Understanding Harmonics in Electrical Power Systems for...
Transcript of Understanding Harmonics in Electrical Power Systems for...
11Classified as Business
Understanding Harmonics in Electrical Power Systemsfor HVAC experts.
Royce MeiliDanfoss DrivesTrane CSO Global Account Manager(316) [email protected]
22Classified as Business
Harmonics in Building Electrical Systems
The Cause
The Effects
The Standards
The Solutions
33Classified as Business
Introduction – Why Harmonics?
• VFD controlled motors saves up to 60% of the energy consumption in pump and fan applications.
• VFDs have a side effect –Harmonics.
• Harmonics prevent energy savings.
• Harmonics effect quality of the electrical energy in the power supply.
• Limiting of Harmonics is also required to ensure safe operation of the installation.
44Classified as Business
Utility power is delivered to a facility
• Voltage is delivered in sinusoidal form, at 60Hz.
• Electrical loads are designed to operate at this frequency and draw sinusoidalcurrents.
55Classified as Business
Two Types of Electrical Loads
Linear loads Linear loads are resistive, inductive or capacitive loads. They consume current equally through each power phase.
Draws power evenly.
Non-Linear loads Non-linear loads contain switching devices that will consume current unevenly between phases.These cause harmonic distortion.
Draws power unevenly.
66Classified as Business
The Challenge: Growing addition of non-linear loads.
As more electronic equipment is installed in buildings there is a greater potential for the effects of harmonics to be seen in the electrical system.
70%
30%
1990's
95%
5%
1960's
40%60%
2000'sVolume of Non-Linear Load Growth in USA
Linear Load
Non Linear Load
77Classified as Business
Harmonics in Building Electrical Systems
The Cause
The Effects
The Standards
The Solutions
88Classified as Business
Harmonic distortion by nonlinear loads
Harmonics created at the non-linear load are reflected upstream to other devices in the electrical distribution system.
Background distortion possible
UtilityTransformer
Linear-Load Motor
Linear-Load Motor
Disturbance to otherdevices
Current Distortion
Affects device level performance.
Voltage Distortion
Affects system level performance.
99Classified as Business
Ideal 3 Phase Sine Waves
1010Classified as Business
Harmonic distortion by nonlinear loads
1111Classified as Business
Harmonic distortion by nonlinear loads
1212Classified as Business
Harmonic distortion by nonlinear loads
1313Classified as Business
The Effects of High Harmonics
Current distortion causes Extra heating of power
transformers
Nuisance tripping of relays and circuit breakers
Cable heating
Causes voltage distortion
Resulting in Equipment downtime
Premature component failures
Higher utility costs
Impacts other customers served by the utility provider.
Voltage distortion Effects other devices connected to the
building’s electrical system.
Cause malfunctioning of sensitive electronic devices: servers, security systems, telecom, MRI, etc.
Can effect devices that rely on timing from a clean sine wave
1414Classified as Business
According to IEEE – Harmonics Will Cause:
• Distortion of mains supply voltage, • Unwanted currents flowing in the supply
network generate additional energy lossesLoss of Energy
• Additional acoustic noise from motors and other apparatus, reducing the efficiency of motors.
Inefficiency of Motors
• High harmonic amplitudes may not only cause malfunctions, additional losses and overheating, but also overload the power distribution network and overheat the neutral conductor and cause it to burn out.
Increased Operating Cost
Loss of Money
1515Classified as Business
Harmonics in Building Electrical Systems
The Cause
The Effects
The Standards
The Solutions
1616Classified as Business
IEEE-519-2014 is the standard.
IEEE – 519 2014 goals: Defines the specific and separate
responsibilities for utilities and users; to maintain the voltage THD within
acceptable limits at the Point of Common Coupling (PCC);
to protect the user and utility equipment from the negative impact of harmonics.
The individual responsibilities are: User - limit harmonic currents at the
PCC to prescribed levels Utility - limit voltage distortion at the
PCC to prescribed levels by maintaining system impedance as necessary
1717Classified as Business
IEEE 519-2014 Harmonic Guidelines
IEEE 519-2014 Standards and Recommendations• Concerned with the Point of Common Coupling (PCC).
(The point where the utility service connects to the customer.)
• The goal of the standard is to limit voltage distortion at PCC1:
Medium Voltage Level
Low Voltage - Plant Level
Equipment Level
1818Classified as Business
Current distortion Limits for General Distribution Systems (120V through 69 kV)
Maximum Harmonic Current Distortion in Percent of IL
ISC/IL <1111<=h<1
7 17<=h<2323<=h<3
535<=h<=5
0TDD (%)
<20 4 2 1.5 0.6 0.3 5
20<50 7 3.5 2.5 1 0.5 8
50<100 10 4.5 4 1.5 0.7 12100<100
0 12 5.5 5 2 1 15
>1000 15 7 6 2.5 1.4 20
Even harmonics are limited to 25% of the odd harmonic limits above
IEEE 519-2014 recommended limits:
Rsc = ISC / ILISC=maximum short circuit current at PCCIL=maximum demand load current (fundamental frequency component) at PCC
1919Classified as Business
MCT-31 Harmonics CalculationModule
Designed to give a valuable estimation with less then 5-10 parameter settings
Has been designed with a high focus on userfriendliness
Does not need support from advanced calculation resources, which allows for usage on a laptop
2020Classified as Business
Harmonic Analysis
• May be required as part of VFD submittal.
• Info needed to perform analysis:- Transformer kVA and
impedance.- List of VFDs you are
providing.- VFD specs.
• Shows harmonic contribution of the VFDs being provided.
2121Classified as Business
Harmonics in Building Electrical Systems
The Cause
The Effects
The Standards
The Solutions
2222Classified as Business
Limiting of Harmonics
Active Front End
Low Harmonic Drive
Two solutions are possible: Compensation at the
Point of Common Coupling (PCC)
Point-of-Load Compensation (PLC)
6-pulse Drives or Drives with 5% Passive Filters
PCC Compensation
PLC compensation
Notes: there are no regulations, which require THDi≤5% at drive terminals.
PLC compensation
Limiting harmonic currents (IEEE 519)
Customers Needs:
2323Classified as Business
Mitigation solutions
All Trane Drives have dual DC-link reactors (chokes) as standard feature. This provides the equivalent harmonic filtering to a 5% line reactor without reducing input voltage or increasing heat generation.
This cancels the need to oversize input cables and provides improved system efficiency.
Technology is good for: Many drives on the same transformer Prolonged product life Perfect motor control
Slightly increase in drive size and weight than a drivewithout a choke
Weakness
Efficient Long lifetime Smoothest possible DCBuild-in Little impact on grid distortion
Strength
TraneIntegrated Solution
<45%
Total harmonic distortion of drives with DC or AC choke
DC drive current waveform
Dual DC Link Reactors $
2424Classified as Business
Mitigation solutions
Passive filters installed ahead of VFD.The absorption circuit is designed to reduce all harmonics.
Requires additional field wiring.
Technology is good for: For drive currents <370 ADrives loaded 40-100% In balanced applications with THDv <5%Drive packages <200 kW
Possible leading power factor at light loads.
Load dependent performance Added electrical wiring costs Limited enclosure types
Weakness
Easy add-onRobust & efficientBetter performance than
other passive filters at light loads
Use when the loading is 40–100%.
Strength
Trane Field Installed Solution
AHF010 AHF005
<5%Total harmonic distortion with AHF005
<10%Total harmonic distortion with AHF010
Passive Filters – Field Installed $$
2525Classified as Business
Mitigation solutions
TR200 drive with 5% passive filter in single enclosure.
Technology is good for:For drive currents <730 A (600 HP)Drives loaded 40-100% In balanced applications with THDv <5%NEMA 1, 12, 3R
Load dependent performance
Limited enclosure types
Weakness
Single point power Uses standard 6-pulse
drive and components.Use when the loading
is 40–100%.Options for disconnect,
bypass, dV/dT filter
Strength
Trane Custom Built-up Solution
<5%Total harmonic distortion above 60% load
Preferred Harmonic Design (PHD) $$$
2626Classified as Business
Mitigation solutions
High power 12 & 18 pulse drives First technology widely adopted and has become the American standard for harmonic mitigation.
Technology is good for:High Power applications: >400A. Loading of drives between 50-100%Balanced application with THvD of <5%Drives packages >300 A
Higher heat productionLoad dependent
performanceNot ideal if grid voltage is
unbalanced or distorted
Weakness
RobustNo resonance pointLow Cost at high powerHigh Efficiency
Strength
TraneCustom Solution
12-pulse drive current waveform
≈12%Total harmonic distortion of drives with 12 pulse rectifier
≈ 7%Total harmonic distortion of drives with 18 pulse rectifier
Multi-Pulse Drives $$$$
2727Classified as Business
Mitigation solutions
Advanced Active Filters have been designed to meet IEEE 519 requirements. AAFs are installed parallel to loads and are perfect for compensating multiple loads simultaneously.
Technology is good for:Group compensation of drives460 VAC 115 – 320 Amp RangeUp to four units can be paralleledApplications always running at partial loadGood retrofit solution
Not a ‘point source’ device for smaller VFDs
Possible resonances with grid equipment
Increasing cost and complexity.
Weakness
THD of 5% or less achievable Highest immunity
against grid and load variationsParallel device which
can’t ‘overload’
Strength
Trane Custom Solution
<5%Total harmonic distortion. Ability to scale
Advanced Active Filters (AAF) $$$$
An Active Filter can be compared to a set of noise cancelling headphones.
2828Classified as Business
Harmonics Solutions Portfolio
Notes:PLC … Point-of-Load Compensation
PCC … Point of Common Coupling
Solution PLC PCC Comments
Passive Filter √ Separate, field installed item Simplicity, traditional, and cost effective
PHD–Passive Filter √ Combines TR-200 VFD with Passive Filter
in single enclosure. Simple technology.
Multi-Pulse √ Traditional, and cost effective for high power applications.
Active Filters √ √ Ability for costs optimizations, ensure 40-60% lower space and highest
operation safety
2929Classified as Business
Mitigation SummaryNo Consideration
1. THvD need
2. Compliance need
3. Mains voltage & tolerance
4. Max voltage unbalance
5 Max grid pre-distortion
6 Generator run/back-up
7. VFD bypass need
8. Displacement PF / Reactive control
9. Amount of loads to be corrected
10. Application/load dynamics
11. Enclosure need
12. Cooling air and segregation need
13. Max ambient temperature
14. Physical size available
15. Efficiency target
16. Initial cost vs running expenses
17. Isolation needed
18. Regeneration need
There is no single solution that:
• Gives the best performance• At the lowest cost• With highest system efficiency• And satisfies all norms• Which is applicable to all size of drives• And can be used in new and retrofit
…………
The “best” fit is found considering the application, grid, and site aspects.
3030Classified as Business
Additional Resources
• Trane Engineering Newsletter, Vol 47-1- A primer for non-electrical
engineers Harmonic Distortion in Electrical Systems
- ADM-APN065-EN (March 2018) • Trane White Paper – Harmonics in
AC Systems, by Ben Sykora. Dec. 2014
• Danfoss Whitepaper- Harmonic Distortion of the AC
Power Line- Copyright 2011
3131Classified as Business
So, what should I do?
1. Review the VFD specifications2. If in doubt – ask for our review3. Take Exception to the harmonics requirement in
the specification:- The specs call for the VFDs to meet IEEE 519
standard. Since IEEE 519 is a systems standard and not a component standard, compliance cannot be determined until a harmonic analysis is performed. This requires knowing the transformer kVA and impedance rating. Once this information is provided an analysis can be performed. If additional harmonic filtering is required it can be provided at an additional cost.
3232Classified as Business
Your Dedicated Sales Support Team
• Pricing on Projects- Send us the VFD specs, schedules or the list of VFDs with the
details. (Don’t send the complete bid packet.)- Custom quotes – (allow 2-3 days)
• Submittal Creation- Send us the quote or list of VFDs and the VFD Specs.
• Harmonic Analysis- Need: Transformer kVA and impedance rating, list of VFDs and
the VFD spec requirements.• Your “Go To Team” for all things Trane Drives.
Tim Whitford• Trane Inside Sales Engineer
- Direct 815-639-8961- [email protected]
Royce Meili• Trane CSO Global Account Mgr.
- Cell: 316-633-3256- [email protected]
Thank you
Royce MeiliDanfoss Drives
Trane CSO Global Account Manager(316) 633-3256
If this webinar was helpful, please let your colleagues know that they
can sign up for the upcoming sessions.