    To calculate the A/C cooling load at split unit / AHU / ACPU / WCPUand compare with actual capacity:

    Testing equipment:

    1- Air Flow meter

    2- Thermometer3- Measuring tape.4- Psychrometric chart or schedule

    Data required:

    1- Measure return air velocity (air flow rate) using the unit Liter/second2- Measure return and supply dry air temperature and relative humidity3- Measuring the area of return air flow (area of air filter) using the unit : Foot

    2

    Calculation

    To Calculate sensible heat in KWr use the formula below:

    KWs= 1.21 * l/s * (T) C / 1000 = KWr

    To calculate Latent heat in KW should use Psychrometric chart to get moisture content for each temperature

    KWl = 3 * l/s * ( m) g/kg /1000 = KWr

    Total A/C heat load = KWs+ KWl = KWr

    Convert to BTU = KWr * 3,412

    Where:

    T in Celsius (return air temperature - supply air temperature)

    m in g/kg Humidity ratio (Moisture content at return air Moisture content at supply air)

    Measure Air speed in foot /Minute

    Air flow = air speed * Area = CFM the convert to Liter/Second

    Remarks:

    - May you down load Psychrometric chart calculator at you PC from web address as below:

    http://www.sugartech.co.za/psychro/

    Enter your Temperature and Relative humidity can get Moisture content in kg/kg

    Then multiply by 1000 to get Humidity ratio (moisture content) in (g/ kg).