Utility Management Software: Integrating AMR-AMI Data Into WindMil 8

download Utility Management Software: Integrating AMR-AMI Data Into WindMil 8

of 19

Transcript of Utility Management Software: Integrating AMR-AMI Data Into WindMil 8

  • 8/13/2019 Utility Management Software: Integrating AMR-AMI Data Into WindMil 8

    1/19

    Integrating AMR-AMI Data into Win

    James S Cross, PE

    Planning Engineer

    Homer Electric Association

    Kenai, Alaska

    http://www.milsoft.com/
  • 8/13/2019 Utility Management Software: Integrating AMR-AMI Data Into WindMil 8

    2/19

    Improving Your WindMil Model w/ AM

    Historically, planners and system operators have had vedata regarding the individual loads on a distribution syste

    Most distribution planning models have used (still use?) billing data (energy) from a CIS system to determine the snapshot (power) for the load-flow analysis.

    This methodology is known as load allocation. Load allocis as much of an art as is system protection. There are hard & fast rules . every system and every case is diffe

    Given the importance of the model loading to the load-floresults, an accurate portrayal of the system loads is criticorder to get good results.

  • 8/13/2019 Utility Management Software: Integrating AMR-AMI Data Into WindMil 8

    3/19

    EA Model Improvements

    The use of GIS systems at utilities has led to sig

    improvements in model data, and large detailedhave become prevalent.

    Load modeling has not seen the significant data

    improvements that the system (impedance) mod

    seen. End-of-line load data is still challenging, especia

    time data.

  • 8/13/2019 Utility Management Software: Integrating AMR-AMI Data Into WindMil 8

    4/19

    AMR/AMI Enters the Utility World

    Utilities now have the ability to obtain more data

    end-of-line loads with the implementation of AMsystems.

    Two-way AMR/AMI systems allow for even mor

    information flow, as some meters can be built or

    programmed to detect more than just kWh usag

  • 8/13/2019 Utility Management Software: Integrating AMR-AMI Data Into WindMil 8

    5/19

    What can AMR/AMI do for me?

    In addition to reading kWh:

    Many AMR meters capture blinks or momentary outage Voltage data

    Ability to create a true monthly kWh reading

    Real demand (kW) data

    Equipment Information

    This information can be used to make your WindM

    better.

  • 8/13/2019 Utility Management Software: Integrating AMR-AMI Data Into WindMil 8

    6/19

    What else can AMR/AMI do for me?

    It can make a large model even larger

    You are counting on another enterprise application to getyou correctly.

    If the meter data moves through multiple enterprise applic

    each interface is a potential source of new data errors.

    It can force you to use mixed methods to populate your m

    AMR to populate 2S meter loads Billing / GIS to populate other loads

  • 8/13/2019 Utility Management Software: Integrating AMR-AMI Data Into WindMil 8

    7/19

    The question you MUST ask yourself

  • 8/13/2019 Utility Management Software: Integrating AMR-AMI Data Into WindMil 8

    8/19

    AMI at Homer Electric

    Homer Electric began implementing a Cannon Technologsystem in 2005.

    We started w/ a two substation / 300 meter pilot project.

    Since then weve deployed ~ 5,000 meters per year. Ninedistribution substations will read approximately 27,000 129 feeders.

    All 2s meters will be changed out by years end.

    We will revisit 3 metering to determine scope / costs.

  • 8/13/2019 Utility Management Software: Integrating AMR-AMI Data Into WindMil 8

    9/19

    AMR WindMil Interface

    WindMil can read data directly from seve

    AMR systems by using a MultiSpeak inte Before using the interface, you need to c

    your AMR/AMI vendor to get MultiSpeakconfiguration files for your enterprise soft

  • 8/13/2019 Utility Management Software: Integrating AMR-AMI Data Into WindMil 8

    10/19

    AMR WindMil Interface

  • 8/13/2019 Utility Management Software: Integrating AMR-AMI Data Into WindMil 8

    11/19

  • 8/13/2019 Utility Management Software: Integrating AMR-AMI Data Into WindMil 8

    12/19

    AMR WindMil Interface

  • 8/13/2019 Utility Management Software: Integrating AMR-AMI Data Into WindMil 8

    13/19

    AMR WindMil Interface

  • 8/13/2019 Utility Management Software: Integrating AMR-AMI Data Into WindMil 8

    14/19

    Distribution System Phasing w/ AMI

    Most power-line carrier (PLC) AMR systems interface somof communications on the primary line buses within the

    substations. There is some sort of coupling onto each phase of each f

    Two-way AMR allows us to send a signal down each phameters connected to that phase, and get a response backmeters that heard the signal.

    If we can determine which meters are on what phase, we

    electrically phase our distribution feeders. If we truly know our system phasing in our WindMil mode

    can then more accurately run unbalanced analysis to modis going on with our distribution system.

  • 8/13/2019 Utility Management Software: Integrating AMR-AMI Data Into WindMil 8

    15/19

    Voltage Drop Balanced Mode

  • 8/13/2019 Utility Management Software: Integrating AMR-AMI Data Into WindMil 8

    16/19

    Voltage Drop Unbalanced Mode

  • 8/13/2019 Utility Management Software: Integrating AMR-AMI Data Into WindMil 8

    17/19

    Distribution System Phasing w/ AMR

    WindMil voltage-drop analyses can be run in un

    mode. This mode will more accurately reflect ph

    unbalances on your distribution system.

    This affects results of:

    Voltage Drop Analysis

    Load Balance Activity

    Set Regulation Activity

    Loss Study

  • 8/13/2019 Utility Management Software: Integrating AMR-AMI Data Into WindMil 8

    18/19

    Past MUC Presentations

    AMR & SCADA Data in WindMil, by

    Wilhite (2007)

    AMR Data vs. Load Allocation, by B

    Kersting (2007)

  • 8/13/2019 Utility Management Software: Integrating AMR-AMI Data Into WindMil 8

    19/19

    Questions???

    http://www.milsoft.com/contact-us