UPS H series introduction UPS training June 2006 Markus Schwab.

21
E nergy S ystems UPS H series introduction UPS training June 2006 Markus Schwab
  • date post

    19-Dec-2015
  • Category

    Documents

  • view

    218
  • download

    3

Transcript of UPS H series introduction UPS training June 2006 Markus Schwab.

E n er gy S ystem s

UPS H series introductionUPS training June 2006

Markus Schwab

© Apr 18, 2023 Delta Energy Systems 2

E n er gy S ystem s

Features:

True Double Conversion On-Line Topology

Wide Input Voltage Range

High Input Power Factor

UPS Auto-Restart

Battery Start Function

Economic mode (for single phase models)

Emergency Power Off (EPO)

Alarm Buzzer Cancel

Bypass:

- Automatic Bypass

- Maintenance Bypass

© Apr 18, 2023 Delta Energy Systems 3

E n er gy S ystem s

Communication:

RS232(DB9), AS400(DB9), Dry-Contact(DB9)

Optional SNMP card

Options:

Optional dual input power:

- For Hot standby Redundant

Optional Output Transformer

- For other voltage ratings or galvanic separation

© Apr 18, 2023 Delta Energy Systems 4

E n er gy S ystem s

H-Series 15kVA - 30kVAGeneral

Technology: On-Line

Input / Output: 3-phase / 3-phase and 3-phase / 1-phase(15/20KVA)

Cabinet type: Tower

Rating: 15kVA, 20kVA, 30kVA

Input nominal: 3-phase 380//400/415VAC

Input range: 270 - 485VAC, 3-phase

Input power factor: >0,95

Input frequency: 50/60Hz (auto-selectable)

Output voltage: 3-phase: 380/400/415VAC1-phase: 220/230/240VAC

Output power factor: 0,8

Output waveform: Pure sine wave

Overload: 102% - 125 for 1 min.126% - 150% for 30sec.> 151% - 2sec.

© Apr 18, 2023 Delta Energy Systems 5

E n er gy S ystem s

H-Series 15kVA - 30kVATemperature range: 0°C - 40°C

Audible noise: 60dBA

Crest factor: 3:1

Software: UPSentry included

Battery

Integrated Battery: Yes, 20 x 26Ah or 20 x 40Ah

Extension possible: Yes

Battery replacement: Yes

Communication

Front: Graphical Interface with LED indicators

Interface1: RS232 (D-Sub Connector)

Interface 2: Dry contacts (D-Sub Connector)

Interface 3: SNMP card (optional)

Interface 4: AS400

© Apr 18, 2023 Delta Energy Systems 6

E n er gy S ystem s

H-Series 15kVA - 30kVA

Battery Size WeightCabinet H*W*D

20 x 26Ah 860x380x650mm 270kg20 x 40Ah 860x380x650mm 370kg

Model I/O Input Input Output Size WeightPhase Voltage Voltage range voltage H*W*D

15kVA 3/3 380/400/415VAC 270 - 485VAC 380/400/415VAC 860x380x650mm 108kg20kVA 3/3 380/400/415VAC 270 - 485VAC 380/400/415VAC 860x380x650mm 108kg30kVA 3/3 380/400/415VAC 270 - 485VAC 380/400/415VAC 860x380x650mm 108kg

15kVA 3/1 380/400/415VAC 270 - 485VAC 220/230/240VAC 860x380x650mm 108kg20kVA 3/1 380/400/415VAC 270 - 485VAC 220/230/240VAC 860x380x650mm 108kg

© Apr 18, 2023 Delta Energy Systems 7

E n er gy S ystem s

1 2 3 4

A

B

C

D

4321

D

C

B

A

DELTA ELECTRONICS, INC.THESE DRAWINGS AND SPECIFICATIONS ARE TH E PROPERTY O F DELTA ELECTRONICS, INC.AND SHALL NO T BE REPRO DUCED OR USED AS THE BASIS FOR THE M ANUFACTURE ORSELL OF APPARATUSES OR DEVICES WITHO UT PERM ISSION.

PCB:

LY.REV:Date:

DESCRIPTION: FILE NAM E:

Drawn:

SCHEM ATIC OF UPS

Checked Approved PART NO:

OF

SHEETREV.

Frame Name:FR9-5R00.DOT

220V 1P2W230V240V

220/380V Y230/400V Y240/415V Y

INPUT

AD/DC DC/DC DC/ACSTATICSWITCH

CHARGER

CONTROLLER

MANUALSWITCH

X-FM

220V230V240V

OPTIONAL

220V230V240Vor

110/220V115/230V120/240V

OUTPUT

UPS 3/1

BATTERY12V*20

05/16/2001 00 JENNY.YANG

00 2 2

H-series Block Diagram

© Apr 18, 2023 Delta Energy Systems 8

E n er gy S ystem s

1 2 3 4

A

B

C

D

4321

D

C

B

A

DELTA ELECTRONICS, INC.THESE DRAWINGS AND SPECIFICATIONS ARE THE PROPERTY OF DELTA ELECTRONICS, INC.AND SHALL NOT BE REPRODUCED OR USED AS THE BASIS FOR THE MANUFACTURE ORSELL OF APPARATUSES OR DEVICES WITHOUT PERMISSION.

PCB:

LY.REV:Date:

DESCRIPTION: FILE NAME:

Drawn:

SCHEMATIC OF UPS

Checked Approved PART NO:

OF

SHEETREV.

Frame Name:FR9-5R00.DOT

220/380V Y230/400V Y240/415V Y

220/380V Y230/400V Y240/415V Y

INPUT

AD/DC DC/DC DC/ACSTATICSWITCH

CHARGER

CONTROLLER

MANUALSWITCH

X-FM

220/380V Y230/400V Y240/415V Y

OPTIONAL

220/380V230/400V240/415V

or127/220V120/208V110/190V

OUTPUT

UPS 3/3

BATTERY12V*20

00 1 205/16/2001 00 JENNY.YANG

© Apr 18, 2023 Delta Energy Systems 9

E n er gy S ystem sOperation modes

On-Line Mode: Press “ON” key in Bypass Mode

Overload back to normal

Utility restored in Back-up Mode

Back-up Mode: Utility is not available

Cold-start (press “battery start” key and “ON” key)

Bypass Mode: Press “OFF” key in On-Line Mode

Overload

Abnormal Fail

© Apr 18, 2023 Delta Energy Systems 10

E n er gy S ystem s Front Control Panel

1. Inverter ON Switch

2. Inverter OFF Switch

3. Language Select and Other

Function Switch

4. LCD Function SELECT and

Alarm Cancel Switch

5. I/P1 LED

6. I/P2 LED

7. Bypass LED

8. AC/DC LED

9. Battery LED

10. DC/AC LED

11. O/P LED

12. Emergency Power Off

13. LCD Display

© Apr 18, 2023 Delta Energy Systems 11

E n er gy S ystem sRear PanelRear Panel

15/20/30KVA 3/3 15/20KVA 3/1

© Apr 18, 2023 Delta Energy Systems 12

E n er gy S ystem s

15/20/30KVA 3/3 with Dual input Battery Cabinet

© Apr 18, 2023 Delta Energy Systems 13

E n er gy S ystem s

1. MANUAL BYPASS SWITCH

2. INPUT TERMINALS

3. OUTPUT TERMINALS

4. EXTERNAL BATTERY CABINET TERMINALS

5. EXHAUST FANS

6. TRUE RS-232 INTERFACE PORT

7. AS-400 INTERFACE PORT

8. DRY CONTACT INTEERFACE PORT

9. REMOTE EMERGENCY POWER OFF

10. SNMP CARD

11. BATTERY START KEY

12. MAIN INPUT BREAKER

13. BYPASS INPUT BREAKER

14. OUTPUT BREAKER

15. BATTERY FUSE

16. BATTERY CABINET AC I/P SOCKET

17. BATTERY CABINET DC O/P TERMINALS

18. BATTERY FUSE

19. BYPASS TERMINALS

20. EXHAUST FAN

© Apr 18, 2023 Delta Energy Systems 14

E n er gy S ystem s H series Runtime table H 26AH BBU 13min

H 40AH BBU 23min

H 26AH BBU*2 35min

H 40AH BBU*2 60min

H 40AH BBU*3 110min

H 26AH BBU 7min

H 40AH BBU 15min

H 26AH BBU*2 25min

H 40AH BBU*2 40min

H 40AH BBU*3 70min

H 40AH BBU*4 110min

H 26AH BBU*2 13min

H 40AH BBU*2 23min

H 40AH BBU*3 40min

H 40AH BBU*4 60min

H 40AH BBU*5 84min

H 40AH BBU*6 120min

H 15KVA3/1 & 3/3

H 20KVA3/1 & 3/3

H 30KVA3/3

H 26AH BBU: 26AH/12V*20

H 40AH BBU: 26AH/12V*20

Both battery cabinets dimension are the same as the UPS

© Apr 18, 2023 Delta Energy Systems 15

E n er gy S ystem s LCD Function Press “SELECT” key

(for 3/1 models)

© Apr 18, 2023 Delta Energy Systems 16

E n er gy S ystem s

Press “SELECT” key

(for 3/3 models)

© Apr 18, 2023 Delta Energy Systems 17

E n er gy S ystem s Communications InterfaceRS-232 :——————————————————————————————————————A 9-pin female SUB-D connector is provided on the UPS’s rear panel to provide signals of the UPS to the computer. Using the software product, the user can check the power status. The detail signals are as follows:

© Apr 18, 2023 Delta Energy Systems 18

E n er gy S ystem s

AS-400:——————————————————————————————————————A 9-Pin female SUB-D connector is provided on the UPS’s rear panel to provide the following signals to IBM AS-400 computer. Operation on normal Operation on battery Operation on bypass Low battery prealarm

© Apr 18, 2023 Delta Energy Systems 19

E n er gy S ystem s

Dry Contact :——————————————————————————————————————The sub-D communication port (9-pin female type) is used to power on/off the UPS by external control signal. UPS also can transfer its status through this port.

© Apr 18, 2023 Delta Energy Systems 20

E n er gy S ystem s

Remote Emergency Power Off :——————————————————————————————————————If short pin(2, 3) or pin(2, 5) or pin( 4, 5) or pin(4, 3), then the UPS will be powered off.(NOTE: This port must not intend to connect to the Telecom. Port. )

© Apr 18, 2023 Delta Energy Systems 21

E n er gy S ystem s

Thank You!