load Spring

400 Kg Max Load Spring

300 Kg Max Load Spring

0,06

0,07

0,08

0,1

0,13

0,17

50

5

100

200

7676

10

145N

OM

INA

L W

OR

KIN

G H

EIG

HT

105

200 Kg Max Load Spring 0,25

TYPICAL ISOLATOR CODE : NRS - 1 - 50 - 7076

2525

6

LOAD/DEFLECTION CHART 50mm DEFLECTION SPRING

0

100

200

300

400

500

600

700

800

900

1000

0 10 20 30 40 50

DEFLECTION mm

LO

AD

Kg

Page 17: Vibration Isolation Equipment - nendle

NendleTM

DATA SHEET No :

HEAD OFFICE:TACITUS HOUSE, 153 HIGH STREET,ALDERSHOT, HANTS. GU11 1TT.TEL: +44 (0) 1252 344222 FAX: +44 (0) 1252 333782

e-mail: [email protected] web site: www.nendle.co.uk

E&EO

Nendle reserve the right to update equipment design at anytime without prior notice.

SOUTH WEST REGIONAL OFFICE:THE SHIP, WEST STREET, BANWELL, SOMERSET, BS29 6DA.TEL: +44 (0) 1934 820777 FAX: +44 (0) 1934 820682

e-mail: [email protected] web site: www.nendle.co.uk

10/1650/F/001EVIBRATION ISOLATORMODEL: NRS-2-50

5 3 2.8 2.5 2.2

1520 Kg Max Load Spring

1200 Kg Max Load Spring

1000 g Max Load Spring

0,03

0,04

0,05

1720 Kg Max Load Spring 0,03

50

126126

300

5

100

TYPICAL ISOLATOR CODE : NRS -2 - 50 - 7076C

145

nom

inal

wor

king

hei

ght

105

10

10

2525

3

4

1

2

KEY :

1. RETAINING CUPS, 2. SPRING ELEMENT, 3. ADJUSTABLE LEVELLING BOLT, 4. HIGH FREQUENCY ISOLATION MEDIA,5. MACHINE BASE PLATE, 6. FIXING BOLT OPTIONAL

NATURAL FREQUENCY fn

Spring RateKg F/mm

Restrained Double Spring Isolator,50mm deflection

THIS DOUBLE RESTRAINED SPRING

ISOLATOR HAS A LOAD

RANGE OF UP TO 1720 Kgs,

WITH A WORKING

DEFLECTION OF Nom. 50 mm.

THE ISOLATORS HAVE BEEN

DESIGNED FOR USE

WITH INERTIA BASES,

FAN BASES AND

GENERAL APPLICATIONS.

Performance may vary depending on installation

LOAD/DEFLECTION CHART 50mm DEFLECTION SPRING

0

200

400

600

800

1000

1200

1400

1600

1800

2000

0 10 20 30 40 50

DEFLECTION mm

LO

AD

Kg

Page 18: Vibration Isolation Equipment - nendle

NendleTM

DATA SHEET No :

HEAD OFFICE:TACITUS HOUSE, 153 HIGH STREET,ALDERSHOT, HANTS. GU11 1TT.TEL: +44 (0) 1252 344222 FAX: +44 (0) 1252 333782

e-mail: [email protected] web site: www.nendle.co.uk

E&EO

Nendle reserve the right to update equipment design at anytime without prior notice.

SOUTH WEST REGIONAL OFFICE:THE SHIP, WEST STREET, BANWELL, SOMERSET, BS29 6DA.TEL: +44 (0) 1934 820777 FAX: +44 (0) 1934 820682

e-mail: [email protected] web site: www.nendle.co.uk

10/1700/F/001EVIBRATION ISOLATORSSPRING HANGER SELECTIONGUIDE

Page 19: Vibration Isolation Equipment - nendle

NendleTM

DATA SHEET No :

HEAD OFFICE:TACITUS HOUSE, 153 HIGH STREET,ALDERSHOT, HANTS. GU11 1TT.TEL: +44 (0) 1252 344222 FAX: +44 (0) 1252 333782

e-mail: [email protected] web site: www.nendle.co.uk

E&EO

Nendle reserve the right to update equipment design at anytime without prior notice.

SOUTH WEST REGIONAL OFFICE:THE SHIP, WEST STREET, BANWELL, SOMERSET, BS29 6DA.TEL: +44 (0) 1934 820777 FAX: +44 (0) 1934 820682

e-mail: [email protected] web site: www.nendle.co.uk

10/1750/F/002EVIBRATION ISOLATORSPRING HANGERMODEL: SH-1-25

3

1

2

KEY :

1. RETAINING CUPS, 2. SPRING ELEMENT,

3. ADJUSTABLE DROP ROD (by others),

4. HANGER CAGE 5. LOWER DROP ROD (by others)

25 Kg Max Load Spring 50 Kg Max Load Spring

120 Kg Max Load Spring

200 Kg Max Load Spring

350 Kg Max Load Spring

7.1 4.9 4.1 3.5 3.2

NATURAL FREQUENCY fn

Spring RateKg F/mm

0,07

0,21

0,13

0,501,00

Unrestrained Single Spring Hanger,25mm deflection

THIS SINGLE SPRING HANGER HAS

A LOAD RANGE OF UP TO 350 Kgs,

WITH A WORKING DEFLECTION

OF Nom. 25 mm.

THE ISOLATORS HAVE BEEN

DESIGNED FOR PLANT

AND PIPEWORK ISOLATION.

Performance may vary depending on installation

Ø30

80

84

5

120

TYPICAL ISOLATOR CODE : SH - 1 - 25 - 6035

80 F

RE

E H

EIG

HT

LOAD / DEFLECTION CHART 25mm DEFLECTION SPRING

0

50

100

150

200

250

300

350

400

0 5 10 15 20 25

DEFLECTION mm

LO

AD

Kg

Page 20: Vibration Isolation Equipment - nendle

NendleTM

DATA SHEET No :

HEAD OFFICE:TACITUS HOUSE, 153 HIGH STREET,ALDERSHOT, HANTS. GU11 1TT.TEL: +44 (0) 1252 344222 FAX: +44 (0) 1252 333782

e-mail: [email protected] web site: www.nendle.co.uk

E&EO

Nendle reserve the right to update equipment design at anytime without prior notice.

SOUTH WEST REGIONAL OFFICE:THE SHIP, WEST STREET, BANWELL, SOMERSET, BS29 6DA.TEL: +44 (0) 1934 820777 FAX: +44 (0) 1934 820682

e-mail: [email protected] web site: www.nendle.co.uk

10/1800/F/002EVIBRATION ISOLATORSPRING HANGERMODEL: SH-2-25

1

2

KEY :

1. RETAINING CUPS, 2. SPRING ELEMENT,

3. ADJUSTABLE DROP ROD (by others),

4. HANGER CAGE 5. LOWER DROP ROD (by others)

400 Kg Max Load Spring

700 Kg Max Load Spring

7.1 4.9 4.1 3.5 3.2

Spring RateKg F/mm

0,04

0,06

Unrestrained Double Spring Hanger,25mm deflection

THIS DOUBLE SPRING

HANGER HAS A LOAD

RANGE OF UP TO 700 Kgs,

WITH A WORKING

DEFLECTION OF Nom. 25 mm.

THE ISOLATORS HAVE BEEN

DESIGNED FOR PLANT

AND PIPEWORK ISOLATION.

Ø30

80

4

160

3

150

TYPICAL ISOLATOR CODE : SH -2 - 25 - 60355

LOAD / DEFLECTION CHART 25mm DEFLECTION SPRING

0

100

200

300

400

500

600

700

800

0 5 10 15 20 25

DEFLECTION mm

LO

AD

Kg

Page 21: Vibration Isolation Equipment - nendle

NendleTM

DATA SHEET No :

HEAD OFFICE:TACITUS HOUSE, 153 HIGH STREET,ALDERSHOT, HANTS. GU11 1TT.TEL: +44 (0) 1252 344222 FAX: +44 (0) 1252 333782

e-mail: [email protected] web site: www.nendle.co.uk

E&EO

Nendle reserve the right to update equipment design at anytime without prior notice.

SOUTH WEST REGIONAL OFFICE:THE SHIP, WEST STREET, BANWELL, SOMERSET, BS29 6DA.TEL: +44 (0) 1934 820777 FAX: +44 (0) 1934 820682

e-mail: [email protected] web site: www.nendle.co.uk

10/1850/F/001EVIBRATION ISOLATORSPRING HANGERMODEL: PH-1-25

3

1

2

KEY :

1. RETAINING CUPS, 2. SPRING ELEMENT,

3. ADJUSTABLE DROP ROD (by others),

4. HANGER CAGE, 5. LOWER DROP ROD (by others)

25 Kg Max Load Spring 50 Kg Max Load Spring

120 Kg Max Load Spring

200 Kg Max Load Spring

350 Kg Max Load Spring

7.1 4.9 4.1 3.5 3.2

NATURAL FREQUENCY fn

Spring RateKg F/mm

0,07

0,21

0,13

0,501,00

Restrained Single Spring Hanger,

25mm deflection

THIS SINGLE SPRING HANGER HAS

A LOAD RANGE OF UP TO 350 Kgs,

WITH A WORKING DEFLECTION

OF Nom. 25 mm.

THE ISOLATORS HAVE BEEN

DESIGNED FOR PRE-LEVELLING

PLANT AND PIPEWORK.

Performance may vary depending on installation

Ø30

80

84

419

0

TYPICAL ISOLATOR CODE : PH - 1 - 25 - 6002 5

LOAD / DEFLECTION CHART 25mm DEFLECTION SPRING

0

50

100

150

200

250

300

350

400

0 5 10 15 20 25

DEFLECTION mm

LO

AD

Kg

Page 22: Vibration Isolation Equipment - nendle

NendleTM

DATA SHEET No :

HEAD OFFICE:TACITUS HOUSE, 153 HIGH STREET,ALDERSHOT, HANTS. GU11 1TT.TEL: +44 (0) 1252 344222 FAX: +44 (0) 1252 333782

e-mail: [email protected] web site: www.nendle.co.uk

E&EO

Nendle reserve the right to update equipment design at anytime without prior notice.

SOUTH WEST REGIONAL OFFICE:THE SHIP, WEST STREET, BANWELL, SOMERSET, BS29 6DA.TEL: +44 (0) 1934 820777 FAX: +44 (0) 1934 820682

e-mail: [email protected] web site: www.nendle.co.uk

10/1900/F/001EINERTIA BASE SYSTEMS

NENDLE RANGE OF INERTIABASE ANTI-VIBRATION SYSTEMS

Nendle inertia base systems offer a flexible approach to isolating rotary plant.Isolation efficiencies of up to 98.5% can be achieved. Acoustic inertia bases (Model A)do not require concrete infill, and when supplied pre-commissioned, useful costsavings can be obtained through accelerated installation programmes.

SPECIFICATION EXAMPLE:Model AR/PS/EP/H3/P(08-D-44-Yellow)/COM.

MODEL SB-PS-H3 INERTIA BASE

MODEL EB-PS-H2 INERTIA BASE

RANGE OF MODELS

MODEL E: Basic inertia frame. " EB: as E but with base " EBC: as EB plus nominated Clampad system. " H1: Height saving angle.

MODEL S: Basic inertia frame. " SB: A S but with base. " H2: Height saving bracket. " H3: Height saving bracket. MODEL A: Basic acoustic inertia frame. " AR: As A but with angle fixing rails. " EP: Electrical fixing plate. " PS: Pre-Assembled springs. " H2: Height saving bracket. " H3: Height saving bracket. MODEL M: Basic modular inertia frame kit. " MB: as M but with base. " H2: Height saving bracket. " H3: Height saving bracket.

TM

HEIGHT SAVING BRACKET TYPE H2

HEIGHT SAVING BRACKET TYPE H3

Page 23: Vibration Isolation Equipment - nendle

NendleTM

DATA SHEET No :

HEAD OFFICE:TACITUS HOUSE, 153 HIGH STREET,ALDERSHOT, HANTS. GU11 1TT.TEL: +44 (0) 1252 344222 FAX: +44 (0) 1252 333782

e-mail: [email protected] web site: www.nendle.co.uk

E&EO

Nendle reserve the right to update equipment design at anytime without prior notice.

SOUTH WEST REGIONAL OFFICE:THE SHIP, WEST STREET, BANWELL, SOMERSET, BS29 6DA.TEL: +44 (0) 1934 820777 FAX: +44 (0) 1934 820682

e-mail: [email protected] web site: www.nendle.co.uk

10/1900/B/001EACOUSTIC INERTIA BASESYSTEMS

MODEL A-R-PS-H3 ACOUSTIC INERTIA BASE

MODEL A-R-PS-H2 ACOUSTIC INERTIA BASE

MODULAR INERTIA BASE TYPE M-H2

MODULAR INERTIA BASE TYPE M-H3

MODEL E

MODEL EB

MODEL E-H2

MODEL EBC-

STANDARD FINISHMODEL E: Galvanised to BS2989 and cold galvanised.MODEL S & A: Two coats shop primer. MODEL M: Railsgalvanised to BS2989. Corners/Height saving brackets two coats of shop primer.

OPTIONAL EXTRASFINISH: Hot-dipped galvanised to BS729. Code G.Painted to any BS colour. Code P.(Specify colour reference No.)CONCRETE: Base models E & S can be supplied complete with concrete. CODE C.TYPICAL SPEC: Portland cement. Aggregate to BS882.Nominal mix 1:1:2. Volume of aggregate per 50 kgcement 0.03cu.m. Strength within 28 days 40 MN/sq.m.Maximum permissible stresses 7.6 MN/sq.m.COMMISSIONING SERVICE: Code COM.