[Sharma, 1(7): Sep., 2012] http: // www.ijesrt.com (C) Intern IJESRT INTERNATIONAL JOUR Transient Stabil *1 YMCA Unive 2 DCR Un This paper presents transient stability a Transient stability of a power system simulations outputs. A self sufficient m stability analysis is done by considering results are found to be more accurate a electromagnetic transient program. Keywords: MATLAB, Simulink, FCT Introduction Modern electric power systems have gr complexity due to interconnections, large generating units and extra high vo etc. Due to increased operations whi power system to be highly stressed need for dynamic stability of power sys Transient stability assessment (TSA dynamic security assessment of power evolves the evolution of the ability of to remain in equilibrium when disturbances. The system respon disturbances involves large variation o power flows bus voltages and other sys Transient stability is a condition that ch dynamics of power system subjected initial state proceeding the fault is ba system is said to posses transient stabil fault it is capable of maintaining operation and returning to initial state The transient stability is a function of condition and the disturbance. Thi transient stability analysis complicate linear ties of the system cannot be ignor In stability assessment the critical (CCT) is a very important param maintain the stability of power system maximum time duration that a fault power system without loss of stability. time is set randomly. If the fault cleari is more than CCT then the relative roto IS national Journal of Engineering Sciences & Research Te RNAL OF ENGINEERING SCIENCES & RE TECHNOLOGY lity Analysis of Power System Using Matla P R Sharma *1 , Narender Hooda 2 ersity of Science and Technology Faridabad, India niversity of Science & Technology, Murthal [email protected] Abstract assessment of multi-machine system with the help of Sim is based on the generator relative rotor angles obtained model of IEEE nine bus system has been given with full g three phase fault at a bus with different Fault Clearing and quiet satisfactory as compared to models simulated i T, transient stability. rown to a large installation of oltage tie-lines ich may cause condition, the stem is arising. A) is part of r system which power system subjected to nse to such of rotor angles, stem variables. haracterizes the to a fault, the alanced one. A ility if after the g synchronous or close to it. both operating is makes the ed as the non red. clearing time meter in order m. The CCT is may occur in . Fault clearing ing time (FCT) or angles will go out of step and the system Methods normally employed to f by using time domain simul artificial intelligence method simulation method is implemen state space differential methods interactive environment for mode a wide variety of dynamic system easily using blocks and results quickly. Simulink is used for stu non-linearity of the system an research tool. Use of Simulink is research work in the area of powe the other areas. In this paper mul system is modeled in Matlab/sim stability analysis is done with th bus. System Modeling The system used is IEEE 9 bus generators, six transmission line and three transformers is shown MVA is 100 and the system freq system data is given in Appen occurring near bus 7 and fault is line 5-7.Fault clearing time is complete system is modeled in mathematical equations. All the machine buses are eliminate representations of the internal nod are obtained. Using the self and SSN: 2277-9655 echnology[418-422] ESEARCH ab mulink based model. d from time domain l detail and transient Time (FCT) and the in PSPICE and other m will lose stability. find out the TSA are lations, direct and ds. Time domain nted by solving the s. Simulink is an eling and simulating ms. A system is built s can be displayed udying the effects of nd thus is an ideal s growing rapidly for er system and also in lti machine nine bus mulink and transient he fault located in a s system with three es, three load buses n in Fig 1. The base quency is 60 Hz. The ndix 1.The fault is s cleared by opening set randomly. The n Simulink with the e buses except the ed and multi-port des of the generators d transfer admittance

description

IEEE RESEARCH PAPER

Transcript of Transient Stability Analysis of Power System Using Matlab

Page 1: Transient Stability Analysis of Power System Using Matlab

[Sharma, 1(7): Sep., 2012]

http: // www.ijesrt.com (C) International Journal of Engineering

IJESRT INTERNATIONAL JOURNA

Transient Stability Analysis of Power System Using Matlab

*1YMCA University of 2DCR University of Science & Technology, Murthal

This paper presents transient stability assessment of multiTransient stability of a power system is based on the generator relative rotor angles obtained from time domain simulations outputs. A self sufficient model of IEEE nine bus system has been given with full detail and transient stability analysis is done by considering three results are found to be more accurate and quiet satisfactory as compared to models simulated in PSPICE and other electromagnetic transient program. Keywords: MATLAB, Simulink, FCT, tra

Introduction Modern electric power systems have grown to a large complexity due to interconnections, installation of large generating units and extra high voltage tieetc. Due to increased operations which may cause power system to be highly stressed condition, tneed for dynamic stability of power system is arising. Transient stability assessment (TSA) is part of dynamic security assessment of power system which evolves the evolution of the ability of power system to remain in equilibrium when subjected to disturbances. The system response to such disturbances involves large variation of rotor angles, power flows bus voltages and other system variables. Transient stability is a condition that characterizes the dynamics of power system subjected to a fault, the initial state proceeding the fault is balanced one. A system is said to posses transient stability if after the fault it is capable of maintaining synchronous operation and returning to initial state or close to it. The transient stability is a function of condition and the disturbance. This makes the transient stability analysis complicated as the non linear ties of the system cannot be ignored. In stability assessment the critical clearing time (CCT) is a very important parameter in order maintain the stability of power system. The CCT is maximum time duration that a fault may occur in power system without loss of stability. Fault clearing time is set randomly. If the fault clearing time (FCT) is more than CCT then the relative rotor angles

ISSN: 2277

International Journal of Engineering Sciences & Research Technology

INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY

Transient Stability Analysis of Power System Using MatlabP R Sharma*1, Narender Hooda2

YMCA University of Science and Technology Faridabad, India DCR University of Science & Technology, Murthal

[email protected] Abstract

This paper presents transient stability assessment of multi-machine system with the help of Simulink based model. of a power system is based on the generator relative rotor angles obtained from time domain

simulations outputs. A self sufficient model of IEEE nine bus system has been given with full detail and transient stability analysis is done by considering three phase fault at a bus with different Fault Clearing Time (FCT) and the results are found to be more accurate and quiet satisfactory as compared to models simulated in PSPICE and other

k, FCT, transient stability.

Modern electric power systems have grown to a large complexity due to interconnections, installation of large generating units and extra high voltage tie-lines etc. Due to increased operations which may cause power system to be highly stressed condition, the need for dynamic stability of power system is arising. Transient stability assessment (TSA) is part of dynamic security assessment of power system which evolves the evolution of the ability of power system to remain in equilibrium when subjected to

urbances. The system response to such disturbances involves large variation of rotor angles, power flows bus voltages and other system variables. Transient stability is a condition that characterizes the dynamics of power system subjected to a fault, the nitial state proceeding the fault is balanced one. A system is said to posses transient stability if after the fault it is capable of maintaining synchronous operation and returning to initial state or close to it. The transient stability is a function of both operating condition and the disturbance. This makes the transient stability analysis complicated as the non linear ties of the system cannot be ignored.

In stability assessment the critical clearing time (CCT) is a very important parameter in order maintain the stability of power system. The CCT is maximum time duration that a fault may occur in power system without loss of stability. Fault clearing time is set randomly. If the fault clearing time (FCT) is more than CCT then the relative rotor angles will

go out of step and the system will lose stability. Methods normally employed to find out the TSA are by using time domain simulations, direct and artificial intelligence methods. Time domain simulation method is implemented by solving the state space differential methods. Simulink is an interactive environment for modeling and simulating a wide variety of dynamic systems. A system is built easily using blocks and results can be displayed quickly. Simulink is used for studying the effects of non-linearity of the system and thus is an ideal research tool. Use of Simulink is growing rapidly for research work in the area of power system and also in the other areas. In this paper multi machine nine bus system is modeled in Matlab/simulink and transientstability analysis is done with the fault located in a bus. System Modeling The system used is IEEE 9 bus system with three generators, six transmission lines, three load buses and three transformers is shown in Fig 1. The base MVA is 100 and the system frequency is 60 Hz. The system data is given in Appendix 1.The fault is occurring near bus 7 and fault is cleared by opening line 5-7.Fault clearing time is set randomly. The complete system is modeled in Simulink with the mathematical equations. All the buses except the machine buses are eliminated and multirepresentations of the internal nodes of the generators are obtained. Using the self and transfer admittance

ISSN: 2277-9655

Sciences & Research Technology[418-422]

ENCES & RESEARCH

Transient Stability Analysis of Power System Using Matlab

machine system with the help of Simulink based model. of a power system is based on the generator relative rotor angles obtained from time domain

simulations outputs. A self sufficient model of IEEE nine bus system has been given with full detail and transient phase fault at a bus with different Fault Clearing Time (FCT) and the

results are found to be more accurate and quiet satisfactory as compared to models simulated in PSPICE and other

go out of step and the system will lose stability. Methods normally employed to find out the TSA are by using time domain simulations, direct and

methods. Time domain simulation method is implemented by solving the

pace differential methods. Simulink is an interactive environment for modeling and simulating a wide variety of dynamic systems. A system is built easily using blocks and results can be displayed quickly. Simulink is used for studying the effects of

inearity of the system and thus is an ideal research tool. Use of Simulink is growing rapidly for research work in the area of power system and also in the other areas. In this paper multi machine nine bus system is modeled in Matlab/simulink and transient stability analysis is done with the fault located in a

The system used is IEEE 9 bus system with three generators, six transmission lines, three load buses and three transformers is shown in Fig 1. The base MVA is 100 and the system frequency is 60 Hz. The system data is given in Appendix 1.The fault is

ing near bus 7 and fault is cleared by opening 7.Fault clearing time is set randomly. The

complete system is modeled in Simulink with the mathematical equations. All the buses except the machine buses are eliminated and multi-port

the internal nodes of the generators are obtained. Using the self and transfer admittance

Page 2: Transient Stability Analysis of Power System Using Matlab

[Sharma, 1(7): Sep., 2012] ISSN: 2277-9655

http: // www.ijesrt.com (C) International Journal of Engineering Sciences & Research Technology[418-422]

parameters of reduced electrical network electric power output of the generators can be obtained. The program to obtain the reduced admittance matrix is given in Appendix. The admittance matrix Ybus,mod is augmented by including the transient reactance of the generators. Let Ybus,mod after inclusion of load impedances be partitioned as

Ybus,mod = 1 2

3 4

Y Y

Y Y

(1)

Where sub matrix Y1 is of order m×m and corresponds to the buses where generators are connected and Y2 , Y3 and Y4 are the other sub matrices. Then the augmented bus admittance matrix Ybus,aug with ground as reference would be represented as

, 1 2

3 4

0

0bus aug

y y

Y y Y y Y

Y Y

− = − +

(2)

The matrix is reduced by applying Kron’s reduction formula eliminating all buses expect the generator buses. For symmetrical three phase to ground at bus k the row and column corresponding to bus k are set to zero before applying network reduction. In stability analysis three reduced matrices are required to be computed pre-fault, during fault and the post fault in power system.

Fig. 1 WSCC 3-machine 9 bus system

The generator electric power output for each machine is computed by following equation

2

1

cos( )n

ei i ii i j ij ij i j

j

P E G E E Y θ δ δ=

= + − +∑

(3) Where

The equation of the motion are given by

2

1

2cos(

ni i

i i mi i ii i j ij ij i jR j

H dD P E G EE Y

dt

ω ω θ δ δω

=

+ = − + − + ∑

(5) And

ii R

d

d t

δ ω ω= − (6)

It is noted that prior to the fault (t=0) Pmi0 = Pei0 The subscript 0 is used to indicate the pre transient conditions. As the network changes due to fault, the corresponding values will be changed in the above equation. Simulink Models The complete three generator system shown in Fig.1 has been simulated as single integral model in Simulink. Fig 2 shows the complete block diagram of the system for transient stability study. Subsystems 1 is meant to compute the electric power output of each generator. The model also facilitates the choice of simulation parameters like start time, stop time, solver etc.

i j i j i j i j i j

i i i i i i i i i

Y Y G jB

Y Y G jB

θθ

= ∠ = +

= ∠ = +

Page 3: Transient Stability Analysis of Power System Using Matlab

[Sharma, 1(7): Sep., 2012] ISSN: 2277-9655

http: // www.ijesrt.com (C) International Journal of Engineering Sciences & Research Technology[418-422]

Fig.2 Complete system Model for Transient stability

Analysis

Fig.3 Simulink model for Computation of electric power

output of generator 1

Simulation Results System Responses are given for different values of FCT. Fault is created near bus 7 and it is cleared at different clearing time by opening line 5-7. Fig 4 (a) and (b) shows the relative angular positions of the generators taking generator one as reference and individuals angles of each generator. Fig(c) and (d) shows the accerlating powers and angular velocities of each generator for the FCT equal to 0.1sec Fig shows that the rotors angles are in synchronism with each other making the system stable when the fault clearing time is 0.1sec.As the FCT increases the system will move towards instability as the FCT will become greater that the CCT. When the FCT in 0.3 sec. the system is unstable. Fig 5(a)-(d) shows the accerlating powers, Relative angular positions and angular velocities of the generators and Fig 5(b) shows as the fault clearing time is increased the rotor angles of the generators go out of synchronism and the system is losing stability. (Fault cleared at 0.1s)

(a) Relative angular positions of angles

(Fault cleared at 0.1s)

(b) Angular positions of individual generators

(Fault cleared at 0.1s)

Page 4: Transient Stability Analysis of Power System Using Matlab

[Sharma, 1(7): Sep., 2012] ISSN: 2277-9655

http: // www.ijesrt.com (C) International Journal of Engineering Sciences & Research Technology[418-422]

(c) Generator accelerating Powers

(Fault cleared at 0.1s)

(d) Angular velocities of generators

Fig 4 (a) – (d) (Fault cleared at 0.3sec)

(a) Accerlating power of generators

(Fault cleared at 0.3sec)

(b) Relative angular positions of generators

(Fault cleared at 0.3 sec)

(c) Angular velocities of individual generators

Fig 5(a)-(c) Fig 6(a)-(b) shows the relative rotor angles and the accelerating powers of the generators. Fig 6(a) shows that the rotor angles synchronism making the system unstable. (Fault cleared at 0.5sec)

(a) Relative angles in degree

(Fault cleared at 0.5sec)

(c) Accerlating powers of the generators

Fig.6 (a) - (b) Conclusion A complete model to study the transient behavior of Multi-machine system was developed using Simulink. It is basically a transfer function and block diagram representation of system equations. The system was simulated for different FCT and the results are highly satisfactory. A Simulink model is very user friendly and for transient stability analysis the model facilitates the fast and precise solution of nonlinear differential equation.

Page 5: Transient Stability Analysis of Power System Using Matlab

[Sharma, 1(7): Sep., 2012] ISSN: 2277-9655

http: // www.ijesrt.com (C) International Journal of Engineering Sciences & Research Technology[418-422]

Appendix n=9; Y=zeros(n); n=n-1; i=1; k=1; for ii=1:locs; add=loc(ii+1)-loc(ii); for kk=1:add; J=c(k); Y(i,i)=Y(i,i)+1/e(k); if J==0; disp('branch') k=k+1; else Y(J,J)=Y(J,J) +1/e(k); Y(i,J)=Y(i,J) -1/e(k); Y(J,i)=Y(i,J); k=k+1; end end i=i+1; end Y References

[1] P.Kundur, Power system Stability and control, EPRI Power Sytem Engineering Series.

[2] I.J.Nagrath and D.P.Kothari, Power system Engineering

[3] Louis-A Dessaint et al., ‘Powe system simulation tool based on Simulink, IEEE Trans. Industrial Electronica 1999, 1252-1254

[4] P.M Anderson and A.A.Fouad, Power System Control and stability 1977

[5] M.Klein ,G.J.Rogers,P Kundur,”A fundamental Study of Inter –Area Oscillation in Power Systems,”IEEE Transsactions on Power System.vol 6, No 3,August 1991

[6] L.Wang ,F Howell ,P.Kundur, C.Y.Ching and w.Xu, “a tool for small Signal assessment of Power Systems,” PICA 2110, Sydney, Australia, May 21-24,2001

[7] M.J.Gibbard,N. Martin, J.J Sanchez-Gasca, N.Uchida,V Vittal and L.Wang, “Recent Applications of Linear Analysis Techniques,” IEEE Trans. On Power Systems, Vol 16,No 1 February 2002

[8] M.Randhawa,B.Sapkota, V. Vittal,S.Kolluri and S.Mondal,”Voltage stability assessment for Large Power Systems,”proc. 2008 IEEE Power and Energy Society General Meeting.