VFD Harmonics Case Study
-
Upload
freddy-cuervo-camargo -
Category
Documents
-
view
2 -
download
0
description
Transcript of VFD Harmonics Case Study
© 2012 Dranetz Technologies www.dranetz.com 800-372-6832 (U.S & Canada) +1-732-287-3680 (International)
HARMONICS & WAVEFORM MEASUREMENTS
LOW PASS FILTER & SINE WAVE FILTER FOR A 460V 100HP AC MOTOR WITH VFD
INTRODUCTION
Harmonics are an important PQ issue today. Variable
Frequency Drives (VFD), Uninterruptible Power Systems
(UPS), computers, LED lighting, electronic ballasts,
etc. are widely used in all kinds of facilities. It is well
known that such devices can cause many problems at
end user’s installations and utility networks, such as:
Voltage distortion, damaged capacitor banks, tripping
breakers, blown fuses, overheating of cables and
transformers, damage to PLC’s and sensitive electronic
loads, etc.
DESCRIPTION
Variable Frequency Dives are becoming very popular in
controlling AC motors for industrial and commercial
applications. They provide speed control for processes
such as ventilators, pumps, air compressors, elevators,
etc. at substantial energy savings. However, VFD’s
generate significant harmonic currents depending upon
the power electronics technology used (number of
pulses, SCR, thyristors, etc.). In many cases, they
exceed IEEE-519 recommendations and cause some of
the problems mentioned above. Also, Pulse Width
Modulated (PWM) drives can cause additional problems
in AC motors, such as premature bearing wear and
short-circuits in windings due to spikes from
modulation if the motor is not designed for this
condition.
In many applications, harmonic mitigation techniques
are required, along with proper power monitoring
instrumentation to measure the harmonics spectrum
and waveforms. This can be essential in assuring such
solutions meet customer requirements. Passive filters
have proven their effectiveness at reasonable prices.
This case study is a customer witness and performance
test carried out at the laboratory of a manufacturer of
two passive filters to be supplied. The test is
conducted with a 460V, 100HP AC motor with a 6-pulse
PWM VFD. One Low Pass Filter (LPF) is installed at the
input of the VFD (load side), and one Sine Wave Filter
(SWF) is installed at the output of the VFD (motor
side).
Figure 1: Low Pass Filter and Sine Wave Filter Locations
Four Dranetz PowerXplorer and PowerVisa Power
Quality analyzers were used to measure the
effectiveness of the filters, monitoring the points
shown in Figure 1 above: Low Pass Filter Input, Low
Pass Filter Output, Sine Wave Filter Input, and Sine
Wave Filter Output.
Figure 2: Test In Progress
Below are waveshapes captured during the test:
© 2012 Dranetz Technologieswww.dranetz.com 800-372-6832 (U.S & Canada) +1-732-287-3680 (International)
LPF OUTPUT (NO HARMONICS FILTERING)
LPF INPUT (HARMONICS FILTERING)
LPF Output voltage waveform (2)
(VFD input 460V 100HP AC motor)
15:43:35.87
23/06/2011
Thursday
15:43:35.88 15:43:35.89 15:43:35.90
-750
-500
-250
0
250
500
750
Volts
A-B [Salida fil tro LPF]V
%THDV Harmonics spectra (2)
(VFD input 460V 100HP AC motor)
H05
H10
H15
H20
H25
H30
H35
H40
H45
H50
0
1
2
3
4
5
6
%
A-B [Salida fil tro LPF]VHarm (max)
LPF Output current waveform (2)
(VFD input 460V 100HP AC motor)
15:43:35.85
23/06/2011
Thursday
15:43:35.86 15:43:35.87 15:43:35.88
-200
-100
0
100
200
Am
ps
A [Salida fil tro LPF]I
%THDI Harmonics spectra (2)
(VFD input 460V 100HP AC motor)
H05
H10
H15
H20
H25
H30
H35
H40
H45
H50
0
10
20
30
40
50
60
70
%
A [Salida fil tro LPF]IHarm (max)
LPF input voltage waveform (1)
15:20:09.850
23/06/2011
Thursday
15:20:09.860 15:20:09.870 15:20:09.880
-750
-500
-250
0
250
500
750
Volts
A-B V
%THDI Harmonics spectra (1)
H05
H10
H15
H20
H25
H30
H35
H40
H45
H50
0
10
20
30
40
50
60
70
%
A IHarm (max)
LPF input current waveform (1)
15:20:09.89
23/06/2011
Thursday
15:20:09.90 15:20:09.91 15:20:09.92 15:20:09.93
-100
-75
-50
-25
0
25
50
75
Am
ps
A I
%THDI Harmonics spectra (1)
H05
H10
H15
H20
H25
H30
H35
H40
H45
H50
0
10
20
30
40
50
60
70
%
A IHarm (max)
© 2012 Dranetz Technologieswww.dranetz.com 800-372-6832 (U.S & Canada) +1-732-287-3680 (International)
SWF INPUT (VFD OUTPUT TERMINALS) SWF OUTPUT (MOTOR TERMINALS)
CONCLUSIONS:
LPF (low pass filter) reduced VTHD from 6.3% to 1.5% and ITHD from 70% to 6%. Corresponding waveforms were also improved as well
SWF (Sine wave filter) effectively improved the voltage waveform at the 100HP AC motor terminals (as shown)
Dranetz Power Quality analyzers advanced capabilities were essential in measuring not only at VFD line side, but also measuring and capturing the PWM waveforms High frequency pulses at VFD output)!
The customer was very satisfied, not only with the filtering results, but with the Dranetz PQ analyzers. He said: “With other manufacturers like Fluke, one PQ instrument and one oscilloscope are required to be able to perform VFD & filtering tests, which implies more cost about instrumentation.”
The filter customer decided to buy one PowerGuide portable instrument from Arteche Inelap, an authorized Dranetz distributor in Mexico who is fully committed to Dranetz products
DRANETZ HAS PROVEN ONCE AGAIN TO BE THE LEADER IN TECHNOLOGY AND “STATE OF THE ART” IN THE PQ BUSINESS!
This case study was submitted by Ing. Leopoldo Martínez Basulto, Dranetz México
PWM without filter (3)
(VFD output terminals)
15:46:30.8223/06/2011Thursday
15:46:30.84 15:46:30.86
-750
-500
-250
0
250
500
750
Volt
s
A-B [Entrada fil tro SWF]V
PWM with SW filter (4)
(Filter output terminals)
15:46:30.8323/06/2011Thursday
15:46:30.84 15:46:30.85 15:46:30.86 15:46:30.87
-750
-500
-250
0
250
500
750
Volt
s
A-B V