TraceTek Water Sensing System External Audible Alarm 95 dB alarm triggered by relay closure;...
Transcript of TraceTek Water Sensing System External Audible Alarm 95 dB alarm triggered by relay closure;...
Scope of this GuideThis guide will help you select TraceTekproducts for water detection in commercialbuildings. Detailed product information inthis guide complements the TraceTekApplication Guide for Commercial BuildingProtection (H53147).Additional TraceTek products are availablefor other liquids—fuels and oils, organic sol-vents—and for other types of applications.See the TraceTek Selection Guide forIndustrial and Environmental Applications(H55869) for further detail.
Modular Design ApproachTraceTek leak detection is a versatilemodular system, with interchangeablecomponents that can be configured inmany different ways. Standard lengths ofTraceTek cable plug together with nospecial tools, making it easy to modify oradd to the system in the future. Therange of TraceTek alarm modules andmodular components allows you to tailorthe monitoring approach and layout tothe application.
Contents of this GuideThe first two pages of this guide showtypical configurations for TraceTek leakdetection systems. Many other configura-tions are possible as well. The last twopages present product listings—detailedtechnical and ordering information for theproducts available.Other Raychem literature can beobtained from our Fax-on-Demand serviceat (800) 329-4494. A voice prompt leadsyou through the process.
TraceTek Leak DetectionProduct Selection Guide for Water Sensing Systems
Elements of a TraceTek System
A Basic SystemEvery TraceTek leak detection systemhas these basic parts:• An alarm module• Leader and/or jumper cables
(nonsensing cables between the module and the areas monitored)
• Sensing cable• End termination• Accessories such as hold-down clips
and tags.
A Locating SystemA TraceTek locating system oftenincludes these additional circuit components:• Branching connectors • Weighted lengthsThese components make it possible for alocating system to monitor one or morelarge areas or lengths.A locating system has one more essentialelement:• A graphic map (see an example on the
next page)
TagsTT-TAG
Hold-Down ClipsTT-HDC-1/4
Water Sensing CableTT1000-x-PC
Modular Leader CableTT-MLC-PC
TraceTekAlarm Module
TTC-1 (or TTA-1)
Modular End TerminationTT-MET-PC
Modular Jumper CableTT-MJC-x-PCbetween module and area monitored
Modular Leader CableTT-MLC-PC
Water Sensing CableTT1000-x-PC
Alarm and Locating ModuleTTDM
Water Sensing CableTT1000-x-PCdaisy-chained togetherto provide as much coverage as needed
Modular BranchingConnectorTT-MBC-PC
TagsTT-TAG
Hold-Down ClipsTT-HDC-1/4
Modular End TerminationTT-MET-PC
(required at end of every branch)
LEAK DETECTION
powered by
® Water Sensing SystemProduct Selection Guide
TTSIM-1A
A TraceTek locating system can monitorone or more large areas. If water contactsthe sensing cable, the alarm and locatingmodule indicates the location with a digitaldisplay. A system map created after instal-lation provides reference points (e.g., in the illustration) to facilitate a quick,effective response.
shows where the sensing circuitjumps to a new room and a weightedlength is used. The weighted length simulates 15 ft of sensing cable so thesystem map will show a clear divisionbetween the separate areas.
shows a branch in the sensing circuit. ATraceTek branching connector is wired sothe connected branches appear in series,middle leg first. The branching connectoralso adds a simulated cable length of 15 fton each branch to make a clear divisionbetween areas. Although not shown, a system may have branches within branches.The number of branches is limited only bythe length of the sensing circuit.
BA
25
Modular jumper cables
Modularbranchingconnector
Modularendtermination
Modular end termination
Weighted LengthTT-WL-4.5M/15FT-PC
Bulk Jumper CableTT-JC
Jumper Splice KitTT-JSK-HS18
Modularleadercable
Watersensingcable
75
90
130
245
395
345
270
295
320
205
230
50
25
180
155115
1
B
Drawingnot to scale
Alarm and locating moduleTTDM
A
370
Wide Area Coverage: TraceTek Locating System
Note: A TraceTek alarm system can include several lengths of sensing cable. However, for large and/or separate areas, consider a TraceTek locating system.
Modularleadercable
Modular jumper cable(s)
Modular endtermination
TTC-1alarmmodule
Hold-down clip
Sensing cables
Tag
TTA-1alarmmodule
Modularleadercable
Alarm relays from the TTC-1 module may be used to control equipment (e.g., close a valve), to annunciate an alarm, and/or to signal an alarm to a host system.
Sensing cable can be positioned to provide complete leakdetection coverage of pumps, boilers, and other equipment.
The TTA-1 module can be installed in an occupied area to make use of the module’s audible alarm. The use of jumper cable allows the alarm module to be positioned in a location remote from the sensing cable it monitors.
Modular endtermination
Hold-down clip
Sensing cable
Tag
Small Area Coverage: Basic TraceTek Alarm System
TTSIM-1Aalarm module
Alarm relays from the TTSIM-1A module may be used to control equipment (e.g., close a valve), to annunciate an alarm, and/or to signal an alarm to a host system.
TTSIM-1Aalarm module
TTSIM-1A module can be installed in an occupied area to make use of the module‘s audible alarm. The use of jumper cable allows the alarm module to be positioned in a location remote from the sensing cable it monitors,
Product Catalog No. Selection DescriptionAlarm Modules
TTDM Alarm and TTDM-1 115 Vac Supply Alarm and locating module; indicates liquid location withLocating Module TTDM-2 230 Vac Supply digital display. Monitors up to 5000 ft (1500 m) of sensing
TTDM-24 24 V Supply cable. Metal enclosure, NEMA 12. Data logging.Outputs: Audible alarm, 4 LEDs, backlit LCD
3 DPDT Form C relays (leak, service, and fault)4-20 mA analog output
For details on approvals Serial port configurable for RS-232 or RS-485see data sheets.
TTA Alarm ModuleTTA-1 115 or 240 Vac Supply Nonlocating single-channel alarm module.
Monitors up to 100 ft (30 m) of sensing cable.Metal enclosure, NEMA 1.Outputs: Audible alarm, 3 LEDs
4PDT Form C relay (leak or fault)
TTC Alarm ModuleTTC-1 24 V Supply Nonlocating single-channel alarm module. Monitors up to
100 ft (30 m) of sensing cable. Plastic enclosure, NEMA 1.Outputs: 3 LEDs
DPDT Form C relay (leak)SPDT Form C relay (fault)
TT-DRC Din Rail Clip Mounting clip for attachment to DIN rail in electrical panel.
External or Remote Alarm
TTE-XAL External Audible Alarm 95 dB alarm triggered by relay closure; requires 24 V supply.
Jumper CablesModular Leader Cable
TT-MLC-PC Modular Leader Cable Cable with one end prepared for connection to terminals(with plastic connector) in module (or for splicing to bulk jumper cable), and with Length: 12 ft (3.5 m) socket-type plastic connector at other end.
Modular Jumper CableTT-MJC-x*-PC Modular Jumper Cable Jumper cable with pin-type plastic connector at one end;
TT-MJC-1M/3FT-PC 1 m 3 ft socket-type plastic connector at other end.TT-MJC-3M/10FT-PC 3 m 10 ftTT-MJC-7.5M/25FT-PC 7.5 m 25 ftTT-MJC-15M/50FT-PC 15 m 50 ft *Cable lengthTT-MJC-30M/100FT-PC 30 m 100 ft
Bulk Jumper CableTT-JC-76M/250FT Bulk Jumper Cable Bulk jumper cable with four color-coded 18 AWG
(250-ft reel) conductors. Connectors not included.
Jumper Splice KitTT-JSK-HS18 Jumper Splice Kit Splice kit for jumper cable; contains parts for 5 splices.
Includes 20 crimps and 5 heat-shrinkable tubes.For use with 18 AWG jumper wire.
Sensing CablesWater Sensing Cable
TT1000-x*-PC Modular Sensing Cable TT1000 water sensing cable with pin-type plastic connector TT1000-1M/3FT-PC 1 m 3 ft at one end, socket-type plastic connector at other end.TT1000-3M/10FT-PC 3 m 10 ftTT1000-7.5M/25FT-PC 7.5 m 25 ftTT1000-15M/50FT-PC 15 m 50 ft *Cable length
®
R
®
R
R RC
F M
APPROVED
PRODUCT SERVICE geprüfteSicherheit
TraceTek Products for Water Detection in Commercial Buildings
Product Catalog No. Selection DescriptionAlarm Modules
TTDM Alarm and TTDM-1 115 Vac Supply Alarm and locating module; indicates liquid location withLocating Module TTDM-2 230 Vac Supply digital display. Monitors up to 5000 ft (1500 m) of sensing
TTDM-24 24 V Supply cable. Metal enclosure, NEMA 12. Data logging.Outputs: Audible alarm, 4 LEDs, backlit LCD
3 DPDT Form C relays (leak, service, and fault)4-20 mA analog output
For details on approvals Serial port configurable for RS-232 or RS-485see data sheets.
TTA Alarm ModuleTTA-1 115 or 240 Vac Supply Nonlocating single-channel alarm module.
Monitors up to 100 ft (30 m) of sensing cable.Metal enclosure, NEMA 1.Outputs: Audible alarm, 3 LEDs
4PDT Form C relay (leak or fault)
TTC Alarm ModuleTTC-1 24 V Supply Nonlocating single-channel alarm module. Monitors up to
100 ft (30 m) of sensing cable. Plastic enclosure, NEMA 1.Outputs: 3 LEDs
DPDT Form C relay (leak)SPDT Form C relay (fault)
TT-DRC Din Rail Clip Mounting clip for attachment to DIN rail in electrical panel.
External or Remote Alarm
TTE-XAL External Audible Alarm 95 dB alarm triggered by relay closure; requires 24 V supply.
Jumper CablesModular Leader Cable
TT-MLC-PC Modular Leader Cable Cable with one end prepared for connection to terminals(with plastic connector) in module (or for splicing to bulk jumper cable), and with Length: 12 ft (3.5 m) socket-type plastic connector at other end.
Modular Jumper CableTT-MJC-x*-PC Modular Jumper Cable Jumper cable with pin-type plastic connector at one end;
TT-MJC-1M/3FT-PC 1 m 3 ft socket-type plastic connector at other end.TT-MJC-3M/10FT-PC 3 m 10 ftTT-MJC-7.5M/25FT-PC 7.5 m 25 ftTT-MJC-15M/50FT-PC 15 m 50 ft *Cable lengthTT-MJC-30M/100FT-PC 30 m 100 ft
Bulk Jumper CableTT-JC-76M/250FT Bulk Jumper Cable Bulk jumper cable with four color-coded 18 AWG
(250-ft reel) conductors. Connectors not included.
Jumper Splice KitTT-JSK-HS18 Jumper Splice Kit Splice kit for jumper cable; contains parts for 5 splices.
Includes 20 crimps and 5 heat-shrinkable tubes.For use with 18 AWG jumper wire.
Sensing CablesWater Sensing Cable
TT1000-x*-PC Modular Sensing Cable TT1000 water sensing cable with pin-type plastic connector TT1000-1M/3FT-PC 1 m 3 ft at one end, socket-type plastic connector at other end.TT1000-3M/10FT-PC 3 m 10 ftTT1000-7.5M/25FT-PC 7.5 m 25 ftTT1000-15M/50FT-PC 15 m 50 ft *Cable length
®
R
®
R
R RC
F M
APPROVED
PRODUCT SERVICE geprüfteSicherheit
TraceTek Products for Water Detection in Commercial Buildings
Sensor-Interface-Module
Sensor-Interface-Module
TTSIM-1
TTSIM-1A
Sensor-Interface-Module for circuit-entering to the TTDM-128 Locating Module or direct to the central computer with supervisor software.For monitoring of max. 1500m sensing cable
Sensor-Interface-Module for circuit-entering to the TTDM-128 Locating Module or direct to the central computer with supervisor software.For monitoring of max. 150m sensing cable
Product Catalog No. Selection DescriptionCircuit Components
End TerminationTT-MET-PC Modular End Termination Terminates sensing circuit; has pin-type plastic connector.
(with plastic connector) Required at end of sensing circuit and all branches.
Branching ConnectorTT-MBC-PC Modular Branching Allows a “T” or branch in the sensing circuit. Has one pin-
Connector (with type connector to connect to cable from alarm module, two plastic connectors) socket-type connectors to connect two branches. Wires the
branches in series and adds a simulated length of 15 fton each branch to make clear division between areas.
Weighted LengthTT-WL-4.5M/15FT-PC Weighted Length Simulates 15 ft (4.5 m) of sensing cable. Makes a
(with plastic connectors) clear division between separate areas in a locating system.
AccessoriesHold-down Clips
TT-HDC-1/4/200-N/A No adhesive (200/bag) Hold-down clips attach cable to flat surfaces.TT-HDC-1/4 Adhesive-backed (50/bag) Pressure-sensitive adhesive bonds to clean, flat surfaces.
Use a clip for each 4 ft (1.3 m) of sensing cable.
TagsTT-TAG TraceTek Tags Tags to identify TraceTek sensing cable and record
mapped distance. Tag attaches to sensing cable by closing on itself (like a cable tie). Package contains 50 high-visibility yellow tags and a permanent marker.Use a tag on each length of cable and at mapping points.
ToolsPortable Test Box
TT-PTB-1000 Portable Test Box Battery-operated device to test TraceTek sensing cables.Allows testing of anything from an individual length up to2000 ft (or 1000 m) of sensing cable. Useful for installationand maintenance.
Crimp ToolAD-1522-1 Crimp Tool Tool sized to properly crimp connectors in TT-JSK-HS18
jumper splice kit
Pre-Packaged KitsComplete Kits
TTC-KIT-1 25 ft of TT1000 Cable Each kit contains a TTC-1 alarm module, a modular TTC-KIT-2 50 ft of TT1000 Cable leader cable, a modular sensing cable of length indicated,
a modular end termination, 15 hold-down clips, and 5 tags.
©19
97 R
aych
em C
orpo
ratio
n P
rinte
d in
US
A
H53
874
P
/N 1
7126
9
3/97
Tr
aceT
ek is
a tr
adem
ark
of R
aych
em C
orpo
ratio
n.
All information, including illustrations, is believed to be reliable. Users, however, should inde-pendently evaluate the suitability of each product for their application. Raychem makes no war-ranties as to the accuracy or completeness of the information, and disclaims any liabilityregarding its use. Raychem’s only obligations are those in the Raychem Standard Terms andConditions of Sale for this product, and in no case will Raychem be liable for any incidental,indirect, or consequential damages arising from the sale, resale, use, or misuse of the product.Specifications are subject to change without notice. In addition, Raychem reserves the right tomake changes—without notification to Buyer—to materials or processing that do not affectcompliance with any applicable specification.
Raychem CorporationCommercial & IndustrialInfrastructure Division300 Constitution DriveMenlo Park, CA 94025-1164Tel (800) 545-6258Fax (800) 611-2323 Fax-on-Demand (800) [email protected]
The TraceTek Products Group is part of the Raychem Chemelex Division.Chemelex Division is ISO 9001 certified.
9 0 01ISO
TraceTek Products for Water Detection in Commercial Buildings (continued)
Vertriebsbüro West
Veilchenweg 13A-4210 GallneukirchenT. +43 7235 66910F: +43 7235 [email protected]
VertriebsgmbH
Industriestrasse B-4A-2345 Brunn/GebirgeT. +43 2236 90300F: +43 2236 90300/[email protected]
2 of 2 (800) 545-6258www.tycothermal.com H58260 5/08
©20
08 T
yco
Ther
mal
Con
trols
LLC
H
5826
0 5
/08
TT1100-OHP
Tyco Thermal Controls307 Constitution DriveMenlo Park, CA 94025-1164USATel (800) 545-6258Fax (650) [email protected]
Important: All information, including illustrations, is believed to be reliable. Users, however, should independently evaluate the suitability of each product for their particular application. Tyco Thermal Controls makes no warranties as to the accuracy or completeness of the information, and disclaims any liability regarding its use. Tyco Thermal Controls' only obligations are those in the Tyco Thermal Controls Standard Terms and Conditions of Sale for this product, and in no case will Tyco Thermal Controls or its distributors be liable for any incidental, indirect, or consequential damages arising from the sale, resale, use, or misuse of the product. Specifications are subject to change without notice. In addition, Tyco Thermal Controls reserves the right to make changes—without notification to Buyer—to processing or materials that do not affect compliance with any applicable specification.
Tyco and TraceTek are trademarks of Tyco Thermal Controls LLC or its affiliates.
Braided fiber jacket(8.2 mm diameter)
Yellow tracer
Sensor wires (2)
Signal wires (2)
0.92 in(23 mm)
Product Characteristics
Finished cable diameter 8.2 mm nominal
Cable diameter with connectors 23 mm nominal
Signal wires 2 x 26 AWG with fluoropolymer insulation
Sensor wires 2 x 30 AWG with conductive fluoropolymer jacket
Carrier rod 20 AWG core wire flame retarded polymer
Cable weight 5.86 kg / 100 m nominal
Breaking strength > 100 kg
Cut-through force > 50 kg (using 0.05” radius blade)
Maximum continuous operatingtemperature
80˚C
Resistance to Humidity <2 µA leakage per 100 feet @ 90% RH / 20C
Approvals
9 0 01ISO The TraceTek products group is a part of Tyco Thermal Controls, Tyco International. Tyco Thermal Controls is ISO 9001 certified.
TraceTek sensing cables are approved only when used with an agency approved TraceTek alarm module.