Ume Pqm300t Eng

86
SERVICE QUALITY REGISTER PQM300T Instruction Manual

description

PQM300t

Transcript of Ume Pqm300t Eng

  • SERVICE QUALITY REGISTER PQM300T

    Instruction Manual

  • UME_PQM300T_eng Rev.: J (10/10)

    All rights reserved. No part of this publication may be reproduced by whatever means, without the prior written permission of Ingeteam T&D. Ingeteam T&D reserves the right to make any changes without prior notice.

  • INDEX

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual III

    1. GENERAL DESCRIPTION .......................................................................................................................................... 51.1 Functions .......................................................................................................................................................... 51.2 User interface .................................................................................................................................................... 61.3 Selecting the model ........................................................................................................................................... 71.4 Environmental conditions ................................................................................................................................... 81.5 Tests ................................................................................................................................................................ 8

    1.5.1 Electrical tests .......................................................................................................................................... 81.5.2 Environmental tests ................................................................................................................................... 81.5.3 Mechanical tests ....................................................................................................................................... 8

    1.6 Wiring diagram .................................................................................................................................................. 91.7 Block diagram ................................................................................................................................................. 13

    2. HARDWARE ........................................................................................................................................................... 142.1 Constructive characteristics. Horizontal box ........................................................................................................ 142.2 Constructive characteristics. Assembly in TCP .................................................................................................... 142.3 Rear terminals ................................................................................................................................................. 152.4 Options for rear communication ports: ............................................................................................................... 152.5 Technical characteristics .................................................................................................................................. 16

    2.5.1 Power supply .......................................................................................................................................... 162.5.2 Output contact ....................................................................................................................................... 162.5.3 Digital inputs (optoisolated) ..................................................................................................................... 162.5.4 IRIG-B input ........................................................................................................................................... 172.5.5 Phase and neutral current circuits (rated current 1/5 A) .............................................................................. 182.5.6 Voltage circuits ....................................................................................................................................... 18

    2.6 Operating frequency ......................................................................................................................................... 183. SAGS, SWELLS AND INTERRUPTIONS .................................................................................................................... 19

    3.1 Sags and swells ............................................................................................................................................... 193.1.1 Events summary ...................................................................................................................................... 203.1.2 Event chronological noting ....................................................................................................................... 213.1.3 Depth-duration tables .............................................................................................................................. 22

    4. ADDITIONAL FUNCTIONS ...................................................................................................................................... 244.1 Overcurrent ..................................................................................................................................................... 244.2 THD overexcitation ........................................................................................................................................... 24

    5. DATA ACQUISITION ............................................................................................................................................... 265.1 Measurements ................................................................................................................................................. 26

    5.1.1 Power calculation .................................................................................................................................... 265.1.2 Single-pole sequence .............................................................................................................................. 275.1.3 Reverse sequence ................................................................................................................................... 275.1.4 Unbalance ............................................................................................................................................. 27

    5.2 Historical/Statistical ......................................................................................................................................... 275.2.1 Historical ............................................................................................................................................... 285.2.2 Statistical .............................................................................................................................................. 31

    5.3 Oscillograph data recording ............................................................................................................................... 335.4 Events ............................................................................................................................................................ 345.5 Control messages ............................................................................................................................................. 34

    6. REGISTER CONFIGURATION .................................................................................................................................. 396.1 Time setting and synchronization ....................................................................................................................... 39

    6.1.1 Time setting ........................................................................................................................................... 396.1.2 Synchronization ...................................................................................................................................... 39

    6.2 Programming digital outputs ............................................................................................................................. 396.3 Programming LEDs ......................................................................................................................................... 406.4 Programming logic outputs ............................................................................................................................... 406.5 Programming General settings ........................................................................................................................... 426.6 Communication configuration ............................................................................................................................ 426.7 Automatic Call ................................................................................................................................................. 436.8 Firmware load .................................................................................................................................................. 43

    APPENDIX I. KEYBOARD / DISPLAY ............................................................................................................................ 44

  • INDEX

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual IV

    I.1. Use of the keyboard/display .............................................................................................................................. 44I.1.1 See settings and magnitudes .................................................................................................................... 44I.1.2 Change settings ....................................................................................................................................... 44

    I.2. Menu .............................................................................................................................................................. 45APPENDIX II. RECEPTION, STORAGE, INSTALLATION AND TESTING ........................................................................... 47

    II.1. Reception and storage ..................................................................................................................................... 47II.2. Wiring procedure ............................................................................................................................................ 47II.3. Register addressing ......................................................................................................................................... 48II.4. Commissioning ............................................................................................................................................... 48II.5. Reception tests .............................................................................................................................................. 48

    II.5.1 Material needed ...................................................................................................................................... 48II.5.2 Measurement tests .................................................................................................................................. 49II.5.3 Register time setting ............................................................................................................................... 49

    APPENDIX III. PREVENTIVE MAINTENANCE ................................................................................................................ 50III.1. Failure detection ........................................................................................................................................... 50III.2. Error handling procedure ................................................................................................................................ 51

    APPENDIX IV. USER INTERFACE ................................................................................................................................ 52IV.1. PQM Console ................................................................................................................................................. 52

    IV.1.1 Software installation ............................................................................................................................... 52IV.1.2 Installation and unit configuration ........................................................................................................... 53IV.1.3 Password ............................................................................................................................................... 56IV.1.4 Remote communication .......................................................................................................................... 57IV.1.5 Tool bar options ..................................................................................................................................... 58IV.1.6 Main menu options ................................................................................................................................ 58IV.1.7 File menu .............................................................................................................................................. 59IV.1.8 Register menu ....................................................................................................................................... 61IV.1.9 Specific menus for each window .............................................................................................................. 73IV.1.10 See menu ............................................................................................................................................ 73IV.1.11 Window menu ...................................................................................................................................... 73IV.1.12 Help menu .......................................................................................................................................... 74IV.1.13 Graphic handling ................................................................................................................................. 74IV.1.14 Automatic Call ..................................................................................................................................... 76

    IV.2. Sipcon Console .............................................................................................................................................. 82IV.2.1 Work installation .................................................................................................................................... 82IV.2.2 Unit selection ........................................................................................................................................ 83IV.2.3 Generals ................................................................................................................................................ 83IV.2.4 PQM settings ......................................................................................................................................... 83IV.2.5 Measurements ....................................................................................................................................... 85IV.2.6 Quality console ...................................................................................................................................... 85

  • 4BGENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 5

    1. GENERAL DESCRIPTION PQM-300 family models are service quality registers and they constitute the basic element for the quality analysis and monitoring according to UNE-EN 50160 standard. They can be used as autonomous elements of an electrical position or as elements integrated in a Protection and Control Integrated System.

    There are different models, which only differ in some hardware points or in its functionality. The Firmware can be loaded in the unit through the serial port, which makes the version upgrading easier.

    This manual does not correspond to a particular PQM300T model, but it refers to the whole family. For each model, it will be only applied everything related to its physical characteristics and its functionalities.

    1.1 FUNCTIONS The requirements of the IEC 61000-4-30 standard are fulfilled for the frequency measurements, simple voltage, unbalance and harmonic measurements.

    Measurements

    Frequency

    Simple voltage

    Compound voltage

    Harmonics up to the 15 one

    Simple current

    Active power (with sign)

    Reactive power (with sign)

    Apparent power

    Active energy counter (positive and negative)

    Reactive energy counter (positive y negative)

    Power factor (with sign)

    Sags, interruptions and overvoltage analysis

    Overcurrent

    Overexcitation THD

    Voltage, current, power and harmonic historicals

    Voltage, current, power and harmonic statistical

    IRIG-B time synchronization

    Data acquisition

    Events recording

    Oscillograph

  • 4BGENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 6

    1.2 USER INTERFACE

    Local. It incorporates a front panel with:

    7 red LED indicator and another one green/red

    Connection via RS232 for direct connection with a PC. Procome Protocol.

    Remote. Depending on the model, it incorporates, on the rear plate, one or two glass Fibre Optic interfaces (ST type connector), plastic Fibre Optic, RS232 or RS485 for connecting to a PC, modem or Substation Control Unit (in Integrated Systems). The protocol is Procome.

    It can optionally dispose of:

    16-key keyboard

    Display of 2 lines with 16 character each one.

  • 4BGENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 7

    1.3 SELECTING THE MODEL The different possibilities defining a model can be the following ones:

  • 4BGENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 8

    1.4 ENVIRONMENTAL CONDITIONS

    Operating temperature -10 up to 55 C Storage temperature -40 up to 85 C Relative humidity up to 95% without condensation

    1.5 TESTS

    1.5.1 Electrical tests

    Measurement of dielectric rigidity s/ IEC60255-5, series C (2 kV, 1 minute) Measur. of insulation resistance s/ IEC 60255-5,>10 Gigaohms at 500 Vdc Pulse (shock wave) s/ IEC -60255-4, appendix E., class III HF disturbances s/ IEC -60255-22-1, class III Fast transients s/ IEC 61000-4-4, class IV Electrostatic discharges s/ IEC 61000-4-2, class IV Overvoltage pulses (surge) s/ IEC 61000-4-5, class IV Micro-cuts s/ IEC 60870-2-1, 100ms at 110 Vdc Radiated electromagnetic interference s/ EN 61000-6-4 Immunity to radiated fields s/ IEC 61000-4-3, class III Immunity to induced signals of radiofrequency s/ IEC 61000-4-6, class III Immunity to low frequency magnetic fields s/ IEC 61000-4-8

    1.5.2 Environmental tests

    Cold s/ IEC 60068-2-1 (-40C) Dry heat s/ IEC 60068-2-2 (+85C) Humid heat s/ IEC 60068-2-78 (+70C, 93% Relat. Hum.) Thermal shock s/ IEC 60068-2-14 (-20/70C 2 cycles of 4-hours each) Operating range -10C. up to 55C

    1.5.3 Mechanical tests

    Vibration test s/ CEI 6025521-1class II Shock and bump test s/ CEI 60255-21-1 class I

  • 4BGENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 9

    1.6 WIRING DIAGRAM In the following graphics one of the possible PQM 300T configurations

    The digital input common point corresponds to the negative level. The input connection is indicated in the Digital inputs (optoisolated) section.

    Figure 1. 14 outputs / 17 inputs box model

  • 4BGENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 10

    Figure 2. 7 outputs / 35 inputs box model

  • 4BGENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 11

    Figure 3. 14 inputs/ 17 outputs TCP model

  • 4BGENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 12

    Figure 4. 7 outputs / 35 inputs TCP model

  • 4BGENERAL DESCRIPTION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 13

    1.7 BLOCK DIAGRAM

    Figure 5. PQM-300 block diagram

  • 5BHARDWARE

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 14

    2. HARDWARE

    2.1 CONSTRUCTIVE CHARACTERISTICS. HORIZONTAL BOX

    Units external dimensions

    2.2 CONSTRUCTIVE CHARACTERISTICS. ASSEMBLY IN TCP

    Units external dimensions

  • 5BHARDWARE

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 15

    2.3 REAR TERMINALS

    PQM-300 T. Pin type terminals

    2.4 OPTIONS FOR REAR COMMUNICATION PORTS:

    Single output

    OF (glass or plastic) RS485 RS232

    Double output OF + OF OF +RS232 RS485+RS232 RS232+RS232

  • 5BHARDWARE

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 16

    2.5 TECHNICAL CHARACTERISTICS

    2.5.1 Power supply

    Model 24 48 Vdc 125 220 Vdc Operating range 18 to 60 Vdc 86 to 280 Vdc Admissible ripple 100 % 100 % Minimum burden 10 W 10 W Maximum burden 20 W 20 W

    2.5.2 Output contact

    2.5.3 Digital inputs (optoisolated)

    Wide range:

    High: Operating range 86 to 280 Vdc (inactive under 60 Vdc)

    Low: Operating range 18 to 160 Vdc (inactive under 15 Vdc)

    Burden: < 3 mA They are single-directionals. In the interconnection wirings, they are represented as:

    n+1n

    And its corresponding polarity is the following one:

    n+1n +

    -

    Restricted range:

    24 Vdc: Operating range 18 to 34 Vdc (inactive under 15 Vdc)

    48 Vdc: Operating range 36 to 60 Vdc (inactive under 26 Vdc)

    Type Trip Signalling Location 1 to 6 7 Carry (permanent) 8 A 10 A Make (0.5 s) 30 A 30 A Breaking capacity (with resistive load) at 220 Vdc 0.5 A 0.15 A at 125 Vdc 1 A 0.4A at 48 Vdc 3 A 2 A Breaking capacity (L/R=40 ms) at 220 Vdc 0.2 A 0.15 A at 125 Vdc 0.5 A 0.5A at 48 Vdc 0.5 A 0.5 A

  • 5BHARDWARE

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 17

    125 Vdc: Operating range 85 to 150 Vdc (inactive under 60 Vdc)

    220 Vdc: Operating range 65 to 264 Vdc (inactive under 110 Vdc)

    Burden:

  • 5BHARDWARE

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 18

    2.5.5 Phase and neutral current circuits (rated current 1/5 A)

    Thermal capacity In =5A In=1A

    Continuous 20 A 3 A

    For 1 second 500 A 10 A

    For half cycle 1250 A 20 A

    Burden for In = 5 A

  • 6BSAGS, SWELLS AND INTERRUPTIONS

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 19

    3. SAGS, SWELLS AND INTERRUPTIONS The analysis fulfils the IEC 61000-4-30 standards for the sag, swell and interruption analyses and results.

    3.1 SAGS AND SWELLS The PQM register analyses the sags and swells of the simple and/or compound voltages, classifying them in 2-input tables and event chronological lists (detailed and summary). The parameters defining these analyses are the depth of the sag or swell and the time this event lasts.

    The depth is calculated according to rated voltage:

    100%Un

    UhsUnDepth = (3.1 equation)

    where:

    Un simple and/or compound nominal voltage (setting)

    Uhs phase maximum simple and/or compound voltage in situation of sag or swell. The analysis is carried out independently for each channel. The refreshed measurement of a cycle is used every half cycle, so that we have an updated measurement every half cycle.

    Sag is considered to occur when the sag threshold is exceeded in any of the three simple and/or compound voltages, depending on the selected unit. The sag is considered to be over, when none of the three voltages is in situation of gap (exceeding in the hysteresis the setting threshold). The duration is considered from the very moment the first channel enters the sag until all of them return to normality. The sag width is the highest depth (minimum voltage) of all the channels in swell.

    Swell is considered to occur when the swell threshold is exceeded in any of the three simple and/or compound voltages, depending on the unit wiring procedure. The overvoltage is considered to be over when none of the three voltages is already in overvoltage situation (exceeding in the hysteresis the setting threshold). The swell duration is considered to be from the very moment the first channel enters in swell until all of them return to normality. The swell width is the highest depth (maximum voltage) of all the channels in swell.

    In the event summary queue, the sags and swells are stored, grouped according to the criteria previously described. The data of each phase is located in the event queue in an individual way.

    The measurement precision is 0.2% of the nominal voltage. The duration precision is cycle of the signal at the beginning plus another cycle at the end.

    The hysteresis can be programmed. For example for a 2% hysteresis, if sag is considered to be a drop higher than the 10%, the voltage measured must be over the 8%, in order to consider it has recovered.

    The parameters used for the gap and swell detection are the following ones:

    Sag threshold. Minimum variation respecting to the nominal voltage to consider sag.

    Sag hysteresis. Minimum variation to recover from the sag.

    Swell threshold. Minimum variation respecting to the nominal voltage to consider swell.

    Swell hysteresis. Minimum variation to recover from the swell.

    Minimum separation between events in order to be considered the same event or a new one. There are also other parameters, used for signalling sags and swells which are those below:

    Sensitivity for sag. Variation to consider the new step inside the sag (increase and decrease events).

  • 6BSAGS, SWELLS AND INTERRUPTIONS

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 20

    Sensitivity for swell. Variation to consider the new step inside the swell (increase and decrease events).

    Maximum number of notes per event. It restricts the number of notes registered in each sag and swell. It only affects to those of increase and decrease notes.

    Sag maximum time . Maximum time since the sag start, during which the sag pulse signal is kept active. Once this time is elapsed, the pulse signal is deactivated, although the sag continues and no more notes are done in that sag. If the time is set to 0, it is the same as if this option would be deactivated, so the sag end is not restricted in a time and the sag pulse signal coincides with the sag one.

    Swell maximum time. Maximum time since the swell start, during which the swell pulse signal is kept active. Once this time is elapsed, the pulse signal is deactivated, although the swell continues and no more notes are done in that swell. If the time is set to 0, it is the same as if this option would be deactivated, so the sag end is not restricted in a time and the sag pulse signal coincides with the one of the sag.

    For example, having the nominal voltage set to 80V, if considering a sag starts from 72V on, the sag threshold must be set in 10%. It is deduced from 3.1 equation:

    10080

    7280%_ =thresholdSag

    In the same way, if considering the swell starts from 88V on, the swell threshold must be set in 10%.

    General setting Setting Min. Max. Step Nominal voltage (simple) 1 V 600 V 0,1 V Sag threshold 1% 100% 1% Sag hysteresis 2% 10% 1% Sag sensitivity threshold 1% 100% 1% Swell threshold 1% 100% 1% Swell hysteresis 2% 10% 1% Swell sensitivity threshold 1% 100% 1% Interruption consideration threshold 1% 100% 1% Minimum separation between events (sec) 0.01 30 0.01 Maximum notes per event 1 16000 1 Sag maximum time 0 100 0.01 Swell maximum time 0 100 0.01

    Sag tables Setting Min. Max. Step Depths (10 lines) 1% 100% 1% Times(10 columns) 0.01 sec. 3600 sec. 0.01 sec.

    Swell tables Setting Min. Max. Step Depths (5 lines) 1% 100% 1% Times(10 columns) 0.01 sec. 3600 sec 0.01 sec.

    3.1.1 Events summary Event chronological noting , showing the event summary data. Access is from Register menu with the option Bring sags. The available data are the following:

    Data

    Event type: sag/ swell

    Phases implicated: Va, Vb orVc (simple) or Vab, Vbc, Vca (compound).

    Maximum/minimum width

  • 6BSAGS, SWELLS AND INTERRUPTIONS

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 21

    Duration It has a queue with 2000 summaries

    Figure 6. Event summary

    3.1.2 Event chronological noting The event representation is done through the chronological annotation and through their phases (simple and/or compound). For simple voltages, the channel is defined through Va, Vb or Vc; meanwhile for the compound ones by Vab, Vbc, Vca.

    It has a queue with 16000 annotations. The number of events stored depends on the annotation done for each of them. By setting, the maximum number of annotations by each events can be limited. These data can be accessed from the Register menu with the option Bring events or from the tool bar with the Event button.

    Together with this annotation, it is shown a graphic with the voltage wave shape during the event. This graphic detail depends on the annotations taken for every event. The graphic has the autoscalar, manual scalar and zoom properties.

    Every event will dispose the following annotations

    Normal before: It is characterised with a N and it has the dated value of the depth and the phase primary voltage 200msec before the considered event happens.

    Sag or swell: It is characterised with a L (sag) or a H (swell), and it has the dated value of the depth and the phase primary voltage in the very moment the event beginning is detected.

    Back to normal: It is characterised with a V it has the dated value of the depth and the phase primary voltage in the very moment the event end is detected.

    Normal After: It is characterised with a n and it has the dated value of the depth and the phase primary voltage 200 msec after the considered event finishes.

    Increase: It is characterised with a I and it has the dated value of the depth and the phase primary voltage while the event lasts. It refers to the increases of the voltage value, and so to a reduction of the event depth.

    Decrease: It is characterised with a D and it has the dated value of the depth and the phase primary voltage while the event lasts. It refers to the decrease of the voltage value, and so to a un increase of the event depth.

    Overvoltage maximum: It is characterised with a M and it has the overvoltage maximum value reaches and the data in which it has occurred.

  • 6BSAGS, SWELLS AND INTERRUPTIONS

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 22

    Sag minimum: It is characterised with a m and it has the sag minimum value reached and the data in which it has occurred.

    Sag/swell average: It is characterised with a A and it has the voltage average value during the sag or swell. The data corresponds to the average data between the beginning and end of the events.

    Sag/swell pulse time expired: It is characterised with a E. In case the pulse duration maximum time is configured, it occurs when the time since the sag or swell starts is elapsed.

    Summary: It has the depth maximum values, the corresponding primary voltage and the duration of this event.

    Figure 7. Event representation

    As it is shown in Figure 7, the event list offers information about the following:

    The type of event (sag: LOW; swell: HIGH).

    Channel in which the event has occurred.

    Event data and time.

    Event depth in %

    Voltage, referred to the primary, for the previous depth.

    Event duration.

    Event evolution graphic according to the annotations. If the event number is high and all of them are desired to have automatically unfolded, inside the Relay menu , of the main menu bar, there is the option Unfold all; the opposite can also occur, that is Compact all.

    3.1.3 Depth-duration tables Independent depth-duration double input tables for sags and swells. The table has a one-year duration. The register can store 15 sag tables and 15 swell tables. These data can be accessed from the Register menu with the option Bring tables.

    A table is considered to be finished and a new one is started in the following examples:

    Changes in the table settings.

  • 6BSAGS, SWELLS AND INTERRUPTIONS

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 23

    Users order (command)

    A year has elapsed since it started. In order the register to start treating a sag or an overvoltage with the aim of storing in the corresponding position in the table, the sag or overvoltage threshold must have been exceeded in depth. When none of the three phases is already in event situation (exceeding the set threshold in the hysteresis) the unit measures its time. This time comprises from the moment the first phase enters the event until the last of the faults leaves the event. This time is noted in the cell defined by that duration and by the maximum depth given during the time in which the event has existed.

    These tables allow seeing, in a global way, the data collected in the Event Summaries queue.

    Figure 8. Sag tables

  • 7BADDITIONAL FUNCTIONS

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 24

    4. ADDITIONAL FUNCTIONS

    4.1 OVERCURRENT Overcurrent function carried out over the current protection transformer (20In background scale). The settings used by this function are the following ones:

    Enable

    Overcurrent threshold. It is set in secondary amperes.

    Additional time

    Baud rate 5A Setting Min. Max. Step Notes Enable YES/NO Overcurrent threshold (A) 0.1 100 0.1 A Additional time (sec) 0 100 0.1 Seconds

    Baud rate 1A Setting Min. Max. Step Notes Enable YES/NO Overcurrent threshold (A) 0.01 20 0.01 A Additional time (sec) 0 100 0.1 Seconds

    The analysis is carried out over the three current protection phases.

    Being this function enabled (setting), when the measured current value excesses the threshold (setting) during the additional time (setting), the signalling is generated and it indicates that an Overcurrent has occurred. Once it is activated, the current value must drop under the 95% of the setting, on order to deactivate it.

    The overcurrent activation generates control digital signals and it acts over the programmed digital outputs.

    The events generated are the following ones:

    Overcurrent pick up: Date, phase and current value

    Overcurrent activation: Date, phase and current value

    Maximum overcurrent: Date, phase and current value

    Overcurrent end: Date, phase and current value

    Overcurrent duration: Fault duration summary

    4.2 THD OVEREXCITATION It checks the harmonic percentage regarding the fundamental one, over the current measurement transformer (1.5In background scale) and over the voltage transformer. The analysis is carried out over the three phases. The settings used by this function are the following ones:

    Enable

    THD current threshold. Set in %.

    THD voltage threshold. Set in %.

  • 7BADDITIONAL FUNCTIONS

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 25

    THD maximum time Setting Min. Max. Step Notes Enable YES/NO THD I threshold 1 100 0.1 % THD V threshold 1 100 0.1 % THD maximum time (sec) 0 100 0.1 Seconds

    Being this function enabled (setting), when the measured THD value excesses the threshold (setting), the signalling is generated and it indicates that an overexcitation has occurred. Once it is activated, the THD value must drop under the 95% of the setting, on order to deactivate it.

    The maximum time THD indicates the time from the starting of the THD, during which the THD pulse signal remains active; when this time ends, the pulse signal is deactivated although the THD keeps on. If the time is set to 0, it is the same as having the option disabled, so that the THD is not limit in a time and the THD pulse signal matches with the THD signal.

    The THD overexcitation activation generates control digital signals and it acts over the programmed digital outputs.

    The events generated are the following ones:

    THD activation: Date and phase

  • 8BDATA ACQUISITION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 26

    5. DATA ACQUISITION

    5.1 MEASUREMENTS The measurements available in the PQM models are the following ones:

    Voltage measurements (in all the models) Frequency Compound voltage Vab (in kVs) Simple voltage phase A (in kVolts) Compound voltage Vbc Angle V phase A Compound voltage Vca Simple voltage phase B Average compound voltage Angle V phase B Voltage unbalance Simple voltage phase C Harmonic distortion in Va, Vb, Vc and average(in %) Angle V phase C Average simple voltage

    Individual measurements of voltage harmonic module by phase Harmonics from 1 to 15 phase A (in V and % of the fundamental) Harmonics from 1 to 15 phase B (in V and % of the fundamental) Harmonics from 1 to 15 phase C (in V and % of the fundamental)

    Individual measurements of current harmonic module by phase (only in models with current) Harmonics from 1 to 15 phase A ( in A and % of the fundamental) Harmonics from 1 to 15 phase B ( in A and % of the fundamental) Harmonics from 1 to 15 phase C ( in A and % of the fundamental)

    Current, power and energy measurements (only in models with current) Current phase A (in Amperes) Active power (kW) Angle I phase A (in grades) Reactive power (kVAR) Current phase B Apparent power (kVA) Angle I phase B Power factor phase A, B, C and medium Current phase C Active energy counter (positive) Angle I phase C Active energy counter (negative) Average current Reactive energy counter (positive) Harmonic distortion in Ia, Ib and Ic (en %) Reactive energy counter (negative) Current unbalance

    5.1.1 Power calculation The powers of each phase are calculated in the following way:

    iii

    iii

    iii

    IVSIVQIVP

    =

    =

    =

    )Im{

    )Re{

    (being i each of the phases A, B and C).

    and the total powers:

    P P P PQ Q Q QS S S S

    T A B C

    T A B C

    T A B C

    = + += + += + +

    The power calculation for the compound voltages setting Vc, is carried out by assuming that the sum of phase currents is null.

  • 8BDATA ACQUISITION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 27

    5.1.2 Single-pole sequence

    Voltage: 30

    cVbVaVV

    ++=

    Current: 30

    cIbIaII

    ++=

    Note: The phase succession order A-B-C or C-B-A is programmable, and the single-pole sequence calculation depends on that setting.

    5.1.3 Reverse sequence

    Voltage: 3

    22

    cVabVaaVV

    ++

    =

    Current. 3

    22

    cIabIaaII

    ++

    = where a=1|

    Note: The phase succession order A-B-C or C-B-A is programmable, and the reverse sequence calculation depends on that setting.

    120

    5.1.4 Unbalance The ratio in modules between the reverse sequence and direct sequence in per cent.

    100

    2

    2

    1

    2

    cVabVaaV

    cVabVaaV

    VV

    ++

    ++=

    100

    2

    2

    1

    2

    cIabIaaI

    cIabIaaI

    II

    ++

    ++=

    where a=1|120

    5.2 HISTORICAL/STATISTICAL It has two independent queues that can be selected in order to store historical, statisticals or in order to be disabled. This selection is carried out with the enable setting.

    NO: It is disabled

    Mean. It is considered as historical and it stores the mean values.

    Maximum/Minimum. It is considered as statistical and it stores the maximum and minimum values.

    Maximum. It stores only the maximum values.

    Minimum. It stores only the minimum values.

    Mean/Maximum. It stores the mean and maximum values.

    Mean/Minimum. It stores the mean and minimum values.

    Mean / Maximum / Minimum. It stores the mean, maximum and minimum values.

  • 8BDATA ACQUISITION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 28

    5.2.1 Historical The storage is carried of the average of the measurements calculated within a determined periodicity out in a circular queue. Both the measurements to be stored and the storage periodicity can be programmed by the user.

    These data are stored in the PC where they are accumulated to the data previously captured, so data corresponding to a long period are available. These data are presented as a list and in a graphic format, allowing different analysis types to be carried out on them in the PC without being connected to the register.

    The historical carried out are the following ones:

    Voltage and current historical.

    Power historical

    Harmonic historical The different historical can be individually enabled, selected which measurements are going to be sent and its integration period.

    The total number of measurement stored is fixed, so depending on the storage period and the number of measurement selected the time will be longer or shorter.

    At least, the historical values corresponding to a month, taken every hour, are stored; that is, 744 registers. If changing the sampling period, the total time stored also changes.

    When the historical configuration is changed, those previously stored in the register are lost, so if they are desired to be kept, before changing the configuration, they have to be requested and stored in the PC.

    Each historical can be deleted via command:

    Delete V-I historical. Command 111

    Delete power historical. Command 112

    Delete harmonic historical. Command 113 The historical are also deleted when deleting all the memory (command 110), which deletes not only the historical, but also all the data stored in the memory.

    The historical display can be carried out as a list, where the data and the value are indicated (Figure 9), or in a graphic way, where apart from the time evolution, each point value can be seen (Figure 10). This representation is valid for the different historical types.

    The access to the historical is from Register menu with the option Bring historical or from the tool bar with the Historical pushbutton. The available data are the following:

    Figure 9 Historical list

  • 8BDATA ACQUISITION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 29

    Figure 10 Historical graphic

    5.2.1.1 Voltage and current historical It calculates in each phase the average value of the voltages and/or currents depending on what is selected.

    The settings are the following:

    Enable

    Measurement period. Setting from 1 to 60 minutes.

    Select the measurement to be registered

    Voltage

    Current This queue is deleted by Command 111 ( V-I historical deletion).

    5.2.1.2 Power historical It calculates the average value of the P, Q, total S and cos by phase and mean depending on what is selected. The settings are the following ones:

    Enable

    Measurement period. Setting from 1 to 60 minutes.

    Select the measurement to be registered

    Active power

    Reactive power

    Apparent power

    cos phase A

    cos phase B

    cos phase C

    cos medium This queue is deleted by Command 112 ( Power historical deletion).

  • 8BDATA ACQUISITION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 30

    5.2.1.3 Harmonic historical It calculates the average value of the individual harmonics (from 1 to 15) of each of the phases V-I and the THD according to the one selected.

    The settings are the following ones:

    Enable

    Measurement period. Setting from 1 to 60 minutes.

    Select the measurement to be registered

    THD

    Individually: harmonics from 1 to 15 The graphic screens can be configured and the measurements to be display can be selected.

    The queue deletion is carried out with the command 113 (Harmonic historical deletion).

    Figure 11 Harmonic Historical list

    Figure 12 Harmonic Historical graphic

  • 8BDATA ACQUISITION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 31

    5.2.2 Statistical The storage of statistical data (maximum, minimum and mean), calculated within a determined periodicity is carried out in a circular queue. Both the measurements and the storage periodicity can be programmed by the user. Additionally, the statistical are calculated with a 1-day, 1-week, 1-month and 1-year periodicity that cannot be programmed by the user.

    These data are stored in the PC where they are accumulated to the data previously captured, so data corresponding to a long period are available. These data are presented as a list, where the date and the registered values are indicated ( Figure 13), allowing these data analysis in the PC without being connected to the register.

    The statisticals to be calculated are the following ones:

    Voltage and current statisticals.

    Power statisticals

    Harmonic statisticals The statisticals can be individually enabled, the measurements to be sent and the integration period can be selected.

    The following statistical data will be stored in the register:

    annual: 1 register

    monthly 12 registers (1 year)

    weekly: 54 registers (1 year)

    daily: 31 days (1 month)

    time schedule: 744 registers are stored, corresponding to the values of one month taken every hour. If changing the sampling period, the total time stored also changes.

    When the statistical configuration is changed, those previously stored in the register are lost, so if they are desired to be kept, before changing the configuration, they have to be requested and stored in the PC.

    The access to the historical is from Register menu with the option Bring historical or from the tool bar with the statistical pushbutton.

    Each statistical can be deleted via command:

    Delete V-I statistical Command 114

    Delete power statistical. Command 115

    Delete harmonic statistical. Command 116 The statisticals are also deleted when deleting all the memory (command 110), which deletes not only the statistical, but also all the data stored in the memory.

  • 8BDATA ACQUISITION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 32

    Figure 13 Statistical list

    5.2.2.1 Voltage and current statistical It calculates in each phase the maximum, minimum and average value of the voltages and/or currents depending on what is selected.

    The settings are the following:

    Enable

    Measurement period. Setting from 1 to 60 minutes.

    Select the measurement to be registered

    Voltage

    Current This queue is deleted by Command 114 ( V-I statistical deletion).

    5.2.2.2 Power statistical It calculates the maximum, minimum and average value of the P, Q, total S and cos by phase and mean depending on which one is selected.

    The settings are the following ones:

    Enable

    Measurement period. Setting from 1 to 60 minutes.

    Select the measurement to be registered

    Active power

    Reactive power

    Apparent power

    cos phase A

  • 8BDATA ACQUISITION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 33

    cos phase B

    cos phase C

    cos medium This queue is deleted by Command 115 ( Power statistical deletion).

    5.2.2.3 Harmonic statistical It calculates the maximum, minimum and average value of the individual harmonics (from 1 to 15) in every phase of V-I and THD according to the selected one.

    The settings are as follows:

    Enable

    Measurement period. Setting from 1 to 60 minutes.

    Select the measurement to be registered

    THD

    Individually: harmonics from 1 to 15 This queue is deleted by Command 116 (Harmonic statistical deletion).

    5.3 OSCILLOGRAPH DATA RECORDING The oscillograph data recorder can be programmed between the following possibilities:

    Perturbations Cycles 10 60 20 30 40 15 60 10 120 5

    The number of selected cycle is stored in each oscillo, being 32 the number of samples per analogue channel cycle.

    The number of cycles previous the pick up is programmable. In each oscillo, up to 8 analogue channels can be registered and also up to 32 digital channels selectable from a list selected among the available signals.

    The oscillo starts by a rising slope of any of the digital signals contemplated in the register.

    The analogue channels are sent to the console multiplied by the transformation ratio in order to appear in primary values.

    When the oscillograph configuration (number of cycles) is changed, those, previously stored in the register are lost, so if they are desired to be kept, they have to be requested and stored in the PC, before changing the configuration.

    The oscillograph stored in the memory can be deleted when resetting the queue The deleting can be individual (only oscillographs) or global (all the memory).

    The access to these data is from Register menu with the option Bring wave shape or from the tool bar with the Wave shape pushbutton.

  • 8BDATA ACQUISITION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 34

    5.4 EVENTS The register generates events with date and time in order to show the incidents detected.

    The protection stores in non-volatile memory a 16,000 event-queue, retrievable from the PC.

    The events generated by the register are the following ones:

    Sags and swells (indicated in section 3.1): 'N', Normal 'R', Summary 'V', Back 'n' normal after 'L', Low 'M' Swell maximum 'H', High 'm' Sag minimum 'I', Increase 'A' Sag/swell mean 'D', Decrease 'E' Sag/swell pulse time expired

    Hardware checking 'FF' DSP reference failure 'FA' Setting failure 'FB' DSP battery failure 'FM' DSP measurement communication failure 'FR' Relay failure 'FC' checksum failure 'FJ' Clock failure 'FP' Recovered failure

    Reset. 'r' Register reset notes

    Overcurrent

    'iA' Overcurrent pickup

    'iD' Overcurrent trip

    'iM' Overcurrent maximum

    'iF' Overcurrent end

    'R' Summary

    THD

    'T' THD threshold exceeded

    The access to these data is from Register menu with the option Bring events or from the tool bar with the Events pushbutton.

    These events ate also available in the SIPC console, and they are registered both in the event screen and in the Events.txt file available for each UCL in the ..\protec.dat\UxxFyyNz installation folder where: xx is the UCL number in hexadecimal, yy for protections is A0 and for automations, it is 64 and z is the protection number. This information is collected, depending on the Protect Period time, in seconds, located in the [Comms] section of the installation .ini. By default, this time is at 600 seconds.

    5.5 CONTROL MESSAGES The register responds to the following control messages:

    Measurement, change and counter request

    Digital status request

    Clock synchronization

    Counter freezing

  • 8BDATA ACQUISITION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 35

    Commands on relays and specified digital signals The digital signals treated (changes and status) are those indicated in the Table 3. Only those corresponding to the available functions will be applied to each determined model.

    The command orders are the following ones:

    Action ISC Activate any relay from 1 to 14 1 to 14

    The measurements transmitted are 2-byte ones and in Procome format:

    Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

    Meaning Signal Measurement value in counts over scale range 4095 X 0: Valid 1 Not valid

    X

    The scale range in counts (4095) corresponds to the measurement scale range

    Type Voltage Current Angle Distortion Unbalance Powers Power factor Frequency Scale 165 V 7,5 A 360 100 % 100 % 3712.5 1 70 Hz Offset 0 0 0 0 0 0 0 29.05

    The measurement is calculate by applying he following equation:

    4095)( countsoffsetScaleoffsettMeasuremen +=

    Example of measurement calculation:

    Type Voltage Current Angle Distortion Unbalance Powers Power factor Frequency Counts 1576 2730 512 41 20 1050 2047 2095 Measurements 63.50 V 5 A 45.01 1 % 0.49 % 951.92 0.50 50

    The measurement transmitted and the order in which they are sent can be programmed. The programming is carried out through the protection console Sipcon/p. In

    Table 1 Control measurement and Table 2, it is displayed the control measurements, all the available measurements, as well as the order with which the models with current measurements leave the factory. Each model will be only applied those which correspond to the measurements it disposes.

    In those models with current measurement, at counter request, the following information is answered.

    Bytes no. Format Specification Data 4 Long Absolute value Positive active energy counter (W+)

    4 Long Absolute value Negative active energy counter (W-)

    4 Long Absolute value Positive reactive energy counter (VAR+)

    4 Long Absolute value Positive reactive energy counter (VAR-)

    The absolute value sent are impulses the correspondence of which with kWh and kVARh is established in the settings Measurement factor (Screen of Console general Setting)

  • 8BDATA ACQUISITION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 36

    Table 1 Control measurement

    Factory Position

    Data Factory Position

    Data Factory Position

    Data

    0 Empty 43 Harmonic module 2 Va 91 Harmonic module 10 Va 1 Frequency 44 Harmonic module 2 Vb 92 Harmonic module 10 Vb 2 Module Va 45 Harmonic module 2 Vc 93 Harmonic module 10 Vc 3 Module Vb 46 Harmonic module 2 Ia 94 Harmonic module 10 Ia 4 Module Vc 47 Harmonic module 2 Ib 95 Harmonic module 10 Ib 5 Module average V 48 Harmonic module 2 Ic 96 Harmonic module 10 Ic 6 Angle Va 49 Harmonic module 3 Va 97 Harmonic module 11 Va 7 Angle Vb 50 Harmonic module 3 Vb 98 Harmonic module 11 Vb 8 Angle Vc 51 Harmonic module 3 Vc 99 Harmonic module 11 Vc 9 Distortion (THD) in Va 52 Harmonic module 3 Ia 100 Harmonic module 11 Ia 10 Distortion (THD) in Vb 53 Harmonic module 3 Ib 101 Harmonic module 11 Ib 11 Distortion (THD) in Vc 54 Harmonic module 3 Ic 102 Harmonic module 11 Ic 12 Average distortion (THD) in V 55 Harmonic module 4 Va 103 Harmonic module 12 Va 13 Voltage unbalance 56 Harmonic module 4 Vb 104 Harmonic module 12 Vb 14 Module Vab 57 Harmonic module 4 Vc 105 Harmonic module 12 Vc 15 Module Vbc 58 Harmonic module 4 Ia 106 Harmonic module 12 Ia 16 Module Vca 59 Harmonic module 4 Ib 107 Harmonic module 12 Ib 17 Module average Vcomp. 60 Harmonic module 4 Ic 108 Harmonic module 12 Ic 18 Module Ia 61 Harmonic module 5Va 109 Harmonic module 13Va 19 Module Ib 62 Harmonic module 5 Vb 110 Harmonic module 13 Vb 20 Module Ic 63 Harmonic module 5 Vc 111 Harmonic module 13 Vc 21 Module average I 64 Harmonic module 5 Ia 112 Harmonic module 13 Ia 22 Angle Ia 65 Harmonic module 5 Ib 113 Harmonic module 13 Ib 23 Angle Ib 66 Harmonic module 5 Ic 114 Harmonic module 13 Ic 24 Angle Ic 67 Harmonic module 6 Va 115 Harmonic module 14 Va 25 Distortion (THD) in Ia 68 Harmonic module 6 Vb 116 Harmonic module 14 Vb 26 Distortion (THD) in Ib 69 Harmonic module 6 Vc 117 Harmonic module 14 Vc 27 Distortion (THD) in Ic 70 Harmonic module 6 Ia 118 Harmonic module 14 Ia 28 Average distortion (THD) in I 71 Harmonic module 6 Ib 119 Harmonic module 14 Ib 29 Current unbalance 72 Harmonic module 6 Ic 120 Harmonic module 14 Ic 30 Active power (P) 73 Harmonic module 7 Va 121 Harmonic module 15 Va 31 Reactive power (Q) 74 Harmonic module 7 Vb 122 Harmonic module 15 Vb 32 Apparent power (S) 75 Harmonic module 7 Vc 123 Harmonic module 15 Vc 33 Power factor phase A 76 Harmonic module 7 Ia 124 Harmonic module 15 Ia 34 Power factor phase B 77 Harmonic module 7 Ib 125 Harmonic module 15 Ib 35 Power factor phase C 78 Harmonic module 7 Ic 126 Harmonic module 15 Ic 36 Average power factor 79 Harmonic module 8 Va 127 Pending oscillograph 37 Harmonic module 1 Va 80 Harmonic module 8 Vb 122 Ia protection module 38 Harmonic module 1 Vb 81 Harmonic module 8 Vc 123 Ib protection module 39 Harmonic module 1 Vc 82 Harmonic module 8 Ia 124 Ic protection module 40 Harmonic module 1 Ia 83 Harmonic module 8 Ib 125 Ia maximum protection 41 Harmonic module 1 Ib 84 Harmonic module 8 Ic 126 Ib maximum protection 42 Harmonic module 1 Ic 85 Harmonic module 9Va 127 Ic maximum protection 86 Harmonic module 9 Vb 128 Ia protection module 87 Harmonic module 9 Vc 129 Ib protection module 88 Harmonic module 9 Ia 130 Ic protection module 89 Harmonic module 9 Ib 131 Ia maximum protection 90 Harmonic module 9 Ic 132 Ib maximum protection 133 Ic maximum protection

    The measurements of the voltage and current individual harmonic are also available in % regarding the fundamental one. These measurements are not configured in the factory (see Table 2).

  • 8BDATA ACQUISITION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 37

    Table 2 Contol measurements not configured by the factory

    Data Data Data Data Harmonic percentage 2 Va Harmonic percentage 9 Va Harmonic percentage 2 Ia Harmonic percentage 9 Ia Harmonic percentage 2 Vb Harmonic percentage 9 Vb Harmonic percentage 2 Ib Harmonic percentage 9 Ib

    Harmonic percentage 2 Vc Harmonic percentage 9 Vc Harmonic percentage 2 Ic Harmonic percentage 9 Ic

    Harmonic percentage 3 Va Harmonic percentage 10 Va Harmonic percentage 3 Ia Harmonic percentage 10 Ia

    Harmonic percentage 3 Vb Harmonic percentage 10 Vb Harmonic percentage 3 Ib Harmonic percentage 10 Ib

    Harmonic percentage 3 Vc Harmonic percentage 10 Vc Harmonic percentage 3 Ic Harmonic percentage 10 Ic

    Harmonic percentage 4 Va Harmonic percentage 11 Va Harmonic percentage 4 Ia Harmonic percentage 11 Ia

    Harmonic percentage 4 Vb Harmonic percentage 11 Vb Harmonic percentage 4 Ib Harmonic percentage 11 Ib

    Harmonic percentage 4 Vc Harmonic percentage 11 Vc Harmonic percentage 4 Ic Harmonic percentage 11 Ic

    Harmonic percentage 5 Va Harmonic percentage 12 Va Harmonic percentage 5 Ia Harmonic percentage 12 Ia

    Harmonic percentage 5 Vb Harmonic percentage 12 Vb Harmonic percentage 5 Ib Harmonic percentage 12 Ib

    Harmonic percentage 5 Vc Harmonic percentage 12 Vc Harmonic percentage 5 Ic Harmonic percentage 12 Ic

    Harmonic percentage 6 Va Harmonic percentage 13 Va Harmonic percentage 6 Ia Harmonic percentage 13 Ia

    Harmonic percentage 6 Vb Harmonic percentage 13 Vb Harmonic percentage 6 Ib Harmonic percentage 13 Ib

    Harmonic percentage 6 Vc Harmonic percentage 13 Vc Harmonic percentage 6 Ic Harmonic percentage 13 Ic

    Harmonic percentage 7 Va Harmonic percentage 14 Va Harmonic percentage 7 Ia Harmonic percentage 14 Ia

    Harmonic percentage 7 Vb Harmonic percentage 14 Vb Harmonic percentage 7 Ib Harmonic percentage 14 Ib

    Harmonic percentage 7 Vc Harmonic percentage 14 Vc Harmonic percentage 7 Ic Harmonic percentage 14 Ic

    Harmonic percentage 8 Va Harmonic percentage 15 Va Harmonic percentage 8 Ia Harmonic percentage 15 Ia

    Harmonic percentage 8 Vb Harmonic percentage 15 Vb Harmonic percentage 8 Ib Harmonic percentage 15 Ib

    Harmonic percentage 8 Vc Harmonic percentage 15 Vc Harmonic percentage 8 Ic Harmonic percentage 15 Ic

  • 8BDATA ACQUISITION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 38

    Table 3 Control digital signals

    Digital inputs Logic Signals Sags and swells Signal No. Signal Signal No Signal Signal No. Signal 0 Input 1 112 Logic 1 136 Va sag end 1 Input 2 113 Logic 2 137 Vb sag end 2 Input 3 114 Logic 3 138 Vc sag end 3 Input 4 115 Logic 4 139 Voltage sag end 4 Input 5 116 Logic 5 140 Va swell end 5 Input 6 117 Logic 6 141 Vb swell end 6 Input 7 118 Logic 7 142 Vc swell end 7 Input 8 119 Logic 8 143 Swell end 8 Input 9 120 Logic 9 144 Va sag 9 Input 10 121 Logic 10 145 Vb sag 10 Input 11 122 Logic 11 146 Vc sag 11 Input 12 123 Logic 12 147 Voltage sag 12 Input 13 124 Logic 13 148 Va swell 13 Input 14 125 Logic 14 149 Vb swell 14 Input 15 126 Logic 15 150 Vc swell 15 Input 16 151 Swell 16 Input 17 Hardware alarms 160 Va sag pulse 17 Input 18 Signal N 161 Vb sag pulse 18 Input 19 128 Reference voltage failure 162 Vc sag pulse 19 Input 20 129 Battery failure 163 Voltage sag pulse 20 Input 21 130 Relay failure 164 Va swell pulse 21 Input 22 131 Clock failure 165 Vb swell pulse 22 Input 23 132 Setting failure 166 Vc swell pulse 23 Input 24 133 DSP communication failure 167 Swell pulse 24 Input 25 25 Input 26 Oscillograph THD 26 Input 27 Signal No. Signal Signal N Signal 27 Input 28 135 Oscillo order 152 THD Ia activation 28 Input 29 153 THD Ib activation 29 Input 30 154 THD Ic activation 30 Input 31 155 THD I activation 31 Input 32 156 THD Va activation 32 Input 33 157 THD Vb activation 33 Input 34 158 THD Vc activation 34 Input 35 159 THD V activation 168 THD Ia pulse Digital outputs 169 THD Ib pulse Signal No. Signal 170 THD Icpulse 64 Output 1 171 THD I pulse 65 Output 2 172 THD Va pulse 66 Output 3 173 THD Vb pulse 67 Output 4 174 THD Vc pulse 68 Output 5 175 THD V pulse 69 Output 6 70 Output 7 Overcurrent 71 Output 8 N signal Signal 72 Output 9 176 IOC Phase A pickup 73 Output 10 177 IOC Phase B pickup 74 Output 11 178 IOC Phase C pickup 75 Output 12 179 IOC pickup 76 Output 13 180 IOC Phase A trip 77 Output 14 181 IOC Phase B trip 182 IOC Phase C trip 183 IOC trip

  • 9BREGISTER CONFIGURATION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 39

    6. REGISTER CONFIGURATION

    6.1 TIME SETTING AND SYNCHRONIZATION

    6.1.1 Time setting It can be carried through the Protection Console with the synchronization pushbutton.

    6.1.2 Synchronization There is an input for synchronization via IRIG-B demodulated. (See section IRIG-B Input inside Technical characteristics).

    The time code IRIG-B is a mesh generated once a second. The code used is B 003, in which the mesh is constituted by a pulse train with TTL of variable widths. The time shown corresponds to the PPS (pulse per second) coinciding with the Mesh Reference Mark of the beginning of the mesh. There are two options.

    Format B002: The year is not sent in the message.

    Format B002 with IEEE 1344: The year is sent in the message. In Integrated Control Systems (SIPC) the register is periodically synchronised (every minute) by the UCS.

    In this case, it is useless to change the time in the Protection Console, because it will be deleted by the UCS.

    6.2 PROGRAMMING DIGITAL OUTPUTS It allows programming a digital input among the different possibilities depending on the model.

    Generals Free Hardware failure

    Sags/Swells Sag Va Sag pulse Va Sag Vb Sag pulse Vb Sag Vc Sag pulse Vc Sag V (any phase) Sag pulse V (any phase) Swell Va Swell pulse Va Swell Vb Swell pulse Vb Swell Vc Swell pulse Vc Swell V (any phase) Swell pulse V (any phase)

    THD THD I activation THD I pulse THD Ia activation THD Ia pulse THD Ib activation THD Ib pulse THD Ic activation THD Ic pulse THD V activation THD V pulse THD Va activation THD Va pulse THD Vb activation THD Vb pulse THD Vc activation THD Vc pulse

  • 9BREGISTER CONFIGURATION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 40

    Overcurrent IOC pick up IOC activation IOC Ia pick up IOC Ia activation IOC Ib pick up IOC Ib activation IOC Ic pick up IOC Ic activation

    Logical signals Logic 1 Logic 6 Logic 11 Logic 2 Logic 7 Logic 12 Logic 3 Logic 8 Logic 13 Logic 4 Logic 9 Logic 14 Logic 5 Logic 10 Logic 15

    Once activated the outputs are kept at least 50 ms.

    6.3 PROGRAMMING LEDS The procedures are totally similar to those of the digital outputs, with the exception that the activation time is not programmed.

    6.4 PROGRAMMING LOGIC OUTPUTS The user can configure up to 15 logic outputs, called logic 1 to logic 15, which can be assigned to relays, as web as to LEDs, locking inputs, signals to be registered on the disturbance recorder, etc.

    The programming of the logic outputs can be only done through the Protections console, from the basic available signals, consigned in the Table 4 (only the functions that the model contains correspond. to each model). The programming procedure is described in other document: the Protections console manual.

    The logic signals are generated according to the following scheme:

    As it can be observed in the definition of a logic output the following elements are involved:

    Up to 16 signals among the available ones (or their negated ones), forming an OR function

    Up to 16 signals among the available ones (or their negated ones), forming an AND function

    an OR or AND function (programmable) of two previous functions results

    a programmable time delay ("delay") to activate the output

  • 9BREGISTER CONFIGURATION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 41

    a programmable time for the duration of the output activation The delay time is the time length since there is a logic 1 at the output of the logic ports until the corresponding logic output is activated. If during this time the 1 disappeared, the output could not be activated. It can be programmed between 0 and 99.9 s, with steps of 0.1 s.

    The pulse time (duration) is the time during which the logic signal remains active. Its programming allows two options:

    "By logic": after the delay, the output is active as long as there is a 1 at the programmed logic output

    "By time": the time during which the output is active is programmed, so that once expired the output is deactivated, independently from the state of the programmed logic output. Only a new step from 0 to 1 will activate the output again, after the delay. The time range goes from 0.1 s to 99.9 s, with steps of 0.1 s.

    A logic output "i" can be used as available signal for programming input of other logic signal "j" or of itself.

    Table 4 Digital control signals

    Digital inputs Digital outputs Sags and swells THD Input 1 Output 1 Va sag end THD Ia activation Input 2 Output 2 Vb sag end THD Ib activation Input 3 Output 3 Vc sag end THD Ic activation Input 4 Output 4 V sag end THD I activation Input 5 Output 5 Va swells end THD Va activation Input 6 Output 6 Vb swells end THD Vb activation Input 7 Output 7 Vc sweels end THD Vc activation Input 8 Output 8 Sweel end THD V activation Input 9 Output 9 Va sag THD Ia pulse Input 10 Output 10 Vb sag THD Ib pulse Input 11 Output 11 Vc sag THD Ic pulse Input 12 Output 12 Voltage sag THD I pulse Input 13 Output 13 Va swell THD Va pulse Input 14 Output 14 Vb swell THD Vb pulse Input 15 Vc swell THD Vc pulse Input 16 Logic signals Swell THD V pulse Input 17 Logic 1 Va sag pulse Input 18 Logic 2 Vb sag pulse Overcurrent Input 19 Logic 3 Vc sag pulse IOC Phase A pickup Input 20 Logic 4 Voltage sag pulse IOC Phase B pickup Input 21 Logic 5 Va swell pulse IOC Phase C pickup Input 22 Logic 6 Vb swell pulse IOC pickup Input 23 Logic 7 Vc swell pulse IOC Phase A trip Input 24 Logic 8 IOC Phase B trip Input 25 Logic 9 IOC Phase C trip Input 26 Logic 10 IOC trip Input 27 Logic 11 Input 28 Logic 12 Input 29 Logic 13 Input 30 Logic 14 Input 31 Logic 15 Input 32 Input 33 Input 34 Input 35

  • 9BREGISTER CONFIGURATION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 42

    A very simple application sample: it is wished that the digital output DO7 follows to the digital input DI6, with a delay of 1 s.

    T delay = 1s.

    Duration = "by logic"

    Programming of output DO7: Logic 1

    6.5 PROGRAMMING GENERAL SETTINGS These setting are in the Console in the PQM general setting screen.

    Transformation ratio: They are only used to give measurements referred to the primary.

    Rated voltage: it is the simple rated voltage. It is used for the de sag and swell calculation.

    Connection type: Star or delta. It shows if the voltages the PQM measures are simple (Star) or compounds(delta). Setting Min. Max. Step Notes Transformer I ratio phases 1 5000 1 Voltage transformer ratio 1 5000 1 Simple rated voltage (V) 10 165 0.01

    Connection type Star Delta

    6.6 COMMUNICATION CONFIGURATION They allow configuring the communication parameters of the PQM ports.

    Setting Min. Max. Step Notes Address 0 253 1 Baud rate 1200 38400 x2 Parity No / Even/ Odd

    Input DI6

    Delay Duration

    Input DI6

    Logic output 1

    Logic output 1

    Logic/i

    Application 1. Timed output

  • 9BREGISTER CONFIGURATION

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 43

    6.7 AUTOMATIC CALL Communications are allowed to be configured, in order to carry out automatic connections with the register. It is configured from the menu see, by selecting options

    Connection frequency in hours.

    Call attempts

    Automatic time synchronization

    6.8 FIRMWARE LOAD The Firmware can be charged in the register through the serial port, what makes the version updating easier.

  • 0BKEYBOARD / DISPLAY

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 44

    APPENDIX I. KEYBOARD / DISPLAY It may optionally dispose of a display (2 lines and 16 characters) and a keyboard with 16 keys.

    The keyboard/display units aim is displaying the states of the digital inputs, measurements and date. The display language can be configured and the date can be changed.

    On standby, the display shows PQM300-T and the software version it has.

    At any moment of the procedure described below, by pushing ESCAPE the unit moves to the menu element of the immediately previous level.

    The menus are scrolled downwards or upwards with the pushbuttons and , and they are circular, that is, after the last position it goes to the first one again.

    In general terms, when a menu is scrolled, the first line of the display indicates the active function, which can be entered by pushing INTRO. That way, we enter the following menu level (if there was) specific for that function.

    The menu tree to display or change settings inside a each group is hierarchical. If on standby (title), we push INTRO, we reach the following menu:

    SEE TIME

    MEASUREMENTS

    SEE SETPOINTS

    CHANGE SETPOINTS

    I.1. USE OF THE KEYBOARD/DISPLAY

    I.1.1 See settings and magnitudes With the keys and it is possible to move around each menu or submenu (indicated in the previous section) upwards or downwards, since the menu are circular.

    By pushing INTRO the following menu level is reached. If it did not have a submenu it would not change its state when pushing INTRO.

    By pushing ESC the element of the previous menu is reached, that is, the one from which can reach the present status..

    In the final menus, those with no submenus (settings), the name of the setting group, selected by means of keyboard, appear on the first row, and on the second row its present value.

    I.1.2 Change settings Up to the last level of the menus everything works in the same way as in See settings and magnitudes (same functions for same keys).

    To access to this function, it is necessary to press the key "". Through this all settings and initializations are made accessible, except the ones contained in the section "Define protection. To access these the key "" is necessary

    In the last level of the menus, where the name of the settings we want to change appear, the keyboard operation is different from the one we have explained until now.

  • 0BKEYBOARD / DISPLAY

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 45

    When entering into each group to change the settings, which are included (final menu), the keyboard operation will be as it follows:

    1) Numerical settings. The first line of the display shows the name of the selected setting followed by its current value. The line 2 shows the text NEW followed by the current setting range, which can be changed by using the numerical keyboard.

    To change the setting range we use the numerical keyboard. The new range has to be literally entered, this means that if we wish to enter the new value of 23 the key 2 will have to be pressed, and followed by the key 3. If the value is not valid, when pushing INTRO to access to the next setting, a warning message will be shown on the line 2 indicating INVALID VALUE. A valid value will have to be entered to be able to access the next setting within the group, by pressing INTRO. The pressing of ESC within the final menu takes us to the menu element, which we came from, without making effective the changes we have made until the moment of pressing.

    The changes are made effective when at the moment of reaching the last group setting and pressing INTRO, we receive the message VALIDATE SETTINGS and press INTRO to validate the changes; if we validate them by pressing INTRO, we would return to the next element of the menu above (see menus chart). By pressing ESC we return to the menu element from which we reached the actual state.

    2) Non numerical settings. There are settings, such as language, that offer some possibilities to choose, because it is clearer to selct them by their name instead of entering its numerical value.

    Whenever possible and clear, on the line 1 the name of the setting will appear along with a text indicating the actual value. On the second line it will gradually appear the possible values to choose for this setting, if we use the keyboard properly. We use the key to go through the different possibilities we have on each state. In the case of inputs, outputs or leds configuration we can use the keys and to select the configuration of each of them; we do it this way because there are many configurations to choose from and this makes it quicker.

    As for the numerical settings, by pushing INTRO, we move to the following setting until reaching the last one of the group, in which we have to valuate by pushing INTRO. The pressing of ESC takes us to the menu element from which we reach the actual status.

    I.2. MENU Below, we enclose a table which graphically illustrates and shows the easy handling of the different menus and settings which can be changed with the keyboard/display. We recommend this appendix be at hand when you start to use the keyboard, in order to easily find the settings to be changed.

    DATE/TIME (see) Unit time and date are displayed DIGITAL INPUTS

    INPUT STATUS State of inputs 1 to 3

    (4 to 9) State of inputs 4 to 9

    (10 a 15) State of inputs 10 to 15

    (16, 21) State of inputs 16 to 21

    (22, 27) State of inputs 22 to 27

    (28, 33) State of inputs 28 to 33

    (34, 35) State of inputs 34 to 35

    MEASUREMENTS See page 45

    SETPOINTS (see) See page 45

    SETPOINTS (change) See page 45

  • 0BKEYBOARD / DISPLAY

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 46

    MEASUREMENTS SECONDARY MEASUR. CURRENTS Phase A current Current in phase A. Phase B current Current in phase B. Phase C current Current in phase C. VOLTAGES VA voltage Voltage in phase A VB voltage Voltage in phase B VC voltage Voltage in phase C FREQUENCY FREQUENCY (Hz) Frequency measurement. PRIMARY MEASUR. CURRENTS Phase A (A) current Current in phase A. Phase B (A) current Current in phase B. Phase C (A) current Current in phase C. VOLTAGES VA voltage (kV) Voltage in phase A VB voltage (kV) Voltage in phase B VC voltage (kV) Voltage in phase C Average Volt (kV) Average voltage of the three phases VAB ph-ph V (kV) Compound voltage between phases _A and B VBC ph-ph V (kV) Compound voltage between phases _B and C VCA ph-ph V (kV) Compound voltage between phases _C and A Averag ph-ph V (kV) Average compound voltage between the three phases FREQUENCY FREQUENCY (Hz) POWER ACTIVE POW (MW) Active power REAC. POWER (MVAR) Reactive power APPARENT P. (MVA) Apparent power PPOWER FACTOR Power factor (Mean cosine) ENERGY COUNT.ACT+(Imp) Positive Active Energy COUNT.ACT -(Imp) Negative Active Energy COUNT.REA +(Imp) Positive Reactive Energy COUNT.REA -(Imp) Negative Reactive Energy DISTORTION CURRENT DISTORT DISTORTION IA(%) Current distortion IA DISTORTION IB(%) Current distortion IB DISTORTION IC(%) Current distortion IC VOLTAGE DISTORT DISTORTION VA(%) Voltage distortion VA DISTORTION VB(%) Voltage distortion VB DISTORTION VC(%) Voltage distortion VC TEMPERATURE (C) TEMPERATURE (C) Unit temperature

    SETPOINTS (see) See TABLE 0 COMMUNICATION COM1 PORT LCU ADDRESS Protection address BAUD RATE Baud rate (bauds) PARITY Parity COM2 PORT LCU ADDRESS Protection address BAUD RATE Baud rate (bauds) PARITY Parity DEFINE EQUIP LANGUAGE SELECT See language SETPOINTS(change) Enter KEYWORD DATE CHANGE DATE CHANGE Enter keyword to change the setpoints TIME CHANGE Change date NEW PAR VALID? Change time Program TABLE 0 COMMUNICATION COM1 PORT LCU ADDRESS Protection address BAUD RATE Baud rate (bauds) PARITY Parity NEW PAR VALID? Validate parameters? COM2 PORT LCU ADDRESS Protection address BAUD RATE Baud rate (bauds) PARITY Parity NEW PAR VALID? Validate parameters? DEFINE EQUIP Enter KEYWORD LANGUAGE SELECT LANGUAGE SELECT Select language NEW PAR VALID?

  • 1BRECEPTION, STORAGE, INSTALLATION AND TESTING

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 47

    APPENDIX II. RECEPTION, STORAGE, INSTALLATION AND TESTING

    II.1. RECEPTION AND STORAGE The register protections are supplied in special packing material for transport.

    Upon reception, they should be checked for any signs of external damage caused during transport; if so the transport firm and manufacturer should be contacted.

    The material received should also be checked to see if it coincides with the order number.

    If the register is not going to be used immediately, it should be stored in its original packaging and in a dry and dirt free place.

    The unit transport must be made in its original packaging.

    II.2. WIRING PROCEDURE The register wiring procedure should be carried out in accordance with the enclosed external connection diagram. It is a general diagram; the programming of inputs and outputs should be taken into consideration in each specific case.

    Power supply The polarity is indifferent.

    Earth connection It is important for the earth connection to be correctly connected, in order for the protection disturbance rejection devices it incorporates to operate properly. The connection should be as short as possible (less than 25 cm.) using multiwired cable with a 4 mm

    2 cross-section.

    RS232 cable connections to be used between the PC and the register PQM300

    Case 1: a 25-pin PC output connector PQM300 side PC side

    Female 9-pin socket female 25-pin socket

    RxD 2 2 TxD

    TxD 3 3 RxD

    GND 5 7 GND

    DSR 6 20 DTR

    RTS 7 8 CD

    CTS 8 5 CTS

    CD 1 4 RTS

    DTR 4 6 DSR

  • 1BRECEPTION, STORAGE, INSTALLATION AND TESTING

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 48

    Case 2: a 9-pin PC output connector.

    PQM300 side PC side

    Female 9-pin socket Female 9-pin socket

    RxD 2 3 TxD

    TxD 3 2 RxD

    GND 5 5 GND

    DSR 6 4 DTR

    RTS 7 1 CD

    CTS 8 8 CTS

    CD 1 7 RTS

    DTR 4 6 DSR

    II.3. REGISTER ADDRESSING See Communications configuration section.

    II.4. COMMISSIONING The PQM300 registers are received with the default settings stipulated by the factory.

    Before commissioning they must be set, with the correct values for the application, following the setting procedures.

    The register has been checked at the factory in order to guarantee its accuracy in all of the setting points of the different parameters. However, it is convenient to test some points during reception and commissioning, in order to ensure it is totally in proper operating condition.

    Once the line is connected the real measurements, the relay is carrying out can be displayed, thus enabling you to check for proper connection and operation.

    II.5. RECEPTION TESTS

    II.5.1 Material needed

    Triple-phase voltage and current generator unit with variable frequency of type

  • 1BRECEPTION, STORAGE, INSTALLATION AND TESTING

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 49

    II.5.2 Measurement tests The measurement range is up to 1.5 times the nominal value (5 A). The error made in this range must be lower than the 0.5% of 1.2*nominal value

    The worker decides the points to check but those below are recommended:

    Current (A) Voltage (V) 0.5 20 1 50 5 (nominal) 65 (aprox. nominal) 6 80

    The measurements will be carried out by injecting voltages and currents in a phase and checking in the console that that phase presents a value different to zero and that is within the defined margins.

    This test must be carried out for all the phases seeing the measurement in the console.

    II.5.3 Register time setting From the synchronization menu, time and date of the PC are introduced.

    Push OK and check if the relay accepts the data/time sent.

  • 2BPREVENTIVE MAINTENANCE

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 50

    APPENDIX III. PREVENTIVE MAINTENANCE The self-checking the register carries out continuously can detect the following situations:

    Failure in the voltage reference of the converter

    Failure in the FLASH memory recording

    Failure in the relay activation

    Failure in the DSP communication

    Failure in the clock synchronization

    Battery failure In case of detecting any failure, the alarm is kept until the failure disappears. This alarm can be displayed through:

    Control events

    Events

    Digital outputs

    Led

    III.1. FAILURE DETECTION The failure detection can happen in various ways.

    Control signals If the hardware status signal (see signals 128 to 133 in the section List of Available signals) are set at 1, they indicate that anomalous situation is occurring in the register. With value at 0 it indicates Hardware OK.

    Digital outputs A digital output can be programmed with the signal HW status, which will be activated in case of critical error and deactivated under normal operation.

    Leds The programmable Leds dispose the same options as the digital outputs.

    The bicolour Led programmed as (Failure HW) indicates:

    Correct functioning, if green

    Critical error detection, if red

    Events The events indicate the type of error detected and they are those quoted in the first part of this chapter.

    The event of corrected hardware errors indicates that the problems have been solved.

  • 2BPREVENTIVE MAINTENANCE

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 51

    III.2. ERROR HANDLING PROCEDURE The procedure will depend on the detected error and the register status and on the state of the register.

    If the register is off, check that the power supply is correct. If the unit is well supplied, contact the technical service.

    If the register is on but it shows failure, return to the events screen and check which type of error it is:

    If critical error, with no specific indication, is shown and the error persists after turning the register off and on, contact the technical service.

    If converter or reference voltage error is shown. Check the measurements, and if they are correct, turn off and on the register; if the error does not disappear, contact the technical service.

    If Clock error is shown, synchronize it manually. If the error persists, contact the technical service.

    If error in the Flash memory recording is shown, send the settings again. If the error persists, contact the technical service.

  • 3BUSER INTERFACE

    Ingeteam Transmission & Distribution S.A.

    PQM300T User Manual 52

    APPENDIX IV. USER INTERFACE The quality register can be monitorized through a PC. That way, both register data and its configuration can be easily accessed. It also allows the displaying of sag and swell stored to the event queue, to the quality historical as well as to the control measurements continuously carried out by the register and to the capture and displaying of the wave shape. Besides, it allows programming the necessary settings for its operation.

    The communication with the register can be LOCAL mode (Null Modem cable) or REMOTE (telephone call via modem).

    Two options of user interface are available:

    PQM Console: it operates only with the quality registers.

    Sipcon Console: it allows the operation inside an integrated control system, with other units such as protections .

    IV.1. PQM CONSOLE This console operates in an autonomous way and allows the automatic control of several registers. It also allows LOCAL and REMOTE communication, as well as working without being connected to the register