Vacuum circuit breaker’s solenoid force evaluation

11
Vacuum circuit breaker’s solenoid force evaluation 29/12/2009

description

Vacuum circuit breaker’s solenoid force evaluation. 29/12/2009. Deliverable 1. Report on the compliance of the brand new trip coil and close coil to specification and their safety factors as derived from the laboratory experiments. EPE Switchgear -11 & 33KV Closing and Opening Coil. coil. - PowerPoint PPT Presentation

Transcript of Vacuum circuit breaker’s solenoid force evaluation

Page 1: Vacuum circuit breaker’s solenoid force evaluation

Vacuum circuit breaker’s solenoid force evaluation

29/12/2009

Page 2: Vacuum circuit breaker’s solenoid force evaluation

Deliverable 1

• Report on the compliance of the brand new trip coil and close coil to specification and their safety factors as derived from the laboratory experiments

Page 3: Vacuum circuit breaker’s solenoid force evaluation

EPE Switchgear -11 & 33KVClosing and Opening Coil

32 mm

Pull gauge

coilStopper block

Plunger

Trip hook/strike

Page 4: Vacuum circuit breaker’s solenoid force evaluation

16Kgf

232

2)(3.5)29(2(2205)7104 3.5A)F(32mm

2x

2Ai2Noμi)F(x,

EPE solenoid Force and Stroke EPE solenoid Force and Stroke RelationshipRelationship!!

μo is the Permeability of free spaceN is the number of coil turnsA is the effective cross sectionali is the max current x is the stroke length of the plunger

N.B. Data sheet of the coil attached in appendix

! A. E. Fitzgerald, Electric Machinery: The process, devices and systems of electromechanical energy conversion, McGraw Hill 1971

Page 5: Vacuum circuit breaker’s solenoid force evaluation

7.5Kgf

28

2)(3.5)23(2(350)7104 3.5A)F(8mm

2x

2Ai2Noμi)F(x,

ETAH solenoid Force and Stroke ETAH solenoid Force and Stroke RelationshipRelationship!!

μo is the Permeability of free spaceN is the number of coil turnsA is the effective cross sectionali is the max current x is the stroke length of the plunger

N.B. Data sheet of the coil attached in appendix

! A. E. Fitzgerald, Electric Machinery: The process, devices and systems of electromechanical energy conversion, McGraw Hill 1971

Page 6: Vacuum circuit breaker’s solenoid force evaluation

Stroke length (x) mm

Forc

e in

Kgf

EPE Solenoid Force & Amps vs Plunger positionEPE Solenoid Force & Amps vs Plunger position

Page 7: Vacuum circuit breaker’s solenoid force evaluation

Forc

e in

Kgf

TAMC) (ETAH) Solenoid Force & Amps vs Plunger positionTAMC) (ETAH) Solenoid Force & Amps vs Plunger position

Stroke length (x) mm

Page 8: Vacuum circuit breaker’s solenoid force evaluation

Photo Gallery

New Solenoid testing

Page 9: Vacuum circuit breaker’s solenoid force evaluation
Page 10: Vacuum circuit breaker’s solenoid force evaluation
Page 11: Vacuum circuit breaker’s solenoid force evaluation

Appendix – Solenoid Data Sheet