To calculate the A/C cooling load at split unit / AHU / ACPU / WCPUand compare with actual capacity:
Testing equipment:
1- Air Flow meter
2- Thermometer3- Measuring tape.4- Psychrometric chart or schedule
Data required:
1- Measure return air velocity (air flow rate) using the unit Liter/second2- Measure return and supply dry air temperature and relative humidity3- Measuring the area of return air flow (area of air filter) using the unit : Foot
2
Calculation
To Calculate sensible heat in KWr use the formula below:
KWs= 1.21 * l/s * (T) C / 1000 = KWr
To calculate Latent heat in KW should use Psychrometric chart to get moisture content for each temperature
KWl = 3 * l/s * ( m) g/kg /1000 = KWr
Total A/C heat load = KWs+ KWl = KWr
Convert to BTU = KWr * 3,412
Where:
T in Celsius (return air temperature - supply air temperature)
m in g/kg Humidity ratio (Moisture content at return air Moisture content at supply air)
Measure Air speed in foot /Minute
Air flow = air speed * Area = CFM the convert to Liter/Second
Remarks:
- May you down load Psychrometric chart calculator at you PC from web address as below:
http://www.sugartech.co.za/psychro/
Enter your Temperature and Relative humidity can get Moisture content in kg/kg
Then multiply by 1000 to get Humidity ratio (moisture content) in (g/ kg).