Transformer on Load
-
Upload
rajatxavier4u -
Category
Documents
-
view
216 -
download
0
Transcript of Transformer on Load
-
8/14/2019 Transformer on Load
1/14
Transformer on Load
V1
I0
I 2
Load
2
2
2
Fig. 4
-
8/14/2019 Transformer on Load
2/14
Phasor diagram for Transformer on Load
E2
V1
I2'
I2
I0
I1
Load I2 is
resistive
K=1
0
E2
V1
I2
'
I 2
I0
I1
Load I2
is
inductive
K=1
01
2
Fig. 5
1
-
8/14/2019 Transformer on Load
3/14
Actual transformer:
Winding resistance & magnetic leakage
R1
X1 I 1
E1
V1
R2
X2
I2
V2
E2
2
1
2
11XRZ +=
R1 & R2 : resistances of primary & secondary windings respectively.
X1 & X2 : leakage reactances of primary & secondary windings respectively.
2
2
2
22 XRZ +=
-
8/14/2019 Transformer on Load
4/14
Phasor diagram of actual transformer
a) I2 is resistive b) I2 is inductive c) I2 is capacitive
-
8/14/2019 Transformer on Load
5/14
Transfer of resistances & reactances to any
side
The Cu loss by I2 in secondary = I22 R2. If is the
equivalent resistance in the primary which wouldhave caused the same loss as R2 in the secondary,
then
Similarly, equivalent primary resistance as referredto secondary is
2
2
2
2
1
2
2
22
122
2
k
R
I
I
RRor,
RIRI
=
=
=
1
2
1RkR =
2
R
-
8/14/2019 Transformer on Load
6/14
Leakage reactances can also be transferred
from one winding to other ;
Total resistance referred to primary is
Total reactance referred to primary is
Total impedance of transformer referred to
primary is
2
2
2kXX =
1
2
1 XkX =
+=2101
RRR
+= 2101 XXX
2
01
2
0101XRZ +=
-
8/14/2019 Transformer on Load
7/14
Similarly, total resistance referred to secondary is
Similarly, total reactance referred to secondary is
Similarly, total impedance of transformer
referred to secondary is
+=
1202
RRR
+= 1202 XXX
2
02
2
0202 XRZ +=
-
8/14/2019 Transformer on Load
8/14
R02
X02
Impedance referred to secondary
Z02
-
8/14/2019 Transformer on Load
9/14
Equivalent circuit of Transformer
I1
E1
V1
I2
V2
E2
R 1 X 1 I 1
I0
I2
'
V 1 E 1 E 2
R 2 X 2
R 0 X 0
I2
Z LV 2
A) Circuit
B) Equivalent circuit of transformer
Iw I
-
8/14/2019 Transformer on Load
10/14
Equivalent circuit of Transformer referred to
primaryR1 X1 I1
I0
I2'
V1 E2'= E1
R2' X2'
R0 X0 ZL'V2
'
I2'
I1
E2' = E2/K, R2' = R2/K
2, X2' = X2/K2, V2' =V2/K, ZL =ZL/K
2
E2/E1 = I1/I2 = K
R1 X1I1
I0
I2'
V1 E2'= E1
R2' X2'
ZL'
I2'
I1
R0 X0
V2'
D) Approximate equivalent circuit
Iw
Iw
I
I
C) Equivalent circuit with secondary impedances transferred to primary
-
8/14/2019 Transformer on Load
11/14
= R1 X01= X1I1
I0
I2'
V1
+R2' + X2'
ZL'
I2'
I1
R0 X0
V2'
R01
Approximate Equivalent circuit with secondary impedances
transferred to primary
-
8/14/2019 Transformer on Load
12/14
Transformer tests
The performance of a transformer can be calculated on the basis of its
equivalent circuit which contains the 4 main parameters:
1. Equivalent resistance R01(or R02)
2. Equivalent leakage reactance X01 (or X02)
3. Core loss resistance R0
4. Magnetizing reactance X0.
These parameters are determined from the following tests:
a) Open circuit test
b) Short circuit test
-
8/14/2019 Transformer on Load
13/14
-
8/14/2019 Transformer on Load
14/14
Short Circuit test
This test is conducted to determine:1. Full-load copper loss
2. Equivalent resistance & reactance referred to metering side.
LV
supply
V
AW
Low Voltage windingHigh Voltage winding
A low voltage (5 -10% of normal primary voltage) at correct frequency is applied
to the primary winding & is continuously increased till full load currents flow both
in primary & secondary. Since applied voltage is small, flux linking with core is
very small & hence, iron loss can be neglected & reading of wattmeter givestotal copper losses at full load.
If Vsc is the voltage required to circulate rated load currents, then
2
01
2
010101
2
01 ; RZXRIWI
VZ
sc
sc
sc===