Transient Angle Stability

download Transient Angle Stability

of 101

Transcript of Transient Angle Stability

  • 8/13/2019 Transient Angle Stability

    1/101

    1539pk TS - 1

    Transient Angle StabilityTransient Angle Stability

    Description of Transient Stability

    An elementary view of TS

    Methods of TS analysis Time-domain simulation

    Structure of power system model

    Representation faults

    Performance of protective relaying

    Concept of electrical centre!

    Case studies

    Methods of TS enhancement

    Ma"or blac#outs caused by Transient $nstability

    %ovember &' (&)* %ortheast +S' ,ntario

    blac#out

    March ((' (&&& ra.il blac#out

    ,utline

  • 8/13/2019 Transient Angle Stability

    2/101

    1539pk TS - 2

    /hat is Transient 0Angle1 Stability2/hat is Transient 0Angle1 Stability2

    The ability of the power system to maintain

    synchronous operation when sub"ected to a severe

    transient disturbance

    faults on transmission circuits' transformers'

    buses

    loss of generation

    loss of loads

    Response involves large e3cursions of generator

    rotor angles4 influenced by nonlinear power-angle

    relationship

    Stability depends on both the initial operating stateof the system and the severity of the disturbance

    Post-disturbance steady-state operating conditions

    usually differ from pre-disturbance conditions

  • 8/13/2019 Transient Angle Stability

    3/101

    1539pk TS - 3

    $n large power systems' transient instability may notalways occur as 5first swing5 instability

    could be as a result of superposition of several

    swing modes causing large e3cursions of rotor

    angle beyond the first swing

    Study period of interest in transient stability studies

    is usually limited to 6 to * seconds following thedisturbance7

    may e3tend up to about (8 seconds for very large

    systems with dominant inter-area swing modes

    Power system designed and operated to be stable for

    specified set of contingencies referred to as 5normal

    design contingencies5

    selected on the basis that they have a reasonable

    probability of occurrence

    $n the future' probabilistic or ris#-based approach

    may be used

  • 8/13/2019 Transient Angle Stability

    4/101

    1539pk TS - 4

    (9 An :lementary ;iew of Transient(9 An :lementary ;iew of Transient

    StabilityStability

    Demonstrate the phenomenon using a very simple

    system and simple models

    System shown in

  • 8/13/2019 Transient Angle Stability

    5/101

    1539pk TS - 5

    The generator>s electrical power output is

    /ith the stator resistance neglected' P e represents the

    air-gap power as well as the terminal power 

  • 8/13/2019 Transient Angle Stability

    6/101

    1539pk TS - 6

    Power-Angle RelationshipPower-Angle Relationship

    oth transmission circuits in-service4 Curve (

    operate at point 5a5 0P e = P 

    m1

    ,ne circuit out-of-service4 Curve ?

    lower P max 

    operate at point 5b5

    higher reactance →  higher δ to transmit samepower 

  • 8/13/2019 Transient Angle Stability

    7/101

    1539pk TS - 7

    The oscillation of δ is superimposed on thesynchronous speed

    8

    Speed deviation

    the generator speed is practically e@ual to 8' and theper unit 0pu1 air-gap tor@ue may be considered to be

    e@ual to the pu air-gap power 

    tor@ue and power are used interchangeably when

    referring to the swing e@uation9

    :@uation of Motion or Swing :@uation

    where4

    P m

    mechanical power input 0pu1

    P max  ma3imum electrical power output 0pm1

    H  inertia constant 0M/-secBM;A1  rotor angle 0elec9 radians1t time 0secs1

    :ffects of Disturbance:ffects of Disturbance

      0 r  dt d  ωω

  • 8/13/2019 Transient Angle Stability

    8/101

    1539pk TS - 8

    Response to a Short Circuit

  • 8/13/2019 Transient Angle Stability

    9/101

    1539pk TS - 9

    Stable CaseStable Case

    Response to a fault cleared in tcl seconds - stable case

  • 8/13/2019 Transient Angle Stability

    10/101

    1539pk TS - 10

    Stable CaseStable Case cont>dcont>d

    Pre-disturbance4

    both circuits $BS 4 Pe  P

    m'

    8

    operating point a

  • 8/13/2019 Transient Angle Stability

    11/101

    1539pk TS - 11

    +nstable Case+nstable Case

    Response to a fault cleared in tc? seconds - unstable case

  • 8/13/2019 Transient Angle Stability

    12/101

    1539pk TS - 12

    +nstable Case+nstable Case cont>dcont>d

    Area A2  above P 

    m is less than A

    1

    /hen the operating point reaches e' the #inetic

    energy gained during the accelerating period has notyet been completely e3pended

    the speed is still greater than ω8 and δ continues to

    increase

    eyond point e, P e

  • 8/13/2019 Transient Angle Stability

    13/101

    1539pk TS - 13

  • 8/13/2019 Transient Angle Stability

    14/101

    1539pk TS - 14

    Practical Method of TS AnalysisPractical Method of TS Analysis

    Practical power systems have comple3 networ#

    structures

    Accurate analysis of transient stability re@uires detailed

    models for4

    generating unit and controls

    voltage dependent load characteristics

    E;DC converters'

  • 8/13/2019 Transient Angle Stability

    15/101

    1539pk TS - 15

    ?9 %umerical $ntegration Methods?9 %umerical $ntegration Methods

    Differential e@uations to be solved are nonlinear

    ordinary differential e@uations with #nown initial

    values4

     x   is the state vector of n dependent variables'

    t  is the independent variable 0time1

    Objectie! solve  x   as a function of t ' with the initial

    values of  x   and t  e@ual to  x 0  and t 

    0 ' respectively9

    "ethods! :uler>s Method

    Modified :uler>s Method

    Runge-Futta 0R-F1 Methods

    Trape.oidal Rule

    ( )t  x f 

    dt 

    dx ,=

  • 8/13/2019 Transient Angle Stability

    16/101

    1539pk TS - 16

    %umerical stability%umerical stability

    Depends on propagation of error 

    %umerically stable if early errors cause no significant

    errors later 

    %umerically unstable otherwise

    $mportant to consider numerical stability in the

    application of numerical integration methods

  • 8/13/2019 Transient Angle Stability

    17/101

    1539pk TS - 17

    Stiffness of Differential :@uationsStiffness of Differential :@uations

    Ratio of largest to smallest time constants or' more

    precisely' eigenvalues

    $ncreases with modelling detail

    Affects numerical stability

    Solution using e3plicit integration methods may

    5blow up5 with stiff systems unless very small time

    step is used9

  • 8/13/2019 Transient Angle Stability

    18/101

    1539pk TS - 18

    %umerical Stability of :3plicit $ntegration%umerical Stability of :3plicit $ntegration

    MethodsMethods

    :3plicit Methods

    :uler>s' Predictor-Corrector' and R-F methods

    Dependent variables 3 at any value of t is computed from

    a #nowledge of the values of 3 from the previous timesteps

    3nG(

     for 0nG(1th step is calculated e3plicitly by

    evaluating f03't 1 with #nown 3

    :asy to implement for the solution of a comple3 set of

    system state e@uations

    Disadvantage

    %ot numerically A-stable

    step si.e limited by small time constants or

    eigenvalues

  • 8/13/2019 Transient Angle Stability

    19/101

    1539pk TS - 19

    $mplicit $ntegration Methods$mplicit $ntegration Methods

    Consider the differential e@uation

    The solution for x at t=t 1=t 0 #  t may be e3pressed inthe integral form as

    $mplicit methods use interpolation functions for the

    e3pression under the integral $nterpolation implies that the functions must pass

    through the yet un#nown points at time t (

    $ra%e&oidal '(le is simplest method

    ( )   ττ∫ +=   d  x f  x  x   t 

    t   ,1

    001

    ( )   00,   t t at  x  x witht  x f dt 

    dx ===

  • 8/13/2019 Transient Angle Stability

    20/101

    1539pk TS - 20

    Trape.oidal RuleTrape.oidal Rule

    Simplest implicit method7 uses linear interpolation

    $ntegral appro3imated by trape.oids

     f(x,t)

     f(x0 ,t 0 ) f(x1 ,t 1 )

    t 0   t 1t 

    ∆t 

  • 8/13/2019 Transient Angle Stability

    21/101

    1539pk TS - 21

    Trape.oidal rule is given by

    A general formula giving the value of 3 at t=t n#1 

    is

    InG( appears on both sides of :@uation

    implies that the variable 3 is computed as a function

    of its value at the previous time step as well as the

    current value 0which is un#nown1

    an implicit e@uation must be solved

    %umerically A-stable 4 stiffness affects accuracy not

    stability

    Trape.oidal rule is a second order method

    Eigher order methods difficult to program and less

    robust

      ]110 0 0 1   t , x f t , x f 2 t  x  x   

    ]1n1nnnn1n   t , x f t , x f 2 

    t  x  x   

  • 8/13/2019 Transient Angle Stability

    22/101

    1539pk TS - 22

    69 Simulation of Power System Dynamic69 Simulation of Power System Dynamic

    ResponseResponse

    Structure of the Power System Model4

    Components4

    Synchronous generators' and the associated e3citationsystems and prime movers

    $nterconnecting transmission networ# including static

    loads

    $nduction and synchronous motor loads

    ,ther devices such as E;DC converters and S;Cs

    Monitored $nformation4

    asic stability information

    us voltages

    Jine flows

    Performance of protective relaying' particularly

    transmission line protection

  • 8/13/2019 Transient Angle Stability

    23/101

    1539pk TS - 23

  • 8/13/2019 Transient Angle Stability

    24/101

    1539pk TS - 24

    Models used must be appropriate for transient

    stability analysis

    transmission networ# and machine stator

    transients are neglected

    dynamics of machine rotors and rotor circuits'

    e3citation systems' prime movers and otherdevices such as E;DC converters are represented

    :@uations must be organi.ed in a form suitable for

    numerical integration

    Jarge set of ordinary differential e@uations and large

    sparse algebraic e@uations

    differential-algebraic initial value problem

  • 8/13/2019 Transient Angle Stability

    25/101

    1539pk TS - 25

    ,verall System :@uations,verall System :@uations

    :@uations for each dynamic device4

    where

    3d

    state vector of individual device

    $d

    '  and ) components of current in"ection from

      the device into the networ#

    ;d '  and )  components of bus voltage

    %etwor# e@uation4

    where

     L% networ# mode admittance matri3$ node current vector  

    ; node voltage vector  

    ( )

    ( )d d d d 

    d d d d 

    V  x g I 

    V  x f  x 

    ,

    ,

    =

    =

    V Y I  N =

  • 8/13/2019 Transient Angle Stability

    26/101

    1539pk TS - 26

    ,verall system e@uations4

    comprises a set of first order differentials

    and a set of algebraic e@uations

    where

    3 state vector of the system

    ; bus voltage vector  

    $ current in"ection vector  

    Time t  does not appear e3plicitly in the above

    e@uations

    Many approaches for solving these e@uations

    characteri.ed by4

    a1 The manner of interface between the differential and

    algebraic e@uations4 partitioned or simultaneous

    b1 $ntegration method used

    c1 Method used for solving the algebraic e@uations4

    - =auss-Seidal method based on admittance matri3

    - direct solution using sparsity oriented triangularfactori.ation

    - iterative solution using %ewton-Raphson method

    ( )V  x f  x    ,=

    ( )   V Y V  x I N 

    =,

  • 8/13/2019 Transient Angle Stability

    27/101

    1539pk TS - 27

    Analy.e transient stability including the effects of

    rotor circuit dynamics and e3citation control of the

    following power plant with four *** M;A units4

    Disturbance4 Three phase fault on circuit ? at

  • 8/13/2019 Transient Angle Stability

    28/101

    1539pk TS - 28

    *enerator %arameters!

    The four generators of the plant are represented by an e@uivalent

    generator whose parameters in per unit on ???8 M;A base are as

    follows4

    The above parameters are unsaturated values9 The effect of

    saturation is to be represented assuming the d - and +axes have

    similar saturation characteristics based on ,CC

    Excitation system %arameters!

    The generators are e@uipped with thyristor e3citers with A;R and

    PSS as shown in

  • 8/13/2019 Transient Angle Stability

    29/101

    1539pk TS - 29

    ,b"ective

    :3amine the stability of the system with the following

    alternative forms of e3citation control4

    0i1 Manual control' i9e9' constant E fd 

    0ii1 A;R with no PSS

    0iii1 A;R with PSS

    Consider the following alternative fault clearing

    times4

    a1 898H s

    b1 89(8 s

  • 8/13/2019 Transient Angle Stability

    30/101

    1539pk TS - 30

    Computed using the =ill>s version of fourth order R-F

    integration method with a time step of 898? s9

    /ith constant E fd ' the system is transiently stable

    however' the level of damping of oscillations islow

    /ith a fast acting A;R and a high e3citer ceiling

    voltage' the first rotor angle swing is significantly

    reduced

    however' the subse@uent swings are negativelydamped

    post-fault system small-signal unstable

    /ith the PSS' the rotor oscillations are very well

    damped without compromising the first swing

    stability

    Case 0a14 Transient response with the fault clearing

    time e@ual to 898H s

  • 8/13/2019 Transient Angle Stability

    31/101

    1539pk TS - 31

  • 8/13/2019 Transient Angle Stability

    32/101

    1539pk TS - 32

  • 8/13/2019 Transient Angle Stability

    33/101

    1539pk TS - 33

    Responses of rotor angle δ with the three alternativeforms of e3citation control are computed

    /ith constant :fd' the generator is first swing

    unstable

    /ith a fast acting e3citer and A;R' the generator

    maintains first swing stability' but loses synchronism

    during the second swing

    The addition of PSS contributes to the damping of

    second and subse@uent swings

    +se of a fast e3citer having a high ceiling

    voltage and e@uipped with a PSS contributes

    significantly to the enhancement of the overall

    system stabilityO

    Case 0b14 Transient response with the fault clearing

    time tc e@ual to 89( s

  • 8/13/2019 Transient Angle Stability

    34/101

    1539pk TS - 34

  • 8/13/2019 Transient Angle Stability

    35/101

    1539pk TS - 35

    *9 Representation of

  • 8/13/2019 Transient Angle Stability

    36/101

  • 8/13/2019 Transient Angle Stability

    37/101

    1539pk TS - 37

    Transmission Jine ProtectionTransmission Jine Protection

  • 8/13/2019 Transient Angle Stability

    38/101

    1539pk TS - 38

    0a1 ,vercurrent Relaying0a1 ,vercurrent Relaying

    Simplest and cheapest form of line protection

    Two basic forms4 instantaneous overcurrent relay and

    time overcurrent relay

    Difficult to apply where coordination' selectivity' and

    speed are important changes to their settings are usually re@uired as

    system configuration changes

    cannot discriminate between load and fault currents7

    therefore' when used for phase-fault protection' they

    are applicable only when the minimum fault current

    e3ceeds the full load current

    +sed principally on subtransmission systems' and

    radial distribution systems

    faults here usually do not affect system stability so

    high-speed protection is not re@uired

  • 8/13/2019 Transient Angle Stability

    39/101

    1539pk TS - 39

    0b1 Distance Relaying0b1 Distance Relaying

    Responds to a ratio of measured voltage to measured

    current

    $mpedance is a measure of distance along the line

    Relatively better discrimination and selectivity' bylimiting relay operation to a certain range of the

    impedance

    Types

    impedance relay

    reactance relay

    mho relay

    modified mho and impedance relays' and hybrids

    Most widely used form for protection of transmission

    lines

    Triggering characteristics shown conveniently onR-I plane

  • 8/13/2019 Transient Angle Stability

    40/101

    1539pk TS - 40

  • 8/13/2019 Transient Angle Stability

    41/101

    1539pk TS - 41

    Three .one approach4

    one ( primary protection for protected line

    K8Q reach and instantaneous

    one ? primary protection for protected line

    (?8Q reach and timed 0896 - 89* s1

    one 6 remote bac#up protection for ad"acent line

    covers ne3t line and timed 0? s1

  • 8/13/2019 Transient Angle Stability

    42/101

    1539pk TS - 42

    0c1 Pilot Relaying Schemes0c1 Pilot Relaying Schemes

    +se communication channels 0pilots1 between the

    terminals of the line that they protect

    Determine whether the fault is internal or e3ternal to

    the protected line' and this information is transmitted

  • 8/13/2019 Transient Angle Stability

    43/101

    1539pk TS - 43

    :ach terminal station of the line has4

    ?nderreachin@ &one 1 phase and ground directionaldistance relays covering about H*-K8Q of the line

    trip local brea#ers instantaneously

    Oerreachin@ &one 2  phase and ground directionaldistance relays covering about (?8Q of the impedance ofthe protected line9

    send permissive signal to remote end

    trip local brea#ers if permissive signal receivedfrom remote end

    if apparent remains inside relay characteristicfor fi3ed time 0typically 89N s1' local brea#erstripped without receiving permissive signal

  • 8/13/2019 Transient Angle Stability

    44/101

    1539pk TS - 44

  • 8/13/2019 Transient Angle Stability

    45/101

    1539pk TS - 45

  • 8/13/2019 Transient Angle Stability

    46/101

  • 8/13/2019 Transient Angle Stability

    47/101

  • 8/13/2019 Transient Angle Stability

    48/101

    1539pk TS - 48

    Relaying uantities During SwingsRelaying uantities During Swings

    The performance of protective relaying during electro-

    mechanical oscillations and out-out-step conditions

    illustrated by considering the following system4

    0a1 Schematic diagram

    0b1 :@uivalent circuit

  • 8/13/2019 Transient Angle Stability

    49/101

    1539pk TS - 49

    The apparent impedance seen by an impedance relay at C

    loo#ing towards the line is given by

    $f :A:-(98 pu

    0 E E 

    E A A 

    ) B

    ) B

    A E B

    ) BE B

    B A

     A$  A

     A A> > 

    ∠∠ =

     

       

     

    2 cot 2 

     j A 2 

    sin2 

    cos1 j 

    1A A 

    sin j 2 

    sin j cos1A A 

    10 110 1

    10 1A A 

    10 1

    A A A 

     A

    $  A

    $  A

    $  A

    $  A> 

     

  • 8/13/2019 Transient Angle Stability

    50/101

    1539pk TS - 50

    During a swing' the angle δ changes9   as a function of δ on an '  diagram' when:

    A:

    -

    %ote4 ,rigin is assumed to be at C' where the relay is located9

      as a function of δ' with E  A=E B

  • 8/13/2019 Transient Angle Stability

    51/101

    1539pk TS - 51

    /hen E  A and E 

    B are e@ual' the locus of  

    >  is seen to be a

    straight line which is the perpendicular bisector of the

    total system impedance between A and ' i9e9' of the

    impedance T  the angle formed by lines from A and to any

    point on the locus is e@ual to the corresponding

    angle δ /hen δ8' the current  I  is .ero and  

    >  is infinite

    /hen δ(K8' the voltage at the electrical centre is .ero the relay at C in effect will see a 6-phase fault at

    the electrical centre9 The electrical centre and

    impedance centre coincide in this case9

    $f E  A is not e@ual to E 

    B' the apparent impedance loci are

    circles' with their centres on e3tensions of the

    impedance line AB

    /hen E  AE 

    B' the electrical centre will be above the

    impedance centre7 when E  AE 

    B' the electrical centre will

    be below the impedance centre9

  • 8/13/2019 Transient Angle Stability

    52/101

    1539pk TS - 52

  • 8/13/2019 Transient Angle Stability

    53/101

    1539pk TS - 53

  • 8/13/2019 Transient Angle Stability

    54/101

    1539pk TS - 54

    Prevention of Transmission Jine TrippingPrevention of Transmission Jine Tripping

    During Transient ConditionsDuring Transient Conditions

    Re@uirements for prevention of tripping during swing

    conditions fall into two categories4

    Prevention of tripping during stable swings' while

    allowing tripping for unstable transients9

    Prevention of tripping during unstable transients' and

    forcing separation at another point9

    Prevention of tripping during stable transients

    UmhoV distance relay characteristic may be too large

    and have regions into which stable swings may enter 

    $n order to minimi.e the possibility of tripping during

    stable swings4

    use of ohm units 0blinders1

    composite relays

    shaped relay 0lens' peanut' etc91

  • 8/13/2019 Transient Angle Stability

    55/101

    1539pk TS - 55

    Tripping can occur

    only for impedance

    between ,( and ,?'

    and within M

  • 8/13/2019 Transient Angle Stability

    56/101

    1539pk TS - 56

    ,ut-of-Step loc#ing and Tripping Relays,ut-of-Step loc#ing and Tripping Relays

    $n some cases' it may be desirable to prevent tripping of

    lines at the natural separation point' and choose the

    separation point so that4

    a1 load and generation are better balanced on both

    sides' or 

    b1 a critical load is protected' or 

    c1 the separation is at a corporate boundary9

    $n certain instances' it may be desirable to trip faster in

    order to prevent voltage declining too far9

    Princi%le of o(tofste% relayin@!

    Movement of the apparent impedance under out-of-step

    conditions is slow compared to its movement when a line

    fault occurs

    transient swing condition can be detected using two

    relays having vertical or circular characteristics on an

    '  plane

    if time re@uired to cross the two characteristics

    0,,S?' ,,S(1 e3ceeds a specified value' the out-of-

    step function is initiated

  • 8/13/2019 Transient Angle Stability

    57/101

    1539pk TS - 57

  • 8/13/2019 Transient Angle Stability

    58/101

    1539pk TS - 58

    $n an o(tofste% tri%%in@ scheme' local brea#ers

    would be tripped9 such a scheme could be used to

    speed up tripping to voltage decline

    ensure tripping of a selected line' instead of other

    more critical circuits

    $n an o(tofste% bloc/in@ scheme'

    relays are prevented from initiating tripping of the

    line monitored' and transfer trip signals are sent

    to open circuits of a remote location

    ob"ective is to cause system separation at a more

    preferable location

  • 8/13/2019 Transient Angle Stability

    59/101

    1539pk TS - 59

    H9 Case Study - Transient StabilityH9 Case Study - Transient Stability

    The ob"ect

    demonstrate transient instability and actions of

    protective relaying

    show methods of maintaining stability

    The system

    ??H& buses' N)H generators' and )*K( branches

    the focus is on a plant with K nuclear units' with a

    total capacity of H888 M/

    all generators and associated controls are modelledin detail

    loads are modelled using voltage-dependent static

    load model 0P*8Q l G *8Q ' (88Q 1

  • 8/13/2019 Transient Angle Stability

    60/101

    1539pk TS - 60

  • 8/13/2019 Transient Angle Stability

    61/101

    1539pk TS - 61

    The Contingency4

    Double line-to-ground 0JJ=1 fault occurs on the *88 #;double circuit line at Wunction I

    Time 0ms1 :vent

    8 %o disturbance

    (88 Apply JJ= fault at Wunction I on circuits ( and ?()N Jocal end clearing4

    ,pen brea#ers at bus ( for circuit (

    ,pen brea#ers at bus ? for circuit ?

    This occurs )N ms after the fault is applied' and this time is computed asthe sum of fault detection time 0?* ms1' au3iliary relay time 0) ms1' andthe brea#er clearing time 066 ms ? cycle19 At this time' the fault remainsconnected on the ends of circuits ( and ? at Wunction I

    (KH Remote end clearing4

    ,pen brea#ers at bus N for circuit ?

    ,pen brea#ers at bus 6 for circuit (

    Clear fault 0the line is isolated1

    This occurs KH ms after the fault is applied' and the time is calculated asthe sum of fault detection time 0?* ms1' au3iliary relay time 0(? ms1'communication time 0(H ms7 microwave1' and brea#er clearing time 066ms ? cycle1

    *888 Terminate simulation

  • 8/13/2019 Transient Angle Stability

    62/101

    1539pk TS - 62

    Simulation4

    A * second simulation was performed

    =6 is seen to lose synchronism and becomes

    monotonically unstable

    similar behaviour for the other H units of the nuclear

    plant

    As =( to =K become unstable' the rest of the system

    becomes generation deficient absolute angles of all machines in the system drift

    slightly

  • 8/13/2019 Transient Angle Stability

    63/101

    1539pk TS - 63

    Analysis4

    Eow does the system come apart as a result of instability2

    ,ut-of-step protection does not operate on =6

  • 8/13/2019 Transient Angle Stability

    64/101

    1539pk TS - 64

  • 8/13/2019 Transient Angle Stability

    65/101

    1539pk TS - 65

    Jine Protection4

    Mho distance relays have .one ( coverage of about H*Q of

    line length' and .one ? over-reach of about (?*Q of line

    length

    Apparent impedance enters the .one ? relays at bus ( and

    enters .one ( and .one ? relays at bus H

    .one ( relay at bus H would trip circuit 6 at bus H and

    send a transfer trip signal to brea#ers at bus ( which

    would then trip circuit 6 at bus (

    true for the companion *88 #; circuit 0N1 which would

    be tripped in an identical manner 

  • 8/13/2019 Transient Angle Stability

    66/101

  • 8/13/2019 Transient Angle Stability

    67/101

    1539pk TS - 67

    Methods of Maintaining Stability4

    Reduction of the pre-contingency output of the plant costly to bottle energy in the plant

    Tripping of ? generating units 0generation re"ection1

    following the disturbance

  • 8/13/2019 Transient Angle Stability

    68/101

    1539pk TS - 68

    K9 Transient Stability :nhancementK9 Transient Stability :nhancement

    ,b"ectives4

    Reduce the disturbing influence by minimi.ing the

    fault severity and duration

    $ncrease the restoring synchroni.ing forces

    Reduce accelerating tor@ue through control of prime-

    mover mechanical power 

    Reduce accelerating tor@ue by applying artificial load

  • 8/13/2019 Transient Angle Stability

    69/101

    1539pk TS - 69

    Eigh-Speed

  • 8/13/2019 Transient Angle Stability

    70/101

    1539pk TS - 70

    Reduction of Transmission SystemReduction of Transmission System

    ReactanceReactance

    Series inductive reactances of transmission networ#s

    are primary determinants of stability limits

    reduction of reactances of various elements of the

    transmission networ# improves transient stability

    by increasing post-fault synchroni.ing powertransfers

    Most direct way of achieving this is by reducing the

    reactances of transmission circuits

    voltage rating' line and conductor configurations'

    and number of parallel circuits determine the

    reactances of transmission lines

    Additional methods of reducing the networ#

    reactances4

    use of transformers with lower lea#age reactances

    series capacitor compensation of transmission

    lines

  • 8/13/2019 Transient Angle Stability

    71/101

    1539pk TS - 71

    Typically' the per unit transformer lea#age reactance

    ranges between 89( and 89(*

    for newer transformers' the minimum acceptable

    lea#age reactance that can be achieved within the

    normal transformer design practices has to be

    established in consultation with the manufacturer 

    May be a significant economic advantage in opting for a

    transformer with the lowest possible reactance

    Series capacitors directly offset the line series reactance

    the ma3imum power transfer capability of a

    transmission line may be significantly increased by

    the use of series capacitor ban#s

    directly translates into enhancement of transientstability' depending on the facilities provided for

    bypassing the capacitor during faults and for

    reinsertion after fault clearing

    speed of reinsertion is an important factor in

    maintaining transient stability7 using nonlinear

    resistors of .inc o3ide' the reinsertion is practically

    instantaneous

  • 8/13/2019 Transient Angle Stability

    72/101

    1539pk TS - 72

    ,ne problem with series capacitor compensation is the

    possibility of subsynchronous resonance with the

    nearby turbo alternators

    must be analy.ed carefully and appropriate

    preventive measures ta#en

    Series capacitors have been used to compensate very

    long overhead lines

    recently' there has been an increasing recognitionof the advantages of compensating shorter' but

    heavily loaded' lines using series capacitors

  • 8/13/2019 Transient Angle Stability

    73/101

    1539pk TS - 73

    Regulated Shunt CompensationRegulated Shunt Compensation

    Can improve system stability by increasing the flow

    of synchroni.ing power among interconnected

    generators 0voltage profile control1

    Static ;AR compensators can be used for this

    purpose

  • 8/13/2019 Transient Angle Stability

    74/101

    1539pk TS - 74

    Regulated Shunt CompensationRegulated Shunt Compensation 0cont>d10cont>d1

  • 8/13/2019 Transient Angle Stability

    75/101

    1539pk TS - 75

    Dynamic ra#ingDynamic ra#ing

    +ses the concept of applying an artificial electrical

    load during a transient disturbance to increase the

    electrical power output of generators and thereby

    reduce rotor acceleration

    ,ne form of dynamic bra#ing involves switching inshunt resistors for about 89* seconds following a

    fault to reduce accelerating power of nearby

    generators and remove the #inetic energy gained

    during the fault

    PA has used such a scheme for enhancing

    transient stability for faults in the +S Pacific%orthwest

    bra#e consists of a (N88 M/' ?N8 #; resistor

    made up of N*'888 ft9 of (B?5 stainless steel wire

    strung on 6 towers

  • 8/13/2019 Transient Angle Stability

    76/101

    1539pk TS - 76

    To date' bra#ing resistors have been applied only to

    hydraulic generating stations remote from load centres hydraulic units' in comparison to thermal units' are

    @uite rugged7 they can' therefore' withstand the

    sudden shoc# of switching in resistors without any

    adverse effect on the units

    $f bra#ing resistors are applied to thermal units' the

    effect on shaft fatigue life must be carefully e3amined

    $f the switching duty is found unacceptable' the

    resistors may have to be switched in three or four steps

    spread over one full cycle of the lowest torsional mode

    ra#ing resistors used to date are all shunt devices

    series resistors may be used to provide the bra#ingeffect

    the energy dissipated is proportional to the

    generator current rather than voltage

    way of inserting the resistors in series is to install a

    star-connected three-phase resistor arrangement

    with a bypass switch in the neutral of the generator-step-up transformer to reduce resistor insulation and

    switch re@uirements

    resistor is inserted during a transient disturbance by

    opening the bypass switch

  • 8/13/2019 Transient Angle Stability

    77/101

    1539pk TS - 77

    Another form of bra#ing resistor application' which

    enhances system stability for only unbalancedground faults' consists of a resistor connected

    permanently between ground and the neutral of the L

    connected high voltage winding of the generator

    step-up transformer 

    under balanced conditions no current flows

    through the neutral resistor 

    when line-to-ground or double line-to-ground

    faults occur' current flows through the neutral

    connection and the resistive losses act as a

    dynamic bra#e

    /ith switched form of bra#ing resistors' theswitching times should be based on detailed

    simulations

    if the resistors remain connected too long' there is

    a possibility of instability on the 5bac#swing5

  • 8/13/2019 Transient Angle Stability

    78/101

    1539pk TS - 78

    Reactor SwitchingReactor Switching

    Shunt reactors near generators provide a simple and

    convenient means of improving transient stability

    Reactor normally remains connected to the networ#

    Resulting reactive load increases the generator

    internal voltage and reduces internal rotor angle

  • 8/13/2019 Transient Angle Stability

    79/101

    1539pk TS - 79

    Steam Turbine

  • 8/13/2019 Transient Angle Stability

    80/101

    1539pk TS - 80

  • 8/13/2019 Transient Angle Stability

    81/101

    1539pk TS - 81

    =enerator Tripping=enerator Tripping

    Selective tripping of generating units for severe

    transmission system contingencies has been used as a

    method of improving system stability for many years

    Re"ection of generation at an appropriate location in the

    system reduces power to be transferred over the critical

    transmission interfaces

    +nits can be tripped rapidly so this is a very effective means

    of improving transient stability

    Eistorically' the application confined to hydro plants7 now

    used on fossil and nuclear plants

    Many utilities design thermal units so that' after tripping'

    they continue to run' supplying unit au3iliaries7 permits theunits to re resynchroni.ed to the system and restored to full

    load in about (* to 68 minutes

    Ma"or turbine-generator concerns4

    the overspeed resulting from tripping the generator 

    thermal stresses due to the rapid load changes

    high levels of shaft tor@ues due to successive

    disturbances

  • 8/13/2019 Transient Angle Stability

    82/101

    1539pk TS - 82

    Controlled System Separation and JoadControlled System Separation and Joad

    SheddingShedding

    May be used to prevent a ma"or disturbance in one part of

    an interconnected system from propagating into the rest of

    the system and causing a severe system brea#up

    Severe disturbance usually characteri.ed by sudden

    changes in tie line power 

    if detected in time and the information is used toinitiate corrective actions' severe system upsets can

    be averted

    $mpending instability detected by monitoring one or more of

    the following4 sudden change in power flow through

    specific transmission circuits' change of bus voltage angle'

    rate of power change' and circuit brea#er au3iliary contacts

    +pon detection of the impeding instability' controlled

    system separation is initiated by opening the appropriate tie

    lines before cascading outages can occur 

    $n some instances it may be necessary to shed selected

    loads to balance generation and load in the separated

    systems

    :3amples4 P  B  θ relay on the tie lines between ,ntarioEydro and Manitoba Eydro

  • 8/13/2019 Transient Angle Stability

    83/101

  • 8/13/2019 Transient Angle Stability

    84/101

    1539pk TS - 84

    Discontinuous :3citation ControlDiscontinuous :3citation Control

    Properly applied PSS provides damping to both local and inter-

    area modes of oscillations

    +nder large signal or transient conditions' the stabili.er

    generally contributes positively to first swing stability

    $n the presence of both local and inter-area swing modes'

    however' the normal stabili.er response can allow thee3citation to be reduced after the pea# of the first local-mode

    swing and before the highest composite pea# of the swing is

    reached

    Additional improvements in transient stability can be reali.ed

    by #eeping the e3citation at ceiling' within terminal voltage

    constraints' until the highest point of the swing is reached

    Discontinuous e3citation control scheme referred to asTransient Stability :3citation Control 0TS:C1 has been

    developed by ,ntario Eydro to achieve the above

    improves transient stability by controlling the generator

    e3citation so that the terminal voltage is maintained near

    the ma3imum permissible value of about (9(? to (9(* pu

    over the entire positive swing of the rotor angle

  • 8/13/2019 Transient Angle Stability

    85/101

    1539pk TS - 85

    uses a signal proportional to change in angle of

    the generator rotor' in addition to the terminal

    voltage and rotor speed signals

    angle signal is used only during the transient

    period of about ? seconds following a severe

    disturbance' since it results in oscillatory

    instability if used continuously

    angle signal prevents premature reversal of field

    voltage and hence maintains the terminal voltageat a high level during the positive swing of the

    rotor angle

    e3cessive terminal voltage is prevented by the

    terminal voltage limiter 

    /hen TS:C used on several generating stations in an

    area7

    system voltage level in the entire area is raised

    increases power consumed by loads in the entire

    area' contributing to further improvement in TS

  • 8/13/2019 Transient Angle Stability

    86/101

    1539pk TS - 86

  • 8/13/2019 Transient Angle Stability

    87/101

    1539pk TS - 87

    $ntegrating E;DC Parallel Jin#s$ntegrating E;DC Parallel Jin#s

    E;DC lin#s are highly controllable9 Possible to ta#e

    advantage of this uni@ue characteristic of the E;DC lin#

    to augment the transient stability of the ac system

    Parallel application with ac transmission can be

    effectively used to bypass ac networ# congestion ,ften' provides the best option for using limited right of

    way

    Provides a firewall against cascading outages during

    ma"or system disturbances

  • 8/13/2019 Transient Angle Stability

    88/101

    1539pk TS - 88

    :3amples of E;DC Parallel Jin#s:3amples of E;DC Parallel Jin#s

    Pacific E;DC $nter-tie in the +S west

    (N88 #m long NN8 #; bipolar E;DC overhead line from

    Columbia River in ,regon to Jos Angeles' California

    uilt in the early (&H8s' with a capacity of ('NN8 M/7

    upgraded over the years to 6'(88 M/

    Eas operated successfully for over 68 years in parallel

    with *88 #; AC transmission

    $taipu E;DC Jin# in ra.il

    K88 #m long )88 #; bipolar E;DC overhead line

    from

  • 8/13/2019 Transient Angle Stability

    89/101

    1539pk TS - 89

    ;SC-ased E;DC Technology;SC-ased E;DC Technology

    E;DC transmission systems built over the years use

    converter bridge circuits that rely on natural voltage

    of the ac system for commutation4 line-commutated

    converter technology!

    Results in generation of lower-order harmonics

    and consumption of reactive power' which in turn

    call for counter measures

    $n recent years' self-commutated voltage-sourced

    converter 0;SC1 technology! has been developed and

    advanced for E;DC transmission application with the

    following technical benefits4

    Active and reactive power can be controlledindependently

    :3cellent dynamic response

    Can be connected to very wea# ac networ#

    Earmonic filter re@uirements are significantly less

    =ood blac#-start! capability

    Jower overall footprint! re@uirements

    ;SC-based E;DC converters are more e3pensive and

    have higher losses

    Depending on the nature of the application' these

    may not be significant issues

  • 8/13/2019 Transient Angle Stability

    90/101

    1539pk 

    %ovember &' (&)* lac#out of%ovember &' (&)* lac#out of

    %ortheast +S and ,ntario%ortheast +S and ,ntario

  • 8/13/2019 Transient Angle Stability

    91/101

    1539pk TS - 91

    %ovember &' (&)* - lac#out of%ovember &' (&)* - lac#out of

    %ortheast +S and Canada%ortheast +S and Canada

    Clear day with mild weather7

    Joad levels in the regional normal

    Problem began at *4() p9m9

    /ithin a few minutes' there was a complete shut

    down of electric service to

    virtually all of the states of %ew Lor#'

    Connecticut' Rhode $sland' Massachusetts'

    ;ermont

    parts of %ew Eampshire' %ew Wersey and

    Pennsylvania

    most of ,ntario' Canada

    %early 68 million people were without power for

    about (6 hours

    President Wohnson ordered Chairman of

  • 8/13/2019 Transient Angle Stability

    92/101

    1539pk TS - 92

    %orth American :astern $nterconnected%orth American :astern $nterconnected

    SystemSystem

  • 8/13/2019 Transient Angle Stability

    93/101

    1539pk TS - 93

    :vents that Caused the (&)* lac#out:vents that Caused the (&)* lac#out

    The initial event was the operation of a bac#up relay

    0one 61 at ec# =S in ,ntario near %iagara

  • 8/13/2019 Transient Angle Stability

    94/101

  • 8/13/2019 Transient Angle Stability

    95/101

  • 8/13/2019 Transient Angle Stability

    96/101

    1539pk TS - 96

    Special Protections $mplemented after theSpecial Protections $mplemented after the

    (&)* lac#out(&)* lac#out

      P Relays on %iagara Ties trip %iagara ties to %L7

    cross-trip St9 Jawrence ties to %L

    in place until mid (&K8s

    +nderfre@uency load shedding 0+

  • 8/13/2019 Transient Angle Stability

    97/101

    1539pk TS - 97

  • 8/13/2019 Transient Angle Stability

    98/101

    1539pk TS - 98

    Reliability :nhancement after the (&)*Reliability :nhancement after the (&)*

    lac#outlac#out

    All utilities in %orth America began to review

    reliability related policies' practices and procedures

    Coordination of activities and information e3change

    between neighbouring utilities became a priority

    :ach Regional Council established detailed Reliability

    criteria and guidelines for member systems

    Power system stability studies became an important

    part of operating studies

    led to the development of improved Transient

    Stability programs

    e3change of data between utilities

    Many of these developments has had an influence on

    utility practices worldwide

  • 8/13/2019 Transient Angle Stability

    99/101

  • 8/13/2019 Transient Angle Stability

    100/101

    1539pk TS - 100

    March ((' (&&& ra.il lac#outMarch ((' (&&& ra.il lac#out

    Time4 ??4()488h' System Joad4 6N'?88 M/

    Description of the event4

    J-= fault at auru substation as a result of lightning

    causing a bus insulator flashover 

    The bus arrangement at auru such that the fault is

    cleared by opening five NN8 #; lines

    The power system survived the initial event' but

    resulted in instability when a short heavily loaded

    NN8 #; line was tripped by .one 6 relay

    Cascading outages of several power plants in Sao

    Paulo area' followed by loss of E;DC and H*8 #; AClin#s from $taipu

    Complete system brea# up4 ?N'H88 M/ load loss7

    several islands remained in operation with a total

    load of about (8'888 M/

    Restoration of different regions varied from 68

    minutes to N hours Complete blac#out of Sao Paulo and Rio de Waneiro

    areas for about N hours

  • 8/13/2019 Transient Angle Stability

    101/101

    March ((' (&&& ra.il lac#outMarch ((' (&&& ra.il lac#out 0cont>d10cont>d1

    Measures to improve system security4

    Woint /or#ing =roup comprising :J:CTR,RAS'

    C:P:J and ,%S staff formed

    ,rgani.ed activities into K Tas#